Program Version:EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:53
Tabular Output Report in Format: HTML
Building: US+MF+CZ8+elecres+heatedbsmt+IECC_2018
Environment: ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2021-05-12 10:53:30
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1332906.80 | 34.17 | 45.33 |
Net Site Energy | 1332906.80 | 34.17 | 45.33 |
Total Source Energy | 4221315.85 | 108.22 | 143.56 |
Net Source Energy | 4221315.85 | 108.22 | 143.56 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.87 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 700722.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14756.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 41293.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299798.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 43883.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 213643.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1332906.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 700722.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 14756.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 41293.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 18809.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 25617.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 18266.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330767.30 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 213643.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 33.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Other | 10.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 45.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 24.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 34.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1332906.804 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1332906.804 | 100.00 |
Total On-Site and Utility Electric Sources | 1332906.804 | 100.00 |
Total Electricity End Uses | 1332906.804 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 330767.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 330767.30 | 100.00 |
Total Water End Uses | 330767.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.83 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3347.50 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| HEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.5.0-Unknown, YMD=2021.05.12 10:53 |
RunPeriod | ANNUAL |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [ft] | 436.37 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58539.52 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6220 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6220 | 600.28 | 2.9092 |
Total | 39005.22 | 325627.71 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.3446 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242278.90 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.4571 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 12-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:09 |
Heating | 277.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 33.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 199.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 526.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 277.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 5.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 0.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 3.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 199.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 2219187.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46734.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 130776.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 59568.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949462.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138979.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 676607.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4221315.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 75.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 143.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 56.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 17.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 108.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
ZoneHVAC:EnergyRecoveryVentilatorUser-Specified Supply Air Flow Rate [ft3/min] | User-Specified Exhaust Air Flow Rate [ft3/min] | |
ERV_UNITHEATEDBSMT | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.99 |
ERV_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.99 |
ERV_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.99 |
User-Specified Maximum Flow Rate [ft3/min] | Design Size Maximum Flow Rate [ft3/min] | |
OASUPPLYFAN_UNITHEATEDBSMT | 44.99 | |
OAEXHAUSTFAN_UNITHEATEDBSMT | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | 44.99 | |
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | 44.99 | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 358.41 | |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 184.78 | |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 282.94 | |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 318.98 | |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 156.58 | |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 234.21 | |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 422.84 | |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 226.85 | |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 339.44 | |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 374.29 | |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 167.21 | |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 286.05 | |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 436.35 | |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 234.26 | |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 333.18 | |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 404.35 | |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 203.45 | |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 280.98 | |
SUPPLY FAN_UNITHEATEDBSMT | 361.76 |
User-Specified Nominal Supply Air Flow Rate [ft3/min] | |
OA_HEAT_RECOVERY_UNITHEATEDBSMT | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | 44.99 |
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | 44.99 |
Design Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 361.76 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 358.41 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 184.78 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 282.94 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 318.98 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 156.58 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 234.21 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 422.84 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 226.85 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 339.44 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 374.29 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 167.21 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 286.05 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 280.98 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 333.18 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 436.35 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 203.45 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 234.26 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 404.35 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 358.41 | 358.41 | 358.41 | 358.41 | 358.41 | 358.41 | 1.00 | 1.00 | 358.41 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 184.78 | 184.78 | 184.78 | 184.78 | 184.78 | 184.78 | 1.00 | 1.00 | 184.78 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 282.94 | 282.94 | 282.94 | 282.94 | 282.94 | 282.94 | 1.00 | 1.00 | 282.94 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 318.98 | 318.98 | 318.98 | 318.98 | 318.98 | 318.98 | 1.00 | 1.00 | 318.98 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 156.58 | 156.58 | 156.58 | 156.58 | 156.58 | 156.58 | 1.00 | 1.00 | 156.58 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 234.21 | 234.21 | 234.21 | 234.21 | 234.21 | 234.21 | 1.00 | 1.00 | 234.21 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 422.84 | 422.84 | 422.84 | 422.84 | 422.84 | 422.84 | 1.00 | 1.00 | 422.84 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 226.85 | 226.85 | 226.85 | 226.85 | 226.85 | 226.85 | 1.00 | 1.00 | 226.85 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 339.44 | 339.44 | 339.44 | 339.44 | 339.44 | 339.44 | 1.00 | 1.00 | 339.44 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 374.29 | 374.29 | 374.29 | 374.29 | 374.29 | 374.29 | 1.00 | 1.00 | 374.29 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.21 | 167.21 | 167.21 | 167.21 | 167.21 | 167.21 | 1.00 | 1.00 | 167.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.05 | 286.05 | 286.05 | 286.05 | 286.05 | 286.05 | 1.00 | 1.00 | 286.05 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 436.35 | 436.35 | 436.35 | 436.35 | 436.35 | 436.35 | 1.00 | 1.00 | 436.35 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 234.26 | 234.26 | 234.26 | 234.26 | 234.26 | 234.26 | 1.00 | 1.00 | 234.26 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.18 | 333.18 | 333.18 | 333.18 | 333.18 | 333.18 | 1.00 | 1.00 | 333.18 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 404.35 | 404.35 | 404.35 | 404.35 | 404.35 | 404.35 | 1.00 | 1.00 | 404.35 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 203.45 | 203.45 | 203.45 | 203.45 | 203.45 | 203.45 | 1.00 | 1.00 | 203.45 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 280.98 | 280.98 | 280.98 | 280.98 | 280.98 | 280.98 | 1.00 | 1.00 | 280.98 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 361.76 | 361.76 | 361.76 | 361.76 | 361.76 | 361.76 | 1.00 | 1.00 | 361.76 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 358.41 | 0.796240 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 184.78 | 0.410505 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 282.94 | 0.628570 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 318.98 | 0.708631 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 156.58 | 0.347850 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 234.21 | 0.520322 | 0.800655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 422.84 | 0.939368 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 226.85 | 0.503954 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 339.44 | 0.754087 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 374.29 | 0.831524 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 167.21 | 0.371477 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 286.05 | 0.635475 | 0.800655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 436.35 | 0.969389 | 0.800655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 234.26 | 0.520422 | 0.800655 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 333.18 | 0.740176 | 0.800655 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 404.35 | 0.898286 | 0.800655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 203.45 | 0.451987 | 0.800655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 280.98 | 0.624222 | 0.800655 |
DX COOLING COIL_UNITHEATEDBSMT | 361.76 | 0.920744 | 0.797912 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 358.41 | 358.41 | 358.41 | 17204.09 | 0.796240 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 184.78 | 184.78 | 184.78 | 13880.28 | 0.410505 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 282.94 | 282.94 | 282.94 | 17198.18 | 0.628570 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 318.98 | 318.98 | 318.98 | 17205.67 | 0.708631 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 156.58 | 156.58 | 156.58 | 13879.41 | 0.347850 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 234.21 | 234.21 | 234.21 | 17194.92 | 0.520322 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 422.84 | 422.84 | 422.84 | 14899.34 | 0.939368 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 226.85 | 226.85 | 226.85 | 11365.62 | 0.503954 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 339.44 | 339.44 | 339.44 | 14891.33 | 0.754087 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 374.29 | 374.29 | 374.29 | 14900.80 | 0.831524 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 167.21 | 167.21 | 167.21 | 11364.50 | 0.371477 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 286.05 | 286.05 | 286.05 | 14887.72 | 0.635475 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 436.35 | 436.35 | 436.35 | 19929.06 | 0.969389 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 234.26 | 234.26 | 234.26 | 16379.85 | 0.520422 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 333.18 | 333.18 | 333.18 | 19919.43 | 0.740176 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 404.35 | 404.35 | 404.35 | 19928.68 | 0.898286 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 203.45 | 203.45 | 203.45 | 16377.62 | 0.451987 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 280.98 | 280.98 | 280.98 | 19915.36 | 0.624222 | 1.00 |
ACANDF_UNITHEATEDBSMT | 361.76 | 361.76 | 361.76 | 24812.60 | 0.920744 | 1.00 |
Design Size Nominal Capacity [Btu/h] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 17204.09 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 13880.28 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 17198.18 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 17205.67 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 13879.41 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 17194.92 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 14899.34 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 11365.62 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 14891.33 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 14900.80 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 11364.50 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 14887.72 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 19929.06 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 16379.85 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 19919.43 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 19928.68 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 16377.62 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 19915.36 |
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | 24812.60 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
VersionVersion ID | |
1 | 9.5 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 2.59 | -0.0 | 4.60 | 11.91 | 30.97 | 45.70 | 55.63 | 58.66 | 53.51 | 42.08 | 26.80 | 12.63 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 436.37 | 14. | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 29.25 | 65.16 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ8+elecres+heatedbsmt+IECC_2018 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.8807 | Rough | 0.1021 | 3.533E-002 | 1.255 | 0.350 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 7.7625 | Rough | 1.5719 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3227 | Rough | 0.4584 | 6.015E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5870 | Smooth | 0.1387 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.4127 | VerySmooth | 0.1373 | 0.101 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | HEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | HEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.622 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.531 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 527.915 | 0.440 | 77.362 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 36.293 | 527.915 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 166.833 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 72.311 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0498 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
10 | BASEMENT WALL | 24 | 3 | 10 | 0.167 | 0.0664 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
11 | iz-EXTERIOR FLOOR | 25 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.1020 | 0.035 | 1.255 | 0.350 | 0.8807 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.1388 | 0.072 | 32.003 | 0.183 | 0.5870 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
25 | BSMTWALL_CONSOL_LAYER | 0.4584 | 0.060 | 7.541 | 0.248 | 2.323 |
26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 10 | 0.51360630E-08 | -0.22035233E-13 | 0.91774209E-08 | -0.50676220E-13 |
2 | 9 | -0.14060012E-04 | 0.39159197E-12 | -0.22958088E-04 | 0.29728831E-08 |
3 | 8 | 0.28980689E-02 | 0.65531654E-09 | 0.46215968E-02 | -0.71708779E-05 |
4 | 7 | -0.65978682E-01 | 0.13350779E-06 | -0.16306378 | 0.13238707E-02 |
5 | 6 | 0.64596177 | 0.50193482E-05 | 2.1320981 | -0.28125917E-01 |
6 | 5 | -3.4215999 | 0.48298777E-04 | -13.652056 | 0.25148823 |
7 | 4 | 10.645660 | 0.13839053E-03 | 47.881148 | -1.1749737 |
8 | 3 | -19.924231 | 0.11919231E-03 | -96.040791 | 3.0621859 |
9 | 2 | 21.976583 | 0.26462555E-04 | 109.48934 | -4.4404618 |
10 | 1 | -13.118296 | 0.91387708E-06 | -65.855375 | 3.3273744 |
11 | 0 | 3.2593552 | 0.33613880E-09 | 16.204438 | |
12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
18 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
19 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
20 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
21 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
22 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
23 | 12 | 0.94888791E-16 | -0.11237443E-15 | 0.21480527E-09 | -0.52606005E-16 |
24 | 11 | -0.44509090E-09 | -0.12338758E-15 | -0.11566016E-03 | 0.28501063E-09 |
25 | 10 | 0.60393314E-04 | 0.62564840E-13 | 0.62960490E-02 | -0.38672578E-04 |
26 | 9 | -0.20055671E-02 | 0.85912012E-10 | -0.12885789 | 0.13084700E-02 |
27 | 8 | 0.28697042E-01 | 0.10381403E-07 | 1.3966036 | -0.19129448E-01 |
28 | 7 | -0.23229993 | 0.28493476E-06 | -9.1473517 | 0.15872626 |
29 | 6 | 1.1750436 | 0.24973161E-05 | 38.552224 | -0.82592201 |
30 | 5 | -3.8729952 | 0.80040830E-05 | -107.65441 | 2.8111251 |
31 | 4 | 8.4143451 | 0.96510929E-05 | 200.56463 | -6.3313915 |
32 | 3 | -11.897084 | 0.41099356E-05 | -245.77565 | 9.3152582 |
33 | 2 | 10.487404 | 0.50788650E-06 | 189.69676 | -8.5734564 |
34 | 1 | -5.2147174 | 0.10902359E-07 | -83.415737 | 4.4633233 |
35 | 0 | 1.1135774 | 0.38882120E-11 | 15.905642 | |
36 | 12 | 0.21480527E-09 | -0.11237443E-15 | 0.94888791E-16 | -0.52606005E-16 |
37 | 11 | -0.11566016E-03 | -0.12338758E-15 | -0.44509090E-09 | 0.28501063E-09 |
38 | 10 | 0.62960490E-02 | 0.62564840E-13 | 0.60393314E-04 | -0.38672578E-04 |
39 | 9 | -0.12885789 | 0.85912012E-10 | -0.20055671E-02 | 0.13084700E-02 |
40 | 8 | 1.3966036 | 0.10381403E-07 | 0.28697042E-01 | -0.19129448E-01 |
41 | 7 | -9.1473517 | 0.28493476E-06 | -0.23229993 | 0.15872626 |
42 | 6 | 38.552224 | 0.24973161E-05 | 1.1750436 | -0.82592201 |
43 | 5 | -107.65441 | 0.80040830E-05 | -3.8729952 | 2.8111251 |
44 | 4 | 200.56463 | 0.96510929E-05 | 8.4143451 | -6.3313915 |
45 | 3 | -245.77565 | 0.41099356E-05 | -11.897084 | 9.3152582 |
46 | 2 | 189.69676 | 0.50788650E-06 | 10.487404 | -8.5734564 |
47 | 1 | -83.415737 | 0.10902359E-07 | -5.2147174 | 4.4633233 |
48 | 0 | 15.905642 | 0.38882120E-11 | 1.1135774 | |
49 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
50 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
51 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
52 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
53 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
54 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
55 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
56 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
57 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
58 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
59 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
60 | 5 | -0.32935335E-06 | 0.42931990E-07 | -0.32935335E-06 | 0.47097488E-08 |
61 | 4 | 0.68052310E-03 | 0.12823787E-03 | 0.68052310E-03 | -0.14200104E-04 |
62 | 3 | -0.11535993 | 0.17375615E-01 | -0.11535993 | 0.40770076E-02 |
63 | 2 | 2.1922172 | 0.21284128 | 2.1922172 | -0.13171357 |
64 | 1 | -7.8704965 | 0.30308566 | -7.8704965 | 0.79499401 |
65 | 0 | 6.3596665 | 0.33276539E-01 | 6.3596665 | |
66 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
67 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
68 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
69 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
70 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
71 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
72 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
73 | 10 | 0.50442590E-10 | 0.37421431E-14 | 0.50442587E-10 | -0.86521684E-16 |
74 | 9 | -0.53972773E-06 | 0.41502128E-13 | -0.53972773E-06 | 0.83963618E-10 |
75 | 8 | 0.10045687E-02 | 0.32837718E-09 | 0.10045687E-02 | -0.39657273E-06 |
76 | 7 | -0.35699803E-01 | 0.19108467E-06 | -0.35699803E-01 | 0.47332591E-03 |
77 | 6 | 0.49910094 | 0.13935795E-04 | 0.49910094 | -0.11937255E-01 |
78 | 5 | -3.5897715 | 0.21519702E-03 | -3.5897715 | 0.12239145 |
79 | 4 | 14.570676 | 0.91210570E-03 | 14.570676 | -0.65483682 |
80 | 3 | -34.297718 | 0.11291753E-02 | -34.297718 | 1.9662386 |
81 | 2 | 45.961246 | 0.36528821E-03 | 45.961246 | -3.3045605 |
82 | 1 | -32.291846 | 0.20188525E-04 | -32.291846 | 2.8751859 |
83 | 0 | 9.1856636 | 0.31580648E-07 | 9.1856636 | |
84 | 4 | 0.60443234E-14 | -0.40788276E-14 | 0.29631924E-13 | -0.77798347E-16 |
85 | 3 | -0.23145793E-05 | 0.79669069E-06 | -0.11254351E-04 | 0.39394231E-13 |
86 | 2 | 0.78801895E-01 | 0.29587917E-01 | 0.49771861 | -0.76025120E-05 |
87 | 1 | -1.1535996 | 0.80192706 | -8.3915550 | 0.21114735 |
88 | 0 | 2.4177143 | 0.51139848 | 9.2367617 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.300 | 0.335 | 0.248 | 0.883 |
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.300 | 0.335 | 0.248 | 0.883 |
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.300 | 0.309 | 4.646E-002 | 0.133 |
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 0.929 | 0.920 | 0.920 |
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 0.906 | 0.900 | 0.900 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13728 | 0.24698 | 0.55113 | 0.55113 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.068 | 0.9692 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
19 | VENTILATION_UNITHEATEDBSMT | ALWAYS_OFF | HEATEDBSMT | 7794.37 | 0.0 | 0.000 | 0.000 | N/A | 0.000 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | HEATEDBSMT | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | HEATEDBSMT | Cooling | 0.00000 | 0.00000 | 0.00000 | 44.99491 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 81.32000 | 0.00701 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 | |
2 | HEATEDBSMT | Heating | 19562.67085 | 19562.67085 | 361.75843 | 361.75843 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | -43.4200 | 0.00006 | 7794.38637 | 0.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 8296.56137 | 8296.56137 | 358.41097 | 358.41097 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 75.99560 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 11842.04478 | 11842.04478 | 218.96184 | 218.96184 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 4277.33803 | 4277.33803 | 184.78091 | 184.78091 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 81.32000 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 8469.06093 | 8469.06093 | 156.59447 | 156.59447 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 6549.59519 | 6549.59519 | 282.94488 | 282.94488 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 77.40320 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 11836.05382 | 11836.05382 | 218.85590 | 218.85590 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 7383.65354 | 7383.65354 | 318.98301 | 318.98301 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.15960 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 11843.65033 | 11843.65033 | 218.98302 | 218.98302 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 2969.14625 | 2969.14625 | 128.26863 | 128.26863 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 70.48760 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 8468.17848 | 8468.17848 | 156.57816 | 156.57816 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 5421.63825 | 5421.63825 | 234.21607 | 234.21607 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 73.30280 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 11832.74551 | 11832.74551 | 218.79235 | 218.79235 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 9787.82629 | 9787.82629 | 422.83893 | 422.83893 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 74.61860 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 9503.01263 | 9503.01263 | 175.72477 | 175.72477 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 5251.04340 | 5251.04340 | 226.84319 | 226.84319 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 80.95280 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 5917.00244 | 5917.00244 | 109.41651 | 109.41651 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 7857.44284 | 7857.44284 | 339.42792 | 339.42792 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 78.01520 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 9494.87658 | 9494.87658 | 175.57434 | 175.57434 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 8664.10665 | 8664.10665 | 374.30080 | 374.30080 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 72.81320 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 9504.48938 | 9504.48938 | 175.75210 | 175.75210 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 3870.62582 | 3870.62582 | 167.21333 | 167.21333 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 69.93680 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 5915.87126 | 5915.87126 | 109.39554 | 109.39554 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6621.50821 | 6621.50821 | 286.03810 | 286.03810 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 74.80220 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 9491.21428 | 9491.21428 | 175.50676 | 175.50676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 6504.28403 | 6504.28403 | 280.97454 | 280.97454 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.26120 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 14593.39440 | 14593.39440 | 269.83047 | 269.83047 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 7712.51933 | 7712.51933 | 333.17792 | 333.17792 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 78.01520 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 14597.51497 | 14597.51497 | 269.91522 | 269.91522 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 10100.64773 | 10100.64773 | 436.35588 | 436.35588 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.15960 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 14607.29318 | 14607.29318 | 270.08471 | 270.08471 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 4587.89732 | 4587.89732 | 198.19892 | 198.19892 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 70.21220 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 11003.31417 | 11003.31417 | 203.45315 | 203.45315 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 5422.66550 | 5422.66550 | 234.25844 | 234.25844 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 80.76920 | 0.00701 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 11005.57421 | 11005.57421 | 203.49510 | 203.49510 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
