Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:52
Tabular Output Report in Format: HTML
Building: US+MF+CZ8+hp+unheatedbsmt+IECC_2015
Environment: ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2021-05-12 10:52:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1193519.73 | 30.60 | 55.23 |
Net Site Energy | 1193519.73 | 30.60 | 55.23 |
Total Source Energy | 3779876.97 | 96.91 | 174.91 |
Net Source Energy | 3779876.97 | 96.91 | 174.91 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.26 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 546097.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16972.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299798.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53963.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 213626.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1193519.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 546097.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16972.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 36658.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 17305.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 213626.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 38.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
Other | 13.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 21.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 30.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1193519.725 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1193519.725 | 100.00 |
Total On-Site and Utility Electric Sources | 1193519.725 | 100.00 |
Total Electricity End Uses | 1193519.725 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 330767.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 330767.30 | 100.00 |
Total Water End Uses | 330767.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 641.83 |
Time Setpoint Not Met During Occupied Cooling | 0.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3401.50 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| UNHEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:52 |
RunPeriod | ANNUAL |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [ft] | 436.37 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 18953.34 | 7014.93 | 2461.74 | 7014.93 | 2461.74 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 11.22 | 7.58 | 21.60 | 7.58 | 21.60 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
UNHEATEDBSMT | 7794.39 | No | Yes | 58539.52 | 1.00 | 185.02 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
Total | 39005.22 | 325627.71 | 16363.00 | 2590.34 | 2126.74 | 2126.74 | 0.3693 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.6665 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.26 | 141888.33 | 1066.39 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 11-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:09 |
Heating | 241.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 50.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 184.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 495.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 241.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 9.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 1.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 5.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 12.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 23.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 1.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 184.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 1729491.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 53752.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140144.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949462.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 170903.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 676553.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3779876.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 80.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 174.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 44.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 96.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
ZoneHVAC:EnergyRecoveryVentilatorUser-Specified Supply Air Flow Rate [ft3/min] | User-Specified Exhaust Air Flow Rate [ft3/min] | |
ERV_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.99 |
User-Specified Maximum Flow Rate [ft3/min] | Design Size Maximum Flow Rate [ft3/min] | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 420.09 | |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 226.39 | |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 339.73 | |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 371.94 | |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 162.47 | |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 285.98 | |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 429.17 | |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 231.80 | |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 344.73 | |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 379.99 | |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 172.29 | |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 290.83 | |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 438.00 | |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 235.39 | |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 333.73 | |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 405.99 | |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 205.56 | |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 281.51 |
User-Specified Nominal Supply Air Flow Rate [ft3/min] | |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | 44.99 |
Design Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 420.09 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 226.39 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 339.73 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 371.94 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 162.47 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 285.98 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 429.17 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 231.80 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 344.73 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 379.99 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 172.29 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 290.83 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 281.51 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 333.73 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 438.00 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 205.56 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 235.39 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 405.99 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 420.09 | 420.09 | 420.09 | 420.09 | 420.09 | 420.09 | 1.00 | 1.00 | 420.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 226.39 | 226.39 | 226.39 | 226.39 | 226.39 | 226.39 | 1.00 | 1.00 | 226.39 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 339.73 | 339.73 | 339.73 | 339.73 | 339.73 | 339.73 | 1.00 | 1.00 | 339.73 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 371.94 | 371.94 | 371.94 | 371.94 | 371.94 | 371.94 | 1.00 | 1.00 | 371.94 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 162.47 | 162.47 | 162.47 | 162.47 | 162.47 | 162.47 | 1.00 | 1.00 | 162.47 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 285.98 | 285.98 | 285.98 | 285.98 | 285.98 | 285.98 | 1.00 | 1.00 | 285.98 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.17 | 429.17 | 429.17 | 429.17 | 429.17 | 429.17 | 1.00 | 1.00 | 429.17 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 231.80 | 231.80 | 231.80 | 231.80 | 231.80 | 231.80 | 1.00 | 1.00 | 231.80 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 344.73 | 344.73 | 344.73 | 344.73 | 344.73 | 344.73 | 1.00 | 1.00 | 344.73 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 379.99 | 379.99 | 379.99 | 379.99 | 379.99 | 379.99 | 1.00 | 1.00 | 379.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 172.29 | 172.29 | 172.29 | 172.29 | 172.29 | 172.29 | 1.00 | 1.00 | 172.29 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 290.83 | 290.83 | 290.83 | 290.83 | 290.83 | 290.83 | 1.00 | 1.00 | 290.83 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.00 | 438.00 | 438.00 | 438.00 | 438.00 | 438.00 | 1.00 | 1.00 | 438.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 235.39 | 235.39 | 235.39 | 235.39 | 235.39 | 235.39 | 1.00 | 1.00 | 235.39 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.73 | 333.73 | 333.73 | 333.73 | 333.73 | 333.73 | 1.00 | 1.00 | 333.73 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 405.99 | 405.99 | 405.99 | 405.99 | 405.99 | 405.99 | 1.00 | 1.00 | 405.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 205.56 | 205.56 | 205.56 | 205.56 | 205.56 | 205.56 | 1.00 | 1.00 | 205.56 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 281.51 | 281.51 | 281.51 | 281.51 | 281.51 | 281.51 | 1.00 | 1.00 | 281.51 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 420.09 | 0.933268 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 226.39 | 0.502949 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 339.73 | 0.754743 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 371.94 | 0.826302 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 162.47 | 0.360939 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 285.98 | 0.635318 | 0.800655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 429.17 | 0.953440 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 231.80 | 0.514954 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 344.73 | 0.765851 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 379.99 | 0.844185 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 172.29 | 0.382761 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 290.83 | 0.646103 | 0.800655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 438.00 | 0.973059 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 235.39 | 0.522939 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 333.73 | 0.741406 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 405.99 | 0.901946 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 205.56 | 0.456664 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 281.51 | 0.625388 | 0.800655 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Supplemental Heating Coil Nominal Capacity [Btu/h] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | 420.09 | 420.09 | 420.09 | 11199.22 | 0.933268 | 17886.01 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | 226.39 | 226.39 | 226.39 | 6035.39 | 0.502949 | 14194.71 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | 339.73 | 339.73 | 339.73 | 9056.92 | 0.754743 | 17878.99 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | 371.94 | 371.94 | 371.94 | 9915.62 | 0.826302 | 17887.48 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | 162.47 | 162.47 | 162.47 | 4331.26 | 0.360939 | 14193.41 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | 285.98 | 285.98 | 285.98 | 7623.82 | 0.635318 | 17874.99 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | 429.17 | 429.17 | 429.17 | 11441.29 | 0.953440 | 15177.25 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | 231.80 | 231.80 | 231.80 | 6179.45 | 0.514954 | 11499.24 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | 344.73 | 344.73 | 344.73 | 9190.22 | 0.765851 | 15168.41 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | 379.99 | 379.99 | 379.99 | 10130.22 | 0.844185 | 15178.37 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | 172.29 | 172.29 | 172.29 | 4593.14 | 0.382761 | 11497.64 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | 290.83 | 290.83 | 290.83 | 7753.24 | 0.646103 | 15164.17 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | 438.00 | 438.00 | 438.00 | 11676.71 | 0.973059 | 20165.75 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | 235.39 | 235.39 | 235.39 | 6275.27 | 0.522939 | 16492.58 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | 333.73 | 333.73 | 333.73 | 8896.88 | 0.741406 | 20155.22 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | 405.99 | 405.99 | 405.99 | 10823.36 | 0.901946 | 20164.95 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | 205.56 | 205.56 | 205.56 | 5479.96 | 0.456664 | 16489.82 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | 281.51 | 281.51 | 281.51 | 7504.66 | 0.625388 | 20150.53 | 1.00 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Heating Capacity [Btu/h] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 420.09 | 11199.22 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 226.39 | 6035.39 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 339.73 | 9056.92 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 371.94 | 9915.62 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 162.47 | 4331.26 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 285.98 | 7623.82 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 429.17 | 11441.29 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 231.80 | 6179.45 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 344.73 | 9190.22 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 379.99 | 10130.22 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 172.29 | 4593.14 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 290.83 | 7753.24 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 438.00 | 11676.71 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 235.39 | 6275.27 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 333.73 | 8896.88 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 405.99 | 10823.36 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 205.56 | 5479.96 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 281.51 | 7504.66 |
Design Size Nominal Capacity [Btu/h] | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 17886.01 |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 14194.71 |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 17878.99 |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 17887.48 |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 14193.41 |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 17874.99 |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 15177.25 |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 11499.24 |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 15168.41 |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 15178.37 |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 11497.64 |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 15164.17 |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 20165.75 |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 16492.58 |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 20155.22 |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 20164.95 |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 16489.82 |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 20150.53 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
VersionVersion ID | |
1 | 9.5 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 2.59 | -0.0 | 4.60 | 11.91 | 30.97 | 45.70 | 55.63 | 58.66 | 53.51 | 42.08 | 26.80 | 12.63 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 436.37 | 14. | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 29.25 | 65.16 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ8+hp+unheatedbsmt+IECC_2015 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.8807 | Rough | 0.1021 | 3.533E-002 | 1.255 | 0.350 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 7.7625 | Rough | 1.5719 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 5.7198 | Rough | 0.9377 | 4.996E-002 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5503 | Smooth | 0.1300 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.3765 | VerySmooth | 0.1318 | 0.107 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | UNHEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | UNHEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0498 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 11 | 0.167 | 0.0279 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
10 | BASEMENT WALL | 24 | 3 | 4 | 0.167 | 0.534 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
11 | iz-EXTERIOR FLOOR | 25 | 3 | 11 | 0.167 | 0.0279 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.1020 | 0.035 | 1.255 | 0.350 | 0.8807 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.9377 | 0.050 | 3.438 | 0.219 | 5.720 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.1299 | 0.072 | 32.003 | 0.183 | 0.5503 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
25 | BSMTWALL_CONSOL_LAYER | 0.0010 | 10.844 | 7.541 | 0.248 | 0.2342E-04 |
26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.9377 | 0.050 | 3.438 | 0.219 | 5.720 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 10 | 0.51360630E-08 | -0.22035233E-13 | 0.91774209E-08 | -0.50676220E-13 |
2 | 9 | -0.14060012E-04 | 0.39159197E-12 | -0.22958088E-04 | 0.29728831E-08 |
3 | 8 | 0.28980689E-02 | 0.65531654E-09 | 0.46215968E-02 | -0.71708779E-05 |
4 | 7 | -0.65978682E-01 | 0.13350779E-06 | -0.16306378 | 0.13238707E-02 |
5 | 6 | 0.64596177 | 0.50193482E-05 | 2.1320981 | -0.28125917E-01 |
6 | 5 | -3.4215999 | 0.48298777E-04 | -13.652056 | 0.25148823 |
7 | 4 | 10.645660 | 0.13839053E-03 | 47.881148 | -1.1749737 |
8 | 3 | -19.924231 | 0.11919231E-03 | -96.040791 | 3.0621859 |
9 | 2 | 21.976583 | 0.26462555E-04 | 109.48934 | -4.4404618 |
10 | 1 | -13.118296 | 0.91387708E-06 | -65.855375 | 3.3273744 |
11 | 0 | 3.2593552 | 0.33613880E-09 | 16.204438 | |
12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
18 | 11 | 0.76541396E-16 | -0.66093266E-16 | -0.60929972E-11 | -0.23847962E-16 |
19 | 10 | 0.39406090E-10 | -0.28120572E-15 | 0.79946244E-05 | -0.23561984E-10 |
20 | 9 | -0.38001770E-04 | 0.83058929E-12 | -0.94209313E-03 | 0.22722403E-04 |
21 | 8 | 0.34824356E-02 | 0.73535950E-09 | 0.22619169E-01 | -0.20949597E-02 |
22 | 7 | -0.63320596E-01 | 0.66026276E-07 | -0.25112985 | 0.39001137E-01 |
23 | 6 | 0.51991450 | 0.13029552E-05 | 1.5768494 | -0.32985332 |
24 | 5 | -2.3541315 | 0.76249747E-05 | -6.0660500 | 1.5461930 |
25 | 4 | 6.3451018 | 0.14779851E-04 | 14.743171 | -4.3333891 |
26 | 3 | -10.407307 | 0.93590033E-05 | -22.616366 | 7.4172847 |
27 | 2 | 10.167838 | 0.16508793E-05 | 21.148526 | -7.5827206 |
28 | 1 | -5.4301916 | 0.50559118E-07 | -10.971024 | 4.2453367 |
29 | 0 | 1.2186872 | 0.30513734E-10 | 2.4143736 | |
30 | 12 | 0.94888791E-16 | -0.11237443E-15 | 0.21480527E-09 | -0.52606005E-16 |
31 | 11 | -0.44509090E-09 | -0.12338758E-15 | -0.11566016E-03 | 0.28501063E-09 |
32 | 10 | 0.60393314E-04 | 0.62564840E-13 | 0.62960490E-02 | -0.38672578E-04 |
33 | 9 | -0.20055671E-02 | 0.85912012E-10 | -0.12885789 | 0.13084700E-02 |
34 | 8 | 0.28697042E-01 | 0.10381403E-07 | 1.3966036 | -0.19129448E-01 |
35 | 7 | -0.23229993 | 0.28493476E-06 | -9.1473517 | 0.15872626 |
36 | 6 | 1.1750436 | 0.24973161E-05 | 38.552224 | -0.82592201 |
37 | 5 | -3.8729952 | 0.80040830E-05 | -107.65441 | 2.8111251 |
38 | 4 | 8.4143451 | 0.96510929E-05 | 200.56463 | -6.3313915 |
39 | 3 | -11.897084 | 0.41099356E-05 | -245.77565 | 9.3152582 |
40 | 2 | 10.487404 | 0.50788650E-06 | 189.69676 | -8.5734564 |
41 | 1 | -5.2147174 | 0.10902359E-07 | -83.415737 | 4.4633233 |
42 | 0 | 1.1135774 | 0.38882120E-11 | 15.905642 | |
43 | 12 | 0.21480527E-09 | -0.11237443E-15 | 0.94888791E-16 | -0.52606005E-16 |
44 | 11 | -0.11566016E-03 | -0.12338758E-15 | -0.44509090E-09 | 0.28501063E-09 |
45 | 10 | 0.62960490E-02 | 0.62564840E-13 | 0.60393314E-04 | -0.38672578E-04 |
46 | 9 | -0.12885789 | 0.85912012E-10 | -0.20055671E-02 | 0.13084700E-02 |
47 | 8 | 1.3966036 | 0.10381403E-07 | 0.28697042E-01 | -0.19129448E-01 |
48 | 7 | -9.1473517 | 0.28493476E-06 | -0.23229993 | 0.15872626 |
49 | 6 | 38.552224 | 0.24973161E-05 | 1.1750436 | -0.82592201 |
50 | 5 | -107.65441 | 0.80040830E-05 | -3.8729952 | 2.8111251 |
51 | 4 | 200.56463 | 0.96510929E-05 | 8.4143451 | -6.3313915 |
52 | 3 | -245.77565 | 0.41099356E-05 | -11.897084 | 9.3152582 |
53 | 2 | 189.69676 | 0.50788650E-06 | 10.487404 | -8.5734564 |
54 | 1 | -83.415737 | 0.10902359E-07 | -5.2147174 | 4.4633233 |
55 | 0 | 15.905642 | 0.38882120E-11 | 1.1135774 | |
56 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
57 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
58 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
59 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
60 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
61 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
62 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
63 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
64 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
65 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
66 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
67 | 5 | -0.47059848E-07 | 0.10808286E-07 | -0.47059848E-07 | 0.33552267E-09 |
68 | 4 | 0.23241354E-03 | 0.64872557E-04 | 0.23241354E-03 | -0.29116876E-05 |
69 | 3 | -0.69106029E-01 | 0.14208819E-01 | -0.69106029E-01 | 0.18005536E-02 |
70 | 2 | 1.8030591 | 0.23437818 | 1.8030591 | -0.90752678E-01 |
71 | 1 | -7.5310044 | 0.40520073 | -7.5310044 | 0.70046896 |
72 | 0 | 6.5027572 | 0.52085640E-01 | 6.5027572 | |
73 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
74 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
75 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
76 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
77 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
78 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
79 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
80 | 4 | 0.69987904E-07 | 0.26228811E-07 | 0.69987904E-07 | -0.89457852E-14 |
81 | 3 | -0.30987589E-02 | 0.10225415E-02 | -0.30987589E-02 | 0.11234143E-06 |
82 | 2 | 0.81559891 | 0.24124884 | 0.81559891 | -0.23762713E-02 |
83 | 1 | -7.9329461 | 1.4912083 | -7.9329461 | 0.29351368 |
84 | 0 | 9.2684202 | 0.41449462 | 9.2684202 | |
85 | 11 | -0.60929972E-11 | -0.66093266E-16 | 0.76541396E-16 | -0.23847962E-16 |
86 | 10 | 0.79946244E-05 | -0.28120572E-15 | 0.39406090E-10 | -0.23561984E-10 |
87 | 9 | -0.94209313E-03 | 0.83058929E-12 | -0.38001770E-04 | 0.22722403E-04 |
88 | 8 | 0.22619169E-01 | 0.73535950E-09 | 0.34824356E-02 | -0.20949597E-02 |
89 | 7 | -0.25112985 | 0.66026276E-07 | -0.63320596E-01 | 0.39001137E-01 |
90 | 6 | 1.5768494 | 0.13029552E-05 | 0.51991450 | -0.32985332 |
91 | 5 | -6.0660500 | 0.76249747E-05 | -2.3541315 | 1.5461930 |
92 | 4 | 14.743171 | 0.14779851E-04 | 6.3451018 | -4.3333891 |
93 | 3 | -22.616366 | 0.93590033E-05 | -10.407307 | 7.4172847 |
94 | 2 | 21.148526 | 0.16508793E-05 | 10.167838 | -7.5827206 |
95 | 1 | -10.971024 | 0.50559118E-07 | -5.4301916 | 4.2453367 |
96 | 0 | 2.4143736 | 0.30513734E-10 | 1.2186872 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.320 | 0.335 | 0.248 | 0.883 |
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.320 | 0.335 | 0.248 | 0.883 |
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.320 | 0.309 | 4.642E-002 | 0.133 |
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 0.929 | 0.920 | 0.920 |
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 0.906 | 0.900 | 0.900 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | UNHEATEDBSMT | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 9724.32386 | 9724.32386 | 420.08469 | 420.08469 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 75.53660 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 12534.04249 | 12534.04249 | 231.75845 | 231.75845 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 5240.59476 | 5240.59476 | 226.39828 | 226.39828 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 81.32000 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 8788.13663 | 8788.13663 | 162.49405 | 162.49405 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 7864.30505 | 7864.30505 | 339.72453 | 339.72453 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | 77.70920 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 12526.92022 | 12526.92022 | 231.61014 | 231.61014 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 8609.72083 | 8609.72083 | 371.94911 | 371.94911 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 73.48640 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 12535.54241 | 12535.54241 | 231.77963 | 231.77963 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 3693.52828 | 3693.52828 | 159.56206 | 159.56206 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 70.21220 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 8786.81384 | 8786.81384 | 162.46968 | 162.46968 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 6619.88495 | 6619.88495 | 285.97454 | 285.97454 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 73.82300 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 12522.85949 | 12522.85949 | 231.54658 | 231.54658 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 9934.43761 | 9934.43761 | 429.17367 | 429.17367 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.15960 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 9785.02617 | 9785.02617 | 180.93960 | 180.93960 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 5365.66156 | 5365.66156 | 231.80082 | 231.80082 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 80.95280 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 6052.60129 | 6052.60129 | 111.92393 | 111.92393 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 7980.02733 | 7980.02733 | 344.72453 | 344.72453 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 78.01520 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 9776.05769 | 9776.05769 | 180.77392 | 180.77392 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 8796.02845 | 8796.02845 | 379.99995 | 379.99995 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 72.81320 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 9786.16584 | 9786.16584 | 180.96078 | 180.96078 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 3988.20420 | 3988.20420 | 172.29277 | 172.29277 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 69.93680 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 6050.97503 | 6050.97503 | 111.89384 | 111.89384 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6732.25521 | 6732.25521 | 290.82623 | 290.82623 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 74.80220 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 9771.75147 | 9771.75147 | 180.69426 | 180.69426 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 6516.43642 | 6516.43642 | 281.50420 | 281.50420 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.26120 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 14832.03790 | 14832.03790 | 274.23725 | 274.23725 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 7725.33685 | 7725.33685 | 333.72877 | 333.72877 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 78.32120 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 14836.79225 | 14836.79225 | 274.32200 | 274.32200 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 10138.88595 | 10138.88595 | 438.00842 | 438.00842 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.15960 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 14847.48532 | 14847.48532 | 274.53386 | 274.53386 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 4634.54099 | 4634.54099 | 200.21396 | 200.21396 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 70.21220 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 11117.17312 | 11117.17312 | 205.55845 | 205.55845 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 5448.88894 | 5448.88894 | 235.38133 | 235.38133 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 80.76920 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 11119.97308 | 11119.97308 | 205.61036 | 205.61036 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 9397.90263 | 9397.90263 | 405.99571 | 405.99571 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 73.14980 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 14846.66798 | 14846.66798 | 274.51268 | 274.51268 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2815.56 | 420.08469 | 420.08469 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 5242.09 | 231.75845 | 231.75845 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1602.11 | 226.39828 | 226.39828 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 4160.23 | 162.49405 | 162.49405 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2308.99 | 339.72453 | 339.72453 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 5240.03 | 231.61014 | 231.61014 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2464.90 | 371.94911 | 371.94911 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 5242.52 | 231.77963 | 231.77963 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 999.27 | 159.56206 | 159.56206 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 4159.85 | 162.46968 | 162.46968 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1895.03 | 285.97454 | 285.97454 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 5238.86 | 231.54658 | 231.54658 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2856.88 | 429.17367 | 429.17367 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4448.20 | 180.93960 | 180.93960 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1633.07 | 231.80082 | 231.80082 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3370.23 | 111.92393 | 111.92393 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2346.71 | 344.72453 | 344.72453 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4445.61 | 180.77392 | 180.77392 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2509.23 | 379.99995 | 379.99995 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4448.53 | 180.96078 | 180.96078 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1080.49 | 172.29277 | 172.29277 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3369.77 | 111.89384 | 111.89384 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1941.24 | 290.82623 | 290.82623 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4444.36 | 180.69426 | 180.69426 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 2915.92 | 438.00842 | 438.00842 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 5910.24 | 274.53386 | 274.53386 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1654.52 | 235.38133 | 235.38133 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 4833.70 | 205.61036 | 205.61036 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2277.46 | 333.72877 | 333.72877 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 5907.16 | 274.32200 | 274.32200 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 2687.76 | 405.99571 | 405.99571 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 5910.01 | 274.51268 | 274.51268 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1271.00 | 200.21396 | 200.21396 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 4832.89 | 205.55845 | 205.55845 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 1885.37 | 281.50420 | 281.50420 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 5905.78 | 274.23725 | 274.23725 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
