Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2023-10-16 08:27:39


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 140.24 274.36 274.36
Net Site Energy 140.24 274.36 274.36
Total Source Energy 444.14 868.90 868.90
Net Source Energy 444.14 868.90 868.90


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 16.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 140.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 16.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 24.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 13.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 16.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 24.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 108.43 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 274.36 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 108.43 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 274.36 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 140.240 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 140.240 100.00
     
Total On-Site and Utility Electric Sources 140.240 100.00
Total Electricity End Uses 140.240 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.50
Time Setpoint Not Met During Occupied Cooling 18.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 261.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
RunPeriod RUNPERIOD 1
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [m] 159.00
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.9815 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.9815 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.9815 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.9815 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.9815 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.9815 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.9815 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.9815 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.9815 9.29 6.7800  
Conditioned Total 511.16             6.9815 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.9815 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-OCT-12:50 03-JAN-06:19 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 3188.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4745.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2191.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1484.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2769.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 14516.43 3188.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 3188.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 4745.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2191.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1484.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2769.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 1.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 43.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 84.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 53.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 76.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 444.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 2.63 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 85.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 105.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 149.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 868.89 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 2.63 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 85.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 105.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 149.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 868.89 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.288615
PERIMETER_ZN_1 DIRECT AIR 0.295704
PERIMETER_ZN_2 DIRECT AIR 0.218662
PERIMETER_ZN_3 DIRECT AIR 0.259834
PERIMETER_ZN_4 DIRECT AIR 0.262505
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.288615 0.288615 0.288615 0.288615 0.288615 0.288615 1.00 1.00 0.288615
PSZ-AC:2 0.295704 0.295704 0.295704 0.295704 0.295704 0.295704 1.00 1.00 0.295704
PSZ-AC:3 0.218662 0.218662 0.218662 0.218662 0.218662 0.218662 1.00 1.00 0.218662
PSZ-AC:4 0.259834 0.259834 0.259834 0.259834 0.259834 0.259834 1.00 1.00 0.259834
PSZ-AC:5 0.262505 0.262505 0.262505 0.262505 0.262505 0.262505 1.00 1.00 0.262505
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.288615 0.064622
PSZ-AC:2_OA_CONTROLLER 0.295704 0.048988
PSZ-AC:3_OA_CONTROLLER 0.218662 0.029060
PSZ-AC:4_OA_CONTROLLER 0.259834 0.048988
PSZ-AC:5_OA_CONTROLLER 0.262505 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.288615 5013.13 0.800382
PSZ-AC:2 HP COOLING COIL 0.295704 4970.97 0.800032
PSZ-AC:3 HP COOLING COIL 0.218662 3619.63 0.800655
PSZ-AC:4 HP COOLING COIL 0.259834 4408.59 0.800697
PSZ-AC:5 HP COOLING COIL 0.262505 4345.38 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.288615 0.288615 0.288615 0.288615 5013.13 5013.13 40.00 2777.99 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.295704 0.295704 0.295704 0.295704 4970.97 4970.97 40.00 3322.94 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.218662 0.218662 0.218662 0.218662 3619.63 3619.63 40.00 2052.24 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.259834 0.259834 0.259834 0.259834 4408.59 4408.59 40.00 3279.01 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.262505 0.262505 0.262505 0.262505 4345.38 4345.38 40.00 2049.15 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.288615
PSZ-AC:2 FAN 0.295704
PSZ-AC:3 FAN 0.218662
PSZ-AC:4 FAN 0.259834
PSZ-AC:5 FAN 0.262505
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.288615 5013.13
PSZ-AC:2 HEATING COIL 0.295704 4970.97
PSZ-AC:3 HEATING COIL 0.218662 3619.63
PSZ-AC:4 HEATING COIL 0.259834 4408.59
PSZ-AC:5 HEATING COIL 0.262505 4345.38
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 2777.99
PSZ-AC:2_SUPPHEATCOIL 3322.94
PSZ-AC:3_SUPPHEATCOIL 2052.24
PSZ-AC:4_SUPPHEATCOIL 3279.01
PSZ-AC:5_SUPPHEATCOIL 2049.15
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.80 14.30 13.60 13.20 13.30 12.60 15.30 15.60 17.70 19.40 19.70 18.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 159.00 99429 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.00 7.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1044.832 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1044.832
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4610


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.2335E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.3922E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.3273E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.4736E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 8.9386E-004
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.0085E-003
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 4.3251E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.8318E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 8.5856E-003
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.8429E-003
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 8.7583E-003
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 8.4113E-003
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 7.7669E-003
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 5.2828E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.6930E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.9875E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.0480E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 5.9617E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.9409E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 6.1680E-003
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.7746E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 4.4268E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 3.0682E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.8375E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.2209E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3471E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.3152E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.4276E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 8.8311E-004
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 9.7745E-004
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 4.2894E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.7533E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1706E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1846E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.2725E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.2844E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 8.4388E-004
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 8.5359E-004
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 4.0429E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 4.0967E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1668E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1696E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.2693E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.2716E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 8.4134E-004
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 8.4316E-004
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 4.0268E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 4.0373E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.8352E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.1671E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.9374E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.2533E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.3586E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.5877E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.8598E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.6907E-004
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.7243E-004
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.7846E-004
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.8006E-004
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.5756E-004
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.5019E-004
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.8433E-004
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.7807E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.2474E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.6281E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.8224E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.8660E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.2809E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.4443E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9376E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3215E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.1121E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 8.3252E-003
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.0988E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 8.3325E-003
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.7544E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 7.6767E-003
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.7183E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.9598E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.2669E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.9701E-004
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.2189E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.3461E-004
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.1543E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 8.2709E-004
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 9.6676E-004
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.8152E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 7.3256E-004
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.6342E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.5349E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.7273E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.4148E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.0802E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.4989E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.2791E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.7227E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.9094E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.4306E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.2615E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.8364E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.0388E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.2157E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.8007E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.7666E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.9359E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.7655E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.0772E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.0969E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.9826E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.4488E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.0538E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.0664E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.7581E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.7931E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.8336E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.6331E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.1936E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.7243E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.3509E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.8799E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.2239E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.3575E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.4024E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.5085E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.8239E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.8992E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.0508E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.1105E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.1837E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.2109E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.3697E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.3916E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.7982E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.8139E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.0325E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.0438E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.0956E-003
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.3603E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.0557E-003
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.3283E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.9497E-004
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0460E-003
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.8264E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 7.3330E-004
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 9.9129E-003
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 4.6236E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.0285E-002
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 4.3763E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 8.4279E-003
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 4.0340E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.9431E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.2376E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.6536E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.8346E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.9421E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.3452E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.6331E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.0892E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.3183E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.0876E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 9.4251E-004
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.0449E-003
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 8.6584E-004
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 9.4144E-004
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 8.1085E-004
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 8.4731E-004
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.7906E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.2545E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3217.03103 3860.43723 0.24051 0.28862 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 30.94400 8.23292E-003 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 694.48926 833.38711 3.05084E-002 6.46221E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3295.93497 3955.12196 0.24642 0.29570 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 31.30000 8.23349E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 1958.50770 2350.20924 8.60340E-002 0.10324 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2437.35507 2924.82609 0.18222 0.21866 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:40:00 27.41367 8.22733E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 1230.33292 1476.39950 5.40464E-002 6.48557E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 2896.22691 3475.47230 0.21653 0.25983 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 31.03300 8.23307E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 1921.35570 2305.62684 8.44020E-002 0.10128 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 2926.05247 3511.26296 0.21875 0.26250 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 29.75733 8.23104E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 1227.72076 1473.26492 5.39317E-002 6.47180E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3.80000 5.05843E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4342.11 0.28862 0.28862 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-AC:1 Heating Sensible 2777.99 6.46221E-002 6.46221E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 4325.09 0.29570 0.29570 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-AC:2 Heating Sensible 3322.94 0.10324 0.10324 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3001.21 0.21866 0.21866 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
6 PSZ-AC:3 Heating Sensible 2052.24 6.48557E-002 6.48557E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 3837.30 0.25983 0.25983 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 PSZ-AC:4 Heating Sensible 3279.01 0.10128 0.10128 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 3659.46 0.26250 0.26250 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 PSZ-AC:5 Heating Sensible 2049.15 6.47180E-002 6.47180E-002 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.28862
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.29570
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.21866
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.25983
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.26250
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.28862
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.28862
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.28862
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.28862
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.28862
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.28862
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.29570
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.29570
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.29570
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.29570
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.29570
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.29570
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.21866
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.21866
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.21866
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.21866
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.21866
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.21866
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.25983
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.25983
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.25983
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.25983
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.25983
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.25983
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.26250
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.26250
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.26250
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.26250
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.26250
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.26250
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.28862
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.29570
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.21866
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.25983
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.26250
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.28862
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28862
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5013.13400
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80038
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.28862
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.28862
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.28862
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.28862
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5013.13400
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5013.13400
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2777.98885
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.28862
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.28862
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5013.13400
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 2777.98885
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.29570
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.29570
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4970.97121
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80003
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.29570
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.29570
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.29570
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.29570
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4970.97121
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4970.97121
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3322.94262
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.29570
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.29570
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4970.97121
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 3322.94262
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.21866
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.21866
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3619.62673
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.21866
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.21866
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.21866
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.21866
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 3619.62673
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 3619.62673
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2052.23845
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.21866
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.21866
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 3619.62673
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 2052.23845
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.25983
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.25983
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4408.58811
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80070
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.25983
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.25983
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.25983
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.25983
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4408.58811
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4408.58811
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3279.00960
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.25983
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.25983
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4408.58811
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 3279.00960
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.26250
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.26250
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4345.38231
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.26250
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.26250
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.26250
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.26250
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4345.38231
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4345.38231
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2049.14953
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.26250
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.26250
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4345.38231
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 2049.14953
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 4786.8 3.32 11.33 11.86 11.22 11.12
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 4739.2 3.30 11.26 11.78 11.14 11.01
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 3448.3 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 4204.9 3.31 11.28 11.80 11.16 11.04
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4139.7 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 5242.4 2914.8 7.34 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 5205.7 2897.7 7.33 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 3793.1 2112.5 7.30 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 4614.9 2568.0 7.35 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 4553.6 2536.1 7.33 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 7.7049799953E-003 4.6153537705E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 3.2328690770E-002 3.3044662950E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 2.6329867552E-002 3.7112031380E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 1.5738002513E-002 1.0346442252E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 2.1965393430E-002 1.3429036369E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.2938586833 0.3257548062 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1313.66 39.76 0.00 80.47 77.04 1510.93



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 3.80 0.00 3.80 Wetbulb [C] 3.00 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 31.30 8.90 18.40 Wetbulb [C] 4.10 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.00 2      
Feb 59.00 53      
Mar 58.58 43      
Apr 46.42 14      
May 18.00 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 3.00 6      
Oct 0.00 0      
Nov 18.00 12      
Dec 4.00 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.424_SHGC_SOUTH_0.249   3.91 0.00 0.00 3.91 3.91 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.409 0.250 0.275                      
North Total or Average             16.72 2.409 0.250 0.275                      
Non-North Total or Average             42.93 2.409 0.250 0.275                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.86 0.84 0.85 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 0.98 0.00 0.00 1.00 0.15 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 1.00 0.00 0.00 0.92 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.9815 149.66 1044.83 LightsWired LTG_SCH_OFFICE 55.32 168.00 44.56 0.0000 Y 8.74
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 36.37 0.0000 Y 5.41
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.19 0.0000 Y 3.37
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 39.57 0.0000 Y 5.88
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.01 0.0000 Y 3.35
Interior Lighting Total       6.9815 511.16 3568.64               26.75


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 87.95 AstronomicalClock -   42.14 42.14 0.70
EXTERIOR_LIGHTS_B 200.47 AstronomicalClock -   83.75 62.95 2.37
EXTERIOR_LIGHTS_C 773.25 AstronomicalClock -   83.75 46.20 6.71
Exterior Lighting Total 1061.67           9.77



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5013.13 4012.42 1000.71 0.80 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4970.97 3976.94 994.03 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   3619.63 2898.07 721.55 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4408.59 3529.94 878.65 0.80 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4345.38 3479.15 866.23 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   4786.8 3.32 11.33 11.86 11.22 11.12
PSZ-AC:2 HP COOLING COIL   4739.2 3.30 11.26 11.78 11.14 11.01
PSZ-AC:3 HP COOLING COIL   3448.3 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   4204.9 3.31 11.28 11.80 11.16 11.04
PSZ-AC:5 HP COOLING COIL   4139.7 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 5242.4 2914.8 7.34 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 5205.7 2897.7 7.33 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 3793.1 2112.5 7.30 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 4614.9 2568.0 7.35 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 4553.6 2536.1 7.33 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   5013.13 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   2777.99 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   4970.97 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   3322.94 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   3619.63 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   2052.24 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   4408.59 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   3279.01 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   4345.38 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   2049.15 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.29 323.28 1120.11 1.00 1.92 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.30 331.22 1120.11 1.00 1.91 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.22 244.92 1120.11 1.00 2.16 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.26 291.04 1120.11 1.00 2.01 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.26 294.03 1120.11 1.00 2.00 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3217.03 3860.44 25.80 0.241 0.289 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 23.89 23.89 0.00906 30.94 0.00823 0.065 0.00
PERIMETER_ZN_1 3295.93 3955.12 34.86 0.246 0.296 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 23.89 23.89 0.00889 31.30 0.00823 0.049 0.00
PERIMETER_ZN_2 2437.36 2924.83 43.46 0.182 0.219 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:40:00 23.89 23.89 0.00881 27.41 0.00823 0.029 0.00
PERIMETER_ZN_3 2896.23 3475.47 30.63 0.217 0.260 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 23.89 23.89 0.00894 31.03 0.00823 0.049 0.00
PERIMETER_ZN_4 2926.05 3511.26 52.17 0.219 0.263 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 23.89 23.89 0.00876 29.76 0.00823 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 694.49 833.39 5.57 0.031 0.065 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 3.80 0.00506 0.065 0.00
PERIMETER_ZN_1 1958.51 2350.21 20.72 0.086 0.103 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00774 3.80 0.00506 0.049 0.00
PERIMETER_ZN_2 1230.33 1476.40 21.94 0.054 0.065 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00773 3.80 0.00506 0.029 0.00
PERIMETER_ZN_3 1921.36 2305.63 20.32 0.084 0.101 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00774 3.80 0.00506 0.049 0.00
PERIMETER_ZN_4 1227.72 1473.26 21.89 0.054 0.065 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00773 3.80 0.00506 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.29 0.29 0.06 0.06 0.2886 0.2886 0.2886 1.0000 1.0000
PSZ-AC:2 0.30 0.30 0.10 0.10 0.2957 0.2957 0.2957 1.0000 1.0000
PSZ-AC:3 0.22 0.22 0.06 0.06 0.2187 0.2187 0.2187 1.0000 1.0000
PSZ-AC:4 0.26 0.26 0.10 0.10 0.2598 0.2598 0.2598 1.0000 1.0000
PSZ-AC:5 0.26 0.26 0.06 0.06 0.2625 0.2625 0.2625 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5013.134 4012.421 0.288615 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 4905.20 4620.25 0.288615 26.40 17.34 0.00887231 12.80 11.93 0.00850000 30.94 0.00823292 18.33 22.3904 23.89 0.00905861 48.1332 3211.00 0.00 5012.27 3969.34
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5013.134 5013.134 0.288615 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 5013.13 5013.13 0.288615 17.23 12.59 0.00734137 40.00 20.96 0.00800000 3.80 0.00505843 3.80 22.3904 21.11 0.00800000 50.4139 693.67 0.00 5019.72 5019.72
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 2777.989 2777.989 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 2777.99 2777.99 0.288615 17.23 12.59 0.00734137 40.00 20.96 0.00800000 3.80 0.00505843 3.80 22.3904 21.11 0.00800000 50.4139 693.67 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 4970.971 3976.938 0.295704 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 4828.36 4611.31 0.295704 26.04 17.14 0.00877757 12.80 11.93 0.00850000 31.30 0.00823349 18.45 16.5665 23.89 0.00888560 47.2270 3295.93 0.00 4970.12 3934.48
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 4970.971 4970.971 0.295704 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4970.97 4970.97 0.295704 18.24 12.95 0.00729954 40.00 20.96 0.00800000 3.80 0.00505843 3.80 16.5665 21.11 0.00774453 48.8251 1958.51 0.00 4977.50 4977.50
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 3322.943 3322.943 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3322.94 3322.94 0.295704 18.24 12.95 0.00729954 40.00 20.96 0.00800000 3.80 0.00505843 3.80 16.5665 21.11 0.00774453 48.8251 1958.51 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 3619.627 2898.073 0.218662 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:40:00 3578.53 3436.20 0.218662 25.29 16.84 0.00873181 12.80 11.93 0.00850000 27.41 0.00822733 17.15 13.2900 23.89 0.00880942 46.8268 2436.91 0.00 3619.01 2866.66
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 3619.627 3619.627 0.218662 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3619.63 3619.63 0.218662 18.81 13.25 0.00737523 40.00 20.96 0.00800000 3.80 0.00505843 3.80 13.2900 21.11 0.00773032 48.7367 1230.33 0.00 3624.38 3624.38
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 2052.238 2052.238 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2052.24 2052.24 0.218662 18.81 13.25 0.00737523 40.00 20.96 0.00800000 3.80 0.00505843 3.80 13.2900 21.11 0.00773032 48.7367 1230.33 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4408.588 3529.943 0.259834 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 4296.90 4088.14 0.259834 26.16 17.20 0.00880356 12.80 11.93 0.00850000 31.03 0.00823307 18.36 18.8535 23.89 0.00893717 47.4967 2892.21 0.00 4407.83 3492.14
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4408.588 4408.588 0.259834 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4408.59 4408.59 0.259834 17.85 12.73 0.00723445 40.00 20.96 0.00800000 3.80 0.00505843 3.80 18.8535 21.11 0.00774003 48.7970 1921.36 0.00 4414.38 4414.38
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 3279.010 3279.010 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3279.01 3279.01 0.259834 17.85 12.73 0.00723445 40.00 20.96 0.00800000 3.80 0.00505843 3.80 18.8535 21.11 0.00774003 48.7970 1921.36 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4345.382 3479.153 0.262505 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 4239.83 4095.04 0.262505 25.47 16.88 0.00870042 12.80 11.93 0.00850000 29.76 0.00823104 17.94 11.0703 23.89 0.00875866 46.5607 2922.59 0.00 4344.64 3441.44
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4345.382 4345.382 0.262505 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4345.38 4345.38 0.262505 19.19 13.45 0.00743407 40.00 20.96 0.00800000 3.80 0.00505843 3.80 11.0703 21.11 0.00772980 48.7335 1227.72 0.00 4351.09 4351.09
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 2049.150 2049.150 -999.0 -999.0 -999.000 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2049.15 2049.15 0.262505 19.19 13.45 0.00743407 40.00 20.96 0.00800000 3.80 0.00505843 3.80 11.0703 21.11 0.00772980 48.7335 1227.72 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5013.134 4012.421 0.288615 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.3332 1004.8586 1.1818 PSZ-AC:1 FAN Fan:OnOff 0.288615 0.34107908   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 Sensible 4905.20 4620.25 0.9785 0.34107908 0.288615 26.40 17.34 0.00887231 49149.2 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 323.280 4581.92 30.94 0.00823292 18.33 0.06462207 22.3904 23.89 0.00905677 23.89 0.00905861 48.1332 3211.00 0.00 5012.27 3969.34 0.32760903 26.67 19.44 0.01118466 55322.4 14.83 14.29 0.00993650 40022.8
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5013.134 5013.134 0.288615 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:1 FAN Fan:OnOff 0.288615 0.34107908   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 5013.13 5013.13 1.0000 0.34107908 0.288615 17.23 12.59 0.00734137 35913.2 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5013.13 3.80 0.00505843 3.80 0.06462207 22.3904 21.11 0.00800000 21.11 0.00800000 50.4139 693.67 0.00 5019.72 5019.72 0.33505210 21.11 15.56 0.00875166 43444.1 35.78 20.46 0.00875166 58426.0
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2777.989 2777.989 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:1 FAN Fan:OnOff 0.288615 0.34107908   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 2777.99 2777.99 1.0000 0.34107908 0.288615 17.23 12.59 0.00734137 35913.2 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2777.99 3.80 0.00505843 3.80 0.06462207 22.3904 21.11 0.00800000 21.11 0.00800000 50.4139 693.67 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4970.971 3976.938 0.295704 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.1571 1004.8586 1.1818 PSZ-AC:2 FAN Fan:OnOff 0.295704 0.34945629   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 Sensible 4828.36 4611.31 0.9713 0.34945629 0.295704 26.04 17.14 0.00877757 48548.2 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 331.220 4497.14 31.30 0.00823349 18.45 0.04898771 16.5665 23.89 0.00888560 23.89 0.00888560 47.2270 3295.93 0.00 4970.12 3934.48 0.33565541 26.67 19.44 0.01118466 55322.4 15.21 14.47 0.00997494 40515.2
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4970.971 4970.971 0.295704 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:2 FAN Fan:OnOff 0.295704 0.34945629   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4970.97 4970.97 1.0000 0.34945629 0.295704 18.24 12.95 0.00729954 36833.5 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4970.97 3.80 0.00505843 3.80 0.04898771 16.5665 21.11 0.00774453 21.11 0.00774453 48.8251 1958.51 0.00 4977.50 4977.50 0.34328129 21.11 15.56 0.00875166 43444.1 35.31 20.32 0.00875166 57943.9
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3322.943 3322.943 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:2 FAN Fan:OnOff 0.295704 0.34945629   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3322.94 3322.94 1.0000 0.34945629 0.295704 18.24 12.95 0.00729954 36833.5 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3322.94 3.80 0.00505843 3.80 0.04898771 16.5665 21.11 0.00774453 21.11 0.00774453 48.8251 1958.51 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 3619.627 2898.073 0.218662 -999.0 -999.000 -999.0000 1.06653 1.00000 1021.0720 1004.8586 1.1818 PSZ-AC:3 FAN Fan:OnOff 0.218662 0.25840967   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:40:00 Sensible 3578.53 3436.20 0.9886 0.25840967 0.218662 25.29 16.84 0.00873181 47656.8 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 244.925 3333.60 27.41 0.00822733 17.15 0.02906014 13.2900 23.89 0.00880913 23.89 0.00880942 46.8268 2436.91 0.00 3619.01 2866.66 0.24820444 26.67 19.44 0.01118466 55322.4 15.38 14.55 0.00999622 40741.6
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 3619.627 3619.627 0.218662 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:3 FAN Fan:OnOff 0.218662 0.25840967   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3619.63 3619.63 1.0000 0.25840967 0.218662 18.81 13.25 0.00737523 37603.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3619.63 3.80 0.00505843 3.80 0.02906014 13.2900 21.11 0.00773032 21.11 0.00773032 48.7367 1230.33 0.00 3624.38 3624.38 0.25384349 21.11 15.56 0.00875166 43444.1 35.09 20.25 0.00875166 57722.1
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2052.238 2052.238 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:3 FAN Fan:OnOff 0.218662 0.25840967   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2052.24 2052.24 1.0000 0.25840967 0.218662 18.81 13.25 0.00737523 37603.0 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2052.24 3.80 0.00505843 3.80 0.02906014 13.2900 21.11 0.00773032 21.11 0.00773032 48.7367 1230.33 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4408.588 3529.943 0.259834 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.2054 1004.8586 1.1818 PSZ-AC:4 FAN Fan:OnOff 0.259834 0.30706575   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 Sensible 4296.90 4088.14 0.9747 0.30706575 0.259834 26.16 17.20 0.00880356 48736.4 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 291.042 4005.86 31.03 0.00823307 18.36 0.04898771 18.8535 23.89 0.00893610 23.89 0.00893717 47.4967 2892.21 0.00 4407.83 3492.14 0.29493897 26.67 19.44 0.01118466 55322.4 15.10 14.42 0.00996739 40377.5
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4408.588 4408.588 0.259834 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:4 FAN Fan:OnOff 0.259834 0.30706575   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4408.59 4408.59 1.0000 0.30706575 0.259834 17.85 12.73 0.00723445 36265.4 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4408.59 3.80 0.00505843 3.80 0.04898771 18.8535 21.11 0.00774003 21.11 0.00774003 48.7970 1921.36 0.00 4414.38 4414.38 0.30163980 21.11 15.56 0.00875166 43444.1 35.44 20.36 0.00875166 58078.7
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3279.010 3279.010 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:4 FAN Fan:OnOff 0.259834 0.30706575   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3279.01 3279.01 1.0000 0.30706575 0.259834 17.85 12.73 0.00723445 36265.4 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3279.01 3.80 0.00505843 3.80 0.04898771 18.8535 21.11 0.00774003 21.11 0.00774003 48.7970 1921.36 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4345.382 3479.153 0.262505 -999.0 -999.000 -999.0000 1.04491 1.00000 1021.0136 1004.8586 1.1818 PSZ-AC:5 FAN Fan:OnOff 0.262505 0.31022227   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 Sensible 4239.83 4095.04 0.9757 0.31022227 0.262505 25.47 16.88 0.00870042 47761.9 12.80 11.93 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 294.033 3945.80 29.76 0.00823104 17.94 0.02906014 11.0703 23.89 0.00875885 23.89 0.00875866 46.5607 2922.59 0.00 4344.64 3441.44 0.29797084 26.67 19.44 0.01118466 55322.4 15.38 14.55 0.00999622 40741.6
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4345.382 4345.382 0.262505 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:5 FAN Fan:OnOff 0.262505 0.31022227   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4345.38 4345.38 1.0000 0.31022227 0.262505 19.19 13.45 0.00743407 38143.6 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4345.38 3.80 0.00505843 3.80 0.02906014 11.0703 21.11 0.00772980 21.11 0.00772980 48.7335 1227.72 0.00 4351.09 4351.09 0.30474055 21.11 15.56 0.00875166 43444.1 35.09 20.25 0.00875166 57722.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2049.150 2049.150 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1818 PSZ-AC:5 FAN Fan:OnOff 0.262505 0.31022227   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2049.15 2049.15 1.0000 0.31022227 0.262505 19.19 13.45 0.00743407 38143.6 40.00 20.96 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2049.15 3.80 0.00505843 3.80 0.02906014 11.0703 21.11 0.00772980 21.11 0.00772980 48.7335 1227.72 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 1758.00 1362.50 113.00
PERIMETER_ZN_1 1148.83 2210.67 135.50
PERIMETER_ZN_2 857.33 2037.50 47.50
PERIMETER_ZN_3 740.17 2818.50 104.50
PERIMETER_ZN_4 1220.83 2243.17 57.67
ATTIC 0.00 0.00 0.00
Facility 2028.33 3048.67 261.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 1.50 0.00 1.50
PERIMETER_ZN_1 0.17 17.67 0.17 17.67
PERIMETER_ZN_2 0.33 0.00 0.33 0.00
PERIMETER_ZN_3 0.50 0.00 0.50 0.00
PERIMETER_ZN_4 0.33 0.00 0.33 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.50 18.83 0.50 18.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.398 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.397 0.391 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.371 0.038 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.397 0.032 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.397 0.036 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762126.79 0.00 762126.79 0.00 762126.79 2037921.45 5484.00 3276.00 0.00 0.00
PERIMETER_ZN_1 577753.09 0.00 577753.09 649101.90 1226854.99 1544876.42 5484.00 3276.00 0.00 0.42
PERIMETER_ZN_2 276027.36 0.00 276027.36 85090.67 361118.03 916440.58 6239.94 2520.06 0.00 547.27
PERIMETER_ZN_3 577741.46 0.00 577741.46 127636.01 705377.47 1544876.42 5484.00 3276.00 0.00 0.00
PERIMETER_ZN_4 342723.67 0.00 342723.67 85090.67 427814.34 916440.58 5484.00 3276.00 0.00 0.00
Total Facility 2536372.36 0.00 2536372.36 946919.26 3483291.62 6960555.45 6239.94 3276.00 0.00 547.69


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0369 0.0743 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0021 0.0229 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0030 0.0405 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0020 0.0242 0.0291 1008.00 3276.00 0.00
Total Facility 0.1673 0.0000 0.1673 0.0440 0.2113 0.2207 1763.94 3276.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 1064386.89 0.00 1064386.89 2037921.45 5484.00 0.00 3276.00 0.00
PSZ-AC:2 806890.43 0.00 806890.43 1544876.42 5484.00 0.00 3276.00 0.42
PSZ-AC:3 385500.03 0.00 385500.03 916440.58 6239.04 0.17 2520.80 528.58
PSZ-AC:4 806874.19 0.00 806874.19 1544876.42 5484.00 0.00 3276.00 0.00
PSZ-AC:5 478648.15 0.00 478648.15 916440.58 5484.00 0.00 3276.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0690 0.0000 0.0690 0.0646 1008.00 0.00 3276.00
PSZ-AC:2 0.0523 0.0000 0.0523 0.0490 1008.00 0.00 3276.00
PSZ-AC:3 0.0290 0.0000 0.0290 0.0291 1008.00 0.00 2520.00
PSZ-AC:4 0.0523 0.0000 0.0523 0.0490 1008.00 0.00 3276.00
PSZ-AC:5 0.0310 0.0000 0.0310 0.0291 1008.00 0.00 3276.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3276.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3048.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0903 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0684 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0406 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0684 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0406 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 555
Defaulted Fields 365
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 140.24 1248.68 01-JAN-07:00 14516.43 16-OCT-12:50
Electricity:Building 75.05 677.68 01-JAN-00:10 5866.25 02-JAN-16:50
Electricity:Zone:CORE_ZN 22.88 198.41 01-JAN-00:10 1717.53 02-JAN-08:10
Electricity:SpaceType:GENERAL 75.05 677.68 01-JAN-00:10 5866.25 02-JAN-16:50
InteriorLights:Electricity 26.75 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.75 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
LightsWired:InteriorLights:Electricity 26.75 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.75 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_1 16.13 150.41 01-JAN-00:10 1302.00 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.41 24.42 01-JAN-00:10 563.96 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.41 24.42 01-JAN-00:10 563.96 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_2 9.73 89.23 01-JAN-00:10 772.36 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.37 14.49 01-JAN-00:10 334.55 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.37 14.49 01-JAN-00:10 334.55 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_3 16.60 150.41 01-JAN-00:10 1302.00 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.88 24.42 01-JAN-00:10 563.96 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.88 24.42 01-JAN-00:10 563.96 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_4 9.71 89.23 01-JAN-00:10 772.36 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.35 14.49 01-JAN-00:10 334.55 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.35 14.49 01-JAN-00:10 334.55 02-JAN-16:50
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
ElectricityPurchased:Plant 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
Cogeneration:ElectricityPurchased 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
General:Cogeneration:ElectricityPurchased 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
ElectricityNet:Plant 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
Cogeneration:ElectricityNet 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
General:Cogeneration:ElectricityNet 140.24 1248.68 14-JAN-09:40 14516.43 16-OCT-12:50
ExteriorLights:Electricity 9.77 0.00 01-JAN-07:00 1061.67 01-JAN-06:10
General:ExteriorLights:Electricity 9.77 0.00 01-JAN-07:00 1061.67 01-JAN-06:10
Electricity:HVAC 31.25 0.00 01-JAN-00:10 6752.41 02-JAN-06:20
Fans:Electricity 16.96 0.00 01-JAN-00:10 1484.50 23-MAR-08:00
General:Fans:Electricity 16.96 0.00 01-JAN-00:10 1484.50 23-MAR-08:00
Cooling:Electricity 13.87 0.00 01-JAN-00:10 4973.36 16-OCT-11:00
General:Cooling:Electricity 13.87 0.00 01-JAN-00:10 4973.36 16-OCT-11:00
Heating:Electricity 0.42 0.00 01-JAN-00:10 5267.91 02-JAN-06:20
General:Heating:Electricity 0.42 0.00 01-JAN-00:10 5267.91 02-JAN-06:20
Electricity:Plant 24.17 571.00 01-JAN-00:10 2790.93 31-JAN-13:00
WaterSystems:Electricity 24.17 571.00 01-JAN-00:10 2790.93 31-JAN-13:00
Water Heater:WaterSystems:Electricity 24.17 571.00 01-JAN-00:10 2790.93 31-JAN-13:00
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-09:40
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-09:40


