Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2022.08.16 14:23

Tabular Output Report in Format: HTML

Building: SW_SanFrancisco_HUD.Mfr-Levy_gasfurnace

Environment: ANNUAL ** San Francisco Intl Ap CA USA TMY3 WMO#=724940

Simulation Timestamp: 2022-08-16 14:23:46


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 52258.46 18.84 56.53
Net Site Energy 52258.46 18.84 56.53
Total Source Energy 100406.08 36.20 108.61
Net Source Energy 100406.08 36.20 108.61


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 2773.28
Net Conditioned Building Area 924.43
Unconditioned Building Area 1848.85


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 14408.39 0.00 0.00 0.00 0.00
Cooling 2574.43 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2843.96 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 593.73 0.00 0.00 0.00 0.00 0.00
Interior Equipment 13158.72 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1836.31 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16842.91 0.00 0.00 0.00 23315.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 21007.16 31251.30 0.00 0.00 0.00 88.26
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 14408.39 0.00 0.00 0.00 0.00
Cooling General 2574.43 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 2843.96 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 457.46 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 136.27 0.00 0.00 0.00 0.00 0.00
Interior Equipment IntGains 13158.72 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 1836.31 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 16842.91 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 23315.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 3.72 0.00 0.00 0.00 0.00 0.00
HVAC 4.77 33.81 0.00 0.00 0.00 25.22
Other 14.23 0.00 0.00 0.00 0.00 0.00
Total 22.72 33.81 0.00 0.00 0.00 0.10


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.24 0.00 0.00 0.00 0.00 0.00
HVAC 1.59 11.27 0.00 0.00 0.00 8.41
Other 4.74 0.00 0.00 0.00 0.00 0.00
Total 7.57 11.27 0.00 0.00 0.00 0.03


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 21007.16 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 21007.16 100.00
     
Total On-Site and Utility Electric Sources 21007.16 100.00
Total Electricity End Uses 21007.16 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 23315.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 23315.79 100.00
Total Water End Uses 23315.79 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 6.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 252.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1 |

COILLOADS

| MAIN GAS HEATING COIL_UNIT1 | DX COOLING COIL_UNIT1 |

WATER HEATER: LOADS

| WATER HEATER_UNIT1 |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2022.08.16 14:23
RunPeriod ANNUAL
Weather File San Francisco Intl Ap CA USA TMY3 WMO#=724940
Latitude [deg] 37.62
Longitude [deg] -122.4
Elevation [ft] 6.56
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 1294.30 528.04 119.11 528.04 119.11
Window Opening Area [ft2] 110.93 27.73 27.73 27.73 27.73
Window-Wall Ratio [%] 8.57 5.25 23.28 5.25 23.28


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 1200.29 495.04 105.10 495.04 105.10
Window Opening Area [ft2] 110.93 27.73 27.73 27.73 27.73
Window-Wall Ratio [%] 9.24 5.60 26.39 5.60 26.39


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 933.78
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Gross Wall Area [ft2] Window Glass Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
LIVING_UNIT1 924.43 Yes Yes 6935.31 1.00 1200.29 110.93 1.0781 462.21 2.4037
ATTIC_UNIT1 924.43 No Yes 461.69 1.00 13.99 0.00 0.0000   0.0000
CRAWLSPACE_UNIT1 924.43 No Yes 1849.42 1.00 80.02 0.00 0.0000   0.0000
Total 2773.28     9246.42   1294.30 110.93 0.3594 1386.64 0.8012
Conditioned Total 924.43     6935.31   1200.29 110.93 1.0781 462.21 2.4037
Unconditioned Total 1848.85     2311.11   94.01 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 30-JUN-18:15 26-DEC-07:15 - - - 01-JAN-08:15
Heating 0.00 9.85 0.00 0.00 0.00 0.00
Cooling 2.57 0.00 0.00 0.00 0.00 0.00
Interior Lighting 0.82 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.14 0.00 0.00 0.00 0.00 0.00
Interior Equipment 2.08 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 0.80 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 3.07 0.00 0.00 0.00 0.08
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 6.42 12.92 0.00 0.00 0.00 0.08


