Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:52
Tabular Output Report in Format: HTML
Building: US+MF+CZ8+oilfurnace+heatedbsmt+IECC_2015
Environment: ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2021-05-12 10:52:17
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1586907.33 | 40.68 | 53.97 |
Net Site Energy | 1586907.33 | 40.68 | 53.97 |
Total Source Energy | 2616393.85 | 67.08 | 88.98 |
Net Source Energy | 2616393.85 | 67.08 | 88.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.87 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 826434.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 17367.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299798.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50011.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 330234.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 430238.26 | 1156669.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 826434.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 17367.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 31744.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 18266.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 330234.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.29 | 39.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Other | 10.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 14.63 | 39.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1.73 | 29.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 11.03 | 29.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 430238.264 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 430238.264 | 100.00 |
Total On-Site and Utility Electric Sources | 430238.264 | 100.00 |
Total Electricity End Uses | 430238.264 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 330767.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 330767.30 | 100.00 |
Total Water End Uses | 330767.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1883.67 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3565.50 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| HEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:52 |
RunPeriod | ANNUAL |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [ft] | 436.37 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58539.52 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
Total | 39005.22 | 325627.71 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.3693 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242278.90 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.4899 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 29-JUL-18:10 | 11-JAN-10:00 | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:09 |
Heating | 0.00 | 301.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 25.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 223.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 105.28 | 524.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 301.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 25.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 4.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 223.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 895855.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 55003.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140144.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949462.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158385.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 357974.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1362564.58 | 1253829.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 30.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 46.34 | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 34.93 | 32.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
ZoneHVAC:EnergyRecoveryVentilatorUser-Specified Supply Air Flow Rate [ft3/min] | User-Specified Exhaust Air Flow Rate [ft3/min] | |
ERV_UNITHEATEDBSMT | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.99 |
User-Specified Maximum Flow Rate [ft3/min] | Design Size Maximum Flow Rate [ft3/min] | |
OASUPPLYFAN_UNITHEATEDBSMT | 44.99 | |
OAEXHAUSTFAN_UNITHEATEDBSMT | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 373.30 | |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 199.07 | |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 296.75 | |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 333.95 | |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 152.22 | |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 247.69 | |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 437.70 | |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 241.12 | |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 353.12 | |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 389.22 | |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 182.41 | |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 299.40 | |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 451.20 | |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 248.51 | |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 346.82 | |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 419.20 | |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 213.42 | |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 294.59 | |
SUPPLY FAN_UNITHEATEDBSMT | 363.38 |
User-Specified Nominal Supply Air Flow Rate [ft3/min] | |
OA_HEAT_RECOVERY_UNITHEATEDBSMT | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | 44.99 |
Design Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 363.38 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 373.30 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 199.07 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 296.75 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 333.95 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 152.22 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 247.69 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 437.70 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 241.12 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 353.12 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 389.22 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 182.41 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 299.40 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 294.59 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 346.82 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 451.20 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 213.42 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 248.51 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 419.20 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 373.30 | 373.30 | 373.30 | 373.30 | 373.30 | 373.30 | 1.00 | 1.00 | 373.30 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 199.07 | 199.07 | 199.07 | 199.07 | 199.07 | 199.07 | 1.00 | 1.00 | 199.07 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 296.75 | 296.75 | 296.75 | 296.75 | 296.75 | 296.75 | 1.00 | 1.00 | 296.75 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 333.95 | 333.95 | 333.95 | 333.95 | 333.95 | 333.95 | 1.00 | 1.00 | 333.95 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 152.22 | 152.22 | 152.22 | 152.22 | 152.22 | 152.22 | 1.00 | 1.00 | 152.22 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 247.69 | 247.69 | 247.69 | 247.69 | 247.69 | 247.69 | 1.00 | 1.00 | 247.69 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 437.70 | 437.70 | 437.70 | 437.70 | 437.70 | 437.70 | 1.00 | 1.00 | 437.70 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 241.12 | 241.12 | 241.12 | 241.12 | 241.12 | 241.12 | 1.00 | 1.00 | 241.12 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.12 | 353.12 | 353.12 | 353.12 | 353.12 | 353.12 | 1.00 | 1.00 | 353.12 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 389.22 | 389.22 | 389.22 | 389.22 | 389.22 | 389.22 | 1.00 | 1.00 | 389.22 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 182.41 | 182.41 | 182.41 | 182.41 | 182.41 | 182.41 | 1.00 | 1.00 | 182.41 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 299.40 | 299.40 | 299.40 | 299.40 | 299.40 | 299.40 | 1.00 | 1.00 | 299.40 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 451.20 | 451.20 | 451.20 | 451.20 | 451.20 | 451.20 | 1.00 | 1.00 | 451.20 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.51 | 248.51 | 248.51 | 248.51 | 248.51 | 248.51 | 1.00 | 1.00 | 248.51 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 346.82 | 346.82 | 346.82 | 346.82 | 346.82 | 346.82 | 1.00 | 1.00 | 346.82 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 419.20 | 419.20 | 419.20 | 419.20 | 419.20 | 419.20 | 1.00 | 1.00 | 419.20 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 213.42 | 213.42 | 213.42 | 213.42 | 213.42 | 213.42 | 1.00 | 1.00 | 213.42 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 294.59 | 294.59 | 294.59 | 294.59 | 294.59 | 294.59 | 1.00 | 1.00 | 294.59 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 363.38 | 363.38 | 363.38 | 363.38 | 363.38 | 363.38 | 1.00 | 1.00 | 363.38 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 373.30 | 0.829309 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 199.07 | 0.442240 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 296.75 | 0.659254 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 333.95 | 0.741897 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 152.22 | 0.338176 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 247.69 | 0.550269 | 0.800655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 437.70 | 0.972388 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 241.12 | 0.535665 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 353.12 | 0.784486 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 389.22 | 0.864685 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 182.41 | 0.405229 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 299.40 | 0.665149 | 0.800655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 451.20 | 1.00 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 248.51 | 0.552094 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 346.82 | 0.770476 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 419.20 | 0.931292 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 213.42 | 0.474122 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 294.59 | 0.654458 | 0.800655 |
DX COOLING COIL_UNITHEATEDBSMT | 363.38 | 0.924858 | 0.797912 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 373.30 | 373.30 | 373.30 | 0.829309 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 199.07 | 199.07 | 199.07 | 0.442240 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 296.75 | 296.75 | 296.75 | 0.659254 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 333.95 | 333.95 | 333.95 | 0.741897 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 152.22 | 152.22 | 152.22 | 0.338176 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 247.69 | 247.69 | 247.69 | 0.550269 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 437.70 | 437.70 | 437.70 | 0.972388 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 241.12 | 241.12 | 241.12 | 0.535665 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 353.12 | 353.12 | 353.12 | 0.784486 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 389.22 | 389.22 | 389.22 | 0.864685 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 182.41 | 182.41 | 182.41 | 0.405229 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 299.40 | 299.40 | 299.40 | 0.665149 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 451.20 | 451.20 | 451.20 | 1.00 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 248.51 | 248.51 | 248.51 | 0.552094 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 346.82 | 346.82 | 346.82 | 0.770476 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 419.20 | 419.20 | 419.20 | 0.931292 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 213.42 | 213.42 | 213.42 | 0.474122 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 294.59 | 294.59 | 294.59 | 0.654458 | 1.00 |
ACANDF_UNITHEATEDBSMT | 363.38 | 363.38 | 363.38 | 0.924858 | 1.00 |
Design Size Rated Capacity [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 25429.84 | 2.61 | 338.01 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 16143.80 | 1.66 | 201.03 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 21350.18 | 2.19 | 278.15 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 23332.79 | 2.40 | 307.30 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 13647.33 | 1.40 | 163.38 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 18735.59 | 1.92 | 239.57 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 28860.42 | 2.96 | 387.96 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 18384.09 | 1.89 | 234.26 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 24353.02 | 2.50 | 322.11 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 26276.85 | 2.70 | 350.25 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 15255.24 | 1.57 | 187.59 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 21490.37 | 2.21 | 280.09 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29581.79 | 3.04 | 398.59 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 18779.16 | 1.93 | 240.20 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 24018.39 | 2.47 | 317.30 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 27876.41 | 2.86 | 373.71 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 16908.63 | 1.74 | 212.43 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 21235.10 | 2.18 | 276.41 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 24898.73 | 2.56 | 329.98 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 5.71 | 11.43 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 5.71 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 416557.73 | 42.76 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
VersionVersion ID | |
1 | 9.5 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 2.59 | -0.0 | 4.60 | 11.91 | 30.97 | 45.70 | 55.63 | 58.66 | 53.51 | 42.08 | 26.80 | 12.63 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 436.37 | 14. | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 29.25 | 65.16 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ8+oilfurnace+heatedbsmt+IECC_2015 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.8807 | Rough | 0.1021 | 3.533E-002 | 1.255 | 0.350 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 7.7625 | Rough | 1.5719 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3227 | Rough | 0.4584 | 6.015E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5503 | Smooth | 0.1300 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.3765 | VerySmooth | 0.1318 | 0.107 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | HEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | HEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0498 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
10 | BASEMENT WALL | 24 | 3 | 10 | 0.167 | 0.0664 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
11 | iz-EXTERIOR FLOOR | 25 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.1020 | 0.035 | 1.255 | 0.350 | 0.8807 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.1299 | 0.072 | 32.003 | 0.183 | 0.5503 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
25 | BSMTWALL_CONSOL_LAYER | 0.4584 | 0.060 | 7.541 | 0.248 | 2.323 |
26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 10 | 0.51360630E-08 | -0.22035233E-13 | 0.91774209E-08 | -0.50676220E-13 |
2 | 9 | -0.14060012E-04 | 0.39159197E-12 | -0.22958088E-04 | 0.29728831E-08 |
3 | 8 | 0.28980689E-02 | 0.65531654E-09 | 0.46215968E-02 | -0.71708779E-05 |
4 | 7 | -0.65978682E-01 | 0.13350779E-06 | -0.16306378 | 0.13238707E-02 |
5 | 6 | 0.64596177 | 0.50193482E-05 | 2.1320981 | -0.28125917E-01 |
6 | 5 | -3.4215999 | 0.48298777E-04 | -13.652056 | 0.25148823 |
7 | 4 | 10.645660 | 0.13839053E-03 | 47.881148 | -1.1749737 |
8 | 3 | -19.924231 | 0.11919231E-03 | -96.040791 | 3.0621859 |
9 | 2 | 21.976583 | 0.26462555E-04 | 109.48934 | -4.4404618 |
10 | 1 | -13.118296 | 0.91387708E-06 | -65.855375 | 3.3273744 |
11 | 0 | 3.2593552 | 0.33613880E-09 | 16.204438 | |
12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
18 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
19 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
20 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
21 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
22 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
23 | 12 | 0.94888791E-16 | -0.11237443E-15 | 0.21480527E-09 | -0.52606005E-16 |
24 | 11 | -0.44509090E-09 | -0.12338758E-15 | -0.11566016E-03 | 0.28501063E-09 |
25 | 10 | 0.60393314E-04 | 0.62564840E-13 | 0.62960490E-02 | -0.38672578E-04 |
26 | 9 | -0.20055671E-02 | 0.85912012E-10 | -0.12885789 | 0.13084700E-02 |
27 | 8 | 0.28697042E-01 | 0.10381403E-07 | 1.3966036 | -0.19129448E-01 |
28 | 7 | -0.23229993 | 0.28493476E-06 | -9.1473517 | 0.15872626 |
29 | 6 | 1.1750436 | 0.24973161E-05 | 38.552224 | -0.82592201 |
30 | 5 | -3.8729952 | 0.80040830E-05 | -107.65441 | 2.8111251 |
31 | 4 | 8.4143451 | 0.96510929E-05 | 200.56463 | -6.3313915 |
32 | 3 | -11.897084 | 0.41099356E-05 | -245.77565 | 9.3152582 |
33 | 2 | 10.487404 | 0.50788650E-06 | 189.69676 | -8.5734564 |
34 | 1 | -5.2147174 | 0.10902359E-07 | -83.415737 | 4.4633233 |
35 | 0 | 1.1135774 | 0.38882120E-11 | 15.905642 | |
36 | 12 | 0.21480527E-09 | -0.11237443E-15 | 0.94888791E-16 | -0.52606005E-16 |
37 | 11 | -0.11566016E-03 | -0.12338758E-15 | -0.44509090E-09 | 0.28501063E-09 |
38 | 10 | 0.62960490E-02 | 0.62564840E-13 | 0.60393314E-04 | -0.38672578E-04 |
39 | 9 | -0.12885789 | 0.85912012E-10 | -0.20055671E-02 | 0.13084700E-02 |
40 | 8 | 1.3966036 | 0.10381403E-07 | 0.28697042E-01 | -0.19129448E-01 |
41 | 7 | -9.1473517 | 0.28493476E-06 | -0.23229993 | 0.15872626 |
42 | 6 | 38.552224 | 0.24973161E-05 | 1.1750436 | -0.82592201 |
43 | 5 | -107.65441 | 0.80040830E-05 | -3.8729952 | 2.8111251 |
44 | 4 | 200.56463 | 0.96510929E-05 | 8.4143451 | -6.3313915 |
45 | 3 | -245.77565 | 0.41099356E-05 | -11.897084 | 9.3152582 |
46 | 2 | 189.69676 | 0.50788650E-06 | 10.487404 | -8.5734564 |
47 | 1 | -83.415737 | 0.10902359E-07 | -5.2147174 | 4.4633233 |
48 | 0 | 15.905642 | 0.38882120E-11 | 1.1135774 | |
49 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
50 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
51 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
52 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
53 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
54 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
55 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
56 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
57 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
58 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
59 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
60 | 5 | -0.47059848E-07 | 0.10808286E-07 | -0.47059848E-07 | 0.33552267E-09 |
61 | 4 | 0.23241354E-03 | 0.64872557E-04 | 0.23241354E-03 | -0.29116876E-05 |
62 | 3 | -0.69106029E-01 | 0.14208819E-01 | -0.69106029E-01 | 0.18005536E-02 |
63 | 2 | 1.8030591 | 0.23437818 | 1.8030591 | -0.90752678E-01 |
64 | 1 | -7.5310044 | 0.40520073 | -7.5310044 | 0.70046896 |
65 | 0 | 6.5027572 | 0.52085640E-01 | 6.5027572 | |
66 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
67 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
68 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
69 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
70 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
71 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
72 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
73 | 10 | 0.50442590E-10 | 0.37421431E-14 | 0.50442587E-10 | -0.86521684E-16 |
74 | 9 | -0.53972773E-06 | 0.41502128E-13 | -0.53972773E-06 | 0.83963618E-10 |
75 | 8 | 0.10045687E-02 | 0.32837718E-09 | 0.10045687E-02 | -0.39657273E-06 |
76 | 7 | -0.35699803E-01 | 0.19108467E-06 | -0.35699803E-01 | 0.47332591E-03 |
77 | 6 | 0.49910094 | 0.13935795E-04 | 0.49910094 | -0.11937255E-01 |
78 | 5 | -3.5897715 | 0.21519702E-03 | -3.5897715 | 0.12239145 |
79 | 4 | 14.570676 | 0.91210570E-03 | 14.570676 | -0.65483682 |
80 | 3 | -34.297718 | 0.11291753E-02 | -34.297718 | 1.9662386 |
81 | 2 | 45.961246 | 0.36528821E-03 | 45.961246 | -3.3045605 |
82 | 1 | -32.291846 | 0.20188525E-04 | -32.291846 | 2.8751859 |
83 | 0 | 9.1856636 | 0.31580648E-07 | 9.1856636 | |
84 | 4 | 0.60443234E-14 | -0.40788276E-14 | 0.29631924E-13 | -0.77798347E-16 |
85 | 3 | -0.23145793E-05 | 0.79669069E-06 | -0.11254351E-04 | 0.39394231E-13 |
86 | 2 | 0.78801895E-01 | 0.29587917E-01 | 0.49771861 | -0.76025120E-05 |
87 | 1 | -1.1535996 | 0.80192706 | -8.3915550 | 0.21114735 |
88 | 0 | 2.4177143 | 0.51139848 | 9.2367617 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.320 | 0.335 | 0.248 | 0.883 |
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.320 | 0.335 | 0.248 | 0.883 |
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.320 | 0.309 | 4.642E-002 | 0.133 |
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 0.929 | 0.920 | 0.920 |
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 0.906 | 0.900 | 0.900 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.821 | 0.5868 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
19 | VENTILATION_UNITHEATEDBSMT | ALWAYS_OFF | HEATEDBSMT | 7794.37 | 0.0 | 0.000 | 0.000 | N/A | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | HEATEDBSMT | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | HEATEDBSMT | Cooling | 0.00000 | 0.00000 | 0.00000 | 44.99491 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 81.32000 | 0.00701 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 | |
2 | HEATEDBSMT | Heating | 19650.07445 | 19650.07445 | 363.36860 | 363.36860 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | -43.4200 | 0.00006 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 8641.13177 | 8641.13177 | 373.30504 | 373.30504 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 75.99560 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 11724.73810 | 11724.73810 | 216.77963 | 216.77963 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 4608.01368 | 4608.01368 | 199.06586 | 199.06586 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 81.32000 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 8233.93885 | 8233.93885 | 152.24701 | 152.24701 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 6869.32009 | 6869.32009 | 296.75844 | 296.75844 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 77.40320 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 11718.14622 | 11718.14622 | 216.67370 | 216.67370 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 7730.26593 | 7730.26593 | 333.94064 | 333.94064 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.15960 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 11726.08714 | 11726.08714 | 216.82201 | 216.82201 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 3320.38388 | 3320.38388 | 143.44214 | 143.44214 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 70.48760 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 8232.66576 | 8232.66576 | 152.22350 | 152.22350 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 5733.67493 | 5733.67493 | 247.69065 | 247.69065 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 73.30280 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 11714.31659 | 11714.31659 | 216.58896 | 216.58896 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 10131.87214 | 10131.87214 | 437.71181 | 437.71181 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 74.61860 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 9399.77216 | 9399.77216 | 173.81587 | 173.81587 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 5581.46356 | 5581.46356 | 241.12285 | 241.12285 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 80.95280 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 5688.61889 | 5688.61889 | 105.19321 | 105.19321 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 8174.19210 | 8174.19210 | 353.11436 | 353.11436 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 78.01520 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 9390.84637 | 9390.84637 | 173.65083 | 173.65083 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 9009.62784 | 9009.62784 | 389.21605 | 389.21605 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 72.81320 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 9400.89846 | 9400.89846 | 173.83663 | 173.83663 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 4222.30428 | 4222.30428 | 182.40591 | 182.40591 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 69.93680 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 5686.99706 | 5686.99706 | 105.16333 | 105.16333 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6930.71040 | 6930.71040 | 299.40674 | 299.40674 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 74.80220 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 9386.55878 | 9386.55878 | 173.57138 | 173.57138 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 6819.33757 | 6819.33757 | 294.59742 | 294.59742 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.26120 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 14487.56375 | 14487.56375 | 267.88132 | 267.88132 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 8028.23660 | 8028.23660 | 346.82199 | 346.82199 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 78.32120 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 14492.31660 | 14492.31660 | 267.96607 | 267.96607 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 10444.38654 | 10444.38654 | 451.20757 | 451.20757 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.15960 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 14503.00653 | 14503.00653 | 268.15675 | 268.15675 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 4940.16305 | 4940.16305 | 213.41099 | 213.41099 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 70.21220 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 10774.49122 | 10774.49122 | 199.22243 | 199.22243 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 5752.67786 | 5752.67786 | 248.51692 | 248.51692 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 80.76920 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 10777.29084 | 10777.29084 | 199.27413 | 199.27413 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
37 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 9703.67597 | 9703.67597 | 419.19486 | 419.19486 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 73.14980 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