37 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 9359.76271 | 9359.76271 | 404.34317 | 404.34317 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 73.14980 | 0.00700 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
38 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 14606.90814 | 14606.90814 | 270.08471 | 270.08471 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -43.4200 | 0.00006 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2409.73 | 358.41097 | 358.41097 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 5042.23 | 218.96184 | 218.96184 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1323.96 | 184.78091 | 184.78091 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 4068.08 | 156.59447 | 156.59447 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1925.05 | 282.94488 | 282.94488 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 5040.50 | 218.85590 | 218.85590 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2120.32 | 318.98301 | 318.98301 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 5042.69 | 218.98302 | 218.98302 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 793.97 | 128.26863 | 128.26863 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 4067.82 | 156.57816 | 156.57816 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1541.71 | 234.21607 | 234.21607 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 5039.54 | 218.79235 | 218.79235 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2821.00 | 422.83893 | 422.83893 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4366.75 | 175.72477 | 175.72477 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1599.97 | 226.84319 | 226.84319 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3331.07 | 109.41651 | 109.41651 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2311.31 | 339.42792 | 339.42792 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4364.40 | 175.57434 | 175.57434 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2471.14 | 374.30080 | 374.30080 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4367.17 | 175.75210 | 175.75210 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1046.54 | 167.21333 | 167.21333 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3330.75 | 109.39554 | 109.39554 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1909.26 | 286.03810 | 286.03810 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4363.34 | 175.50676 | 175.50676 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 2904.88 | 436.35588 | 436.35588 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 5840.87 | 270.08471 | 270.08471 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1646.95 | 234.25844 | 234.25844 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 4800.66 | 203.49510 | 203.49510 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2269.46 | 333.17792 | 333.17792 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 5838.05 | 269.91522 | 269.91522 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 2676.75 | 404.34317 | 404.34317 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 5840.76 | 270.08471 | 270.08471 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1257.53 | 198.19892 | 198.19892 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 4800.01 | 203.45315 | 203.45315 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 1881.86 | 280.97454 | 280.97454 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 5836.86 | 269.83047 | 269.83047 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
37 | CENTRAL SYSTEM_UNITHEATEDBSMT | Cooling | Sensible | 389.59 | 44.99491 | 44.99491 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
38 | CENTRAL SYSTEM_UNITHEATEDBSMT | Heating | Sensible | 7272.16 | 361.75843 | 361.75843 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
2 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNITHEATEDBSMT | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
3 | Fan:OnOff | OASUPPLYFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
4 | Fan:OnOff | OAEXHAUSTFAN_UNITHEATEDBSMT | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
5 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNITHEATEDBSMT | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNITHEATEDBSMT | Design Size Maximum Air Flow Rate [ft3/min] | 361.75843 |
7 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
8 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
9 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
10 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
11 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 358.41097 |
13 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
14 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
15 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
16 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
17 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 184.78091 |
19 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
20 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
21 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
22 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
23 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
24 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 282.94488 |
25 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
26 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
27 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
28 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
29 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
30 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 318.98301 |
31 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
32 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
33 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
34 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
35 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
36 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 156.57816 |
37 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
38 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
39 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
40 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
41 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
42 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 234.21607 |
43 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
44 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
45 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
46 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
47 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
48 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 422.83893 |
49 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
50 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
51 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
52 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
53 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
54 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 226.84319 |
55 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
56 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
57 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
58 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
59 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
60 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 339.42792 |
61 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
62 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
63 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
64 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
65 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
66 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 374.30080 |
67 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
68 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
69 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
70 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
71 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
72 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 167.21333 |
73 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
74 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
75 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
76 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
77 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
78 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 286.03810 |
79 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
80 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
81 | Fan:OnOff | OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
82 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
83 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
84 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 280.97454 |
85 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
86 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT3_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
87 | Fan:OnOff | OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
88 | Fan:OnOff | OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
89 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
90 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 333.17792 |
91 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
92 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
93 | Fan:OnOff | OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
94 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
95 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
96 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 436.35588 |
97 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
98 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
99 | Fan:OnOff | OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
100 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
101 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
102 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 203.45315 |
103 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
104 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT2_FRONTROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
105 | Fan:OnOff | OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
106 | Fan:OnOff | OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
107 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
108 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 234.25844 |
109 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Supply Air Flow Rate [ft3/min] | 44.99491 |
110 | ZoneHVAC:EnergyRecoveryVentilator | ERV_UNIT1_BACKROW_TOPFLOOR | User-Specified Exhaust Air Flow Rate [ft3/min] | 44.99491 |
111 | Fan:OnOff | OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
112 | Fan:OnOff | OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | User-Specified Maximum Flow Rate [ft3/min] | 44.99491 |
113 | HeatExchanger:AirToAir:SensibleAndLatent | OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR | User-Specified Nominal Supply Air Flow Rate [ft3/min] | 44.99491 |
114 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 404.34317 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 358.41097 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 358.41097 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 358.41097 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 358.41097 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 358.41097 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 358.41097 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 184.78091 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 184.78091 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 184.78091 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 184.78091 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 184.78091 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 184.78091 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 282.94488 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 282.94488 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 282.94488 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 282.94488 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 282.94488 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 282.94488 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 318.98301 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 318.98301 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 318.98301 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 318.98301 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 318.98301 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 318.98301 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 156.57816 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 156.57816 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 156.57816 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 156.57816 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 156.57816 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 156.57816 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 234.21607 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 234.21607 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 234.21607 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 234.21607 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 234.21607 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 234.21607 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 422.83893 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 422.83893 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 422.83893 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 422.83893 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 422.83893 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 422.83893 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 226.84319 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 226.84319 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 226.84319 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 226.84319 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 226.84319 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 226.84319 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 339.42792 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 339.42792 |
181 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 339.42792 |
182 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 339.42792 |
183 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 339.42792 |
184 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 339.42792 |
185 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
186 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
187 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 374.30080 |
188 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 374.30080 |
189 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 374.30080 |
190 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 374.30080 |
191 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 374.30080 |
192 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 374.30080 |
193 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
194 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
195 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 167.21333 |
196 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 167.21333 |
197 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 167.21333 |
198 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 167.21333 |
199 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 167.21333 |
200 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 167.21333 |
201 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
202 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
203 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 286.03810 |
204 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 286.03810 |
205 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 286.03810 |
206 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 286.03810 |
207 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 286.03810 |
208 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 286.03810 |
209 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
210 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
211 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 436.35588 |
212 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 436.35588 |
213 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 436.35588 |
214 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 436.35588 |
215 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 436.35588 |
216 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 436.35588 |
217 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
218 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
219 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 234.25844 |
220 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 234.25844 |
221 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 234.25844 |
222 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 234.25844 |
223 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 234.25844 |
224 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 234.25844 |
225 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
226 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
227 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 333.17792 |
228 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 333.17792 |
229 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 333.17792 |
230 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 333.17792 |
231 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 333.17792 |
232 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 333.17792 |
233 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
234 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
235 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 404.34317 |
236 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 404.34317 |
237 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 404.34317 |
238 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 404.34317 |
239 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 404.34317 |
240 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 404.34317 |
241 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
242 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
243 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 203.45315 |
244 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 203.45315 |
245 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 203.45315 |
246 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 203.45315 |
247 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 203.45315 |
248 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 203.45315 |
249 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
251 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 280.97454 |
252 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 280.97454 |
253 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 280.97454 |
254 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 280.97454 |
255 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 280.97454 |
256 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 280.97454 |
257 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 361.75843 |
260 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 361.75843 |
261 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 361.75843 |
262 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Heating Design Air Flow Rate [ft3/min] | 361.75843 |
263 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Cooling Design Air Flow Rate [ft3/min] | 361.75843 |
264 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Adjusted Main Design Air Flow Rate [ft3/min] | 361.75843 |
265 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 358.41097 |
268 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 184.78091 |
269 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 282.94488 |
270 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 318.98301 |
271 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 156.57816 |
272 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 234.21607 |
273 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 422.83893 |
274 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 226.84319 |
275 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 339.42792 |
276 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 374.30080 |
277 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 167.21333 |
278 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 286.03810 |
279 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 436.35588 |
280 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 234.25844 |
281 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 333.17792 |
282 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 404.34317 |
283 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 203.45315 |
284 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 280.97454 |
285 | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | Design Supply Air Flow Rate [ft3/min] | 361.75843 |
286 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 358.41097 |
287 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.79624 |
288 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
289 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 358.41097 |
290 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 358.41097 |
291 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 358.41097 |
292 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 17204.08849 |
293 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.79624 |
294 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
295 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 358.41097 |
296 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17204.08849 |
297 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 184.78091 |
298 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.41050 |
299 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
300 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 184.78091 |
301 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 184.78091 |
302 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 184.78091 |
303 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 13880.28156 |
304 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.41050 |
305 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
306 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 184.78091 |
307 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 13880.28156 |
308 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 282.94488 |
309 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.62857 |
310 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
311 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 282.94488 |
312 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 282.94488 |
313 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 282.94488 |
314 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 17198.18481 |
315 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.62857 |
316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
317 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 282.94488 |
318 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17198.18481 |
319 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 318.98301 |
320 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.70863 |
321 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
322 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 318.98301 |
323 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 318.98301 |
324 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 318.98301 |
325 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 17205.67067 |
326 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.70863 |
327 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
328 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 318.98301 |
329 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17205.67067 |
330 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 156.57816 |
331 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.34785 |
332 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
333 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 156.57816 |
334 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 156.57816 |
335 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 156.57816 |
336 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 13879.41197 |
337 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.34785 |
338 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
339 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 156.57816 |
340 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 13879.41197 |
341 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 234.21607 |
342 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.52032 |
343 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
344 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 234.21607 |