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 9.85 0.00 0.00 0.00 0.00
Cooling General 2.57 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 0.82 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.10 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.04 0.00 0.00 0.00 0.00 0.00
Interior Equipment IntGains 2.08 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.80 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 3.07 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.08
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 15618.70 0.00 0.00 0.00
Cooling 8153.22 0.00 0.00 0.00 0.00
Interior Lighting 9006.84 0.00 0.00 0.00 0.00
Exterior Lighting 1880.35 0.00 0.00 0.00 0.00
Interior Equipment 41673.67 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 5815.58 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 18257.72 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 66529.66 33876.41 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 16.90 0.00 0.00 0.00
Cooling 8.82 0.00 0.00 0.00 0.00
Interior Lighting 9.74 0.00 0.00 0.00 0.00
Exterior Lighting 2.03 0.00 0.00 0.00 0.00
Interior Equipment 45.08 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 6.29 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.75 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 71.97 36.65 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 16.90 0.00 0.00 0.00
Cooling 8.82 0.00 0.00 0.00 0.00
Interior Lighting 9.74 0.00 0.00 0.00 0.00
Exterior Lighting 2.03 0.00 0.00 0.00 0.00
Interior Equipment 45.08 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 6.29 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 19.75 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 71.97 36.65 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 38.84 0.00 38.84 Wetbulb [F] 433.09 150.00
SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 82.94 15.30 62.96 Wetbulb [F] 1161.47 310.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
WALL_LDF_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 495.04 180.00 90.00 S
WALL_SDR_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 105.10 90.00 90.00 E
WALL_LDB_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 495.04 0.00 90.00 N
WALL_SDL_1.UNIT1 EXTERIOR WALL 0.30 0.098 0.106 105.10 270.00 90.00 W
ROOF_RIGHT_UNIT1 GABLE_END 0.30 0.314 0.428 7.00 90.00 90.00 E
ROOF_LEFT_UNIT1 GABLE_END 0.30 0.314 0.428 7.00 270.00 90.00 W
ROOF_FRONT_UNIT1 EXTERIOR ROOF 0.25 0.469 0.943 466.89 180.00 8.12  
ROOF_BACK_UNIT1 EXTERIOR ROOF 0.25 0.469 0.943 466.89 0.00 8.12  
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 33.00 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 7.01 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 33.00 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 7.01 270.00 90.00 W


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 0.501 0.600 0.881     Yes WALL_LDF_1.UNIT1 180.00 90.00 S
WINDOW_SDR_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 0.501 0.600 0.881     Yes WALL_SDR_1.UNIT1 90.00 90.00 E
WINDOW_LDB_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 0.501 0.600 0.881     Yes WALL_LDB_1.UNIT1 0.00 90.00 N
WINDOW_SDL_1.UNIT1 EXTERIOR WINDOW 27.73 0.00 0.00 27.73 27.73 0.501 0.600 0.881     Yes WALL_SDL_1.UNIT1 270.00 90.00 W
Total or Average           110.93 0.501 0.600 0.881              
North Total or Average           27.73 0.501 0.600 0.881              
Non-North Total or Average           83.20 0.501 0.600 0.881              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDF_UNIT1 EXTERIOR DOOR 0.400 0.400 18.01 WALL_LDF_1.UNIT1
DOOR_LDB_UNIT1 EXTERIOR DOOR 0.400 0.400 18.01 WALL_LDB_1.UNIT1



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_1.UNIT1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_1.UNIT1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_1.UNIT1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_1.UNIT1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_1.UNIT1 SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1 LIVING_UNIT1 0.8625 924.43 797.30 General INTERIORLIGHTING 54.69 168.00 54.69 0.0000 Y 666.34
LIVING PLUG-IN LIGHTING1 LIVING_UNIT1 0.2156 924.43 199.33 General INTERIORLIGHTING 54.69 168.00 54.69 0.0000 Y 166.59
Interior Lighting Total   0.5391 1848.85 996.63               832.93


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1 30.59 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 133.98
GARAGE-LIGHTS_UNIT1 14.00 Schedule INTERIORLIGHTING 54.69 168.00 54.69 39.91
Exterior Lighting Total 44.58           173.89



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed   14149.06 11300.22 2848.84 0.80 4.22    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed 1.1 3.36 11.47 12.13 11.58
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN GAS HEATING COIL_UNIT1 Coil:Heating:Gas   10763.58 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1 Fan:OnOff 0.38 0.06 530.74 265.79 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1 Pump:VariableSpeed Intermittent 0.00 7.8159 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1 WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Zone Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak Temperature at Peak [F] Humidity Ratio at Peak [lbWater/lbAir]
LIVING_UNIT1 12467.16 12467.16 530.744 530.744 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 81.41 0.00771


Zone Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak Temperature at Peak [F] Humidity Ratio at Peak [lbWater/lbAir]
LIVING_UNIT1 9101.08 9101.08 165.659 165.659 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:00:00 38.84 0.00496


System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1 530.74 530.74 165.66 165.66