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.00 0.00 01-JAN-00:10 3188.15 03-JAN-06:20
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 3188.15 03-JAN-06:20
Heating:NaturalGas 0.00 0.00 01-JAN-00:10 3188.15 03-JAN-06:20
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 3188.15 03-JAN-06:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 28-FEB-12:20
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 28-FEB-12:20
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 06-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 06-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 119.18 0.00 01-JAN-00:10 34525.49 02-JAN-06:20
EnergyTransfer:Building 53.96 0.00 01-JAN-00:10 16598.99 02-JAN-06:20
EnergyTransfer:Zone:CORE_ZN 18.32 0.00 01-JAN-00:10 4049.50 02-OCT-05:10
Heating:EnergyTransfer 0.98 0.00 01-JAN-00:10 16598.99 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_ZN 0.03 0.00 01-JAN-00:10 3112.29 02-JAN-06:10
General:Heating:EnergyTransfer 0.98 0.00 01-JAN-00:10 16598.99 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.03 0.00 01-JAN-00:10 3112.29 02-JAN-06:10
Cooling:EnergyTransfer 52.98 0.00 01-JAN-00:10 15186.64 16-OCT-14:30
Cooling:EnergyTransfer:Zone:CORE_ZN 18.30 0.00 01-JAN-00:10 4049.50 02-OCT-05:10
General:Cooling:EnergyTransfer 52.98 0.00 01-JAN-00:10 15186.64 16-OCT-14:30
General:Cooling:EnergyTransfer:Zone:CORE_ZN 18.30 0.00 01-JAN-00:10 4049.50 02-OCT-05:10
EnergyTransfer:Zone:PERIMETER_ZN_1 13.22 0.00 01-JAN-00:10 4488.67 30-OCT-12:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.41 0.00 01-JAN-00:10 3930.95 03-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.41 0.00 01-JAN-00:10 3930.95 03-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 12.80 0.00 01-JAN-00:10 4488.67 30-OCT-12:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 12.80 0.00 01-JAN-00:10 4488.67 30-OCT-12:20
EnergyTransfer:Zone:PERIMETER_ZN_2 6.70 0.00 01-JAN-00:10 2572.91 16-OCT-10:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.10 0.00 01-JAN-00:10 2567.86 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.10 0.00 01-JAN-00:10 2567.86 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 6.60 0.00 01-JAN-00:10 2572.91 16-OCT-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 6.60 0.00 01-JAN-00:10 2572.91 16-OCT-10:10
EnergyTransfer:Zone:PERIMETER_ZN_3 8.43 0.00 01-JAN-00:10 4476.37 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.28 0.00 01-JAN-00:10 4476.37 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.28 0.00 01-JAN-00:10 4476.37 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 8.15 0.00 01-JAN-00:10 2713.68 16-OCT-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 8.15 0.00 01-JAN-00:10 2713.68 16-OCT-13:30
EnergyTransfer:Zone:PERIMETER_ZN_4 7.29 0.00 01-JAN-00:10 2912.33 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.16 0.00 01-JAN-00:10 2912.33 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.16 0.00 01-JAN-00:10 2912.33 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 7.13 0.00 01-JAN-00:10 2807.39 16-OCT-15:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 7.13 0.00 01-JAN-00:10 2807.39 16-OCT-15:40
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 03-FEB-07:10 93.25 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 03-FEB-07:10 93.25 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 03-FEB-07:10 93.25 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 03-FEB-07:10 93.25 02-JAN-07:10
EnergyTransfer:HVAC 65.22 0.00 01-JAN-00:10 18830.93 16-OCT-12:10
CoolingCoils:EnergyTransfer 63.98 0.00 01-JAN-00:10 18830.93 16-OCT-12:10
HeatingCoils:EnergyTransfer 1.24 0.00 01-JAN-00:10 17926.49 02-JAN-06:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 03-FEB-07:10 93.25 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 03-FEB-07:10 93.25 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 03-FEB-07:10 93.25 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.026 -18.295 0.000 0.000 4.989 8.739 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -9.599
PERIMETER_ZN_1 0.000 0.000 0.412 -12.804 0.000 0.000 3.828 5.408 10.719 16.332 0.000 0.078 0.000 0.000 -7.714 0.000 -4.872 -11.386
PERIMETER_ZN_2 0.000 0.000 0.102 -6.597 0.000 0.000 1.657 3.368 6.359 7.053 0.000 0.005 0.000 0.000 -3.963 0.000 -0.795 -7.188
PERIMETER_ZN_3 0.000 0.000 0.281 -8.152 0.000 0.000 3.862 5.883 10.719 3.505 0.000 0.010 0.000 0.000 -5.936 0.000 -1.126 -9.046
PERIMETER_ZN_4 0.000 0.000 0.156 -7.130 0.000 0.000 2.266 3.353 6.359 8.094 0.000 0.006 0.000 0.000 -4.179 0.000 -0.814 -8.111
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 11.033 37.094 0.000 0.000 0.000 -48.127 -0.000
Total Facility 0.000 0.000 0.978 -52.979 0.000 0.000 16.601 26.750 48.296 34.984 0.000 11.132 37.095 0.000 -21.792 0.000 -55.735 -45.330


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 16-OCT-05:01 0.00 0.00 0.00 -5185.25 0.00 0.00 51.14 32.22 486.79 0.00 0.00 0.00 4615.09 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 17-OCT-05:01 0.00 0.00 0.00 -4880.75 0.00 0.00 40.23 24.42 369.02 0.00 0.00 0.00 5192.94 0.00 -471.04 0.00 -274.82 0.00
PERIMETER_ZN_2 17-OCT-05:01 0.00 0.00 0.00 -3404.14 0.00 0.00 25.91 14.49 218.91 0.00 0.00 0.00 3426.10 0.00 -231.51 0.00 -49.76 0.00
PERIMETER_ZN_3 17-OCT-05:01 0.00 0.00 0.00 -4277.09 0.00 0.00 45.09 24.42 369.02 0.00 0.00 0.00 4243.94 0.00 -333.55 0.00 -71.83 0.00
PERIMETER_ZN_4 17-OCT-05:01 0.00 0.00 0.00 -4020.50 0.00 0.00 25.58 14.49 218.91 0.00 0.00 0.00 4047.88 0.00 -236.24 0.00 -50.12 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-OCT-05:01 0.00 0.00 0.00 -21674.84 0.00 0.00 189.26 110.04 1662.65 0.00 0.00 1514.79 19916.95 0.00 -1272.34 0.00 -446.52 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-06:01 0.00 0.00 5056.19 0.00 0.00 0.00 79.95 32.22 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -5655.16
PERIMETER_ZN_1 03-JAN-06:12 0.00 0.00 5978.08 0.00 0.00 0.00 55.22 144.12 369.02 0.00 0.00 0.00 0.00 0.00 -692.73 0.00 -475.32 -5378.39
PERIMETER_ZN_2 03-JAN-06:12 0.00 0.00 4794.98 0.00 0.00 0.00 32.75 85.49 218.91 0.00 0.00 0.00 0.00 0.00 -363.34 0.00 -51.03 -4717.77
PERIMETER_ZN_3 03-JAN-06:12 0.00 0.00 6205.58 0.00 0.00 0.00 55.79 144.12 369.02 0.00 0.00 0.00 0.00 0.00 -535.44 0.00 -72.82 -6166.25
PERIMETER_ZN_4 09-JAN-06:01 0.00 0.00 5034.62 0.00 0.00 0.00 35.29 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -416.73 0.00 -121.23 -4765.34
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-JAN-06:12 0.00 0.00 24459.89 0.00 0.00 0.00 249.36 649.35 1662.65 0.00 0.00 1205.51 0.00 0.00 -1952.32 0.00 -650.74 -25623.70



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2886 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2886 0.2239 1.0000 Not calculated 0.0646 0.2239    
PSZ-AC:2 0.2957 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2957 0.1657 1.0000 Not calculated 0.0490 0.1657    
PSZ-AC:3 0.2187 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2187 0.1329 1.0000 Not calculated 0.0291 0.1329    
PSZ-AC:4 0.2598 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2598 0.1885 1.0000 Not calculated 0.0490 0.1885    
PSZ-AC:5 0.2625 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2625 0.1107 1.0000 Not calculated 0.0291 0.1107    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2886 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2886 1.0000 1.0000 Not calculated 0.0646 0.2239    
PSZ-AC:2 0.2957 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2957 1.0000 1.0000 Not calculated 0.0490 0.1657    
PSZ-AC:3 0.2187 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2187 1.0000 1.0000 Not calculated 0.0291 0.1329    
PSZ-AC:4 0.2598 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2598 1.0000 1.0000 Not calculated 0.0490 0.1885    
PSZ-AC:5 0.2625 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2625 1.0000 1.0000 Not calculated 0.0291 0.1107    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2886 0.2886 0.2886 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2957 0.2957 0.2957 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2187 0.2187 0.2187 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2598 0.2598 0.2598 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2625 0.2625 0.2625 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2886 0.2886 0.2886 0.2886 0.0646 1.0000
PSZ-AC:2 0.2957 0.2957 0.2957 0.2957 0.0490 1.0000
PSZ-AC:3 0.2187 0.2187 0.2187 0.2187 0.0291 1.0000
PSZ-AC:4 0.2598 0.2598 0.2598 0.2598 0.0490 1.0000
PSZ-AC:5 0.2625 0.2625 0.2625 0.2625 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2886 0.2886 0.2886 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2957 0.2957 0.2957 No 0.0490 0.4745 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2187 0.2187 0.2187 No 0.0291 0.4481 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2598 0.2598 0.2598 No 0.0490 0.4837 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2625 0.2625 0.2625 No 0.0291 0.4490 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2886 0.2886 0.2886 0.2886 0.0646 1.0000
PSZ-AC:2 0.2957 0.2957 0.2957 0.2957 0.0490 1.0000
PSZ-AC:3 0.2187 0.2187 0.2187 0.2187 0.0291 1.0000
PSZ-AC:4 0.2598 0.2598 0.2598 0.2598 0.0490 1.0000
PSZ-AC:5 0.2625 0.2625 0.2625 0.2625 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.50
Number of hours cooling loads not met 18.83
Number of hours not met 19.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.42 5267.91 0.00 3188.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 13.87 4973.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.75 2540.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.77 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 16.96 1484.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 24.17 2790.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 140.24
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 48.30 140.24


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 52.33
Space Heating 0.83
Space Cooling 27.14
Fans (All) 33.18
Service Water Heating 47.28
Receptacle Equipment 94.48
Miscellaneous (All) 274.36
Subtotal 274.36


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.01
Service Water Heating 0.00
Miscellaneous (All) 0.01
Subtotal 0.01


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 19.07
Space Heating 0.31
Space Cooling 9.89
Fans (All) 12.09
Service Water Heating 17.23
Receptacle Equipment 34.44
Miscellaneous 6.97


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2885. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365
HTGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL January 20.55 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 8749.00 11.00 0.00 0.00 0.00
PERIMETER_ZN_1 8677.17 82.83 0.00 0.00 0.00
PERIMETER_ZN_2 8700.83 59.17 0.00 0.00 0.00
PERIMETER_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 8592.83 167.17 0.00 0.00 0.00
ATTIC 6113.33 809.33 689.83 1011.00 136.50
Min 6113.33 0.00 0.00 0.00 0.00
Max 8760.00 809.33 689.83 1011.00 136.50
Average 8265.53 188.25 114.97 168.50 22.75
Sum 49593.17 1129.50 689.83 1011.00 136.50


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 6809.17 1950.83 0.00 0.00 0.00
PERIMETER_ZN_1 7985.00 775.00 0.00 0.00 0.00
PERIMETER_ZN_2 8177.17 582.83 0.00 0.00 0.00
PERIMETER_ZN_3 8291.17 468.83 0.00 0.00 0.00
PERIMETER_ZN_4 8041.67 718.33 0.00 0.00 0.00
ATTIC 6149.50 1256.50 401.00 426.17 526.83
Min 6149.50 468.83 0.00 0.00 0.00
Max 8291.17 1950.83 401.00 426.17 526.83
Average 7575.61 958.72 66.83 71.03 87.81
Sum 45453.67 5752.33 401.00 426.17 526.83


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17843.67 48.33 0.00 0.00 0.00
PERIMETER_ZN_1 13305.67 50.33 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13355.33 0.67 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17843.67 50.33 0.00 0.00 0.00
Average 9349.44 16.56 0.00 0.00 0.00
Sum 56096.67 99.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:39

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.221
February 13.282
March 12.638
April 15.303
May 15.556
June 17.667
July 19.435
August 19.664
September 18.470
October 18.770
November 14.323
December 13.589
   
Annual Sum or Average 16.011
Minimum of Months 12.638
Maximum of Months 19.664



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.973214E+09 2226.75 25-JAN-06:05 16.00 11.06 0.288459E+09 402.35 25-JAN-10:50 17.83 13.12
February 0.915309E+09 1989.59 03-FEB-15:53 21.00 10.02 0.265595E+09 402.35 09-FEB-13:00 15.30 10.94
March 0.107158E+10 2206.53 24-MAR-05:05 12.00 12.00 0.320540E+09 402.34 28-MAR-15:50 12.00 7.97
April 0.126895E+10 4154.60 28-APR-05:03 14.00 12.23 0.282439E+09 402.36 28-APR-13:50 18.83 14.27
May 0.152964E+10 4301.15 02-MAY-05:03 13.17 11.36 0.311393E+09 402.36 24-MAY-13:09 21.00 15.42
June 0.183367E+10 4307.75 07-JUN-05:03 13.17 12.03 0.312247E+09 402.36 26-JUN-12:09 23.00 18.43
July 0.208517E+10 4228.88 06-JUL-05:02 14.33 13.55 0.284530E+09 402.36 11-JUL-12:09 21.17 16.67
August 0.236806E+10 4257.58 22-AUG-05:02 15.00 13.18 0.327099E+09 402.36 03-AUG-12:09 15.00 13.18
September 0.180055E+10 4257.11 20-SEP-05:03 12.00 10.91 0.283982E+09 402.36 26-SEP-13:50 19.00 15.88
October 0.199329E+10 5185.50 16-OCT-05:01 18.67 9.56 0.298229E+09 402.36 06-OCT-10:00 18.67 9.56
November 0.134865E+10 4401.06 02-NOV-05:03 11.67 10.11 0.296548E+09 402.36 01-NOV-14:30 11.67 10.11
December 0.110736E+10 2578.89 08-DEC-06:05 11.95 11.53 0.281141E+09 402.35 07-DEC-11:00 11.95 11.53
                     
Annual Sum or Average 0.182954E+11         0.355220E+10        
Minimum of Months 0.915309E+09 1989.59   11.67 9.56 0.265595E+09 402.34   11.67 7.97
Maximum of Months 0.236806E+10 5185.50   21.00 13.55 0.327099E+09 402.36   23.00 18.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.114120E+10 3524.75 20-JAN-13:05 18.67 15.16 0.218448E+09 305.01 31-JAN-14:30 15.00 11.91
February 0.742220E+09 3031.64 03-FEB-14:20 23.00 8.84 0.194414E+09 305.01 16-FEB-14:09 17.02 13.92
March 0.554111E+09 2557.85 23-MAR-14:00 23.00 17.27 0.228875E+09 305.02 24-MAR-12:00 19.00 15.88
April 0.565178E+09 2115.44 26-APR-13:50 26.17 16.81 0.207593E+09 305.94 03-APR-09:00 26.17 16.81
May 0.500254E+09 1737.15 04-MAY-13:53 23.00 16.67 0.229124E+09 305.01 02-MAY-13:39 23.00 16.67
June 0.747957E+09 1776.34 30-JUN-14:40 23.00 17.85 0.233041E+09 305.01 12-JUN-12:09 23.00 17.85
July 0.109666E+10 3336.84 24-JUL-05:02 16.83 16.83 0.214225E+09 305.02 19-JUL-13:39 16.83 16.83
August 0.141901E+10 3543.06 21-AUG-05:02 16.92 15.63 0.246506E+09 305.02 07-AUG-13:09 16.92 15.63
September 0.133359E+10 4077.86 29-SEP-16:52 30.00 16.76 0.214515E+09 363.18 29-SEP-12:09 30.00 16.76
October 0.196814E+10 4880.90 17-OCT-05:01 17.00 8.55 0.227354E+09 398.30 16-OCT-12:09 17.00 8.55
November 0.141066E+10 3804.94 28-NOV-13:30 24.50 10.63 0.222343E+09 305.01 09-NOV-14:00 24.50 10.63
December 0.132532E+10 4182.37 19-DEC-13:00 26.00 11.60 0.210149E+09 305.01 01-DEC-11:50 26.00 11.60
                     
Annual Sum or Average 0.128043E+11         0.264659E+10        
Minimum of Months 0.500254E+09 1737.15   16.83 8.55 0.194414E+09 305.01   15.00 8.55
Maximum of Months 0.196814E+10 4880.90   30.00 17.85 0.246506E+09 398.30   30.00 17.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.228524E+09 2557.39 18-JAN-11:02 23.17 14.12 92969224.82 190.45 27-JAN-13:09 18.00 12.39
February 0.183012E+09 2060.00 22-FEB-15:02 17.50 12.38 83941469.18 190.45 01-FEB-13:09 17.50 12.38
March 0.216798E+09 2940.30 24-MAR-10:01 17.17 14.66 0.100573E+09 190.52 09-MAR-13:09 17.17 14.66
April 0.468922E+09 3113.73 14-APR-14:02 18.00 12.03 92034772.85 190.45 27-APR-12:09 21.00 15.98
May 0.531841E+09 3096.81 02-MAY-10:02 21.17 15.13 0.101706E+09 190.45 24-MAY-12:09 21.00 15.42
June 0.707617E+09 3020.37 06-JUN-10:02 19.33 14.38 0.102615E+09 190.45 29-JUN-12:09 24.00 19.31
July 0.985777E+09 3103.03 10-JUL-10:02 21.17 15.59 94002703.37 190.45 13-JUL-12:09 23.00 18.43
August 0.112903E+10 3036.53 23-AUG-10:02 23.17 16.83 0.108041E+09 190.45 02-AUG-12:09 23.17 16.83
September 0.717863E+09 3007.20 12-SEP-10:02 22.83 17.20 93570790.61 190.45 29-SEP-12:09 36.00 18.21
October 0.798479E+09 3404.22 17-OCT-05:01 17.00 8.55 98192569.44 190.45 13-OCT-12:09 17.00 8.55
November 0.370043E+09 3228.85 01-NOV-10:01 16.17 13.01 96570020.51 190.45 29-NOV-13:09 22.83 9.56
December 0.258913E+09 2678.81 19-DEC-11:02 25.00 11.06 90507768.78 190.45 19-DEC-13:09 25.50 11.30
                     
Annual Sum or Average 0.659682E+10         0.115472E+10        
Minimum of Months 0.183012E+09 2060.00   16.17 8.55 83941469.18 190.45   17.00 8.55
Maximum of Months 0.112903E+10 3404.22   25.00 17.20 0.108041E+09 190.52   36.00 19.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.256037E+09 1057.65 18-JAN-15:25 22.50 15.11 0.205363E+09 308.55 13-JAN-13:09 22.50 15.11
February 0.207772E+09 917.39 03-FEB-15:35 21.67 9.69 0.187424E+09 305.00 07-FEB-16:40 14.67 10.04
March 0.280428E+09 1069.49 23-MAR-15:53 21.00 17.19 0.223532E+09 304.99 03-MAR-15:30 21.00 17.19
April 0.493293E+09 1472.23 26-APR-14:27 24.50 16.53 0.208410E+09 305.01 26-APR-12:50 24.50 16.53
May 0.691728E+09 1729.27 04-MAY-14:02 22.83 16.63 0.232328E+09 305.01 02-MAY-13:39 22.83 16.63
June 0.957090E+09 1837.68 30-JUN-14:40 23.00 17.85 0.235065E+09 305.01 23-JUN-13:50 23.00 17.85
July 0.123034E+10 3213.37 28-JUL-05:02 17.00 17.00 0.215024E+09 305.02 20-JUL-13:50 17.00 17.00
August 0.135259E+10 3219.25 01-AUG-05:02 17.00 15.07 0.246984E+09 305.02 10-AUG-13:00 24.00 18.72
September 0.930945E+09 2381.04 29-SEP-14:23 33.50 17.67 0.213961E+09 305.01 01-SEP-13:09 33.50 17.67
October 0.103401E+10 4277.21 17-OCT-05:01 17.00 8.55 0.224047E+09 305.02 03-OCT-12:39 17.00 8.55
November 0.441044E+09 1142.95 10-NOV-14:23 19.50 15.78 0.218357E+09 305.36 27-NOV-13:09 23.00 9.44
December 0.276781E+09 1013.22 07-DEC-15:13 18.67 15.17 0.202024E+09 305.00 01-DEC-13:30 18.67 15.17
                     
Annual Sum or Average 0.815205E+10         0.261252E+10        
Minimum of Months 0.207772E+09 917.39   17.00 8.55 0.187424E+09 304.99   14.67 8.55
Maximum of Months 0.135259E+10 4277.21   33.50 17.85 0.246984E+09 308.55   33.50 18.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.251689E+09 1258.07 18-JAN-15:25 22.50 15.11 0.126000E+09 181.01 23-JAN-11:20 18.33 11.76
February 0.213892E+09 1316.62 01-FEB-16:23 17.50 15.03 0.114597E+09 180.94 02-FEB-09:30 16.00 12.29
March 0.243686E+09 1635.41 23-MAR-16:00 21.00 17.19 0.136914E+09 181.19 22-MAR-09:39 21.00 17.19
April 0.485737E+09 1942.53 26-APR-15:55 22.00 16.41 0.125786E+09 180.94 26-APR-13:39 22.00 16.41
May 0.573709E+09 1879.91 03-MAY-15:55 21.00 15.00 0.139256E+09 180.94 04-MAY-12:50 23.17 16.65
June 0.774697E+09 2805.85 26-JUN-05:02 17.17 15.13 0.140426E+09 180.94 07-JUN-15:20 17.17 15.13
July 0.102190E+10 3493.89 10-JUL-05:02 17.00 13.94 0.128382E+09 180.94 24-JUL-14:09 26.83 20.15
August 0.114818E+10 3155.09 01-AUG-05:02 17.00 15.07 0.147456E+09 180.94 17-AUG-14:30 27.35 20.98
September 0.823704E+09 2560.20 29-SEP-15:53 32.00 16.86 0.127784E+09 180.94 18-SEP-15:20 32.00 16.86
October 0.851182E+09 4020.60 17-OCT-05:01 17.00 8.55 0.133750E+09 180.94 20-OCT-13:09 20.83 15.02
November 0.443884E+09 1430.52 10-NOV-15:35 18.33 15.59 0.131536E+09 181.45 28-NOV-08:50 19.67 7.55
December 0.298169E+09 1362.12 19-DEC-15:35 21.33 8.71 0.122792E+09 181.10 07-DEC-08:50 21.33 8.71
                     
Annual Sum or Average 0.713043E+10         0.157468E+10        
Minimum of Months 0.213892E+09 1258.07   17.00 8.55 0.114597E+09 180.94   16.00 7.55
Maximum of Months 0.114818E+10 4020.60   32.00 17.19 0.147456E+09 181.45   32.00 20.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83 8.36 0.00 0.00 01-JAN-00:10 8.83 8.36
February 0.00 0.00 01-FEB-00:10 13.23 11.35 0.00 0.00 01-FEB-00:10 13.23 11.35
March 0.00 0.00 01-MAR-00:10 7.63 6.62 0.00 0.00 01-MAR-00:10 7.63 6.62
April 0.00 0.00 01-APR-00:10 9.63 8.61 0.00 0.00 01-APR-00:10 9.63 8.61
May 0.00 0.00 01-MAY-00:10 15.20 14.50 0.00 0.00 01-MAY-00:10 15.20 14.50
June 0.00 0.00 01-JUN-00:10 13.07 12.03 0.00 0.00 01-JUN-00:10 13.07 12.03
July 0.00 0.00 01-JUL-00:10 16.43 15.81 0.00 0.00 01-JUL-00:10 16.43 15.81
August 0.00 0.00 01-AUG-00:10 18.07 17.20 0.00 0.00 01-AUG-00:10 18.07 17.20
September 0.00 0.00 01-SEP-00:10 16.07 14.83 0.00 0.00 01-SEP-00:10 16.07 14.83
October 0.00 0.00 01-OCT-00:10 18.42 17.39 0.00 0.00 01-OCT-00:10 18.42 17.39
November 0.00 0.00 01-NOV-00:10 14.77 11.07 0.00 0.00 01-NOV-00:10 14.77 11.07
December 0.00 0.00 01-DEC-00:10 10.63 5.44 0.00 0.00 01-DEC-00:10 10.63 5.44
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   7.63 5.44 0.00 0.00   7.63 5.44
Maximum of Months 0.00 0.00   18.42 17.39 0.00 0.00   18.42 17.39



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 19724202.46 5056.22 02-JAN-06:01 11.00
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 41749.67 95.28 26-APR-17:02 21.50
May 0.00 0.00 01-MAY-00:10 15.20
June 269068.26 169.64 29-JUN-17:03 22.83
July 2347054.10 268.24 18-JUL-17:12 24.00
August 754012.94 181.77 17-AUG-17:02 22.92
September 1913483.16 677.06 29-SEP-17:02 29.50
October 1158789.63 436.59 16-OCT-17:02 26.50
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 26208360.22      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 19724202.46 5056.22   29.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 95681870.14 5978.16 03-JAN-06:12 4.33
February 52190277.17 4431.84 27-FEB-06:02 11.00
March 0.156829E+09 4149.12 01-MAR-06:02 7.00
April 34074551.40 1606.56 03-APR-06:10 10.17
May 24750764.37 1689.00 15-MAY-05:05 8.50
June 4817854.58 606.22 13-JUN-06:10 13.67
July 6258522.15 286.76 18-JUL-17:12 24.00
August 5366686.14 205.31 17-AUG-17:02 22.92
September 2456072.13 526.89 29-SEP-17:12 29.00
October 1661338.36 303.42 16-OCT-17:02 26.50
November 591707.85 591.96 24-NOV-07:10 8.75
December 27835070.22 1923.64 13-DEC-07:10 7.17
         
Annual Sum or Average 0.412514E+09      
Minimum of Months 591707.85 205.31   4.33
Maximum of Months 0.156829E+09 5978.16   29.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42044092.51 4795.03 03-JAN-06:12 4.33
February 12395473.76 3643.02 27-FEB-06:02 11.00
March 23320051.68 3566.77 06-MAR-06:03 11.17
April 668131.06 216.99 03-APR-10:04 22.67
May 604822.35 303.28 15-MAY-05:05 8.50
June 1676099.48 151.57 29-JUN-17:03 22.83
July 4678326.43 208.34 18-JUL-17:12 24.00
August 4222692.32 153.80 15-AUG-17:12 22.33
September 2091889.44 373.17 29-SEP-17:12 29.00
October 3107710.49 248.78 16-OCT-17:02 26.50
November 768758.77 327.53 27-NOV-06:03 10.67
December 6610628.36 1812.53 26-DEC-06:03 7.00
         
Annual Sum or Average 0.102189E+09      
Minimum of Months 604822.35 151.57   4.33
Maximum of Months 42044092.51 4795.03   29.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128910E+09 6205.64 03-JAN-06:12 4.33
February 37273977.55 4376.13 27-FEB-06:02 11.00
March 60903874.85 4348.35 06-MAR-06:03 11.17
April 3918605.19 1456.16 03-APR-05:05 10.83
May 305898.48 830.09 15-MAY-05:05 8.50
June 487861.61 170.80 29-JUN-17:03 22.83
July 3160492.89 245.93 18-JUL-17:12 24.00
August 2069255.88 178.64 17-AUG-17:02 22.92
September 1766091.55 546.26 29-SEP-17:02 29.50
October 2056597.00 371.38 16-OCT-17:02 26.50
November 6093482.84 3045.30 27-NOV-06:03 10.67
December 34115844.21 3595.86 26-DEC-06:03 7.00
         
Annual Sum or Average 0.281062E+09      
Minimum of Months 305898.48 170.80   4.33
Maximum of Months 0.128910E+09 6205.64   29.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 65063387.90 5034.72 09-JAN-06:01 2.17
February 18286841.32 4370.62 27-FEB-06:02 11.00
March 32246290.14 3741.68 01-MAR-06:02 7.00
April 2354621.49 242.59 03-APR-09:42 22.50
May 1333109.77 102.22 15-MAY-09:43 18.67
June 1913579.08 148.24 26-JUN-05:04 17.17
July 4159706.38 222.12 18-JUL-17:12 24.00
August 3827537.37 183.49 03-AUG-05:04 18.00
September 2599193.45 400.17 29-SEP-17:12 29.00
October 4403150.91 235.21 16-OCT-17:02 26.50
November 4081459.25 220.01 27-NOV-09:43 21.83
December 16072922.40 1415.11 13-DEC-06:03 6.17
         
Annual Sum or Average 0.156342E+09      
Minimum of Months 1333109.77 102.22   2.17
Maximum of Months 65063387.90 5034.72   29.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 8.83
February 0.00 0.00 01-FEB-00:10 13.23
March 0.00 0.00 01-MAR-00:10 7.63
April 0.00 0.00 01-APR-00:10 9.63
May 0.00 0.00 01-MAY-00:10 15.20
June 0.00 0.00 01-JUN-00:10 13.07
July 0.00 0.00 01-JUL-00:10 16.43
August 0.00 0.00 01-AUG-00:10 18.07
September 0.00 0.00 01-SEP-00:10 16.07
October 0.00 0.00 01-OCT-00:10 18.42
November 0.00 0.00 01-NOV-00:10 14.77
December 0.00 0.00 01-DEC-00:10 10.63
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.63
Maximum of Months 0.00 0.00   18.42