2 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
3 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
4 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
5 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 420.08469 |
7 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
8 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
9 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
10 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
11 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 226.39828 |
13 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
14 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
15 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
16 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
17 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 339.72453 |
19 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
20 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
21 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
22 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
23 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
24 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 371.94911 |
25 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
26 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
27 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
28 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
29 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
30 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 162.46968 |
31 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
32 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
33 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
34 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
35 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
36 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 285.97454 |
37 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
38 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
39 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
40 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
41 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
42 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 429.17367 |
43 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
44 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
45 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
46 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
47 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
48 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 231.80082 |
49 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
50 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
51 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
52 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
53 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
54 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 344.72453 |
55 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
56 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
57 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
58 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
59 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
60 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 379.99995 |
61 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
62 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
63 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
64 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
65 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
66 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 172.29277 |
67 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
68 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
69 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
70 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
71 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
72 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 290.82623 |
73 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
74 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
75 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
76 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
77 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
78 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 281.50420 |
79 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
80 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
81 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
82 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
83 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
84 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 333.72877 |
85 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
86 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
87 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
88 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
89 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
90 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 438.00842 |
91 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
92 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
93 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
94 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
95 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 205.55845 |
97 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
98 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
99 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
100 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
101 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
102 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 235.38133 |
103 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
104 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
105 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
106 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
107 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
108 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 405.99571 |
109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 420.08469 |
110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 420.08469 |
111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 420.08469 |
112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 420.08469 |
113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 420.08469 |
114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 420.08469 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 226.39828 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 226.39828 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 226.39828 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 226.39828 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 226.39828 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 226.39828 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 339.72453 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 339.72453 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 339.72453 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 339.72453 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 339.72453 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 339.72453 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 371.94911 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 371.94911 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 371.94911 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 371.94911 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 371.94911 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 371.94911 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 162.46968 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 162.46968 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 162.46968 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 162.46968 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 162.46968 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 162.46968 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 285.97454 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 285.97454 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 285.97454 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 285.97454 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 285.97454 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 285.97454 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 429.17367 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 429.17367 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 429.17367 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 429.17367 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 429.17367 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 429.17367 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 231.80082 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 231.80082 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 231.80082 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 231.80082 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 231.80082 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 231.80082 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 344.72453 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 344.72453 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 344.72453 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 344.72453 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 344.72453 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 344.72453 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 379.99995 |
182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 379.99995 |
183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 379.99995 |
184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 379.99995 |
185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 379.99995 |
186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 379.99995 |
187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 172.29277 |
190 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 172.29277 |
191 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 172.29277 |
192 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 172.29277 |
193 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 172.29277 |
194 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 172.29277 |
195 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
196 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
197 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 290.82623 |
198 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 290.82623 |
199 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 290.82623 |
200 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 290.82623 |
201 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 290.82623 |
202 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 290.82623 |
203 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
204 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
205 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 438.00842 |
206 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 438.00842 |
207 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 438.00842 |
208 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 438.00842 |
209 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 438.00842 |
210 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 438.00842 |
211 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
212 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
213 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 235.38133 |
214 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 235.38133 |
215 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 235.38133 |
216 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 235.38133 |
217 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 235.38133 |
218 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 235.38133 |
219 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
220 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
221 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 333.72877 |
222 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 333.72877 |
223 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 333.72877 |
224 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 333.72877 |
225 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 333.72877 |
226 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 333.72877 |
227 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
228 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
229 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 405.99571 |
230 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 405.99571 |
231 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 405.99571 |
232 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 405.99571 |
233 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 405.99571 |
234 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 405.99571 |
235 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
236 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
237 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 205.55845 |
238 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 205.55845 |
239 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 205.55845 |
240 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 205.55845 |
241 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 205.55845 |
242 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 205.55845 |
243 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
244 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
245 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 281.50420 |
246 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 281.50420 |
247 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 281.50420 |
248 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 281.50420 |
249 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 281.50420 |
250 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 281.50420 |
251 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
252 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
253 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 420.08469 |
254 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 226.39828 |
255 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 339.72453 |
256 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 371.94911 |
257 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 162.46968 |
258 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 285.97454 |
259 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 429.17367 |
260 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 231.80082 |
261 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 344.72453 |
262 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 379.99995 |
263 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 172.29277 |
264 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 290.82623 |
265 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 438.00842 |
266 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 235.38133 |
267 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 333.72877 |
268 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 405.99571 |
269 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 205.55845 |
270 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 281.50420 |
271 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 420.08469 |
272 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.93327 |
273 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
274 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 420.08469 |
275 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 420.08469 |
276 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 420.08469 |
277 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 11199.21872 |
278 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.93327 |
279 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 17886.00685 |
280 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
281 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 420.08469 |
282 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 420.08469 |
283 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11199.21872 |
284 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17886.00685 |
285 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 226.39828 |
286 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.50295 |
287 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
288 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 226.39828 |
289 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 226.39828 |
290 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 226.39828 |
291 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 6035.39106 |
292 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.50295 |
293 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 14194.70950 |
294 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
295 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 226.39828 |
296 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 226.39828 |
297 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 6035.39106 |
298 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 14194.70950 |
299 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 339.72453 |
300 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.75474 |
301 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
302 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 339.72453 |
303 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 339.72453 |
304 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 339.72453 |
305 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 9056.91970 |
306 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.75474 |
307 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 17878.98830 |
308 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
309 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 339.72453 |
310 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 339.72453 |
311 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 9056.91970 |
312 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17878.98830 |
313 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 371.94911 |
314 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.82630 |
315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
316 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 371.94911 |
317 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 371.94911 |
318 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 371.94911 |
319 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 9915.62415 |
320 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.82630 |
321 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 17887.48489 |
322 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
323 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 371.94911 |
324 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 371.94911 |
325 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 9915.62415 |
326 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17887.48489 |
327 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 162.46968 |
328 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.36094 |
329 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
330 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 162.46968 |
331 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 162.46968 |
332 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 162.46968 |
333 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 4331.26285 |
334 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.36094 |
335 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 14193.40598 |
336 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
337 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 162.46968 |
338 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 162.46968 |
339 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 4331.26285 |
340 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 14193.40598 |
341 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 285.97454 |
342 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.63532 |
343 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
344 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 285.97454 |
345 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 285.97454 |
346 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 285.97454 |
347 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 7623.81596 |
348 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.63532 |
349 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 17874.98674 |
350 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
351 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 285.97454 |
352 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 285.97454 |
353 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 7623.81596 |
354 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17874.98674 |
355 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 429.17367 |
356 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95344 |
357 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
358 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 429.17367 |
359 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 429.17367 |
360 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 429.17367 |
361 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11441.28532 |
362 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.95344 |
363 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 15177.24963 |
364 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
365 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 429.17367 |
366 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 429.17367 |
367 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11441.28532 |
368 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15177.24963 |
369 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 231.80082 |
370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.51495 |
371 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
372 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 231.80082 |
373 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 231.80082 |
374 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 231.80082 |
375 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 6179.45464 |
376 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.51495 |
377 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11499.24124 |
378 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
379 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 231.80082 |
380 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 231.80082 |
381 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 6179.45464 |
382 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11499.24124 |
383 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 344.72453 |
384 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.76585 |
385 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
386 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 344.72453 |
387 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 344.72453 |
388 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 344.72453 |
389 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 9190.21753 |
390 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.76585 |
391 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 15168.41173 |
392 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 344.72453 |
394 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 344.72453 |
395 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 9190.21753 |
396 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15168.41173 |
397 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 379.99995 |
398 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.84419 |
399 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
400 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 379.99995 |
401 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 379.99995 |
402 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 379.99995 |
403 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 10130.22172 |
404 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.84419 |
405 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 15178.37269 |
406 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
407 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 379.99995 |
408 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 379.99995 |
409 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 10130.22172 |
410 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15178.37269 |
411 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 172.29277 |
412 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.38276 |
413 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
414 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 172.29277 |
415 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 172.29277 |
416 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 172.29277 |
417 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4593.13637 |
418 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.38276 |
419 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 11497.63866 |
420 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
421 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 172.29277 |
422 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 172.29277 |
423 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 4593.13637 |
424 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11497.63866 |
425 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 290.82623 |
426 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.64610 |
427 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
428 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 290.82623 |
429 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 290.82623 |
430 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 290.82623 |
431 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 7753.24012 |
432 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.64610 |
433 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 15164.16826 |
434 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 290.82623 |
436 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 290.82623 |
437 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 7753.24012 |
438 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15164.16826 |
439 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 438.00842 |
440 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.97306 |
441 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
442 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 438.00842 |
443 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 438.00842 |
444 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 438.00842 |
445 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 11676.70864 |