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1 1776.25 6323.00 252.75
ATTIC_UNIT1 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00
Facility 1776.25 6323.00 252.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1 0.00 6.00 0.00 6.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00
Facility 0.00 6.00 0.00 6.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1 1.38 2.00 6935.31 0.000 0.571 0.000 0.447
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1 1.38 2.00 6935.31 0.000 0.001 0.000 0.007
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Surfaces by Class

Total Outdoors
Wall 14 10
Floor 3 0
Roof 4 2
Internal Mass 1 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 4 4
Door 2 2
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 1
Conditioned Zones 1
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 317
Defaulted Fields 43
Fields with Defaults 1098
Autosized Fields 25
Autosizable Fields 30
Autocalculated Fields 16
Autocalculatable Fields 40



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum Electricity Maximum Value [W] Timestamp of Maximum
Electricity:Facility 6152.49 372.58 14-FEB-09:30 1880.17 30-JUN-18:15
Electricity:Building 4686.80 370.94 01-JAN-09:15 943.35 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1 4686.80 370.94 01-JAN-09:15 943.35 01-JAN-20:15
InteriorLights:Electricity 832.93 18.26 01-JAN-00:15 292.10 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1 832.93 18.26 01-JAN-00:15 292.10 01-JAN-20:15
General:InteriorLights:Electricity 832.93 18.26 01-JAN-00:15 292.10 01-JAN-20:15
InteriorEquipment:Electricity 3853.87 336.71 01-JAN-09:15 651.25 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1 3853.87 336.71 01-JAN-09:15 651.25 01-JAN-20:15
IntGains:InteriorEquipment:Electricity 3853.87 336.71 01-JAN-09:15 651.25 01-JAN-20:15
Fans:Electricity 537.81 0.00 01-JAN-11:00 265.79 02-APR-15:00
Fans:Electricity:Zone:LIVING_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 6152.49 372.58 15-FEB-09:45 1880.17 30-JUN-18:15
ElectricityPurchased:Plant 6152.49 372.58 15-FEB-09:45 1880.17 30-JUN-18:15
Cogeneration:ElectricityPurchased 6152.49 372.58 15-FEB-09:45 1880.17 30-JUN-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 6152.49 372.58 15-FEB-09:45 1880.17 30-JUN-18:15
ElectricityNet:Plant 6152.49 372.58 15-FEB-09:45 1880.17 30-JUN-18:15
Cogeneration:ElectricityNet 6152.49 372.58 15-FEB-09:45 1880.17 30-JUN-18:15
ExteriorLights:Electricity 173.89 1.64 01-JAN-09:15 44.58 01-JAN-20:15
Exterior-Lights:ExteriorLights:Electricity 133.98 0.00 01-JAN-06:15 30.59 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 39.91 0.87 01-JAN-00:15 14.00 01-JAN-20:15
Electricity:HVAC 1291.80 0.00 01-JAN-11:00 1194.62 30-JUN-14:00
General:Fans:Electricity 537.81 0.00 01-JAN-11:00 265.79 02-APR-15:00
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 753.99 0.00 01-JAN-00:15 928.83 30-JUN-14:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum Gas Maximum Value [Btu/h] Timestamp of Maximum
Gas:Facility 312.51 782.91 24-SEP-02:15 12907.11 26-DEC-07:15
Gas:Plant 168.43 782.91 24-SEP-02:15 3242.74 05-FEB-09:00
WaterSystems:Gas 168.43 782.91 24-SEP-02:15 3242.74 05-FEB-09:00
Water Heater:WaterSystems:Gas 168.43 782.91 24-SEP-02:15 3242.74 05-FEB-09:00
Gas:HVAC 144.08 0.00 01-JAN-11:00 10255.65 24-JAN-06:00
Heating:Gas 144.08 0.00 01-JAN-11:00 10255.65 24-JAN-06:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum Cooling Maximum Value [ton] Timestamp of Maximum
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum Maximum Value [ft3/min] Timestamp of Maximum
Water:Facility 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15
Water:Plant 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15
WaterSystems:Water 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15
MainsWater:Plant 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15
WaterSystems:MainsWater 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 3117.32 0.00 03-JAN-02:45 0.01 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum Maximum Value [lb/s] Timestamp of Maximum
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum Maximum Value [ft3/min] Timestamp of Maximum
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum Maximum Value [gal] Timestamp of Maximum
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum Maximum Value [Btu/h] Timestamp of Maximum
PlantLoopHeatingDemand:Facility 8766.88 87.29 08-AUG-02:15 2041.90 05-FEB-08:15
PlantLoopHeatingDemand:Plant 8766.88 87.29 08-AUG-02:15 2041.90 05-FEB-08:15
WaterSystems:PlantLoopHeatingDemand 8766.88 87.29 08-AUG-02:15 2041.90 05-FEB-08:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 56876.41 89.59 25-SEP-02:15 28039.69 15-SEP-16:15
EnergyTransfer:Building 23719.20 0.00 01-JAN-11:00 12956.64 15-SEP-16:15
EnergyTransfer:Zone:LIVING_UNIT1 23719.20 0.00 01-JAN-11:00 12956.64 15-SEP-16:15
Heating:EnergyTransfer 12498.05 0.00 01-JAN-11:00 8895.80 24-JAN-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1 12498.05 0.00 01-JAN-11:00 8895.80 24-JAN-06:00
Cooling:EnergyTransfer 11221.15 0.00 01-JAN-00:15 12956.64 15-SEP-16:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1 11221.15 0.00 01-JAN-00:15 12956.64 15-SEP-16:15
EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Plant 8766.88 87.29 08-AUG-02:15 2041.90 05-FEB-08:15
WaterSystems:EnergyTransfer 8766.88 87.29 08-AUG-02:15 2041.90 05-FEB-08:15
Domestic Hot Water:WaterSystems:EnergyTransfer 8766.88 87.29 08-AUG-02:15 2041.90 05-FEB-08:15
EnergyTransfer:HVAC 24390.33 0.00 01-JAN-11:00 14305.57 02-JUN-16:00
HeatingCoils:EnergyTransfer 11526.71 0.00 01-JAN-11:00 8204.52 24-JAN-06:00
CoolingCoils:EnergyTransfer 12863.62 0.00 01-JAN-00:15 14305.57 02-JUN-16:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Annual Building Sensible Heat Gain Components

