Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940

Simulation Timestamp: 2023-10-16 08:27:32


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 192.84 377.25 377.25
Net Site Energy 192.84 377.25 377.25
Total Source Energy 610.71 1194.76 1194.76
Net Source Energy 610.71 1194.76 1194.76


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 62.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 22.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 192.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31


End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 62.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 23.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 22.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 62.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 23.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 22.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 211.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 377.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 211.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 377.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 192.836 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 192.836 100.00
     
Total On-Site and Utility Electric Sources 192.836 100.00
Total Electricity End Uses 192.836 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 629.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 1139.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
RunPeriod RUNPERIOD 1
Weather File Dubai Intl AP - ARE IWEC2 WMO#=411940
Latitude [deg] 25.25
Longitude [deg] 55.33
Elevation [m] 5.00
Time Zone 4.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.9815 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.9815 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.9815 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.9815 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.9815 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.9815 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.9815 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.9815 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.9815 9.29 6.7800  
Conditioned Total 511.16             6.9815 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.9815 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 16-AUG-12:00 - - - - - - - - - - - 02-JAN-12:09
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 9968.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2135.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1994.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2720.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 20144.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 9968.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2135.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1994.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2720.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 196.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 83.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 74.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 71.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 610.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 384.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 164.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 145.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 140.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1194.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 384.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 164.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 60.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 145.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 140.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1194.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.320853
PERIMETER_ZN_1 DIRECT AIR 0.432156
PERIMETER_ZN_2 DIRECT AIR 0.280606
PERIMETER_ZN_3 DIRECT AIR 0.422344
PERIMETER_ZN_4 DIRECT AIR 0.324733
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.320853 0.320853 0.320853 0.320853 0.320853 0.320853 1.00 1.00 0.320853
PSZ-AC:2 0.432156 0.432156 0.432156 0.432156 0.432156 0.432156 1.00 1.00 0.432156
PSZ-AC:3 0.280606 0.280606 0.280606 0.280606 0.280606 0.280606 1.00 1.00 0.280606
PSZ-AC:4 0.422344 0.422344 0.422344 0.422344 0.422344 0.422344 1.00 1.000000 0.422344
PSZ-AC:5 0.324733 0.324733 0.324733 0.324733 0.324733 0.324733 1.00 1.000000 0.324733
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.320853 0.064622
PSZ-AC:2_OA_CONTROLLER 0.432156 0.048988
PSZ-AC:3_OA_CONTROLLER 0.280606 0.029060
PSZ-AC:4_OA_CONTROLLER 0.422344 0.048988
PSZ-AC:5_OA_CONTROLLER 0.324733 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.320853 7476.58 0.721177
PSZ-AC:2 HP COOLING COIL 0.432156 9068.19 0.758036
PSZ-AC:3 HP COOLING COIL 0.280606 5567.17 0.779757
PSZ-AC:4 HP COOLING COIL 0.422344 8898.02 0.755871
PSZ-AC:5 HP COOLING COIL 0.324733 6449.03 0.779453
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.320853 0.320853 0.320853 0.320853 7476.58 7476.58 40.00 2133.68 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.432156 0.432156 0.432156 0.432156 9068.19 9068.19 40.00 1617.47 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.280606 0.280606 0.280606 0.280606 5567.17 5567.17 40.00 959.50 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.422344 0.422344 0.422344 0.422344 8898.02 8898.02 40.00 1617.47 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.324733 0.324733 0.324733 0.324733 6449.03 6449.03 40.00 959.50 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.320853
PSZ-AC:2 FAN 0.432156
PSZ-AC:3 FAN 0.280606
PSZ-AC:4 FAN 0.422344
PSZ-AC:5 FAN 0.324733
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.320853 7476.58
PSZ-AC:2 HEATING COIL 0.432156 9068.19
PSZ-AC:3 HEATING COIL 0.280606 5567.17
PSZ-AC:4 HEATING COIL 0.422344 8898.02
PSZ-AC:5 HEATING COIL 0.324733 6449.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 2133.68
PSZ-AC:2_SUPPHEATCOIL 1617.47
PSZ-AC:3_SUPPHEATCOIL 959.50
PSZ-AC:4_SUPPHEATCOIL 1617.47
PSZ-AC:5_SUPPHEATCOIL 959.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 29.50 25.50 21.10 19.20 20.80 23.10 26.50 31.40 33.00 35.10 35.30 32.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Dubai Intl AP - ARE IWEC2 WMO#=411940 25.25 55.33 4.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 27.75 16.10 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1044.832 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1044.832
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4610


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 9.0605E-004
2 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.0108E-003
3 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 9.4281E-004
4 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.0331E-003
5 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 7.1833E-004
6 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 7.9327E-004
7 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 3.8057E-004
8 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.2514E-004
9 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.4346E-003
10 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.4699E-003
11 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.1742E-003
12 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.4092E-003
13 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.2653E-003
14 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 3.5922E-003
15 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.2482E-003
16 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.7482E-003
17 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.0233E-003
18 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 5.2725E-003
19 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.0507E-003
20 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 5.4443E-003
21 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.3570E-003
22 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 3.8396E-003
23 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 2.6987E-003
24 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.6162E-003
25 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 9.0921E-004
26 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.0324E-003
27 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 9.4764E-004
28 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.0601E-003
29 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 7.2244E-004
30 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 8.0783E-004
31 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 3.7743E-004
32 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.1823E-004
33 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 8.6072E-004
34 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 8.7408E-004
35 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 9.0540E-004
36 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 9.1704E-004
37 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 6.8646E-004
38 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 6.9528E-004
39 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 3.5576E-004
40 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 3.6049E-004
41 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 8.5722E-004
42 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 8.5980E-004
43 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 9.0242E-004
44 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 9.0463E-004
45 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 6.8414E-004
46 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 6.8579E-004
47 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 3.5434E-004
48 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 3.5526E-004
49 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.4173E-003
50 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.7349E-003
51 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.4506E-003
52 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.7588E-003
53 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.1301E-003
54 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.3323E-003
55 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.0357E-004
56 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 6.7665E-004
57 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.1844E-004
58 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.9927E-004
59 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.5629E-004
60 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.1679E-004
61 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.0052E-004
62 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.3098E-004
63 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 5.9661E-004
64 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.3767E-004
65 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.0217E-003
66 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.4198E-003
67 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.4699E-003
68 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.0228E-003
69 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.2127E-003
70 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.7806E-003
71 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.9216E-003
72 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.8579E-003
73 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 8.4727E-003
74 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.0896E-003
75 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 8.7300E-003
76 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.8686E-003
77 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 7.1838E-003
78 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.4384E-003
79 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.4829E-003
80 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 1.9940E-003
81 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.0070E-004
82 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.1019E-003
83 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 8.5403E-004
84 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0553E-003
85 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 7.5904E-004
86 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 8.7959E-004
87 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 5.9965E-004
88 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 6.4454E-004
89 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.8522E-004
90 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.5775E-004
91 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.1416E-004
92 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.7087E-004
93 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 2.5920E-004
94 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 2.9728E-004
95 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.7650E-004
96 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.1551E-004
97 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.4124E-003
98 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.9149E-003
99 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 1.9240E-003
100 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.4816E-003
101 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 1.8323E-003
102 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.0638E-003
103 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.4634E-003
104 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.5539E-003
105 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.2913E-003
106 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.2774E-003
107 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.5487E-003
108 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.7235E-003
109 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.1221E-003
110 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.0793E-003
111 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.5656E-003
112 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.8176E-003
113 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.9343E-004
114 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.8203E-004
115 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.1937E-004
116 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.8629E-004
117 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 2.5938E-004
118 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 2.9535E-004
119 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.8281E-004
120 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.2934E-004
121 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.4920E-004
122 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.6048E-004
123 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.8475E-004
124 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.9344E-004
125 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.3491E-004
126 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.3993E-004
127 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.5641E-004
128 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.6167E-004
129 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.4590E-004
130 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.4818E-004
131 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.8216E-004
132 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.8393E-004
133 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.3321E-004
134 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.3426E-004
135 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.5480E-004
136 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.5580E-004
137 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 7.6626E-004
138 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 9.1177E-004
139 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.9183E-004
140 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 8.2706E-004
141 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.3824E-004
142 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 7.3691E-004
143 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.0063E-004
144 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 6.4519E-004
145 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.8933E-003
146 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.0823E-003
147 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.6154E-003
148 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.7248E-003
149 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.6177E-003
150 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.6853E-003
151 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.4683E-003
152 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 1.9683E-003
153 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.9558E-003
154 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.2957E-003
155 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.3287E-003
156 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.8368E-003
157 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 1.8812E-003
158 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.4508E-003
159 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.9188E-003
160 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.8363E-003
161 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.0195E-004
162 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.8661E-004
163 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.1523E-004
164 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.7727E-004
165 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 5.8326E-004
166 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.0952E-004
167 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 5.9749E-004
168 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.3829E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3642.39487 4370.87385 0.26738 0.32085 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 42.21800 1.07808E-002 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 342.33502 410.80202 1.47660E-002 6.46221E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12.70000 9.15345E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 4905.84725 5887.01670 0.36013 0.43216 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 42.50900 1.07813E-002 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 784.99317 941.99180 3.38594E-002 4.89877E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12.70000 9.15345E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 3185.53526 3822.64231 0.23384 0.28061 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 40.32650 1.07776E-002 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 476.32832 571.59398 2.05456E-002 2.90601E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12.70000 9.15345E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 4794.45409 5753.34491 0.35195 0.42234 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 42.50900 1.07813E-002 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 762.83564 915.40277 3.29036E-002 4.89877E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12.70000 9.15345E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3686.45857 4423.75029 0.27061 0.32473 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 41.57133 1.07797E-002 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 478.61094 574.33313 2.06441E-002 2.90601E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 12.70000 9.15345E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 5735.79 0.32085 0.32085 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-AC:1 Heating Sensible 2133.68 6.46221E-002 6.46221E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 6899.17 0.43216 0.43216 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-AC:2 Heating Sensible 1617.47 4.89877E-002 4.89877E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00
5 PSZ-AC:3 Cooling Sensible 4341.23 0.28061 0.28061 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
6 PSZ-AC:3 Heating Sensible 959.50 2.90601E-002 2.90601E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00
7 PSZ-AC:4 Cooling Sensible 6767.56 0.42234 0.42234 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 PSZ-AC:4 Heating Sensible 1617.47 4.89877E-002 4.89877E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 PSZ-AC:5 Cooling Sensible 4976.80 0.32473 0.32473 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 PSZ-AC:5 Heating Sensible 959.50 2.90601E-002 2.90601E-002 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.32085
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.43216
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.28061
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.42234
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.32473
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.32085
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.32085
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.32085
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.32085
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.32085
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.32085
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.43216
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.43216
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.43216
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.43216
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.43216
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.43216
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.28061
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.28061
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.28061
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.28061
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.28061
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.28061
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.42234
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.42234
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.42234
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.42234
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.42234
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.42234
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.32473
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.32473
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.32473
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.32473
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.32473
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.32473
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.32085
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.43216
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.28061
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.42234
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.32473
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.32085
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.32085
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7476.58059
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.72118
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.32085
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.32085
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.32085
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.32085
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7476.58059
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7476.58059
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2133.67760
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.32085
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.32085
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7476.58059
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 2133.67760
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.43216
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.43216
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 9068.18515
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.75804
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.43216
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.43216
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.43216
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.43216
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 9068.18515
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 9068.18515
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 1617.46579
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.43216
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.43216
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 9068.18515
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 1617.46579
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.28061
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28061
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5567.17075
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.77976
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.28061
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.28061
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.28061
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.28061
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5567.17075
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5567.17075
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 959.50152
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.28061
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.28061
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5567.17075
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 959.50152
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.42234
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.42234
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 8898.02235
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.75587
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.42234
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.42234
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.42234
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.42234
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 8898.02235
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 8898.02235
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 1617.46579
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.42234
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.42234
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 8898.02235
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 1617.46579
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.32473
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.32473
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6449.02910
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.77945
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.32473
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.32473
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.32473
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.32473
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6449.02910
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6449.02910
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 959.50152
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.32473
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.32473
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6449.02910
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 959.50152
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 7223.8 3.50 11.94 12.53 11.85 12.04
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 8728.3 3.44 11.74 12.30 11.64 11.73
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 5346.7 3.41 11.62 12.18 11.52 11.55
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 8565.8 3.44 11.75 12.31 11.65 11.74
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 6193.9 3.41 11.63 12.18 11.52 11.56


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 7733.8 4262.4 7.50 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 9413.4 5203.1 7.46 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 5790.9 3206.1 7.42 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 9235.4 5104.1 7.46 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 6708.0 3713.7 7.41 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 9.4095397161E-003 5.8401944947E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 3.5679470730E-002 2.7560945924E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 2.3758416546E-002 1.3650870166E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 2.2149612343E-002 1.4299858637E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 3.1582369326E-002 1.8494554794E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.3808188753 0.3072339349 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 949.55 7.93 0.00 -59.3 -0.119434E+11 -0.119434E+11



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 12.70 0.00 12.70 Wetbulb [C] 2.00 170.00
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 42.80 9.70 23.80 Wetbulb [C] 5.00 80.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 2.40 26      
Feb 9.60 38      
Mar 3.60 37      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 1.20 13      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 18.00 37      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.504_SHGC_SOUTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.504_SHGC_SOUTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.504_SHGC_SOUTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.504_SHGC_SOUTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.504_SHGC_SOUTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.504_SHGC_SOUTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.504_SHGC_SOUTH_0.219   3.91 0.00 0.00 3.91 3.91 2.865 0.220 0.242             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.504_SHGC_EAST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.504_SHGC_EAST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.504_SHGC_EAST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.504_SHGC_EAST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.504_SHGC_NORTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.504_SHGC_NORTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.504_SHGC_NORTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.504_SHGC_NORTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.504_SHGC_NORTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.504_SHGC_NORTH_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.504_SHGC_WEST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.504_SHGC_WEST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.504_SHGC_WEST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.504_SHGC_WEST_0.219   2.79 0.00 0.00 2.79 2.79 2.865 0.220 0.242             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.865 0.220 0.242                      
North Total or Average             16.72 2.865 0.220 0.242                      
Non-North Total or Average             42.93 2.865 0.220 0.242                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.69 0.64 0.65 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.69 0.64 0.65 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.69 0.64 0.65 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.69 0.64 0.65 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.69 0.64 0.65 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.69 0.64 0.65 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 0.91 0.88 0.89 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.03 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.04 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.88 0.00 0.00 0.78 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.88 0.00 0.00 0.78 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.88 0.00 0.00 0.78 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.88 0.00 0.00 0.78 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.9815 149.66 1044.83 LightsWired LTG_SCH_OFFICE 55.32 168.00 44.56 0.0000 Y 8.74
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 36.16 0.0000 Y 5.38
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 37.56 0.0000 Y 3.31
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.65 0.0000 Y 5.75
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 37.69 0.0000 Y 3.32
Interior Lighting Total       6.9815 511.16 3568.64               26.50


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 87.95 AstronomicalClock -   41.85 41.85 0.69
EXTERIOR_LIGHTS_B 200.47 AstronomicalClock -   83.85 62.85 2.37
EXTERIOR_LIGHTS_C 773.25 AstronomicalClock -   83.85 46.68 6.78
Exterior Lighting Total 1061.67           9.83



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7476.58 5391.94 2084.64 0.72 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   9068.19 6874.01 2194.17 0.76 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5567.17 4341.04 1226.13 0.78 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   8898.02 6725.76 2172.26 0.76 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6449.03 5026.71 1422.31 0.78 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   7223.8 3.50 11.94 12.53 11.85 12.04
PSZ-AC:2 HP COOLING COIL   8728.3 3.44 11.74 12.30 11.64 11.73
PSZ-AC:3 HP COOLING COIL   5346.7 3.41 11.62 12.18 11.52 11.55
PSZ-AC:4 HP COOLING COIL   8565.8 3.44 11.75 12.31 11.65 11.74
PSZ-AC:5 HP COOLING COIL   6193.9 3.41 11.63 12.18 11.52 11.56
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 7733.8 4262.4 7.50 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 9413.4 5203.1 7.46 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 5790.9 3206.1 7.42 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 9235.4 5104.1 7.46 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 6708.0 3713.7 7.41 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   7476.58 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   2133.68 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   9068.19 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   1617.47 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   5567.17 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   959.50 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   8898.02 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   1617.47 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   6449.03 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   959.50 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.32 359.39 1120.11 1.00 1.85 General DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.43 484.06 1120.11 1.00 1.68 General DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.28 314.31 1120.11 1.00 1.95 General DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.42 473.07 1120.11 1.00 1.69 General DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.32 363.74 1120.11 1.00 1.84 General DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3642.39 4370.87 29.21 0.267 0.321 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 23.89 23.89 0.00899 42.22 0.01078 0.065 0.00
PERIMETER_ZN_1 4905.85 5887.02 51.89 0.360 0.432 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 23.89 23.89 0.00884 42.51 0.01078 0.049 0.00
PERIMETER_ZN_2 3185.54 3822.64 56.80 0.234 0.281 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 23.89 23.89 0.00882 40.33 0.01078 0.029 0.00
PERIMETER_ZN_3 4794.45 5753.34 50.71 0.352 0.422 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 23.89 23.89 0.00885 42.51 0.01078 0.049 0.00
PERIMETER_ZN_4 3686.46 4423.75 65.73 0.271 0.325 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 23.89 23.89 0.00878 41.57 0.01078 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 342.34 410.80 2.74 0.015 0.065 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00800 12.70 0.00915 0.065 0.00
PERIMETER_ZN_1 784.99 941.99 8.30 0.034 0.049 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00815 12.70 0.00915 0.049 0.00
PERIMETER_ZN_2 476.33 571.59 8.49 0.021 0.029 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00817 12.70 0.00915 0.029 0.00
PERIMETER_ZN_3 762.84 915.40 8.07 0.033 0.049 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00816 12.70 0.00915 0.049 0.00
PERIMETER_ZN_4 478.61 574.33 8.53 0.021 0.029 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00817 12.70 0.00915 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.32 0.32 0.06 0.06 0.3209 0.3209 0.3209 1.0000 1.0000
PSZ-AC:2 0.43 0.43 0.05 0.05 0.4322 0.4322 0.4322 1.0000 1.0000
PSZ-AC:3 0.28 0.28 0.03 0.03 0.2806 0.2806 0.2806 1.0000 1.0000
PSZ-AC:4 0.42 0.42 0.05 0.05 0.4223 0.4223 0.4223 1.0000 1.0000
PSZ-AC:5 0.32 0.32 0.03 0.03 0.3247 0.3247 0.3247 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 7476.581 5391.937 0.320853 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 6760.77 6003.49 0.320853 28.49 18.62 0.00935194 12.80 12.09 0.00850000 42.22 0.01078081 23.70 20.1407 23.89 0.00899433 48.6792 3627.54 0.00 7475.30 5385.95
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 7476.581 7476.581 0.320853 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 7476.58 7476.58 0.320853 19.42 14.46 0.00823231 40.00 21.18 0.00800000 12.70 0.00915345 12.70 20.1407 21.11 0.00800005 51.3449 341.75 0.00 7486.41 7486.41
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 2133.678 2133.678 -999.0 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 2133.68 2133.68 0.320853 19.42 14.46 0.00823231 40.00 21.18 0.00800000 12.70 0.00915345 12.70 20.1407 21.11 0.00800005 51.3449 341.75 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 9068.185 6874.013 0.432156 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 7970.30 7302.61 0.432156 26.91 17.86 0.00906041 12.80 12.09 0.00850000 42.51 0.01078131 23.78 11.3357 23.89 0.00884043 47.8582 4901.79 0.00 9066.63 6867.90
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 9068.185 9068.185 0.432156 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9068.19 9068.19 0.432156 20.16 14.77 0.00826807 40.00 21.18 0.00800000 12.70 0.00915345 12.70 11.3357 21.11 0.00815509 52.3268 784.80 0.00 9080.10 9080.10
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 1617.466 1617.466 -999.0 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1617.47 1617.47 0.432156 20.16 14.77 0.00826807 40.00 21.18 0.00800000 12.70 0.00915345 12.70 11.3357 21.11 0.00815509 52.3268 784.80 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5567.171 4341.038 0.280606 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 5014.26 4610.71 0.280606 26.50 17.69 0.00902233 12.80 12.09 0.00850000 40.33 0.01077755 23.19 10.3562 23.89 0.00882159 47.7583 3156.64 0.00 5566.22 4336.73
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5567.171 5567.171 0.280606 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 5567.17 5567.17 0.280606 20.24 14.81 0.00826999 40.00 21.18 0.00800000 12.70 0.00915345 12.70 10.3562 21.11 0.00816813 52.4093 476.23 0.00 5574.49 5574.49
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 959.502 959.502 -999.0 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 959.50 959.50 0.280606 20.24 14.81 0.00826999 40.00 21.18 0.00800000 12.70 0.00915345 12.70 10.3562 21.11 0.00816813 52.4093 476.23 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 8898.022 6725.759 0.422344 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 7827.42 7160.95 0.422344 26.96 17.88 0.00907226 12.80 12.09 0.00850000 42.51 0.01078131 23.78 11.5990 23.89 0.00884827 47.9001 4787.81 0.00 8896.50 6717.62
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 8898.022 8898.022 0.422344 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8898.02 8898.02 0.422344 20.13 14.77 0.00827413 40.00 21.18 0.00800000 12.70 0.00915345 12.70 11.5990 21.11 0.00815898 52.3514 762.64 0.00 8909.72 8909.72
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 1617.466 1617.466 -999.0 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1617.47 1617.47 0.422344 20.13 14.77 0.00827413 40.00 21.18 0.00800000 12.70 0.00915345 12.70 11.5990 21.11 0.00815898 52.3514 762.64 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6449.029 5026.715 0.324733 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 5695.27 5287.96 0.324733 26.38 17.59 0.00895602 12.80 12.09 0.00850000 41.57 0.01077970 23.53 8.9489 23.89 0.00877679 47.5175 3686.46 0.00 6447.92 5021.52
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6449.029 6449.029 0.324733 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6449.03 6449.03 0.324733 20.36 14.84 0.00825549 40.00 21.18 0.00800000 12.70 0.00915345 12.70 8.9489 21.11 0.00816744 52.4049 478.51 0.00 6457.50 6457.50
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 959.502 959.502 -999.0 -999.0 -999.000 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 959.50 959.50 0.324733 20.36 14.84 0.00825549 40.00 21.18 0.00800000 12.70 0.00915345 12.70 8.9489 21.11 0.00816744 52.4049 478.51 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7476.581 5391.937 0.320853 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.2248 1004.8586 1.2036 PSZ-AC:1 FAN Fan:OnOff 0.320853 0.38617686   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 Sensible 6760.77 6003.49 0.9043 0.38617686 0.320853 28.49 18.62 0.00935194 52513.2 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 359.390 6401.38 42.22 0.01078081 23.70 0.06462207 20.1407 23.89 0.00899157 23.89 0.00899433 48.6792 3627.54 0.00 7475.30 5385.95 0.37092579 26.67 19.44 0.01118466 55322.4 12.45 12.43 0.00897617 35169.3
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7476.581 7476.581 0.320853 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:1 FAN Fan:OnOff 0.320853 0.38617686   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 7476.58 7476.58 1.0000 0.38617686 0.320853 19.42 14.46 0.00823231 40395.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7476.58 12.70 0.00915345 12.70 0.06462207 20.1407 21.11 0.00800000 21.11 0.00800005 51.3449 341.75 0.00 7486.41 7486.41 0.37935300 21.11 15.56 0.00875166 43444.1 40.44 21.85 0.00875166 63178.8
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2133.678 2133.678 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:1 FAN Fan:OnOff 0.320853 0.38617686   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 2133.68 2133.68 1.0000 0.38617686 0.320853 19.42 14.46 0.00823231 40395.8 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2133.68 12.70 0.00915345 12.70 0.06462207 20.1407 21.11 0.00800000 21.11 0.00800005 51.3449 341.75 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 9068.185 6874.013 0.432156 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.6828 1004.8586 1.2036 PSZ-AC:2 FAN Fan:OnOff 0.432156 0.52014098   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 Sensible 7970.30 7302.61 0.8789 0.52014098 0.432156 26.91 17.86 0.00906041 50153.8 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 484.062 7486.24 42.51 0.01078131 23.78 0.04898771 11.3357 23.89 0.00884040 23.89 0.00884043 47.8582 4901.79 0.00 9066.63 6867.90 0.49959934 26.67 19.44 0.01118466 55322.4 13.22 13.21 0.00945914 37174.6
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 9068.185 9068.185 0.432156 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:2 FAN Fan:OnOff 0.432156 0.52014098   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9068.19 9068.19 1.0000 0.52014098 0.432156 20.16 14.77 0.00826807 41242.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9068.19 12.70 0.00915345 12.70 0.04898771 11.3357 21.11 0.00815487 21.11 0.00815509 52.3268 784.80 0.00 9080.10 9080.10 0.51094993 21.11 15.56 0.00875166 43444.1 38.51 21.28 0.00875166 61215.1
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 1617.466 1617.466 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:2 FAN Fan:OnOff 0.432156 0.52014098   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1617.47 1617.47 1.0000 0.52014098 0.432156 20.16 14.77 0.00826807 41242.1 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1617.47 12.70 0.00915345 12.70 0.04898771 11.3357 21.11 0.00815487 21.11 0.00815509 52.3268 784.80 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5567.171 4341.038 0.280606 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.6121 1004.8586 1.2036 PSZ-AC:3 FAN Fan:OnOff 0.280606 0.33773565   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 10:50:00 Sensible 5014.26 4610.71 0.9007 0.33773565 0.280606 26.50 17.69 0.00902233 49639.8 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 314.309 4699.95 40.33 0.01077755 23.19 0.02906014 10.3562 23.89 0.00881955 23.89 0.00882159 47.7583 3156.64 0.00 5566.22 4336.73 0.32439765 26.67 19.44 0.01118466 55322.4 13.60 13.59 0.00969867 38163.8
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5567.171 5567.171 0.280606 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:3 FAN Fan:OnOff 0.280606 0.33773565   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 5567.17 5567.17 1.0000 0.33773565 0.280606 20.24 14.81 0.00826999 41331.0 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5567.17 12.70 0.00915345 12.70 0.02906014 10.3562 21.11 0.00816792 21.11 0.00816813 52.4093 476.23 0.00 5574.49 5574.49 0.33176776 21.11 15.56 0.00875166 43444.1 37.57 21.00 0.00875166 60246.5
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 959.502 959.502 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:3 FAN Fan:OnOff 0.280606 0.33773565   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 959.50 959.50 1.0000 0.33773565 0.280606 20.24 14.81 0.00826999 41331.0 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 959.50 12.70 0.00915345 12.70 0.02906014 10.3562 21.11 0.00816792 21.11 0.00816813 52.4093 476.23 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8898.022 6725.759 0.422344 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.7049 1004.8586 1.2036 PSZ-AC:4 FAN Fan:OnOff 0.422344 0.50833061   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 Sensible 7827.42 7160.95 0.8797 0.50833061 0.422344 26.96 17.88 0.00907226 50234.1 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 473.070 7354.35 42.51 0.01078131 23.78 0.04898771 11.5990 23.89 0.00884802 23.89 0.00884827 47.9001 4787.81 0.00 8896.50 6717.62 0.48825539 26.67 19.44 0.01118466 55322.4 13.21 13.18 0.00943498 37101.4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 8898.022 8898.022 0.422344 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:4 FAN Fan:OnOff 0.422344 0.50833061   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 8898.02 8898.02 1.0000 0.50833061 0.422344 20.13 14.77 0.00827413 41234.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8898.02 12.70 0.00915345 12.70 0.04898771 11.5990 21.11 0.00815875 21.11 0.00815898 52.3514 762.64 0.00 8909.72 8909.72 0.49934825 21.11 15.56 0.00875166 43444.1 38.58 21.30 0.00875166 61286.8
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 1617.466 1617.466 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:4 FAN Fan:OnOff 0.422344 0.50833061   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1617.47 1617.47 1.0000 0.50833061 0.422344 20.13 14.77 0.00827413 41234.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1617.47 12.70 0.00915345 12.70 0.04898771 11.5990 21.11 0.00815875 21.11 0.00815898 52.3514 762.64 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6449.029 5026.715 0.324733 -999.0 -999.000 -999.0000 1.00000 1.00000 1021.4888 1004.8586 1.2036 PSZ-AC:5 FAN Fan:OnOff 0.324733 0.39084681   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 Sensible 5695.27 5287.96 0.8831 0.39084681 0.324733 26.38 17.59 0.00895602 49348.3 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 363.736 5331.53 41.57 0.01077970 23.53 0.02906014 8.9489 23.89 0.00877679 23.89 0.00877679 47.5175 3686.46 0.00 6447.92 5021.52 0.37541131 26.67 19.44 0.01118466 55322.4 13.59 13.58 0.00969494 38146.8
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6449.029 6449.029 0.324733 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:5 FAN Fan:OnOff 0.324733 0.39084681   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6449.03 6449.03 1.0000 0.39084681 0.324733 20.36 14.84 0.00825549 41414.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6449.03 12.70 0.00915345 12.70 0.02906014 8.9489 21.11 0.00816724 21.11 0.00816744 52.4049 478.51 0.00 6457.50 6457.50 0.38394042 21.11 15.56 0.00875166 43444.1 37.58 21.01 0.00875166 60263.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 959.502 959.502 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 PSZ-AC:5 FAN Fan:OnOff 0.324733 0.39084681   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 959.50 959.50 1.0000 0.39084681 0.324733 20.36 14.84 0.00825549 41414.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 959.50 12.70 0.00915345 12.70 0.02906014 8.9489 21.11 0.00816724 21.11 0.00816744 52.4049 478.51 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 3693.83 779.17 771.33
PERIMETER_ZN_1 3861.67 1099.33 1030.83
PERIMETER_ZN_2 3057.67 806.33 748.00
PERIMETER_ZN_3 3461.50 825.83 702.67
PERIMETER_ZN_4 3687.33 863.83 778.17
ATTIC 0.00 0.00 0.00
Facility 3939.17 1267.33 1139.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 582.67 0.00 582.50
PERIMETER_ZN_1 0.00 363.17 0.00 329.17
PERIMETER_ZN_2 0.00 118.83 0.00 69.83
PERIMETER_ZN_3 0.00 81.67 0.00 61.17
PERIMETER_ZN_4 0.00 103.33 0.00 42.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 761.33 0.00 629.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.402 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.402 0.388 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.375 0.053 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.401 0.044 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.401 0.049 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 763875.36 0.00 763875.36 0.00 763875.36 2037921.45 5484.00 3276.00 0.00 37.41
PERIMETER_ZN_1 588641.17 0.00 588641.17 657321.52 1245962.68 1544876.42 5483.02 3276.98 0.00 345.85
PERIMETER_ZN_2 307593.10 0.00 307593.10 108188.23 415781.33 916440.58 6235.48 2524.52 0.00 1144.99
PERIMETER_ZN_3 585895.32 0.00 585895.32 162282.34 748177.66 1544876.42 5483.33 3276.68 0.00 267.55
PERIMETER_ZN_4 349630.14 0.00 349630.14 108188.23 457818.37 916440.58 5482.61 3277.39 0.00 393.31
Total Facility 2595635.09 0.00 2595635.09 1035980.32 3631615.41 6960555.45 6237.18 3280.06 0.00 1406.11


