Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:40
Tabular Output Report in Format: HTML
Building: US+MF+CZ6A+elecres+crawlspace+IECC_2021
Environment: ANNUAL ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2021-05-12 10:40:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 931297.99 | 23.88 | 43.10 |
Net Site Energy | 931297.99 | 23.88 | 43.10 |
Total Source Energy | 2949420.72 | 75.62 | 136.48 |
Net Source Energy | 2949420.72 | 75.62 | 136.48 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.26 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 445379.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28686.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299798.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 35275.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64640.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 931297.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 445379.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28686.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 26623.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation | 8652.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 4468.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 60171.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 26.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
Other | 13.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 43.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 14.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 23.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 931297.986 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 931297.986 | 100.00 |
Total On-Site and Utility Electric Sources | 931297.986 | 100.00 |
Total Electricity End Uses | 931297.986 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 330767.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 330767.30 | 100.00 |
Total Water End Uses | 330767.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 320.17 |
Time Setpoint Not Met During Occupied Cooling | 12.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1872.83 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:40 |
RunPeriod | ANNUAL |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [ft] | 1305.84 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 17103.09 | 6415.36 | 2136.19 | 6415.36 | 2136.19 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 12.43 | 8.29 | 24.89 | 8.29 | 24.89 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
CRAWLSPACE | 7794.39 | No | Yes | 19513.17 | 1.00 | 185.02 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
Total | 39005.22 | 286601.37 | 16363.00 | 740.10 | 2126.74 | 2126.74 | 0.3230 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.5831 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.26 | 102861.98 | 1066.39 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 18-JAN-19:49 | - | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:09 |
Heating | 224.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 47.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 327.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 224.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 5.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 5.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 26.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 9.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation | 0.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 1410516.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 90848.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122590.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949462.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 111719.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 204715.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2949420.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 65.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 9.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 136.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 36.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 75.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
ZoneHVAC:EnergyRecoveryVentilatorUser-Specified Supply Air Flow Rate [ft3/min] | User-Specified Exhaust Air Flow Rate [ft3/min] | |
ERV_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.99 |
User-Specified Maximum Flow Rate [ft3/min] | Design Size Maximum Flow Rate [ft3/min] | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 417.19 | |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 180.75 | |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 317.05 | |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 403.05 | |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 178.53 | |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 300.90 | |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 408.92 | |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 180.13 | |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 394.95 | |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 175.96 | |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 303.67 | |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 420.52 | |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 195.96 | |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 321.92 | |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 415.80 | |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 199.44 | |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 304.93 | |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | 160.01 | |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | 160.01 |
User-Specified Nominal Supply Air Flow Rate [ft3/min] | |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | 44.99 |
Design Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 417.19 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 180.75 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 317.05 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 403.05 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 178.53 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 300.90 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 408.92 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 180.13 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 394.95 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 175.96 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 303.67 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 304.93 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 321.92 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 420.52 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 199.44 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 195.96 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 415.80 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 417.19 | 417.19 | 417.19 | 417.19 | 417.19 | 417.19 | 1.00 | 1.00 | 417.19 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.75 | 180.75 | 180.75 | 180.75 | 180.75 | 180.75 | 1.00 | 1.00 | 180.75 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 317.05 | 317.05 | 317.05 | 317.05 | 317.05 | 317.05 | 1.00 | 1.00 | 317.05 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 403.05 | 403.05 | 403.05 | 403.05 | 403.05 | 403.05 | 1.00 | 1.00 | 403.05 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 178.53 | 178.53 | 178.53 | 178.53 | 178.53 | 178.53 | 1.00 | 1.00 | 178.53 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 300.90 | 300.90 | 300.90 | 300.90 | 300.90 | 300.90 | 1.00 | 1.00 | 300.90 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 408.92 | 408.92 | 408.92 | 408.92 | 408.92 | 408.92 | 1.00 | 1.00 | 408.92 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 180.13 | 180.13 | 180.13 | 180.13 | 180.13 | 180.13 | 1.00 | 1.00 | 180.13 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 321.05 | 321.05 | 321.05 | 321.05 | 321.05 | 1.00 | 1.00 | 321.05 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 394.95 | 394.95 | 394.95 | 394.95 | 394.95 | 394.95 | 1.00 | 1.00 | 394.95 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 175.96 | 175.96 | 175.96 | 175.96 | 175.96 | 175.96 | 1.00 | 1.00 | 175.96 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 303.67 | 303.67 | 303.67 | 303.67 | 303.67 | 303.67 | 1.00 | 1.00 | 303.67 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.52 | 420.52 | 420.52 | 420.52 | 420.52 | 420.52 | 1.00 | 1.00 | 420.52 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 195.96 | 195.96 | 195.96 | 195.96 | 195.96 | 195.96 | 1.00 | 1.00 | 195.96 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.92 | 321.92 | 321.92 | 321.92 | 321.92 | 321.92 | 1.00 | 1.00 | 321.92 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 415.80 | 415.80 | 415.80 | 415.80 | 415.80 | 415.80 | 1.00 | 1.00 | 415.80 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 199.44 | 199.44 | 199.44 | 199.44 | 199.44 | 199.44 | 1.00 | 1.00 | 199.44 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 304.93 | 304.93 | 304.93 | 304.93 | 304.93 | 304.93 | 1.00 | 1.00 | 304.93 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 417.19 | 1.07 | 0.792991 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 180.75 | 0.543907 | 0.734425 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 317.05 | 0.833866 | 0.784551 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 403.05 | 1.04 | 0.792622 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 178.53 | 0.538851 | 0.732617 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 300.90 | 0.786243 | 0.786587 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 408.92 | 1.03 | 0.800133 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 180.13 | 0.525651 | 0.744895 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 0.822867 | 0.794675 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 394.95 | 0.995193 | 0.800147 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 175.96 | 0.513917 | 0.744647 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 303.67 | 0.773455 | 0.797675 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 420.52 | 1.08 | 0.794059 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 195.96 | 0.578048 | 0.740885 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 321.92 | 0.847686 | 0.784183 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 415.80 | 1.06 | 0.795365 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 199.44 | 0.582403 | 0.744696 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 304.93 | 0.798139 | 0.786047 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 417.19 | 417.19 | 417.19 | 14760.01 | 1.07 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 180.75 | 180.75 | 180.75 | 11896.53 | 0.543907 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 317.05 | 317.05 | 317.05 | 14735.82 | 0.833866 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 403.05 | 403.05 | 403.05 | 14770.69 | 1.04 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 178.53 | 178.53 | 178.53 | 11905.08 | 0.538851 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 300.90 | 300.90 | 300.90 | 14742.34 | 0.786243 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 408.92 | 408.92 | 408.92 | 11320.54 | 1.03 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 180.13 | 180.13 | 180.13 | 8472.93 | 0.525651 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 321.05 | 321.05 | 11289.53 | 0.822867 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 394.95 | 394.95 | 394.95 | 11333.33 | 0.995193 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 175.96 | 175.96 | 175.96 | 8483.75 | 0.513917 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 303.67 | 303.67 | 303.67 | 11298.64 | 0.773455 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 420.52 | 420.52 | 420.52 | 14556.14 | 1.08 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 195.96 | 195.96 | 195.96 | 11696.19 | 0.578048 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 321.92 | 321.92 | 321.92 | 14521.49 | 0.847686 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 415.80 | 415.80 | 415.80 | 14572.62 | 1.06 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 199.44 | 199.44 | 199.44 | 11711.36 | 0.582403 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 304.93 | 304.93 | 304.93 | 14535.39 | 0.798139 | 1.00 |
Design Size Nominal Capacity [Btu/h] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 14760.01 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 11896.53 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 14735.82 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 14770.69 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 11905.08 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 14742.34 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 11320.54 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 8472.93 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 11289.53 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 11333.33 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 8483.75 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 11298.64 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 14556.14 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 11696.19 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 14521.49 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 14572.62 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 11711.36 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 14535.39 |
Evaporator air flow rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
VersionVersion ID | |
1 | 9.5 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 28.06 | 18.73 | 16.21 | 18.41 | 30.99 | 45.09 | 58.35 | 67.95 | 70.75 | 66.24 | 55.38 | 41.68 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 1305.84 | 14. | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 43.48 | 60.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ6A+elecres+crawlspace+IECC_2021 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.8807 | Rough | 0.1021 | 3.533E-002 | 1.255 | 0.350 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 9.1788 | Rough | 1.8587 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 4.5576 | Rough | 0.7710 | 5.155E-002 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5870 | Smooth | 0.1387 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.4127 | VerySmooth | 0.1373 | 0.101 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFSLABAVERAGE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABAVERAGESURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFSLABPERIMETER | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABPERIMETERTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFSLABCORE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABCORETEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CRAWLSPACE | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -0.8 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -2.0 | 0.49 | 2.49 | 19513.15 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | CRAWLSPACE | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0498 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 9 | 0.167 | 0.0342 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR FLOOR | 5 | 2 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | INTERIOR CEILING | 6 | 2 | 13 | 0.167 | 0.0190 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | ATTIC FLOOR | 7 | 2 | 13 | 0.167 | 0.0190 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
9 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
11 | CRAWL WALL | 24 | 1 | 5 | 0.167 | 2.28 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
12 | iz-EXTERIOR FLOOR | 25 | 3 | 9 | 0.167 | 0.0342 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.1020 | 0.035 | 1.255 | 0.350 | 0.8807 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.7707 | 0.052 | 3.438 | 0.219 | 4.558 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
11 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
12 | CEIL_CONSOL_LAYER | 1.8587 | 0.062 | 2.618 | 0.185 | 9.179 |
13 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | CEIL_CONSOL_LAYER | 1.8587 | 0.062 | 2.618 | 0.185 | 9.179 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
18 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
19 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
20 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
21 | DOOR_CONST | 0.1388 | 0.072 | 32.003 | 0.183 | 0.5870 |
22 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
23 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
24 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
25 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
26 | CONCRETE_4IN | 0.3330 | 1.312 | 140.014 | 0.111 | 0.7736E-01 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.7707 | 0.052 | 3.438 | 0.219 | 4.558 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 10 | 0.51360630E-08 | -0.22035233E-13 | 0.91774209E-08 | -0.50676220E-13 |
2 | 9 | -0.14060012E-04 | 0.39159197E-12 | -0.22958088E-04 | 0.29728831E-08 |
3 | 8 | 0.28980689E-02 | 0.65531654E-09 | 0.46215968E-02 | -0.71708779E-05 |
4 | 7 | -0.65978682E-01 | 0.13350779E-06 | -0.16306378 | 0.13238707E-02 |
5 | 6 | 0.64596177 | 0.50193482E-05 | 2.1320981 | -0.28125917E-01 |
6 | 5 | -3.4215999 | 0.48298777E-04 | -13.652056 | 0.25148823 |
7 | 4 | 10.645660 | 0.13839053E-03 | 47.881148 | -1.1749737 |
8 | 3 | -19.924231 | 0.11919231E-03 | -96.040791 | 3.0621859 |
9 | 2 | 21.976583 | 0.26462555E-04 | 109.48934 | -4.4404618 |
10 | 1 | -13.118296 | 0.91387708E-06 | -65.855375 | 3.3273744 |
11 | 0 | 3.2593552 | 0.33613880E-09 | 16.204438 | |
12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
18 | 9 | -0.61797381E-16 | 0.10275554E-15 | -0.94176193E-10 | 0.70550100E-16 |
19 | 8 | 0.55018702E-09 | 0.40996745E-13 | 0.10446581E-03 | -0.35964092E-09 |
20 | 7 | -0.45325743E-03 | 0.10183730E-08 | -0.10651944E-01 | 0.29628111E-03 |
21 | 6 | 0.35000963E-01 | 0.28248981E-06 | 0.18262466 | -0.23007581E-01 |
22 | 5 | -0.40204458 | 0.87190144E-05 | -1.3453660 | 0.27251248 |
23 | 4 | 1.9371679 | 0.56641591E-04 | 5.2219591 | -1.3641479 |
24 | 3 | -4.7809977 | 0.95620201E-04 | -11.428910 | 3.5178846 |
25 | 2 | 6.3416706 | 0.40914426E-04 | 14.116582 | -4.8962826 |
26 | 1 | -4.2976303 | 0.32019284E-05 | -9.1505965 | 3.4916880 |
27 | 0 | 1.1674918 | 0.10995666E-07 | 2.4144591 | |
28 | 4 | 0.50405178E-13 | 0.16668152E-13 | 0.29402090E-13 | -0.58636069E-16 |
29 | 3 | -0.78967347E-05 | 0.18486376E-05 | -0.51544008E-05 | 0.20741056E-12 |
30 | 2 | 0.37655193 | 0.34407043E-01 | 0.80677627E-01 | -0.16328896E-04 |
31 | 1 | -8.0349315 | 0.81344511 | -1.1624309 | 0.21506451 |
32 | 0 | 8.9946927 | 0.48845120 | 2.4180636 | |
33 | 13 | -0.95016766E-17 | -0.11776553E-17 | -0.33255767E-09 | 0.99855310E-17 |
34 | 12 | 0.61338794E-09 | -0.58488406E-15 | 0.16056222E-03 | -0.43490528E-09 |
35 | 11 | -0.75116140E-04 | -0.12733754E-14 | -0.83172474E-02 | 0.53259175E-04 |
36 | 10 | 0.23489104E-02 | 0.19285539E-11 | 0.16199673 | -0.16913697E-02 |
37 | 9 | -0.32325933E-01 | 0.31831827E-09 | -1.7014869 | 0.23684835E-01 |
38 | 8 | 0.25799047 | 0.11552332E-07 | 11.081256 | -0.19274894 |
39 | 7 | -1.3247958 | 0.13607244E-06 | -47.903612 | 1.0115855 |
40 | 6 | 4.5908388 | 0.61202310E-06 | 142.28685 | -3.5913725 |
41 | 5 | -10.947340 | 0.11168173E-05 | -294.46769 | 8.7955522 |
42 | 4 | 17.960252 | 0.81578039E-06 | 423.45640 | -14.856181 |
43 | 3 | -19.872933 | 0.21758675E-06 | -414.30161 | 16.962607 |
44 | 2 | 14.135270 | 0.16726228E-07 | 262.68178 | -12.475847 |
45 | 1 | -5.8235685 | 0.25078833E-09 | -97.209670 | 5.3243306 |
46 | 0 | 1.0543411 | -0.72051379E-11 | 15.923944 | |
47 | 13 | -0.33255767E-09 | -0.11776553E-17 | -0.95016766E-17 | 0.99855310E-17 |
48 | 12 | 0.16056222E-03 | -0.58488406E-15 | 0.61338794E-09 | -0.43490528E-09 |
49 | 11 | -0.83172474E-02 | -0.12733754E-14 | -0.75116140E-04 | 0.53259175E-04 |
50 | 10 | 0.16199673 | 0.19285539E-11 | 0.23489104E-02 | -0.16913697E-02 |
51 | 9 | -1.7014869 | 0.31831827E-09 | -0.32325933E-01 | 0.23684835E-01 |
52 | 8 | 11.081256 | 0.11552332E-07 | 0.25799047 | -0.19274894 |
53 | 7 | -47.903612 | 0.13607244E-06 | -1.3247958 | 1.0115855 |
54 | 6 | 142.28685 | 0.61202310E-06 | 4.5908388 | -3.5913725 |
55 | 5 | -294.46769 | 0.11168173E-05 | -10.947340 | 8.7955522 |
56 | 4 | 423.45640 | 0.81578039E-06 | 17.960252 | -14.856181 |
57 | 3 | -414.30161 | 0.21758675E-06 | -19.872933 | 16.962607 |
58 | 2 | 262.68178 | 0.16726228E-07 | 14.135270 | -12.475847 |
59 | 1 | -97.209670 | 0.25078833E-09 | -5.8235685 | 5.3243306 |
60 | 0 | 15.923944 | -0.72051379E-11 | 1.0543411 | |
61 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
62 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
63 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
64 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
65 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
66 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
67 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
68 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
69 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
70 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
71 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
72 | 5 | -0.32935335E-06 | 0.42931990E-07 | -0.32935335E-06 | 0.47097488E-08 |
73 | 4 | 0.68052310E-03 | 0.12823787E-03 | 0.68052310E-03 | -0.14200104E-04 |
74 | 3 | -0.11535993 | 0.17375615E-01 | -0.11535993 | 0.40770076E-02 |
75 | 2 | 2.1922172 | 0.21284128 | 2.1922172 | -0.13171357 |
76 | 1 | -7.8704965 | 0.30308566 | -7.8704965 | 0.79499401 |
77 | 0 | 6.3596665 | 0.33276539E-01 | 6.3596665 | |
78 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
79 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
80 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
81 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
82 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
83 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
84 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
85 | 5 | -0.15664505E-06 | 0.43005807E-07 | -0.15664505E-06 | 0.11899247E-09 |
86 | 4 | 0.10791049E-02 | 0.34140917E-03 | 0.10791049E-02 | -0.15677434E-05 |
87 | 3 | -0.39592122 | 0.90314630E-01 | -0.39592122 | 0.13116776E-02 |
88 | 2 | 11.651569 | 1.6702487 | 11.651569 | -0.78737360E-01 |
89 | 1 | -51.506798 | 3.1050242 | -51.506798 | 0.66829999 |
90 | 0 | 45.538973 | 0.42297268 | 45.538973 | |
91 | 9 | -0.94176193E-10 | 0.10275554E-15 | -0.61797381E-16 | 0.70550100E-16 |
92 | 8 | 0.10446581E-03 | 0.40996745E-13 | 0.55018702E-09 | -0.35964092E-09 |
93 | 7 | -0.10651944E-01 | 0.10183730E-08 | -0.45325743E-03 | 0.29628111E-03 |
94 | 6 | 0.18262466 | 0.28248981E-06 | 0.35000963E-01 | -0.23007581E-01 |
95 | 5 | -1.3453660 | 0.87190144E-05 | -0.40204458 | 0.27251248 |
96 | 4 | 5.2219591 | 0.56641591E-04 | 1.9371679 | -1.3641479 |
97 | 3 | -11.428910 | 0.95620201E-04 | -4.7809977 | 3.5178846 |
98 | 2 | 14.116582 | 0.40914426E-04 | 6.3416706 | -4.8962826 |
99 | 1 | -9.1505965 | 0.32019284E-05 | -4.2976303 | 3.4916880 |
100 | 0 | 2.4144591 | 0.10995666E-07 | 1.1674918 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.300 | 0.335 | 0.248 | 0.883 |
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.300 | 0.335 | 0.248 | 0.883 |
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.300 | 0.309 | 4.646E-002 | 0.133 |
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 0.929 | 0.920 | 0.920 |
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 0.906 | 0.900 | 0.900 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
2 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
3 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
4 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
5 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
6 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
7 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
8 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
9 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
10 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
11 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
12 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
13 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
14 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
15 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
16 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
17 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 | |
18 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 4427.4 | 0.000 | 0.0000 | 785 |
Node Number | Height {ft} | Volume {ft3} | Maximum Capacity {Btu/h} | Off-Cycle UA {Btu/h-F} | On-Cycle UA {Btu/h-F} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
2 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
3 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
4 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
5 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
6 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
7 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
8 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
9 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
10 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
11 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
12 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
13 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
14 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
15 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
16 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
17 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
18 | 1 | 5.2299 | 6.9509 | 0.000 | 2.9246 | 2.9246 | 1 | 1 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