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.729889E+09 743.94 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.660244E+09 743.94 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.791184E+09 743.94 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.696458E+09 743.94 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.760537E+09 743.94 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.757753E+09 743.94 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.699242E+09 743.94 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.791184E+09 743.94 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.696458E+09 743.94 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.729889E+09 743.94 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.727106E+09 743.94 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.699242E+09 743.94 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.873919E+10     0.141401E+11    
Minimum of Months 0.660244E+09 743.94   0.107295E+10 973.59  
Maximum of Months 0.791184E+09 743.94   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.457159E+09 563.96 02-JAN-16:49 0.899552E+09 738.04 02-JAN-08:09
February 0.406424E+09 553.65 27-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.487804E+09 531.91 16-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.425631E+09 528.34 21-APR-15:00 0.862580E+09 738.04 03-APR-07:10
May 0.468026E+09 523.63 09-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.470313E+09 518.95 09-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.432547E+09 511.00 12-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.482709E+09 523.39 21-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.429246E+09 538.03 18-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.454512E+09 536.06 24-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.453299E+09 563.96 06-NOV-16:00 0.888667E+09 738.04 01-NOV-07:10
December 0.440013E+09 563.96 01-DEC-16:40 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.540768E+10     0.107191E+11    
Minimum of Months 0.406424E+09 511.00   0.813362E+09 738.04  
Maximum of Months 0.487804E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.288719E+09 334.55 02-JAN-16:49 0.533626E+09 437.82 02-JAN-08:09
February 0.255324E+09 329.41 27-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.303053E+09 318.01 02-MAR-16:00 0.565383E+09 437.82 01-MAR-08:09
April 0.264325E+09 317.72 21-APR-15:00 0.511694E+09 437.82 03-APR-07:10
May 0.287974E+09 307.02 09-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.286743E+09 302.67 09-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.264055E+09 299.03 28-JUL-15:39 0.518151E+09 437.82 03-JUL-07:10
August 0.299431E+09 306.56 21-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.268125E+09 318.71 21-SEP-07:30 0.510887E+09 437.82 01-SEP-07:10
October 0.287437E+09 323.04 20-OCT-15:00 0.534030E+09 437.82 02-OCT-07:10
November 0.285101E+09 334.55 06-NOV-16:00 0.527169E+09 437.82 01-NOV-07:10
December 0.278008E+09 334.55 01-DEC-16:40 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.336830E+10     0.635872E+10    
Minimum of Months 0.255324E+09 299.03   0.482497E+09 437.82  
Maximum of Months 0.303053E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.517182E+09 563.96 02-JAN-16:49 0.899552E+09 738.04 02-JAN-08:09
February 0.456557E+09 554.95 27-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.535153E+09 537.75 16-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.459863E+09 531.85 21-APR-15:00 0.862580E+09 738.04 03-APR-07:10
May 0.482785E+09 525.31 09-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.476864E+09 518.69 09-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.444584E+09 510.31 12-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.516739E+09 526.04 21-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.471863E+09 541.39 21-SEP-07:30 0.861220E+09 738.04 01-SEP-07:10
October 0.511217E+09 542.39 24-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.511105E+09 563.96 06-NOV-16:00 0.888667E+09 738.04 01-NOV-07:10
December 0.498826E+09 563.96 01-DEC-16:40 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.588274E+10     0.107191E+11    
Minimum of Months 0.444584E+09 510.31   0.813362E+09 738.04  
Maximum of Months 0.535153E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.288179E+09 334.55 02-JAN-16:49 0.533626E+09 437.82 02-JAN-08:09
February 0.253477E+09 328.52 27-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.301980E+09 320.95 16-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.264443E+09 316.79 05-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.285810E+09 315.66 09-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.284274E+09 313.36 09-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.262983E+09 310.90 12-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.298727E+09 316.35 21-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.266488E+09 322.44 21-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.285155E+09 322.80 24-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.283126E+09 334.55 06-NOV-16:00 0.527169E+09 437.82 01-NOV-07:10
December 0.277857E+09 334.55 01-DEC-16:40 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.335250E+10     0.635872E+10    
Minimum of Months 0.253477E+09 310.90   0.482497E+09 437.82  
Maximum of Months 0.301980E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.729889E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.696458E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.760537E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.757753E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.699242E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.696458E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.729889E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.727106E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.699242E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.873919E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.457159E+09 0.899552E+09 0.00 0.00 0.00 0.00 1232787.78 0.559201E+09
February 0.488155E+09 0.406424E+09 0.813362E+09 0.00 0.00 0.00 0.00 612140.70 0.534657E+09
March 0.590925E+09 0.487804E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.00 0.655748E+09
April 0.513848E+09 0.425631E+09 0.862580E+09 0.00 0.00 0.00 0.00 2051344.40 0.395334E+09
May 0.565233E+09 0.468026E+09 0.926320E+09 0.00 0.00 0.00 0.00 30391.16 0.410792E+09
June 0.565233E+09 0.470313E+09 0.914754E+09 0.00 0.00 0.00 0.00 541687.01 0.289227E+09
July 0.513848E+09 0.432547E+09 0.873466E+09 0.00 0.00 0.00 0.00 12278765.78 0.189509E+09
August 0.590925E+09 0.482709E+09 0.953087E+09 0.00 0.00 0.00 0.00 12316013.10 0.220514E+09
September 0.513848E+09 0.429246E+09 0.861220E+09 0.00 0.00 0.00 0.00 17111141.49 0.270723E+09
October 0.539540E+09 0.454512E+09 0.900233E+09 0.00 0.00 0.00 0.00 29792538.17 0.297858E+09
November 0.539540E+09 0.453299E+09 0.888667E+09 0.00 0.00 0.00 0.00 146614.54 0.521827E+09
December 0.513848E+09 0.440013E+09 0.872785E+09 0.00 0.00 0.00 0.00 1872427.43 0.527007E+09
                   
Annual Sum or Average 0.647448E+10 0.540768E+10 0.107191E+11 0.00 0.00 0.00 0.00 77985851.56 0.487240E+10
Minimum of Months 0.488155E+09 0.406424E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.189509E+09
Maximum of Months 0.590925E+09 0.487804E+09 0.953087E+09 0.00 0.00 0.00 0.00 29792538.17 0.655748E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.288719E+09 0.533626E+09 0.00 0.00 0.00 0.00 166364.61 78441938.53
February 0.211974E+09 0.255324E+09 0.482497E+09 0.00 0.00 0.00 0.00 10863.51 90615473.62
March 0.256600E+09 0.303053E+09 0.565383E+09 0.00 0.00 0.00 0.00 0.00 0.102141E+09
April 0.223130E+09 0.264325E+09 0.511694E+09 0.00 0.00 0.00 0.00 84097.02 62656111.50
May 0.245443E+09 0.287974E+09 0.549505E+09 0.00 0.00 0.00 0.00 773.74 75667899.82
June 0.245443E+09 0.286743E+09 0.542644E+09 0.00 0.00 0.00 0.00 8962.28 44956841.35
July 0.223130E+09 0.264055E+09 0.518151E+09 0.00 0.00 0.00 0.00 489754.92 36758225.03
August 0.256600E+09 0.299431E+09 0.565383E+09 0.00 0.00 0.00 0.00 441426.16 43893534.13
September 0.223130E+09 0.268125E+09 0.510887E+09 0.00 0.00 0.00 0.00 742859.95 37933843.28
October 0.234287E+09 0.287437E+09 0.534030E+09 0.00 0.00 0.00 0.00 2641120.77 58233712.73
November 0.234287E+09 0.285101E+09 0.527169E+09 0.00 0.00 0.00 0.00 165903.24 80022021.40
December 0.223130E+09 0.278008E+09 0.517747E+09 0.00 0.00 0.00 0.00 79962.59 83914267.67
                   
Annual Sum or Average 0.281144E+10 0.336830E+10 0.635872E+10 0.00 0.00 0.00 0.00 4832088.80 0.795235E+09
Minimum of Months 0.211974E+09 0.255324E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 36758225.03
Maximum of Months 0.256600E+09 0.303053E+09 0.565383E+09 0.00 0.00 0.00 0.00 2641120.77 0.102141E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.517182E+09 0.899552E+09 0.00 0.00 0.00 0.00 466946.99 0.110296E+09
February 0.488155E+09 0.456557E+09 0.813362E+09 0.00 0.00 0.00 0.00 22287.90 0.130068E+09
March 0.590925E+09 0.535153E+09 0.953087E+09 0.00 0.00 0.00 0.00 73414.04 0.147212E+09
April 0.513848E+09 0.459863E+09 0.862580E+09 0.00 0.00 0.00 0.00 742902.22 88357914.09
May 0.565233E+09 0.482785E+09 0.926320E+09 0.00 0.00 0.00 0.00 1646.67 0.108949E+09
June 0.565233E+09 0.476864E+09 0.914754E+09 0.00 0.00 0.00 0.00 22749.10 64693408.54
July 0.513848E+09 0.444584E+09 0.873466E+09 0.00 0.00 0.00 0.00 855124.03 50268971.28
August 0.590925E+09 0.516739E+09 0.953087E+09 0.00 0.00 0.00 0.00 849816.46 60191178.78
September 0.513848E+09 0.471863E+09 0.861220E+09 0.00 0.00 0.00 0.00 1262483.75 52873737.67
October 0.539540E+09 0.511217E+09 0.900233E+09 0.00 0.00 0.00 0.00 4978773.24 81518743.96
November 0.539540E+09 0.511105E+09 0.888667E+09 0.00 0.00 0.00 0.00 636402.97 0.113759E+09
December 0.513848E+09 0.498826E+09 0.872785E+09 0.00 0.00 0.00 0.00 463351.87 0.118271E+09
                   
Annual Sum or Average 0.647448E+10 0.588274E+10 0.107191E+11 0.00 0.00 0.00 0.00 10375899.24 0.112646E+10
Minimum of Months 0.488155E+09 0.444584E+09 0.813362E+09 0.00 0.00 0.00 0.00 1646.67 50268971.28
Maximum of Months 0.590925E+09 0.535153E+09 0.953087E+09 0.00 0.00 0.00 0.00 4978773.24 0.147212E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.288179E+09 0.533626E+09 0.00 0.00 0.00 0.00 188333.37 78032291.88
February 0.289580E+09 0.253477E+09 0.482497E+09 0.00 0.00 0.00 0.00 14858.61 91700055.09
March 0.350544E+09 0.301980E+09 0.565383E+09 0.00 0.00 0.00 0.00 26775.94 0.103011E+09
April 0.304821E+09 0.264443E+09 0.511694E+09 0.00 0.00 0.00 0.00 380951.37 64786234.97
May 0.335303E+09 0.285810E+09 0.549505E+09 0.00 0.00 0.00 0.00 1096.43 78456942.54
June 0.335303E+09 0.284274E+09 0.542644E+09 0.00 0.00 0.00 0.00 15166.80 47710224.67
July 0.304821E+09 0.262983E+09 0.518151E+09 0.00 0.00 0.00 0.00 556330.36 38988963.45
August 0.350544E+09 0.298727E+09 0.565383E+09 0.00 0.00 0.00 0.00 544273.07 46006484.23
September 0.304821E+09 0.266488E+09 0.510887E+09 0.00 0.00 0.00 0.00 792902.29 40144373.47
October 0.320062E+09 0.285155E+09 0.534030E+09 0.00 0.00 0.00 0.00 2951757.62 59572802.84
November 0.320062E+09 0.283126E+09 0.527169E+09 0.00 0.00 0.00 0.00 293939.23 80892427.00
December 0.304821E+09 0.277857E+09 0.517747E+09 0.00 0.00 0.00 0.00 154678.29 84258863.66
                   
Annual Sum or Average 0.384075E+10 0.335250E+10 0.635872E+10 0.00 0.00 0.00 0.00 5921063.40 0.813560E+09
Minimum of Months 0.289580E+09 0.253477E+09 0.482497E+09 0.00 0.00 0.00 0.00 1096.43 38988963.45
Maximum of Months 0.350544E+09 0.301980E+09 0.565383E+09 0.00 0.00 0.00 0.00 2951757.62 0.103011E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131482E+10 0.251517E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.890394E+09 0.257927E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.819172E+09 0.379338E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.787837E+09 0.512401E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.716891E+09 0.523754E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.538787E+09 0.536420E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.663215E+09 0.596386E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.710125E+09 0.547039E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.874340E+09 0.419527E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110217E+10 0.303552E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118404E+10 0.258167E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143140E+10 0.226713E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110332E+11 0.481274E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.538787E+09 0.226713E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143140E+10 0.596386E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 743.94 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 743.94 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 743.94 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 743.94 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 743.94 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 743.94 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 743.94 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 743.94 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 743.94 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 743.94 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 743.94 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 743.94 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 563.96 02-JAN-16:49 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 325.91 18-JAN-13:00 2907.72 09-JAN-07:10
February 732.70 01-FEB-08:09 553.65 27-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 275.29 01-FEB-12:10 2304.96 09-FEB-07:10
March 732.70 01-MAR-08:09 531.91 16-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2580.88 30-MAR-06:10
April 732.70 03-APR-07:10 528.34 21-APR-15:00 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 326.34 26-APR-11:10 1777.95 03-APR-06:10
May 732.70 01-MAY-07:10 523.63 09-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 17.10 03-MAY-12:00 1588.22 15-MAY-06:03
June 732.70 01-JUN-07:10 518.95 09-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 146.90 29-JUN-11:05 1347.21 01-JUN-06:03
July 732.70 03-JUL-07:10 511.00 12-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 633.09 19-JUL-12:00 1300.09 27-JUL-06:05
August 732.70 01-AUG-07:10 523.39 21-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 631.33 18-AUG-11:55 1428.77 28-AUG-06:05
September 732.70 01-SEP-07:10 538.03 18-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 1691.97 29-SEP-11:03 1597.07 20-SEP-06:05
October 732.70 02-OCT-07:10 536.06 24-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 1641.87 16-OCT-11:03 2025.32 30-OCT-06:03
November 732.70 01-NOV-07:10 563.96 06-NOV-16:00 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 26.60 28-NOV-13:55 2112.59 24-NOV-07:03
December 732.70 01-DEC-08:09 563.96 01-DEC-16:40 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 326.14 19-DEC-13:00 2579.89 22-DEC-07:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   511.00   738.04   0.00 0.00 0.00 0.00 0.00   1300.09  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 1691.97   2907.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 334.55 02-JAN-16:49 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 17.54 15-JAN-09:52 158.18 27-JAN-04:55
February 434.65 01-FEB-08:09 329.41 27-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 4.37 01-FEB-11:55 149.57 25-FEB-03:00
March 434.65 01-MAR-08:09 318.01 02-MAR-16:00 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 171.49 28-MAR-18:55
April 434.65 03-APR-07:10 317.72 21-APR-15:00 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 6.42 26-APR-13:00 117.76 28-APR-18:53
May 434.65 01-MAY-07:10 307.02 09-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 0.23 03-MAY-13:00 138.55 12-MAY-19:00
June 434.65 01-JUN-07:10 302.67 09-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 2.59 29-JUN-10:55 77.49 06-JUN-18:52
July 434.65 03-JUL-07:10 299.03 28-JUL-15:39 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 10.51 31-JUL-13:00 103.33 20-JUL-18:02
August 434.65 01-AUG-07:10 306.56 21-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 7.94 17-AUG-14:10 58.80 21-AUG-18:02
September 434.65 01-SEP-07:10 318.71 21-SEP-07:30 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 24.47 29-SEP-14:10 72.47 25-SEP-18:55
October 434.65 02-OCT-07:10 323.04 20-OCT-15:00 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 52.31 15-OCT-08:51 120.71 30-OCT-03:00
November 434.65 01-NOV-07:10 334.55 06-NOV-16:00 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 16.82 19-NOV-13:00 152.18 23-NOV-04:00
December 434.65 01-DEC-08:09 334.55 01-DEC-16:40 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 7.13 25-DEC-11:55 144.01 23-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   299.03   437.82   0.00 0.00 0.00 0.00 0.00   58.80  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 52.31   171.49  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 563.96 02-JAN-16:49 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 34.96 15-JAN-09:52 234.71 27-JAN-04:55
February 732.70 01-FEB-08:09 554.95 27-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 6.56 01-FEB-11:55 222.18 25-FEB-03:00
March 732.70 01-MAR-08:09 537.75 16-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 5.81 12-MAR-09:51 256.69 28-MAR-18:55
April 732.70 03-APR-07:10 531.85 21-APR-15:00 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 31.06 02-APR-13:00 173.33 28-APR-18:53
May 732.70 01-MAY-07:10 525.31 09-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 0.34 03-MAY-12:10 207.53 12-MAY-19:00
June 732.70 01-JUN-07:10 518.69 09-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 3.89 29-JUN-11:00 115.66 06-JUN-18:52
July 732.70 03-JUL-07:10 510.31 12-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 15.76 31-JUL-13:00 146.68 20-JUL-18:02
August 732.70 01-AUG-07:10 526.04 21-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 12.70 17-AUG-14:00 85.14 21-AUG-18:10
September 732.70 01-SEP-07:10 541.39 21-SEP-07:30 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 37.92 29-SEP-13:53 105.41 25-SEP-18:55
October 732.70 02-OCT-07:10 542.39 24-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 112.50 15-OCT-08:51 170.51 30-OCT-03:00
November 732.70 01-NOV-07:10 563.96 06-NOV-16:00 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 44.38 19-NOV-13:00 222.16 23-NOV-04:00
December 732.70 01-DEC-08:09 563.96 01-DEC-16:40 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 43.86 25-DEC-11:55 211.62 23-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   510.31   738.04   0.00 0.00 0.00 0.00 0.34   85.14  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 112.50   256.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 334.55 02-JAN-16:49 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 19.44 15-JAN-09:52 158.52 27-JAN-04:55
February 434.65 01-FEB-08:09 328.52 27-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 4.37 01-FEB-11:55 150.62 25-FEB-03:00
March 434.65 01-MAR-08:09 320.95 16-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 2.34 11-MAR-12:50 176.36 28-MAR-18:55
April 434.65 03-APR-07:10 316.79 05-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 17.68 02-APR-13:00 133.03 28-APR-18:53
May 434.65 01-MAY-07:10 315.66 09-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 0.23 03-MAY-12:10 140.13 12-MAY-19:00
June 434.65 01-JUN-07:10 313.36 09-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 2.59 29-JUN-11:00 94.36 13-JUN-18:02
July 434.65 03-JUL-07:10 310.90 12-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 10.51 31-JUL-13:00 113.87 20-JUL-18:02
August 434.65 01-AUG-07:10 316.35 21-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 8.47 17-AUG-14:00 69.22 27-AUG-17:52
September 434.65 01-SEP-07:10 322.44 21-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 25.28 29-SEP-13:53 83.16 03-SEP-16:52
October 434.65 02-OCT-07:10 322.80 24-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 70.05 15-OCT-08:51 121.57 30-OCT-03:00
November 434.65 01-NOV-07:10 334.55 06-NOV-16:00 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 21.49 19-NOV-13:00 154.73 23-NOV-04:00
December 434.65 01-DEC-08:09 334.55 01-DEC-16:40 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 19.30 25-DEC-11:55 145.11 23-DEC-03:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   310.90   437.82   0.00 0.00 0.00 0.00 0.23   69.22  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 70.05   176.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2072.85 14-JAN-07:42 4866.92 30-JAN-11:50
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1783.29 01-FEB-02:30 5443.55 18-FEB-12:40
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1638.42 07-MAR-06:00 6591.90 15-MAR-12:20
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1560.34 16-APR-01:00 7016.42 23-APR-12:30
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1476.20 16-MAY-24:00 7394.34 31-MAY-12:55
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1435.98 18-JUN-01:50 7091.96 01-JUN-12:10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1404.83 14-JUL-05:25 7011.10 03-JUL-13:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1469.94 24-AUG-03:40 6622.39 01-AUG-13:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1662.47 29-SEP-06:42 6255.67 02-SEP-12:30
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2250.55 16-OCT-06:52 5650.76 18-OCT-12:05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1989.67 27-NOV-06:53 4967.92 04-NOV-11:50
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2016.76 26-DEC-05:00 4592.39 02-DEC-12:10
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1404.83   4592.39  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2250.55   7394.34  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2226.75 25-JAN-06:05 212.64 64.44 973.59 0.00 0.00 0.00 0.00 0.00 0.00
February 1989.59 03-FEB-15:53 3866.15 2975.76 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
March 2206.53 24-MAR-05:05 212.64 64.44 973.59 0.00 0.00 0.00 0.00 0.00 0.00
April 4154.60 28-APR-05:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
May 4301.15 02-MAY-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
June 4307.75 07-JUN-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
July 4228.88 06-JUL-05:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
August 4257.58 22-AUG-05:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
September 4257.11 20-SEP-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
October 5185.50 16-OCT-05:01 850.55 257.74 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
November 4401.06 02-NOV-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
December 2578.89 08-DEC-06:05 212.64 64.44 973.59 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1989.59   212.64 64.44 973.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5185.50   3866.15 2975.76 3894.35 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3524.75 20-JAN-13:05 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 0.00 143.91
February 3031.64 03-FEB-14:20 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 23.96
March 2557.85 23-MAR-14:00 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 22.45
April 2115.44 26-APR-13:50 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 55.96 0.00
May 1737.15 04-MAY-13:53 2930.79 1646.52 2952.17 0.00 0.00 0.00 0.00 0.00 24.24
June 1776.34 30-JUN-14:40 1465.40 836.60 1476.09 0.00 0.00 0.00 0.00 0.00 22.29
July 3336.84 24-JUL-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 162.54
August 3543.06 21-AUG-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 208.13
September 4077.86 29-SEP-16:52 1172.32 1705.72 1845.11 0.00 0.00 0.00 0.00 905.01 0.00
October 4880.90 17-OCT-05:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 274.82
November 3804.94 28-NOV-13:30 732.70 411.63 738.04 0.00 0.00 0.00 0.00 15.00 0.00
December 4182.37 19-DEC-13:00 447.24 365.89 693.76 0.00 0.00 0.00 0.00 326.14 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1737.15   402.98 122.12 693.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4880.90   2930.79 1705.72 2952.17 0.00 0.00 0.00 0.00 905.01 274.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2557.39 18-JAN-11:02 2173.23 1231.98 2189.08 0.00 0.00 0.00 0.00 0.00 1.01
February 2060.00 22-FEB-15:02 1738.59 1201.90 1751.27 0.00 0.00 0.00 0.00 0.00 11.19
March 2940.30 24-MAR-10:01 3042.52 1709.29 3064.72 0.00 0.00 0.00 0.00 0.00 8.09
April 3113.73 14-APR-14:02 2607.88 1722.98 2626.90 0.00 0.00 0.00 0.00 0.00 20.08
May 3096.81 02-MAY-10:02 2173.23 1220.92 2189.08 0.00 0.00 0.00 0.00 0.00 0.50
June 3020.37 06-JUN-10:02 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 8.97
July 3103.03 10-JUL-10:02 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 0.85
August 3036.53 23-AUG-10:02 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 1.47
September 3007.20 12-SEP-10:02 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 2.44
October 3404.22 17-OCT-05:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 49.76
November 3228.85 01-NOV-10:01 3911.82 2197.66 3940.35 0.00 0.00 0.00 0.00 0.00 11.73
December 2678.81 19-DEC-11:02 2173.23 1382.54 2189.08 0.00 0.00 0.00 0.00 0.16 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2060.00   334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3404.22   3911.82 2197.66 3940.35 0.00 0.00 0.00 0.00 0.16 49.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1057.65 18-JAN-15:25 2930.79 2026.64 2952.17 0.00 0.00 0.00 0.00 0.00 4.39
February 917.39 03-FEB-15:35 2930.79 2009.35 2952.17 0.00 0.00 0.00 0.00 0.00 6.74
March 1069.49 23-MAR-15:53 2930.79 1946.47 2952.17 0.00 0.00 0.00 0.00 0.00 6.91
April 1472.23 26-APR-14:27 2198.10 1414.42 2214.13 0.00 0.00 0.00 0.00 1.79 0.00
May 1729.27 04-MAY-14:02 2930.79 1671.24 2952.17 0.00 0.00 0.00 0.00 0.00 5.30
June 1837.68 30-JUN-14:40 1465.40 919.21 1476.09 0.00 0.00 0.00 0.00 0.00 2.68
July 3213.37 28-JUL-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 0.00
August 3219.25 01-AUG-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 43.87
September 2381.04 29-SEP-14:23 2198.10 1442.17 2214.13 0.00 0.00 0.00 0.00 34.33 0.00
October 4277.21 17-OCT-05:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 71.83
November 1142.95 10-NOV-14:23 2930.79 2014.44 2952.17 0.00 0.00 0.00 0.00 0.00 17.38
December 1013.22 07-DEC-15:13 2930.79 2060.22 2952.17 0.00 0.00 0.00 0.00 0.00 17.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 917.39   402.98 122.12 1476.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4277.21   2930.79 2060.22 2952.17 0.00 0.00 0.00 0.00 34.33 71.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1258.07 18-JAN-15:25 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 2.93
February 1316.62 01-FEB-16:23 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 8.63
March 1635.41 23-MAR-16:00 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 4.61
April 1942.53 26-APR-15:55 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 3.00
May 1879.91 03-MAY-15:55 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 5.36
June 2805.85 26-JUN-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 3.53
July 3493.89 10-JUL-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 7.56
August 3155.09 01-AUG-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 30.10
September 2560.20 29-SEP-15:53 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 14.41 0.00
October 4020.60 17-OCT-05:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 50.12
November 1430.52 10-NOV-15:35 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 14.73
December 1362.12 19-DEC-15:35 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 4.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1258.07   239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4020.60   1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 14.41 50.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 390.19 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1529.54 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 975.30 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.89
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 934.23 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 647.28 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 329.89 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1009.68 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1011.06 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 993.55 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 873.16 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 581.89 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1529.54 30.89



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.116040E+11 11978.02 20-JAN-11:00 3844101.39 3188.15 03-JAN-06:19
February 0.101727E+11 11671.17 03-FEB-13:00 0.00 0.00 01-FEB-00:10
March 0.117522E+11 12101.11 23-MAR-15:30 0.00 0.00 01-MAR-00:10
April 0.108659E+11 12361.86 26-APR-14:09 0.00 0.00 01-APR-00:10
May 0.116183E+11 12107.07 04-MAY-14:30 0.00 0.00 01-MAY-00:10
June 0.119173E+11 12611.95 29-JUN-12:30 0.00 0.00 01-JUN-00:10
July 0.120003E+11 13616.99 31-JUL-12:50 0.00 0.00 01-JUL-00:10
August 0.132942E+11 13453.98 17-AUG-14:20 0.00 0.00 01-AUG-00:10
September 0.117071E+11 14214.64 29-SEP-12:50 0.00 0.00 01-SEP-00:10
October 0.125087E+11 14516.43 16-OCT-12:50 0.00 0.00 01-OCT-00:10
November 0.115190E+11 12460.11 28-NOV-16:00 0.00 0.00 01-NOV-00:10
December 0.112800E+11 12485.58 18-DEC-16:49 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.140240E+12     3844101.39    
Minimum of Months 0.101727E+11 11671.17   0.00 0.00  
Maximum of Months 0.132942E+11 14516.43   3844101.39 3188.15  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.228113E+10 0.104411E+10 0.405300E+10 0.00 0.140564E+10 0.02 0.163989E+09 0.589128E+09 0.00 0.00 0.00 0.206696E+10 0.00
February 0.203203E+10 0.863359E+09 0.366466E+10 0.00 0.127109E+10 0.00 55241381.48 0.419063E+09 0.00 0.00 0.00 0.186725E+10 0.00
March 0.241917E+10 0.840269E+09 0.429420E+10 0.00 0.153892E+10 0.00 0.135269E+09 0.422245E+09 0.00 0.00 0.00 0.210212E+10 0.00
April 0.211072E+10 0.705324E+09 0.388642E+10 0.00 0.134468E+10 0.00 16235508.43 0.821801E+09 0.00 0.00 0.00 0.198072E+10 0.00
May 0.228513E+10 0.655482E+09 0.417360E+10 0.00 0.147904E+10 0.00 9514726.68 0.955947E+09 0.00 0.00 0.00 0.205957E+10 0.00
June 0.227595E+10 0.605779E+09 0.412149E+10 0.00 0.148371E+10 0.00 546648.85 0.143402E+10 0.00 0.00 0.00 0.199580E+10 0.00
July 0.210341E+10 0.636173E+09 0.393546E+10 0.00 0.135684E+10 0.00 0.00 0.196282E+10 0.00 0.00 0.00 0.200561E+10 0.00
August 0.238879E+10 0.694536E+09 0.429420E+10 0.00 0.156067E+10 0.00 0.00 0.229703E+10 0.00 0.00 0.00 0.205897E+10 0.00
September 0.213218E+10 0.764963E+09 0.388029E+10 0.00 0.135098E+10 0.00 0.00 0.162085E+10 0.00 0.00 0.00 0.195784E+10 0.00
October 0.226821E+10 0.907791E+09 0.405607E+10 0.00 0.141897E+10 0.00 12477.09 0.182161E+10 0.00 0.00 0.00 0.203604E+10 0.00
November 0.225974E+10 0.981312E+09 0.400396E+10 0.00 0.140828E+10 0.00 3312302.00 0.864824E+09 0.00 0.00 0.00 0.199757E+10 0.00
December 0.219395E+10 0.107214E+10 0.393240E+10 0.00 0.133902E+10 0.00 39958829.16 0.662121E+09 0.00 0.00 0.00 0.204047E+10 0.00
                           
