Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2022.08.16 14:22

Tabular Output Report in Format: HTML

Building: SW_Atlanta_HUD.Mfr-Levy_electricfurnace

Environment: ANNUAL ** Atlanta Hartsfield Intl Ap GA USA TMY3 WMO#=722190

Simulation Timestamp: 2022-08-16 14:22:49


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 54955.99 19.82 59.45
Net Site Energy 54955.99 19.82 59.45
Total Source Energy 174045.62 62.76 188.27
Net Source Energy 174045.62 62.76 188.27


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 2773.28
Net Conditioned Building Area 924.43
Unconditioned Building Area 1848.85


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 18283.33 0.00 0.00 0.00 0.00 0.00
Cooling 8064.01 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2843.96 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 593.73 0.00 0.00 0.00 0.00 0.00
Interior Equipment 13158.72 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3315.66 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 8696.56 0.00 0.00 0.00 0.00 23315.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 54955.99 0.00 0.00 0.00 0.00 88.26
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 18283.33 0.00 0.00 0.00 0.00 0.00
Cooling General 8064.01 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 2843.96 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 457.46 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 136.27 0.00 0.00 0.00 0.00 0.00
Interior Equipment IntGains 13158.72 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 3315.66 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 8696.56 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 23315.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 3.72 0.00 0.00 0.00 0.00 0.00
HVAC 41.50 0.00 0.00 0.00 0.00 25.22
Other 14.23 0.00 0.00 0.00 0.00 0.00
Total 59.45 0.00 0.00 0.00 0.00 0.10


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.24 0.00 0.00 0.00 0.00 0.00
HVAC 13.83 0.00 0.00 0.00 0.00 8.41
Other 4.74 0.00 0.00 0.00 0.00 0.00
Total 19.82 0.00 0.00 0.00 0.00 0.03


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 54955.99 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 54955.99 100.00
     
Total On-Site and Utility Electric Sources 54955.99 100.00
Total Electricity End Uses 54955.99 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 23315.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 23315.79 100.00
Total Water End Uses 23315.79 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 5.00
Time Setpoint Not Met During Occupied Cooling 12.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 2310.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1 |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1 | DX COOLING COIL_UNIT1 |

WATER HEATER: LOADS

| WATER HEATER_UNIT1 |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2022.08.16 14:22
RunPeriod ANNUAL
Weather File Atlanta Hartsfield Intl Ap GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [ft] 1010.55
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 1294.30 528.04 119.11 528.04 119.11
Window Opening Area [ft2] 110.93 27.73 27.73 27.73 27.73
Window-Wall Ratio [%] 8.57 5.25 23.28 5.25 23.28


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 1200.29 495.04 105.10 495.04 105.10
Window Opening Area [ft2] 110.93 27.73 27.73 27.73 27.73
Window-Wall Ratio [%] 9.24 5.60 26.39 5.60 26.39


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 933.78
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Gross Wall Area [ft2] Window Glass Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
LIVING_UNIT1 924.43 Yes Yes 6935.31 1.00 1200.29 110.93 1.0781 462.21 2.4037
ATTIC_UNIT1 924.43 No Yes 461.69 1.00 13.99 0.00 0.0000   0.0000
CRAWLSPACE_UNIT1 924.43 No Yes 1849.42 1.00 80.02 0.00 0.0000   0.0000
Total 2773.28     9246.42   1294.30 110.93 0.3594 1386.64 0.8012
Conditioned Total 924.43     6935.31   1200.29 110.93 1.0781 462.21 2.4037
Unconditioned Total 1848.85     2311.11   94.01 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 12-FEB-07:15 - - - - 01-JAN-08:30
Heating 20.92 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 0.39 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.02 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1.60 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1.28 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2.24 0.00 0.00 0.00 0.00 0.08
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 26.45 0.00 0.00 0.00 0.00 0.08