20 | CRAWLVENT | ALWAYS_AVAIL | CRAWLSPACE | 7794.37 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CRAWLSPACE | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 9356.09256 | 9356.09256 | 417.18215 | 417.18215 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 83.89881 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 10868.99253 | 10868.99253 | 207.42137 | 207.42137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 4053.53270 | 4053.53270 | 180.74786 | 180.74786 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 80.71880 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 7963.14216 | 7963.14216 | 151.96968 | 151.96968 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 7110.37786 | 7110.37786 | 317.05504 | 317.05504 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 81.86360 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 10844.44654 | 10844.44654 | 206.95294 | 206.95294 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 9038.91137 | 9038.91137 | 403.05080 | 403.05080 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 83.10380 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 10879.82765 | 10879.82765 | 207.62815 | 207.62815 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 4003.86019 | 4003.86019 | 178.53409 | 178.53409 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 80.36901 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 7971.81301 | 7971.81301 | 152.13515 | 152.13515 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 6748.23125 | 6748.23125 | 300.91098 | 300.91098 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 79.82839 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 10851.05981 | 10851.05981 | 207.07900 | 207.07900 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 9170.92141 | 9170.92141 | 408.91944 | 408.91944 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 83.58080 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 7378.48617 | 7378.48617 | 140.82117 | 140.82117 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 4039.84359 | 4039.84359 | 180.13176 | 180.13176 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 80.71880 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 4488.73668 | 4488.73668 | 85.67096 | 85.67096 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 7200.39263 | 7200.39263 | 321.05928 | 321.05928 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 82.34060 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 7347.00869 | 7347.00869 | 140.22053 | 140.22053 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 8857.67169 | 8857.67169 | 394.95758 | 394.95758 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 82.62680 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 7391.46576 | 7391.46576 | 141.06905 | 141.06905 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 3946.14727 | 3946.14727 | 175.95506 | 175.95506 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 80.01919 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 4499.71435 | 4499.71435 | 85.88050 | 85.88050 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6810.45231 | 6810.45231 | 303.66522 | 303.66522 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 80.36901 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 7356.25760 | 7356.25760 | 140.39702 | 140.39702 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 6838.50939 | 6838.50939 | 304.93640 | 304.93640 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 80.36901 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 10641.04732 | 10641.04732 | 203.07137 | 203.07137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 7219.67452 | 7219.67452 | 321.92793 | 321.92793 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 82.34060 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 10626.94259 | 10626.94259 | 202.80209 | 202.80209 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 9430.84405 | 9430.84405 | 420.52961 | 420.52961 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 83.58080 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 10662.11144 | 10662.11144 | 203.47328 | 203.47328 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 4472.65333 | 4472.65333 | 199.43769 | 199.43769 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 80.01919 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 7775.23837 | 7775.23837 | 148.38367 | 148.38367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 4394.61990 | 4394.61990 | 195.95718 | 195.95718 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 80.71880 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 7759.84097 | 7759.84097 | 148.08981 | 148.08981 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 9324.82738 | 9324.82738 | 415.80503 | 415.80503 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 82.62680 | 0.01536 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 10678.83447 | 10678.83447 | 203.79235 | 203.79235 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -15.1600 | 0.00036 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2822.88 | 417.18215 | 417.18215 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 4325.91 | 207.42137 | 207.42137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1248.41 | 180.74786 | 180.74786 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3486.67 | 151.96968 | 151.96968 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2146.69 | 317.05504 | 317.05504 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 4318.82 | 206.95294 | 206.95294 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2720.47 | 403.05080 | 403.05080 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 4329.04 | 207.62815 | 207.62815 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1229.30 | 178.53409 | 178.53409 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3489.18 | 152.13515 | 152.13515 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2014.40 | 300.91098 | 300.91098 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 4320.73 | 207.07900 | 207.07900 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2765.07 | 408.91944 | 408.91944 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3317.86 | 140.82117 | 140.82117 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1244.44 | 180.13176 | 180.13176 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2483.27 | 85.67096 | 85.67096 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2179.17 | 321.05928 | 321.05928 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3308.77 | 140.22053 | 140.22053 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2661.63 | 394.95758 | 394.95758 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3321.61 | 141.06905 | 141.06905 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1207.86 | 175.95506 | 175.95506 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2486.45 | 85.88050 | 85.88050 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2039.72 | 303.66522 | 303.66522 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3311.44 | 140.39702 | 140.39702 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 2840.14 | 420.52961 | 420.52961 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 4266.16 | 203.47328 | 203.47328 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1346.90 | 195.95718 | 195.95718 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 3427.96 | 148.08981 | 148.08981 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2184.75 | 321.92793 | 321.92793 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 4256.00 | 202.80209 | 202.80209 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 2796.54 | 415.80503 | 415.80503 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 4270.99 | 203.79235 | 203.79235 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1359.91 | 199.43769 | 199.43769 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 3432.40 | 148.38367 | 148.38367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 2047.83 | 304.93640 | 304.93640 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 4260.08 | 203.07137 | 203.07137 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
2 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
3 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
4 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
5 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 417.18215 |
7 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
8 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
9 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
10 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
11 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 180.74786 |
13 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
14 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
15 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
16 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
17 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 317.05504 |
19 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
20 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
21 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
22 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
23 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
24 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 403.05080 |
25 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
26 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
27 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
28 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
29 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
30 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 178.53409 |
31 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
32 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
33 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
34 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
35 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
36 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 300.91098 |
37 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
38 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
39 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
40 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
41 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
42 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 408.91944 |
43 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
44 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
45 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
46 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
47 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
48 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 180.13176 |
49 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
50 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
51 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
52 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
53 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
54 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 321.05928 |
55 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
56 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
57 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
58 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
59 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
60 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 394.95758 |
61 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
62 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
63 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
64 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
65 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
66 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 175.95506 |
67 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
68 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
69 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
70 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
71 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
72 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 303.66522 |
73 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
74 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
75 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
76 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
77 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
78 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 304.93640 |
79 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
80 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
81 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
82 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
83 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
84 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 321.92793 |
85 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
86 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
87 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
88 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
89 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
90 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 420.52961 |
91 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
92 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
93 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
94 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
95 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 199.43769 |
97 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
98 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
99 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
100 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
101 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
102 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 195.95718 |
103 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
104 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
105 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
106 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
107 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
108 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 415.80503 |
109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 417.18215 |
110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 417.18215 |
111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 417.18215 |
112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 417.18215 |
113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 417.18215 |
114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 417.18215 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 180.74786 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 180.74786 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 180.74786 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 180.74786 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 180.74786 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 180.74786 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 317.05504 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 317.05504 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 317.05504 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 317.05504 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 317.05504 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 317.05504 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 403.05080 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 403.05080 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 403.05080 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 403.05080 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 403.05080 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 403.05080 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 178.53409 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 178.53409 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 178.53409 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 178.53409 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 178.53409 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 178.53409 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 300.91098 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 300.91098 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 300.91098 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 300.91098 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 300.91098 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 300.91098 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 408.91944 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 408.91944 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 408.91944 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 408.91944 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 408.91944 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 408.91944 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 180.13176 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 180.13176 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 180.13176 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 180.13176 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 180.13176 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 180.13176 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 321.05928 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 321.05928 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 321.05928 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 321.05928 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 321.05928 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 321.05928 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 394.95758 |
182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 394.95758 |
183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 394.95758 |
184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 394.95758 |
185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 394.95758 |
186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 394.95758 |
187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 175.95506 |
190 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 175.95506 |
191 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 175.95506 |
192 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 175.95506 |
193 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 175.95506 |
194 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 175.95506 |
195 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
196 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
197 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 303.66522 |
198 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 303.66522 |
199 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 303.66522 |
200 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 303.66522 |
201 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 303.66522 |
202 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 303.66522 |
203 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
204 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
205 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 420.52961 |
206 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 420.52961 |
207 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 420.52961 |
208 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 420.52961 |
209 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 420.52961 |
210 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 420.52961 |
211 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
212 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
213 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 195.95718 |
214 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 195.95718 |
215 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 195.95718 |
216 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 195.95718 |
217 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 195.95718 |
218 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 195.95718 |
219 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
220 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 321.92793 |
222 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 321.92793 |
223 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 321.92793 |
224 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 321.92793 |
225 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 321.92793 |
226 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 321.92793 |
227 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
228 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
229 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 415.80503 |
230 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 415.80503 |
231 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 415.80503 |
232 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 415.80503 |
233 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 415.80503 |
234 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 415.80503 |
235 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
236 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
237 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 199.43769 |
238 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 199.43769 |
239 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 199.43769 |
240 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 199.43769 |
241 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 199.43769 |
242 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 199.43769 |
243 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 304.93640 |
246 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 304.93640 |
247 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 304.93640 |
248 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 304.93640 |
249 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 304.93640 |
250 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 304.93640 |
251 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
253 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 417.18215 |
254 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 180.74786 |
255 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 317.05504 |
256 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 403.05080 |
257 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 178.53409 |
258 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 300.91098 |
259 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 408.91944 |
260 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 180.13176 |
261 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 321.05928 |
262 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 394.95758 |
263 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 175.95506 |
264 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 303.66522 |
265 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 420.52961 |
266 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 195.95718 |
267 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 321.92793 |
268 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 415.80503 |
269 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 199.43769 |
270 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 304.93640 |
271 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 417.18215 |
272 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.07495 |
273 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79299 |
274 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 417.18215 |
275 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 417.18215 |
276 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 417.18215 |
277 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 14760.01147 |
278 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.07495 |
279 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
280 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 417.18215 |
281 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 14760.01147 |
282 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 180.74786 |
283 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.54391 |
284 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73443 |
285 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 180.74786 |
286 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 180.74786 |
287 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 180.74786 |
288 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 11896.53083 |
289 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.54391 |
290 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
291 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 180.74786 |
292 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 11896.53083 |
293 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 317.05504 |
294 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.83387 |
295 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.78455 |
296 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 317.05504 |
297 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 317.05504 |
298 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 317.05504 |
299 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 14735.82305 |
300 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.83387 |
301 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
302 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 317.05504 |
303 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 14735.82305 |
304 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 403.05080 |
305 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.03972 |
306 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79262 |
307 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 403.05080 |
308 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 403.05080 |
309 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 403.05080 |
310 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 14770.68871 |
311 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.03972 |
312 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
313 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 403.05080 |
314 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 14770.68871 |
315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 178.53409 |