HVAC Input Sensible Air Heating [kBtu] HVAC Input Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1 12497.941 -934.46 0.000 0.000 3084.262 2843.965 13158.722 12251.900 0.000 64.756 0.000 0.000 -4212.19 0.000 -18184.79 -10283.56
ATTIC_UNIT1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 614.651 6450.251 0.000 0.000 0.000 -7064.90 -0.03
CRAWLSPACE_UNIT1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 29.367 6821.279 0.000 0.000 0.000 -6850.65 0.000
Total Facility 12497.941 -934.46 0.000 0.000 3084.262 2843.965 13158.722 12251.900 0.000 708.774 13271.529 0.000 -4212.19 0.000 -32100.34 -10283.59


Peak Cooling Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [Btu/h] HVAC Input Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1 15-SEP-16:15 0.00 -1.1 0.00 0.00 139.14 436.03 1577.93 3988.68 0.00 595.94 6266.10 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 15-SEP-16:15 0.00 -1.1 0.00 0.00 139.14 436.03 1577.93 3988.68 0.00 668.58 8457.45 0.00 0.00 0.00 -2264.0 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak HVAC Input Sensible Air Heating [Btu/h] HVAC Input Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1 24-JAN-06:00 8895.69 0.00 0.00 0.00 526.31 389.31 1300.53 0.00 0.00 0.00 0.00 0.00 -1565.9 0.00 -4578.0 -4968.0
ATTIC_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 24-JAN-06:00 8895.69 0.00 0.00 0.00 526.31 389.31 1300.53 0.00 0.00 146.48 0.00 0.00 -1565.9 0.00 -6286.5 -3405.9



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
None                    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
None                    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
None                    


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
None              


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
None            


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
None                          


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
None            



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Sec1.1A-General Information

Data
Weather File ANNUAL ** San Francisco Intl Ap CA USA TMY3 WMO#=724940
HDD and CDD data source Weather File Stat
Total gross floor area [m2] 2773.28
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1 924.43 924.43 0.00 168.00
ATTIC_UNIT1 924.43 0.00 924.43 0.00
CRAWLSPACE_UNIT1 924.43 0.00 924.43 0.00
Totals 2773.28 924.43 1848.85  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 6.00
Number of hours not met 6.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 832.93 239.61 0.00 0.00 0.00 0.00
Exterior Lighting 173.89 42.07 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 144.08 9838.31 0.00 0.00
Space Cooling 753.99 752.98 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 537.81 235.54 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 168.43 3068.80 0.00 0.00
Receptacle Equipment 3853.87 609.97 0.00 0.00 0.00 0.00
Interior Lighting (process) 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 6152.49   312.51   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 13158.72 21007.16
Natural Gas 0.00 31251.30
Additional 0.00 0.00
Total 13158.72 52258.46