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0362 0.0736 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0029 0.0237 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0041 0.0415 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0027 0.0249 0.0291 1008.00 3276.00 0.00
Total Facility 0.1673 0.0000 0.1673 0.0459 0.2132 0.2207 1761.18 3276.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 1106581.07 0.00 1106581.07 2037921.45 5483.14 0.12 3276.74 37.24
PSZ-AC:2 852729.66 0.00 852729.66 1544876.42 5476.62 0.53 3282.84 341.24
PSZ-AC:3 445591.94 0.00 445591.94 916440.58 6068.79 12.24 2678.97 1133.55
PSZ-AC:4 848751.91 0.00 848751.91 1544876.42 5479.33 0.16 3280.52 264.24
PSZ-AC:5 506488.52 0.00 506488.52 916440.58 5476.30 0.63 3283.08 379.54


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0716 0.0000 0.0716 0.0646 1008.00 0.00 3276.00
PSZ-AC:2 0.0543 0.0000 0.0543 0.0490 1008.00 0.00 3276.00
PSZ-AC:3 0.0301 0.0000 0.0301 0.0291 1008.00 0.00 2520.00
PSZ-AC:4 0.0543 0.0000 0.0543 0.0490 1008.00 0.00 3276.00
PSZ-AC:5 0.0322 0.0000 0.0322 0.0291 1008.00 0.00 3276.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3313.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3617.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3653.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3540.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3655.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0936 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0710 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0421 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0710 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0421 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 555
Defaulted Fields 365
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 192.84 1248.68 01-JAN-07:10 20144.52 16-AUG-13:00
Electricity:Building 74.79 677.68 01-JAN-00:10 5841.75 15-MAR-07:10
Electricity:Zone:CORE_ZN 22.88 198.41 01-JAN-00:10 1717.53 02-JAN-08:10
Electricity:SpaceType:GENERAL 74.79 677.68 01-JAN-00:10 5841.75 15-MAR-07:10
InteriorLights:Electricity 26.50 110.04 01-JAN-00:10 2516.44 15-MAR-07:10
InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.50 110.04 01-JAN-00:10 2516.44 15-MAR-07:10
LightsWired:InteriorLights:Electricity 26.50 110.04 01-JAN-00:10 2516.44 15-MAR-07:10
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.50 110.04 01-JAN-00:10 2516.44 15-MAR-07:10
Electricity:Zone:PERIMETER_ZN_1 16.10 150.41 01-JAN-00:10 1293.87 15-MAR-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.38 24.42 01-JAN-00:10 555.83 15-MAR-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.38 24.42 01-JAN-00:10 555.83 15-MAR-07:10
Electricity:Zone:PERIMETER_ZN_2 9.67 89.23 01-JAN-00:10 767.51 15-MAR-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.31 14.49 01-JAN-00:10 329.69 15-MAR-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.31 14.49 01-JAN-00:10 329.69 15-MAR-07:10
Electricity:Zone:PERIMETER_ZN_3 16.47 150.41 01-JAN-00:10 1294.65 15-MAR-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.75 24.42 01-JAN-00:10 556.60 15-MAR-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.75 24.42 01-JAN-00:10 556.60 15-MAR-07:10
Electricity:Zone:PERIMETER_ZN_4 9.68 89.23 01-JAN-00:10 768.20 14-MAR-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.32 14.49 01-JAN-00:10 330.39 14-MAR-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.32 14.49 01-JAN-00:10 330.39 14-MAR-07:10
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
ElectricityPurchased:Plant 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
Cogeneration:ElectricityPurchased 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
General:Cogeneration:ElectricityPurchased 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
ElectricityNet:Plant 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
Cogeneration:ElectricityNet 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
General:Cogeneration:ElectricityNet 192.84 1248.68 04-FEB-09:30 20144.52 16-AUG-13:00
ExteriorLights:Electricity 9.83 0.00 01-JAN-07:10 1061.67 01-JAN-06:10
General:ExteriorLights:Electricity 9.83 0.00 01-JAN-07:10 1061.67 01-JAN-06:10
Electricity:HVAC 85.55 0.00 01-JAN-00:10 12110.03 16-AUG-12:10
Fans:Electricity 23.50 0.00 01-JAN-00:10 1994.57 02-JAN-06:10
General:Fans:Electricity 23.50 0.00 01-JAN-00:10 1994.57 02-JAN-06:10
Cooling:Electricity 62.05 0.00 01-JAN-00:10 10115.46 16-AUG-12:10
General:Cooling:Electricity 62.05 0.00 01-JAN-00:10 10115.46 16-AUG-12:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:Plant 22.66 571.00 01-JAN-00:10 2765.59 11-JAN-12:50
WaterSystems:Electricity 22.66 571.00 01-JAN-00:10 2765.59 11-JAN-12:50
Water Heater:WaterSystems:Electricity 22.66 571.00 01-JAN-00:10 2765.59 11-JAN-12:50
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-07:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 02-JAN-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:NaturalGas 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 21-MAR-11:10
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 21-MAR-11:10
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 17-JAN-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 17-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 424.76 0.00 01-JAN-00:10 66580.50 03-JUL-05:20
EnergyTransfer:Building 167.67 0.00 01-JAN-00:10 28485.89 03-JUL-05:20
EnergyTransfer:Zone:CORE_ZN 37.66 0.00 01-JAN-00:10 5927.71 03-JUL-07:10
Heating:EnergyTransfer 2.25 0.00 01-JAN-00:10 5466.85 21-JUL-17:20
Heating:EnergyTransfer:Zone:CORE_ZN 0.55 0.00 01-JAN-00:10 1538.12 21-JUL-17:10
General:Heating:EnergyTransfer 2.25 0.00 01-JAN-00:10 5466.85 21-JUL-17:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.55 0.00 01-JAN-00:10 1538.12 21-JUL-17:10
Cooling:EnergyTransfer 165.42 0.00 01-JAN-00:10 28485.89 03-JUL-05:20
Cooling:EnergyTransfer:Zone:CORE_ZN 37.11 0.00 01-JAN-00:10 5927.71 03-JUL-07:10
General:Cooling:EnergyTransfer 165.42 0.00 01-JAN-00:10 28485.89 03-JUL-05:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 37.11 0.00 01-JAN-00:10 5927.71 03-JUL-07:10
EnergyTransfer:Zone:PERIMETER_ZN_1 43.93 0.00 01-JAN-00:10 7275.22 02-OCT-11:50
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.50 0.00 01-JAN-00:10 1202.09 21-JUL-17:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.50 0.00 01-JAN-00:10 1202.09 21-JUL-17:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 43.43 0.00 01-JAN-00:10 7275.22 02-OCT-11:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 43.43 0.00 01-JAN-00:10 7275.22 02-OCT-11:50
EnergyTransfer:Zone:PERIMETER_ZN_2 24.49 0.00 01-JAN-00:10 4423.79 03-JUL-05:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.33 0.00 01-JAN-00:10 749.38 21-JUL-17:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.33 0.00 01-JAN-00:10 749.38 21-JUL-17:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 24.16 0.00 01-JAN-00:10 4423.79 03-JUL-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 24.16 0.00 01-JAN-00:10 4423.79 03-JUL-05:20
EnergyTransfer:Zone:PERIMETER_ZN_3 36.67 0.00 01-JAN-00:10 6931.59 03-JUL-05:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.54 0.00 01-JAN-00:10 1235.08 21-JUL-17:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.54 0.00 01-JAN-00:10 1235.08 21-JUL-17:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 36.13 0.00 01-JAN-00:10 6931.59 03-JUL-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 36.13 0.00 01-JAN-00:10 6931.59 03-JUL-05:20
EnergyTransfer:Zone:PERIMETER_ZN_4 24.92 0.00 01-JAN-00:10 4847.25 03-JUL-05:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.33 0.00 01-JAN-00:10 763.10 21-JUL-17:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.33 0.00 01-JAN-00:10 763.10 21-JUL-17:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 24.59 0.00 01-JAN-00:10 4847.25 03-JUL-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 24.59 0.00 01-JAN-00:10 4847.25 03-JUL-05:20
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 13-JAN-07:10 64.86 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 13-JAN-07:10 64.86 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 13-JAN-07:10 64.86 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 13-JAN-07:10 64.86 02-JAN-07:10
EnergyTransfer:HVAC 257.09 0.00 01-JAN-00:10 43019.06 12-SEP-05:10
CoolingCoils:EnergyTransfer 257.09 0.00 01-JAN-00:10 43019.06 12-SEP-05:10
HeatingCoils:EnergyTransfer 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 13-JAN-07:10 64.86 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 13-JAN-07:10 64.86 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 13-JAN-07:10 64.86 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.548 -37.109 0.000 0.000 4.857 8.739 14.140 0.000 0.000 0.000 8.825 0.000 0.000 0.000 0.000 -0.000
PERIMETER_ZN_1 0.000 0.000 0.499 -43.426 0.000 0.000 3.708 5.376 10.719 15.642 0.000 4.058 7.559 0.000 -3.140 0.000 -0.995 -0.000
PERIMETER_ZN_2 0.000 0.000 0.333 -24.159 0.000 0.000 1.608 3.313 6.359 8.236 0.000 0.408 5.733 0.000 -1.606 0.000 -0.225 -0.000
PERIMETER_ZN_3 0.000 0.000 0.537 -36.131 0.000 0.000 3.735 5.746 10.719 8.202 0.000 0.635 9.338 0.000 -2.465 0.000 -0.316 -0.000
PERIMETER_ZN_4 0.000 0.000 0.335 -24.588 0.000 0.000 2.213 3.324 6.359 8.442 0.000 0.407 5.472 0.000 -1.734 0.000 -0.229 -0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 14.065 22.923 0.000 0.000 0.000 -36.988 -0.000
Total Facility 0.000 0.000 2.251 -165.413 0.000 0.000 16.121 26.498 48.296 40.522 0.000 19.573 59.850 0.000 -8.945 0.000 -38.753 -0.001


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 26-APR-05:01 0.00 0.00 0.00 -6687.07 0.00 0.00 49.91 32.22 486.79 0.00 0.00 0.00 6118.14 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 17-JAN-06:02 0.00 0.00 0.00 -8519.59 0.00 0.00 41.50 24.42 369.02 0.00 0.00 0.00 8847.37 0.00 -522.19 0.00 -240.54 0.00
PERIMETER_ZN_2 24-APR-05:01 0.00 0.00 0.00 -5164.45 0.00 0.00 21.42 14.49 218.91 0.00 0.00 0.00 5117.41 0.00 -194.35 0.00 -13.42 0.00
PERIMETER_ZN_3 26-APR-05:01 0.00 0.00 0.00 -8200.92 0.00 0.00 39.75 24.42 369.02 0.00 0.00 0.00 7987.37 0.00 -216.29 0.00 -3.35 0.00
PERIMETER_ZN_4 03-JUL-05:01 0.00 0.00 0.00 -6053.22 0.00 0.00 15.31 14.49 218.91 0.00 0.00 0.00 5900.29 0.00 -94.96 0.00 -0.81 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 26-APR-05:01 0.00 0.00 0.00 -34265.27 0.00 0.00 175.74 110.04 1662.65 0.00 0.00 1507.17 31647.73 0.00 -778.23 0.00 -59.84 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 21-JUL-17:01 0.00 0.00 1652.04 0.00 0.00 0.00 62.06 347.17 194.72 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2255.98
PERIMETER_ZN_1 21-JUL-17:11 0.00 0.00 1339.05 0.00 0.00 0.00 32.60 228.38 147.61 946.40 0.00 381.74 0.00 0.00 -0.00 0.00 0.00 -3075.78
PERIMETER_ZN_2 21-JUL-17:11 0.00 0.00 842.63 0.00 0.00 0.00 20.48 143.35 87.56 535.58 0.00 49.99 0.00 0.00 -0.00 0.00 0.00 -1679.60
PERIMETER_ZN_3 21-JUL-17:11 0.00 0.00 1378.82 0.00 0.00 0.00 35.16 215.50 147.61 896.90 0.00 75.65 0.00 0.00 -0.00 0.00 0.00 -2749.63
PERIMETER_ZN_4 21-JUL-17:11 0.00 0.00 871.98 0.00 0.00 0.00 19.76 113.95 87.56 988.12 0.00 49.23 0.00 0.00 -0.00 0.00 0.00 -2130.61
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 21-JUL-17:11 0.00 0.00 6069.87 0.00 0.00 0.00 157.86 1048.35 665.06 3367.00 0.00 556.61 0.00 0.00 0.00 0.00 -2136.83 -9727.93



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3209 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3209 0.2014 1.0000 Not calculated 0.0646 0.2014    
PSZ-AC:2 0.4322 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4322 0.1134 1.0000 Not calculated 0.0490 0.1134    
PSZ-AC:3 0.2806 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2806 0.1036 1.0000 Not calculated 0.0291 0.1036    
PSZ-AC:4 0.4223 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4223 0.1160 1.0000 Not calculated 0.0490 0.1160    
PSZ-AC:5 0.3247 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3247 0.0895 1.0000 Not calculated 0.0291 0.0895    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3209 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3209 1.0000 1.0000 Not calculated 0.0646 0.2014    
PSZ-AC:2 0.4322 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4322 1.0000 1.0000 Not calculated 0.0490 0.1134    
PSZ-AC:3 0.2806 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2806 1.0000 1.0000 Not calculated 0.0291 0.1036    
PSZ-AC:4 0.4223 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4223 1.0000 1.0000 Not calculated 0.0490 0.1160    
PSZ-AC:5 0.3247 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3247 1.0000 1.0000 Not calculated 0.0291 0.0895    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3209 0.3209 0.3209 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4322 0.4322 0.4322 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2806 0.2806 0.2806 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4223 0.4223 0.4223 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3247 0.3247 0.3247 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3209 0.3209 0.3209 0.3209 0.0646 1.0000
PSZ-AC:2 0.4322 0.4322 0.4322 0.4322 0.0490 1.0000
PSZ-AC:3 0.2806 0.2806 0.2806 0.2806 0.0291 1.0000
PSZ-AC:4 0.4223 0.4223 0.4223 0.4223 0.0490 1.0000
PSZ-AC:5 0.3247 0.3247 0.3247 0.3247 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3209 0.3209 0.3209 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4322 0.4322 0.4322 No 0.0490 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2806 0.2806 0.2806 No 0.0291 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4223 0.4223 0.4223 No 0.0490 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3247 0.3247 0.3247 No 0.0291 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3209 0.3209 0.3209 0.3209 0.0646 1.0000
PSZ-AC:2 0.4322 0.4322 0.4322 0.4322 0.0490 1.0000
PSZ-AC:3 0.2806 0.2806 0.2806 0.2806 0.0291 1.0000
PSZ-AC:4 0.4223 0.4223 0.4223 0.4223 0.0490 1.0000
PSZ-AC:5 0.3247 0.3247 0.3247 0.3247 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Total gross floor area [m2] 511.16


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 629.50
Number of hours not met 629.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 62.05 10115.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.50 2516.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.83 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 23.50 1994.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 22.66 2765.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 192.84
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 48.30 192.84


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 51.84
Space Heating 0.00
Space Cooling 121.40
Fans (All) 45.97
Service Water Heating 44.33
Receptacle Equipment 94.48
Miscellaneous (All) 377.25
Subtotal 377.25


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 13.74
Space Heating 0.00
Space Cooling 32.18
Fans (All) 12.18
Service Water Heating 11.75
Receptacle Equipment 25.04
Miscellaneous 5.10


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2885. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365
HTGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL January 20.55 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 5404.33 3286.83 68.83 0.00 0.00
PERIMETER_ZN_1 4971.33 3144.50 644.17 0.00 0.00
PERIMETER_ZN_2 5198.50 3157.50 404.00 0.00 0.00
PERIMETER_ZN_3 5442.50 2857.83 459.67 0.00 0.00
PERIMETER_ZN_4 5148.67 3249.33 362.00 0.00 0.00
ATTIC 3740.00 1006.33 1372.17 1347.50 1294.00
Min 3740.00 1006.33 68.83 0.00 0.00
Max 5442.50 3286.83 1372.17 1347.50 1294.00
Average 4984.22 2783.72 551.81 224.58 215.67
Sum 29905.33 16702.33 3310.83 1347.50 1294.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13354.83 1.17 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 1.17 0.00 0.00 0.00
Average 9365.81 0.19 0.00 0.00 0.00
Sum 56194.83 1.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 3221.83 5537.83 0.33 0.00 0.00
PERIMETER_ZN_1 3721.50 4745.33 293.17 0.00 0.00
PERIMETER_ZN_2 4277.67 4332.00 150.33 0.00 0.00
PERIMETER_ZN_3 4448.67 4174.83 136.50 0.00 0.00
PERIMETER_ZN_4 4285.17 4367.67 107.17 0.00 0.00
ATTIC 2890.83 2260.17 1165.33 679.50 1764.17
Min 2890.83 2260.17 0.33 0.00 0.00
Max 4448.67 5537.83 1165.33 679.50 1764.17
Average 3807.61 4236.31 308.81 113.25 294.03
Sum 22845.67 25417.83 1852.83 679.50 1764.17


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 15867.00 2025.00 0.00 0.00 0.00
PERIMETER_ZN_1 12433.33 922.67 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13354.00 2.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 15867.00 2025.00 0.00 0.00 0.00
Average 8874.39 491.61 0.00 0.00 0.00
Sum 53246.33 2949.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:32

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.235
February 20.749
March 23.120
April 26.486
May 31.365
June 32.970
July 35.085
August 35.314
September 32.488
October 29.531
November 25.532
December 21.128
   
Annual Sum or Average 27.790
Minimum of Months 19.235
Maximum of Months 35.314



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.202480E+10 6536.21 19-JAN-06:02 12.83 9.70 0.298423E+09 402.36 18-JAN-14:39 12.83 9.70
February 0.200305E+10 6441.04 13-FEB-06:02 13.03 10.83 0.270262E+09 402.36 23-FEB-14:09 28.72 16.49
March 0.259333E+10 6357.50 28-MAR-05:01 25.67 14.74 0.327676E+09 402.37 28-MAR-13:50 31.00 19.51
April 0.261805E+10 6687.59 26-APR-05:01 23.17 12.12 0.285520E+09 402.37 10-APR-13:39 23.17 12.12
May 0.367010E+10 6204.25 08-MAY-05:01 26.00 16.57 0.317996E+09 457.19 30-MAY-13:09 36.58 27.13
June 0.384673E+10 5777.59 16-JUN-05:01 28.17 20.46 0.322895E+09 459.20 12-JUN-13:39 28.17 20.46
July 0.356561E+10 5957.67 03-JUL-07:10 29.67 17.12 0.313093E+09 489.02 17-JUL-13:39 37.43 29.79
August 0.408231E+10 5680.75 07-AUG-05:01 32.82 23.16 0.361690E+09 485.84 21-AUG-14:09 35.93 29.69
September 0.359068E+10 5689.42 05-SEP-05:01 30.17 24.66 0.298607E+09 479.92 11-SEP-12:39 34.80 29.13
October 0.367169E+10 6502.24 20-OCT-05:01 23.17 16.23 0.303341E+09 451.22 10-OCT-07:30 23.17 16.23
November 0.311448E+10 6129.32 20-NOV-06:01 25.85 18.49 0.299971E+09 402.37 14-NOV-14:09 25.85 18.49
December 0.232992E+10 6253.46 13-DEC-06:01 15.02 12.69 0.284750E+09 402.37 18-DEC-13:00 25.00 14.81
                     
Annual Sum or Average 0.371107E+11         0.368422E+10        
Minimum of Months 0.200305E+10 5680.75   12.83 9.70 0.270262E+09 402.36   12.83 9.70
Maximum of Months 0.408231E+10 6687.59   32.82 24.66 0.361690E+09 489.02   37.43 29.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.195515E+10 8519.53 17-JAN-06:02 15.98 11.75 0.225817E+09 305.03 17-JAN-14:09 24.83 17.87
February 0.190850E+10 7515.46 10-FEB-06:02 19.82 12.70 0.204599E+09 305.03 27-FEB-14:39 23.67 16.94
March 0.232360E+10 8254.40 28-MAR-05:01 25.67 14.74 0.248305E+09 305.03 28-MAR-13:50 31.00 19.51
April 0.233044E+10 8350.02 26-APR-05:01 23.17 12.12 0.216577E+09 307.09 28-APR-12:09 41.12 20.13
May 0.392406E+10 8256.70 11-MAY-05:01 28.00 16.07 0.240001E+09 343.03 30-MAY-12:09 36.22 27.34
June 0.444544E+10 7262.57 16-JUN-05:01 28.17 20.46 0.241515E+09 357.69 12-JUN-12:09 28.17 20.46
July 0.479881E+10 8317.77 03-JUL-05:01 28.83 16.82 0.227065E+09 379.79 17-JUL-12:09 38.05 29.50
August 0.559395E+10 7380.71 07-AUG-05:01 32.82 23.16 0.264991E+09 377.79 22-AUG-12:09 41.07 28.76
September 0.476051E+10 7653.82 04-SEP-17:32 38.67 24.37 0.223484E+09 375.95 11-SEP-12:09 34.65 29.27
October 0.490756E+10 8173.56 20-OCT-05:01 23.17 16.23 0.230091E+09 332.68 16-OCT-12:09 23.17 16.23
November 0.397092E+10 8106.90 13-NOV-06:01 20.92 17.72 0.228359E+09 323.80 01-NOV-12:09 20.92 17.72
December 0.250819E+10 8069.39 18-DEC-06:01 13.17 10.39 0.216149E+09 305.04 05-DEC-14:09 13.17 10.39
                     
Annual Sum or Average 0.434271E+11         0.276695E+10        
Minimum of Months 0.190850E+10 7262.57   13.17 10.39 0.204599E+09 305.03   13.17 10.39
Maximum of Months 0.559395E+10 8519.53   38.67 24.37 0.264991E+09 379.79   41.12 29.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.881869E+09 4520.06 17-JAN-06:02 15.98 11.75 98664629.37 190.45 18-JAN-13:09 20.17 12.13
February 0.893562E+09 4768.84 10-FEB-06:02 19.82 12.70 89410889.07 190.45 06-FEB-15:09 19.82 12.70
March 0.121494E+10 5153.89 27-MAR-05:01 21.92 13.45 0.108603E+09 190.45 13-MAR-14:09 21.92 13.45
April 0.139263E+10 5164.65 24-APR-05:01 21.83 13.96 94895943.06 190.45 06-APR-14:09 21.83 13.96
May 0.236400E+10 5102.82 11-MAY-05:01 28.00 16.07 0.105283E+09 190.46 22-MAY-10:09 36.92 22.60
June 0.263902E+10 4568.57 16-JUN-05:01 28.17 20.46 0.105678E+09 190.48 26-JUN-14:09 39.00 26.70
July 0.295998E+10 5159.02 03-JUL-05:01 28.83 16.82 96989671.82 192.93 17-JUL-10:50 37.83 28.12
August 0.349885E+10 4722.34 06-AUG-10:13 38.47 24.31 0.112264E+09 192.01 07-AUG-12:00 36.90 28.77
September 0.276660E+10 4706.45 04-SEP-14:32 41.00 24.55 96406800.54 190.53 05-SEP-10:30 38.30 24.39
October 0.251926E+10 5057.13 20-OCT-05:01 23.17 16.23 0.100611E+09 190.46 10-OCT-10:09 23.17 16.23
November 0.188087E+10 4988.47 13-NOV-06:01 20.92 17.72 99859151.09 190.45 13-NOV-15:09 32.53 19.09
December 0.114810E+10 4958.82 18-DEC-06:01 13.17 10.39 94372004.71 190.45 12-DEC-11:09 13.17 10.39
                     
Annual Sum or Average 0.241597E+11         0.120304E+10        
Minimum of Months 0.881869E+09 4520.06   13.17 10.39 89410889.07 190.45   13.17 10.39
Maximum of Months 0.349885E+10 5164.65   41.00 24.55 0.112264E+09 192.93   39.00 28.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.131356E+10 6901.14 23-JAN-06:01 17.98 16.09 0.225617E+09 305.01 19-JAN-15:09 17.98 16.09
February 0.135070E+10 7404.21 10-FEB-06:02 19.82 12.70 0.204434E+09 305.02 08-FEB-14:30 19.82 12.70
March 0.187132E+10 8086.35 28-MAR-05:01 25.67 14.74 0.248114E+09 305.03 28-MAR-13:00 31.00 19.33
April 0.209374E+10 8201.21 26-APR-05:01 23.17 12.12 0.216501E+09 305.03 17-APR-13:09 23.17 12.12
May 0.348561E+10 8034.27 11-MAY-05:01 28.00 16.07 0.239664E+09 305.03 01-MAY-13:39 28.00 16.07
June 0.396619E+10 7080.70 16-JUN-05:01 28.17 20.46 0.240353E+09 308.68 12-JUN-13:20 28.17 20.46
July 0.444754E+10 8138.85 03-JUL-05:01 28.83 16.82 0.219907E+09 321.37 17-JUL-13:50 37.22 29.85
August 0.522542E+10 7209.17 07-AUG-05:01 32.82 23.16 0.253444E+09 320.98 07-AUG-15:09 39.15 28.53
September 0.409026E+10 7407.56 04-SEP-17:32 38.67 24.37 0.218829E+09 312.26 05-SEP-14:09 39.83 25.07
October 0.370904E+10 7843.29 20-OCT-05:01 23.17 16.23 0.228898E+09 305.04 16-OCT-07:10 23.17 16.23
November 0.281364E+10 7615.16 13-NOV-06:01 20.92 17.72 0.227648E+09 305.03 03-NOV-12:50 20.92 17.72
December 0.176563E+10 7673.76 13-DEC-06:01 15.02 12.69 0.215629E+09 305.03 11-DEC-14:39 15.02 12.69
                     
Annual Sum or Average 0.361326E+11         0.273904E+10        
Minimum of Months 0.131356E+10 6901.14   15.02 12.12 0.204434E+09 305.01   15.02 12.12
Maximum of Months 0.522542E+10 8201.21   38.67 24.37 0.253444E+09 321.37   39.83 29.85



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.926891E+09 5096.22 25-JAN-06:02 17.88 14.29 0.134113E+09 180.94 31-JAN-14:09 23.00 16.33
February 0.943026E+09 5018.28 27-FEB-06:01 17.77 15.99 0.121494E+09 180.94 08-FEB-14:30 17.77 15.99
March 0.128984E+10 5919.77 27-MAR-05:01 21.92 13.45 0.147552E+09 180.95 28-MAR-13:00 31.00 19.33
April 0.140313E+10 5943.25 24-APR-05:01 21.83 13.96 0.128783E+09 180.95 17-APR-14:39 21.83 13.96
May 0.233827E+10 5879.03 11-MAY-05:01 28.00 16.07 0.142589E+09 180.96 15-MAY-14:09 32.00 25.14
June 0.266263E+10 5273.51 16-JUN-05:01 28.17 20.46 0.142990E+09 180.95 13-JUN-12:00 28.17 20.46
July 0.299195E+10 6053.44 03-JUL-05:01 28.83 16.82 0.130368E+09 180.95 28-JUL-13:09 36.92 28.57
August 0.353740E+10 5438.92 07-AUG-05:01 32.82 23.16 0.150089E+09 181.22 10-AUG-15:00 41.60 30.36
September 0.279989E+10 5447.32 04-SEP-14:32 41.00 24.55 0.130069E+09 180.95 08-SEP-12:09 35.33 28.87
October 0.254332E+10 5816.25 20-OCT-05:01 23.17 16.23 0.136147E+09 180.95 10-OCT-07:10 23.17 16.23
November 0.193240E+10 5747.73 13-NOV-06:01 20.92 17.72 0.135315E+09 180.95 15-NOV-14:09 29.00 20.82
December 0.122065E+10 5639.50 13-DEC-06:01 15.02 12.69 0.128125E+09 180.95 11-DEC-13:00 15.02 12.69
                     
Annual Sum or Average 0.245894E+11         0.162763E+10        
Minimum of Months 0.926891E+09 5018.28   15.02 12.69 0.121494E+09 180.94   15.02 12.69
Maximum of Months 0.353740E+10 6053.44   41.00 24.55 0.150089E+09 181.22   41.60 30.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 15.70 12.84 0.00 0.00 01-JAN-00:10 15.70 12.84
February 0.00 0.00 01-FEB-00:10 17.20 14.59 0.00 0.00 01-FEB-00:10 17.20 14.59
March 0.00 0.00 01-MAR-00:10 22.85 18.46 0.00 0.00 01-MAR-00:10 22.85 18.46
April 0.00 0.00 01-APR-00:10 22.05 20.11 0.00 0.00 01-APR-00:10 22.05 20.11
May 0.00 0.00 01-MAY-00:10 26.90 23.56 0.00 0.00 01-MAY-00:10 26.90 23.56
June 0.00 0.00 01-JUN-00:10 32.60 23.24 0.00 0.00 01-JUN-00:10 32.60 23.24
July 0.00 0.00 01-JUL-00:10 31.72 27.02 0.00 0.00 01-JUL-00:10 31.72 27.02
August 0.00 0.00 01-AUG-00:10 33.23 28.28 0.00 0.00 01-AUG-00:10 33.23 28.28
September 0.00 0.00 01-SEP-00:10 31.93 25.04 0.00 0.00 01-SEP-00:10 31.93 25.04
October 0.00 0.00 01-OCT-00:10 28.98 26.77 0.00 0.00 01-OCT-00:10 28.98 26.77
November 0.00 0.00 01-NOV-00:10 27.12 21.17 0.00 0.00 01-NOV-00:10 27.12 21.17
December 0.00 0.00 01-DEC-00:10 21.12 15.63 0.00 0.00 01-DEC-00:10 21.12 15.63
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   15.70 12.84 0.00 0.00   15.70 12.84
Maximum of Months 0.00 0.00   33.23 28.28 0.00 0.00   33.23 28.28



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1882057.83 239.15 23-JAN-18:03 23.75
February 6248823.44 492.08 07-FEB-18:03 26.97
March 24529687.13 1030.68 27-MAR-17:02 33.85
April 38805572.08 1056.03 28-APR-17:02 34.05
May 69323602.41 1327.76 30-MAY-17:01 38.33
June 78824949.10 1586.58 09-JUN-17:01 40.83
July 78645970.65 1651.97 21-JUL-17:01 42.00
August 88338450.35 1583.29 16-AUG-17:01 41.00
September 64524097.57 1262.05 13-SEP-17:01 36.83
October 56149621.10 1182.26 05-OCT-17:02 35.83
November 31912158.46 887.51 01-NOV-17:02 31.83
December 8632208.20 412.11 06-DEC-18:03 25.87
         