Annual Sum or Average 0.267504E+11 0.977124E+10 0.482958E+11 0.00 0.169578E+11 0.02 0.424081E+09 0.138715E+11 0.00 0.00 0.00 0.241689E+11 0.00
Minimum of Months 0.203203E+10 0.605779E+09 0.366466E+10 0.00 0.127109E+10 0.00 0.00 0.419063E+09 0.00 0.00 0.00 0.186725E+10 0.00
Maximum of Months 0.241917E+10 0.107214E+10 0.429420E+10 0.00 0.156067E+10 0.02 0.163989E+09 0.229703E+10 0.00 0.00 0.00 0.210212E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 3844101.39 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 3844101.39 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 3844101.39 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2540.94 02-JAN-16:49 1061.67 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1484.50 02-JAN-06:30 0.00 05-JAN-09:39 5267.91 02-JAN-06:19
February 2510.48 27-FEB-16:00 1061.67 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1484.50 01-FEB-06:10 0.00 01-FEB-07:10 1638.49 27-FEB-06:10
March 2448.48 16-MAR-07:10 1061.67 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1484.50 01-MAR-06:19 0.00 01-MAR-00:10 3201.09 30-MAR-05:10
April 2434.17 21-APR-15:00 1061.67 01-APR-05:10 3325.31 03-APR-07:10 0.00 1484.50 03-APR-05:19 0.00 01-APR-00:10 778.33 03-APR-06:10
May 2415.56 09-MAY-07:10 675.04 01-MAY-18:30 3325.31 01-MAY-07:10 0.00 1484.50 01-MAY-05:10 0.00 01-MAY-00:10 765.95 15-MAY-05:10
June 2397.61 09-JUN-07:10 675.04 01-JUN-18:49 3325.31 01-JUN-07:10 0.00 1484.50 01-JUN-05:10 0.00 01-JUN-00:10 125.58 12-JUN-06:19
July 2371.18 12-JUL-07:10 675.04 01-JUL-18:00 3325.31 03-JUL-07:10 0.00 1484.50 03-JUL-05:19 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2416.28 21-AUG-07:10 1061.67 08-AUG-05:10 3325.31 01-AUG-07:10 0.00 1484.50 01-AUG-05:19 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2464.01 18-SEP-07:10 1061.67 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1484.50 01-SEP-05:19 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2462.47 24-OCT-07:10 1061.67 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1484.50 02-OCT-05:10 0.00 01-OCT-00:10 20.80 12-OCT-06:19
November 2540.94 06-NOV-16:00 1061.67 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1484.50 01-NOV-05:10 0.00 01-NOV-00:10 420.15 27-NOV-06:10
December 2540.94 01-DEC-16:40 1061.67 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1484.50 01-DEC-06:10 0.00 01-DEC-00:10 1343.11 13-DEC-06:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2371.18   675.04   3325.31   0.00 1484.50   0.00   0.00  
Maximum of Months 2540.94   1061.67   3325.31   0.00 1484.50   0.00   5267.91  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 2219.33 18-JAN-13:00 0.00 0.00 0.00 2790.93 31-JAN-12:00 0.00
February 2001.66 01-FEB-11:00 0.00 0.00 0.00 2790.85 13-FEB-12:00 0.00
March 2366.36 23-MAR-14:00 0.00 0.00 0.00 2790.20 01-MAR-12:39 0.00
April 2666.45 26-APR-14:09 0.00 0.00 0.00 2787.48 03-APR-11:09 0.00
May 2528.87 04-MAY-14:09 0.00 0.00 0.00 2784.45 01-MAY-11:39 0.00
June 2877.60 29-JUN-15:00 0.00 0.00 0.00 2780.94 01-JUN-11:00 0.00
July 3902.33 31-JUL-12:00 0.00 0.00 0.00 2778.15 03-JUL-11:39 0.00
August 3820.40 17-AUG-14:09 0.00 0.00 0.00 2777.81 30-AUG-11:30 0.00
September 4504.73 29-SEP-12:00 0.00 0.00 0.00 2780.19 29-SEP-11:50 0.00
October 4973.36 16-OCT-10:00 0.00 0.00 0.00 2783.58 30-OCT-11:50 0.00
November 2300.24 10-NOV-13:09 0.00 0.00 0.00 2786.76 27-NOV-12:20 0.00
December 2345.93 19-DEC-13:09 0.00 0.00 0.00 2789.69 29-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 2001.66   0.00 0.00 0.00 2777.81   0.00
Maximum of Months 4973.36   0.00 0.00 0.00 2790.93   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 11978.02 20-JAN-11:00 2220.27 3325.31 0.00 0.00 1484.50 0.00 0.00 2182.64 0.00
February 11671.17 03-FEB-13:00 2190.83 3325.31 0.00 0.00 1484.50 0.00 0.00 1892.81 0.00
March 12101.11 23-MAR-15:30 2184.66 3325.31 0.00 0.00 1484.50 0.00 0.00 2355.67 0.00
April 12361.86 26-APR-14:09 2160.20 3325.31 0.00 0.00 1484.50 0.00 0.00 2666.45 0.00
May 12107.07 04-MAY-14:30 2095.84 3325.31 0.00 0.00 1484.50 0.00 0.00 2476.70 0.00
June 12611.95 29-JUN-12:30 2174.13 3325.31 0.00 0.00 1484.50 0.00 0.00 2861.13 0.00
July 13616.99 31-JUL-12:50 2152.33 3325.31 0.00 0.00 1484.50 0.00 0.00 3889.17 0.00
August 13453.98 17-AUG-14:20 2176.03 3325.31 0.00 0.00 1484.50 0.00 0.00 3746.75 0.00
September 14214.64 29-SEP-12:50 2152.54 3325.31 0.00 0.00 1484.50 0.00 0.00 4484.21 0.00
October 14516.43 16-OCT-12:50 2191.14 3325.31 0.00 0.00 1484.50 0.00 0.00 4745.56 0.00
November 12460.11 28-NOV-16:00 2540.94 3325.31 1061.67 0.00 1484.50 0.00 0.00 1297.86 0.00
December 12485.58 18-DEC-16:49 2540.94 3325.31 1061.67 0.00 1484.50 0.00 0.00 1321.59 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 11671.17   2095.84 3325.31 0.00 0.00 1484.50 0.00 0.00 1297.86 0.00
Maximum of Months 14516.43   2540.94 3325.31 1061.67 0.00 1484.50 0.00 0.00 4745.56 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 3188.15 03-JAN-06:19 0.00 0.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 3188.15   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 24.54 0.33 24.54
August 0.00 0.00 0.00 0.00 0.33 24.52 0.33 24.52
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.83 24.62 0.83 24.62
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.50 24.58 1.50 24.58
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.83 24.62 0.83 24.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.45 0.17 20.45 0.00 20.45 0.00 20.45
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 4.67 25.06 4.67 25.06
October 0.00 0.00 0.00 0.00 13.00 25.30 13.00 25.30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 20.45 0.17 20.45 17.67 25.15 17.67 25.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.45 0.17 20.45 13.00 25.30 13.00 25.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.38 0.33 20.38 0.00 20.38 0.00 20.38
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.38 0.33 20.38 0.00 20.38 0.00 20.38
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.38 0.33 20.38 0.00 20.38 0.00 20.38



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 19.93 0.50 19.93 0.00 19.93 0.00 19.93
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.50 19.93 0.50 19.93 0.00 19.93 0.00 19.93
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 19.93 0.50 19.93 0.00 19.93 0.00 19.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 20.46 0.33 20.46 0.00 20.46 0.00 20.46
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 20.46 0.33 20.46 0.00 20.46 0.00 20.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 20.46 0.33 20.46 0.00 20.46 0.00 20.46



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 225.17 23.20 24.33 23.28 3.33 23.25
February 231.00 23.60 17.50 23.61 14.00 23.60
March 273.83 23.50 25.33 23.57 0.00 23.57
April 71.33 23.65 85.67 24.11 0.00 24.11
May 53.33 23.74 110.50 24.33 0.00 24.33
June 12.83 24.31 244.67 24.44 3.83 24.45
July 28.50 25.64 325.00 24.51 28.50 24.60
August 38.83 25.53 378.83 24.49 38.83 24.58
September 10.17 25.21 274.33 24.40 10.00 24.43
October 45.00 24.36 214.50 24.52 13.50 24.57
November 125.83 23.82 49.67 24.02 1.00 24.02
December 246.67 23.74 7.67 23.77 0.00 23.77
             
Annual Sum or Average 1362.50 23.71 1758.00 24.11 113.00 24.15
Minimum of Months 10.17 23.20 7.67 23.28 0.00 23.25
Maximum of Months 273.83 25.64 378.83 24.52 38.83 24.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 226.83 22.99 41.17 23.03 10.33 22.95
February 247.17 22.84 9.33 22.88 0.00 22.88
March 330.50 22.53 31.17 22.56 12.00 22.50
April 247.33 23.08 2.17 23.09 0.00 23.09
May 316.50 23.24 0.00 23.24 0.00 23.24
June 187.00 23.42 58.00 23.60 0.00 23.60
July 68.83 24.05 219.67 24.21 37.83 24.25
August 75.50 24.02 310.67 24.17 51.33 24.20
September 58.17 23.44 218.67 24.12 7.33 24.11
October 66.83 23.78 195.17 24.40 16.67 24.44
November 170.83 23.40 52.00 23.54 0.00 23.54
December 215.17 23.27 10.83 23.30 0.00 23.30
             
Annual Sum or Average 2210.67 23.15 1148.83 23.51 135.50 23.53
Minimum of Months 58.17 22.53 0.00 22.56 0.00 22.50
Maximum of Months 330.50 24.05 310.67 24.40 51.33 24.44



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 281.67 22.84 21.83 22.69 21.83 22.55
February 266.00 22.82 5.67 22.78 5.67 22.74
March 302.67 22.65 12.17 22.58 12.17 22.51
April 188.83 23.31 5.33 23.34 0.00 23.34
May 189.50 23.44 9.00 23.50 0.00 23.50
June 93.00 23.62 85.67 23.99 0.00 23.99
July 11.33 23.88 227.50 24.40 0.33 24.39
August 9.17 23.88 271.50 24.35 1.00 24.35
September 49.33 23.74 124.00 24.17 0.00 24.17
October 91.50 23.74 89.33 24.12 1.17 24.12
November 277.83 23.40 1.17 23.39 1.17 23.38
December 276.67 23.10 4.17 23.08 4.17 23.05
             
Annual Sum or Average 2037.50 23.13 857.33 23.45 47.50 23.41
Minimum of Months 9.17 22.65 1.17 22.58 0.00 22.51
Maximum of Months 302.67 23.88 271.50 24.40 21.83 24.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 22.54 49.00 22.33 49.00 22.17
February 323.00 22.59 11.00 22.54 11.00 22.50
March 386.00 22.46 21.17 22.38 21.17 22.31
April 301.17 23.26 0.00 23.26 0.00 23.26
May 301.00 23.49 1.83 23.49 0.00 23.49
June 137.67 23.65 62.17 23.90 0.00 23.90
July 18.83 23.86 209.67 24.34 0.50 24.34
August 23.17 23.81 233.33 24.24 3.17 24.23
September 90.33 23.71 50.33 23.93 0.00 23.93
October 188.17 23.70 84.00 23.89 2.00 23.90
November 352.17 23.20 4.00 23.18 4.00 23.16
December 340.00 22.84 13.67 22.78 13.67 22.72
             
Annual Sum or Average 2818.50 23.02 740.17 23.20 104.50 23.14
Minimum of Months 18.83 22.46 0.00 22.33 0.00 22.17
Maximum of Months 386.00 23.86 233.33 24.34 49.00 24.34



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 330.00 22.93 28.33 22.77 28.33 22.63
February 303.50 22.99 5.67 22.96 5.67 22.92
March 347.33 22.82 23.67 22.82 11.67 22.76
April 200.67 23.46 60.33 23.76 0.00 23.76
May 198.50 23.59 71.50 23.93 0.00 23.93
June 88.33 23.71 155.00 24.48 0.00 24.48
July 6.00 26.11 251.67 24.83 4.00 24.86
August 8.00 23.96 298.00 24.66 1.00 24.66
September 39.67 23.85 183.33 24.51 0.00 24.51
October 102.17 23.76 135.33 24.22 1.17 24.23
November 289.00 23.47 3.67 23.47 1.50 23.46
December 330.00 23.22 4.33 23.19 4.33 23.17
             
Annual Sum or Average 2243.17 23.24 1220.83 23.71 57.67 23.67
Minimum of Months 6.00 22.82 3.67 22.77 0.00 22.63
Maximum of Months 347.33 26.11 298.00 24.83 28.33 24.86



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.840872E+09 0.184663E+09 165.92 0.700849E+09 0.140023E+09 0.00 0.54 20-JAN-12:00 0.00 01-JAN-00:10 2594.10 20-JAN-12:00 2234.78 24-JAN-15:00 750.90 26-JAN-06:05 564.10 24-JAN-15:00 0.00
February 0.729024E+09 0.160418E+09 163.42 0.606121E+09 0.122903E+09 0.00 0.50 03-FEB-15:00 0.00 01-FEB-00:10 2374.23 01-FEB-16:00 2222.71 03-FEB-15:00 575.81 01-FEB-16:30 512.26 01-FEB-12:00 0.00
March 0.830399E+09 0.181785E+09 185.30 0.636659E+09 0.193741E+09 0.00 0.60 23-MAR-14:45 0.00 01-MAR-00:10 2940.81 23-MAR-14:57 2240.54 23-MAR-14:00 863.65 24-MAR-05:05 625.45 23-MAR-14:00 0.00
April 0.139406E+10 0.300970E+09 206.12 0.109659E+10 0.297467E+09 0.00 1.00 14-APR-05:03 0.00 01-APR-00:10 5237.28 27-APR-05:03 3804.47 28-APR-05:03 1611.80 27-APR-05:03 1021.38 27-APR-05:03 0.00
May 0.169297E+10 0.363510E+09 237.26 0.136744E+10 0.325527E+09 0.00 1.00 01-MAY-05:03 0.00 01-MAY-00:10 5225.77 03-MAY-05:03 3974.04 02-MAY-05:03 1583.42 03-MAY-05:03 1019.77 03-MAY-05:03 0.00
June 0.234575E+10 0.496147E+09 255.54 0.180795E+10 0.537806E+09 0.00 1.00 06-JUN-05:03 0.00 01-JUN-00:10 5346.00 30-JUN-05:02 3969.66 07-JUN-05:03 1907.81 28-JUN-05:04 1035.04 30-JUN-05:02 0.00
July 0.293236E+10 0.612352E+09 238.72 0.219531E+10 0.737048E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 5388.79 20-JUL-05:02 3951.44 11-JUL-05:02 2065.90 20-JUL-05:15 1063.14 31-JUL-13:00 0.00
August 0.338643E+10 0.706810E+09 274.82 0.250014E+10 0.886287E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5401.00 18-AUG-05:02 3903.98 22-AUG-05:02 2083.67 18-AUG-05:15 1040.85 18-AUG-05:02 0.00
September 0.237217E+10 0.503558E+09 238.09 0.181254E+10 0.559625E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 5354.60 25-SEP-05:03 4065.77 29-SEP-13:00 1972.99 25-SEP-05:05 1061.41 29-SEP-13:00 0.00
October 0.247117E+10 0.530898E+09 245.77 0.207254E+10 0.398623E+09 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 5427.57 05-OCT-05:02 5030.04 16-OCT-05:01 2061.31 06-OCT-05:15 1224.70 16-OCT-10:53 0.00
November 0.128785E+10 0.280177E+09 217.84 0.109422E+10 0.193633E+09 0.00 1.00 01-NOV-05:03 0.00 01-NOV-00:10 5155.33 01-NOV-05:03 3945.84 02-NOV-05:03 1326.97 01-NOV-05:03 1009.27 01-NOV-05:03 0.00
December 0.947934E+09 0.209277E+09 194.94 0.861692E+09 86241871.92 0.00 0.65 08-DEC-06:05 0.00 01-DEC-00:10 3155.95 08-DEC-06:05 2290.54 05-DEC-14:55 1030.98 08-DEC-06:05 655.41 08-DEC-06:05 0.00
                                       
Annual Sum or Average 0.212310E+11 0.453057E+10 2623.75 0.167521E+11 0.447893E+10 0.00                         0.00
Minimum of Months 0.729024E+09 0.160418E+09 163.42 0.606121E+09 86241871.92 0.00 0.50   0.00   2374.23   2222.71   575.81   512.26   0.00
Maximum of Months 0.338643E+10 0.706810E+09 274.82 0.250014E+10 0.886287E+09 0.00 1.00   0.00   5427.57   5030.04   2083.67   1224.70   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.111491E+10 0.239690E+09 162.63 0.105038E+10 64535863.75 0.00 0.85 20-JAN-13:10 0.00 01-JAN-00:10 4160.12 20-JAN-13:10 3825.76 18-JAN-13:55 617.54 20-JAN-13:10 838.22 20-JAN-13:10 0.00
February 0.676133E+09 0.146258E+09 120.48 0.632205E+09 43928604.40 0.00 0.74 03-FEB-14:20 0.00 01-FEB-00:10 3309.96 03-FEB-14:20 3309.96 03-FEB-14:20 456.43 01-FEB-16:00 733.81 01-FEB-12:05 0.00
March 0.489008E+09 0.106523E+09 106.66 0.420048E+09 68960030.93 0.00 0.70 23-MAR-14:00 0.00 01-MAR-00:10 3359.25 23-MAR-14:00 2834.01 23-MAR-14:00 589.16 24-MAR-12:40 710.66 23-MAR-14:00 0.00
April 0.654470E+09 0.144318E+09 141.09 0.555557E+09 98912367.01 0.00 0.61 26-APR-13:30 0.00 01-APR-00:10 2860.15 26-APR-13:30 2591.83 26-APR-13:30 461.85 27-APR-10:55 653.45 26-APR-13:00 0.00
May 0.581885E+09 0.129063E+09 153.28 0.502900E+09 78984951.94 0.00 0.51 04-MAY-14:00 0.00 01-MAY-00:10 2358.34 04-MAY-14:00 2014.41 04-MAY-13:53 363.39 05-MAY-15:00 515.20 04-MAY-14:00 0.00
June 0.104947E+10 0.230293E+09 192.91 0.833991E+09 0.215476E+09 0.00 0.57 29-JUN-13:00 0.00 01-JUN-00:10 2776.26 29-JUN-13:00 2053.04 30-JUN-14:40 801.99 28-JUN-12:05 601.34 29-JUN-13:00 0.00
July 0.166877E+10 0.361986E+09 205.75 0.126291E+10 0.405854E+09 0.00 1.00 20-JUL-05:02 0.00 01-JUL-00:10 5313.23 25-JUL-05:02 3447.32 26-JUL-05:02 1970.30 20-JUL-05:02 1027.69 25-JUL-05:02 0.00
August 0.214034E+10 0.460281E+09 240.06 0.161357E+10 0.526773E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5342.19 07-AUG-05:02 3601.01 21-AUG-05:02 2066.05 07-AUG-05:02 1030.75 07-AUG-05:02 0.00
September 0.175914E+10 0.378549E+09 199.16 0.142805E+10 0.331090E+09 0.00 1.00 29-SEP-10:02 0.00 01-SEP-00:10 4776.80 29-SEP-16:12 4776.80 29-SEP-16:12 1346.47 11-SEP-05:02 1201.15 29-SEP-12:05 0.00
October 0.237075E+10 0.507828E+09 221.04 0.211345E+10 0.257298E+09 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 5381.71 05-OCT-05:02 4896.29 31-OCT-13:30 1996.96 05-OCT-05:04 1213.52 16-OCT-11:10 0.00
November 0.141736E+10 0.300862E+09 183.91 0.132000E+10 97354490.94 0.00 0.91 28-NOV-13:40 0.00 01-NOV-00:10 4510.92 20-NOV-13:05 4177.88 28-NOV-13:40 752.08 20-NOV-13:05 899.28 20-NOV-13:05 0.00
December 0.128684E+10 0.273860E+09 164.59 0.125473E+10 32109637.82 0.00 0.99 19-DEC-13:00 0.00 01-DEC-00:10 4636.31 19-DEC-13:00 4636.31 19-DEC-13:00 525.67 07-DEC-13:05 994.79 19-DEC-13:00 0.00
                                       
Annual Sum or Average 0.152091E+11 0.327951E+10 2091.54 0.129878E+11 0.222128E+10 0.00                         0.00
Minimum of Months 0.489008E+09 0.106523E+09 106.66 0.420048E+09 32109637.82 0.00 0.51   0.00   2358.34   2014.41   363.39   515.20   0.00
Maximum of Months 0.237075E+10 0.507828E+09 240.06 0.211345E+10 0.526773E+09 0.00 1.00   0.00   5381.71   4896.29   2066.05   1213.52   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.226586E+09 50927723.31 118.59 0.207513E+09 19073922.29 0.00 0.85 18-JAN-11:02 0.00 01-JAN-00:10 3009.99 18-JAN-11:02 2893.20 18-JAN-11:02 376.57 17-JAN-15:03 624.58 18-JAN-11:02 0.00
February 0.164359E+09 36898037.50 99.29 0.151447E+09 12911577.08 0.00 0.73 17-FEB-15:02 0.00 01-FEB-00:10 2591.90 17-FEB-15:02 2196.29 22-FEB-15:02 431.33 17-FEB-15:02 531.82 17-FEB-15:02 0.00
March 0.192875E+09 42949143.30 97.96 0.165307E+09 27568426.96 0.00 1.00 24-MAR-10:01 0.00 01-MAR-00:10 3719.73 24-MAR-10:01 3045.11 22-MAR-10:02 684.30 24-MAR-10:01 728.32 24-MAR-10:01 0.00
April 0.542628E+09 0.119952E+09 180.14 0.475236E+09 67392434.77 0.00 1.00 12-APR-10:02 0.00 01-APR-00:10 3716.88 12-APR-10:02 3282.91 26-APR-10:02 542.84 12-APR-10:02 741.79 26-APR-10:02 0.00
May 0.615856E+09 0.135618E+09 199.72 0.550535E+09 65321774.97 0.00 1.00 31-MAY-10:02 0.00 01-MAY-00:10 3682.07 31-MAY-10:02 3362.13 02-MAY-10:02 430.09 31-MAY-10:02 722.16 31-MAY-10:02 0.00
June 0.911339E+09 0.199238E+09 227.98 0.774000E+09 0.137339E+09 0.00 1.00 06-JUN-10:02 0.00 01-JUN-00:10 3777.26 28-JUN-10:01 3294.08 21-JUN-10:02 830.24 28-JUN-10:01 758.45 29-JUN-10:02 0.00
July 0.132332E+10 0.287118E+09 236.59 0.109572E+10 0.227604E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 3872.66 24-JUL-05:02 3367.09 10-JUL-10:02 1345.98 31-JUL-05:02 785.04 19-JUL-10:02 0.00
August 0.153769E+10 0.333468E+09 271.91 0.125770E+10 0.279994E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 3901.85 07-AUG-05:02 3365.56 23-AUG-10:02 1427.98 07-AUG-05:02 785.48 14-AUG-10:02 0.00
September 0.940333E+09 0.207685E+09 219.12 0.792081E+09 0.148251E+09 0.00 1.00 05-SEP-10:01 0.00 01-SEP-00:10 3821.03 22-SEP-10:02 3404.20 29-SEP-14:03 1035.18 22-SEP-10:02 859.19 29-SEP-12:05 0.00
October 0.996849E+09 0.224262E+09 225.70 0.898410E+09 98439095.72 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 3881.36 05-OCT-05:02 3532.24 17-OCT-05:01 1262.00 06-OCT-05:02 865.58 16-OCT-11:07 0.00
November 0.379240E+09 84718659.23 185.47 0.349198E+09 30041292.42 0.00 1.00 01-NOV-10:01 0.00 01-NOV-00:10 3646.50 01-NOV-10:01 3278.51 01-NOV-10:01 448.43 10-NOV-15:02 715.97 01-NOV-10:01 0.00
December 0.249073E+09 56170758.00 134.66 0.242185E+09 6888031.83 0.00 0.92 19-DEC-11:02 0.00 01-DEC-00:10 3078.83 19-DEC-11:02 3078.83 19-DEC-11:02 303.80 08-DEC-13:05 656.82 19-DEC-11:02 0.00
                                       
Annual Sum or Average 0.808015E+10 0.177900E+10 2197.14 0.695933E+10 0.112082E+10 0.00                         0.00
Minimum of Months 0.164359E+09 36898037.50 97.96 0.151447E+09 6888031.83 0.00 0.73   0.00   2591.90   2196.29   303.80   531.82   0.00
Maximum of Months 0.153769E+10 0.333468E+09 271.91 0.125770E+10 0.279994E+09 0.00 1.00   0.00   3901.85   3532.24   1427.98   865.58   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.198865E+09 44953704.39 74.56 0.174636E+09 24228542.97 0.00 0.36 24-JAN-15:00 0.00 01-JAN-00:10 1403.32 24-JAN-15:05 1338.43 18-JAN-13:50 247.41 20-JAN-15:30 325.31 24-JAN-15:00 0.00
February 95482349.48 21607354.35 50.44 85016630.25 10465719.23 0.00 0.31 03-FEB-14:55 0.00 01-FEB-00:10 1148.42 01-FEB-11:55 1148.42 01-FEB-11:55 220.24 01-FEB-16:00 274.67 01-FEB-11:55 0.00
March 0.135478E+09 30236759.63 58.00 0.107226E+09 28251999.18 0.00 0.39 23-MAR-15:00 0.00 01-MAR-00:10 1593.68 23-MAR-15:00 1243.01 23-MAR-14:15 376.14 23-MAR-16:00 349.28 23-MAR-14:40 0.00
April 0.521023E+09 0.115791E+09 152.29 0.430575E+09 90448029.64 0.00 0.52 26-APR-13:45 0.00 01-APR-00:10 2114.14 26-APR-13:45 1875.36 26-APR-14:00 377.36 27-APR-10:55 485.31 26-APR-13:30 0.00
May 0.742125E+09 0.163639E+09 191.65 0.634406E+09 0.107719E+09 0.00 0.55 04-MAY-14:00 0.00 01-MAY-00:10 2298.22 04-MAY-14:00 1961.33 04-MAY-13:53 382.00 05-MAY-15:00 498.32 04-MAY-14:00 0.00
June 0.123444E+10 0.268780E+09 223.64 0.991905E+09 0.242534E+09 0.00 0.62 29-JUN-13:00 0.00 01-JUN-00:10 2688.66 29-JUN-13:00 2074.25 30-JUN-14:40 676.74 30-JUN-05:02 579.14 29-JUN-13:00 0.00
July 0.175028E+10 0.377223E+09 234.05 0.135688E+10 0.393401E+09 0.00 1.00 19-JUL-05:02 0.00 01-JUL-00:10 4695.53 31-JUL-05:02 3195.93 28-JUL-05:02 1726.46 31-JUL-05:02 909.57 31-JUL-05:02 0.00
August 0.197316E+10 0.425515E+09 264.20 0.150327E+10 0.469895E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 4730.15 07-AUG-05:02 3201.58 01-AUG-05:02 1861.47 07-AUG-05:02 913.35 07-AUG-05:02 0.00
September 0.124770E+10 0.274307E+09 202.41 0.988268E+09 0.259435E+09 0.00 0.83 29-SEP-13:00 0.00 01-SEP-00:10 3304.12 29-SEP-13:00 3304.12 29-SEP-13:00 845.86 22-SEP-12:10 880.89 29-SEP-13:00 0.00
October 0.133447E+10 0.297361E+09 217.31 0.114809E+10 0.186379E+09 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 4727.09 05-OCT-05:02 4267.63 17-OCT-05:01 1623.97 05-OCT-05:02 956.46 16-OCT-10:53 0.00
November 0.365285E+09 81962893.62 147.19 0.323397E+09 41887658.26 0.00 0.37 10-NOV-13:10 0.00 01-NOV-00:10 1535.62 10-NOV-13:10 1261.40 28-NOV-13:55 323.46 10-NOV-15:00 333.59 10-NOV-13:10 0.00
December 0.197425E+09 44924691.20 89.72 0.189192E+09 8232606.70 0.00 0.35 05-DEC-14:55 0.00 01-DEC-00:10 1358.39 05-DEC-14:55 1358.39 05-DEC-14:55 236.06 07-DEC-16:00 316.96 05-DEC-14:55 0.00
                                       
Annual Sum or Average 0.979573E+10 0.214630E+10 1905.46 0.793285E+10 0.186288E+10 0.00                         0.00
Minimum of Months 95482349.48 21607354.35 50.44 85016630.25 8232606.70 0.00 0.31   0.00   1148.42   1148.42   220.24   274.67   0.00
Maximum of Months 0.197316E+10 0.425515E+09 264.20 0.150327E+10 0.469895E+09 0.00 1.00   0.00   4730.15   4267.63   1861.47   956.46   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.305577E+09 68892831.03 127.97 0.276739E+09 28837402.79 0.00 0.41 18-JAN-15:30 0.00 01-JAN-00:10 1603.27 18-JAN-15:30 1503.05 18-JAN-15:25 239.10 20-JAN-15:25 354.71 18-JAN-15:30 0.00
February 0.240339E+09 53881282.38 110.34 0.217148E+09 23191279.37 0.00 0.41 01-FEB-16:30 0.00 01-FEB-00:10 1637.60 01-FEB-16:30 1463.11 03-FEB-15:58 252.09 01-FEB-16:30 354.69 01-FEB-16:30 0.00
March 0.272968E+09 60750912.65 111.08 0.231179E+09 41789208.65 0.00 0.54 23-MAR-15:53 0.00 01-MAR-00:10 2210.88 23-MAR-15:53 1826.63 23-MAR-16:00 384.76 23-MAR-15:53 468.40 23-MAR-15:53 0.00
April 0.636560E+09 0.140770E+09 178.22 0.547382E+09 89177387.31 0.00 0.60 26-APR-15:53 0.00 01-APR-00:10 2447.21 26-APR-15:53 2169.17 26-APR-15:55 307.42 11-APR-15:23 520.50 26-APR-15:53 0.00
May 0.742920E+09 0.164117E+09 209.56 0.653060E+09 89860387.67 0.00 0.56 03-MAY-15:53 0.00 01-MAY-00:10 2288.04 03-MAY-15:53 2071.65 03-MAY-15:55 275.89 02-MAY-15:32 483.89 03-MAY-15:53 0.00
June 0.109186E+10 0.239565E+09 240.85 0.911072E+09 0.180790E+09 0.00 0.87 26-JUN-05:02 0.00 01-JUN-00:10 3816.42 26-JUN-05:02 3049.58 26-JUN-05:02 993.60 30-JUN-05:02 763.36 26-JUN-05:02 0.00
July 0.148257E+10 0.324140E+09 238.50 0.120264E+10 0.279937E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 4660.43 31-JUL-05:02 3777.85 10-JUL-05:02 1533.78 31-JUL-05:02 900.06 31-JUL-05:02 0.00
August 0.169813E+10 0.370953E+09 274.44 0.135904E+10 0.339085E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 4686.34 07-AUG-05:02 3422.19 03-AUG-05:02 1684.46 07-AUG-05:02 902.67 07-AUG-05:02 0.00
September 0.116189E+10 0.256747E+09 233.42 0.963608E+09 0.198286E+09 0.00 0.79 29-SEP-15:43 0.00 01-SEP-00:10 3139.44 29-SEP-15:48 3139.44 29-SEP-15:48 671.53 11-SEP-05:02 780.30 29-SEP-15:35 0.00
October 0.115917E+10 0.261258E+09 229.65 0.102894E+10 0.130221E+09 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 4658.50 05-OCT-05:02 4260.13 17-OCT-05:01 1471.47 05-OCT-05:02 899.85 05-OCT-05:02 0.00
November 0.525402E+09 0.117103E+09 185.44 0.478103E+09 47298805.09 0.00 0.45 10-NOV-15:23 0.00 01-NOV-00:10 1842.43 10-NOV-15:23 1532.79 10-NOV-15:25 310.03 10-NOV-15:13 395.86 10-NOV-15:23 0.00
December 0.345267E+09 77888607.02 143.17 0.331990E+09 13276984.40 0.00 0.42 07-DEC-15:40 0.00 01-DEC-00:10 1663.84 07-DEC-15:40 1591.79 05-DEC-15:30 239.79 07-DEC-15:40 361.43 05-DEC-15:23 0.00
                                       