446 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.97306 |
447 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 20165.75427 |
448 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
449 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 438.00842 |
450 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 438.00842 |
451 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 11676.70864 |
452 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 20165.75427 |
453 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 235.38133 |
454 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.52294 |
455 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
456 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 235.38133 |
457 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 235.38133 |
458 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 235.38133 |
459 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6275.26612 |
460 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.52294 |
461 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 16492.58153 |
462 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
463 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 235.38133 |
464 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 235.38133 |
465 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 6275.26612 |
466 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 16492.58153 |
467 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 333.72877 |
468 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.74141 |
469 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
470 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 333.72877 |
471 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 333.72877 |
472 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 333.72877 |
473 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 8896.87608 |
474 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.74141 |
475 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 20155.21699 |
476 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
477 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 333.72877 |
478 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 333.72877 |
479 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 8896.87608 |
480 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 20155.21699 |
481 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 405.99571 |
482 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.90195 |
483 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
484 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 405.99571 |
485 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 405.99571 |
486 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 405.99571 |
487 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 10823.35714 |
488 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.90195 |
489 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 20164.94887 |
490 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
491 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 405.99571 |
492 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 405.99571 |
493 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 10823.35714 |
494 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 20164.94887 |
495 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 205.55845 |
496 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.45666 |
497 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
498 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 205.55845 |
499 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 205.55845 |
500 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 205.55845 |
501 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 5479.96311 |
502 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.45666 |
503 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 16489.82232 |
504 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
505 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 205.55845 |
506 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 205.55845 |
507 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 5479.96311 |
508 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 16489.82232 |
509 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 281.50420 |
510 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.62539 |
511 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
512 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 281.50420 |
513 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 281.50420 |
514 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 281.50420 |
515 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 7504.66165 |
516 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.62539 |
517 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 20150.53190 |
518 | AirLoopHVAC:UnitaryHeatPump:AirToAir | HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
519 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 281.50420 |
520 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 281.50420 |
521 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Heating Capacity [Btu/h] | 7504.66165 |
522 | Coil:Heating:Electric | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 20150.53190 |
523 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
524 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
525 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
526 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
527 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
528 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
529 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
530 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
531 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
532 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
533 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
534 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
535 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
536 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
537 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
538 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
539 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
540 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
541 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
542 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
543 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
544 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
545 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
546 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
547 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
548 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
549 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
550 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
551 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
552 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
553 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
554 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
555 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
556 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
557 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
558 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
559 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
560 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
561 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
562 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
563 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
564 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
565 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
566 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
567 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
568 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
569 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
570 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
571 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
572 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
573 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
574 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
575 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
576 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
577 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
578 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
579 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
580 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
581 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
582 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
583 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
584 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
585 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
586 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
587 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
588 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
589 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
590 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
591 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
592 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
593 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
594 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
595 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
596 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
597 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
598 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
599 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
600 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
601 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
602 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
603 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
604 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
605 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
606 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
607 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
608 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
609 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
610 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
611 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
612 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.8 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.6 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.8 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.4 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
Component Type | Component Name | High Temperature Heating (net) Rating Capacity {Btu/h} | Low Temperature Heating (net) Rating Capacity {Btu/h} | HSPF {Btu/W-h} | Region Number | |
1 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 11735.9 | 6536.4 | 7.89 | 4 |
2 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 6324.5 | 3522.5 | 7.88 | 4 |
3 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 9491.2 | 5285.9 | 7.85 | 4 |
4 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 10390.9 | 5787.1 | 7.88 | 4 |
5 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 4539.0 | 2528.0 | 7.84 | 4 |
6 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 7989.2 | 4449.6 | 7.72 | 4 |
7 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 11989.8 | 6677.6 | 7.89 | 4 |
8 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 6475.6 | 3606.5 | 7.87 | 4 |
9 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 9630.7 | 5363.7 | 7.85 | 4 |
10 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 10615.8 | 5912.3 | 7.89 | 4 |
11 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 4813.3 | 2680.8 | 7.85 | 4 |
12 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 8125.0 | 4525.0 | 7.74 | 4 |
13 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 12236.5 | 6814.8 | 7.88 | 4 |
14 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 6575.9 | 3662.4 | 7.87 | 4 |
15 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 9323.3 | 5192.4 | 7.84 | 4 |
16 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 11342.2 | 6317.0 | 7.90 | 4 |
17 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 5742.7 | 3198.4 | 7.90 | 4 |
18 | Coil:Heating:DX:SingleSpeed | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 7864.3 | 4380.0 | 7.70 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 01/21 | 01/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 9 |
2 | 6 |
3 | 8 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | -43.4 | 0.00 | DefaultMultipliers | Wetbulb | -41.90 | {C} | 14. | 20 | 59.1 | 0.00 | No | No |
2 | 81.32 | 10.20 | DefaultMultipliers | Wetbulb | 16.10 | {C} | 14. | 180 | 610.3 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 21 | 1229.0 | 0.1415 | 5.7310E-002 | 1.0 | -11.15 | -20. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | UNHEATEDBSMT | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000624804 | 0.000367469 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.001305574 | 0.000236410 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.007045343 | 0.013080461 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.023421738 | 0.022570436 | Pass | Pass | 0.003110334 | 0.003010037 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.001828122 | 0.005659509 | Pass | Pass | 0.006691606 | 0.013009609 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.007577438 | 0.015578282 | Pass | Pass | 0.005452252 | 0.011057992 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.026712472 | 0.026775277 | Pass | Pass | 0.003687429 | 0.003697168 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.022476014 | 0.021218672 | Pass | Pass | 0.002352686 | 0.002232011 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.008841458 | 0.016179488 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.022090781 | 0.024454200 | Pass | Pass | 0.004144814 | 0.009340327 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.004642612 | 0.010638238 | Pass | Pass | 0.007474721 | 0.014713793 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.003828254 | 0.008761831 | Pass | Pass | 0.007775310 | 0.015151669 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.024515123 | 0.023009070 | Pass | Pass | 0.003686498 | 0.003463339 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.027377078 | 0.022405062 | Pass | Pass | 0.000897463 | 0.001586960 | Pass | Pass |
15 | ATTIC | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000148751 | 0.000088923 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.021578327 | 0.019974744 | Pass | Pass | 0.002057126 | 0.001912923 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.020345924 | 0.018645466 | Pass | Pass | 0.002043305 | 0.001884133 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.005800017 | 0.009981654 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.023684238 | 0.022325857 | Pass | Pass | 0.002644336 | 0.002499162 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.022471784 | 0.020802497 | Pass | Pass | 0.002607607 | 0.002421711 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.006893222 | 0.013787359 | Pass | Pass | 0.004572215 | 0.009110920 | Pass | Pass |
22 | UNHEATEDBSMT | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.022056965 | 0.010615950 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.040053978 | 0.021922017 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000095681 | 0.000381946 | Pass | Pass | 0.116097068 | 0.069676088 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.001853205 | 0.006510614 | Pass | Pass | 0.086615774 | 0.066879306 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000090373 | 0.000385686 | Pass | Pass | 0.104707018 | 0.079473452 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000089891 | 0.000378102 | Pass | Pass | 0.106627152 | 0.075464034 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000063732 | 0.000366450 | Pass | Pass | 0.068167360 | 0.071227458 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000085427 | 0.000384887 | Pass | Pass | 0.104702794 | 0.089147650 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000095536 | 0.000382359 | Pass | Pass | 0.101592290 | 0.060535509 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.001742140 | 0.006096601 | Pass | Pass | 0.072574503 | 0.057669812 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000113227 | 0.000428556 | Pass | Pass | 0.088562324 | 0.063633549 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000090024 | 0.000379824 | Pass | Pass | 0.091319222 | 0.065673545 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000076104 | 0.000377905 | Pass | Pass | 0.055530621 | 0.059399404 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000084997 | 0.000381983 | Pass | Pass | 0.087284406 | 0.070360482 | Pass | Pass |
36 | ATTIC | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.468501167 | 0.284499246 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000084073 | 0.000376437 | Pass | Pass | 0.084260453 | 0.072644691 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000087943 | 0.000367770 | Pass | Pass | 0.087572788 | 0.066459375 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000098219 | 0.000388184 | Pass | Pass | 0.106961377 | 0.062922810 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000078907 | 0.000379890 | Pass | Pass | 0.063282714 | 0.057477919 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.001457855 | 0.005185484 | Pass | Pass | 0.076817283 | 0.062218943 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000093474 | 0.000386247 | Pass | Pass | 0.096567092 | 0.065225737 | Pass | Pass |
43 | UNHEATEDBSMT | RunPeriod: ANNUAL | 0.002979376 | 0.002236986 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.002700821 | 0.002065534 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.018206759 | 0.026640185 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.025147250 | 0.041903501 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.019056370 | 0.027667154 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017577494 | 0.025983799 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.024269565 | 0.041184001 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.018248852 | 0.026133444 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000040941 | 0.000321446 | Pass | Pass | 0.018752213 | 0.033030959 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000054389 | 0.000437297 | Pass | Pass | 0.033134679 | 0.063262038 | Pass | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.019481207 | 0.034079950 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017670216 | 0.032443988 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.031217511 | 0.062164452 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.018442075 | 0.032578570 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.091548350 | 0.081819701 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.014291932 | 0.019662361 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.014607333 | 0.020413863 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.014012774 | 0.019875456 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017222435 | 0.028399279 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017533125 | 0.028692536 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.013797473 | 0.019595983 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 1425407.98 | 233756.76 | 0.00 | 0.00 | 38927.52 | 1698095.55 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -43.4 | 0.00 | -43.4 | Wetbulb [F] | 59.06 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 81.32 | 18.36 | 60.98 | Wetbulb [F] | 610.27 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.320 | 0.335 | 0.883 | ||||||||||||
North Total or Average | 531.68 | 0.320 | 0.335 | 0.883 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.320 | 0.335 | 0.883 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3333 | 43219.92 | 14404.00 | 12960.20 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1257.69 | 5508.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11199.22 | 8966.71 | 2232.51 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6035.39 | 4832.27 | 1203.12 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9056.92 | 7251.47 | 1805.45 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9915.62 | 7939.00 | 1976.63 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4331.26 | 3467.85 | 863.41 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7623.82 | 6104.05 | 1519.77 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11441.29 | 9160.53 | 2280.76 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6179.45 | 4947.61 | 1231.84 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9190.22 | 7358.20 | 1832.02 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10130.22 | 8110.82 | 2019.41 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4593.14 | 3677.52 | 915.62 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7753.24 | 6207.67 | 1545.57 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11676.71 | 9349.02 | 2327.69 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6275.27 | 5024.32 | 1250.94 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8896.88 | 7123.33 | 1773.55 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10823.36 | 8665.78 | 2157.58 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 5479.96 | 4387.56 | 1092.40 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7504.66 | 6008.65 | 1496.01 | 0.80 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.8 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.6 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.8 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.4 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.26 | 11.11 | 11.62 | 10.99 | 10.86 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 11736.0 | 6536.2 | 7.89 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6324.7 | 3522.5 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9491.0 | 5285.9 | 7.85 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 10390.9 | 5787.1 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 4538.8 | 2527.9 | 7.84 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 7989.2 | 4449.5 | 7.72 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 11989.6 | 6677.5 | 7.89 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 6475.6 | 3606.5 | 7.87 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9630.7 | 5363.7 | 7.85 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 10615.7 | 5912.3 | 7.89 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 4813.3 | 2680.7 | 7.85 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 8124.8 | 4525.0 | 7.74 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12236.3 | 6814.9 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6576.0 | 3662.5 | 7.87 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 9323.3 | 5192.5 | 7.84 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 11342.1 | 6316.9 | 7.90 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 5742.6 | 3198.3 | 7.90 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 7864.3 | 4380.0 | 7.70 | 4 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 11199.22 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 17886.01 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6035.39 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 14194.71 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9056.92 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 17878.99 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 9915.62 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 17887.48 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 4331.26 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 14193.41 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 7623.82 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 17874.99 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 11441.29 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 15177.25 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 6179.45 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 11499.24 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 9190.22 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 15168.41 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 10130.22 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 15178.37 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 4593.14 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 11497.64 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 7753.24 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 15164.17 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 11676.71 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 20165.75 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6275.27 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 16492.58 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 8896.88 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 20155.22 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 10823.36 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 20164.95 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 5479.96 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 16489.82 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 7504.66 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 20150.53 | 1.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 420.09 | 158.46 | 0.38 | 1.00 | 2.32 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 226.39 | 85.39 | 0.38 | 1.00 | 3.26 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 339.73 | 128.14 | 0.38 | 1.00 | 2.58 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 371.94 | 140.29 | 0.38 | 1.00 | 2.46 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 162.47 | 61.28 | 0.38 | 1.00 | 4.05 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 285.98 | 107.87 | 0.38 | 1.00 | 2.84 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 429.17 | 161.88 | 0.38 | 1.00 | 2.30 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 231.80 | 87.43 | 0.38 | 1.00 | 3.21 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 344.73 | 130.03 | 0.38 | 1.00 | 2.56 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 379.99 | 143.33 | 0.38 | 1.00 | 2.44 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 172.29 | 64.99 | 0.38 | 1.00 | 3.89 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 290.83 | 109.70 | 0.38 | 1.00 | 2.81 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 438.00 | 165.21 | 0.38 | 1.00 | 2.27 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 235.39 | 88.79 | 0.38 | 1.00 | 3.18 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 333.73 | 125.88 | 0.38 | 1.00 | 2.61 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 405.99 | 153.14 | 0.38 | 1.00 | 2.