316 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.53885 |
317 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73262 |
318 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 178.53409 |
319 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 178.53409 |
320 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 178.53409 |
321 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 11905.07534 |
322 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.53885 |
323 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
324 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 178.53409 |
325 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 11905.07534 |
326 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 300.91098 |
327 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.78624 |
328 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.78659 |
329 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 300.91098 |
330 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 300.91098 |
331 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 300.91098 |
332 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 14742.33997 |
333 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.78624 |
334 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
335 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 300.91098 |
336 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 14742.33997 |
337 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 408.91944 |
338 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.03043 |
339 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80013 |
340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 408.91944 |
341 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 408.91944 |
342 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 408.91944 |
343 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11320.54402 |
344 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.03043 |
345 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
346 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 408.91944 |
347 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11320.54402 |
348 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 180.13176 |
349 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.52565 |
350 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74489 |
351 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 180.13176 |
352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 180.13176 |
353 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 180.13176 |
354 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 8472.93420 |
355 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.52565 |
356 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
357 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 180.13176 |
358 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8472.93420 |
359 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 321.05928 |
360 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.82287 |
361 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79468 |
362 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 321.05928 |
363 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 321.05928 |
364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 321.05928 |
365 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11289.52505 |
366 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.82287 |
367 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
368 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 321.05928 |
369 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11289.52505 |
370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 394.95758 |
371 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.99519 |
372 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80015 |
373 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 394.95758 |
374 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 394.95758 |
375 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 394.95758 |
376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11333.33455 |
377 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.99519 |
378 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
379 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 394.95758 |
380 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11333.33455 |
381 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 175.95506 |
382 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.51392 |
383 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74465 |
384 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 175.95506 |
385 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 175.95506 |
386 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 175.95506 |
387 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 8483.75191 |
388 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.51392 |
389 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 175.95506 |
391 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8483.75191 |
392 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 303.66522 |
393 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.77345 |
394 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79767 |
395 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 303.66522 |
396 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 303.66522 |
397 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 303.66522 |
398 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11298.63922 |
399 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.77345 |
400 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
401 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 303.66522 |
402 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11298.63922 |
403 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 420.52961 |
404 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.07990 |
405 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79406 |
406 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 420.52961 |
407 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 420.52961 |
408 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 420.52961 |
409 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 14556.14386 |
410 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.07990 |
411 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 420.52961 |
413 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14556.14386 |
414 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 195.95718 |
415 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.57805 |
416 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74088 |
417 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 195.95718 |
418 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 195.95718 |
419 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 195.95718 |
420 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 11696.19123 |
421 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.57805 |
422 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
423 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 195.95718 |
424 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11696.19123 |
425 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 321.92793 |
426 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.84769 |
427 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.78418 |
428 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 321.92793 |
429 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 321.92793 |
430 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 321.92793 |
431 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 14521.48735 |
432 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.84769 |
433 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
434 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 321.92793 |
435 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14521.48735 |
436 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 415.80503 |
437 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.06340 |
438 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79537 |
439 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 415.80503 |
440 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 415.80503 |
441 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 415.80503 |
442 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 14572.62327 |
443 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.06340 |
444 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
445 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 415.80503 |
446 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14572.62327 |
447 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 199.43769 |
448 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.58240 |
449 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74470 |
450 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 199.43769 |
451 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 199.43769 |
452 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 199.43769 |
453 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 11711.36429 |
454 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.58240 |
455 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
456 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 199.43769 |
457 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 11711.36429 |
458 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 304.93640 |
459 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.79814 |
460 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.78605 |
461 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 304.93640 |
462 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 304.93640 |
463 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 304.93640 |
464 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 14535.38661 |
465 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.79814 |
466 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
467 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 304.93640 |
468 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 14535.38661 |
469 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
470 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
471 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
472 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
473 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
474 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
475 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
476 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
477 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
478 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
479 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
480 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
481 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
482 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
483 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
484 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
485 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
486 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
487 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
488 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
489 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
490 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
491 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
492 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
493 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
494 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
495 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
496 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
497 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
498 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
499 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
500 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
501 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
502 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
503 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
504 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
505 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
506 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
507 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
508 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
509 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
510 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
511 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
512 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
513 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
514 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
515 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
516 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
517 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
518 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
519 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
520 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
521 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
522 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
523 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
524 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
525 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
526 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
527 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
528 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
529 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
530 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
531 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
532 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
533 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
534 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
535 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
536 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
537 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
538 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
539 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
540 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
541 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
542 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
543 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
544 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
545 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
546 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
547 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
548 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
549 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
550 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
551 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
552 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
553 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
554 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
555 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
556 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
557 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
558 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
559 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
560 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
561 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
562 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
563 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
564 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
565 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
566 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
567 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
568 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
569 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
570 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
571 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
572 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
573 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
574 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
575 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
576 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
577 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
578 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
579 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
580 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
581 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
582 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
583 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
584 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
585 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
586 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
587 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
588 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
589 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
590 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
591 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
592 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
593 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
594 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.0 | 3.28 | 11.21 | 11.88 | 11.42 | 11.58 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.37 | 11.50 | 12.21 | 11.74 | 12.07 |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.30 | 11.25 | 11.93 | 11.46 | 11.64 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.0 | 3.29 | 11.21 | 11.88 | 11.42 | 11.58 |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.5 | 3.37 | 11.51 | 12.21 | 11.74 | 12.08 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.29 | 11.24 | 11.91 | 11.45 | 11.62 |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.0 | 3.27 | 11.16 | 11.83 | 11.37 | 11.50 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.36 | 11.45 | 12.15 | 11.68 | 11.97 |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.28 | 11.20 | 11.87 | 11.41 | 11.56 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.0 | 3.27 | 11.16 | 11.83 | 11.37 | 11.50 |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.36 | 11.45 | 12.15 | 11.68 | 11.98 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.86 | 11.40 | 11.54 |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.28 | 11.20 | 11.87 | 11.41 | 11.57 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.36 | 11.47 | 12.17 | 11.70 | 12.01 |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.30 | 11.25 | 11.93 | 11.47 | 11.65 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.28 | 11.19 | 11.87 | 11.41 | 11.55 |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.6 | 3.36 | 11.45 | 12.15 | 11.68 | 11.98 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.8 | 3.29 | 11.24 | 11.92 | 11.45 | 11.63 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 01/21 | 01/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 8 |
2 | 8 |
3 | 7 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | -15.2 | 0.00 | DefaultMultipliers | Wetbulb | -26.20 | {C} | 14. | 310 | 1122.1 | 0.00 | No | No |
2 | 88.16 | 10.60 | DefaultMultipliers | Wetbulb | 23.10 | {C} | 14. | 200 | 1319.0 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 21 | 1229.0 | 0.1415 | 5.7310E-002 | 1.0 | -11.15 | -20. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CRAWLSPACE | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.000211534 | 0.000155953 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.000783203 | 0.000220943 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.108646060 | 0.191847929 | Pass | Pass | 0.053501808 | 0.150994825 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.125693152 | 0.225163831 | Pass | Pass | 0.069608379 | 0.243919215 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.108540403 | 0.197468920 | Pass | Pass | 0.048258534 | 0.152102238 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.110131281 | 0.193614368 | Pass | Pass | 0.053590913 | 0.152250187 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.126121556 | 0.225548403 | Pass | Pass | 0.069581953 | 0.244160115 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.110140134 | 0.199522623 | Pass | Pass | 0.047533768 | 0.153229751 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.105691013 | 0.193634959 | Pass | Pass | 0.072396673 | 0.215842956 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.137241404 | 0.243988593 | Pass | Pass | 0.150482982 | 0.556127351 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.114174314 | 0.207096107 | Pass | Pass | 0.074815047 | 0.235225047 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.106894339 | 0.195373136 | Pass | Pass | 0.072561041 | 0.218015732 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.137439570 | 0.244289246 | Pass | Pass | 0.150571717 | 0.556069420 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.115866017 | 0.209627763 | Pass | Pass | 0.074116801 | 0.238171800 | Pass | Pass |
15 | ATTIC | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.000084819 | 0.000036400 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.104420337 | 0.194861209 | Pass | Pass | 0.048439772 | 0.157646483 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.102812044 | 0.192584207 | Pass | Pass | 0.049161629 | 0.156049306 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.102784324 | 0.186997111 | Pass | Pass | 0.055037049 | 0.154846300 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.119125100 | 0.219232827 | Pass | Pass | 0.070987108 | 0.250473912 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.119281942 | 0.219617114 | Pass | Pass | 0.071247318 | 0.251656653 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 0.103261434 | 0.187641842 | Pass | Pass | 0.054878043 | 0.154993757 | Pass | Pass |
22 | CRAWLSPACE | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.213878112 | 0.125823073 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.043880984 | 0.023979616 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.008569706 | 0.049869769 | Pass | Pass | 0.141276606 | 0.270469397 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.014302869 | 0.070801075 | Pass | Pass | 0.124607710 | 0.358432206 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000187087 | 0.000791015 | Pass | Pass | 0.088015910 | 0.090704735 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.007146613 | 0.040763340 | Pass | Pass | 0.136755181 | 0.235462299 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.011076947 | 0.062529414 | Pass | Pass | 0.118027638 | 0.340882983 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000196480 | 0.000804373 | Pass | Pass | 0.088359963 | 0.097263482 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.006822688 | 0.037202277 | Pass | Pass | 0.117188701 | 0.199551626 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.011281428 | 0.057937855 | Pass | Pass | 0.099127349 | 0.280275183 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000186835 | 0.000786094 | Pass | Pass | 0.077583371 | 0.074185648 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.005292788 | 0.027472504 | Pass | Pass | 0.112346760 | 0.173922944 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.008499501 | 0.047671365 | Pass | Pass | 0.088866883 | 0.228793708 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000854835 | 0.007482190 | Pass | Pass | 0.082283454 | 0.089067994 | Pass | Pass |
36 | ATTIC | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.411738964 | 0.279764402 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000231110 | 0.000802506 | Pass | Pass | 0.075608529 | 0.078142566 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000207438 | 0.000785248 | Pass | Pass | 0.075967940 | 0.072695999 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.005677145 | 0.028464878 | Pass | Pass | 0.114820576 | 0.202565186 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.006272204 | 0.036266989 | Pass | Pass | 0.084327307 | 0.193955146 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.008460999 | 0.045479847 | Pass | Pass | 0.090029558 | 0.232704295 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.004256820 | 0.020672172 | Pass | Pass | 0.111859947 | 0.168628493 | Pass | Pass |
43 | CRAWLSPACE | RunPeriod: ANNUAL | 0.123472497 | 0.119974858 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.008025530 | 0.004292060 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000197 | 0.000000897 | Pass | Pass | 0.037769945 | 0.052842728 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000127 | 0.000000577 | Pass | Pass | 0.050509965 | 0.080417853 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000191 | 0.000000885 | Pass | Pass | 0.043316839 | 0.064754929 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000208 | 0.000000937 | Pass | Pass | 0.032947165 | 0.044188342 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000139 | 0.000000624 | Pass | Pass | 0.043931985 | 0.073051162 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000202 | 0.000000920 | Pass | Pass | 0.035233370 | 0.048846764 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000141 | 0.000000643 | Pass | Pass | 0.052610208 | 0.082502206 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000059 | 0.000000266 | Pass | Pass | 0.145344058 | 0.323164929 | Pass | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000135 | 0.000000626 | Pass | Pass | 0.059636973 | 0.098148841 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000154 | 0.000000698 | Pass | Pass | 0.045504980 | 0.070703019 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000072 | 0.000000334 | Pass | Pass | 0.118159010 | 0.257056855 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000148 | 0.000000674 | Pass | Pass | 0.048191943 | 0.076151704 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.131963443 | 0.139336814 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000201 | 0.000000909 | Pass | Pass | 0.033216661 | 0.043604010 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000191 | 0.000000876 | Pass | Pass | 0.038996049 | 0.054246721 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000196 | 0.000000887 | Pass | Pass | 0.035707379 | 0.046254357 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000136 | 0.000000608 | Pass | Pass | 0.043174177 | 0.067503132 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000125 | 0.000000566 | Pass | Pass | 0.047941079 | 0.072227087 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000206 | 0.000000922 | Pass | Pass | 0.031856638 | 0.040496849 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2293276.17 | 564169.28 | 0.00 | 0.00 | 155539.38 | 3012988.87 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -15.2 | 0.00 | -15.2 | Wetbulb [F] | 1122.10 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 88.16 | 19.08 | 73.58 | Wetbulb [F] | 1318.96 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 270.00 | 90.00 | W |