Annual Sum or Average 0.966265E+10 0.213607E+10 2282.64 0.820090E+10 0.146175E+10 0.00                         0.00
Minimum of Months 0.240339E+09 53881282.38 110.34 0.217148E+09 13276984.40 0.00 0.41   0.00   1603.27   1463.11   239.10   354.69   0.00
Maximum of Months 0.169813E+10 0.370953E+09 274.44 0.135904E+10 0.339085E+09 0.00 1.00   0.00   4686.34   4260.13   1684.46   902.67   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 81.65 60.29 21.36 121.74 44.07 0.00 0.00 0.00
February 63.77 39.79 23.98 90.75 38.74 0.00 0.00 0.00
March 45.89 21.38 24.50 63.22 39.60 0.00 0.00 0.00
April 29.76 6.95 22.81 38.41 32.35 0.00 0.00 0.00
May 22.97 0.00 22.97 22.74 29.32 0.00 0.00 0.00
June 22.76 0.00 22.76 25.15 23.15 0.00 0.00 0.00
July 22.45 0.07 22.38 26.89 21.63 0.00 0.00 0.00
August 24.15 2.91 21.24 32.29 22.76 0.00 0.00 0.00
September 41.09 18.63 22.46 63.37 27.25 0.00 0.00 0.00
October 62.53 41.94 20.59 100.15 31.15 0.00 0.00 0.00
November 78.07 55.55 22.53 115.63 41.64 0.00 0.00 0.00
December 87.34 66.83 20.51 130.41 45.24 0.00 0.00 0.00
                 
Annual Sum or Average 48.47 26.15 22.32 69.15 33.05 0.00 0.00 0.00
Minimum of Months 22.45 0.00 20.51 22.74 21.63 0.00 0.00 0.00
Maximum of Months 87.34 66.83 24.50 130.41 45.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 81.65 60.29 21.36 121.74 44.07 0.00 0.00 0.00
February 63.77 39.79 23.98 90.75 38.74 0.00 0.00 0.00
March 45.87 21.37 24.50 63.20 39.60 0.00 0.00 0.00
April 29.61 6.88 22.72 38.06 32.35 0.00 0.00 0.00
May 22.97 0.00 22.97 22.74 29.32 0.00 0.00 0.00
June 22.76 0.00 22.76 25.15 23.15 0.00 0.00 0.00
July 22.45 0.07 22.38 26.89 21.63 0.00 0.00 0.00
August 24.11 2.90 21.22 32.21 22.76 0.00 0.00 0.00
September 40.96 18.58 22.38 63.14 27.30 0.00 0.00 0.00
October 62.53 41.94 20.59 100.15 31.15 0.00 0.00 0.00
November 78.07 55.55 22.53 115.62 41.63 0.00 0.00 0.00
December 87.34 66.83 20.51 130.41 45.24 0.00 0.00 0.00
                 
Annual Sum or Average 48.44 26.14 22.31 69.09 33.05 0.00 0.00 0.00
Minimum of Months 22.45 0.00 20.51 22.74 21.63 0.00 0.00 0.00
Maximum of Months 87.34 66.83 24.50 130.41 45.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 81.65 60.29 21.36 121.74 44.07 0.00 0.00 0.00
February 63.77 39.79 23.98 90.75 38.74 0.00 0.00 0.00
March 45.87 21.37 24.50 63.20 39.60 0.00 0.00 0.00
April 29.61 6.88 22.72 38.06 32.35 0.00 0.00 0.00
May 22.97 0.00 22.97 22.74 29.32 0.00 0.00 0.00
June 22.76 0.00 22.76 25.15 23.15 0.00 0.00 0.00
July 22.45 0.07 22.38 26.89 21.63 0.00 0.00 0.00
August 24.11 2.90 21.22 32.20 22.76 0.00 0.00 0.00
September 40.95 18.58 22.37 63.14 27.33 0.00 0.00 0.00
October 62.53 41.94 20.59 100.15 31.15 0.00 0.00 0.00
November 78.07 55.55 22.53 115.62 41.63 0.00 0.00 0.00
December 87.34 66.83 20.51 130.41 45.24 0.00 0.00 0.00
                 
Annual Sum or Average 48.44 26.14 22.31 69.09 33.06 0.00 0.00 0.00
Minimum of Months 22.45 0.00 20.51 22.74 21.63 0.00 0.00 0.00
Maximum of Months 87.34 66.83 24.50 130.41 45.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 81.65 60.29 21.36 121.74 44.07 0.00 0.00 0.00
February 63.77 39.79 23.98 90.75 38.74 0.00 0.00 0.00
March 45.87 21.37 24.50 63.20 39.60 0.00 0.00 0.00
April 29.61 6.88 22.72 38.06 32.35 0.00 0.00 0.00
May 22.97 0.00 22.97 22.74 29.32 0.00 0.00 0.00
June 22.76 0.00 22.76 25.15 23.15 0.00 0.00 0.00
July 22.45 0.07 22.38 26.89 21.63 0.00 0.00 0.00
August 24.11 2.90 21.22 32.20 22.76 0.00 0.00 0.00
September 40.95 18.58 22.37 63.14 27.33 0.00 0.00 0.00
October 62.53 41.94 20.59 100.15 31.15 0.00 0.00 0.00
November 78.07 55.55 22.53 115.62 41.63 0.00 0.00 0.00
December 87.34 66.83 20.51 130.41 45.24 0.00 0.00 0.00
                 
Annual Sum or Average 48.44 26.14 22.31 69.09 33.06 0.00 0.00 0.00
Minimum of Months 22.45 0.00 20.51 22.74 21.63 0.00 0.00 0.00
Maximum of Months 87.34 66.83 24.50 130.41 45.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 81.65 60.29 21.36 121.74 44.07 0.00 0.00 0.00
February 63.77 39.79 23.98 90.75 38.74 0.00 0.00 0.00
March 45.87 21.37 24.50 63.20 39.60 0.00 0.00 0.00
April 29.61 6.88 22.72 38.06 32.35 0.00 0.00 0.00
May 22.97 0.00 22.97 22.74 29.32 0.00 0.00 0.00
June 22.76 0.00 22.76 25.15 23.15 0.00 0.00 0.00
July 22.45 0.07 22.38 26.89 21.63 0.00 0.00 0.00
August 24.11 2.90 21.22 32.20 22.76 0.00 0.00 0.00
September 40.95 18.58 22.37 63.14 27.32 0.00 0.00 0.00
October 62.53 41.94 20.59 100.15 31.15 0.00 0.00 0.00
November 78.07 55.55 22.53 115.62 41.63 0.00 0.00 0.00
December 87.34 66.83 20.51 130.41 45.24 0.00 0.00 0.00
                 
Annual Sum or Average 48.44 26.14 22.31 69.09 33.06 0.00 0.00 0.00
Minimum of Months 22.45 0.00 20.51 22.74 21.63 0.00 0.00 0.00
Maximum of Months 87.34 66.83 24.50 130.41 45.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 81.65 60.29 21.36 121.74 44.07 0.00 0.00 0.00
February 63.77 39.79 23.98 90.75 38.74 0.00 0.00 0.00
March 45.88 21.38 24.50 63.21 39.59 0.00 0.00 0.00
April 29.73 6.94 22.79 38.33 32.32 0.00 0.00 0.00
May 22.97 0.00 22.97 22.74 29.32 0.00 0.00 0.00
June 22.76 0.00 22.76 25.15 23.15 0.00 0.00 0.00
July 22.45 0.07 22.38 26.89 21.63 0.00 0.00 0.00
August 24.14 2.91 21.24 32.28 22.76 0.00 0.00 0.00
September 41.01 18.60 22.41 63.21 27.27 0.00 0.00 0.00
October 62.53 41.94 20.59 100.15 31.15 0.00 0.00 0.00
November 78.07 55.55 22.53 115.63 41.64 0.00 0.00 0.00
December 87.34 66.83 20.51 130.41 45.24 0.00 0.00 0.00
                 
Annual Sum or Average 48.46 26.15 22.32 69.12 33.05 0.00 0.00 0.00
Minimum of Months 22.45 0.00 20.51 22.74 21.63 0.00 0.00 0.00
Maximum of Months 87.34 66.83 24.50 130.41 45.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 114.77 84.47 30.30 170.68 61.79 0.00 0.00 0.00
February 89.92 55.75 34.17 127.79 54.19 0.00 0.00 0.00
March 71.41 34.85 36.56 101.32 55.20 0.00 0.00 0.00
April 51.00 16.52 34.47 72.71 45.25 0.00 0.00 0.00
May 34.64 1.05 33.59 36.64 40.96 0.00 0.00 0.00
June 32.57 0.00 32.57 35.97 32.38 0.00 0.00 0.00
July 32.31 0.39 31.92 38.85 30.35 0.00 0.00 0.00
August 41.19 9.35 31.84 60.83 31.95 0.00 0.00 0.00
September 66.75 33.04 33.72 106.24 38.26 0.00 0.00 0.00
October 90.23 60.63 29.60 144.35 43.75 0.00 0.00 0.00
November 109.80 77.82 31.98 162.23 58.37 0.00 0.00 0.00
December 122.69 93.64 29.05 182.70 63.46 0.00 0.00 0.00
                 
Annual Sum or Average 71.36 38.90 32.46 103.26 46.29 0.00 0.00 0.00
Minimum of Months 32.31 0.00 29.05 35.97 30.35 0.00 0.00 0.00
Maximum of Months 122.69 93.64 36.56 182.70 63.46 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.14 17.30 14.83 40.13 40.95 0.00 0.00 0.00
February 33.45 15.44 18.00 39.39 36.41 0.00 0.00 0.00
March 40.46 18.14 22.32 49.52 37.42 0.00 0.00 0.00
April 51.15 25.24 25.91 69.68 30.88 0.00 0.00 0.00
May 47.80 19.64 28.17 62.43 28.56 0.00 0.00 0.00
June 47.23 19.87 27.36 65.36 22.97 0.00 0.00 0.00
July 53.73 26.03 27.70 78.90 21.96 0.00 0.00 0.00
August 53.55 27.88 25.68 79.86 22.46 0.00 0.00 0.00
September 38.97 17.51 21.47 55.05 25.54 0.00 0.00 0.00
October 35.16 18.07 17.09 51.02 28.86 0.00 0.00 0.00
November 32.33 16.53 15.80 39.58 39.13 0.00 0.00 0.00
December 31.05 17.36 13.70 38.52 42.11 0.00 0.00 0.00
                 
Annual Sum or Average 41.47 19.95 21.52 55.90 31.42 0.00 0.00 0.00
Minimum of Months 31.05 15.44 13.70 38.52 21.96 0.00 0.00 0.00
Maximum of Months 53.73 27.88 28.17 79.86 42.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.14 17.30 14.83 40.13 40.95 0.00 0.00 0.00
February 33.45 15.44 18.00 39.39 36.41 0.00 0.00 0.00
March 40.46 18.14 22.32 49.52 37.42 0.00 0.00 0.00
April 51.15 25.24 25.91 69.68 30.88 0.00 0.00 0.00
May 47.80 19.64 28.17 62.43 28.56 0.00 0.00 0.00
June 47.23 19.87 27.36 65.36 22.97 0.00 0.00 0.00
July 53.73 26.03 27.70 78.90 21.96 0.00 0.00 0.00
August 53.55 27.88 25.68 79.86 22.46 0.00 0.00 0.00
September 38.97 17.51 21.46 55.05 25.54 0.00 0.00 0.00
October 35.16 18.07 17.09 51.02 28.86 0.00 0.00 0.00
November 32.33 16.53 15.80 39.58 39.13 0.00 0.00 0.00
December 31.05 17.36 13.70 38.52 42.11 0.00 0.00 0.00
                 
Annual Sum or Average 41.47 19.95 21.52 55.90 31.42 0.00 0.00 0.00
Minimum of Months 31.05 15.44 13.70 38.52 21.96 0.00 0.00 0.00
Maximum of Months 53.73 27.88 28.17 79.86 42.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.14 17.30 14.83 40.13 40.95 0.00 0.00 0.00
February 33.45 15.44 18.00 39.39 36.41 0.00 0.00 0.00
March 40.46 18.14 22.32 49.52 37.42 0.00 0.00 0.00
April 51.15 25.24 25.91 69.68 30.88 0.00 0.00 0.00
May 47.80 19.64 28.17 62.43 28.56 0.00 0.00 0.00
June 47.23 19.87 27.36 65.36 22.97 0.00 0.00 0.00
July 53.73 26.03 27.70 78.90 21.96 0.00 0.00 0.00
August 53.55 27.88 25.68 79.86 22.46 0.00 0.00 0.00
September 38.97 17.51 21.46 55.05 25.54 0.00 0.00 0.00
October 35.16 18.07 17.09 51.02 28.86 0.00 0.00 0.00
November 32.33 16.53 15.80 39.58 39.13 0.00 0.00 0.00
December 31.05 17.36 13.70 38.52 42.11 0.00 0.00 0.00
                 
Annual Sum or Average 41.47 19.95 21.52 55.90 31.42 0.00 0.00 0.00
Minimum of Months 31.05 15.44 13.70 38.52 21.96 0.00 0.00 0.00
Maximum of Months 53.73 27.88 28.17 79.86 42.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 32.17 17.32 14.85 40.20 40.95 0.00 0.00 0.00
February 33.45 15.45 18.01 39.40 36.41 0.00 0.00 0.00
March 40.46 18.14 22.32 49.52 37.42 0.00 0.00 0.00
April 51.15 25.24 25.91 69.68 30.88 0.00 0.00 0.00
May 47.80 19.64 28.17 62.43 28.56 0.00 0.00 0.00
June 47.23 19.87 27.36 65.36 22.97 0.00 0.00 0.00
July 53.73 26.03 27.70 78.90 21.96 0.00 0.00 0.00
August 53.55 27.88 25.68 79.86 22.46 0.00 0.00 0.00
September 38.97 17.51 21.47 55.05 25.54 0.00 0.00 0.00
October 35.16 18.07 17.09 51.03 28.86 0.00 0.00 0.00
November 32.35 16.54 15.81 39.62 39.13 0.00 0.00 0.00
December 31.10 17.38 13.71 38.63 42.11 0.00 0.00 0.00
                 
Annual Sum or Average 41.48 19.96 21.52 55.92 31.42 0.00 0.00 0.00
Minimum of Months 31.10 15.45 13.71 38.63 21.96 0.00 0.00 0.00
Maximum of Months 53.73 27.88 28.17 79.86 42.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.91 0.00 11.91 8.99 41.76 0.00 0.00 0.00
February 14.80 0.00 14.80 10.59 37.28 0.00 0.00 0.00
March 18.12 0.00 18.12 14.99 38.46 0.00 0.00 0.00
April 21.22 0.08 21.14 20.75 30.72 0.00 0.00 0.00
May 24.99 1.07 23.92 24.71 27.42 0.00 0.00 0.00
June 26.35 2.31 24.03 29.93 21.68 0.00 0.00 0.00
July 25.27 1.86 23.42 30.89 20.42 0.00 0.00 0.00
August 21.44 0.39 21.06 25.97 21.45 0.00 0.00 0.00
September 18.09 0.00 18.08 20.41 25.46 0.00 0.00 0.00
October 14.27 0.00 14.27 17.45 28.93 0.00 0.00 0.00
November 12.91 0.00 12.91 9.55 39.92 0.00 0.00 0.00
December 11.13 0.00 11.13 7.92 43.26 0.00 0.00 0.00
                 
Annual Sum or Average 18.39 0.48 17.91 18.56 31.37 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 7.92 20.42 0.00 0.00 0.00
Maximum of Months 26.35 2.31 24.03 30.89 43.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.91 0.00 11.91 8.99 41.76 0.00 0.00 0.00
February 14.80 0.00 14.80 10.59 37.28 0.00 0.00 0.00
March 18.11 0.00 18.11 14.99 38.46 0.00 0.00 0.00
April 21.19 0.07 21.12 20.74 30.78 0.00 0.00 0.00
May 24.91 1.03 23.87 24.52 27.43 0.00 0.00 0.00
June 26.29 2.29 24.00 29.79 21.68 0.00 0.00 0.00
July 25.18 1.82 23.37 30.68 20.42 0.00 0.00 0.00
August 21.38 0.36 21.02 25.83 21.46 0.00 0.00 0.00
September 18.09 0.00 18.08 20.41 25.46 0.00 0.00 0.00
October 14.27 0.00 14.27 17.45 28.93 0.00 0.00 0.00
November 12.91 0.00 12.91 9.55 39.92 0.00 0.00 0.00
December 11.13 0.00 11.13 7.92 43.25 0.00 0.00 0.00
                 
Annual Sum or Average 18.36 0.47 17.90 18.50 31.38 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 7.92 20.42 0.00 0.00 0.00
Maximum of Months 26.29 2.29 24.00 30.68 43.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.91 0.00 11.91 8.99 41.76 0.00 0.00 0.00
February 14.80 0.00 14.80 10.59 37.28 0.00 0.00 0.00
March 18.11 0.00 18.11 14.99 38.46 0.00 0.00 0.00
April 21.19 0.07 21.12 20.74 30.79 0.00 0.00 0.00
May 24.91 1.03 23.87 24.52 27.43 0.00 0.00 0.00
June 26.29 2.29 24.00 29.79 21.68 0.00 0.00 0.00
July 25.18 1.82 23.37 30.68 20.42 0.00 0.00 0.00
August 21.38 0.36 21.02 25.83 21.47 0.00 0.00 0.00
September 18.08 0.00 18.08 20.41 25.46 0.00 0.00 0.00
October 14.27 0.00 14.27 17.45 28.93 0.00 0.00 0.00
November 12.91 0.00 12.91 9.55 39.92 0.00 0.00 0.00
December 11.13 0.00 11.13 7.92 43.25 0.00 0.00 0.00
                 
Annual Sum or Average 18.36 0.47 17.90 18.50 31.38 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 7.92 20.42 0.00 0.00 0.00
Maximum of Months 26.29 2.29 24.00 30.68 43.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.91 0.00 11.91 8.99 41.76 0.00 0.00 0.00
February 14.80 0.00 14.80 10.59 37.28 0.00 0.00 0.00
March 18.11 0.00 18.11 14.99 38.46 0.00 0.00 0.00
April 21.19 0.07 21.12 20.74 30.79 0.00 0.00 0.00
May 24.91 1.03 23.87 24.52 27.43 0.00 0.00 0.00
June 26.29 2.29 24.00 29.79 21.68 0.00 0.00 0.00
July 25.18 1.82 23.37 30.68 20.42 0.00 0.00 0.00
August 21.38 0.36 21.02 25.83 21.47 0.00 0.00 0.00
September 18.08 0.00 18.08 20.41 25.46 0.00 0.00 0.00
October 14.27 0.00 14.27 17.45 28.93 0.00 0.00 0.00
November 12.91 0.00 12.91 9.55 39.92 0.00 0.00 0.00
December 11.13 0.00 11.13 7.92 43.25 0.00 0.00 0.00
                 
Annual Sum or Average 18.36 0.47 17.90 18.50 31.38 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 7.92 20.42 0.00 0.00 0.00
Maximum of Months 26.29 2.29 24.00 30.68 43.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.91 0.00 11.91 8.99 41.76 0.00 0.00 0.00
February 14.80 0.00 14.80 10.59 37.28 0.00 0.00 0.00
March 18.11 0.00 18.11 14.99 38.46 0.00 0.00 0.00
April 21.19 0.07 21.12 20.75 30.78 0.00 0.00 0.00
May 24.91 1.03 23.87 24.52 27.43 0.00 0.00 0.00
June 26.29 2.29 24.00 29.79 21.68 0.00 0.00 0.00
July 25.18 1.82 23.37 30.68 20.42 0.00 0.00 0.00
August 21.38 0.36 21.02 25.83 21.47 0.00 0.00 0.00
September 18.08 0.00 18.08 20.41 25.46 0.00 0.00 0.00
October 14.27 0.00 14.27 17.45 28.93 0.00 0.00 0.00
November 12.91 0.00 12.91 9.55 39.92 0.00 0.00 0.00
December 11.13 0.00 11.13 7.92 43.25 0.00 0.00 0.00
                 
Annual Sum or Average 18.36 0.47 17.90 18.50 31.38 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 7.92 20.42 0.00 0.00 0.00
Maximum of Months 26.29 2.29 24.00 30.68 43.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.91 0.00 11.91 8.99 41.76 0.00 0.00 0.00
February 14.80 0.00 14.80 10.59 37.28 0.00 0.00 0.00
March 18.12 0.00 18.12 14.99 38.46 0.00 0.00 0.00
April 21.25 0.08 21.17 20.81 30.74 0.00 0.00 0.00
May 25.02 1.08 23.94 24.78 27.43 0.00 0.00 0.00
June 26.38 2.33 24.05 30.01 21.68 0.00 0.00 0.00
July 25.30 1.87 23.43 30.96 20.42 0.00 0.00 0.00
August 21.47 0.39 21.08 26.04 21.46 0.00 0.00 0.00
September 18.09 0.00 18.08 20.41 25.46 0.00 0.00 0.00
October 14.27 0.00 14.27 17.45 28.93 0.00 0.00 0.00
November 12.91 0.00 12.91 9.55 39.92 0.00 0.00 0.00
December 11.13 0.00 11.13 7.92 43.26 0.00 0.00 0.00
                 
Annual Sum or Average 18.40 0.48 17.92 18.59 31.37 0.00 0.00 0.00
Minimum of Months 11.13 0.00 11.13 7.92 20.42 0.00 0.00 0.00
Maximum of Months 26.38 2.33 24.05 30.96 43.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.56 15.50 15.06 39.83 43.04 0.00 0.00 0.00
February 36.24 16.90 19.34 45.19 38.29 0.00 0.00 0.00
March 41.04 18.24 22.79 51.66 39.21 0.00 0.00 0.00
April 56.32 28.95 27.37 78.77 32.90 0.00 0.00 0.00
May 54.89 25.04 29.85 74.16 30.28 0.00 0.00 0.00
June 58.21 28.78 29.43 82.62 24.21 0.00 0.00 0.00
July 61.69 32.49 29.20 91.22 23.00 0.00 0.00 0.00
August 58.14 31.04 27.10 87.42 23.92 0.00 0.00 0.00
September 50.03 26.61 23.43 73.08 27.09 0.00 0.00 0.00
October 38.61 21.09 17.52 57.90 30.48 0.00 0.00 0.00
November 35.14 18.51 16.63 46.02 40.97 0.00 0.00 0.00
December 31.27 16.87 14.40 41.22 44.38 0.00 0.00 0.00
                 
Annual Sum or Average 46.05 23.36 22.69 64.18 33.13 0.00 0.00 0.00
Minimum of Months 30.56 15.50 14.40 39.83 23.00 0.00 0.00 0.00
Maximum of Months 61.69 32.49 29.85 91.22 44.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.53 15.49 15.05 39.76 43.04 0.00 0.00 0.00
February 36.24 16.90 19.34 45.18 38.28 0.00 0.00 0.00
March 41.04 18.24 22.79 51.65 39.21 0.00 0.00 0.00
April 56.32 28.95 27.37 78.77 32.90 0.00 0.00 0.00
May 54.89 25.04 29.85 74.16 30.28 0.00 0.00 0.00
June 58.21 28.78 29.43 82.62 24.21 0.00 0.00 0.00
July 61.69 32.49 29.20 91.22 23.00 0.00 0.00 0.00
August 58.14 31.04 27.10 87.42 23.91 0.00 0.00 0.00
September 50.03 26.61 23.43 73.08 27.09 0.00 0.00 0.00
October 38.60 21.09 17.51 57.89 30.48 0.00 0.00 0.00
November 35.12 18.50 16.63 45.97 40.97 0.00 0.00 0.00
December 31.23 16.84 14.39 41.12 44.38 0.00 0.00 0.00
                 
Annual Sum or Average 46.04 23.36 22.68 64.16 33.12 0.00 0.00 0.00
Minimum of Months 30.53 15.49 14.39 39.76 23.00 0.00 0.00 0.00
Maximum of Months 61.69 32.49 29.85 91.22 44.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.53 15.49 15.05 39.76 43.04 0.00 0.00 0.00
February 36.24 16.90 19.34 45.18 38.28 0.00 0.00 0.00
March 41.04 18.24 22.79 51.65 39.21 0.00 0.00 0.00
April 56.32 28.95 27.37 78.77 32.90 0.00 0.00 0.00
May 54.89 25.04 29.85 74.16 30.28 0.00 0.00 0.00
June 58.21 28.78 29.43 82.62 24.21 0.00 0.00 0.00
July 61.69 32.49 29.20 91.22 23.00 0.00 0.00 0.00
August 58.14 31.04 27.10 87.42 23.91 0.00 0.00 0.00
September 50.03 26.61 23.43 73.08 27.09 0.00 0.00 0.00
October 38.60 21.09 17.51 57.89 30.48 0.00 0.00 0.00
November 35.12 18.50 16.63 45.97 40.97 0.00 0.00 0.00
December 31.23 16.84 14.39 41.12 44.38 0.00 0.00 0.00
                 
Annual Sum or Average 46.04 23.36 22.68 64.16 33.12 0.00 0.00 0.00
Minimum of Months 30.53 15.49 14.39 39.76 23.00 0.00 0.00 0.00
Maximum of Months 61.69 32.49 29.85 91.22 44.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.53 15.49 15.05 39.76 43.04 0.00 0.00 0.00
February 36.24 16.90 19.34 45.19 38.29 0.00 0.00 0.00
March 41.04 18.24 22.79 51.66 39.21 0.00 0.00 0.00
April 56.32 28.95 27.37 78.77 32.90 0.00 0.00 0.00
May 54.89 25.04 29.85 74.16 30.28 0.00 0.00 0.00
June 58.21 28.78 29.43 82.62 24.21 0.00 0.00 0.00
July 61.69 32.49 29.20 91.22 23.00 0.00 0.00 0.00
August 58.14 31.04 27.10 87.42 23.92 0.00 0.00 0.00
September 50.03 26.61 23.43 73.08 27.09 0.00 0.00 0.00
October 38.60 21.09 17.52 57.89 30.48 0.00 0.00 0.00
November 35.12 18.50 16.63 45.98 40.97 0.00 0.00 0.00
December 31.23 16.84 14.39 41.12 44.38 0.00 0.00 0.00
                 
Annual Sum or Average 46.04 23.36 22.68 64.16 33.13 0.00 0.00 0.00
Minimum of Months 30.53 15.49 14.39 39.76 23.00 0.00 0.00 0.00
Maximum of Months 61.69 32.49 29.85 91.22 44.38 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.218702E+09 0.161489E+09 57212967.06 0.326066E+09 0.118038E+09
February 0.154269E+09 96260515.21 58008085.92 0.219549E+09 93730628.66
March 0.122899E+09 57265003.66 65633633.85 0.169324E+09 0.106056E+09
April 77125192.46 18014455.89 59110736.57 99565552.50 83839236.11
May 61524986.38 914.05 61524072.32 60917793.97 78534459.21
June 59004246.40 0.34 59004246.06 65184460.98 59998922.93
July 60123143.21 189009.92 59934133.29 72030340.93 57927734.25
August 64682100.86 7799350.54 56882750.32 86492357.33 60959899.83
September 0.106495E+09 48282561.67 58212733.26 0.164267E+09 70622541.67
October 0.167484E+09 0.112343E+09 55140747.33 0.268230E+09 83424911.73
November 0.202370E+09 0.143974E+09 58395846.21 0.299700E+09 0.107918E+09
December 0.233936E+09 0.179009E+09 54926829.03 0.349288E+09 0.121167E+09
           
Annual Sum or Average 0.152861E+10 0.824628E+09 0.703987E+09 0.218061E+10 0.104222E+10
Minimum of Months 59004246.40 0.34 54926829.03 60917793.97 57927734.25
Maximum of Months 0.233936E+09 0.179009E+09 65633633.85 0.349288E+09 0.121167E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.218700E+09 0.161489E+09 57211371.57 0.326065E+09 0.118036E+09
February 0.154266E+09 96260515.21 58005866.80 0.219546E+09 93729333.38
March 0.122863E+09 57248974.06 65613706.35 0.169266E+09 0.106075E+09
April 76748096.74 17845530.30 58902566.44 98664467.81 83855019.03
May 61516457.38 0.00 61516457.38 60903016.70 78533578.97
June 59001459.05 0.00 59001459.05 65181537.67 59998184.19
July 60118747.94 187362.76 59931385.18 72021701.58 57926649.29
August 64587783.88 7757453.48 56830330.40 86258657.28 60960970.24
September 0.106168E+09 48153474.50 58014502.94 0.163652E+09 70770025.87
October 0.167482E+09 0.112343E+09 55138822.18 0.268229E+09 83423144.36
November 0.202369E+09 0.143974E+09 58394121.12 0.299699E+09 0.107916E+09
December 0.233935E+09 0.179009E+09 54925447.32 0.349287E+09 0.121164E+09
           
Annual Sum or Average 0.152776E+10 0.824269E+09 0.703486E+09 0.217877E+10 0.104239E+10
Minimum of Months 59001459.05 0.00 54925447.32 60903016.70 57926649.29
Maximum of Months 0.233935E+09 0.179009E+09 65613706.35 0.349287E+09 0.121164E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.218700E+09 0.161489E+09 57211371.57 0.326065E+09 0.118036E+09
February 0.154266E+09 96260515.21 58005866.80 0.219546E+09 93729333.38
March 0.122863E+09 57248974.06 65613706.35 0.169266E+09 0.106075E+09
April 76748096.74 17845530.30 58902566.44 98664467.81 83855019.03
May 61516457.38 0.00 61516457.38 60903016.70 78533578.97
June 59001459.05 0.00 59001459.05 65181537.67 59998184.19
July 60118747.94 187362.76 59931385.18 72021701.58 57926649.29
August 64587186.05 7756870.44 56830315.61 86257788.48 60962453.72
September 0.106138E+09 48149122.20 57988702.93 0.163649E+09 70831188.86
October 0.167482E+09 0.112343E+09 55138822.18 0.268229E+09 83423144.36
November 0.202369E+09 0.143974E+09 58394121.12 0.299699E+09 0.107916E+09
December 0.233935E+09 0.179009E+09 54925447.32 0.349287E+09 0.121164E+09
           
Annual Sum or Average 0.152772E+10 0.824264E+09 0.703460E+09 0.217877E+10 0.104245E+10
Minimum of Months 59001459.05 0.00 54925447.32 60903016.70 57926649.29
Maximum of Months 0.233935E+09 0.179009E+09 65613706.35 0.349287E+09 0.121164E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.218700E+09 0.161489E+09 57211371.57 0.326065E+09 0.118036E+09
February 0.154266E+09 96260515.21 58005866.80 0.219546E+09 93729333.38
March 0.122863E+09 57248974.06 65613706.35 0.169266E+09 0.106075E+09
April 76748096.74 17845530.30 58902566.44 98664467.81 83855019.03
May 61516457.38 0.00 61516457.38 60903016.70 78533578.97
June 59001459.05 0.00 59001459.05 65181537.67 59998184.19
July 60118747.94 187362.76 59931385.18 72021701.58 57926649.29
August 64587185.61 7756870.00 56830315.61 86257788.48 60962455.74
September 0.106137E+09 48149091.73 57987727.13 0.163649E+09 70833077.75
October 0.167482E+09 0.112343E+09 55138822.18 0.268229E+09 83423144.36
November 0.202369E+09 0.143974E+09 58394121.12 0.299699E+09 0.107916E+09
December 0.233935E+09 0.179009E+09 54925447.32 0.349287E+09 0.121164E+09
           