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 205.56 | 77.54 | 0.38 | 1.00 | 3.47 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 281.51 | 106.18 | 0.38 | 1.00 | 2.86 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9724.32 | 9724.32 | 8.10 | 420.093 | 420.093 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 75.00 | 75.00 | 0.00833 | 75.54 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5240.59 | 5240.59 | 4.37 | 226.393 | 226.393 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 75.00 | 75.00 | 0.00825 | 81.32 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7864.31 | 7864.31 | 6.55 | 339.733 | 339.733 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | 75.00 | 75.00 | 0.00820 | 77.71 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8609.72 | 8609.72 | 7.17 | 371.944 | 371.944 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 75.00 | 75.00 | 0.00837 | 73.49 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3693.53 | 3693.53 | 3.08 | 159.562 | 159.562 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 75.00 | 75.00 | 0.00865 | 70.21 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6619.88 | 6619.88 | 5.51 | 285.976 | 285.976 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 75.00 | 75.00 | 0.00824 | 73.82 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9934.44 | 9934.44 | 8.27 | 429.173 | 429.173 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00836 | 74.16 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5365.66 | 5365.66 | 4.47 | 231.797 | 231.797 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 75.00 | 75.00 | 0.00829 | 80.95 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7980.03 | 7980.03 | 6.65 | 344.734 | 344.734 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 75.00 | 75.00 | 0.00823 | 78.02 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8796.03 | 8796.03 | 7.33 | 379.994 | 379.994 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 75.00 | 75.00 | 0.00837 | 72.81 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3988.20 | 3988.20 | 3.32 | 172.293 | 172.293 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 75.00 | 75.00 | 0.00867 | 69.94 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6732.26 | 6732.26 | 5.61 | 290.831 | 290.831 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 75.00 | 75.00 | 0.00826 | 74.80 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6516.44 | 6516.44 | 5.43 | 281.507 | 281.507 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.00 | 75.00 | 0.00823 | 75.26 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7725.34 | 7725.34 | 6.43 | 333.730 | 333.730 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 75.00 | 75.00 | 0.00821 | 78.32 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10138.89 | 10138.89 | 8.45 | 438.004 | 438.004 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00834 | 74.16 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4634.54 | 4634.54 | 3.86 | 200.214 | 200.214 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 75.00 | 75.00 | 0.00853 | 70.21 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5448.89 | 5448.89 | 4.54 | 235.391 | 235.391 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 75.00 | 75.00 | 0.00825 | 80.77 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9397.90 | 9397.90 | 7.83 | 405.994 | 405.994 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 75.00 | 75.00 | 0.00834 | 73.15 | 0.00700 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12534.04 | 12534.04 | 10.44 | 231.752 | 231.752 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00701 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8788.14 | 8788.14 | 7.32 | 162.494 | 162.494 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00683 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12526.92 | 12526.92 | 10.43 | 231.620 | 231.620 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00701 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12535.54 | 12535.54 | 10.44 | 231.780 | 231.780 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00701 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8786.81 | 8786.81 | 7.32 | 162.470 | 162.470 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00683 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12522.86 | 12522.86 | 10.43 | 231.545 | 231.545 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00701 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9785.03 | 9785.03 | 8.15 | 180.940 | 180.940 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00754 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6052.60 | 6052.60 | 5.04 | 111.924 | 111.924 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00757 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9776.06 | 9776.06 | 8.14 | 180.774 | 180.774 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00754 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9786.17 | 9786.17 | 8.15 | 180.961 | 180.961 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00754 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6050.98 | 6050.98 | 5.04 | 111.894 | 111.894 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00757 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9771.75 | 9771.75 | 8.14 | 180.694 | 180.694 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00754 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 14832.04 | 14832.04 | 12.35 | 274.242 | 274.242 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00715 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 14836.79 | 14836.79 | 12.36 | 274.330 | 274.330 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00715 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 14847.49 | 14847.49 | 12.37 | 274.527 | 274.527 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00715 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 11117.17 | 11117.17 | 9.26 | 205.558 | 205.558 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00704 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 11119.97 | 11119.97 | 9.26 | 205.610 | 205.610 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00704 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 14846.67 | 14846.67 | 12.37 | 274.512 | 274.512 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00715 | -43.4 | 0.00006 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 420.09 | 420.09 | 231.75 | 231.75 | 420.0930 | 420.0930 | 420.0930 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 226.39 | 226.39 | 162.49 | 162.49 | 226.3931 | 226.3931 | 226.3931 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 339.73 | 339.73 | 231.62 | 231.62 | 339.7334 | 339.7334 | 339.7334 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 371.94 | 371.94 | 231.78 | 231.78 | 371.9442 | 371.9442 | 371.9442 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 159.56 | 159.56 | 162.47 | 162.47 | 162.4697 | 162.4697 | 162.4697 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 285.98 | 285.98 | 231.55 | 231.55 | 285.9764 | 285.9764 | 285.9764 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.17 | 429.17 | 180.94 | 180.94 | 429.1732 | 429.1732 | 429.1732 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 231.80 | 231.80 | 111.92 | 111.92 | 231.7971 | 231.7971 | 231.7971 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 344.73 | 344.73 | 180.77 | 180.77 | 344.7335 | 344.7335 | 344.7335 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 379.99 | 379.99 | 180.96 | 180.96 | 379.9940 | 379.9940 | 379.9940 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 172.29 | 172.29 | 111.89 | 111.89 | 172.2928 | 172.2928 | 172.2928 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 290.83 | 290.83 | 180.69 | 180.69 | 290.8312 | 290.8312 | 290.8312 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.00 | 438.00 | 274.53 | 274.53 | 438.0041 | 438.0041 | 438.0041 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 235.39 | 235.39 | 205.61 | 205.61 | 235.3910 | 235.3910 | 235.3910 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.73 | 333.73 | 274.33 | 274.33 | 333.7300 | 333.7300 | 333.7300 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 405.99 | 405.99 | 274.51 | 274.51 | 405.9941 | 405.9941 | 405.9941 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 200.21 | 200.21 | 205.56 | 205.56 | 205.5585 | 205.5585 | 205.5585 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 281.51 | 281.51 | 274.24 | 274.24 | 281.5068 | 281.5068 | 281.5068 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 11199.219 | 8966.713 | 420.093040 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 11322.94 | 10959.00 | 420.093040 | 76.25 | 61.10 | 0.00818775 | 53.60 | 52.02 | 0.00800000 | 75.54 | 0.00700229 | 58.96 | 10.7107 | 75.00 | 0.00830685 | 44.3306 | 9702.59 | 0.00 | 11197.30 | 8883.88 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 11199.219 | 11199.219 | 420.093040 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11199.22 | 11199.22 | 420.093040 | 59.63 | 51.35 | 0.00626859 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.7107 | 71.99 | 0.00701280 | 41.4899 | 12534.04 | 0.00 | 11213.94 | 11213.94 |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 17886.007 | 17886.007 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17886.01 | 17886.01 | 420.093040 | 59.63 | 51.35 | 0.00626859 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.7107 | 71.99 | 0.00701280 | 41.4899 | 12534.04 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 6035.391 | 4832.268 | 226.393094 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 6186.03 | 6179.07 | 226.393094 | 77.45 | 61.24 | 0.00800666 | 53.60 | 52.02 | 0.00800000 | 81.32 | 0.00700714 | 61.07 | 19.8747 | 75.00 | 0.00825459 | 44.0551 | 5240.59 | 0.00 | 6034.36 | 4787.63 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 6035.391 | 6035.391 | 226.393094 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6035.39 | 6035.39 | 226.393094 | 49.06 | 45.00 | 0.00548763 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.8747 | 71.99 | 0.00683281 | 40.4353 | 8788.14 | 0.00 | 6043.32 | 6043.32 |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 14194.710 | 14194.710 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14194.71 | 14194.71 | 226.393094 | 49.06 | 45.00 | 0.00548763 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.8747 | 71.99 | 0.00683281 | 40.4353 | 8788.14 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 9056.920 | 7251.470 | 339.733424 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | 9216.64 | 9144.33 | 339.733424 | 76.55 | 60.99 | 0.00804523 | 53.60 | 52.02 | 0.00800000 | 77.71 | 0.00700410 | 59.76 | 13.2442 | 75.00 | 0.00820470 | 43.7920 | 7853.52 | 0.00 | 9055.37 | 7184.48 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 9056.920 | 9056.920 | 339.733424 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 9056.92 | 9056.92 | 339.733424 | 56.71 | 49.75 | 0.00609214 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.2442 | 71.99 | 0.00701232 | 41.4871 | 12526.92 | 0.00 | 9068.82 | 9068.82 |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 17878.988 | 17878.988 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17878.99 | 17878.99 | 339.733424 | 56.71 | 49.75 | 0.00609214 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.2442 | 71.99 | 0.00701232 | 41.4871 | 12526.92 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 9915.624 | 7938.997 | 371.944222 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 9990.53 | 9638.64 | 371.944222 | 76.01 | 61.04 | 0.00820446 | 53.60 | 52.02 | 0.00800000 | 73.49 | 0.00700058 | 58.20 | 12.0972 | 75.00 | 0.00837759 | 44.7033 | 8594.32 | 0.00 | 9913.92 | 7865.66 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 9915.624 | 9915.624 | 371.944222 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 9915.62 | 9915.62 | 371.944222 | 58.03 | 50.48 | 0.00617234 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.0972 | 71.99 | 0.00701290 | 41.4905 | 12535.54 | 0.00 | 9928.65 | 9928.65 |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 17887.485 | 17887.485 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17887.48 | 17887.48 | 371.944222 | 58.03 | 50.48 | 0.00617234 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.0972 | 71.99 | 0.00701290 | 41.4905 | 12535.54 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 4331.263 | 3467.848 | 162.469670 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 4362.15 | 4215.68 | 162.469670 | 74.84 | 60.59 | 0.00818565 | 53.60 | 52.02 | 0.00800000 | 70.21 | 0.00699788 | 56.95 | 27.6944 | 75.00 | 0.00866049 | 46.1920 | 3687.64 | 0.00 | 4330.52 | 3435.81 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 4331.263 | 4331.263 | 162.469670 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4331.26 | 4331.26 | 162.469670 | 40.03 | 39.27 | 0.00495826 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 27.6944 | 71.99 | 0.00683266 | 40.4344 | 8786.81 | 0.00 | 4336.95 | 4336.95 |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 14193.406 | 14193.406 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14193.41 | 14193.41 | 162.469670 | 40.03 | 39.27 | 0.00495826 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 27.6944 | 71.99 | 0.00683266 | 40.4344 | 8786.81 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 7623.816 | 6104.048 | 285.976379 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 7707.77 | 7646.27 | 285.976379 | 76.00 | 60.79 | 0.00804505 | 53.60 | 52.02 | 0.00800000 | 73.82 | 0.00700086 | 58.32 | 15.7338 | 75.00 | 0.00823289 | 43.9405 | 6592.99 | 0.00 | 7622.51 | 6047.66 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 7623.816 | 7623.816 | 285.976379 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 7623.82 | 7623.82 | 285.976379 | 53.83 | 48.12 | 0.00591894 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.7338 | 71.99 | 0.00701205 | 41.4855 | 12522.86 | 0.00 | 7633.83 | 7633.83 |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 17874.987 | 17874.987 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17874.99 | 17874.99 | 285.976379 | 53.83 | 48.12 | 0.00591894 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.7338 | 71.99 | 0.00701205 | 41.4855 | 12522.86 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11441.285 | 9160.525 | 429.173181 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11535.41 | 11104.79 | 429.173181 | 76.10 | 61.09 | 0.00821798 | 53.60 | 52.02 | 0.00800000 | 74.16 | 0.00700114 | 58.45 | 10.4841 | 75.00 | 0.00834509 | 44.5322 | 9904.21 | 0.00 | 11439.32 | 9075.90 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11441.285 | 11441.285 | 429.173181 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11441.29 | 11441.29 | 429.173181 | 59.90 | 52.37 | 0.00675279 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.4841 | 72.00 | 0.00753612 | 44.5421 | 9785.03 | 0.00 | 11456.32 | 11456.32 |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 15177.250 | 15177.250 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 15177.25 | 15177.25 | 429.173181 | 59.90 | 52.37 | 0.00675279 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.4841 | 72.00 | 0.00753612 | 44.5421 | 9785.03 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6179.455 | 4947.613 | 231.797052 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 6325.36 | 6284.18 | 231.797052 | 77.34 | 61.26 | 0.00803864 | 53.60 | 52.02 | 0.00800000 | 80.95 | 0.00700683 | 60.93 | 19.4114 | 75.00 | 0.00828689 | 44.2253 | 5363.35 | 0.00 | 6178.39 | 4901.91 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6179.455 | 6179.455 | 231.797052 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6179.45 | 6179.45 | 231.797052 | 49.59 | 46.55 | 0.00611000 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.4114 | 72.00 | 0.00756618 | 44.7160 | 6052.60 | 0.00 | 6187.58 | 6187.58 |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 11499.241 | 11499.241 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11499.24 | 11499.24 | 231.797052 | 49.59 | 46.55 | 0.00611000 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.4114 | 72.00 | 0.00756618 | 44.7160 | 6052.60 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 9190.218 | 7358.196 | 344.733549 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 9354.78 | 9248.55 | 344.733549 | 76.58 | 61.03 | 0.00806579 | 53.60 | 52.02 | 0.00800000 | 78.02 | 0.00700436 | 59.88 | 13.0521 | 75.00 | 0.00822545 | 43.9014 | 7972.95 | 0.00 | 9188.64 | 7290.22 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 9190.218 | 9190.218 | 344.733549 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 9190.22 | 9190.22 | 344.733549 | 56.93 | 50.74 | 0.00656058 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.0521 | 72.00 | 0.00753574 | 44.5399 | 9776.06 | 0.00 | 9202.29 | 9202.29 |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 15168.412 | 15168.412 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 15168.41 | 15168.41 | 344.733549 | 56.93 | 50.74 | 0.00656058 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.0521 | 72.00 | 0.00753574 | 44.5399 | 9776.06 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 10130.222 | 8110.815 | 379.993975 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 10196.50 | 9827.05 | 379.993975 | 75.93 | 61.02 | 0.00820993 | 53.60 | 52.02 | 0.00800000 | 72.81 | 0.00700003 | 57.94 | 11.8410 | 75.00 | 0.00837841 | 44.7077 | 8791.52 | 0.00 | 10128.48 | 8035.89 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 10130.222 | 10130.222 | 379.993975 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 10130.22 | 10130.22 | 379.993975 | 58.33 | 51.52 | 0.00665145 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 11.8410 | 72.00 | 0.00753617 | 44.5424 | 9786.17 | 0.00 | 10143.53 | 10143.53 |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 15178.373 | 15178.373 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 15178.37 | 15178.37 | 379.993975 | 58.33 | 51.52 | 0.00665145 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 11.8410 | 72.00 | 0.00753617 | 44.5424 | 9786.17 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 4593.136 | 3677.519 | 172.292788 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 4620.31 | 4426.39 | 172.292788 | 74.87 | 60.68 | 0.00823437 | 53.60 | 52.02 | 0.00800000 | 69.94 | 0.00699765 | 56.84 | 26.1154 | 75.00 | 0.00867718 | 46.2799 | 3983.83 | 0.00 | 4592.35 | 3643.55 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 4593.136 | 4593.136 | 172.292788 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4593.14 | 4593.14 | 172.292788 | 41.86 | 41.70 | 0.00560701 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 26.1154 | 72.00 | 0.00756607 | 44.7155 | 6050.98 | 0.00 | 4599.17 | 4599.17 |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 11497.639 | 11497.639 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11497.64 | 11497.64 | 172.292788 | 41.86 | 41.70 | 0.00560701 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 26.1154 | 72.00 | 0.00756607 | 44.7155 | 6050.98 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 7753.240 | 6207.672 | 290.831199 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 7846.67 | 7758.97 | 290.831199 | 76.16 | 60.88 | 0.00806369 | 53.60 | 52.02 | 0.00800000 | 74.80 | 0.00700167 | 58.69 | 15.4712 | 75.00 | 0.00825476 | 44.0558 | 6725.37 | 0.00 | 7751.91 | 6150.33 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 7753.240 | 7753.240 | 290.831199 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 7753.24 | 7753.24 | 290.831199 | 54.14 | 49.17 | 0.00637969 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.4712 | 72.00 | 0.00753555 | 44.5388 | 9771.75 | 0.00 | 7763.43 | 7763.43 |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 15164.168 | 15164.168 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 15164.17 | 15164.17 | 290.831199 | 54.14 | 49.17 | 0.00637969 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.4712 | 72.00 | 0.00753555 | 44.5388 | 9771.75 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 11676.709 | 9349.018 | 438.004128 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11776.32 | 11371.20 | 438.004128 | 76.10 | 61.07 | 0.00820029 | 53.60 | 52.02 | 0.00800000 | 74.16 | 0.00700114 | 58.45 | 10.2727 | 75.00 | 0.00832956 | 44.4504 | 10122.19 | 0.00 | 11674.71 | 9262.66 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 11676.709 | 11676.709 | 438.004128 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11676.71 | 11676.71 | 438.004128 | 60.14 | 51.85 | 0.00641914 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.2727 | 71.99 | 0.00714668 | 42.2729 | 14847.49 | 0.00 | 11692.05 | 11692.05 |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 20165.754 | 20165.754 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 20165.75 | 20165.75 | 438.004128 | 60.14 | 51.85 | 0.00641914 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.2727 | 71.99 | 0.00714668 | 42.2729 | 14847.49 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6275.266 | 5024.325 | 235.391029 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 6424.60 | 6411.65 | 235.391029 | 77.29 | 61.20 | 0.00801188 | 53.60 | 52.02 | 0.00800000 | 80.77 | 0.00700668 | 60.87 | 19.1150 | 75.00 | 0.00824787 | 44.0196 | 5445.08 | 0.00 | 6274.19 | 4977.91 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6275.266 | 6275.266 | 235.391029 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6275.27 | 6275.27 | 235.391029 | 49.93 | 45.88 | 0.00570761 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.1150 | 71.99 | 0.00704120 | 41.6547 | 11119.97 | 0.00 | 6283.51 | 6283.51 |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 16492.582 | 16492.582 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 16492.58 | 16492.58 | 235.391029 | 49.93 | 45.88 | 0.00570761 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.1150 | 71.99 | 0.00704120 | 41.6547 | 11119.97 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 8896.876 | 7123.331 | 333.730041 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 9064.94 | 8994.58 | 333.730041 | 76.64 | 61.02 | 0.00804489 | 53.60 | 52.02 | 0.00800000 | 78.32 | 0.00700461 | 59.99 | 13.4824 | 75.00 | 0.00820701 | 43.8041 | 7725.34 | 0.00 | 8895.35 | 7057.53 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 8896.876 | 8896.876 | 333.730041 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 8896.88 | 8896.88 | 333.730041 | 56.43 | 49.82 | 0.00619136 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.4824 | 71.99 | 0.00714614 | 42.2698 | 14836.79 | 0.00 | 8908.57 | 8908.57 |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 20155.217 | 20155.217 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 20155.22 | 20155.22 | 333.730041 | 56.43 | 49.82 | 0.00619136 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.4824 | 71.99 | 0.00714614 | 42.2698 | 14836.79 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 10823.357 | 8665.778 | 405.994124 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 10901.84 | 10541.36 | 405.994124 | 75.98 | 61.01 | 0.00819135 | 53.60 | 52.02 | 0.00800000 | 73.15 | 0.00700030 | 58.07 | 11.0827 | 75.00 | 0.00834854 | 44.5503 | 9385.56 | 0.00 | 10821.50 | 8585.73 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 10823.357 | 10823.357 | 405.994124 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 10823.36 | 10823.36 | 405.994124 | 59.20 | 51.35 | 0.00636175 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 11.0827 | 71.99 | 0.00714664 | 42.2727 | 14846.67 | 0.00 | 10837.58 | 10837.58 |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 20164.949 | 20164.949 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 20164.95 | 20164.95 | 405.994124 | 59.20 | 51.35 | 0.00636175 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 11.0827 | 71.99 | 0.00714664 | 42.2727 | 14846.67 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 5479.963 | 4387.561 | 205.558478 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 5512.90 | 5326.10 | 205.558478 | 75.11 | 60.70 | 0.00818952 | 53.60 | 52.02 | 0.00800000 | 70.21 | 0.00699788 | 56.95 | 21.8891 | 75.00 | 0.00854084 | 45.5625 | 4626.89 | 0.00 | 5479.02 | 4347.03 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 5479.963 | 5479.963 | 205.558478 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5479.96 | 5479.96 | 205.558478 | 46.73 | 43.93 | 0.00551390 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 21.8891 | 71.99 | 0.00704100 | 41.6535 | 11117.17 | 0.00 | 5487.16 | 5487.16 |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 16489.822 | 16489.822 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 16489.82 | 16489.82 | 205.558478 | 46.73 | 43.93 | 0.00551390 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 21.8891 | 71.99 | 0.00704100 | 41.6535 | 11117.17 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 7504.662 | 6008.647 | 281.506791 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 7604.04 | 7555.68 | 281.506791 | 76.23 | 60.86 | 0.00803616 | 53.60 | 52.02 | 0.00800000 | 75.26 | 0.00700206 | 58.86 | 15.9836 | 75.00 | 0.00823060 | 43.9284 | 6504.05 | 0.00 | 7503.37 | 5953.14 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 7504.662 | 7504.662 | 281.506791 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 7504.66 | 7504.66 | 281.506791 | 53.55 | 48.18 | 0.00601404 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.9836 | 71.99 | 0.00714590 | 42.2684 | 14832.04 | 0.00 | 7514.52 | 7514.52 |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 20150.532 | 20150.532 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 20150.53 | 20150.53 | 281.506791 | 53.55 | 48.18 | 0.00601404 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.9836 | 71.99 | 0.00714590 | 42.2684 | 14832.04 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11199.219 | 8966.713 | 420.093040 | -999. | -999.00 | -999.0000 | 1.06415 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 420.093040 | 0.51819911 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 11322.94 | 10959.00 | 0.9891 | 0.51819911 | 420.093040 | 76.25 | 61.10 | 0.00818775 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 540.652 | 10782.29 | 75.54 | 0.00700229 | 58.96 | 44.99498340 | 10.7107 | 75.00 | 0.00832995 | 75.00 | 0.00830685 | 44.3306 | 9702.59 | 0.00 | 11197.30 | 8883.88 | 0.49773416 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11199.219 | 11199.219 | 420.093040 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 420.093040 | 0.51819911 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11199.22 | 11199.22 | 1.0000 | 0.51819911 | 420.093040 | 59.63 | 51.35 | 0.00626859 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11199.22 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.7107 | 71.99 | 0.00701280 | 71.99 | 0.00701280 | 41.4899 | 12534.04 | 0.00 | 11213.94 | 11213.94 | 0.50904237 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17886.007 | 17886.007 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 420.093040 | 0.51819911 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17886.01 | 17886.01 | 1.0000 | 0.51819911 | 420.093040 | 59.63 | 51.35 | 0.00626859 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17886.01 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.7107 | 71.99 | 0.00701280 | 71.99 | 0.00701280 | 41.4899 | 12534.04 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6035.391 | 4832.268 | 226.393094 | -999. | -999.00 | -999.0000 | 1.03470 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 226.393094 | 0.27926361 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 6186.03 | 6179.07 | 0.9756 | 0.27926361 | 226.393094 | 77.45 | 61.24 | 0.00800666 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 291.364 | 5894.67 | 81.32 | 0.00700714 | 61.07 | 44.99498340 | 19.8747 | 75.00 | 0.00825459 | 75.00 | 0.00825459 | 44.0551 | 5240.59 | 0.00 | 6034.36 | 4787.63 | 0.26823481 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6035.391 | 6035.391 | 226.393094 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 226.393094 | 0.27926361 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6035.39 | 6035.39 | 1.0000 | 0.27926361 | 226.393094 | 49.06 | 45.00 | 0.00548763 | 5.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6035.39 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.8747 | 71.99 | 0.00683281 | 71.99 | 0.00683281 | 40.4353 | 8788.14 | 0.00 | 6043.32 | 6043.32 | 0.27432894 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14194.710 | 14194.710 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 226.393094 | 0.27926361 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14194.71 | 14194.71 | 1.0000 | 0.27926361 | 226.393094 | 49.06 | 45.00 | 0.00548763 | 5.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14194.71 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.8747 | 71.99 | 0.00683281 | 71.99 | 0.00683281 | 40.4353 | 8788.14 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9056.920 | 7251.470 | 339.733424 | -999. | -999.00 | -999.0000 | 1.07304 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 339.733424 | 0.41907278 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | Sensible | 9216.64 | 9144.33 | 0.9827 | 0.41907278 | 339.733424 | 76.55 | 60.99 | 0.00804523 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 437.231 | 8779.41 | 77.71 | 0.00700410 | 59.76 | 44.99498340 | 13.2442 | 75.00 | 0.00820417 | 75.00 | 0.00820470 | 43.7920 | 7853.52 | 0.00 | 9055.37 | 7184.48 | 0.40252257 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 9056.920 | 9056.920 | 339.733424 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 339.733424 | 0.41907278 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 9056.92 | 9056.92 | 1.0000 | 0.41907278 | 339.733424 | 56.71 | 49.75 | 0.00609214 | 7.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 9056.92 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.2442 | 71.99 | 0.00701232 | 71.99 | 0.00701232 | 41.4871 | 12526.92 | 0.00 | 9068.82 | 9068.82 | 0.41166763 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17878.988 | 17878.988 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 339.733424 | 0.41907278 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17878.99 | 17878.99 | 1.0000 | 0.41907278 | 339.733424 | 56.71 | 49.75 | 0.00609214 | 7.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17878.99 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.2442 | 71.99 | 0.00701232 | 71.99 | 0.00701232 | 41.4871 | 12526.92 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9915.624 | 7938.997 | 371.944222 | -999. | -999.00 | -999.0000 | 1.07498 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 371.944222 | 0.45880590 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 9990.53 | 9638.64 | 0.9925 | 0.45880590 | 371.944222 | 76.01 | 61.04 | 0.00820446 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 478.685 | 9511.84 | 73.49 | 0.00700058 | 58.20 | 44.99498340 | 12.0972 | 75.00 | 0.00837014 | 75.00 | 0.00837759 | 44.7033 | 8594.32 | 0.00 | 9913.92 | 7865.66 | 0.44068653 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 9915.624 | 9915.624 | 371.944222 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 371.944222 | 0.45880590 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 9915.62 | 9915.62 | 1.0000 | 0.45880590 | 371.944222 | 58.03 | 50.48 | 0.00617234 | 7.2 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 9915.62 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.0972 | 71.99 | 0.00701290 | 71.99 | 0.00701290 | 41.4905 | 12535.54 | 0.00 | 9928.65 | 9928.65 | 0.45069866 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17887.485 | 17887.485 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 371.944222 | 0.45880590 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17887.48 | 17887.48 | 1.0000 | 0.45880590 | 371.944222 | 58.03 | 50.48 | 0.00617234 | 7.2 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17887.48 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.0972 | 71.99 | 0.00701290 | 71.99 | 0.00701290 | 41.4905 | 12535.54 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4331.263 | 3467.848 | 162.469670 | -999. | -999.00 | -999.0000 | 1.13395 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 162.469670 | 0.20041189 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | Sensible | 4362.15 | 4215.68 | 0.9929 | 0.20041189 | 162.469670 | 74.84 | 60.59 | 0.00818565 | 10.7 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 209.095 | 4153.06 | 70.21 | 0.00699788 | 56.95 | 44.99498340 | 27.6944 | 75.00 | 0.00865214 | 75.00 | 0.00866049 | 46.1920 | 3687.64 | 0.00 | 4330.52 | 3435.81 | 0.19249713 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 4331.263 | 4331.263 | 162.469670 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 162.469670 | 0.20041189 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 4331.26 | 4331.26 | 1.0000 | 0.20041189 | 162.469670 | 40.03 | 39.27 | 0.00495826 | 4.