BGFLOOR | INTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.018 | 0.019 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.300 | 0.335 | 0.883 | ||||||||||||
North Total or Average | 531.68 | 0.300 | 0.335 | 0.883 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.300 | 0.335 | 0.883 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.94 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.94 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.94 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.94 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.94 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.94 | 0.00 | 1.00 | 0.97 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.95 | 0.98 | 0.97 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.2915 | 43219.92 | 12599.76 | 11336.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1257.69 | 5508.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 12899.40 | 10229.11 | 2670.29 | 0.79 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6526.88 | 4793.51 | 1733.37 | 0.73 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10006.39 | 7850.52 | 2155.87 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 12476.69 | 9889.30 | 2587.39 | 0.79 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6466.21 | 4737.25 | 1728.96 | 0.73 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9434.92 | 7421.39 | 2013.54 | 0.79 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12365.12 | 9893.74 | 2471.38 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6307.81 | 4698.66 | 1609.16 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9874.41 | 7846.95 | 2027.46 | 0.79 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11942.32 | 9555.61 | 2386.71 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6167.00 | 4592.24 | 1574.76 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9281.46 | 7403.58 | 1877.87 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12958.82 | 10290.08 | 2668.75 | 0.79 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6936.57 | 5139.20 | 1797.37 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10172.23 | 7976.90 | 2195.34 | 0.78 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12760.82 | 10149.51 | 2611.31 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6988.83 | 5204.55 | 1784.28 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9577.67 | 7528.50 | 2049.17 | 0.79 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.0 | 3.28 | 11.21 | 11.88 | 11.42 | 11.58 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.37 | 11.50 | 12.21 | 11.74 | 12.07 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.30 | 11.25 | 11.93 | 11.46 | 11.64 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.0 | 3.29 | 11.21 | 11.88 | 11.42 | 11.58 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.5 | 3.37 | 11.51 | 12.21 | 11.74 | 12.08 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.29 | 11.24 | 11.91 | 11.45 | 11.62 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.0 | 3.27 | 11.16 | 11.83 | 11.37 | 11.50 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.36 | 11.45 | 12.15 | 11.68 | 11.97 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.28 | 11.20 | 11.87 | 11.41 | 11.56 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.0 | 3.27 | 11.16 | 11.83 | 11.37 | 11.50 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.36 | 11.45 | 12.15 | 11.68 | 11.98 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.7 | 3.28 | 11.18 | 11.86 | 11.40 | 11.54 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.28 | 11.20 | 11.87 | 11.41 | 11.57 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.36 | 11.47 | 12.17 | 11.70 | 12.01 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.30 | 11.25 | 11.93 | 11.47 | 11.65 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.28 | 11.19 | 11.87 | 11.41 | 11.55 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.6 | 3.36 | 11.45 | 12.15 | 11.68 | 11.98 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.8 | 3.29 | 11.24 | 11.92 | 11.45 | 11.63 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 14760.01 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 11896.53 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 14735.82 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 14770.69 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 11905.08 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 14742.34 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 11320.54 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 8472.93 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 11289.53 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 11333.33 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 8483.75 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 11298.64 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 14556.14 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 11696.19 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 14521.49 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 14572.62 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 11711.36 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 14535.39 | 1.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3319.56 | 3.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.03 | 44.99 | 8.04 | 0.18 | 0.00 | 17.66 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 417.19 | 208.93 | 0.50 | 1.00 | 1.75 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 180.75 | 90.52 | 0.50 | 1.00 | 2.84 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 317.05 | 158.78 | 0.50 | 1.00 | 2.02 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 403.05 | 201.85 | 0.50 | 1.00 | 1.78 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 178.53 | 89.41 | 0.50 | 1.00 | 2.86 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 300.90 | 150.69 | 0.50 | 1.00 | 2.08 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 408.92 | 204.79 | 0.50 | 1.00 | 1.77 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 180.13 | 90.21 | 0.50 | 1.00 | 2.85 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 321.05 | 160.78 | 0.50 | 1.00 | 2.00 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 394.95 | 197.79 | 0.50 | 1.00 | 1.80 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 175.96 | 88.12 | 0.50 | 1.00 | 2.89 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 303.67 | 152.08 | 0.50 | 1.00 | 2.07 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 420.52 | 210.60 | 0.50 | 1.00 | 1.75 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 195.96 | 98.13 | 0.50 | 1.00 | 2.69 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 321.92 | 161.22 | 0.50 | 1.00 | 2.00 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 415.80 | 208.23 | 0.50 | 1.00 | 1.76 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 199.44 | 99.88 | 0.50 | 1.00 | 2.66 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 304.93 | 152.71 | 0.50 | 1.00 | 2.06 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.95 | 4427.63 | 1.00 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9356.09 | 9356.09 | 7.79 | 417.190 | 417.190 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00872 | 83.90 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4053.53 | 4053.53 | 3.38 | 180.748 | 180.748 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00942 | 80.72 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7110.38 | 7110.38 | 5.92 | 317.049 | 317.049 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.00 | 75.00 | 0.00875 | 81.86 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9038.91 | 9038.91 | 7.53 | 403.049 | 403.049 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00875 | 83.10 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4003.86 | 4003.86 | 3.34 | 178.534 | 178.534 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 75.00 | 75.00 | 0.00948 | 80.37 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6748.23 | 6748.23 | 5.62 | 300.903 | 300.903 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 75.00 | 75.00 | 0.00880 | 79.83 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9170.92 | 9170.92 | 7.64 | 408.920 | 408.920 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00852 | 83.58 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4039.84 | 4039.84 | 3.36 | 180.132 | 180.132 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00900 | 80.72 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7200.39 | 7200.39 | 6.00 | 321.053 | 321.053 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 75.00 | 75.00 | 0.00848 | 82.34 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8857.67 | 8857.67 | 7.38 | 394.955 | 394.955 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 75.00 | 75.00 | 0.00856 | 82.63 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3946.15 | 3946.15 | 3.29 | 175.955 | 175.955 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 75.00 | 75.00 | 0.00905 | 80.02 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6810.45 | 6810.45 | 5.67 | 303.667 | 303.667 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 75.00 | 75.00 | 0.00851 | 80.37 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6838.51 | 6838.51 | 5.70 | 304.928 | 304.928 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 75.00 | 75.00 | 0.00878 | 80.37 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7219.67 | 7219.67 | 6.01 | 321.923 | 321.923 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 75.00 | 75.00 | 0.00874 | 82.34 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9430.84 | 9430.84 | 7.86 | 420.524 | 420.524 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00872 | 83.58 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4472.65 | 4472.65 | 3.73 | 199.438 | 199.438 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 75.00 | 75.00 | 0.00933 | 80.02 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 4394.62 | 4394.62 | 3.66 | 195.957 | 195.957 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00933 | 80.72 | 0.01536 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9324.83 | 9324.83 | 7.77 | 415.799 | 415.799 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 75.00 | 75.00 | 0.00874 | 82.63 | 0.01536 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10868.99 | 10868.99 | 9.05 | 207.421 | 207.421 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7963.14 | 7963.14 | 6.63 | 151.970 | 151.970 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00682 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10844.45 | 10844.45 | 9.03 | 206.953 | 206.953 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10879.83 | 10879.83 | 9.06 | 207.628 | 207.628 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7971.81 | 7971.81 | 6.64 | 152.135 | 152.135 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00682 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10851.06 | 10851.06 | 9.04 | 207.079 | 207.079 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7378.49 | 7378.49 | 6.15 | 140.821 | 140.821 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00746 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4488.74 | 4488.74 | 3.74 | 85.671 | 85.671 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00750 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7347.01 | 7347.01 | 6.12 | 140.220 | 140.220 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00745 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7391.47 | 7391.47 | 6.16 | 141.069 | 141.069 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00746 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4499.71 | 4499.71 | 3.75 | 85.881 | 85.881 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00750 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7356.26 | 7356.26 | 6.13 | 140.397 | 140.397 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00745 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 10641.05 | 10641.05 | 8.86 | 203.071 | 203.071 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00694 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 10626.94 | 10626.94 | 8.85 | 202.802 | 202.802 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00694 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10662.11 | 10662.11 | 8.88 | 203.473 | 203.473 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00694 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 7775.24 | 7775.24 | 6.48 | 148.384 | 148.384 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00680 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7759.84 | 7759.84 | 6.46 | 148.090 | 148.090 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00680 | -15.2 | 0.00036 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10678.83 | 10678.83 | 8.89 | 203.792 | 203.792 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00695 | -15.2 | 0.00036 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 417.19 | 417.19 | 207.42 | 207.42 | 417.1900 | 417.1900 | 417.1900 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.75 | 180.75 | 151.97 | 151.97 | 180.7479 | 180.7479 | 180.7479 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 317.05 | 317.05 | 206.95 | 206.95 | 317.0495 | 317.0495 | 317.0495 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 403.05 | 403.05 | 207.63 | 207.63 | 403.0487 | 403.0487 | 403.0487 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 178.53 | 178.53 | 152.14 | 152.14 | 178.5341 | 178.5341 | 178.5341 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 300.90 | 300.90 | 207.08 | 207.08 | 300.9027 | 300.9027 | 300.9027 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 408.92 | 408.92 | 140.82 | 140.82 | 408.9205 | 408.9205 | 408.9205 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 180.13 | 180.13 | 85.67 | 85.67 | 180.1318 | 180.1318 | 180.1318 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.05 | 321.05 | 140.22 | 140.22 | 321.0528 | 321.0528 | 321.0528 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 394.95 | 394.95 | 141.07 | 141.07 | 394.9548 | 394.9548 | 394.9548 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 175.96 | 175.96 | 85.88 | 85.88 | 175.9550 | 175.9550 | 175.9550 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 303.67 | 303.67 | 140.40 | 140.40 | 303.6671 | 303.6671 | 303.6671 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.52 | 420.52 | 203.47 | 203.47 | 420.5241 | 420.5241 | 420.5241 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 195.96 | 195.96 | 148.09 | 148.09 | 195.9572 | 195.9572 | 195.9572 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.92 | 321.92 | 202.80 | 202.80 | 321.9229 | 321.9229 | 321.9229 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 415.80 | 415.80 | 203.79 | 203.79 | 415.7985 | 415.7985 | 415.7985 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 199.44 | 199.44 | 148.38 | 148.38 | 199.4378 | 199.4378 | 199.4378 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 304.93 | 304.93 | 203.07 | 203.07 | 304.9279 | 304.9279 | 304.9279 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 12899.397 | 10229.111 | 417.190047 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 12870.07 | 10435.08 | 417.190047 | 77.58 | 62.84 | 0.00943207 | 53.60 | 51.52 | 0.00800000 | 83.90 | 0.01536070 | 72.47 | 10.7852 | 75.00 | 0.00871535 | 45.0364 | 9356.09 | 0.00 | 12904.78 | 9979.14 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 14760.011 | 14760.011 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14760.01 | 14760.01 | 417.190047 | 62.59 | 52.07 | 0.00624968 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 10.7852 | 71.99 | 0.00696153 | 39.9077 | 10868.99 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 6526.879 | 4793.507 | 180.747862 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6194.86 | 4230.18 | 180.747862 | 78.04 | 65.07 | 0.01089726 | 53.60 | 51.52 | 0.00800000 | 80.72 | 0.01535744 | 71.59 | 24.8938 | 75.00 | 0.00913786 | 47.1890 | 4020.58 | 0.00 | 6529.60 | 4689.91 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 11896.531 | 11896.531 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11896.53 | 11896.53 | 180.747862 | 50.30 | 44.58 | 0.00521350 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 24.8938 | 71.99 | 0.00682173 | 39.1137 | 7963.14 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 10006.389 | 7850.520 | 317.049477 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 9823.15 | 7707.56 | 317.049477 | 77.60 | 63.21 | 0.00968535 | 53.60 | 51.52 | 0.00800000 | 81.86 | 0.01535861 | 71.91 | 14.1918 | 75.00 | 0.00874558 | 45.1898 | 7097.85 | 0.00 | 10010.56 | 7661.61 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 14735.823 | 14735.823 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14735.82 | 14735.82 | 317.049477 | 59.62 | 50.40 | 0.00602316 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 14.1918 | 71.99 | 0.00695956 | 39.8965 | 10844.45 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 12476.690 | 9889.300 | 403.048691 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 12383.63 | 9963.62 | 403.048691 | 77.53 | 62.90 | 0.00948765 | 53.60 | 51.52 | 0.00800000 | 83.10 | 0.01535988 | 72.26 | 11.1637 | 75.00 | 0.00874971 | 45.2115 | 9038.91 | 0.00 | 12481.90 | 9647.34 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 14770.689 | 14770.689 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14770.69 | 14770.69 | 403.048691 | 62.26 | 51.89 | 0.00622548 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 11.1637 | 71.99 | 0.00696239 | 39.9126 | 10879.83 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 6466.209 | 4737.253 | 178.534136 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 6118.76 | 4144.98 | 178.534136 | 77.97 | 65.14 | 0.01096311 | 53.60 | 51.52 | 0.00800000 | 80.37 | 0.01535708 | 71.50 | 25.2025 | 75.00 | 0.00948924 | 48.9754 | 3992.37 | 0.00 | 6468.91 | 4634.83 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 11905.075 | 11905.075 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11905.08 | 11905.08 | 178.534136 | 50.03 | 44.41 | 0.00519433 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 25.2025 | 71.99 | 0.00682277 | 39.1196 | 7971.81 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 9434.921 | 7421.386 | 300.902709 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 9154.00 | 7085.61 | 300.902709 | 77.35 | 63.26 | 0.00977619 | 53.60 | 51.52 | 0.00800000 | 79.83 | 0.01535653 | 71.34 | 14.9533 | 75.00 | 0.00878901 | 45.4111 | 6728.29 | 0.00 | 9438.86 | 7241.25 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 14742.340 | 14742.340 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14742.34 | 14742.34 | 300.902709 | 58.96 | 50.02 | 0.00597336 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 14.9533 | 71.99 | 0.00696009 | 39.8995 | 10851.06 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 12365.117 | 9893.742 | 408.920461 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 12352.93 | 10226.07 | 408.920461 | 77.57 | 62.61 | 0.00927575 | 53.60 | 51.52 | 0.00800000 | 83.58 | 0.01536037 | 72.39 | 11.0034 | 75.00 | 0.00852346 | 44.0572 | 9170.92 | 0.00 | 12370.28 | 9649.40 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11320.544 | 11320.544 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11320.54 | 11320.54 | 408.920461 | 62.41 | 52.77 | 0.00667545 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 11.0034 | 72.00 | 0.00745611 | 42.7032 | 7378.49 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6307.812 | 4698.656 | 180.131848 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6027.14 | 4261.23 | 180.131848 | 78.05 | 64.64 | 0.01058573 | 53.60 | 51.52 | 0.00800000 | 80.72 | 0.01535744 | 71.59 | 24.9789 | 75.00 | 0.00869066 | 44.9097 | 3960.44 | 0.00 | 6310.44 | 4595.02 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 8472.934 | 8472.934 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8472.93 | 8472.93 | 180.131848 | 50.23 | 45.60 | 0.00571904 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 24.9789 | 72.00 | 0.00750293 | 42.9667 | 4488.74 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 9874.410 | 7846.949 | 321.052752 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 9762.75 | 7907.74 | 321.052752 | 77.65 | 62.88 | 0.00944324 | 53.60 | 51.52 | 0.00800000 | 82.34 | 0.01535910 | 72.05 | 14.0148 | 75.00 | 0.00847738 | 43.8216 | 7189.54 | 0.00 | 9878.53 | 7653.18 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 11289.525 | 11289.525 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11289.53 | 11289.53 | 321.052752 | 59.78 | 51.28 | 0.00646003 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 14.0148 | 72.00 | 0.00745407 | 42.6916 | 7347.01 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 11942.318 | 9555.608 | 394.954795 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 11859.61 | 9739.59 | 394.954795 | 77.49 | 62.66 | 0.00933155 | 53.60 | 51.52 | 0.00800000 | 82.63 | 0.01535940 | 72.12 | 11.3924 | 75.00 | 0.00855654 | 44.2260 | 8857.67 | 0.00 | 11947.30 | 9319.63 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 11333.335 | 11333.335 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11333.33 | 11333.33 | 394.954795 | 62.07 | 52.58 | 0.00664858 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 11.3924 | 72.00 | 0.00745695 | 42.7079 | 7391.47 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 6167.003 | 4592.242 | 175.955008 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 5864.41 | 4103.97 | 175.955008 | 77.91 | 64.70 | 0.01066280 | 53.60 | 51.52 | 0.00800000 | 80.02 | 0.01535672 | 71.40 | 25.5719 | 75.00 | 0.00905941 | 46.7878 | 3941.65 | 0.00 | 6169.58 | 4490.85 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 8483.752 | 8483.752 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8483.75 | 8483.75 | 175.955008 | 49.71 | 45.27 | 0.00567743 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 25.5719 | 72.00 | 0.00750392 | 42.9722 | 4499.71 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 9281.457 | 7403.583 | 303.667141 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 9073.01 | 7255.76 | 303.667141 | 77.42 | 62.92 | 0.00952805 | 53.60 | 51.52 | 0.00800000 | 80.37 | 0.01535708 | 71.50 | 14.8172 | 75.00 | 0.00850541 | 43.9646 | 6776.75 | 0.00 | 9285.33 | 7221.62 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 11298.639 | 11298.639 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11298.64 | 11298.64 | 303.667141 | 59.08 | 50.88 | 0.00640363 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 14.8172 | 72.00 | 0.00745467 | 42.6950 | 7356.26 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 12958.824 | 10290.077 | 420.524099 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 12910.02 | 10469.88 | 420.524099 | 77.54 | 62.82 | 0.00942819 | 53.60 | 51.52 | 0.00800000 | 83.58 | 0.01536037 | 72.39 | 10.6997 | 75.00 | 0.00871741 | 45.0469 | 9430.84 | 0.00 | 12964.23 | 10035.49 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 14556.144 | 14556.144 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14556.14 | 14556.14 | 420.524099 | 62.67 | 52.08 | 0.00623994 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 10.6997 | 71.99 | 0.00694430 | 39.8100 | 10662.11 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6936.574 | 5139.203 | 195.957243 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6613.05 | 4601.09 | 195.957243 | 77.93 | 64.79 | 0.01071723 | 53.60 | 51.52 | 0.00800000 | 80.72 | 0.01535744 | 71.59 | 22.9616 | 75.00 | 0.00908866 | 46.9385 | 4208.44 | 0.00 | 6939.47 | 5026.00 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 11696.191 | 11696.191 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11696.19 | 11696.19 | 195.957243 | 51.98 | 45.59 | 0.00531878 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 22.9616 | 71.99 | 0.00679636 | 38.9698 | 7759.84 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 10172.230 | 7976.895 | 321.922868 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 10014.28 | 7883.59 | 321.922868 | 77.65 | 63.20 | 0.00966257 | 53.60 | 51.52 | 0.00800000 | 82.34 | 0.01535910 | 72.05 | 13.9769 | 75.00 | 0.00873589 | 45.1404 | 7212.29 | 0.00 | 10176.48 | 7784.70 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 14521.487 | 14521.487 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14521.49 | 14521.49 | 321.922868 | 59.81 | 50.48 | 0.00602170 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 13.9769 | 71.99 | 0.00694139 | 39.7935 | 10626.94 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 12760.819 | 10149.510 | 415.798520 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 12644.48 | 10209.26 | 415.798520 | 77.45 | 62.83 | 0.00945681 | 53.60 | 51.52 | 0.00800000 | 82.63 | 0.01535940 | 72.12 | 10.8213 | 75.00 | 0.00873259 | 45.1243 | 9302.85 | 0.00 | 12766.14 | 9899.41 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 14572.623 | 14572.623 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14572.62 | 14572.62 | 415.798520 | 62.56 | 52.03 | 0.00623317 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 