Annual Sum or Average 0.152772E+10 0.824264E+09 0.703459E+09 0.217877E+10 0.104245E+10
Minimum of Months 59001459.05 0.00 54925447.32 60903016.70 57926649.29
Maximum of Months 0.233935E+09 0.179009E+09 65613706.35 0.349287E+09 0.121164E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.218700E+09 0.161489E+09 57211371.57 0.326065E+09 0.118036E+09
February 0.154266E+09 96260515.21 58005866.80 0.219546E+09 93729333.38
March 0.122863E+09 57248974.06 65613706.35 0.169266E+09 0.106075E+09
April 76748096.74 17845530.30 58902566.44 98664467.81 83855019.03
May 61516457.38 0.00 61516457.38 60903016.70 78533578.97
June 59001459.05 0.00 59001459.05 65181537.67 59998184.19
July 60118747.94 187362.76 59931385.18 72021701.58 57926649.29
August 64587682.42 7757366.81 56830315.61 86257784.98 60960495.35
September 0.106147E+09 48151085.57 57995925.27 0.163649E+09 70810184.38
October 0.167482E+09 0.112343E+09 55138822.18 0.268229E+09 83423144.36
November 0.202369E+09 0.143974E+09 58394121.12 0.299699E+09 0.107916E+09
December 0.233935E+09 0.179009E+09 54925447.32 0.349287E+09 0.121164E+09
           
Annual Sum or Average 0.152773E+10 0.824267E+09 0.703467E+09 0.217877E+10 0.104243E+10
Minimum of Months 59001459.05 0.00 54925447.32 60903016.70 57926649.29
Maximum of Months 0.233935E+09 0.179009E+09 65613706.35 0.349287E+09 0.121164E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.218702E+09 0.161489E+09 57212966.98 0.326066E+09 0.118038E+09
February 0.154269E+09 96260515.21 58008085.81 0.219549E+09 93730628.59
March 0.122895E+09 57265032.83 65629490.98 0.169297E+09 0.106037E+09
April 77062431.21 17980346.77 59082084.43 99342014.84 83774613.78
May 61524223.51 678.74 61523544.76 60916213.47 78534451.50
June 59004245.99 0.38 59004245.61 65184460.45 59998922.89
July 60122802.43 188831.45 59933970.99 72029289.00 57927734.20
August 64669387.43 7791435.87 56877951.57 86450829.52 60955208.88
September 0.106286E+09 48210363.66 58076067.48 0.163850E+09 70681219.97
October 0.167484E+09 0.112343E+09 55140747.23 0.268230E+09 83424911.64
November 0.202370E+09 0.143974E+09 58395846.12 0.299700E+09 0.107918E+09
December 0.233936E+09 0.179009E+09 54926828.96 0.349288E+09 0.121167E+09
           
Annual Sum or Average 0.152832E+10 0.824513E+09 0.703812E+09 0.217990E+10 0.104219E+10
Minimum of Months 59004245.99 0.38 54926828.96 60916213.47 57927734.20
Maximum of Months 0.233936E+09 0.179009E+09 65629490.98 0.349288E+09 0.121167E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.307405E+09 0.226248E+09 81157255.78 0.457151E+09 0.165489E+09
February 0.217525E+09 0.134862E+09 82662550.57 0.309140E+09 0.131100E+09
March 0.191278E+09 93352343.63 97925237.44 0.271379E+09 0.147854E+09
April 0.132180E+09 42828033.90 89351894.89 0.188456E+09 0.117284E+09
May 92777068.68 2811580.32 89965488.36 98123639.27 0.109713E+09
June 84414327.93 0.00 84414327.93 93240756.72 83926834.29
July 86544794.02 1057047.51 85487746.51 0.104065E+09 81296141.01
August 0.110327E+09 25038271.73 85288255.01 0.162939E+09 85580188.77
September 0.173021E+09 85627673.41 87393806.21 0.275366E+09 99168986.95
October 0.241678E+09 0.162395E+09 79282271.44 0.386622E+09 0.117192E+09
November 0.284606E+09 0.201710E+09 82895807.77 0.420504E+09 0.151288E+09
December 0.328615E+09 0.250794E+09 77820206.44 0.489344E+09 0.169978E+09
           
Annual Sum or Average 0.225037E+10 0.122673E+10 0.102364E+10 0.325633E+10 0.145987E+10
Minimum of Months 84414327.93 0.00 77820206.44 93240756.72 81296141.01
Maximum of Months 0.328615E+09 0.250794E+09 97925237.44 0.489344E+09 0.169978E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86079032.57 46349475.55 39729557.03 0.107474E+09 0.109685E+09
February 80918048.88 37361964.32 43556084.56 95300732.58 88090436.76
March 0.108361E+09 48586023.10 59774814.64 0.132631E+09 0.100233E+09
April 0.132576E+09 65417104.67 67158857.32 0.180612E+09 80052419.75
May 0.128040E+09 52591481.15 75448234.18 0.167205E+09 76486129.36
June 0.122419E+09 51506524.37 70912328.86 0.169422E+09 59534526.33
July 0.143907E+09 69708652.99 74198544.00 0.211327E+09 58827214.97
August 0.143441E+09 74661266.83 68779832.78 0.213893E+09 60167531.48
September 0.101016E+09 45377370.66 55638529.23 0.142697E+09 66211252.51
October 94175193.15 48390838.95 45784354.20 0.136663E+09 77288288.79
November 83794726.31 42838146.69 40956579.62 0.102585E+09 0.101436E+09
December 83174061.81 46491696.85 36682364.96 0.103176E+09 0.112798E+09
           
Annual Sum or Average 0.130790E+10 0.629281E+09 0.678620E+09 0.176299E+10 0.990809E+09
Minimum of Months 80918048.88 37361964.32 36682364.96 95300732.58 58827214.97
Maximum of Months 0.143907E+09 74661266.83 75448234.18 0.213893E+09 0.112798E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86077437.17 46349475.55 39727961.62 0.107473E+09 0.109683E+09
February 80915829.87 37361964.32 43553865.56 95298386.84 88089264.31
March 0.108358E+09 48586023.10 59771734.39 0.132627E+09 0.100232E+09
April 0.132574E+09 65417104.67 67156595.16 0.180610E+09 80051233.94
May 0.128036E+09 52591481.15 75445010.02 0.167201E+09 76485147.65
June 0.122416E+09 51506524.37 70909542.31 0.169419E+09 59533705.60
July 0.143905E+09 69708652.99 74196546.64 0.211326E+09 58826061.56
August 0.143439E+09 74661266.83 68778036.84 0.213892E+09 60166223.12
September 0.101014E+09 45377370.66 55636466.42 0.142695E+09 66209894.69
October 94173268.10 48390838.95 45782429.15 0.136661E+09 77286497.28
November 83793001.31 42838146.69 40954854.62 0.102583E+09 0.101434E+09
December 83172680.17 46491696.85 36680983.32 0.103176E+09 0.112796E+09
           
Annual Sum or Average 0.130787E+10 0.629281E+09 0.678594E+09 0.176296E+10 0.990792E+09
Minimum of Months 80915829.87 37361964.32 36680983.32 95298386.84 58826061.56
Maximum of Months 0.143905E+09 74661266.83 75445010.02 0.213892E+09 0.112796E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86077437.17 46349475.55 39727961.62 0.107473E+09 0.109683E+09
February 80915829.87 37361964.32 43553865.56 95298386.84 88089264.31
March 0.108358E+09 48586023.10 59771734.39 0.132627E+09 0.100232E+09
April 0.132574E+09 65417104.67 67156595.16 0.180610E+09 80051233.94
May 0.128036E+09 52591481.15 75445010.02 0.167201E+09 76485147.65
June 0.122416E+09 51506524.37 70909542.31 0.169419E+09 59533705.60
July 0.143905E+09 69708652.99 74196546.64 0.211326E+09 58826061.56
August 0.143439E+09 74661266.83 68778036.84 0.213892E+09 60166223.12
September 0.101014E+09 45377370.66 55636466.42 0.142695E+09 66209894.69
October 94173268.10 48390838.95 45782429.15 0.136661E+09 77286497.28
November 83793001.31 42838146.69 40954854.62 0.102583E+09 0.101434E+09
December 83172680.17 46491696.85 36680983.32 0.103176E+09 0.112796E+09
           
Annual Sum or Average 0.130787E+10 0.629281E+09 0.678594E+09 0.176296E+10 0.990792E+09
Minimum of Months 80915829.87 37361964.32 36680983.32 95298386.84 58826061.56
Maximum of Months 0.143905E+09 74661266.83 75445010.02 0.213892E+09 0.112796E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 86155344.63 46394490.45 39760854.18 0.107674E+09 0.109685E+09
February 80923353.02 37364631.66 43558721.36 95313549.35 88090436.82
March 0.108361E+09 48586184.32 59774892.89 0.132632E+09 0.100233E+09
April 0.132576E+09 65417104.67 67158857.44 0.180612E+09 80052419.81
May 0.128040E+09 52591481.15 75448234.35 0.167205E+09 76486129.41
June 0.122419E+09 51506524.37 70912329.00 0.169422E+09 59534526.38
July 0.143907E+09 69708652.99 74198544.11 0.211327E+09 58827215.03
August 0.143441E+09 74661266.83 68779832.87 0.213893E+09 60167531.54
September 0.101016E+09 45377370.66 55638529.34 0.142697E+09 66211252.58
October 94180766.88 48395233.06 45785533.83 0.136678E+09 77288288.88
November 83840473.26 42865308.68 40975164.58 0.102702E+09 0.101436E+09
December 83285835.07 46558411.64 36727423.43 0.103468E+09 0.112798E+09
           
Annual Sum or Average 0.130815E+10 0.629427E+09 0.678719E+09 0.176362E+10 0.990809E+09
Minimum of Months 80923353.02 37364631.66 36727423.43 95313549.35 58827215.03
Maximum of Months 0.143907E+09 74661266.83 75448234.35 0.213893E+09 0.112798E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31912839.45 0.00 31912839.45 24078523.88 0.111850E+09
February 35810603.46 0.00 35810603.46 25628494.87 90181243.86
March 48521677.31 0.00 48521677.31 40144209.98 0.103023E+09
April 54999144.17 201565.24 54797578.92 53777609.27 79635508.42
May 66938524.03 2862411.87 64076112.16 66172637.45 73437038.21
June 68293571.87 5996748.83 62296823.04 77590004.87 56186621.13
July 67695338.62 4975247.99 62720090.63 82748797.47 54683526.41
August 57434386.96 1034247.04 56400139.92 69549708.66 57443787.11
September 46879584.41 6897.56 46872686.85 52910302.01 65995514.35
October 38219101.53 0.00 38219101.53 46732898.96 77487872.04
November 33453723.30 0.00 33453723.30 24753671.09 0.103476E+09
December 29802006.56 0.00 29802006.56 21219317.88 0.115856E+09
           
Annual Sum or Average 0.579961E+09 15077118.53 0.564883E+09 0.585306E+09 0.989255E+09
Minimum of Months 29802006.56 0.00 29802006.56 21219317.88 54683526.41
Maximum of Months 68293571.87 5996748.83 64076112.16 82748797.47 0.115856E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31911243.97 0.00 31911243.97 24077291.11 0.111848E+09
February 35808384.34 0.00 35808384.34 25626249.20 90180068.31
March 48518596.90 0.00 48518596.90 40140566.65 0.103022E+09
April 54929583.64 185641.66 54743941.98 53767930.95 79779981.77
May 66710494.08 2771934.75 63938559.33 65662590.57 73464204.06
June 68135379.45 5923908.26 62211471.18 77218034.18 56187064.03
July 67454207.69 4862571.09 62591636.61 82173879.36 54686331.11
August 57259526.03 967878.88 56291647.15 69173475.15 57488432.96
September 46876614.24 6875.41 46869738.83 52908376.33 65995931.26
October 38217176.38 0.00 38217176.38 46731179.77 77486003.48
November 33451998.21 0.00 33451998.21 24752248.56 0.103474E+09
December 29800624.85 0.00 29800624.85 21218637.39 0.115853E+09
           
Annual Sum or Average 0.579074E+09 14718810.05 0.564355E+09 0.583450E+09 0.989465E+09
Minimum of Months 29800624.85 0.00 29800624.85 21218637.39 54686331.11
Maximum of Months 68135379.45 5923908.26 63938559.33 82173879.36 0.115853E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31911243.97 0.00 31911243.97 24077291.11 0.111848E+09
February 35808384.34 0.00 35808384.34 25626249.20 90180068.31
March 48518596.90 0.00 48518596.90 40140566.65 0.103022E+09
April 54918887.27 183115.77 54735771.50 53767794.13 79804600.52
May 66710494.08 2771934.75 63938559.33 65662590.57 73464204.06
June 68135379.45 5923908.26 62211471.18 77218034.18 56187064.03
July 67454207.69 4862571.09 62591636.61 82173879.36 54686331.11
August 57256962.09 967837.23 56289124.86 69173475.21 57493156.66
September 46874831.69 6914.02 46867917.67 52908376.33 65999075.35
October 38217176.38 0.00 38217176.38 46731179.77 77486003.48
November 33451998.21 0.00 33451998.21 24752248.56 0.103474E+09
December 29800624.85 0.00 29800624.85 21218637.39 0.115853E+09
           
Annual Sum or Average 0.579059E+09 14716281.12 0.564343E+09 0.583450E+09 0.989497E+09
Minimum of Months 29800624.85 0.00 29800624.85 21218637.39 54686331.11
Maximum of Months 68135379.45 5923908.26 63938559.33 82173879.36 0.115853E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31911243.97 0.00 31911243.97 24077291.11 0.111848E+09
February 35808384.34 0.00 35808384.34 25626249.20 90180068.31
March 48518596.90 0.00 48518596.90 40140566.65 0.103022E+09
April 54918887.27 183115.77 54735771.50 53767794.13 79804600.52
May 66710494.08 2771934.75 63938559.33 65662590.57 73464204.06
June 68135379.45 5923908.26 62211471.18 77218034.18 56187064.03
July 67454207.69 4862571.09 62591636.61 82173879.36 54686331.11
August 57255354.38 967809.26 56287545.12 69173475.21 57496054.71
September 46874916.35 7043.49 46867872.86 52908376.33 65998590.84
October 38217176.38 0.00 38217176.38 46731179.77 77486003.48
November 33451998.21 0.00 33451998.21 24752248.56 0.103474E+09
December 29800624.85 0.00 29800624.85 21218637.39 0.115853E+09
           
Annual Sum or Average 0.579057E+09 14716382.62 0.564341E+09 0.583450E+09 0.989500E+09
Minimum of Months 29800624.85 0.00 29800624.85 21218637.39 54686331.11
Maximum of Months 68135379.45 5923908.26 63938559.33 82173879.36 0.115853E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31911243.97 0.00 31911243.97 24077291.11 0.111848E+09
February 35808384.34 0.00 35808384.34 25626249.20 90180068.31
March 48518596.90 0.00 48518596.90 40140566.65 0.103022E+09
April 54937107.26 185574.56 54751532.70 53779500.48 79778541.58
May 66710494.08 2771934.75 63938559.33 65662590.57 73464204.06
June 68135379.45 5923908.26 62211471.18 77218034.18 56187064.03
July 67454207.69 4862571.09 62591636.61 82173879.36 54686331.11
August 57254849.38 967784.91 56287064.47 69173475.20 57496965.77
September 46875976.17 7198.04 46868778.12 52908376.33 65996304.22
October 38217176.38 0.00 38217176.38 46731179.77 77486003.48
November 33451998.21 0.00 33451998.21 24752248.56 0.103474E+09
December 29800624.85 0.00 29800624.85 21218637.39 0.115853E+09
           
Annual Sum or Average 0.579076E+09 14718971.61 0.564357E+09 0.583462E+09 0.989472E+09
Minimum of Months 29800624.85 0.00 29800624.85 21218637.39 54686331.11
Maximum of Months 68135379.45 5923908.26 63938559.33 82173879.36 0.115853E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31912839.37 0.00 31912839.37 24078523.81 0.111850E+09
February 35810603.34 0.00 35810603.34 25628494.76 90181243.80
March 48521677.15 0.00 48521677.15 40144209.79 0.103023E+09
April 55068719.46 200178.06 54868541.41 53929515.42 79669611.93
May 67022079.03 2892192.88 64129886.14 66369280.65 73457360.88
June 68369894.57 6041057.72 62328836.85 77773234.66 56187818.62
July 67772069.41 5011348.12 62760721.29 82935607.76 54687373.95
August 57510155.28 1055728.41 56454426.88 69758028.93 57488028.58
September 46878824.41 7229.63 46871594.78 52910301.91 65996065.63
October 38219101.43 0.00 38219101.43 46732898.87 77487871.94
November 33453723.21 0.00 33453723.21 24753671.02 0.103476E+09
December 29802006.49 0.00 29802006.49 21219317.85 0.115856E+09
           
Annual Sum or Average 0.580342E+09 15207734.82 0.565134E+09 0.586233E+09 0.989360E+09
Minimum of Months 29802006.49 0.00 29802006.49 21219317.85 54687373.95
Maximum of Months 68369894.57 6041057.72 64129886.14 82935607.76 0.115856E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 81854845.98 41522307.39 40332538.60 0.106689E+09 0.115270E+09
February 87669455.35 40878149.51 46791305.84 0.109322E+09 92619421.78
March 0.109914E+09 48859943.87 61053837.64 0.138355E+09 0.105025E+09
April 0.145978E+09 75034539.89 70943438.42 0.204176E+09 85288644.65
May 0.147019E+09 67072420.47 79946835.11 0.198633E+09 81101632.46
June 0.150891E+09 74608560.72 76282325.89 0.214161E+09 62760606.76
July 0.165230E+09 87009393.60 78220215.51 0.244327E+09 61602925.28
August 0.155720E+09 83128406.64 72591136.14 0.234137E+09 64054447.88
September 0.129689E+09 68966364.22 60722567.39 0.189436E+09 70208732.13
October 0.103402E+09 56487207.35 46914650.42 0.155076E+09 81639157.96
November 91091084.00 47973884.87 43117199.13 0.119287E+09 0.106199E+09
December 83761230.45 45184882.47 38576347.98 0.110416E+09 0.118876E+09
           
Annual Sum or Average 0.145222E+10 0.736726E+09 0.715492E+09 0.202401E+10 0.104465E+10
Minimum of Months 81854845.98 40878149.51 38576347.98 0.106689E+09 61602925.28
Maximum of Months 0.165230E+09 87009393.60 79946835.11 0.244327E+09 0.118876E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 81778455.53 41478270.65 40300184.88 0.106499E+09 0.115268E+09
February 87663066.80 40876082.03 46786984.77 0.109310E+09 92618235.24
March 0.109910E+09 48859806.73 61050675.74 0.138351E+09 0.105024E+09
April 0.145976E+09 75034539.89 70941176.25 0.204173E+09 85287511.85
May 0.147016E+09 67072420.47 79943610.94 0.198629E+09 81100689.01
June 0.150888E+09 74608560.72 76279539.34 0.214158E+09 62759954.24
July 0.165228E+09 87009393.60 78218218.15 0.244325E+09 61601996.99
August 0.155718E+09 83128406.64 72589340.20 0.234136E+09 64053288.38
September 0.129687E+09 68966364.22 60720504.58 0.189434E+09 70207530.27
October 0.103395E+09 56483375.37 46911586.08 0.155061E+09 81637325.54
November 91041101.40 47947527.52 43093573.88 0.119166E+09 0.106197E+09
December 83648155.31 45117439.76 38530715.55 0.110129E+09 0.118874E+09
           
Annual Sum or Average 0.145195E+10 0.736582E+09 0.715366E+09 0.202337E+10 0.104463E+10
Minimum of Months 81778455.53 40876082.03 38530715.55 0.106499E+09 61601996.99
Maximum of Months 0.165228E+09 87009393.60 79943610.94 0.244325E+09 0.118874E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 81778455.53 41478270.65 40300184.88 0.106499E+09 0.115268E+09
February 87663066.80 40876082.03 46786984.77 0.109310E+09 92618235.24
March 0.109910E+09 48859806.73 61050675.74 0.138351E+09 0.105024E+09
April 0.145976E+09 75034539.89 70941176.25 0.204173E+09 85287511.85
May 0.147016E+09 67072420.47 79943610.94 0.198629E+09 81100689.01
June 0.150888E+09 74608560.72 76279539.34 0.214158E+09 62759954.24
July 0.165228E+09 87009393.60 78218218.15 0.244325E+09 61601996.99
August 0.155718E+09 83128406.64 72589340.20 0.234136E+09 64053288.38
September 0.129687E+09 68966364.22 60720504.58 0.189434E+09 70207530.27
October 0.103395E+09 56483375.37 46911586.08 0.155061E+09 81637325.54
November 91041101.40 47947527.52 43093573.88 0.119166E+09 0.106197E+09
December 83648155.31 45117439.76 38530715.55 0.110129E+09 0.118874E+09
           
Annual Sum or Average 0.145195E+10 0.736582E+09 0.715366E+09 0.202337E+10 0.104463E+10
Minimum of Months 81778455.53 40876082.03 38530715.55 0.106499E+09 61601996.99
Maximum of Months 0.165228E+09 87009393.60 79943610.94 0.244325E+09 0.118874E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 81780051.02 41478270.65 40301780.37 0.106500E+09 0.115270E+09
February 87665285.92 40876082.03 46789203.89 0.109312E+09 92619440.07
March 0.109914E+09 48859806.73 61053756.14 0.138354E+09 0.105025E+09
April 0.145978E+09 75034539.89 70943438.53 0.204176E+09 85288644.71
May 0.147019E+09 67072420.47 79946835.28 0.198633E+09 81101632.51
June 0.150891E+09 74608560.72 76282326.04 0.214161E+09 62760606.79
July 0.165230E+09 87009393.60 78220215.61 0.244327E+09 61602925.33
August 0.155720E+09 83128406.64 72591136.23 0.234137E+09 64054447.94
September 0.129689E+09 68966364.22 60722567.50 0.189436E+09 70208732.20
October 0.103397E+09 56483375.37 46913511.23 0.155062E+09 81639158.06
November 91042826.49 47947527.52 43095298.97 0.119168E+09 0.106199E+09
December 83649537.02 45117439.76 38532097.26 0.110130E+09 0.118877E+09
           
Annual Sum or Average 0.145197E+10 0.736582E+09 0.715392E+09 0.202339E+10 0.104465E+10
Minimum of Months 81780051.02 40876082.03 38532097.26 0.106500E+09 61602925.33
Maximum of Months 0.165230E+09 87009393.60 79946835.28 0.244327E+09 0.118877E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 901.11 326.20 604.69 446.23 158.46 0.00 0.00
February 672.30 286.65 472.52 294.49 178.03 0.00 0.00
March 480.52 292.79 346.67 163.11 183.56 0.00 0.00
April 301.70 239.31 228.92 57.95 170.97 0.00 0.00
May 173.07 216.89 172.45 1.05 171.40 0.00 0.00
June 186.86 171.26 169.15 0.00 169.15 0.00 0.00
July 200.20 160.12 166.99 0.82 166.17 0.00 0.00
August 254.22 168.51 185.94 26.75 159.19 0.00 0.00
September 485.33 202.01 312.65 144.57 168.08 0.00 0.00
October 745.22 230.63 465.42 312.30 153.12 0.00 0.00
November 855.98 308.17 578.25 411.09 167.15 0.00 0.00
December 965.15 334.89 646.74 494.64 152.10 0.00 0.00
               
Annual Sum or Average 517.88 244.60 362.07 195.74 166.33 0.00 0.00
Minimum of Months 173.07 160.12 166.99 0.00 152.10 0.00 0.00
Maximum of Months 965.15 334.89 646.74 494.64 183.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 160.58 163.81 128.58 69.24 59.34 0.00 0.00
February 157.58 145.65 133.79 61.78 72.02 0.00 0.00
March 198.07 149.69 161.83 72.56 89.27 0.00 0.00
April 278.72 123.54 204.59 100.95 103.64 0.00 0.00
May 249.71 114.23 191.22 78.54 112.67 0.00 0.00
June 261.45 91.87 188.92 79.49 109.43 0.00 0.00
July 315.60 87.85 214.91 104.10 110.81 0.00 0.00
August 319.43 89.85 214.22 111.50 102.72 0.00 0.00
September 220.21 102.18 155.89 70.03 85.86 0.00 0.00
October 204.10 115.42 140.64 72.27 68.37 0.00 0.00
November 158.35 156.53 129.33 66.12 63.21 0.00 0.00
December 154.19 168.45 124.26 69.46 54.80 0.00 0.00
               
Annual Sum or Average 223.63 125.67 165.90 79.82 86.08 0.00 0.00
Minimum of Months 154.19 87.85 124.26 61.78 54.80 0.00 0.00
Maximum of Months 319.43 168.45 214.91 111.50 112.67 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 53.94 250.56 71.49 0.00 71.49 0.00 0.00
February 63.56 223.66 88.81 0.00 88.81 0.00 0.00
March 89.92 230.78 108.69 0.00 108.69 0.00 0.00
April 124.52 184.58 127.23 0.44 126.79 0.00 0.00
May 147.54 164.55 149.64 6.29 143.35 0.00 0.00
June 179.10 130.06 157.87 13.79 144.09 0.00 0.00
July 184.58 122.50 151.32 10.99 140.33 0.00 0.00
August 155.31 128.76 128.42 2.23 126.20 0.00 0.00
September 122.47 152.77 108.51 0.02 108.49 0.00 0.00
October 104.69 173.58 85.61 0.00 85.61 0.00 0.00
November 57.30 239.52 77.44 0.00 77.44 0.00 0.00
December 47.53 259.53 66.76 0.00 66.76 0.00 0.00
               
Annual Sum or Average 111.15 188.24 110.24 2.83 107.41 0.00 0.00
Minimum of Months 47.53 122.50 66.76 0.00 66.76 0.00 0.00
Maximum of Months 184.58 259.53 157.87 13.79 144.09 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 159.12 172.15 122.16 61.96 60.20 0.00 0.00
February 180.74 153.14 144.95 67.59 77.36 0.00 0.00
March 206.62 156.85 164.15 72.97 91.18 0.00 0.00
April 315.08 131.62 225.27 115.79 109.48 0.00 0.00
May 296.64 121.12 219.56 100.17 119.39 0.00 0.00
June 330.49 96.85 232.85 115.14 117.72 0.00 0.00
July 364.88 92.00 246.76 129.94 116.81 0.00 0.00
August 349.67 95.66 232.55 124.15 108.41 0.00 0.00
September 292.34 108.35 200.14 106.43 93.71 0.00 0.00
October 231.58 121.92 154.42 84.36 70.06 0.00 0.00
November 183.95 163.89 140.52 74.00 66.51 0.00 0.00
December 164.58 177.53 124.97 67.40 57.56 0.00 0.00
               
Annual Sum or Average 256.66 132.50 184.17 93.43 90.74 0.00 0.00
Minimum of Months 159.12 92.00 122.16 61.96 57.56 0.00 0.00
Maximum of Months 364.88 177.53 246.76 129.94 119.39 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.241354E+10 0.873706E+09 0.161961E+10 0.119518E+10 0.424429E+09 0.00 0.00
February 0.162642E+10 0.693474E+09 0.114313E+10 0.712425E+09 0.430702E+09 0.00 0.00
March 0.128702E+10 0.784208E+09 0.928521E+09 0.436878E+09 0.491643E+09 0.00 0.00
April 0.781997E+09 0.620294E+09 0.593360E+09 0.150205E+09 0.443155E+09 0.00 0.00
May 0.463559E+09 0.580906E+09 0.461892E+09 2813173.12 0.459079E+09 0.00 0.00
June 0.484328E+09 0.443910E+09 0.438429E+09 0.73 0.438429E+09 0.00 0.00
July 0.536209E+09 0.428856E+09 0.447266E+09 2184339.92 0.445081E+09 0.00 0.00
August 0.680907E+09 0.451334E+09 0.498028E+09 71657618.86 0.426370E+09 0.00 0.00
September 0.125798E+10 0.523611E+09 0.810393E+09 0.374723E+09 0.435669E+09 0.00 0.00
October 0.199599E+10 0.617732E+09 0.124657E+10 0.836455E+09 0.410119E+09 0.00 0.00
November 0.221870E+10 0.798789E+09 0.149882E+10 0.106556E+10 0.433264E+09 0.00 0.00
December 0.258507E+10 0.896967E+09 0.173223E+10 0.132485E+10 0.407376E+09 0.00 0.00
               
Annual Sum or Average 0.163317E+11 0.771379E+10 0.114182E+11 0.617293E+10 0.524532E+10 0.00 0.00
Minimum of Months 0.463559E+09 0.428856E+09 0.438429E+09 0.73 0.407376E+09 0.00 0.00
Maximum of Months 0.258507E+10 0.896967E+09 0.173223E+10 0.132485E+10 0.491643E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.430095E+09 0.438736E+09 0.344389E+09 0.185443E+09 0.158946E+09 0.00 0.00
February 0.381211E+09 0.352359E+09 0.323673E+09 0.149451E+09 0.174223E+09 0.00 0.00
March 0.530517E+09 0.400928E+09 0.433437E+09 0.194344E+09 0.239093E+09 0.00 0.00
April 0.722442E+09 0.320207E+09 0.530299E+09 0.261668E+09 0.268631E+09 0.00 0.00
May 0.668813E+09 0.305943E+09 0.512152E+09 0.210366E+09 0.301786E+09 0.00 0.00
June 0.677682E+09 0.238136E+09 0.489670E+09 0.206026E+09 0.283644E+09 0.00 0.00
July 0.845305E+09 0.235307E+09 0.575625E+09 0.278835E+09 0.296790E+09 0.00 0.00
August 0.855569E+09 0.240668E+09 0.573761E+09 0.298645E+09 0.275116E+09 0.00 0.00
September 0.570784E+09 0.264842E+09 0.404059E+09 0.181509E+09 0.222550E+09 0.00 0.00
October 0.546663E+09 0.309150E+09 0.376702E+09 0.193568E+09 0.183135E+09 0.00 0.00
November 0.410453E+09 0.405739E+09 0.335221E+09 0.171380E+09 0.163841E+09 0.00 0.00
December 0.412995E+09 0.451187E+09 0.332805E+09 0.186034E+09 0.146772E+09 0.00 0.00
               