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 20.92 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 0.39 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.02 0.00 0.00 0.00 0.00 0.00
Interior Equipment IntGains 1.60 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 1.28 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 2.24 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.08
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 57903.31 0.00 0.00 0.00 0.00
Cooling 25538.73 0.00 0.00 0.00 0.00
Interior Lighting 9006.84 0.00 0.00 0.00 0.00
Exterior Lighting 1880.35 0.00 0.00 0.00 0.00
Interior Equipment 41673.67 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 10500.71 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 27542.01 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 174045.62 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 62.64 0.00 0.00 0.00 0.00
Cooling 27.63 0.00 0.00 0.00 0.00
Interior Lighting 9.74 0.00 0.00 0.00 0.00
Exterior Lighting 2.03 0.00 0.00 0.00 0.00
Interior Equipment 45.08 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 11.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 29.79 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 188.27 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 62.64 0.00 0.00 0.00 0.00
Cooling 27.63 0.00 0.00 0.00 0.00
Interior Lighting 9.74 0.00 0.00 0.00 0.00
Exterior Lighting 2.03 0.00 0.00 0.00 0.00
Interior Equipment 45.08 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 11.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 29.79 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 188.27 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
ATLANTA HARTSFIELD INTL AP ANN HTG 99.6% CONDNS DB 20.66 0.00 20.66 Wetbulb [F] 1043.36 320.00
ATLANTA HARTSFIELD INTL AP ANN CLG .4% CONDNS DB=>MWB 93.92 17.10 74.30 Wetbulb [F] 787.44 300.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
WALL_LDF_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 495.04 180.00 90.00 S
WALL_SDR_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 105.10 90.00 90.00 E
WALL_LDB_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 495.04 0.00 90.00 N
WALL_SDL_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 105.10 270.00 90.00 W
ROOF_RIGHT_UNIT1 GABLE_END 0.30 0.314 0.428 7.00 90.00 90.00 E
ROOF_LEFT_UNIT1 GABLE_END 0.30 0.314 0.428 7.00 270.00 90.00 W
ROOF_FRONT_UNIT1 EXTERIOR ROOF 0.25 0.469 0.943 466.89 180.00 8.12  
ROOF_BACK_UNIT1 EXTERIOR ROOF 0.25 0.469 0.943 466.89 0.00 8.12  
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 33.00 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 7.01 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 33.00 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 7.01 270.00 90.00 W


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 1.026 0.700 0.881     Yes WALL_LDF_1.UNIT1 180.00 90.00 S
WINDOW_SDR_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 1.026 0.700 0.881     Yes WALL_SDR_1.UNIT1 90.00 90.00 E
WINDOW_LDB_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 1.026 0.700 0.881     Yes WALL_LDB_1.UNIT1 0.00 90.00 N
WINDOW_SDL_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 1.026 0.700 0.881     Yes WALL_SDL_1.UNIT1 270.00 90.00 W
Total or Average           110.93 1.026 0.700 0.881              
North Total or Average           27.73 1.026 0.700 0.881              
Non-North Total or Average           83.20 1.026 0.700 0.881              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDF_UNIT1 EXTERIOR DOOR 0.400 0.400 18.01 WALL_LDF_1.UNIT1
DOOR_LDB_UNIT1 EXTERIOR DOOR 0.400 0.400 18.01 WALL_LDB_1.UNIT1



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_1.UNIT1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_1.UNIT1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_1.UNIT1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_1.UNIT1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1 LIVING_UNIT1 0.8625 924.43 797.30 General INTERIORLIGHTING 54.69 168.00 54.69 0.0000 Y 666.34
LIVING PLUG-IN LIGHTING1 LIVING_UNIT1 0.2156 924.43 199.33 General INTERIORLIGHTING 54.69 168.00 54.69 0.0000 Y 166.59
Interior Lighting Total   0.5391 1848.85 996.63               832.93


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1 30.59 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 133.98
GARAGE-LIGHTS_UNIT1 14.00 Schedule INTERIORLIGHTING 54.69 168.00 54.69 39.91
Exterior Lighting Total 44.58           173.89



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed   22386.92 16965.38 5421.54 0.76 4.22    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed 1.8 3.44 11.74 12.44 12.01
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1 Coil:Heating:Electric   20909.95 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1 Fan:OnOff 0.38 0.06 746.50 373.84 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1 Pump:VariableSpeed Intermittent 0.00 7.8159 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1 WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Zone Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak Temperature at Peak [F] Humidity Ratio at Peak [lbWater/lbAir]
LIVING_UNIT1 16904.24 16904.24 746.496 746.496 ATLANTA HARTSFIELD INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 91.87 0.01443