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4331.26 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 27.6944 | 71.99 | 0.00683266 | 71.99 | 0.00683266 | 40.4344 | 8786.81 | 0.00 | 4336.95 | 4336.95 | 0.19687055 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14193.406 | 14193.406 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 162.469670 | 0.20041189 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14193.41 | 14193.41 | 1.0000 | 0.20041189 | 162.469670 | 40.03 | 39.27 | 0.00495826 | 4.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14193.41 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 27.6944 | 71.99 | 0.00683266 | 71.99 | 0.00683266 | 40.4344 | 8786.81 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7623.816 | 6104.048 | 285.976379 | -999. | -999.00 | -999.0000 | 1.10500 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 285.976379 | 0.35276163 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | Sensible | 7707.77 | 7646.27 | 0.9891 | 0.35276163 | 285.976379 | 76.00 | 60.79 | 0.00804505 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 368.046 | 7339.73 | 73.82 | 0.00700086 | 58.32 | 44.99498340 | 15.7338 | 75.00 | 0.00824001 | 75.00 | 0.00823289 | 43.9405 | 6592.99 | 0.00 | 7622.51 | 6047.66 | 0.33883021 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7623.816 | 7623.816 | 285.976379 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 285.976379 | 0.35276163 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 7623.82 | 7623.82 | 1.0000 | 0.35276163 | 285.976379 | 53.83 | 48.12 | 0.00591894 | 6.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7623.82 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.7338 | 71.99 | 0.00701205 | 71.99 | 0.00701205 | 41.4855 | 12522.86 | 0.00 | 7633.83 | 7633.83 | 0.34652822 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17874.987 | 17874.987 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 285.976379 | 0.35276163 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17874.99 | 17874.99 | 1.0000 | 0.35276163 | 285.976379 | 53.83 | 48.12 | 0.00591894 | 6.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17874.99 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.7338 | 71.99 | 0.00701205 | 71.99 | 0.00701205 | 41.4855 | 12522.86 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11441.285 | 9160.525 | 429.173181 | -999. | -999.00 | -999.0000 | 1.06734 | 1.00000 | 0.2437 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 429.173181 | 0.52939977 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11535.41 | 11104.79 | 0.9918 | 0.52939977 | 429.173181 | 76.10 | 61.09 | 0.00821798 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 552.338 | 10983.07 | 74.16 | 0.00700114 | 58.45 | 44.99498340 | 10.4841 | 75.00 | 0.00836050 | 75.00 | 0.00834509 | 44.5322 | 9904.21 | 0.00 | 11439.32 | 9075.90 | 0.50849248 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11441.285 | 11441.285 | 429.173181 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 429.173181 | 0.52939977 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11441.29 | 11441.29 | 1.0000 | 0.52939977 | 429.173181 | 59.90 | 52.37 | 0.00675279 | 7.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11441.29 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.4841 | 72.00 | 0.00753612 | 72.00 | 0.00753612 | 44.5421 | 9785.03 | 0.00 | 11456.32 | 11456.32 | 0.52004512 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15177.250 | 15177.250 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 429.173181 | 0.52939977 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 15177.25 | 15177.25 | 1.0000 | 0.52939977 | 429.173181 | 59.90 | 52.37 | 0.00675279 | 7.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15177.25 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.4841 | 72.00 | 0.00753612 | 72.00 | 0.00753612 | 44.5421 | 9785.03 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6179.455 | 4947.613 | 231.797052 | -999. | -999.00 | -999.0000 | 1.03407 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 231.797052 | 0.28592958 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 6325.36 | 6284.18 | 0.9769 | 0.28592958 | 231.797052 | 77.34 | 61.26 | 0.00803864 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 298.319 | 6027.04 | 80.95 | 0.00700683 | 60.93 | 44.99498340 | 19.4114 | 75.00 | 0.00828717 | 75.00 | 0.00828689 | 44.2253 | 5363.35 | 0.00 | 6178.39 | 4901.91 | 0.27463752 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6179.455 | 6179.455 | 231.797052 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 231.797052 | 0.28592958 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6179.45 | 6179.45 | 1.0000 | 0.28592958 | 231.797052 | 49.59 | 46.55 | 0.00611000 | 6.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6179.45 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.4114 | 72.00 | 0.00756618 | 72.00 | 0.00756618 | 44.7160 | 6052.60 | 0.00 | 6187.58 | 6187.58 | 0.28087711 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11499.241 | 11499.241 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 231.797052 | 0.28592958 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11499.24 | 11499.24 | 1.0000 | 0.28592958 | 231.797052 | 49.59 | 46.55 | 0.00611000 | 6.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11499.24 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.4114 | 72.00 | 0.00756618 | 72.00 | 0.00756618 | 44.7160 | 6052.60 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9190.218 | 7358.196 | 344.733549 | -999. | -999.00 | -999.0000 | 1.06701 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 344.733549 | 0.42524060 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | Sensible | 9354.78 | 9248.55 | 0.9824 | 0.42524060 | 344.733549 | 76.58 | 61.03 | 0.00806579 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 443.666 | 8911.11 | 78.02 | 0.00700436 | 59.88 | 44.99498340 | 13.0521 | 75.00 | 0.00822513 | 75.00 | 0.00822545 | 43.9014 | 7972.95 | 0.00 | 9188.64 | 7290.22 | 0.40844681 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 9190.218 | 9190.218 | 344.733549 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 344.733549 | 0.42524060 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 9190.22 | 9190.22 | 1.0000 | 0.42524060 | 344.733549 | 56.93 | 50.74 | 0.00656058 | 7.3 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 9190.22 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.0521 | 72.00 | 0.00753574 | 72.00 | 0.00753574 | 44.5399 | 9776.06 | 0.00 | 9202.29 | 9202.29 | 0.41772647 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15168.412 | 15168.412 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 344.733549 | 0.42524060 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 15168.41 | 15168.41 | 1.0000 | 0.42524060 | 344.733549 | 56.93 | 50.74 | 0.00656058 | 7.3 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15168.41 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.0521 | 72.00 | 0.00753574 | 72.00 | 0.00753574 | 44.5399 | 9776.06 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10130.222 | 8110.815 | 379.993975 | -999. | -999.00 | -999.0000 | 1.07829 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 379.993975 | 0.46873554 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | Sensible | 10196.50 | 9827.05 | 0.9935 | 0.46873554 | 379.993975 | 75.93 | 61.02 | 0.00820993 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 489.045 | 9707.45 | 72.81 | 0.00700003 | 57.94 | 44.99498340 | 11.8410 | 75.00 | 0.00837243 | 75.00 | 0.00837841 | 44.7077 | 8791.52 | 0.00 | 10128.48 | 8035.89 | 0.45022403 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 10130.222 | 10130.222 | 379.993975 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 379.993975 | 0.46873554 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 10130.22 | 10130.22 | 1.0000 | 0.46873554 | 379.993975 | 58.33 | 51.52 | 0.00665145 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10130.22 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 11.8410 | 72.00 | 0.00753617 | 72.00 | 0.00753617 | 44.5424 | 9786.17 | 0.00 | 10143.53 | 10143.53 | 0.46045284 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15178.373 | 15178.373 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 379.993975 | 0.46873554 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 15178.37 | 15178.37 | 1.0000 | 0.46873554 | 379.993975 | 58.33 | 51.52 | 0.00665145 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15178.37 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 11.8410 | 72.00 | 0.00753617 | 72.00 | 0.00753617 | 44.5424 | 9786.17 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4593.136 | 3677.519 | 172.292788 | -999. | -999.00 | -999.0000 | 1.12294 | 1.00000 | 0.2437 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 172.292788 | 0.21252904 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | Sensible | 4620.31 | 4426.39 | 0.9941 | 0.21252904 | 172.292788 | 74.87 | 60.68 | 0.00823437 | 10.7 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 221.738 | 4398.57 | 69.94 | 0.00699765 | 56.84 | 44.99498340 | 26.1154 | 75.00 | 0.00867150 | 75.00 | 0.00867718 | 46.2799 | 3983.83 | 0.00 | 4592.35 | 3643.55 | 0.20413575 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 4593.136 | 4593.136 | 172.292788 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 172.292788 | 0.21252904 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 4593.14 | 4593.14 | 1.0000 | 0.21252904 | 172.292788 | 41.86 | 41.70 | 0.00560701 | 4.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4593.14 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 26.1154 | 72.00 | 0.00756607 | 72.00 | 0.00756607 | 44.7155 | 6050.98 | 0.00 | 4599.17 | 4599.17 | 0.20877358 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11497.639 | 11497.639 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 172.292788 | 0.21252904 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11497.64 | 11497.64 | 1.0000 | 0.21252904 | 172.292788 | 41.86 | 41.70 | 0.00560701 | 4.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11497.64 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 26.1154 | 72.00 | 0.00756607 | 72.00 | 0.00756607 | 44.7155 | 6050.98 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7753.240 | 6207.672 | 290.831199 | -999. | -999.00 | -999.0000 | 1.09270 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 290.831199 | 0.35875021 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | Sensible | 7846.67 | 7758.97 | 0.9881 | 0.35875021 | 290.831199 | 76.16 | 60.88 | 0.00806369 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 374.294 | 7472.38 | 74.80 | 0.00700167 | 58.69 | 44.99498340 | 15.4712 | 75.00 | 0.00825807 | 75.00 | 0.00825476 | 44.0558 | 6725.37 | 0.00 | 7751.91 | 6150.33 | 0.34458229 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7753.240 | 7753.240 | 290.831199 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 290.831199 | 0.35875021 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 7753.24 | 7753.24 | 1.0000 | 0.35875021 | 290.831199 | 54.14 | 49.17 | 0.00637969 | 6.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7753.24 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.4712 | 72.00 | 0.00753555 | 72.00 | 0.00753555 | 44.5388 | 9771.75 | 0.00 | 7763.43 | 7763.43 | 0.35241099 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15164.168 | 15164.168 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 290.831199 | 0.35875021 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 15164.17 | 15164.17 | 1.0000 | 0.35875021 | 290.831199 | 54.14 | 49.17 | 0.00637969 | 6.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15164.17 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.4712 | 72.00 | 0.00753555 | 72.00 | 0.00753555 | 44.5388 | 9771.75 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11676.709 | 9349.018 | 438.004128 | -999. | -999.00 | -999.0000 | 1.07053 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 438.004128 | 0.54029305 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11776.32 | 11371.20 | 0.9915 | 0.54029305 | 438.004128 | 76.10 | 61.07 | 0.00820029 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 563.703 | 11212.62 | 74.16 | 0.00700114 | 58.45 | 44.99498340 | 10.2727 | 75.00 | 0.00833758 | 75.00 | 0.00832956 | 44.4504 | 10122.19 | 0.00 | 11674.71 | 9262.66 | 0.51895556 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 11676.709 | 11676.709 | 438.004128 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 438.004128 | 0.54029305 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11676.71 | 11676.71 | 1.0000 | 0.54029305 | 438.004128 | 60.14 | 51.85 | 0.00641914 | 7.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11676.71 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.2727 | 71.99 | 0.00714668 | 71.99 | 0.00714668 | 42.2729 | 14847.49 | 0.00 | 11692.05 | 11692.05 | 0.53074590 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20165.754 | 20165.754 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 438.004128 | 0.54029305 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 20165.75 | 20165.75 | 1.0000 | 0.54029305 | 438.004128 | 60.14 | 51.85 | 0.00641914 | 7.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 20165.75 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.2727 | 71.99 | 0.00714668 | 71.99 | 0.00714668 | 42.2729 | 14847.49 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6275.266 | 5024.325 | 235.391029 | -999. | -999.00 | -999.0000 | 1.04126 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 235.391029 | 0.29036287 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 6424.60 | 6411.65 | 0.9768 | 0.29036287 | 235.391029 | 77.29 | 61.20 | 0.00801188 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 302.944 | 6121.65 | 80.77 | 0.00700668 | 60.87 | 44.99498340 | 19.1150 | 75.00 | 0.00824943 | 75.00 | 0.00824787 | 44.0196 | 5445.08 | 0.00 | 6274.19 | 4977.91 | 0.27889573 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 6275.266 | 6275.266 | 235.391029 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 235.391029 | 0.29036287 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6275.27 | 6275.27 | 1.0000 | 0.29036287 | 235.391029 | 49.93 | 45.88 | 0.00570761 | 5.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6275.27 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.1150 | 71.99 | 0.00704120 | 71.99 | 0.00704120 | 41.6547 | 11119.97 | 0.00 | 6283.51 | 6283.51 | 0.28523207 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16492.582 | 16492.582 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 235.391029 | 0.29036287 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 16492.58 | 16492.58 | 1.0000 | 0.29036287 | 235.391029 | 49.93 | 45.88 | 0.00570761 | 5.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 16492.58 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.1150 | 71.99 | 0.00704120 | 71.99 | 0.00704120 | 41.6547 | 11119.97 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8896.876 | 7123.331 | 333.730041 | -999. | -999.00 | -999.0000 | 1.06786 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 333.730041 | 0.41166740 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | Sensible | 9064.94 | 8994.58 | 0.9815 | 0.41166740 | 333.730041 | 76.64 | 61.02 | 0.00804489 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 429.504 | 8635.43 | 78.32 | 0.00700461 | 59.99 | 44.99498340 | 13.4824 | 75.00 | 0.00820701 | 75.00 | 0.00820701 | 43.8041 | 7725.34 | 0.00 | 8895.35 | 7057.53 | 0.39540965 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 8896.876 | 8896.876 | 333.730041 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 333.730041 | 0.41166740 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 8896.88 | 8896.88 | 1.0000 | 0.41166740 | 333.730041 | 56.43 | 49.82 | 0.00619136 | 7.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8896.88 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.4824 | 71.99 | 0.00714614 | 71.99 | 0.00714614 | 42.2698 | 14836.79 | 0.00 | 8908.57 | 8908.57 | 0.40439311 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20155.217 | 20155.217 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 333.730041 | 0.41166740 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 20155.22 | 20155.22 | 1.0000 | 0.41166740 | 333.730041 | 56.43 | 49.82 | 0.00619136 | 7.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 20155.22 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.4824 | 71.99 | 0.00714614 | 71.99 | 0.00714614 | 42.2698 | 14836.79 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10823.357 | 8665.778 | 405.994124 | -999. | -999.00 | -999.0000 | 1.07897 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 405.994124 | 0.50080761 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 10901.84 | 10541.36 | 0.9928 | 0.50080761 | 405.994124 | 75.98 | 61.01 | 0.00819135 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 522.507 | 10379.33 | 73.15 | 0.00700030 | 58.07 | 44.99498340 | 11.0827 | 75.00 | 0.00833981 | 75.00 | 0.00834854 | 44.5503 | 9385.56 | 0.00 | 10821.50 | 8585.73 | 0.48102950 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 10823.357 | 10823.357 | 405.994124 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 405.994124 | 0.50080761 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 10823.36 | 10823.36 | 1.0000 | 0.50080761 | 405.994124 | 59.20 | 51.35 | 0.00636175 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10823.36 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 11.0827 | 71.99 | 0.00714664 | 71.99 | 0.00714664 | 42.2727 | 14846.67 | 0.00 | 10837.58 | 10837.58 | 0.49195819 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20164.949 | 20164.949 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 405.994124 | 0.50080761 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 20164.95 | 20164.95 | 1.0000 | 0.50080761 | 405.994124 | 59.20 | 51.35 | 0.00636175 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 20164.95 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 11.0827 | 71.99 | 0.00714664 | 71.99 | 0.00714664 | 42.2727 | 14846.67 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5479.963 | 4387.561 | 205.558478 | -999. | -999.00 | -999.0000 | 1.12099 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 205.558478 | 0.25356340 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | Sensible | 5512.90 | 5326.10 | 0.9940 | 0.25356340 | 205.558478 | 75.11 | 60.70 | 0.00818952 | 10.7 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 264.550 | 5248.35 | 70.21 | 0.00699788 | 56.95 | 44.99498340 | 21.8891 | 75.00 | 0.00853496 | 75.00 | 0.00854084 | 45.5625 | 4626.89 | 0.00 | 5479.02 | 4347.03 | 0.24354956 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 5479.963 | 5479.963 | 205.558478 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 205.558478 | 0.25356340 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5479.96 | 5479.96 | 1.0000 | 0.25356340 | 205.558478 | 46.73 | 43.93 | 0.00551390 | 5.3 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5479.96 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 21.8891 | 71.99 | 0.00704100 | 71.99 | 0.00704100 | 41.6535 | 11117.17 | 0.00 | 5487.16 | 5487.16 | 0.24908286 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16489.822 | 16489.822 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 205.558478 | 0.25356340 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 16489.82 | 16489.82 | 1.0000 | 0.25356340 | 205.558478 | 46.73 | 43.93 | 0.00551390 | 5.3 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 16489.82 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 21.8891 | 71.99 | 0.00704100 | 71.99 | 0.00704100 | 41.6535 | 11117.17 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7504.662 | 6008.647 | 281.506791 | -999. | -999.00 | -999.0000 | 1.09396 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 281.506791 | 0.34724824 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 7604.04 | 7555.68 | 0.9869 | 0.34724824 | 281.506791 | 76.23 | 60.86 | 0.00803616 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 362.294 | 7241.74 | 75.26 | 0.00700206 | 58.86 | 44.99498340 | 15.9836 | 75.00 | 0.00823290 | 75.00 | 0.00823060 | 43.9284 | 6504.05 | 0.00 | 7503.37 | 5953.14 | 0.33353456 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.72 | 58.22 | 0.01000719 | 9.7 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | Yes | unknown | No | 7504.662 | 7504.662 | 281.506791 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 281.506791 | 0.34724824 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 7504.66 | 7504.66 | 1.0000 | 0.34724824 | 281.506791 | 53.55 | 48.18 | 0.00601404 | 6.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7504.66 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.9836 | 71.99 | 0.00714590 | 71.99 | 0.00714590 | 42.2684 | 14832.04 | 0.00 | 7514.52 | 7514.52 | 0.34111226 | 70.00 | 60.00 | 0.00875166 | 10.4 | 95.09 | 68.43 | 0.00875166 | 13.8 | |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20150.532 | 20150.532 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 281.506791 | 0.34724824 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 20150.53 | 20150.53 | 1.0000 | 0.34724824 | 281.506791 | 53.55 | 48.18 | 0.00601404 | 6.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 20150.53 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.9836 | 71.99 | 0.00714590 | 71.99 | 0.00714590 | 42.2684 | 14832.04 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3119.17 | 7055.50 | 2467.17 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1223.17 | 7105.67 | 833.83 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3166.50 | 6757.00 | 2395.17 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3230.33 | 7341.17 | 2816.83 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1344.67 | 7411.33 | 1210.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3221.17 | 7102.50 | 2698.83 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3039.67 | 6859.67 | 2302.67 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1081.00 | 6810.00 | 574.83 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3111.67 | 6540.17 | 2233.33 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3131.17 | 7126.00 | 2629.83 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1070.17 | 7132.17 | 862.50 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3159.33 | 6889.83 | 2514.17 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3904.83 | 7055.83 | 3272.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3807.67 | 6828.33 | 3002.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3764.67 | 7092.83 | 3093.33 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2716.83 | 7305.33 | 2468.67 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2592.17 | 7133.00 | 2117.67 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3857.00 | 7295.50 | 3356.83 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4514.50 | 7664.33 | 3401.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9.33 | 0.00 | 9.33 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 639.83 | 0.00 | 639.83 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 19.50 | 0.00 | 19.50 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.83 | 0.00 | 0.83 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.33 | 0.00 | 0.33 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.50 | 0.17 | 1.50 | 0.17 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 76.67 | 0.00 | 76.67 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 83.67 | 0.00 | 83.67 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7.67 | 0.00 | 7.67 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 305.33 | 0.00 | 305.33 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 64.17 | 0.00 | 64.17 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 641.83 | 0.17 | 641.83 | 0.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.044 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.044 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.137 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.261 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12134455.05 | 35919536.74 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10691487.36 | 34476569.05 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12149186.34 | 35934268.03 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12121909.77 | 35906991.46 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10661522.20 | 34446603.88 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12133750.90 | 35918832.58 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5321065.51 | 29106147.20 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3872763.99 | 27657845.68 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5326772.92 | 29111854.61 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5315430.73 | 29100512.41 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3865144.03 | 27650225.72 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5320365.44 | 29105447.13 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12138433.41 | 35923515.10 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12154208.98 | 35939290.67 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12140770.67 | 35925852.36 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10675174.70 | 34460256.39 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10694633.97 | 34479715.66 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12130808.72 | 35915890.41 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
Total Facility | 0.428131E+09 | 0.00 | 0.428131E+09 | 0.168848E+09 | 0.596979E+09 | 0.428131E+09 | 0.00 | 8808.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9551 | 67.9501 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.2254 | 65.2204 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9830 | 67.9780 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9314 | 67.9264 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.1687 | 65.1637 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9538 | 67.9488 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0660 | 55.0610 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.3262 | 52.3212 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0768 | 55.0718 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0554 | 55.0504 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.3118 | 52.3068 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0647 | 55.0597 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9627 | 67.9576 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9925 | 67.9875 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9671 | 67.9621 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.1946 | 65.1895 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.2314 | 65.2264 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9482 | 67.9432 | 44.9950 | 0.00 | 8808.00 | 0.00 |
Total Facility | 809.9097 | 0.0000 | 809.9097 | 319.4148 | 1129.3245 | 809.9097 | 0.00 | 8808.00 | 0.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1986 |
Defaulted Fields | 1647 |
Fields with Defaults | 6465 |
Autosized Fields | 360 |
Autosizable Fields | 648 |
Autocalculated Fields | 161 |
Autocalculatable Fields | 349 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
Electricity:Building | 100764.00 | 6307.12 | 02-JAN-03:10 | 19198.06 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5598.00 | 350.40 | 02-JAN-03:10 | 1066.56 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 87803.80 | 5989.14 | 02-JAN-04:10 | 15388.75 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:10 | 880.12 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:10 | 381.47 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
Fans:Electricity | 15804.68 | 578.57 | 16-APR-17:10 | 2674.11 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
ElectricityPurchased:Plant | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
Cogeneration:ElectricityPurchased | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