Annual Sum or Average 0.547817E+09      
Minimum of Months 1882057.83 239.15   23.75
Maximum of Months 88338450.35 1651.97   42.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 12625649.87 362.48 18-JAN-06:03 17.83
February 16509871.45 543.58 07-FEB-18:23 26.90
March 35276615.72 882.29 27-MAR-17:22 33.55
April 40571048.40 933.51 28-APR-17:23 34.15
May 61938895.15 1136.93 31-MAY-17:23 38.50
June 68103526.87 1294.38 09-JUN-17:11 40.67
July 58295328.03 1339.03 21-JUL-17:11 42.00
August 56165885.74 1234.58 16-AUG-17:23 41.00
September 52258299.32 1033.13 06-SEP-17:11 36.67
October 49132339.13 1022.62 05-OCT-17:11 35.67
November 31766771.20 764.82 01-NOV-17:23 31.50
December 16098321.90 491.22 11-DEC-18:25 25.75
         
Annual Sum or Average 0.498743E+09      
Minimum of Months 12625649.87 362.48   17.83
Maximum of Months 68103526.87 1339.03   42.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 9409175.36 231.97 25-JAN-06:03 17.88
February 11013286.87 367.56 09-FEB-06:05 22.92
March 21154952.58 558.08 27-MAR-17:22 33.55
April 25151570.50 581.60 28-APR-17:23 34.15
May 38367842.96 712.19 31-MAY-17:23 38.50
June 42342290.60 807.46 09-JUN-17:11 40.67
July 40476591.26 842.62 21-JUL-17:11 42.00
August 45003135.13 790.18 16-AUG-17:23 41.00
September 34886715.16 671.14 06-SEP-17:11 36.67
October 31789903.17 640.87 05-OCT-17:11 35.67
November 21565055.82 491.54 01-NOV-17:23 31.50
December 11808597.43 350.43 12-DEC-06:05 23.03
         
Annual Sum or Average 0.332969E+09      
Minimum of Months 9409175.36 231.97   17.88
Maximum of Months 45003135.13 842.62   42.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 13432776.34 337.40 23-JAN-18:35 23.00
February 16380784.07 552.99 07-FEB-18:23 26.90
March 32780765.44 895.95 27-MAR-17:22 33.55
April 40214829.05 934.06 27-APR-17:12 33.67
May 62116901.44 1147.78 31-MAY-17:23 38.50
June 68514711.22 1316.34 09-JUN-17:11 40.67
July 67048659.42 1378.80 21-JUL-17:11 42.00
August 75728164.01 1285.49 16-AUG-17:23 41.00
September 57080408.51 1090.45 06-SEP-17:11 36.67
October 51452865.88 1039.40 05-OCT-17:11 35.67
November 34386912.32 781.91 01-NOV-17:23 31.50
December 17687460.96 514.56 12-DEC-06:05 23.03
         
Annual Sum or Average 0.536825E+09      
Minimum of Months 13432776.34 337.40   23.00
Maximum of Months 75728164.01 1378.80   42.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 11716540.13 353.28 30-JAN-06:04 20.03
February 13094597.09 414.46 08-FEB-06:04 21.85
March 22734054.26 593.35 27-MAR-17:22 33.55
April 26574473.88 617.04 28-APR-17:23 34.15
May 38895878.78 742.50 31-MAY-17:23 38.50
June 42020768.86 831.63 09-JUN-17:11 40.67
July 36757709.13 871.97 21-JUL-17:11 42.00
August 37471058.40 825.94 16-AUG-17:23 41.00
September 34637155.69 700.59 06-SEP-17:11 36.67
October 33285466.59 672.00 05-OCT-17:11 35.67
November 23463237.47 537.35 01-NOV-17:23 31.50
December 13916537.52 370.93 27-DEC-06:04 20.98
         
Annual Sum or Average 0.334567E+09      
Minimum of Months 11716540.13 353.28   20.03
Maximum of Months 42020768.86 871.97   42.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 15.70
February 0.00 0.00 01-FEB-00:10 17.20
March 0.00 0.00 01-MAR-00:10 22.85
April 0.00 0.00 01-APR-00:10 22.05
May 0.00 0.00 01-MAY-00:10 26.90
June 0.00 0.00 01-JUN-00:10 32.60
July 0.00 0.00 01-JUL-00:10 31.72
August 0.00 0.00 01-AUG-00:10 33.23
September 0.00 0.00 01-SEP-00:10 31.93
October 0.00 0.00 01-OCT-00:10 28.98
November 0.00 0.00 01-NOV-00:10 27.12
December 0.00 0.00 01-DEC-00:10 21.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   15.70
Maximum of Months 0.00 0.00   33.23



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.729889E+09 743.94 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.660244E+09 743.94 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.791184E+09 743.94 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.696458E+09 743.94 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.760537E+09 743.94 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.757753E+09 743.94 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.699242E+09 743.94 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.791184E+09 743.94 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.696458E+09 743.94 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.729889E+09 743.94 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.727106E+09 743.94 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.699242E+09 743.94 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.873919E+10     0.141401E+11    
Minimum of Months 0.660244E+09 743.94   0.107295E+10 973.59  
Maximum of Months 0.791184E+09 743.94   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.450155E+09 534.18 23-JAN-16:00 0.899552E+09 738.04 02-JAN-08:09
February 0.406862E+09 541.76 09-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.489196E+09 555.83 15-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.429847E+09 543.47 18-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.467800E+09 504.90 23-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.465257E+09 510.32 08-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.431797E+09 535.82 20-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.482998E+09 510.81 29-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.426948E+09 519.44 06-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.444538E+09 488.84 27-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.446874E+09 534.41 29-NOV-16:00 0.888667E+09 738.04 01-NOV-07:10
December 0.433774E+09 547.34 15-DEC-08:09 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.537605E+10     0.107191E+11    
Minimum of Months 0.406862E+09 488.84   0.813362E+09 738.04  
Maximum of Months 0.489196E+09 555.83   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.281934E+09 324.13 04-JAN-16:00 0.533626E+09 437.82 02-JAN-08:09
February 0.253018E+09 324.97 09-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.300768E+09 329.69 15-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.263466E+09 321.11 18-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.285259E+09 295.78 25-MAY-15:00 0.549505E+09 437.82 01-MAY-07:10
June 0.282699E+09 294.20 15-JUN-15:00 0.542644E+09 437.82 01-JUN-07:10
July 0.261884E+09 313.86 20-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.294516E+09 291.70 18-AUG-15:00 0.565383E+09 437.82 01-AUG-07:10
September 0.261373E+09 298.34 26-SEP-15:00 0.510887E+09 437.82 01-SEP-07:10
October 0.276352E+09 307.07 27-OCT-15:00 0.534030E+09 437.82 02-OCT-07:10
November 0.279311E+09 327.80 29-NOV-16:00 0.527169E+09 437.82 01-NOV-07:10
December 0.272094E+09 328.57 14-DEC-16:00 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.331267E+10     0.635872E+10    
Minimum of Months 0.253018E+09 291.70   0.482497E+09 437.82  
Maximum of Months 0.300768E+09 329.69   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.508573E+09 543.82 23-JAN-16:00 0.899552E+09 738.04 02-JAN-08:09
February 0.452342E+09 546.30 09-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.530543E+09 556.60 15-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.452072E+09 544.73 18-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.472289E+09 498.31 23-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.463290E+09 499.59 08-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.432550E+09 534.12 20-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.495399E+09 518.37 29-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.454244E+09 525.30 06-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.493002E+09 537.21 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.501979E+09 550.64 29-NOV-16:00 0.888667E+09 738.04 01-NOV-07:10
December 0.489646E+09 552.98 15-DEC-16:00 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.574593E+10     0.107191E+11    
Minimum of Months 0.432550E+09 498.31   0.813362E+09 738.04  
Maximum of Months 0.530543E+09 556.60   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.281681E+09 322.82 09-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.252424E+09 321.07 09-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.301131E+09 330.39 14-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.264974E+09 324.65 18-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.287880E+09 311.44 23-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.284971E+09 312.17 08-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.264502E+09 321.12 20-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.297768E+09 316.83 29-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.263345E+09 318.42 06-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.277493E+09 321.20 31-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.277650E+09 321.32 03-NOV-07:10 0.527169E+09 437.82 01-NOV-07:10
December 0.270613E+09 327.01 15-DEC-08:09 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.332443E+10     0.635872E+10    
Minimum of Months 0.252424E+09 311.44   0.482497E+09 437.82  
Maximum of Months 0.301131E+09 330.39   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.729889E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.696458E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.760537E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.757753E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.699242E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.696458E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.729889E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.727106E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.699242E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.873919E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.450155E+09 0.899552E+09 0.00 0.00 0.00 0.00 3389959.47 0.297279E+09
February 0.488155E+09 0.406862E+09 0.813362E+09 0.00 0.00 0.00 0.00 36741749.48 0.210333E+09
March 0.590925E+09 0.489196E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.127913E+09 0.135466E+09
April 0.513848E+09 0.429847E+09 0.862580E+09 0.00 0.00 0.00 0.00 0.240143E+09 53669531.01
May 0.565233E+09 0.467800E+09 0.926320E+09 0.00 0.00 0.00 0.00 0.523494E+09 8694669.58
June 0.565233E+09 0.465257E+09 0.914754E+09 0.00 0.00 0.00 0.00 0.622451E+09 1490171.02
July 0.513848E+09 0.431797E+09 0.873466E+09 0.00 0.00 0.00 0.00 0.660444E+09 32988.24
August 0.590925E+09 0.482998E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.737972E+09 5864.36
September 0.513848E+09 0.426948E+09 0.861220E+09 0.00 0.00 0.00 0.00 0.520363E+09 2401746.84
October 0.539540E+09 0.444538E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.371508E+09 13100093.45
November 0.539540E+09 0.446874E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.185334E+09 74664956.90
December 0.513848E+09 0.433774E+09 0.872785E+09 0.00 0.00 0.00 0.00 28343306.53 0.197430E+09
                   
Annual Sum or Average 0.647448E+10 0.537605E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.405810E+10 0.994569E+09
Minimum of Months 0.488155E+09 0.406862E+09 0.813362E+09 0.00 0.00 0.00 0.00 3389959.47 5864.36
Maximum of Months 0.590925E+09 0.489196E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.737972E+09 0.297279E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.281934E+09 0.533626E+09 0.00 0.00 0.00 0.00 135089.07 54356471.57
February 0.211974E+09 0.253018E+09 0.482497E+09 0.00 0.00 0.00 0.00 2944897.04 51798324.67
March 0.256600E+09 0.300768E+09 0.565383E+09 0.00 0.00 0.00 0.00 8699058.77 29084049.13
April 0.223130E+09 0.263466E+09 0.511694E+09 0.00 0.00 0.00 0.00 18027417.83 13971646.03
May 0.245443E+09 0.285259E+09 0.549505E+09 0.00 0.00 0.00 0.00 48596898.31 2973945.01
June 0.245443E+09 0.282699E+09 0.542644E+09 0.00 0.00 0.00 0.00 62792083.96 1055185.52
July 0.223130E+09 0.261884E+09 0.518151E+09 0.00 0.00 0.00 0.00 86824838.71 15137.75
August 0.256600E+09 0.294516E+09 0.565383E+09 0.00 0.00 0.00 0.00 85656985.62 7311.70
September 0.223130E+09 0.261373E+09 0.510887E+09 0.00 0.00 0.00 0.00 54569700.68 1447048.46
October 0.234287E+09 0.276352E+09 0.534030E+09 0.00 0.00 0.00 0.00 28714540.77 6986323.55
November 0.234287E+09 0.279311E+09 0.527169E+09 0.00 0.00 0.00 0.00 9837990.13 20371543.65
December 0.223130E+09 0.272094E+09 0.517747E+09 0.00 0.00 0.00 0.00 1324193.02 43251807.01
                   
Annual Sum or Average 0.281144E+10 0.331267E+10 0.635872E+10 0.00 0.00 0.00 0.00 0.408124E+09 0.225319E+09
Minimum of Months 0.211974E+09 0.253018E+09 0.482497E+09 0.00 0.00 0.00 0.00 135089.07 7311.70
Maximum of Months 0.256600E+09 0.300768E+09 0.565383E+09 0.00 0.00 0.00 0.00 86824838.71 54356471.57



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.508573E+09 0.899552E+09 0.00 0.00 0.00 0.00 390940.47 76642099.25
February 0.488155E+09 0.452342E+09 0.813362E+09 0.00 0.00 0.00 0.00 5236157.23 73886224.65
March 0.590925E+09 0.530543E+09 0.953087E+09 0.00 0.00 0.00 0.00 14156481.78 41240686.66
April 0.513848E+09 0.452072E+09 0.862580E+09 0.00 0.00 0.00 0.00 30361870.95 19470683.96
May 0.565233E+09 0.472289E+09 0.926320E+09 0.00 0.00 0.00 0.00 75641117.24 3972781.57
June 0.565233E+09 0.463290E+09 0.914754E+09 0.00 0.00 0.00 0.00 96267745.01 1366371.18
July 0.513848E+09 0.432550E+09 0.873466E+09 0.00 0.00 0.00 0.00 0.132456E+09 31034.38
August 0.590925E+09 0.495399E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.131407E+09 3707.55
September 0.513848E+09 0.454244E+09 0.861220E+09 0.00 0.00 0.00 0.00 84378416.89 1762926.99
October 0.539540E+09 0.493002E+09 0.900233E+09 0.00 0.00 0.00 0.00 45319505.26 9108105.85
November 0.539540E+09 0.501979E+09 0.888667E+09 0.00 0.00 0.00 0.00 17085112.50 27321175.27
December 0.513848E+09 0.489646E+09 0.872785E+09 0.00 0.00 0.00 0.00 2438462.58 61258990.39
                   
Annual Sum or Average 0.647448E+10 0.574593E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.635139E+09 0.316065E+09
Minimum of Months 0.488155E+09 0.432550E+09 0.813362E+09 0.00 0.00 0.00 0.00 390940.47 3707.55
Maximum of Months 0.590925E+09 0.530543E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.132456E+09 76642099.25



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.281681E+09 0.533626E+09 0.00 0.00 0.00 0.00 208629.45 54375426.16
February 0.289580E+09 0.252424E+09 0.482497E+09 0.00 0.00 0.00 0.00 3189002.13 52289171.59
March 0.350544E+09 0.301131E+09 0.565383E+09 0.00 0.00 0.00 0.00 8803165.81 30400761.26
April 0.304821E+09 0.264974E+09 0.511694E+09 0.00 0.00 0.00 0.00 18281553.12 14763187.22
May 0.335303E+09 0.287880E+09 0.549505E+09 0.00 0.00 0.00 0.00 48246167.74 3040510.55
June 0.335303E+09 0.284971E+09 0.542644E+09 0.00 0.00 0.00 0.00 61869206.31 1123587.61
July 0.304821E+09 0.264502E+09 0.518151E+09 0.00 0.00 0.00 0.00 86447388.57 13904.47
August 0.350544E+09 0.297768E+09 0.565383E+09 0.00 0.00 0.00 0.00 85431512.65 7727.90
September 0.304821E+09 0.263345E+09 0.510887E+09 0.00 0.00 0.00 0.00 54165964.81 1472681.00
October 0.320062E+09 0.277493E+09 0.534030E+09 0.00 0.00 0.00 0.00 28513818.68 7058613.61
November 0.320062E+09 0.277650E+09 0.527169E+09 0.00 0.00 0.00 0.00 10140176.90 20749081.26
December 0.304821E+09 0.270613E+09 0.517747E+09 0.00 0.00 0.00 0.00 1515088.50 43591604.53
                   
Annual Sum or Average 0.384075E+10 0.332443E+10 0.635872E+10 0.00 0.00 0.00 0.00 0.406812E+09 0.228886E+09
Minimum of Months 0.289580E+09 0.252424E+09 0.482497E+09 0.00 0.00 0.00 0.00 208629.45 7727.90
Maximum of Months 0.350544E+09 0.301131E+09 0.565383E+09 0.00 0.00 0.00 0.00 86447388.57 54375426.16



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122692E+10 0.230988E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.978253E+09 0.248544E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118961E+10 0.319222E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.114794E+10 0.350752E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.111451E+10 0.387117E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108475E+10 0.376315E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.106331E+10 0.383638E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109179E+10 0.362405E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.118362E+10 0.319522E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.136220E+10 0.283382E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.137809E+10 0.227547E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.124365E+10 0.209354E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.140646E+11 0.369878E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.978253E+09 0.209354E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.137809E+10 0.387117E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 743.94 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 743.94 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 743.94 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 743.94 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 743.94 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 743.94 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 743.94 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 743.94 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 743.94 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 743.94 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 743.94 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 743.94 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 534.18 23-JAN-16:00 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 555.16 23-JAN-13:00 1885.99 19-JAN-07:05
February 732.70 01-FEB-08:09 541.76 09-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 1111.76 07-FEB-12:55 1683.44 01-FEB-07:05
March 732.70 01-MAR-08:09 555.83 15-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 2144.40 27-MAR-11:02 1423.30 07-MAR-07:05
April 732.70 03-APR-07:10 543.47 18-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 2666.74 28-APR-11:55 1091.45 05-APR-06:10
May 732.70 01-MAY-07:10 504.90 23-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 2531.12 09-MAY-11:55 535.98 01-MAY-06:10
June 732.70 01-JUN-07:10 510.32 08-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 2610.57 12-JUN-11:02 95.79 07-JUN-05:01
July 732.70 03-JUL-07:10 535.82 20-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 3027.73 21-JUL-11:02 11.11 03-JUL-05:01
August 732.70 01-AUG-07:10 510.81 29-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 2981.30 16-AUG-11:53 3.51 27-AUG-06:00
September 732.70 01-SEP-07:10 519.44 06-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 2452.62 26-SEP-11:53 174.71 25-SEP-05:01
October 732.70 02-OCT-07:10 488.84 27-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 2053.17 04-OCT-11:55 308.58 30-OCT-06:10
November 732.70 01-NOV-07:10 534.41 29-NOV-16:00 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 1261.89 01-NOV-16:03 1104.77 22-NOV-07:10
December 732.70 01-DEC-08:09 547.34 15-DEC-08:09 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 674.15 01-DEC-13:00 1600.37 26-DEC-07:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   488.84   738.04   0.00 0.00 0.00 0.00 555.16   3.51  
Maximum of Months 732.70   555.83   738.04   0.00 0.00 0.00 0.00 3027.73   1885.99  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 324.13 04-JAN-16:00 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 10.95 23-JAN-13:10 119.18 18-JAN-04:00
February 434.65 01-FEB-08:09 324.97 09-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 63.64 05-FEB-14:55 106.09 10-FEB-19:03
March 434.65 01-MAR-08:09 329.69 15-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 71.57 02-MAR-06:10 79.02 06-MAR-07:00
April 434.65 03-APR-07:10 321.11 18-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 106.81 28-APR-18:10 62.48 05-APR-01:00
May 434.65 01-MAY-07:10 295.78 25-MAY-15:00 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 439.83 21-MAY-12:53 30.15 15-MAY-03:00
June 434.65 01-JUN-07:10 294.20 15-JUN-15:00 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 137.88 09-JUN-18:10 25.06 07-JUN-05:00
July 434.65 03-JUL-07:10 313.86 20-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 186.72 30-JUL-14:20 3.97 03-JUL-04:40
August 434.65 01-AUG-07:10 291.70 18-AUG-15:00 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 167.92 13-AUG-14:00 3.38 27-AUG-06:00
September 434.65 01-SEP-07:10 298.34 26-SEP-15:00 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 127.84 04-SEP-14:00 28.75 25-SEP-05:00
October 434.65 02-OCT-07:10 307.07 27-OCT-15:00 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 109.08 19-OCT-18:10 45.11 20-OCT-05:00
November 434.65 01-NOV-07:10 327.80 29-NOV-16:00 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 38.54 05-NOV-14:10 58.67 13-NOV-04:00
December 434.65 01-DEC-08:09 328.57 14-DEC-16:00 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 22.33 10-DEC-11:55 82.03 16-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   291.70   437.82   0.00 0.00 0.00 0.00 10.95   3.38  
Maximum of Months 434.65   329.69   437.82   0.00 0.00 0.00 0.00 439.83   119.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 543.82 23-JAN-16:00 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 24.68 29-JAN-11:55 172.82 18-JAN-04:00
February 732.70 01-FEB-08:09 546.30 09-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 112.38 05-FEB-14:55 154.43 10-FEB-19:03
March 732.70 01-MAR-08:09 556.60 15-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 107.37 02-MAR-06:10 118.53 06-MAR-07:00
April 732.70 03-APR-07:10 544.73 18-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 165.41 28-APR-18:10 92.59 05-APR-01:00
May 732.70 01-MAY-07:10 498.31 23-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 669.80 21-MAY-12:53 43.24 15-MAY-03:00
June 732.70 01-JUN-07:10 499.59 08-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 208.81 09-JUN-18:10 36.62 07-JUN-05:00
July 732.70 03-JUL-07:10 534.12 20-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 281.00 30-JUL-14:25 5.60 03-JUL-04:10
August 732.70 01-AUG-07:10 518.37 29-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 251.89 13-AUG-13:53 2.91 27-AUG-06:00
September 732.70 01-SEP-07:10 525.30 06-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 197.19 04-SEP-16:55 41.65 25-SEP-05:00
October 732.70 02-OCT-07:10 537.21 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 170.03 19-OCT-18:10 64.91 20-OCT-05:00
November 732.70 01-NOV-07:10 550.64 29-NOV-16:00 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 70.15 19-NOV-13:55 86.24 22-NOV-06:00
December 732.70 01-DEC-08:09 552.98 15-DEC-16:00 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 40.06 10-DEC-11:55 122.84 16-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   498.31   738.04   0.00 0.00 0.00 0.00 24.68   2.91  
Maximum of Months 732.70   556.60   738.04   0.00 0.00 0.00 0.00 669.80   172.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 322.82 09-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 12.01 29-JAN-11:55 119.08 18-JAN-04:00
February 434.65 01-FEB-08:09 321.07 09-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 65.15 05-FEB-14:25 111.96 10-FEB-19:03
March 434.65 01-MAR-08:09 330.39 14-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 71.57 02-MAR-06:10 80.52 17-MAR-21:00
April 434.65 03-APR-07:10 324.65 18-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 97.84 28-APR-18:10 64.06 05-APR-01:00
May 434.65 01-MAY-07:10 311.44 23-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 443.61 21-MAY-12:53 30.36 15-MAY-03:00
June 434.65 01-JUN-07:10 312.17 08-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 130.72 09-JUN-18:10 25.77 07-JUN-05:00
July 434.65 03-JUL-07:10 321.12 20-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 189.70 30-JUL-13:57 3.95 03-JUL-04:10
August 434.65 01-AUG-07:10 316.83 29-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 167.92 13-AUG-14:00 3.57 27-AUG-06:00
September 434.65 01-SEP-07:10 318.42 06-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 127.84 04-SEP-14:00 28.78 25-SEP-05:00
October 434.65 02-OCT-07:10 321.20 31-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 100.40 19-OCT-18:10 46.02 20-OCT-05:00
November 434.65 01-NOV-07:10 321.32 03-NOV-07:10 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 38.60 05-NOV-14:10 59.23 13-NOV-04:00
December 434.65 01-DEC-08:09 327.01 15-DEC-08:09 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 25.14 10-DEC-11:55 81.58 16-DEC-07:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   311.44   437.82   0.00 0.00 0.00 0.00 12.01   3.57  
Maximum of Months 434.65   330.39   437.82   0.00 0.00 0.00 0.00 443.61   119.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1462.18 03-JAN-07:15 4471.43 31-JAN-13:40
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2361.53 15-FEB-07:52 4762.96 22-FEB-13:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2015.18 27-MAR-06:53 5379.24 30-MAR-13:30
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1698.48 26-APR-06:00 5578.86 30-APR-13:23
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2140.67 28-MAY-03:53 5422.25 03-MAY-13:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1408.34 05-JUN-06:42 5582.53 27-JUN-12:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1485.66 04-JUL-04:20 5606.87 20-JUL-14:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1285.02 01-AUG-24:00 5368.26 04-AUG-13:52
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2227.35 30-SEP-07:51 4895.49 17-SEP-13:43
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2110.32 29-OCT-04:55 4481.75 04-OCT-13:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1504.81 17-NOV-01:00 4044.41 07-NOV-13:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1470.45 30-DEC-07:20 4234.34 25-DEC-13:30
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1285.02   4044.41  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2361.53   5606.87  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 6536.21 19-JAN-06:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
February 6441.04 13-FEB-06:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
March 6357.50 28-MAR-05:01 850.55 257.74 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
April 6687.59 26-APR-05:01 850.55 257.74 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
May 6204.25 08-MAY-05:01 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
June 5777.59 16-JUN-05:01 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
July 5957.67 03-JUL-07:10 2899.62 2231.82 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
August 5680.75 07-AUG-05:01 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
September 5689.42 05-SEP-05:01 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
October 6502.24 20-OCT-05:01 956.87 289.96 4381.15 0.00 0.00 0.00 0.00 0.00 0.00
November 6129.32 20-NOV-06:01 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
December 6253.46 13-DEC-06:01 744.23 225.53 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5680.75   531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6687.59   2899.62 2231.82 4867.94 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8519.53 17-JAN-06:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 240.54
February 7515.46 10-FEB-06:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 195.81
March 8254.40 28-MAR-05:01 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 8.64
April 8350.02 26-APR-05:01 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 51.87
May 8256.70 11-MAY-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 29.65 0.00
June 7262.57 16-JUN-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 26.21 0.00
July 8317.77 03-JUL-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 11.11
August 7380.71 07-AUG-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 106.22 0.00
September 7653.82 04-SEP-17:32 0.00 122.12 629.93 0.00 0.00 0.00 0.00 150.30 0.00
October 8173.56 20-OCT-05:01 725.37 219.81 3321.19 0.00 0.00 0.00 0.00 0.00 130.71
November 8106.90 13-NOV-06:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 205.26
December 8069.39 18-DEC-06:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 337.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 7262.57   0.00 122.12 629.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8519.53   805.97 244.23 3690.21 0.00 0.00 0.00 0.00 150.30 337.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4520.06 17-JAN-06:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 27.19
February 4768.84 10-FEB-06:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 62.82
March 5153.89 27-MAR-05:01 382.49 115.91 1751.27 0.00 0.00 0.00 0.00 0.00 7.62
April 5164.65 24-APR-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 13.42
May 5102.82 11-MAY-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 1.36 0.00
June 4568.57 16-JUN-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 1.05 0.00
July 5159.02 03-JUL-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.53 0.00
August 4722.34 06-AUG-10:13 0.00 57.95 298.95 0.00 0.00 0.00 0.00 56.22 0.00
September 4706.45 04-SEP-14:32 0.00 57.95 298.95 0.00 0.00 0.00 0.00 113.53 0.00
October 5057.13 20-OCT-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 33.45
November 4988.47 13-NOV-06:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 28.83
December 4958.82 18-DEC-06:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 44.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4520.06   0.00 57.95 298.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5164.65   478.11 144.88 2189.08 0.00 0.00 0.00 0.00 113.53 62.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6901.14 23-JAN-06:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 40.92
February 7404.21 10-FEB-06:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 96.09
March 8086.35 28-MAR-05:01 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 0.04
April 8201.21 26-APR-05:01 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 3.35
May 8034.27 11-MAY-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 2.25 0.00
June 7080.70 16-JUN-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 1.70 0.00
July 8138.85 03-JUL-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 2.34
August 7209.17 07-AUG-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 23.23 0.00
September 7407.56 04-SEP-17:32 0.00 122.12 629.93 0.00 0.00 0.00 0.00 152.65 0.00
October 7843.29 20-OCT-05:01 725.37 219.81 3321.19 0.00 0.00 0.00 0.00 0.00 48.43
November 7615.16 13-NOV-06:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 40.86
December 7673.76 13-DEC-06:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 68.47
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6901.14   0.00 122.12 629.93 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8201.21   805.97 244.23 3690.21 0.00 0.00 0.00 0.00 152.65 96.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5096.22 25-JAN-06:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 51.39
February 5018.28 27-FEB-06:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 33.54
March 5919.77 27-MAR-05:01 382.49 115.91 1751.27 0.00 0.00 0.00 0.00 0.00 7.54
April 5943.25 24-APR-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 13.42
May 5879.03 11-MAY-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 1.41 0.00
June 5273.51 16-JUN-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 1.00 0.00
July 6053.44 03-JUL-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 0.81
August 5438.92 07-AUG-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 14.43 0.00
September 5447.32 04-SEP-14:32 0.00 57.95 298.95 0.00 0.00 0.00 0.00 114.10 0.00
October 5816.25 20-OCT-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 33.23
November 5747.73 13-NOV-06:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 28.69
December 5639.50 13-DEC-06:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 45.33
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5018.28   0.00 57.95 298.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6053.44   478.11 144.88 2189.08 0.00 0.00 0.00 0.00 114.10 51.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 968.81 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1082.05 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1052.03 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 934.57 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 854.57 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 905.89 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1081.71 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 663.59 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1017.42 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 990.06 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 853.74 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1009.23 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 663.59 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1082.05 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.132679E+11 14393.48 30-JAN-13:09 0.00 0.00 01-JAN-00:10
February 0.122992E+11 15398.63 07-FEB-13:39 0.00 0.00 01-FEB-00:10
March 0.147448E+11 16468.58 27-MAR-12:39 0.00 0.00 01-MAR-00:10
April 0.139739E+11 16772.55 28-APR-12:39 0.00 0.00 01-APR-00:10
May 0.170774E+11 19197.66 30-MAY-14:50 0.00 0.00 01-MAY-00:10
June 0.180360E+11 19898.40 12-JUN-12:30 0.00 0.00 01-JUN-00:10
July 0.184210E+11 19829.00 31-JUL-12:50 0.00 0.00 01-JUL-00:10
August 0.207971E+11 20144.52 16-AUG-12:00 0.00 0.00 01-AUG-00:10
September 0.176650E+11 19775.22 05-SEP-12:20 0.00 0.00 01-SEP-00:10
October 0.172637E+11 18331.03 02-OCT-12:50 0.00 0.00 01-OCT-00:10
November 0.156196E+11 17497.18 01-NOV-12:50 0.00 0.00 01-NOV-00:10
December 0.136707E+11 15709.96 04-DEC-13:50 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.192836E+12     0.00    
Minimum of Months 0.122992E+11 14393.48   0.00 0.00  
Maximum of Months 0.207971E+11 20144.52   0.00 0.00  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.225223E+10 0.982320E+09 0.405300E+10 0.00 0.190233E+10 0.01 0.00 0.209189E+10 0.00 0.00 0.00 0.198617E+10 0.00
February 0.202489E+10 0.830872E+09 0.366466E+10 0.00 0.172338E+10 0.00 0.00 0.227030E+10 0.00 0.00 0.00 0.178506E+10 0.00
March 0.241282E+10 0.847464E+09 0.429420E+10 0.00 0.208867E+10 0.00 0.00 0.312047E+10 0.00 0.00 0.00 0.198116E+10 0.00
April 0.210682E+10 0.746291E+09 0.388642E+10 0.00 0.182303E+10 0.00 0.00 0.355921E+10 0.00 0.00 0.00 0.185216E+10 0.00
May 0.227376E+10 0.710601E+09 0.417360E+10 0.00 0.203498E+10 0.00 0.00 0.598629E+10 0.00 0.00 0.00 0.189816E+10 0.00
June 0.225397E+10 0.664435E+09 0.412149E+10 0.00 0.205851E+10 0.00 0.00 0.711756E+10 0.00 0.00 0.00 0.182008E+10 0.00
July 0.208998E+10 0.698686E+09 0.393546E+10 0.00 0.196250E+10 0.00 0.00 0.789222E+10 0.00 0.00 0.00 0.184216E+10 0.00
August 0.236186E+10 0.748066E+09 0.429420E+10 0.00 0.224738E+10 0.00 0.00 0.926066E+10 0.00 0.00 0.00 0.188492E+10 0.00
September 0.210237E+10 0.782814E+09 0.388029E+10 0.00 0.193538E+10 0.00 0.00 0.713960E+10 0.00 0.00 0.00 0.182457E+10 0.00
October 0.222127E+10 0.884859E+09 0.405607E+10 0.00 0.197796E+10 0.00 0.00 0.620127E+10 0.00 0.00 0.00 0.192227E+10 0.00
November 0.223292E+10 0.930988E+09 0.400396E+10 0.00 0.192449E+10 0.00 0.00 0.462611E+10 0.00 0.00 0.00 0.190111E+10 0.00
December 0.216537E+10 0.100462E+10 0.393240E+10 0.00 0.181690E+10 0.00 0.00 0.278891E+10 0.00 0.00 0.00 0.196250E+10 0.00
                           