38 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 14502.18799 | 14502.18799 | 268.13556 | 268.13556 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2509.23 | 373.30504 | 373.30504 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 5008.35 | 216.77963 | 216.77963 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1419.45 | 199.06586 | 199.06586 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 4000.17 | 152.24701 | 152.24701 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2017.38 | 296.75844 | 296.75844 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 5006.45 | 216.67370 | 216.67370 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2220.40 | 333.94064 | 333.94064 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 5008.74 | 216.82201 | 216.82201 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 895.39 | 143.44214 | 143.44214 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3999.80 | 152.22350 | 152.22350 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1631.82 | 247.69065 | 247.69065 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 5005.34 | 216.58896 | 216.58896 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2920.35 | 437.71181 | 437.71181 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4336.93 | 173.81587 | 173.81587 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1695.39 | 241.12285 | 241.12285 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3265.11 | 105.19321 | 105.19321 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2402.78 | 353.11436 | 353.11436 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4334.35 | 173.65083 | 173.65083 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2570.91 | 389.21605 | 389.21605 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4337.26 | 173.83663 | 173.83663 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1148.09 | 182.40591 | 182.40591 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3264.64 | 105.16333 | 105.16333 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1998.55 | 299.40674 | 299.40674 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4333.11 | 173.57138 | 173.57138 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 3004.14 | 451.20757 | 451.20757 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 5810.75 | 268.15675 | 268.15675 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1742.24 | 248.51692 | 248.51692 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 4734.73 | 199.27413 | 199.27413 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2364.93 | 346.82199 | 346.82199 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 5807.67 | 267.96607 | 267.96607 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 2776.06 | 419.19486 | 419.19486 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 5810.52 | 268.13556 | 268.13556 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1359.25 | 213.41099 | 213.41099 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 4733.92 | 199.22243 | 199.22243 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 1972.84 | 294.59742 | 294.59742 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 5806.29 | 267.88132 | 267.88132 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
37 | CENTRAL SYSTEM_UNITHEATEDBSMT | Cooling | Sensible | 389.59 | 44.99491 | 44.99491 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
38 | CENTRAL SYSTEM_UNITHEATEDBSMT | Heating | Sensible | 7297.40 | 363.36860 | 363.36860 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
2 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
3 | Fan:OnOff | OASUPPLYFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
4 | Fan:OnOff | OAEXHAUSTFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
5 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNITHEATEDBSMT | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNITHEATEDBSMT | Design Size Maximum Air Flow Rate [ft3/min] | 363.36860 |
7 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
8 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
9 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
10 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
11 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 373.30504 |
13 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
14 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
15 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
16 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
17 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 199.06586 |
19 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
20 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
21 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
22 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
23 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
24 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 296.75844 |
25 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
26 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
27 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
28 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
29 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
30 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 333.94064 |
31 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
32 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
33 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
34 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
35 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
36 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 152.22350 |
37 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
38 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
39 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
40 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
41 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
42 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 247.69065 |
43 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
44 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
45 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
46 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
47 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
48 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 437.71181 |
49 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
50 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
51 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
52 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
53 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
54 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 241.12285 |
55 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
56 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
57 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
58 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
59 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
60 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 353.11436 |
61 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
62 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
63 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
64 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
65 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
66 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 389.21605 |
67 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
68 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
69 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
70 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
71 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
72 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 182.40591 |
73 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
74 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
75 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
76 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
77 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
78 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 299.40674 |
79 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
80 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
81 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
82 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
83 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
84 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 294.59742 |
85 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
86 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
87 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
88 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
89 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
90 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 346.82199 |
91 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
92 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
93 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
94 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
95 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 451.20757 |
97 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
98 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
99 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
100 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
101 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
102 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 213.41099 |
103 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
104 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
105 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
106 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
107 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
108 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 248.51692 |
109 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
110 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
111 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
112 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
113 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 419.19486 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 373.30504 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 373.30504 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 373.30504 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 373.30504 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 373.30504 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 373.30504 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 199.06586 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 199.06586 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 199.06586 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 199.06586 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 199.06586 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 199.06586 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 296.75844 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 296.75844 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 296.75844 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 296.75844 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 296.75844 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 296.75844 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 333.94064 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 333.94064 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 333.94064 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 333.94064 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 333.94064 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 333.94064 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 152.22350 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 152.22350 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 152.22350 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 152.22350 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 152.22350 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 152.22350 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 247.69065 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 247.69065 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 247.69065 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 247.69065 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 247.69065 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 247.69065 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 437.71181 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 437.71181 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 437.71181 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 437.71181 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 437.71181 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 437.71181 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 241.12285 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 241.12285 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 241.12285 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 241.12285 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 241.12285 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 241.12285 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 353.11436 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 353.11436 |
181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 353.11436 |
182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 353.11436 |
183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 353.11436 |
184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 353.11436 |
185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 389.21605 |
188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 389.21605 |
189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 389.21605 |
190 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 389.21605 |
191 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 389.21605 |
192 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 389.21605 |
193 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
194 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
195 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 182.40591 |
196 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 182.40591 |
197 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 182.40591 |
198 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 182.40591 |
199 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 182.40591 |
200 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 182.40591 |
201 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
202 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
203 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 299.40674 |
204 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 299.40674 |
205 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 299.40674 |
206 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 299.40674 |
207 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 299.40674 |
208 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 299.40674 |
209 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
210 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
211 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 451.20757 |
212 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 451.20757 |
213 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 451.20757 |
214 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 451.20757 |
215 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 451.20757 |
216 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 451.20757 |
217 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
218 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
219 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 248.51692 |
220 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 248.51692 |
221 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 248.51692 |
222 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 248.51692 |
223 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 248.51692 |
224 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 248.51692 |
225 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
226 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
227 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 346.82199 |
228 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 346.82199 |
229 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 346.82199 |
230 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 346.82199 |
231 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 346.82199 |
232 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 346.82199 |
233 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
234 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
235 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 419.19486 |
236 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 419.19486 |
237 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 419.19486 |
238 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 419.19486 |
239 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 419.19486 |
240 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 419.19486 |
241 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
242 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 213.41099 |
244 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 213.41099 |
245 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 213.41099 |
246 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 213.41099 |
247 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 213.41099 |
248 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 213.41099 |
249 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
251 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 294.59742 |
252 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 294.59742 |
253 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 294.59742 |
254 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 294.59742 |
255 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 294.59742 |
256 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 294.59742 |
257 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 363.36860 |
260 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 363.36860 |
261 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 363.36860 |
262 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Heating Design Air Flow Rate [ft3/min] | 363.36860 |
263 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Cooling Design Air Flow Rate [ft3/min] | 363.36860 |
264 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Main Design Air Flow Rate [ft3/min] | 363.36860 |
265 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 373.30504 |
268 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 199.06586 |
269 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 296.75844 |
270 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 333.94064 |
271 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 152.22350 |
272 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 247.69065 |
273 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 437.71181 |
274 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 241.12285 |
275 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 353.11436 |
276 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 389.21605 |
277 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 182.40591 |
278 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 299.40674 |
279 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 451.20757 |
280 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 248.51692 |
281 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 346.82199 |
282 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 419.19486 |
283 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 213.41099 |
284 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 294.59742 |
285 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Design Supply Air Flow Rate [ft3/min] | 363.36860 |
286 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 373.30504 |
287 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.82931 |
288 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
289 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 373.30504 |
290 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 373.30504 |
291 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 373.30504 |
292 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.82931 |
293 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 25429.83779 |
294 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.61029 |
295 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 338.00918 |
296 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
297 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 373.30504 |
298 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 199.06586 |
299 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.44224 |
300 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
301 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 199.06586 |
302 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 199.06586 |
303 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 199.06586 |
304 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.44224 |
305 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 16143.79540 |
306 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.65710 |
307 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 201.03215 |
308 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
309 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 199.06586 |
310 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 296.75844 |
311 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.65925 |
312 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
313 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 296.75844 |
314 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 296.75844 |
315 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 296.75844 |
316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.65925 |
317 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 21350.17684 |
318 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.19152 |
319 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 278.14683 |
320 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
321 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 296.75844 |
322 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 333.94064 |
323 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.74190 |
324 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
325 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 333.94064 |
326 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 333.94064 |
327 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 333.94064 |
328 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.74190 |
329 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 23332.78686 |
330 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.39503 |
331 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 307.29605 |
332 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
333 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 333.94064 |
334 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 152.22350 |
335 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.33818 |
336 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
337 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 152.22350 |
338 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 152.22350 |
339 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 152.22350 |
340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.33818 |
341 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 13647.33169 |
342 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.40085 |
343 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 163.37875 |
344 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
345 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 152.22350 |
346 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 247.69065 |
347 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.55027 |
348 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
349 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 247.69065 |
350 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 247.69065 |
351 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 247.69065 |
352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.55027 |
353 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 18735.58803 |
354 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.92315 |
355 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 239.56885 |
356 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
357 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 247.69065 |
358 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 437.71181 |
359 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.97239 |
360 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
361 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 437.71181 |
362 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 437.71181 |
363 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 437.71181 |
364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.97239 |
365 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 28860.42319 |
366 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.96242 |
367 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 387.95689 |
368 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
369 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 437.71181 |
370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 241.12285 |
371 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.53567 |
372 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
373 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 241.12285 |
374 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 241.12285 |
375 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 241.12285 |
376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.53567 |
377 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 18384.09129 |
378 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.88707 |
379 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 234.25676 |
380 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
381 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 241.12285 |
382 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 353.11436 |
383 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.78449 |
384 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
385 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 353.11436 |
386 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 353.11436 |
387 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 353.11436 |
388 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.78449 |
389 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 24353.01912 |
390 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.49975 |
391 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 322.11056 |
392 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 353.11436 |
394 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 389.21605 |
395 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.86468 |
396 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
397 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 389.21605 |
398 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 389.21605 |
399 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 389.21605 |
400 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.86468 |
401 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 26276.84536 |
402 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.69723 |
403 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 350.24677 |
404 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
405 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 389.21605 |
406 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 182.40591 |
407 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.40523 |
408 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
409 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 182.40591 |
410 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 182.40591 |
411 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 182.40591 |
412 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.40523 |
413 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 15255.23539 |
414 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.56590 |
415 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 187.58900 |