General:Cogeneration:ElectricityPurchased | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
ElectricityNet:Plant | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
Cogeneration:ElectricityNet | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
General:Cogeneration:ElectricityNet | 349552.98 | 8143.39 | 15-JUN-03:10 | 145101.89 | 11-JAN-18:00 |
Electricity:HVAC | 180714.38 | 578.57 | 05-MAY-11:10 | 82065.03 | 12-JAN-10:00 |
HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Fans:Electricity | 10736.39 | 0.00 | 16-APR-17:10 | 2095.54 | 01-JAN-00:10 |
Ventilation:Fans:Electricity | 5068.29 | 578.57 | 01-JAN-00:10 | 578.57 | 01-JAN-00:10 |
ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 4970.89 | 0.00 | 01-JAN-00:10 | 7837.81 | 29-JUL-16:10 |
General:Cooling:Electricity | 4970.89 | 0.00 | 01-JAN-00:10 | 7837.81 | 29-JUL-16:10 |
Heating:Electricity | 159938.81 | 0.00 | 17-APR-15:40 | 79390.93 | 12-JAN-10:00 |
General:Heating:Electricity | 159938.81 | 0.00 | 17-APR-15:40 | 79390.93 | 12-JAN-10:00 |
Electricity:Plant | 62565.89 | 0.00 | 01-JAN-00:10 | 58955.40 | 07-JAN-08:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 62565.89 | 0.00 | 01-JAN-00:10 | 58955.40 | 07-JAN-08:10 |
Water Heater:WaterSystems:Electricity | 62565.89 | 0.00 | 01-JAN-00:10 | 58955.40 | 07-JAN-08:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1360175.05 | 16493.33 | 26-JUN-03:00 | 472594.67 | 12-JAN-10:00 |
EnergyTransfer:Building | 484649.90 | 7241.75 | 19-SEP-13:20 | 174155.76 | 12-JAN-10:20 |
EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer | 363794.24 | 0.00 | 13-APR-19:50 | 174155.76 | 12-JAN-10:20 |
Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 363794.24 | 0.00 | 13-APR-19:50 | 174155.76 | 12-JAN-10:20 |
Cooling:EnergyTransfer | 120855.66 | 0.00 | 01-JAN-00:10 | 102081.79 | 11-JUL-18:10 |
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer | 120855.66 | 0.00 | 01-JAN-00:10 | 102081.79 | 11-JUL-18:10 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29817.23 | 0.23 | 17-SEP-02:00 | 11498.76 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 22270.13 | 0.00 | 06-MAR-14:50 | 11498.76 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 7547.10 | 0.00 | 01-JAN-00:10 | 8816.19 | 06-JUL-18:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 20008.74 | 0.09 | 12-MAR-12:30 | 7323.36 | 12-JAN-10:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13531.79 | 0.00 | 09-FEB-13:20 | 7323.36 | 12-JAN-10:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6476.95 | 0.00 | 01-JAN-00:10 | 5011.11 | 23-JUL-14:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 30149.63 | 0.42 | 25-SEP-14:00 | 11505.05 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21636.38 | 0.00 | 06-MAR-13:30 | 11505.05 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8513.26 | 0.00 | 01-JAN-00:10 | 8134.44 | 22-JUL-10:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 29736.05 | 0.10 | 26-MAY-01:30 | 11845.63 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24443.83 | 0.00 | 20-MAR-17:30 | 11845.63 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5292.22 | 0.00 | 01-JAN-00:10 | 7818.47 | 11-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19165.00 | 0.20 | 20-APR-13:50 | 5445.64 | 13-JAN-16:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 15044.01 | 0.00 | 22-MAR-18:40 | 5445.64 | 13-JAN-16:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4121.00 | 0.00 | 01-JAN-00:10 | 3548.25 | 11-JUL-20:40 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 29846.74 | 0.06 | 28-MAY-06:30 | 10852.42 | 12-JAN-10:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23702.89 | 0.00 | 20-MAR-11:30 | 10852.42 | 12-JAN-10:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6143.85 | 0.00 | 01-JAN-00:10 | 7291.89 | 07-JUL-07:50 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 25547.32 | 0.09 | 04-SEP-02:30 | 8981.86 | 06-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 16935.03 | 0.00 | 09-FEB-13:50 | 8978.22 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8612.29 | 0.00 | 01-JAN-00:10 | 8981.86 | 06-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16424.26 | 0.36 | 01-MAY-03:20 | 5868.69 | 12-JAN-10:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8552.63 | 0.00 | 08-FEB-23:10 | 5868.69 | 12-JAN-10:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7871.63 | 0.00 | 01-JAN-00:10 | 5145.14 | 23-JUL-14:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 26180.50 | 0.04 | 29-SEP-12:20 | 9040.64 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16415.76 | 0.00 | 09-FEB-13:50 | 9040.64 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9764.74 | 0.00 | 01-JAN-00:10 | 8228.28 | 22-JUL-10:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25016.23 | 0.02 | 06-SEP-03:50 | 9208.74 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 18820.01 | 0.00 | 20-MAR-16:10 | 9208.74 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 6196.22 | 0.00 | 01-JAN-00:10 | 7953.45 | 06-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15475.22 | 0.05 | 02-SEP-05:10 | 5438.87 | 13-JAN-17:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 10226.51 | 0.00 | 18-MAR-18:50 | 5438.87 | 13-JAN-17:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5248.71 | 0.00 | 01-JAN-00:10 | 3829.62 | 11-JUL-20:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25349.40 | 0.34 | 14-SEP-14:20 | 9930.79 | 12-JAN-10:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 18183.28 | 0.00 | 20-MAR-11:20 | 9930.79 | 12-JAN-10:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7166.13 | 0.00 | 01-JAN-00:10 | 7386.29 | 07-JUL-07:40 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 35507.50 | 0.22 | 21-SEP-00:50 | 11684.37 | 12-JAN-16:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29174.28 | 0.00 | 22-MAR-11:10 | 11684.37 | 12-JAN-16:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 6333.21 | 0.00 | 01-JAN-00:10 | 7150.92 | 07-JUL-07:50 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 35305.90 | 0.45 | 06-SEP-00:30 | 13090.55 | 12-JAN-10:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 27204.63 | 0.00 | 19-MAR-13:20 | 13090.55 | 12-JAN-10:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 8101.27 | 0.00 | 01-JAN-00:10 | 7933.92 | 22-JUL-10:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 35220.29 | 0.73 | 25-JUN-04:00 | 13695.97 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 27944.65 | 0.00 | 20-MAR-13:00 | 13695.97 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 7275.64 | 0.00 | 01-JAN-00:10 | 9048.96 | 11-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 25235.48 | 0.03 | 05-MAY-13:40 | 7826.55 | 12-JAN-16:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 20782.76 | 0.00 | 22-MAR-19:10 | 7826.55 | 12-JAN-16:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4452.72 | 0.00 | 01-JAN-00:10 | 4328.47 | 11-JUL-20:40 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 25022.46 | 0.12 | 13-OCT-16:30 | 8464.08 | 12-JAN-10:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 18861.39 | 0.00 | 19-MAR-13:20 | 8464.08 | 12-JAN-10:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 6161.07 | 0.00 | 01-JAN-00:10 | 5120.54 | 23-JUL-14:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 35641.95 | 1.51 | 17-SEP-14:20 | 13916.02 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30064.29 | 0.00 | 05-APR-18:10 | 13916.02 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5577.66 | 0.00 | 01-JAN-00:10 | 8436.73 | 11-JUL-18:40 |
EnergyTransfer:HVAC | 678635.44 | 0.00 | 16-APR-17:10 | 258598.64 | 12-JAN-10:00 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 77115.60 | 0.00 | 01-JAN-00:10 | 115588.55 | 11-JUL-18:10 |
HeatingCoils:EnergyTransfer | 601519.84 | 0.00 | 13-APR-19:50 | 258598.64 | 12-JAN-10:00 |
EnergyTransfer:Plant | 196889.71 | 1908.79 | 04-SEP-02:10 | 45344.48 | 01-JAN-09:00 |
WaterSystems:EnergyTransfer | 196889.71 | 1908.79 | 04-SEP-02:10 | 45344.48 | 01-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 196889.71 | 1908.79 | 04-SEP-02:10 | 45344.48 | 01-JAN-09:00 |
PlantLoopHeatingDemand:Facility | 196889.71 | 1908.79 | 04-SEP-02:10 | 45344.48 | 01-JAN-09:00 |
PlantLoopHeatingDemand:Plant | 196889.71 | 1908.79 | 04-SEP-02:10 | 45344.48 | 01-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 196889.71 | 1908.79 | 04-SEP-02:10 | 45344.48 | 01-JAN-09:00 |
General:WaterSystems:PlantLoopHeatingDemand | 196889.71 | 1908.79 | 04-SEP-02:10 | 45344.48 | 01-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21.634 | -1488.28 | 37284.086 | -392.36 | 0.000 | 0.000 | 3100.887 | 2458.419 | 10401.374 | 6931.556 | 0.000 | 4.504 | 0.000 | 0.000 | -11908.73 | 0.000 | -10750.46 | -14960.49 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21.634 | -1490.25 | 28033.317 | -258.59 | 0.000 | 0.000 | 3094.176 | 2458.419 | 10401.374 | 4115.461 | 0.000 | 3.965 | 0.000 | 0.000 | -4738.56 | 0.000 | -9475.04 | -12914.60 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21.611 | -1491.87 | 36414.700 | -449.60 | 0.000 | 0.000 | 3094.747 | 2458.419 | 10401.374 | 8402.957 | 0.000 | 4.500 | 0.000 | 0.000 | -11642.82 | 0.000 | -10771.25 | -15070.99 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21.639 | -1484.81 | 39983.783 | -251.86 | 0.000 | 0.000 | 3106.361 | 2458.419 | 10401.374 | 3938.480 | 0.000 | 4.504 | 0.000 | 0.000 | -12590.37 | 0.000 | -10727.90 | -15742.40 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21.644 | -1480.10 | 30328.897 | -137.78 | 0.000 | 0.000 | 3116.178 | 2458.419 | 10401.374 | 848.930 | 0.000 | 3.966 | 0.000 | 0.000 | -5213.11 | 0.000 | -9390.14 | -13148.58 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21.636 | -1487.89 | 39042.763 | -303.03 | 0.000 | 0.000 | 3102.964 | 2458.419 | 10401.374 | 5325.311 | 0.000 | 4.505 | 0.000 | 0.000 | -12233.70 | 0.000 | -10744.23 | -15873.63 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21.636 | -1492.11 | 31513.806 | -440.99 | 0.000 | 0.000 | 3089.683 | 2458.419 | 10401.374 | 6881.264 | 0.000 | 1.950 | 0.000 | 0.000 | -12033.47 | 0.000 | -4721.21 | -14400.68 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21.636 | -1494.66 | 22367.016 | -313.11 | 0.000 | 0.000 | 3081.472 | 2458.419 | 10401.374 | 4089.164 | 0.000 | 1.418 | 0.000 | 0.000 | -4786.71 | 0.000 | -3437.93 | -12488.16 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21.610 | -1495.34 | 30732.629 | -511.92 | 0.000 | 0.000 | 3084.671 | 2458.419 | 10401.374 | 8342.191 | 0.000 | 1.948 | 0.000 | 0.000 | -11757.92 | 0.000 | -4729.43 | -14452.23 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21.641 | -1488.53 | 34017.404 | -294.89 | 0.000 | 0.000 | 3095.996 | 2458.419 | 10401.374 | 3896.965 | 0.000 | 1.950 | 0.000 | 0.000 | -12718.03 | 0.000 | -4710.81 | -15049.58 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21.646 | -1488.21 | 25031.499 | -183.63 | 0.000 | 0.000 | 3095.959 | 2458.419 | 10401.374 | 833.920 | 0.000 | 1.418 | 0.000 | 0.000 | -5277.47 | 0.000 | -3423.10 | -13068.29 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21.636 | -1491.44 | 33207.825 | -358.35 | 0.000 | 0.000 | 3093.353 | 2458.419 | 10401.374 | 5276.459 | 0.000 | 1.950 | 0.000 | 0.000 | -12355.70 | 0.000 | -4718.01 | -15174.95 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21.632 | -1486.92 | 44649.070 | -331.01 | 0.000 | 0.000 | 3103.419 | 2458.419 | 10401.374 | 5295.639 | 0.000 | 4.405 | 0.000 | 0.000 | -12269.44 | 0.000 | -10751.86 | -21082.96 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21.608 | -1491.07 | 42296.616 | -442.21 | 0.000 | 0.000 | 3094.719 | 2458.419 | 10401.374 | 8371.568 | 0.000 | 4.400 | 0.000 | 0.000 | -11668.96 | 0.000 | -10784.87 | -20979.94 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 21.634 | -1487.67 | 43216.924 | -391.88 | 0.000 | 0.000 | 3099.963 | 2458.419 | 10401.374 | 6905.788 | 0.000 | 4.405 | 0.000 | 0.000 | -11939.40 | 0.000 | -10765.88 | -20833.57 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21.643 | -1482.65 | 36252.566 | -178.26 | 0.000 | 0.000 | 3108.605 | 2458.419 | 10401.374 | 840.153 | 0.000 | 3.879 | 0.000 | 0.000 | -5233.76 | 0.000 | -9434.86 | -18473.80 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21.635 | -1488.99 | 33789.079 | -269.04 | 0.000 | 0.000 | 3095.023 | 2458.419 | 10401.374 | 4100.517 | 0.000 | 3.878 | 0.000 | 0.000 | -4741.82 | 0.000 | -9482.75 | -18534.91 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 21.638 | -1484.91 | 45713.088 | -284.59 | 0.000 | 0.000 | 3104.403 | 2458.419 | 10401.374 | 3909.845 | 0.000 | 4.405 | 0.000 | 0.000 | -12633.82 | 0.000 | -10748.27 | -20982.89 |
UNHEATEDBSMT | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28126.021 | 71328.174 | 0.000 | 0.000 | 0.000 | -99454.20 | -0.19 |
Total Facility | 389.395 | -26795.69 | 633875.069 | -5793.10 | 0.000 | 0.000 | 55762.578 | 44251.534 | 187224.736 | 88306.168 | 0.000 | 28187.971 | 71328.174 | 0.000 | -175743.80 | 0.000 | -249022.20 | -293232.84 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 06-JUL-18:20 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.74 | 722.08 | 1713.00 | 6730.03 | 0.00 | 11.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -786.6 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23-JUL-14:00 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 103.15 | 1099.93 | 4188.90 | 0.00 | 15.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -511.6 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22-JUL-10:00 | 0.00 | -0.0 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 103.15 | 1112.20 | 8778.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32.9 | -1941.4 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11-JUL-18:10 | 0.00 | 0.02 | 0.00 | -0.7 | 0.00 | 0.00 | 426.75 | 722.08 | 1713.00 | 6353.44 | 0.00 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1483.2 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11-JUL-20:25 | 0.00 | -0.0 | 0.00 | -0.3 | 0.00 | 0.00 | 426.74 | 800.22 | 1615.87 | 1061.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29.2 | -326.6 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 07-JUL-08:00 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 417.98 | 343.85 | 1204.45 | 7916.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72.8 | -2512.9 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 06-JUL-18:30 | 0.00 | 0.01 | 0.00 | -0.8 | 0.00 | 0.00 | 426.74 | 722.08 | 1713.00 | 6576.86 | 0.00 | 4.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -461.5 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23-JUL-14:10 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 103.15 | 1105.69 | 4020.46 | 0.00 | 6.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -205.7 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 22-JUL-10:10 | 0.00 | -0.0 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 103.15 | 1108.25 | 8702.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11.2 | -1789.6 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 06-JUL-19:30 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.75 | 800.22 | 1650.38 | 5964.78 | 0.00 | 2.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -891.1 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11-JUL-20:50 | 0.00 | -0.0 | 0.00 | -0.3 | 0.00 | 0.00 | 426.76 | 800.22 | 1615.87 | 995.80 | 0.00 | 0.00 | 8.96 | 0.00 | 0.00 | 0.00 | -17.6 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 07-JUL-08:00 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 418.79 | 343.85 | 1204.45 | 7916.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31.8 | -2460.4 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 07-JUL-08:00 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 419.87 | 343.85 | 1204.45 | 7923.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -72.0 | -2668.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 22-JUL-10:10 | 0.00 | -0.0 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 103.15 | 1108.25 | 8690.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25.7 | -2057.1 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11-JUL-18:10 | 0.00 | 0.02 | 0.00 | -0.8 | 0.00 | 0.00 | 426.74 | 722.08 | 1713.00 | 6305.78 | 0.00 | 84.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203.5 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 11-JUL-20:35 | 0.00 | -0.0 | 0.00 | -0.4 | 0.00 | 0.00 | 426.76 | 800.22 | 1615.87 | 1026.99 | 0.00 | 0.00 | 498.65 | 0.00 | 0.00 | 0.00 | -40.0 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23-JUL-14:30 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 103.15 | 1105.69 | 3675.97 | 0.00 | 21.23 | 99.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11-JUL-18:40 | 0.00 | 0.02 | 0.00 | -0.7 | 0.00 | 0.00 | 426.75 | 722.08 | 1713.00 | 5758.77 | 0.00 | 86.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -269.7 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-18:10 | 0.00 | 0.36 | 0.00 | -8.9 | 0.00 | 0.00 | 7681.54 | 12997.36 | 30834.00 | 46419.30 | 0.00 | 1190.19 | 45219.59 | 0.00 | 0.00 | 0.00 | -42261.0 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.2 | 0.00 | 16675.66 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4146.3 | 0.00 | -4391.4 | -4275.1 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12-JAN-10:50 | -5041.3 | 0.00 | 12364.51 | 0.00 | 0.00 | 0.00 | 131.85 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1632.8 | 0.00 | -3702.9 | -3301.0 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.1 | 0.00 | 16681.88 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4146.2 | 0.00 | -4391.4 | -4281.4 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.1 | 0.00 | 17022.48 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4140.5 | 0.00 | -4391.4 | -4627.6 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 02-MAR-10:42 | -3207.3 | 0.00 | 8679.10 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -787.9 | 0.00 | -1838.9 | -4154.0 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12-JAN-10:50 | -5003.3 | 0.00 | 15855.54 | 0.00 | 0.00 | 0.00 | 134.75 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3999.0 | 0.00 | -4158.9 | -4010.8 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.1 | 0.00 | 14158.05 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4148.9 | 0.00 | -1924.1 | -4219.2 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12-JAN-10:40 | -5116.8 | 0.00 | 10985.31 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1651.6 | 0.00 | -1369.7 | -4156.2 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.0 | 0.00 | 14220.39 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4147.8 | 0.00 | -1924.1 | -4282.7 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.0 | 0.00 | 14388.52 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4145.0 | 0.00 | -1924.1 | -4453.6 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 13-JAN-17:00 | -3782.7 | 0.00 | 9221.71 | 0.00 | 0.00 | 0.00 | 156.21 | 385.11 | 1343.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1200.4 | 0.00 | -821.5 | -5301.9 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12-JAN-10:30 | -5132.0 | 0.00 | 15062.50 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4086.4 | 0.00 | -1893.5 | -5259.6 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-JAN-16:00 | -4720.2 | 0.00 | 16404.59 | 0.00 | 0.00 | 0.00 | 144.17 | 178.80 | 1140.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3755.3 | 0.00 | -3787.4 | -5605.2 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12-JAN-10:50 | -5052.2 | 0.00 | 18142.52 | 0.00 | 0.00 | 0.00 | 130.94 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4008.6 | 0.00 | -4223.4 | -6170.9 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12-JAN-10:00 | -5177.2 | 0.00 | 18872.83 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4112.8 | 0.00 | -4395.7 | -6501.4 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12-JAN-16:00 | -4618.3 | 0.00 | 12444.90 | 0.00 | 0.00 | 0.00 | 151.11 | 178.80 | 1140.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1486.3 | 0.00 | -3228.9 | -4581.9 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12-JAN-10:50 | -4936.7 | 0.00 | 13400.62 | 0.00 | 0.00 | 0.00 | 139.73 | 103.15 | 1078.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1587.8 | 0.00 | -3593.7 | -4603.9 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12-JAN-10:00 | -5177.2 | 0.00 | 19092.85 | 0.00 | 0.00 | 0.00 | 127.29 | 103.15 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4109.5 | 0.00 | -4395.7 | -6724.7 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JAN-10:30 | -90878.1 | 0.00 | 265029.97 | 0.00 | 0.00 | 0.00 | 2401.31 | 1856.77 | 19414.36 | 0.00 | 0.00 | 19446.47 | 0.00 | 0.00 | -58368.8 | 0.00 | -58626.1 | -100275.9 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 420.0930 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 420.0930 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 226.3931 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 226.3931 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 339.7334 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 339.7334 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 371.9442 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 371.9442 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 162.4697 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 162.4697 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 285.9764 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 285.9764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.1732 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 429.1732 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 231.7971 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 231.7971 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 344.7335 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 344.7335 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 379.9940 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 379.9940 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 172.2928 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 172.2928 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 290.8312 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 290.8312 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.0041 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 438.0041 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 235.3910 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 235.3910 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.7300 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 333.7300 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 405.9941 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 405.9941 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 205.5585 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 205.5585 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 281.5068 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 281.5068 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 420.0930 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 420.0930 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 226.3931 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 226.3931 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 339.7334 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 339.7334 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 371.9442 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 371.9442 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 162.4697 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 162.4697 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 285.9764 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 285.9764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.1732 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 429.1732 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 231.7971 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 231.7971 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 344.7335 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 344.7335 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 379.9940 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 379.9940 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 172.2928 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 172.2928 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 290.8312 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 290.8312 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.0041 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 438.0041 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 235.3910 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 235.3910 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.7300 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 333.7300 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 405.9941 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 405.9941 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 205.5585 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 205.5585 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 281.5068 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 281.5068 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 420.0930 | 420.0930 | 420.0930 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 226.3931 | 226.3931 | 226.3931 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 339.7334 | 339.7334 | 339.7334 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 371.9442 | 371.9442 | 371.9442 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 162.4697 | 162.4697 | 162.4697 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 285.9764 | 285.9764 | 285.9764 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 429.1732 | 429.1732 | 429.1732 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 231.7971 | 231.7971 | 231.7971 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 344.7335 | 344.7335 | 344.7335 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 379.9940 | 379.9940 | 379.9940 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 172.2928 | 172.2928 | 172.2928 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 290.8312 | 290.8312 | 290.8312 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 281.5068 | 281.5068 | 281.5068 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 333.7300 | 333.7300 | 333.7300 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 438.0041 | 438.0041 | 438.0041 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 205.5585 | 205.5585 | 205.5585 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 235.3910 | 235.3910 | 235.3910 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 405.9941 | 405.9941 | 405.9941 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 420.0930 | 420.0930 | 420.0930 | 420.0930 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 226.3931 | 226.3931 | 226.3931 | 226.3931 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 339.7334 | 339.7334 | 339.7334 | 339.7334 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 371.9442 | 371.9442 | 371.9442 | 371.9442 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 162.4697 | 162.4697 | 162.4697 | 162.4697 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 285.9764 | 285.9764 | 285.9764 | 285.9764 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.1732 | 429.1732 | 429.1732 | 429.1732 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 231.7971 | 231.7971 | 231.7971 | 231.7971 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 344.7335 | 344.7335 | 344.7335 | 344.7335 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 379.9940 | 379.9940 | 379.9940 | 379.9940 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 172.2928 | 172.2928 | 172.2928 | 172.2928 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 290.8312 | 290.8312 | 290.8312 | 290.8312 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.0041 | 438.0041 | 438.0041 | 438.0041 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 235.3910 | 235.3910 | 235.3910 | 235.3910 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.7300 | 333.7300 | 333.7300 | 333.7300 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 405.9941 | 405.9941 | 405.9941 | 405.9941 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 205.5585 | 205.5585 | 205.5585 | 205.5585 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 281.5068 | 281.5068 | 281.5068 | 281.5068 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 420.0930 | 420.0930 | 420.0930 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 226.3931 | 226.3931 | 226.3931 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 339.7334 | 339.7334 | 339.7334 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 371.9442 | 371.9442 | 371.9442 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 162.4697 | 162.4697 | 162.4697 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 285.9764 | 285.9764 | 285.9764 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 429.1732 | 429.1732 | 429.1732 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 231.7971 | 231.7971 | 231.7971 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 344.7335 | 344.7335 | 344.7335 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 379.9940 | 379.9940 | 379.9940 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 172.2928 | 172.2928 | 172.2928 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 290.8312 | 290.8312 | 290.8312 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 281.5068 | 281.5068 | 281.5068 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 333.7300 | 333.7300 | 333.7300 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 438.0041 | 438.0041 | 438.0041 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 205.5585 | 205.5585 | 205.5585 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 235.3910 | 235.3910 | 235.3910 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 405.9941 | 405.9941 | 405.9941 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 420.0930 | 420.0930 | 420.0930 | 420.0930 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 226.3931 | 226.3931 | 226.3931 | 226.3931 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 339.7334 | 339.7334 | 339.7334 | 339.7334 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 371.9442 | 371.9442 | 371.9442 | 371.9442 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 162.4697 | 162.4697 | 162.4697 | 162.4697 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 285.9764 | 285.9764 | 285.9764 | 285.9764 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.1732 | 429.1732 | 429.1732 | 429.1732 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 231.7971 | 231.7971 | 231.7971 | 231.7971 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 344.7335 | 344.7335 | 344.7335 | 344.7335 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 379.9940 | 379.9940 | 379.9940 | 379.9940 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 172.2928 | 172.2928 | 172.2928 | 172.2928 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 290.8312 | 290.8312 | 290.8312 | 290.8312 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.0041 | 438.0041 | 438.0041 | 438.0041 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 235.3910 | 235.3910 | 235.3910 | 235.3910 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.7300 | 333.7300 | 333.7300 | 333.7300 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 405.9941 | 405.9941 | 405.9941 | 405.9941 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 205.5585 | 205.5585 | 205.5585 | 205.5585 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 281.5068 | 281.5068 | 281.5068 | 281.5068 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
