Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280

Simulation Timestamp: 2023-10-16 08:27:02


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 170.53 333.61 333.61
Net Site Energy 170.53 333.61 333.61
Total Source Energy 511.16 1000.00 1000.00
Net Source Energy 511.16 1000.00 1000.00


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 19.92 13.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 9.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 17.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 156.65 13.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 19.92 13.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 9.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 17.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 25.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 19.92 13.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 9.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 17.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 25.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 140.86 27.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 306.47 27.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 140.86 27.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 306.47 27.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 156.653 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 156.653 100.00
     
Total On-Site and Utility Electric Sources 156.653 100.00
Total Electricity End Uses 156.653 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 67.33
Time Setpoint Not Met During Occupied Cooling 5.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 2129.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
RunPeriod RUNPERIOD 1
Weather File Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Latitude [deg] 42.93
Longitude [deg] -78.7
Elevation [m] 215.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.9815 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.9815 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.9815 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.9815 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.9815 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.9815 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.9815 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.9815 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.9815 9.29 6.7800  
Conditioned Total 511.16             6.9815 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.9815 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 02-JAN-08:30 06-FEB-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 7650.34 31791.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2463.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1507.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2745.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 17692.60 31791.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 7650.34 31791.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2463.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1507.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2745.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 63.08 15.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 29.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 83.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 56.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 79.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 496.12 15.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 123.40 29.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 57.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 163.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 110.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 155.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 970.58 29.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 123.40 29.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 57.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 163.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 110.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 155.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 970.58 29.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.283813
PERIMETER_ZN_1 DIRECT AIR 0.305503
PERIMETER_ZN_2 DIRECT AIR 0.231915
PERIMETER_ZN_3 DIRECT AIR 0.256784
PERIMETER_ZN_4 DIRECT AIR 0.268252
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.283813 0.283813 0.283813 0.283813 0.283813 0.283813 1.00 1.00 0.283813
PSZ-AC:2 0.305503 0.305503 0.305503 0.305503 0.305503 0.305503 1.00 1.00 0.305503
PSZ-AC:3 0.231915 0.231915 0.231915 0.231915 0.231915 0.231915 1.00 1.00 0.231915
PSZ-AC:4 0.256784 0.256784 0.256784 0.256784 0.256784 0.256784 1.00 1.00 0.256784
PSZ-AC:5 0.268252 0.268252 0.268252 0.268252 0.268252 0.268252 1.00 1.00 0.268252
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.283813 0.064622
PSZ-AC:2_OA_CONTROLLER 0.305503 0.048988
PSZ-AC:3_OA_CONTROLLER 0.231915 0.029060
PSZ-AC:4_OA_CONTROLLER 0.256784 0.048988
PSZ-AC:5_OA_CONTROLLER 0.268252 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.283813 5623.57 0.780152
PSZ-AC:2 HP COOLING COIL 0.305503 5829.62 0.794938
PSZ-AC:3 HP COOLING COIL 0.231915 4050.16 0.800489
PSZ-AC:4 HP COOLING COIL 0.256784 5061.34 0.781770
PSZ-AC:5 HP COOLING COIL 0.268252 4645.18 0.800456
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.283813 0.283813 0.283813 0.283813 5623.57 5623.57 40.00 4291.75 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.305503 0.305503 0.305503 0.305503 5829.62 5829.62 40.00 6556.65 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.231915 0.231915 0.231915 0.231915 4050.16 4050.16 40.00 4027.65 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.256784 0.256784 0.256784 0.256784 5061.34 5061.34 40.00 6510.19 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.268252 0.268252 0.268252 0.268252 4645.18 4645.18 40.00 4046.60 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.283813
PSZ-AC:2 FAN 0.305503
PSZ-AC:3 FAN 0.231915
PSZ-AC:4 FAN 0.256784
PSZ-AC:5 FAN 0.268252
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.283813 5623.57
PSZ-AC:2 HEATING COIL 0.305503 5829.62
PSZ-AC:3 HEATING COIL 0.231915 4050.16
PSZ-AC:4 HEATING COIL 0.256784 5061.34
PSZ-AC:5 HEATING COIL 0.268252 4645.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 4291.75
PSZ-AC:2_SUPPHEATCOIL 6556.65
PSZ-AC:3_SUPPHEATCOIL 4027.65
PSZ-AC:4_SUPPHEATCOIL 6510.19
PSZ-AC:5_SUPPHEATCOIL 4046.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 9.70 6.00 -2.20 -3.40 -4.20 2.70 7.50 13.70 18.60 22.00 20.70 16.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 42.93 -78.73 -5.00 215.00 98769 1.1739