10.8213 | 71.99 | 0.00694568 | 39.8178 | 10678.83 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 6988.831 | 5204.553 | 199.437765 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 6646.65 | 4628.27 | 199.437765 | 77.75 | 64.69 | 0.01069258 | 53.60 | 51.52 | 0.00800000 | 80.02 | 0.01535672 | 71.40 | 22.5609 | 75.00 | 0.00934691 | 48.2517 | 4468.81 | 0.00 | 6991.75 | 5089.67 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 11711.364 | 11711.364 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11711.36 | 11711.36 | 199.437765 | 52.33 | 45.81 | 0.00534605 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 22.5609 | 71.99 | 0.00679829 | 38.9807 | 7775.24 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 9577.669 | 7528.500 | 304.927860 | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 9321.40 | 7242.12 | 304.927860 | 77.42 | 63.25 | 0.00975139 | 53.60 | 51.52 | 0.00800000 | 80.37 | 0.01535708 | 71.50 | 14.7559 | 75.00 | 0.00877318 | 45.3305 | 6815.92 | 0.00 | 9581.67 | 7345.45 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 14535.387 | 14535.387 | -999. | -999. | -999.00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14535.39 | 14535.39 | 304.927860 | 59.13 | 50.09 | 0.00597144 | 122.00 | 74.12 | 0.00800000 | -15.2 | 0.00036134 | -15.2 | 14.7559 | 71.99 | 0.00694256 | 39.8001 | 10641.05 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3407.232 | 3342.494 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3435.032 | 3369.766 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3422.966 | 3357.930 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3405.810 | 3341.099 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3434.979 | 3369.715 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3422.881 | 3357.847 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3496.174 | 3429.747 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3517.771 | 3450.933 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3496.148 | 3429.721 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3496.170 | 3429.743 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3517.715 | 3450.878 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3495.942 | 3429.519 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3409.212 | 3344.437 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3434.827 | 3369.566 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3422.874 | 3357.840 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3408.619 | 3343.855 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3434.807 | 3369.546 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3422.777 | 3357.745 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3319.56 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12899.397 | 10229.111 | 417.190047 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 417.190047 | 0.49860646 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 12870.07 | 10435.08 | 1.0023 | 0.49860646 | 417.190047 | 77.58 | 62.84 | 0.00943207 | 11.8 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 712.859 | 12157.21 | 83.90 | 0.01536070 | 72.47 | 44.99498340 | 10.7852 | 75.00 | 0.00871535 | 75.00 | 0.00871535 | 45.0364 | 9356.09 | 0.00 | 12904.78 | 9979.14 | 0.47891528 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.31 | 56.29 | 0.00963707 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14760.011 | 14760.011 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 417.190047 | 0.49860646 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14760.01 | 14760.01 | 1.0000 | 0.49860646 | 417.190047 | 62.59 | 52.07 | 0.00624968 | 7.9 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14760.01 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 10.7852 | 71.99 | 0.00696153 | 71.99 | 0.00696153 | 39.9077 | 10868.99 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6526.879 | 4793.507 | 180.747862 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2448 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 180.747862 | 0.21602158 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6194.86 | 4230.18 | 1.0536 | 0.21602158 | 180.747862 | 78.04 | 65.07 | 0.01089726 | 12.8 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 308.847 | 5886.01 | 80.72 | 0.01535744 | 71.59 | 44.99498340 | 24.8938 | 75.00 | 0.00941894 | 75.00 | 0.00913786 | 47.1890 | 4020.58 | 0.00 | 6529.60 | 4689.91 | 0.20749036 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.26 | 54.25 | 0.00893850 | 8.4 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11896.531 | 11896.531 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 180.747862 | 0.21602158 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11896.53 | 11896.53 | 1.0000 | 0.21602158 | 180.747862 | 50.30 | 44.58 | 0.00521350 | 5.6 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11896.53 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 24.8938 | 71.99 | 0.00682173 | 71.99 | 0.00682173 | 39.1137 | 7963.14 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10006.389 | 7850.520 | 317.049477 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2443 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 317.049477 | 0.37892304 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 9823.15 | 7707.56 | 1.0187 | 0.37892304 | 317.049477 | 77.60 | 63.21 | 0.00968535 | 12.0 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 541.747 | 9281.40 | 81.86 | 0.01535861 | 71.91 | 44.99498340 | 14.1918 | 75.00 | 0.00874705 | 75.00 | 0.00874558 | 45.1898 | 7097.85 | 0.00 | 10010.56 | 7661.61 | 0.36395844 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.06 | 56.04 | 0.00954967 | 9.0 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14735.823 | 14735.823 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 317.049477 | 0.37892304 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14735.82 | 14735.82 | 1.0000 | 0.37892304 | 317.049477 | 59.62 | 50.40 | 0.00602316 | 7.3 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14735.82 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 14.1918 | 71.99 | 0.00695956 | 71.99 | 0.00695956 | 39.8965 | 10844.45 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12476.690 | 9889.300 | 403.048691 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 403.048691 | 0.48170536 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 12383.63 | 9963.62 | 1.0075 | 0.48170536 | 403.048691 | 77.53 | 62.90 | 0.00948765 | 11.8 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 688.695 | 11694.94 | 83.10 | 0.01535988 | 72.26 | 44.99498340 | 11.1637 | 75.00 | 0.00874971 | 75.00 | 0.00874971 | 45.2115 | 9038.91 | 0.00 | 12481.90 | 9647.34 | 0.46268164 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.29 | 56.27 | 0.00963265 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14770.689 | 14770.689 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 403.048691 | 0.48170536 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14770.69 | 14770.69 | 1.0000 | 0.48170536 | 403.048691 | 62.26 | 51.89 | 0.00622548 | 7.8 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14770.69 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 11.1637 | 71.99 | 0.00696239 | 71.99 | 0.00696239 | 39.9126 | 10879.83 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6466.209 | 4737.253 | 178.534136 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2449 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 178.534136 | 0.21337583 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 6118.76 | 4144.98 | 1.0568 | 0.21337583 | 178.534136 | 77.97 | 65.14 | 0.01096311 | 12.8 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 305.064 | 5813.70 | 80.37 | 0.01535708 | 71.50 | 44.99498340 | 25.2025 | 75.00 | 0.00948260 | 75.00 | 0.00948924 | 48.9754 | 3992.37 | 0.00 | 6468.91 | 4634.83 | 0.20494910 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.25 | 54.20 | 0.00891759 | 8.3 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11905.075 | 11905.075 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 178.534136 | 0.21337583 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11905.08 | 11905.08 | 1.0000 | 0.21337583 | 178.534136 | 50.03 | 44.41 | 0.00519433 | 5.5 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11905.08 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 25.2025 | 71.99 | 0.00682277 | 71.99 | 0.00682277 | 39.1196 | 7971.81 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9434.921 | 7421.386 | 300.902709 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2443 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 300.902709 | 0.35962516 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | Sensible | 9154.00 | 7085.61 | 1.0307 | 0.35962516 | 300.902709 | 77.35 | 63.26 | 0.00977619 | 12.0 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 514.157 | 8639.84 | 79.83 | 0.01535653 | 71.34 | 44.99498340 | 14.9533 | 75.00 | 0.00879503 | 75.00 | 0.00878901 | 45.4111 | 6728.29 | 0.00 | 9438.86 | 7241.25 | 0.34542268 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.16 | 56.12 | 0.00957293 | 9.0 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14742.340 | 14742.340 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 300.902709 | 0.35962516 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14742.34 | 14742.34 | 1.0000 | 0.35962516 | 300.902709 | 58.96 | 50.02 | 0.00597336 | 7.2 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14742.34 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 14.9533 | 71.99 | 0.00696009 | 71.99 | 0.00696009 | 39.8995 | 10851.06 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12365.117 | 9893.742 | 408.920461 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 408.920461 | 0.48872303 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 12352.93 | 10226.07 | 1.0010 | 0.48872303 | 408.920461 | 77.57 | 62.61 | 0.00927575 | 11.7 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 698.729 | 11654.20 | 83.58 | 0.01536037 | 72.39 | 44.99498340 | 11.0034 | 75.00 | 0.00852346 | 75.00 | 0.00852346 | 44.0572 | 9170.92 | 0.00 | 12370.28 | 9649.40 | 0.46942217 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.63 | 56.55 | 0.00971628 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11320.544 | 11320.544 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 408.920461 | 0.48872303 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11320.54 | 11320.54 | 1.0000 | 0.48872303 | 408.920461 | 62.41 | 52.77 | 0.00667545 | 8.1 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11320.54 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 11.0034 | 72.00 | 0.00745611 | 72.00 | 0.00745611 | 42.7032 | 7378.49 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6307.812 | 4698.656 | 180.131848 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2447 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 180.131848 | 0.21528535 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6027.14 | 4261.23 | 1.0466 | 0.21528535 | 180.131848 | 78.05 | 64.64 | 0.01058573 | 12.6 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 307.794 | 5719.35 | 80.72 | 0.01535744 | 71.59 | 44.99498340 | 24.9789 | 75.00 | 0.00899695 | 75.00 | 0.00869066 | 44.9097 | 3960.44 | 0.00 | 6310.44 | 4595.02 | 0.20678320 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.71 | 54.68 | 0.00908307 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8472.934 | 8472.934 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 180.131848 | 0.21528535 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8472.93 | 8472.93 | 1.0000 | 0.21528535 | 180.131848 | 50.23 | 45.60 | 0.00571904 | 5.9 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8472.93 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 24.9789 | 72.00 | 0.00750293 | 72.00 | 0.00750293 | 42.9667 | 4488.74 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9874.410 | 7846.949 | 321.052752 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 321.052752 | 0.38370757 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | Sensible | 9762.75 | 7907.74 | 1.0114 | 0.38370757 | 321.052752 | 77.65 | 62.88 | 0.00944324 | 11.8 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 548.588 | 9214.16 | 82.34 | 0.01535910 | 72.05 | 44.99498340 | 14.0148 | 75.00 | 0.00847901 | 75.00 | 0.00847738 | 43.8216 | 7189.54 | 0.00 | 9878.53 | 7653.18 | 0.36855402 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.39 | 56.35 | 0.00965502 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11289.525 | 11289.525 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 321.052752 | 0.38370757 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11289.53 | 11289.53 | 1.0000 | 0.38370757 | 321.052752 | 59.78 | 51.28 | 0.00646003 | 7.6 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11289.53 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 14.0148 | 72.00 | 0.00745407 | 72.00 | 0.00745407 | 42.6916 | 7347.01 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11942.318 | 9555.608 | 394.954795 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2441 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 394.954795 | 0.47203191 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 11859.61 | 9739.59 | 1.0070 | 0.47203191 | 394.954795 | 77.49 | 62.66 | 0.00933155 | 11.7 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 674.865 | 11184.75 | 82.63 | 0.01535940 | 72.12 | 44.99498340 | 11.3924 | 75.00 | 0.00855654 | 75.00 | 0.00855654 | 44.2260 | 8857.67 | 0.00 | 11947.30 | 9319.63 | 0.45339022 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.63 | 56.55 | 0.00971644 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11333.335 | 11333.335 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 394.954795 | 0.47203191 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11333.33 | 11333.33 | 1.0000 | 0.47203191 | 394.954795 | 62.07 | 52.58 | 0.00664858 | 8.0 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11333.33 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 11.3924 | 72.00 | 0.00745695 | 72.00 | 0.00745695 | 42.7079 | 7391.47 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6167.003 | 4592.242 | 175.955008 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2447 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 175.955008 | 0.21029338 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 5864.41 | 4103.97 | 1.0516 | 0.21029338 | 175.955008 | 77.91 | 64.70 | 0.01066280 | 12.6 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 300.657 | 5563.75 | 80.02 | 0.01535672 | 71.40 | 44.99498340 | 25.5719 | 75.00 | 0.00905007 | 75.00 | 0.00905941 | 46.7878 | 3941.65 | 0.00 | 6169.58 | 4490.85 | 0.20198838 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.69 | 54.67 | 0.00907921 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8483.752 | 8483.752 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 175.955008 | 0.21029338 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8483.75 | 8483.75 | 1.0000 | 0.21029338 | 175.955008 | 49.71 | 45.27 | 0.00567743 | 5.8 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8483.75 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 25.5719 | 72.00 | 0.00750392 | 72.00 | 0.00750392 | 42.9722 | 4499.71 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9281.457 | 7403.583 | 303.667141 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 303.667141 | 0.36292908 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | Sensible | 9073.01 | 7255.76 | 1.0230 | 0.36292908 | 303.667141 | 77.42 | 62.92 | 0.00952805 | 11.9 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 518.881 | 8554.13 | 80.37 | 0.01535708 | 71.50 | 44.99498340 | 14.8172 | 75.00 | 0.00851411 | 75.00 | 0.00850541 | 43.9646 | 6776.75 | 0.00 | 9285.33 | 7221.62 | 0.34859612 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.44 | 56.42 | 0.00968491 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11298.639 | 11298.639 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 303.667141 | 0.36292908 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11298.64 | 11298.64 | 1.0000 | 0.36292908 | 303.667141 | 59.08 | 50.88 | 0.00640363 | 7.5 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11298.64 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 14.8172 | 72.00 | 0.00745467 | 72.00 | 0.00745467 | 42.6950 | 7356.26 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12958.824 | 10290.077 | 420.524099 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 420.524099 | 0.50259117 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 12910.02 | 10469.88 | 1.0038 | 0.50259117 | 420.524099 | 77.54 | 62.82 | 0.00942819 | 11.8 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 718.556 | 12191.46 | 83.58 | 0.01536037 | 72.39 | 44.99498340 | 10.6997 | 75.00 | 0.00871741 | 75.00 | 0.00871741 | 45.0469 | 9430.84 | 0.00 | 12964.23 | 10035.49 | 0.48274262 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.36 | 56.33 | 0.00964772 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14556.144 | 14556.144 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 420.524099 | 0.50259117 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14556.14 | 14556.14 | 1.0000 | 0.50259117 | 420.524099 | 62.67 | 52.08 | 0.00623994 | 7.9 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14556.14 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 10.6997 | 71.99 | 0.00694430 | 71.99 | 0.00694430 | 39.8100 | 10662.11 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6936.574 | 5139.203 | 195.957243 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2448 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 195.957243 | 0.23419913 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6613.05 | 4601.09 | 1.0489 | 0.23419913 | 195.957243 | 77.93 | 64.79 | 0.01071723 | 12.6 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 334.835 | 6278.22 | 80.72 | 0.01535744 | 71.59 | 44.99498340 | 22.9616 | 75.00 | 0.00933419 | 75.00 | 0.00908866 | 46.9385 | 4208.44 | 0.00 | 6939.47 | 5026.00 | 0.22495004 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.56 | 54.53 | 0.00902975 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11696.191 | 11696.191 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 195.957243 | 0.23419913 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11696.19 | 11696.19 | 1.0000 | 0.23419913 | 195.957243 | 51.98 | 45.59 | 0.00531878 | 5.9 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11696.19 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 22.9616 | 71.99 | 0.00679636 | 71.99 | 0.00679636 | 38.9698 | 7759.84 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10172.230 | 7976.895 | 321.922868 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2443 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 321.922868 | 0.38474749 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | Sensible | 10014.28 | 7883.59 | 1.0158 | 0.38474749 | 321.922868 | 77.65 | 63.20 | 0.00966257 | 12.0 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 550.075 | 9464.21 | 82.34 | 0.01535910 | 72.05 | 44.99498340 | 13.9769 | 75.00 | 0.00873701 | 75.00 | 0.00873589 | 45.1404 | 7212.29 | 0.00 | 10176.48 | 7784.70 | 0.36955287 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.04 | 56.02 | 0.00954507 | 9.0 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14521.487 | 14521.487 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 321.922868 | 0.38474749 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14521.49 | 14521.49 | 1.0000 | 0.38474749 | 321.922868 | 59.81 | 50.48 | 0.00602170 | 7.3 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14521.49 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 13.9769 | 71.99 | 0.00694139 | 71.99 | 0.00694139 | 39.7935 | 10626.94 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12760.819 | 10149.510 | 415.798520 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2442 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 415.798520 | 0.49694338 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 12644.48 | 10209.26 | 1.0092 | 0.49694338 | 415.798520 | 77.45 | 62.83 | 0.00945681 | 11.8 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 710.481 | 11934.00 | 82.63 | 0.01535940 | 72.12 | 44.99498340 | 10.8213 | 75.00 | 0.00874057 | 75.00 | 0.00873259 | 45.1243 | 9302.85 | 0.00 | 12766.14 | 9899.41 | 0.47731787 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.42 | 56.37 | 0.00966316 | 9.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14572.623 | 14572.623 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 415.798520 | 0.49694338 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14572.62 | 14572.62 | 1.0000 | 0.49694338 | 415.798520 | 62.56 | 52.03 | 0.00623317 | 7.8 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14572.62 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 10.8213 | 71.99 | 0.00694568 | 71.99 | 0.00694568 | 39.8178 | 10678.83 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6988.831 | 5204.553 | 199.437765 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2447 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 199.437765 | 0.23835890 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 6646.65 | 4628.27 | 1.0515 | 0.23835890 | 199.437765 | 77.75 | 64.69 | 0.01069258 | 12.6 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 340.782 | 6305.87 | 80.02 | 0.01535672 | 71.40 | 44.99498340 | 22.5609 | 75.00 | 0.00933374 | 75.00 | 0.00934691 | 48.2517 | 4468.81 | 0.00 | 6991.75 | 5089.67 | 0.22894552 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.69 | 54.67 | 0.00907997 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11711.364 | 11711.364 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 199.437765 | 0.23835890 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11711.36 | 11711.36 | 1.0000 | 0.23835890 | 199.437765 | 52.33 | 45.81 | 0.00534605 | 5.9 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11711.36 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 22.5609 | 71.99 | 0.00679829 | 71.99 | 0.00679829 | 38.9807 | 7775.24 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9577.669 | 7528.500 | 304.927860 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2443 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 304.927860 | 0.36443583 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | Sensible | 9321.40 | 7242.12 | 1.0275 | 0.36443583 | 304.927860 | 77.42 | 63.25 | 0.00975139 | 12.0 | 53.60 | 51.52 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 521.035 | 8800.37 | 80.37 | 0.01535708 | 71.50 | 44.99498340 | 14.7559 | 75.00 | 0.00878103 | 75.00 | 0.00877318 | 45.3305 | 6815.92 | 0.00 | 9581.67 | 7345.45 | 0.35004337 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.13 | 56.10 | 0.00956626 | 9.0 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14535.387 | 14535.387 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0717 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 304.927860 | 0.36443583 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14535.39 | 14535.39 | 1.0000 | 0.36443583 | 304.927860 | 59.13 | 50.09 | 0.00597144 | 7.2 | 122.00 | 74.12 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14535.39 | -15.2 | 0.00036134 | -15.2 | 44.99498340 | 14.7559 | 71.99 | 0.00694256 | 71.99 | 0.00694256 | 39.8001 | 10641.05 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3407.232 | 3342.494 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3435.032 | 3369.766 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3422.966 | 3357.930 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3405.810 | 3341.099 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3434.979 | 3369.715 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3422.881 | 3357.847 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3496.174 | 3429.747 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3517.771 | 3450.933 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3496.148 | 3429.721 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3496.170 | 3429.743 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3517.715 | 3450.878 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3495.942 | 3429.519 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3409.212 | 3344.437 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3434.827 | 3369.566 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3422.874 | 3357.840 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3408.619 | 3343.855 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3434.807 | 3369.546 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3422.777 | 3357.745 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0717 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19123732 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3319.56 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3319.56 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2961.00 | 6544.17 | 1376.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2169.00 | 6694.50 | 871.17 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3005.00 | 6443.33 | 1313.83 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3051.17 | 6785.50 | 1623.17 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2218.67 | 6951.67 | 1146.17 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3202.00 | 6687.33 | 1659.83 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2643.00 | 6108.33 | 773.50 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1881.17 | 6176.00 | 275.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2707.67 | 6028.83 | 745.67 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2699.17 | 6364.83 | 981.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1828.17 | 6454.00 | 438.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2777.00 | 6287.83 | 936.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3151.50 | 6397.17 | 1330.67 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2982.50 | 6220.33 | 1079.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2943.67 | 6328.50 | 1145.33 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2301.00 | 6583.67 | 873.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2213.83 | 6389.33 | 630.