UNHEATEDBSMT | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 21609.96 | 17395.26 |
Data | |
Number of hours heating loads not met | 641.83 |
Number of hours cooling loads not met | 0.17 |
Number of hours not met | 642.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 159938.81 | 79390.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4970.89 | 7837.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 12960.20 | 4221.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 5508.71 | 1257.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 2758.31 | 880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1408.53 | 381.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 10736.39 | 2095.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 5068.29 | 578.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 62565.89 | 58955.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299798.81 | 1193519.73 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 299798.81 | 1193519.73 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.33 |
Space Heating | 4.10 |
Space Cooling | 0.13 |
Fans (All) | 0.41 |
Service Water Heating | 1.60 |
Receptacle Equipment | 2.25 |
Miscellaneous (All) | 8.96 |
Subtotal | 8.96 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.71 |
Space Heating | 45.76 |
Space Cooling | 1.42 |
Fans (All) | 4.52 |
Service Water Heating | 17.90 |
Receptacle Equipment | 25.12 |
Miscellaneous | 1.58 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DHW_SCH | 365. | 8760. |
DISHWASHER | 2799. | 8760. |
CLOTHESWASHER | 3297. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SINKS | 4179. | 8760. |
SHOWERS | 2640. | 8760. |
BATHS | 2586. | 8760. |
DHWDIST | 4662. | 8760. |
SHADING_2012IECC | 0. | 0. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 8548.50 | 201.17 | 10.33 | 0.00 | 0.00 |
Min | 8548.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 201.17 | 10.33 | 0.00 | 0.00 |
Average | 8749.93 | 9.58 | 0.49 | 0.00 | 0.00 |
Sum | 183748.50 | 201.17 | 10.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 8609.17 | 150.83 | 0.00 | 0.00 | 0.00 |
Min | 8609.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 150.83 | 0.00 | 0.00 | 0.00 |
Average | 8752.82 | 7.18 | 0.00 | 0.00 | 0.00 |
Sum | 183809.17 | 150.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (F) | SET ≤ 12.2°C OccupantHours (F) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (F) | SET > 30°C OccupantHours (F) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:52:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 117.050 | 117.050 |
February | 0.000 | 0.000 | 671.417 | 99.430 | 99.430 |
March | 0.000 | 0.000 | 688.194 | 94.334 | 94.334 |
April | 118.500 | 4.986 | 402.856 | 39.690 | 44.676 |
May | 272.139 | 11.669 | 166.278 | 7.120 | 18.789 |
June | 441.028 | 22.299 | 12.417 | 0.373 | 22.672 |
July | 473.139 | 24.000 | 10.472 | 0.278 | 24.277 |
August | 361.778 | 15.878 | 55.333 | 2.397 | 18.275 |
September | 86.083 | 2.502 | 367.139 | 20.705 | 23.207 |
October | 2.333 | 0.031 | 688.889 | 75.441 | 75.472 |
November | 0.000 | 0.000 | 720.000 | 114.058 | 114.058 |
December | 0.000 | 0.000 | 744.000 | 116.168 | 116.168 |
Annual Sum or Average | 1755.000 | 81.364 | 5270.994 | 687.043 | 768.408 |
Minimum of Months | 0.000 | 0.000 | 10.472 | 0.278 | 18.275 |
Maximum of Months | 473.139 | 24.000 | 744.000 | 117.050 | 117.050 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 63.471 | 63.471 |
February | 0.000 | 0.000 | 667.278 | 55.565 | 55.565 |
March | 0.000 | 0.000 | 659.333 | 53.762 | 53.762 |
April | 85.333 | 1.577 | 371.508 | 25.906 | 27.483 |
May | 261.861 | 6.561 | 97.792 | 4.046 | 10.606 |
June | 460.389 | 14.618 | 7.250 | 0.154 | 14.773 |
July | 507.778 | 17.474 | 5.500 | 0.117 | 17.591 |
August | 392.139 | 11.804 | 31.028 | 1.258 | 13.062 |
September | 93.167 | 1.552 | 256.792 | 12.688 | 14.240 |
October | 3.333 | 0.027 | 629.611 | 45.443 | 45.470 |
November | 0.000 | 0.000 | 720.000 | 61.484 | 61.484 |
December | 0.000 | 0.000 | 744.000 | 63.326 | 63.326 |
Annual Sum or Average | 1804.000 | 53.614 | 4934.092 | 387.218 | 440.832 |
Minimum of Months | 0.000 | 0.000 | 5.500 | 0.117 | 10.606 |
Maximum of Months | 507.778 | 17.474 | 744.000 | 63.471 | 63.471 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 95.206 | 95.206 |
February | 0.000 | 0.000 | 670.750 | 82.597 | 82.597 |
March | 0.000 | 0.000 | 669.806 | 78.507 | 78.507 |
April | 119.578 | 3.315 | 381.414 | 35.357 | 38.672 |
May | 366.931 | 15.194 | 110.417 | 5.390 | 20.583 |
June | 524.417 | 24.804 | 8.917 | 0.256 | 25.060 |
July | 534.556 | 28.396 | 8.083 | 0.202 | 28.598 |
August | 421.292 | 17.907 | 33.917 | 1.603 | 19.510 |
September | 108.000 | 2.634 | 336.194 | 18.205 | 20.839 |
October | 5.167 | 0.080 | 672.722 | 65.595 | 65.675 |
November | 0.000 | 0.000 | 720.000 | 92.264 | 92.264 |
December | 0.000 | 0.000 | 744.000 | 94.786 | 94.786 |
Annual Sum or Average | 2079.939 | 92.330 | 5100.219 | 569.966 | 662.296 |
Minimum of Months | 0.000 | 0.000 | 8.083 | 0.202 | 19.510 |
Maximum of Months | 534.556 | 28.396 | 744.000 | 95.206 | 95.206 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 104.114 | 104.114 |
February | 0.000 | 0.000 | 672.000 | 91.138 | 91.138 |
March | 0.000 | 0.000 | 741.000 | 94.567 | 94.567 |
April | 38.194 | 1.159 | 522.750 | 46.253 | 47.413 |
May | 173.111 | 5.735 | 193.236 | 7.609 | 13.344 |
June | 448.694 | 17.800 | 9.889 | 0.293 | 18.093 |
July | 479.972 | 18.762 | 8.833 | 0.225 | 18.986 |
August | 287.833 | 9.150 | 73.194 | 3.016 | 12.165 |
September | 19.250 | 0.293 | 477.444 | 25.296 | 25.588 |
October | 0.000 | 0.000 | 729.583 | 75.128 | 75.128 |
November | 0.000 | 0.000 | 720.000 | 101.012 | 101.012 |
December | 0.000 | 0.000 | 744.000 | 103.419 | 103.419 |
Annual Sum or Average | 1447.056 | 52.899 | 5635.931 | 652.071 | 704.969 |
Minimum of Months | 0.000 | 0.000 | 8.833 | 0.225 | 12.165 |
Maximum of Months | 479.972 | 18.762 | 744.000 | 104.114 | 104.114 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 45.594 | 45.594 |
February | 0.000 | 0.000 | 672.000 | 41.112 | 41.112 |
March | 0.000 | 0.000 | 740.806 | 44.477 | 44.477 |
April | 0.000 | 0.000 | 570.194 | 28.810 | 28.810 |
May | 113.167 | 1.539 | 120.986 | 4.583 | 6.122 |
June | 485.139 | 10.097 | 6.250 | 0.114 | 10.212 |
July | 517.944 | 12.186 | 5.250 | 0.105 | 12.291 |
August | 298.333 | 5.312 | 53.722 | 1.866 | 7.178 |
September | 0.000 | 0.000 | 401.472 | 16.452 | 16.452 |
October | 0.000 | 0.000 | 699.417 | 38.776 | 38.776 |
November | 0.000 | 0.000 | 720.000 | 44.123 | 44.123 |
December | 0.000 | 0.000 | 744.000 | 45.594 | 45.594 |
Annual Sum or Average | 1414.583 | 29.134 | 5478.097 | 311.608 | 340.742 |
Minimum of Months | 0.000 | 0.000 | 5.250 | 0.105 | 6.122 |
Maximum of Months | 517.944 | 12.186 | 744.000 | 45.594 | 45.594 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 80.222 | 80.222 |
February | 0.000 | 0.000 | 672.000 | 71.582 | 71.582 |
March | 0.000 | 0.000 | 736.833 | 75.136 | 75.136 |
April | 9.861 | 0.098 | 509.847 | 40.505 | 40.602 |
May | 304.403 | 8.345 | 120.500 | 5.904 | 14.249 |
June | 531.944 | 20.439 | 8.833 | 0.241 | 20.680 |
July | 538.931 | 23.173 | 8.417 | 0.210 | 23.382 |
August | 360.389 | 10.794 | 43.083 | 1.968 | 12.762 |
September | 7.778 | 0.067 | 422.750 | 21.904 | 21.972 |
October | 0.000 | 0.000 | 719.917 | 62.940 | 62.940 |
November | 0.000 | 0.000 | 720.000 | 77.665 | 77.665 |
December | 0.000 | 0.000 | 744.000 | 80.165 | 80.165 |
Annual Sum or Average | 1753.306 | 62.916 | 5450.181 | 518.441 | 581.357 |
Minimum of Months | 0.000 | 0.000 | 8.417 | 0.210 | 12.762 |
Maximum of Months | 538.931 | 23.173 | 744.000 | 80.222 | 80.222 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 118.389 | 118.389 |
February | 0.000 | 0.000 | 668.444 | 98.301 | 98.301 |
March | 0.000 | 0.000 | 660.833 | 87.961 | 87.961 |
April | 137.167 | 5.687 | 347.664 | 32.758 | 38.445 |
May | 305.500 | 13.210 | 96.569 | 4.209 | 17.419 |
June | 495.903 | 24.969 | 6.361 | 0.135 | 25.104 |
July | 533.667 | 26.896 | 5.583 | 0.127 | 27.022 |
August | 410.250 | 18.005 | 34.778 | 1.540 | 19.545 |
September | 100.167 | 2.852 | 307.097 | 16.156 | 19.008 |
October | 3.167 | 0.033 | 659.444 | 69.481 | 69.514 |
November | 0.000 | 0.000 | 720.000 | 115.975 | 115.975 |
December | 0.000 | 0.000 | 744.000 | 117.822 | 117.822 |
Annual Sum or Average | 1985.819 | 91.652 | 4994.775 | 662.856 | 754.507 |
Minimum of Months | 0.000 | 0.000 | 5.583 | 0.127 | 17.419 |
Maximum of Months | 533.667 | 26.896 | 744.000 | 118.389 | 118.389 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 64.778 | 64.778 |
February | 0.000 | 0.000 | 648.972 | 54.430 | 54.430 |
March | 0.000 | 0.000 | 613.028 | 49.894 | 49.894 |
April | 109.222 | 2.153 | 279.689 | 19.833 | 21.986 |
May | 325.056 | 8.255 | 47.319 | 1.885 | 10.140 |
June | 539.306 | 17.549 | 1.167 | 0.019 | 17.568 |
July | 588.222 | 20.701 | 1.167 | 0.019 | 20.721 |
August | 454.250 | 14.249 | 12.444 | 0.624 | 14.873 |
September | 107.750 | 2.018 | 174.250 | 8.614 | 10.632 |
October | 6.333 | 0.051 | 563.278 | 40.633 | 40.684 |
November | 0.000 | 0.000 | 720.000 | 62.947 | 62.947 |
December | 0.000 | 0.000 | 744.000 | 64.336 | 64.336 |
Annual Sum or Average | 2130.139 | 64.976 | 4549.314 | 368.014 | 432.990 |
Minimum of Months | 0.000 | 0.000 | 1.167 | 0.019 | 10.140 |
Maximum of Months | 588.222 | 20.701 | 744.000 | 64.778 | 64.778 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 96.286 | 96.286 |
February | 0.000 | 0.000 | 667.694 | 81.698 | 81.698 |
March | 1.000 | 0.002 | 633.067 | 72.338 | 72.341 |
April | 138.567 | 4.068 | 324.628 | 29.164 | 33.232 |
May | 407.556 | 17.449 | 64.667 | 3.126 | 20.575 |
June | 571.444 | 28.111 | 3.833 | 0.079 | 28.190 |
July | 589.653 | 31.673 | 4.083 | 0.090 | 31.763 |
August | 476.639 | 20.558 | 20.500 | 0.976 | 21.535 |
September | 123.250 | 3.166 | 263.333 | 13.918 | 17.084 |
October | 7.083 | 0.105 | 634.861 | 60.392 | 60.497 |
November | 0.000 | 0.000 | 720.000 | 93.617 | 93.617 |
December | 0.000 | 0.000 | 744.000 | 95.576 | 95.576 |
Annual Sum or Average | 2315.192 | 105.133 | 4824.667 | 547.259 | 652.392 |
Minimum of Months | 0.000 | 0.000 | 3.833 | 0.079 | 17.084 |
Maximum of Months | 589.653 | 31.673 | 744.000 | 96.286 | 96.286 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 105.819 | 105.819 |
February | 0.000 | 0.000 | 672.000 | 91.129 | 91.129 |
March | 0.000 | 0.000 | 731.972 | 91.689 | 91.689 |
April | 46.917 | 1.357 | 479.083 | 39.538 | 40.896 |
May | 208.278 | 6.787 | 108.500 | 4.458 | 11.245 |
June | 532.067 | 20.797 | 5.000 | 0.093 | 20.891 |
July | 546.444 | 21.899 | 4.583 | 0.102 | 22.001 |
August | 342.972 | 10.959 | 49.264 | 2.051 | 13.011 |
September | 23.833 | 0.325 | 408.889 | 20.481 | 20.806 |
October | 0.000 | 0.000 | 714.750 | 70.289 | 70.289 |
November | 0.000 | 0.000 | 720.000 | 103.136 | 103.136 |
December | 0.000 | 0.000 | 744.000 | 104.930 | 104.930 |
Annual Sum or Average | 1700.511 | 62.125 | 5382.042 | 633.716 | 695.841 |
Minimum of Months | 0.000 | 0.000 | 4.583 | 0.093 | 11.245 |
Maximum of Months | 546.444 | 21.899 | 744.000 | 105.819 | 105.819 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 48.322 | 48.322 |
February | 0.000 | 0.000 | 670.750 | 43.150 | 43.150 |
March | 0.000 | 0.000 | 724.111 | 45.672 | 45.672 |
April | 0.000 | 0.000 | 472.875 | 25.058 | 25.058 |
May | 154.639 | 2.366 | 60.361 | 2.234 | 4.601 |
June | 585.667 | 13.467 | 1.167 | 0.018 | 13.485 |
July | 604.111 | 15.658 | 1.250 | 0.020 | 15.679 |
August | 381.972 | 7.359 | 30.417 | 1.075 | 8.434 |
September | 0.000 | 0.000 | 292.556 | 12.443 | 12.443 |
October | 0.000 | 0.000 | 653.333 | 37.606 | 37.606 |
November | 0.000 | 0.000 | 720.000 | 46.791 | 46.791 |
December | 0.000 | 0.000 | 744.000 | 48.273 | 48.273 |
Annual Sum or Average | 1726.389 | 38.851 | 5114.819 | 310.664 | 349.515 |
Minimum of Months | 0.000 | 0.000 | 1.167 | 0.018 | 4.601 |
Maximum of Months | 604.111 | 15.658 | 744.000 | 48.322 | 48.322 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 81.523 | 81.523 |
February | 0.000 | 0.000 | 672.000 | 71.919 | 71.919 |
March | 0.000 | 0.000 | 730.375 | 73.956 | 73.956 |
April | 15.167 | 0.176 | 448.847 | 35.353 | 35.529 |
May | 360.472 | 10.359 | 74.167 | 3.523 | 13.881 |
June | 585.667 | 23.961 | 4.000 | 0.072 | 24.033 |
July | 594.028 | 26.600 | 4.083 | 0.090 | 26.689 |
August | 422.778 | 13.179 | 25.917 | 1.253 | 14.432 |
September | 11.472 | 0.110 | 349.111 | 17.611 | 17.721 |
October | 0.000 | 0.000 | 700.500 | 59.226 | 59.226 |
November | 0.000 | 0.000 | 720.000 | 78.984 | 78.984 |
December | 0.000 | 0.000 | 744.000 | 81.195 | 81.195 |
Annual Sum or Average | 1989.583 | 74.384 | 5217.000 | 504.704 | 579.088 |
Minimum of Months | 0.000 | 0.000 | 4.000 | 0.072 | 13.881 |
Maximum of Months | 594.028 | 26.600 | 744.000 | 81.523 | 81.523 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 122.590 | 122.590 |
February | 0.000 | 0.000 | 672.000 | 105.896 | 105.896 |
March | 0.000 | 0.000 | 718.375 | 104.917 | 104.917 |
April | 90.667 | 3.635 | 441.181 | 45.711 | 49.345 |
May | 249.833 | 10.769 | 184.806 | 7.958 | 18.726 |
June | 449.528 | 23.527 | 17.000 | 0.407 | 23.934 |
July | 488.722 | 25.683 | 11.611 | 0.319 | 26.003 |
August | 361.806 | 15.995 | 65.000 | 2.769 | 18.764 |
September | 70.083 | 1.821 | 416.722 | 24.564 | 26.386 |
October | 0.000 | 0.000 | 712.333 | 83.869 | 83.869 |
November | 0.000 | 0.000 | 720.000 | 118.953 | 118.953 |
December | 0.000 | 0.000 | 744.000 | 121.717 | 121.717 |
Annual Sum or Average | 1710.639 | 81.430 | 5447.028 | 739.671 | 821.101 |
Minimum of Months | 0.000 | 0.000 | 11.611 | 0.319 | 18.726 |
Maximum of Months | 488.722 | 25.683 | 744.000 | 122.590 | 122.590 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 66.045 | 66.045 |
February | 0.000 | 0.000 | 671.333 | 58.923 | 58.923 |
March | 0.000 | 0.000 | 714.403 | 60.832 | 60.832 |
April | 55.000 | 0.966 | 427.642 | 30.405 | 31.371 |
May | 238.306 | 6.041 | 118.944 | 4.786 | 10.827 |
June | 477.000 | 16.122 | 8.000 | 0.189 | 16.311 |
July | 531.028 | 19.404 | 7.083 | 0.158 | 19.562 |
August | 388.639 | 12.213 | 35.389 | 1.493 | 13.707 |
September | 73.333 | 0.964 | 319.278 | 16.007 | 16.970 |
October | 0.000 | 0.000 | 677.472 | 50.978 | 50.978 |
November | 0.000 | 0.000 | 720.000 | 63.927 | 63.927 |
December | 0.000 | 0.000 | 744.000 | 66.045 | 66.045 |
Annual Sum or Average | 1763.306 | 55.710 | 5187.544 | 419.789 | 475.499 |
Minimum of Months | 0.000 | 0.000 | 7.083 | 0.158 | 10.827 |
Maximum of Months | 531.028 | 19.404 | 744.000 | 66.045 | 66.045 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 93.626 | 93.626 |
February | 0.000 | 0.000 | 672.000 | 83.006 | 83.006 |
March | 0.000 | 0.000 | 717.903 | 84.042 | 84.042 |
April | 84.250 | 2.075 | 426.528 | 39.614 | 41.689 |
May | 348.236 | 13.517 | 119.250 | 5.967 | 19.484 |
June | 533.056 | 25.837 | 9.333 | 0.283 | 26.120 |
July | 552.097 | 29.819 | 8.333 | 0.231 | 30.049 |
August | 417.917 | 17.783 | 40.028 | 1.843 | 19.626 |
September | 93.944 | 1.741 | 378.903 | 21.591 | 23.332 |
October | 1.000 | 0.003 | 698.389 | 70.076 | 70.079 |
November | 0.000 | 0.000 | 720.000 | 90.634 | 90.634 |
December | 0.000 | 0.000 | 744.000 | 93.543 | 93.543 |
Annual Sum or Average | 2030.500 | 90.775 | 5278.667 | 584.456 | 675.230 |
Minimum of Months | 0.000 | 0.000 | 8.333 | 0.231 | 19.484 |
Maximum of Months | 552.097 | 29.819 | 744.000 | 93.626 | 93.626 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 113.799 | 113.799 |
February | 0.000 | 0.000 | 672.000 | 100.237 | 100.237 |
March | 0.000 | 0.000 | 743.167 | 104.484 | 104.484 |
April | 33.583 | 0.997 | 540.056 | 52.033 | 53.030 |
May | 174.833 | 6.116 | 217.847 | 8.553 | 14.669 |
June | 462.667 | 20.241 | 12.861 | 0.335 | 20.576 |
July | 503.083 | 21.690 | 9.833 | 0.259 | 21.949 |
August | 301.164 | 10.491 | 84.083 | 3.408 | 13.898 |
September | 14.333 | 0.196 | 515.750 | 29.211 | 29.408 |
October | 0.000 | 0.000 | 738.000 | 84.333 | 84.333 |
November | 0.000 | 0.000 | 720.000 | 110.259 | 110.259 |
December | 0.000 | 0.000 | 744.000 | 113.186 | 113.186 |
Annual Sum or Average | 1489.664 | 59.732 | 5741.597 | 720.097 | 779.829 |
Minimum of Months | 0.000 | 0.000 | 9.833 | 0.259 | 13.898 |
Maximum of Months | 503.083 | 21.690 | 744.000 | 113.799 | 113.799 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 57.686 | 57.686 |
February | 0.000 | 0.000 | 672.000 | 51.997 | 51.997 |
March | 0.000 | 0.000 | 742.167 | 56.053 | 56.053 |
April | 0.000 | 0.000 | 591.639 | 35.357 | 35.357 |
May | 126.750 | 2.191 | 151.986 | 5.488 | 7.679 |
June | 501.528 | 12.913 | 6.500 | 0.139 | 13.052 |
July | 546.444 | 15.520 | 6.583 | 0.142 | 15.662 |
August | 312.583 | 6.974 | 61.028 | 2.258 | 9.232 |
September | 0.000 | 0.000 | 459.750 | 20.482 | 20.482 |
October | 0.000 | 0.000 | 720.417 | 48.830 | 48.830 |
November | 0.000 | 0.000 | 720.000 | 55.825 | 55.825 |
December | 0.000 | 0.000 | 744.000 | 57.686 | 57.686 |
Annual Sum or Average | 1487.306 | 37.597 | 5620.069 | 391.945 | 429.541 |
Minimum of Months | 0.000 | 0.000 | 6.500 | 0.139 | 7.679 |
Maximum of Months | 546.444 | 15.520 | 744.000 | 57.686 | 57.686 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 79.000 | 79.000 |
February | 0.000 | 0.000 | 672.000 | 71.144 | 71.144 |
March | 0.000 | 0.000 | 742.056 | 75.482 | 75.482 |
April | 10.917 | 0.046 | 539.181 | 43.042 | 43.088 |
May | 296.847 | 7.964 | 125.111 | 6.269 | 14.234 |
June | 551.000 | 22.623 | 9.083 | 0.265 | 22.889 |
July | 560.264 | 25.771 | 8.500 | 0.230 | 26.000 |
August | 367.028 | 12.006 | 49.486 | 2.211 | 14.217 |
September | 4.750 | 0.013 | 468.319 | 25.185 | 25.197 |
October | 0.000 | 0.000 | 738.583 | 65.551 | 65.551 |
November | 0.000 | 0.000 | 720.000 | 76.451 | 76.451 |
December | 0.000 | 0.000 | 744.000 | 78.999 | 78.999 |
Annual Sum or Average | 1790.806 | 68.423 | 5560.319 | 523.828 | 592.251 |
Minimum of Months | 0.000 | 0.000 | 8.500 | 0.230 | 14.217 |
Maximum of Months | 560.264 | 25.771 | 744.000 | 79.000 | 79.000 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2076.33 | 0.00 | 0.00 |
February | 2299.67 | 0.00 | 0.00 |
March | 3030.85 | 0.00 | 0.00 |
April | 1929.72 | 0.00 | 0.00 |
May | 467.95 | 0.00 | 0.00 |
June | 31.16 | 0.00 | 0.00 |
July | 23.45 | 0.00 | 0.00 |
August | 158.31 | 0.00 | 0.00 |
September | 1283.79 | 0.00 | 0.00 |
October | 3320.28 | 0.00 | 0.00 |
November | 2125.37 | 0.00 | 0.00 |
December | 1354.04 | 0.00 | 0.00 |
Annual Sum or Average | 1503.72 | 0.00 | 0.00 |
Minimum of Months | 23.45 | 0.00 | 0.00 |
Maximum of Months | 3320.28 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1141.04 | 0.00 | 0.00 |
February | 1369.23 | 0.00 | 0.00 |
March | 1818.56 | 0.00 | 0.00 |
April | 1320.85 | 0.00 | 0.00 |
May | 269.75 | 0.00 | 0.00 |
June | 13.43 | 0.00 | 0.00 |
July | 10.04 | 0.00 | 0.00 |
August | 80.69 | 0.00 | 0.00 |
September | 804.25 | 0.00 | 0.00 |
October | 2083.27 | 0.00 | 0.00 |
November | 1146.32 | 0.00 | 0.00 |
December | 773.54 | 0.00 | 0.00 |
Annual Sum or Average | 899.64 | 0.00 | 0.00 |
Minimum of Months | 10.04 | 0.00 | 0.00 |
Maximum of Months | 2083.27 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1709.90 | 0.00 | 0.00 |
February | 1999.10 | 0.00 | 0.00 |
March | 2588.43 | 0.00 | 0.00 |
April | 1739.88 | 0.00 | 0.00 |
May | 338.06 | 0.00 | 0.00 |
June | 21.50 | 0.00 | 0.00 |
July | 17.10 | 0.00 | 0.00 |
August | 103.01 | 0.00 | 0.00 |
September | 1137.18 | 0.00 | 0.00 |
October | 2957.49 | 0.00 | 0.00 |
November | 1720.21 | 0.00 | 0.00 |
December | 1145.54 | 0.00 | 0.00 |
Annual Sum or Average | 1285.43 | 0.00 | 0.00 |
Minimum of Months | 17.10 | 0.00 | 0.00 |
Maximum of Months | 2957.49 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1865.08 | 0.00 | 0.00 |
February | 2230.75 | 0.00 | 0.00 |
March | 3246.23 | 0.00 | 0.00 |
April | 2409.06 | 0.00 | 0.00 |
May | 509.44 | 0.00 | 0.00 |
June | 24.76 | 0.00 | 0.00 |
July | 19.05 | 0.00 | 0.00 |
August | 208.18 | 0.00 | 0.00 |
September | 1630.39 | 0.00 | 0.00 |
October | 3455.58 | 0.00 | 0.00 |
November | 1883.31 | 0.00 | 0.00 |
December | 1232.54 | 0.00 | 0.00 |
Annual Sum or Average | 1554.81 | 0.00 | 0.00 |
Minimum of Months | 19.05 | 0.00 | 0.00 |
Maximum of Months | 3455.58 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 821.62 | 0.00 | 0.00 |
February | 1067.77 | 0.00 | 0.00 |
March | 1619.42 | 0.00 | 0.00 |
April | 1660.95 | 0.00 | 0.00 |
May | 319.91 | 0.00 | 0.00 |
June | 10.71 | 0.00 | 0.00 |
July | 9.25 | 0.00 | 0.00 |
August | 132.51 | 0.00 | 0.00 |
September | 1124.10 | 0.00 | 0.00 |
October | 1913.67 | 0.00 | 0.00 |
November | 822.65 | 0.00 | 0.00 |
December | 564.72 | 0.00 | 0.00 |
Annual Sum or Average | 836.34 | 0.00 | 0.00 |
Minimum of Months | 9.25 | 0.00 | 0.00 |
Maximum of Months | 1913.67 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1444.19 | 0.00 | 0.00 |
February | 1820.40 | 0.00 | 0.00 |
March | 2639.84 | 0.00 | 0.00 |
April | 2155.68 | 0.00 | 0.00 |
May | 380.37 | 0.00 | 0.00 |
June | 20.77 | 0.00 | 0.00 |
July | 17.88 | 0.00 | 0.00 |
August | 131.40 | 0.00 | 0.00 |
September | 1423.34 | 0.00 | 0.00 |
October | 2985.33 | 0.00 | 0.00 |
November | 1448.02 | 0.00 | 0.00 |
December | 988.11 | 0.00 | 0.00 |
Annual Sum or Average | 1283.85 | 0.00 | 0.00 |
Minimum of Months | 17.88 | 0.00 | 0.00 |
Maximum of Months | 2985.33 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2057.99 | 0.00 | 0.00 |
February | 2156.79 | 0.00 | 0.00 |
March | 2692.83 | 0.00 | 0.00 |
April | 1535.44 | 0.00 | 0.00 |
May | 271.74 | 0.00 | 0.00 |
June | 11.27 | 0.00 | 0.00 |
July | 10.67 | 0.00 | 0.00 |
August | 96.67 | 0.00 | 0.00 |
September | 981.60 | 0.00 | 0.00 |
October | 2958.08 | 0.00 | 0.00 |
November | 2142.53 | 0.00 | 0.00 |
December | 1334.73 | 0.00 | 0.00 |
Annual Sum or Average | 1349.64 | 0.00 | 0.00 |
Minimum of Months | 10.67 | 0.00 | 0.00 |
Maximum of Months | 2958.08 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1156.44 | 0.00 | 0.00 |
February | 1263.22 | 0.00 | 0.00 |
March | 1620.25 | 0.00 | 0.00 |
April | 966.14 | 0.00 | 0.00 |
May | 121.70 | 0.00 | 0.00 |
June | 1.72 | 0.00 | 0.00 |
July | 1.69 | 0.00 | 0.00 |
August | 38.75 | 0.00 | 0.00 |
September | 531.82 | 0.00 | 0.00 |
October | 1788.68 | 0.00 | 0.00 |
November | 1173.47 | 0.00 | 0.00 |
December | 761.64 | 0.00 | 0.00 |
Annual Sum or Average | 782.82 | 0.00 | 0.00 |
Minimum of Months | 1.69 | 0.00 | 0.00 |
Maximum of Months | 1788.68 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1716.87 | 0.00 | 0.00 |
February | 1897.49 | 0.00 | 0.00 |
March | 2278.64 | 0.00 | 0.00 |
April | 1380.99 | 0.00 | 0.00 |
May | 189.24 | 0.00 | 0.00 |
June | 6.80 | 0.00 | 0.00 |
July | 7.56 | 0.00 | 0.00 |
August | 59.12 | 0.00 | 0.00 |
September | 848.89 | 0.00 | 0.00 |
October | 2636.13 | 0.00 | 0.00 |
November | 1745.23 | 0.00 | 0.00 |
December | 1125.92 | 0.00 | 0.00 |
Annual Sum or Average | 1153.44 | 0.00 | 0.00 |
Minimum of Months | 6.80 | 0.00 | 0.00 |
Maximum of Months | 2636.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1874.92 | 0.00 | 0.00 |
February | 2151.00 | 0.00 | 0.00 |
March | 3047.64 | 0.00 | 0.00 |
April | 1991.55 | 0.00 | 0.00 |
May | 292.38 | 0.00 | 0.00 |
June | 8.38 | 0.00 | 0.00 |
July | 8.62 | 0.00 | 0.00 |
August | 135.31 | 0.00 | 0.00 |
September | 1294.36 | 0.00 | 0.00 |
October | 3134.57 | 0.00 | 0.00 |
November | 1920.43 | 0.00 | 0.00 |
December | 1216.32 | 0.00 | 0.00 |
Annual Sum or Average | 1418.28 | 0.00 | 0.00 |
Minimum of Months | 8.38 | 0.00 | 0.00 |
Maximum of Months | 3134.57 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 869.51 | 0.00 | 0.00 |
February | 1099.72 | 0.00 | 0.00 |
March | 1624.67 | 0.00 | 0.00 |
April | 1388.26 | 0.00 | 0.00 |
May | 151.20 | 0.00 | 0.00 |
June | 1.66 | 0.00 | 0.00 |
July | 1.81 | 0.00 | 0.00 |
August | 72.94 | 0.00 | 0.00 |
September | 829.05 | 0.00 | 0.00 |
October | 1791.51 | 0.00 | 0.00 |
November | 872.39 | 0.00 | 0.00 |
December | 593.85 | 0.00 | 0.00 |
Annual Sum or Average | 772.06 | 0.00 | 0.00 |
Minimum of Months | 1.66 | 0.00 | 0.00 |
Maximum of Months | 1791.51 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1465.02 | 0.00 | 0.00 |
February | 1789.36 | 0.00 | 0.00 |
March | 2539.50 | 0.00 | 0.00 |
April | 1811.65 | 0.00 | 0.00 |
May | 218.68 | 0.00 | 0.00 |
June | 6.45 | 0.00 | 0.00 |
July | 7.59 | 0.00 | 0.00 |
August | 78.20 | 0.00 | 0.00 |
September | 1114.99 | 0.00 | 0.00 |
October | 2724.85 | 0.00 | 0.00 |
November | 1472.60 | 0.00 | 0.00 |
December | 984.03 | 0.00 | 0.00 |
Annual Sum or Average | 1180.35 | 0.00 | 0.00 |
Minimum of Months | 6.45 | 0.00 | 0.00 |
Maximum of Months | 2724.85 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2195.66 | 0.00 | 0.00 |
February | 2536.30 | 0.00 | 0.00 |
March | 3482.19 | 0.00 | 0.00 |
April | 2275.66 | 0.00 | 0.00 |
May | 532.88 | 0.00 | 0.00 |
June | 34.58 | 0.00 | 0.00 |
July | 27.23 | 0.00 | 0.00 |
August | 185.84 | 0.00 | 0.00 |
September | 1543.80 | 0.00 | 0.00 |
October | 3773.92 | 0.00 | 0.00 |
November | 2217.80 | 0.00 | 0.00 |
December | 1447.35 | 0.00 | 0.00 |
Annual Sum or Average | 1682.65 | 0.00 | 0.00 |
Minimum of Months | 27.23 | 0.00 | 0.00 |
Maximum of Months | 3773.92 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1189.58 | 0.00 | 0.00 |
February | 1500.35 | 0.00 | 0.00 |
March | 2126.18 | 0.00 | 0.00 |
April | 1593.46 | 0.00 | 0.00 |
May | 327.91 | 0.00 | 0.00 |
June | 16.81 | 0.00 | 0.00 |
July | 13.66 | 0.00 | 0.00 |
August | 99.31 | 0.00 | 0.00 |
September | 1030.08 | 0.00 | 0.00 |
October | 2399.79 | 0.00 | 0.00 |
November | 1191.88 | 0.00 | 0.00 |
December | 817.28 | 0.00 | 0.00 |
Annual Sum or Average | 1022.36 | 0.00 | 0.00 |
Minimum of Months | 13.66 | 0.00 | 0.00 |
Maximum of Months | 2399.79 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1685.84 | 0.00 | 0.00 |
February | 2088.05 | 0.00 | 0.00 |
March | 2875.80 | 0.00 | 0.00 |
April | 2002.71 | 0.00 | 0.00 |
May | 378.91 | 0.00 | 0.00 |
June | 24.33 | 0.00 | 0.00 |
July | 19.67 | 0.00 | 0.00 |
August | 119.64 | 0.00 | 0.00 |
September | 1369.47 | 0.00 | 0.00 |
October | 3258.40 | 0.00 | 0.00 |
November | 1689.81 | 0.00 | 0.00 |
December | 1152.50 | 0.00 | 0.00 |
Annual Sum or Average | 1384.30 | 0.00 | 0.00 |
Minimum of Months | 19.67 | 0.00 | 0.00 |
Maximum of Months | 3258.40 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 2044.83 | 0.00 | 0.00 |
February | 2486.69 | 0.00 | 0.00 |
March | 3618.14 | 0.00 | 0.00 |
April | 2740.39 | 0.00 | 0.00 |
May | 582.17 | 0.00 | 0.00 |
June | 28.91 | 0.00 | 0.00 |
July | 22.01 | 0.00 | 0.00 |
August | 237.76 | 0.00 | 0.00 |
September | 1897.58 | 0.00 | 0.00 |
October | 3922.10 | 0.00 | 0.00 |
November | 2055.72 | 0.00 | 0.00 |
December | 1363.71 | 0.00 | 0.00 |
Annual Sum or Average | 1744.71 | 0.00 | 0.00 |
Minimum of Months | 22.01 | 0.00 | 0.00 |
Maximum of Months | 3922.10 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1039.55 | 0.00 | 0.00 |
February | 1349.56 | 0.00 | 0.00 |
March | 2033.87 | 0.00 | 0.00 |
April | 2024.93 | 0.00 | 0.00 |
May | 385.02 | 0.00 | 0.00 |
June | 13.13 | 0.00 | 0.00 |
July | 12.42 | 0.00 | 0.00 |