416 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 182.40591 |
418 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 299.40674 |
419 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.66515 |
420 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
421 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 299.40674 |
422 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 299.40674 |
423 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 299.40674 |
424 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.66515 |
425 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 21490.37394 |
426 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.20592 |
427 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 280.08871 |
428 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
429 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 299.40674 |
430 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 451.20757 |
431 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.00238 |
432 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
433 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 451.20757 |
434 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 451.20757 |
435 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 451.20757 |
436 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.00238 |
437 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 29581.78956 |
438 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 3.03647 |
439 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 398.58522 |
440 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
441 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 451.20757 |
442 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 248.51692 |
443 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.55209 |
444 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
445 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 248.51692 |
446 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 248.51692 |
447 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 248.51692 |
448 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.55209 |
449 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 18779.16326 |
450 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.92762 |
451 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 240.20334 |
452 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
453 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 248.51692 |
454 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 346.82199 |
455 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.77048 |
456 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
457 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 346.82199 |
458 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 346.82199 |
459 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 346.82199 |
460 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.77048 |
461 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 24018.39117 |
462 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.46541 |
463 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 317.30140 |
464 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
465 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 346.82199 |
466 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 419.19486 |
467 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.93129 |
468 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
469 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 419.19486 |
470 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 419.19486 |
471 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 419.19486 |
472 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.93129 |
473 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 27876.41256 |
474 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.86143 |
475 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 373.70813 |
476 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
477 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 419.19486 |
478 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 213.41099 |
479 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.47412 |
480 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
481 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 213.41099 |
482 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 213.41099 |
483 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 213.41099 |
484 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.47412 |
485 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 16908.63211 |
486 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.73562 |
487 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 212.42889 |
488 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
489 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 213.41099 |
490 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 294.59742 |
491 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.65446 |
492 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
493 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 294.59742 |
494 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 294.59742 |
495 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 294.59742 |
496 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.65446 |
497 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 21235.10387 |
498 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.17971 |
499 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 276.41457 |
500 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
501 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 294.59742 |
502 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Rated Air Flow Rate [ft3/min] | 363.36860 |
503 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Total Cooling Capacity [ton] | 0.92486 |
504 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Sensible Heat Ratio | 0.79791 |
505 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate [ft3/min] | 363.36860 |
506 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Heating Operation [ft3/min] | 363.36860 |
507 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Cooling Operation [ft3/min] | 363.36860 |
508 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Nominal Cooling Capacity [ton] | 0.92486 |
509 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | Design Size Rated Capacity [Btu/h] | 24898.73095 |
510 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | Design Size Maximum Water Flow Rate [gal/min] | 2.55577 |
511 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | Design Size U-Factor Times Area Value [Btu/h-F] | 329.97547 |
512 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
513 | Fan:OnOff | SUPPLY FAN_UNITHEATEDBSMT | Design Size Maximum Flow Rate [ft3/min] | 363.36860 |
514 | PlantLoop | BOILER LOOP | Maximum Loop Flow Rate [ft3/min] | 5.71470 |
515 | PlantLoop | BOILER LOOP | Plant Loop Volume [ft3] | 11.43232 |
516 | Pump:VariableSpeed | BOILER CIRC PUMP | Design Flow Rate [ft3/min] | 5.71470 |
517 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [Btu/h] | 0.416558E+06 |
518 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [gal/min] | 42.75823 |
519 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
520 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
521 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
522 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
523 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
524 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
525 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
526 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
527 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
528 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
529 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
530 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
531 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
532 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
533 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
534 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
535 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
536 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
537 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
538 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
539 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
540 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
541 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
542 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
543 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
544 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
545 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
546 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
547 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
548 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
549 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
550 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
551 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
552 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
553 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
554 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
555 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
556 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
557 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
558 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
559 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
560 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
561 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
562 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
563 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
564 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
565 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
566 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
567 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
568 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
569 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
570 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
571 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
572 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
573 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
574 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
575 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
576 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
577 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
578 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
579 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
580 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
581 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
582 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
583 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
584 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
585 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
586 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
587 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
588 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
589 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
590 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
591 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
592 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
593 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
594 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
595 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
596 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
597 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
598 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
599 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
600 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
601 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
602 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
603 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
604 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
605 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
606 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
607 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
608 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | 0.9 | 3.28 | 11.18 | 11.85 | 11.40 | 11.54 |
Component Type | Name | Nominal Total Capacity {Btu/h} | |
1 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 24746.18 |
2 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 14283.49 |
3 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 20180.75 |
4 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 22404.18 |
5 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 11394.00 |
6 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 17233.50 |
7 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 28557.62 |
8 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 16831.36 |
9 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 23538.98 |
10 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 25684.17 |
11 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 13257.39 |
12 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 20333.44 |
13 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29363.06 |
14 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 17282.46 |
15 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 23168.74 |
16 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 27468.14 |
17 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 15157.30 |
18 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 20049.80 |
19 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNITHEATEDBSMT | 24142.97 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 01/21 | 01/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 6 |
2 | 6 |
3 | 6 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | -43.4 | 0.00 | DefaultMultipliers | Wetbulb | -41.90 | {C} | 14. | 20 | 59.1 | 0.00 | No | No |
2 | 81.32 | 10.20 | DefaultMultipliers | Wetbulb | 16.10 | {C} | 14. | 180 | 610.3 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 21 | 1229.0 | 0.1415 | 5.7310E-002 | 1.0 | -11.15 | -20. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | HEATEDBSMT | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.007262342 | 0.005029747 | Pass | Pass | 0.000358674 | 0.000250007 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000002977 | 0.000001559 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000056470 | 0.000210454 | Pass | Pass | 0.007893026 | 0.013486689 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.025940099 | 0.024669829 | Pass | Pass | 0.001907632 | 0.002156271 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.026336607 | 0.024845358 | Pass | Pass | 0.001666721 | 0.002042278 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000025322 | 0.000039950 | Pass | Pass | 0.007723829 | 0.013122644 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.027914383 | 0.026861489 | Pass | Pass | 0.002375019 | 0.002612673 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.028069696 | 0.027306527 | Pass | Pass | 0.001932305 | 0.002500468 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000003422 | 0.000005136 | Pass | Pass | 0.010134322 | 0.016972153 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000004583 | 0.000008350 | Pass | Pass | 0.016107526 | 0.025967223 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000059189 | 0.000288097 | Pass | Pass | 0.009240945 | 0.014734420 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000007681 | 0.000012081 | Pass | Pass | 0.010033237 | 0.016623107 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.025277456 | 0.022150308 | Pass | Pass | 0.002052258 | 0.002126684 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.025922910 | 0.022465641 | Pass | Pass | 0.001685401 | 0.002016028 | Pass | Pass |
15 | ATTIC | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000151083 | 0.000090579 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.025242544 | 0.023044004 | Pass | Pass | 0.001381153 | 0.001680473 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.024473285 | 0.021309498 | Pass | Pass | 0.001340385 | 0.001539347 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000007001 | 0.000009976 | Pass | Pass | 0.006627269 | 0.010416656 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.025037492 | 0.021670778 | Pass | Pass | 0.001628590 | 0.001661260 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.023961954 | 0.021072767 | Pass | Pass | 0.001508653 | 0.001621256 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000013024 | 0.000019020 | Pass | Pass | 0.006483834 | 0.010203527 | Pass | Pass |
22 | HEATEDBSMT | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.019755167 | 0.017339513 | Pass | Pass | 1.285177039 | 6.138014204 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.314976919 | 0.170368096 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000093170 | 0.000385290 | Pass | Pass | 0.129677915 | 0.085220405 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.002450371 | 0.008219383 | Pass | Pass | 0.095962697 | 0.082496412 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000088285 | 0.000390497 | Pass | Pass | 0.112031432 | 0.088613402 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000088688 | 0.000384644 | Pass | Pass | 0.120496144 | 0.090795253 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000058523 | 0.000352548 | Pass | Pass | 0.077607444 | 0.087387510 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000074533 | 0.000375049 | Pass | Pass | 0.113093486 | 0.097938134 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000098954 | 0.000399489 | Pass | Pass | 0.095372792 | 0.057599707 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.001418909 | 0.005575826 | Pass | Pass | 0.067650548 | 0.053856163 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000093401 | 0.000395831 | Pass | Pass | 0.082360032 | 0.058488695 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000087921 | 0.000384400 | Pass | Pass | 0.085267164 | 0.063304525 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000066223 | 0.000367711 | Pass | Pass | 0.050555591 | 0.056099535 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000091527 | 0.000393331 | Pass | Pass | 0.081767561 | 0.063837767 | Pass | Pass |
36 | ATTIC | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.468463086 | 0.284352656 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000073690 | 0.000366347 | Pass | Pass | 0.076939843 | 0.064046514 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000093882 | 0.000391697 | Pass | Pass | 0.079467437 | 0.058750745 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000100666 | 0.000403221 | Pass | Pass | 0.097328699 | 0.056907683 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000066783 | 0.000363429 | Pass | Pass | 0.056094877 | 0.052152915 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.001128189 | 0.004265516 | Pass | Pass | 0.069440447 | 0.054636257 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000089576 | 0.000387488 | Pass | Pass | 0.087764622 | 0.060948647 | Pass | Pass |
43 | HEATEDBSMT | RunPeriod: ANNUAL | 0.004850476 | 0.003846549 | Pass | Pass | 0.001273651 | 0.001075589 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.032930703 | 0.022659416 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000004551 | 0.000005953 | Pass | Pass | 0.020275001 | 0.029031439 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000009304 | 0.000013277 | Pass | Pass | 0.028937358 | 0.045340645 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000006124 | 0.000007888 | Pass | Pass | 0.021204396 | 0.030189300 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000004664 | 0.000005926 | Pass | Pass | 0.019454223 | 0.028275833 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000008074 | 0.000011813 | Pass | Pass | 0.027783683 | 0.044481187 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000004029 | 0.000004839 | Pass | Pass | 0.020207864 | 0.028502899 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000006996 | 0.000010446 | Pass | Pass | 0.022208617 | 0.036185183 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000047009 | 0.000148710 | Pass | Pass | 0.043554705 | 0.075598022 | Pass | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000003309 | 0.000004867 | Pass | Pass | 0.023112242 | 0.037341889 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000002432 | 0.000003654 | Pass | Pass | 0.021274551 | 0.035298178 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000005906 | 0.000009753 | Pass | Pass | 0.041776380 | 0.073614178 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000939 | 0.000001189 | Pass | Pass | 0.022014545 | 0.035569215 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.091534951 | 0.081815373 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000005039 | 0.000005956 | Pass | Pass | 0.015619701 | 0.021100747 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000003410 | 0.000004165 | Pass | Pass | 0.016062037 | 0.021911871 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000003191 | 0.000003880 | Pass | Pass | 0.015417394 | 0.021320128 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000009943 | 0.000013672 | Pass | Pass | 0.020093419 | 0.030843305 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000009671 | 0.000013302 | Pass | Pass | 0.020609787 | 0.031207295 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000003573 | 0.000004315 | Pass | Pass | 0.015089137 | 0.020983980 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 1419596.34 | 233607.52 | 0.00 | 0.00 | 263812.37 | 1917019.72 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -43.4 | 0.00 | -43.4 | Wetbulb [F] | 59.06 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 81.32 | 18.36 | 60.98 | Wetbulb [F] | 610.27 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.212 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.320 | 0.335 | 0.883 | ||||||||||||
North Total or Average | 531.68 | 0.320 | 0.335 | 0.883 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.320 | 0.335 | 0.883 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3333 | 43219.92 | 14404.00 | 12960.20 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1257.69 | 5508.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 416557.73 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9951.71 | 7967.89 | 1983.82 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5306.88 | 4248.98 | 1057.90 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7911.05 | 6334.02 | 1577.03 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8902.76 | 7128.04 | 1774.72 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4058.11 | 3249.15 | 808.96 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6603.22 | 5286.91 | 1316.32 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11668.65 | 9342.57 | 2326.08 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6427.99 | 5146.60 | 1281.39 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9413.83 | 7537.23 | 1876.60 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10376.22 | 8307.78 | 2068.44 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4862.74 | 3893.38 | 969.36 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7981.79 | 6390.66 | 1591.13 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12028.55 | 9630.72 | 2397.83 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6625.13 | 5304.44 | 1320.68 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9245.71 | 7402.63 | 1843.08 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11175.51 | 8947.73 | 2227.78 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 5689.46 | 4555.30 | 1134.16 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7853.50 | 6287.94 | 1565.55 | 0.80 | 3.97 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 11098.30 | 8855.46 | 2242.84 | 0.80 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.9 | 3.28 | 11.18 | 11.85 | 11.40 | 11.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 25429.84 | 24746.16 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 16143.80 | 14283.50 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 21350.18 | 20180.76 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 23332.79 | 22404.19 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 13647.33 | 11393.98 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 18735.59 | 17233.50 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 28860.42 | 28557.62 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 18384.09 | 16831.36 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 24353.02 | 23538.98 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 26276.85 | 25684.17 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 15255.24 | 13257.40 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 21490.37 | 20333.43 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 29581.79 | 29363.05 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 18779.16 | 17282.46 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 24018.39 | 23168.73 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 27876.41 | 27468.15 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 16908.63 | 15157.29 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 21235.10 | 20049.79 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 24898.73 | 24142.96 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
OASUPPLYFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 373.30 | 186.95 | 0.50 | 1.00 | 1.85 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 199.07 | 99.69 | 0.50 | 1.00 | 2.67 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 296.75 | 148.61 | 0.50 | 1.00 | 2.09 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 333.95 | 167.24 | 0.50 | 1.00 | 1.96 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 152.22 | 76.23 | 0.50 | 1.00 | 3.20 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 247.69 | 124.04 | 0.50 | 1.00 | 2.32 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 437.70 | 219.20 | 0.50 | 1.00 | 1.71 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 241.12 | 120.75 | 0.50 | 1.00 | 2.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 353.12 | 176.84 | 0.50 | 1.00 | 1.91 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 389.22 | 194.92 | 0.50 | 1.00 | 1.81 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 182.41 | 91.35 | 0.50 | 1.00 | 2.82 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 299.40 | 149.94 | 0.50 | 1.00 | 2.08 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 451.20 | 225.96 | 0.50 | 1.00 | 1.69 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 248.51 | 124.46 | 0.50 | 1.00 | 2.32 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 346.82 | 173.68 | 0.50 | 1.00 | 1.92 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 419.20 | 209.94 | 0.50 | 1.00 | 1.75 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 213.42 | 106.88 | 0.50 | 1.00 | 2.55 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 294.59 | 147.53 | 0.50 | 1.00 | 2.10 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.38 | 0.06 | 363.38 | 181.98 | 0.50 | 1.00 | 1.88 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 42.758279 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.59 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8641.13 | 8641.13 | 7.20 | 373.298 | 373.298 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 75.00 | 75.00 | 0.00834 | 76.00 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4608.01 | 4608.01 | 3.84 | 199.066 | 199.066 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 75.00 | 75.00 | 0.00828 | 81.32 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6869.32 | 6869.32 | 5.72 | 296.751 | 296.751 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 75.00 | 75.00 | 0.00822 | 77.40 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7730.27 | 7730.27 | 6.44 | 333.951 | 333.951 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00841 | 74.16 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3320.38 | 3320.38 | 2.77 | 143.442 | 143.442 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 75.00 | 75.00 | 0.00872 | 70.49 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5733.67 | 5733.67 | 4.78 | 247.693 | 247.693 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 75.00 | 75.00 | 0.00828 | 73.30 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10131.87 | 10131.87 | 8.44 | 437.702 | 437.702 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00835 | 74.62 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5581.46 | 5581.46 | 4.65 | 241.120 | 241.120 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 75.00 | 75.00 | 0.00828 | 80.95 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8174.19 | 8174.19 | 6.81 | 353.121 | 353.121 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 75.00 | 75.00 | 0.00822 | 78.02 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9009.63 | 9009.63 | 7.50 | 389.222 | 389.222 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 75.00 | 75.00 | 0.00837 | 72.81 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4222.30 | 4222.30 | 3.52 | 182.406 | 182.406 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 75.00 | 75.00 | 0.00864 | 69.94 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6930.71 | 6930.71 | 5.77 | 299.404 | 299.404 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 75.00 | 75.00 | 0.00825 | 74.80 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6819.34 | 6819.34 | 5.68 | 294.592 | 294.592 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.00 | 75.00 | 0.00823 | 75.26 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8028.24 | 8028.24 | 6.69 | 346.815 | 346.815 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 75.00 | 75.00 | 0.00820 | 78.32 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10444.39 | 10444.39 | 8.70 | 451.202 | 451.202 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00833 | 74.16 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4940.16 | 4940.16 | 4.11 | 213.417 | 213.417 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 75.00 | 75.00 | 0.00851 | 70.21 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5752.68 | 5752.68 | 4.79 | 248.515 | 248.515 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 75.00 | 75.00 | 0.00824 | 80.77 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9703.68 | 9703.68 | 8.08 | 419.204 | 419.204 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 75.00 | 75.00 | 0.00833 | 73.15 | 0.00700 | 44.995 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 72.85 | 75.00 | 0.00730 | 81.32 | 0.00701 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 11724.74 | 11724.74 | 9.77 | 216.788 | 216.788 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8233.94 | 8233.94 | 6.86 | 152.247 | 152.247 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00677 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11718.15 | 11718.15 | 9.76 | 216.666 | 216.666 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00695 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11726.09 | 11726.09 | 9.77 | 216.813 | 216.813 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8232.67 | 8232.67 | 6.86 | 152.224 | 152.224 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00677 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11714.32 | 11714.32 | 9.76 | 216.596 | 216.596 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00695 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9399.77 | 9399.77 | 7.83 | 173.816 | 173.816 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5688.62 | 5688.62 | 4.74 | 105.193 | 105.193 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00754 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9390.85 | 9390.85 | 7.82 | 173.651 | 173.651 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9400.90 | 9400.90 | 7.83 | 173.837 | 173.837 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5687.00 | 5687.00 | 4.74 | 105.163 | 105.163 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00754 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9386.56 | 9386.56 | 7.82 | 173.571 | 173.571 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 14487.56 | 14487.56 | 12.07 | 267.873 | 267.873 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 14492.32 | 14492.32 | 12.07 | 267.961 | 267.961 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 14503.01 | 14503.01 | 12.08 | 268.158 | 268.158 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 10774.49 | 10774.49 | 8.97 | 199.222 | 199.222 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00702 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 10777.29 | 10777.29 | 8.98 | 199.274 | 199.274 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00702 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 14502.19 | 14502.19 | 12.08 | 268.143 | 268.143 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
HEATEDBSMT | 19650.07 | 19650.07 | 2.52 | 363.378 | 363.378 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | 72.00 | 72.00 | 0.00800 | -43.4 | 0.00006 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 373.30 | 373.30 | 216.79 | 216.79 | 373.2980 | 373.2980 | 373.2980 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 199.07 | 199.07 | 152.25 | 152.25 | 199.0659 | 199.0659 | 199.0659 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 296.75 | 296.75 | 216.67 | 216.67 | 296.7508 | 296.7508 | 296.7508 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 333.95 | 333.95 | 216.81 | 216.81 | 333.9508 | 333.9508 | 333.9508 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 143.44 | 143.44 | 152.22 | 152.22 | 152.2235 | 152.2235 | 152.2235 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 247.69 | 247.69 | 216.60 | 216.60 | 247.6930 | 247.6930 | 247.6930 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 437.70 | 437.70 | 173.82 | 173.82 | 437.7020 | 437.7020 | 437.7020 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 241.12 | 241.12 | 105.19 | 105.19 | 241.1197 | 241.1197 | 241.1197 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.12 | 353.12 | 173.65 | 173.65 | 353.1214 | 353.1214 | 353.1214 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 389.22 | 389.22 | 173.84 | 173.84 | 389.2216 | 389.2216 | 389.2216 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 182.41 | 182.41 | 105.16 | 105.16 | 182.4060 | 182.4060 | 182.4060 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 299.40 | 299.40 | 173.57 | 173.57 | 299.4043 | 299.4043 | 299.4043 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 451.20 | 451.20 | 268.16 | 268.16 | 451.2019 | 451.2019 | 451.2019 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.51 | 248.51 | 199.27 | 199.27 | 248.5146 | 248.5146 | 248.5146 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 346.82 | 346.82 | 267.96 | 267.96 | 346.8151 | 346.8151 | 346.8151 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 419.20 | 419.20 | 268.14 | 268.14 | 419.2037 | 419.2037 | 419.2037 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 213.42 | 213.42 | 199.22 | 199.22 | 213.4169 | 213.4169 | 213.4169 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 294.59 | 294.59 | 267.87 | 267.87 | 294.5919 | 294.5919 | 294.5919 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.99 | 363.38 | 363.38 | 363.3783 | 363.3783 | 363.3783 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 9951.715 | 7967.893 | 373.298018 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 9711.34 | 9416.05 | 373.298018 | 76.70 | 61.25 | 0.00818042 | 53.60 | 52.02 | 0.00800000 | 76.00 | 0.00700266 | 59.13 | 12.0534 | 75.00 | 0.00831995 | 44.3995 | 8623.30 | 0.00 | 9955.87 | 7896.50 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 25429.838 | 25429.838 | 373.298018 | 0.34886909 | 338.009 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 25429.84 | 25429.84 | 373.298018 | 58.08 | 50.41 | 0.00612474 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.0534 | 71.99 | 0.00695532 | 41.1535 | 11724.74 | 0.00 | 24748.60 | 24748.60 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 5306.878 | 4248.980 | 199.065889 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 5314.45 | 5314.45 | 199.065889 | 78.01 | 61.42 | 0.00799106 | 53.60 | 52.00 | 0.00799106 | 81.32 | 0.00700714 | 61.07 | 22.6031 | 75.00 | 0.00827840 | 44.1805 | 4608.01 | 0.00 | 5309.09 | 4210.91 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 16143.795 | 16143.795 | 199.065889 | 0.22147492 | 201.032 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 16143.80 | 16143.80 | 199.065889 | 45.91 | 42.96 | 0.00525369 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 22.6031 | 71.99 | 0.00676914 | 40.0625 | 8233.94 | 0.00 | 14277.30 | 14277.30 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 7911.051 | 6334.025 | 296.750838 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 7788.90 | 7741.34 | 296.750838 | 76.94 | 61.11 | 0.00803568 | 53.60 | 52.02 | 0.00800000 | 77.40 | 0.00700385 | 59.65 | 15.1625 | 75.00 | 0.00821981 | 43.8716 | 6869.11 | 0.00 | 7914.35 | 6277.27 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 21350.177 | 21350.177 | 296.750838 | 0.29290068 | 278.147 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 21350.18 | 21350.18 | 296.750838 | 54.49 | 48.40 | 0.00591007 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.1625 | 71.99 | 0.00695482 | 41.1506 | 11718.15 | 0.00 | 20180.32 | 20180.32 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 8902.761 | 7128.043 | 333.950793 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8609.28 | 8294.65 | 333.950793 | 76.47 | 61.22 | 0.00821628 | 53.60 | 52.02 | 0.00800000 | 74.16 | 0.00700114 | 58.45 | 13.4735 | 75.00 | 0.00840549 | 44.8502 | 7730.27 | 0.00 | 8906.48 | 7064.18 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 23332.787 | 23332.787 | 333.950793 | 0.32009989 | 307.296 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 23332.79 | 23332.79 | 333.950793 | 56.44 | 49.50 | 0.00602697 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.4735 | 71.99 | 0.00695542 | 41.1541 | 11726.09 | 0.00 | 22405.19 | 22405.19 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 4058.112 | 3249.148 | 152.223513 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 3876.64 | 3751.58 | 152.223513 | 75.16 | 60.70 | 0.00818050 | 53.60 | 52.02 | 0.00800000 | 70.49 | 0.00699811 | 57.06 | 29.5585 | 75.00 | 0.00873132 | 46.5646 | 3307.55 | 0.00 | 4059.80 | 3220.04 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 13647.332 | 13647.332 | 152.223513 | 0.18722621 | 163.379 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 13647.33 | 13647.33 | 152.223513 | 37.88 | 37.72 | 0.00478724 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 29.5585 | 71.99 | 0.00676899 | 40.0616 | 8232.67 | 0.00 | 11385.17 | 11385.17 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 6603.223 | 5286.905 | 247.692987 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 6383.48 | 6334.77 | 247.692987 | 76.27 | 60.88 | 0.00804351 | 53.60 | 52.02 | 0.00800000 | 73.30 | 0.00700043 | 58.13 | 18.1656 | 75.00 | 0.00825758 | 44.0705 | 5687.00 | 0.00 | 6605.98 | 5239.54 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 18735.588 | 18735.588 | 247.692987 | 0.25703143 | 239.569 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 18735.59 | 18735.59 | 247.692987 | 51.03 | 46.38 | 0.00570291 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 18.1656 | 71.99 | 0.00695453 | 41.1489 | 11714.32 | 0.00 | 17230.98 | 17230.98 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11668.654 | 9342.569 | 437.701981 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 11307.46 | 10900.64 | 437.701981 | 76.54 | 61.24 | 0.00821340 | 53.60 | 52.02 | 0.00800000 | 74.62 | 0.00700152 | 58.62 | 10.2798 | 75.00 | 0.00834076 | 44.5094 | 10103.36 | 0.00 | 11673.52 | 9258.86 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 28860.423 | 28860.423 | 437.701981 | 0.39593291 | 387.957 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 28860.42 | 28860.42 | 437.701981 | 60.13 | 52.47 | 0.00675270 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.2798 | 72.00 | 0.00751902 | 44.4422 | 9399.77 | 0.00 | 28570.11 | 28570.11 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6427.985 | 5146.600 | 241.119662 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 6427.14 | 6382.55 | 241.119662 | 77.69 | 61.38 | 0.00804172 | 53.60 | 52.02 | 0.00800000 | 80.95 | 0.00700683 | 60.93 | 18.6609 | 75.00 | 0.00827860 | 44.1817 | 5579.33 | 0.00 | 6430.67 | 5100.49 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 18384.091 | 18384.091 | 241.119662 | 0.25220929 | 234.257 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 18384.09 | 18384.09 | 241.119662 | 50.46 | 47.03 | 0.00614691 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 18.6609 | 72.00 | 0.00754234 | 44.5769 | 5688.62 | 0.00 | 16833.38 | 16833.38 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 9413.827 | 7537.230 | 353.121365 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 9291.96 | 9186.25 | 353.121365 | 76.96 | 61.17 | 0.00806687 | 53.60 | 52.02 | 0.00800000 | 78.02 | 0.00700436 | 59.88 | 12.7421 | 75.00 | 0.00822240 | 43.8853 | 8166.82 | 0.00 | 9417.76 | 7469.70 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 24353.019 | 24353.019 | 353.121365 | 0.33409634 | 322.111 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 24353.02 | 24353.02 | 353.121365 | 57.29 | 50.92 | 0.00656880 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.7421 | 72.00 | 0.00751860 | 44.4398 | 9390.85 | 0.00 | 23547.18 | 23547.18 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 10376.220 | 8307.775 | 389.221614 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 9973.47 | 9620.80 | 389.221614 | 76.33 | 61.16 | 0.00820788 | 53.60 | 52.02 | 0.00800000 | 72.81 | 0.00700003 | 57.94 | 11.5602 | 75.00 | 0.00838052 | 44.7188 | 8989.64 | 0.00 | 10380.55 | 8233.34 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 26276.845 | 26276.845 | 389.221614 | 0.36048910 | 350.247 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 26276.85 | 26276.85 | 389.221614 | 58.65 | 51.67 | 0.00665730 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 11.5602 | 72.00 | 0.00751907 | 44.4425 | 9400.90 | 0.00 | 25694.24 | 25694.24 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 4862.744 | 3893.381 | 182.406011 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 4624.94 | 4435.73 | 182.406011 | 75.33 | 60.84 | 0.00823254 | 53.60 | 52.02 | 0.00800000 | 69.94 | 0.00699765 | 56.84 | 24.6675 | 75.00 | 0.00864187 | 46.0942 | 4217.91 | 0.00 | 4864.77 | 3858.50 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 15255.235 | 15255.235 | 182.406011 | 0.20928486 | 187.589 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 15255.24 | 15255.24 | 182.406011 | 43.53 | 42.75 | 0.00569766 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 24.6675 | 72.00 | 0.00754223 | 44.5762 | 5687.00 | 0.00 | 13255.29 | 13255.29 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 7981.791 | 6390.663 | 299.404350 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 7762.92 | 7676.22 | 299.404350 | 76.55 | 61.02 | 0.00806461 | 53.60 | 52.02 | 0.00800000 | 74.80 | 0.00700167 | 58.69 | 15.0282 | 75.00 | 0.00824958 | 44.0285 | 6923.58 | 0.00 | 7985.12 | 6333.41 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 21490.374 | 21490.374 | 299.404350 | 0.29482403 | 280.089 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 21490.37 | 21490.37 | 299.404350 | 54.65 | 49.43 | 0.00639822 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.0282 | 72.00 | 0.00751841 | 44.4387 | 9386.56 | 0.00 | 20338.71 | 20338.71 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 12028.548 | 9630.720 | 451.201932 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11634.41 | 11243.42 | 451.201932 | 76.49 | 61.20 | 0.00819850 | 53.60 | 52.02 | 0.00800000 | 74.16 | 0.00700114 | 58.45 | 9.9722 | 75.00 | 0.00832355 | 44.4187 | 10427.61 | 0.00 | 12033.57 | 9544.43 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 29581.790 | 29581.790 | 451.201932 | 0.40582925 | 398.585 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 29581.79 | 29581.79 | 451.201932 | 60.48 | 52.01 | 0.00642455 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 9.9722 | 71.99 | 0.00712904 | 42.1697 | 14503.01 | 0.00 | 29370.63 | 29370.63 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6625.126 | 5304.442 | 248.514601 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 6622.47 | 6602.87 | 248.514601 | 77.62 | 61.32 | 0.00801769 | 53.60 | 52.02 | 0.00800000 | 80.77 | 0.00700668 | 60.87 | 18.1056 | 75.00 | 0.00823943 | 43.9752 | 5748.72 | 0.00 | 6627.89 | 5256.92 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 18779.163 | 18779.163 | 248.514601 | 0.25762923 | 240.203 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 18779.16 | 18779.16 | 248.514601 | 51.10 | 46.53 | 0.00575684 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 18.1056 | 71.99 | 0.00701532 | 41.5032 | 10777.29 | 0.00 | 17280.49 | 17280.49 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 9245.710 | 7402.626 | 346.815118 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 9142.01 | 9068.08 | 346.815118 | 77.01 | 61.15 | 0.00804746 | 53.60 | 52.02 | 0.00800000 | 78.32 | 0.00700461 | 59.99 | 12.9738 | 75.00 | 0.00820293 | 43.7826 | 8028.24 | 0.00 | 9249.57 | 7336.30 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 24018.391 | 24018.391 | 346.815118 | 0.32950562 | 317.301 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 24018.39 | 24018.39 | 346.815118 | 57.02 | 50.12 | 0.00621202 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.9738 | 71.99 | 0.00712848 | 42.1665 | 14492.32 | 0.00 | 23172.18 | 23172.18 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 11175.510 | 8947.731 | 419.203708 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 10761.26 | 10414.54 | 419.203708 | 76.38 | 61.15 | 0.00818919 | 53.60 | 52.02 | 0.00800000 | 73.15 | 0.00700030 | 58.07 | 10.7334 | 75.00 | 0.00834079 | 44.5095 | 9691.23 | 0.00 | 11180.17 | 8867.56 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 27876.413 | 27876.413 | 419.203708 | 0.38243338 | 373.708 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 27876.41 | 27876.41 | 419.203708 | 59.61 | 51.54 | 0.00637074 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.7334 | 71.99 | 0.00712900 | 42.1695 | 14502.19 | 0.00 | 27474.51 | 27474.51 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 5689.460 | 4555.296 | 213.416904 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 5417.48 | 5237.90 | 213.416904 | 75.57 | 60.86 | 0.00818872 | 53.60 | 52.02 | 0.00800000 | 70.21 | 0.00699788 | 56.95 | 21.0831 | 75.00 | 0.00851214 | 45.4114 | 4932.43 | 0.00 | 5691.83 | 4514.48 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 16908.632 | 16908.632 | 213.416904 | 0.23196763 | 212.429 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 16908.63 | 16908.63 | 213.416904 | 47.66 | 44.46 | 0.00554970 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 21.0831 | 71.99 | 0.00701510 | 41.5020 | 10774.49 | 0.00 | 15153.57 | 15153.57 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 7853.497 | 6287.943 | 294.591914 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 7657.38 | 7605.48 | 294.591914 | 76.62 | 61.00 | 0.00803914 | 53.60 | 52.02 | 0.00800000 | 75.26 | 0.00700206 | 58.86 | 15.2737 | 75.00 | 0.00822409 | 43.8941 | 6807.08 | 0.00 | 7856.77 | 6231.61 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 21235.104 | 21235.104 | 294.591914 | 0.29132201 | 276.415 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 21235.10 | 21235.10 | 294.591914 | 54.37 | 48.62 | 0.00604934 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.2737 | 71.99 | 0.00712824 | 42.1650 | 14487.56 | 0.00 | 20050.98 | 20050.98 |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 11098.298 | 8855.462 | 363.378264 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11087.15 | 11087.15 | 363.378264 | 82.90 | 61.62 | 0.00700714 | 53.60 | 50.15 | 0.00700714 | 81.32 | 0.00700714 | 61.07 | 12.3824 | 72.85 | 0.00730186 | 41.9413 | 0.00 | 0.00 | 11102.93 | 8779.88 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 24898.731 | 24898.731 | 363.378264 | 0.34158290 | 329.975 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | 24898.73 | 24898.73 | 363.378264 | 57.71 | 51.94 | 0.00701739 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.3824 | 72.00 | 0.00800000 | 47.2448 | 19650.07 | 0.00 | 24157.37 | 24157.37 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9951.715 | 7967.893 | 373.298018 | -999. | -999.00 | -999.0000 | 1.08284 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 373.298018 | 0.46047585 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 9711.34 | 9416.05 | 1.0248 | 0.46047585 | 373.298018 | 76.70 | 61.25 | 0.00818042 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 637.860 | 9073.48 | 76.00 | 0.00700266 | 59.13 | 44.99498340 | 12.0534 | 75.00 | 0.00834183 | 75.00 | 0.00831995 | 44.3995 | 8623.30 | 0.00 | 9955.87 | 7896.50 | 0.44229054 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25429.838 | 25429.838 | 373.298018 | 0.34886909 | 338.009 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 373.298018 | 0.46047585 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 5.9843 | 6.104757 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 25429.84 | 25429.84 | 1.0000 | 0.46047585 | 373.298018 | 58.08 | 50.41 | 0.00612474 | 7.2 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.36298615 | 140.00 | 120.20 | 19.80 | 0.000 | 25429.84 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.0534 | 71.99 | 0.00695532 | 71.99 | 0.00695532 | 41.1535 | 11724.74 | 0.00 | 24748.60 | 24748.60 | 0.46047585 | 61.88 | 52.29 | 0.00612474 | 7.7 | 123.39 | 73.31 | 0.00612474 | 16.0 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5306.878 | 4248.980 | 199.065889 | -999. | -999.00 | -999.0000 | 1.03578 | 1.00000 | 0.2435 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 199.065889 | 0.24555457 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 5314.45 | 5314.45 | 0.9986 | 0.24555457 | 199.065889 | 78.01 | 61.42 | 0.00799106 | 11.0 | 53.60 | 52.00 | 0.00799106 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 340.147 | 4974.30 | 81.32 | 0.00700714 | 61.07 | 44.99498340 | 22.6031 | 75.00 | 0.00827840 | 75.00 | 0.00827840 | 44.1805 | 4608.01 | 0.00 | 5309.09 | 4210.91 | 0.23585702 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16143.795 | 16143.795 | 199.065889 | 0.22147492 | 201.032 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 199.065889 | 0.24555457 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 3.7991 | 3.875524 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 16143.80 | 16143.80 | 1.0000 | 0.24555457 | 199.065889 | 45.91 | 42.96 | 0.00525369 | 5.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.23043694 | 140.00 | 120.20 | 19.80 | 0.000 | 16143.80 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 22.6031 | 71.99 | 0.00676914 | 71.99 | 0.00676914 | 40.0625 | 8233.94 | 0.00 | 14277.30 | 14277.30 | 0.24555457 | 61.88 | 50.64 | 0.00525369 | 7.2 | 128.53 | 73.66 | 0.00525369 | 16.1 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7911.051 | 6334.025 | 296.750838 | -999. | -999.00 | -999.0000 | 1.09198 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 296.750838 | 0.36605229 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | Sensible | 7788.90 | 7741.34 | 1.0157 | 0.36605229 | 296.750838 | 76.94 | 61.11 | 0.00803568 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 507.063 | 7281.84 | 77.40 | 0.00700385 | 59.65 | 44.99498340 | 15.1625 | 75.00 | 0.00822009 | 75.00 | 0.00821981 | 43.8716 | 6869.11 | 0.00 | 7914.35 | 6277.27 | 0.35159599 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 21350.177 | 21350.177 | 296.750838 | 0.29290068 | 278.147 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 296.750838 | 0.36605229 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 5.0243 | 5.125382 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 21350.18 | 21350.18 | 1.0000 | 0.36605229 | 296.750838 | 54.49 | 48.40 | 0.00591007 | 6.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.30475296 | 140.00 | 120.20 | 19.80 | 0.000 | 21350.18 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.1625 | 71.99 | 0.00695482 | 71.99 | 0.00695482 | 41.1506 | 11718.15 | 0.00 | 20180.32 | 20180.32 | 0.36605229 | 61.88 | 51.89 | 0.00591007 | 7.6 | 125.00 | 73.49 | 0.00591007 | 16.1 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8902.761 | 7128.043 | 333.950793 | -999. | -999.00 | -999.0000 | 1.09563 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 333.950793 | 0.41193971 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8609.28 | 8294.65 | 1.0341 | 0.41193971 | 333.950793 | 76.47 | 61.22 | 0.00821628 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 570.627 | 8038.65 | 74.16 | 0.00700114 | 58.45 | 44.99498340 | 13.4735 | 75.00 | 0.00840549 | 75.00 | 0.00840549 | 44.8502 | 7730.27 | 0.00 | 8906.48 | 7064.18 | 0.39567120 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23332.787 | 23332.787 | 333.950793 | 0.32009989 | 307.296 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 333.950793 | 0.41193971 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 5.4908 | 5.601333 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 23332.79 | 23332.79 | 1.0000 | 0.41193971 | 333.950793 | 56.44 | 49.50 | 0.00602697 | 6.9 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.33305279 | 140.00 | 120.20 | 19.80 | 0.000 | 23332.79 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.4735 | 71.99 | 0.00695542 | 71.99 | 0.00695542 | 41.1541 | 11726.09 | 0.00 | 22405.19 | 22405.19 | 0.41193971 | 61.88 | 52.11 | 0.00602697 | 7.6 | 124.14 | 73.40 | 0.00602697 | 16.0 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4058.112 | 3249.148 | 152.223513 | -999. | -999.00 | -999.0000 | 1.17878 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 152.223513 | 0.18777290 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | Sensible | 3876.64 | 3751.58 | 1.0468 | 0.18777290 | 152.223513 | 75.16 | 60.70 | 0.00818050 | 10.7 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 260.107 | 3616.53 | 70.49 | 0.00699811 | 57.06 | 44.99498340 | 29.5585 | 75.00 | 0.00872091 | 75.00 | 0.00873132 | 46.5646 | 3307.55 | 0.00 | 4059.80 | 3220.04 | 0.18035729 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 13647.332 | 13647.332 | 152.223513 | 0.18722621 | 163.379 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 152.223513 | 0.18777290 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 3.2116 | 3.276216 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 13647.33 | 13647.33 | 1.0000 | 0.18777290 | 152.223513 | 37.88 | 37.72 | 0.00478724 | 3.