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3034.33 | 6500.33 | 1357.33 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3804.33 | 7356.00 | 1872.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 67.33 | 0.00 | 67.33 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 92.00 | 9.50 | 92.00 | 9.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 66.50 | 0.00 | 66.50 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 101.83 | 0.00 | 101.83 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 162.50 | 0.17 | 162.50 | 0.17 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 105.00 | 0.00 | 105.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 61.17 | 0.00 | 61.17 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 103.33 | 9.33 | 103.33 | 9.33 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 65.67 | 0.00 | 65.67 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 95.67 | 0.00 | 95.67 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 183.50 | 0.00 | 183.50 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 104.67 | 0.00 | 104.67 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 100.33 | 0.00 | 100.33 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 68.67 | 0.00 | 68.67 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 62.33 | 0.00 | 62.33 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 153.33 | 0.00 | 153.33 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 90.00 | 5.67 | 90.00 | 5.67 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 91.67 | 0.00 | 91.67 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 320.17 | 12.33 | 320.17 | 12.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.160 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.140 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.160 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.159 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.140 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.269 | 0.159 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.070 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.051 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.070 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.070 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.051 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.070 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.160 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.160 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.160 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.140 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.141 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.269 | 0.160 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.259 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.258 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14131337.94 | 37916419.63 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12441136.46 | 36226218.15 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14134182.31 | 37919263.99 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14123080.59 | 37908162.28 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12431334.74 | 36216416.42 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14124551.98 | 37909633.67 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6195804.67 | 29980886.35 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 4505490.40 | 28290572.09 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6196811.25 | 29981892.94 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6191464.40 | 29976546.09 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 4501165.69 | 28286247.38 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 6192012.36 | 29977094.05 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14138318.76 | 37923400.45 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14146299.05 | 37931380.74 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14143738.82 | 37928820.51 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12444218.30 | 36229299.99 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12452732.98 | 36237814.67 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 14136676.74 | 37921758.43 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
Total Facility | 0.428131E+09 | 0.00 | 0.428131E+09 | 0.196630E+09 | 0.624762E+09 | 0.428131E+09 | 0.00 | 8808.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7327 | 71.7277 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 23.5353 | 68.5303 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7381 | 71.7331 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7171 | 71.7121 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 23.5167 | 68.5117 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7199 | 71.7148 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.7208 | 56.7158 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 8.5232 | 53.5182 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.7227 | 56.7177 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.7126 | 56.7076 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 8.5150 | 53.5100 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 11.7136 | 56.7086 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7459 | 71.7409 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7610 | 71.7560 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7562 | 71.7511 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 23.5411 | 68.5361 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 23.5572 | 68.5522 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 26.7428 | 71.7378 | 44.9950 | 0.00 | 8808.00 | 0.00 |
Total Facility | 809.9097 | 0.0000 | 809.9097 | 371.9718 | 1181.8815 | 809.9097 | 0.00 | 8808.00 | 0.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 2040 |
Defaulted Fields | 1700 |
Fields with Defaults | 7086 |
Autosized Fields | 360 |
Autosizable Fields | 612 |
Autocalculated Fields | 197 |
Autocalculatable Fields | 421 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
Electricity:Building | 99140.61 | 6270.77 | 02-JAN-03:10 | 18720.91 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5507.81 | 348.38 | 02-JAN-03:10 | 1040.05 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 87803.80 | 5989.14 | 02-JAN-04:10 | 15388.75 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:10 | 880.12 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:10 | 381.47 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
Electricity:HVAC | 149173.71 | 289.29 | 19-MAR-23:30 | 69621.55 | 06-JAN-07:20 |
Cooling:Electricity | 8401.45 | 0.00 | 01-JAN-00:10 | 12021.14 | 04-AUG-15:40 |
General:Cooling:Electricity | 8401.45 | 0.00 | 01-JAN-00:10 | 12021.14 | 04-AUG-15:40 |
Electricity:Plant | 18931.57 | 149.40 | 01-JAN-00:10 | 9389.63 | 26-JUN-07:50 |
WaterSystems:Electricity | 18931.57 | 149.40 | 01-JAN-00:10 | 9389.63 | 26-JUN-07:50 |
Fans:Electricity | 10331.48 | 289.29 | 19-MAR-23:30 | 3208.18 | 06-JAN-07:20 |
General:Fans:Electricity | 7797.33 | 0.00 | 19-MAR-23:30 | 2918.90 | 06-JAN-07:20 |
Ventilation:Fans:Electricity | 2534.14 | 289.29 | 01-JAN-00:10 | 289.29 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
ElectricityPurchased:Plant | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
Cogeneration:ElectricityPurchased | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
General:Cogeneration:ElectricityPurchased | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
ElectricityNet:Plant | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
Cogeneration:ElectricityNet | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
General:Cogeneration:ElectricityNet | 272754.59 | 7967.15 | 11-APR-03:10 | 96055.87 | 18-JAN-19:50 |
HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 130440.78 | 0.00 | 18-MAR-16:10 | 66413.36 | 06-JAN-07:20 |
General:Heating:Electricity | 130440.78 | 0.00 | 18-MAR-16:10 | 66413.36 | 06-JAN-07:20 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:Electricity | 1308.75 | 149.40 | 31-JUL-10:50 | 149.40 | 02-JAN-13:20 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1251993.96 | 13115.50 | 24-JUN-03:20 | 438090.67 | 29-JAN-07:10 |
EnergyTransfer:HVAC | 694290.27 | 0.00 | 19-MAR-23:30 | 275463.37 | 29-JAN-06:50 |
CoolingCoils:EnergyTransfer | 248911.01 | 0.00 | 01-JAN-00:10 | 173464.67 | 04-AUG-14:50 |
EnergyTransfer:Building | 396025.44 | 2966.18 | 08-NOV-11:30 | 167992.60 | 09-DEC-13:30 |
EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer | 222629.89 | 0.00 | 18-MAR-16:10 | 167992.60 | 09-DEC-13:30 |
Heating:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 222629.89 | 0.00 | 18-MAR-16:10 | 167992.60 | 09-DEC-13:30 |
Cooling:EnergyTransfer | 173395.55 | 0.00 | 01-JAN-00:10 | 111262.78 | 25-JUN-18:10 |
Cooling:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer | 173395.55 | 0.00 | 01-JAN-00:10 | 111262.78 | 25-JUN-18:10 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 25885.98 | 1.38 | 07-AUG-03:10 | 11981.88 | 09-DEC-13:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 15315.29 | 0.00 | 12-JAN-12:40 | 11981.88 | 09-DEC-13:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10570.70 | 0.00 | 01-JAN-00:10 | 9461.60 | 25-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18466.60 | 0.13 | 11-APR-14:50 | 8819.82 | 09-DEC-15:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 10390.61 | 0.00 | 12-JAN-12:00 | 8819.82 | 09-DEC-15:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8075.99 | 0.00 | 01-JAN-00:10 | 5711.57 | 04-AUG-14:50 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 25407.73 | 0.70 | 05-JUN-15:00 | 11814.25 | 09-DEC-15:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 15154.83 | 0.00 | 12-JAN-11:40 | 11814.25 | 09-DEC-15:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10252.90 | 0.00 | 01-JAN-00:10 | 6882.73 | 07-SEP-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 26121.12 | 0.10 | 03-JUN-03:00 | 11975.19 | 09-DEC-15:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 17525.79 | 0.00 | 08-FEB-16:20 | 11975.19 | 09-DEC-15:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8595.33 | 0.00 | 01-JAN-00:10 | 9178.05 | 25-JUN-18:20 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 18628.31 | 0.21 | 03-OCT-14:40 | 8840.18 | 09-DEC-15:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12554.56 | 0.00 | 18-MAR-16:10 | 8840.18 | 09-DEC-15:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6073.75 | 0.00 | 01-JAN-00:10 | 4880.79 | 25-JUN-18:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25625.73 | 0.94 | 25-SEP-23:50 | 11816.33 | 09-DEC-15:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 17372.16 | 0.00 | 18-MAR-16:10 | 11816.33 | 09-DEC-15:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8253.57 | 0.00 | 01-JAN-00:10 | 6665.06 | 26-JUN-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21488.42 | 0.26 | 26-MAY-02:40 | 9169.66 | 25-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8837.82 | 0.00 | 02-JAN-14:50 | 8393.09 | 09-DEC-12:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12650.61 | 0.00 | 01-JAN-00:10 | 9169.66 | 25-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 15250.24 | 0.45 | 18-OCT-01:00 | 5366.03 | 09-DEC-15:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4577.93 | 0.00 | 02-JAN-12:20 | 5366.03 | 09-DEC-15:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 10672.31 | 0.00 | 01-JAN-00:10 | 5128.32 | 08-SEP-15:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21122.52 | 0.12 | 29-OCT-01:00 | 8260.70 | 09-DEC-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8710.85 | 0.00 | 12-JAN-11:00 | 8260.70 | 09-DEC-16:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12411.67 | 0.00 | 01-JAN-00:10 | 7006.30 | 07-SEP-10:40 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20762.05 | 0.73 | 02-MAY-12:10 | 8915.74 | 25-JUN-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10493.61 | 0.00 | 12-JAN-15:40 | 8361.60 | 09-DEC-12:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10268.44 | 0.00 | 01-JAN-00:10 | 8915.74 | 25-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 13907.35 | 0.72 | 19-OCT-11:30 | 5378.47 | 09-DEC-15:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5878.55 | 0.00 | 07-FEB-19:40 | 5378.47 | 09-DEC-15:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8028.80 | 0.00 | 01-JAN-00:10 | 4576.30 | 06-MAY-21:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 20386.45 | 0.31 | 06-JUN-09:00 | 8264.93 | 09-DEC-13:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 10372.00 | 0.00 | 08-FEB-11:10 | 8264.93 | 09-DEC-13:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 10014.45 | 0.00 | 01-JAN-00:10 | 6662.31 | 26-JUN-09:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 26070.62 | 0.20 | 10-APR-13:00 | 11608.88 | 09-DEC-15:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 16736.52 | 0.00 | 18-MAR-15:20 | 11608.88 | 09-DEC-15:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 9334.10 | 0.00 | 01-JAN-00:10 | 6764.56 | 26-JUN-09:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 25816.74 | 0.32 | 07-NOV-04:30 | 11598.48 | 09-DEC-15:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 14814.93 | 0.00 | 12-JAN-12:00 | 11598.48 | 09-DEC-15:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 11001.82 | 0.00 | 01-JAN-00:10 | 6906.17 | 26-JUN-10:20 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 26277.46 | 0.11 | 13-JAN-15:50 | 11700.52 | 09-DEC-12:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 14982.03 | 0.00 | 12-JAN-15:20 | 11700.52 | 09-DEC-12:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11295.42 | 0.00 | 01-JAN-00:10 | 9492.07 | 25-JUN-17:40 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 19237.91 | 0.14 | 18-MAY-03:30 | 8663.60 | 09-DEC-15:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 11952.58 | 0.00 | 18-MAR-16:10 | 8663.60 | 09-DEC-15:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7285.33 | 0.00 | 01-JAN-00:10 | 4913.77 | 25-JUN-18:50 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 18996.62 | 0.13 | 02-MAY-11:40 | 8629.25 | 09-DEC-15:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 10040.65 | 0.00 | 12-JAN-12:00 | 8629.25 | 09-DEC-15:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8955.97 | 0.00 | 01-JAN-00:10 | 5945.36 | 04-AUG-14:50 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 26573.59 | 0.33 | 20-MAR-02:40 | 11726.30 | 09-DEC-15:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 16919.20 | 0.00 | 08-FEB-16:30 | 11726.30 | 09-DEC-15:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 9654.40 | 0.00 | 01-JAN-00:10 | 9414.21 | 25-JUN-18:20 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:EnergyTransfer | 445379.26 | 0.00 | 18-MAR-16:10 | 226602.39 | 06-JAN-07:20 |
EnergyTransfer:Plant | 161678.26 | 1385.00 | 22-AUG-03:00 | 42300.19 | 18-FEB-09:00 |
WaterSystems:EnergyTransfer | 161678.26 | 1385.00 | 22-AUG-03:00 | 42300.19 | 18-FEB-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 161678.26 | 1385.00 | 22-AUG-03:00 | 42300.19 | 18-FEB-09:00 |
PlantLoopHeatingDemand:Facility | 161678.26 | 1385.00 | 22-AUG-03:00 | 42300.19 | 18-FEB-09:00 |
PlantLoopHeatingDemand:Plant | 161678.26 | 1385.00 | 22-AUG-03:00 | 42300.19 | 18-FEB-09:00 |
WaterSystems:PlantLoopHeatingDemand | 161678.26 | 1385.00 | 22-AUG-03:00 | 42300.19 | 18-FEB-09:00 |
General:WaterSystems:PlantLoopHeatingDemand | 161678.26 | 1385.00 | 22-AUG-03:00 | 42300.19 | 18-FEB-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 149.745 | -1493.03 | 28858.839 | -527.61 | 0.000 | 0.000 | 3084.083 | 2150.478 | 10401.374 | 9725.590 | 0.000 | 80.592 | 0.000 | 0.000 | -7351.88 | 0.000 | -8508.74 | -14326.14 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 149.367 | -1490.58 | 23688.083 | -301.79 | 0.000 | 0.000 | 3084.331 | 2150.478 | 10401.374 | 4679.632 | 0.000 | 71.064 | 0.000 | 0.000 | -2945.09 | 0.000 | -7482.76 | -12273.67 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 149.743 | -1495.85 | 28573.693 | -487.95 | 0.000 | 0.000 | 3084.788 | 2150.478 | 10401.374 | 9474.098 | 0.000 | 80.282 | 0.000 | 0.000 | -7225.89 | 0.000 | -8512.87 | -14354.16 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 150.150 | -1488.61 | 31767.533 | -425.70 | 0.000 | 0.000 | 3089.846 | 2150.478 | 10401.374 | 6461.005 | 0.000 | 81.109 | 0.000 | 0.000 | -7783.89 | 0.000 | -8482.53 | -14847.92 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 150.227 | -1483.79 | 26833.173 | -223.62 | 0.000 | 0.000 | 3093.290 | 2150.478 | 10401.374 | 1255.884 | 0.000 | 72.591 | 0.000 | 0.000 | -3300.55 | 0.000 | -7450.53 | -12703.37 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 149.895 | -1491.04 | 31576.840 | -391.72 | 0.000 | 0.000 | 3091.313 | 2150.478 | 10401.374 | 6183.380 | 0.000 | 80.377 | 0.000 | 0.000 | -7627.95 | 0.000 | -8483.30 | -14914.23 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 149.944 | -1500.34 | 21198.858 | -595.05 | 0.000 | 0.000 | 3070.429 | 2150.478 | 10401.374 | 9622.505 | 0.000 | 35.047 | 0.000 | 0.000 | -7549.14 | 0.000 | -3743.22 | -10174.73 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 149.309 | -1499.07 | 16126.974 | -363.90 | 0.000 | 0.000 | 3069.653 | 2150.478 | 10401.374 | 4630.999 | 0.000 | 25.502 | 0.000 | 0.000 | -3023.32 | 0.000 | -2719.33 | -8441.01 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 149.438 | -1502.73 | 20963.752 | -563.73 | 0.000 | 0.000 | 3071.957 | 2150.478 | 10401.374 | 9370.049 | 0.000 | 34.955 | 0.000 | 0.000 | -7411.97 | 0.000 | -3744.65 | -10171.34 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 150.369 | -1495.24 | 23828.768 | -482.93 | 0.000 | 0.000 | 3077.823 | 2150.478 | 10401.374 | 6388.787 | 0.000 | 35.245 | 0.000 | 0.000 | -7995.58 | 0.000 | -3729.70 | -10553.65 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 150.645 | -1491.34 | 18919.643 | -275.86 | 0.000 | 0.000 | 3081.344 | 2150.478 | 10401.374 | 1234.648 | 0.000 | 25.969 | 0.000 | 0.000 | -3391.06 | 0.000 | -2705.07 | -8647.47 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 149.784 | -1497.42 | 23670.342 | -456.49 | 0.000 | 0.000 | 3080.122 | 2150.478 | 10401.374 | 6109.324 | 0.000 | 34.974 | 0.000 | 0.000 | -7827.77 | 0.000 | -3729.39 | -10576.64 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 149.870 | -1494.92 | 30770.298 | -463.59 | 0.000 | 0.000 | 3083.686 | 2150.478 | 10401.374 | 6111.708 | 0.000 | 79.404 | 0.000 | 0.000 | -7814.16 | 0.000 | -8514.61 | -12900.26 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 149.763 | -1498.78 | 28132.997 | -539.00 | 0.000 | 0.000 | 3078.093 | 2150.478 | 10401.374 | 9379.815 | 0.000 | 79.357 | 0.000 | 0.000 | -7385.28 | 0.000 | -8540.02 | -12976.88 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 149.530 | -1496.07 | 28375.599 | -572.42 | 0.000 | 0.000 | 3077.154 | 2150.478 | 10401.374 | 9627.029 | 0.000 | 79.571 | 0.000 | 0.000 | -7520.83 | 0.000 | -8536.63 | -12964.80 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 150.536 | -1488.81 | 25914.338 | -293.13 | 0.000 | 0.000 | 3084.789 | 2150.478 | 10401.374 | 1235.504 | 0.000 | 71.147 | 0.000 | 0.000 | -3383.99 | 0.000 | -7481.16 | -10745.40 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 149.460 | -1494.29 | 23144.033 | -355.20 | 0.000 | 0.000 | 3076.949 | 2150.478 | 10401.374 | 4631.993 | 0.000 | 70.180 | 0.000 | 0.000 | -3009.82 | 0.000 | -7509.22 | -10896.63 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 149.798 | -1492.39 | 30958.043 | -493.20 | 0.000 | 0.000 | 3082.118 | 2150.478 | 10401.374 | 6386.501 | 0.000 | 79.946 | 0.000 | 0.000 | -7979.78 | 0.000 | -8514.33 | -12871.16 |
CRAWLSPACE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19284.787 | 324181.566 | 0.000 | 0.000 | 0.000 | -343466.35 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 14731.094 | 116922.305 | 0.000 | 0.000 | 0.000 | -131653.40 | -0.25 |
Total Facility | 2697.572 | -26894.29 | 463301.804 | -7812.91 | 0.000 | 0.000 | 55461.769 | 38708.604 | 187224.736 | 112508.449 | 0.000 | 35133.194 | 441103.871 | 0.000 | -110527.94 | 0.000 | -593507.79 | -215339.70 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 25-JUN-17:30 | 0.00 | 0.06 | 0.00 | -0.8 | 0.00 | 0.00 | 262.48 | 469.21 | 1675.86 | 7204.20 | 0.00 | 488.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -638.5 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 06-SEP-16:15 | 0.00 | -0.2 | 0.00 | -0.3 | 0.00 | 0.00 | 137.96 | 336.87 | 1343.44 | 1163.77 | 0.00 | 273.40 | 3092.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 07-SEP-10:30 | 0.00 | 0.04 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1078.58 | 7438.86 | 0.00 | 116.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1954.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 25-JUN-18:25 | 0.00 | 0.05 | 0.00 | -0.8 | 0.00 | 0.00 | 424.42 | 631.63 | 1734.73 | 5608.52 | 0.00 | 353.49 | 430.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 25-JUN-18:50 | 0.00 | -0.2 | 0.00 | -0.3 | 0.00 | 0.00 | 421.06 | 631.63 | 1734.73 | 1031.45 | 0.00 | 268.14 | 1587.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 26-JUN-09:00 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 194.42 | 132.34 | 1145.20 | 6617.77 | 0.00 | 137.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1561.6 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 25-JUN-17:30 | 0.00 | 0.06 | 0.00 | -0.8 | 0.00 | 0.00 | 263.17 | 469.21 | 1675.86 | 7193.57 | 0.00 | 214.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -647.0 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 06-SEP-16:15 | 0.00 | -0.2 | 0.00 | -0.3 | 0.00 | 0.00 | 137.76 | 336.87 | 1343.44 | 1161.98 | 0.00 | 98.58 | 3385.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 07-SEP-10:40 | 0.00 | 0.04 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1078.58 | 7152.56 | 0.00 | 54.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1484.3 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25-JUN-18:25 | 0.00 | 0.05 | 0.00 | -0.8 | 0.00 | 0.00 | 425.19 | 631.63 | 1734.73 | 5600.20 | 0.00 | 154.80 | 377.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 10-MAR-21:15 | 0.00 | -0.4 | 0.00 | 0.00 | 0.00 | 0.00 | 527.51 | 529.36 | 1545.38 | 0.00 | 0.00 | 0.00 | 4040.98 | 0.00 | -866.1 | 0.00 | -432.8 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 26-JUN-09:00 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 194.42 | 132.34 | 1145.20 | 6601.81 | 0.00 | 59.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1470.9 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 26-JUN-09:00 | 0.00 | 0.03 | 0.00 | -0.6 | 0.00 | 0.00 | 194.42 | 132.34 | 1145.20 | 6592.89 | 0.00 | 135.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1435.8 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 26-JUN-10:20 | 0.00 | 0.04 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1078.58 | 5915.11 | 0.00 | 194.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -486.8 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 25-JUN-17:40 | 0.00 | 0.05 | 0.00 | -0.8 | 0.00 | 0.00 | 262.83 | 469.21 | 1675.86 | 6844.95 | 0.00 | 470.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -231.4 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 25-JUN-18:50 | 0.00 | -0.2 | 0.00 | -0.2 | 0.00 | 0.00 | 423.86 | 631.63 | 1734.73 | 1030.29 | 0.00 | 267.09 | 1225.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 04-AUG-14:45 | 0.00 | -0.2 | 0.00 | -0.4 | 0.00 | 0.00 | 109.90 | 90.23 | 1084.62 | 1947.10 | 0.00 | 285.61 | 2574.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 25-JUN-18:25 | 0.00 | 0.05 | 0.00 | -0.8 | 0.00 | 0.00 | 425.45 | 631.63 | 1734.73 | 5588.92 | 0.00 | 353.18 | 694.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-JUN-18:10 | 0.00 | 0.92 | 0.00 | -10.2 | 0.00 | 0.00 | 7671.52 | 11369.32 | 31225.16 | 49991.41 | 0.00 | 37241.86 | 0.00 | 0.00 | 0.00 | 0.00 | -25662.2 | -570.6 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 09-DEC-13:25 | -3476.7 | 0.00 | 15468.01 | 0.00 | 0.00 | 0.00 | 128.01 | 90.23 | 1099.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2402.7 | 0.00 | -4549.4 | -6357.4 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 09-DEC-15:05 | -3275.7 | 0.00 | 12114.05 | 0.00 | 0.00 | 0.00 | 140.31 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -617.0 | 0.00 | -4075.4 | -5603.1 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 09-DEC-15:20 | -3380.5 | 0.00 | 15208.99 | 0.00 | 0.00 | 0.00 | 132.46 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2104.7 | 0.00 | -4702.7 | -6470.4 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 09-DEC-15:20 | -3398.5 | 0.00 | 15401.90 | 0.00 | 0.00 | 0.00 | 130.11 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2003.5 | 0.00 | -4730.6 | -6716.3 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 09-DEC-15:05 | -3267.7 | 0.00 | 12127.95 | 0.00 | 0.00 | 0.00 | 140.82 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1032.0 | 0.00 | -4064.6 | -5221.4 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 09-DEC-16:05 | -3411.7 | 0.00 | 15240.77 | 0.00 | 0.00 | 0.00 | 156.82 | 336.87 | 1363.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2839.4 | 0.00 | -4398.2 | -6448.3 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 09-DEC-16:05 | -3421.9 | 0.00 | 11840.55 | 0.00 | 0.00 | 0.00 | 157.68 | 336.87 | 1363.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2405.8 | 0.00 | -1931.4 | -5939.2 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 17-DEC-11:47 | -2042.2 | 0.00 | 8622.09 | 0.00 | 0.00 | 0.00 | 127.29 | 90.23 | 1111.29 | 2398.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.1 | -9948.4 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 09-DEC-16:05 | -3397.4 | 0.00 | 11692.80 | 0.00 | 0.00 | 0.00 | 160.20 | 336.87 | 1363.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2695.7 | 0.00 | -1916.0 | -5544.1 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 09-DEC-12:30 | -3541.4 | 0.00 | 11921.66 | 0.00 | 0.00 | 0.00 | 130.77 | 90.23 | 1107.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2483.0 | 0.00 | -2070.3 | -5156.0 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21-FEB-20:17 | -1935.5 | 0.00 | 8309.38 | 0.00 | 0.00 | 0.00 | 472.00 | 699.99 | 1615.