Zone Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak Temperature at Peak [F] Humidity Ratio at Peak [lbWater/lbAir]
LIVING_UNIT1 18500.03 18500.03 349.112 349.112 ATLANTA HARTSFIELD INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:00:00 20.66 0.00230


System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1 746.50 746.50 349.11 349.11



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1 5027.25 5399.00 2310.00
ATTIC_UNIT1 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00
Facility 5027.25 5399.00 2310.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1 5.00 12.75 5.00 12.75
ATTIC_UNIT1 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00
Facility 5.00 12.75 5.00 12.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1 1.38 2.00 6935.31 0.000 0.488 0.000 0.443
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1 1.38 2.00 6935.31 0.000 0.001 0.000 0.007
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Surfaces by Class

Total Outdoors
Wall 14 10
Floor 3 0
Roof 4 2
Internal Mass 1 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 4 4
Door 2 2
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 1
Conditioned Zones 1
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 317
Defaulted Fields 43
Fields with Defaults 1098
Autosized Fields 25
Autosizable Fields 30
Autocalculated Fields 16
Autocalculatable Fields 40



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 16095.28 454.17 28-JUL-03:15 7746.33 12-FEB-07:15
Electricity:Building 4686.80 370.94 01-JAN-09:15 943.35 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1 4686.80 370.94 01-JAN-09:15 943.35 01-JAN-20:15
InteriorLights:Electricity 832.93 18.26 01-JAN-00:15 292.10 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1 832.93 18.26 01-JAN-00:15 292.10 01-JAN-20:15
General:InteriorLights:Electricity 832.93 18.26 01-JAN-00:15 292.10 01-JAN-20:15
InteriorEquipment:Electricity 3853.87 336.71 01-JAN-09:15 651.25 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1 3853.87 336.71 01-JAN-09:15 651.25 01-JAN-20:15
IntGains:InteriorEquipment:Electricity 3853.87 336.71 01-JAN-09:15 651.25 01-JAN-20:15
Electricity:Plant 2547.01 47.07 03-AUG-02:45 670.69 04-FEB-08:15
WaterSystems:Electricity 2547.01 47.07 03-AUG-02:45 670.69 04-FEB-08:15
Water Heater:WaterSystems:Electricity 2547.01 47.07 03-AUG-02:45 670.69 04-FEB-08:15
Fans:Electricity 971.08 0.00 10-JAN-14:15 373.84 01-AUG-17:00
Fans:Electricity:Zone:LIVING_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 16095.28 454.17 28-JUL-03:15 7746.33 12-FEB-07:15
ElectricityPurchased:Plant 16095.28 454.17 28-JUL-03:15 7746.33 12-FEB-07:15
Cogeneration:ElectricityPurchased 16095.28 454.17 28-JUL-03:15 7746.33 12-FEB-07:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 16095.28 454.17 28-JUL-03:15 7746.33 12-FEB-07:15
ElectricityNet:Plant 16095.28 454.17 28-JUL-03:15 7746.33 12-FEB-07:15
Cogeneration:ElectricityNet 16095.28 454.17 28-JUL-03:15 7746.33 12-FEB-07:15
ExteriorLights:Electricity 173.89 1.64 01-JAN-09:15 44.58 01-JAN-20:15
Exterior-Lights:ExteriorLights:Electricity 133.98 0.00 01-JAN-06:15 30.59 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 39.91 0.87 01-JAN-00:15 14.00 01-JAN-20:15
Electricity:HVAC 8687.58 0.00 10-JAN-14:15 6502.20 12-FEB-00:45
General:Fans:Electricity 971.08 0.00 10-JAN-14:15 373.84 01-AUG-17:00
Heating:Electricity 5354.74 0.00 10-JAN-14:15 6128.36 12-FEB-00:45
Cooling:Electricity 2361.75 0.00 01-JAN-00:15 1541.23 08-JUL-16:00
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum Gas Maximum Value [Btu/h] Timestamp of Maximum
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum Cooling Maximum Value [ton] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum Maximum Value [ft3/min] Timestamp of Maximum
Water:Facility 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30
Water:Plant 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30
WaterSystems:Water 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30
MainsWater:Plant 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30
WaterSystems:MainsWater 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30
Domestic Hot Water:WaterSystems:MainsWater 3117.32 0.00 02-JAN-02:15 0.01 01-JAN-08:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum Maximum Value [lb/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum Maximum Value [ft3/min] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum Maximum Value [gal] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum Maximum Value [Btu/h] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 7780.97 59.19 03-AUG-02:15 2179.45 04-FEB-08:15
PlantLoopHeatingDemand:Plant 7780.97 59.19 03-AUG-02:15 2179.45 04-FEB-08:15
WaterSystems:PlantLoopHeatingDemand 7780.97 59.19 03-AUG-02:15 2179.45 04-FEB-08:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 108805.45 62.28 30-JUL-02:15 45186.24 12-FEB-07:15
EnergyTransfer:Building 46863.48 0.00 10-JAN-14:15 22400.62 12-FEB-06:00
EnergyTransfer:Zone:LIVING_UNIT1 46863.48 0.00 10-JAN-14:15 22400.62 12-FEB-06:00
Heating:EnergyTransfer 19398.78 0.00 10-JAN-14:15 22400.62 12-FEB-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1 19398.78 0.00 10-JAN-14:15 22400.62 12-FEB-06:00
Cooling:EnergyTransfer 27464.70 0.00 01-JAN-00:15 17579.12 18-AUG-17:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1 27464.70 0.00 01-JAN-00:15 17579.12 18-AUG-17:15
EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 7780.97 59.19 03-AUG-02:15 2179.45 04-FEB-08:15
WaterSystems:EnergyTransfer 7780.97 59.19 03-AUG-02:15 2179.45 04-FEB-08:15
Domestic Hot Water:WaterSystems:EnergyTransfer 7780.97 59.19 03-AUG-02:15 2179.45 04-FEB-08:15
EnergyTransfer:HVAC 54161.00 0.00 10-JAN-14:15 21385.72 06-JUL-17:30
HeatingCoils:EnergyTransfer 18283.33 0.00 10-JAN-14:15 20909.95 12-FEB-00:45
CoolingCoils:EnergyTransfer 35877.67 0.00 01-JAN-00:15 21385.72 06-JUL-17:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [kBtu] HVAC Input Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1 19398.672 -2287.18 0.000 0.000 3020.741 2843.965 13158.722 17083.164 0.000 1475.673 0.000 0.000 -6658.61 0.000 -14953.03 -7904.78
ATTIC_UNIT1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 493.737 5831.372 0.000 0.000 0.000 -6325.11 -0.03
CRAWLSPACE_UNIT1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 522.684 5233.709 0.000 0.000 0.000 -5756.39 0.000
Total Facility 19398.672 -2287.18 0.000 0.000 3020.741 2843.965 13158.722 17083.164 0.000 2492.093 11065.081 0.000 -6658.61 0.000 -27034.54 -7904.81