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.19480236 | 140.00 | 120.20 | 19.80 | 0.000 | 13647.33 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 29.5585 | 71.99 | 0.00676899 | 71.99 | 0.00676899 | 40.0616 | 8232.67 | 0.00 | 11385.17 | 11385.17 | 0.18777290 | 61.88 | 49.73 | 0.00478724 | 6.9 | 131.44 | 73.89 | 0.00478724 | 16.2 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6603.223 | 5286.905 | 247.692987 | -999. | -999.00 | -999.0000 | 1.14176 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 247.692987 | 0.30553776 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | Sensible | 6383.48 | 6334.77 | 1.0344 | 0.30553776 | 247.692987 | 76.27 | 60.88 | 0.00804351 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 423.237 | 5960.24 | 73.30 | 0.00700043 | 58.13 | 44.99498340 | 18.1656 | 75.00 | 0.00827505 | 75.00 | 0.00825758 | 44.0705 | 5687.00 | 0.00 | 6605.98 | 5239.54 | 0.29347133 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 18735.588 | 18735.588 | 247.692987 | 0.25703143 | 239.569 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 247.692987 | 0.30553776 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 4.4090 | 4.497717 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 18735.59 | 18735.59 | 1.0000 | 0.30553776 | 247.692987 | 51.03 | 46.38 | 0.00570291 | 6.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.26743226 | 140.00 | 120.20 | 19.80 | 0.000 | 18735.59 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 18.1656 | 71.99 | 0.00695453 | 71.99 | 0.00695453 | 41.1489 | 11714.32 | 0.00 | 17230.98 | 17230.98 | 0.30553776 | 61.88 | 51.50 | 0.00570291 | 7.4 | 126.47 | 73.65 | 0.00570291 | 16.1 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11668.654 | 9342.569 | 437.701981 | -999. | -999.00 | -999.0000 | 1.09070 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 437.701981 | 0.53992034 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 11307.46 | 10900.64 | 1.0319 | 0.53992034 | 437.701981 | 76.54 | 61.24 | 0.00821340 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 747.908 | 10559.55 | 74.62 | 0.00700152 | 58.62 | 44.99498340 | 10.2798 | 75.00 | 0.00835225 | 75.00 | 0.00834076 | 44.5094 | 10103.36 | 0.00 | 11673.52 | 9258.86 | 0.51859757 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 28860.423 | 28860.423 | 437.701981 | 0.39593291 | 387.957 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 437.701981 | 0.53992034 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 6.7916 | 6.928313 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 28860.42 | 28860.42 | 1.0000 | 0.53992034 | 437.701981 | 60.13 | 52.47 | 0.00675270 | 7.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.41195441 | 140.00 | 120.20 | 19.80 | 0.000 | 28860.42 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.2798 | 72.00 | 0.00751902 | 72.00 | 0.00751902 | 44.4422 | 9399.77 | 0.00 | 28570.11 | 28570.11 | 0.53992034 | 61.88 | 53.45 | 0.00675270 | 8.1 | 122.37 | 73.79 | 0.00675270 | 16.2 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6427.985 | 5146.600 | 241.119662 | -999. | -999.00 | -999.0000 | 1.04243 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 241.119662 | 0.29742934 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 6427.14 | 6382.55 | 1.0001 | 0.29742934 | 241.119662 | 77.69 | 61.38 | 0.00804172 | 11.0 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 412.005 | 6015.14 | 80.95 | 0.00700683 | 60.93 | 44.99498340 | 18.6609 | 75.00 | 0.00827914 | 75.00 | 0.00827860 | 44.1817 | 5579.33 | 0.00 | 6430.67 | 5100.49 | 0.28568313 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 18384.091 | 18384.091 | 241.119662 | 0.25220929 | 234.257 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 241.119662 | 0.29742934 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 4.3263 | 4.413336 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 18384.09 | 18384.09 | 1.0000 | 0.29742934 | 241.119662 | 50.46 | 47.03 | 0.00614691 | 6.2 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.26241498 | 140.00 | 120.20 | 19.80 | 0.000 | 18384.09 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 18.6609 | 72.00 | 0.00754234 | 72.00 | 0.00754234 | 44.5769 | 5688.62 | 0.00 | 16833.38 | 16833.38 | 0.29742934 | 61.88 | 52.33 | 0.00614691 | 7.7 | 126.65 | 74.23 | 0.00614691 | 16.4 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9413.827 | 7537.230 | 353.121365 | -999. | -999.00 | -999.0000 | 1.08196 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 353.121365 | 0.43558726 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | Sensible | 9291.96 | 9186.25 | 1.0131 | 0.43558726 | 353.121365 | 76.96 | 61.17 | 0.00806687 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 603.384 | 8688.58 | 78.02 | 0.00700436 | 59.88 | 44.99498340 | 12.7421 | 75.00 | 0.00822203 | 75.00 | 0.00822240 | 43.8853 | 8166.82 | 0.00 | 9417.76 | 7469.70 | 0.41838486 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24353.019 | 24353.019 | 353.121365 | 0.33409634 | 322.111 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 353.121365 | 0.43558726 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 5.7309 | 5.846253 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 24353.02 | 24353.02 | 1.0000 | 0.43558726 | 353.121365 | 57.29 | 50.92 | 0.00656880 | 7.3 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.34761561 | 140.00 | 120.20 | 19.80 | 0.000 | 24353.02 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.7421 | 72.00 | 0.00751860 | 72.00 | 0.00751860 | 44.4398 | 9390.85 | 0.00 | 23547.18 | 23547.18 | 0.43558726 | 61.88 | 53.11 | 0.00656880 | 8.0 | 123.70 | 73.93 | 0.00656880 | 16.3 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10376.220 | 8307.775 | 389.221614 | -999. | -999.00 | -999.0000 | 1.11027 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 389.221614 | 0.48011815 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | Sensible | 9973.47 | 9620.80 | 1.0404 | 0.48011815 | 389.221614 | 76.33 | 61.16 | 0.00820788 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 665.069 | 9308.40 | 72.81 | 0.00700003 | 57.94 | 44.99498340 | 11.5602 | 75.00 | 0.00836576 | 75.00 | 0.00838052 | 44.7188 | 8989.64 | 0.00 | 10380.55 | 8233.34 | 0.46115711 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 26276.845 | 26276.845 | 389.221614 | 0.36048910 | 350.247 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 389.221614 | 0.48011815 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 6.1836 | 6.308092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 26276.85 | 26276.85 | 1.0000 | 0.48011815 | 389.221614 | 58.65 | 51.67 | 0.00665730 | 7.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.37507636 | 140.00 | 120.20 | 19.80 | 0.000 | 26276.85 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 11.5602 | 72.00 | 0.00751907 | 72.00 | 0.00751907 | 44.4425 | 9400.90 | 0.00 | 25694.24 | 25694.24 | 0.48011815 | 61.88 | 53.27 | 0.00665730 | 8.0 | 123.07 | 73.87 | 0.00665730 | 16.3 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4862.744 | 3893.381 | 182.406011 | -999. | -999.00 | -999.0000 | 1.16362 | 1.00000 | 0.2437 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 182.406011 | 0.22500404 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | Sensible | 4624.94 | 4435.73 | 1.0514 | 0.22500404 | 182.406011 | 75.33 | 60.84 | 0.00823254 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 311.680 | 4313.26 | 69.94 | 0.00699765 | 56.84 | 44.99498340 | 24.6675 | 75.00 | 0.00863690 | 75.00 | 0.00864187 | 46.0942 | 4217.91 | 0.00 | 4864.77 | 3858.50 | 0.21611808 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 15255.235 | 15255.235 | 182.406011 | 0.20928486 | 187.589 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 182.406011 | 0.22500404 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 3.5900 | 3.662214 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 15255.24 | 15255.24 | 1.0000 | 0.22500404 | 182.406011 | 43.53 | 42.75 | 0.00569766 | 5.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.21775362 | 140.00 | 120.20 | 19.80 | 0.000 | 15255.24 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 24.6675 | 72.00 | 0.00754223 | 72.00 | 0.00754223 | 44.5762 | 5687.00 | 0.00 | 13255.29 | 13255.29 | 0.22500404 | 61.88 | 51.49 | 0.00569766 | 7.4 | 129.35 | 74.42 | 0.00569766 | 16.5 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7981.791 | 6390.663 | 299.404350 | -999. | -999.00 | -999.0000 | 1.11726 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 299.404350 | 0.36932549 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | Sensible | 7762.92 | 7676.22 | 1.0282 | 0.36932549 | 299.404350 | 76.55 | 61.02 | 0.00806461 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 511.597 | 7251.33 | 74.80 | 0.00700167 | 58.69 | 44.99498340 | 15.0282 | 75.00 | 0.00825261 | 75.00 | 0.00824958 | 44.0285 | 6923.58 | 0.00 | 7985.12 | 6333.41 | 0.35473992 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 21490.374 | 21490.374 | 299.404350 | 0.29482403 | 280.089 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 299.404350 | 0.36932549 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 5.0573 | 5.159039 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 21490.37 | 21490.37 | 1.0000 | 0.36932549 | 299.404350 | 54.65 | 49.43 | 0.00639822 | 6.9 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.30675414 | 140.00 | 120.20 | 19.80 | 0.000 | 21490.37 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.0282 | 72.00 | 0.00751841 | 72.00 | 0.00751841 | 44.4387 | 9386.56 | 0.00 | 20338.71 | 20338.71 | 0.36932549 | 61.88 | 52.80 | 0.00639822 | 7.9 | 124.87 | 74.05 | 0.00639822 | 16.4 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 12028.548 | 9630.720 | 451.201932 | -999. | -999.00 | -999.0000 | 1.09775 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 451.201932 | 0.55657299 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11634.41 | 11243.42 | 1.0339 | 0.55657299 | 451.201932 | 76.49 | 61.20 | 0.00819850 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 770.976 | 10863.44 | 74.16 | 0.00700114 | 58.45 | 44.99498340 | 9.9722 | 75.00 | 0.00833113 | 75.00 | 0.00832355 | 44.4187 | 10427.61 | 0.00 | 12033.57 | 9544.43 | 0.53459256 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 29581.790 | 29581.790 | 451.201932 | 0.40582925 | 398.585 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 451.201932 | 0.55657299 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 6.9614 | 7.101486 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 29581.79 | 29581.79 | 1.0000 | 0.55657299 | 451.201932 | 60.48 | 52.01 | 0.00642455 | 7.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.42225121 | 140.00 | 120.20 | 19.80 | 0.000 | 29581.79 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 9.9722 | 71.99 | 0.00712904 | 71.99 | 0.00712904 | 42.1697 | 14503.01 | 0.00 | 29370.63 | 29370.63 | 0.55657299 | 61.88 | 52.85 | 0.00642455 | 7.9 | 122.24 | 73.36 | 0.00642455 | 16.0 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6625.126 | 5304.442 | 248.514601 | -999. | -999.00 | -999.0000 | 1.05008 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 248.514601 | 0.30655125 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 6622.47 | 6602.87 | 1.0004 | 0.30655125 | 248.514601 | 77.62 | 61.32 | 0.00801769 | 11.0 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 424.641 | 6197.83 | 80.77 | 0.00700668 | 60.87 | 44.99498340 | 18.1056 | 75.00 | 0.00824120 | 75.00 | 0.00823943 | 43.9752 | 5748.72 | 0.00 | 6627.89 | 5256.92 | 0.29444479 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 18779.163 | 18779.163 | 248.514601 | 0.25762923 | 240.203 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 248.514601 | 0.30655125 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 4.4192 | 4.508178 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 18779.16 | 18779.16 | 1.0000 | 0.30655125 | 248.514601 | 51.10 | 46.53 | 0.00575684 | 6.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.26805425 | 140.00 | 120.20 | 19.80 | 0.000 | 18779.16 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 18.1056 | 71.99 | 0.00701532 | 71.99 | 0.00701532 | 41.5032 | 10777.29 | 0.00 | 17280.49 | 17280.49 | 0.30655125 | 61.88 | 51.60 | 0.00575684 | 7.5 | 126.44 | 73.70 | 0.00575684 | 16.2 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9245.710 | 7402.626 | 346.815118 | -999. | -999.00 | -999.0000 | 1.08197 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 346.815118 | 0.42780829 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | Sensible | 9142.01 | 9068.08 | 1.0113 | 0.42780829 | 346.815118 | 77.01 | 61.15 | 0.00804746 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 592.608 | 8549.40 | 78.32 | 0.00700461 | 59.99 | 44.99498340 | 12.9738 | 75.00 | 0.00820293 | 75.00 | 0.00820293 | 43.7826 | 8028.24 | 0.00 | 9249.57 | 7336.30 | 0.41091310 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24018.391 | 24018.391 | 346.815118 | 0.32950562 | 317.301 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 346.815118 | 0.42780829 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 5.6522 | 5.765921 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 24018.39 | 24018.39 | 1.0000 | 0.42780829 | 346.815118 | 57.02 | 50.12 | 0.00621202 | 7.1 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.34283912 | 140.00 | 120.20 | 19.80 | 0.000 | 24018.39 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.9738 | 71.99 | 0.00712848 | 71.99 | 0.00712848 | 42.1665 | 14492.32 | 0.00 | 23172.18 | 23172.18 | 0.42780829 | 61.88 | 52.45 | 0.00621202 | 7.7 | 123.86 | 73.55 | 0.00621202 | 16.1 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11175.510 | 8947.731 | 419.203708 | -999. | -999.00 | -999.0000 | 1.10972 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 419.203708 | 0.51710209 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 10761.26 | 10414.54 | 1.0385 | 0.51710209 | 419.203708 | 76.38 | 61.15 | 0.00818919 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 716.300 | 10044.96 | 73.15 | 0.00700030 | 58.07 | 44.99498340 | 10.7334 | 75.00 | 0.00833215 | 75.00 | 0.00834079 | 44.5095 | 9691.23 | 0.00 | 11180.17 | 8867.56 | 0.49668046 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 27876.413 | 27876.413 | 419.203708 | 0.38243338 | 373.708 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 419.203708 | 0.51710209 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 6.5601 | 6.692089 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 27876.41 | 27876.41 | 1.0000 | 0.51710209 | 419.203708 | 59.61 | 51.54 | 0.00637074 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.39790862 | 140.00 | 120.20 | 19.80 | 0.000 | 27876.41 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.7334 | 71.99 | 0.00712900 | 71.99 | 0.00712900 | 42.1695 | 14502.19 | 0.00 | 27474.51 | 27474.51 | 0.51710209 | 61.88 | 52.75 | 0.00637074 | 7.8 | 122.66 | 73.41 | 0.00637074 | 16.0 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5689.460 | 4555.296 | 213.416904 | -999. | -999.00 | -999.0000 | 1.16051 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 213.416904 | 0.26325704 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | Sensible | 5417.48 | 5237.90 | 1.0502 | 0.26325704 | 213.416904 | 75.57 | 60.86 | 0.00818872 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 364.669 | 5052.81 | 70.21 | 0.00699788 | 56.95 | 44.99498340 | 21.0831 | 75.00 | 0.00850685 | 75.00 | 0.00851214 | 45.4114 | 4932.43 | 0.00 | 5691.83 | 4514.48 | 0.25286037 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 16908.632 | 16908.632 | 213.416904 | 0.23196763 | 212.429 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 213.416904 | 0.26325704 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 3.9791 | 4.059133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 16908.63 | 16908.63 | 1.0000 | 0.26325704 | 213.416904 | 47.66 | 44.46 | 0.00554970 | 5.4 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.24135424 | 140.00 | 120.20 | 19.80 | 0.000 | 16908.63 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 21.0831 | 71.99 | 0.00701510 | 71.99 | 0.00701510 | 41.5020 | 10774.49 | 0.00 | 15153.57 | 15153.57 | 0.26325704 | 61.88 | 51.20 | 0.00554970 | 7.3 | 127.83 | 73.83 | 0.00554970 | 16.2 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7853.497 | 6287.943 | 294.591914 | -999. | -999.00 | -999.0000 | 1.11669 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 294.591914 | 0.36338918 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 7657.38 | 7605.48 | 1.0256 | 0.36338918 | 294.591914 | 76.62 | 61.00 | 0.00803914 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 503.374 | 7154.00 | 75.26 | 0.00700206 | 58.86 | 44.99498340 | 15.2737 | 75.00 | 0.00822609 | 75.00 | 0.00822409 | 43.8941 | 6807.08 | 0.00 | 7856.77 | 6231.61 | 0.34903806 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 21235.104 | 21235.104 | 294.591914 | 0.29132201 | 276.415 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 294.591914 | 0.36338918 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 4.9972 | 5.097758 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 21235.10 | 21235.10 | 1.0000 | 0.36338918 | 294.591914 | 54.37 | 48.62 | 0.00604934 | 6.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.30311041 | 140.00 | 120.20 | 19.80 | 0.000 | 21235.10 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.2737 | 71.99 | 0.00712824 | 71.99 | 0.00712824 | 42.1650 | 14487.56 | 0.00 | 20050.98 | 20050.98 | 0.36338918 | 61.88 | 52.15 | 0.00604934 | 7.6 | 125.04 | 73.67 | 0.00604934 | 16.2 | |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11098.298 | 8855.462 | 363.378264 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0740 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 363.378264 | 0.44823950 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11087.15 | 11087.15 | 1.0010 | 0.44823950 | 363.378264 | 82.90 | 61.62 | 0.00700714 | 11.1 | 53.60 | 50.15 | 0.00700714 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 620.910 | 10466.24 | 81.32 | 0.00700714 | 61.07 | 44.99498340 | 12.3824 | 75.00 | 0.00730186 | 72.85 | 0.00730186 | 41.9413 | 0.00 | 0.00 | 11102.93 | 8779.88 | 0.43053742 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.82 | 56.79 | 0.00981775 | 9.2 | |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24898.731 | 24898.731 | 363.378264 | 0.34158290 | 329.975 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 363.378264 | 0.44823950 | 1.0027 | 62.4216 | 5.94595556 | 159.80 | 179.60 | 19.80 | 424941.12 | 5.8593 | 5.977258 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:50:00 | Sensible | 24898.73 | 24898.73 | 1.0000 | 0.44823950 | 363.378264 | 57.71 | 51.94 | 0.00701739 | 7.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | 0.35540512 | 140.00 | 120.20 | 19.80 | 0.000 | 24898.73 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.3824 | 72.00 | 0.00800000 | 72.00 | 0.00800000 | 47.2448 | 19650.07 | 0.00 | 24157.37 | 24157.37 | 0.44823950 | 61.88 | 53.93 | 0.00701739 | 8.2 | 123.46 | 74.40 | 0.00701739 | 16.5 |
Report: System Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2835.67 | 7418.00 | 2447.67 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1065.67 | 7573.33 | 956.67 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2806.50 | 7203.33 | 2381.83 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3075.50 | 7683.00 | 2877.83 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1252.17 | 7883.17 | 1228.83 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2865.33 | 7454.33 | 2645.67 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2958.50 | 6852.67 | 2301.33 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 970.67 | 6801.67 | 589.17 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3013.83 | 6545.00 | 2234.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3172.50 | 7103.67 | 2759.83 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 942.67 | 7101.17 | 837.33 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3036.00 | 6879.83 | 2515.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3857.17 | 6971.17 | 3281.83 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3766.67 | 6742.17 | 3009.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3747.67 | 7014.17 | 3115.50 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2666.00 | 7203.00 | 2477.50 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2534.83 | 7018.50 | 2121.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3926.50 | 7192.50 | 3473.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4583.83 | 8028.17 | 3565.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2.00 | 0.00 | 2.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 88.00 | 0.00 | 88.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 253.50 | 0.00 | 253.50 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 349.50 | 0.00 | 349.50 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 219.50 | 0.00 | 219.50 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 630.50 | 0.00 | 630.50 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 61.83 | 0.00 | 61.83 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 74.00 | 0.00 | 74.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 307.00 | 0.00 | 307.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 390.83 | 0.00 | 390.83 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 105.33 | 0.00 | 105.33 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 282.83 | 0.00 | 282.83 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 243.33 | 0.00 | 243.33 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 200.17 | 0.00 | 200.17 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 228.50 | 0.00 | 228.50 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 108.33 | 0.00 | 108.33 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 63.17 | 0.00 | 63.17 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 302.83 | 0.00 | 302.83 | 0.00 |
HEATEDBSMT | 3282.83 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4261.83 | 0.00 | 1883.67 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.044 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.044 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.137 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.261 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.261 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.261 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.261 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.261 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.261 | 0.000 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 58539.52 | 7794.39 | 0.0000 | 0.000 | |
Total Facility | 24.79 | 36.00 | 242278.90 | 29404.35 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12126909.40 | 35911991.09 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10682694.67 | 34467776.36 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12136634.17 | 35921715.86 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12106347.90 | 35891429.59 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10665418.45 | 34450500.14 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12113949.64 | 35899031.32 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5323824.45 | 29108906.14 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3875363.70 | 27660445.39 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5327866.58 | 29112948.27 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5314241.86 | 29099323.55 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3868871.55 | 27653953.24 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5321464.03 | 29106545.72 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12144293.75 | 35929375.44 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12159455.96 | 35944537.65 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12145641.54 | 35930723.23 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10690681.22 | 34475762.91 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10705775.84 | 34490857.53 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12132234.26 | 35917315.95 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
HEATEDBSMT | 23785081.69 | 0.00 | 23785081.69 | 0.00 | 23785081.69 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Total Facility | 0.451917E+09 | 0.00 | 0.451917E+09 | 0.168842E+09 | 0.620758E+09 | 0.451917E+09 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9409 | 67.9358 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.2088 | 65.2038 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9593 | 67.9542 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9020 | 67.8969 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.1761 | 65.1711 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9163 | 67.9113 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0712 | 55.0662 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.3311 | 52.3261 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0789 | 55.0739 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0531 | 55.0481 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.3189 | 52.3138 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0668 | 55.0618 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9737 | 67.9687 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 23.0024 | 67.9974 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9763 | 67.9713 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.2239 | 65.2189 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.2525 | 65.2474 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9509 | 67.9459 | 44.9950 | 0.00 | 8808.00 | 0.00 |
Total Facility | 809.9097 | 0.0000 | 809.9097 | 319.4031 | 1129.3128 | 809.9097 | 0.00 | 8808.00 | 0.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 2039 |
Defaulted Fields | 1583 |
Fields with Defaults | 6565 |
Autosized Fields | 380 |
Autosizable Fields | 644 |
Autocalculated Fields | 162 |
Autocalculatable Fields | 350 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
Electricity:Building | 100764.00 | 6307.12 | 02-JAN-03:10 | 19198.06 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 87803.80 | 5989.14 | 02-JAN-04:10 | 15388.75 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:10 | 880.12 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:10 | 381.47 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
Fans:Electricity | 14647.09 | 610.71 | 11-SEP-16:20 | 3214.32 | 12-JAN-10:00 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
ElectricityPurchased:Plant | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
Cogeneration:ElectricityPurchased | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
ElectricityNet:Plant | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
Cogeneration:ElectricityNet | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
General:Cogeneration:ElectricityNet | 126006.35 | 8225.31 | 17-JUN-04:00 | 30834.40 | 29-JUL-18:10 |
Electricity:HVAC | 19733.64 | 610.71 | 11-SEP-16:20 | 10981.70 | 29-JUL-16:10 |
HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Fans:Electricity | 9297.23 | 0.00 | 11-SEP-16:20 | 2603.60 | 12-JAN-10:00 |
Ventilation:Fans:Electricity | 5349.86 | 610.71 | 01-JAN-00:10 | 610.71 | 01-JAN-00:10 |
ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 5086.56 | 0.00 | 01-JAN-00:10 | 8109.99 | 29-JUL-16:10 |
General:Cooling:Electricity | 5086.56 | 0.00 | 01-JAN-00:10 | 8109.99 | 29-JUL-16:10 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 11566.69 | 0.00 | 20-APR-15:50 | 523835.57 | 11-JAN-11:00 |
NaturalGas:Plant | 11566.69 | 0.00 | 20-APR-15:50 | 523835.57 | 11-JAN-11:00 |
Heating:NaturalGas | 8264.35 | 0.00 | 06-APR-18:20 | 334163.43 | 12-JAN-10:00 |
Boiler:Heating:NaturalGas | 8264.35 | 0.00 | 06-APR-18:20 | 334163.43 | 12-JAN-10:00 |
WaterSystems:NaturalGas | 3302.35 | 0.00 | 01-JAN-00:10 | 227018.88 | 07-JAN-09:00 |
Water Heater:WaterSystems:NaturalGas | 3302.35 | 0.00 | 01-JAN-00:10 | 227018.88 | 07-JAN-09:00 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2140399.85 | 17003.22 | 26-JUN-03:00 | 755316.57 | 12-JAN-10:00 |