345 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 234.21607 |
346 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 234.21607 |
347 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 17194.92471 |
348 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.52032 |
349 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
350 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 234.21607 |
351 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 17194.92471 |
352 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 422.83893 |
353 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.93937 |
354 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
355 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 422.83893 |
356 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 422.83893 |
357 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 422.83893 |
358 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 14899.34387 |
359 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.93937 |
360 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
361 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 422.83893 |
362 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 14899.34387 |
363 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 226.84319 |
364 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.50395 |
365 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
366 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 226.84319 |
367 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 226.84319 |
368 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 226.84319 |
369 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11365.61760 |
370 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.50395 |
371 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
372 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 226.84319 |
373 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11365.61760 |
374 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 339.42792 |
375 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.75409 |
376 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
377 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 339.42792 |
378 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 339.42792 |
379 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 339.42792 |
380 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 14891.32632 |
381 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.75409 |
382 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
383 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 339.42792 |
384 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 14891.32632 |
385 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 374.30080 |
386 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.83152 |
387 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
388 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 374.30080 |
389 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 374.30080 |
390 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 374.30080 |
391 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 14900.79909 |
392 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.83152 |
393 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 374.30080 |
395 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 14900.79909 |
396 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 167.21333 |
397 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.37148 |
398 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
399 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 167.21333 |
400 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 167.21333 |
401 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 167.21333 |
402 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 11364.50290 |
403 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.37148 |
404 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
405 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 167.21333 |
406 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 11364.50290 |
407 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 286.03810 |
408 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.63547 |
409 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
410 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 286.03810 |
411 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 286.03810 |
412 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 286.03810 |
413 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 14887.71734 |
414 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.63547 |
415 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
416 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 286.03810 |
417 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 14887.71734 |
418 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 436.35588 |
419 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.96939 |
420 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
421 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 436.35588 |
422 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 436.35588 |
423 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 436.35588 |
424 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 19929.06089 |
425 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.96939 |
426 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
427 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 436.35588 |
428 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 19929.06089 |
429 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 234.25844 |
430 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.52042 |
431 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
432 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 234.25844 |
433 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 234.25844 |
434 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 234.25844 |
435 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 16379.84909 |
436 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.52042 |
437 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
438 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 234.25844 |
439 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 16379.84909 |
440 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 333.17792 |
441 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.74018 |
442 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
443 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 333.17792 |
444 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 333.17792 |
445 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 333.17792 |
446 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 19919.42513 |
447 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.74018 |
448 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
449 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 333.17792 |
450 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 19919.42513 |
451 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 404.34317 |
452 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.89829 |
453 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
454 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 404.34317 |
455 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 404.34317 |
456 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 404.34317 |
457 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 19928.68148 |
458 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.89829 |
459 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
460 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 404.34317 |
461 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 19928.68148 |
462 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 203.45315 |
463 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.45199 |
464 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
465 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 203.45315 |
466 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 203.45315 |
467 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 203.45315 |
468 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 16377.62197 |
469 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.45199 |
470 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
471 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 203.45315 |
472 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 16377.62197 |
473 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 280.97454 |
474 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.62422 |
475 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
476 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 280.97454 |
477 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 280.97454 |
478 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 280.97454 |
479 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 19915.36461 |
480 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.62422 |
481 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
482 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 280.97454 |
483 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 19915.36461 |
484 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Rated Air Flow Rate [ft3/min] | 361.75843 |
485 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Total Cooling Capacity [ton] | 0.92074 |
486 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | Design Size Gross Rated Sensible Heat Ratio | 0.79791 |
487 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate [ft3/min] | 361.75843 |
488 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Heating Operation [ft3/min] | 361.75843 |
489 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Supply Air Flow Rate During Cooling Operation [ft3/min] | 361.75843 |
490 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Nominal Heating Capacity [Btu/h] | 24812.60047 |
491 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Nominal Cooling Capacity [ton] | 0.92074 |
492 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNITHEATEDBSMT | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
493 | Fan:OnOff | SUPPLY FAN_UNITHEATEDBSMT | Design Size Maximum Flow Rate [ft3/min] | 361.75843 |
494 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | Design Size Nominal Capacity [Btu/h] | 24812.60047 |
495 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
496 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
497 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
498 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
499 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
500 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
501 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
502 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
503 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
504 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
505 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
506 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
507 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
508 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
509 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
510 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
511 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
512 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
513 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
514 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
515 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
516 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
517 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
518 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
519 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
520 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
521 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
522 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
523 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
524 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
525 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
526 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
527 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
528 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
529 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
530 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
531 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
532 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
533 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
534 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
535 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
536 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
537 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
538 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
539 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
540 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
541 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
542 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
543 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
544 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
545 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
546 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
547 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
548 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
549 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
550 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
551 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
552 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
553 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
554 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
555 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
556 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
557 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
558 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
559 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
560 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
561 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
562 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
563 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
564 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
565 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
566 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
567 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
568 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
569 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
570 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
571 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
572 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
573 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
574 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
575 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
576 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
577 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
578 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
579 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
580 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
581 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
582 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
583 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
584 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 |
19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNITHEATEDBSMT | 0.9 | 3.28 | 11.18 | 11.85 | 11.40 | 11.54 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 01/21 | 01/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 6 |
2 | 6 |
3 | 6 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | -43.4 | 0.00 | DefaultMultipliers | Wetbulb | -41.90 | {C} | 14. | 20 | 59.1 | 0.00 | No | No |
2 | 81.32 | 10.20 | DefaultMultipliers | Wetbulb | 16.10 | {C} | 14. | 180 | 610.3 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 21 | 1229.0 | 0.1415 | 5.7310E-002 | 1.0 | -11.15 | -20. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | HEATEDBSMT | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.002465987 | 0.002281260 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000001574 | 0.000000781 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006963604 | 0.013694840 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009667391 | 0.018977932 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006967120 | 0.013701991 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006962838 | 0.013693413 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009668634 | 0.018980505 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006969151 | 0.013706123 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.008874097 | 0.016576654 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.014390532 | 0.026973691 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.008881854 | 0.016591598 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.008872958 | 0.016574559 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.014393921 | 0.026980150 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.008885515 | 0.016598612 | Pass | Pass |
15 | ATTIC | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000074523 | 0.000063668 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.005806710 | 0.010222082 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.005804994 | 0.010218942 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.005801081 | 0.010211818 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.007689974 | 0.013504883 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.007688244 | 0.013501701 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.005801348 | 0.010212367 | Pass | Pass |
22 | HEATEDBSMT | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.019704314 | 0.017253325 | Pass | Pass | 1.173279419 | 4.809825743 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.314976984 | 0.170368112 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.002198518 | 0.006821454 | Pass | Pass | 0.148225150 | 0.110959429 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.003196962 | 0.009497318 | Pass | Pass | 0.118376888 | 0.105972421 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.002958827 | 0.012102007 | Pass | Pass | 0.123485489 | 0.131221012 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000088034 | 0.000382929 | Pass | Pass | 0.144450087 | 0.106478399 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000053467 | 0.000366867 | Pass | Pass | 0.098116414 | 0.105683045 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.002543112 | 0.010644669 | Pass | Pass | 0.123606056 | 0.127286537 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000098289 | 0.000397032 | Pass | Pass | 0.104388462 | 0.062616059 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.001846955 | 0.006472956 | Pass | Pass | 0.074939495 | 0.060438339 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000090101 | 0.000389467 | Pass | Pass | 0.090563870 | 0.065123231 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000087195 | 0.000382294 | Pass | Pass | 0.093630058 | 0.067137851 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000064475 | 0.000367424 | Pass | Pass | 0.057307275 | 0.061214683 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000090300 | 0.000390868 | Pass | Pass | 0.089229507 | 0.071934644 | Pass | Pass |
36 | ATTIC | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.468464773 | 0.284353440 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000074527 | 0.000367568 | Pass | Pass | 0.083527212 | 0.071954774 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000090644 | 0.000385872 | Pass | Pass | 0.086881130 | 0.065658779 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000099740 | 0.000400152 | Pass | Pass | 0.106306937 | 0.062430962 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000065134 | 0.000364363 | Pass | Pass | 0.062985242 | 0.057253053 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.001469383 | 0.005279156 | Pass | Pass | 0.076773299 | 0.062010632 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 0.000088908 | 0.000385253 | Pass | Pass | 0.096006770 | 0.064760864 | Pass | Pass |
43 | HEATEDBSMT | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.003113976 | 0.002536163 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.032930517 | 0.022659476 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.018418145 | 0.027144707 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.024463577 | 0.040932997 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.019301225 | 0.028227187 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017757073 | 0.026452788 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.023573105 | 0.040230162 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.018438800 | 0.026615050 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.018657812 | 0.033651190 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.032791346 | 0.063546324 | Pass | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.019562336 | 0.034655088 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017719735 | 0.032962203 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.031094063 | 0.062399059 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.018489619 | 0.033094940 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.091530154 | 0.081808707 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.014117153 | 0.019753250 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.014464048 | 0.020518518 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.013894892 | 0.019965289 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017044174 | 0.028219521 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.017377038 | 0.028507454 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000000 | 0.000000000 | Pass | Pass | 0.013654284 | 0.019682122 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 1412232.88 | 233666.07 | 0.00 | 0.00 | 83293.93 | 1729196.51 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -43.4 | 0.00 | -43.4 | Wetbulb [F] | 59.06 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 81.32 | 18.36 | 60.98 | Wetbulb [F] | 610.27 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.063 | 0.066 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.048 | 0.050 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.062 | 0.066 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.212 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.205 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.300 | 0.335 | 0.883 | ||||||||||||
North Total or Average | 531.68 | 0.300 | 0.335 | 0.883 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.300 | 0.335 | 0.883 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.99 | 0.00 | 0.99 | 0.98 | 0.00 | 0.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.98 | 0.99 | 0.99 | 0.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4397 | 1200.55 | 527.92 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 475.00 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3110 | 43219.92 | 13441.11 | 12093.82 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 69.87 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 306.04 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1257.69 | 5508.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9554.88 | 7650.17 | 1904.72 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4926.06 | 3944.07 | 981.98 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7542.84 | 6039.22 | 1503.63 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8503.57 | 6808.43 | 1695.14 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4174.20 | 3342.09 | 832.10 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6243.87 | 4999.19 | 1244.68 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11272.42 | 9025.32 | 2247.10 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6047.45 | 4841.93 | 1205.53 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9049.04 | 7245.16 | 1803.88 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9978.29 | 7989.17 | 1989.12 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4457.72 | 3569.10 | 888.62 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7625.70 | 6105.56 | 1520.14 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11632.67 | 9313.76 | 2318.91 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6245.07 | 5000.14 | 1244.92 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8882.12 | 7111.51 | 1770.60 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10779.43 | 8630.61 | 2148.82 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 5423.84 | 4342.63 | 1081.21 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7490.67 | 5997.44 | 1493.22 | 0.80 | 3.97 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 11048.93 | 8816.07 | 2232.86 | 0.80 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.4 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.09 | 11.07 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.9 | 3.28 | 11.18 | 11.85 | 11.40 | 11.54 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 17204.09 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 13880.28 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 17198.18 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 17205.67 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 13879.41 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 17194.92 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 14899.34 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 11365.62 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 14891.33 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 14900.80 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 11364.50 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 14887.72 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 19929.06 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 16379.85 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 19919.43 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 19928.68 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 16377.62 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 19915.36 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Electric | 24812.60 | 1.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
OASUPPLYFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNITHEATEDBSMT | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 0.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 358.41 | 179.49 | 0.50 | 1.00 | 1.89 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 184.78 | 92.54 | 0.50 | 1.00 | 2.80 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 282.94 | 141.69 | 0.50 | 1.00 | 2.15 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 318.98 | 159.74 | 0.50 | 1.00 | 2.01 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 156.58 | 78.41 | 0.50 | 1.00 | 3.13 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 234.21 | 117.29 | 0.50 | 1.00 | 2.41 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 422.84 | 211.76 | 0.50 | 1.00 | 1.74 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 226.85 | 113.60 | 0.50 | 1.00 | 2.45 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 339.44 | 169.99 | 0.50 | 1.00 | 1.95 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 374.29 | 187.45 | 0.50 | 1.00 | 1.85 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 167.21 | 83.74 | 0.50 | 1.00 | 2.99 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 286.05 | 143.25 | 0.50 | 1.00 | 2.14 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 436.35 | 218.52 | 0.50 | 1.00 | 1.72 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 234.26 | 117.32 | 0.50 | 1.00 | 2.40 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 333.18 | 166.85 | 0.50 | 1.00 | 1.97 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 404.35 | 202.50 | 0.50 | 1.00 | 1.78 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 203.45 | 101.89 | 0.50 | 1.00 | 2.63 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 280.98 | 140.71 | 0.50 | 1.00 | 2.16 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.38 | 0.06 | 361.76 | 181.17 | 0.50 | 1.00 | 1.88 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.97 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8296.56 | 8296.56 | 6.91 | 358.412 | 358.412 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 75.00 | 75.00 | 0.00835 | 76.00 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4277.34 | 4277.34 | 3.56 | 184.781 | 184.781 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 75.00 | 75.00 | 0.00830 | 81.32 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6549.60 | 6549.60 | 5.46 | 282.939 | 282.939 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 75.00 | 75.00 | 0.00823 | 77.40 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7383.65 | 7383.65 | 6.15 | 318.977 | 318.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00842 | 74.16 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2969.15 | 2969.15 | 2.47 | 128.269 | 128.269 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 75.00 | 75.00 | 0.00880 | 70.49 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5421.64 | 5421.64 | 4.52 | 234.213 | 234.213 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 75.00 | 75.00 | 0.00829 | 73.30 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9787.83 | 9787.83 | 8.15 | 422.839 | 422.839 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00836 | 74.62 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5251.04 | 5251.04 | 4.37 | 226.846 | 226.846 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 75.00 | 75.00 | 0.00829 | 80.95 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7857.44 | 7857.44 | 6.54 | 339.438 | 339.438 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 75.00 | 75.00 | 0.00823 | 78.02 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8664.11 | 8664.11 | 7.22 | 374.295 | 374.295 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 75.00 | 75.00 | 0.00838 | 72.81 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3870.63 | 3870.63 | 3.22 | 167.213 | 167.213 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 75.00 | 75.00 | 0.00869 | 69.94 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6621.51 | 6621.51 | 5.52 | 286.047 | 286.047 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 75.00 | 75.00 | 0.00826 | 74.80 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6504.28 | 6504.28 | 5.42 | 280.982 | 280.982 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.00 | 75.00 | 0.00823 | 75.26 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7712.52 | 7712.52 | 6.42 | 333.176 | 333.176 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 75.00 | 75.00 | 0.00821 | 78.02 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10100.65 | 10100.65 | 8.41 | 436.352 | 436.352 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00834 | 74.16 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4587.90 | 4587.90 | 3.82 | 198.199 | 198.199 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 75.00 | 75.00 | 0.00854 | 70.21 | 0.00700 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5422.67 | 5422.67 | 4.52 | 234.258 | 234.258 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 75.00 | 75.00 | 0.00825 | 80.77 | 0.00701 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9359.76 | 9359.76 | 7.80 | 404.346 | 404.346 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 75.00 | 75.00 | 0.00834 | 73.15 | 0.00700 | 44.995 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 72.85 | 75.00 | 0.00731 | 81.32 | 0.00701 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 11842.04 | 11842.04 | 9.86 | 218.957 | 218.957 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8469.06 | 8469.06 | 7.05 | 156.594 | 156.594 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00680 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11836.05 | 11836.05 | 9.86 | 218.846 | 218.846 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11843.65 | 11843.65 | 9.87 | 218.987 | 218.987 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8468.18 | 8468.18 | 7.05 | 156.578 | 156.578 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00680 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11832.75 | 11832.75 | 9.86 | 218.785 | 218.785 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00696 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9503.01 | 9503.01 | 7.92 | 175.725 | 175.725 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5917.00 | 5917.00 | 4.93 | 109.416 | 109.416 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00756 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9494.88 | 9494.88 | 7.91 | 175.574 | 175.574 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9504.49 | 9504.49 | 7.92 | 175.752 | 175.752 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5915.87 | 5915.87 | 4.93 | 109.396 | 109.396 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00756 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9491.21 | 9491.21 | 7.91 | 175.507 | 175.507 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00752 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 14593.39 | 14593.39 | 12.16 | 269.829 | 269.829 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 14597.51 | 14597.51 | 12.16 | 269.906 | 269.906 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 14607.29 | 14607.29 | 12.17 | 270.086 | 270.086 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 11003.31 | 11003.31 | 9.17 | 203.453 | 203.453 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00703 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 11005.57 | 11005.57 | 9.17 | 203.495 | 203.495 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00703 | -43.4 | 0.00006 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 14606.91 | 14606.91 | 12.17 | 270.079 | 270.079 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00713 | -43.4 | 0.00006 | 44.995 | 0.00 |
HEATEDBSMT | 19562.67 | 19562.67 | 2.51 | 361.762 | 361.762 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 72.00 | 72.00 | 0.00800 | -43.4 | 0.00006 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 358.41 | 358.41 | 218.96 | 218.96 | 358.4125 | 358.4125 | 358.4125 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 184.78 | 184.78 | 156.59 | 156.59 | 184.7810 | 184.7810 | 184.7810 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 282.94 | 282.94 | 218.85 | 218.85 | 282.9390 | 282.9390 | 282.9390 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 318.98 | 318.98 | 218.99 | 218.99 | 318.9770 | 318.9770 | 318.9770 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 128.27 | 128.27 | 156.58 | 156.58 | 156.5781 | 156.5781 | 156.5781 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 234.21 | 234.21 | 218.79 | 218.79 | 234.2133 | 234.2133 | 234.2133 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 422.84 | 422.84 | 175.72 | 175.72 | 422.8390 | 422.8390 | 422.8390 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 226.85 | 226.85 | 109.42 | 109.42 | 226.8456 | 226.8456 | 226.8456 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 339.44 | 339.44 | 175.57 | 175.57 | 339.4380 | 339.4380 | 339.4380 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 374.29 | 374.29 | 175.75 | 175.75 | 374.2949 | 374.2949 | 374.2949 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.21 | 167.21 | 109.40 | 109.40 | 167.2134 | 167.2134 | 167.2134 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.05 | 286.05 | 175.51 | 175.51 | 286.0470 | 286.0470 | 286.0470 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 436.35 | 436.35 | 270.09 | 270.09 | 436.3522 | 436.3522 | 436.3522 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 234.26 | 234.26 | 203.50 | 203.50 | 234.2582 | 234.2582 | 234.2582 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.18 | 333.18 | 269.91 | 269.91 | 333.1764 | 333.1764 | 333.1764 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 404.35 | 404.35 | 270.08 | 270.08 | 404.3465 | 404.3465 | 404.3465 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 198.20 | 198.20 | 203.45 | 203.45 | 203.4532 | 203.4532 | 203.4532 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 280.98 | 280.98 | 269.83 | 269.83 | 280.9818 | 280.9818 | 280.9818 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.99 | 361.76 | 361.76 | 361.7620 | 361.7620 | 361.7620 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 9554.882 | 7650.167 | 358.412456 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 9323.78 | 9039.26 | 358.412456 | 76.70 | 61.25 | 0.00818111 | 53.60 | 52.02 | 0.00800000 | 76.00 | 0.00700266 | 59.13 | 12.5540 | 75.00 | 0.00832747 | 44.4391 | 8279.99 | 0.00 | 9558.87 | 7581.62 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 17204.089 | 17204.089 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17204.09 | 17204.09 | 358.412456 | 57.50 | 50.11 | 0.00609790 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.5540 | 71.99 | 0.00696407 | 41.2048 | 11842.04 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 4926.058 | 3944.074 | 184.780977 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 4931.50 | 4931.50 | 184.780977 | 78.12 | 61.45 | 0.00798360 | 53.60 | 51.99 | 0.00798360 | 81.32 | 0.00700714 | 61.07 | 24.3504 | 75.00 | 0.00829791 | 44.2833 | 4277.34 | 0.00 | 4928.11 | 3908.74 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 13880.282 | 13880.282 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 13880.28 | 13880.28 | 184.780977 | 43.89 | 41.73 | 0.00515763 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 24.3504 | 71.99 | 0.00679703 | 40.2258 | 8469.06 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 7542.842 | 6039.216 | 282.938955 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 7426.28 | 7385.17 | 282.938955 | 76.96 | 61.11 | 0.00803234 | 53.60 | 52.02 | 0.00800000 | 77.40 | 0.00700385 | 59.65 | 15.9027 | 75.00 | 0.00822627 | 43.9056 | 6548.70 | 0.00 | 7545.99 | 5985.11 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 17198.185 | 17198.185 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17198.18 | 17198.18 | 282.938955 | 53.64 | 47.92 | 0.00586648 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.9027 | 71.99 | 0.00696363 | 41.2022 | 11836.05 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 8503.575 | 6808.432 | 318.976950 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8223.07 | 7919.32 | 318.976950 | 76.46 | 61.22 | 0.00821865 | 53.60 | 52.02 | 0.00800000 | 74.16 | 0.00700114 | 58.45 | 14.1060 | 75.00 | 0.00841859 | 44.9192 | 7383.65 | 0.00 | 8507.12 | 6747.43 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 17205.671 | 17205.671 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17205.67 | 17205.67 | 318.976950 | 55.71 | 49.11 | 0.00599092 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 14.1060 | 71.99 | 0.00696419 | 41.2055 | 11843.65 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 4174.199 | 3342.094 | 156.578057 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 3991.31 | 3870.89 | 156.578057 | 75.00 | 60.62 | 0.00816730 | 53.60 | 52.02 | 0.00800000 | 70.49 | 0.00699811 | 57.06 | 28.7365 | 75.00 | 0.00881098 | 46.9835 | 2956.39 | 0.00 | 4175.94 | 3312.15 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 13879.412 | 13879.412 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 13879.41 | 13879.41 | 156.578057 | 38.83 | 38.41 | 0.00486227 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 28.7365 | 71.99 | 0.00679693 | 40.2252 | 8468.18 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 6243.868 | 4999.186 | 234.213255 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 6036.67 | 5991.94 | 234.213255 | 76.25 | 60.88 | 0.00804222 | 53.60 | 52.02 | 0.00800000 | 73.30 | 0.00700043 | 58.13 | 19.2111 | 75.00 | 0.00826948 | 44.1332 | 5373.48 | 0.00 | 6246.47 | 4954.40 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 17194.925 | 17194.925 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 17194.92 | 17194.92 | 234.213255 | 49.82 | 45.68 | 0.00563803 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.2111 | 71.99 | 0.00696338 | 41.2008 | 11832.75 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11272.422 | 9025.324 | 422.838975 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 10923.06 | 10525.74 | 422.838975 | 76.54 | 61.25 | 0.00821583 | 53.60 | 52.02 | 0.00800000 | 74.62 | 0.00700152 | 58.62 | 10.6412 | 75.00 | 0.00834831 | 44.5492 | 9760.51 | 0.00 | 11277.13 | 8944.46 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 14899.344 | 14899.344 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14899.34 | 14899.34 | 422.838975 | 59.72 | 52.25 | 0.00672998 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.6412 | 72.00 | 0.00752373 | 44.4698 | 9503.01 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6047.454 | 4841.926 | 226.845592 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 6045.44 | 6008.38 | 226.845592 | 77.76 | 61.40 | 0.00803693 | 53.60 | 52.02 | 0.00800000 | 80.95 | 0.00700683 | 60.93 | 19.8351 | 75.00 | 0.00829168 | 44.2506 | 5249.12 | 0.00 | 6049.98 | 4798.54 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 11365.618 | 11365.618 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11365.62 | 11365.62 | 226.845592 | 49.11 | 46.24 | 0.00607136 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.8351 | 72.00 | 0.00755762 | 44.6661 | 5917.00 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 9049.043 | 7245.164 | 339.437969 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 8931.62 | 8832.80 | 339.437969 | 76.98 | 61.17 | 0.00806505 | 53.60 | 52.02 | 0.00800000 | 78.02 | 0.00700436 | 59.88 | 13.2557 | 75.00 | 0.00822745 | 43.9119 | 7849.41 | 0.00 | 9052.82 | 7180.25 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 14891.326 | 14891.326 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14891.33 | 14891.33 | 339.437969 | 56.70 | 50.59 | 0.00653464 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.2557 | 72.00 | 0.00752336 | 44.4676 | 9494.88 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 9978.290 | 7989.170 | 374.294879 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | 9590.80 | 9246.31 | 374.294879 | 76.32 | 61.16 | 0.00821120 | 53.60 | 52.02 | 0.00800000 | 72.81 | 0.00700003 | 57.94 | 12.0213 | 75.00 | 0.00839174 | 44.7779 | 8644.15 | 0.00 | 9982.45 | 7917.59 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 14900.799 | 14900.799 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14900.80 | 14900.80 | 374.294879 | 58.12 | 51.38 | 0.00662710 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.0213 | 72.00 | 0.00752380 | 44.4702 | 9504.49 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 4457.725 | 3569.101 | 167.213366 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | 4241.59 | 4065.53 | 167.213366 | 75.22 | 60.81 | 0.00823500 | 53.60 | 52.02 | 0.00800000 | 69.94 | 0.00699765 | 56.84 | 26.9087 | 75.00 | 0.00869664 | 46.3823 | 3865.48 | 0.00 | 4459.58 | 3537.12 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 11364.503 | 11364.503 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 11364.50 | 11364.50 | 167.213366 | 40.94 | 40.94 | 0.00554126 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 26.9087 | 72.00 | 0.00755755 | 44.6657 | 5915.87 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 7625.699 | 6105.556 | 286.046999 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 7416.84 | 7335.90 | 286.046999 | 76.55 | 61.01 | 0.00806312 | 53.60 | 52.02 | 0.00800000 | 74.80 | 0.00700167 | 58.69 | 15.7299 | 75.00 | 0.00825781 | 44.0718 | 6613.67 | 0.00 | 7628.88 | 6050.85 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 14887.717 | 14887.717 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 14887.72 | 14887.72 | 286.046999 | 53.84 | 48.98 | 0.00634995 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 15.7299 | 72.00 | 0.00752320 | 44.4667 | 9491.21 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 11632.670 | 9313.759 | 436.352216 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 11251.22 | 10869.38 | 436.352216 | 76.49 | 61.21 | 0.00820051 | 53.60 | 52.02 | 0.00800000 | 74.16 | 0.00700114 | 58.45 | 10.3116 | 75.00 | 0.00833031 | 44.4543 | 10085.35 | 0.00 | 11637.52 | 9230.31 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 19929.061 | 19929.061 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 19929.06 | 19929.06 | 436.352216 | 60.09 | 51.81 | 0.00640543 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 10.3116 | 71.99 | 0.00713446 | 42.2015 | 14607.29 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6245.066 | 5000.145 | 234.258189 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 6241.64 | 6229.80 | 234.258189 | 77.69 | 61.34 | 0.00801135 | 53.60 | 52.02 | 0.00800000 | 80.77 | 0.00700668 | 60.87 | 19.2074 | 75.00 | 0.00824866 | 44.0238 | 5418.90 | 0.00 | 6247.67 | 4955.35 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 16379.849 | 16379.849 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 16379.85 | 16379.85 | 234.258189 | 49.83 | 45.80 | 0.00569431 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 19.2074 | 71.99 | 0.00703273 | 41.6051 | 11005.57 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 8882.116 | 7111.513 | 333.176376 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 8769.81 | 8702.98 | 333.176376 | 76.99 | 61.14 | 0.00804467 | 53.60 | 52.02 | 0.00800000 | 78.02 | 0.00700436 | 59.88 | 13.5049 | 75.00 | 0.00820718 | 43.8050 | 7712.02 | 0.00 | 8885.82 | 7047.80 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 19919.425 | 19919.425 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 19919.43 | 19919.43 | 333.176376 | 56.41 | 49.78 | 0.00617924 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 13.5049 | 71.99 | 0.00713396 | 42.1985 | 14597.51 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 10779.432 | 8630.609 | 404.346462 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 10379.72 | 10041.04 | 404.346462 | 76.37 | 61.15 | 0.00819163 | 53.60 | 52.02 | 0.00800000 | 73.15 | 0.00700030 | 58.07 | 11.1278 | 75.00 | 0.00834954 | 44.5556 | 9347.33 | 0.00 | 10783.93 | 8553.28 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 19928.681 | 19928.681 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 19928.68 | 19928.68 | 404.346462 | 59.15 | 51.30 | 0.00634771 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 11.1278 | 71.99 | 0.00713444 | 42.2013 | 14606.91 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 5423.839 | 4342.625 | 203.453218 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 5166.18 | 4993.69 | 203.453218 | 75.49 | 60.83 | 0.00818955 | 53.60 | 52.02 | 0.00800000 | 70.21 | 0.00699788 | 56.95 | 22.1156 | 75.00 | 0.00854550 | 45.5870 | 4579.69 | 0.00 | 5426.10 | 4303.72 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 16377.622 | 16377.622 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 16377.62 | 16377.62 | 203.453218 | 46.47 | 43.75 | 0.00549153 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 22.1156 | 71.99 | 0.00703256 | 41.6041 | 11003.31 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 7490.666 | 5997.441 | 280.981813 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 7303.97 | 7258.42 | 280.981813 | 76.62 | 61.00 | 0.00803599 | 53.60 | 52.02 | 0.00800000 | 75.26 | 0.00700206 | 58.86 | 16.0135 | 75.00 | 0.00823084 | 43.9297 | 6491.24 | 0.00 | 7493.79 | 5943.71 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 19915.365 | 19915.365 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 19915.36 | 19915.36 | 280.981813 | 53.51 | 48.14 | 0.00600171 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 16.0135 | 71.99 | 0.00713374 | 42.1973 | 14593.39 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 11048.932 | 8816.073 | 361.761957 | -999. | -999.00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11037.83 | 11037.83 | 361.761957 | 82.90 | 61.62 | 0.00700714 | 53.60 | 50.15 | 0.00700714 | 81.32 | 0.00700714 | 61.07 | 12.4377 | 72.85 | 0.00731053 | 41.9922 | 0.00 | 0.00 | 11053.54 | 8740.83 |
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | 24812.600 | 24812.600 | -999. | -999. | -999.00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | 24812.60 | 24812.60 | 361.761957 | 57.64 | 51.90 | 0.00701300 | 122.00 | 74.82 | 0.00800000 | -43.4 | 0.00006450 | -43.4 | 12.4377 | 72.00 | 0.00800000 | 47.2448 | 19562.67 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9554.882 | 7650.167 | 358.412456 | -999. | -999.00 | -999.0000 | 1.08252 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 358.412456 | 0.44211400 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | Sensible | 9323.78 | 9039.26 | 1.0248 | 0.44211400 | 358.412456 | 76.70 | 61.25 | 0.00818111 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 612.425 | 8711.35 | 76.00 | 0.00700266 | 59.13 | 44.99498340 | 12.5540 | 75.00 | 0.00835030 | 75.00 | 0.00832747 | 44.4391 | 8279.99 | 0.00 | 9558.87 | 7581.62 | 0.42465384 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17204.089 | 17204.089 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 358.412456 | 0.44211400 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17204.09 | 17204.09 | 1.0000 | 0.44211400 | 358.412456 | 57.50 | 50.11 | 0.00609790 | 7.1 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17204.09 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.5540 | 71.99 | 0.00696407 | 71.99 | 0.00696407 | 41.2048 | 11842.04 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4926.058 | 3944.074 | 184.780977 | -999. | -999.00 | -999.0000 | 1.03165 | 1.00000 | 0.2435 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 184.780977 | 0.22793364 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 4931.50 | 4931.50 | 0.9989 | 0.22793364 | 184.780977 | 78.12 | 61.45 | 0.00798360 | 11.0 | 53.60 | 51.99 | 0.00798360 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 315.738 | 4615.76 | 81.32 | 0.00700714 | 61.07 | 44.99498340 | 24.3504 | 75.00 | 0.00829791 | 75.00 | 0.00829791 | 44.2833 | 4277.34 | 0.00 | 4928.11 | 3908.74 | 0.21893199 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13880.282 | 13880.282 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 184.780977 | 0.22793364 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 13880.28 | 13880.28 | 1.0000 | 0.22793364 | 184.780977 | 43.89 | 41.73 | 0.00515763 | 4.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 13880.28 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 24.3504 | 71.99 | 0.00679703 | 71.99 | 0.00679703 | 40.2258 | 8469.06 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7542.842 | 6039.216 | 282.938955 | -999. | -999.00 | -999.0000 | 1.09189 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 282.938955 | 0.34901486 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | Sensible | 7426.28 | 7385.17 | 1.0157 | 0.34901486 | 282.938955 | 76.96 | 61.11 | 0.00803234 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 483.462 | 6942.82 | 77.40 | 0.00700385 | 59.65 | 44.99498340 | 15.9027 | 75.00 | 0.00822683 | 75.00 | 0.00822627 | 43.9056 | 6548.70 | 0.00 | 7545.99 | 5985.11 | 0.33523141 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17198.185 | 17198.185 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 282.938955 | 0.34901486 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17198.18 | 17198.18 | 1.0000 | 0.34901486 | 282.938955 | 53.64 | 47.92 | 0.00586648 | 6.4 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17198.18 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.9027 | 71.99 | 0.00696363 | 71.99 | 0.00696363 | 41.2022 | 11836.05 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8503.575 | 6808.432 | 318.976950 | -999. | -999.00 | -999.0000 | 1.09540 | 1.00000 | 0.2437 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 318.976950 | 0.39346896 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8223.07 | 7919.32 | 1.0341 | 0.39346896 | 318.976950 | 76.46 | 61.22 | 0.00821865 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 545.041 | 7678.03 | 74.16 | 0.00700114 | 58.45 | 44.99498340 | 14.1060 | 75.00 | 0.00841859 | 75.00 | 0.00841859 | 44.9192 | 7383.65 | 0.00 | 8507.12 | 6747.43 | 0.37792991 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17205.671 | 17205.671 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 318.976950 | 0.39346896 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17205.67 | 17205.67 | 1.0000 | 0.39346896 | 318.976950 | 55.71 | 49.11 | 0.00599092 | 6.