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.30
Space Heating 0.00
Space Cooling 0.27
Fans-Interior 0.19
Service Water Heating 0.00
Receptacle Equipment 1.39
Miscellaneous 0.06
Subtotal 2.22


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kBtu/ft2]
Space Heating 5.19
Service Water Heating 6.06
Miscellaneous -0.0
Subtotal 11.25


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.44
Space Heating 27.57
Space Cooling 4.93
Fans-Interior 3.51
Service Water Heating 32.23
Receptacle Equipment 25.18
Miscellaneous 1.14



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1 530.74


Branch

Maximum Flow Rate [ft3/min]
AIR LOOP MAIN BRANCH_UNIT1 530.74


AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1 530.74


Coil:Cooling:DX:SingleSpeed

Rated Air Flow Rate [ft3/min] Rated Total Cooling Capacity (gross) [ton] Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1 530.74 1.18 0.798655


AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1 530.74 530.74 530.74 10763.58 1.18 1.00


Fan:OnOff

Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1 530.74


Coil:Heating:Gas

Nominal Capacity [Btu/h]
MAIN GAS HEATING COIL_UNIT1 10763.58


PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1 1.04 19.59


WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1 36002.06 1.04


Pump:VariableSpeed

Rated Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1 1.04



Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1 WINDOW_LDF_1.UNIT1 |DOOR_LDF_UNIT1 |
WALL_SDR_1.UNIT1 WINDOW_SDR_1.UNIT1 |
WALL_LDB_1.UNIT1 WINDOW_LDB_1.UNIT1 |DOOR_LDB_UNIT1 |
WALL_SDL_1.UNIT1 WINDOW_SDL_1.UNIT1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2022-08-16 14:23:46

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1

Timestamp: 2022-08-16 14:23:46

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 64.721 2.771 592.271 50.630 53.401
February 149.821 10.564 409.000 33.774 44.338
March 222.073 18.545 407.850 30.241 48.786
April 241.709 19.153 340.625 21.790 40.943
May 313.063 24.145 280.292 17.154 41.298
June 322.057 30.083 279.282 16.481 46.565
July 366.184 31.250 241.938 10.647 41.897
August 371.899 36.989 237.792 9.485 46.474
September 350.154 37.680 231.554 8.612 46.293
October 280.953 24.864 312.333 16.788 41.652
November 183.022 12.053 399.187 26.158 38.211
December 104.958 5.274 517.149 42.677 47.952
           
Annual Sum or Average 2970.615 253.372 4249.272 284.438 537.809
Minimum of Months 64.721 2.771 231.554 8.612 38.211
Maximum of Months 371.899 37.680 592.271 50.630 53.401



Table of Contents

Report: COILLOADS

For: MAIN GAS HEATING COIL_UNIT1

Timestamp: 2022-08-16 14:23:46

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2755.78 0.00
February 0.00 2035.30 0.00
March 0.00 1646.02 0.00
April 0.00 1225.57 0.00
May 0.00 933.66 0.00
June 0.00 926.97 0.00
July 0.00 579.52 0.00
August 0.00 516.27 0.00
September 0.00 484.39 0.00
October 0.00 913.78 0.00
November 0.00 1471.22 0.00
December 0.00 2322.93 0.00
       
Annual Sum or Average 0.00 1314.90 0.00
Minimum of Months 0.00 484.39 0.00
Maximum of Months 0.00 2755.78 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1

Timestamp: 2022-08-16 14:23:46

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.07
March 0.00 0.00 0.11
April 0.00 0.00 0.11
May 0.00 0.00 0.13
June 0.00 0.00 0.18
July 0.00 0.00 0.18
August 0.00 0.00 0.21
September 0.00 0.00 0.23
October 0.00 0.00 0.14
November 0.00 0.00 0.07
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1

Timestamp: 2022-08-16 14:23:46

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1615.55 1202.82
February 0.00 0.00 1614.97 1086.03
March 0.00 0.00 1597.35 1189.27
April 0.00 0.00 1569.15 1130.59
May 0.00 0.00 1524.07 1134.71
June 0.00 0.00 1488.46 1072.45
July 0.00 0.00 1465.22 1090.90
August 0.00 0.00 1456.53 1084.43
September 0.00 0.00 1473.03 1061.34
October 0.00 0.00 1506.66 1121.75
November 0.00 0.00 1548.17 1115.47
December 0.00 0.00 1591.04 1184.57
         
Annual Sum or Average 0.00 0.00 1537.08 13474.33
Minimum of Months 0.00 0.00 1456.53 1061.34
Maximum of Months 0.00 0.00 1615.55 1202.82