EnergyTransfer:Building | 539543.02 | 9135.00 | 01-OCT-13:20 | 180197.24 | 12-JAN-10:40 |
EnergyTransfer:Zone:HEATEDBSMT | 69822.82 | 0.03 | 26-JUN-19:40 | 16176.90 | 18-JAN-10:20 |
Heating:EnergyTransfer | 408778.54 | 0.00 | 06-APR-18:20 | 180197.24 | 12-JAN-10:40 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 69215.59 | 0.00 | 22-MAR-10:40 | 16176.90 | 18-JAN-10:20 |
General:Heating:EnergyTransfer | 408778.54 | 0.00 | 06-APR-18:20 | 180197.24 | 12-JAN-10:40 |
Cooling:EnergyTransfer | 130764.48 | 0.00 | 01-JAN-00:10 | 101237.50 | 11-JUL-18:10 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 607.23 | 0.00 | 01-JAN-00:10 | 1486.14 | 31-AUG-07:20 |
General:Cooling:EnergyTransfer | 130764.48 | 0.00 | 01-JAN-00:10 | 101237.50 | 11-JUL-18:10 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27237.29 | 1.71 | 19-SEP-06:30 | 11155.63 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 20791.78 | 0.00 | 06-MAR-15:30 | 11155.63 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6445.50 | 0.00 | 01-JAN-00:10 | 7866.21 | 06-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18476.26 | 0.29 | 02-OCT-18:00 | 7700.15 | 12-JAN-10:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12804.31 | 0.00 | 09-FEB-12:40 | 7700.15 | 12-JAN-10:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5671.95 | 0.00 | 01-JAN-00:10 | 4399.77 | 23-JUL-14:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27900.32 | 1.07 | 11-SEP-12:10 | 9458.76 | 13-JAN-10:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20479.51 | 0.00 | 09-FEB-12:40 | 9458.76 | 13-JAN-10:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7420.81 | 0.00 | 01-JAN-00:10 | 7176.57 | 22-JUL-10:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 27812.61 | 0.22 | 05-SEP-10:20 | 11344.95 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22721.78 | 0.00 | 06-MAR-14:30 | 11344.95 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5090.83 | 0.00 | 01-JAN-00:10 | 7038.59 | 11-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 18442.04 | 1.10 | 05-MAY-04:50 | 6215.32 | 13-JAN-16:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 14435.90 | 0.00 | 19-MAR-13:20 | 6215.32 | 13-JAN-16:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4006.14 | 0.00 | 01-JAN-00:10 | 3177.62 | 11-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 27209.63 | 0.51 | 08-MAY-05:30 | 7665.89 | 28-JAN-15:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21675.28 | 0.00 | 19-MAR-14:10 | 7665.89 | 28-JAN-15:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5534.35 | 0.00 | 01-JAN-00:10 | 6548.53 | 07-JUL-07:50 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 24946.16 | 1.68 | 10-MAY-04:40 | 9226.13 | 06-JUL-18:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15503.99 | 0.00 | 09-FEB-13:30 | 8643.23 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9442.17 | 0.00 | 01-JAN-00:10 | 9226.13 | 06-JUL-18:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16206.22 | 0.29 | 06-OCT-16:20 | 5455.00 | 22-OCT-18:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7412.46 | 0.00 | 08-FEB-21:50 | 5215.56 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8793.76 | 0.00 | 01-JAN-00:10 | 5337.34 | 23-JUL-14:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 26379.91 | 2.05 | 20-AUG-09:20 | 9100.53 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15405.66 | 0.00 | 02-FEB-19:40 | 9100.53 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10974.25 | 0.00 | 01-JAN-00:10 | 8530.65 | 22-JUL-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 24890.29 | 0.33 | 19-APR-13:40 | 12276.37 | 31-MAR-12:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 17437.23 | 0.00 | 09-FEB-12:10 | 11329.32 | 31-MAR-12:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7453.06 | 0.00 | 01-JAN-00:10 | 8223.89 | 06-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15247.35 | 0.02 | 05-OCT-18:10 | 6040.92 | 12-JAN-15:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8952.58 | 0.00 | 08-FEB-21:50 | 6040.92 | 12-JAN-15:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6294.77 | 0.00 | 01-JAN-00:10 | 4057.64 | 11-JUL-20:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25365.53 | 4.85 | 12-APR-17:00 | 8704.37 | 13-JAN-10:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 17032.98 | 0.00 | 07-FEB-18:10 | 8704.37 | 13-JAN-10:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8332.55 | 0.00 | 01-JAN-00:10 | 7856.89 | 07-JUL-08:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 34990.71 | 5.63 | 27-MAY-17:20 | 10818.23 | 13-JAN-16:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 27551.99 | 0.00 | 20-MAR-12:00 | 10818.23 | 13-JAN-16:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 7438.72 | 0.00 | 01-JAN-00:10 | 7599.31 | 07-JUL-08:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 35128.30 | 1.40 | 27-MAY-19:20 | 12058.75 | 12-JAN-10:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 25773.59 | 0.00 | 09-FEB-13:30 | 12058.75 | 12-JAN-10:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 9354.71 | 0.00 | 01-JAN-00:10 | 8349.39 | 22-JUL-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 34807.11 | 0.96 | 11-SEP-13:30 | 13234.09 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 26359.95 | 0.00 | 09-FEB-18:30 | 13234.09 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 8447.15 | 0.00 | 01-JAN-00:10 | 9351.67 | 06-JUL-18:40 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24910.02 | 1.22 | 25-JUN-07:10 | 9003.42 | 13-JAN-10:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 19414.54 | 0.00 | 18-MAR-18:40 | 9003.42 | 13-JAN-10:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5495.48 | 0.00 | 01-JAN-00:10 | 4628.35 | 11-JUL-20:40 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 24781.98 | 2.25 | 25-JUN-07:20 | 9844.90 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 17479.34 | 0.00 | 09-FEB-13:30 | 9844.90 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 7302.64 | 0.00 | 01-JAN-00:10 | 5414.00 | 23-JUL-14:40 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 34988.48 | 0.30 | 11-SEP-02:30 | 13343.65 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 28330.08 | 0.00 | 18-MAR-22:00 | 13343.65 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 6658.39 | 0.00 | 01-JAN-00:10 | 8789.61 | 06-JUL-19:30 |
EnergyTransfer:HVAC | 742821.36 | 0.00 | 22-APR-23:10 | 267943.67 | 12-JAN-10:00 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:EnergyTransfer | 661663.52 | 0.00 | 06-APR-18:20 | 267943.67 | 12-JAN-10:00 |
PlantLoopHeatingDemand:Facility | 858551.36 | 1908.67 | 04-SEP-02:10 | 308363.93 | 12-JAN-08:50 |
PlantLoopHeatingDemand:HVAC | 661663.52 | 0.00 | 06-APR-18:20 | 267943.67 | 12-JAN-10:00 |
HeatingCoils:PlantLoopHeatingDemand | 661663.52 | 0.00 | 06-APR-18:20 | 267943.67 | 12-JAN-10:00 |
CoolingCoils:EnergyTransfer | 81157.84 | 0.00 | 01-JAN-00:10 | 116757.81 | 11-JUL-18:10 |
EnergyTransfer:Plant | 858035.47 | 1908.67 | 04-SEP-02:10 | 307774.24 | 12-JAN-08:50 |
Boilers:EnergyTransfer | 661147.64 | 0.00 | 06-APR-18:20 | 267330.74 | 12-JAN-10:00 |
WaterSystems:EnergyTransfer | 196887.83 | 1908.67 | 04-SEP-02:10 | 45341.80 | 01-JAN-08:50 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 196887.83 | 1908.67 | 04-SEP-02:10 | 45341.80 | 01-JAN-08:50 |
PlantLoopHeatingDemand:Plant | 196887.83 | 1908.67 | 04-SEP-02:10 | 45341.80 | 01-JAN-08:50 |
WaterSystems:PlantLoopHeatingDemand | 196887.83 | 1908.67 | 04-SEP-02:10 | 45341.80 | 01-JAN-08:50 |
General:WaterSystems:PlantLoopHeatingDemand | 196887.83 | 1908.67 | 04-SEP-02:10 | 45341.80 | 01-JAN-08:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21.635 | -1486.18 | 35902.793 | -310.81 | 0.000 | 0.000 | 3108.518 | 2458.419 | 10401.374 | 6976.407 | 0.000 | 4.504 | 0.000 | 0.000 | -11854.79 | 0.000 | -10736.78 | -14703.84 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21.631 | -1487.35 | 27326.353 | -196.16 | 0.000 | 0.000 | 3103.983 | 2458.419 | 10401.374 | 4133.961 | 0.000 | 3.964 | 0.000 | 0.000 | -4706.21 | 0.000 | -9458.02 | -13069.79 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21.619 | -1488.53 | 35011.466 | -341.45 | 0.000 | 0.000 | 3105.906 | 2458.419 | 10401.374 | 8463.177 | 0.000 | 4.502 | 0.000 | 0.000 | -11584.05 | 0.000 | -10746.55 | -15161.42 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21.641 | -1480.38 | 37799.188 | -200.99 | 0.000 | 0.000 | 3116.897 | 2458.419 | 10401.374 | 3993.393 | 0.000 | 4.504 | 0.000 | 0.000 | -12550.11 | 0.000 | -10697.03 | -14358.31 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21.646 | -1482.03 | 29458.869 | -104.48 | 0.000 | 0.000 | 3113.599 | 2458.419 | 10401.374 | 867.015 | 0.000 | 3.967 | 0.000 | 0.000 | -5206.57 | 0.000 | -9423.03 | -12644.48 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21.637 | -1481.89 | 36669.980 | -229.53 | 0.000 | 0.000 | 3119.614 | 2458.419 | 10401.374 | 5380.636 | 0.000 | 4.505 | 0.000 | 0.000 | -12169.64 | 0.000 | -10681.32 | -14654.46 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21.635 | -1493.78 | 29756.097 | -481.23 | 0.000 | 0.000 | 3084.771 | 2458.419 | 10401.374 | 6880.315 | 0.000 | 1.950 | 0.000 | 0.000 | -12033.36 | 0.000 | -4725.89 | -12129.32 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21.635 | -1496.87 | 20857.004 | -356.89 | 0.000 | 0.000 | 3075.044 | 2458.419 | 10401.374 | 4088.084 | 0.000 | 1.418 | 0.000 | 0.000 | -4786.48 | 0.000 | -3442.52 | -10413.98 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21.619 | -1495.93 | 29032.608 | -554.60 | 0.000 | 0.000 | 3083.203 | 2458.419 | 10401.374 | 8343.286 | 0.000 | 1.949 | 0.000 | 0.000 | -11750.60 | 0.000 | -4730.48 | -12238.49 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21.639 | -1487.32 | 31805.008 | -331.67 | 0.000 | 0.000 | 3095.113 | 2458.419 | 10401.374 | 3905.727 | 0.000 | 1.950 | 0.000 | 0.000 | -12705.87 | 0.000 | -4704.88 | -12435.92 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21.644 | -1491.18 | 23193.327 | -220.77 | 0.000 | 0.000 | 3087.472 | 2458.419 | 10401.374 | 832.362 | 0.000 | 1.418 | 0.000 | 0.000 | -5281.60 | 0.000 | -3430.44 | -10726.77 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21.636 | -1492.20 | 31365.910 | -397.13 | 0.000 | 0.000 | 3091.269 | 2458.419 | 10401.374 | 5276.473 | 0.000 | 1.950 | 0.000 | 0.000 | -12349.48 | 0.000 | -4718.77 | -12861.61 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21.633 | -1488.56 | 42578.727 | -384.12 | 0.000 | 0.000 | 3098.567 | 2458.419 | 10401.374 | 5286.654 | 0.000 | 4.405 | 0.000 | 0.000 | -12274.01 | 0.000 | -10759.64 | -18328.97 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21.617 | -1492.53 | 40346.617 | -501.92 | 0.000 | 0.000 | 3090.309 | 2458.419 | 10401.374 | 8363.795 | 0.000 | 4.402 | 0.000 | 0.000 | -11672.88 | 0.000 | -10793.27 | -18270.95 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 21.633 | -1488.78 | 41099.557 | -443.97 | 0.000 | 0.000 | 3095.634 | 2458.419 | 10401.374 | 6902.523 | 0.000 | 4.405 | 0.000 | 0.000 | -11946.13 | 0.000 | -10771.21 | -18057.72 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21.640 | -1487.70 | 34462.106 | -224.89 | 0.000 | 0.000 | 3095.396 | 2458.419 | 10401.374 | 834.860 | 0.000 | 3.879 | 0.000 | 0.000 | -5245.62 | 0.000 | -9476.60 | -15990.70 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21.633 | -1492.22 | 31960.061 | -323.65 | 0.000 | 0.000 | 3085.630 | 2458.419 | 10401.374 | 4096.123 | 0.000 | 3.878 | 0.000 | 0.000 | -4748.06 | 0.000 | -9503.52 | -15970.47 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 21.636 | -1485.04 | 43465.703 | -331.72 | 0.000 | 0.000 | 3100.660 | 2458.419 | 10401.374 | 3910.429 | 0.000 | 4.405 | 0.000 | 0.000 | -12634.29 | 0.000 | -10746.35 | -18166.25 |
HEATEDBSMT | 42.992 | -1443.88 | 85903.469 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -68608.35 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28075.426 | 71329.369 | 0.000 | 0.000 | 0.000 | -99404.79 | -3.62 |
Total Facility | 432.401 | -28242.35 | 687994.844 | -5936.00 | 0.000 | 0.000 | 55751.585 | 44251.534 | 187224.736 | 88535.222 | 0.000 | 28137.381 | 71329.369 | 0.000 | -175499.76 | 0.000 | -248951.11 | -328795.43 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 06-JUL-18:10 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.73 | 722.08 | 1713.00 | 6868.67 | 0.00 | 10.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1875.0 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23-JUL-14:00 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 103.15 | 1099.93 | 4196.20 | 0.00 | 15.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1130.3 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22-JUL-10:10 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 103.15 | 1108.25 | 8759.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25.0 | -2883.7 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11-JUL-18:10 | 0.00 | 0.02 | 0.00 | -0.6 | 0.00 | 0.00 | 426.74 | 722.08 | 1713.00 | 6374.28 | 0.00 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2283.9 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11-JUL-20:25 | 0.00 | -0.0 | 0.00 | -0.3 | 0.00 | 0.00 | 426.74 | 800.22 | 1615.87 | 1068.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29.2 | -702.2 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 07-JUL-07:43 | 0.00 | -0.0 | 0.00 | -0.5 | 0.00 | 0.00 | 420.18 | 343.85 | 1204.45 | 7922.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74.8 | -3267.1 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 06-JUL-18:20 | 0.00 | 0.01 | 0.00 | -0.8 | 0.00 | 0.00 | 426.73 | 722.08 | 1713.00 | 6707.35 | 0.00 | 4.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -347.5 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23-JUL-14:10 | 0.00 | 0.01 | 0.00 | -0.5 | 0.00 | 0.00 | 115.09 | 103.15 | 1105.69 | 4021.28 | 0.00 | 6.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14.4 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 22-JUL-10:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 103.15 | 1108.25 | 8538.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4.8 | -1327.2 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 06-JUL-19:30 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.74 | 800.22 | 1650.38 | 5965.39 | 0.00 | 2.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -621.3 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11-JUL-20:50 | 0.00 | -0.0 | 0.00 | -0.3 | 0.00 | 0.00 | 426.76 | 800.22 | 1615.87 | 996.65 | 0.00 | 0.00 | 236.87 | 0.00 | 0.00 | 0.00 | -17.6 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 07-JUL-07:55 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 420.18 | 343.85 | 1204.45 | 7920.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31.0 | -2000.7 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 07-JUL-08:00 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 420.18 | 343.85 | 1204.45 | 7924.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71.1 | -2221.4 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 22-JUL-10:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 103.15 | 1108.25 | 8524.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11.2 | -1490.1 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 06-JUL-18:40 | 0.00 | 0.01 | 0.00 | -0.8 | 0.00 | 0.00 | 426.73 | 722.08 | 1713.00 | 6376.37 | 0.00 | 10.92 | 102.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 11-JUL-20:40 | 0.00 | -0.0 | 0.00 | -0.4 | 0.00 | 0.00 | 426.75 | 800.22 | 1615.87 | 1027.11 | 0.00 | 0.00 | 799.10 | 0.00 | 0.00 | 0.00 | -40.0 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23-JUL-14:40 | 0.00 | 0.02 | 0.00 | -0.5 | 0.00 | 0.00 | 115.09 | 103.15 | 1105.69 | 3473.40 | 0.00 | 23.57 | 592.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 06-JUL-19:30 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.73 | 800.22 | 1650.38 | 5946.39 | 0.00 | 5.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -39.2 |
HEATEDBSMT | 30-SEP-09:53 | 0.00 | -0.2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2157.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-18:10 | 0.00 | 0.39 | 0.00 | -8.8 | 0.00 | 0.00 | 7681.58 | 12997.36 | 30834.00 | 46537.91 | 0.00 | 1190.17 | 43985.30 | 0.00 | 0.00 | 0.00 | -42316.9 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.0 | 0.00 | 16332.38 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4146.8 | 0.00 | -4391.4 | -3931.5 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 26-MAR-16:43 | -2510.6 | 0.00 | 11621.05 | 0.00 | 0.00 | 0.00 | 163.81 | 385.11 | 1363.24 | 739.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1145.7 | -10616.3 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22-OCT-12:15 | -2984.4 | 0.00 | 13668.55 | 0.00 | 0.00 | 0.00 | 133.92 | 103.15 | 1107.94 | 3117.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1740.2 | -13405.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-MAR-11:43 | -2655.6 | 0.00 | 18127.45 | 0.00 | 0.00 | 0.00 | 134.12 | 103.15 | 1111.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1396.8 | 0.00 | -1713.5 | -13710.0 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 31-MAR-12:30 | -2905.2 | 0.00 | 10180.38 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1082.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -474.5 | 0.00 | -1501.6 | -6611.6 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 26-MAR-19:23 | -2881.2 | 0.00 | 11005.01 | 0.00 | 0.00 | 0.00 | 479.67 | 800.22 | 1673.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2534.1 | 0.00 | -1761.4 | -6781.6 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13-APR-08:53 | -1965.2 | 0.00 | 12706.26 | 0.00 | 0.00 | 0.00 | 225.23 | 151.29 | 1145.20 | 805.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -416.7 | -12651.9 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 22-OCT-18:45 | -2999.1 | 0.00 | 10893.44 | 0.00 | 0.00 | 0.00 | 493.89 | 722.08 | 1734.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1082.8 | 0.00 | -622.9 | -9139.3 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 08-MAR-20:22 | -2435.0 | 0.00 | 15054.33 | 0.00 | 0.00 | 0.00 | 512.59 | 800.22 | 1615.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2089.1 | 0.00 | -581.2 | -12877.8 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 31-MAR-12:20 | -2685.1 | 0.00 | 22192.64 | 0.00 | 0.00 | 0.00 | 151.94 | 103.15 | 1082.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1005.2 | 0.00 | -649.6 | -19189.9 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15-MAR-13:20 | -2901.3 | 0.00 | 11838.51 | 0.00 | 0.00 | 0.00 | 129.39 | 103.15 | 1076.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -639.3 | 0.00 | -600.3 | -9006.2 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 03-MAR-17:43 | -2989.4 | 0.00 | 13283.77 | 0.00 | 0.00 | 0.00 | 302.56 | 536.40 | 1655.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2515.3 | 0.00 | -768.6 | -9505.2 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-MAR-19:25 | -3022.2 | 0.00 | 14573.58 | 0.00 | 0.00 | 0.00 | 489.99 | 800.22 | 1673.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2678.7 | 0.00 | -1964.4 | -9871.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 01-APR-19:17 | -2477.9 | 0.00 | 14719.50 | 0.00 | 0.00 | 0.00 | 476.28 | 800.22 | 1673.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2296.0 | 0.00 | -2478.3 | -10417.2 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 27-MAR-08:36 | -2974.0 | 0.00 | 19789.73 | 0.00 | 0.00 | 0.00 | 215.03 | 151.29 | 1145.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -279.4 | 0.00 | -1833.8 | -16214.1 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 15-MAR-16:55 | -2915.9 | 0.00 | 13442.57 | 0.00 | 0.00 | 0.00 | 160.87 | 385.11 | 1343.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -908.3 | 0.00 | -1590.4 | -9917.4 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 29-MAR-10:02 | -2802.2 | 0.00 | 15085.59 | 0.00 | 0.00 | 0.00 | 130.88 | 103.15 | 1078.58 | 2687.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1370.3 | -14913.3 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 31-MAR-10:34 | -3189.4 | 0.00 | 21581.19 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1521.1 | 0.00 | -2011.4 | -16168.3 |
HEATEDBSMT | 18-JAN-10:20 | -2891.6 | 0.00 | 19069.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16177.8 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JAN-10:40 | -95583.4 | 0.00 | 275777.22 | 0.00 | 0.00 | 0.00 | 2399.78 | 1856.77 | 19414.36 | 0.00 | 0.00 | 20342.92 | 0.00 | 0.00 | -57896.7 | 0.00 | -58196.0 | -108115.0 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 373.2980 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 373.2980 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 199.0659 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 199.0659 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 296.7508 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 296.7508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 333.9508 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 333.9508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 152.2235 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 152.2235 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 247.6930 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 247.6930 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 437.7020 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 437.7020 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 241.1197 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 241.1197 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.1214 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 353.1214 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 389.2216 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 389.2216 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 182.4060 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 182.4060 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 299.4043 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 299.4043 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 451.2019 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 451.2019 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.5146 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 248.5146 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 346.8151 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 346.8151 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 419.2037 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 419.2037 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 213.4169 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 213.4169 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 294.5919 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 294.5919 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 363.3783 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 363.3783 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 373.2980 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 373.2980 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 199.0659 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 199.0659 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 296.7508 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 296.7508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 333.9508 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 333.9508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 152.2235 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 152.2235 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 247.6930 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 247.6930 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 437.7020 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 437.7020 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 241.1197 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 241.1197 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.1214 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 353.1214 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 389.2216 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 389.2216 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 182.4060 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 182.4060 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 299.4043 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 299.4043 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 451.2019 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 451.2019 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.5146 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 248.5146 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 346.8151 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 346.8151 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 419.2037 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 419.2037 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 213.4169 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 213.4169 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 294.5919 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 294.5919 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 363.3783 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 363.3783 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.0000 | 0.000000 | 7794.39 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.3864 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 373.2980 | 373.2980 | 373.2980 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 199.0659 | 199.0659 | 199.0659 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 296.7508 | 296.7508 | 296.7508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 333.9508 | 333.9508 | 333.9508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 152.2235 | 152.2235 | 152.2235 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 247.6930 | 247.6930 | 247.6930 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 437.7020 | 437.7020 | 437.7020 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 241.1197 | 241.1197 | 241.1197 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 353.1214 | 353.1214 | 353.1214 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 389.2216 | 389.2216 | 389.2216 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 182.4060 | 182.4060 | 182.4060 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 299.4043 | 299.4043 | 299.4043 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 294.5919 | 294.5919 | 294.5919 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 346.8151 | 346.8151 | 346.8151 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 451.2019 | 451.2019 | 451.2019 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 213.4169 | 213.4169 | 213.4169 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 248.5146 | 248.5146 | 248.5146 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 419.2037 | 419.2037 | 419.2037 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 363.3783 | 363.3783 | 363.3783 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 373.2980 | 373.2980 | 373.2980 | 373.2980 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 199.0659 | 199.0659 | 199.0659 | 199.0659 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 296.7508 | 296.7508 | 296.7508 | 296.7508 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 333.9508 | 333.9508 | 333.9508 | 333.9508 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 152.2235 | 152.2235 | 152.2235 | 152.2235 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 247.6930 | 247.6930 | 247.6930 | 247.6930 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 437.7020 | 437.7020 | 437.7020 | 437.7020 