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [Btu/h] HVAC Input Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1 18-AUG-16:18 0.00 -1.5 0.00 0.00 133.58 436.03 1577.93 7295.24 0.00 1907.80 6262.47 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 18-AUG-16:18 0.00 -1.5 0.00 0.00 133.58 436.03 1577.93 7295.24 0.00 2590.55 8254.07 0.00 0.00 0.00 -2674.4 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [Btu/h] HVAC Input Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1 12-FEB-06:00 22400.35 0.00 0.00 0.00 548.78 389.31 1300.53 0.00 0.00 0.00 0.00 0.00 -5165.2 0.00 -11566.8 -7906.9
ATTIC_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-FEB-06:00 22400.35 0.00 0.00 0.00 548.78 389.31 1300.53 0.00 0.00 0.00 0.00 0.00 -5165.2 0.00 -17020.2 -2453.5



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Sec1.1A-General Information

Data
Weather File ANNUAL ** Atlanta Hartsfield Intl Ap GA USA TMY3 WMO#=722190
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 2773.28
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1 924.43 924.43 0.00 168.00
ATTIC_UNIT1 924.43 0.00 924.43 0.00
CRAWLSPACE_UNIT1 924.43 0.00 924.43 0.00
Totals 2773.28 924.43 1848.85  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 5.00
Number of hours cooling loads not met 12.75
Number of hours not met 17.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 832.93 114.10 0.00 0.00 0.00 0.00
Exterior Lighting 173.89 5.47 0.00 0.00 0.00 0.00
Space Heating 5354.74 6128.36 0.00 0.00 0.00 0.00
Space Cooling 2361.75 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 971.08 373.84 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 2547.01 656.61 0.00 0.00 0.00 0.00
Receptacle Equipment 3853.87 467.95 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 16095.28   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 13158.72 54955.99
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 13158.72 54955.99