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17205.67 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 14.1060 | 71.99 | 0.00696419 | 71.99 | 0.00696419 | 41.2055 | 11843.65 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4174.199 | 3342.094 | 156.578057 | -999. | -999.00 | -999.0000 | 1.18933 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 156.578057 | 0.19314438 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | Sensible | 3991.31 | 3870.89 | 1.0458 | 0.19314438 | 156.578057 | 75.00 | 60.62 | 0.00816730 | 10.7 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 267.547 | 3723.76 | 70.49 | 0.00699811 | 57.06 | 44.99498340 | 28.7365 | 75.00 | 0.00879905 | 75.00 | 0.00881098 | 46.9835 | 2956.39 | 0.00 | 4175.94 | 3312.15 | 0.18551664 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13879.412 | 13879.412 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 156.578057 | 0.19314438 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 13879.41 | 13879.41 | 1.0000 | 0.19314438 | 156.578057 | 38.83 | 38.41 | 0.00486227 | 3.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 13879.41 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 28.7365 | 71.99 | 0.00679693 | 71.99 | 0.00679693 | 40.2252 | 8468.18 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6243.868 | 4999.186 | 234.213255 | -999. | -999.00 | -999.0000 | 1.14279 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 234.213255 | 0.28891005 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | Sensible | 6036.67 | 5991.94 | 1.0343 | 0.28891005 | 234.213255 | 76.25 | 60.88 | 0.00804222 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 400.204 | 5636.47 | 73.30 | 0.00700043 | 58.13 | 44.99498340 | 19.2111 | 75.00 | 0.00828995 | 75.00 | 0.00826948 | 44.1332 | 5373.48 | 0.00 | 6246.47 | 4954.40 | 0.27750028 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17194.925 | 17194.925 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 234.213255 | 0.28891005 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 17194.92 | 17194.92 | 1.0000 | 0.28891005 | 234.213255 | 49.82 | 45.68 | 0.00563803 | 5.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17194.92 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.2111 | 71.99 | 0.00696338 | 71.99 | 0.00696338 | 41.2008 | 11832.75 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11272.422 | 9025.324 | 422.838975 | -999. | -999.00 | -999.0000 | 1.09031 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 422.838975 | 0.52158631 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 10923.06 | 10525.74 | 1.0320 | 0.52158631 | 422.838975 | 76.54 | 61.25 | 0.00821583 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 722.511 | 10200.55 | 74.62 | 0.00700152 | 58.62 | 44.99498340 | 10.6412 | 75.00 | 0.00836043 | 75.00 | 0.00834831 | 44.5492 | 9760.51 | 0.00 | 11277.13 | 8944.46 | 0.50098760 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14899.344 | 14899.344 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 422.838975 | 0.52158631 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14899.34 | 14899.34 | 1.0000 | 0.52158631 | 422.838975 | 59.72 | 52.25 | 0.00672998 | 7.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14899.34 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.6412 | 72.00 | 0.00752373 | 72.00 | 0.00752373 | 44.4698 | 9503.01 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6047.454 | 4841.926 | 226.845592 | -999. | -999.00 | -999.0000 | 1.04069 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 226.845592 | 0.27982178 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 6045.44 | 6008.38 | 1.0003 | 0.27982178 | 226.845592 | 77.76 | 61.40 | 0.00803693 | 11.0 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 387.615 | 5657.82 | 80.95 | 0.00700683 | 60.93 | 44.99498340 | 19.8351 | 75.00 | 0.00829180 | 75.00 | 0.00829168 | 44.2506 | 5249.12 | 0.00 | 6049.98 | 4798.54 | 0.26877094 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11365.618 | 11365.618 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 226.845592 | 0.27982178 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11365.62 | 11365.62 | 1.0000 | 0.27982178 | 226.845592 | 49.11 | 46.24 | 0.00607136 | 5.9 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11365.62 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.8351 | 72.00 | 0.00755762 | 72.00 | 0.00755762 | 44.6661 | 5917.00 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9049.043 | 7245.164 | 339.437969 | -999. | -999.00 | -999.0000 | 1.08169 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 339.437969 | 0.41870832 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | Sensible | 8931.62 | 8832.80 | 1.0131 | 0.41870832 | 339.437969 | 76.98 | 61.17 | 0.00806505 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 580.003 | 8351.62 | 78.02 | 0.00700436 | 59.88 | 44.99498340 | 13.2557 | 75.00 | 0.00822714 | 75.00 | 0.00822745 | 43.9119 | 7849.41 | 0.00 | 9052.82 | 7180.25 | 0.40217251 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14891.326 | 14891.326 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 339.437969 | 0.41870832 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14891.33 | 14891.33 | 1.0000 | 0.41870832 | 339.437969 | 56.70 | 50.59 | 0.00653464 | 7.2 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14891.33 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.2557 | 72.00 | 0.00752336 | 72.00 | 0.00752336 | 44.4676 | 9494.88 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 9978.290 | 7989.170 | 374.294879 | -999. | -999.00 | -999.0000 | 1.11005 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 374.294879 | 0.46170551 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:40:00 | Sensible | 9590.80 | 9246.31 | 1.0404 | 0.46170551 | 374.294879 | 76.32 | 61.16 | 0.00821120 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 639.563 | 8951.24 | 72.81 | 0.00700003 | 57.94 | 44.99498340 | 12.0213 | 75.00 | 0.00837670 | 75.00 | 0.00839174 | 44.7779 | 8644.15 | 0.00 | 9982.45 | 7917.59 | 0.44347164 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14900.799 | 14900.799 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 374.294879 | 0.46170551 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14900.80 | 14900.80 | 1.0000 | 0.46170551 | 374.294879 | 58.12 | 51.38 | 0.00662710 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14900.80 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.0213 | 72.00 | 0.00752380 | 72.00 | 0.00752380 | 44.4702 | 9504.49 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 4457.725 | 3569.101 | 167.213366 | -999. | -999.00 | -999.0000 | 1.16813 | 1.00000 | 0.2437 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 167.213366 | 0.20626340 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:20:00 | Sensible | 4241.59 | 4065.53 | 1.0510 | 0.20626340 | 167.213366 | 75.22 | 60.81 | 0.00823500 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 285.720 | 3955.87 | 69.94 | 0.00699765 | 56.84 | 44.99498340 | 26.9087 | 75.00 | 0.00869053 | 75.00 | 0.00869664 | 46.3823 | 3865.48 | 0.00 | 4459.58 | 3537.12 | 0.19811755 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11364.503 | 11364.503 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 167.213366 | 0.20626340 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 11364.50 | 11364.50 | 1.0000 | 0.20626340 | 167.213366 | 40.94 | 40.94 | 0.00554126 | 4.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 11364.50 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 26.9087 | 72.00 | 0.00755755 | 72.00 | 0.00755755 | 44.6657 | 5915.87 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7625.699 | 6105.556 | 286.046999 | -999. | -999.00 | -999.0000 | 1.11761 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 286.046999 | 0.35284874 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | Sensible | 7416.84 | 7335.90 | 1.0282 | 0.35284874 | 286.046999 | 76.55 | 61.01 | 0.00806312 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 488.773 | 6928.07 | 74.80 | 0.00700167 | 58.69 | 44.99498340 | 15.7299 | 75.00 | 0.00826124 | 75.00 | 0.00825781 | 44.0718 | 6613.67 | 0.00 | 7628.88 | 6050.85 | 0.33891388 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14887.717 | 14887.717 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 286.046999 | 0.35284874 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 14887.72 | 14887.72 | 1.0000 | 0.35284874 | 286.046999 | 53.84 | 48.98 | 0.00634995 | 6.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 14887.72 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 15.7299 | 72.00 | 0.00752320 | 72.00 | 0.00752320 | 44.4667 | 9491.21 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11632.670 | 9313.759 | 436.352216 | -999. | -999.00 | -999.0000 | 1.09749 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 436.352216 | 0.53825536 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 11251.22 | 10869.38 | 1.0339 | 0.53825536 | 436.352216 | 76.49 | 61.21 | 0.00820051 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 745.602 | 10505.62 | 74.16 | 0.00700114 | 58.45 | 44.99498340 | 10.3116 | 75.00 | 0.00833840 | 75.00 | 0.00833031 | 44.4543 | 10085.35 | 0.00 | 11637.52 | 9230.31 | 0.51699834 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19929.061 | 19929.061 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 436.352216 | 0.53825536 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 19929.06 | 19929.06 | 1.0000 | 0.53825536 | 436.352216 | 60.09 | 51.81 | 0.00640543 | 7.6 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19929.06 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 10.3116 | 71.99 | 0.00713446 | 71.99 | 0.00713446 | 42.2015 | 14607.29 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 6245.066 | 5000.145 | 234.258189 | -999. | -999.00 | -999.0000 | 1.04881 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 234.258189 | 0.28896547 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 6241.64 | 6229.80 | 1.0005 | 0.28896547 | 234.258189 | 77.69 | 61.34 | 0.00801135 | 11.0 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 400.281 | 5841.36 | 80.77 | 0.00700668 | 60.87 | 44.99498340 | 19.2074 | 75.00 | 0.00825020 | 75.00 | 0.00824866 | 44.0238 | 5418.90 | 0.00 | 6247.67 | 4955.35 | 0.27755352 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16379.849 | 16379.849 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 234.258189 | 0.28896547 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 16379.85 | 16379.85 | 1.0000 | 0.28896547 | 234.258189 | 49.83 | 45.80 | 0.00569431 | 5.8 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 16379.85 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 19.2074 | 71.99 | 0.00703273 | 71.99 | 0.00703273 | 41.6051 | 11005.57 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 8882.116 | 7111.513 | 333.176376 | -999. | -999.00 | -999.0000 | 1.08515 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 333.176376 | 0.41098444 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | Sensible | 8769.81 | 8702.98 | 1.0128 | 0.41098444 | 333.176376 | 76.99 | 61.14 | 0.00804467 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 569.304 | 8200.51 | 78.02 | 0.00700436 | 59.88 | 44.99498340 | 13.5049 | 75.00 | 0.00820710 | 75.00 | 0.00820718 | 43.8050 | 7712.02 | 0.00 | 8885.82 | 7047.80 | 0.39475366 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19919.425 | 19919.425 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 333.176376 | 0.41098444 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 19919.43 | 19919.43 | 1.0000 | 0.41098444 | 333.176376 | 56.41 | 49.78 | 0.00617924 | 7.0 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19919.43 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 13.5049 | 71.99 | 0.00713396 | 71.99 | 0.00713396 | 42.1985 | 14597.51 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 10779.432 | 8630.609 | 404.346462 | -999. | -999.00 | -999.0000 | 1.10955 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 404.346462 | 0.49877517 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 10379.72 | 10041.04 | 1.0385 | 0.49877517 | 404.346462 | 76.37 | 61.15 | 0.00819163 | 10.9 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 690.913 | 9688.80 | 73.15 | 0.00700030 | 58.07 | 44.99498340 | 11.1278 | 75.00 | 0.00834080 | 75.00 | 0.00834954 | 44.5556 | 9347.33 | 0.00 | 10783.93 | 8553.28 | 0.47907732 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19928.681 | 19928.681 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 404.346462 | 0.49877517 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 19928.68 | 19928.68 | 1.0000 | 0.49877517 | 404.346462 | 59.15 | 51.30 | 0.00634771 | 7.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19928.68 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 11.1278 | 71.99 | 0.00713444 | 71.99 | 0.00713444 | 42.2013 | 14606.91 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 5423.839 | 4342.625 | 203.453218 | -999. | -999.00 | -999.0000 | 1.16375 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 203.453218 | 0.25096649 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | Sensible | 5166.18 | 4993.69 | 1.0499 | 0.25096649 | 203.453218 | 75.49 | 60.83 | 0.00818955 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 347.644 | 4818.54 | 70.21 | 0.00699788 | 56.95 | 44.99498340 | 22.1156 | 75.00 | 0.00853953 | 75.00 | 0.00854550 | 45.5870 | 4579.69 | 0.00 | 5426.10 | 4303.72 | 0.24105521 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16377.622 | 16377.622 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 203.453218 | 0.25096649 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 16377.62 | 16377.62 | 1.0000 | 0.25096649 | 203.453218 | 46.47 | 43.75 | 0.00549153 | 5.2 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 16377.62 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 22.1156 | 71.99 | 0.00703256 | 71.99 | 0.00703256 | 41.6041 | 11003.31 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 7490.666 | 5997.441 | 280.981813 | -999. | -999.00 | -999.0000 | 1.11722 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 280.981813 | 0.34660066 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 7303.97 | 7258.42 | 1.0256 | 0.34660066 | 280.981813 | 76.62 | 61.00 | 0.00803599 | 10.8 | 53.60 | 52.02 | 0.00800000 | 7.7 | -999. | -999.0 | -999.0 | -999.0 | 480.118 | 6823.85 | 75.26 | 0.00700206 | 58.86 | 44.99498340 | 16.0135 | 75.00 | 0.00823313 | 75.00 | 0.00823084 | 43.9297 | 6491.24 | 0.00 | 7493.79 | 5943.71 | 0.33291255 | 80.00 | 67.00 | 0.01118466 | 13.2 | 59.71 | 58.22 | 0.01000511 | 9.7 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19915.365 | 19915.365 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 280.981813 | 0.34660066 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 19915.36 | 19915.36 | 1.0000 | 0.34660066 | 280.981813 | 53.51 | 48.14 | 0.00600171 | 6.5 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 19915.36 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 16.0135 | 71.99 | 0.00713374 | 71.99 | 0.00713374 | 42.1973 | 14593.39 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 11048.932 | 8816.073 | 361.761957 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0740 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 361.761957 | 0.44624573 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11037.83 | 11037.83 | 1.0010 | 0.44624573 | 361.761957 | 82.90 | 61.62 | 0.00700714 | 11.1 | 53.60 | 50.15 | 0.00700714 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 618.148 | 10419.68 | 81.32 | 0.00700714 | 61.07 | 44.99498340 | 12.4377 | 75.00 | 0.00731053 | 72.85 | 0.00731053 | 41.9922 | 0.00 | 0.00 | 11053.54 | 8740.83 | 0.42862239 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.82 | 56.79 | 0.00981775 | 9.2 | |
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNITHEATEDBSMT | HEATEDBSMT | Non-Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24812.600 | 24812.600 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0740 | SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 361.761957 | 0.44624573 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | Sensible | 24812.60 | 24812.60 | 1.0000 | 0.44624573 | 361.761957 | 57.64 | 51.90 | 0.00701300 | 7.7 | 122.00 | 74.82 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 24812.60 | -43.4 | 0.00006450 | -43.4 | 44.99498340 | 12.4377 | 72.00 | 0.00800000 | 72.00 | 0.00800000 | 47.2448 | 19562.67 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2757.00 | 7475.17 | 2360.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 928.17 | 7679.00 | 799.33 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2741.50 | 7256.33 | 2301.17 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2868.00 | 7773.50 | 2660.17 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1101.17 | 8005.00 | 1065.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2788.50 | 7516.33 | 2550.50 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2880.67 | 6937.00 | 2208.83 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 939.33 | 6934.17 | 527.17 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2955.67 | 6614.00 | 2153.67 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2971.00 | 7210.67 | 2532.83 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 891.00 | 7229.83 | 751.50 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2974.50 | 6960.00 | 2422.17 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3813.33 | 7053.67 | 3217.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3728.17 | 6819.00 | 2954.67 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3685.83 | 7088.67 | 3042.33 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2641.33 | 7323.67 | 2430.17 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2504.67 | 7146.83 | 2076.33 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3783.33 | 7293.33 | 3310.33 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4386.17 | 8118.83 | 3347.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.83 | 0.00 | 0.83 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.50 | 0.00 | 0.50 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.83 | 0.00 | 0.83 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.83 | 0.00 | 0.83 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.270 | 0.137 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.044 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.044 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.060 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.138 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.121 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.270 | 0.137 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.262 | 0.000 | 0.000 | 0.000 |
HEATEDBSMT | 58539.52 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 58539.52 | 7794.39 | 0.0000 | 0.000 | |
Total Facility | 24.79 | 36.00 | 242278.90 | 29404.35 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12117141.55 | 35902223.24 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10672574.26 | 34457655.94 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12132529.74 | 35917611.43 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12105174.99 | 35890256.68 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10656983.11 | 34442064.80 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12119092.07 | 35904173.76 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5320056.82 | 29105138.51 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3871618.48 | 27656700.17 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5325943.06 | 29111024.75 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5314466.24 | 29099547.92 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 3865099.95 | 27650181.64 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 23785081.69 | 0.00 | 23785081.69 | 5319772.66 | 29104854.35 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12143080.36 | 35928162.05 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12155501.39 | 35940583.08 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12141255.02 | 35926336.70 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10682268.45 | 34467350.13 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 10696447.69 | 34481529.37 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 23785081.69 | 0.00 | 23785081.69 | 12131214.42 | 35916296.11 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 0.00 |
HEATEDBSMT | 23785081.69 | 0.00 | 23785081.69 | 0.00 | 23785081.69 | 23785081.69 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Total Facility | 0.451917E+09 | 0.00 | 0.451917E+09 | 0.168770E+09 | 0.620687E+09 | 0.451917E+09 | 0.00 | 8808.00 | 0.00 | 8808.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9224 | 67.9174 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.1896 | 65.1846 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9515 | 67.9465 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.8997 | 67.8947 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.1601 | 65.1551 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9261 | 67.9210 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0641 | 55.0591 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.3241 | 52.3190 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0753 | 55.0702 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0535 | 55.0485 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 7.3117 | 52.3067 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.9950 | 0.0000 | 44.9950 | 10.0636 | 55.0586 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9714 | 67.9664 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9949 | 67.9899 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9680 | 67.9630 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.2080 | 65.2030 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 20.2348 | 65.2298 | 44.9950 | 0.00 | 8808.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 44.9950 | 0.0000 | 44.9950 | 22.9490 | 67.9440 | 44.9950 | 0.00 | 8808.00 | 0.00 |
Total Facility | 809.9097 | 0.0000 | 809.9097 | 319.2679 | 1129.1776 | 809.9097 | 0.00 | 8808.00 | 0.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 23785081.69 | 8808.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 44.9950 | 8808.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1995 |
Defaulted Fields | 1573 |
Fields with Defaults | 6378 |
Autosized Fields | 338 |
Autosizable Fields | 600 |
Autocalculated Fields | 161 |
Autocalculatable Fields | 349 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
Electricity:Building | 99897.62 | 6287.72 | 02-JAN-03:10 | 18943.41 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity | 12093.82 | 270.83 | 01-JAN-00:10 | 3939.36 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 12093.82 | 270.83 | 01-JAN-00:10 | 3939.36 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5549.87 | 349.32 | 02-JAN-03:10 | 1052.41 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 671.88 | 15.05 | 01-JAN-00:10 | 218.85 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 87803.80 | 5989.14 | 02-JAN-04:10 | 15388.75 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:10 | 880.12 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:10 | 381.47 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4877.99 | 332.73 | 02-JAN-04:10 | 854.93 | 01-JAN-18:10 |
Fans:Electricity | 12852.46 | 622.49 | 07-AUG-14:20 | 3149.13 | 12-JAN-10:00 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
ElectricityPurchased:Plant | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
Cogeneration:ElectricityPurchased | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
General:Cogeneration:ElectricityPurchased | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
ElectricityNet:Plant | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
Cogeneration:ElectricityNet | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
General:Cogeneration:ElectricityNet | 390376.07 | 8716.56 | 01-AUG-03:40 | 154292.36 | 12-JAN-07:30 |
Electricity:HVAC | 222398.85 | 781.04 | 10-AUG-00:50 | 87097.89 | 12-JAN-10:00 |
HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:HeatRecovery:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Fans:Electricity | 7502.60 | 11.77 | 07-AUG-14:20 | 2538.41 | 12-JAN-10:00 |
Ventilation:Fans:Electricity | 5349.86 | 610.71 | 01-JAN-00:10 | 610.71 | 01-JAN-00:10 |
ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 5508.71 | 0.00 | 01-JAN-06:10 | 1257.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 205224.53 | 0.00 | 02-JUN-15:30 | 83948.76 | 12-JAN-10:00 |
General:Heating:Electricity | 205224.53 | 0.00 | 02-JUN-15:30 | 83948.76 | 12-JAN-10:00 |
Cooling:Electricity | 4321.86 | 0.00 | 01-JAN-00:10 | 7654.16 | 29-JUL-16:10 |
General:Cooling:Electricity | 4321.86 | 0.00 | 01-JAN-00:10 | 7654.16 | 29-JUL-16:10 |
Electricity:Plant | 62570.89 | 0.00 | 01-JAN-00:10 | 58955.33 | 07-JAN-08:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 62570.89 | 0.00 | 01-JAN-00:10 | 58955.33 | 07-JAN-08:10 |
Water Heater:WaterSystems:Electricity | 62570.89 | 0.00 | 01-JAN-00:10 | 58955.33 | 07-JAN-08:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Facility | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
MainsWater:Plant | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 44223.64 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1508608.57 | 18934.97 | 13-AUG-04:00 | 523070.14 | 12-JAN-10:00 |
EnergyTransfer:Building | 542459.40 | 9380.18 | 07-AUG-16:00 | 196712.79 | 12-JAN-10:00 |
EnergyTransfer:Zone:HEATEDBSMT | 76938.47 | 0.06 | 27-JUL-18:30 | 19178.08 | 12-JAN-05:00 |
Heating:EnergyTransfer | 432622.37 | 0.00 | 02-JUN-15:30 | 196712.79 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 76800.49 | 0.00 | 02-JUN-15:30 | 19178.08 | 12-JAN-05:00 |
General:Heating:EnergyTransfer | 432622.37 | 0.00 | 02-JUN-15:30 | 196712.79 | 12-JAN-10:00 |
Cooling:EnergyTransfer | 109837.04 | 0.00 | 01-JAN-00:10 | 95297.48 | 11-JUL-18:10 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 137.98 | 0.00 | 01-JAN-00:10 | 1145.09 | 30-AUG-18:50 |