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 241.1197 | 241.1197 | 241.1197 | 241.1197 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.1214 | 353.1214 | 353.1214 | 353.1214 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 389.2216 | 389.2216 | 389.2216 | 389.2216 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 182.4060 | 182.4060 | 182.4060 | 182.4060 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 299.4043 | 299.4043 | 299.4043 | 299.4043 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 451.2019 | 451.2019 | 451.2019 | 451.2019 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.5146 | 248.5146 | 248.5146 | 248.5146 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 346.8151 | 346.8151 | 346.8151 | 346.8151 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 419.2037 | 419.2037 | 419.2037 | 419.2037 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 213.4169 | 213.4169 | 213.4169 | 213.4169 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 294.5919 | 294.5919 | 294.5919 | 294.5919 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 363.3783 | 363.3783 | 363.3783 | 363.3783 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 373.2980 | 373.2980 | 373.2980 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 199.0659 | 199.0659 | 199.0659 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 296.7508 | 296.7508 | 296.7508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 333.9508 | 333.9508 | 333.9508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 152.2235 | 152.2235 | 152.2235 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 247.6930 | 247.6930 | 247.6930 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 437.7020 | 437.7020 | 437.7020 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 241.1197 | 241.1197 | 241.1197 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 353.1214 | 353.1214 | 353.1214 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 389.2216 | 389.2216 | 389.2216 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 182.4060 | 182.4060 | 182.4060 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 299.4043 | 299.4043 | 299.4043 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 294.5919 | 294.5919 | 294.5919 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 346.8151 | 346.8151 | 346.8151 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 451.2019 | 451.2019 | 451.2019 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 213.4169 | 213.4169 | 213.4169 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 248.5146 | 248.5146 | 248.5146 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 419.2037 | 419.2037 | 419.2037 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 363.3783 | 363.3783 | 363.3783 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 373.2980 | 373.2980 | 373.2980 | 373.2980 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 199.0659 | 199.0659 | 199.0659 | 199.0659 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 296.7508 | 296.7508 | 296.7508 | 296.7508 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 333.9508 | 333.9508 | 333.9508 | 333.9508 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 152.2235 | 152.2235 | 152.2235 | 152.2235 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 247.6930 | 247.6930 | 247.6930 | 247.6930 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 437.7020 | 437.7020 | 437.7020 | 437.7020 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 241.1197 | 241.1197 | 241.1197 | 241.1197 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.1214 | 353.1214 | 353.1214 | 353.1214 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 389.2216 | 389.2216 | 389.2216 | 389.2216 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 182.4060 | 182.4060 | 182.4060 | 182.4060 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 299.4043 | 299.4043 | 299.4043 | 299.4043 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 451.2019 | 451.2019 | 451.2019 | 451.2019 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.5146 | 248.5146 | 248.5146 | 248.5146 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 346.8151 | 346.8151 | 346.8151 | 346.8151 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 419.2037 | 419.2037 | 419.2037 | 419.2037 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 213.4169 | 213.4169 | 213.4169 | 213.4169 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 294.5919 | 294.5919 | 294.5919 | 294.5919 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 363.3783 | 363.3783 | 363.3783 | 363.3783 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 29404.35 | 9600.87 |
Data | |
Number of hours heating loads not met | 1883.67 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 1883.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 8264.35 | 334163.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5086.56 | 8109.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 12960.20 | 4221.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 5508.71 | 1257.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 2758.31 | 880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1408.53 | 381.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 9297.23 | 2603.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 5349.86 | 610.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 3302.35 | 227018.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299798.81 | 430238.26 |
Natural Gas | 0.00 | 1156669.06 |
Additional | 0.00 | 0.00 |
Total | 299798.81 | 1586907.33 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.33 |
Space Heating | 0.00 |
Space Cooling | 0.13 |
Fans (All) | 0.38 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.25 |
Miscellaneous (All) | 3.23 |
Subtotal | 3.23 |
Natural Gas [kWh/ft2] | |
Space Heating | 6.21 |
Service Water Heating | 2.48 |
Miscellaneous (All) | 8.68 |
Subtotal | 8.68 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 2.79 |
Space Heating | 52.08 |
Space Cooling | 1.09 |
Fans (All) | 3.15 |
Service Water Heating | 20.81 |
Receptacle Equipment | 18.89 |
Miscellaneous | 1.19 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DHW_SCH | 365. | 8760. |
DISHWASHER | 2799. | 8760. |
CLOTHESWASHER | 3297. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SINKS | 4179. | 8760. |
SHOWERS | 2640. | 8760. |
BATHS | 2586. | 8760. |
DHWDIST | 4662. | 8760. |
SHADING_2012IECC | 0. | 0. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 8548.67 | 201.17 | 10.17 | 0.00 | 0.00 |
Min | 8548.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 201.17 | 10.17 | 0.00 | 0.00 |
Average | 8747.99 | 11.52 | 0.48 | 0.00 | 0.00 |
Sum | 183707.83 | 242.00 | 10.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 8609.17 | 150.83 | 0.00 | 0.00 | 0.00 |
Min | 8609.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 150.83 | 0.00 | 0.00 | 0.00 |
Average | 8752.82 | 7.18 | 0.00 | 0.00 | 0.00 |
Sum | 183809.17 | 150.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (F) | SET ≤ 12.2°C OccupantHours (F) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (F) | SET > 30°C OccupantHours (F) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:17
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 58.527 | 58.527 |
February | 0.000 | 0.000 | 671.111 | 46.488 | 46.488 |
March | 0.000 | 0.000 | 698.306 | 38.471 | 38.471 |
April | 79.000 | 3.279 | 433.863 | 18.163 | 21.277 |
May | 235.167 | 11.284 | 198.083 | 4.917 | 16.310 |
June | 405.361 | 23.815 | 17.611 | 0.386 | 24.290 |
July | 432.250 | 26.593 | 12.472 | 0.257 | 26.928 |
August | 333.806 | 17.405 | 56.819 | 1.461 | 19.178 |
September | 74.333 | 2.476 | 354.361 | 9.980 | 13.193 |
October | 1.833 | 0.028 | 677.738 | 29.270 | 29.360 |
November | 0.000 | 0.000 | 720.000 | 53.165 | 53.165 |
December | 0.000 | 0.000 | 744.000 | 61.734 | 61.734 |
Annual Sum or Average | 1561.750 | 84.880 | 5328.364 | 322.820 | 408.922 |
Minimum of Months | 0.000 | 0.000 | 12.472 | 0.257 | 13.193 |
Maximum of Months | 432.250 | 26.593 | 744.000 | 61.734 | 61.734 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 33.837 | 33.837 |
February | 0.000 | 0.000 | 667.528 | 25.970 | 26.014 |
March | 0.000 | 0.000 | 669.650 | 20.569 | 22.226 |
April | 35.889 | 0.562 | 385.833 | 9.246 | 14.208 |
May | 215.444 | 5.762 | 110.097 | 1.959 | 9.965 |
June | 419.083 | 14.872 | 6.667 | 0.086 | 15.265 |
July | 458.028 | 18.651 | 3.583 | 0.041 | 18.966 |
August | 352.611 | 12.389 | 25.951 | 0.441 | 13.491 |
September | 80.583 | 1.358 | 224.703 | 3.970 | 8.033 |
October | 2.208 | 0.020 | 603.944 | 14.006 | 14.984 |
November | 0.000 | 0.000 | 720.000 | 29.832 | 29.832 |
December | 0.000 | 0.000 | 744.000 | 36.076 | 36.076 |
Annual Sum or Average | 1563.847 | 53.614 | 4905.957 | 176.032 | 242.896 |
Minimum of Months | 0.000 | 0.000 | 3.583 | 0.041 | 8.033 |
Maximum of Months | 458.028 | 18.651 | 744.000 | 36.076 | 36.076 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 72.166 | 72.166 |
February | 0.000 | 0.000 | 667.417 | 56.859 | 57.194 |
March | 0.000 | 0.000 | 657.931 | 45.128 | 48.752 |
April | 64.631 | 1.418 | 354.761 | 20.499 | 31.517 |
May | 311.125 | 13.539 | 83.306 | 3.667 | 26.941 |
June | 485.556 | 25.349 | 6.333 | 0.197 | 26.499 |
July | 494.681 | 30.541 | 3.250 | 0.091 | 32.242 |
August | 382.439 | 18.666 | 17.750 | 0.840 | 23.308 |
September | 95.344 | 2.268 | 218.736 | 9.617 | 28.918 |
October | 4.222 | 0.055 | 596.056 | 34.248 | 42.646 |
November | 0.000 | 0.000 | 720.000 | 66.121 | 66.121 |
December | 0.000 | 0.000 | 744.000 | 76.720 | 76.720 |
Annual Sum or Average | 1837.998 | 91.836 | 4813.539 | 386.155 | 533.024 |
Minimum of Months | 0.000 | 0.000 | 3.250 | 0.091 | 23.308 |
Maximum of Months | 494.681 | 30.541 | 744.000 | 76.720 | 76.720 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 62.410 | 62.410 |
February | 0.000 | 0.000 | 669.500 | 51.810 | 52.186 |
March | 0.000 | 0.000 | 676.131 | 45.095 | 54.100 |
April | 21.500 | 0.707 | 413.575 | 21.116 | 45.273 |
May | 150.833 | 5.673 | 142.458 | 4.736 | 23.821 |
June | 404.708 | 18.478 | 8.194 | 0.227 | 19.616 |
July | 433.361 | 20.465 | 7.250 | 0.158 | 21.417 |
August | 269.306 | 10.330 | 40.158 | 1.400 | 19.006 |
September | 19.500 | 0.353 | 310.870 | 11.072 | 34.688 |
October | 0.000 | 0.000 | 642.216 | 32.944 | 43.550 |
November | 0.000 | 0.000 | 720.000 | 57.367 | 57.367 |
December | 0.000 | 0.000 | 744.000 | 64.953 | 64.953 |
Annual Sum or Average | 1299.208 | 56.007 | 5118.352 | 353.289 | 498.388 |
Minimum of Months | 0.000 | 0.000 | 7.250 | 0.158 | 19.006 |
Maximum of Months | 433.361 | 20.465 | 744.000 | 64.953 | 64.953 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 35.408 | 35.408 |
February | 0.000 | 0.000 | 671.500 | 29.566 | 29.591 |
March | 0.000 | 0.000 | 720.656 | 25.281 | 26.083 |
April | 0.000 | 0.000 | 512.942 | 12.906 | 19.928 |
May | 94.083 | 1.327 | 116.403 | 1.954 | 5.544 |
June | 410.250 | 9.694 | 5.250 | 0.060 | 9.925 |
July | 461.750 | 12.653 | 3.167 | 0.031 | 12.837 |
August | 274.486 | 5.780 | 39.360 | 0.630 | 7.238 |
September | 0.667 | 0.001 | 302.525 | 5.312 | 8.096 |
October | 0.000 | 0.000 | 652.633 | 16.247 | 17.273 |
November | 0.000 | 0.000 | 720.000 | 32.553 | 32.553 |
December | 0.000 | 0.000 | 744.000 | 37.905 | 37.905 |
Annual Sum or Average | 1241.236 | 29.456 | 5232.435 | 197.853 | 242.380 |
Minimum of Months | 0.000 | 0.000 | 3.167 | 0.031 | 5.544 |
Maximum of Months | 461.750 | 12.653 | 744.000 | 37.905 | 37.905 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 74.293 | 74.293 |
February | 0.000 | 0.000 | 671.750 | 62.232 | 62.253 |
March | 0.000 | 0.000 | 724.406 | 53.520 | 54.595 |
April | 1.833 | 0.012 | 484.225 | 27.437 | 33.815 |
May | 243.750 | 6.775 | 87.778 | 4.047 | 19.357 |
June | 500.083 | 20.235 | 5.667 | 0.191 | 21.253 |
July | 498.444 | 24.508 | 2.833 | 0.092 | 26.006 |
August | 331.750 | 11.189 | 21.389 | 1.059 | 16.327 |
September | 5.111 | 0.049 | 279.839 | 12.455 | 26.683 |
October | 0.000 | 0.000 | 652.992 | 39.626 | 44.874 |
November | 0.000 | 0.000 | 720.000 | 70.348 | 70.348 |
December | 0.000 | 0.000 | 744.000 | 78.748 | 78.748 |
Annual Sum or Average | 1580.972 | 62.767 | 5138.878 | 424.047 | 528.551 |
Minimum of Months | 0.000 | 0.000 | 2.833 | 0.092 | 16.327 |
Maximum of Months | 500.083 | 24.508 | 744.000 | 78.748 | 78.748 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 72.447 | 72.447 |
February | 0.000 | 0.000 | 666.944 | 56.325 | 56.343 |
March | 0.000 | 0.000 | 641.739 | 44.232 | 44.752 |
April | 143.688 | 7.386 | 300.365 | 17.060 | 30.875 |
May | 327.750 | 18.500 | 52.569 | 2.108 | 29.045 |
June | 534.250 | 35.447 | 0.667 | 0.015 | 36.046 |
July | 573.611 | 38.660 | 0.667 | 0.017 | 38.860 |
August | 440.528 | 26.304 | 14.097 | 0.595 | 30.116 |
September | 115.976 | 4.296 | 219.481 | 9.069 | 23.146 |
October | 4.750 | 0.068 | 609.552 | 35.291 | 37.413 |
November | 0.000 | 0.000 | 720.000 | 66.886 | 66.886 |
December | 0.000 | 0.000 | 744.000 | 77.361 | 77.361 |
Annual Sum or Average | 2140.554 | 130.661 | 4714.080 | 381.404 | 543.290 |
Minimum of Months | 0.000 | 0.000 | 0.667 | 0.015 | 23.146 |
Maximum of Months | 573.611 | 38.660 | 744.000 | 77.361 | 77.361 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.167 | 24.984 | 24.984 |
February | 0.000 | 0.000 | 633.778 | 18.984 | 19.172 |
March | 0.000 | 0.000 | 571.158 | 14.389 | 17.410 |
April | 122.387 | 3.053 | 251.778 | 5.487 | 12.403 |
May | 356.750 | 12.354 | 27.681 | 0.458 | 13.550 |
June | 586.750 | 25.762 | 0.000 | 0.000 | 25.762 |
July | 634.861 | 30.374 | 0.000 | 0.000 | 30.374 |
August | 509.417 | 21.440 | 8.228 | 0.157 | 21.775 |
September | 133.329 | 3.313 | 123.154 | 2.241 | 7.833 |
October | 8.667 | 0.115 | 510.319 | 10.754 | 13.017 |
November | 0.000 | 0.000 | 718.500 | 22.802 | 22.802 |
December | 0.000 | 0.000 | 741.750 | 27.061 | 27.061 |
Annual Sum or Average | 2352.161 | 96.412 | 4329.513 | 127.317 | 236.145 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 7.833 |
Maximum of Months | 634.861 | 30.374 | 743.167 | 27.061 | 30.374 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.083 | 62.408 | 62.555 |
February | 0.000 | 0.000 | 633.139 | 47.597 | 50.992 |
March | 2.167 | 0.013 | 555.044 | 34.844 | 44.930 |
April | 149.427 | 5.518 | 235.094 | 13.179 | 35.277 |
May | 427.264 | 23.920 | 23.042 | 1.022 | 33.787 |
June | 601.806 | 39.288 | 0.000 | 0.000 | 39.450 |
July | 616.639 | 44.526 | 0.000 | 0.000 | 44.644 |
August | 515.951 | 29.558 | 5.944 | 0.315 | 32.197 |
September | 139.258 | 4.772 | 119.750 | 5.686 | 34.338 |
October | 8.071 | 0.182 | 505.625 | 28.096 | 46.578 |
November | 0.000 | 0.000 | 718.500 | 57.786 | 58.017 |
December | 0.000 | 0.000 | 741.750 | 66.764 | 67.102 |
Annual Sum or Average | 2460.583 | 147.777 | 4280.972 | 317.698 | 549.867 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 32.197 |
Maximum of Months | 616.639 | 44.526 | 743.083 | 66.764 | 67.102 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.833 | 53.784 | 53.800 |
February | 0.000 | 0.000 | 649.889 | 44.189 | 47.760 |
March | 0.000 | 0.000 | 600.894 | 36.425 | 57.092 |
April | 48.278 | 1.759 | 325.104 | 14.899 | 41.678 |
May | 237.583 | 10.181 | 52.917 | 1.580 | 21.404 |
June | 572.944 | 30.088 | 0.333 | 0.007 | 30.338 |
July | 592.972 | 32.199 | 0.333 | 0.006 | 32.336 |
August | 393.972 | 17.129 | 23.201 | 0.725 | 21.382 |
September | 37.083 | 0.647 | 219.116 | 7.787 | 34.552 |
October | 0.000 | 0.000 | 589.984 | 27.937 | 46.288 |
November | 0.000 | 0.000 | 719.667 | 50.439 | 50.477 |
December | 0.000 | 0.000 | 743.333 | 56.468 | 56.533 |
Annual Sum or Average | 1882.833 | 92.003 | 4668.606 | 294.245 | 493.639 |
Minimum of Months | 0.000 | 0.000 | 0.333 | 0.006 | 21.382 |
Maximum of Months | 592.972 | 32.199 | 743.833 | 56.468 | 57.092 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.333 | 26.768 | 26.776 |
February | 0.000 | 0.000 | 659.194 | 21.770 | 22.065 |
March | 0.000 | 0.000 | 670.761 | 18.534 | 20.145 |
April | 0.917 | 0.002 | 364.974 | 8.014 | 14.687 |
May | 205.167 | 4.310 | 35.333 | 0.530 | 5.661 |
June | 629.306 | 20.506 | 0.000 | 0.000 | 20.506 |
July | 648.917 | 23.814 | 0.000 | 0.000 | 23.814 |
August | 438.889 | 12.350 | 15.808 | 0.276 | 13.055 |
September | 11.250 | 0.054 | 198.690 | 3.342 | 6.397 |
October | 0.000 | 0.000 | 591.508 | 12.602 | 14.066 |
November | 0.000 | 0.000 | 719.778 | 24.728 | 24.741 |
December | 0.000 | 0.000 | 741.833 | 28.133 | 28.133 |
Annual Sum or Average | 1934.444 | 61.037 | 4741.213 | 144.695 | 220.045 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 5.661 |
Maximum of Months | 648.917 | 23.814 | 743.333 | 28.133 | 28.133 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.333 | 68.310 | 68.398 |
February | 0.000 | 0.000 | 660.500 | 55.299 | 56.638 |
March | 0.000 | 0.000 | 664.303 | 44.905 | 49.661 |
April | 18.917 | 0.273 | 330.164 | 18.953 | 30.856 |
May | 386.250 | 14.968 | 30.444 | 1.411 | 24.101 |
June | 611.861 | 33.877 | 0.000 | 0.000 | 34.002 |
July | 620.972 | 37.906 | 0.000 | 0.000 | 38.044 |
August | 471.423 | 20.032 | 8.000 | 0.467 | 22.775 |
September | 30.583 | 0.296 | 180.948 | 8.621 | 30.156 |
October | 0.000 | 0.000 | 587.855 | 34.625 | 46.545 |
November | 0.000 | 0.000 | 719.917 | 64.087 | 64.099 |
December | 0.000 | 0.000 | 741.750 | 71.878 | 72.166 |
Annual Sum or Average | 2140.006 | 107.354 | 4667.215 | 368.556 | 537.441 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 22.775 |
Maximum of Months | 620.972 | 37.906 | 743.333 | 71.878 | 72.166 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.917 | 87.620 | 87.638 |
February | 0.000 | 0.000 | 668.444 | 69.557 | 70.157 |
March | 0.000 | 0.000 | 666.400 | 56.544 | 63.777 |
April | 100.056 | 5.053 | 320.714 | 22.220 | 48.483 |
May | 285.361 | 15.860 | 78.597 | 3.505 | 37.012 |
June | 496.778 | 34.587 | 1.722 | 0.049 | 37.555 |
July | 541.361 | 38.187 | 1.417 | 0.036 | 39.880 |
August | 405.194 | 24.396 | 20.348 | 0.982 | 32.603 |
September | 82.917 | 2.879 | 254.156 | 12.742 | 41.676 |
October | 0.000 | 0.000 | 636.329 | 45.120 | 55.944 |
November | 0.000 | 0.000 | 720.000 | 81.588 | 81.588 |
December | 0.000 | 0.000 | 743.667 | 93.076 | 93.151 |
Annual Sum or Average | 1911.667 | 120.962 | 4855.711 | 473.039 | 689.466 |
Minimum of Months | 0.000 | 0.000 | 1.417 | 0.036 | 32.603 |
Maximum of Months | 541.361 | 38.187 | 743.917 | 93.076 | 93.151 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 40.061 | 40.061 |
February | 0.000 | 0.000 | 668.444 | 30.793 | 30.898 |
March | 0.000 | 0.000 | 668.533 | 24.124 | 25.931 |
April | 71.167 | 1.694 | 347.321 | 9.699 | 16.366 |
May | 291.833 | 9.850 | 72.028 | 1.369 | 12.882 |
June | 534.028 | 24.852 | 3.000 | 0.036 | 25.033 |
July | 588.861 | 29.785 | 1.583 | 0.017 | 29.864 |
August | 443.611 | 19.433 | 22.960 | 0.404 | 20.140 |
September | 94.000 | 1.944 | 246.964 | 4.857 | 10.008 |
October | 0.000 | 0.000 | 639.747 | 18.021 | 19.238 |
November | 0.000 | 0.000 | 720.000 | 36.730 | 36.730 |
December | 0.000 | 0.000 | 744.000 | 43.265 | 43.265 |
Annual Sum or Average | 2023.500 | 87.558 | 4878.580 | 209.374 | 310.416 |
Minimum of Months | 0.000 | 0.000 | 1.583 | 0.017 | 10.008 |
Maximum of Months | 588.861 | 29.785 | 744.000 | 43.265 | 43.265 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 81.024 | 81.024 |
February | 0.000 | 0.000 | 668.639 | 63.663 | 63.979 |
March | 0.000 | 0.000 | 664.769 | 49.849 | 55.029 |
April | 100.790 | 3.301 | 330.694 | 20.263 | 35.252 |
May | 382.069 | 19.824 | 54.694 | 2.441 | 31.735 |
June | 571.278 | 37.651 | 2.750 | 0.073 | 39.084 |
July | 592.639 | 43.424 | 1.417 | 0.032 | 44.425 |
August | 465.594 | 26.832 | 14.361 | 0.673 | 30.636 |
September | 106.039 | 2.995 | 238.764 | 10.820 | 32.595 |
October | 2.482 | 0.025 | 637.146 | 40.668 | 47.911 |
November | 0.000 | 0.000 | 720.000 | 75.787 | 75.787 |
December | 0.000 | 0.000 | 744.000 | 86.415 | 86.415 |
Annual Sum or Average | 2220.891 | 134.050 | 4821.235 | 431.706 | 623.872 |
Minimum of Months | 0.000 | 0.000 | 1.417 | 0.032 | 30.636 |
Maximum of Months | 592.639 | 43.424 | 744.000 | 86.415 | 86.415 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 76.685 | 76.685 |
February | 0.000 | 0.000 | 670.292 | 63.558 | 63.882 |
March | 0.000 | 0.000 | 689.011 | 54.724 | 64.673 |
April | 36.167 | 1.449 | 390.127 | 23.350 | 52.671 |
May | 207.417 | 9.610 | 102.778 | 3.679 | 27.023 |
June | 526.278 | 30.377 | 5.833 | 0.136 | 31.225 |
July | 558.167 | 33.038 | 3.417 | 0.074 | 33.567 |
August | 352.111 | 16.967 | 34.774 | 1.427 | 24.723 |
September | 20.917 | 0.394 | 338.306 | 14.091 | 43.667 |
October | 0.000 | 0.000 | 671.030 | 42.817 | 54.184 |
November | 0.000 | 0.000 | 720.000 | 72.204 | 72.204 |
December | 0.000 | 0.000 | 744.000 | 80.476 | 80.476 |
Annual Sum or Average | 1701.056 | 91.835 | 5113.568 | 433.222 | 624.981 |
Minimum of Months | 0.000 | 0.000 | 3.417 | 0.074 | 24.723 |
Maximum of Months | 558.167 | 33.038 | 744.000 | 80.476 | 80.476 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 42.144 | 42.144 |
February | 0.000 | 0.000 | 671.667 | 34.422 | 34.440 |
March | 0.000 | 0.000 | 720.750 | 28.824 | 29.496 |
April | 1.167 | 0.004 | 476.137 | 13.142 | 20.457 |
May | 171.250 | 4.245 | 81.889 | 1.448 | 7.679 |
June | 576.011 | 20.780 | 2.167 | 0.024 | 21.036 |
July | 605.806 | 24.717 | 1.500 | 0.015 | 24.777 |
August | 394.278 | 12.304 | 37.115 | 0.634 | 13.845 |
September | 3.667 | 0.015 | 353.169 | 6.535 | 9.530 |
October | 0.000 | 0.000 | 696.161 | 20.482 | 21.407 |
November | 0.000 | 0.000 | 720.000 | 39.395 | 39.395 |
December | 0.000 | 0.000 | 744.000 | 44.803 | 44.803 |
Annual Sum or Average | 1752.178 | 62.064 | 5248.554 | 231.868 | 309.009 |
Minimum of Months | 0.000 | 0.000 | 1.500 | 0.015 | 7.679 |
Maximum of Months | 605.806 | 24.717 | 744.000 | 44.803 | 44.803 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 79.441 | 79.441 |
February | 0.000 | 0.000 | 671.750 | 65.937 | 65.962 |
March | 0.000 | 0.000 | 719.044 | 55.352 | 57.125 |
April | 14.222 | 0.162 | 445.590 | 25.340 | 33.418 |
May | 343.097 | 12.585 | 63.722 | 2.703 | 22.844 |
June | 585.139 | 33.441 | 2.500 | 0.067 | 34.602 |
July | 599.639 | 38.094 | 1.583 | 0.037 | 38.955 |
August | 424.889 | 19.120 | 18.056 | 0.857 | 22.812 |
September | 13.028 | 0.103 | 318.220 | 13.608 | 28.071 |
October | 0.000 | 0.000 | 694.633 | 43.960 | 47.937 |
November | 0.000 | 0.000 | 720.000 | 76.134 | 76.134 |
December | 0.000 | 0.000 | 744.000 | 84.622 | 84.622 |
Annual Sum or Average | 1980.014 | 103.506 | 5143.099 | 448.058 | 591.925 |
Minimum of Months | 0.000 | 0.000 | 1.583 | 0.037 | 22.812 |
Maximum of Months | 599.639 | 38.094 | 744.000 | 84.622 | 84.622 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 135.392 | 135.392 |
February | 0.000 | 0.000 | 671.917 | 122.094 | 122.109 |
March | 0.000 | 0.000 | 730.753 | 129.621 | 132.032 |
April | 0.000 | 0.000 | 516.847 | 90.546 | 127.516 |
May | 0.000 | 0.000 | 495.569 | 34.838 | 79.971 |
June | 0.000 | 0.000 | 410.139 | 11.230 | 29.524 |
July | 0.000 | 0.000 | 280.819 | 7.205 | 27.225 |
August | 0.000 | 0.000 | 245.978 | 8.273 | 52.654 |
September | 0.000 | 0.000 | 430.226 | 33.343 | 83.626 |
October | 0.000 | 0.000 | 720.595 | 63.070 | 67.207 |
November | 0.000 | 0.000 | 720.000 | 120.323 | 120.323 |
December | 0.000 | 0.000 | 744.000 | 135.388 | 135.388 |
Annual Sum or Average | 0.000 | 0.000 | 6710.844 | 891.326 | 1112.968 |
Minimum of Months | 0.000 | 0.000 | 245.978 | 7.205 | 27.225 |
Maximum of Months | 0.000 | 0.000 | 744.000 | 135.392 | 135.392 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8794.56 | 0.00 | 0.00 |
February | 7614.66 | 0.00 | 0.00 |
March | 5561.20 | 0.00 | 0.00 |
April | 2441.48 | 0.00 | 0.00 |
May | 530.35 | 0.00 | 0.00 |
June | 39.10 | 0.00 | 0.00 |
July | 25.31 | 0.00 | 0.00 |
August | 158.08 | 0.00 | 0.00 |
September | 1164.39 | 0.00 | 0.00 |
October | 3930.71 | 0.00 | 0.00 |
November | 8300.88 | 0.00 | 0.00 |
December | 9307.71 | 0.00 | 0.00 |
Annual Sum or Average | 3970.22 | 0.00 | 0.00 |
Minimum of Months | 25.31 | 0.00 | 0.00 |
Maximum of Months | 9307.71 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6850.40 | 0.00 | 0.00 |
February | 5902.17 | 0.00 | 0.00 |
March | 4319.39 | 0.00 | 0.00 |
April | 1887.98 | 0.00 | 0.00 |
May | 321.92 | 0.00 | 0.00 |
June | 13.73 | 0.00 | 0.00 |
July | 6.30 | 0.00 | 0.00 |
August | 75.51 | 0.00 | 0.00 |
September | 731.64 | 0.00 | 0.00 |
October | 2879.58 | 0.00 | 0.00 |
November | 6443.12 | 0.00 | 0.00 |
December | 7269.45 | 0.00 | 0.00 |
Annual Sum or Average | 3043.71 | 0.00 | 0.00 |
Minimum of Months | 6.30 | 0.00 | 0.00 |
Maximum of Months | 7269.45 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8664.18 | 0.00 | 0.00 |
February | 7437.27 | 0.00 | 0.00 |
March | 5216.67 | 0.00 | 0.00 |
April | 2243.07 | 0.00 | 0.00 |
May | 326.49 | 0.00 | 0.00 |
June | 16.09 | 0.00 | 0.00 |
July | 7.23 | 0.00 | 0.00 |
August | 76.55 | 0.00 | 0.00 |
September | 911.58 | 0.00 | 0.00 |
October | 3704.85 | 0.00 | 0.00 |
November | 8240.17 | 0.00 | 0.00 |
December | 9232.99 | 0.00 | 0.00 |
Annual Sum or Average | 3821.01 | 0.00 | 0.00 |
Minimum of Months | 7.23 | 0.00 | 0.00 |
Maximum of Months | 9232.99 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8951.85 | 0.00 | 0.00 |
February | 8095.56 | 0.00 | 0.00 |
March | 6217.21 | 0.00 | 0.00 |
April | 2693.86 | 0.00 | 0.00 |
May | 452.78 | 0.00 | 0.00 |
June | 19.29 | 0.00 | 0.00 |
July | 14.65 | 0.00 | 0.00 |
August | 137.06 | 0.00 | 0.00 |
September | 1212.26 | 0.00 | 0.00 |
October | 4222.00 | 0.00 | 0.00 |
November | 8549.41 | 0.00 | 0.00 |
December | 9347.01 | 0.00 | 0.00 |
Annual Sum or Average | 4138.47 | 0.00 | 0.00 |
Minimum of Months | 14.65 | 0.00 | 0.00 |
Maximum of Months | 9347.01 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6914.07 | 0.00 | 0.00 |
February | 6371.48 | 0.00 | 0.00 |
March | 5053.96 | 0.00 | 0.00 |
April | 2505.50 | 0.00 | 0.00 |
May | 336.70 | 0.00 | 0.00 |
June | 10.03 | 0.00 | 0.00 |
July | 5.24 | 0.00 | 0.00 |
August | 110.32 | 0.00 | 0.00 |
September | 978.12 | 0.00 | 0.00 |
October | 3248.07 | 0.00 | 0.00 |
November | 6698.66 | 0.00 | 0.00 |
December | 7303.96 | 0.00 | 0.00 |
Annual Sum or Average | 3277.57 | 0.00 | 0.00 |
Minimum of Months | 5.24 | 0.00 | 0.00 |
Maximum of Months | 7303.96 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8581.43 | 0.00 | 0.00 |
February | 7805.05 | 0.00 | 0.00 |
March | 5906.96 | 0.00 | 0.00 |
April | 2800.71 | 0.00 | 0.00 |
May | 343.28 | 0.00 | 0.00 |
June | 14.65 | 0.00 | 0.00 |
July | 6.98 | 0.00 | 0.00 |
August | 91.47 | 0.00 | 0.00 |
September | 1119.95 | 0.00 | 0.00 |
October | 4078.98 | 0.00 | 0.00 |
November | 8409.57 | 0.00 | 0.00 |
December | 9104.23 | 0.00 | 0.00 |
Annual Sum or Average | 4001.10 | 0.00 | 0.00 |
Minimum of Months | 6.98 | 0.00 | 0.00 |
Maximum of Months | 9104.23 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7424.63 | 0.00 | 0.00 |
February | 6299.51 | 0.00 | 0.00 |
March | 4380.15 | 0.00 | 0.00 |
April | 1600.67 | 0.00 | 0.00 |
May | 158.60 | 0.00 | 0.00 |
June | 0.99 | 0.00 | 0.00 |
July | 1.15 | 0.00 | 0.00 |
August | 46.93 | 0.00 | 0.00 |
September | 743.08 | 0.00 | 0.00 |
October | 3268.24 | 0.00 | 0.00 |
November | 7120.92 | 0.00 | 0.00 |
December | 7954.44 | 0.00 | 0.00 |
Annual Sum or Average | 3234.56 | 0.00 | 0.00 |
Minimum of Months | 0.99 | 0.00 | 0.00 |
Maximum of Months | 7954.44 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5438.49 | 0.00 | 0.00 |
February | 4561.90 | 0.00 | 0.00 |
March | 3101.62 | 0.00 | 0.00 |
April | 1122.22 | 0.00 | 0.00 |
May | 77.95 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 28.01 | 0.00 | 0.00 |
September | 407.55 | 0.00 | 0.00 |
October | 2204.85 | 0.00 | 0.00 |
November | 5221.33 | 0.00 | 0.00 |
December | 5874.23 | 0.00 | 0.00 |