Annual Sum or Average 0.264983E+11 0.983201E+10 0.482958E+11 0.00 0.234955E+11 0.01 0.00 0.620545E+11 0.00 0.00 0.00 0.226603E+11 0.00
Minimum of Months 0.202489E+10 0.664435E+09 0.366466E+10 0.00 0.172338E+10 0.00 0.00 0.209189E+10 0.00 0.00 0.00 0.178506E+10 0.00
Maximum of Months 0.241282E+10 0.100462E+10 0.429420E+10 0.00 0.224738E+10 0.01 0.00 0.926066E+10 0.00 0.00 0.00 0.198617E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2463.17 23-JAN-16:00 1061.67 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1994.57 02-JAN-06:10 0.00 02-JAN-07:10 0.00 01-JAN-00:10
February 2477.97 09-FEB-16:00 1061.67 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1994.57 01-FEB-06:19 0.00 01-FEB-00:10 0.00 01-FEB-00:10
March 2516.44 15-MAR-07:10 1061.67 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1994.57 01-MAR-06:19 0.00 01-MAR-00:10 0.00 01-MAR-00:10
April 2477.89 18-APR-07:10 1061.67 01-APR-05:10 3325.31 03-APR-07:10 0.00 1994.57 03-APR-05:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 2336.34 23-MAY-07:10 1061.67 01-MAY-05:10 3325.31 01-MAY-07:10 0.00 1994.57 01-MAY-05:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 2349.17 08-JUN-07:10 1061.67 01-JUN-05:10 3325.31 01-JUN-07:10 0.00 1994.57 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 2448.86 20-JUL-07:10 1061.67 01-JUL-05:10 3325.31 03-JUL-07:10 0.00 1994.57 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2375.76 29-AUG-07:10 1061.67 01-AUG-05:10 3325.31 01-AUG-07:10 0.00 1994.57 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2403.52 06-SEP-07:10 1061.67 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1994.57 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2379.96 27-OCT-07:10 1061.67 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1994.57 02-OCT-05:10 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 2476.69 29-NOV-16:00 1061.67 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1994.57 01-NOV-05:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10
December 2494.61 15-DEC-08:09 1061.67 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1994.57 01-DEC-06:19 0.00 01-DEC-00:10 0.00 01-DEC-00:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2336.34   1061.67   3325.31   0.00 1994.57   0.00   0.00  
Maximum of Months 2516.44   1061.67   3325.31   0.00 1994.57   0.00   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 4166.24 30-JAN-13:09 0.00 0.00 0.00 2765.59 11-JAN-12:50 0.00
February 5220.52 06-FEB-15:09 0.00 0.00 0.00 2763.92 02-FEB-12:20 0.00
March 6376.09 27-MAR-12:09 0.00 0.00 0.00 2758.79 01-MAR-12:30 0.00
April 7273.14 28-APR-11:00 0.00 0.00 0.00 2748.33 03-APR-11:30 0.00
May 9109.21 30-MAY-14:00 0.00 0.00 0.00 2738.62 01-MAY-11:09 0.00
June 9779.61 12-JUN-12:09 0.00 0.00 0.00 2729.34 02-JUN-11:09 0.00
July 9751.20 21-JUL-14:20 0.00 0.00 0.00 2724.92 31-JUL-11:00 0.00
August 10115.46 16-AUG-12:09 0.00 0.00 0.00 2730.55 30-AUG-11:00 0.00
September 9613.48 05-SEP-12:09 0.00 0.00 0.00 2739.82 29-SEP-11:50 0.00
October 8303.39 02-OCT-05:30 0.00 0.00 0.00 2751.02 31-OCT-11:20 0.00
November 7406.32 01-NOV-14:09 0.00 0.00 0.00 2759.98 30-NOV-12:20 0.00
December 5609.76 04-DEC-13:09 0.00 0.00 0.00 2764.77 27-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 4166.24   0.00 0.00 0.00 2724.92   0.00
Maximum of Months 10115.46   0.00 0.00 0.00 2765.59   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 14393.48 30-JAN-13:09 2153.08 3325.31 0.00 0.00 1994.57 0.00 0.00 4166.24 0.00
February 15398.63 07-FEB-13:39 2147.44 3325.31 0.00 0.00 1994.57 0.00 0.00 5177.89 0.00
March 16468.58 27-MAR-12:39 2122.12 3325.31 0.00 0.00 1994.57 0.00 0.00 6284.83 0.00
April 16772.55 28-APR-12:39 2139.33 3325.31 0.00 0.00 1994.57 0.00 0.00 6581.88 0.00
May 19197.66 30-MAY-14:50 2104.02 3325.31 0.00 0.00 1994.57 0.00 0.00 9077.72 0.00
June 19898.40 12-JUN-12:30 2130.79 3325.31 0.00 0.00 1994.57 0.00 0.00 9727.31 0.00
July 19829.00 31-JUL-12:50 2125.33 3325.31 0.00 0.00 1994.57 0.00 0.00 9665.45 0.00
August 20144.52 16-AUG-12:00 2135.28 3325.31 0.00 0.00 1994.57 0.00 0.00 9968.60 0.00
September 19775.22 05-SEP-12:20 2117.31 3325.31 0.00 0.00 1994.57 0.00 0.00 9613.19 0.00
October 18331.03 02-OCT-12:50 2123.90 3325.31 0.00 0.00 1994.57 0.00 0.00 8154.20 0.00
November 17497.18 01-NOV-12:50 2120.07 3325.31 0.00 0.00 1994.57 0.00 0.00 7314.66 0.00
December 15709.96 04-DEC-13:50 2165.08 3325.31 0.00 0.00 1994.57 0.00 0.00 5473.94 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 14393.48   2104.02 3325.31 0.00 0.00 1994.57 0.00 0.00 4166.24 0.00
Maximum of Months 20144.52   2165.08 3325.31 0.00 0.00 1994.57 0.00 0.00 9968.60 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 24.55 0.17 24.55
February 0.00 0.00 0.00 0.00 0.67 24.58 0.67 24.58
March 0.00 0.00 0.00 0.00 0.83 24.65 0.83 24.65
April 0.00 0.00 0.00 0.00 2.33 24.75 2.33 24.75
May 0.00 0.00 0.00 0.00 22.67 25.09 22.67 25.09
June 0.00 0.00 0.00 0.00 57.50 24.99 57.50 24.99
July 0.00 0.00 0.00 0.00 171.00 25.19 170.83 25.19
August 0.00 0.00 0.00 0.00 208.50 25.17 208.50 25.17
September 0.00 0.00 0.00 0.00 91.33 25.09 91.33 25.09
October 0.00 0.00 0.00 0.00 21.83 25.12 21.83 25.12
November 0.00 0.00 0.00 0.00 4.67 25.00 4.67 25.00
December 0.00 0.00 0.00 0.00 1.17 24.74 1.17 24.74
                 
Annual Sum or Average 0.00   0.00   582.67 25.14 582.50 25.14
Minimum of Months 0.00 0.00 0.00 0.00 0.17 24.55 0.17 24.55
Maximum of Months 0.00 0.00 0.00 0.00 208.50 25.19 208.50 25.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 6.67 24.91 6.67 24.91
June 0.00 0.00 0.00 0.00 18.17 25.03 18.17 25.03
July 0.00 0.00 0.00 0.00 103.50 25.37 96.17 25.19
August 0.00 0.00 0.00 0.00 151.33 25.41 141.67 25.26
September 0.00 0.00 0.00 0.00 61.50 25.67 53.67 25.36
October 0.00 0.00 0.00 0.00 17.83 27.36 9.67 26.53
November 0.00 0.00 0.00 0.00 3.83 26.14 2.83 25.55
December 0.00 0.00 0.00 0.00 0.33 24.57 0.33 24.57
                 
Annual Sum or Average 0.00   0.00   363.17 25.52 329.17 25.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 151.33 27.36 141.67 26.53



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 5.50 26.22 4.17 25.69
June 0.00 0.00 0.00 0.00 9.83 26.34 7.67 25.87
July 0.00 0.00 0.00 0.00 33.00 27.60 17.33 26.80
August 0.00 0.00 0.00 0.00 39.33 27.30 23.50 26.56
September 0.00 0.00 0.00 0.00 21.33 27.89 10.17 27.06
October 0.00 0.00 0.00 0.00 8.33 26.87 5.50 26.20
November 0.00 0.00 0.00 0.00 1.50 24.74 1.50 24.74
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   118.83 27.30 69.83 26.55
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 39.33 27.89 23.50 27.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 4.17 25.00 4.17 25.00
June 0.00 0.00 0.00 0.00 7.83 25.32 7.83 25.32
July 0.00 0.00 0.00 0.00 21.50 26.82 15.00 26.23
August 0.00 0.00 0.00 0.00 25.83 26.91 18.00 26.33
September 0.00 0.00 0.00 0.00 14.33 27.04 9.33 26.39
October 0.00 0.00 0.00 0.00 6.67 26.06 5.50 25.68
November 0.00 0.00 0.00 0.00 1.33 24.70 1.33 24.70
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   81.67 26.55 61.17 26.04
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 25.83 27.04 18.00 26.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 5.33 27.55 2.67 26.69
June 0.00 0.00 0.00 0.00 11.33 27.65 5.67 26.82
July 0.00 0.00 0.00 0.00 25.33 28.49 9.17 27.68
August 0.00 0.00 0.00 0.00 30.67 28.37 12.17 27.56
September 0.00 0.00 0.00 0.00 20.00 28.53 6.83 27.70
October 0.00 0.00 0.00 0.00 9.33 27.88 4.17 27.01
November 0.00 0.00 0.00 0.00 1.33 24.66 1.33 24.66
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   103.33 28.22 42.00 27.38
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 30.67 28.53 12.17 27.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.83 23.85 165.67 24.78 0.00 24.78
February 5.67 25.90 200.67 24.72 5.67 24.75
March 11.00 26.07 252.17 24.84 11.00 24.89
April 11.00 26.17 296.50 24.74 11.00 24.79
May 57.83 27.14 372.33 25.19 57.83 25.42
June 98.83 27.22 374.00 25.54 98.83 25.83
July 156.50 27.08 340.00 26.20 156.50 26.41
August 190.50 27.07 391.00 26.26 190.50 26.46
September 119.17 27.11 340.00 25.75 119.17 26.03
October 64.00 27.08 355.17 25.24 64.00 25.48
November 43.17 26.38 354.67 24.82 43.17 24.97
December 13.67 25.99 251.67 24.70 13.67 24.77
             
Annual Sum or Average 779.17 26.98 3693.83 25.39 771.33 25.63
Minimum of Months 5.67 23.85 165.67 24.70 0.00 24.75
Maximum of Months 190.50 27.22 391.00 26.26 190.50 26.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 29.50 23.41 227.67 24.45 0.00 24.45
February 28.67 24.40 254.67 24.50 11.33 24.56
March 39.83 24.75 265.67 24.76 18.17 24.83
April 29.33 25.98 279.50 24.89 29.33 24.98
May 106.17 27.20 370.17 25.48 106.17 25.80
June 144.17 27.07 374.00 25.70 144.17 26.00
July 172.67 27.19 340.00 26.20 172.67 26.45
August 204.83 27.35 391.00 26.39 204.83 26.64
September 141.50 27.35 340.00 26.00 141.50 26.31
October 114.17 27.65 357.00 25.75 114.17 26.12
November 72.00 27.11 357.00 25.22 72.00 25.49
December 16.50 26.48 305.00 24.69 16.50 24.78
             
Annual Sum or Average 1099.33 26.96 3861.67 25.50 1030.83 25.79
Minimum of Months 16.50 23.41 227.67 24.45 0.00 24.45
Maximum of Months 204.83 27.65 391.00 26.39 204.83 26.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 32.83 23.84 129.67 24.56 0.00 24.56
February 14.50 24.30 163.33 24.66 3.50 24.68
March 21.33 24.59 210.83 24.88 7.00 24.91
April 12.83 26.34 251.67 24.99 12.83 25.05
May 100.17 27.54 308.00 25.80 100.17 26.15
June 118.50 27.73 308.00 26.06 118.50 26.42
July 114.33 28.18 280.00 26.42 114.33 26.82
August 131.83 28.37 322.00 26.56 131.83 26.97
September 110.50 27.89 280.00 26.19 110.50 26.57
October 105.00 27.67 294.00 25.93 105.00 26.29
November 41.17 26.94 293.67 25.18 41.17 25.37
December 3.33 26.03 216.50 24.74 3.17 24.76
             
Annual Sum or Average 806.33 27.52 3057.67 25.70 748.00 26.04
Minimum of Months 3.33 23.84 129.67 24.56 0.00 24.56
Maximum of Months 131.83 28.37 322.00 26.56 131.83 26.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 63.83 23.84 93.67 24.41 0.00 24.41
February 28.83 24.01 138.50 24.56 2.50 24.58
March 31.67 24.26 209.17 24.74 6.17 24.77
April 7.00 25.62 279.67 24.77 7.00 24.79
May 89.83 27.40 372.33 25.43 89.83 25.75
June 117.67 27.62 374.00 25.71 117.67 26.08
July 113.17 28.06 340.00 26.01 113.17 26.42
August 131.33 28.16 391.00 26.08 131.33 26.50
September 109.33 27.71 340.00 25.78 109.33 26.15
October 91.00 27.49 357.00 25.49 91.00 25.83
November 31.33 26.68 352.50 24.85 31.33 24.99
December 10.83 24.51 213.67 24.64 3.33 24.66
             
Annual Sum or Average 825.83 27.10 3461.50 25.40 702.67 25.72
Minimum of Months 7.00 23.84 93.67 24.41 0.00 24.41
Maximum of Months 131.33 28.16 391.00 26.08 131.33 26.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 46.17 23.87 154.33 24.54 0.00 24.54
February 23.00 24.13 199.50 24.58 3.00 24.60
March 28.00 24.83 251.33 24.89 9.00 24.95
April 28.50 27.25 290.17 25.10 28.50 25.28
May 109.83 27.85 373.67 25.73 109.83 26.12
June 118.67 28.12 374.00 25.95 118.67 26.37
July 112.67 28.44 340.00 26.17 112.67 26.62
August 130.83 28.60 391.00 26.26 130.83 26.73
September 109.83 28.17 340.00 26.00 109.83 26.42
October 106.67 27.91 357.00 25.76 106.67 26.16
November 46.83 27.11 354.33 25.07 46.83 25.28
December 2.83 25.79 262.00 24.64 2.33 24.66
             
Annual Sum or Average 863.83 27.65 3687.33 25.56 778.17 25.93
Minimum of Months 2.83 23.87 154.33 24.54 0.00 24.54
Maximum of Months 130.83 28.60 391.00 26.26 130.83 26.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.267294E+10 0.580395E+09 246.71 0.207777E+10 0.595169E+09 0.00 1.00 04-JAN-06:03 0.00 01-JAN-00:10 7940.29 30-JAN-06:01 6150.24 19-JAN-06:02 2922.85 10-JAN-06:04 1539.89 30-JAN-06:01 0.00
February 0.284110E+10 0.625015E+09 225.99 0.218582E+10 0.655288E+09 0.00 1.00 01-FEB-06:02 0.00 01-FEB-00:10 8109.51 07-FEB-06:01 6058.50 13-FEB-06:02 3108.05 03-FEB-06:04 1583.04 09-FEB-06:02 0.00
March 0.375044E+10 0.851538E+09 274.68 0.300630E+10 0.744140E+09 0.00 1.00 01-MAR-06:02 0.00 01-MAR-00:10 8149.83 29-MAR-05:02 6780.31 28-MAR-05:01 3290.40 29-MAR-05:07 1677.89 02-MAR-06:01 0.00
April 0.401044E+10 0.935112E+09 239.92 0.320480E+10 0.805633E+09 0.00 1.00 03-APR-05:01 0.00 01-APR-00:10 8219.54 03-APR-05:01 6939.71 26-APR-05:01 3307.79 20-APR-05:07 1622.81 03-APR-05:01 0.00
May 0.585559E+10 0.142171E+10 264.00 0.467845E+10 0.117714E+10 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 8431.09 30-MAY-05:01 6660.03 11-MAY-05:01 3646.36 25-MAY-05:08 1951.30 31-MAY-12:00 0.00
June 0.663415E+10 0.161125E+10 264.00 0.497444E+10 0.165971E+10 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 8585.67 27-JUN-05:01 6318.95 16-JUN-05:01 4114.15 08-JUN-05:09 2020.30 12-JUN-11:57 0.00
July 0.667259E+10 0.160792E+10 248.47 0.466470E+10 0.200789E+10 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 8571.99 06-JUL-05:01 6736.23 03-JUL-07:10 4543.29 27-JUL-05:10 2048.55 21-JUL-12:00 0.00
August 0.777600E+10 0.187591E+10 291.85 0.536945E+10 0.240655E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 8571.99 31-AUG-05:02 6476.09 15-AUG-09:51 4445.21 23-AUG-05:10 2088.45 16-AUG-12:00 0.00
September 0.640420E+10 0.151249E+10 250.27 0.456405E+10 0.184015E+10 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 8592.70 22-SEP-05:01 6279.28 26-SEP-12:45 4551.91 12-SEP-05:10 1971.71 05-SEP-12:00 0.00
October 0.599753E+10 0.137709E+10 255.18 0.447952E+10 0.151801E+10 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 8594.73 02-OCT-05:01 6699.85 20-OCT-05:01 3874.33 02-OCT-05:09 1832.36 02-OCT-13:00 0.00
November 0.490034E+10 0.109206E+10 252.00 0.365692E+10 0.124342E+10 0.00 1.00 01-NOV-05:01 0.00 01-NOV-00:10 8330.77 03-NOV-05:01 6422.42 20-NOV-06:01 3660.84 03-NOV-05:08 1655.75 01-NOV-14:00 0.00
December 0.333035E+10 0.723776E+09 239.11 0.252522E+10 0.805128E+09 0.00 1.00 01-DEC-06:01 0.00 01-DEC-00:10 8163.77 06-DEC-06:01 5905.11 13-DEC-06:01 3501.76 06-DEC-06:06 1573.29 12-DEC-06:01 0.00
                                       
Annual Sum or Average 0.608457E+11 0.142143E+11 3052.20 0.453874E+11 0.154582E+11 0.00                         0.00
Minimum of Months 0.267294E+10 0.580395E+09 225.99 0.207777E+10 0.595169E+09 0.00 1.00   0.00   7940.29   5905.11   2922.85   1539.89   0.00
Maximum of Months 0.777600E+10 0.187591E+10 291.85 0.536945E+10 0.240655E+10 0.00 1.00   0.00   8594.73   6939.71   4551.91   2088.45   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.254800E+10 0.559611E+09 227.82 0.219289E+10 0.355108E+09 0.00 1.00 09-JAN-06:02 0.00 01-JAN-00:10 9779.05 30-JAN-06:01 8985.52 17-JAN-06:02 2960.74 30-JAN-06:04 1883.69 30-JAN-06:01 0.00
February 0.264914E+10 0.594038E+09 210.71 0.222296E+10 0.426177E+09 0.00 1.00 06-FEB-06:01 0.00 01-FEB-00:10 9938.99 09-FEB-06:02 8162.12 10-FEB-06:02 3731.12 09-FEB-06:03 1927.53 09-FEB-06:02 0.00
March 0.329589E+10 0.772694E+09 261.50 0.284603E+10 0.449858E+09 0.00 1.00 01-MAR-06:02 0.00 01-MAR-00:10 10005.19 29-MAR-05:02 9076.92 28-MAR-05:01 4178.75 29-MAR-05:03 2035.58 27-MAR-11:25 0.00
April 0.352175E+10 0.853950E+09 238.55 0.295908E+10 0.562676E+09 0.00 1.00 03-APR-05:01 0.00 01-APR-00:10 10026.05 10-APR-05:01 9068.26 26-APR-05:01 4275.17 20-APR-05:03 2302.04 28-APR-11:55 0.00
May 0.594368E+10 0.148999E+10 273.57 0.490058E+10 0.104309E+10 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 10453.96 24-MAY-05:01 9106.62 11-MAY-05:01 5543.59 24-MAY-05:05 2365.90 31-MAY-12:00 0.00
June 0.725436E+10 0.180621E+10 285.93 0.552429E+10 0.173006E+10 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 10456.42 08-JUN-05:02 8077.63 01-JUN-11:55 6130.99 27-JUN-05:06 2442.59 12-JUN-11:57 0.00
July 0.820920E+10 0.202728E+10 330.93 0.590258E+10 0.230662E+10 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 10396.78 06-JUL-05:17 9070.04 03-JUL-05:01 6442.51 27-JUL-05:06 2461.37 21-JUL-12:00 0.00
August 0.961060E+10 0.237079E+10 369.63 0.687290E+10 0.273769E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 10396.78 31-AUG-05:13 8515.84 06-AUG-16:42 6230.53 09-AUG-05:07 2523.56 16-AUG-12:00 0.00
September 0.778842E+10 0.187614E+10 311.06 0.573830E+10 0.205012E+10 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 10453.96 29-SEP-05:06 9040.88 04-SEP-16:53 6093.74 22-SEP-05:06 2387.93 04-SEP-16:12 0.00
October 0.729204E+10 0.170621E+10 312.22 0.574851E+10 0.154353E+10 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 10463.46 18-OCT-05:01 9253.33 09-OCT-14:02 5315.14 18-OCT-05:07 2279.13 09-OCT-14:02 0.00
November 0.570114E+10 0.128823E+10 266.95 0.457986E+10 0.112128E+10 0.00 1.00 01-NOV-05:01 0.00 01-NOV-00:10 10290.82 03-NOV-05:01 8489.91 20-NOV-06:01 4725.81 03-NOV-05:07 2148.81 01-NOV-11:55 0.00
December 0.342875E+10 0.754430E+09 231.69 0.284086E+10 0.587888E+09 0.00 1.00 01-DEC-06:01 0.00 01-DEC-00:10 9983.05 06-DEC-06:01 8266.19 18-DEC-06:01 4050.47 06-DEC-06:03 1919.09 12-DEC-06:01 0.00
                                       
Annual Sum or Average 0.672430E+11 0.160996E+11 3320.57 0.523288E+11 0.149141E+11 0.00                         0.00
Minimum of Months 0.254800E+10 0.559611E+09 210.71 0.219289E+10 0.355108E+09 0.00 1.00   0.00   9779.05   8077.63   2960.74   1883.69   0.00
Maximum of Months 0.961060E+10 0.237079E+10 369.63 0.687290E+10 0.273769E+10 0.00 1.00   0.00   10463.46   9253.33   6442.51   2523.56   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.113196E+10 0.252679E+09 240.96 0.100236E+10 0.129597E+09 0.00 1.00 23-JAN-06:01 0.00 01-JAN-00:10 5994.69 30-JAN-06:01 4833.94 17-JAN-06:02 1734.50 30-JAN-06:02 1155.56 30-JAN-06:01 0.00
February 0.121661E+10 0.276521E+09 223.02 0.105140E+10 0.165211E+09 0.00 1.00 06-FEB-06:01 0.00 01-FEB-00:10 6085.24 09-FEB-06:02 5230.52 10-FEB-06:02 2182.93 09-FEB-06:03 1182.37 09-FEB-06:02 0.00
March 0.165565E+10 0.391316E+09 272.86 0.148006E+10 0.175587E+09 0.00 1.00 01-MAR-06:02 0.00 01-MAR-00:10 6102.82 29-MAR-05:02 5603.59 28-MAR-05:01 2313.82 29-MAR-05:03 1323.59 27-MAR-10:02 0.00
April 0.194455E+10 0.473575E+09 238.57 0.171615E+10 0.228400E+09 0.00 1.00 03-APR-05:01 0.00 01-APR-00:10 6158.55 10-APR-05:01 5611.81 26-APR-05:01 2419.91 20-APR-05:03 1383.31 28-APR-10:02 0.00
May 0.331964E+10 0.841809E+09 290.83 0.289738E+10 0.422257E+09 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 6417.03 24-MAY-05:01 5658.04 11-MAY-05:01 3237.88 24-MAY-05:06 1432.13 31-MAY-12:05 0.00
June 0.396690E+10 0.100724E+10 305.67 0.324839E+10 0.718506E+09 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 6419.44 08-JUN-05:01 5097.79 16-JUN-10:02 3540.77 27-JUN-05:08 1478.99 12-JUN-12:03 0.00
July 0.460390E+10 0.116948E+10 350.45 0.362454E+10 0.979359E+09 0.00 1.00 02-JUL-08:42 0.00 01-JUL-00:10 6382.83 06-JUL-05:01 5674.14 03-JUL-05:01 3640.63 27-JUL-05:09 1498.85 21-JUL-12:03 0.00
August 0.544289E+10 0.137929E+10 373.84 0.427182E+10 0.117107E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 6382.83 31-AUG-05:01 5595.66 06-AUG-10:53 3736.10 09-AUG-05:07 1527.84 16-AUG-12:10 0.00
September 0.417850E+10 0.103137E+10 319.24 0.333255E+10 0.845955E+09 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 6417.93 29-SEP-05:01 5612.60 04-SEP-14:32 3498.73 12-SEP-05:09 1476.64 04-SEP-14:32 0.00
October 0.357736E+10 0.854938E+09 299.03 0.297947E+10 0.597885E+09 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 6402.51 17-OCT-05:01 5504.51 09-OCT-14:43 3069.98 18-OCT-05:07 1360.22 09-OCT-14:43 0.00
November 0.261419E+10 0.603861E+09 252.81 0.220192E+10 0.412273E+09 0.00 1.00 01-NOV-05:01 0.00 01-NOV-00:10 6281.47 03-NOV-05:01 5266.31 20-NOV-06:01 2738.16 03-NOV-05:06 1293.45 06-NOV-11:02 0.00
December 0.153519E+10 0.344571E+09 237.30 0.132033E+10 0.214863E+09 0.00 1.00 01-DEC-06:01 0.00 01-DEC-00:10 6060.10 06-DEC-06:01 5158.53 13-DEC-06:01 2168.35 06-DEC-06:03 1177.73 12-DEC-06:01 0.00
                                       
Annual Sum or Average 0.351873E+11 0.862664E+10 3404.57 0.291264E+11 0.606096E+10 0.00                         0.00
Minimum of Months 0.113196E+10 0.252679E+09 223.02 0.100236E+10 0.129597E+09 0.00 1.00   0.00   5994.69   4833.94   1734.50   1155.56   0.00
Maximum of Months 0.544289E+10 0.137929E+10 373.84 0.427182E+10 0.117107E+10 0.00 1.00   0.00   6419.44   5674.14   3736.10   1527.84   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.182160E+10 0.407495E+09 239.47 0.153901E+10 0.282592E+09 0.00 1.00 23-JAN-06:01 0.00 01-JAN-00:10 9546.33 30-JAN-06:01 7362.09 25-JAN-06:02 3010.29 30-JAN-06:02 1843.38 30-JAN-06:01 0.00
February 0.199943E+10 0.455674E+09 220.75 0.165555E+10 0.343880E+09 0.00 1.00 06-FEB-06:01 0.00 01-FEB-00:10 9712.47 09-FEB-06:02 8022.34 10-FEB-06:02 3627.49 09-FEB-06:03 1888.93 09-FEB-06:02 0.00
March 0.276534E+10 0.654167E+09 273.38 0.238489E+10 0.380456E+09 0.00 1.00 01-MAR-06:02 0.00 01-MAR-00:10 9732.28 29-MAR-05:02 8898.20 28-MAR-05:01 3807.25 29-MAR-05:03 1974.05 02-MAR-06:01 0.00
April 0.318361E+10 0.776627E+09 239.51 0.271374E+10 0.469878E+09 0.00 1.00 03-APR-05:01 0.00 01-APR-00:10 9828.78 10-APR-05:01 8890.13 26-APR-05:01 3971.57 20-APR-05:03 1912.21 28-APR-05:01 0.00
May 0.526388E+10 0.133786E+10 273.77 0.445461E+10 0.809265E+09 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 10230.55 30-MAY-05:01 8858.50 11-MAY-05:01 5148.90 24-MAY-05:06 2112.38 30-MAY-15:00 0.00
June 0.634972E+10 0.161300E+10 286.24 0.504192E+10 0.130779E+10 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 10260.21 08-JUN-05:02 7855.85 16-JUN-05:01 5636.09 27-JUN-05:06 2358.73 12-JUN-12:10 0.00
July 0.729386E+10 0.184844E+10 324.16 0.555854E+10 0.173532E+10 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 10201.69 06-JUL-05:10 8865.22 03-JUL-05:01 5819.94 27-JUL-05:09 2344.62 30-JUL-15:02 0.00
August 0.856967E+10 0.217290E+10 354.48 0.651096E+10 0.205871E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 10201.69 31-AUG-05:06 8311.57 06-AUG-16:42 5952.49 09-AUG-05:09 2428.80 16-AUG-12:10 0.00
September 0.655955E+10 0.162058E+10 294.00 0.505767E+10 0.150188E+10 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 10271.72 25-SEP-05:02 8793.02 04-SEP-16:53 5624.93 12-SEP-05:09 2343.08 04-SEP-16:12 0.00
October 0.562922E+10 0.134747E+10 273.41 0.452205E+10 0.110717E+10 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 10246.44 02-OCT-05:01 8410.62 20-OCT-05:01 5045.09 02-OCT-05:07 1976.11 05-OCT-05:02 0.00
November 0.422214E+10 0.978388E+09 251.78 0.341000E+10 0.812142E+09 0.00 1.00 01-NOV-05:01 0.00 01-NOV-00:10 10011.70 03-NOV-05:01 8033.08 20-NOV-06:01 4444.19 03-NOV-05:06 1935.75 20-NOV-06:01 0.00
December 0.254197E+10 0.571189E+09 238.44 0.208907E+10 0.452896E+09 0.00 1.00 01-DEC-06:01 0.00 01-DEC-00:10 9670.16 06-DEC-06:01 7938.42 13-DEC-06:01 3657.67 06-DEC-06:03 1880.63 12-DEC-06:01 0.00
                                       