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.6 | 0.00 | -360.1 | -8123.1 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 09-DEC-13:00 | -3510.1 | 0.00 | 11775.00 | 0.00 | 0.00 | 0.00 | 127.94 | 90.23 | 1107.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2443.2 | 0.00 | -1920.5 | -5227.3 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 09-DEC-15:20 | -3387.7 | 0.00 | 15005.62 | 0.00 | 0.00 | 0.00 | 131.52 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2651.6 | 0.00 | -4718.9 | -5695.8 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 09-DEC-15:20 | -3397.7 | 0.00 | 15013.80 | 0.00 | 0.00 | 0.00 | 130.79 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2179.1 | 0.00 | -4734.2 | -6150.4 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 09-DEC-15:20 | -3417.1 | 0.00 | 15153.74 | 0.00 | 0.00 | 0.00 | 129.28 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1600.7 | 0.00 | -4763.7 | -6818.5 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 09-DEC-15:20 | -3346.2 | 0.00 | 12011.12 | 0.00 | 0.00 | 0.00 | 135.21 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1081.9 | 0.00 | -4099.1 | -4936.0 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 09-DEC-15:20 | -3353.4 | 0.00 | 11987.87 | 0.00 | 0.00 | 0.00 | 134.76 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -602.8 | 0.00 | -4108.7 | -5374.6 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 09-DEC-15:20 | -3410.1 | 0.00 | 15206.40 | 0.00 | 0.00 | 0.00 | 129.78 | 156.40 | 1160.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2076.0 | 0.00 | -4753.0 | -6414.0 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-DEC-13:25 | -64688.4 | 0.00 | 232836.98 | 0.00 | 0.00 | 0.00 | 2335.42 | 1624.19 | 19798.67 | 0.00 | 0.00 | 0.00 | 43957.72 | 0.00 | -35309.5 | 0.00 | -200555.1 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 417.1900 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 417.1900 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.7479 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 180.7479 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 317.0495 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 317.0495 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 403.0487 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 403.0487 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 178.5341 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 178.5341 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 300.9027 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 300.9027 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 408.9205 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 408.9205 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 180.1318 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 180.1318 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.0528 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 321.0528 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 394.9548 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 394.9548 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 175.9550 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 175.9550 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 303.6671 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 303.6671 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.5241 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 420.5241 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 195.9572 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 195.9572 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.9229 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 321.9229 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 415.7985 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 415.7985 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 199.4378 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 199.4378 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 304.9279 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 304.9279 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 417.1900 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 417.1900 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.7479 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 180.7479 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 317.0495 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 317.0495 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 403.0487 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 403.0487 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 178.5341 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 178.5341 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 300.9027 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 300.9027 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 408.9205 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 408.9205 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 180.1318 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 180.1318 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.0528 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 321.0528 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 394.9548 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 394.9548 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 175.9550 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 175.9550 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 303.6671 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 303.6671 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.5241 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 420.5241 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 195.9572 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 195.9572 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.9229 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 321.9229 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 415.7985 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 415.7985 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 199.4378 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 199.4378 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 304.9279 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 304.9279 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 417.1900 | 417.1900 | 417.1900 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 180.7479 | 180.7479 | 180.7479 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 317.0495 | 317.0495 | 317.0495 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 403.0487 | 403.0487 | 403.0487 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 178.5341 | 178.5341 | 178.5341 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 300.9027 | 300.9027 | 300.9027 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 408.9205 | 408.9205 | 408.9205 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 180.1318 | 180.1318 | 180.1318 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 321.0528 | 321.0528 | 321.0528 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 394.9548 | 394.9548 | 394.9548 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 175.9550 | 175.9550 | 175.9550 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 303.6671 | 303.6671 | 303.6671 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 304.9279 | 304.9279 | 304.9279 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 321.9229 | 321.9229 | 321.9229 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 420.5241 | 420.5241 | 420.5241 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 199.4378 | 199.4378 | 199.4378 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 195.9572 | 195.9572 | 195.9572 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 415.7985 | 415.7985 | 415.7985 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 417.1900 | 417.1900 | 417.1900 | 417.1900 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.7479 | 180.7479 | 180.7479 | 180.7479 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 317.0495 | 317.0495 | 317.0495 | 317.0495 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 403.0487 | 403.0487 | 403.0487 | 403.0487 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 178.5341 | 178.5341 | 178.5341 | 178.5341 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 300.9027 | 300.9027 | 300.9027 | 300.9027 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 408.9205 | 408.9205 | 408.9205 | 408.9205 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 180.1318 | 180.1318 | 180.1318 | 180.1318 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.0528 | 321.0528 | 321.0528 | 321.0528 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 394.9548 | 394.9548 | 394.9548 | 394.9548 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 175.9550 | 175.9550 | 175.9550 | 175.9550 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 303.6671 | 303.6671 | 303.6671 | 303.6671 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.5241 | 420.5241 | 420.5241 | 420.5241 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 195.9572 | 195.9572 | 195.9572 | 195.9572 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.9229 | 321.9229 | 321.9229 | 321.9229 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 415.7985 | 415.7985 | 415.7985 | 415.7985 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 199.4378 | 199.4378 | 199.4378 | 199.4378 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 304.9279 | 304.9279 | 304.9279 | 304.9279 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 417.1900 | 417.1900 | 417.1900 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 180.7479 | 180.7479 | 180.7479 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 317.0495 | 317.0495 | 317.0495 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 403.0487 | 403.0487 | 403.0487 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 178.5341 | 178.5341 | 178.5341 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 300.9027 | 300.9027 | 300.9027 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 408.9205 | 408.9205 | 408.9205 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 180.1318 | 180.1318 | 180.1318 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 321.0528 | 321.0528 | 321.0528 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 394.9548 | 394.9548 | 394.9548 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 175.9550 | 175.9550 | 175.9550 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 303.6671 | 303.6671 | 303.6671 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 304.9279 | 304.9279 | 304.9279 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 321.9229 | 321.9229 | 321.9229 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 420.5241 | 420.5241 | 420.5241 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 199.4378 | 199.4378 | 199.4378 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 195.9572 | 195.9572 | 195.9572 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 415.7985 | 415.7985 | 415.7985 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 417.1900 | 417.1900 | 417.1900 | 417.1900 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.7479 | 180.7479 | 180.7479 | 180.7479 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 317.0495 | 317.0495 | 317.0495 | 317.0495 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 403.0487 | 403.0487 | 403.0487 | 403.0487 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 178.5341 | 178.5341 | 178.5341 | 178.5341 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 300.9027 | 300.9027 | 300.9027 | 300.9027 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 408.9205 | 408.9205 | 408.9205 | 408.9205 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 180.1318 | 180.1318 | 180.1318 | 180.1318 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.0528 | 321.0528 | 321.0528 | 321.0528 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 394.9548 | 394.9548 | 394.9548 | 394.9548 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 175.9550 | 175.9550 | 175.9550 | 175.9550 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 303.6671 | 303.6671 | 303.6671 | 303.6671 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.5241 | 420.5241 | 420.5241 | 420.5241 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 195.9572 | 195.9572 | 195.9572 | 195.9572 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.9229 | 321.9229 | 321.9229 | 321.9229 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 415.7985 | 415.7985 | 415.7985 | 415.7985 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 199.4378 | 199.4378 | 199.4378 | 199.4378 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 304.9279 | 304.9279 | 304.9279 | 304.9279 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
CRAWLSPACE | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 21609.96 | 17395.26 |
Data | |
Number of hours heating loads not met | 320.17 |
Number of hours cooling loads not met | 12.33 |
Number of hours not met | 332.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 130440.78 | 66413.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8401.45 | 12021.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 11336.81 | 3692.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 5508.71 | 1257.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 2758.31 | 880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1408.53 | 381.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 7797.33 | 2918.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 2534.14 | 289.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 1308.75 | 149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 17622.82 | 9240.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299798.81 | 931297.99 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 299798.81 | 931297.99 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.29 |
Space Heating | 3.34 |
Space Cooling | 0.22 |
Fans (All) | 0.26 |
Service Water Heating | 0.49 |
Receptacle Equipment | 2.25 |
Miscellaneous (All) | 6.99 |
Subtotal | 6.99 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 4.16 |
Space Heating | 47.82 |
Space Cooling | 3.08 |
Fans (All) | 3.79 |
Service Water Heating | 6.94 |
Receptacle Equipment | 32.19 |
Miscellaneous | 2.02 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DHW_SCH | 365. | 8760. |
DISHWASHER | 2799. | 8760. |
CLOTHESWASHER | 3297. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SINKS | 4179. | 8760. |
SHOWERS | 2640. | 8760. |
BATHS | 2586. | 8760. |
DHWDIST | 4662. | 8760. |
SHADING_2012IECC | 0. | 0. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 8612.00 | 140.17 | 7.83 | 0.00 | 0.00 |
BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7986.50 | 479.50 | 258.17 | 35.83 | 0.00 |
Min | 7986.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 479.50 | 258.17 | 35.83 | 0.00 |
Average | 8716.12 | 29.51 | 12.67 | 1.71 | 0.00 |
Sum | 183038.50 | 619.67 | 266.00 | 35.83 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8603.00 | 157.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8632.50 | 127.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8620.33 | 139.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8589.83 | 170.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8620.17 | 139.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8613.83 | 146.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8700.67 | 59.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8730.50 | 29.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8702.00 | 58.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8698.00 | 62.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8721.00 | 39.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8697.83 | 62.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8681.17 | 78.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8682.67 | 77.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8672.83 | 87.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8701.50 | 58.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8667.33 | 92.67 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 8234.17 | 522.00 | 3.83 | 0.00 | 0.00 |
BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7744.67 | 866.00 | 127.00 | 19.17 | 3.17 |
Min | 7744.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 866.00 | 127.00 | 19.17 | 3.17 |
Average | 8607.65 | 145.06 | 6.23 | 0.91 | 0.15 |
Sum | 180760.67 | 3046.17 | 130.83 | 19.17 | 3.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8886.83 | 238.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8967.50 | 157.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8891.83 | 233.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8881.17 | 243.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8965.50 | 159.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8882.83 | 242.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9038.33 | 86.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9096.67 | 28.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9028.17 | 96.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9038.00 | 87.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9088.33 | 36.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9020.50 | 104.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9001.00 | 124.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9002.33 | 122.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9004.67 | 120.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9065.67 | 59.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9065.83 | 59.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9005.33 | 119.67 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9096.67 | 243.83 | 0.00 | 0.00 | 0.00 |
Average | 7710.98 | 110.45 | 0.00 | 0.00 | 0.00 |
Sum | 161930.50 | 2319.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (F) | SET ≤ 12.2°C OccupantHours (F) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (F) | SET > 30°C OccupantHours (F) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:40:10
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 733.861 | 90.900 | 90.900 |
February | 3.500 | 0.091 | 630.569 | 65.227 | 65.318 |
March | 14.194 | 0.325 | 624.931 | 46.488 | 46.813 |
April | 112.389 | 6.634 | 416.055 | 24.830 | 31.465 |
May | 200.264 | 10.858 | 156.328 | 6.405 | 17.263 |
June | 428.250 | 30.039 | 59.944 | 2.244 | 32.283 |
July | 554.250 | 38.466 | 2.667 | 0.146 | 38.613 |
August | 502.458 | 33.563 | 9.289 | 0.404 | 33.966 |
September | 282.787 | 18.889 | 173.319 | 6.845 | 25.734 |
October | 64.278 | 2.515 | 460.347 | 21.487 | 24.002 |
November | 10.639 | 0.507 | 621.597 | 48.725 | 49.232 |
December | 0.000 | 0.000 | 724.917 | 75.855 | 75.855 |
Annual Sum or Average | 2173.009 | 141.887 | 4613.824 | 389.557 | 531.445 |
Minimum of Months | 0.000 | 0.000 | 2.667 | 0.146 | 17.263 |
Maximum of Months | 554.250 | 38.466 | 733.861 | 90.900 | 90.900 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 734.056 | 40.741 | 40.741 |
February | 0.000 | 0.000 | 631.667 | 29.631 | 29.631 |
March | 5.361 | 0.064 | 620.347 | 21.656 | 21.721 |
April | 68.278 | 2.567 | 412.595 | 11.934 | 14.500 |
May | 151.361 | 4.264 | 119.503 | 2.917 | 7.181 |
June | 401.253 | 16.154 | 46.000 | 1.016 | 17.169 |
July | 545.106 | 21.150 | 1.597 | 0.049 | 21.199 |
August | 499.875 | 19.058 | 4.689 | 0.135 | 19.193 |
September | 280.034 | 10.479 | 129.681 | 2.820 | 13.299 |
October | 36.056 | 0.681 | 408.875 | 9.376 | 10.057 |
November | 7.722 | 0.153 | 593.944 | 21.659 | 21.813 |
December | 0.000 | 0.000 | 723.278 | 33.681 | 33.681 |
Annual Sum or Average | 1995.045 | 74.569 | 4426.231 | 175.615 | 250.184 |
Minimum of Months | 0.000 | 0.000 | 1.597 | 0.049 | 7.181 |
Maximum of Months | 545.106 | 21.150 | 734.056 | 40.741 | 40.741 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.167 | 69.801 | 69.801 |
February | 0.889 | 0.002 | 636.639 | 50.314 | 50.316 |
March | 8.139 | 0.153 | 624.528 | 35.388 | 35.541 |
April | 102.111 | 4.988 | 422.974 | 19.115 | 24.104 |
May | 230.275 | 9.574 | 120.125 | 3.847 | 13.421 |
June | 451.417 | 28.769 | 54.778 | 1.456 | 30.225 |
July | 584.219 | 36.270 | 0.972 | 0.033 | 36.303 |
August | 525.831 | 31.078 | 5.875 | 0.162 | 31.241 |
September | 299.983 | 17.474 | 155.931 | 4.650 | 22.124 |
October | 45.028 | 1.209 | 448.042 | 16.075 | 17.284 |
November | 9.472 | 0.225 | 623.472 | 37.488 | 37.713 |
December | 0.000 | 0.000 | 732.500 | 58.516 | 58.516 |
Annual Sum or Average | 2257.363 | 129.741 | 4562.002 | 296.848 | 426.589 |
Minimum of Months | 0.000 | 0.000 | 0.972 | 0.033 | 13.421 |
Maximum of Months | 584.219 | 36.270 | 736.167 | 69.801 | 69.801 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 95.124 | 95.124 |
February | 0.000 | 0.000 | 662.167 | 69.643 | 69.643 |
March | 3.250 | 0.022 | 671.653 | 49.753 | 49.774 |
April | 77.333 | 4.276 | 468.514 | 26.457 | 30.733 |
May | 173.750 | 8.520 | 171.425 | 6.732 | 15.252 |
June | 422.153 | 27.970 | 63.514 | 2.252 | 30.222 |
July | 544.000 | 35.026 | 2.208 | 0.125 | 35.151 |
August | 479.653 | 28.459 | 10.219 | 0.424 | 28.884 |
September | 244.151 | 13.027 | 206.633 | 7.797 | 20.824 |
October | 13.278 | 0.357 | 563.944 | 25.403 | 25.760 |
November | 0.000 | 0.000 | 661.875 | 51.531 | 51.531 |
December | 0.000 | 0.000 | 744.000 | 79.353 | 79.353 |
Annual Sum or Average | 1957.568 | 117.655 | 4970.153 | 414.595 | 532.250 |
Minimum of Months | 0.000 | 0.000 | 2.208 | 0.125 | 15.252 |
Maximum of Months | 544.000 | 35.026 | 744.000 | 95.124 | 95.124 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 44.290 | 44.290 |
February | 0.000 | 0.000 | 672.000 | 32.879 | 32.879 |
March | 0.000 | 0.000 | 692.111 | 24.243 | 24.243 |
April | 46.333 | 1.534 | 494.722 | 13.573 | 15.107 |
May | 116.444 | 2.930 | 149.989 | 3.431 | 6.361 |
June | 392.833 | 14.509 | 49.597 | 1.052 | 15.562 |
July | 524.794 | 18.309 | 1.514 | 0.043 | 18.352 |
August | 462.319 | 14.793 | 6.036 | 0.164 | 14.957 |
September | 208.950 | 5.968 | 178.847 | 3.622 | 9.590 |
October | 0.000 | 0.000 | 573.194 | 12.412 | 12.412 |
November | 0.000 | 0.000 | 642.306 | 24.011 | 24.011 |
December | 0.000 | 0.000 | 744.000 | 36.670 | 36.670 |
Annual Sum or Average | 1751.674 | 58.043 | 4948.317 | 196.390 | 254.433 |
Minimum of Months | 0.000 | 0.000 | 1.514 | 0.043 | 6.361 |
Maximum of Months | 524.794 | 18.309 | 744.000 | 44.290 | 44.290 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 71.888 | 71.888 |
February | 0.000 | 0.000 | 670.694 | 52.861 | 52.861 |
March | 0.000 | 0.000 | 683.861 | 37.330 | 37.330 |
April | 64.944 | 3.107 | 478.822 | 20.203 | 23.310 |
May | 183.614 | 7.214 | 135.367 | 4.029 | 11.243 |
June | 449.764 | 26.844 | 57.083 | 1.447 | 28.291 |
July | 576.711 | 33.078 | 1.222 | 0.033 | 33.110 |
August | 508.464 | 26.115 | 6.778 | 0.171 | 26.286 |
September | 255.933 | 11.703 | 187.181 | 5.273 | 16.976 |
October | 1.250 | 0.006 | 590.111 | 19.161 | 19.168 |
November | 0.000 | 0.000 | 671.500 | 39.175 | 39.175 |
December | 0.000 | 0.000 | 744.000 | 60.163 | 60.163 |
Annual Sum or Average | 2040.681 | 108.067 | 4970.619 | 311.735 | 419.802 |
Minimum of Months | 0.000 | 0.000 | 1.222 | 0.033 | 11.243 |
Maximum of Months | 576.711 | 33.078 | 744.000 | 71.888 | 71.888 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 717.069 | 86.263 | 86.263 |
February | 8.722 | 0.194 | 594.542 | 61.360 | 61.554 |
March | 27.972 | 0.661 | 548.306 | 42.744 | 43.405 |
April | 136.958 | 7.878 | 342.861 | 22.448 | 30.326 |
May | 256.392 | 13.142 | 78.044 | 4.691 | 17.833 |
June | 467.222 | 33.048 | 30.264 | 1.694 | 34.742 |
July | 612.985 | 42.755 | 0.653 | 0.043 | 42.798 |
August | 571.267 | 37.562 | 3.164 | 0.190 | 37.753 |
September | 337.869 | 21.269 | 107.003 | 5.568 | 26.838 |
October | 84.903 | 3.278 | 329.403 | 18.583 | 21.861 |
November | 18.292 | 0.609 | 549.542 | 45.270 | 45.879 |
December | 0.000 | 0.000 | 695.583 | 72.484 | 72.484 |
Annual Sum or Average | 2522.582 | 160.396 | 3996.433 | 361.340 | 521.736 |
Minimum of Months | 0.000 | 0.000 | 0.653 | 0.043 | 17.833 |
Maximum of Months | 612.985 | 42.755 | 717.069 | 86.263 | 86.263 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 704.111 | 39.533 | 39.533 |
February | 1.500 | 0.015 | 560.569 | 28.468 | 28.483 |
March | 7.028 | 0.136 | 498.097 | 20.351 | 20.487 |
April | 102.111 | 3.161 | 292.817 | 11.005 | 14.166 |
May | 231.114 | 5.887 | 49.736 | 2.164 | 8.051 |
June | 448.664 | 18.698 | 20.278 | 0.744 | 19.441 |
July | 598.536 | 24.930 | 0.194 | 0.008 | 24.938 |
August | 571.206 | 22.704 | 1.103 | 0.052 | 22.757 |
September | 337.910 | 12.584 | 59.181 | 2.211 | 14.795 |
October | 65.806 | 1.243 | 227.069 | 8.023 | 9.266 |
November | 12.278 | 0.247 | 480.708 | 20.402 | 20.649 |
December | 0.000 | 0.000 | 667.389 | 32.830 | 32.830 |
Annual Sum or Average | 2376.151 | 89.605 | 3561.253 | 165.790 | 255.395 |
Minimum of Months | 0.000 | 0.000 | 0.194 | 0.008 | 8.051 |
Maximum of Months | 598.536 | 24.930 | 704.111 | 39.533 | 39.533 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 722.333 | 68.612 | 68.612 |
February | 2.500 | 0.048 | 599.111 | 48.952 | 49.000 |
March | 16.333 | 0.380 | 537.181 | 33.304 | 33.684 |
April | 121.889 | 6.137 | 341.044 | 17.804 | 23.941 |
May | 289.725 | 12.341 | 57.028 | 2.668 | 15.009 |
June | 503.569 | 32.244 | 26.639 | 1.136 | 33.381 |
July | 643.314 | 40.862 | 0.083 | 0.004 | 40.866 |
August | 587.181 | 35.368 | 1.556 | 0.080 | 35.448 |
September | 352.194 | 20.135 | 92.722 | 3.859 | 23.994 |
October | 77.111 | 1.997 | 328.792 | 14.432 | 16.428 |
November | 11.306 | 0.340 | 549.806 | 36.085 | 36.425 |
December | 0.000 | 0.000 | 701.139 | 57.856 | 57.856 |
Annual Sum or Average | 2605.122 | 149.853 | 3957.433 | 284.792 | 434.644 |
Minimum of Months | 0.000 | 0.000 | 0.083 | 0.004 | 15.009 |
Maximum of Months | 643.314 | 40.862 | 722.333 | 68.612 | 68.612 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.250 | 91.971 | 91.971 |
February | 0.000 | 0.000 | 645.069 | 67.021 | 67.021 |
March | 4.389 | 0.051 | 613.514 | 46.756 | 46.808 |
April | 93.583 | 4.926 | 385.894 | 24.114 | 29.040 |