Annual Sum or Average | 2325.33 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5874.23 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7449.71 | 0.00 | 0.00 |
February | 6202.67 | 0.00 | 0.00 |
March | 4028.13 | 0.00 | 0.00 |
April | 1461.25 | 0.00 | 0.00 |
May | 91.49 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 29.54 | 0.00 | 0.00 |
September | 548.49 | 0.00 | 0.00 |
October | 3055.35 | 0.00 | 0.00 |
November | 7166.38 | 0.00 | 0.00 |
December | 7996.54 | 0.00 | 0.00 |
Annual Sum or Average | 3153.79 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7996.54 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7695.25 | 0.00 | 0.00 |
February | 6893.82 | 0.00 | 0.00 |
March | 5031.23 | 0.00 | 0.00 |
April | 1921.42 | 0.00 | 0.00 |
May | 164.42 | 0.00 | 0.00 |
June | 0.61 | 0.00 | 0.00 |
July | 0.60 | 0.00 | 0.00 |
August | 76.30 | 0.00 | 0.00 |
September | 867.49 | 0.00 | 0.00 |
October | 3597.29 | 0.00 | 0.00 |
November | 7497.99 | 0.00 | 0.00 |
December | 8106.90 | 0.00 | 0.00 |
Annual Sum or Average | 3469.82 | 0.00 | 0.00 |
Minimum of Months | 0.60 | 0.00 | 0.00 |
Maximum of Months | 8106.90 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5644.65 | 0.00 | 0.00 |
February | 5096.31 | 0.00 | 0.00 |
March | 3934.36 | 0.00 | 0.00 |
April | 1642.72 | 0.00 | 0.00 |
May | 96.87 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 49.68 | 0.00 | 0.00 |
September | 635.26 | 0.00 | 0.00 |
October | 2631.85 | 0.00 | 0.00 |
November | 5505.01 | 0.00 | 0.00 |
December | 5930.40 | 0.00 | 0.00 |
Annual Sum or Average | 2583.86 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5930.40 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7651.25 | 0.00 | 0.00 |
February | 6745.08 | 0.00 | 0.00 |
March | 4843.17 | 0.00 | 0.00 |
April | 1938.05 | 0.00 | 0.00 |
May | 119.73 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 41.22 | 0.00 | 0.00 |
September | 771.01 | 0.00 | 0.00 |
October | 3496.17 | 0.00 | 0.00 |
November | 7448.21 | 0.00 | 0.00 |
December | 8068.24 | 0.00 | 0.00 |
Annual Sum or Average | 3409.30 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8068.24 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10031.78 | 0.00 | 0.00 |
February | 8684.51 | 0.00 | 0.00 |
March | 6243.92 | 0.00 | 0.00 |
April | 2325.75 | 0.00 | 0.00 |
May | 283.59 | 0.00 | 0.00 |
June | 3.76 | 0.00 | 0.00 |
July | 2.71 | 0.00 | 0.00 |
August | 82.72 | 0.00 | 0.00 |
September | 1147.78 | 0.00 | 0.00 |
October | 4640.60 | 0.00 | 0.00 |
November | 9704.67 | 0.00 | 0.00 |
December | 10691.68 | 0.00 | 0.00 |
Annual Sum or Average | 4465.51 | 0.00 | 0.00 |
Minimum of Months | 2.71 | 0.00 | 0.00 |
Maximum of Months | 10691.68 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8016.41 | 0.00 | 0.00 |
February | 6896.40 | 0.00 | 0.00 |
March | 4979.74 | 0.00 | 0.00 |
April | 1939.05 | 0.00 | 0.00 |
May | 221.76 | 0.00 | 0.00 |
June | 5.33 | 0.00 | 0.00 |
July | 2.42 | 0.00 | 0.00 |
August | 68.48 | 0.00 | 0.00 |
September | 852.57 | 0.00 | 0.00 |
October | 3572.76 | 0.00 | 0.00 |
November | 7773.66 | 0.00 | 0.00 |
December | 8584.88 | 0.00 | 0.00 |
Annual Sum or Average | 3559.06 | 0.00 | 0.00 |
Minimum of Months | 2.42 | 0.00 | 0.00 |
Maximum of Months | 8584.88 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10019.85 | 0.00 | 0.00 |
February | 8581.47 | 0.00 | 0.00 |
March | 5946.63 | 0.00 | 0.00 |
April | 2304.68 | 0.00 | 0.00 |
May | 227.04 | 0.00 | 0.00 |
June | 5.89 | 0.00 | 0.00 |
July | 2.58 | 0.00 | 0.00 |
August | 64.67 | 0.00 | 0.00 |
September | 1058.14 | 0.00 | 0.00 |
October | 4520.19 | 0.00 | 0.00 |
November | 9733.78 | 0.00 | 0.00 |
December | 10719.13 | 0.00 | 0.00 |
Annual Sum or Average | 4410.57 | 0.00 | 0.00 |
Minimum of Months | 2.58 | 0.00 | 0.00 |
Maximum of Months | 10719.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10262.44 | 0.00 | 0.00 |
February | 9266.33 | 0.00 | 0.00 |
March | 7046.78 | 0.00 | 0.00 |
April | 2809.60 | 0.00 | 0.00 |
May | 345.20 | 0.00 | 0.00 |
June | 11.94 | 0.00 | 0.00 |
July | 6.56 | 0.00 | 0.00 |
August | 133.83 | 0.00 | 0.00 |
September | 1440.96 | 0.00 | 0.00 |
October | 5106.41 | 0.00 | 0.00 |
November | 10039.50 | 0.00 | 0.00 |
December | 10805.27 | 0.00 | 0.00 |
Annual Sum or Average | 4749.09 | 0.00 | 0.00 |
Minimum of Months | 6.56 | 0.00 | 0.00 |
Maximum of Months | 10805.27 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8177.22 | 0.00 | 0.00 |
February | 7435.48 | 0.00 | 0.00 |
March | 5793.39 | 0.00 | 0.00 |
April | 2585.57 | 0.00 | 0.00 |
May | 246.82 | 0.00 | 0.00 |
June | 3.73 | 0.00 | 0.00 |
July | 2.36 | 0.00 | 0.00 |
August | 108.92 | 0.00 | 0.00 |
September | 1182.28 | 0.00 | 0.00 |
October | 4027.15 | 0.00 | 0.00 |
November | 8055.82 | 0.00 | 0.00 |
December | 8634.87 | 0.00 | 0.00 |
Annual Sum or Average | 3834.87 | 0.00 | 0.00 |
Minimum of Months | 2.36 | 0.00 | 0.00 |
Maximum of Months | 8634.87 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10098.45 | 0.00 | 0.00 |
February | 9102.80 | 0.00 | 0.00 |
March | 6740.42 | 0.00 | 0.00 |
April | 2891.81 | 0.00 | 0.00 |
May | 256.21 | 0.00 | 0.00 |
June | 5.49 | 0.00 | 0.00 |
July | 3.07 | 0.00 | 0.00 |
August | 83.73 | 0.00 | 0.00 |
September | 1347.21 | 0.00 | 0.00 |
October | 4967.95 | 0.00 | 0.00 |
November | 10020.54 | 0.00 | 0.00 |
December | 10761.49 | 0.00 | 0.00 |
Annual Sum or Average | 4665.97 | 0.00 | 0.00 |
Minimum of Months | 3.07 | 0.00 | 0.00 |
Maximum of Months | 10761.49 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 18148.44 | 0.00 | 0.00 |
February | 17646.12 | 0.00 | 0.00 |
March | 16379.33 | 0.00 | 0.00 |
April | 10357.55 | 0.00 | 0.00 |
May | 2937.87 | 0.00 | 0.00 |
June | 902.01 | 0.00 | 0.00 |
July | 556.66 | 0.00 | 0.00 |
August | 693.32 | 0.00 | 0.00 |
September | 3297.91 | 0.00 | 0.00 |
October | 7199.36 | 0.00 | 0.00 |
November | 16683.42 | 0.00 | 0.00 |
December | 18179.02 | 0.00 | 0.00 |
Annual Sum or Average | 9365.02 | 0.00 | 0.00 |
Minimum of Months | 556.66 | 0.00 | 0.00 |
Maximum of Months | 18179.02 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.10 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.11 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.11 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.11 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.11 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.07 |
August | 0.00 | 0.00 | 0.03 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.13 |
June | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.17 |
September | 0.00 | 0.00 | 0.03 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.43 | 1182.50 |
March | 0.00 | 0.00 | 1759.68 | 1310.13 |
April | 0.00 | 0.00 | 1756.77 | 1265.77 |
May | 0.00 | 0.00 | 1731.59 | 1289.22 |
June | 0.00 | 0.00 | 1655.55 | 1192.84 |
July | 0.00 | 0.00 | 1589.87 | 1183.70 |
August | 0.00 | 0.00 | 1549.57 | 1153.70 |
September | 0.00 | 0.00 | 1559.12 | 1123.36 |
October | 0.00 | 0.00 | 1595.83 | 1188.14 |
November | 0.00 | 0.00 | 1655.00 | 1192.45 |
December | 0.00 | 0.00 | 1733.75 | 1290.82 |
Annual Sum or Average | 0.00 | 0.00 | 1674.93 | 14682.77 |
Minimum of Months | 0.00 | 0.00 | 1549.57 | 1123.36 |
Maximum of Months | 0.00 | 0.00 | 1759.68 | 1310.13 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.43 | 1182.50 |
March | 0.00 | 0.00 | 1759.63 | 1310.10 |
April | 0.00 | 0.00 | 1759.33 | 1267.62 |
May | 0.00 | 0.00 | 1731.59 | 1289.22 |
June | 0.00 | 0.00 | 1653.19 | 1191.14 |
July | 0.00 | 0.00 | 1589.49 | 1183.42 |
August | 0.00 | 0.00 | 1547.48 | 1152.15 |
September | 0.00 | 0.00 | 1558.66 | 1123.03 |
October | 0.00 | 0.00 | 1596.18 | 1188.40 |
November | 0.00 | 0.00 | 1655.16 | 1192.56 |
December | 0.00 | 0.00 | 1731.56 | 1289.19 |
Annual Sum or Average | 0.00 | 0.00 | 1674.55 | 14679.46 |
Minimum of Months | 0.00 | 0.00 | 1547.48 | 1123.03 |
Maximum of Months | 0.00 | 0.00 | 1759.68 | 1310.13 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.77 | 1310.19 |
February | 0.00 | 0.00 | 1760.66 | 1184.01 |
March | 0.00 | 0.00 | 1757.59 | 1308.57 |
April | 0.00 | 0.00 | 1759.34 | 1267.62 |
May | 0.00 | 0.00 | 1727.87 | 1286.45 |
June | 0.00 | 0.00 | 1652.11 | 1190.36 |
July | 0.00 | 0.00 | 1589.48 | 1183.41 |
August | 0.00 | 0.00 | 1547.37 | 1152.06 |
September | 0.00 | 0.00 | 1558.74 | 1123.09 |
October | 0.00 | 0.00 | 1595.96 | 1188.24 |
November | 0.00 | 0.00 | 1655.03 | 1192.47 |
December | 0.00 | 0.00 | 1733.63 | 1290.73 |
Annual Sum or Average | 0.00 | 0.00 | 1674.29 | 14677.20 |
Minimum of Months | 0.00 | 0.00 | 1547.37 | 1123.09 |
Maximum of Months | 0.00 | 0.00 | 1760.66 | 1310.19 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.44 | 1182.51 |
March | 0.00 | 0.00 | 1759.75 | 1310.18 |
April | 0.00 | 0.00 | 1766.56 | 1272.83 |
May | 0.00 | 0.00 | 1734.08 | 1291.07 |
June | 0.00 | 0.00 | 1655.50 | 1192.80 |
July | 0.00 | 0.00 | 1589.52 | 1183.44 |
August | 0.00 | 0.00 | 1552.11 | 1155.59 |
September | 0.00 | 0.00 | 1563.99 | 1126.87 |
October | 0.00 | 0.00 | 1596.02 | 1188.28 |
November | 0.00 | 0.00 | 1655.25 | 1192.63 |
December | 0.00 | 0.00 | 1733.78 | 1290.85 |
Annual Sum or Average | 0.00 | 0.00 | 1676.57 | 14697.18 |
Minimum of Months | 0.00 | 0.00 | 1552.11 | 1126.87 |
Maximum of Months | 0.00 | 0.00 | 1766.56 | 1310.18 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1761.97 | 1311.84 |
February | 0.00 | 0.00 | 1758.34 | 1182.44 |
March | 0.00 | 0.00 | 1759.65 | 1310.11 |
April | 0.00 | 0.00 | 1764.30 | 1271.20 |
May | 0.00 | 0.00 | 1736.43 | 1292.82 |
June | 0.00 | 0.00 | 1650.85 | 1189.46 |
July | 0.00 | 0.00 | 1589.53 | 1183.45 |
August | 0.00 | 0.00 | 1549.84 | 1153.90 |
September | 0.00 | 0.00 | 1563.48 | 1126.51 |
October | 0.00 | 0.00 | 1595.97 | 1188.25 |
November | 0.00 | 0.00 | 1655.09 | 1192.51 |
December | 0.00 | 0.00 | 1733.65 | 1290.75 |
Annual Sum or Average | 0.00 | 0.00 | 1676.12 | 14693.22 |
Minimum of Months | 0.00 | 0.00 | 1549.84 | 1126.51 |
Maximum of Months | 0.00 | 0.00 | 1764.30 | 1311.84 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1764.37 | 1313.62 |
February | 0.00 | 0.00 | 1760.83 | 1184.12 |
March | 0.00 | 0.00 | 1759.63 | 1310.09 |
April | 0.00 | 0.00 | 1761.90 | 1269.47 |
May | 0.00 | 0.00 | 1731.08 | 1288.83 |
June | 0.00 | 0.00 | 1653.04 | 1191.03 |
July | 0.00 | 0.00 | 1587.29 | 1181.78 |
August | 0.00 | 0.00 | 1549.87 | 1153.92 |
September | 0.00 | 0.00 | 1561.55 | 1125.11 |
October | 0.00 | 0.00 | 1596.21 | 1188.42 |
November | 0.00 | 0.00 | 1657.57 | 1194.30 |
December | 0.00 | 0.00 | 1735.97 | 1292.47 |
Annual Sum or Average | 0.00 | 0.00 | 1676.11 | 14693.17 |
Minimum of Months | 0.00 | 0.00 | 1549.87 | 1125.11 |
Maximum of Months | 0.00 | 0.00 | 1764.37 | 1313.62 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.44 | 1182.51 |
March | 0.00 | 0.00 | 1759.71 | 1310.15 |
April | 0.00 | 0.00 | 1754.45 | 1264.10 |
May | 0.00 | 0.00 | 1727.30 | 1286.02 |
June | 0.00 | 0.00 | 1650.64 | 1189.31 |
July | 0.00 | 0.00 | 1587.40 | 1181.86 |
August | 0.00 | 0.00 | 1543.23 | 1148.98 |
September | 0.00 | 0.00 | 1556.87 | 1121.74 |
October | 0.00 | 0.00 | 1595.86 | 1188.16 |
November | 0.00 | 0.00 | 1655.03 | 1192.47 |
December | 0.00 | 0.00 | 1733.65 | 1290.75 |
Annual Sum or Average | 0.00 | 0.00 | 1673.03 | 14666.18 |
Minimum of Months | 0.00 | 0.00 | 1543.23 | 1121.74 |
Maximum of Months | 0.00 | 0.00 | 1759.71 | 1310.15 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1760.83 | 1184.12 |
March | 0.00 | 0.00 | 1757.40 | 1308.43 |
April | 0.00 | 0.00 | 1755.80 | 1265.07 |
May | 0.00 | 0.00 | 1725.90 | 1284.98 |
June | 0.00 | 0.00 | 1648.61 | 1187.84 |
July | 0.00 | 0.00 | 1584.92 | 1180.02 |
August | 0.00 | 0.00 | 1541.06 | 1147.36 |
September | 0.00 | 0.00 | 1554.45 | 1120.00 |
October | 0.00 | 0.00 | 1595.82 | 1188.13 |
November | 0.00 | 0.00 | 1655.27 | 1192.64 |
December | 0.00 | 0.00 | 1733.89 | 1290.93 |
Annual Sum or Average | 0.00 | 0.00 | 1672.29 | 14659.65 |
Minimum of Months | 0.00 | 0.00 | 1541.06 | 1120.00 |
Maximum of Months | 0.00 | 0.00 | 1760.83 | 1310.13 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1760.84 | 1184.12 |
March | 0.00 | 0.00 | 1757.49 | 1308.50 |
April | 0.00 | 0.00 | 1754.53 | 1264.16 |
May | 0.00 | 0.00 | 1724.51 | 1283.94 |
June | 0.00 | 0.00 | 1650.58 | 1189.26 |
July | 0.00 | 0.00 | 1585.28 | 1180.29 |
August | 0.00 | 0.00 | 1542.98 | 1148.79 |
September | 0.00 | 0.00 | 1554.46 | 1120.01 |
October | 0.00 | 0.00 | 1596.32 | 1188.51 |
November | 0.00 | 0.00 | 1657.37 | 1194.15 |
December | 0.00 | 0.00 | 1731.77 | 1289.35 |
Annual Sum or Average | 0.00 | 0.00 | 1672.47 | 14661.21 |
Minimum of Months | 0.00 | 0.00 | 1542.98 | 1120.01 |
Maximum of Months | 0.00 | 0.00 | 1760.84 | 1310.13 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.54 | 1182.57 |
March | 0.00 | 0.00 | 1762.06 | 1311.91 |
April | 0.00 | 0.00 | 1763.78 | 1270.82 |
May | 0.00 | 0.00 | 1729.48 | 1287.65 |
June | 0.00 | 0.00 | 1650.21 | 1189.00 |
July | 0.00 | 0.00 | 1585.55 | 1180.48 |
August | 0.00 | 0.00 | 1545.57 | 1150.72 |
September | 0.00 | 0.00 | 1561.47 | 1125.06 |
October | 0.00 | 0.00 | 1598.45 | 1190.09 |
November | 0.00 | 0.00 | 1657.26 | 1194.07 |
December | 0.00 | 0.00 | 1731.69 | 1289.29 |
Annual Sum or Average | 0.00 | 0.00 | 1674.82 | 14681.80 |
Minimum of Months | 0.00 | 0.00 | 1545.57 | 1125.06 |
Maximum of Months | 0.00 | 0.00 | 1763.78 | 1311.91 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.49 | 1182.54 |
March | 0.00 | 0.00 | 1759.69 | 1310.14 |
April | 0.00 | 0.00 | 1761.76 | 1269.37 |
May | 0.00 | 0.00 | 1729.61 | 1287.74 |
June | 0.00 | 0.00 | 1648.53 | 1187.78 |
July | 0.00 | 0.00 | 1585.00 | 1180.08 |
August | 0.00 | 0.00 | 1543.17 | 1148.94 |
September | 0.00 | 0.00 | 1561.21 | 1124.87 |
October | 0.00 | 0.00 | 1595.97 | 1188.25 |
November | 0.00 | 0.00 | 1655.26 | 1192.63 |
December | 0.00 | 0.00 | 1733.85 | 1290.90 |
Annual Sum or Average | 0.00 | 0.00 | 1673.85 | 14673.36 |
Minimum of Months | 0.00 | 0.00 | 1543.17 | 1124.87 |
Maximum of Months | 0.00 | 0.00 | 1761.76 | 1310.14 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.82 | 1310.23 |
February | 0.00 | 0.00 | 1760.73 | 1184.05 |
March | 0.00 | 0.00 | 1757.55 | 1308.54 |
April | 0.00 | 0.00 | 1761.60 | 1269.25 |
May | 0.00 | 0.00 | 1724.65 | 1284.05 |
June | 0.00 | 0.00 | 1648.67 | 1187.88 |
July | 0.00 | 0.00 | 1587.10 | 1181.64 |
August | 0.00 | 0.00 | 1542.90 | 1148.74 |
September | 0.00 | 0.00 | 1559.08 | 1123.33 |
October | 0.00 | 0.00 | 1598.27 | 1189.96 |
November | 0.00 | 0.00 | 1655.15 | 1192.56 |
December | 0.00 | 0.00 | 1731.65 | 1289.26 |
Annual Sum or Average | 0.00 | 0.00 | 1673.41 | 14669.50 |
Minimum of Months | 0.00 | 0.00 | 1542.90 | 1123.33 |
Maximum of Months | 0.00 | 0.00 | 1761.60 | 1310.23 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.45 | 1182.51 |
March | 0.00 | 0.00 | 1759.62 | 1310.09 |
April | 0.00 | 0.00 | 1757.14 | 1266.04 |
May | 0.00 | 0.00 | 1731.45 | 1289.11 |
June | 0.00 | 0.00 | 1650.86 | 1189.46 |
July | 0.00 | 0.00 | 1587.49 | 1181.93 |
August | 0.00 | 0.00 | 1547.66 | 1152.28 |
September | 0.00 | 0.00 | 1559.12 | 1123.36 |
October | 0.00 | 0.00 | 1595.94 | 1188.22 |
November | 0.00 | 0.00 | 1655.27 | 1192.64 |
December | 0.00 | 0.00 | 1733.81 | 1290.87 |
Annual Sum or Average | 0.00 | 0.00 | 1674.23 | 14676.65 |
Minimum of Months | 0.00 | 0.00 | 1547.66 | 1123.36 |
Maximum of Months | 0.00 | 0.00 | 1759.68 | 1310.13 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.42 | 1182.50 |
March | 0.00 | 0.00 | 1759.60 | 1310.07 |
April | 0.00 | 0.00 | 1757.03 | 1265.96 |
May | 0.00 | 0.00 | 1729.21 | 1287.44 |
June | 0.00 | 0.00 | 1648.84 | 1188.00 |
July | 0.00 | 0.00 | 1586.96 | 1181.54 |
August | 0.00 | 0.00 | 1543.28 | 1149.02 |
September | 0.00 | 0.00 | 1558.88 | 1123.19 |
October | 0.00 | 0.00 | 1594.18 | 1186.91 |
November | 0.00 | 0.00 | 1657.34 | 1194.13 |
December | 0.00 | 0.00 | 1731.73 | 1289.32 |
Annual Sum or Average | 0.00 | 0.00 | 1673.27 | 14668.21 |
Minimum of Months | 0.00 | 0.00 | 1543.28 | 1123.19 |
Maximum of Months | 0.00 | 0.00 | 1759.68 | 1310.13 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.77 | 1310.19 |
February | 0.00 | 0.00 | 1760.82 | 1184.11 |
March | 0.00 | 0.00 | 1757.39 | 1308.42 |
April | 0.00 | 0.00 | 1756.91 | 1265.87 |
May | 0.00 | 0.00 | 1726.82 | 1285.67 |
June | 0.00 | 0.00 | 1648.74 | 1187.93 |
July | 0.00 | 0.00 | 1587.18 | 1181.70 |
August | 0.00 | 0.00 | 1543.26 | 1149.00 |
September | 0.00 | 0.00 | 1558.89 | 1123.20 |
October | 0.00 | 0.00 | 1595.94 | 1188.22 |
November | 0.00 | 0.00 | 1655.04 | 1192.47 |
December | 0.00 | 0.00 | 1733.56 | 1290.68 |
Annual Sum or Average | 0.00 | 0.00 | 1673.18 | 14667.47 |
Minimum of Months | 0.00 | 0.00 | 1543.26 | 1123.20 |
Maximum of Months | 0.00 | 0.00 | 1760.82 | 1310.19 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.68 | 1310.13 |
February | 0.00 | 0.00 | 1758.43 | 1182.50 |
March | 0.00 | 0.00 | 1759.76 | 1310.19 |
April | 0.00 | 0.00 | 1764.11 | 1271.06 |
May | 0.00 | 0.00 | 1731.86 | 1289.42 |
June | 0.00 | 0.00 | 1650.87 | 1189.47 |
July | 0.00 | 0.00 | 1587.28 | 1181.77 |
August | 0.00 | 0.00 | 1547.75 | 1152.34 |
September | 0.00 | 0.00 | 1563.61 | 1126.59 |
October | 0.00 | 0.00 | 1596.17 | 1188.40 |
November | 0.00 | 0.00 | 1657.42 | 1194.19 |
December | 0.00 | 0.00 | 1731.77 | 1289.35 |
Annual Sum or Average | 0.00 | 0.00 | 1675.23 | 14685.42 |
Minimum of Months | 0.00 | 0.00 | 1547.75 | 1126.59 |
Maximum of Months | 0.00 | 0.00 | 1764.11 | 1310.19 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1759.72 | 1310.16 |
February | 0.00 | 0.00 | 1760.80 | 1184.10 |
March | 0.00 | 0.00 | 1757.46 | 1308.48 |
April | 0.00 | 0.00 | 1761.92 | 1269.48 |
May | 0.00 | 0.00 | 1731.89 | 1289.44 |
June | 0.00 | 0.00 | 1650.61 | 1189.28 |
July | 0.00 | 0.00 | 1585.38 | 1180.36 |
August | 0.00 | 0.00 | 1545.42 | 1150.61 |
September | 0.00 | 0.00 | 1563.45 | 1126.48 |
October | 0.00 | 0.00 | 1596.15 | 1188.38 |
November | 0.00 | 0.00 | 1655.10 | 1192.52 |
December | 0.00 | 0.00 | 1731.59 | 1289.22 |
Annual Sum or Average | 0.00 | 0.00 | 1674.44 | 14678.51 |
Minimum of Months | 0.00 | 0.00 | 1545.42 | 1126.48 |
Maximum of Months | 0.00 | 0.00 | 1761.92 | 1310.16 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1762.03 | 1311.88 |
February | 0.00 | 0.00 | 1760.70 | 1184.03 |
March | 0.00 | 0.00 | 1757.46 | 1308.48 |
April | 0.00 | 0.00 | 1761.63 | 1269.28 |
May | 0.00 | 0.00 | 1727.08 | 1285.86 |
June | 0.00 | 0.00 | 1650.75 | 1189.38 |
July | 0.00 | 0.00 | 1585.22 | 1180.24 |
August | 0.00 | 0.00 | 1545.36 | 1150.56 |
September | 0.00 | 0.00 | 1561.47 | 1125.06 |
October | 0.00 | 0.00 | 1596.11 | 1188.35 |
November | 0.00 | 0.00 | 1655.27 | 1192.64 |
December | 0.00 | 0.00 | 1733.87 | 1290.91 |
Annual Sum or Average | 0.00 | 0.00 | 1674.23 | 14676.66 |
Minimum of Months | 0.00 | 0.00 | 1545.36 | 1125.06 |
Maximum of Months | 0.00 | 0.00 | 1762.03 | 1311.88 |
Report: HEATING AND COOLING LOADS
For: HEATEDBSMT
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 11481.28 |
February | 0.01 | 10153.04 |
March | 0.97 | 10618.06 |
April | 7.29 | 6731.85 |
May | 8.89 | 1881.96 |
June | 4.56 | 455.94 |
July | 7.43 | 287.52 |
August | 11.25 | 361.51 |
September | 9.01 | 1848.91 |
October | 1.15 | 4012.67 |
November | 0.00 | 9988.89 |
December | 0.00 | 11393.96 |
Annual Sum or Average | 50.57 | 69215.59 |
Minimum of Months | 0.00 | 287.52 |
Maximum of Months | 11.25 | 11481.28 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4219.72 |
February | 0.14 | 3126.15 |
March | 8.06 | 2312.14 |
April | 45.46 | 889.98 |
May | 82.71 | 130.29 |
June | 122.66 | 9.37 |
July | 126.47 | 5.58 |
August | 101.90 | 42.79 |
September | 42.02 | 313.46 |
October | 7.35 | 1518.73 |
November | 0.00 | 3715.31 |
December | 0.00 | 4508.26 |
Annual Sum or Average | 536.77 | 20791.78 |
Minimum of Months | 0.00 | 5.58 |
Maximum of Months | 126.47 | 4508.26 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2687.71 |
February | 0.76 | 1911.98 |
March | 12.82 | 1390.37 |
April | 40.03 | 546.65 |
May | 70.95 | 83.33 |
June | 90.93 | 2.82 |
July | 99.91 | 0.85 |
August | 87.69 | 16.56 |
September | 52.82 | 167.51 |
October | 16.44 | 796.83 |
November | 0.00 | 2296.86 |
December | 0.00 | 2902.83 |
Annual Sum or Average | 472.35 | 12804.31 |
Minimum of Months | 0.00 | 0.85 |
Maximum of Months | 99.91 | 2902.83 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4171.70 |
February | 0.68 | 3050.35 |
March | 14.62 | 2171.19 |
April | 45.71 | 885.84 |
May | 102.54 | 124.82 |
June | 130.98 | 5.14 |
July | 144.29 | 2.00 |
August | 111.39 | 30.86 |
September | 52.52 | 325.12 |
October | 15.25 | 1492.71 |
November | 0.00 | 3715.81 |
December | 0.00 | 4503.95 |
Annual Sum or Average | 617.99 | 20479.51 |
Minimum of Months | 0.00 | 2.00 |
Maximum of Months | 144.29 | 4503.95 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4350.08 |
February | 0.30 | 3471.22 |
March | 9.02 | 2871.82 |
April | 30.29 | 1130.72 |
May | 62.83 | 153.22 |
June | 103.23 | 5.96 |
July | 103.76 | 3.15 |
August | 74.49 | 50.56 |
September | 31.82 | 424.91 |
October | 8.22 | 1802.89 |
November | 0.00 | 3908.73 |
December | 0.00 | 4548.51 |
Annual Sum or Average | 423.95 | 22721.78 |
Minimum of Months | 0.00 | 3.15 |
Maximum of Months | 103.76 | 4548.51 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2747.52 |
February | 0.08 | 2232.63 |
March | 3.65 | 1840.04 |
April | 20.56 | 820.26 |
May | 52.21 | 89.28 |
June | 71.64 | 2.09 |
July | 77.32 | 0.55 |
August | 60.50 | 27.25 |
September | 37.60 | 245.06 |
October | 10.07 | 1004.92 |
November | 0.00 | 2490.29 |
December | 0.00 | 2936.02 |
Annual Sum or Average | 333.62 | 14435.90 |
Minimum of Months | 0.00 | 0.55 |
Maximum of Months | 77.32 | 2936.02 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4133.64 |
February | 0.03 | 3313.16 |
March | 2.57 | 2561.01 |
April | 23.50 | 1110.56 |
May | 75.49 | 131.99 |
June | 111.61 | 5.25 |
July | 121.30 | 2.30 |
August | 81.27 | 37.17 |
September | 36.52 | 395.75 |
October | 8.59 | 1701.45 |
November | 0.00 | 3857.08 |
December | 0.00 | 4425.91 |
Annual Sum or Average | 460.89 | 21675.28 |
Minimum of Months | 0.00 | 2.30 |
Maximum of Months | 121.30 | 4425.91 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3246.04 |
February | 0.91 | 2283.54 |
March | 19.27 | 1586.09 |
April | 80.83 | 519.63 |
May | 126.07 | 42.65 |
June | 169.35 | 0.10 |
July | 171.91 | 0.16 |
August | 139.26 | 13.25 |
September | 63.03 | 199.49 |
October | 15.69 | 1149.49 |
November | 0.00 | 2910.78 |
December | 0.00 | 3552.77 |
Annual Sum or Average | 786.32 | 15503.99 |
Minimum of Months | 0.00 | 0.10 |
Maximum of Months | 171.91 | 3552.77 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.14 | 1606.56 |
February | 7.60 | 1068.25 |
March | 33.16 | 709.84 |
April | 72.64 | 237.74 |
May | 108.94 | 14.83 |
June | 134.62 | 0.00 |
July | 144.03 | 0.00 |
August | 125.03 | 6.69 |
September | 74.66 | 84.10 |
October | 30.67 | 451.57 |
November | 0.40 | 1396.00 |
December | 0.42 | 1836.88 |
Annual Sum or Average | 732.32 | 7412.46 |
Minimum of Months | 0.14 | 0.00 |
Maximum of Months | 144.03 | 1836.88 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.10 | 3232.25 |
February | 6.55 | 2269.86 |
March | 34.09 | 1507.77 |
April | 80.04 | 530.66 |
May | 152.84 | 31.91 |
June | 186.72 | 0.00 |
July | 198.00 | 0.00 |
August | 155.31 | 12.14 |
September | 73.58 | 201.27 |
October | 26.07 | 1149.85 |
November | 0.31 | 2917.13 |
December | 0.29 | 3552.82 |
Annual Sum or Average | 913.91 | 15405.66 |
Minimum of Months | 0.10 | 0.00 |
Maximum of Months | 198.00 | 3552.82 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.02 | 3384.13 |
February | 3.12 | 2683.48 |
March | 20.50 | 2146.95 |
April | 48.73 | 720.51 |
May | 92.76 | 46.44 |
June | 148.74 | 0.13 |
July | 147.11 | 0.07 |
August | 102.86 | 24.74 |
September | 43.64 | 297.88 |
October | 13.03 | 1409.16 |
November | 0.07 | 3127.34 |
December | 0.10 | 3596.39 |
Annual Sum or Average | 620.67 | 17437.23 |
Minimum of Months | 0.02 | 0.07 |
Maximum of Months | 148.74 | 3596.39 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.11 | 1765.79 |
February | 2.27 | 1373.65 |
March | 13.29 | 1101.34 |
April | 41.36 | 424.19 |
May | 75.83 | 18.44 |
June | 114.46 | 0.00 |
July | 119.02 | 0.00 |
August | 88.48 | 12.83 |
September | 50.76 | 139.11 |
October | 18.18 | 632.15 |
November | 0.05 | 1602.92 |
December | 0.40 | 1882.16 |
Annual Sum or Average | 524.21 | 8952.58 |
Minimum of Months | 0.05 | 0.00 |
Maximum of Months | 119.02 | 1882.16 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.08 | 3404.79 |
February | 1.58 | 2593.12 |
March | 12.72 | 1872.94 |
April | 44.91 | 715.50 |
May | 116.23 | 42.77 |
June | 165.87 | 0.00 |
July | 172.37 | 0.00 |
August | 117.06 | 17.55 |
September | 47.93 | 274.35 |
October | 14.83 | 1351.04 |
November | 0.02 | 3137.28 |
December | 0.31 | 3623.64 |
Annual Sum or Average | 693.92 | 17032.98 |
Minimum of Months | 0.02 | 0.00 |
Maximum of Months | 172.37 | 3623.64 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5272.65 |
February | 0.04 | 4193.15 |
March | 3.15 | 3195.90 |
April | 28.53 | 1223.65 |
May | 101.94 | 98.85 |
June | 163.98 | 1.74 |
July | 173.46 | 0.76 |
August | 112.10 | 34.51 |
September | 32.22 | 507.97 |
October | 4.07 | 2319.40 |
November | 0.00 | 5032.91 |
December | 0.00 | 5670.50 |
Annual Sum or Average | 619.48 | 27551.99 |
Minimum of Months | 0.00 | 0.76 |
Maximum of Months | 173.46 | 5670.50 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5209.75 |
February | 0.46 | 3840.16 |
March | 12.04 | 2706.01 |
April | 56.26 | 972.20 |
May | 131.30 | 89.31 |
June | 179.78 | 1.74 |
July | 193.76 | 0.53 |
August | 143.21 | 25.78 |
September | 52.24 | 404.03 |
October | 9.99 | 2055.77 |
November | 0.00 | 4824.95 |
December | 0.00 | 5643.35 |
Annual Sum or Average | 779.04 | 25773.59 |
Minimum of Months | 0.00 | 0.53 |
Maximum of Months | 193.76 | 5643.35 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.01 | 5240.34 |
February | 0.43 | 3930.43 |
March | 11.15 | 2947.20 |
April | 61.99 | 1013.58 |
May | 109.22 | 107.97 |
June | 164.93 | 1.09 |
July | 169.73 | 0.60 |
August | 129.66 | 32.37 |
September | 47.53 | 454.58 |
October | 8.78 | 2161.62 |
November | 0.00 | 4823.81 |
December | 0.03 | 5646.38 |
Annual Sum or Average | 703.46 | 26359.95 |
Minimum of Months | 0.00 | 0.60 |
Maximum of Months | 169.73 | 5646.38 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3705.83 |
February | 0.06 | 2963.40 |
March | 3.56 | 2400.90 |
April | 25.48 | 934.48 |
May | 68.81 | 69.85 |
June | 114.98 | 0.62 |
July | 122.10 | 0.27 |
August | 85.35 | 29.90 |
September | 32.23 | 329.29 |
October | 5.10 | 1539.29 |
November | 0.00 | 3491.47 |
December | 0.00 | 3949.22 |
Annual Sum or Average | 457.65 | 19414.54 |
Minimum of Months | 0.00 | 0.27 |
Maximum of Months | 122.10 | 3949.22 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3577.04 |
February | 0.59 | 2595.23 |
March | 12.54 | 1891.55 |
April | 50.61 | 654.82 |
May | 92.58 | 62.14 |
June | 130.76 | 0.82 |
July | 141.97 | 0.21 |
August | 115.08 | 15.19 |
September | 52.45 | 226.39 |
October | 11.57 | 1270.12 |
November | 0.00 | 3279.08 |
December | 0.00 | 3906.75 |
Annual Sum or Average | 608.15 | 17479.34 |
Minimum of Months | 0.00 | 0.21 |
Maximum of Months | 141.97 | 3906.75 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:17
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5374.59 |
February | 0.17 | 4296.93 |
March | 5.66 | 3485.36 |
April | 35.26 | 1257.40 |
May | 83.00 | 123.42 |
June | 149.06 | 3.12 |
July | 149.97 | 1.21 |
August | 99.82 | 54.67 |
September | 27.17 | 561.67 |
October | 4.39 | 2451.48 |
November | 0.00 | 5033.01 |
December | 0.00 | 5687.23 |
Annual Sum or Average | 554.50 | 28330.08 |
Minimum of Months | 0.00 | 1.21 |
Maximum of Months | 149.97 | 5687.23 |