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.30
Space Heating 1.93
Space Cooling 0.85
Fans-Interior 0.35
Service Water Heating 0.92
Receptacle Equipment 1.39
Miscellaneous 0.06
Subtotal 5.80


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kBtu/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.17
Space Heating 33.27
Space Cooling 14.67
Fans-Interior 6.03
Service Water Heating 15.82
Receptacle Equipment 23.94
Miscellaneous 1.08



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1 746.50


Branch

Maximum Flow Rate [ft3/min]
AIR LOOP MAIN BRANCH_UNIT1 746.50


AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1 746.50


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [ft3/min] Rated Total Cooling Capacity (gross) [ton] Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1 746.50 1.87 0.757826


AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1 746.50 746.50 746.50 20909.95 1.87 1.00


Fan:OnOff

Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1 746.50


Coil:Heating:Electric

Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1 20909.95


PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1 1.04 19.59


WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1 15354.00 1.04


Pump:VariableSpeed

Rated Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1 1.04



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1 WINDOW_LDF_1.UNIT1 |DOOR_LDF_UNIT1 |
WALL_SDR_1.UNIT1 WINDOW_SDR_1.UNIT1 |
WALL_LDB_1.UNIT1 WINDOW_LDB_1.UNIT1 |DOOR_LDB_UNIT1 |
WALL_SDL_1.UNIT1 WINDOW_SDL_1.UNIT1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2022-08-16 14:22:49

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1

Timestamp: 2022-08-16 14:22:49

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 51.921 2.280 644.522 92.208 94.488
February 106.309 9.162 505.471 62.284 71.446
March 264.018 26.581 379.000 27.984 54.565
April 359.569 45.296 247.875 14.139 59.435
May 486.302 71.174 114.937 3.468 74.642
June 641.899 104.687 26.375 0.777 105.463
July 714.548 122.524 2.000 0.004 122.528
August 739.625 128.313 0.000 0.000 128.313
September 563.114 74.911 66.000 1.767 76.678
October 318.209 37.439 327.833 19.563 57.002
November 197.439 16.693 417.083 38.115 54.808
December 87.435 5.368 590.196 66.342 71.710
           
Annual Sum or Average 4530.386 644.428 3321.293 326.650 971.078
Minimum of Months 51.921 2.280 0.000 0.000 54.565
Maximum of Months 739.625 128.313 644.522 92.208 128.313



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1

Timestamp: 2022-08-16 14:22:49

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6932.04 0.00
February 0.00 5184.04 0.00
March 0.00 2103.81 0.00
April 0.00 1098.34 0.00
May 0.00 260.73 0.00
June 0.00 60.33 0.00
July 0.00 0.27 0.00
August 0.00 0.00 0.00
September 0.00 137.28 0.00
October 0.00 1470.67 0.00
November 0.00 2960.96 0.00
December 0.00 4987.49 0.00
       
Annual Sum or Average 0.00 2085.66 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6932.04 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1

Timestamp: 2022-08-16 14:22:49

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.16
April 0.00 0.00 0.29
May 0.00 0.00 0.44
June 0.00 0.00 0.67
July 0.00 0.00 0.77
August 0.00 0.00 0.81
September 0.00 0.00 0.48
October 0.00 0.00 0.23
November 0.00 0.00 0.10
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.81



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1

Timestamp: 2022-08-16 14:22:49

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1240.70 923.73
February 0.00 0.00 1246.33 838.13
March 0.00 0.00 1185.10 882.34
April 0.00 0.00 1076.90 775.92
May 0.00 0.00 939.32 699.35
June 0.00 0.00 819.03 590.12
July 0.00 0.00 747.00 556.16
August 0.00 0.00 736.99 548.71
September 0.00 0.00 799.80 576.26
October 0.00 0.00 914.08 680.56
November 0.00 0.00 1047.17 754.50
December 0.00 0.00 1169.57 870.78
         
Annual Sum or Average 0.00 0.00 992.05 8696.56
Minimum of Months 0.00 0.00 736.99 548.71
Maximum of Months 0.00 0.00 1246.33 923.73