Annual Sum or Average 0.562000E+11 0.137838E+11 3269.38 0.449380E+11 0.112620E+11 0.00                         0.00
Minimum of Months 0.182160E+10 0.407495E+09 220.75 0.153901E+10 0.282592E+09 0.00 1.00   0.00   9546.33   7362.09   3010.29   1843.38   0.00
Maximum of Months 0.856967E+10 0.217290E+10 354.48 0.651096E+10 0.205871E+10 0.00 1.00   0.00   10271.72   8898.20   5952.49   2428.80   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.130258E+10 0.291706E+09 245.22 0.113561E+10 0.166975E+09 0.00 1.00 23-JAN-06:01 0.00 01-JAN-00:10 6948.12 30-JAN-06:01 5607.12 25-JAN-06:02 2008.25 30-JAN-06:02 1338.99 30-JAN-06:01 0.00
February 0.139762E+10 0.319057E+09 225.36 0.119199E+10 0.205631E+09 0.00 1.00 06-FEB-06:01 0.00 01-FEB-00:10 7050.62 09-FEB-06:02 5460.22 27-FEB-06:01 2442.16 09-FEB-06:02 1369.75 09-FEB-06:02 0.00
March 0.190023E+10 0.450753E+09 275.04 0.167733E+10 0.222905E+09 0.00 1.00 01-MAR-06:02 0.00 01-MAR-00:10 7070.67 29-MAR-05:02 6499.55 28-MAR-05:01 2570.13 29-MAR-05:02 1430.42 02-MAR-06:01 0.00
April 0.211913E+10 0.519950E+09 239.49 0.184297E+10 0.276158E+09 0.00 1.00 03-APR-05:01 0.00 01-APR-00:10 7139.52 10-APR-05:01 6516.35 26-APR-05:01 2719.87 10-APR-05:03 1387.24 28-APR-05:01 0.00
May 0.348061E+10 0.894926E+09 291.38 0.299990E+10 0.480712E+09 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 7430.83 24-MAY-05:01 6557.36 11-MAY-05:01 3714.47 24-MAY-05:06 1489.89 23-MAY-05:04 0.00
June 0.419018E+10 0.107987E+10 310.45 0.339267E+10 0.797510E+09 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 7436.30 08-JUN-05:01 5912.03 16-JUN-05:01 4080.07 27-JUN-05:06 1529.78 29-JUN-05:23 0.00
July 0.480186E+10 0.123910E+10 349.08 0.374643E+10 0.105543E+10 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 7393.89 06-JUL-05:07 6695.64 03-JUL-05:01 4199.69 06-JUL-05:07 1686.99 30-JUL-15:13 0.00
August 0.566532E+10 0.146177E+10 376.73 0.441224E+10 0.125308E+10 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 7393.89 31-AUG-05:01 6311.23 06-AUG-15:02 4307.53 09-AUG-05:07 1711.89 10-AUG-15:40 0.00
September 0.438448E+10 0.109902E+10 319.95 0.346252E+10 0.921963E+09 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 7434.55 29-SEP-05:01 6486.60 04-SEP-14:32 4035.02 12-SEP-05:08 1710.58 04-SEP-14:32 0.00
October 0.377852E+10 0.915550E+09 297.99 0.311060E+10 0.667925E+09 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 7410.42 17-OCT-05:01 6578.46 09-OCT-16:12 3526.78 18-OCT-05:07 1609.62 09-OCT-16:12 0.00
November 0.284425E+10 0.663575E+09 254.34 0.236273E+10 0.481523E+09 0.00 1.00 01-NOV-05:01 0.00 01-NOV-00:10 7272.77 03-NOV-05:01 6137.34 13-NOV-06:01 3110.48 03-NOV-05:04 1405.04 20-NOV-06:01 0.00
December 0.175232E+10 0.394944E+09 238.76 0.148440E+10 0.267922E+09 0.00 1.00 01-DEC-06:01 0.00 01-DEC-00:10 7018.54 11-DEC-06:01 6026.25 13-DEC-06:01 2447.51 06-DEC-06:03 1364.53 12-DEC-06:01 0.00
                                       
Annual Sum or Average 0.376171E+11 0.933022E+10 3423.79 0.308194E+11 0.679773E+10 0.00                         0.00
Minimum of Months 0.130258E+10 0.291706E+09 225.36 0.113561E+10 0.166975E+09 0.00 1.00   0.00   6948.12   5460.22   2008.25   1338.99   0.00
Maximum of Months 0.566532E+10 0.146177E+10 376.73 0.441224E+10 0.125308E+10 0.00 1.00   0.00   7436.30   6695.64   4307.53   1711.89   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 42.65 20.45 22.21 67.50 32.66 0.00 0.00 0.00
February 38.54 15.78 22.76 65.04 27.54 0.00 0.00 0.00
March 27.28 6.06 21.22 51.24 20.68 0.00 0.00 0.00
April 18.70 0.01 18.69 41.65 13.10 0.00 0.00 0.00
May 19.69 0.00 19.69 58.10 4.42 0.00 0.00 0.00
June 19.80 0.00 19.80 63.58 1.83 0.00 0.00 0.00
July 19.28 0.00 19.28 70.18 0.34 0.00 0.00 0.00
August 19.33 0.22 19.11 71.31 0.26 0.00 0.00 0.00
September 23.63 3.37 20.25 66.73 3.21 0.00 0.00 0.00
October 37.69 14.41 23.28 84.10 9.66 0.00 0.00 0.00
November 45.62 22.36 23.26 87.05 19.17 0.00 0.00 0.00
December 42.49 21.38 21.11 70.96 29.00 0.00 0.00 0.00
                 
Annual Sum or Average 29.51 8.64 20.88 66.48 13.42 0.00 0.00 0.00
Minimum of Months 18.70 0.00 18.69 41.65 0.26 0.00 0.00 0.00
Maximum of Months 45.62 22.36 23.28 87.05 32.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 42.65 20.45 22.21 67.49 32.65 0.00 0.00 0.00
February 38.54 15.78 22.76 65.04 27.54 0.00 0.00 0.00
March 27.26 6.06 21.20 51.20 20.69 0.00 0.00 0.00
April 18.67 0.00 18.66 41.58 13.10 0.00 0.00 0.00
May 19.69 0.00 19.69 58.10 4.42 0.00 0.00 0.00
June 19.80 0.00 19.80 63.58 1.83 0.00 0.00 0.00
July 19.28 0.00 19.28 70.18 0.34 0.00 0.00 0.00
August 19.32 0.21 19.11 71.29 0.26 0.00 0.00 0.00
September 23.52 3.35 20.18 66.47 3.21 0.00 0.00 0.00
October 37.69 14.41 23.28 84.10 9.66 0.00 0.00 0.00
November 45.62 22.36 23.26 87.05 19.17 0.00 0.00 0.00
December 42.49 21.38 21.11 70.96 29.00 0.00 0.00 0.00
                 
Annual Sum or Average 29.50 8.63 20.87 66.45 13.42 0.00 0.00 0.00
Minimum of Months 18.67 0.00 18.66 41.58 0.26 0.00 0.00 0.00
Maximum of Months 45.62 22.36 23.28 87.05 32.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 42.65 20.45 22.21 67.49 32.65 0.00 0.00 0.00
February 38.54 15.78 22.76 65.04 27.54 0.00 0.00 0.00
March 27.26 6.06 21.20 51.20 20.69 0.00 0.00 0.00
April 18.67 0.00 18.66 41.58 13.10 0.00 0.00 0.00
May 19.69 0.00 19.69 58.10 4.42 0.00 0.00 0.00
June 19.80 0.00 19.80 63.58 1.83 0.00 0.00 0.00
July 19.28 0.00 19.28 70.18 0.34 0.00 0.00 0.00
August 19.32 0.21 19.11 71.29 0.26 0.00 0.00 0.00
September 23.52 3.35 20.17 66.47 3.21 0.00 0.00 0.00
October 37.69 14.41 23.28 84.10 9.66 0.00 0.00 0.00
November 45.62 22.36 23.26 87.05 19.17 0.00 0.00 0.00
December 42.49 21.38 21.11 70.96 29.00 0.00 0.00 0.00
                 
Annual Sum or Average 29.50 8.63 20.87 66.45 13.42 0.00 0.00 0.00
Minimum of Months 18.67 0.00 18.66 41.58 0.26 0.00 0.00 0.00
Maximum of Months 45.62 22.36 23.28 87.05 32.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 42.65 20.45 22.21 67.49 32.65 0.00 0.00 0.00
February 38.54 15.78 22.76 65.04 27.54 0.00 0.00 0.00
March 27.26 6.06 21.20 51.20 20.69 0.00 0.00 0.00
April 18.67 0.00 18.66 41.58 13.10 0.00 0.00 0.00
May 19.69 0.00 19.69 58.10 4.42 0.00 0.00 0.00
June 19.80 0.00 19.80 63.58 1.83 0.00 0.00 0.00
July 19.28 0.00 19.28 70.18 0.34 0.00 0.00 0.00
August 19.32 0.21 19.11 71.29 0.26 0.00 0.00 0.00
September 23.52 3.35 20.17 66.47 3.21 0.00 0.00 0.00
October 37.69 14.41 23.28 84.10 9.66 0.00 0.00 0.00
November 45.62 22.36 23.26 87.05 19.17 0.00 0.00 0.00
December 42.49 21.38 21.11 70.96 29.00 0.00 0.00 0.00
                 
Annual Sum or Average 29.50 8.63 20.87 66.45 13.42 0.00 0.00 0.00
Minimum of Months 18.67 0.00 18.66 41.58 0.26 0.00 0.00 0.00
Maximum of Months 45.62 22.36 23.28 87.05 32.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 42.65 20.45 22.21 67.49 32.65 0.00 0.00 0.00
February 38.54 15.78 22.76 65.04 27.54 0.00 0.00 0.00
March 27.26 6.06 21.20 51.20 20.69 0.00 0.00 0.00
April 18.67 0.00 18.66 41.58 13.10 0.00 0.00 0.00
May 19.69 0.00 19.69 58.10 4.42 0.00 0.00 0.00
June 19.80 0.00 19.80 63.58 1.83 0.00 0.00 0.00
July 19.28 0.00 19.28 70.18 0.34 0.00 0.00 0.00
August 19.32 0.21 19.11 71.29 0.26 0.00 0.00 0.00
September 23.52 3.35 20.18 66.48 3.21 0.00 0.00 0.00
October 37.69 14.41 23.28 84.10 9.66 0.00 0.00 0.00
November 45.62 22.36 23.26 87.05 19.17 0.00 0.00 0.00
December 42.49 21.38 21.11 70.96 29.00 0.00 0.00 0.00
                 
Annual Sum or Average 29.50 8.63 20.87 66.45 13.42 0.00 0.00 0.00
Minimum of Months 18.67 0.00 18.66 41.58 0.26 0.00 0.00 0.00
Maximum of Months 45.62 22.36 23.28 87.05 32.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 42.65 20.45 22.21 67.50 32.66 0.00 0.00 0.00
February 38.54 15.78 22.76 65.04 27.54 0.00 0.00 0.00
March 27.28 6.06 21.21 51.21 20.66 0.00 0.00 0.00
April 18.70 0.01 18.69 41.65 13.10 0.00 0.00 0.00
May 19.69 0.00 19.69 58.10 4.42 0.00 0.00 0.00
June 19.80 0.00 19.80 63.58 1.83 0.00 0.00 0.00
July 19.28 0.00 19.28 70.18 0.34 0.00 0.00 0.00
August 19.33 0.22 19.11 71.31 0.26 0.00 0.00 0.00
September 23.63 3.37 20.26 66.74 3.20 0.00 0.00 0.00
October 37.69 14.41 23.28 84.10 9.66 0.00 0.00 0.00
November 45.62 22.36 23.26 87.05 19.17 0.00 0.00 0.00
December 42.49 21.38 21.11 70.96 29.00 0.00 0.00 0.00
                 
Annual Sum or Average 29.51 8.64 20.88 66.48 13.42 0.00 0.00 0.00
Minimum of Months 18.70 0.00 18.69 41.65 0.26 0.00 0.00 0.00
Maximum of Months 45.62 22.36 23.28 87.05 32.66 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 60.42 28.69 31.73 95.36 45.97 0.00 0.00 0.00
February 56.63 23.44 33.19 95.74 38.80 0.00 0.00 0.00
March 44.01 11.41 32.60 83.39 29.25 0.00 0.00 0.00
April 30.08 1.39 28.69 66.45 18.75 0.00 0.00 0.00
May 28.32 0.00 28.32 81.49 6.48 0.00 0.00 0.00
June 28.44 0.00 28.44 88.83 2.78 0.00 0.00 0.00
July 27.70 0.00 27.70 97.96 0.54 0.00 0.00 0.00
August 28.23 0.57 27.65 100.55 0.42 0.00 0.00 0.00
September 39.24 7.68 31.56 105.87 4.78 0.00 0.00 0.00
October 58.44 23.46 34.98 128.32 14.02 0.00 0.00 0.00
November 64.74 31.49 33.24 122.71 27.33 0.00 0.00 0.00
December 60.08 29.96 30.12 99.93 40.91 0.00 0.00 0.00
                 
Annual Sum or Average 43.79 13.12 30.67 97.24 19.07 0.00 0.00 0.00
Minimum of Months 27.70 0.00 27.65 66.45 0.42 0.00 0.00 0.00
Maximum of Months 64.74 31.49 34.98 128.32 45.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.74 7.00 15.74 29.86 31.11 0.00 0.00 0.00
February 24.55 6.67 17.88 36.60 25.86 0.00 0.00 0.00
March 26.86 6.55 20.31 47.27 19.29 0.00 0.00 0.00
April 32.45 9.25 23.20 66.90 12.79 0.00 0.00 0.00
May 36.38 11.43 24.95 89.18 4.45 0.00 0.00 0.00
June 35.39 10.52 24.87 92.79 2.01 0.00 0.00 0.00
July 32.84 9.07 23.76 96.99 0.37 0.00 0.00 0.00
August 33.89 10.12 23.76 100.30 0.24 0.00 0.00 0.00
September 32.17 9.82 22.35 81.73 3.01 0.00 0.00 0.00
October 29.52 9.65 19.87 65.21 9.03 0.00 0.00 0.00
November 24.90 7.95 16.95 46.10 17.88 0.00 0.00 0.00
December 20.15 5.62 14.53 28.64 27.49 0.00 0.00 0.00
                 
Annual Sum or Average 29.34 8.65 20.69 65.29 12.73 0.00 0.00 0.00
Minimum of Months 20.15 5.62 14.53 28.64 0.24 0.00 0.00 0.00
Maximum of Months 36.38 11.43 24.95 100.30 31.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.74 7.00 15.74 29.86 31.11 0.00 0.00 0.00
February 24.55 6.67 17.88 36.60 25.86 0.00 0.00 0.00
March 26.86 6.55 20.31 47.27 19.29 0.00 0.00 0.00
April 32.45 9.25 23.20 66.90 12.79 0.00 0.00 0.00
May 36.38 11.43 24.95 89.18 4.45 0.00 0.00 0.00
June 35.39 10.52 24.87 92.79 2.01 0.00 0.00 0.00
July 32.83 9.07 23.76 96.99 0.37 0.00 0.00 0.00
August 33.89 10.12 23.76 100.30 0.24 0.00 0.00 0.00
September 32.17 9.82 22.35 81.73 3.01 0.00 0.00 0.00
October 29.52 9.65 19.87 65.21 9.03 0.00 0.00 0.00
November 24.90 7.95 16.94 46.10 17.88 0.00 0.00 0.00
December 20.14 5.62 14.53 28.64 27.49 0.00 0.00 0.00
                 
Annual Sum or Average 29.34 8.65 20.69 65.29 12.73 0.00 0.00 0.00
Minimum of Months 20.14 5.62 14.53 28.64 0.24 0.00 0.00 0.00
Maximum of Months 36.38 11.43 24.95 100.30 31.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.74 7.00 15.74 29.86 31.11 0.00 0.00 0.00
February 24.55 6.67 17.88 36.60 25.86 0.00 0.00 0.00
March 26.86 6.55 20.31 47.27 19.29 0.00 0.00 0.00
April 32.45 9.25 23.20 66.90 12.79 0.00 0.00 0.00
May 36.38 11.43 24.95 89.18 4.45 0.00 0.00 0.00
June 35.39 10.52 24.87 92.79 2.01 0.00 0.00 0.00
July 32.83 9.07 23.76 96.99 0.37 0.00 0.00 0.00
August 33.89 10.12 23.76 100.30 0.24 0.00 0.00 0.00
September 32.17 9.82 22.35 81.73 3.01 0.00 0.00 0.00
October 29.52 9.65 19.87 65.21 9.03 0.00 0.00 0.00
November 24.90 7.95 16.94 46.10 17.88 0.00 0.00 0.00
December 20.14 5.62 14.53 28.64 27.49 0.00 0.00 0.00
                 
Annual Sum or Average 29.34 8.65 20.69 65.29 12.73 0.00 0.00 0.00
Minimum of Months 20.14 5.62 14.53 28.64 0.24 0.00 0.00 0.00
Maximum of Months 36.38 11.43 24.95 100.30 31.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.74 7.00 15.74 29.86 31.11 0.00 0.00 0.00
February 24.55 6.67 17.88 36.60 25.86 0.00 0.00 0.00
March 26.86 6.55 20.31 47.27 19.29 0.00 0.00 0.00
April 32.45 9.25 23.20 66.90 12.79 0.00 0.00 0.00
May 36.38 11.43 24.95 89.18 4.45 0.00 0.00 0.00
June 35.39 10.52 24.87 92.79 2.01 0.00 0.00 0.00
July 32.84 9.07 23.76 96.99 0.37 0.00 0.00 0.00
August 33.89 10.12 23.76 100.30 0.24 0.00 0.00 0.00
September 32.17 9.82 22.35 81.73 3.01 0.00 0.00 0.00
October 29.52 9.65 19.87 65.21 9.03 0.00 0.00 0.00
November 24.90 7.95 16.95 46.10 17.88 0.00 0.00 0.00
December 20.15 5.62 14.53 28.65 27.49 0.00 0.00 0.00
                 
Annual Sum or Average 29.34 8.65 20.69 65.29 12.73 0.00 0.00 0.00
Minimum of Months 20.15 5.62 14.53 28.65 0.24 0.00 0.00 0.00
Maximum of Months 36.38 11.43 24.95 100.30 31.11 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.62 0.00 12.62 13.91 32.70 0.00 0.00 0.00
February 14.50 0.00 14.50 19.91 26.91 0.00 0.00 0.00
March 16.69 0.00 16.69 29.48 19.83 0.00 0.00 0.00
April 18.83 0.04 18.80 42.22 12.76 0.00 0.00 0.00
May 20.84 0.49 20.34 60.85 4.26 0.00 0.00 0.00
June 21.67 0.88 20.78 67.93 1.91 0.00 0.00 0.00
July 20.19 0.38 19.80 73.96 0.34 0.00 0.00 0.00
August 19.38 0.13 19.25 73.72 0.22 0.00 0.00 0.00
September 17.76 0.00 17.76 55.40 2.91 0.00 0.00 0.00
October 15.71 0.00 15.71 40.17 8.85 0.00 0.00 0.00
November 13.43 0.00 13.43 26.12 17.98 0.00 0.00 0.00
December 11.78 0.00 11.78 15.18 28.45 0.00 0.00 0.00
                 
Annual Sum or Average 16.96 0.16 16.80 43.38 13.03 0.00 0.00 0.00
Minimum of Months 11.78 0.00 11.78 13.91 0.22 0.00 0.00 0.00
Maximum of Months 21.67 0.88 20.78 73.96 32.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.62 0.00 12.62 13.91 32.69 0.00 0.00 0.00
February 14.50 0.00 14.50 19.91 26.90 0.00 0.00 0.00
March 16.69 0.00 16.69 29.48 19.83 0.00 0.00 0.00
April 18.80 0.03 18.77 42.17 12.78 0.00 0.00 0.00
May 20.77 0.47 20.29 60.67 4.25 0.00 0.00 0.00
June 21.64 0.87 20.76 67.84 1.91 0.00 0.00 0.00
July 20.14 0.37 19.77 73.85 0.34 0.00 0.00 0.00
August 19.32 0.12 19.20 73.57 0.22 0.00 0.00 0.00
September 17.76 0.00 17.76 55.40 2.91 0.00 0.00 0.00
October 15.70 0.00 15.70 40.17 8.85 0.00 0.00 0.00
November 13.43 0.00 13.43 26.12 17.98 0.00 0.00 0.00
December 11.78 0.00 11.78 15.18 28.45 0.00 0.00 0.00
                 
Annual Sum or Average 16.94 0.16 16.78 43.33 13.03 0.00 0.00 0.00
Minimum of Months 11.78 0.00 11.78 13.91 0.22 0.00 0.00 0.00
Maximum of Months 21.64 0.87 20.76 73.85 32.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.62 0.00 12.62 13.91 32.69 0.00 0.00 0.00
February 14.50 0.00 14.50 19.91 26.90 0.00 0.00 0.00
March 16.69 0.00 16.69 29.48 19.83 0.00 0.00 0.00
April 18.80 0.03 18.77 42.17 12.78 0.00 0.00 0.00
May 20.77 0.47 20.29 60.67 4.25 0.00 0.00 0.00
June 21.64 0.87 20.76 67.84 1.91 0.00 0.00 0.00
July 20.14 0.37 19.77 73.85 0.34 0.00 0.00 0.00
August 19.32 0.12 19.20 73.57 0.22 0.00 0.00 0.00
September 17.76 0.00 17.75 55.40 2.91 0.00 0.00 0.00
October 15.70 0.00 15.70 40.17 8.85 0.00 0.00 0.00
November 13.43 0.00 13.43 26.12 17.98 0.00 0.00 0.00
December 11.78 0.00 11.78 15.18 28.45 0.00 0.00 0.00
                 
Annual Sum or Average 16.94 0.16 16.78 43.33 13.03 0.00 0.00 0.00
Minimum of Months 11.78 0.00 11.78 13.91 0.22 0.00 0.00 0.00
Maximum of Months 21.64 0.87 20.76 73.85 32.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.62 0.00 12.62 13.91 32.69 0.00 0.00 0.00
February 14.50 0.00 14.50 19.91 26.90 0.00 0.00 0.00
March 16.69 0.00 16.69 29.48 19.83 0.00 0.00 0.00
April 18.80 0.03 18.77 42.17 12.78 0.00 0.00 0.00
May 20.77 0.47 20.29 60.67 4.25 0.00 0.00 0.00
June 21.64 0.87 20.76 67.84 1.91 0.00 0.00 0.00
July 20.14 0.37 19.77 73.85 0.34 0.00 0.00 0.00
August 19.32 0.12 19.20 73.57 0.22 0.00 0.00 0.00
September 17.76 0.00 17.76 55.40 2.91 0.00 0.00 0.00
October 15.70 0.00 15.70 40.17 8.85 0.00 0.00 0.00
November 13.43 0.00 13.43 26.12 17.98 0.00 0.00 0.00
December 11.78 0.00 11.78 15.18 28.45 0.00 0.00 0.00
                 
Annual Sum or Average 16.94 0.16 16.78 43.33 13.03 0.00 0.00 0.00
Minimum of Months 11.78 0.00 11.78 13.91 0.22 0.00 0.00 0.00
Maximum of Months 21.64 0.87 20.76 73.85 32.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.62 0.00 12.62 13.91 32.69 0.00 0.00 0.00
February 14.50 0.00 14.50 19.91 26.90 0.00 0.00 0.00
March 16.69 0.00 16.69 29.48 19.83 0.00 0.00 0.00
April 18.80 0.03 18.77 42.17 12.78 0.00 0.00 0.00
May 20.77 0.47 20.29 60.67 4.25 0.00 0.00 0.00
June 21.64 0.87 20.76 67.84 1.91 0.00 0.00 0.00
July 20.14 0.37 19.77 73.85 0.34 0.00 0.00 0.00
August 19.32 0.12 19.20 73.57 0.22 0.00 0.00 0.00
September 17.76 0.00 17.76 55.41 2.91 0.00 0.00 0.00
October 15.70 0.00 15.70 40.17 8.85 0.00 0.00 0.00
November 13.43 0.00 13.43 26.12 17.98 0.00 0.00 0.00
December 11.78 0.00 11.78 15.18 28.45 0.00 0.00 0.00
                 
Annual Sum or Average 16.94 0.16 16.78 43.33 13.03 0.00 0.00 0.00
Minimum of Months 11.78 0.00 11.78 13.91 0.22 0.00 0.00 0.00
Maximum of Months 21.64 0.87 20.76 73.85 32.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.62 0.00 12.62 13.91 32.70 0.00 0.00 0.00
February 14.50 0.00 14.50 19.91 26.91 0.00 0.00 0.00
March 16.69 0.00 16.69 29.48 19.83 0.00 0.00 0.00
April 18.84 0.04 18.80 42.25 12.78 0.00 0.00 0.00
May 20.83 0.49 20.34 60.83 4.26 0.00 0.00 0.00
June 21.67 0.89 20.79 67.93 1.91 0.00 0.00 0.00
July 20.19 0.38 19.80 73.96 0.34 0.00 0.00 0.00
August 19.38 0.13 19.25 73.72 0.22 0.00 0.00 0.00
September 17.76 0.00 17.76 55.41 2.91 0.00 0.00 0.00
October 15.71 0.00 15.71 40.17 8.85 0.00 0.00 0.00
November 13.43 0.00 13.43 26.12 17.98 0.00 0.00 0.00
December 11.78 0.00 11.78 15.18 28.45 0.00 0.00 0.00
                 
Annual Sum or Average 16.96 0.16 16.80 43.38 13.03 0.00 0.00 0.00
Minimum of Months 11.78 0.00 11.78 13.91 0.22 0.00 0.00 0.00
Maximum of Months 21.67 0.89 20.79 73.96 32.70 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.27 6.49 15.77 31.33 33.47 0.00 0.00 0.00
February 25.18 7.18 18.00 39.56 27.61 0.00 0.00 0.00
March 29.66 8.75 20.91 53.59 20.79 0.00 0.00 0.00
April 32.29 9.00 23.30 67.42 13.93 0.00 0.00 0.00
May 34.87 10.18 24.69 87.02 5.04 0.00 0.00 0.00
June 36.02 11.08 24.94 94.42 2.19 0.00 0.00 0.00
July 32.84 9.02 23.82 97.13 0.42 0.00 0.00 0.00
August 34.11 10.20 23.91 100.66 0.30 0.00 0.00 0.00
September 32.61 10.13 22.48 83.01 3.47 0.00 0.00 0.00
October 29.25 9.44 19.81 65.63 9.92 0.00 0.00 0.00
November 25.35 8.38 16.97 48.71 19.31 0.00 0.00 0.00
December 21.24 6.52 14.72 32.80 29.34 0.00 0.00 0.00
                 
Annual Sum or Average 29.66 8.87 20.79 66.92 13.75 0.00 0.00 0.00
Minimum of Months 21.24 6.49 14.72 31.33 0.30 0.00 0.00 0.00
Maximum of Months 36.02 11.08 24.94 100.66 33.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.26 6.49 15.77 31.32 33.47 0.00 0.00 0.00
February 25.18 7.18 18.00 39.55 27.61 0.00 0.00 0.00
March 29.65 8.75 20.91 53.59 20.79 0.00 0.00 0.00
April 32.29 9.00 23.30 67.42 13.92 0.00 0.00 0.00
May 34.87 10.18 24.69 87.01 5.04 0.00 0.00 0.00
June 36.02 11.08 24.94 94.42 2.19 0.00 0.00 0.00
July 32.84 9.02 23.82 97.13 0.42 0.00 0.00 0.00
August 34.11 10.20 23.90 100.66 0.30 0.00 0.00 0.00
September 32.60 10.13 22.48 83.01 3.47 0.00 0.00 0.00
October 29.25 9.44 19.81 65.62 9.92 0.00 0.00 0.00
November 25.35 8.38 16.97 48.71 19.31 0.00 0.00 0.00
December 21.23 6.51 14.72 32.78 29.34 0.00 0.00 0.00
                 
Annual Sum or Average 29.65 8.87 20.79 66.92 13.75 0.00 0.00 0.00
Minimum of Months 21.23 6.49 14.72 31.32 0.30 0.00 0.00 0.00
Maximum of Months 36.02 11.08 24.94 100.66 33.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.26 6.49 15.77 31.32 33.47 0.00 0.00 0.00
February 25.18 7.18 18.00 39.55 27.61 0.00 0.00 0.00
March 29.65 8.75 20.91 53.59 20.79 0.00 0.00 0.00
April 32.29 9.00 23.30 67.42 13.92 0.00 0.00 0.00
May 34.87 10.18 24.69 87.01 5.04 0.00 0.00 0.00
June 36.02 11.08 24.94 94.42 2.19 0.00 0.00 0.00
July 32.84 9.02 23.82 97.13 0.42 0.00 0.00 0.00
August 34.11 10.20 23.90 100.66 0.30 0.00 0.00 0.00
September 32.60 10.13 22.48 83.01 3.47 0.00 0.00 0.00
October 29.25 9.44 19.81 65.62 9.92 0.00 0.00 0.00
November 25.35 8.38 16.97 48.71 19.31 0.00 0.00 0.00
December 21.23 6.51 14.72 32.78 29.34 0.00 0.00 0.00
                 
Annual Sum or Average 29.65 8.87 20.79 66.92 13.75 0.00 0.00 0.00
Minimum of Months 21.23 6.49 14.72 31.32 0.30 0.00 0.00 0.00
Maximum of Months 36.02 11.08 24.94 100.66 33.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.26 6.49 15.77 31.32 33.47 0.00 0.00 0.00
February 25.18 7.18 18.00 39.56 27.61 0.00 0.00 0.00
March 29.66 8.75 20.91 53.59 20.79 0.00 0.00 0.00
April 32.29 9.00 23.30 67.42 13.93 0.00 0.00 0.00
May 34.87 10.18 24.69 87.02 5.04 0.00 0.00 0.00
June 36.02 11.08 24.94 94.42 2.19 0.00 0.00 0.00
July 32.84 9.02 23.82 97.13 0.42 0.00 0.00 0.00
August 34.11 10.20 23.91 100.66 0.30 0.00 0.00 0.00
September 32.61 10.13 22.48 83.01 3.47 0.00 0.00 0.00
October 29.25 9.44 19.81 65.63 9.92 0.00 0.00 0.00
November 25.35 8.38 16.97 48.71 19.31 0.00 0.00 0.00
December 21.23 6.51 14.72 32.78 29.34 0.00 0.00 0.00
                 