General:Cooling:EnergyTransfer | 109837.04 | 0.00 | 01-JAN-00:10 | 95297.48 | 11-JUL-18:10 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27427.65 | 0.01 | 07-AUG-02:50 | 10852.60 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21684.55 | 0.00 | 06-MAR-14:30 | 10852.60 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5743.09 | 0.00 | 01-JAN-00:10 | 7524.97 | 06-JUL-18:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18563.68 | 0.05 | 13-SEP-23:10 | 7709.82 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13818.51 | 0.00 | 09-FEB-13:00 | 7709.82 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4745.18 | 0.00 | 01-JAN-00:10 | 4057.15 | 23-JUL-13:40 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27434.13 | 0.07 | 08-MAY-05:20 | 10855.07 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21100.81 | 0.00 | 11-MAR-12:20 | 10855.07 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6333.32 | 0.00 | 01-JAN-00:10 | 6836.43 | 22-JUL-10:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 27475.14 | 0.16 | 15-SEP-13:20 | 10860.79 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23464.69 | 0.00 | 22-MAR-15:20 | 10860.79 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4010.45 | 0.00 | 01-JAN-00:10 | 6708.78 | 11-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 18516.02 | 1.29 | 03-MAY-14:30 | 7715.69 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 15485.26 | 0.00 | 05-APR-18:10 | 7715.69 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3030.76 | 0.00 | 01-JAN-00:10 | 2822.20 | 11-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 27340.10 | 0.24 | 07-AUG-04:00 | 10858.05 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22806.69 | 0.00 | 22-MAR-10:40 | 10858.05 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4533.41 | 0.00 | 01-JAN-00:10 | 6199.06 | 07-JUL-07:50 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 24750.36 | 0.63 | 14-APR-11:20 | 8860.86 | 06-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 16366.10 | 0.00 | 09-FEB-13:50 | 8697.48 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8384.26 | 0.00 | 01-JAN-00:10 | 8860.86 | 06-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 15944.30 | 0.19 | 19-APR-02:30 | 5357.93 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8389.73 | 0.00 | 09-FEB-12:40 | 5357.93 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7554.57 | 0.00 | 01-JAN-00:10 | 5011.62 | 23-JUL-14:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 25366.83 | 0.00 | 01-SEP-06:20 | 8700.10 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15862.81 | 0.00 | 09-FEB-13:00 | 8700.10 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9504.02 | 0.00 | 01-JAN-00:10 | 8210.81 | 22-JUL-10:20 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 24168.60 | 0.81 | 05-SEP-14:10 | 8707.03 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 18158.28 | 0.00 | 20-MAR-16:20 | 8707.03 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 6010.33 | 0.00 | 01-JAN-00:10 | 7823.33 | 06-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 14850.36 | 0.46 | 19-SEP-08:00 | 5365.25 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9875.63 | 0.00 | 18-MAR-18:30 | 5365.25 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4974.73 | 0.00 | 01-JAN-00:10 | 3704.82 | 11-JUL-20:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 24469.88 | 0.16 | 11-APR-13:10 | 8704.16 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 17514.50 | 0.00 | 20-MAR-10:40 | 8704.16 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6955.38 | 0.00 | 01-JAN-00:10 | 7508.38 | 07-JUL-08:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 34917.17 | 0.02 | 18-MAY-02:10 | 13329.23 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 28580.80 | 0.00 | 22-MAR-11:30 | 13329.23 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 6336.37 | 0.00 | 01-JAN-00:10 | 7298.97 | 07-JUL-08:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 34754.17 | 0.58 | 30-MAY-01:30 | 13325.02 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 26607.85 | 0.00 | 19-MAR-14:30 | 13325.02 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 8146.32 | 0.00 | 01-JAN-00:10 | 8010.68 | 22-JUL-10:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 34648.38 | 0.10 | 06-SEP-14:10 | 13323.18 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 27332.57 | 0.00 | 20-MAR-13:30 | 13323.18 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 7315.82 | 0.00 | 01-JAN-00:10 | 9007.60 | 11-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 25155.92 | 0.18 | 15-SEP-14:40 | 9974.64 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 20726.24 | 0.00 | 22-MAR-19:10 | 9974.64 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4429.68 | 0.00 | 01-JAN-00:10 | 4272.14 | 11-JUL-20:40 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 24770.30 | 0.08 | 03-SEP-10:40 | 9967.83 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 18661.26 | 0.00 | 09-FEB-13:50 | 9967.83 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 6109.05 | 0.00 | 01-JAN-00:10 | 5089.61 | 23-JUL-14:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 34967.94 | 0.02 | 19-AUG-04:30 | 13331.43 | 12-JAN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29385.60 | 0.00 | 05-APR-18:10 | 13331.43 | 12-JAN-10:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5582.33 | 0.00 | 01-JAN-00:10 | 8394.93 | 11-JUL-18:40 |
EnergyTransfer:HVAC | 769259.47 | 1612.42 | 07-AUG-14:20 | 286433.19 | 12-JAN-10:00 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRecoveryForCooling:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:EnergyTransfer | 700722.18 | 0.00 | 02-JUN-15:30 | 286433.19 | 12-JAN-10:00 |
CoolingCoils:EnergyTransfer | 68537.29 | 0.00 | 01-JAN-00:10 | 110344.08 | 11-JUL-18:10 |
EnergyTransfer:Plant | 196889.70 | 1908.72 | 04-SEP-02:20 | 45345.70 | 01-JAN-09:00 |
WaterSystems:EnergyTransfer | 196889.70 | 1908.72 | 04-SEP-02:20 | 45345.70 | 01-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 196889.70 | 1908.72 | 04-SEP-02:20 | 45345.70 | 01-JAN-09:00 |
PlantLoopHeatingDemand:Facility | 196889.70 | 1908.72 | 04-SEP-02:20 | 45345.70 | 01-JAN-09:00 |
PlantLoopHeatingDemand:Plant | 196889.70 | 1908.72 | 04-SEP-02:20 | 45345.70 | 01-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 196889.70 | 1908.72 | 04-SEP-02:20 | 45345.70 | 01-JAN-09:00 |
General:WaterSystems:PlantLoopHeatingDemand | 196889.70 | 1908.72 | 04-SEP-02:20 | 45345.70 | 01-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21.636 | -1483.76 | 36988.251 | -270.78 | 0.000 | 0.000 | 3115.688 | 2294.076 | 10401.374 | 7119.319 | 0.000 | 4.504 | 0.000 | 0.000 | -11147.77 | 0.000 | -10722.80 | -17005.77 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21.632 | -1484.35 | 28720.510 | -153.63 | 0.000 | 0.000 | 3113.031 | 2294.076 | 10401.374 | 4198.396 | 0.000 | 3.963 | 0.000 | 0.000 | -4426.72 | 0.000 | -9442.75 | -15214.65 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21.618 | -1487.34 | 36164.209 | -296.34 | 0.000 | 0.000 | 3109.680 | 2294.076 | 10401.374 | 8632.052 | 0.000 | 4.501 | 0.000 | 0.000 | -10913.93 | 0.000 | -10742.34 | -17552.84 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21.643 | -1480.47 | 39199.128 | -165.65 | 0.000 | 0.000 | 3120.296 | 2294.076 | 10401.374 | 4089.800 | 0.000 | 4.505 | 0.000 | 0.000 | -11818.25 | 0.000 | -10702.05 | -16843.91 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21.649 | -1479.55 | 31050.853 | -70.92 | 0.000 | 0.000 | 3121.146 | 2294.076 | 10401.374 | 904.931 | 0.000 | 3.967 | 0.000 | 0.000 | -4901.13 | 0.000 | -9417.10 | -14861.70 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21.638 | -1483.71 | 38325.803 | -188.02 | 0.000 | 0.000 | 3116.040 | 2294.076 | 10401.374 | 5511.398 | 0.000 | 4.505 | 0.000 | 0.000 | -11488.87 | 0.000 | -10719.53 | -17392.21 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21.636 | -1491.48 | 30948.833 | -422.96 | 0.000 | 0.000 | 3091.802 | 2294.076 | 10401.374 | 7030.488 | 0.000 | 1.950 | 0.000 | 0.000 | -11301.92 | 0.000 | -4719.57 | -14779.96 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21.637 | -1493.58 | 22220.633 | -289.16 | 0.000 | 0.000 | 3084.973 | 2294.076 | 10401.374 | 4156.814 | 0.000 | 1.418 | 0.000 | 0.000 | -4495.50 | 0.000 | -3435.68 | -12842.59 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21.617 | -1494.77 | 30169.996 | -489.98 | 0.000 | 0.000 | 3086.775 | 2294.076 | 10401.374 | 8522.497 | 0.000 | 1.948 | 0.000 | 0.000 | -11057.70 | 0.000 | -4727.82 | -14879.88 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21.641 | -1487.91 | 33339.360 | -278.67 | 0.000 | 0.000 | 3097.928 | 2294.076 | 10401.374 | 4010.050 | 0.000 | 1.950 | 0.000 | 0.000 | -11955.83 | 0.000 | -4709.16 | -15288.26 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21.646 | -1487.85 | 24714.081 | -163.95 | 0.000 | 0.000 | 3097.338 | 2294.076 | 10401.374 | 873.561 | 0.000 | 1.418 | 0.000 | 0.000 | -4962.28 | 0.000 | -3423.84 | -13182.51 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21.636 | -1490.84 | 32513.053 | -339.23 | 0.000 | 0.000 | 3095.391 | 2294.076 | 10401.374 | 5417.064 | 0.000 | 1.950 | 0.000 | 0.000 | -11621.97 | 0.000 | -4716.33 | -15430.63 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21.634 | -1487.86 | 44057.554 | -330.49 | 0.000 | 0.000 | 3101.056 | 2294.076 | 10401.374 | 5428.708 | 0.000 | 4.405 | 0.000 | 0.000 | -11550.59 | 0.000 | -10764.65 | -21158.73 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21.615 | -1491.21 | 41659.474 | -442.47 | 0.000 | 0.000 | 3094.299 | 2294.076 | 10401.374 | 8544.204 | 0.000 | 4.401 | 0.000 | 0.000 | -10979.91 | 0.000 | -10786.07 | -21033.82 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 21.634 | -1487.77 | 42561.571 | -391.52 | 0.000 | 0.000 | 3099.600 | 2294.076 | 10401.374 | 7048.664 | 0.000 | 4.405 | 0.000 | 0.000 | -11219.38 | 0.000 | -10766.68 | -20878.71 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21.642 | -1484.81 | 36197.232 | -174.28 | 0.000 | 0.000 | 3103.785 | 2294.076 | 10401.374 | 876.218 | 0.000 | 3.879 | 0.000 | 0.000 | -4926.94 | 0.000 | -9462.17 | -18586.72 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21.634 | -1489.27 | 33594.311 | -264.87 | 0.000 | 0.000 | 3094.251 | 2294.076 | 10401.374 | 4165.087 | 0.000 | 3.878 | 0.000 | 0.000 | -4458.52 | 0.000 | -9487.18 | -18565.12 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 21.638 | -1485.00 | 45016.214 | -283.38 | 0.000 | 0.000 | 3104.007 | 2294.076 | 10401.374 | 4015.859 | 0.000 | 4.405 | 0.000 | 0.000 | -11878.78 | 0.000 | -10748.92 | -20995.20 |
HEATEDBSMT | 43.175 | -1460.14 | 94152.776 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -76662.50 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 28073.155 | 71364.762 | 0.000 | 0.000 | 0.000 | -99437.92 | -2.84 |
Total Facility | 432.600 | -28231.68 | 721593.843 | -5016.29 | 0.000 | 0.000 | 55847.086 | 41293.362 | 187224.736 | 90545.110 | 0.000 | 28135.109 | 71364.762 | 0.000 | -165105.99 | 0.000 | -248932.57 | -383158.56 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 06-JUL-18:20 | 0.00 | 0.01 | 0.00 | -0.6 | 0.00 | 0.00 | 426.74 | 673.81 | 1713.00 | 6759.02 | 0.00 | 11.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2058.6 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 23-JUL-13:40 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 96.26 | 1099.93 | 4453.54 | 0.00 | 15.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1723.5 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22-JUL-10:10 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 96.26 | 1108.25 | 8766.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25.1 | -3223.6 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11-JUL-18:10 | 0.00 | 0.02 | 0.00 | -0.6 | 0.00 | 0.00 | 426.74 | 673.81 | 1713.00 | 6374.40 | 0.00 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2565.5 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11-JUL-20:25 | 0.00 | -0.0 | 0.00 | -0.2 | 0.00 | 0.00 | 426.75 | 746.73 | 1615.87 | 1075.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29.2 | -1009.9 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 07-JUL-07:50 | 0.00 | -0.0 | 0.00 | -0.5 | 0.00 | 0.00 | 420.18 | 320.86 | 1204.45 | 7934.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75.1 | -3605.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 06-JUL-18:30 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.73 | 673.81 | 1713.00 | 6588.00 | 0.00 | 4.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -545.3 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23-JUL-14:10 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 96.26 | 1105.69 | 4018.34 | 0.00 | 6.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -330.3 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 22-JUL-10:20 | 0.00 | -0.0 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 96.26 | 1108.25 | 8642.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7.8 | -1743.9 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 06-JUL-19:30 | 0.00 | 0.01 | 0.00 | -0.7 | 0.00 | 0.00 | 426.74 | 746.73 | 1650.38 | 5976.71 | 0.00 | 2.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -979.7 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 11-JUL-20:50 | 0.00 | -0.0 | 0.00 | -0.3 | 0.00 | 0.00 | 426.76 | 746.73 | 1615.87 | 1005.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17.6 | -71.5 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 07-JUL-08:00 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 420.18 | 320.86 | 1204.45 | 7933.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31.1 | -2339.4 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 07-JUL-07:55 | 0.00 | -0.0 | 0.00 | -0.6 | 0.00 | 0.00 | 420.18 | 320.86 | 1204.45 | 7937.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -71.1 | -2511.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 22-JUL-10:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 96.26 | 1108.25 | 8533.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11.4 | -1828.6 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11-JUL-18:10 | 0.00 | 0.02 | 0.00 | -0.8 | 0.00 | 0.00 | 426.73 | 673.81 | 1713.00 | 6310.66 | 0.00 | 84.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -201.5 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 11-JUL-20:25 | 0.00 | -0.0 | 0.00 | -0.4 | 0.00 | 0.00 | 426.73 | 746.73 | 1615.87 | 1055.94 | 0.00 | 0.00 | 459.11 | 0.00 | 0.00 | 0.00 | -30.4 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 23-JUL-14:30 | 0.00 | 0.01 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 96.26 | 1105.69 | 3674.16 | 0.00 | 21.23 | 76.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11-JUL-18:40 | 0.00 | 0.02 | 0.00 | -0.7 | 0.00 | 0.00 | 426.75 | 673.81 | 1713.00 | 5766.08 | 0.00 | 86.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -270.5 |
HEATEDBSMT | 30-AUG-20:10 | 0.00 | -0.1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-JUL-18:10 | 0.00 | 0.39 | 0.00 | -8.3 | 0.00 | 0.00 | 7681.59 | 12128.50 | 30834.00 | 46591.72 | 0.00 | 1190.20 | 38859.20 | 0.00 | 0.00 | 0.00 | -42316.1 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.1 | 0.00 | 16029.43 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3937.2 | 0.00 | -4391.4 | -3831.1 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.4 | 0.00 | 12887.05 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1590.3 | 0.00 | -3866.9 | -3559.7 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.0 | 0.00 | 16031.84 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3937.2 | 0.00 | -4391.4 | -3833.5 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.1 | 0.00 | 16037.59 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3937.1 | 0.00 | -4391.4 | -3839.4 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.4 | 0.00 | 12892.89 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1590.3 | 0.00 | -3866.9 | -3565.6 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12-JAN-10:00 | -5177.0 | 0.00 | 16034.78 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3937.1 | 0.00 | -4391.4 | -3836.6 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.0 | 0.00 | 13877.27 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3932.4 | 0.00 | -1924.1 | -4148.1 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.8 | 0.00 | 10538.51 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1590.0 | 0.00 | -1399.4 | -3675.8 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.0 | 0.00 | 13879.82 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3932.4 | 0.00 | -1924.1 | -4150.7 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.0 | 0.00 | 13886.78 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3932.3 | 0.00 | -1924.1 | -4157.7 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12-JAN-10:00 | -5180.7 | 0.00 | 10545.77 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1589.9 | 0.00 | -1399.4 | -3683.2 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12-JAN-10:00 | -5179.9 | 0.00 | 13883.83 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3932.3 | 0.00 | -1924.1 | -4154.8 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-JAN-10:00 | -5177.0 | 0.00 | 18505.93 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3899.1 | 0.00 | -4395.7 | -6341.4 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12-JAN-10:00 | -5177.1 | 0.00 | 18501.77 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3899.2 | 0.00 | -4395.7 | -6337.2 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12-JAN-10:00 | -5177.1 | 0.00 | 18500.01 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3899.2 | 0.00 | -4395.7 | -6335.3 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12-JAN-10:00 | -5177.5 | 0.00 | 15151.83 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1575.2 | 0.00 | -3870.7 | -5835.8 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12-JAN-10:00 | -5177.5 | 0.00 | 15145.04 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1575.2 | 0.00 | -3870.7 | -5829.0 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12-JAN-10:00 | -5177.1 | 0.00 | 18508.23 | 0.00 | 0.00 | 0.00 | 127.29 | 96.26 | 1083.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3899.1 | 0.00 | -4395.7 | -6343.7 |
HEATEDBSMT | 12-JAN-05:00 | -5128.4 | 0.00 | 24306.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19178.0 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JAN-10:00 | -98378.9 | 0.00 | 295087.03 | 0.00 | 0.00 | 0.00 | 2291.27 | 1732.64 | 19508.63 | 0.00 | 0.00 | 15320.17 | 0.00 | 0.00 | -56585.6 | 0.00 | -61118.9 | -117856.2 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 358.4125 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 358.4125 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 184.7810 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 184.7810 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 282.9390 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 282.9390 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 318.9770 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 318.9770 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 156.5781 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 156.5781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 234.2133 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 234.2133 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 422.8390 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 422.8390 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 226.8456 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 226.8456 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 339.4380 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 339.4380 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 374.2949 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 374.2949 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.2134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 167.2134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.0470 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 286.0470 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 436.3522 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 436.3522 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 234.2582 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 234.2582 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.1764 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 333.1764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 404.3465 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 404.3465 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 203.4532 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 203.4532 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 280.9818 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 280.9818 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 361.7620 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 361.7620 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 358.4125 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 358.4125 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 184.7810 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 184.7810 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 282.9390 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 282.9390 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 318.9770 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 318.9770 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 156.5781 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 156.5781 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 234.2133 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 234.2133 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 422.8390 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 422.8390 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 226.8456 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 226.8456 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 339.4380 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 339.4380 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 374.2949 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 374.2949 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.2134 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 167.2134 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.0470 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 286.0470 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 436.3522 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 436.3522 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 234.2582 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 234.2582 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.1764 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 333.1764 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 404.3465 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 404.3465 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 203.4532 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 203.4532 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 280.9818 | 0.0000 | 2.0000 | 1.0000 | 0.0000 | 280.9818 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNITHEATEDBSMT | 361.7620 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 361.7620 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.0000 | 0.000000 | 7794.39 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.3864 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 358.4125 | 358.4125 | 358.4125 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 184.7810 | 184.7810 | 184.7810 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 282.9390 | 282.9390 | 282.9390 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 318.9770 | 318.9770 | 318.9770 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 156.5781 | 156.5781 | 156.5781 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 234.2133 | 234.2133 | 234.2133 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 422.8390 | 422.8390 | 422.8390 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 226.8456 | 226.8456 | 226.8456 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 339.4380 | 339.4380 | 339.4380 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 374.2949 | 374.2949 | 374.2949 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 167.2134 | 167.2134 | 167.2134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 286.0470 | 286.0470 | 286.0470 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 280.9818 | 280.9818 | 280.9818 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 333.1764 | 333.1764 | 333.1764 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 436.3522 | 436.3522 | 436.3522 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 203.4532 | 203.4532 | 203.4532 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 234.2582 | 234.2582 | 234.2582 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 404.3465 | 404.3465 | 404.3465 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 361.7620 | 361.7620 | 361.7620 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 358.4125 | 358.4125 | 358.4125 | 358.4125 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 184.7810 | 184.7810 | 184.7810 | 184.7810 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 282.9390 | 282.9390 | 282.9390 | 282.9390 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 318.9770 | 318.9770 | 318.9770 | 318.9770 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 156.5781 | 156.5781 | 156.5781 | 156.5781 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 234.2133 | 234.2133 | 234.2133 | 234.2133 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 422.8390 | 422.8390 | 422.8390 | 422.8390 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 226.8456 | 226.8456 | 226.8456 | 226.8456 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 339.4380 | 339.4380 | 339.4380 | 339.4380 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 374.2949 | 374.2949 | 374.2949 | 374.2949 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.2134 | 167.2134 | 167.2134 | 167.2134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.0470 | 286.0470 | 286.0470 | 286.0470 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 436.3522 | 436.3522 | 436.3522 | 436.3522 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 234.2582 | 234.2582 | 234.2582 | 234.2582 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.1764 | 333.1764 | 333.1764 | 333.1764 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 404.3465 | 404.3465 | 404.3465 | 404.3465 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 203.4532 | 203.4532 | 203.4532 | 203.4532 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 280.9818 | 280.9818 | 280.9818 | 280.9818 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 361.7620 | 361.7620 | 361.7620 | 361.7620 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 358.4125 | 358.4125 | 358.4125 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 184.7810 | 184.7810 | 184.7810 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 282.9390 | 282.9390 | 282.9390 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 318.9770 | 318.9770 | 318.9770 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 156.5781 | 156.5781 | 156.5781 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 234.2133 | 234.2133 | 234.2133 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 422.8390 | 422.8390 | 422.8390 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 226.8456 | 226.8456 | 226.8456 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 339.4380 | 339.4380 | 339.4380 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 374.2949 | 374.2949 | 374.2949 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 167.2134 | 167.2134 | 167.2134 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 286.0470 | 286.0470 | 286.0470 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 280.9818 | 280.9818 | 280.9818 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 333.1764 | 333.1764 | 333.1764 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 436.3522 | 436.3522 | 436.3522 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 203.4532 | 203.4532 | 203.4532 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 234.2582 | 234.2582 | 234.2582 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 404.3465 | 404.3465 | 404.3465 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 361.7620 | 361.7620 | 361.7620 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 358.4125 | 358.4125 | 358.4125 | 358.4125 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 184.7810 | 184.7810 | 184.7810 | 184.7810 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 282.9390 | 282.9390 | 282.9390 | 282.9390 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 318.9770 | 318.9770 | 318.9770 | 318.9770 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 156.5781 | 156.5781 | 156.5781 | 156.5781 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 234.2133 | 234.2133 | 234.2133 | 234.2133 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 422.8390 | 422.8390 | 422.8390 | 422.8390 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 226.8456 | 226.8456 | 226.8456 | 226.8456 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 339.4380 | 339.4380 | 339.4380 | 339.4380 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 374.2949 | 374.2949 | 374.2949 | 374.2949 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 167.2134 | 167.2134 | 167.2134 | 167.2134 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 286.0470 | 286.0470 | 286.0470 | 286.0470 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 436.3522 | 436.3522 | 436.3522 | 436.3522 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 234.2582 | 234.2582 | 234.2582 | 234.2582 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 333.1764 | 333.1764 | 333.1764 | 333.1764 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 404.3465 | 404.3465 | 404.3465 | 404.3465 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 203.4532 | 203.4532 | 203.4532 | 203.4532 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 280.9818 | 280.9818 | 280.9818 | 280.9818 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 361.7620 | 361.7620 | 361.7620 | 361.7620 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 29404.35 | 9600.87 |