Annual Sum or Average 0.705253E+10 0.396320E+10 0.523180E+10 0.251727E+10 0.271453E+10 0.00 0.00
Minimum of Months 0.381211E+09 0.235307E+09 0.323673E+09 0.149451E+09 0.146772E+09 0.00 0.00
Maximum of Months 0.855569E+09 0.451187E+09 0.575625E+09 0.298645E+09 0.301786E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.144466E+09 0.671090E+09 0.191471E+09 0.00 0.191471E+09 0.00 0.00
February 0.153762E+09 0.541083E+09 0.214855E+09 0.00 0.214855E+09 0.00 0.00
March 0.240851E+09 0.618133E+09 0.291118E+09 0.00 0.291118E+09 0.00 0.00
April 0.322748E+09 0.478430E+09 0.329772E+09 1139191.06 0.328633E+09 0.00 0.00
May 0.395162E+09 0.440721E+09 0.400803E+09 16842343.76 0.383960E+09 0.00 0.00
June 0.464235E+09 0.337123E+09 0.409205E+09 35733439.60 0.373472E+09 0.00 0.00
July 0.494380E+09 0.328116E+09 0.405284E+09 29436880.47 0.375847E+09 0.00 0.00
August 0.415976E+09 0.344881E+09 0.343971E+09 5961285.72 0.338010E+09 0.00 0.00
September 0.317454E+09 0.395981E+09 0.281261E+09 42158.15 0.281219E+09 0.00 0.00
October 0.280391E+09 0.464920E+09 0.229307E+09 0.00 0.229307E+09 0.00 0.00
November 0.148516E+09 0.620847E+09 0.200715E+09 0.00 0.200715E+09 0.00 0.00
December 0.127313E+09 0.695126E+09 0.178807E+09 0.00 0.178807E+09 0.00 0.00
               
Annual Sum or Average 0.350525E+10 0.593645E+10 0.347657E+10 89155298.75 0.338741E+10 0.00 0.00
Minimum of Months 0.127313E+09 0.328116E+09 0.178807E+09 0.00 0.178807E+09 0.00 0.00
Maximum of Months 0.494380E+09 0.695126E+09 0.409205E+09 35733439.60 0.383960E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.426186E+09 0.461077E+09 0.327192E+09 0.165957E+09 0.161235E+09 0.00 0.00
February 0.437253E+09 0.370475E+09 0.350661E+09 0.163506E+09 0.187154E+09 0.00 0.00
March 0.553411E+09 0.420096E+09 0.439648E+09 0.195439E+09 0.244209E+09 0.00 0.00
April 0.816698E+09 0.341152E+09 0.583907E+09 0.300138E+09 0.283769E+09 0.00 0.00
May 0.794525E+09 0.324405E+09 0.588071E+09 0.268290E+09 0.319781E+09 0.00 0.00
June 0.856637E+09 0.251041E+09 0.603558E+09 0.298434E+09 0.305124E+09 0.00 0.00
July 0.977303E+09 0.246410E+09 0.660914E+09 0.348038E+09 0.312877E+09 0.00 0.00
August 0.936546E+09 0.256215E+09 0.622875E+09 0.332514E+09 0.290361E+09 0.00 0.00
September 0.757738E+09 0.280833E+09 0.518752E+09 0.275865E+09 0.242886E+09 0.00 0.00
October 0.620260E+09 0.326553E+09 0.413589E+09 0.225937E+09 0.187651E+09 0.00 0.00
November 0.476786E+09 0.424792E+09 0.364216E+09 0.191816E+09 0.172400E+09 0.00 0.00
December 0.440804E+09 0.475501E+09 0.334707E+09 0.180537E+09 0.154170E+09 0.00 0.00
               
Annual Sum or Average 0.809415E+10 0.417855E+10 0.580809E+10 0.294647E+10 0.286162E+10 0.00 0.00
Minimum of Months 0.426186E+09 0.246410E+09 0.327192E+09 0.163506E+09 0.154170E+09 0.00 0.00
Maximum of Months 0.977303E+09 0.475501E+09 0.660914E+09 0.348038E+09 0.319781E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.22 9.61 5.99 2.23 0.81 45.19 208.20 0.00
February 13.28 10.20 7.03 3.12 2.96 66.07 175.60 0.04
March 12.64 10.61 8.97 2.93 3.55 84.90 179.28 0.03
April 15.30 12.62 10.61 2.62 4.76 81.20 282.81 0.02
May 15.56 12.65 10.56 2.92 6.17 105.80 234.18 0.01
June 17.67 14.80 13.02 2.53 9.03 98.05 261.27 0.00
July 19.43 16.76 15.28 2.35 9.62 86.54 312.15 0.00
August 19.66 17.23 15.95 2.55 9.62 74.58 307.55 0.00
September 18.47 15.50 13.65 2.19 8.99 70.75 240.05 0.00
October 18.77 13.72 9.60 2.71 7.74 53.88 216.36 0.00
November 14.32 10.43 6.22 2.47 2.41 50.75 207.87 0.01
December 13.59 8.82 3.19 2.50 0.05 39.49 221.83 0.00
                 
Annual Sum or Average 16.01 12.76 10.02 2.59 5.49 71.44 237.65 0.01
Minimum of Months 12.64 8.82 3.19 2.19 0.05 39.49 175.60 0.00
Maximum of Months 19.66 17.23 15.95 3.12 9.62 105.80 312.15 0.04



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 26.00 13-JAN-13:00 15.46 8.00 3.10 11.84 120.00 725.00
February 26.00 01-FEB-11:00 14.67 6.00 4.10 10.11 166.00 715.50
March 24.00 11-MAR-10:00 13.82 6.00 2.60 8.15 120.00 907.00
April 27.00 26-APR-12:00 17.13 11.00 4.10 12.22 159.00 884.00
May 24.00 03-MAY-11:00 15.05 9.00 4.10 12.98 187.00 842.50
June 25.00 29-JUN-10:00 19.59 17.00 4.60 11.65 177.50 829.00
July 28.00 19-JUL-10:00 20.49 17.00 3.60 14.65 173.00 813.00
August 28.00 14-AUG-10:00 21.19 18.00 3.60 14.84 148.00 840.00
September 36.00 29-SEP-10:00 17.91 5.00 3.60 19.35 159.50 790.00
October 37.00 16-OCT-10:00 17.87 4.00 5.70 20.05 122.00 871.50
November 27.00 19-NOV-12:00 14.96 6.00 4.10 11.07 128.50 796.00
December 26.00 05-DEC-09:00 13.09 1.00 3.60 8.94 75.50 857.00
                 
Annual Sum or Average                
Minimum of Months 24.00   13.09 1.00 2.60 8.15 75.50 715.50
Maximum of Months 37.00   21.19 18.00 5.70 20.05 187.00 907.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.00 08-JAN-06:00 -0.3 -2.0 3.10 -15.5 11.50 193.50
February 5.00 04-FEB-05:00 0.22 -8.0 4.10 -10.9 0.00 0.00
March 4.00 07-MAR-04:00 3.53 3.00 0.00 -11.4 0.00 0.00
April 7.00 01-APR-05:00 4.33 1.00 4.10 -9.0 23.50 211.00
May 8.00 14-MAY-03:00 7.45 7.00 1.50 -6.6 0.00 0.00
June 11.00 13-JUN-03:00 9.85 9.00 2.10 -3.4 0.00 0.00
July 13.00 06-JUL-00:00 13.00 13.00 0.00 -0.6 0.00 0.00
August 14.00 24-AUG-01:00 14.00 14.00 0.00 0.51 0.00 0.00
September 11.00 20-SEP-02:00 9.85 9.00 1.50 -3.4 0.00 0.00
October 9.00 12-OCT-04:00 6.56 4.00 3.10 -6.4 0.00 0.00
November 7.00 05-NOV-01:00 5.54 4.00 3.10 -8.3 0.00 0.00
December 5.00 03-DEC-00:00 5.00 5.00 2.10 -0.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.00   -0.3 -8.0 0.00 -15.5 0.00 0.00
Maximum of Months 14.00   14.00 14.00 4.10 0.51 23.50 211.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 17.04 17-JAN-11:00 24.00 13.00 3.10 12.79 223.50 9.00
February 16.80 11-FEB-13:00 18.00 16.20 1.10 15.02 241.00 12.50
March 17.41 22-MAR-12:00 22.00 15.00 3.10 8.35 145.50 876.00
April 18.33 26-APR-10:00 26.00 14.00 4.10 12.03 141.50 915.50
May 16.69 05-MAY-14:00 18.00 16.00 5.10 8.74 303.50 269.00
June 19.59 29-JUN-10:00 25.00 17.00 4.60 11.65 177.50 829.00
July 21.19 19-JUL-11:00 28.00 18.00 4.60 14.84 182.50 808.00
August 21.20 18-AUG-11:00 28.00 18.00 3.60 17.21 244.00 667.50
September 21.85 22-SEP-11:00 26.00 20.00 2.60 20.05 284.00 21.00
October 21.09 01-OCT-11:00 26.00 19.00 3.60 13.16 102.00 899.50
November 16.52 10-NOV-12:00 21.00 14.00 5.10 7.15 131.00 808.50
December 15.64 07-DEC-12:00 20.00 13.00 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 15.64   18.00 13.00 1.10 5.94 89.00 9.00
Maximum of Months 21.85   28.00 20.00 5.10 20.05 303.50 915.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.00 17-JAN-12:00 22.00 16.85 2.10 11.65 241.50 67.50
February 16.20 11-FEB-13:00 18.00 16.80 1.10 15.02 241.00 12.50
March 15.00 23-MAR-15:20 21.67 17.34 3.77 8.02 112.00 809.83
April 15.00 26-APR-21:19 16.00 15.39 2.23 6.15 0.00 0.00
May 16.00 05-MAY-14:00 18.00 16.69 5.10 8.74 303.50 269.00
June 17.00 28-JUN-08:00 19.00 17.66 1.50 16.12 285.00 428.50
July 18.00 18-JUL-10:00 26.00 20.47 4.60 12.79 169.00 819.00
August 18.10 14-AUG-09:00 26.90 20.93 3.40 13.73 139.00 817.00
September 20.00 22-SEP-09:00 22.00 20.55 1.50 16.30 296.00 18.00
October 19.00 01-OCT-07:10 19.17 19.06 0.25 16.82 53.33 0.00
November 15.00 10-NOV-17:19 16.67 15.62 2.77 3.34 0.00 0.00
December 13.00 07-DEC-12:00 20.00 15.64 5.10 5.94 89.00 868.50
                 
Annual Sum or Average                
Minimum of Months 13.00   16.00 15.39 0.25 3.34 0.00 0.00
Maximum of Months 20.00   26.90 20.93 5.10 16.82 303.50 868.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 17.43 27.46 0.00
February 18.00 13.00 16.00 17.38 30.87 0.00
March 18.00 13.00 16.00 17.83 38.09 0.00
April 18.00 13.00 16.00 18.69 55.75 0.00
May 18.00 13.00 16.00 19.73 55.13 0.00
June 18.00 13.00 16.00 20.65 58.21 0.00
July 18.00 13.00 16.00 21.22 63.49 0.00
August 18.00 13.00 16.00 21.28 59.02 0.00
September 18.00 13.00 16.00 20.81 46.26 0.00
October 18.00 13.00 16.00 19.94 34.64 0.00
November 18.00 13.00 16.00 18.91 29.25 0.00
December 18.00 13.00 16.00 17.99 26.27 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.33 43.77 0.00
Minimum of Months 18.00 13.00 16.00 17.38 26.27 0.00
Maximum of Months 18.00 13.00 16.00 21.28 63.49 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.537839E+09 -422568518.6 0.00 0.00 744.00 0.00 -115270478.7 59.00 0.00 0.00
February 0.486299E+09 -382797411.2 0.00 0.00 672.00 0.00 -103501754.3 58.99 0.00 0.00
March 0.572676E+09 -458194170.0 0.00 0.00 744.00 0.00 -114481716.6 58.99 0.00 0.00
April 0.499538E+09 -390208973.1 0.00 0.00 720.00 0.00 -109328936.1 58.99 0.00 0.00
May 0.530908E+09 -418565305.8 0.00 0.00 744.00 0.00 -112343077.5 58.99 0.00 0.00
June 0.515826E+09 -408212540.9 0.00 0.00 720.00 0.00 -107613006.0 58.99 0.00 0.00
July 0.475290E+09 -365588749.0 0.00 0.00 744.00 0.00 -109701638.0 58.99 0.00 0.00
August 0.529945E+09 -419906434.2 0.00 0.00 744.00 0.00 -110038147.9 59.00 0.00 0.00
September 0.476860E+09 -369851978.4 0.00 0.00 720.00 0.00 -107007719.6 58.99 0.00 0.00
October 0.507592E+09 -397119862.5 0.00 0.00 744.00 0.00 -110472215.1 58.99 0.00 0.00
November 0.516651E+09 -407456555.1 0.00 0.00 720.00 0.00 -109194249.2 58.99 0.00 0.00
December 0.510740E+09 -396857284.1 0.00 0.00 744.00 0.00 -113883210.0 58.99 0.00 0.00
                     
Annual Sum or Average 0.616016E+10 -0.483733E+10 0.00 0.00 8760.00 0.00 -0.132284E+10 58.99 0.00 0.00
Minimum of Months 0.475290E+09 -458194170.0 0.00 0.00 672.00 0.00 -115270478.7 58.99 0.00 0.00
Maximum of Months 0.572676E+09 -365588749.0 0.00 0.00 744.00 0.00 -103501754.3 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.75 0.73 01-JAN-07:30 1863.33 27.92 160.83 256.83 742.94 25.39 239.00 232.00
February 279.67 0.75 0.73 01-FEB-08:09 1778.61 27.32 153.67 233.83 479.33 22.31 197.83 175.17
March 338.17 0.77 0.73 01-MAR-07:30 562.92 17.52 6.33 234.00 370.35 21.33 232.83 173.33
April 358.33 0.78 0.73 01-APR-09:50 360.35 16.86 0.00 211.83 269.15 21.08 203.33 50.67
May 393.83 0.79 0.73 02-MAY-09:20 302.01 16.33 0.00 111.00 221.39 20.54 136.50 2.50
June 381.00 0.80 0.73 03-JUN-13:30 272.59 15.86 0.00 44.17 202.70 20.09 78.67 0.00
July 408.67 0.80 0.73 01-JUL-11:20 277.02 15.94 0.00 55.67 207.76 20.19 116.50 2.00
August 390.67 0.79 0.73 01-AUG-08:30 308.62 16.32 0.00 107.83 230.63 20.51 156.33 19.83
September 328.83 0.77 0.73 01-SEP-07:00 499.21 17.34 5.50 224.33 333.22 21.27 205.83 145.00
October 296.17 0.76 0.73 01-OCT-10:09 1169.64 20.49 57.00 234.83 483.69 22.25 154.33 184.33
November 300.00 0.76 0.73 01-NOV-06:49 1817.36 26.53 148.50 253.33 677.94 26.64 257.83 244.83
December 297.00 0.75 0.73 01-DEC-07:40 1273.24 26.29 138.33 259.67 796.77 25.14 234.67 233.17
                         
Annual Sum or Average 4065.67 0.77     800.36 19.85 670.17 2227.33 395.00 22.01 2213.67 1462.83
Minimum of Months 279.67 0.75 0.73   272.59 15.86 0.00 44.17 202.70 20.09 78.67 0.00
Maximum of Months 408.67 0.80 0.73   1863.33 27.92 160.83 259.67 796.77 26.64 257.83 244.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.82 0.73 01-JAN-07:49 803.37 18.88 54.33 95.83 430.04 23.12 108.33 76.83
February 279.67 0.82 0.73 01-FEB-07:40 334.79 15.38 0.00 95.33 461.64 22.52 99.33 70.33
March 338.17 0.82 0.73 01-MAR-06:00 336.32 14.90 0.00 119.50 284.12 19.67 107.00 80.33
April 358.33 0.82 0.73 01-APR-06:30 337.86 14.85 0.00 121.00 294.11 19.99 101.67 100.50
May 393.83 0.82 0.73 01-MAY-06:00 319.66 14.99 0.00 121.33 272.79 20.00 114.83 97.33
June 381.00 0.82 0.73 01-JUN-06:49 304.70 14.69 0.00 102.67 265.30 19.75 93.00 85.17
July 408.67 0.82 0.73 01-JUL-05:00 320.57 14.58 0.00 132.17 287.10 19.79 119.50 113.17
August 390.67 0.82 0.73 01-AUG-07:40 322.33 14.45 0.00 125.17 288.18 19.71 100.83 109.00
September 328.83 0.82 0.73 01-SEP-07:10 412.69 15.03 5.50 96.17 258.70 19.55 72.00 71.17
October 296.17 0.84 0.73 01-OCT-10:39 965.48 17.12 46.67 90.17 362.90 19.84 74.00 65.00
November 300.00 0.82 0.73 01-NOV-07:10 846.02 17.84 52.17 103.17 614.61 23.60 116.50 77.50
December 297.00 0.83 0.73 01-DEC-07:49 815.89 18.46 55.67 93.33 479.91 23.43 96.50 76.67
                         
Annual Sum or Average 4065.67 0.82     487.20 15.78 214.33 1295.83 347.94 20.77 1203.50 1023.00
Minimum of Months 279.67 0.82 0.73   304.70 14.45 0.00 90.17 258.70 19.55 72.00 65.00
Maximum of Months 408.67 0.84 0.73   965.48 18.88 55.67 132.17 614.61 23.60 119.50 113.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.91 0.83 30-JAN-12:30 132.92 12.85 0.00 0.00 102.01 17.24 0.00 0.00
February 279.67 0.89 0.81 26-FEB-13:30 160.69 13.80 0.00 0.00 117.04 17.81 0.00 0.00
March 338.17 0.87 0.74 29-MAR-13:30 189.02 14.29 0.00 0.00 133.59 18.04 0.00 0.00
April 358.33 0.85 0.74 17-APR-14:30 216.14 15.44 0.00 0.00 154.60 19.33 0.00 0.00
May 393.83 0.81 0.74 04-MAY-15:30 291.52 16.34 0.00 36.50 179.09 20.09 28.00 0.00
June 381.00 0.80 0.74 26-JUN-16:30 276.95 16.54 0.00 50.17 187.62 20.25 62.50 0.00
July 408.67 0.81 0.74 22-JUL-14:30 264.73 16.34 0.00 29.67 181.60 20.08 38.17 0.00
August 390.67 0.84 0.74 05-AUG-13:30 230.95 15.52 0.00 12.83 157.21 19.35 0.00 0.00
September 328.83 0.87 0.74 08-SEP-14:30 189.53 14.69 0.00 0.00 138.43 18.63 0.00 0.00
October 296.17 0.90 0.74 07-OCT-13:30 141.08 13.03 0.00 0.00 106.22 17.17 0.00 0.00
November 300.00 0.91 0.81 02-NOV-13:30 135.46 12.60 0.00 0.00 102.68 16.73 0.00 0.00
December 297.00 0.92 0.85 12-DEC-13:30 120.39 12.15 0.00 0.00 94.23 16.55 0.00 0.00
                         
Annual Sum or Average 4065.67 0.86     202.81 14.65 0.00 129.17 141.83 18.60 128.67 0.00
Minimum of Months 279.67 0.80 0.74   120.39 12.15 0.00 0.00 94.23 16.55 0.00 0.00
Maximum of Months 408.67 0.92 0.85   291.52 16.54 0.00 50.17 187.62 20.25 62.50 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 293.33 0.83 0.73 01-JAN-15:09 1345.23 20.62 85.50 101.00 383.21 22.28 106.33 77.67
February 279.67 0.82 0.73 01-FEB-13:09 827.39 18.46 47.50 109.50 525.66 22.66 112.83 77.33
March 338.17 0.82 0.73 01-MAR-13:20 376.05 15.19 1.83 123.67 292.65 19.66 119.83 86.33
April 358.33 0.82 0.73 01-APR-12:39 354.56 15.08 0.00 122.67 311.65 20.00 121.00 104.67
May 393.83 0.81 0.73 01-MAY-13:20 344.34 15.23 0.00 131.17 298.73 20.15 131.17 111.17
June 381.00 0.81 0.73 01-JUN-13:20 346.26 15.10 0.00 131.83 309.59 20.27 134.67 117.83
July 408.67 0.81 0.73 01-JUL-13:30 345.88 14.91 0.00 143.67 314.75 20.22 142.17 130.67
August 390.67 0.82 0.73 01-AUG-13:20 342.22 14.73 0.00 137.33 308.89 19.84 131.83 121.17
September 328.83 0.81 0.73 01-SEP-13:09 363.94 15.18 0.00 127.67 312.19 20.03 123.17 103.67
October 296.17 0.82 0.73 01-OCT-13:09 464.21 15.21 7.33 101.00 394.70 20.25 79.83 78.00
November 300.00 0.83 0.73 01-NOV-12:39 973.47 18.34 57.00 112.17 713.98 24.01 130.00 84.33
December 297.00 0.84 0.73 01-DEC-12:20 1203.72 20.12 84.17 99.83 588.18 23.47 112.67 79.83
                         
Annual Sum or Average 4065.67 0.82     572.97 16.31 283.33 1441.50 384.54 20.93 1445.50 1172.67
Minimum of Months 279.67 0.81 0.73   342.22 14.73 0.00 99.83 292.65 19.66 79.83 77.33
Maximum of Months 408.67 0.84 0.73   1345.23 20.62 85.50 143.67 713.98 24.01 142.17 130.67



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 35382832.18 5456.33 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 35382832.18     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 35382832.18 5456.33   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.129724E+09 5410.44 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 71156530.71 4878.49 27-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.210897E+09 4814.08 31-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 44209493.37 1920.77 03-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 28078417.99 2240.23 15-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 1727259.80 707.82 13-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 36971.30 114.86 12-OCT-06:15 0.00 0.00 0.00 0.00 0.00
November 2142097.12 940.23 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 46112983.23 2411.47 13-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.534084E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.210897E+09 5410.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 55464102.76 3939.63 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 18337342.08 3939.63 27-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 37141635.77 3917.29 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 233683.49 80.00 03-APR-05:30 0.00 0.00 0.00 0.00 0.00
May 189574.59 551.10 15-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 265842.25 479.56 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 10185809.90 2177.01 26-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121818E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 55464102.76 3939.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.178339E+09 4798.34 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 64344417.83 4798.34 27-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.110901E+09 4822.08 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 5850724.91 1896.92 03-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 1420144.16 1359.61 15-MAY-05:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 7563357.05 3541.64 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 51190702.31 4247.15 26-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.419610E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.178339E+09 4822.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 64105359.27 4729.55 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 15449486.49 4729.55 27-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 38257838.19 4186.25 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 149956.34 66.07 03-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 97913.61 119.30 15-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 11053.86 34.78 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 9994089.58 1793.48 13-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128066E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 64105359.27 4729.55   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 476981.76 2360.06 03-JAN-06:12 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 476981.76     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 476981.76 2360.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 431973.52 2052.24 03-JAN-06:12 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 431973.52     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 431973.52 2052.24   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1822470.50 3279.01 09-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1822470.50     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1822470.50 3279.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 343855.33 2049.15 09-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 343855.33     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 343855.33 2049.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.840872E+09 0.700849E+09 2594.10 20-JAN-12:00 2069.38 0.00
February 0.00 0.00 0.729024E+09 0.606121E+09 2374.23 01-FEB-16:00 1798.62 0.00
March 0.00 0.00 0.830399E+09 0.636659E+09 2940.81 23-MAR-14:57 2214.50 0.00
April 0.00 0.00 0.139406E+10 0.109659E+10 5237.28 27-APR-05:03 3625.49 0.00
May 0.00 0.00 0.169297E+10 0.136744E+10 5225.77 03-MAY-05:03 3642.35 0.00
June 0.00 0.00 0.234575E+10 0.180795E+10 5346.00 30-JUN-05:02 3491.11 0.00
July 0.00 0.00 0.293236E+10 0.219531E+10 5388.79 20-JUL-05:02 3402.28 0.00
August 0.00 0.00 0.338643E+10 0.250014E+10 5401.00 18-AUG-05:02 3396.03 0.00
September 0.00 0.00 0.237217E+10 0.181254E+10 5354.60 25-SEP-05:03 3414.71 0.00
October 0.00 0.00 0.247117E+10 0.207254E+10 5427.57 05-OCT-05:02 3492.21 0.00
November 0.00 0.00 0.128785E+10 0.109422E+10 5155.33 01-NOV-05:03 3828.36 0.00
December 0.00 0.00 0.947934E+09 0.861692E+09 3155.95 08-DEC-06:05 2124.97 0.00
                 
Annual Sum or Average 0.00 0.00 0.212310E+11 0.167521E+11       0.00
Minimum of Months 0.00 0.00 0.729024E+09 0.606121E+09 2374.23   1798.62 0.00
Maximum of Months 0.00 0.00 0.338643E+10 0.250014E+10 5427.57   3828.36 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.111491E+10 0.105038E+10 4160.12 20-JAN-13:10 3542.58 0.00
February 0.00 0.00 0.676133E+09 0.632205E+09 3309.96 03-FEB-14:20 3309.96 0.00
March 0.00 0.00 0.489008E+09 0.420048E+09 3359.25 23-MAR-14:00 2834.01 0.00
April 0.00 0.00 0.654470E+09 0.555557E+09 2860.15 26-APR-13:30 2591.83 0.00
May 0.00 0.00 0.581885E+09 0.502900E+09 2358.34 04-MAY-14:00 2014.38 0.00
June 0.00 0.00 0.104947E+10 0.833991E+09 2776.26 29-JUN-13:00 2030.74 0.00
July 0.00 0.00 0.166877E+10 0.126291E+10 5313.23 25-JUL-05:02 3360.13 0.00
August 0.00 0.00 0.214034E+10 0.161357E+10 5342.19 07-AUG-05:02 3276.14 0.00
September 0.00 0.00 0.175914E+10 0.142805E+10 4776.80 29-SEP-16:12 4776.80 0.00
October 0.00 0.00 0.237075E+10 0.211345E+10 5381.71 05-OCT-05:02 3425.60 0.00
November 0.00 0.00 0.141736E+10 0.132000E+10 4510.92 20-NOV-13:05 3758.84 0.00
December 0.00 0.00 0.128684E+10 0.125473E+10 4636.31 19-DEC-13:00 4636.31 0.00
                 
Annual Sum or Average 0.00 0.00 0.152091E+11 0.129878E+11       0.00
Minimum of Months 0.00 0.00 0.489008E+09 0.420048E+09 2358.34   2014.38 0.00
Maximum of Months 0.00 0.00 0.237075E+10 0.211345E+10 5381.71   4776.80 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.226586E+09 0.207513E+09 3009.99 18-JAN-11:02 2893.20 0.00
February 0.00 0.00 0.164359E+09 0.151447E+09 2591.90 17-FEB-15:02 2160.58 0.00
March 0.00 0.00 0.192875E+09 0.165307E+09 3719.73 24-MAR-10:01 3035.42 0.00
April 0.00 0.00 0.542628E+09 0.475236E+09 3716.88 12-APR-10:02 3174.04 0.00
May 0.00 0.00 0.615856E+09 0.550535E+09 3682.07 31-MAY-10:02 3251.98 0.00
June 0.00 0.00 0.911339E+09 0.774000E+09 3777.26 28-JUN-10:01 2947.02 0.00
July 0.00 0.00 0.132332E+10 0.109572E+10 3872.66 24-JUL-05:02 2581.52 0.00
August 0.00 0.00 0.153769E+10 0.125770E+10 3901.85 07-AUG-05:02 2473.87 0.00
September 0.00 0.00 0.940333E+09 0.792081E+09 3821.03 22-SEP-10:02 2785.86 0.00
October 0.00 0.00 0.996849E+09 0.898410E+09 3881.36 05-OCT-05:02 2621.23 0.00
November 0.00 0.00 0.379240E+09 0.349198E+09 3646.50 01-NOV-10:01 3278.51 0.00
December 0.00 0.00 0.249073E+09 0.242185E+09 3078.83 19-DEC-11:02 3078.83 0.00
                 
Annual Sum or Average 0.00 0.00 0.808015E+10 0.695933E+10       0.00
Minimum of Months 0.00 0.00 0.164359E+09 0.151447E+09 2591.90   2160.58 0.00
Maximum of Months 0.00 0.00 0.153769E+10 0.125770E+10 3901.85   3278.51 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.198865E+09 0.174636E+09 1403.32 24-JAN-15:05 1323.80 0.00
February 0.00 0.00 95482349.48 85016630.25 1148.42 01-FEB-11:55 1148.42 0.00
March 0.00 0.00 0.135478E+09 0.107226E+09 1593.68 23-MAR-15:00 1234.63 0.00
April 0.00 0.00 0.521023E+09 0.430575E+09 2114.14 26-APR-13:45 1873.71 0.00
May 0.00 0.00 0.742125E+09 0.634406E+09 2298.22 04-MAY-14:00 1961.31 0.00
June 0.00 0.00 0.123444E+10 0.991905E+09 2688.66 29-JUN-13:00 2041.15 0.00
July 0.00 0.00 0.175028E+10 0.135688E+10 4695.53 31-JUL-05:02 2969.06 0.00
August 0.00 0.00 0.197316E+10 0.150327E+10 4730.15 07-AUG-05:02 2868.69 0.00
September 0.00 0.00 0.124770E+10 0.988268E+09 3304.12 29-SEP-13:00 3304.12 0.00
October 0.00 0.00 0.133447E+10 0.114809E+10 4727.09 05-OCT-05:02 3103.12 0.00
November 0.00 0.00 0.365285E+09 0.323397E+09 1535.62 10-NOV-13:10 1214.46 0.00
December 0.00 0.00 0.197425E+09 0.189192E+09 1358.39 05-DEC-14:55 1358.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.979573E+10 0.793285E+10       0.00
Minimum of Months 0.00 0.00 95482349.48 85016630.25 1148.42   1148.42 0.00
Maximum of Months 0.00 0.00 0.197316E+10 0.150327E+10 4730.15   3304.12 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.305577E+09 0.276739E+09 1603.27 18-JAN-15:30 1502.97 0.00
February 0.00 0.00 0.240339E+09 0.217148E+09 1637.60 01-FEB-16:30 1385.51 0.00
March 0.00 0.00 0.272968E+09 0.231179E+09 2210.88 23-MAR-15:53 1826.12 0.00
April 0.00 0.00 0.636560E+09 0.547382E+09 2447.21 26-APR-15:53 2169.12 0.00
May 0.00 0.00 0.742920E+09 0.653060E+09 2288.04 03-MAY-15:53 2071.49 0.00
June 0.00 0.00 0.109186E+10 0.911072E+09 3816.42 26-JUN-05:02 3049.58 0.00
July 0.00 0.00 0.148257E+10 0.120264E+10 4660.43 31-JUL-05:02 3126.65 0.00
August 0.00 0.00 0.169813E+10 0.135904E+10 4686.34 07-AUG-05:02 3001.88 0.00
September 0.00 0.00 0.116189E+10 0.963608E+09 3139.44 29-SEP-15:48 3139.44 0.00
October 0.00 0.00 0.115917E+10 0.102894E+10 4658.50 05-OCT-05:02 3187.03 0.00
November 0.00 0.00 0.525402E+09 0.478103E+09 1842.43 10-NOV-15:23 1532.69 0.00
December 0.00 0.00 0.345267E+09 0.331990E+09 1663.84 07-DEC-15:40 1424.05 0.00
                 