August | 160.84 | 0.00 | 0.00 |
September | 1391.57 | 0.00 | 0.00 |
October | 2402.33 | 0.00 | 0.00 |
November | 1040.83 | 0.00 | 0.00 |
December | 714.50 | 0.00 | 0.00 |
Annual Sum or Average | 1044.13 | 0.00 | 0.00 |
Minimum of Months | 12.42 | 0.00 | 0.00 |
Maximum of Months | 2402.33 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1423.63 | 0.00 | 0.00 |
February | 1842.89 | 0.00 | 0.00 |
March | 2694.95 | 0.00 | 0.00 |
April | 2336.67 | 0.00 | 0.00 |
May | 405.50 | 0.00 | 0.00 |
June | 23.38 | 0.00 | 0.00 |
July | 19.74 | 0.00 | 0.00 |
August | 148.30 | 0.00 | 0.00 |
September | 1660.29 | 0.00 | 0.00 |
October | 3184.89 | 0.00 | 0.00 |
November | 1425.39 | 0.00 | 0.00 |
December | 978.46 | 0.00 | 0.00 |
Annual Sum or Average | 1341.07 | 0.00 | 0.00 |
Minimum of Months | 19.74 | 0.00 | 0.00 |
Maximum of Months | 3184.89 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6771.99 | 0.00 | 0.00 |
February | 5279.79 | 0.00 | 0.00 |
March | 2359.94 | 0.00 | 0.00 |
April | 255.15 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 808.05 | 0.00 | 0.00 |
November | 6372.31 | 0.00 | 0.00 |
December | 8113.14 | 0.00 | 0.00 |
Annual Sum or Average | 2483.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8113.14 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5720.81 | 0.00 | 0.00 |
February | 4470.07 | 0.00 | 0.00 |
March | 2347.97 | 0.00 | 0.00 |
April | 361.11 | 0.00 | 0.00 |
May | 0.02 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 4.69 | 0.00 | 0.00 |
October | 955.32 | 0.00 | 0.00 |
November | 5464.31 | 0.00 | 0.00 |
December | 6601.84 | 0.00 | 0.00 |
Annual Sum or Average | 2149.23 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6601.84 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7205.39 | 0.00 | 0.00 |
February | 5522.77 | 0.00 | 0.00 |
March | 2525.17 | 0.00 | 0.00 |
April | 350.44 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.06 | 0.00 | 0.00 |
October | 1042.65 | 0.00 | 0.00 |
November | 6881.61 | 0.00 | 0.00 |
December | 8415.42 | 0.00 | 0.00 |
Annual Sum or Average | 2647.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8415.42 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7267.24 | 0.00 | 0.00 |
February | 6006.97 | 0.00 | 0.00 |
March | 3050.51 | 0.00 | 0.00 |
April | 369.32 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.02 | 0.00 | 0.00 |
October | 1160.72 | 0.00 | 0.00 |
November | 7005.61 | 0.00 | 0.00 |
December | 8375.49 | 0.00 | 0.00 |
Annual Sum or Average | 2753.19 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8375.49 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6089.08 | 0.00 | 0.00 |
February | 5310.49 | 0.00 | 0.00 |
March | 3479.70 | 0.00 | 0.00 |
April | 771.65 | 0.00 | 0.00 |
May | 3.58 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 1.13 | 0.00 | 0.00 |
September | 60.82 | 0.00 | 0.00 |
October | 1640.94 | 0.00 | 0.00 |
November | 6070.33 | 0.00 | 0.00 |
December | 6781.40 | 0.00 | 0.00 |
Annual Sum or Average | 2503.15 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6781.40 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7745.49 | 0.00 | 0.00 |
February | 6365.62 | 0.00 | 0.00 |
March | 3382.09 | 0.00 | 0.00 |
April | 559.90 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 12.70 | 0.00 | 0.00 |
October | 1500.69 | 0.00 | 0.00 |
November | 7549.80 | 0.00 | 0.00 |
December | 8718.12 | 0.00 | 0.00 |
Annual Sum or Average | 2968.90 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8718.12 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5481.45 | 0.00 | 0.00 |
February | 4240.94 | 0.00 | 0.00 |
March | 1768.14 | 0.00 | 0.00 |
April | 150.62 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 494.59 | 0.00 | 0.00 |
November | 5089.24 | 0.00 | 0.00 |
December | 6768.78 | 0.00 | 0.00 |
Annual Sum or Average | 1988.61 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6768.78 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4417.87 | 0.00 | 0.00 |
February | 3397.81 | 0.00 | 0.00 |
March | 1606.92 | 0.00 | 0.00 |
April | 195.38 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.13 | 0.00 | 0.00 |
September | 1.02 | 0.00 | 0.00 |
October | 578.75 | 0.00 | 0.00 |
November | 4181.04 | 0.00 | 0.00 |
December | 5259.44 | 0.00 | 0.00 |
Annual Sum or Average | 1628.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5259.44 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5892.84 | 0.00 | 0.00 |
February | 4444.82 | 0.00 | 0.00 |
March | 1901.69 | 0.00 | 0.00 |
April | 223.64 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.03 | 0.00 | 0.00 |
October | 694.06 | 0.00 | 0.00 |
November | 5593.91 | 0.00 | 0.00 |
December | 7075.37 | 0.00 | 0.00 |
Annual Sum or Average | 2141.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7075.37 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5923.71 | 0.00 | 0.00 |
February | 4867.86 | 0.00 | 0.00 |
March | 2267.29 | 0.00 | 0.00 |
April | 223.74 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 784.99 | 0.00 | 0.00 |
November | 5680.67 | 0.00 | 0.00 |
December | 7010.74 | 0.00 | 0.00 |
Annual Sum or Average | 2216.50 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7010.74 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 4981.14 | 0.00 | 0.00 |
February | 4226.03 | 0.00 | 0.00 |
March | 2494.47 | 0.00 | 0.00 |
April | 420.35 | 0.00 | 0.00 |
May | 1.20 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 2.21 | 0.00 | 0.00 |
September | 26.75 | 0.00 | 0.00 |
October | 1041.80 | 0.00 | 0.00 |
November | 4899.89 | 0.00 | 0.00 |
December | 5613.15 | 0.00 | 0.00 |
Annual Sum or Average | 1964.09 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5613.15 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6442.67 | 0.00 | 0.00 |
February | 5183.17 | 0.00 | 0.00 |
March | 2502.27 | 0.00 | 0.00 |
April | 333.69 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.69 | 0.00 | 0.00 |
October | 1063.61 | 0.00 | 0.00 |
November | 6242.05 | 0.00 | 0.00 |
December | 7348.16 | 0.00 | 0.00 |
Annual Sum or Average | 2412.35 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7348.16 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8007.84 | 0.00 | 0.00 |
February | 6291.88 | 0.00 | 0.00 |
March | 2907.53 | 0.00 | 0.00 |
April | 339.47 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 1091.87 | 0.00 | 0.00 |
November | 7638.33 | 0.00 | 0.00 |
December | 9442.12 | 0.00 | 0.00 |
Annual Sum or Average | 2960.10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9442.12 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 6981.35 | 0.00 | 0.00 |
February | 5569.43 | 0.00 | 0.00 |
March | 3021.82 | 0.00 | 0.00 |
April | 505.64 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.03 | 0.00 | 0.00 |
September | 17.05 | 0.00 | 0.00 |
October | 1354.71 | 0.00 | 0.00 |
November | 6778.51 | 0.00 | 0.00 |
December | 7980.91 | 0.00 | 0.00 |
Annual Sum or Average | 2669.82 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7980.91 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8615.90 | 0.00 | 0.00 |
February | 6718.35 | 0.00 | 0.00 |
March | 3264.31 | 0.00 | 0.00 |
April | 510.35 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 8.87 | 0.00 | 0.00 |
October | 1494.97 | 0.00 | 0.00 |
November | 8301.74 | 0.00 | 0.00 |
December | 9861.51 | 0.00 | 0.00 |
Annual Sum or Average | 3213.92 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9861.51 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8394.37 | 0.00 | 0.00 |
February | 6925.30 | 0.00 | 0.00 |
March | 3579.72 | 0.00 | 0.00 |
April | 445.11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.74 | 0.00 | 0.00 |
October | 1395.09 | 0.00 | 0.00 |
November | 8138.75 | 0.00 | 0.00 |
December | 9629.55 | 0.00 | 0.00 |
Annual Sum or Average | 3190.16 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9629.55 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7258.91 | 0.00 | 0.00 |
February | 6272.27 | 0.00 | 0.00 |
March | 3947.27 | 0.00 | 0.00 |
April | 791.59 | 0.00 | 0.00 |
May | 0.57 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.22 | 0.00 | 0.00 |
September | 47.49 | 0.00 | 0.00 |
October | 1825.67 | 0.00 | 0.00 |
November | 7218.59 | 0.00 | 0.00 |
December | 8115.27 | 0.00 | 0.00 |
Annual Sum or Average | 2939.56 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8115.27 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 9042.33 | 0.00 | 0.00 |
February | 7565.64 | 0.00 | 0.00 |
March | 4284.35 | 0.00 | 0.00 |
April | 792.54 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.01 | 0.00 | 0.00 |
September | 33.27 | 0.00 | 0.00 |
October | 2038.48 | 0.00 | 0.00 |
November | 8928.13 | 0.00 | 0.00 |
December | 10147.36 | 0.00 | 0.00 |
Annual Sum or Average | 3548.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10147.36 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.13 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.13 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.13 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.13 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.09 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.09 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.08 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.10 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.16 |
August | 0.00 | 0.00 | 0.08 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.12 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.12 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.20 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.20 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.19 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.16 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.11 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.11 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.30 |
April | 0.00 | 0.00 | 1435.28 | 1034.14 |
May | 0.00 | 0.00 | 1415.28 | 1053.72 |
June | 0.00 | 0.00 | 1342.82 | 967.52 |
July | 0.00 | 0.00 | 1282.37 | 954.76 |
August | 0.00 | 0.00 | 1235.77 | 920.06 |
September | 0.00 | 0.00 | 1235.71 | 890.34 |
October | 0.00 | 0.00 | 1269.32 | 945.04 |
November | 0.00 | 0.00 | 1331.05 | 959.04 |
December | 0.00 | 0.00 | 1404.72 | 1045.85 |
Annual Sum or Average | 0.00 | 0.00 | 1353.77 | 11867.45 |
Minimum of Months | 0.00 | 0.00 | 1235.71 | 890.34 |
Maximum of Months | 0.00 | 0.00 | 1435.28 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.92 | 1067.59 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.88 | 1065.33 |
April | 0.00 | 0.00 | 1435.36 | 1034.19 |
May | 0.00 | 0.00 | 1413.14 | 1052.12 |
June | 0.00 | 0.00 | 1344.58 | 968.78 |
July | 0.00 | 0.00 | 1282.22 | 954.65 |
August | 0.00 | 0.00 | 1235.05 | 919.53 |
September | 0.00 | 0.00 | 1235.84 | 890.43 |
October | 0.00 | 0.00 | 1269.15 | 944.92 |
November | 0.00 | 0.00 | 1330.87 | 958.91 |
December | 0.00 | 0.00 | 1404.80 | 1045.92 |
Annual Sum or Average | 0.00 | 0.00 | 1353.66 | 11866.47 |
Minimum of Months | 0.00 | 0.00 | 1235.05 | 890.43 |
Maximum of Months | 0.00 | 0.00 | 1435.36 | 1067.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.27 | 1034.12 |
May | 0.00 | 0.00 | 1413.05 | 1052.05 |
June | 0.00 | 0.00 | 1345.06 | 969.13 |
July | 0.00 | 0.00 | 1279.86 | 952.89 |
August | 0.00 | 0.00 | 1235.85 | 920.12 |
September | 0.00 | 0.00 | 1235.77 | 890.39 |
October | 0.00 | 0.00 | 1269.11 | 944.89 |
November | 0.00 | 0.00 | 1330.87 | 958.90 |
December | 0.00 | 0.00 | 1404.80 | 1045.92 |
Annual Sum or Average | 0.00 | 0.00 | 1353.54 | 11865.38 |
Minimum of Months | 0.00 | 0.00 | 1235.77 | 890.39 |
Maximum of Months | 0.00 | 0.00 | 1435.27 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.64 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.20 | 1034.08 |
May | 0.00 | 0.00 | 1415.36 | 1053.78 |
June | 0.00 | 0.00 | 1344.53 | 968.75 |
July | 0.00 | 0.00 | 1282.24 | 954.67 |
August | 0.00 | 0.00 | 1235.30 | 919.72 |
September | 0.00 | 0.00 | 1238.77 | 892.54 |
October | 0.00 | 0.00 | 1269.15 | 944.91 |
November | 0.00 | 0.00 | 1330.24 | 958.45 |
December | 0.00 | 0.00 | 1405.09 | 1046.13 |
Annual Sum or Average | 0.00 | 0.00 | 1354.06 | 11869.99 |
Minimum of Months | 0.00 | 0.00 | 1235.30 | 892.54 |
Maximum of Months | 0.00 | 0.00 | 1435.20 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1434.18 | 1067.79 |
February | 0.00 | 0.00 | 1434.08 | 964.39 |
March | 0.00 | 0.00 | 1432.78 | 1066.75 |
April | 0.00 | 0.00 | 1436.17 | 1034.78 |
May | 0.00 | 0.00 | 1415.46 | 1053.85 |
June | 0.00 | 0.00 | 1345.02 | 969.10 |
July | 0.00 | 0.00 | 1279.98 | 952.98 |
August | 0.00 | 0.00 | 1235.96 | 920.21 |
September | 0.00 | 0.00 | 1238.19 | 892.13 |
October | 0.00 | 0.00 | 1269.88 | 945.46 |
November | 0.00 | 0.00 | 1328.74 | 957.37 |
December | 0.00 | 0.00 | 1407.07 | 1047.60 |
Annual Sum or Average | 0.00 | 0.00 | 1354.34 | 11872.40 |
Minimum of Months | 0.00 | 0.00 | 1235.96 | 892.13 |
Maximum of Months | 0.00 | 0.00 | 1436.17 | 1067.79 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.97 | 1067.63 |
February | 0.00 | 0.00 | 1433.66 | 964.10 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.36 | 1034.19 |
May | 0.00 | 0.00 | 1414.96 | 1053.47 |
June | 0.00 | 0.00 | 1344.87 | 968.99 |
July | 0.00 | 0.00 | 1279.93 | 952.94 |
August | 0.00 | 0.00 | 1235.87 | 920.14 |
September | 0.00 | 0.00 | 1236.34 | 890.80 |
October | 0.00 | 0.00 | 1271.06 | 946.34 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.93 | 11868.80 |
Minimum of Months | 0.00 | 0.00 | 1235.87 | 890.80 |
Maximum of Months | 0.00 | 0.00 | 1435.36 | 1067.63 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.35 | 1034.18 |
May | 0.00 | 0.00 | 1413.08 | 1052.08 |
June | 0.00 | 0.00 | 1344.30 | 968.58 |
July | 0.00 | 0.00 | 1281.81 | 954.34 |
August | 0.00 | 0.00 | 1235.73 | 920.04 |
September | 0.00 | 0.00 | 1234.31 | 889.33 |
October | 0.00 | 0.00 | 1271.00 | 946.30 |
November | 0.00 | 0.00 | 1328.66 | 957.31 |
December | 0.00 | 0.00 | 1407.03 | 1047.57 |
Annual Sum or Average | 0.00 | 0.00 | 1353.69 | 11866.70 |
Minimum of Months | 0.00 | 0.00 | 1234.31 | 889.33 |
Maximum of Months | 0.00 | 0.00 | 1435.35 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.68 | 964.12 |
March | 0.00 | 0.00 | 1430.93 | 1065.36 |
April | 0.00 | 0.00 | 1435.30 | 1034.15 |
May | 0.00 | 0.00 | 1413.12 | 1052.11 |
June | 0.00 | 0.00 | 1342.89 | 967.57 |
July | 0.00 | 0.00 | 1282.14 | 954.59 |
August | 0.00 | 0.00 | 1234.20 | 918.90 |
September | 0.00 | 0.00 | 1236.56 | 890.96 |
October | 0.00 | 0.00 | 1269.40 | 945.10 |
November | 0.00 | 0.00 | 1328.70 | 957.35 |
December | 0.00 | 0.00 | 1407.04 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.53 | 11865.36 |
Minimum of Months | 0.00 | 0.00 | 1234.20 | 890.96 |
Maximum of Months | 0.00 | 0.00 | 1435.30 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.48 | 1034.28 |
May | 0.00 | 0.00 | 1412.54 | 1051.67 |
June | 0.00 | 0.00 | 1342.60 | 967.36 |
July | 0.00 | 0.00 | 1282.19 | 954.63 |
August | 0.00 | 0.00 | 1234.27 | 918.95 |
September | 0.00 | 0.00 | 1236.71 | 891.06 |
October | 0.00 | 0.00 | 1269.17 | 944.93 |
November | 0.00 | 0.00 | 1328.68 | 957.33 |
December | 0.00 | 0.00 | 1407.04 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.46 | 11864.76 |
Minimum of Months | 0.00 | 0.00 | 1234.27 | 891.06 |
Maximum of Months | 0.00 | 0.00 | 1435.48 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.64 | 964.09 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.48 | 1034.28 |
May | 0.00 | 0.00 | 1415.26 | 1053.70 |
June | 0.00 | 0.00 | 1343.19 | 967.79 |
July | 0.00 | 0.00 | 1281.92 | 954.43 |
August | 0.00 | 0.00 | 1235.40 | 919.79 |
September | 0.00 | 0.00 | 1236.22 | 890.71 |
October | 0.00 | 0.00 | 1271.07 | 946.34 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.94 | 11868.90 |
Minimum of Months | 0.00 | 0.00 | 1235.40 | 890.71 |
Maximum of Months | 0.00 | 0.00 | 1435.48 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1434.19 | 1067.79 |
February | 0.00 | 0.00 | 1433.76 | 964.17 |
March | 0.00 | 0.00 | 1430.88 | 1065.33 |
April | 0.00 | 0.00 | 1437.59 | 1035.80 |
May | 0.00 | 0.00 | 1413.18 | 1052.15 |
June | 0.00 | 0.00 | 1344.95 | 969.05 |
July | 0.00 | 0.00 | 1279.81 | 952.85 |
August | 0.00 | 0.00 | 1235.31 | 919.72 |
September | 0.00 | 0.00 | 1236.57 | 890.96 |
October | 0.00 | 0.00 | 1271.16 | 946.41 |
November | 0.00 | 0.00 | 1328.68 | 957.33 |
December | 0.00 | 0.00 | 1407.08 | 1047.61 |
Annual Sum or Average | 0.00 | 0.00 | 1353.97 | 11869.19 |
Minimum of Months | 0.00 | 0.00 | 1235.31 | 890.96 |
Maximum of Months | 0.00 | 0.00 | 1437.59 | 1067.79 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.64 | 964.09 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.60 | 1034.36 |
May | 0.00 | 0.00 | 1414.89 | 1053.42 |
June | 0.00 | 0.00 | 1342.11 | 967.01 |
July | 0.00 | 0.00 | 1281.82 | 954.35 |
August | 0.00 | 0.00 | 1234.51 | 919.12 |
September | 0.00 | 0.00 | 1236.11 | 890.63 |
October | 0.00 | 0.00 | 1271.08 | 946.35 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.73 | 11867.12 |
Minimum of Months | 0.00 | 0.00 | 1234.51 | 890.63 |
Maximum of Months | 0.00 | 0.00 | 1435.60 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.64 | 964.09 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.37 | 1034.20 |
May | 0.00 | 0.00 | 1414.87 | 1053.41 |
June | 0.00 | 0.00 | 1345.23 | 969.25 |
July | 0.00 | 0.00 | 1279.87 | 952.90 |
August | 0.00 | 0.00 | 1236.01 | 920.25 |
September | 0.00 | 0.00 | 1236.26 | 890.74 |
October | 0.00 | 0.00 | 1271.01 | 946.30 |
November | 0.00 | 0.00 | 1328.66 | 957.31 |
December | 0.00 | 0.00 | 1407.03 | 1047.57 |
Annual Sum or Average | 0.00 | 0.00 | 1353.94 | 11868.91 |
Minimum of Months | 0.00 | 0.00 | 1236.01 | 890.74 |
Maximum of Months | 0.00 | 0.00 | 1435.37 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1434.09 | 1067.72 |
February | 0.00 | 0.00 | 1433.72 | 964.14 |
March | 0.00 | 0.00 | 1430.86 | 1065.32 |
April | 0.00 | 0.00 | 1435.57 | 1034.34 |
May | 0.00 | 0.00 | 1415.18 | 1053.64 |
June | 0.00 | 0.00 | 1342.69 | 967.42 |
July | 0.00 | 0.00 | 1282.24 | 954.66 |
August | 0.00 | 0.00 | 1235.19 | 919.64 |
September | 0.00 | 0.00 | 1235.92 | 890.50 |
October | 0.00 | 0.00 | 1269.11 | 944.89 |
November | 0.00 | 0.00 | 1330.99 | 958.99 |
December | 0.00 | 0.00 | 1404.67 | 1045.82 |
Annual Sum or Average | 0.00 | 0.00 | 1353.73 | 11867.08 |
Minimum of Months | 0.00 | 0.00 | 1235.19 | 890.50 |
Maximum of Months | 0.00 | 0.00 | 1435.57 | 1067.72 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.91 | 1067.59 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.41 | 1034.23 |
May | 0.00 | 0.00 | 1412.95 | 1051.98 |
June | 0.00 | 0.00 | 1344.25 | 968.55 |
July | 0.00 | 0.00 | 1281.97 | 954.46 |
August | 0.00 | 0.00 | 1234.99 | 919.49 |
September | 0.00 | 0.00 | 1235.77 | 890.38 |
October | 0.00 | 0.00 | 1269.15 | 944.92 |
November | 0.00 | 0.00 | 1330.99 | 958.99 |
December | 0.00 | 0.00 | 1404.80 | 1045.91 |
Annual Sum or Average | 0.00 | 0.00 | 1353.59 | 11865.88 |
Minimum of Months | 0.00 | 0.00 | 1234.99 | 890.38 |
Maximum of Months | 0.00 | 0.00 | 1435.41 | 1067.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.64 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.09 | 1034.00 |
May | 0.00 | 0.00 | 1415.48 | 1053.87 |
June | 0.00 | 0.00 | 1344.52 | 968.74 |
July | 0.00 | 0.00 | 1282.32 | 954.72 |
August | 0.00 | 0.00 | 1235.68 | 920.00 |
September | 0.00 | 0.00 | 1236.74 | 891.09 |
October | 0.00 | 0.00 | 1271.05 | 946.33 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1354.13 | 11870.61 |
Minimum of Months | 0.00 | 0.00 | 1235.68 | 891.09 |
Maximum of Months | 0.00 | 0.00 | 1435.09 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.85 | 1067.54 |
February | 0.00 | 0.00 | 1433.81 | 964.20 |
March | 0.00 | 0.00 | 1432.41 | 1066.47 |
April | 0.00 | 0.00 | 1436.16 | 1034.77 |
May | 0.00 | 0.00 | 1415.42 | 1053.82 |
June | 0.00 | 0.00 | 1345.08 | 969.15 |
July | 0.00 | 0.00 | 1279.89 | 952.91 |
August | 0.00 | 0.00 | 1235.93 | 920.18 |
September | 0.00 | 0.00 | 1237.29 | 891.48 |
October | 0.00 | 0.00 | 1270.68 | 946.06 |
November | 0.00 | 0.00 | 1328.71 | 957.35 |
December | 0.00 | 0.00 | 1407.27 | 1047.75 |
Annual Sum or Average | 0.00 | 0.00 | 1354.25 | 11871.68 |
Minimum of Months | 0.00 | 0.00 | 1235.93 | 891.48 |
Maximum of Months | 0.00 | 0.00 | 1436.16 | 1067.54 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1434.30 | 1067.87 |
February | 0.00 | 0.00 | 1433.80 | 964.20 |
March | 0.00 | 0.00 | 1430.86 | 1065.31 |
April | 0.00 | 0.00 | 1437.06 | 1035.41 |
May | 0.00 | 0.00 | 1413.17 | 1052.14 |
June | 0.00 | 0.00 | 1345.04 | 969.12 |
July | 0.00 | 0.00 | 1279.94 | 952.95 |
August | 0.00 | 0.00 | 1235.84 | 920.12 |
September | 0.00 | 0.00 | 1236.57 | 890.96 |
October | 0.00 | 0.00 | 1271.04 | 946.33 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.12 | 1047.64 |
Annual Sum or Average | 0.00 | 0.00 | 1353.99 | 11869.37 |
Minimum of Months | 0.00 | 0.00 | 1235.84 | 890.96 |
Maximum of Months | 0.00 | 0.00 | 1437.06 | 1067.87 |
Report: HEATING AND COOLING LOADS
For: UNHEATEDBSMT
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4459.54 |
February | 0.09 | 3282.61 |
March | 10.11 | 2398.69 |
April | 61.62 | 830.88 |
May | 100.68 | 133.05 |
June | 144.53 | 10.04 |
July | 146.28 | 6.69 |
August | 115.53 | 47.29 |
September | 43.64 | 417.02 |
October | 6.03 | 1806.47 |
November | 0.00 | 4065.01 |
December | 0.00 | 4812.83 |
Annual Sum or Average | 628.50 | 22270.13 |
Minimum of Months | 0.00 | 6.69 |
Maximum of Months | 146.28 | 4812.83 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2797.78 |
February | 0.82 | 1971.16 |
March | 15.83 | 1416.58 |
April | 49.24 | 471.88 |
May | 83.92 | 67.89 |
June | 107.97 | 2.68 |
July | 116.37 | 1.81 |
August | 99.34 | 16.01 |
September | 52.46 | 205.44 |
October | 13.43 | 980.12 |
November | 0.00 | 2525.66 |
December | 0.00 | 3074.78 |
Annual Sum or Average | 539.38 | 13531.79 |
Minimum of Months | 0.00 | 1.81 |
Maximum of Months | 116.37 | 3074.78 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4434.83 |
February | 0.20 | 3187.72 |
March | 13.72 | 2180.19 |
April | 55.54 | 772.33 |
May | 125.12 | 97.14 |
June | 158.68 | 6.87 |
July | 170.30 | 4.29 |
August | 129.09 | 30.67 |
September | 48.07 | 346.23 |
October | 8.25 | 1700.83 |
November | 0.00 | 4065.63 |
December | 0.00 | 4809.65 |
Annual Sum or Average | 708.96 | 21636.38 |
Minimum of Months | 0.00 | 4.29 |
Maximum of Months | 170.30 | 4809.65 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4626.82 |
February | 0.00 | 3695.93 |
March | 0.38 | 2959.24 |
April | 26.93 | 1100.43 |
May | 68.16 | 137.65 |
June | 122.53 | 8.13 |
July | 120.30 | 5.03 |
August | 80.04 | 66.91 |
September | 21.05 | 552.04 |
October | 1.32 | 2115.11 |
November | 0.00 | 4302.36 |
December | 0.00 | 4874.17 |
Annual Sum or Average | 440.72 | 24443.83 |
Minimum of Months | 0.00 | 5.03 |
Maximum of Months | 122.53 | 4874.17 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2793.31 |
February | 0.00 | 2284.17 |
March | 0.45 | 1899.17 |
April | 15.03 | 724.68 |
May | 55.39 | 81.79 |
June | 85.85 | 2.11 |
July | 90.10 | 1.58 |
August | 64.11 | 31.16 |
September | 27.59 | 300.34 |
October | 4.66 | 1240.08 |
November | 0.00 | 2678.74 |
December | 0.00 | 3006.88 |
Annual Sum or Average | 343.19 | 15044.01 |
Minimum of Months | 0.00 | 1.58 |
Maximum of Months | 90.10 | 3006.88 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4589.28 |
February | 0.00 | 3594.39 |
March | 0.94 | 2694.93 |
April | 21.71 | 1036.71 |
May | 89.47 | 116.53 |
June | 136.73 | 6.57 |
July | 143.73 | 4.52 |
August | 91.69 | 41.61 |
September | 25.08 | 461.08 |
October | 2.30 | 1988.29 |
November | 0.00 | 4301.11 |
December | 0.00 | 4867.89 |
Annual Sum or Average | 511.65 | 23702.89 |
Minimum of Months | 0.00 | 4.52 |
Maximum of Months | 143.73 | 4867.89 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3488.37 |
February | 0.61 | 2489.16 |
March | 15.77 | 1749.66 |
April | 74.12 | 552.25 |
May | 116.82 | 73.71 |
June | 158.81 | 1.66 |
July | 160.56 | 2.09 |
August | 128.13 | 24.15 |
September | 52.74 | 269.07 |
October | 9.65 | 1324.78 |
November | 0.00 | 3158.25 |
December | 0.00 | 3801.89 |
Annual Sum or Average | 717.21 | 16935.03 |
Minimum of Months | 0.00 | 1.66 |
Maximum of Months | 160.56 | 3801.89 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 1841.86 |
February | 4.58 | 1217.71 |
March | 25.59 | 817.98 |
April | 67.46 | 254.61 |
May | 99.20 | 23.57 |
June | 123.69 | 0.14 |
July | 132.29 | 0.12 |
August | 113.93 | 10.26 |
September | 65.70 | 118.54 |
October | 23.09 | 575.12 |
November | 0.00 | 1624.26 |
December | 0.00 | 2068.47 |
Annual Sum or Average | 655.53 | 8552.63 |
Minimum of Months | 0.00 | 0.12 |
Maximum of Months | 132.29 | 2068.47 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3465.22 |
February | 0.74 | 2396.72 |
March | 21.61 | 1556.43 |
April | 68.64 | 509.17 |
May | 142.58 | 46.11 |
June | 176.15 | 1.17 |
July | 186.69 | 1.26 |
August | 143.84 | 13.92 |
September | 59.78 | 227.74 |
October | 13.16 | 1240.01 |
November | 0.00 | 3159.28 |
December | 0.00 | 3798.74 |
Annual Sum or Average | 813.18 | 16415.76 |
Minimum of Months | 0.00 | 1.17 |
Maximum of Months | 186.69 | 3798.74 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3638.43 |
February | 0.00 | 2875.17 |
March | 2.04 | 2236.62 |
April | 34.28 | 745.40 |
May | 83.23 | 76.78 |
June | 138.12 | 1.38 |
July | 135.49 | 1.57 |
August | 91.31 | 37.05 |
September | 28.67 | 379.63 |
October | 2.87 | 1597.58 |
November | 0.00 | 3380.53 |
December | 0.00 | 3849.87 |
Annual Sum or Average | 516.01 | 18820.01 |
Minimum of Months | 0.00 | 1.38 |
Maximum of Months | 138.12 | 3849.87 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 1997.22 |
February | 0.20 | 1575.32 |
March | 3.07 | 1201.32 |
April | 28.18 | 416.50 |
May | 67.55 | 31.03 |
June | 103.28 | 0.10 |
July | 106.95 | 0.14 |
August | 76.84 | 14.36 |
September | 40.58 | 200.89 |
October | 10.45 | 766.78 |
November | 0.00 | 1870.12 |
December | 0.00 | 2152.74 |
Annual Sum or Average | 437.10 | 10226.51 |
Minimum of Months | 0.00 | 0.10 |
Maximum of Months | 106.95 | 2152.74 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3636.67 |
February | 0.00 | 2778.43 |
March | 1.92 | 1971.79 |
April | 30.19 | 701.63 |
May | 105.63 | 55.65 |
June | 155.14 | 0.85 |
July | 160.80 | 1.30 |
August | 105.38 | 21.03 |
September | 33.49 | 310.30 |
October | 4.24 | 1478.65 |
November | 0.00 | 3379.87 |
December | 0.00 | 3847.10 |
Annual Sum or Average | 596.78 | 18183.28 |
Minimum of Months | 0.00 | 0.85 |
Maximum of Months | 160.80 | 3847.10 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5542.02 |
February | 0.00 | 4415.71 |
March | 0.26 | 3400.81 |
April | 17.58 | 1299.20 |
May | 86.93 | 130.45 |
June | 148.12 | 8.37 |
July | 157.02 | 6.00 |
August | 96.96 | 47.07 |
September | 20.01 | 603.37 |
October | 0.55 | 2525.26 |
November | 0.00 | 5273.84 |
December | 0.00 | 5922.18 |
Annual Sum or Average | 527.42 | 29174.28 |
Minimum of Months | 0.00 | 6.00 |
Maximum of Months | 157.02 | 5922.18 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5461.93 |
February | 0.00 | 4050.59 |
March | 3.79 | 2846.66 |
April | 42.57 | 1012.91 |
May | 115.56 | 117.92 |
June | 164.08 | 8.60 |
July | 177.49 | 6.08 |
August | 127.71 | 36.22 |
September | 38.74 | 475.49 |
October | 4.73 | 2239.60 |
November | 0.00 | 5061.39 |
December | 0.00 | 5887.24 |
Annual Sum or Average | 674.66 | 27204.63 |
Minimum of Months | 0.00 | 6.08 |
Maximum of Months | 177.49 | 5887.24 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5487.43 |
February | 0.00 | 4143.38 |
March | 4.19 | 3108.60 |
April | 49.50 | 1099.05 |
May | 94.57 | 167.59 |
June | 150.20 | 8.58 |
July | 154.26 | 8.74 |
August | 114.96 | 59.28 |
September | 35.10 | 559.00 |
October | 3.12 | 2351.77 |
November | 0.00 | 5060.50 |
December | 0.00 | 5890.72 |
Annual Sum or Average | 605.90 | 27944.65 |
Minimum of Months | 0.00 | 8.58 |
Maximum of Months | 154.26 | 5890.72 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3861.30 |
February | 0.00 | 3151.76 |
March | 0.25 | 2591.53 |
April | 13.14 | 1000.71 |
May | 55.87 | 98.84 |
June | 99.66 | 3.77 |
July | 105.80 | 2.66 |
August | 71.43 | 46.28 |
September | 22.17 | 433.11 |
October | 2.49 | 1750.07 |
November | 0.00 | 3698.08 |
December | 0.00 | 4144.65 |
Annual Sum or Average | 370.81 | 20782.76 |
Minimum of Months | 0.00 | 2.66 |
Maximum of Months | 105.80 | 4144.65 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3784.66 |
February | 0.10 | 2801.85 |
March | 4.68 | 2039.49 |
April | 37.90 | 693.29 |
May | 79.20 | 90.47 |
June | 115.63 | 4.53 |
July | 125.78 | 3.01 |
August | 100.75 | 26.28 |
September | 41.98 | 301.74 |
October | 7.06 | 1458.45 |
November | 0.00 | 3513.72 |
December | 0.00 | 4143.90 |
Annual Sum or Average | 513.08 | 18861.39 |
Minimum of Months | 0.00 | 3.01 |
Maximum of Months | 125.78 | 4143.90 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:52:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5632.89 |
February | 0.00 | 4516.67 |
March | 0.10 | 3660.64 |
April | 24.34 | 1393.08 |
May | 68.17 | 173.94 |
June | 134.31 | 8.53 |
July | 134.29 | 6.42 |
August | 85.58 | 80.71 |
September | 17.17 | 718.92 |
October | 0.53 | 2659.04 |
November | 0.00 | 5274.60 |
December | 0.00 | 5938.86 |
Annual Sum or Average | 464.49 | 30064.29 |
Minimum of Months | 0.00 | 6.42 |
Maximum of Months | 134.31 | 5938.86 |