Data | |
Number of hours heating loads not met | 0.83 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 205224.53 | 83948.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4321.86 | 7654.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 12093.82 | 3939.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 5508.71 | 1257.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 2758.31 | 880.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1408.53 | 381.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 7502.60 | 2538.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 5349.86 | 610.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 62570.89 | 58955.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299798.81 | 1332906.80 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 299798.81 | 1332906.80 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.31 |
Space Heating | 5.26 |
Space Cooling | 0.11 |
Fans (All) | 0.33 |
Service Water Heating | 1.60 |
Receptacle Equipment | 2.25 |
Miscellaneous (All) | 10.01 |
Subtotal | 10.01 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 3.10 |
Space Heating | 52.57 |
Space Cooling | 1.11 |
Fans (All) | 3.29 |
Service Water Heating | 16.03 |
Receptacle Equipment | 22.49 |
Miscellaneous | 1.41 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DHW_SCH | 365. | 8760. |
DISHWASHER | 2799. | 8760. |
CLOTHESWASHER | 3297. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SINKS | 4179. | 8760. |
SHOWERS | 2640. | 8760. |
BATHS | 2586. | 8760. |
DHWDIST | 4662. | 8760. |
SHADING_2012IECC | 0. | 0. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 8548.67 | 201.17 | 10.17 | 0.00 | 0.00 |
Min | 8548.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 201.17 | 10.17 | 0.00 | 0.00 |
Average | 8747.99 | 11.52 | 0.48 | 0.00 | 0.00 |
Sum | 183707.83 | 242.00 | 10.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 8609.17 | 150.83 | 0.00 | 0.00 | 0.00 |
Min | 8609.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 150.83 | 0.00 | 0.00 | 0.00 |
Average | 8752.82 | 7.18 | 0.00 | 0.00 | 0.00 |
Sum | 183809.17 | 150.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9125.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7821.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 164250.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (F) | SET ≤ 12.2°C OccupantHours (F) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (F) | SET > 30°C OccupantHours (F) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2021-05-12 10:53:30
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 68.531 | 68.531 |
February | 0.000 | 0.000 | 672.000 | 53.978 | 53.978 |
March | 0.000 | 0.000 | 700.847 | 44.286 | 44.286 |
April | 79.667 | 3.310 | 448.183 | 19.134 | 22.444 |
May | 205.917 | 9.719 | 221.250 | 4.946 | 14.665 |
June | 363.861 | 20.779 | 31.972 | 0.557 | 21.336 |
July | 378.014 | 23.231 | 23.000 | 0.389 | 23.621 |
August | 291.625 | 14.827 | 86.861 | 1.794 | 16.621 |
September | 58.833 | 2.030 | 394.750 | 10.433 | 12.462 |
October | 1.500 | 0.015 | 693.806 | 32.281 | 32.295 |
November | 0.000 | 0.000 | 720.000 | 63.474 | 63.474 |
December | 0.000 | 0.000 | 744.000 | 72.624 | 72.624 |
Annual Sum or Average | 1379.417 | 73.911 | 5480.669 | 372.426 | 446.337 |
Minimum of Months | 0.000 | 0.000 | 23.000 | 0.389 | 12.462 |
Maximum of Months | 378.014 | 23.231 | 744.000 | 72.624 | 72.624 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 34.736 | 34.736 |
February | 0.000 | 0.000 | 670.167 | 27.295 | 27.295 |
March | 0.000 | 0.000 | 690.375 | 22.619 | 22.619 |
April | 36.944 | 0.550 | 440.747 | 9.972 | 10.522 |
May | 174.056 | 4.252 | 156.278 | 2.157 | 6.409 |
June | 361.444 | 11.712 | 14.611 | 0.159 | 11.870 |
July | 384.694 | 15.123 | 12.583 | 0.122 | 15.245 |
August | 297.078 | 9.647 | 47.583 | 0.619 | 10.266 |
September | 55.500 | 0.835 | 301.042 | 4.618 | 5.453 |
October | 1.167 | 0.004 | 644.639 | 15.726 | 15.730 |
November | 0.000 | 0.000 | 720.000 | 32.171 | 32.171 |
December | 0.000 | 0.000 | 744.000 | 36.921 | 36.921 |
Annual Sum or Average | 1310.883 | 42.123 | 5186.025 | 187.114 | 229.237 |
Minimum of Months | 0.000 | 0.000 | 12.583 | 0.122 | 5.453 |
Maximum of Months | 384.694 | 15.123 | 744.000 | 36.921 | 36.921 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 54.343 | 54.343 |
February | 0.000 | 0.000 | 672.000 | 42.292 | 42.292 |
March | 0.000 | 0.000 | 694.194 | 33.500 | 33.500 |
April | 67.881 | 1.566 | 431.764 | 14.583 | 16.149 |
May | 281.486 | 11.755 | 154.639 | 3.002 | 14.758 |
June | 449.778 | 21.936 | 16.750 | 0.247 | 22.183 |
July | 450.639 | 26.903 | 18.000 | 0.234 | 27.138 |
August | 346.028 | 15.908 | 53.250 | 0.937 | 16.845 |
September | 85.111 | 1.734 | 360.694 | 7.447 | 9.181 |
October | 2.833 | 0.028 | 679.306 | 24.813 | 24.841 |
November | 0.000 | 0.000 | 720.000 | 50.494 | 50.494 |
December | 0.000 | 0.000 | 744.000 | 57.747 | 57.747 |
Annual Sum or Average | 1683.756 | 79.831 | 5288.597 | 289.638 | 369.469 |
Minimum of Months | 0.000 | 0.000 | 16.750 | 0.234 | 9.181 |
Maximum of Months | 450.639 | 26.903 | 744.000 | 57.747 | 57.747 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 62.319 | 62.319 |
February | 0.000 | 0.000 | 672.000 | 51.274 | 51.274 |
March | 0.000 | 0.000 | 742.750 | 44.602 | 44.602 |
April | 22.917 | 0.723 | 557.139 | 20.647 | 21.370 |
May | 123.667 | 4.527 | 252.806 | 4.745 | 9.272 |
June | 344.028 | 15.486 | 18.722 | 0.310 | 15.796 |
July | 370.514 | 17.068 | 20.472 | 0.298 | 17.365 |
August | 215.361 | 8.101 | 106.417 | 1.925 | 10.027 |
September | 13.833 | 0.233 | 486.278 | 11.252 | 11.485 |
October | 0.000 | 0.000 | 732.500 | 31.522 | 31.522 |
November | 0.000 | 0.000 | 720.000 | 58.432 | 58.432 |
December | 0.000 | 0.000 | 744.000 | 65.220 | 65.220 |
Annual Sum or Average | 1090.319 | 46.138 | 5797.083 | 352.547 | 398.684 |
Minimum of Months | 0.000 | 0.000 | 18.722 | 0.298 | 9.272 |
Maximum of Months | 370.514 | 17.068 | 744.000 | 65.220 | 65.220 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 30.196 | 30.196 |
February | 0.000 | 0.000 | 672.000 | 25.052 | 25.052 |
March | 0.000 | 0.000 | 744.000 | 22.314 | 22.314 |
April | 0.000 | 0.000 | 624.361 | 11.223 | 11.223 |
May | 50.917 | 0.629 | 197.667 | 2.097 | 2.726 |
June | 321.639 | 6.795 | 10.361 | 0.096 | 6.891 |
July | 365.903 | 9.241 | 11.167 | 0.089 | 9.329 |
August | 189.361 | 3.666 | 71.778 | 0.744 | 4.409 |
September | 0.000 | 0.000 | 419.611 | 5.218 | 5.218 |
October | 0.000 | 0.000 | 700.500 | 14.975 | 14.975 |
November | 0.000 | 0.000 | 720.000 | 28.402 | 28.402 |
December | 0.000 | 0.000 | 744.000 | 31.597 | 31.597 |
Annual Sum or Average | 927.819 | 20.330 | 5659.444 | 172.002 | 192.332 |
Minimum of Months | 0.000 | 0.000 | 10.361 | 0.089 | 2.726 |
Maximum of Months | 365.903 | 9.241 | 744.000 | 31.597 | 31.597 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 45.996 | 45.996 |
February | 0.000 | 0.000 | 672.000 | 37.403 | 37.403 |
March | 0.000 | 0.000 | 738.875 | 31.521 | 31.521 |
April | 2.056 | 0.015 | 554.875 | 14.898 | 14.913 |
May | 209.417 | 5.295 | 163.333 | 2.636 | 7.931 |
June | 454.500 | 16.726 | 15.500 | 0.191 | 16.917 |
July | 450.625 | 20.851 | 17.667 | 0.191 | 21.042 |
August | 288.000 | 8.662 | 66.028 | 0.940 | 9.602 |
September | 2.667 | 0.026 | 434.361 | 7.416 | 7.442 |
October | 0.000 | 0.000 | 725.639 | 22.586 | 22.586 |
November | 0.000 | 0.000 | 720.000 | 43.276 | 43.276 |
December | 0.000 | 0.000 | 744.000 | 48.274 | 48.274 |
Annual Sum or Average | 1407.264 | 51.576 | 5596.278 | 255.327 | 306.903 |
Minimum of Months | 0.000 | 0.000 | 15.500 | 0.191 | 7.442 |
Maximum of Months | 454.500 | 20.851 | 744.000 | 48.274 | 48.274 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 79.955 | 79.955 |
February | 0.000 | 0.000 | 668.778 | 61.676 | 61.676 |
March | 0.000 | 0.000 | 661.028 | 48.199 | 48.199 |
April | 134.111 | 6.690 | 355.469 | 17.998 | 24.688 |
May | 298.444 | 16.191 | 100.889 | 3.030 | 19.222 |
June | 477.361 | 31.460 | 7.083 | 0.135 | 31.595 |
July | 512.583 | 34.178 | 6.000 | 0.125 | 34.303 |
August | 401.528 | 22.789 | 34.917 | 1.069 | 23.858 |
September | 98.500 | 3.546 | 300.903 | 10.106 | 13.653 |
October | 3.167 | 0.044 | 654.222 | 37.074 | 37.118 |
November | 0.000 | 0.000 | 720.000 | 74.445 | 74.445 |
December | 0.000 | 0.000 | 744.000 | 85.508 | 85.508 |
Annual Sum or Average | 1925.694 | 114.899 | 4997.289 | 419.321 | 534.220 |
Minimum of Months | 0.000 | 0.000 | 6.000 | 0.125 | 13.653 |
Maximum of Months | 512.583 | 34.178 | 744.000 | 85.508 | 85.508 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 41.740 | 41.740 |
February | 0.000 | 0.000 | 648.444 | 31.846 | 31.846 |
March | 0.000 | 0.000 | 609.056 | 24.680 | 24.680 |
April | 100.167 | 2.312 | 292.147 | 8.988 | 11.299 |
May | 302.139 | 9.571 | 51.819 | 1.056 | 10.627 |
June | 511.472 | 21.318 | 1.500 | 0.018 | 21.336 |
July | 562.000 | 25.460 | 2.167 | 0.025 | 25.485 |
August | 431.444 | 17.351 | 14.528 | 0.329 | 17.680 |
September | 104.250 | 2.367 | 178.750 | 4.074 | 6.441 |
October | 6.000 | 0.057 | 559.056 | 18.062 | 18.119 |
November | 0.000 | 0.000 | 719.583 | 38.941 | 38.941 |
December | 0.000 | 0.000 | 744.000 | 44.955 | 44.955 |
Annual Sum or Average | 2017.472 | 78.435 | 4565.050 | 214.714 | 293.149 |
Minimum of Months | 0.000 | 0.000 | 1.500 | 0.018 | 6.441 |
Maximum of Months | 562.000 | 25.460 | 744.000 | 44.955 | 44.955 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 64.551 | 64.551 |
February | 0.000 | 0.000 | 668.194 | 48.991 | 48.991 |
March | 0.500 | 0.001 | 631.564 | 36.257 | 36.258 |
April | 132.519 | 4.718 | 327.531 | 13.699 | 18.416 |
May | 397.319 | 21.126 | 66.667 | 1.699 | 22.825 |
June | 560.861 | 35.143 | 4.917 | 0.070 | 35.213 |
July | 572.819 | 40.030 | 4.417 | 0.071 | 40.101 |
August | 461.278 | 25.689 | 20.833 | 0.530 | 26.219 |
September | 120.444 | 3.880 | 259.972 | 7.112 | 10.992 |
October | 6.833 | 0.131 | 628.500 | 28.722 | 28.852 |
November | 0.000 | 0.000 | 720.000 | 60.353 | 60.353 |
December | 0.000 | 0.000 | 744.000 | 69.276 | 69.276 |
Annual Sum or Average | 2252.575 | 130.718 | 4820.594 | 331.330 | 462.048 |
Minimum of Months | 0.000 | 0.000 | 4.417 | 0.070 | 10.992 |
Maximum of Months | 572.819 | 40.030 | 744.000 | 69.276 | 69.276 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 72.784 | 72.784 |
February | 0.000 | 0.000 | 672.000 | 59.454 | 59.454 |
March | 0.000 | 0.000 | 728.833 | 50.453 | 50.453 |
April | 45.778 | 1.602 | 476.750 | 20.586 | 22.188 |
May | 200.778 | 8.224 | 114.236 | 2.885 | 11.109 |
June | 502.917 | 25.853 | 6.000 | 0.094 | 25.947 |
July | 527.722 | 27.577 | 4.750 | 0.087 | 27.664 |
August | 332.514 | 13.730 | 48.347 | 1.273 | 15.004 |
September | 23.333 | 0.423 | 402.472 | 11.793 | 12.216 |
October | 0.000 | 0.000 | 710.750 | 37.060 | 37.060 |
November | 0.000 | 0.000 | 720.000 | 68.842 | 68.842 |
December | 0.000 | 0.000 | 744.000 | 76.601 | 76.601 |
Annual Sum or Average | 1633.042 | 77.409 | 5372.139 | 401.913 | 479.322 |
Minimum of Months | 0.000 | 0.000 | 4.750 | 0.087 | 11.109 |
Maximum of Months | 527.722 | 27.577 | 744.000 | 76.601 | 76.601 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 31.986 | 31.986 |
February | 0.000 | 0.000 | 670.833 | 26.363 | 26.363 |
March | 0.000 | 0.000 | 726.861 | 22.990 | 22.990 |
April | 0.000 | 0.000 | 483.542 | 10.063 | 10.063 |
May | 139.667 | 2.519 | 65.139 | 0.949 | 3.467 |
June | 553.528 | 15.796 | 1.667 | 0.014 | 15.810 |
July | 575.583 | 18.804 | 2.083 | 0.017 | 18.821 |
August | 346.472 | 8.547 | 32.264 | 0.445 | 8.991 |
September | 0.000 | 0.000 | 290.389 | 4.677 | 4.677 |
October | 0.000 | 0.000 | 652.417 | 15.848 | 15.848 |
November | 0.000 | 0.000 | 720.000 | 30.476 | 30.476 |
December | 0.000 | 0.000 | 744.000 | 33.721 | 33.721 |
Annual Sum or Average | 1615.250 | 45.665 | 5133.194 | 177.549 | 223.214 |
Minimum of Months | 0.000 | 0.000 | 1.667 | 0.014 | 3.467 |
Maximum of Months | 575.583 | 18.804 | 744.000 | 33.721 | 33.721 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 55.962 | 55.962 |
February | 0.000 | 0.000 | 672.000 | 45.022 | 45.022 |
March | 0.000 | 0.000 | 722.264 | 36.569 | 36.569 |
April | 12.833 | 0.169 | 450.431 | 15.324 | 15.492 |
May | 344.681 | 12.295 | 74.250 | 1.641 | 13.936 |
June | 575.306 | 29.728 | 4.333 | 0.054 | 29.782 |
July | 579.903 | 33.393 | 4.583 | 0.061 | 33.454 |
August | 408.000 | 16.295 | 26.222 | 0.583 | 16.877 |
September | 11.139 | 0.127 | 345.250 | 7.845 | 7.973 |
October | 0.000 | 0.000 | 696.528 | 27.397 | 27.397 |
November | 0.000 | 0.000 | 720.000 | 53.164 | 53.164 |
December | 0.000 | 0.000 | 744.000 | 59.106 | 59.106 |
Annual Sum or Average | 1931.861 | 92.007 | 5203.861 | 302.727 | 394.734 |
Minimum of Months | 0.000 | 0.000 | 4.333 | 0.054 | 7.973 |
Maximum of Months | 579.903 | 33.393 | 744.000 | 59.106 | 59.106 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 83.480 | 83.480 |
February | 0.000 | 0.000 | 672.000 | 65.574 | 65.574 |
March | 0.000 | 0.000 | 714.708 | 53.115 | 53.115 |
April | 91.167 | 4.545 | 434.681 | 21.076 | 25.621 |
May | 251.139 | 13.823 | 181.889 | 4.315 | 18.139 |
June | 450.361 | 30.867 | 14.917 | 0.273 | 31.139 |
July | 488.778 | 33.995 | 11.306 | 0.218 | 34.212 |
August | 363.722 | 21.130 | 63.306 | 1.524 | 22.654 |
September | 71.083 | 2.376 | 407.028 | 12.356 | 14.732 |
October | 0.000 | 0.000 | 710.417 | 40.568 | 40.568 |
November | 0.000 | 0.000 | 720.000 | 78.241 | 78.241 |
December | 0.000 | 0.000 | 744.000 | 88.843 | 88.843 |
Annual Sum or Average | 1716.250 | 106.735 | 5418.250 | 449.583 | 556.318 |
Minimum of Months | 0.000 | 0.000 | 11.306 | 0.218 | 14.732 |
Maximum of Months | 488.778 | 33.995 | 744.000 | 88.843 | 88.843 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 44.008 | 44.008 |
February | 0.000 | 0.000 | 670.000 | 34.381 | 34.381 |
March | 0.000 | 0.000 | 715.431 | 27.970 | 27.970 |
April | 54.250 | 1.190 | 426.919 | 11.219 | 12.409 |
May | 236.722 | 7.604 | 117.389 | 1.792 | 9.395 |
June | 475.306 | 20.823 | 8.306 | 0.094 | 20.917 |
July | 528.194 | 25.258 | 6.972 | 0.076 | 25.334 |
August | 386.694 | 15.821 | 36.472 | 0.563 | 16.384 |
September | 73.167 | 1.218 | 324.250 | 5.682 | 6.901 |
October | 0.000 | 0.000 | 672.472 | 20.550 | 20.550 |
November | 0.000 | 0.000 | 720.000 | 41.351 | 41.351 |
December | 0.000 | 0.000 | 744.000 | 47.040 | 47.040 |
Annual Sum or Average | 1754.333 | 71.914 | 5186.211 | 234.726 | 306.640 |
Minimum of Months | 0.000 | 0.000 | 6.972 | 0.076 | 6.901 |
Maximum of Months | 528.194 | 25.258 | 744.000 | 47.040 | 47.040 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 64.127 | 64.127 |
February | 0.000 | 0.000 | 672.000 | 49.773 | 49.773 |
March | 0.000 | 0.000 | 708.875 | 38.821 | 38.821 |
April | 85.236 | 2.653 | 420.958 | 15.526 | 18.179 |
May | 350.444 | 17.277 | 121.194 | 2.389 | 19.666 |
June | 535.139 | 33.706 | 9.250 | 0.148 | 33.855 |
July | 552.264 | 39.156 | 8.333 | 0.123 | 39.278 |
August | 419.847 | 23.316 | 39.222 | 0.758 | 24.075 |
September | 95.306 | 2.287 | 370.056 | 8.452 | 10.738 |
October | 1.500 | 0.007 | 697.417 | 30.215 | 30.222 |
November | 0.000 | 0.000 | 720.000 | 60.290 | 60.290 |
December | 0.000 | 0.000 | 744.000 | 68.423 | 68.423 |
Annual Sum or Average | 2039.736 | 118.402 | 5255.306 | 339.045 | 457.448 |
Minimum of Months | 0.000 | 0.000 | 8.333 | 0.123 | 10.738 |
Maximum of Months | 552.264 | 39.156 | 744.000 | 68.423 | 68.423 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 78.851 | 78.851 |
February | 0.000 | 0.000 | 672.000 | 64.531 | 64.531 |
March | 0.000 | 0.000 | 743.167 | 55.232 | 55.232 |
April | 34.583 | 1.258 | 538.583 | 23.813 | 25.071 |
May | 175.917 | 7.851 | 213.222 | 4.391 | 12.242 |
June | 463.111 | 26.564 | 10.611 | 0.212 | 26.776 |
July | 503.167 | 28.721 | 9.167 | 0.164 | 28.885 |
August | 302.081 | 13.879 | 83.750 | 1.818 | 15.697 |
September | 14.639 | 0.264 | 510.417 | 14.100 | 14.365 |
October | 0.000 | 0.000 | 737.833 | 40.993 | 40.993 |
November | 0.000 | 0.000 | 720.000 | 74.746 | 74.746 |
December | 0.000 | 0.000 | 744.000 | 82.946 | 82.946 |
Annual Sum or Average | 1493.497 | 78.539 | 5726.750 | 441.796 | 520.335 |
Minimum of Months | 0.000 | 0.000 | 9.167 | 0.164 | 12.242 |
Maximum of Months | 503.167 | 28.721 | 744.000 | 82.946 | 82.946 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 39.146 | 39.146 |
February | 0.000 | 0.000 | 672.000 | 32.232 | 32.232 |
March | 0.000 | 0.000 | 743.167 | 28.089 | 28.089 |
April | 0.000 | 0.000 | 588.611 | 12.971 | 12.971 |
May | 122.500 | 2.699 | 148.611 | 1.841 | 4.540 |
June | 497.694 | 16.637 | 6.833 | 0.065 | 16.702 |
July | 543.111 | 20.143 | 6.750 | 0.061 | 20.204 |
August | 307.425 | 8.974 | 62.278 | 0.780 | 9.754 |
September | 0.000 | 0.000 | 449.500 | 6.635 | 6.635 |
October | 0.000 | 0.000 | 717.500 | 19.995 | 19.995 |
November | 0.000 | 0.000 | 720.000 | 37.321 | 37.321 |
December | 0.000 | 0.000 | 744.000 | 41.232 | 41.232 |
Annual Sum or Average | 1470.731 | 48.453 | 5603.250 | 220.368 | 268.821 |
Minimum of Months | 0.000 | 0.000 | 6.750 | 0.061 | 4.540 |
Maximum of Months | 543.111 | 20.143 | 744.000 | 41.232 | 41.232 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 55.213 | 55.213 |
February | 0.000 | 0.000 | 672.000 | 44.680 | 44.680 |
March | 0.000 | 0.000 | 742.028 | 37.010 | 37.010 |
April | 10.722 | 0.062 | 538.556 | 16.239 | 16.300 |
May | 298.806 | 10.228 | 129.056 | 2.187 | 12.414 |
June | 553.889 | 29.467 | 9.083 | 0.122 | 29.588 |
July | 560.931 | 33.788 | 8.333 | 0.104 | 33.892 |
August | 367.472 | 15.790 | 48.222 | 0.790 | 16.580 |
September | 5.750 | 0.020 | 460.500 | 8.796 | 8.817 |
October | 0.000 | 0.000 | 736.111 | 27.880 | 27.880 |
November | 0.000 | 0.000 | 720.000 | 52.511 | 52.511 |
December | 0.000 | 0.000 | 744.000 | 58.232 | 58.232 |
Annual Sum or Average | 1797.569 | 89.355 | 5551.889 | 303.765 | 393.119 |
Minimum of Months | 0.000 | 0.000 | 8.333 | 0.104 | 8.817 |
Maximum of Months | 560.931 | 33.788 | 744.000 | 58.232 | 58.232 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 109.574 | 109.574 |
February | 0.000 | 0.000 | 672.000 | 94.245 | 94.245 |
March | 0.000 | 0.000 | 744.000 | 94.078 | 94.078 |
April | 0.000 | 0.000 | 720.000 | 70.225 | 70.225 |
May | 0.000 | 0.000 | 744.000 | 24.035 | 24.035 |
June | 0.000 | 0.000 | 525.806 | 7.351 | 7.351 |
July | 0.000 | 0.000 | 410.292 | 5.487 | 5.487 |
August | 0.000 | 0.000 | 506.414 | 8.083 | 8.083 |
September | 0.000 | 0.000 | 712.500 | 21.379 | 21.379 |
October | 0.000 | 0.000 | 744.000 | 39.609 | 39.609 |
November | 0.000 | 0.000 | 720.000 | 88.277 | 88.277 |
December | 0.000 | 0.000 | 744.000 | 107.928 | 107.928 |
Annual Sum or Average | 0.000 | 0.000 | 7987.011 | 670.271 | 670.271 |
Minimum of Months | 0.000 | 0.000 | 410.292 | 5.487 | 5.487 |
Maximum of Months | 0.000 | 0.000 | 744.000 | 109.574 | 109.574 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8828.82 | 0.00 | 0.00 |
February | 7698.99 | 0.00 | 0.00 |
March | 5705.36 | 0.00 | 0.00 |
April | 2547.18 | 0.00 | 0.00 |
May | 637.17 | 0.00 | 0.00 |
June | 74.13 | 0.00 | 0.00 |
July | 50.12 | 0.00 | 0.00 |
August | 231.07 | 0.00 | 0.00 |
September | 1388.83 | 0.00 | 0.00 |
October | 4158.69 | 0.00 | 0.00 |
November | 8449.88 | 0.00 | 0.00 |
December | 9356.14 | 0.00 | 0.00 |
Annual Sum or Average | 4074.96 | 0.00 | 0.00 |
Minimum of Months | 50.12 | 0.00 | 0.00 |
Maximum of Months | 9356.14 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7003.06 | 0.00 | 0.00 |
February | 6092.47 | 0.00 | 0.00 |
March | 4560.08 | 0.00 | 0.00 |
April | 2077.44 | 0.00 | 0.00 |
May | 434.87 | 0.00 | 0.00 |
June | 33.05 | 0.00 | 0.00 |
July | 24.52 | 0.00 | 0.00 |
August | 124.73 | 0.00 | 0.00 |
September | 962.09 | 0.00 | 0.00 |
October | 3170.47 | 0.00 | 0.00 |
November | 6702.11 | 0.00 | 0.00 |
December | 7443.63 | 0.00 | 0.00 |
Annual Sum or Average | 3203.92 | 0.00 | 0.00 |
Minimum of Months | 24.52 | 0.00 | 0.00 |
Maximum of Months | 7443.63 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8865.35 | 0.00 | 0.00 |
February | 7638.69 | 0.00 | 0.00 |
March | 5465.12 | 0.00 | 0.00 |
April | 2458.29 | 0.00 | 0.00 |
May | 489.78 | 0.00 | 0.00 |
June | 41.60 | 0.00 | 0.00 |
July | 38.24 | 0.00 | 0.00 |
August | 152.86 | 0.00 | 0.00 |
September | 1255.43 | 0.00 | 0.00 |
October | 4047.87 | 0.00 | 0.00 |
November | 8512.08 | 0.00 | 0.00 |
December | 9420.67 | 0.00 | 0.00 |
Annual Sum or Average | 4013.10 | 0.00 | 0.00 |
Minimum of Months | 38.24 | 0.00 | 0.00 |
Maximum of Months | 9420.67 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 9021.97 | 0.00 | 0.00 |
February | 8218.31 | 0.00 | 0.00 |
March | 6457.02 | 0.00 | 0.00 |
April | 3088.69 | 0.00 | 0.00 |
May | 686.87 | 0.00 | 0.00 |
June | 46.42 | 0.00 | 0.00 |
July | 43.08 | 0.00 | 0.00 |
August | 278.72 | 0.00 | 0.00 |
September | 1683.25 | 0.00 | 0.00 |
October | 4563.45 | 0.00 | 0.00 |
November | 8741.23 | 0.00 | 0.00 |
December | 9441.91 | 0.00 | 0.00 |
Annual Sum or Average | 4334.75 | 0.00 | 0.00 |
Minimum of Months | 43.08 | 0.00 | 0.00 |
Maximum of Months | 9441.91 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7183.78 | 0.00 | 0.00 |
February | 6598.50 | 0.00 | 0.00 |
March | 5308.75 | 0.00 | 0.00 |
April | 2758.95 | 0.00 | 0.00 |
May | 498.89 | 0.00 | 0.00 |
June | 23.55 | 0.00 | 0.00 |
July | 21.07 | 0.00 | 0.00 |
August | 176.92 | 0.00 | 0.00 |
September | 1282.68 | 0.00 | 0.00 |
October | 3562.66 | 0.00 | 0.00 |
November | 6982.28 | 0.00 | 0.00 |
December | 7517.23 | 0.00 | 0.00 |
Annual Sum or Average | 3475.42 | 0.00 | 0.00 |
Minimum of Months | 21.07 | 0.00 | 0.00 |
Maximum of Months | 7517.23 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 9063.07 | 0.00 | 0.00 |
February | 8159.62 | 0.00 | 0.00 |
March | 6210.84 | 0.00 | 0.00 |
April | 3033.26 | 0.00 | 0.00 |
May | 519.38 | 0.00 | 0.00 |
June | 38.83 | 0.00 | 0.00 |
July | 37.63 | 0.00 | 0.00 |
August | 185.31 | 0.00 | 0.00 |
September | 1509.92 | 0.00 | 0.00 |
October | 4450.35 | 0.00 | 0.00 |
November | 8811.43 | 0.00 | 0.00 |
December | 9511.83 | 0.00 | 0.00 |
Annual Sum or Average | 4272.89 | 0.00 | 0.00 |
Minimum of Months | 37.63 | 0.00 | 0.00 |
Maximum of Months | 9511.83 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7561.45 | 0.00 | 0.00 |
February | 6457.74 | 0.00 | 0.00 |
March | 4558.24 | 0.00 | 0.00 |
April | 1758.82 | 0.00 | 0.00 |
May | 286.59 | 0.00 | 0.00 |
June | 13.22 | 0.00 | 0.00 |
July | 11.83 | 0.00 | 0.00 |
August | 101.11 | 0.00 | 0.00 |
September | 987.61 | 0.00 | 0.00 |
October | 3506.10 | 0.00 | 0.00 |
November | 7274.98 | 0.00 | 0.00 |
December | 8086.55 | 0.00 | 0.00 |
Annual Sum or Average | 3368.01 | 0.00 | 0.00 |
Minimum of Months | 11.83 | 0.00 | 0.00 |
Maximum of Months | 8086.55 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5612.86 | 0.00 | 0.00 |
February | 4741.24 | 0.00 | 0.00 |
March | 3318.68 | 0.00 | 0.00 |
April | 1248.87 | 0.00 | 0.00 |