Annual Sum or Average 29.66 8.87 20.79 66.92 13.75 0.00 0.00 0.00
Minimum of Months 21.23 6.49 14.72 31.32 0.30 0.00 0.00 0.00
Maximum of Months 36.02 11.08 24.94 100.66 33.47 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114247E+09 54760641.60 59486022.69 0.180781E+09 87464405.28
February 93235981.51 38183583.93 55052397.58 0.157354E+09 66633550.40
March 73068050.49 16239044.52 56829005.97 0.137248E+09 55396607.93
April 48468737.19 20873.13 48447864.06 0.107967E+09 33951880.33
May 52741152.68 0.00 52741152.68 0.155627E+09 11840403.34
June 51334512.70 0.00 51334512.70 0.164803E+09 4744683.73
July 51630802.91 12.24 51630790.67 0.187961E+09 902367.77
August 51768249.49 581108.71 51187140.77 0.190991E+09 689749.86
September 61243171.80 8746736.09 52496435.71 0.172962E+09 8313027.13
October 0.100956E+09 38592077.57 62364036.16 0.225254E+09 25880255.39
November 0.118240E+09 57949152.84 60290953.06 0.225645E+09 49683058.11
December 0.113807E+09 57271237.76 56535333.55 0.190054E+09 77675822.45
           
Annual Sum or Average 0.930740E+09 0.272344E+09 0.658396E+09 0.209665E+10 0.423176E+09
Minimum of Months 48468737.19 0.00 48447864.06 0.107967E+09 689749.86
Maximum of Months 0.118240E+09 57949152.84 62364036.16 0.225645E+09 87464405.28



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114244E+09 54760641.60 59483501.91 0.180777E+09 87461952.73
February 93233450.21 38183583.93 55049866.28 0.157350E+09 66631576.99
March 73009314.42 16219480.30 56789834.12 0.137121E+09 55409553.19
April 48386647.23 8824.82 48377822.41 0.107780E+09 33949851.84
May 52738037.32 0.00 52738037.32 0.155624E+09 11839149.25
June 51331665.05 0.00 51331665.05 0.164801E+09 4743877.55
July 51627840.60 0.00 51627840.60 0.187959E+09 902114.65
August 51746726.78 572513.80 51174212.99 0.190937E+09 689532.36
September 60970434.95 8674846.23 52295588.72 0.172302E+09 8311900.73
October 0.100953E+09 38592077.57 62361334.24 0.225251E+09 25878110.54
November 0.118238E+09 57949152.84 60288556.40 0.225642E+09 49680477.77
December 0.113804E+09 57271237.76 56532979.41 0.190051E+09 77673347.73
           
Annual Sum or Average 0.930284E+09 0.272232E+09 0.658051E+09 0.209560E+10 0.423171E+09
Minimum of Months 48386647.23 0.00 48377822.41 0.107780E+09 689532.36
Maximum of Months 0.118238E+09 57949152.84 62361334.24 0.225642E+09 87461952.73



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114244E+09 54760641.60 59483501.91 0.180777E+09 87461952.73
February 93233450.21 38183583.93 55049866.28 0.157350E+09 66631576.99
March 73008991.98 16219433.42 56789558.56 0.137121E+09 55410144.60
April 48386647.23 8824.82 48377822.41 0.107780E+09 33949851.84
May 52738037.32 0.00 52738037.32 0.155624E+09 11839149.25
June 51331665.05 0.00 51331665.05 0.164801E+09 4743877.55
July 51627840.60 0.00 51627840.60 0.187959E+09 902114.65
August 51746691.30 572478.31 51174212.99 0.190937E+09 689532.36
September 60965009.77 8674577.41 52290432.36 0.172291E+09 8311900.73
October 0.100953E+09 38592077.57 62361334.24 0.225251E+09 25878110.54
November 0.118238E+09 57949152.84 60288556.40 0.225642E+09 49680477.77
December 0.113804E+09 57271237.76 56532979.41 0.190051E+09 77673347.73
           
Annual Sum or Average 0.930278E+09 0.272232E+09 0.658046E+09 0.209559E+10 0.423172E+09
Minimum of Months 48386647.23 0.00 48377822.41 0.107780E+09 689532.36
Maximum of Months 0.118238E+09 57949152.84 62361334.24 0.225642E+09 87461952.73



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114244E+09 54760641.60 59483501.91 0.180777E+09 87461952.73
February 93233450.21 38183583.93 55049866.28 0.157350E+09 66631576.99
March 73008991.98 16219433.42 56789558.56 0.137121E+09 55410144.60
April 48386647.23 8824.82 48377822.41 0.107780E+09 33949851.84
May 52738037.32 0.00 52738037.32 0.155624E+09 11839149.25
June 51331665.05 0.00 51331665.05 0.164801E+09 4743877.55
July 51627840.60 0.00 51627840.60 0.187959E+09 902114.65
August 51746691.30 572478.31 51174212.99 0.190937E+09 689532.36
September 60965009.77 8674577.41 52290432.36 0.172291E+09 8311900.73
October 0.100953E+09 38592077.57 62361334.24 0.225251E+09 25878110.54
November 0.118238E+09 57949152.84 60288556.40 0.225642E+09 49680477.77
December 0.113804E+09 57271237.76 56532979.41 0.190051E+09 77673347.73
           
Annual Sum or Average 0.930278E+09 0.272232E+09 0.658046E+09 0.209559E+10 0.423172E+09
Minimum of Months 48386647.23 0.00 48377822.41 0.107780E+09 689532.36
Maximum of Months 0.118238E+09 57949152.84 62361334.24 0.225642E+09 87461952.73



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114244E+09 54760641.60 59483501.91 0.180777E+09 87461952.73
February 93233450.21 38183583.93 55049866.28 0.157350E+09 66631576.99
March 73009127.52 16219453.99 56789673.52 0.137121E+09 55409820.34
April 48386647.23 8824.82 48377822.41 0.107780E+09 33949851.84
May 52738037.32 0.00 52738037.32 0.155624E+09 11839149.25
June 51331665.05 0.00 51331665.05 0.164801E+09 4743877.55
July 51627840.60 0.00 51627840.60 0.187959E+09 902114.65
August 51746717.22 572504.23 51174212.99 0.190937E+09 689532.36
September 60972081.09 8674867.39 52297213.70 0.172304E+09 8309523.98
October 0.100953E+09 38592077.57 62361334.24 0.225251E+09 25878110.54
November 0.118238E+09 57949152.84 60288556.40 0.225642E+09 49680477.77
December 0.113804E+09 57271237.76 56532979.41 0.190051E+09 77673347.73
           
Annual Sum or Average 0.930285E+09 0.272232E+09 0.658053E+09 0.209560E+10 0.423169E+09
Minimum of Months 48386647.23 0.00 48377822.41 0.107780E+09 689532.36
Maximum of Months 0.118238E+09 57949152.84 62361334.24 0.225642E+09 87461952.73



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.114247E+09 54760641.60 59486022.56 0.180781E+09 87464405.15
February 93235981.38 38183583.93 55052397.45 0.157354E+09 66633550.30
March 73056279.22 16234445.99 56821833.23 0.137168E+09 55346856.12
April 48462993.81 21377.17 48441616.65 0.107956E+09 33950369.85
May 52741152.52 0.00 52741152.52 0.155627E+09 11840403.28
June 51334512.55 0.00 51334512.55 0.164803E+09 4744683.69
July 51630813.12 22.60 51630790.52 0.187961E+09 902367.76
August 51766117.02 579962.94 51186154.08 0.190985E+09 689749.85
September 61256672.13 8745703.45 52510968.68 0.172981E+09 8305051.79
October 0.100956E+09 38592077.57 62364036.02 0.225254E+09 25880255.28
November 0.118240E+09 57949152.84 60290952.93 0.225645E+09 49683057.98
December 0.113807E+09 57271237.76 56535333.43 0.190054E+09 77675822.32
           
Annual Sum or Average 0.930734E+09 0.272338E+09 0.658396E+09 0.209657E+10 0.423117E+09
Minimum of Months 48462993.81 0.00 48441616.65 0.107956E+09 689749.85
Maximum of Months 0.118240E+09 57949152.84 62364036.02 0.225645E+09 87464405.15



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.161829E+09 76844830.42 84984338.42 0.255411E+09 0.123121E+09
February 0.137005E+09 56706650.96 80298846.90 0.231611E+09 93876800.93
March 0.117873E+09 30557739.25 87315148.84 0.223350E+09 78345548.67
April 77974394.42 3609637.78 74364756.64 0.172234E+09 48602505.58
May 75845889.72 0.00 75845889.72 0.218272E+09 17363084.45
June 73707182.24 0.00 73707182.24 0.230252E+09 7213060.14
July 74186536.67 0.00 74186536.67 0.262365E+09 1451193.06
August 75605975.83 1538611.37 74067364.45 0.269324E+09 1131628.61
September 0.101705E+09 19909372.17 81795557.50 0.274427E+09 12398291.95
October 0.156523E+09 62825631.56 93697405.70 0.343691E+09 37541203.09
November 0.167795E+09 81632349.20 86163033.99 0.318053E+09 70848355.01
December 0.160922E+09 80237747.69 80683929.28 0.267655E+09 0.109584E+09
           
Annual Sum or Average 0.138097E+10 0.413863E+09 0.967110E+09 0.306664E+10 0.601477E+09
Minimum of Months 73707182.24 0.00 73707182.24 0.172234E+09 1131628.61
Maximum of Months 0.167795E+09 81632349.20 93697405.70 0.343691E+09 0.123121E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60899030.81 18740989.76 42158041.05 79968308.25 83330464.04
February 59381893.55 16135466.79 43246426.75 88546388.21 62572289.11
March 71946938.83 17544303.12 54402635.72 0.126600E+09 51656018.05
April 84108792.14 23970847.62 60137944.52 0.173412E+09 33163442.58
May 97447390.17 30608738.83 66838651.34 0.238866E+09 11913520.02
June 91727359.82 27272516.34 64454843.48 0.240505E+09 5209507.96
July 87945918.47 24295877.75 63650040.72 0.259772E+09 982604.98
August 90763587.80 27116597.45 63646990.35 0.268650E+09 647777.70
September 83392786.18 25462573.51 57930212.67 0.211840E+09 7790041.57
October 79060370.29 25839941.96 53220428.32 0.174671E+09 24188950.23
November 64535163.88 20612337.86 43922826.02 0.119489E+09 46356622.18
December 53957532.71 15042630.12 38914902.59 76705577.20 73638309.93
           
Annual Sum or Average 0.925167E+09 0.272643E+09 0.652524E+09 0.205903E+10 0.401450E+09
Minimum of Months 53957532.71 15042630.12 38914902.59 76705577.20 647777.70
Maximum of Months 97447390.17 30608738.83 66838651.34 0.268650E+09 83330464.04



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60896510.15 18740989.76 42155520.39 79965066.35 83328015.05
February 59379362.38 16135466.79 43243895.58 88543121.70 62570341.33
March 71943822.79 17544303.12 54399519.67 0.126596E+09 51653772.21
April 84105628.08 23970847.62 60134780.46 0.173409E+09 33161400.49
May 97444274.97 30608738.83 66835536.13 0.238863E+09 11912254.49
June 91724512.32 27272516.34 64451995.98 0.240503E+09 5208614.14
July 87942968.55 24295877.75 63647090.81 0.259770E+09 982335.00
August 90760601.11 27116597.45 63644003.66 0.268648E+09 647578.05
September 83389982.20 25462573.51 57927408.69 0.211838E+09 7789002.65
October 79057668.51 25839941.96 53217726.54 0.174669E+09 24186930.24
November 64532767.35 20612337.86 43920429.49 0.119487E+09 46354085.02
December 53955178.69 15042630.12 38912548.57 76702599.50 73635866.71
           
Annual Sum or Average 0.925133E+09 0.272643E+09 0.652490E+09 0.205899E+10 0.401430E+09
Minimum of Months 53955178.69 15042630.12 38912548.57 76702599.50 647578.05
Maximum of Months 97444274.97 30608738.83 66835536.13 0.268648E+09 83328015.05



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60896510.15 18740989.76 42155520.39 79965066.35 83328015.05
February 59379362.38 16135466.79 43243895.58 88543121.70 62570341.33
March 71943822.79 17544303.12 54399519.67 0.126596E+09 51653772.21
April 84105628.08 23970847.62 60134780.46 0.173409E+09 33161400.49
May 97444274.97 30608738.83 66835536.13 0.238863E+09 11912254.49
June 91724512.32 27272516.34 64451995.98 0.240503E+09 5208614.14
July 87942968.55 24295877.75 63647090.81 0.259770E+09 982335.00
August 90760601.11 27116597.45 63644003.66 0.268648E+09 647578.05
September 83389982.20 25462573.51 57927408.69 0.211838E+09 7789002.65
October 79057668.51 25839941.96 53217726.54 0.174669E+09 24186930.24
November 64532767.35 20612337.86 43920429.49 0.119487E+09 46354085.02
December 53955178.69 15042630.12 38912548.57 76702599.50 73635866.71
           
Annual Sum or Average 0.925133E+09 0.272643E+09 0.652490E+09 0.205899E+10 0.401430E+09
Minimum of Months 53955178.69 15042630.12 38912548.57 76702599.50 647578.05
Maximum of Months 97444274.97 30608738.83 66835536.13 0.268648E+09 83328015.05



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60906491.19 18743367.15 42163124.04 79986705.84 83330464.17
February 59381893.68 16135466.79 43246426.88 88546388.38 62572289.21
March 71946938.99 17544303.12 54402635.88 0.126600E+09 51656018.17
April 84108792.31 23970847.62 60137944.69 0.173412E+09 33163442.69
May 97447390.33 30608738.83 66838651.50 0.238866E+09 11913520.08
June 91727359.97 27272516.34 64454843.63 0.240505E+09 5209508.01
July 87945918.62 24295877.75 63650040.88 0.259772E+09 982604.99
August 90763587.95 27116597.45 63646990.51 0.268650E+09 647777.71
September 83392786.33 25462573.51 57930212.81 0.211840E+09 7790041.62
October 79060370.43 25839941.96 53220428.46 0.174671E+09 24188950.34
November 64536807.80 20612933.90 43923873.91 0.119494E+09 46356622.31
December 53973845.78 15047811.83 38926033.95 76746943.97 73638310.06
           
Annual Sum or Average 0.925192E+09 0.272651E+09 0.652541E+09 0.205909E+10 0.401450E+09
Minimum of Months 53973845.78 15047811.83 38926033.95 76746943.97 647777.71
Maximum of Months 97447390.33 30608738.83 66838651.50 0.268650E+09 83330464.17



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33812708.35 0.00 33812708.35 37259609.69 87570851.32
February 35079433.14 0.00 35079433.14 48173317.30 65089293.24
March 44703855.60 0.00 44703855.60 78964259.92 53116479.81
April 48818375.63 91470.41 48726905.21 0.109444E+09 33063656.30
May 55809306.38 1320808.94 54488497.44 0.162990E+09 11397107.10
June 56165374.15 2291372.16 53874002.00 0.176065E+09 4953557.75
July 54064100.08 1028337.63 53035762.44 0.198098E+09 923312.68
August 51905865.48 352744.45 51553121.03 0.197448E+09 588366.47
September 46036352.97 5021.91 46031331.05 0.143609E+09 7542618.04
October 42065302.28 0.00 42065302.28 0.107588E+09 23711627.62
November 34809516.82 0.00 34809516.82 67700988.33 46599938.46
December 31558595.27 0.00 31558595.27 40661951.19 76204299.30
           
Annual Sum or Average 0.534829E+09 5089755.50 0.529739E+09 0.136800E+10 0.410761E+09
Minimum of Months 31558595.27 0.00 31558595.27 37259609.69 588366.47
Maximum of Months 56165374.15 2291372.16 54488497.44 0.198098E+09 87570851.32



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33810187.57 0.00 33810187.57 37256475.90 87568544.35
February 35076901.84 0.00 35076901.84 48170127.12 65087431.75
March 44700739.40 0.00 44700739.40 78960233.57 53114290.51
April 48724404.14 81314.78 48643089.36 0.109302E+09 33130311.64
May 55617081.28 1259574.06 54357507.22 0.162506E+09 11395842.69
June 56078405.14 2260580.01 53817825.13 0.175852E+09 4952668.32
July 53940553.44 992437.56 52948115.88 0.197801E+09 923038.86
August 51739084.93 314910.93 51424174.00 0.197047E+09 588183.29
September 46030103.74 4966.85 46025136.90 0.143600E+09 7541699.48
October 42062600.37 0.00 42062600.37 0.107585E+09 23709589.33
November 34807120.16 0.00 34807120.16 67698402.31 46597416.91
December 31556241.12 0.00 31556241.12 40659080.35 76201914.91
           
Annual Sum or Average 0.534143E+09 4913784.18 0.529230E+09 0.136644E+10 0.410811E+09
Minimum of Months 31556241.12 0.00 31556241.12 37256475.90 588183.29
Maximum of Months 56078405.14 2260580.01 54357507.22 0.197801E+09 87568544.35



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33810187.57 0.00 33810187.57 37256475.90 87568544.35
February 35076901.84 0.00 35076901.84 48170127.12 65087431.75
March 44700739.40 0.00 44700739.40 78960233.57 53114290.51
April 48721342.74 80898.92 48640443.83 0.109298E+09 33133734.69
May 55617081.28 1259574.06 54357507.22 0.162506E+09 11395842.69
June 56078405.14 2260580.01 53817825.13 0.175852E+09 4952668.32
July 53940553.44 992437.56 52948115.88 0.197801E+09 923038.86
August 51737513.00 314900.96 51422612.04 0.197044E+09 588183.29
September 46024460.08 4792.00 46019668.08 0.143589E+09 7542242.99
October 42062600.37 0.00 42062600.37 0.107585E+09 23709589.33
November 34807120.16 0.00 34807120.16 67698402.31 46597416.91
December 31556241.12 0.00 31556241.12 40659080.35 76201914.91
           
Annual Sum or Average 0.534133E+09 4913183.51 0.529220E+09 0.136642E+10 0.410815E+09
Minimum of Months 31556241.12 0.00 31556241.12 37256475.90 588183.29
Maximum of Months 56078405.14 2260580.01 54357507.22 0.197801E+09 87568544.35



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33810187.57 0.00 33810187.57 37256475.90 87568544.35
February 35076901.84 0.00 35076901.84 48170127.12 65087431.75
March 44700739.40 0.00 44700739.40 78960233.57 53114290.51
April 48721342.74 80898.92 48640443.83 0.109298E+09 33133734.69
May 55617081.28 1259574.06 54357507.22 0.162506E+09 11395842.69
June 56078405.14 2260580.01 53817825.13 0.175852E+09 4952668.32
July 53940553.44 992437.56 52948115.88 0.197801E+09 923038.86
August 51738459.97 314915.13 51423544.84 0.197046E+09 588183.29
September 46026276.69 4858.76 46021417.92 0.143594E+09 7542795.17
October 42062600.37 0.00 42062600.37 0.107585E+09 23709589.33
November 34807120.16 0.00 34807120.16 67698402.31 46597416.91
December 31556241.12 0.00 31556241.12 40659080.35 76201914.91
           
Annual Sum or Average 0.534136E+09 4913264.44 0.529223E+09 0.136643E+10 0.410815E+09
Minimum of Months 31556241.12 0.00 31556241.12 37256475.90 588183.29
Maximum of Months 56078405.14 2260580.01 54357507.22 0.197801E+09 87568544.35



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33810187.57 0.00 33810187.57 37256475.90 87568544.35
February 35076901.84 0.00 35076901.84 48170127.12 65087431.75
March 44700739.40 0.00 44700739.40 78960233.57 53114290.51
April 48724557.35 81376.04 48643181.31 0.109305E+09 33133734.65
May 55617081.28 1259574.06 54357507.22 0.162506E+09 11395842.69
June 56078405.14 2260580.01 53817825.13 0.175852E+09 4952668.32
July 53940553.44 992437.56 52948115.88 0.197801E+09 923038.86
August 51741411.69 314943.57 51426468.12 0.197051E+09 588183.29
September 46034230.56 5122.17 46029108.39 0.143610E+09 7542802.18
October 42062600.37 0.00 42062600.37 0.107585E+09 23709589.33
November 34807120.16 0.00 34807120.16 67698402.31 46597416.91
December 31556241.12 0.00 31556241.12 40659080.35 76201914.91
           
Annual Sum or Average 0.534150E+09 4914033.41 0.529236E+09 0.136645E+10 0.410815E+09
Minimum of Months 31556241.12 0.00 31556241.12 37256475.90 588183.29
Maximum of Months 56078405.14 2260580.01 54357507.22 0.197801E+09 87568544.35



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33812708.22 0.00 33812708.22 37259609.53 87570851.20
February 35079433.01 0.00 35079433.01 48173317.14 65089293.14
March 44703855.44 0.00 44703855.44 78964259.71 53116479.69
April 48823725.29 93633.89 48730091.40 0.109522E+09 33135573.26
May 55795282.52 1311497.37 54483785.15 0.162934E+09 11397107.04
June 56169765.05 2294047.63 53875717.42 0.176072E+09 4953557.71
July 54065068.44 1029938.91 53035129.52 0.198095E+09 923312.67
August 51910062.03 353486.40 51556575.63 0.197447E+09 588366.46
September 46040993.46 5196.58 46035796.88 0.143620E+09 7543840.54
October 42065302.14 0.00 42065302.14 0.107588E+09 23711627.51
November 34809516.70 0.00 34809516.70 67700988.20 46599938.33
December 31558595.14 0.00 31558595.14 40661951.04 76204299.18
           
Annual Sum or Average 0.534834E+09 5087800.80 0.529747E+09 0.136804E+10 0.410834E+09
Minimum of Months 31558595.14 0.00 31558595.14 37259609.53 588366.46
Maximum of Months 56169765.05 2294047.63 54483785.15 0.198095E+09 87570851.20



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59636974.42 17388945.71 42248028.71 83908028.25 89636622.91
February 60920520.79 17370013.23 43550507.56 95693350.66 66784462.24
March 79430028.57 23424346.85 56005681.72 0.143538E+09 55680875.43
April 83707133.36 23316350.78 60390782.58 0.174748E+09 36093959.43
May 93399365.73 27274730.21 66124635.52 0.233063E+09 13506562.92
June 93371908.23 28721762.72 64650145.51 0.244738E+09 5678799.18
July 87971149.54 24158511.27 63812638.27 0.260159E+09 1115262.28
August 91358901.29 27331260.73 64027640.56 0.269606E+09 792457.72
September 84514692.76 26246104.26 58268588.50 0.215154E+09 8986898.52
October 78337500.20 25286757.87 53050742.33 0.175771E+09 26582333.22
November 65699010.99 21709204.05 43989806.93 0.126259E+09 50052351.43
December 56880424.39 17450146.70 39430277.68 87844207.86 78587274.71
           
Annual Sum or Average 0.935228E+09 0.279678E+09 0.655549E+09 0.211048E+10 0.433498E+09
Minimum of Months 56880424.39 17370013.23 39430277.68 83908028.25 792457.72
Maximum of Months 93399365.73 28721762.72 66124635.52 0.269606E+09 89636622.91



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59627789.66 17386948.86 42240840.80 83888708.61 89634360.01
February 60917989.63 17370013.23 43547976.39 95690134.68 66782607.08
March 79426912.53 23424346.85 56002565.68 0.143534E+09 55678709.63
April 83703969.29 23316350.78 60387618.52 0.174744E+09 36091881.92
May 93396250.52 27274730.21 66121520.31 0.233060E+09 13505179.32
June 93369060.73 28721762.72 64647298.01 0.244736E+09 5677873.46
July 87968199.63 24158511.27 63809688.36 0.260157E+09 1114955.94
August 91355914.60 27331260.73 64024653.87 0.269604E+09 792213.37
September 84511888.78 26246104.26 58265784.52 0.215152E+09 8985691.18
October 78334798.42 25286757.87 53048040.55 0.175768E+09 26580132.14
November 65694419.32 21708635.66 43985783.67 0.126252E+09 50049718.49
December 56861546.03 17444379.46 39417166.57 87799672.25 78584885.39
           
Annual Sum or Average 0.935169E+09 0.279670E+09 0.655499E+09 0.211038E+10 0.433478E+09
Minimum of Months 56861546.03 17370013.23 39417166.57 83888708.61 792213.37
Maximum of Months 93396250.52 28721762.72 66121520.31 0.269604E+09 89634360.01



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59627789.66 17386948.86 42240840.80 83888708.61 89634360.01
February 60917989.63 17370013.23 43547976.39 95690134.68 66782607.08
March 79426912.53 23424346.85 56002565.68 0.143534E+09 55678709.63
April 83703969.29 23316350.78 60387618.52 0.174744E+09 36091881.92
May 93396250.52 27274730.21 66121520.31 0.233060E+09 13505179.32
June 93369060.73 28721762.72 64647298.01 0.244736E+09 5677873.46
July 87968199.63 24158511.27 63809688.36 0.260157E+09 1114955.94
August 91355914.60 27331260.73 64024653.87 0.269604E+09 792213.37
September 84511888.78 26246104.26 58265784.52 0.215152E+09 8985691.18
October 78334798.42 25286757.87 53048040.55 0.175768E+09 26580132.14
November 65694419.32 21708635.66 43985783.67 0.126252E+09 50049718.49
December 56861546.03 17444379.46 39417166.57 87799672.25 78584885.39
           
Annual Sum or Average 0.935169E+09 0.279670E+09 0.655499E+09 0.211038E+10 0.433478E+09
Minimum of Months 56861546.03 17370013.23 39417166.57 83888708.61 792213.37
Maximum of Months 93396250.52 28721762.72 66121520.31 0.269604E+09 89634360.01



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 59630310.44 17386948.86 42243361.59 83891802.37 89636623.03
February 60920520.93 17370013.23 43550507.69 95693350.83 66784462.34
March 79430028.74 23424346.85 56005681.89 0.143538E+09 55680875.54
April 83707133.52 23316350.78 60390782.75 0.174748E+09 36093959.54
May 93399365.89 27274730.21 66124635.68 0.233063E+09 13506562.99
June 93371908.38 28721762.72 64650145.66 0.244738E+09 5678799.22
July 87971149.70 24158511.27 63812638.43 0.260159E+09 1115262.29
August 91358901.45 27331260.73 64027640.72 0.269606E+09 792457.73
September 84514692.91 26246104.26 58268588.64 0.215154E+09 8986898.59
October 78337500.34 25286757.87 53050742.47 0.175771E+09 26582333.34
November 65696815.98 21708635.66 43988180.33 0.126254E+09 50052351.56
December 56863900.17 17444379.46 39419520.71 87802547.05 78587274.83
           
Annual Sum or Average 0.935202E+09 0.279670E+09 0.655532E+09 0.211042E+10 0.433498E+09
Minimum of Months 56863900.17 17370013.23 39419520.71 83891802.37 792457.73
Maximum of Months 93399365.89 28721762.72 66124635.68 0.269606E+09 89636623.03



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 500.33 241.90 316.35 151.36 164.98 0.00 0.00
February 485.99 204.06 287.87 118.14 169.73 0.00 0.00
March 390.62 153.34 207.60 47.76 159.84 0.00 0.00
April 316.08 97.34 142.15 1.42 140.73 0.00 0.00
May 430.11 33.00 146.46 0.00 146.46 0.00 0.00
June 470.31 13.76 147.26 0.00 147.26 0.00 0.00
July 519.01 2.56 143.35 0.00 143.35 0.00 0.00
August 528.32 1.96 144.16 1.86 142.30 0.00 0.00
September 505.22 24.01 180.59 27.82 152.77 0.00 0.00
October 632.91 71.98 284.59 109.91 174.68 0.00 0.00
November 645.03 142.33 338.44 165.64 172.80 0.00 0.00
December 525.68 214.91 315.02 158.25 156.77 0.00 0.00
               
Annual Sum or Average 496.01 99.58 220.81 64.92 155.89 0.00 0.00
Minimum of Months 316.08 1.96 142.15 0.00 140.73 0.00 0.00
Maximum of Months 645.03 241.90 338.44 165.64 174.68 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 119.43 124.45 90.95 27.99 62.96 0.00 0.00
February 146.40 103.46 98.18 26.68 71.50 0.00 0.00
March 189.07 77.14 107.45 26.20 81.24 0.00 0.00
April 267.61 51.18 129.80 36.99 92.80 0.00 0.00
May 356.73 17.79 145.53 45.71 99.82 0.00 0.00
June 371.15 8.04 141.55 42.09 99.47 0.00 0.00
July 387.95 1.47 131.34 36.28 95.05 0.00 0.00
August 401.21 0.97 135.55 40.50 95.05 0.00 0.00
September 326.91 12.02 128.69 39.29 89.40 0.00 0.00
October 260.86 36.12 118.07 38.59 79.48 0.00 0.00
November 184.40 71.54 99.59 31.81 67.78 0.00 0.00
December 114.57 109.97 80.59 22.47 58.12 0.00 0.00
               
Annual Sum or Average 261.17 50.92 117.35 34.58 82.76 0.00 0.00
Minimum of Months 114.57 0.97 80.59 22.47 58.12 0.00 0.00
Maximum of Months 401.21 124.45 145.53 45.71 99.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 83.46 196.17 75.74 0.00 75.74 0.00 0.00
February 119.47 161.43 87.00 0.00 87.00 0.00 0.00
March 176.89 118.99 100.14 0.00 100.14 0.00 0.00
April 253.15 76.67 112.86 0.20 112.66 0.00 0.00
May 364.38 25.53 124.73 2.86 121.86 0.00 0.00
June 407.23 11.47 129.88 5.26 124.62 0.00 0.00
July 443.32 2.07 120.93 2.25 118.68 0.00 0.00
August 441.71 1.32 116.03 0.73 115.30 0.00 0.00
September 332.42 17.46 106.56 0.01 106.54 0.00 0.00
October 241.01 53.11 94.23 0.00 94.23 0.00 0.00
November 156.71 107.87 80.57 0.00 80.57 0.00 0.00
December 91.08 170.70 70.69 0.00 70.69 0.00 0.00
               
Annual Sum or Average 260.08 78.16 101.67 0.95 100.72 0.00 0.00
Minimum of Months 83.46 1.32 70.69 0.00 70.69 0.00 0.00
Maximum of Months 443.32 196.17 129.88 5.26 124.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 125.29 133.86 89.05 25.97 63.09 0.00 0.00
February 158.22 110.42 100.73 28.72 72.01 0.00 0.00
March 214.36 83.15 118.62 34.98 83.64 0.00 0.00
April 269.67 55.70 129.18 35.98 93.19 0.00 0.00
May 348.06 20.17 139.48 40.73 98.75 0.00 0.00
June 377.68 8.76 144.09 44.32 99.77 0.00 0.00
July 388.53 1.67 131.38 36.08 95.30 0.00 0.00
August 402.64 1.18 136.44 40.82 95.62 0.00 0.00
September 332.03 13.87 130.42 40.50 89.92 0.00 0.00
October 262.50 39.70 116.99 37.76 79.23 0.00 0.00
November 194.84 77.24 101.38 33.50 67.88 0.00 0.00
December 131.14 117.36 84.93 26.05 58.87 0.00 0.00
               