May | 231.500 | 10.474 | 91.128 | 5.054 | 15.528 |
June | 463.514 | 31.034 | 31.472 | 1.729 | 32.763 |
July | 609.853 | 39.415 | 0.500 | 0.035 | 39.450 |
August | 547.314 | 32.367 | 3.375 | 0.201 | 32.568 |
September | 291.944 | 14.994 | 129.639 | 6.474 | 21.469 |
October | 23.806 | 0.529 | 439.875 | 22.989 | 23.518 |
November | 0.611 | 0.005 | 607.486 | 48.963 | 48.967 |
December | 0.000 | 0.000 | 742.250 | 77.192 | 77.192 |
Annual Sum or Average | 2266.514 | 133.795 | 4433.453 | 392.498 | 526.293 |
Minimum of Months | 0.000 | 0.000 | 0.500 | 0.035 | 15.528 |
Maximum of Months | 609.853 | 39.415 | 743.250 | 91.971 | 91.971 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 740.986 | 43.589 | 43.589 |
February | 0.000 | 0.000 | 651.917 | 32.375 | 32.375 |
March | 0.000 | 0.000 | 602.264 | 23.483 | 23.483 |
April | 55.056 | 1.764 | 363.528 | 12.862 | 14.626 |
May | 183.211 | 4.155 | 65.256 | 2.617 | 6.772 |
June | 444.117 | 17.083 | 21.694 | 0.791 | 17.875 |
July | 584.765 | 22.138 | 0.111 | 0.004 | 22.142 |
August | 540.544 | 18.300 | 1.319 | 0.056 | 18.356 |
September | 264.828 | 7.586 | 87.944 | 3.016 | 10.602 |
October | 1.111 | 0.002 | 375.556 | 11.394 | 11.396 |
November | 0.000 | 0.000 | 571.417 | 23.263 | 23.263 |
December | 0.000 | 0.000 | 742.625 | 36.348 | 36.348 |
Annual Sum or Average | 2073.631 | 71.029 | 4224.617 | 189.798 | 260.827 |
Minimum of Months | 0.000 | 0.000 | 0.111 | 0.004 | 6.772 |
Maximum of Months | 584.765 | 22.138 | 742.625 | 43.589 | 43.589 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 71.716 | 71.716 |
February | 0.000 | 0.000 | 662.972 | 52.576 | 52.576 |
March | 0.000 | 0.000 | 617.722 | 36.065 | 36.065 |
April | 85.056 | 3.679 | 388.658 | 19.030 | 22.709 |
May | 255.781 | 9.491 | 67.042 | 2.835 | 12.327 |
June | 496.000 | 30.283 | 27.222 | 1.121 | 31.403 |
July | 637.053 | 37.675 | 0.083 | 0.004 | 37.680 |
August | 571.717 | 30.379 | 1.972 | 0.074 | 30.453 |
September | 307.472 | 13.873 | 118.500 | 4.502 | 18.375 |
October | 4.667 | 0.033 | 433.403 | 17.780 | 17.812 |
November | 0.000 | 0.000 | 610.972 | 38.407 | 38.407 |
December | 0.000 | 0.000 | 744.000 | 60.457 | 60.457 |
Annual Sum or Average | 2357.744 | 125.413 | 4416.547 | 304.566 | 429.979 |
Minimum of Months | 0.000 | 0.000 | 0.083 | 0.004 | 12.327 |
Maximum of Months | 637.053 | 37.675 | 744.000 | 71.716 | 71.716 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 735.806 | 92.172 | 92.172 |
February | 1.722 | 0.051 | 631.639 | 66.191 | 66.242 |
March | 10.222 | 0.244 | 618.931 | 46.742 | 46.986 |
April | 111.181 | 6.629 | 406.092 | 24.433 | 31.062 |
May | 231.381 | 11.797 | 124.253 | 5.511 | 17.308 |
June | 454.556 | 33.272 | 50.847 | 1.965 | 35.237 |
July | 599.861 | 42.866 | 1.319 | 0.070 | 42.936 |
August | 545.139 | 36.884 | 4.528 | 0.242 | 37.125 |
September | 313.544 | 20.032 | 156.139 | 6.445 | 26.476 |
October | 60.333 | 2.080 | 445.000 | 21.143 | 23.223 |
November | 9.417 | 0.400 | 612.181 | 49.136 | 49.536 |
December | 0.000 | 0.000 | 728.028 | 77.059 | 77.059 |
Annual Sum or Average | 2337.355 | 154.255 | 4514.762 | 391.109 | 545.364 |
Minimum of Months | 0.000 | 0.000 | 1.319 | 0.070 | 17.308 |
Maximum of Months | 599.861 | 42.866 | 735.806 | 92.172 | 92.172 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 734.000 | 44.328 | 44.328 |
February | 0.000 | 0.000 | 632.514 | 32.249 | 32.249 |
March | 4.861 | 0.051 | 613.333 | 23.275 | 23.327 |
April | 77.139 | 2.852 | 397.258 | 12.569 | 15.421 |
May | 181.889 | 5.231 | 89.931 | 2.621 | 7.852 |
June | 437.417 | 19.394 | 36.833 | 0.921 | 20.315 |
July | 590.828 | 25.637 | 0.444 | 0.015 | 25.652 |
August | 544.778 | 22.614 | 1.969 | 0.073 | 22.687 |
September | 306.432 | 11.962 | 108.986 | 2.784 | 14.745 |
October | 33.583 | 0.574 | 381.972 | 9.783 | 10.357 |
November | 6.472 | 0.109 | 584.972 | 23.390 | 23.499 |
December | 0.000 | 0.000 | 725.278 | 36.718 | 36.718 |
Annual Sum or Average | 2183.398 | 88.424 | 4307.491 | 188.725 | 277.149 |
Minimum of Months | 0.000 | 0.000 | 0.444 | 0.015 | 7.852 |
Maximum of Months | 590.828 | 25.637 | 734.000 | 44.328 | 44.328 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.972 | 71.357 | 71.357 |
February | 0.000 | 0.000 | 638.861 | 51.483 | 51.483 |
March | 6.889 | 0.123 | 619.222 | 35.859 | 35.983 |
April | 101.778 | 5.166 | 413.845 | 19.011 | 24.178 |
May | 253.600 | 10.606 | 96.769 | 3.283 | 13.889 |
June | 482.833 | 31.939 | 43.417 | 1.276 | 33.215 |
July | 627.222 | 40.538 | 0.250 | 0.008 | 40.546 |
August | 571.406 | 34.381 | 2.694 | 0.087 | 34.467 |
September | 322.075 | 18.625 | 138.653 | 4.391 | 23.016 |
October | 40.833 | 1.028 | 437.847 | 16.038 | 17.067 |
November | 6.861 | 0.141 | 618.361 | 38.141 | 38.282 |
December | 0.000 | 0.000 | 734.389 | 59.887 | 59.887 |
Annual Sum or Average | 2413.497 | 142.547 | 4481.281 | 300.821 | 443.368 |
Minimum of Months | 0.000 | 0.000 | 0.250 | 0.008 | 13.889 |
Maximum of Months | 627.222 | 40.538 | 736.972 | 71.357 | 71.357 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 97.747 | 97.747 |
February | 0.000 | 0.000 | 662.111 | 71.523 | 71.523 |
March | 2.806 | 0.012 | 666.528 | 50.537 | 50.549 |
April | 85.194 | 4.744 | 446.375 | 26.197 | 30.941 |
May | 206.569 | 10.060 | 138.739 | 5.887 | 15.947 |
June | 451.417 | 32.021 | 52.625 | 1.991 | 34.013 |
July | 593.953 | 40.665 | 1.125 | 0.059 | 40.723 |
August | 529.597 | 33.110 | 4.639 | 0.248 | 33.357 |
September | 278.921 | 15.160 | 186.750 | 7.409 | 22.570 |
October | 15.944 | 0.314 | 543.708 | 25.465 | 25.779 |
November | 0.000 | 0.000 | 653.222 | 52.797 | 52.797 |
December | 0.000 | 0.000 | 744.000 | 81.766 | 81.766 |
Annual Sum or Average | 2164.401 | 136.086 | 4843.822 | 421.627 | 557.713 |
Minimum of Months | 0.000 | 0.000 | 1.125 | 0.059 | 15.947 |
Maximum of Months | 593.953 | 40.665 | 744.000 | 97.747 | 97.747 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 49.118 | 49.118 |
February | 0.000 | 0.000 | 670.667 | 36.404 | 36.404 |
March | 0.000 | 0.000 | 675.528 | 26.449 | 26.449 |
April | 52.944 | 1.917 | 454.725 | 14.328 | 16.245 |
May | 152.564 | 4.157 | 110.611 | 3.109 | 7.265 |
June | 436.264 | 18.452 | 39.472 | 0.989 | 19.441 |
July | 579.825 | 23.896 | 0.389 | 0.013 | 23.909 |
August | 522.969 | 19.445 | 2.189 | 0.085 | 19.530 |
September | 252.653 | 8.106 | 149.247 | 3.590 | 11.696 |
October | 0.000 | 0.000 | 541.306 | 13.294 | 13.294 |
November | 0.000 | 0.000 | 633.847 | 26.493 | 26.493 |
December | 0.000 | 0.000 | 744.000 | 40.793 | 40.793 |
Annual Sum or Average | 1997.219 | 75.974 | 4765.981 | 214.663 | 290.637 |
Minimum of Months | 0.000 | 0.000 | 0.389 | 0.013 | 7.265 |
Maximum of Months | 579.825 | 23.896 | 744.000 | 49.118 | 49.118 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 72.661 | 72.661 |
February | 0.000 | 0.000 | 670.861 | 53.375 | 53.375 |
March | 0.000 | 0.000 | 677.056 | 37.318 | 37.318 |
April | 73.722 | 3.560 | 459.781 | 19.670 | 23.230 |
May | 218.878 | 8.670 | 103.819 | 3.348 | 12.018 |
June | 488.181 | 30.687 | 45.778 | 1.265 | 31.952 |
July | 626.192 | 38.370 | 0.139 | 0.005 | 38.375 |
August | 562.503 | 30.624 | 2.417 | 0.086 | 30.710 |
September | 286.325 | 13.832 | 162.750 | 4.886 | 18.718 |
October | 1.806 | 0.009 | 575.972 | 18.885 | 18.894 |
November | 0.000 | 0.000 | 659.917 | 39.456 | 39.456 |
December | 0.000 | 0.000 | 744.000 | 60.973 | 60.973 |
Annual Sum or Average | 2257.606 | 125.753 | 4846.489 | 311.927 | 437.679 |
Minimum of Months | 0.000 | 0.000 | 0.139 | 0.005 | 12.018 |
Maximum of Months | 626.192 | 38.370 | 744.000 | 72.661 | 72.661 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8631.47 | 0.00 | 0.00 |
February | 6857.29 | 0.00 | 0.00 |
March | 4414.32 | 0.00 | 0.00 |
April | 2436.37 | 0.00 | 0.00 |
May | 608.16 | 0.00 | 0.00 |
June | 220.15 | 0.00 | 0.00 |
July | 13.91 | 0.00 | 0.00 |
August | 38.33 | 0.00 | 0.00 |
September | 671.64 | 0.00 | 0.00 |
October | 2040.30 | 0.00 | 0.00 |
November | 4780.88 | 0.00 | 0.00 |
December | 7202.86 | 0.00 | 0.00 |
Annual Sum or Average | 3141.66 | 0.00 | 0.00 |
Minimum of Months | 13.91 | 0.00 | 0.00 |
Maximum of Months | 8631.47 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7196.96 | 0.00 | 0.00 |
February | 5795.12 | 0.00 | 0.00 |
March | 3825.56 | 0.00 | 0.00 |
April | 2178.36 | 0.00 | 0.00 |
May | 515.25 | 0.00 | 0.00 |
June | 185.40 | 0.00 | 0.00 |
July | 8.64 | 0.00 | 0.00 |
August | 23.78 | 0.00 | 0.00 |
September | 514.72 | 0.00 | 0.00 |
October | 1656.35 | 0.00 | 0.00 |
November | 3953.66 | 0.00 | 0.00 |
December | 5949.73 | 0.00 | 0.00 |
Annual Sum or Average | 2634.77 | 0.00 | 0.00 |
Minimum of Months | 8.64 | 0.00 | 0.00 |
Maximum of Months | 7196.96 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8707.17 | 0.00 | 0.00 |
February | 6948.78 | 0.00 | 0.00 |
March | 4414.40 | 0.00 | 0.00 |
April | 2463.97 | 0.00 | 0.00 |
May | 479.89 | 0.00 | 0.00 |
June | 187.71 | 0.00 | 0.00 |
July | 4.13 | 0.00 | 0.00 |
August | 20.25 | 0.00 | 0.00 |
September | 599.44 | 0.00 | 0.00 |
October | 2005.29 | 0.00 | 0.00 |
November | 4832.24 | 0.00 | 0.00 |
December | 7299.39 | 0.00 | 0.00 |
Annual Sum or Average | 3144.97 | 0.00 | 0.00 |
Minimum of Months | 4.13 | 0.00 | 0.00 |
Maximum of Months | 8707.17 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 9356.17 | 0.00 | 0.00 |
February | 7583.91 | 0.00 | 0.00 |
March | 4893.59 | 0.00 | 0.00 |
April | 2688.98 | 0.00 | 0.00 |
May | 662.13 | 0.00 | 0.00 |
June | 228.91 | 0.00 | 0.00 |
July | 12.32 | 0.00 | 0.00 |
August | 41.75 | 0.00 | 0.00 |
September | 792.46 | 0.00 | 0.00 |
October | 2498.63 | 0.00 | 0.00 |
November | 5237.41 | 0.00 | 0.00 |
December | 7804.95 | 0.00 | 0.00 |
Annual Sum or Average | 3463.39 | 0.00 | 0.00 |
Minimum of Months | 12.32 | 0.00 | 0.00 |
Maximum of Months | 9356.17 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7926.45 | 0.00 | 0.00 |
February | 6514.72 | 0.00 | 0.00 |
March | 4338.76 | 0.00 | 0.00 |
April | 2510.13 | 0.00 | 0.00 |
May | 614.08 | 0.00 | 0.00 |
June | 194.61 | 0.00 | 0.00 |
July | 7.68 | 0.00 | 0.00 |
August | 29.27 | 0.00 | 0.00 |
September | 669.82 | 0.00 | 0.00 |
October | 2221.43 | 0.00 | 0.00 |
November | 4440.47 | 0.00 | 0.00 |
December | 6562.73 | 0.00 | 0.00 |
Annual Sum or Average | 2985.14 | 0.00 | 0.00 |
Minimum of Months | 7.68 | 0.00 | 0.00 |
Maximum of Months | 7926.45 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 9452.90 | 0.00 | 0.00 |
February | 7695.70 | 0.00 | 0.00 |
March | 4908.73 | 0.00 | 0.00 |
April | 2745.12 | 0.00 | 0.00 |
May | 529.83 | 0.00 | 0.00 |
June | 196.56 | 0.00 | 0.00 |
July | 4.30 | 0.00 | 0.00 |
August | 22.43 | 0.00 | 0.00 |
September | 716.54 | 0.00 | 0.00 |
October | 2519.61 | 0.00 | 0.00 |
November | 5323.02 | 0.00 | 0.00 |
December | 7911.09 | 0.00 | 0.00 |
Annual Sum or Average | 3481.46 | 0.00 | 0.00 |
Minimum of Months | 4.30 | 0.00 | 0.00 |
Maximum of Months | 9452.90 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6409.44 | 0.00 | 0.00 |
February | 5047.62 | 0.00 | 0.00 |
March | 3175.90 | 0.00 | 0.00 |
April | 1723.52 | 0.00 | 0.00 |
May | 348.58 | 0.00 | 0.00 |
June | 130.06 | 0.00 | 0.00 |
July | 3.19 | 0.00 | 0.00 |
August | 14.15 | 0.00 | 0.00 |
September | 427.53 | 0.00 | 0.00 |
October | 1380.71 | 0.00 | 0.00 |
November | 3475.72 | 0.00 | 0.00 |
December | 5385.65 | 0.00 | 0.00 |
Annual Sum or Average | 2280.23 | 0.00 | 0.00 |
Minimum of Months | 3.19 | 0.00 | 0.00 |
Maximum of Months | 6409.44 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4990.79 | 0.00 | 0.00 |
February | 3978.96 | 0.00 | 0.00 |
March | 2569.13 | 0.00 | 0.00 |
April | 1435.57 | 0.00 | 0.00 |
May | 273.20 | 0.00 | 0.00 |
June | 97.01 | 0.00 | 0.00 |
July | 0.99 | 0.00 | 0.00 |
August | 6.59 | 0.00 | 0.00 |
September | 288.44 | 0.00 | 0.00 |
October | 1012.88 | 0.00 | 0.00 |
November | 2661.48 | 0.00 | 0.00 |
December | 4144.59 | 0.00 | 0.00 |
Annual Sum or Average | 1777.61 | 0.00 | 0.00 |
Minimum of Months | 0.99 | 0.00 | 0.00 |
Maximum of Months | 4990.79 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6475.34 | 0.00 | 0.00 |
February | 5114.93 | 0.00 | 0.00 |
March | 3143.14 | 0.00 | 0.00 |
April | 1736.27 | 0.00 | 0.00 |
May | 251.81 | 0.00 | 0.00 |
June | 110.82 | 0.00 | 0.00 |
July | 0.42 | 0.00 | 0.00 |
August | 7.58 | 0.00 | 0.00 |
September | 376.33 | 0.00 | 0.00 |
October | 1362.01 | 0.00 | 0.00 |
November | 3519.06 | 0.00 | 0.00 |
December | 5460.25 | 0.00 | 0.00 |
Annual Sum or Average | 2282.77 | 0.00 | 0.00 |
Minimum of Months | 0.42 | 0.00 | 0.00 |
Maximum of Months | 6475.34 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7083.13 | 0.00 | 0.00 |
February | 5714.64 | 0.00 | 0.00 |
March | 3600.93 | 0.00 | 0.00 |
April | 1919.08 | 0.00 | 0.00 |
May | 389.25 | 0.00 | 0.00 |
June | 137.59 | 0.00 | 0.00 |
July | 2.69 | 0.00 | 0.00 |
August | 15.47 | 0.00 | 0.00 |
September | 515.25 | 0.00 | 0.00 |
October | 1770.50 | 0.00 | 0.00 |
November | 3896.55 | 0.00 | 0.00 |
December | 5944.92 | 0.00 | 0.00 |
Annual Sum or Average | 2567.34 | 0.00 | 0.00 |
Minimum of Months | 2.69 | 0.00 | 0.00 |
Maximum of Months | 7083.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5640.65 | 0.00 | 0.00 |
February | 4638.38 | 0.00 | 0.00 |
March | 3038.85 | 0.00 | 0.00 |
April | 1719.85 | 0.00 | 0.00 |
May | 338.66 | 0.00 | 0.00 |
June | 105.82 | 0.00 | 0.00 |
July | 0.51 | 0.00 | 0.00 |
August | 7.25 | 0.00 | 0.00 |
September | 403.26 | 0.00 | 0.00 |
October | 1474.50 | 0.00 | 0.00 |
November | 3110.72 | 0.00 | 0.00 |
December | 4703.56 | 0.00 | 0.00 |
Annual Sum or Average | 2085.99 | 0.00 | 0.00 |
Minimum of Months | 0.51 | 0.00 | 0.00 |
Maximum of Months | 5640.65 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7161.56 | 0.00 | 0.00 |
February | 5812.86 | 0.00 | 0.00 |
March | 3601.47 | 0.00 | 0.00 |
April | 1963.65 | 0.00 | 0.00 |
May | 283.12 | 0.00 | 0.00 |
June | 115.64 | 0.00 | 0.00 |
July | 0.42 | 0.00 | 0.00 |
August | 7.40 | 0.00 | 0.00 |
September | 464.54 | 0.00 | 0.00 |
October | 1775.51 | 0.00 | 0.00 |
November | 3963.16 | 0.00 | 0.00 |
December | 6037.25 | 0.00 | 0.00 |
Annual Sum or Average | 2583.12 | 0.00 | 0.00 |
Minimum of Months | 0.42 | 0.00 | 0.00 |
Maximum of Months | 7161.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8562.93 | 0.00 | 0.00 |
February | 6808.05 | 0.00 | 0.00 |
March | 4342.41 | 0.00 | 0.00 |
April | 2345.52 | 0.00 | 0.00 |
May | 511.98 | 0.00 | 0.00 |
June | 188.68 | 0.00 | 0.00 |
July | 6.49 | 0.00 | 0.00 |
August | 22.45 | 0.00 | 0.00 |
September | 618.66 | 0.00 | 0.00 |
October | 1964.25 | 0.00 | 0.00 |
November | 4716.91 | 0.00 | 0.00 |
December | 7158.86 | 0.00 | 0.00 |
Annual Sum or Average | 3085.94 | 0.00 | 0.00 |
Minimum of Months | 6.49 | 0.00 | 0.00 |
Maximum of Months | 8562.93 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7101.06 | 0.00 | 0.00 |
February | 5719.58 | 0.00 | 0.00 |
March | 3728.59 | 0.00 | 0.00 |
April | 2080.65 | 0.00 | 0.00 |
May | 419.88 | 0.00 | 0.00 |
June | 152.44 | 0.00 | 0.00 |
July | 2.33 | 0.00 | 0.00 |
August | 11.63 | 0.00 | 0.00 |
September | 460.78 | 0.00 | 0.00 |
October | 1567.24 | 0.00 | 0.00 |
November | 3871.88 | 0.00 | 0.00 |
December | 5882.00 | 0.00 | 0.00 |
Annual Sum or Average | 2567.71 | 0.00 | 0.00 |
Minimum of Months | 2.33 | 0.00 | 0.00 |
Maximum of Months | 7101.06 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8638.93 | 0.00 | 0.00 |
February | 6900.66 | 0.00 | 0.00 |
March | 4341.39 | 0.00 | 0.00 |
April | 2378.34 | 0.00 | 0.00 |
May | 397.46 | 0.00 | 0.00 |
June | 159.64 | 0.00 | 0.00 |
July | 0.99 | 0.00 | 0.00 |
August | 10.48 | 0.00 | 0.00 |
September | 549.36 | 0.00 | 0.00 |
October | 1941.67 | 0.00 | 0.00 |
November | 4771.47 | 0.00 | 0.00 |
December | 7250.39 | 0.00 | 0.00 |
Annual Sum or Average | 3093.16 | 0.00 | 0.00 |
Minimum of Months | 0.99 | 0.00 | 0.00 |
Maximum of Months | 8638.93 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 9194.44 | 0.00 | 0.00 |
February | 7448.54 | 0.00 | 0.00 |
March | 4753.69 | 0.00 | 0.00 |
April | 2546.28 | 0.00 | 0.00 |
May | 553.78 | 0.00 | 0.00 |
June | 193.57 | 0.00 | 0.00 |
July | 5.51 | 0.00 | 0.00 |
August | 23.29 | 0.00 | 0.00 |
September | 720.17 | 0.00 | 0.00 |
October | 2395.34 | 0.00 | 0.00 |
November | 5131.81 | 0.00 | 0.00 |
December | 7691.20 | 0.00 | 0.00 |
Annual Sum or Average | 3368.36 | 0.00 | 0.00 |
Minimum of Months | 5.51 | 0.00 | 0.00 |
Maximum of Months | 9194.44 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7741.10 | 0.00 | 0.00 |
February | 6352.14 | 0.00 | 0.00 |
March | 4168.41 | 0.00 | 0.00 |
April | 2333.48 | 0.00 | 0.00 |
May | 489.94 | 0.00 | 0.00 |
June | 160.98 | 0.00 | 0.00 |
July | 1.98 | 0.00 | 0.00 |
August | 13.32 | 0.00 | 0.00 |
September | 584.66 | 0.00 | 0.00 |
October | 2095.16 | 0.00 | 0.00 |
November | 4314.53 | 0.00 | 0.00 |
December | 6429.17 | 0.00 | 0.00 |
Annual Sum or Average | 2873.37 | 0.00 | 0.00 |
Minimum of Months | 1.98 | 0.00 | 0.00 |
Maximum of Months | 7741.10 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 9296.03 | 0.00 | 0.00 |
February | 7560.20 | 0.00 | 0.00 |
March | 4774.31 | 0.00 | 0.00 |
April | 2600.34 | 0.00 | 0.00 |
May | 428.33 | 0.00 | 0.00 |
June | 167.18 | 0.00 | 0.00 |
July | 0.68 | 0.00 | 0.00 |
August | 10.95 | 0.00 | 0.00 |
September | 645.91 | 0.00 | 0.00 |
October | 2416.13 | 0.00 | 0.00 |
November | 5216.09 | 0.00 | 0.00 |
December | 7800.75 | 0.00 | 0.00 |
Annual Sum or Average | 3389.35 | 0.00 | 0.00 |
Minimum of Months | 0.68 | 0.00 | 0.00 |
Maximum of Months | 9296.03 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.19 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.19 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.20 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.20 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: CRAWLSPACE
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 2.27 | 3993.91 |
February | 8.55 | 2681.11 |
March | 20.29 | 1677.71 |
April | 65.22 | 806.55 |
May | 101.02 | 149.18 |
June | 153.14 | 51.60 |
July | 179.59 | 2.47 |
August | 164.50 | 7.94 |
September | 119.26 | 175.10 |
October | 47.72 | 614.90 |
November | 14.93 | 1915.88 |
December | 3.84 | 3238.93 |
Annual Sum or Average | 880.30 | 15315.29 |
Minimum of Months | 2.27 | 2.47 |
Maximum of Months | 179.59 | 3993.91 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 2.10 | 2753.11 |
February | 8.21 | 1847.35 |
March | 18.70 | 1150.55 |
April | 47.94 | 560.49 |
May | 79.72 | 119.04 |
June | 109.15 | 42.20 |
July | 124.00 | 1.48 |
August | 119.50 | 5.20 |
September | 96.31 | 116.05 |
October | 46.25 | 364.11 |
November | 16.39 | 1263.35 |
December | 4.29 | 2167.67 |
Annual Sum or Average | 672.55 | 10390.61 |
Minimum of Months | 2.10 | 1.48 |
Maximum of Months | 124.00 | 2753.11 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.56 | 3969.78 |
February | 7.10 | 2681.14 |
March | 18.99 | 1632.68 |
April | 58.17 | 804.26 |
May | 103.48 | 131.69 |
June | 153.11 | 41.85 |
July | 175.20 | 0.73 |
August | 158.53 | 3.63 |
September | 118.09 | 149.64 |
October | 44.01 | 594.95 |
November | 13.28 | 1912.31 |
December | 2.33 | 3232.16 |
Annual Sum or Average | 853.84 | 15154.83 |
Minimum of Months | 1.56 | 0.73 |
Maximum of Months | 175.20 | 3969.78 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4522.10 |
February | 1.95 | 3118.09 |
March | 10.40 | 1943.54 |
April | 45.08 | 880.11 |
May | 88.39 | 163.28 |
June | 144.22 | 53.05 |
July | 165.48 | 2.63 |
August | 142.85 | 9.22 |
September | 88.82 | 213.07 |
October | 21.77 | 780.10 |
November | 6.84 | 2187.19 |
December | 0.00 | 3653.43 |
Annual Sum or Average | 715.80 | 17525.79 |
Minimum of Months | 0.00 | 2.63 |
Maximum of Months | 165.48 | 4522.10 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3286.16 |
February | 0.00 | 2254.30 |
March | 6.57 | 1401.86 |
April | 29.26 | 646.76 |
May | 68.33 | 140.15 |
June | 100.77 | 43.95 |
July | 110.29 | 1.58 |
August | 98.36 | 6.62 |
September | 65.58 | 143.53 |
October | 18.15 | 507.68 |
November | 8.49 | 1540.64 |
December | 0.00 | 2581.33 |
Annual Sum or Average | 505.81 | 12554.56 |
Minimum of Months | 0.00 | 1.58 |
Maximum of Months | 110.29 | 3286.16 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4514.19 |
February | 0.27 | 3117.44 |
March | 8.01 | 1885.88 |
April | 39.11 | 887.83 |
May | 90.14 | 138.92 |
June | 143.83 | 44.47 |
July | 160.64 | 0.91 |
August | 136.16 | 4.59 |
September | 86.88 | 184.34 |
October | 16.75 | 734.96 |
November | 5.55 | 2191.47 |
December | 0.00 | 3667.16 |
Annual Sum or Average | 687.34 | 17372.16 |
Minimum of Months | 0.00 | 0.91 |
Maximum of Months | 160.64 | 4514.19 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 6.25 | 2366.20 |
February | 17.63 | 1546.76 |
March | 36.37 | 912.51 |
April | 82.92 | 426.69 |
May | 121.74 | 88.65 |
June | 168.87 | 33.49 |
July | 196.35 | 0.38 |
August | 180.77 | 2.42 |
September | 137.00 | 97.04 |
October | 68.96 | 326.15 |
November | 26.09 | 1089.65 |
December | 10.55 | 1947.87 |
Annual Sum or Average | 1053.51 | 8837.82 |
Minimum of Months | 6.25 | 0.38 |
Maximum of Months | 196.35 | 2366.20 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 9.24 | 1186.55 |
February | 22.65 | 787.20 |
March | 42.22 | 482.41 |
April | 71.00 | 257.20 |
May | 98.33 | 66.26 |
June | 124.17 | 20.62 |
July | 140.93 | 0.06 |
August | 136.35 | 1.09 |
September | 115.14 | 62.77 |
October | 76.21 | 198.15 |
November | 35.41 | 549.07 |
December | 17.10 | 966.53 |
Annual Sum or Average | 888.77 | 4577.93 |
Minimum of Months | 9.24 | 0.06 |
Maximum of Months | 140.93 | 1186.55 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 4.86 | 2338.76 |
February | 16.02 | 1539.50 |
March | 37.48 | 884.80 |
April | 76.70 | 431.51 |
May | 123.69 | 61.54 |
June | 170.41 | 28.96 |
July | 193.16 | 0.05 |
August | 175.87 | 1.49 |
September | 136.91 | 87.42 |
October | 64.82 | 312.78 |
November | 24.32 | 1083.92 |
December | 9.37 | 1940.11 |
Annual Sum or Average | 1033.62 | 8710.85 |
Minimum of Months | 4.86 | 0.05 |
Maximum of Months | 193.16 | 2338.76 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.10 | 2815.75 |
February | 5.36 | 1885.33 |
March | 20.20 | 1083.82 |
April | 61.36 | 474.06 |
May | 107.78 | 92.96 |
June | 160.26 | 36.28 |
July | 182.37 | 0.37 |
August | 158.82 | 3.24 |
September | 105.85 | 124.58 |
October | 39.86 | 435.79 |
November | 12.93 | 1283.17 |
December | 0.24 | 2258.26 |
Annual Sum or Average | 855.13 | 10493.61 |
Minimum of Months | 0.10 | 0.37 |
Maximum of Months | 182.37 | 2815.75 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.62 | 1584.84 |
February | 4.30 | 1037.20 |
March | 20.41 | 594.58 |
April | 50.18 | 305.45 |
May | 86.74 | 81.69 |
June | 115.99 | 23.79 |
July | 127.30 | 0.15 |
August | 114.60 | 1.33 |
September | 84.96 | 93.86 |
October | 45.83 | 278.03 |
November | 17.38 | 682.87 |
December | 0.31 | 1194.76 |
Annual Sum or Average | 668.62 | 5878.55 |
Minimum of Months | 0.31 | 0.15 |
Maximum of Months | 127.30 | 1584.84 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2803.32 |
February | 1.88 | 1862.35 |
March | 18.62 | 1033.93 |
April | 56.10 | 487.90 |
May | 109.21 | 65.49 |
June | 161.48 | 31.35 |
July | 178.80 | 0.04 |
August | 153.53 | 1.39 |
September | 104.14 | 103.22 |
October | 38.08 | 429.13 |
November | 12.15 | 1286.68 |
December | 0.00 | 2267.21 |
Annual Sum or Average | 833.98 | 10372.00 |
Minimum of Months | 0.00 | 0.04 |
Maximum of Months | 178.80 | 2803.32 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4399.69 |
February | 0.21 | 3026.72 |
March | 8.64 | 1793.27 |
April | 43.36 | 807.72 |
May | 100.91 | 112.18 |
June | 161.85 | 39.40 |
July | 183.05 | 0.05 |
August | 155.47 | 2.85 |
September | 99.07 | 166.02 |
October | 18.04 | 672.01 |
November | 6.71 | 2129.14 |
December | 0.00 | 3587.46 |
Annual Sum or Average | 777.32 | 16736.52 |
Minimum of Months | 0.00 | 0.05 |
Maximum of Months | 183.05 | 4399.69 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.38 | 3921.97 |
February | 6.69 | 2647.97 |
March | 19.63 | 1589.09 |
April | 59.80 | 751.93 |
May | 110.87 | 101.81 |
June | 168.05 | 37.70 |
July | 193.12 | 0.09 |
August | 172.59 | 2.37 |
September | 125.39 | 141.20 |
October | 43.45 | 549.63 |
November | 13.34 | 1874.64 |
December | 1.89 | 3196.53 |
Annual Sum or Average | 916.21 | 14814.93 |
Minimum of Months | 1.38 | 0.09 |
Maximum of Months | 193.12 | 3921.97 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.80 | 3941.51 |
February | 8.43 | 2653.93 |
March | 20.56 | 1630.44 |
April | 66.50 | 756.23 |
May | 109.02 | 123.81 |
June | 167.33 | 44.25 |
July | 197.06 | 0.77 |
August | 177.98 | 5.11 |
September | 125.77 | 161.01 |
October | 47.56 | 579.07 |
November | 15.35 | 1882.47 |
December | 3.29 | 3203.44 |
Annual Sum or Average | 940.66 | 14982.03 |
Minimum of Months | 1.80 | 0.77 |
Maximum of Months | 197.06 | 3941.51 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3163.58 |
February | 0.33 | 2159.84 |
March | 9.22 | 1314.17 |
April | 36.98 | 594.32 |
May | 79.69 | 113.62 |
June | 118.37 | 37.90 |
July | 133.17 | 0.25 |
August | 117.85 | 2.95 |
September | 79.07 | 132.07 |
October | 22.73 | 470.64 |
November | 9.29 | 1467.73 |
December | 0.00 | 2495.52 |
Annual Sum or Average | 606.71 | 11952.58 |
Minimum of Months | 0.00 | 0.25 |
Maximum of Months | 133.17 | 3163.58 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 2.10 | 2693.61 |
February | 7.96 | 1802.35 |
March | 19.72 | 1096.73 |
April | 51.54 | 521.23 |
May | 88.20 | 96.24 |
June | 124.27 | 36.09 |
July | 142.78 | 0.23 |
August | 134.32 | 2.50 |
September | 104.81 | 106.81 |
October | 49.04 | 339.70 |
November | 17.40 | 1225.27 |
December | 3.68 | 2119.89 |
Annual Sum or Average | 745.83 | 10040.65 |
Minimum of Months | 2.10 | 0.23 |
Maximum of Months | 142.78 | 2693.61 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:40:10
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4410.14 |
February | 2.09 | 3034.62 |
March | 11.07 | 1850.47 |
April | 50.65 | 820.05 |
May | 98.80 | 130.67 |
June | 161.59 | 46.26 |
July | 187.21 | 0.97 |
August | 161.29 | 5.52 |
September | 99.85 | 189.75 |
October | 23.93 | 730.82 |
November | 7.53 | 2123.23 |
December | 0.00 | 3576.69 |
Annual Sum or Average | 804.00 | 16919.20 |
Minimum of Months | 0.00 | 0.97 |