May | 141.94 | 0.00 | 0.00 |
June | 2.51 | 0.00 | 0.00 |
July | 3.39 | 0.00 | 0.00 |
August | 44.25 | 0.00 | 0.00 |
September | 566.15 | 0.00 | 0.00 |
October | 2428.79 | 0.00 | 0.00 |
November | 5410.98 | 0.00 | 0.00 |
December | 6045.12 | 0.00 | 0.00 |
Annual Sum or Average | 2452.21 | 0.00 | 0.00 |
Minimum of Months | 2.51 | 0.00 | 0.00 |
Maximum of Months | 6045.12 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7600.54 | 0.00 | 0.00 |
February | 6386.46 | 0.00 | 0.00 |
March | 4269.03 | 0.00 | 0.00 |
April | 1666.68 | 0.00 | 0.00 |
May | 200.07 | 0.00 | 0.00 |
June | 8.51 | 0.00 | 0.00 |
July | 8.36 | 0.00 | 0.00 |
August | 62.39 | 0.00 | 0.00 |
September | 865.29 | 0.00 | 0.00 |
October | 3381.81 | 0.00 | 0.00 |
November | 7343.09 | 0.00 | 0.00 |
December | 8156.81 | 0.00 | 0.00 |
Annual Sum or Average | 3313.36 | 0.00 | 0.00 |
Minimum of Months | 8.36 | 0.00 | 0.00 |
Maximum of Months | 8156.81 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7776.79 | 0.00 | 0.00 |
February | 7033.12 | 0.00 | 0.00 |
March | 5390.75 | 0.00 | 0.00 |
April | 2272.90 | 0.00 | 0.00 |
May | 308.27 | 0.00 | 0.00 |
June | 10.38 | 0.00 | 0.00 |
July | 9.29 | 0.00 | 0.00 |
August | 136.07 | 0.00 | 0.00 |
September | 1302.03 | 0.00 | 0.00 |
October | 3959.75 | 0.00 | 0.00 |
November | 7600.71 | 0.00 | 0.00 |
December | 8184.52 | 0.00 | 0.00 |
Annual Sum or Average | 3647.22 | 0.00 | 0.00 |
Minimum of Months | 9.29 | 0.00 | 0.00 |
Maximum of Months | 8184.52 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 5834.45 | 0.00 | 0.00 |
February | 5323.98 | 0.00 | 0.00 |
March | 4193.54 | 0.00 | 0.00 |
April | 1896.80 | 0.00 | 0.00 |
May | 173.02 | 0.00 | 0.00 |
June | 2.69 | 0.00 | 0.00 |
July | 3.11 | 0.00 | 0.00 |
August | 81.09 | 0.00 | 0.00 |
September | 881.64 | 0.00 | 0.00 |
October | 2890.88 | 0.00 | 0.00 |
November | 5744.41 | 0.00 | 0.00 |
December | 6151.03 | 0.00 | 0.00 |
Annual Sum or Average | 2750.63 | 0.00 | 0.00 |
Minimum of Months | 2.69 | 0.00 | 0.00 |
Maximum of Months | 6151.03 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 7817.16 | 0.00 | 0.00 |
February | 6962.81 | 0.00 | 0.00 |
March | 5108.17 | 0.00 | 0.00 |
April | 2211.87 | 0.00 | 0.00 |
May | 229.16 | 0.00 | 0.00 |
June | 7.81 | 0.00 | 0.00 |
July | 8.52 | 0.00 | 0.00 |
August | 81.39 | 0.00 | 0.00 |
September | 1132.43 | 0.00 | 0.00 |
October | 3827.07 | 0.00 | 0.00 |
November | 7673.86 | 0.00 | 0.00 |
December | 8256.34 | 0.00 | 0.00 |
Annual Sum or Average | 3591.51 | 0.00 | 0.00 |
Minimum of Months | 7.81 | 0.00 | 0.00 |
Maximum of Months | 8256.34 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10232.89 | 0.00 | 0.00 |
February | 8899.16 | 0.00 | 0.00 |
March | 6510.77 | 0.00 | 0.00 |
April | 2669.58 | 0.00 | 0.00 |
May | 528.95 | 0.00 | 0.00 |
June | 34.55 | 0.00 | 0.00 |
July | 26.70 | 0.00 | 0.00 |
August | 186.82 | 0.00 | 0.00 |
September | 1565.09 | 0.00 | 0.00 |
October | 4972.82 | 0.00 | 0.00 |
November | 9910.43 | 0.00 | 0.00 |
December | 10890.25 | 0.00 | 0.00 |
Annual Sum or Average | 4680.52 | 0.00 | 0.00 |
Minimum of Months | 26.70 | 0.00 | 0.00 |
Maximum of Months | 10890.25 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8258.70 | 0.00 | 0.00 |
February | 7143.39 | 0.00 | 0.00 |
March | 5248.90 | 0.00 | 0.00 |
April | 2175.49 | 0.00 | 0.00 |
May | 336.26 | 0.00 | 0.00 |
June | 18.28 | 0.00 | 0.00 |
July | 14.27 | 0.00 | 0.00 |
August | 105.58 | 0.00 | 0.00 |
September | 1101.86 | 0.00 | 0.00 |
October | 3856.55 | 0.00 | 0.00 |
November | 8018.85 | 0.00 | 0.00 |
December | 8827.75 | 0.00 | 0.00 |
Annual Sum or Average | 3741.20 | 0.00 | 0.00 |
Minimum of Months | 14.27 | 0.00 | 0.00 |
Maximum of Months | 8827.75 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10289.92 | 0.00 | 0.00 |
February | 8842.30 | 0.00 | 0.00 |
March | 6229.30 | 0.00 | 0.00 |
April | 2574.33 | 0.00 | 0.00 |
May | 383.27 | 0.00 | 0.00 |
June | 24.58 | 0.00 | 0.00 |
July | 19.67 | 0.00 | 0.00 |
August | 121.67 | 0.00 | 0.00 |
September | 1401.35 | 0.00 | 0.00 |
October | 4848.34 | 0.00 | 0.00 |
November | 9996.65 | 0.00 | 0.00 |
December | 10979.24 | 0.00 | 0.00 |
Annual Sum or Average | 4620.56 | 0.00 | 0.00 |
Minimum of Months | 19.67 | 0.00 | 0.00 |
Maximum of Months | 10979.24 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10430.28 | 0.00 | 0.00 |
February | 9450.73 | 0.00 | 0.00 |
March | 7306.01 | 0.00 | 0.00 |
April | 3254.94 | 0.00 | 0.00 |
May | 580.83 | 0.00 | 0.00 |
June | 29.02 | 0.00 | 0.00 |
July | 21.67 | 0.00 | 0.00 |
August | 240.45 | 0.00 | 0.00 |
September | 1927.37 | 0.00 | 0.00 |
October | 5422.48 | 0.00 | 0.00 |
November | 10216.94 | 0.00 | 0.00 |
December | 10971.95 | 0.00 | 0.00 |
Annual Sum or Average | 4963.43 | 0.00 | 0.00 |
Minimum of Months | 21.67 | 0.00 | 0.00 |
Maximum of Months | 10971.95 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 8457.39 | 0.00 | 0.00 |
February | 7709.91 | 0.00 | 0.00 |
March | 6068.49 | 0.00 | 0.00 |
April | 2895.73 | 0.00 | 0.00 |
May | 397.80 | 0.00 | 0.00 |
June | 14.56 | 0.00 | 0.00 |
July | 13.22 | 0.00 | 0.00 |
August | 168.50 | 0.00 | 0.00 |
September | 1481.36 | 0.00 | 0.00 |
October | 4319.95 | 0.00 | 0.00 |
November | 8331.99 | 0.00 | 0.00 |
December | 8908.04 | 0.00 | 0.00 |
Annual Sum or Average | 4043.62 | 0.00 | 0.00 |
Minimum of Months | 13.22 | 0.00 | 0.00 |
Maximum of Months | 8908.04 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 10503.13 | 0.00 | 0.00 |
February | 9410.11 | 0.00 | 0.00 |
March | 7040.40 | 0.00 | 0.00 |
April | 3192.01 | 0.00 | 0.00 |
May | 415.94 | 0.00 | 0.00 |
June | 23.93 | 0.00 | 0.00 |
July | 19.85 | 0.00 | 0.00 |
August | 150.33 | 0.00 | 0.00 |
September | 1729.08 | 0.00 | 0.00 |
October | 5303.55 | 0.00 | 0.00 |
November | 10322.07 | 0.00 | 0.00 |
December | 11077.49 | 0.00 | 0.00 |
Annual Sum or Average | 4907.74 | 0.00 | 0.00 |
Minimum of Months | 19.85 | 0.00 | 0.00 |
Maximum of Months | 11077.49 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 20170.78 | 0.00 | 0.00 |
February | 19207.82 | 0.00 | 0.00 |
March | 17318.27 | 0.00 | 0.00 |
April | 13358.13 | 0.00 | 0.00 |
May | 4424.46 | 0.00 | 0.00 |
June | 1398.23 | 0.00 | 0.00 |
July | 1010.15 | 0.00 | 0.00 |
August | 1488.02 | 0.00 | 0.00 |
September | 4066.79 | 0.00 | 0.00 |
October | 7291.29 | 0.00 | 0.00 |
November | 16791.96 | 0.00 | 0.00 |
December | 19867.74 | 0.00 | 0.00 |
Annual Sum or Average | 10479.35 | 0.00 | 0.00 |
Minimum of Months | 1010.15 | 0.00 | 0.00 |
Maximum of Months | 20170.78 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.13 |
August | 0.00 | 0.00 | 0.08 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.13 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.09 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.09 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.09 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.09 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.12 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.12 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.10 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.08 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.11 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.11 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.16 |
August | 0.00 | 0.00 | 0.08 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.12 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.12 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.86 | 1065.31 |
April | 0.00 | 0.00 | 1435.38 | 1034.20 |
May | 0.00 | 0.00 | 1415.09 | 1053.57 |
June | 0.00 | 0.00 | 1344.73 | 968.89 |
July | 0.00 | 0.00 | 1282.68 | 954.99 |
August | 0.00 | 0.00 | 1237.97 | 921.70 |
September | 0.00 | 0.00 | 1236.07 | 890.60 |
October | 0.00 | 0.00 | 1269.28 | 945.01 |
November | 0.00 | 0.00 | 1330.25 | 958.46 |
December | 0.00 | 0.00 | 1405.01 | 1046.07 |
Annual Sum or Average | 0.00 | 0.00 | 1354.12 | 11870.49 |
Minimum of Months | 0.00 | 0.00 | 1236.07 | 890.60 |
Maximum of Months | 0.00 | 0.00 | 1435.38 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.89 | 1065.33 |
April | 0.00 | 0.00 | 1435.57 | 1034.34 |
May | 0.00 | 0.00 | 1415.28 | 1053.71 |
June | 0.00 | 0.00 | 1344.58 | 968.79 |
July | 0.00 | 0.00 | 1282.66 | 954.97 |
August | 0.00 | 0.00 | 1235.84 | 920.12 |
September | 0.00 | 0.00 | 1236.41 | 890.84 |
October | 0.00 | 0.00 | 1271.03 | 946.32 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1354.18 | 11871.00 |
Minimum of Months | 0.00 | 0.00 | 1235.84 | 890.84 |
Maximum of Months | 0.00 | 0.00 | 1435.57 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.86 | 1065.31 |
April | 0.00 | 0.00 | 1435.50 | 1034.29 |
May | 0.00 | 0.00 | 1415.19 | 1053.64 |
June | 0.00 | 0.00 | 1342.93 | 967.59 |
July | 0.00 | 0.00 | 1282.52 | 954.87 |
August | 0.00 | 0.00 | 1236.06 | 920.28 |
September | 0.00 | 0.00 | 1235.74 | 890.36 |
October | 0.00 | 0.00 | 1271.04 | 946.33 |
November | 0.00 | 0.00 | 1328.53 | 957.22 |
December | 0.00 | 0.00 | 1406.99 | 1047.54 |
Annual Sum or Average | 0.00 | 0.00 | 1353.96 | 11869.12 |
Minimum of Months | 0.00 | 0.00 | 1235.74 | 890.36 |
Maximum of Months | 0.00 | 0.00 | 1435.50 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1436.51 | 1035.02 |
May | 0.00 | 0.00 | 1415.82 | 1054.12 |
June | 0.00 | 0.00 | 1344.48 | 968.71 |
July | 0.00 | 0.00 | 1282.70 | 955.01 |
August | 0.00 | 0.00 | 1238.26 | 921.92 |
September | 0.00 | 0.00 | 1235.63 | 890.29 |
October | 0.00 | 0.00 | 1271.04 | 946.33 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1354.43 | 11873.25 |
Minimum of Months | 0.00 | 0.00 | 1235.63 | 890.29 |
Maximum of Months | 0.00 | 0.00 | 1436.51 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1437.68 | 1035.86 |
May | 0.00 | 0.00 | 1415.37 | 1053.78 |
June | 0.00 | 0.00 | 1344.63 | 968.82 |
July | 0.00 | 0.00 | 1282.57 | 954.91 |
August | 0.00 | 0.00 | 1238.13 | 921.83 |
September | 0.00 | 0.00 | 1235.89 | 890.47 |
October | 0.00 | 0.00 | 1271.09 | 946.36 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1354.51 | 11873.90 |
Minimum of Months | 0.00 | 0.00 | 1235.89 | 890.47 |
Maximum of Months | 0.00 | 0.00 | 1437.68 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1437.54 | 1035.76 |
May | 0.00 | 0.00 | 1413.02 | 1052.04 |
June | 0.00 | 0.00 | 1344.69 | 968.86 |
July | 0.00 | 0.00 | 1282.47 | 954.83 |
August | 0.00 | 0.00 | 1235.79 | 920.08 |
September | 0.00 | 0.00 | 1239.21 | 892.86 |
October | 0.00 | 0.00 | 1269.20 | 944.95 |
November | 0.00 | 0.00 | 1328.71 | 957.35 |
December | 0.00 | 0.00 | 1407.04 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1354.21 | 11871.29 |
Minimum of Months | 0.00 | 0.00 | 1235.79 | 892.86 |
Maximum of Months | 0.00 | 0.00 | 1437.54 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.35 | 1034.18 |
May | 0.00 | 0.00 | 1413.09 | 1052.08 |
June | 0.00 | 0.00 | 1344.24 | 968.54 |
July | 0.00 | 0.00 | 1282.12 | 954.58 |
August | 0.00 | 0.00 | 1235.08 | 919.55 |
September | 0.00 | 0.00 | 1235.80 | 890.41 |
October | 0.00 | 0.00 | 1269.17 | 944.93 |
November | 0.00 | 0.00 | 1330.88 | 958.91 |
December | 0.00 | 0.00 | 1404.80 | 1045.92 |
Annual Sum or Average | 0.00 | 0.00 | 1353.61 | 11866.06 |
Minimum of Months | 0.00 | 0.00 | 1235.08 | 890.41 |
Maximum of Months | 0.00 | 0.00 | 1435.35 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.68 | 964.12 |
March | 0.00 | 0.00 | 1430.93 | 1065.37 |
April | 0.00 | 0.00 | 1435.32 | 1034.16 |
May | 0.00 | 0.00 | 1413.27 | 1052.22 |
June | 0.00 | 0.00 | 1345.10 | 969.16 |
July | 0.00 | 0.00 | 1280.03 | 953.02 |
August | 0.00 | 0.00 | 1235.66 | 919.98 |
September | 0.00 | 0.00 | 1234.21 | 889.26 |
October | 0.00 | 0.00 | 1271.06 | 946.34 |
November | 0.00 | 0.00 | 1328.59 | 957.26 |
December | 0.00 | 0.00 | 1407.00 | 1047.55 |
Annual Sum or Average | 0.00 | 0.00 | 1353.61 | 11866.00 |
Minimum of Months | 0.00 | 0.00 | 1234.21 | 889.26 |
Maximum of Months | 0.00 | 0.00 | 1435.32 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.37 | 1034.20 |
May | 0.00 | 0.00 | 1412.65 | 1051.76 |
June | 0.00 | 0.00 | 1343.04 | 967.68 |
July | 0.00 | 0.00 | 1281.95 | 954.44 |
August | 0.00 | 0.00 | 1235.39 | 919.78 |
September | 0.00 | 0.00 | 1234.17 | 889.23 |
October | 0.00 | 0.00 | 1269.44 | 945.13 |
November | 0.00 | 0.00 | 1330.96 | 958.97 |
December | 0.00 | 0.00 | 1404.72 | 1045.85 |
Annual Sum or Average | 0.00 | 0.00 | 1353.38 | 11864.02 |
Minimum of Months | 0.00 | 0.00 | 1234.17 | 889.23 |
Maximum of Months | 0.00 | 0.00 | 1435.37 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.45 | 1034.26 |
May | 0.00 | 0.00 | 1415.36 | 1053.77 |
June | 0.00 | 0.00 | 1345.08 | 969.14 |
July | 0.00 | 0.00 | 1280.16 | 953.12 |
August | 0.00 | 0.00 | 1235.70 | 920.01 |
September | 0.00 | 0.00 | 1236.24 | 890.72 |
October | 0.00 | 0.00 | 1271.07 | 946.35 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.98 | 11869.24 |
Minimum of Months | 0.00 | 0.00 | 1235.70 | 890.72 |
Maximum of Months | 0.00 | 0.00 | 1435.45 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.85 | 1065.31 |
April | 0.00 | 0.00 | 1437.61 | 1035.81 |
May | 0.00 | 0.00 | 1413.10 | 1052.09 |
June | 0.00 | 0.00 | 1344.92 | 969.03 |
July | 0.00 | 0.00 | 1280.08 | 953.05 |
August | 0.00 | 0.00 | 1235.80 | 920.09 |
September | 0.00 | 0.00 | 1236.63 | 891.00 |
October | 0.00 | 0.00 | 1271.16 | 946.41 |
November | 0.00 | 0.00 | 1328.68 | 957.33 |
December | 0.00 | 0.00 | 1407.04 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.99 | 11869.38 |
Minimum of Months | 0.00 | 0.00 | 1235.80 | 891.00 |
Maximum of Months | 0.00 | 0.00 | 1437.61 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.55 | 1034.33 |
May | 0.00 | 0.00 | 1415.09 | 1053.57 |
June | 0.00 | 0.00 | 1342.13 | 967.02 |
July | 0.00 | 0.00 | 1281.94 | 954.44 |
August | 0.00 | 0.00 | 1234.62 | 919.21 |
September | 0.00 | 0.00 | 1236.15 | 890.66 |
October | 0.00 | 0.00 | 1271.08 | 946.35 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.77 | 11867.45 |
Minimum of Months | 0.00 | 0.00 | 1234.62 | 890.66 |
Maximum of Months | 0.00 | 0.00 | 1435.55 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.36 | 1034.19 |
May | 0.00 | 0.00 | 1414.85 | 1053.39 |
June | 0.00 | 0.00 | 1345.20 | 969.23 |
July | 0.00 | 0.00 | 1279.86 | 952.89 |
August | 0.00 | 0.00 | 1236.05 | 920.28 |
September | 0.00 | 0.00 | 1236.18 | 890.68 |
October | 0.00 | 0.00 | 1271.00 | 946.29 |
November | 0.00 | 0.00 | 1328.66 | 957.31 |
December | 0.00 | 0.00 | 1407.03 | 1047.57 |
Annual Sum or Average | 0.00 | 0.00 | 1353.93 | 11868.82 |
Minimum of Months | 0.00 | 0.00 | 1236.05 | 890.68 |
Maximum of Months | 0.00 | 0.00 | 1435.36 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.10 |
March | 0.00 | 0.00 | 1430.85 | 1065.31 |
April | 0.00 | 0.00 | 1435.57 | 1034.34 |
May | 0.00 | 0.00 | 1415.21 | 1053.66 |
June | 0.00 | 0.00 | 1342.70 | 967.43 |
July | 0.00 | 0.00 | 1282.24 | 954.67 |
August | 0.00 | 0.00 | 1235.08 | 919.55 |
September | 0.00 | 0.00 | 1235.91 | 890.49 |
October | 0.00 | 0.00 | 1269.08 | 944.86 |
November | 0.00 | 0.00 | 1331.18 | 959.13 |
December | 0.00 | 0.00 | 1404.76 | 1045.88 |
Annual Sum or Average | 0.00 | 0.00 | 1353.72 | 11866.99 |
Minimum of Months | 0.00 | 0.00 | 1235.08 | 890.49 |
Maximum of Months | 0.00 | 0.00 | 1435.57 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.84 | 1065.30 |
April | 0.00 | 0.00 | 1435.39 | 1034.21 |
May | 0.00 | 0.00 | 1412.91 | 1051.95 |
June | 0.00 | 0.00 | 1344.34 | 968.61 |
July | 0.00 | 0.00 | 1281.87 | 954.39 |
August | 0.00 | 0.00 | 1235.17 | 919.62 |
September | 0.00 | 0.00 | 1236.32 | 890.78 |
October | 0.00 | 0.00 | 1269.22 | 944.97 |
November | 0.00 | 0.00 | 1330.25 | 958.46 |
December | 0.00 | 0.00 | 1405.07 | 1046.11 |
Annual Sum or Average | 0.00 | 0.00 | 1353.61 | 11866.07 |
Minimum of Months | 0.00 | 0.00 | 1235.17 | 890.78 |
Maximum of Months | 0.00 | 0.00 | 1435.39 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1435.14 | 1034.04 |
May | 0.00 | 0.00 | 1415.41 | 1053.81 |
June | 0.00 | 0.00 | 1344.50 | 968.73 |
July | 0.00 | 0.00 | 1282.32 | 954.72 |
August | 0.00 | 0.00 | 1235.72 | 920.03 |
September | 0.00 | 0.00 | 1236.65 | 891.02 |
October | 0.00 | 0.00 | 1271.05 | 946.33 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1354.12 | 11870.53 |
Minimum of Months | 0.00 | 0.00 | 1235.72 | 891.02 |
Maximum of Months | 0.00 | 0.00 | 1435.14 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1437.59 | 1035.80 |
May | 0.00 | 0.00 | 1415.23 | 1053.67 |
June | 0.00 | 0.00 | 1342.53 | 967.31 |
July | 0.00 | 0.00 | 1282.25 | 954.67 |
August | 0.00 | 0.00 | 1235.54 | 919.90 |
September | 0.00 | 0.00 | 1237.08 | 891.33 |
October | 0.00 | 0.00 | 1270.84 | 946.18 |
November | 0.00 | 0.00 | 1328.69 | 957.33 |
December | 0.00 | 0.00 | 1407.04 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1354.15 | 11870.73 |
Minimum of Months | 0.00 | 0.00 | 1235.54 | 891.33 |
Maximum of Months | 0.00 | 0.00 | 1437.59 | 1067.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1433.90 | 1067.58 |
February | 0.00 | 0.00 | 1433.65 | 964.09 |
March | 0.00 | 0.00 | 1430.83 | 1065.29 |
April | 0.00 | 0.00 | 1436.87 | 1035.28 |
May | 0.00 | 0.00 | 1413.32 | 1052.25 |
June | 0.00 | 0.00 | 1345.05 | 969.12 |
July | 0.00 | 0.00 | 1279.89 | 952.92 |
August | 0.00 | 0.00 | 1235.81 | 920.09 |
September | 0.00 | 0.00 | 1236.55 | 890.94 |
October | 0.00 | 0.00 | 1271.04 | 946.33 |
November | 0.00 | 0.00 | 1328.67 | 957.32 |
December | 0.00 | 0.00 | 1407.03 | 1047.58 |
Annual Sum or Average | 0.00 | 0.00 | 1353.92 | 11868.79 |
Minimum of Months | 0.00 | 0.00 | 1235.81 | 890.94 |
Maximum of Months | 0.00 | 0.00 | 1436.87 | 1067.58 |
Report: HEATING AND COOLING LOADS
For: HEATEDBSMT
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 12868.02 |
February | 0.00 | 11087.28 |
March | 0.00 | 11162.41 |
April | 0.00 | 8562.70 |
May | 0.00 | 2665.04 |
June | 1.95 | 699.27 |
July | 4.25 | 505.85 |
August | 4.90 | 712.13 |
September | 0.39 | 2075.50 |
October | 0.00 | 3972.41 |
November | 0.00 | 9957.20 |
December | 0.00 | 12532.67 |
Annual Sum or Average | 11.49 | 76800.49 |
Minimum of Months | 0.00 | 505.85 |
Maximum of Months | 4.90 | 12868.02 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4279.36 |
February | 0.00 | 3206.76 |
March | 7.54 | 2433.02 |
April | 43.42 | 944.24 |
May | 74.09 | 181.84 |
June | 109.49 | 20.31 |
July | 112.95 | 13.89 |
August | 89.52 | 66.82 |
September | 35.86 | 422.91 |
October | 5.40 | 1676.06 |
November | 0.00 | 3857.85 |
December | 0.00 | 4581.49 |
Annual Sum or Average | 478.27 | 21684.55 |
Minimum of Months | 0.00 | 13.89 |
Maximum of Months | 112.95 | 4581.49 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2804.43 |
February | 0.29 | 2038.60 |
March | 9.67 | 1531.88 |
April | 32.91 | 583.60 |
May | 60.46 | 109.29 |
June | 77.62 | 8.25 |
July | 85.73 | 4.95 |
August | 74.80 | 27.14 |
September | 42.35 | 228.05 |
October | 11.33 | 955.38 |
November | 0.00 | 2491.49 |
December | 0.00 | 3035.44 |
Annual Sum or Average | 395.17 | 13818.51 |
Minimum of Months | 0.00 | 4.95 |
Maximum of Months | 85.73 | 3035.44 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4258.11 |
February | 0.00 | 3126.31 |
March | 8.84 | 2232.69 |
April | 37.85 | 882.10 |
May | 89.97 | 143.10 |
June | 116.90 | 13.11 |
July | 129.52 | 9.58 |
August | 98.20 | 45.21 |
September | 38.84 | 363.50 |
October | 7.31 | 1590.00 |
November | 0.00 | 3858.35 |
December | 0.00 | 4578.73 |
Annual Sum or Average | 527.42 | 21100.81 |
Minimum of Months | 0.00 | 9.58 |
Maximum of Months | 129.52 | 4578.73 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4401.96 |
February | 0.00 | 3546.77 |
March | 0.15 | 2905.20 |
April | 19.66 | 1187.11 |
May | 50.75 | 189.96 |
June | 90.85 | 14.70 |
July | 90.29 | 10.79 |
August | 61.94 | 82.74 |
September | 19.35 | 531.66 |
October | 0.99 | 1923.19 |
November | 0.00 | 4050.56 |
December | 0.00 | 4620.06 |
Annual Sum or Average | 333.98 | 23464.69 |
Minimum of Months | 0.00 | 10.79 |
Maximum of Months | 90.85 | 4620.06 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 2923.48 |
February | 0.00 | 2367.77 |
March | 0.00 | 1972.25 |
April | 9.06 | 830.53 |
May | 41.20 | 110.27 |
June | 59.41 | 6.47 |
July | 63.51 | 4.13 |
August | 49.03 | 39.72 |
September | 25.61 | 313.31 |
October | 4.58 | 1164.78 |
November | 0.00 | 2680.48 |
December | 0.00 | 3072.06 |
Annual Sum or Average | 252.39 | 15485.26 |
Minimum of Months | 0.00 | 4.13 |
Maximum of Months | 63.51 | 3072.06 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 4376.83 |
February | 0.00 | 3459.94 |
March | 0.69 | 2683.76 |
April | 15.70 | 1117.55 |
May | 63.47 | 154.20 |
June | 97.30 | 12.62 |
July | 106.51 | 9.43 |
August | 68.51 | 55.69 |
September | 23.53 | 454.69 |
October | 1.81 | 1818.33 |
November | 0.00 | 4049.40 |
December | 0.00 | 4614.26 |
Annual Sum or Average | 377.53 | 22806.69 |
Minimum of Months | 0.00 | 9.43 |
Maximum of Months | 106.51 | 4614.26 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3373.53 |
February | 0.56 | 2403.95 |
March | 15.87 | 1689.56 |
April | 71.97 | 542.06 |
May | 113.80 | 75.96 |
June | 153.41 | 2.32 |
July | 154.91 | 2.47 |
August | 124.39 | 25.88 |
September | 53.00 | 261.61 |
October | 10.30 | 1262.25 |
November | 0.00 | 3047.58 |
December | 0.00 | 3678.93 |
Annual Sum or Average | 698.22 | 16366.10 |
Minimum of Months | 0.00 | 2.32 |
Maximum of Months | 154.91 | 3678.93 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 1791.91 |
February | 4.77 | 1197.84 |
March | 26.43 | 813.68 |
April | 63.91 | 259.24 |
May | 94.81 | 30.81 |
June | 117.03 | 0.38 |
July | 125.40 | 0.26 |
August | 108.49 | 10.97 |
September | 64.36 | 123.95 |
October | 23.83 | 556.27 |
November | 0.11 | 1584.23 |
December | 0.00 | 2020.19 |
Annual Sum or Average | 629.13 | 8389.73 |
Minimum of Months | 0.00 | 0.26 |
Maximum of Months | 125.40 | 2020.19 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3350.04 |
February | 0.68 | 2314.10 |
March | 22.04 | 1507.47 |
April | 66.85 | 497.02 |
May | 138.52 | 47.15 |
June | 169.99 | 1.29 |
July | 180.52 | 1.43 |
August | 139.23 | 14.96 |
September | 59.67 | 223.81 |
October | 13.99 | 1181.16 |
November | 0.00 | 3048.55 |
December | 0.00 | 3675.83 |
Annual Sum or Average | 791.47 | 15862.81 |
Minimum of Months | 0.00 | 1.29 |
Maximum of Months | 180.52 | 3675.83 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3509.37 |
February | 0.00 | 2776.61 |
March | 2.56 | 2159.18 |
April | 34.40 | 728.39 |
May | 80.63 | 75.55 |
June | 132.15 | 1.71 |
July | 129.91 | 1.85 |
August | 88.26 | 36.74 |
September | 29.31 | 364.68 |
October | 3.31 | 1519.60 |
November | 0.00 | 3263.14 |
December | 0.00 | 3721.46 |
Annual Sum or Average | 500.53 | 18158.28 |
Minimum of Months | 0.00 | 1.71 |
Maximum of Months | 132.15 | 3721.46 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 1923.59 |
February | 0.19 | 1516.21 |
March | 2.62 | 1174.63 |
April | 26.72 | 414.21 |
May | 64.72 | 36.73 |
June | 96.07 | 0.36 |
July | 100.21 | 0.15 |
August | 72.24 | 14.69 |
September | 40.92 | 200.93 |
October | 10.59 | 739.12 |
November | 0.00 | 1794.33 |
December | 0.00 | 2060.69 |
Annual Sum or Average | 414.28 | 9875.63 |
Minimum of Months | 0.00 | 0.15 |
Maximum of Months | 100.21 | 2060.69 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3482.00 |
February | 0.00 | 2680.06 |
March | 3.41 | 1911.73 |
April | 29.77 | 681.01 |
May | 102.19 | 57.98 |
June | 149.19 | 1.45 |
July | 154.86 | 1.36 |
August | 101.29 | 21.18 |
September | 33.84 | 295.76 |
October | 4.68 | 1404.44 |
November | 0.00 | 3262.33 |
December | 0.00 | 3715.21 |
Annual Sum or Average | 579.23 | 17514.50 |
Minimum of Months | 0.00 | 1.36 |
Maximum of Months | 154.86 | 3715.21 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5480.46 |
February | 0.00 | 4325.72 |
March | 0.26 | 3315.02 |
April | 17.69 | 1254.89 |
May | 86.69 | 119.33 |
June | 147.98 | 8.36 |
July | 156.64 | 5.90 |
August | 96.85 | 45.47 |
September | 20.79 | 583.18 |
October | 0.78 | 2459.17 |
November | 0.00 | 5169.36 |
December | 0.00 | 5813.94 |
Annual Sum or Average | 527.68 | 28580.80 |
Minimum of Months | 0.00 | 5.90 |
Maximum of Months | 156.64 | 5813.94 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5352.16 |
February | 0.00 | 3961.26 |
March | 5.46 | 2779.38 |
April | 43.56 | 984.52 |
May | 115.74 | 106.93 |
June | 163.96 | 8.54 |
July | 177.09 | 5.82 |
August | 127.70 | 35.18 |
September | 40.06 | 461.45 |
October | 4.82 | 2175.58 |
November | 0.00 | 4961.45 |
December | 0.00 | 5775.59 |
Annual Sum or Average | 678.41 | 26607.85 |
Minimum of Months | 0.00 | 5.82 |
Maximum of Months | 177.09 | 5775.59 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5375.78 |
February | 0.00 | 4053.44 |
March | 4.94 | 3031.54 |
April | 50.74 | 1066.13 |
May | 95.22 | 157.84 |
June | 150.04 | 10.17 |
July | 153.77 | 8.45 |
August | 114.94 | 57.88 |
September | 36.28 | 545.52 |
October | 3.32 | 2286.17 |
November | 0.00 | 4960.62 |
December | 0.00 | 5779.05 |
Annual Sum or Average | 609.24 | 27332.57 |
Minimum of Months | 0.00 | 8.45 |
Maximum of Months | 153.77 | 5779.05 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3902.28 |
February | 0.00 | 3139.69 |
March | 0.11 | 2558.95 |
April | 13.59 | 987.72 |
May | 55.83 | 102.60 |
June | 98.37 | 4.27 |
July | 104.43 | 2.84 |
August | 70.29 | 45.65 |
September | 23.42 | 433.44 |
October | 2.86 | 1724.95 |
November | 0.00 | 3683.41 |
December | 0.00 | 4140.45 |
Annual Sum or Average | 368.89 | 20726.24 |
Minimum of Months | 0.00 | 2.84 |
Maximum of Months | 104.43 | 4140.45 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 3770.95 |
February | 0.31 | 2769.79 |
March | 4.33 | 1999.04 |
April | 37.88 | 684.91 |
May | 78.91 | 90.73 |
June | 114.34 | 5.08 |
July | 124.46 | 3.35 |
August | 99.62 | 26.70 |
September | 41.13 | 298.67 |
October | 7.76 | 1439.97 |
November | 0.00 | 3471.56 |
December | 0.00 | 4100.51 |
Annual Sum or Average | 508.75 | 18661.26 |
Minimum of Months | 0.00 | 3.35 |
Maximum of Months | 124.46 | 4100.51 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2021-05-12 10:53:30
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 5506.93 |
February | 0.00 | 4420.80 |
March | 0.10 | 3573.01 |
April | 24.64 | 1349.84 |
May | 68.74 | 165.98 |
June | 134.09 | 10.48 |
July | 133.79 | 6.59 |
August | 85.23 | 77.52 |
September | 17.75 | 695.43 |
October | 0.55 | 2589.75 |
November | 0.00 | 5169.53 |
December | 0.00 | 5819.74 |
Annual Sum or Average | 464.88 | 29385.60 |
Minimum of Months | 0.00 | 6.59 |
Maximum of Months | 134.09 | 5819.74 |