Annual Sum or Average 0.00 0.00 0.966265E+10 0.820090E+10       0.00
Minimum of Months 0.00 0.00 0.240339E+09 0.217148E+09 1603.27   1385.51 0.00
Maximum of Months 0.00 0.00 0.169813E+10 0.135904E+10 4686.34   3187.03 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 225.41 534.56 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 35.80 534.58 02-FEB-12:15
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     21.89    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   225.41 534.58  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.317720E+09 0.34 323.28 02-JAN-06:01 0.93
February 0.287461E+09 0.34 323.28 01-FEB-06:10 0.93
March 0.347979E+09 0.37 323.28 01-MAR-06:02 0.93
April 0.302590E+09 0.33 323.28 03-APR-05:05 0.93
May 0.332849E+09 0.36 323.28 01-MAY-05:03 0.93
June 0.332849E+09 0.37 323.28 01-JUN-05:05 0.93
July 0.302590E+09 0.32 323.28 03-JUL-05:02 0.92
August 0.347979E+09 0.37 323.28 01-AUG-05:02 0.92
September 0.302590E+09 0.33 323.28 01-SEP-05:02 0.92
October 0.317720E+09 0.34 323.28 02-OCT-05:01 0.93
November 0.317720E+09 0.35 323.28 01-NOV-05:03 0.93
December 0.302590E+09 0.33 323.28 01-DEC-06:05 0.93
           
Annual Sum or Average 0.381263E+10 0.35      
Minimum of Months 0.287461E+09 0.32 323.28   0.92
Maximum of Months 0.347979E+09 0.37 323.28   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.325523E+09 0.34 331.22 02-JAN-06:01 0.93
February 0.294521E+09 0.34 331.22 01-FEB-06:10 0.93
March 0.356525E+09 0.37 331.22 01-MAR-06:02 0.93
April 0.310022E+09 0.34 331.22 03-APR-05:05 0.93
May 0.341024E+09 0.36 331.22 01-MAY-05:03 0.93
June 0.341024E+09 0.37 331.22 01-JUN-05:05 0.93
July 0.310022E+09 0.32 331.22 03-JUL-05:02 0.93
August 0.356525E+09 0.37 331.22 01-AUG-05:02 0.92
September 0.310022E+09 0.33 331.22 01-SEP-05:02 0.92
October 0.325612E+09 0.34 331.22 02-OCT-05:01 0.92
November 0.325523E+09 0.35 331.22 01-NOV-05:03 0.93
December 0.310022E+09 0.33 331.22 01-DEC-06:05 0.93
           
Annual Sum or Average 0.390637E+10 0.35      
Minimum of Months 0.294521E+09 0.32 331.22   0.92
Maximum of Months 0.356525E+09 0.37 331.22   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.187386E+09 0.30 244.92 02-JAN-06:01 0.93
February 0.168865E+09 0.30 244.92 01-FEB-06:10 0.93
March 0.204639E+09 0.31 244.92 01-MAR-06:02 0.93
April 0.184438E+09 0.33 244.92 03-APR-05:10 0.93
May 0.202774E+09 0.35 244.92 01-MAY-05:03 0.93
June 0.207441E+09 0.37 244.92 01-JUN-05:05 0.93
July 0.196593E+09 0.33 244.92 03-JUL-05:02 0.93
August 0.226395E+09 0.38 244.92 01-AUG-05:02 0.92
September 0.190734E+09 0.34 244.92 01-SEP-05:02 0.93
October 0.200629E+09 0.35 244.92 02-OCT-05:01 0.92
November 0.190023E+09 0.35 244.92 01-NOV-05:03 0.93
December 0.178773E+09 0.30 244.92 01-DEC-06:05 0.93
           
Annual Sum or Average 0.233869E+10 0.33      
Minimum of Months 0.168865E+09 0.30 244.92   0.92
Maximum of Months 0.226395E+09 0.38 244.92   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.286036E+09 0.34 291.04 02-JAN-06:01 0.93
February 0.258794E+09 0.34 291.04 01-FEB-06:10 0.93
March 0.313277E+09 0.37 291.04 01-MAR-06:02 0.93
April 0.272415E+09 0.34 291.04 03-APR-05:05 0.93
May 0.299656E+09 0.36 291.04 01-MAY-05:03 0.93
June 0.299656E+09 0.37 291.04 01-JUN-05:05 0.93
July 0.272415E+09 0.32 291.04 03-JUL-05:02 0.93
August 0.313277E+09 0.37 291.04 01-AUG-05:02 0.92
September 0.272415E+09 0.33 291.04 01-SEP-05:02 0.93
October 0.286036E+09 0.34 291.04 02-OCT-05:01 0.92
November 0.286036E+09 0.35 291.04 01-NOV-05:03 0.93
December 0.272415E+09 0.33 291.04 01-DEC-06:05 0.93
           
Annual Sum or Average 0.343243E+10 0.35      
Minimum of Months 0.258794E+09 0.32 291.04   0.92
Maximum of Months 0.313277E+09 0.37 291.04   0.93



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.288976E+09 0.34 294.03 02-JAN-06:01 0.93
February 0.261455E+09 0.34 294.03 01-FEB-06:10 0.93
March 0.316498E+09 0.37 294.03 01-MAR-06:02 0.93
April 0.275215E+09 0.34 294.03 03-APR-05:05 0.93
May 0.302737E+09 0.36 294.03 01-MAY-05:03 0.93
June 0.302737E+09 0.37 294.03 01-JUN-05:05 0.93
July 0.275215E+09 0.32 294.03 03-JUL-05:02 0.93
August 0.316498E+09 0.37 294.03 01-AUG-05:02 0.92
September 0.275215E+09 0.33 294.03 01-SEP-05:02 0.93
October 0.288976E+09 0.34 294.03 02-OCT-05:01 0.92
November 0.288976E+09 0.35 294.03 01-NOV-05:03 0.93
December 0.275215E+09 0.33 294.03 01-DEC-06:05 0.93
           
Annual Sum or Average 0.346771E+10 0.35      
Minimum of Months 0.261455E+09 0.32 294.03   0.92
Maximum of Months 0.316498E+09 0.37 294.03   0.93



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:10 0.00 0.00 34.14 0.00
February 0.00 0.00 0.00 01-FEB-07:05 0.00 0.00 17.32 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 17.32 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 17.32 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 17.32 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 17.32 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 17.32 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 17.32 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 17.32 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 17.32 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 17.32 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 17.32 0.00
                 
Annual Sum or Average 0.02 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 17.32 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 34.14 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.89 48.89 225.41 534.56 31-JAN-12:20
February 0.00 0.00 01-FEB-00:10 17.32 17.32 35.80 534.58 02-FEB-12:15
March 0.00 0.00 01-MAR-00:10 17.32 17.32 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 17.32 17.32 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 17.32 17.32 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 17.32 17.32 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 17.32 17.32 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 17.32 17.32 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 17.32 17.32 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 17.32 17.32 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 17.32 17.32 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 17.32 17.32 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         21.89    
Minimum of Months 0.00 0.00   17.32 17.32 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 225.41 534.58  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.514435E+09 0.00 0.00
February 0.00 0.00 0.00 0.447879E+09 0.00 0.00
March 0.00 0.00 0.00 0.529764E+09 0.00 0.00
April 0.00 0.00 0.00 0.603560E+09 0.00 0.00
May 0.00 0.00 0.00 0.696359E+09 0.00 0.00
June 0.00 0.00 0.00 0.828997E+09 0.00 0.00
July 0.00 0.00 0.00 0.914942E+09 0.00 0.00
August 0.00 0.00 0.00 0.105479E+10 0.00 0.00
September 0.00 0.00 0.00 0.806148E+09 0.00 0.00
October 0.00 0.00 0.00 0.848617E+09 0.00 0.00
November 0.00 0.00 0.00 0.597896E+09 0.00 0.00
December 0.00 0.00 0.00 0.511867E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.835525E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.447879E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.105479E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.608152E+09 0.00 0.00
February 0.00 0.00 0.00 0.463753E+09 0.00 0.00
March 0.00 0.00 0.00 0.531775E+09 0.00 0.00
April 0.00 0.00 0.00 0.468514E+09 0.00 0.00
May 0.00 0.00 0.00 0.479028E+09 0.00 0.00
June 0.00 0.00 0.00 0.571864E+09 0.00 0.00
July 0.00 0.00 0.00 0.672008E+09 0.00 0.00
August 0.00 0.00 0.00 0.816807E+09 0.00 0.00
September 0.00 0.00 0.00 0.688571E+09 0.00 0.00
October 0.00 0.00 0.00 0.833453E+09 0.00 0.00
November 0.00 0.00 0.00 0.627107E+09 0.00 0.00
December 0.00 0.00 0.00 0.599412E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.736044E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.463753E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.833453E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.257288E+09 0.00 0.00
February 0.00 0.00 0.00 0.211804E+09 0.00 0.00
March 0.00 0.00 0.00 0.260193E+09 0.00 0.00
April 0.00 0.00 0.00 0.304468E+09 0.00 0.00
May 0.00 0.00 0.00 0.338456E+09 0.00 0.00
June 0.00 0.00 0.00 0.406678E+09 0.00 0.00
July 0.00 0.00 0.00 0.483711E+09 0.00 0.00
August 0.00 0.00 0.00 0.559863E+09 0.00 0.00
September 0.00 0.00 0.00 0.398419E+09 0.00 0.00
October 0.00 0.00 0.00 0.424891E+09 0.00 0.00
November 0.00 0.00 0.00 0.274831E+09 0.00 0.00
December 0.00 0.00 0.00 0.238493E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.415909E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.211804E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.559863E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.389423E+09 0.00 0.00
February 0.00 0.00 0.00 0.301495E+09 0.00 0.00
March 0.00 0.00 0.00 0.380556E+09 0.00 0.00
April 0.00 0.00 0.00 0.390138E+09 0.00 0.00
May 0.00 0.00 0.00 0.463771E+09 0.00 0.00
June 0.00 0.00 0.00 0.568437E+09 0.00 0.00
July 0.00 0.00 0.00 0.649638E+09 0.00 0.00
August 0.00 0.00 0.00 0.738792E+09 0.00 0.00
September 0.00 0.00 0.00 0.546722E+09 0.00 0.00
October 0.00 0.00 0.00 0.583397E+09 0.00 0.00
November 0.00 0.00 0.00 0.370495E+09 0.00 0.00
December 0.00 0.00 0.00 0.334712E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.571758E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.301495E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.738792E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.379860E+09 0.00 0.00
February 0.00 0.00 0.00 0.320469E+09 0.00 0.00
March 0.00 0.00 0.00 0.390395E+09 0.00 0.00
April 0.00 0.00 0.00 0.416036E+09 0.00 0.00
May 0.00 0.00 0.00 0.466888E+09 0.00 0.00
June 0.00 0.00 0.00 0.542302E+09 0.00 0.00
July 0.00 0.00 0.00 0.599355E+09 0.00 0.00
August 0.00 0.00 0.00 0.687451E+09 0.00 0.00
September 0.00 0.00 0.00 0.531962E+09 0.00 0.00
October 0.00 0.00 0.00 0.550234E+09 0.00 0.00
November 0.00 0.00 0.00 0.406083E+09 0.00 0.00
December 0.00 0.00 0.00 0.356611E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.564765E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.320469E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.687451E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.317720E+09 0.840872E+09 35382832.18 0.00 0.00 0.00 0.00 0.00
February 0.287461E+09 0.729024E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.347979E+09 0.830399E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.302590E+09 0.139406E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.332849E+09 0.169297E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.332849E+09 0.234575E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.302590E+09 0.293236E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.347979E+09 0.338643E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.302590E+09 0.237217E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.317720E+09 0.247117E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.317720E+09 0.128785E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.302590E+09 0.947934E+09 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.381263E+10 0.212310E+11 35382832.18 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.287461E+09 0.729024E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.347979E+09 0.338643E+10 35382832.18 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.325523E+09 0.111491E+10 0.130201E+09 0.00 0.00 0.00 0.00 0.00
February 0.294521E+09 0.676133E+09 71156530.71 0.00 0.00 0.00 0.00 0.00
March 0.356525E+09 0.489008E+09 0.210897E+09 0.00 0.00 0.00 0.00 0.00
April 0.310022E+09 0.654470E+09 44209493.37 0.00 0.00 0.00 0.00 0.00
May 0.341024E+09 0.581885E+09 28078417.99 0.00 0.00 0.00 0.00 0.00
June 0.341024E+09 0.104947E+10 1727259.80 0.00 0.00 0.00 0.00 0.00
July 0.310022E+09 0.166877E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.356525E+09 0.214034E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.310022E+09 0.175914E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.325612E+09 0.237075E+10 36971.30 0.00 0.00 0.00 0.00 0.00
November 0.325523E+09 0.141736E+10 2142097.12 0.00 0.00 0.00 0.00 0.00
December 0.310022E+09 0.128684E+10 46112983.23 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.390637E+10 0.152091E+11 0.534561E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.294521E+09 0.489008E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.356525E+09 0.237075E+10 0.210897E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.187386E+09 0.226586E+09 55896076.28 0.00 0.00 0.00 0.00 0.00
February 0.168865E+09 0.164359E+09 18337342.08 0.00 0.00 0.00 0.00 0.00
March 0.204639E+09 0.192875E+09 37141635.77 0.00 0.00 0.00 0.00 0.00
April 0.184438E+09 0.542628E+09 233683.49 0.00 0.00 0.00 0.00 0.00
May 0.202774E+09 0.615856E+09 189574.59 0.00 0.00 0.00 0.00 0.00
June 0.207441E+09 0.911339E+09 0.00 0.00 0.00 0.00 0.00 0.00
July 0.196593E+09 0.132332E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.226395E+09 0.153769E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.190734E+09 0.940333E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.200629E+09 0.996849E+09 0.00 0.00 0.00 0.00 0.00 0.00
November 0.190023E+09 0.379240E+09 265842.25 0.00 0.00 0.00 0.00 0.00
December 0.178773E+09 0.249073E+09 10185809.90 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.233869E+10 0.808015E+10 0.122250E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.168865E+09 0.164359E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.226395E+09 0.153769E+10 55896076.28 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.286036E+09 0.198865E+09 0.180162E+09 0.00 0.00 0.00 0.00 0.00
February 0.258794E+09 95482349.48 64344417.83 0.00 0.00 0.00 0.00 0.00
March 0.313277E+09 0.135478E+09 0.110901E+09 0.00 0.00 0.00 0.00 0.00
April 0.272415E+09 0.521023E+09 5850724.91 0.00 0.00 0.00 0.00 0.00
May 0.299656E+09 0.742125E+09 1420144.16 0.00 0.00 0.00 0.00 0.00
June 0.299656E+09 0.123444E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.272415E+09 0.175028E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.313277E+09 0.197316E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.272415E+09 0.124770E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.286036E+09 0.133447E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.286036E+09 0.365285E+09 7563357.05 0.00 0.00 0.00 0.00 0.00
December 0.272415E+09 0.197425E+09 51190702.31 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.343243E+10 0.979573E+10 0.421432E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.258794E+09 95482349.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.313277E+09 0.197316E+10 0.180162E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.288976E+09 0.305577E+09 64449214.60 0.00 0.00 0.00 0.00 0.00
February 0.261455E+09 0.240339E+09 15449486.49 0.00 0.00 0.00 0.00 0.00
March 0.316498E+09 0.272968E+09 38257838.19 0.00 0.00 0.00 0.00 0.00
April 0.275215E+09 0.636560E+09 149956.34 0.00 0.00 0.00 0.00 0.00
May 0.302737E+09 0.742920E+09 97913.61 0.00 0.00 0.00 0.00 0.00
June 0.302737E+09 0.109186E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.275215E+09 0.148257E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.316498E+09 0.169813E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.275215E+09 0.116189E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.288976E+09 0.115917E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.288976E+09 0.525402E+09 11053.86 0.00 0.00 0.00 0.00 0.00
December 0.275215E+09 0.345267E+09 9994089.58 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.346771E+10 0.966265E+10 0.128410E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.261455E+09 0.240339E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.316498E+09 0.169813E+10 64449214.60 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.317720E+09 0.00 0.00 12052119.35 0.184663E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.287461E+09 0.00 0.00 0.00 0.160418E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.347979E+09 0.00 0.00 0.00 0.181785E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.302590E+09 0.00 0.00 0.00 0.300970E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.332849E+09 0.00 0.00 0.00 0.363510E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.332849E+09 0.00 0.00 0.00 0.496147E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.302590E+09 0.00 0.00 0.00 0.612352E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.347979E+09 0.00 0.00 0.00 0.706810E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.302590E+09 0.00 0.00 0.00 0.503558E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.317720E+09 0.00 0.00 0.00 0.530898E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.317720E+09 0.00 0.00 0.00 0.280177E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.302590E+09 0.00 0.00 0.00 0.209277E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.381263E+10 0.00 0.00 12052119.35 0.453057E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.287461E+09 0.00 0.00 0.00 0.160418E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.347979E+09 0.00 0.00 12052119.35 0.706810E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.325523E+09 0.00 0.00 42938869.96 0.239690E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.294521E+09 0.00 0.00 22974430.20 0.146258E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.356525E+09 0.00 0.00 68726632.54 0.106523E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.310022E+09 0.00 0.00 14174304.66 0.144318E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.341024E+09 0.00 0.00 8940348.26 0.129063E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.341024E+09 0.00 0.00 546648.85 0.230293E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.310022E+09 0.00 0.00 0.00 0.361986E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.356525E+09 0.00 0.00 0.00 0.460281E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.310022E+09 0.00 0.00 0.00 0.378549E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.325612E+09 0.00 0.00 12477.09 0.507828E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.325523E+09 0.00 0.00 722041.57 0.300862E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.310022E+09 0.00 0.00 15530447.41 0.273860E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.390637E+10 0.00 0.00 0.174566E+09 0.327951E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.294521E+09 0.00 0.00 0.00 0.106523E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.356525E+09 0.00 0.00 68726632.54 0.507828E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.187386E+09 0.00 0.00 18973674.89 50927723.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.168865E+09 0.00 0.00 6040766.24 36898037.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.204639E+09 0.00 0.00 12605036.05 42949143.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.184438E+09 0.00 0.00 78383.94 0.119952E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.202774E+09 0.00 0.00 64583.94 0.135618E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.207441E+09 0.00 0.00 0.00 0.199238E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.196593E+09 0.00 0.00 0.00 0.287118E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.226395E+09 0.00 0.00 0.00 0.333468E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.190734E+09 0.00 0.00 0.00 0.207685E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.200629E+09 0.00 0.00 0.00 0.224262E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.190023E+09 0.00 0.00 89699.28 84718659.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.178773E+09 0.00 0.00 3548644.05 56170758.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.233869E+10 0.00 0.00 41400788.40 0.177900E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.168865E+09 0.00 0.00 0.00 36898037.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.226395E+09 0.00 0.00 18973674.89 0.333468E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.286036E+09 0.00 0.00 58433670.26 44953704.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.258794E+09 0.00 0.00 21093367.68 21607354.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.313277E+09 0.00 0.00 37041535.08 30236759.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.272415E+09 0.00 0.00 1932099.17 0.115791E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.299656E+09 0.00 0.00 475952.80 0.163639E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.299656E+09 0.00 0.00 0.00 0.268780E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.272415E+09 0.00 0.00 0.00 0.377223E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.313277E+09 0.00 0.00 0.00 0.425515E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.272415E+09 0.00 0.00 0.00 0.274307E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.286036E+09 0.00 0.00 0.00 0.297361E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.286036E+09 0.00 0.00 2496841.56 81962893.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.272415E+09 0.00 0.00 17372837.95 44924691.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.343243E+10 0.00 0.00 0.138846E+09 0.214630E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.258794E+09 0.00 0.00 0.00 21607354.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.313277E+09 0.00 0.00 58433670.26 0.425515E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.288976E+09 0.00 0.00 21990988.06 68892831.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.261455E+09 0.00 0.00 5132817.37 53881282.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.316498E+09 0.00 0.00 13146214.63 60750912.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.275215E+09 0.00 0.00 50720.66 0.140770E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.302737E+09 0.00 0.00 33841.69 0.164117E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.302737E+09 0.00 0.00 0.00 0.239565E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.275215E+09 0.00 0.00 0.00 0.324140E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.316498E+09 0.00 0.00 0.00 0.370953E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.275215E+09 0.00 0.00 0.00 0.256747E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.288976E+09 0.00 0.00 0.00 0.261258E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.288976E+09 0.00 0.00 3719.59 0.117103E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.275215E+09 0.00 0.00 3506899.75 77888607.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.346771E+10 0.00 0.00 43865201.74 0.213607E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.261455E+09 0.00 0.00 0.00 53881282.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.316498E+09 0.00 0.00 21990988.06 0.370953E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.479825E+09 0.00 0.00 4275837.39 0.00 27111798.26 0.553044E+09 0.00 0.19
February 0.392250E+09 0.00 0.00 3988821.03 0.00 0.00 0.626012E+09 0.00 0.19
March 0.515403E+09 0.00 0.00 4236979.34 0.00 0.00 0.733534E+09 0.00 0.21
April 0.182007E+09 186875.63 0.00 6744811.78 0.00 0.00 0.559487E+09 0.00 0.19
May 0.150037E+09 0.00 0.00 7879260.65 0.00 0.00 0.637140E+09 0.00 0.20
June 62389619.98 19270082.84 0.00 7626670.83 206542.20 0.00 0.397053E+09 0.00 0.21
July 16895460.17 0.127569E+09 0.00 5857185.29 3876563.26 0.00 0.137808E+09 0.00 0.18
August 20286603.81 0.155330E+09 0.00 5431223.47 1963671.38 0.00 0.128807E+09 0.00 0.21
September 38078776.95 30441516.77 0.00 7645617.71 2409.02 0.00 0.286228E+09 0.00 0.19
October 52118134.68 54303587.37 0.00 8256217.73 806898.43 0.00 0.437321E+09 0.00 0.19
November 0.232481E+09 0.00 0.00 6826579.99 0.00 0.00 0.760735E+09 0.00 0.20
December 0.319773E+09 0.00 0.00 5283414.64 0.00 0.00 0.718285E+09 0.00 0.18
                   
Annual Sum or Average 0.246154E+10 0.387101E+09 0.00 74052619.85 6856084.29 27111798.26 0.597545E+10 0.00 0.19
Minimum of Months 16895460.17 0.00 0.00 3988821.03 0.00 0.00 0.128807E+09 0.00 0.18
Maximum of Months 0.515403E+09 0.155330E+09 0.00 8256217.73 3876563.26 27111798.26 0.760735E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.216042E+09 553265.73 0.00 5409566.30 0.00 64671355.58 0.237976E+09 0.00 0.19
February 0.240416E+09 390147.89 0.00 3162733.18 0.00 43464752.14 0.205854E+09 0.00 0.19
March 0.351235E+09 1069400.12 0.00 1883199.29 0.00 0.104698E+09 0.166159E+09 0.00 0.21
April 0.199965E+09 1567900.72 0.00 2250611.36 0.00 28550480.45 0.157264E+09 0.00 0.19
May 0.214497E+09 635814.92 0.00 2145769.30 0.00 21576298.21 0.181027E+09 0.00 0.20
June 0.137802E+09 15059748.76 0.00 2429026.45 38663.29 2818878.74 0.134094E+09 0.00 0.21
July 61128856.90 91081915.54 0.00 2351875.41 1125163.36 0.00 61753071.18 0.00 0.18
August 65141802.61 0.122601E+09 0.00 2248980.27 298351.56 0.00 63614832.70 0.00 0.21
September 92695116.21 46362748.55 0.00 3537460.97 444781.18 0.00 0.104535E+09 0.00 0.19
October 99083228.07 67782732.38 0.00 5197502.44 137001.83 0.00 0.121044E+09 0.00 0.19
November 0.200795E+09 1944.22 0.00 6956748.96 0.00 1478406.76 0.268809E+09 0.00 0.20
December 0.201400E+09 84423.71 0.00 6363980.26 0.00 30940177.80 0.236409E+09 0.00 0.18
                   
Annual Sum or Average 0.208020E+10 0.347191E+09 0.00 43937454.20 2043961.23 0.298198E+09 0.193854E+10 0.00 0.19
Minimum of Months 61128856.90 1944.22 0.00 1883199.29 0.00 0.00 61753071.18 0.00 0.18
Maximum of Months 0.351235E+09 0.122601E+09 0.00 6956748.96 1125163.36 0.104698E+09 0.268809E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.146141E+09 26759.55 0.00 1079823.49 0.00 36659430.45 91720132.50 0.00 0.15
February 0.146355E+09 102626.76 0.00 791440.45 0.00 17391578.68 89826676.26 0.00 0.15
March 0.208686E+09 871932.68 0.00 797937.03 0.00 26994930.86 85933315.70 0.00 0.16
April 91998494.04 1885316.37 0.00 2462836.58 2305.15 0.00 0.100417E+09 0.00 0.15
May 89532901.85 816648.35 0.00 2730658.08 0.00 143651.40 0.117712E+09 0.00 0.16
June 47056938.10 20418279.67 0.00 2369691.28 336334.99 0.00 77294489.83 0.00 0.17
July 5766959.12 82782503.80 0.00 1578863.58 3406765.21 0.00 40068187.58 0.00 0.15
August 6902436.82 0.105851E+09 0.00 1523779.10 2440595.72 0.00 43421780.06 0.00 0.18
September 25541147.75 30479794.10 0.00 2286359.62 246344.16 0.00 71523426.63 0.00 0.16
October 51355972.89 38589085.35 0.00 2353360.59 1008278.32 0.00 75144677.60 0.00 0.16
November 0.110531E+09 3347.26 0.00 1940075.88 2155.94 121940.20 0.145955E+09 0.00 0.15
December 0.140237E+09 138523.36 0.00 1191479.01 3835.04 11051472.69 98289179.48 0.00 0.14
                   
Annual Sum or Average 0.107011E+10 0.281966E+09 0.00 21106304.70 7446614.53 92363004.29 0.103731E+10 0.00 0.16
Minimum of Months 5766959.12 3347.26 0.00 791440.45 0.00 0.00 40068187.58 0.00 0.14
Maximum of Months 0.208686E+09 0.105851E+09 0.00 2730658.08 3406765.21 36659430.45 0.145955E+09 0.00 0.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.342595E+09 45806.86 0.00 810744.92 0.00 0.113824E+09 0.107812E+09 0.00 0.19
February 0.381375E+09 83898.74 0.00 410448.32 0.00 54464542.21 0.108982E+09 0.00 0.19
March 0.515117E+09 0.00 0.00 497024.25 0.00 79883017.61 99269217.09 0.00 0.21
April 0.218902E+09 714944.54 0.00 1979628.08 0.00 3991312.45 0.211358E+09 0.00 0.19
May 0.188489E+09 379593.09 0.00 3052360.34 0.00 674610.23 0.269389E+09 0.00 0.20
June 96202498.09 23659412.59 0.00 3300691.12 408470.49 0.00 0.179031E+09 0.00 0.21
July 15027330.02 0.121509E+09 0.00 2709632.06 4690180.38 0.00 86070909.31 0.00 0.18
August 26576881.98 0.147396E+09 0.00 2237650.27 2979470.35 0.00 82914048.65 0.00 0.21
September 87725620.45 39243108.89 0.00 3152726.44 320298.06 0.00 0.125557E+09 0.00 0.19
October 0.108557E+09 64323097.66 0.00 2750428.60 1383381.54 0.00 0.144267E+09 0.00 0.19
November 0.278806E+09 0.00 0.00 1736885.10 0.00 7610805.38 0.261859E+09 0.00 0.20
December 0.345722E+09 185.68 0.00 820549.76 0.00 45864786.92 0.124235E+09 0.00 0.18
                   
Annual Sum or Average 0.260509E+10 0.397356E+09 0.00 23458769.25 9781800.82 0.306313E+09 0.180075E+10 0.00 0.19
Minimum of Months 15027330.02 0.00 0.00 410448.32 0.00 0.00 82914048.65 0.00 0.18
Maximum of Months 0.515117E+09 0.147396E+09 0.00 3300691.12 4690180.38 0.113824E+09 0.269389E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.171033E+09 35491.40 0.00 1245105.01 0.00 47857879.25 0.118118E+09 0.00 0.19
February 0.178983E+09 69153.11 0.00 1003986.91 0.00 17643681.75 0.123499E+09 0.00 0.19
March 0.250287E+09 312885.94 0.00 1032224.73 0.00 36975096.73 0.118891E+09 0.00 0.21
April 0.104348E+09 1240449.40 0.00 2330815.11 14771.64 0.00 0.133686E+09 0.00 0.19
May 93986162.15 433320.62 0.00 2869185.12 0.00 0.00 0.163321E+09 0.00 0.20
June 41567783.41 20817452.77 0.00 2421326.32 450832.08 0.00 0.104059E+09 0.00 0.21
July 5721464.05 88959537.08 0.00 1689610.31 3828698.90 0.00 39826615.82 0.00 0.18
August 5918324.17 0.112142E+09 0.00 1443224.91 3078385.91 0.00 43529796.24 0.00 0.21
September 18600623.54 33154180.04 0.00 2349439.79 274736.23 0.00 85017260.05 0.00 0.19
October 52094843.10 44113286.39 0.00 2289366.36 1003841.80 0.00 92110759.19 0.00 0.19
November 0.127804E+09 0.00 0.00 2253402.31 0.00 0.00 0.184795E+09 0.00 0.20
December 0.161521E+09 2205.75 0.00 1452614.74 0.00 14886120.40 0.130467E+09 0.00 0.18
                   
Annual Sum or Average 0.121187E+10 0.301280E+09 0.00 22380301.63 8651266.56 0.117363E+09 0.133732E+10 0.00 0.19
Minimum of Months 5721464.05 0.00 0.00 1003986.91 0.00 0.00 39826615.82 0.00 0.18
Maximum of Months 0.250287E+09 0.112142E+09 0.00 2869185.12 3828698.90 47857879.25 0.184795E+09 0.00 0.21



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:27:39

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.573869E+11 0.172743E+10 0.00 0.937144E+10 0.297768E+10
February 0.717132E+11 0.236276E+10 0.00 0.827321E+10 0.221035E+10
March 0.102773E+12 0.364677E+10 0.00 0.941762E+10 0.208105E+10
April 0.144357E+12 0.444348E+10 0.00 0.700312E+10 0.453633E+10
May 0.152422E+12 0.488350E+10 0.00 0.718654E+10 0.531143E+10
June 0.154150E+12 0.496384E+10 0.00 0.500903E+10 0.806570E+10
July 0.167872E+12 0.488424E+10 0.00 0.331932E+10 0.111201E+11
August 0.153081E+12 0.423400E+10 0.00 0.267009E+10 0.130328E+11
September 0.116055E+12 0.310345E+10 0.00 0.437725E+10 0.910208E+10
October 0.786856E+11 0.221021E+10 0.00 0.518769E+10 0.101540E+11
November 0.639552E+11 0.187403E+10 0.00 0.869806E+10 0.483329E+10
December 0.512080E+11 0.142856E+10 0.00 0.995101E+10 0.361113E+10
           
Annual Sum or Average 0.131366E+13 0.397623E+11 0.00 0.804644E+11 0.770359E+11
Minimum of Months 0.512080E+11 0.142856E+10 0.00 0.267009E+10 0.208105E+10
Maximum of Months 0.167872E+12 0.496384E+10 0.00 0.995101E+10 0.130328E+11