Annual Sum or Average 267.68 54.98 118.62 35.47 83.15 0.00 0.00
Minimum of Months 125.29 1.18 84.93 25.97 58.87 0.00 0.00
Maximum of Months 402.64 133.86 144.09 44.32 99.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.134008E+10 0.647897E+09 0.847299E+09 0.405409E+09 0.441890E+09 0.00 0.00
February 0.117572E+10 0.493668E+09 0.696411E+09 0.285808E+09 0.410603E+09 0.00 0.00
March 0.104623E+10 0.410712E+09 0.556034E+09 0.127909E+09 0.428125E+09 0.00 0.00
April 0.819274E+09 0.252301E+09 0.368453E+09 3687187.34 0.364766E+09 0.00 0.00
May 0.115201E+10 88392208.05 0.392280E+09 0.00 0.392280E+09 0.00 0.00
June 0.121905E+10 35665510.24 0.381703E+09 0.00 0.381703E+09 0.00 0.00
July 0.139011E+10 6855759.83 0.383960E+09 34.85 0.383959E+09 0.00 0.00
August 0.141504E+10 5259481.18 0.386127E+09 4989657.67 0.381138E+09 0.00 0.00
September 0.130954E+10 62245610.91 0.468077E+09 72100680.16 0.395977E+09 0.00 0.00
October 0.169519E+10 0.192803E+09 0.762249E+09 0.294378E+09 0.467871E+09 0.00 0.00
November 0.167191E+10 0.368931E+09 0.877226E+09 0.429327E+09 0.447899E+09 0.00 0.00
December 0.140797E+10 0.575628E+09 0.843752E+09 0.423865E+09 0.419887E+09 0.00 0.00
               
Annual Sum or Average 0.156421E+11 0.314036E+10 0.696357E+10 0.204747E+10 0.491610E+10 0.00 0.00
Minimum of Months 0.819274E+09 5259481.18 0.368453E+09 0.00 0.364766E+09 0.00 0.00
Maximum of Months 0.169519E+10 0.647897E+09 0.877226E+09 0.429327E+09 0.467871E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.319885E+09 0.333317E+09 0.243599E+09 74966336.43 0.168632E+09 0.00 0.00
February 0.354179E+09 0.250285E+09 0.237523E+09 64541867.18 0.172981E+09 0.00 0.00
March 0.506392E+09 0.206620E+09 0.287782E+09 70177212.46 0.217604E+09 0.00 0.00
April 0.693642E+09 0.132650E+09 0.336429E+09 95883390.49 0.240545E+09 0.00 0.00
May 0.955458E+09 47651549.08 0.389783E+09 0.122435E+09 0.267348E+09 0.00 0.00
June 0.962016E+09 20836244.26 0.366904E+09 0.109090E+09 0.257814E+09 0.00 0.00
July 0.103909E+10 3929879.97 0.351778E+09 97183510.99 0.254594E+09 0.00 0.00
August 0.107459E+10 2590711.51 0.363048E+09 0.108466E+09 0.254582E+09 0.00 0.00
September 0.847355E+09 31158088.49 0.333566E+09 0.101850E+09 0.231715E+09 0.00 0.00
October 0.698680E+09 96751761.06 0.316236E+09 0.103360E+09 0.212876E+09 0.00 0.00
November 0.477956E+09 0.185421E+09 0.258138E+09 82449947.48 0.175688E+09 0.00 0.00
December 0.306858E+09 0.294548E+09 0.215842E+09 60175702.20 0.155666E+09 0.00 0.00
               
Annual Sum or Average 0.823610E+10 0.160576E+10 0.370063E+10 0.109058E+10 0.261005E+10 0.00 0.00
Minimum of Months 0.306858E+09 2590711.51 0.215842E+09 60175702.20 0.155666E+09 0.00 0.00
Maximum of Months 0.107459E+10 0.333317E+09 0.389783E+09 0.122435E+09 0.267348E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.223545E+09 0.525416E+09 0.202866E+09 0.00 0.202866E+09 0.00 0.00
February 0.289027E+09 0.390528E+09 0.210466E+09 0.00 0.210466E+09 0.00 0.00
March 0.473769E+09 0.318690E+09 0.268211E+09 0.00 0.268211E+09 0.00 0.00
April 0.656163E+09 0.198725E+09 0.292534E+09 509592.96 0.292024E+09 0.00 0.00
May 0.975946E+09 68377584.89 0.334073E+09 7670602.56 0.326402E+09 0.00 0.00
June 0.105555E+10 29717788.72 0.336649E+09 13627739.82 0.323021E+09 0.00 0.00
July 0.118740E+10 5538780.79 0.323891E+09 6028026.79 0.317863E+09 0.00 0.00
August 0.118308E+10 3529466.08 0.310772E+09 1965901.44 0.308806E+09 0.00 0.00
September 0.861623E+09 45255555.00 0.276192E+09 29958.27 0.276162E+09 0.00 0.00
October 0.645515E+09 0.142262E+09 0.252381E+09 0.00 0.252381E+09 0.00 0.00
November 0.406196E+09 0.279590E+09 0.208848E+09 0.00 0.208848E+09 0.00 0.00
December 0.243960E+09 0.457216E+09 0.189342E+09 0.00 0.189342E+09 0.00 0.00
               
Annual Sum or Average 0.820177E+10 0.246485E+10 0.320623E+10 29831821.84 0.317639E+10 0.00 0.00
Minimum of Months 0.223545E+09 3529466.08 0.189342E+09 0.00 0.189342E+09 0.00 0.00
Maximum of Months 0.118740E+10 0.525416E+09 0.336649E+09 13627739.82 0.326402E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.335577E+09 0.358542E+09 0.238523E+09 69549792.28 0.168973E+09 0.00 0.00
February 0.382767E+09 0.267134E+09 0.243677E+09 69480052.93 0.174197E+09 0.00 0.00
March 0.574144E+09 0.222719E+09 0.317714E+09 93697387.40 0.224016E+09 0.00 0.00
April 0.698985E+09 0.144372E+09 0.334822E+09 93265403.11 0.241557E+09 0.00 0.00
May 0.932244E+09 54023484.55 0.373591E+09 0.109099E+09 0.264492E+09 0.00 0.00
June 0.978946E+09 22713345.33 0.373482E+09 0.114887E+09 0.258595E+09 0.00 0.00
July 0.104063E+10 4460436.46 0.351879E+09 96634045.07 0.255245E+09 0.00 0.00
August 0.107842E+10 3169342.19 0.365430E+09 0.109325E+09 0.256105E+09 0.00 0.00
September 0.860611E+09 35945179.39 0.338053E+09 0.104984E+09 0.233069E+09 0.00 0.00
October 0.703077E+09 0.106325E+09 0.313345E+09 0.101147E+09 0.212198E+09 0.00 0.00
November 0.505017E+09 0.200204E+09 0.262785E+09 86835111.02 0.175950E+09 0.00 0.00
December 0.351246E+09 0.314344E+09 0.227467E+09 69783285.09 0.157684E+09 0.00 0.00
               
Annual Sum or Average 0.844167E+10 0.173395E+10 0.374077E+10 0.111869E+10 0.262208E+10 0.00 0.00
Minimum of Months 0.335577E+09 3169342.19 0.227467E+09 69480052.93 0.157684E+09 0.00 0.00
Maximum of Months 0.107842E+10 0.358542E+09 0.373591E+09 0.114887E+09 0.264492E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 19.24 14.74 11.63 2.95 7.91 83.00 101.34 0.00
February 20.75 16.26 13.46 3.66 9.80 96.50 106.33 0.00
March 23.12 16.75 12.67 3.48 11.63 114.51 110.36 0.00
April 26.49 19.17 14.91 3.36 14.65 129.52 127.73 0.00
May 31.37 21.91 17.14 3.30 19.37 135.62 152.47 0.00
June 32.97 24.78 21.39 3.95 20.59 135.23 162.31 0.00
July 35.08 26.48 23.16 3.85 24.14 131.49 150.69 0.00
August 35.31 27.02 24.10 3.89 24.33 129.32 147.63 0.00
September 32.49 25.68 23.13 3.64 20.59 118.70 140.92 0.00
October 29.53 22.66 19.34 3.16 16.84 101.82 135.23 0.00
November 25.53 19.62 16.50 2.98 12.88 85.82 121.41 0.00
December 21.13 16.84 14.23 2.84 10.14 76.46 98.30 0.00
                 
Annual Sum or Average 27.79 21.02 17.66 3.42 16.11 111.56 129.66 0.00
Minimum of Months 19.24 14.74 11.63 2.84 7.91 76.46 98.30 0.00
Maximum of Months 35.31 27.02 24.10 3.95 24.33 135.62 162.31 0.00



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 28.00 23-JAN-13:00 16.55 9.00 4.60 16.85 268.00 249.50
February 32.50 06-FEB-14:00 17.28 6.50 6.20 21.27 242.00 327.50
March 38.00 27-MAR-10:00 18.84 6.00 7.70 21.44 329.50 440.00
April 42.00 28-APR-11:00 19.18 2.00 2.60 24.16 371.50 432.50
May 42.10 31-MAY-18:00 20.76 8.00 5.10 30.18 0.00 0.00
June 43.00 12-JUN-11:00 24.56 17.00 3.60 28.91 372.00 427.00
July 46.00 21-JUL-11:00 22.01 9.00 3.60 32.99 306.00 562.50
August 46.00 16-AUG-11:00 25.38 17.00 7.20 31.75 273.00 629.50
September 41.20 26-SEP-12:00 22.43 13.00 4.10 26.15 325.00 455.00
October 38.00 04-OCT-11:00 19.81 9.00 1.00 22.13 338.00 421.50
November 34.00 05-NOV-11:00 17.15 5.00 2.10 17.39 294.00 427.50
December 30.00 10-DEC-11:00 19.04 13.00 4.10 21.27 305.00 214.50
                 
Annual Sum or Average                
Minimum of Months 28.00   16.55 2.00 1.00 16.85 0.00 0.00
Maximum of Months 46.00   25.38 17.00 7.70 32.99 372.00 629.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.00 09-JAN-07:00 12.00 12.00 1.00 -1.9 54.50 10.00
February 13.00 01-FEB-04:00 12.45 12.00 1.00 -0.8 0.00 0.00
March 14.00 07-MAR-05:00 11.74 10.00 0.50 2.64 0.00 0.00
April 17.00 01-APR-05:00 15.74 15.00 0.50 3.69 0.00 0.00
May 20.40 01-MAY-05:00 20.40 20.40 2.10 9.33 28.50 50.50
June 21.00 22-JUN-07:00 19.59 19.00 1.50 8.35 206.50 266.00
July 28.00 03-JUL-05:00 16.06 8.00 1.00 12.41 32.50 30.50
August 28.80 31-AUG-03:00 25.95 25.00 1.50 17.03 0.00 0.00
September 23.00 25-SEP-04:00 22.27 22.00 2.10 10.88 0.00 0.00
October 20.60 29-OCT-06:00 17.24 15.40 0.50 7.15 49.50 123.00
November 16.90 22-NOV-06:00 14.44 12.90 3.10 3.06 31.00 106.50
December 13.00 18-DEC-04:00 10.82 9.00 1.80 -1.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 12.00   10.82 8.00 0.50 -1.9 0.00 0.00
Maximum of Months 28.80   25.95 25.00 3.10 17.03 206.50 266.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 20.89 30-JAN-13:00 23.00 20.00 3.60 18.82 266.50 27.50
February 23.21 07-FEB-15:00 28.00 21.30 6.20 18.64 178.50 219.50
March 23.05 28-MAR-10:00 28.00 21.00 7.20 23.82 374.50 58.00
April 26.40 30-APR-14:00 31.00 25.00 8.70 22.98 350.50 184.00
May 29.11 29-MAY-12:00 33.40 27.90 7.70 22.13 421.00 303.50
June 29.09 04-JUN-18:00 33.20 28.00 4.10 21.96 16.50 15.50
July 30.86 18-JUL-20:00 34.00 30.00 3.60 26.32 0.00 0.00
August 31.14 22-AUG-16:00 36.00 30.00 9.30 25.16 159.00 168.50
September 30.39 09-SEP-13:00 36.00 29.00 5.70 28.11 339.50 377.00
October 30.18 07-OCT-09:00 30.60 30.10 4.60 19.87 295.50 353.00
November 26.24 01-NOV-13:00 33.00 24.00 6.20 20.92 269.00 349.50
December 23.18 05-DEC-14:00 26.00 22.00 4.60 16.85 185.00 295.00
                 
Annual Sum or Average                
Minimum of Months 20.89   23.00 20.00 3.60 16.85 0.00 0.00
Maximum of Months 31.14   36.00 30.10 9.30 28.11 421.00 377.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 20.00 30-JAN-13:00 23.00 20.89 3.60 18.82 266.50 27.50
February 21.30 07-FEB-15:00 28.00 23.21 6.20 18.64 178.50 219.50
March 22.00 31-MAR-09:00 23.00 22.27 0.50 10.88 323.50 305.50
April 25.00 30-APR-14:00 31.00 26.40 8.70 22.98 350.50 184.00
May 27.90 29-MAY-12:00 33.40 29.11 7.70 22.13 421.00 303.50
June 28.00 04-JUN-18:00 33.20 29.09 4.10 21.96 16.50 15.50
July 30.00 19-JUL-23:19 34.00 30.86 0.83 25.33 0.00 0.00
August 30.00 07-AUG-23:19 33.00 30.56 3.43 22.30 0.00 0.00
September 29.00 08-SEP-07:00 31.00 29.41 1.50 24.33 179.00 151.00
October 30.10 07-OCT-09:00 30.60 30.18 4.60 19.87 295.50 353.00
November 24.00 01-NOV-10:00 32.00 26.10 3.10 20.05 300.50 377.00
December 23.00 25-DEC-10:00 23.00 23.00 0.80 14.10 245.00 376.50
                 
Annual Sum or Average                
Minimum of Months 20.00   23.00 20.89 0.50 10.88 0.00 0.00
Maximum of Months 30.10   34.00 30.86 8.70 25.33 421.00 377.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 24.90 26.90 0.00
February 18.00 13.00 16.00 25.87 32.18 0.00
March 18.00 13.00 16.00 28.18 38.22 0.00
April 18.00 13.00 16.00 31.32 44.91 0.00
May 18.00 13.00 16.00 34.39 50.41 0.00
June 18.00 13.00 16.00 36.58 52.39 0.00
July 18.00 13.00 16.00 37.28 50.68 0.00
August 18.00 13.00 16.00 36.29 48.56 0.00
September 18.00 13.00 16.00 33.90 43.99 0.00
October 18.00 13.00 16.00 30.75 37.43 0.00
November 18.00 13.00 16.00 27.69 30.34 0.00
December 18.00 13.00 16.00 25.55 25.09 0.00
             
Annual Sum or Average 18.00 13.00 16.00 31.09 40.13 0.00
Minimum of Months 18.00 13.00 16.00 24.90 25.09 0.00
Maximum of Months 18.00 13.00 16.00 37.28 52.39 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.456768E+09 -346608056.5 0.00 0.00 744.00 0.00 -110159498.6 58.99 0.00 0.00
February 0.403935E+09 -304904853.6 0.00 0.00 672.00 0.00 -99030169.4 58.99 0.00 0.00
March 0.452043E+09 -342710111.7 0.00 0.00 744.00 0.00 -109332548.2 58.98 0.00 0.00
April 0.372321E+09 -267941524.1 0.00 0.00 720.00 0.00 -104379606.8 58.99 0.00 0.00
May 0.368616E+09 -262936926.2 0.00 0.00 744.00 0.00 -105678996.1 58.99 0.00 0.00
June 0.340017E+09 -238443650.1 0.00 0.00 720.00 0.00 -101573237.1 58.98 0.00 0.00
July 0.312335E+09 -210120039.5 0.00 0.00 744.00 0.00 -102215322.3 58.99 0.00 0.00
August 0.355358E+09 -252810932.9 0.00 0.00 744.00 0.00 -102546593.8 58.99 0.00 0.00
September 0.344075E+09 -243659291.2 0.00 0.00 720.00 0.00 -100416042.0 58.99 0.00 0.00
October 0.392519E+09 -287403028.7 0.00 0.00 744.00 0.00 -105116132.5 58.99 0.00 0.00
November 0.421742E+09 -318042839.5 0.00 0.00 720.00 0.00 -103699241.5 58.99 0.00 0.00
December 0.432428E+09 -323575615.8 0.00 0.00 744.00 0.00 -108852222.8 58.99 0.00 0.00
                     
Annual Sum or Average 0.465216E+10 -0.339916E+10 0.00 0.00 8760.00 0.00 -0.125300E+10 58.99 0.00 0.00
Minimum of Months 0.312335E+09 -346608056.5 0.00 0.00 672.00 0.00 -110159498.6 58.98 0.00 0.00
Maximum of Months 0.456768E+09 -210120039.5 0.00 0.00 744.00 0.00 -99030169.4 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 325.00 0.76 0.73 01-JAN-10:30 1030.63 27.63 186.17 270.83 421.31 24.25 274.67 208.67
February 308.33 0.77 0.73 01-FEB-09:09 765.77 23.65 121.50 233.67 367.13 21.82 206.33 164.83
March 357.50 0.78 0.73 01-MAR-09:30 416.09 17.15 4.17 224.67 298.67 21.19 229.33 151.00
April 375.00 0.79 0.73 01-APR-11:39 320.87 15.98 0.00 201.50 229.77 20.02 216.00 0.00
May 405.33 0.80 0.73 15-MAY-13:50 281.92 15.74 0.00 81.83 203.96 19.84 183.67 0.00
June 403.50 0.80 0.74 25-JUN-14:30 272.25 15.58 0.00 49.67 198.43 19.76 161.67 0.00
July 405.00 0.80 0.73 05-JUL-09:39 284.30 15.59 0.00 100.33 206.41 19.75 207.00 0.00
August 395.83 0.79 0.73 01-AUG-09:39 330.15 16.21 0.00 224.67 237.28 20.34 250.50 16.67
September 358.83 0.78 0.73 01-SEP-08:39 409.46 17.14 0.00 241.50 294.26 21.32 247.33 142.50
October 351.17 0.76 0.73 01-OCT-08:20 607.86 18.89 24.50 271.00 371.79 21.96 253.17 203.83
November 318.83 0.75 0.73 01-NOV-08:09 1144.07 27.54 178.00 272.33 429.80 23.32 248.17 202.67
December 319.00 0.76 0.73 01-DEC-07:30 971.74 27.57 180.50 260.50 450.34 26.13 288.50 210.00
                         
Annual Sum or Average 4323.33 0.78     542.46 19.47 694.83 2432.50 300.73 21.49 2766.33 1300.17
Minimum of Months 308.33 0.75 0.73   272.25 15.58 0.00 49.67 198.43 19.75 161.67 0.00
Maximum of Months 405.33 0.80 0.74   1144.07 27.63 186.17 272.33 450.34 26.13 288.50 210.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 325.00 0.82 0.73 01-JAN-09:09 545.35 17.76 56.83 117.83 394.06 23.45 146.33 79.50
February 308.33 0.82 0.73 01-FEB-08:30 568.96 17.68 50.50 106.00 222.87 19.57 102.83 56.17
March 357.50 0.82 0.73 01-MAR-09:20 305.23 15.10 1.83 112.67 228.14 19.44 110.00 66.00
April 375.00 0.82 0.73 01-APR-07:00 292.55 14.51 0.00 114.50 232.73 18.93 115.33 80.33
May 405.33 0.82 0.73 01-MAY-07:19 297.91 14.78 0.00 120.17 246.16 19.48 127.50 97.50
June 403.50 0.82 0.73 01-JUN-07:10 299.46 14.84 0.00 121.50 246.93 19.64 130.50 98.50
July 405.00 0.82 0.73 01-JUL-07:19 298.57 14.77 0.00 122.50 242.82 19.39 131.17 94.83
August 395.83 0.82 0.73 01-AUG-07:19 312.24 14.97 0.00 131.17 252.09 19.55 137.17 98.50
September 358.83 0.81 0.73 01-SEP-07:30 329.78 15.32 0.00 131.00 258.56 19.90 135.00 93.00
October 351.17 0.81 0.73 01-OCT-07:40 337.49 15.35 0.00 134.50 269.75 20.20 138.83 92.33
November 318.83 0.81 0.73 01-NOV-07:40 352.09 16.07 7.33 121.33 326.00 22.65 145.67 88.00
December 319.00 0.82 0.73 01-DEC-07:49 462.87 18.35 60.50 113.00 248.33 21.97 135.17 58.67
                         
Annual Sum or Average 4323.33 0.82     359.53 15.69 177.00 1446.17 262.26 20.26 1555.50 1003.33
Minimum of Months 308.33 0.81 0.73   292.55 14.51 0.00 106.00 222.87 18.93 102.83 56.17
Maximum of Months 405.33 0.82 0.73   568.96 18.35 60.50 134.50 394.06 23.45 146.33 98.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 325.00 0.90 0.85 29-JAN-13:30 149.11 13.13 0.00 0.00 103.78 16.80 0.00 0.00
February 308.33 0.88 0.83 27-FEB-14:30 169.17 13.98 0.00 0.00 117.39 17.72 0.00 0.00
March 357.50 0.86 0.80 30-MAR-15:20 197.36 14.70 0.00 0.00 135.27 18.39 0.00 0.00
April 375.00 0.84 0.74 30-APR-09:30 228.00 15.11 0.00 0.00 154.26 18.71 0.00 0.00
May 405.33 0.80 0.74 31-MAY-15:30 278.08 16.09 0.00 40.00 180.51 19.85 36.00 0.00
June 403.50 0.79 0.74 25-JUN-15:30 296.62 16.50 0.00 103.50 202.35 21.73 168.50 0.00
July 405.00 0.80 0.74 19-JUL-15:30 286.01 16.05 0.00 83.83 192.46 19.87 107.50 0.00
August 395.83 0.81 0.74 03-AUG-15:30 263.63 15.84 0.00 27.00 178.02 19.58 35.00 0.00
September 358.83 0.84 0.74 07-SEP-14:39 228.98 15.40 0.00 0.00 157.20 19.14 0.00 0.00
October 351.17 0.87 0.81 01-OCT-14:30 188.40 14.40 0.00 0.00 131.82 18.16 0.00 0.00
November 318.83 0.89 0.83 01-NOV-13:30 162.51 13.96 0.00 0.00 114.62 17.81 0.00 0.00
December 319.00 0.90 0.85 06-DEC-11:30 144.39 13.16 0.00 0.00 101.05 16.93 0.00 0.00
                         
Annual Sum or Average 4323.33 0.84     221.00 14.96 0.00 254.33 150.54 18.84 347.00 0.00
Minimum of Months 308.33 0.79 0.74   144.39 13.13 0.00 0.00 101.05 16.80 0.00 0.00
Maximum of Months 405.33 0.90 0.85   296.62 16.50 0.00 103.50 202.35 21.73 168.50 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 325.00 0.82 0.73 01-JAN-13:39 526.05 17.81 54.83 117.17 363.73 23.29 152.17 76.17
February 308.33 0.82 0.73 01-FEB-13:30 314.54 15.42 0.00 109.50 280.50 22.17 142.00 80.67
March 357.50 0.82 0.73 01-MAR-13:09 316.52 15.32 0.00 124.67 242.68 19.66 126.50 79.50
April 375.00 0.82 0.73 01-APR-13:30 296.18 14.75 0.00 116.00 234.10 19.09 119.33 79.83
May 405.33 0.82 0.73 01-MAY-13:20 294.11 14.88 0.00 123.33 239.23 19.44 129.33 94.67
June 403.50 0.82 0.73 01-JUN-13:30 302.04 15.07 0.00 126.00 247.69 19.67 136.17 101.17
July 405.00 0.82 0.73 01-JUL-13:20 300.67 14.96 0.00 124.17 242.45 19.40 134.83 94.83
August 395.83 0.82 0.73 01-AUG-13:20 316.48 15.13 0.00 131.00 253.77 19.60 140.17 101.83
September 358.83 0.81 0.73 01-SEP-12:00 333.61 15.55 0.00 132.00 260.16 19.92 138.00 96.00
October 351.17 0.81 0.73 01-OCT-12:30 372.61 15.87 7.33 133.67 270.35 20.39 142.17 92.00
November 318.83 0.81 0.73 01-NOV-12:30 585.13 18.72 55.00 122.67 367.04 23.86 155.50 94.17
December 319.00 0.82 0.73 01-DEC-13:20 512.04 18.23 56.83 113.00 320.15 23.35 146.83 72.33
                         
Annual Sum or Average 4323.33 0.82     365.63 15.88 174.00 1473.17 273.46 20.68 1663.00 1063.17
Minimum of Months 308.33 0.81 0.73   294.11 14.75 0.00 109.50 234.10 19.09 119.33 72.33
Maximum of Months 405.33 0.82 0.73   585.13 18.72 56.83 133.67 367.04 23.86 155.50 101.83



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.267294E+10 0.207777E+10 7940.29 30-JAN-06:01 5660.02 0.00
February 0.00 0.00 0.284110E+10 0.218582E+10 8109.51 07-FEB-06:01 5143.76 0.00
March 0.00 0.00 0.375044E+10 0.300630E+10 8149.83 29-MAR-05:02 4972.60 0.00
April 0.00 0.00 0.401044E+10 0.320480E+10 8219.54 03-APR-05:01 5207.69 0.00
May 0.00 0.00 0.585559E+10 0.467845E+10 8431.09 30-MAY-05:01 5477.44 0.00
June 0.00 0.00 0.663415E+10 0.497444E+10 8585.67 27-JUN-05:01 4652.53 0.00
July 0.00 0.00 0.667259E+10 0.466470E+10 8571.99 06-JUL-05:01 4446.98 0.00
August 0.00 0.00 0.777600E+10 0.536945E+10 8571.99 31-AUG-05:02 4388.10 0.00
September 0.00 0.00 0.640420E+10 0.456405E+10 8592.70 22-SEP-05:01 4227.72 0.00
October 0.00 0.00 0.599753E+10 0.447952E+10 8594.73 02-OCT-05:01 4900.56 0.00
November 0.00 0.00 0.490034E+10 0.365692E+10 8330.77 03-NOV-05:01 4802.77 0.00
December 0.00 0.00 0.333035E+10 0.252522E+10 8163.77 06-DEC-06:01 4736.91 0.00
                 
Annual Sum or Average 0.00 0.00 0.608457E+11 0.453874E+11       0.00
Minimum of Months 0.00 0.00 0.267294E+10 0.207777E+10 7940.29   4227.72 0.00
Maximum of Months 0.00 0.00 0.777600E+10 0.536945E+10 8594.73   5660.02 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.254800E+10 0.219289E+10 9779.05 30-JAN-06:01 7081.34 0.00
February 0.00 0.00 0.264914E+10 0.222296E+10 9938.99 09-FEB-06:02 6296.04 0.00
March 0.00 0.00 0.329589E+10 0.284603E+10 10005.19 29-MAR-05:02 5904.68 0.00
April 0.00 0.00 0.352175E+10 0.295908E+10 10026.05 10-APR-05:01 6063.46 0.00
May 0.00 0.00 0.594368E+10 0.490058E+10 10453.96 24-MAY-05:01 5029.33 0.00
June 0.00 0.00 0.725436E+10 0.552429E+10 10456.42 08-JUN-05:02 4608.55 0.00
July 0.00 0.00 0.820920E+10 0.590258E+10 10396.78 06-JUL-05:17 4284.43 0.00
August 0.00 0.00 0.961060E+10 0.687290E+10 10396.78 31-AUG-05:13 4383.22 0.00
September 0.00 0.00 0.778842E+10 0.573830E+10 10453.96 29-SEP-05:06 4461.53 0.00
October 0.00 0.00 0.729204E+10 0.574851E+10 10463.46 18-OCT-05:01 5360.18 0.00
November 0.00 0.00 0.570114E+10 0.457986E+10 10290.82 03-NOV-05:01 5837.82 0.00
December 0.00 0.00 0.342875E+10 0.284086E+10 9983.05 06-DEC-06:01 6007.61 0.00
                 
Annual Sum or Average 0.00 0.00 0.672430E+11 0.523288E+11       0.00
Minimum of Months 0.00 0.00 0.254800E+10 0.219289E+10 9779.05   4284.43 0.00
Maximum of Months 0.00 0.00 0.961060E+10 0.687290E+10 10463.46   7081.34 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.113196E+10 0.100236E+10 5994.69 30-JAN-06:01 4333.04 0.00
February 0.00 0.00 0.121661E+10 0.105140E+10 6085.24 09-FEB-06:02 3969.79 0.00
March 0.00 0.00 0.165565E+10 0.148006E+10 6102.82 29-MAR-05:02 3856.56 0.00
April 0.00 0.00 0.194455E+10 0.171615E+10 6158.55 10-APR-05:01 3858.78 0.00
May 0.00 0.00 0.331964E+10 0.289738E+10 6417.03 24-MAY-05:01 3278.49 0.00
June 0.00 0.00 0.396690E+10 0.324839E+10 6419.44 08-JUN-05:01 3105.01 0.00
July 0.00 0.00 0.460390E+10 0.362454E+10 6382.83 06-JUL-05:01 2923.07 0.00
August 0.00 0.00 0.544289E+10 0.427182E+10 6382.83 31-AUG-05:01 3100.50 0.00
September 0.00 0.00 0.417850E+10 0.333255E+10 6417.93 29-SEP-05:01 3192.62 0.00
October 0.00 0.00 0.357736E+10 0.297947E+10 6402.51 17-OCT-05:01 3656.77 0.00
November 0.00 0.00 0.261419E+10 0.220192E+10 6281.47 03-NOV-05:01 3746.90 0.00
December 0.00 0.00 0.153519E+10 0.132033E+10 6060.10 06-DEC-06:01 3956.16 0.00
                 
Annual Sum or Average 0.00 0.00 0.351873E+11 0.291264E+11       0.00
Minimum of Months 0.00 0.00 0.113196E+10 0.100236E+10 5994.69   2923.07 0.00
Maximum of Months 0.00 0.00 0.544289E+10 0.427182E+10 6419.44   4333.04 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.182160E+10 0.153901E+10 9546.33 30-JAN-06:01 6622.86 0.00
February 0.00 0.00 0.199943E+10 0.165555E+10 9712.47 09-FEB-06:02 6166.83 0.00
March 0.00 0.00 0.276534E+10 0.238489E+10 9732.28 29-MAR-05:02 6008.52 0.00
April 0.00 0.00 0.318361E+10 0.271374E+10 9828.78 10-APR-05:01 5927.01 0.00
May 0.00 0.00 0.526388E+10 0.445461E+10 10230.55 30-MAY-05:01 6288.45 0.00
June 0.00 0.00 0.634972E+10 0.504192E+10 10260.21 08-JUN-05:02 4856.31 0.00
July 0.00 0.00 0.729386E+10 0.555854E+10 10201.69 06-JUL-05:10 4415.18 0.00
August 0.00 0.00 0.856967E+10 0.651096E+10 10201.69 31-AUG-05:06 4656.55 0.00
September 0.00 0.00 0.655955E+10 0.505767E+10 10271.72 25-SEP-05:02 5542.98 0.00
October 0.00 0.00 0.562922E+10 0.452205E+10 10246.44 02-OCT-05:01 5612.96 0.00
November 0.00 0.00 0.422214E+10 0.341000E+10 10011.70 03-NOV-05:01 5812.09 0.00
December 0.00 0.00 0.254197E+10 0.208907E+10 9670.16 06-DEC-06:01 6089.44 0.00
                 
Annual Sum or Average 0.00 0.00 0.562000E+11 0.449380E+11       0.00
Minimum of Months 0.00 0.00 0.182160E+10 0.153901E+10 9546.33   4415.18 0.00
Maximum of Months 0.00 0.00 0.856967E+10 0.651096E+10 10271.72   6622.86 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.130258E+10 0.113561E+10 6948.12 30-JAN-06:01 5038.72 0.00
February 0.00 0.00 0.139762E+10 0.119199E+10 7050.62 09-FEB-06:02 4608.47 0.00
March 0.00 0.00 0.190023E+10 0.167733E+10 7070.67 29-MAR-05:02 4500.54 0.00
April 0.00 0.00 0.211913E+10 0.184297E+10 7139.52 10-APR-05:01 4498.65 0.00
May 0.00 0.00 0.348061E+10 0.299990E+10 7430.83 24-MAY-05:01 3858.05 0.00
June 0.00 0.00 0.419018E+10 0.339267E+10 7436.30 08-JUN-05:01 3666.03 0.00
July 0.00 0.00 0.480186E+10 0.374643E+10 7393.89 06-JUL-05:07 3194.20 0.00
August 0.00 0.00 0.566532E+10 0.441224E+10 7393.89 31-AUG-05:01 3625.88 0.00
September 0.00 0.00 0.438448E+10 0.346252E+10 7434.55 29-SEP-05:01 3765.30 0.00
October 0.00 0.00 0.377852E+10 0.311060E+10 7410.42 17-OCT-05:01 4286.81 0.00
November 0.00 0.00 0.284425E+10 0.236273E+10 7272.77 03-NOV-05:01 4392.48 0.00
December 0.00 0.00 0.175232E+10 0.148440E+10 7018.54 11-DEC-06:01 5071.77 0.00
                 
Annual Sum or Average 0.00 0.00 0.376171E+11 0.308194E+11       0.00
Minimum of Months 0.00 0.00 0.130258E+10 0.113561E+10 6948.12   3194.20 0.00
Maximum of Months 0.00 0.00 0.566532E+10 0.441224E+10 7436.30   5071.77 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 81.95 407.35 12-JAN-12:15
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     6.96    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   81.95 407.35  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.353208E+09 0.33 359.39 02-JAN-06:05 0.91
February 0.319569E+09 0.33 359.39 01-FEB-06:02 0.91
March 0.386847E+09 0.37 359.39 01-MAR-06:02 0.91
April 0.336389E+09 0.33 359.39 03-APR-05:01 0.90
May 0.370028E+09 0.35 359.39 01-MAY-05:01 0.91
June 0.370028E+09 0.36 359.39 01-JUN-05:01 0.91
July 0.338847E+09 0.33 359.39 03-JUL-05:01 0.90
August 0.391380E+09 0.39 359.39 01-AUG-05:01 0.90
September 0.339338E+09 0.34 359.39 01-SEP-05:01 0.90
October 0.354028E+09 0.34 359.39 02-OCT-05:01 0.90
November 0.353208E+09 0.34 359.39 01-NOV-05:01 0.91
December 0.336389E+09 0.32 359.39 01-DEC-06:01 0.91
           
Annual Sum or Average 0.424926E+10 0.34      
Minimum of Months 0.319569E+09 0.32 359.39   0.90
Maximum of Months 0.391380E+09 0.39 359.39   0.91



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.475736E+09 0.33 484.06 02-JAN-06:05 0.91
February 0.430428E+09 0.33 484.06 01-FEB-06:02 0.91
March 0.521044E+09 0.37 484.06 01-MAR-06:02 0.91
April 0.453082E+09 0.33 484.06 03-APR-05:01 0.91
May 0.500793E+09 0.36 484.06 01-MAY-05:01 0.90
June 0.504721E+09 0.39 484.06 01-JUN-05:01 0.90
July 0.482217E+09 0.44 484.06 03-JUL-05:01 0.91
August 0.551901E+09 0.48 484.06 01-AUG-05:01 0.90
September 0.480139E+09 0.43 484.06 01-SEP-05:01 0.90
October 0.496753E+09 0.42 484.06 02-OCT-05:01 0.90
November 0.479311E+09 0.37 484.06 01-NOV-05:01 0.90
December 0.453082E+09 0.32 484.06 01-DEC-06:01 0.91
           
Annual Sum or Average 0.582921E+10 0.38      
Minimum of Months 0.430428E+09 0.32 484.06   0.90
Maximum of Months 0.551901E+09 0.48 484.06   0.91



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.250974E+09 0.34 314.31 02-JAN-06:05 0.91
February 0.229292E+09 0.34 314.31 01-FEB-06:02 0.91
March 0.280042E+09 0.37 314.31 01-MAR-06:02 0.91
April 0.250312E+09 0.34 314.31 03-APR-05:01 0.91
May 0.294903E+09 0.39 314.31 01-MAY-05:01 0.90
June 0.305734E+09 0.43 314.31 01-JUN-05:01 0.91
July 0.305421E+09 0.47 314.31 02-JUL-08:42 0.90
August 0.350419E+09 0.50 314.31 01-AUG-05:01 0.90
September 0.293701E+09 0.44 314.31 01-SEP-05:01 0.90
October 0.288853E+09 0.40 314.31 02-OCT-05:01 0.90
November 0.269231E+09 0.35 314.31 01-NOV-05:01 0.90
December 0.244176E+09 0.33 314.31 01-DEC-06:01 0.91
           
Annual Sum or Average 0.336306E+10 0.39      
Minimum of Months 0.229292E+09 0.33 314.31   0.90
Maximum of Months 0.350419E+09 0.50 314.31   0.91



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.464934E+09 0.33 473.07 02-JAN-06:05 0.91
February 0.420654E+09 0.33 473.07 01-FEB-06:02 0.91
March 0.509213E+09 0.37 473.07 01-MAR-06:02 0.91
April 0.442794E+09 0.33 473.07 03-APR-05:01 0.91
May 0.489455E+09 0.36 473.07 01-MAY-05:01 0.90
June 0.493449E+09 0.39 473.07 01-JUN-05:01 0.91
July 0.469999E+09 0.43 473.07 03-JUL-05:01 0.91
August 0.536609E+09 0.47 473.07 01-AUG-05:01 0.90
September 0.461469E+09 0.40 473.07 01-SEP-05:01 0.90
October 0.471066E+09 0.36 473.07 02-OCT-05:01 0.90
November 0.464934E+09 0.35 473.07 01-NOV-05:01 0.90
December 0.442794E+09 0.32 473.07 01-DEC-06:01 0.91
           
Annual Sum or Average 0.566737E+10 0.37      
Minimum of Months 0.420654E+09 0.32 473.07   0.90
Maximum of Months 0.536609E+09 0.47 473.07   0.91



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.357480E+09 0.33 363.74 02-JAN-06:05 0.91
February 0.323434E+09 0.33 363.74 01-FEB-06:02 0.91
March 0.391525E+09 0.37 363.74 01-MAR-06:02 0.91
April 0.340457E+09 0.33 363.74 03-APR-05:01 0.91
May 0.379801E+09 0.39 363.74 01-MAY-05:01 0.90
June 0.384573E+09 0.42 363.74 01-JUN-05:01 0.91
July 0.366012E+09 0.46 363.74 03-JUL-05:01 0.91
August 0.417073E+09 0.49 363.74 01-AUG-05:01 0.90
September 0.360730E+09 0.44 363.74 01-SEP-05:01 0.90
October 0.367263E+09 0.40 363.74 02-OCT-05:01 0.90
November 0.357803E+09 0.35 363.74 01-NOV-05:01 0.90
December 0.340457E+09 0.32 363.74 01-DEC-06:01 0.91
           
Annual Sum or Average 0.438661E+10 0.39      
Minimum of Months 0.323434E+09 0.32 363.74   0.90
Maximum of Months 0.417073E+09 0.49 363.74   0.91



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.01 0.00 0.00 02-JAN-07:05 0.00 0.00 40.13 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 24.81 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 24.81 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 24.81 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 24.81 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 24.81 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 24.81 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 24.81 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 24.81 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 24.81 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 24.81 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 24.81 0.00
                 
Annual Sum or Average 0.01 0.00            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 24.81 0.00
Maximum of Months 0.01 0.00 0.00   0.00 0.00 40.13 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.89 48.89 81.95 407.35 12-JAN-12:15
February 0.00 0.00 01-FEB-00:10 24.81 24.81 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 24.81 24.81 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 24.81 24.81 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 24.81 24.81 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 24.81 24.81 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 24.81 24.81 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 24.81 24.81 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 24.81 24.81 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 24.81 24.81 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 24.81 24.81 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 24.81 24.81 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         6.96    
Minimum of Months 0.00 0.00   24.81 24.81 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 81.95 407.35  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.933603E+09 0.00 0.00
February 0.00 0.00 0.00 0.944584E+09 0.00 0.00
March 0.00 0.00 0.00 0.123839E+10 0.00 0.00
April 0.00 0.00 0.00 0.127150E+10 0.00 0.00
May 0.00 0.00 0.00 0.179174E+10 0.00 0.00
June 0.00 0.00 0.00 0.198128E+10 0.00 0.00
July 0.00 0.00 0.00 0.194677E+10 0.00 0.00
August 0.00 0.00 0.00 0.226729E+10 0.00 0.00
September 0.00 0.00 0.00 0.185183E+10 0.00 0.00
October 0.00 0.00 0.00 0.173112E+10 0.00 0.00
November 0.00 0.00 0.00 0.144527E+10 0.00 0.00
December 0.00 0.00 0.00 0.106016E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.184635E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.933603E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.226729E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.103535E+10 0.00 0.00
February 0.00 0.00 0.00 0.102447E+10 0.00 0.00
March 0.00 0.00 0.00 0.129374E+10 0.00 0.00
April 0.00 0.00 0.00 0.130703E+10 0.00 0.00
May 0.00 0.00 0.00 0.199078E+10 0.00 0.00
June 0.00 0.00 0.00 0.231093E+10 0.00 0.00
July 0.00 0.00 0.00 0.250950E+10 0.00 0.00
August 0.00 0.00 0.00 0.292269E+10 0.00 0.00
September 0.00 0.00 0.00 0.235628E+10 0.00 0.00
October 0.00 0.00 0.00 0.220297E+10 0.00 0.00
November 0.00 0.00 0.00 0.176754E+10 0.00 0.00
December 0.00 0.00 0.00 0.120751E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.219288E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.102447E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.292269E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.503653E+09 0.00 0.00
February 0.00 0.00 0.00 0.505813E+09 0.00 0.00
March 0.00 0.00 0.00 0.671359E+09 0.00 0.00
April 0.00 0.00 0.00 0.723887E+09 0.00 0.00
May 0.00 0.00 0.00 0.113671E+10 0.00 0.00
June 0.00 0.00 0.00 0.131297E+10 0.00 0.00
July 0.00 0.00 0.00 0.147490E+10 0.00 0.00
August 0.00 0.00 0.00 0.172971E+10 0.00 0.00
September 0.00 0.00 0.00 0.132507E+10 0.00 0.00
October 0.00 0.00 0.00 0.114379E+10 0.00 0.00
November 0.00 0.00 0.00 0.873092E+09 0.00 0.00
December 0.00 0.00 0.00 0.588747E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.119897E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.503653E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.172971E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.872429E+09 0.00 0.00
February 0.00 0.00 0.00 0.876328E+09 0.00 0.00
March 0.00 0.00 0.00 0.116338E+10 0.00 0.00
April 0.00 0.00 0.00 0.121942E+10 0.00 0.00
May 0.00 0.00 0.00 0.182732E+10 0.00 0.00
June 0.00 0.00 0.00 0.210645E+10 0.00 0.00
July 0.00 0.00 0.00 0.231844E+10 0.00 0.00
August 0.00 0.00 0.00 0.270951E+10 0.00 0.00
September 0.00 0.00 0.00 0.208205E+10 0.00 0.00
October 0.00 0.00 0.00 0.181854E+10 0.00 0.00
November 0.00 0.00 0.00 0.144332E+10 0.00 0.00
December 0.00 0.00 0.00 0.101398E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.194512E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.872429E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.270951E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.649186E+09 0.00 0.00
February 0.00 0.00 0.00 0.642491E+09 0.00 0.00
March 0.00 0.00 0.00 0.842278E+09 0.00 0.00
April 0.00 0.00 0.00 0.860407E+09 0.00 0.00
May 0.00 0.00 0.00 0.127473E+10 0.00 0.00
June 0.00 0.00 0.00 0.146444E+10 0.00 0.00
July 0.00 0.00 0.00 0.160511E+10 0.00 0.00
August 0.00 0.00 0.00 0.187884E+10 0.00 0.00
September 0.00 0.00 0.00 0.145975E+10 0.00 0.00
October 0.00 0.00 0.00 0.128281E+10 0.00 0.00
November 0.00 0.00 0.00 0.102138E+10 0.00 0.00
December 0.00 0.00 0.00 0.735401E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.137168E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.642491E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.187884E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.353208E+09 0.267294E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.319569E+09 0.284110E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.386847E+09 0.375044E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.336389E+09 0.401044E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.370028E+09 0.585559E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.370028E+09 0.663415E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.338847E+09 0.667259E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.391380E+09 0.777600E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.339338E+09 0.640420E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.354028E+09 0.599753E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.353208E+09 0.490034E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.336389E+09 0.333035E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.424926E+10 0.608457E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.319569E+09 0.267294E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.391380E+09 0.777600E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.475736E+09 0.254800E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.430428E+09 0.264914E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.521044E+09 0.329589E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453082E+09 0.352175E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.500793E+09 0.594368E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.504721E+09 0.725436E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.482217E+09 0.820920E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.551901E+09 0.961060E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.480139E+09 0.778842E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.496753E+09 0.729204E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.479311E+09 0.570114E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.453082E+09 0.342875E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.582921E+10 0.672430E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.430428E+09 0.254800E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.551901E+09 0.961060E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.250974E+09 0.113196E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.229292E+09 0.121661E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.280042E+09 0.165565E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.250312E+09 0.194455E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.294903E+09 0.331964E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.305734E+09 0.396690E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.305421E+09 0.460390E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.350419E+09 0.544289E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.293701E+09 0.417850E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.288853E+09 0.357736E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.269231E+09 0.261419E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.244176E+09 0.153519E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.336306E+10 0.351873E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.229292E+09 0.113196E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.350419E+09 0.544289E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.464934E+09 0.182160E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.420654E+09 0.199943E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.509213E+09 0.276534E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.442794E+09 0.318361E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.489455E+09 0.526388E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.493449E+09 0.634972E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.469999E+09 0.729386E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.536609E+09 0.856967E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.461469E+09 0.655955E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471066E+09 0.562922E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.464934E+09 0.422214E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.442794E+09 0.254197E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.566737E+10 0.562000E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.420654E+09 0.182160E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.536609E+09 0.856967E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.357480E+09 0.130258E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.323434E+09 0.139762E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.391525E+09 0.190023E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.340457E+09 0.211913E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.379801E+09 0.348061E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.384573E+09 0.419018E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.366012E+09 0.480186E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.417073E+09 0.566532E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.360730E+09 0.438448E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.367263E+09 0.377852E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.357803E+09 0.284425E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.340457E+09 0.175232E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.438661E+10 0.376171E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.323434E+09 0.130258E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.417073E+09 0.566532E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.353208E+09 0.00 0.00 0.00 0.580395E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.319569E+09 0.00 0.00 0.00 0.625015E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.386847E+09 0.00 0.00 0.00 0.851538E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.336389E+09 0.00 0.00 0.00 0.935112E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.370028E+09 0.00 0.00 0.00 0.142171E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.370028E+09 0.00 0.00 0.00 0.161125E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.338847E+09 0.00 0.00 0.00 0.160792E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.391380E+09 0.00 0.00 0.00 0.187591E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.339338E+09 0.00 0.00 0.00 0.151249E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.354028E+09 0.00 0.00 0.00 0.137709E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.353208E+09 0.00 0.00 0.00 0.109206E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.336389E+09 0.00 0.00 0.00 0.723776E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.424926E+10 0.00 0.00 0.00 0.142143E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.319569E+09 0.00 0.00 0.00 0.580395E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.391380E+09 0.00 0.00 0.00 0.187591E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.475736E+09 0.00 0.00 0.00 0.559611E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.430428E+09 0.00 0.00 0.00 0.594038E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.521044E+09 0.00 0.00 0.00 0.772694E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.453082E+09 0.00 0.00 0.00 0.853950E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.500793E+09 0.00 0.00 0.00 0.148999E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.504721E+09 0.00 0.00 0.00 0.180621E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.482217E+09 0.00 0.00 0.00 0.202728E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.551901E+09 0.00 0.00 0.00 0.237079E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.480139E+09 0.00 0.00 0.00 0.187614E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.496753E+09 0.00 0.00 0.00 0.170621E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.479311E+09 0.00 0.00 0.00 0.128823E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.453082E+09 0.00 0.00 0.00 0.754430E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.582921E+10 0.00 0.00 0.00 0.160996E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.430428E+09 0.00 0.00 0.00 0.559611E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.551901E+09 0.00 0.00 0.00 0.237079E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.250974E+09 0.00 0.00 0.00 0.252679E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.229292E+09 0.00 0.00 0.00 0.276521E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.280042E+09 0.00 0.00 0.00 0.391316E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.250312E+09 0.00 0.00 0.00 0.473575E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.294903E+09 0.00 0.00 0.00 0.841809E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.305734E+09 0.00 0.00 0.00 0.100724E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.305421E+09 0.00 0.00 0.00 0.116948E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.350419E+09 0.00 0.00 0.00 0.137929E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.293701E+09 0.00 0.00 0.00 0.103137E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.288853E+09 0.00 0.00 0.00 0.854938E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.269231E+09 0.00 0.00 0.00 0.603861E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.244176E+09 0.00 0.00 0.00 0.344571E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.336306E+10 0.00 0.00 0.00 0.862664E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.229292E+09 0.00 0.00 0.00 0.252679E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.350419E+09 0.00 0.00 0.00 0.137929E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.464934E+09 0.00 0.00 0.00 0.407495E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.420654E+09 0.00 0.00 0.00 0.455674E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.509213E+09 0.00 0.00 0.00 0.654167E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.442794E+09 0.00 0.00 0.00 0.776627E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.489455E+09 0.00 0.00 0.00 0.133786E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.493449E+09 0.00 0.00 0.00 0.161300E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.469999E+09 0.00 0.00 0.00 0.184844E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.536609E+09 0.00 0.00 0.00 0.217290E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.461469E+09 0.00 0.00 0.00 0.162058E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.471066E+09 0.00 0.00 0.00 0.134747E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.464934E+09 0.00 0.00 0.00 0.978388E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.442794E+09 0.00 0.00 0.00 0.571189E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.566737E+10 0.00 0.00 0.00 0.137838E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.420654E+09 0.00 0.00 0.00 0.407495E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.536609E+09 0.00 0.00 0.00 0.217290E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.357480E+09 0.00 0.00 0.00 0.291706E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.323434E+09 0.00 0.00 0.00 0.319057E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.391525E+09 0.00 0.00 0.00 0.450753E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.340457E+09 0.00 0.00 0.00 0.519950E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.379801E+09 0.00 0.00 0.00 0.894926E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.384573E+09 0.00 0.00 0.00 0.107987E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.366012E+09 0.00 0.00 0.00 0.123910E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.417073E+09 0.00 0.00 0.00 0.146177E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.360730E+09 0.00 0.00 0.00 0.109902E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.367263E+09 0.00 0.00 0.00 0.915550E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.357803E+09 0.00 0.00 0.00 0.663575E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.340457E+09 0.00 0.00 0.00 0.394944E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.438661E+10 0.00 0.00 0.00 0.933022E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.323434E+09 0.00 0.00 0.00 0.291706E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.417073E+09 0.00 0.00 0.00 0.146177E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 26633780.94 63502834.65 0.00 6947550.86 2013520.31 0.00 0.336570E+09 0.00 0.19
February 10187418.40 0.144744E+09 0.00 5169103.06 10781690.41 0.00 0.155616E+09 0.00 0.19
March 7754281.10 0.267602E+09 0.00 5350007.84 21823569.82 0.00 0.139047E+09 0.00 0.21
April 0.00 0.517588E+09 0.00 3041686.08 44709214.65 0.00 46144604.29 0.00 0.19
May 0.00 0.114223E+10 0.00 2397939.85 0.100562E+09 0.00 7469168.01 0.00 0.20
June 0.00 0.170387E+10 0.00 458601.28 0.131760E+09 0.00 146532.11 0.00 0.21
July 0.00 0.208745E+10 0.00 1324764.60 0.151809E+09 0.00 2479935.42 0.00 0.19
August 0.00 0.249252E+10 0.00 7583.84 0.193882E+09 0.00 0.00 0.00 0.22
September 0.00 0.177599E+10 0.00 691029.41 0.156554E+09 0.00 848226.38 0.00 0.19
October 0.00 0.130262E+10 0.00 664245.20 89825651.53 0.00 878605.68 0.00 0.19
November 22922.31 0.795633E+09 0.00 3102498.13 57506578.39 0.00 10985279.21 0.00 0.20
December 8405924.26 0.207645E+09 0.00 5297161.02 13806538.86 0.00 0.125462E+09 0.00 0.18
                   
Annual Sum or Average 53004327.01 0.125014E+11 0.00 34452171.16 0.975033E+09 0.00 0.825649E+09 0.00 0.20
Minimum of Months 0.00 63502834.65 0.00 7583.84 2013520.31 0.00 0.00 0.00 0.18
Maximum of Months 26633780.94 0.249252E+10 0.00 6947550.86 0.193882E+09 0.00 0.336570E+09 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 68056011.91 65804132.92 0.00 4863875.72 583653.45 0.00 0.140372E+09 0.00 0.19
February 42589405.42 0.124584E+09 0.00 3220086.68 4774814.44 0.00 64517037.65 0.00 0.19
March 30412721.14 0.228106E+09 0.00 2535598.68 12931829.22 0.00 60033689.82 0.00 0.21
April 2748679.09 0.398323E+09 0.00 1288453.41 27857676.51 0.00 30931738.43 0.00 0.19
May 54645.92 0.864525E+09 0.00 1422648.81 64446021.76 0.00 3551166.07 0.00 0.20
June 0.00 0.127139E+10 0.00 413204.94 83956052.03 0.00 178525.73 0.00 0.21
July 0.00 0.163280E+10 0.00 796648.98 91810183.35 0.00 831572.43 0.00 0.20
August 0.00 0.193259E+10 0.00 198010.27 0.109255E+09 0.00 0.00 0.00 0.23
September 0.00 0.136510E+10 0.00 669910.83 91018724.97 0.00 1134851.27 0.00 0.20
October 2949.13 0.993916E+09 0.00 441045.03 55434277.54 0.00 2212724.73 0.00 0.20
November 117807.18 0.609516E+09 0.00 1862834.66 32950514.26 0.00 8280642.52 0.00 0.20
December 21611535.16 0.176578E+09 0.00 3288860.83 6033689.43 0.00 62021059.55 0.00 0.18
                   
Annual Sum or Average 0.165594E+09 0.966323E+10 0.00 21001178.83 0.581053E+09 0.00 0.374065E+09 0.00 0.20
Minimum of Months 0.00 65804132.92 0.00 198010.27 583653.45 0.00 0.00 0.00 0.18
Maximum of Months 68056011.91 0.193259E+10 0.00 4863875.72 0.109255E+09 0.00 0.140372E+09 0.00 0.23



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 19233103.84 30645835.53 0.00 2383930.27 1317055.55 0.00 99694398.11 0.00 0.15
February 7088029.98 59523152.44 0.00 1809140.43 5486250.47 0.00 53715911.87 0.00 0.16
March 3303992.27 0.110951E+09 0.00 1581603.82 10797650.40 0.00 50466464.69 0.00 0.17
April 284873.08 0.203950E+09 0.00 992474.31 21073184.20 0.00 20122418.48 0.00 0.16
May 29292.71 0.469536E+09 0.00 868597.82 45556887.67 0.00 1892420.25 0.00 0.18
June 0.00 0.731233E+09 0.00 183086.91 59857093.81 0.00 89173.82 0.00 0.20
July 0.00 0.100065E+10 0.00 404337.46 71343209.95 0.00 341989.97 0.00 0.19
August 0.00 0.121096E+10 0.00 28608.56 91532960.50 0.00 13506.48 0.00 0.22
September 0.00 0.808180E+09 0.00 301156.14 71718761.11 0.00 504536.13 0.00 0.19
October 0.00 0.547320E+09 0.00 223014.07 40746497.76 0.00 846632.68 0.00 0.18
November 86971.82 0.318433E+09 0.00 840215.15 26857282.05 0.00 3889434.65 0.00 0.17
December 4354364.05 85702768.92 0.00 1704613.48 7061706.12 0.00 42138179.48 0.00 0.15
                   
Annual Sum or Average 34380627.74 0.557709E+10 0.00 11320778.43 0.453349E+09 0.00 0.273715E+09 0.00 0.18
Minimum of Months 0.00 30645835.53 0.00 28608.56 1317055.55 0.00 13506.48 0.00 0.15
Maximum of Months 19233103.84 0.121096E+10 0.00 2383930.27 91532960.50 0.00 99694398.11 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 40500908.83 59686754.17 0.00 3587190.09 2345656.85 0.00 0.187252E+09 0.00 0.19
February 15821578.22 0.123330E+09 0.00 2767789.08 9811282.50 0.00 96950214.97 0.00 0.19
March 5326799.88 0.233868E+09 0.00 2396416.13 19210454.16 0.00 88153159.67 0.00 0.21
April 454226.54 0.422403E+09 0.00 1419342.70 37306277.40 0.00 32566050.82 0.00 0.19
May 33346.19 0.917063E+09 0.00 1280396.87 79190437.46 0.00 2934133.33 0.00 0.20
June 0.00 0.136577E+10 0.00 297282.55 0.103065E+09 0.00 105181.96 0.00 0.21
July 0.00 0.179437E+10 0.00 710854.02 0.122379E+09 0.00 650379.72 0.00 0.20
August 0.00 0.214443E+10 0.00 25101.37 0.156638E+09 0.00 8282.49 0.00 0.22
September 0.00 0.147116E+10 0.00 498569.79 0.122910E+09 0.00 607683.22 0.00 0.20
October 0.00 0.103577E+10 0.00 269961.29 70989461.65 0.00 1130159.06 0.00 0.19
November 141385.57 0.638452E+09 0.00 1207189.24 47084499.59 0.00 6357771.52 0.00 0.20
December 7006434.26 0.178253E+09 0.00 2554489.29 12558686.98 0.00 74750283.91 0.00 0.18
                   
Annual Sum or Average 69284679.49 0.103846E+11 0.00 17014582.41 0.783489E+09 0.00 0.491465E+09 0.00 0.20
Minimum of Months 0.00 59686754.17 0.00 25101.37 2345656.85 0.00 8282.49 0.00 0.18
Maximum of Months 40500908.83 0.214443E+10 0.00 3587190.09 0.156638E+09 0.00 0.187252E+09 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 18205537.90 34832456.58 0.00 2517925.13 1407891.60 0.00 0.119470E+09 0.00 0.19
February 6475690.35 71166604.55 0.00 1908678.95 5690966.41 0.00 61109616.11 0.00 0.19
March 3363402.32 0.134153E+09 0.00 1669980.05 10646017.43 0.00 53479334.85 0.00 0.21
April 355707.80 0.244053E+09 0.00 946059.25 20896993.30 0.00 19956267.19 0.00 0.19
May 1805.38 0.535233E+09 0.00 762860.91 45461220.86 0.00 1872284.10 0.00 0.20
June 0.00 0.808246E+09 0.00 166801.34 59796837.43 0.00 76124.56 0.00 0.22
July 0.00 0.106534E+10 0.00 362577.86 70786569.73 0.00 306105.49 0.00 0.20
August 0.00 0.127462E+10 0.00 19534.89 91678854.95 0.00 368.24 0.00 0.23
September 0.00 0.875410E+09 0.00 226832.22 71886856.40 0.00 312732.41 0.00 0.20
October 4134.43 0.609093E+09 0.00 197219.09 40753598.91 0.00 592388.26 0.00 0.20
November 89549.48 0.371032E+09 0.00 770959.61 27194417.85 0.00 3872247.48 0.00 0.20
December 4400552.59 0.102245E+09 0.00 1846338.27 7288270.11 0.00 45347355.38 0.00 0.18
                   
Annual Sum or Average 32896380.25 0.612543E+10 0.00 11395767.58 0.453488E+09 0.00 0.306395E+09 0.00 0.20
Minimum of Months 0.00 34832456.58 0.00 19534.89 1407891.60 0.00 368.24 0.00 0.18
Maximum of Months 18205537.90 0.127462E+10 0.00 2517925.13 91678854.95 0.00 0.119470E+09 0.00 0.23



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:27:32

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.514510E+11 0.125406E+10 0.00 0.453563E+10 -0.876100E+18
February 0.606160E+11 0.143342E+10 0.00 0.243773E+10 -0.832700E+18
March 0.810161E+11 0.178152E+10 0.00 0.129993E+10 -0.983000E+18
April 0.926948E+11 0.167866E+10 0.00 -0.149940E+10 -0.101930E+19
May 0.105454E+12 0.146666E+10 0.00 -0.648302E+10 -0.110020E+19
June 0.105298E+12 0.502682E+09 0.00 -0.114147E+11 -0.106110E+19
July 0.105684E+12 0.206119E+09 0.00 -0.145916E+11 -0.112440E+19
August 0.100469E+12 -423006053.3 0.00 -0.154939E+11 -0.110720E+19
September 0.842466E+11 -358126158.4 0.00 -0.113822E+11 -0.105920E+19
October 0.675809E+11 -244215121.3 0.00 -0.718182E+10 -0.102240E+19
November 0.499969E+11 47946286.06 0.00 -0.207248E+10 -0.901600E+18
December 0.450460E+11 0.585744E+09 0.00 0.249778E+10 -0.856100E+18
           
Annual Sum or Average 0.949553E+12 0.793147E+10 0.00 -0.593479E+11 -0.119433E+20
Minimum of Months 0.450460E+11 -423006053.3 0.00 -0.154939E+11 -0.112440E+19
Maximum of Months 0.105684E+12 0.178152E+10 0.00 0.453563E+10 -0.832700E+18