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 8.97 26.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1044.832 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1044.832
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4610


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 7.646E-002 6.739E-004 9.053E-004 0.795 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.0791E-003
2 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.2902E-003
3 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.2971E-003
4 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.4868E-003
5 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.3550E-003
6 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.5150E-003
7 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 6.4849E-004
8 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 7.2446E-004
9 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.1070E-002
10 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.0640E-002
11 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.1010E-002
12 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.1258E-002
13 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.0592E-002
14 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.4668E-003
15 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.5319E-003
16 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 2.9977E-003
17 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.1836E-002
18 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.2982E-002
19 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.2301E-002
20 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.4381E-002
21 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.0077E-002
22 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 7.7344E-003
23 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 4.5925E-003
24 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 2.7695E-003
25 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.0829E-003
26 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.3291E-003
27 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.3040E-003
28 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.5377E-003
29 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.3578E-003
30 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.5284E-003
31 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 6.4323E-004
32 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 7.1273E-004
33 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.9943E-003
34 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.0196E-003
35 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.2251E-003
36 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.2478E-003
37 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.2876E-003
38 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.3050E-003
39 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 6.0704E-004
40 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 6.1499E-004
41 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.9880E-003
42 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.9928E-003
43 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.2196E-003
44 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.2238E-003
45 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.2831E-003
46 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.2863E-003
47 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 6.0468E-004
48 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 6.0622E-004
49 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.1550E-003
50 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 3.8742E-003
51 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.4237E-003
52 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 4.1621E-003
53 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 2.1295E-003
54 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.5448E-003
55 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.0270E-003
56 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.1536E-003
57 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.5343E-003
58 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.6991E-003
59 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.4417E-003
60 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.5641E-003
61 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.2964E-003
62 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.3571E-003
63 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.0176E-003
64 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.0875E-003
65 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 5.8387E-003
66 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 4.5828E-003
67 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.7534E-003
68 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.8492E-003
69 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.3069E-003
70 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.4801E-003
71 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.9721E-003
72 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.1821E-003
73 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.7599E-002
74 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 8.0127E-003
75 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.8934E-002
76 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 7.8300E-003
77 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.3557E-002
78 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 6.7018E-003
79 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 5.9313E-003
80 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.4175E-003
81 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.8630E-003
82 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.3812E-003
83 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.8609E-003
84 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.4233E-003
85 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.4280E-003
86 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.6800E-003
87 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.0227E-003
88 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0991E-003
89 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 7.3939E-004
90 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 8.7708E-004
91 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 5.9455E-004
92 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.0269E-004
93 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.9406E-004
94 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.7095E-004
95 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.4191E-004
96 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.0833E-004
97 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.5445E-003
98 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 3.8308E-003
99 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.5988E-003
100 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.9328E-003
101 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 3.6208E-003
102 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.1213E-003
103 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.1909E-003
104 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.6620E-003
105 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 6.4506E-003
106 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 4.6592E-003
107 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.9644E-003
108 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.4913E-003
109 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.3952E-003
110 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.2028E-003
111 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 6.0751E-003
112 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.1179E-003
113 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 7.5681E-004
114 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 9.2961E-004
115 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.0645E-004
116 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 7.3787E-004
117 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.9827E-004
118 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.7520E-004
119 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.5248E-004
120 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 7.3182E-004
121 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 6.7487E-004
122 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 6.9605E-004
123 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 5.4140E-004
124 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.5795E-004
125 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.4665E-004
126 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.5728E-004
127 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 6.0837E-004
128 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 6.1721E-004
129 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 6.6883E-004
130 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 6.7305E-004
131 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.3657E-004
132 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 5.3990E-004
133 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.4309E-004
134 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.4529E-004
135 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 6.0570E-004
136 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 6.0737E-004
137 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.5708E-003
138 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.9093E-003
139 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.4868E-003
140 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.8232E-003
141 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.2656E-003
142 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.4775E-003
143 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.0243E-003
144 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.1003E-003
145 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.2250E-002
146 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.1250E-003
147 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.2232E-002
148 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.6095E-003
149 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.1372E-002
150 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 5.6138E-003
151 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 5.9077E-003
152 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.3736E-003
153 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 5.8564E-003
154 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 4.4713E-003
155 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.5993E-003
156 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.5986E-003
157 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.8362E-003
158 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.0037E-003
159 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.9684E-003
160 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.1454E-003
161 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.3410E-003
162 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.5150E-003
163 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.1940E-003
164 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.3210E-003
165 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.1435E-003
166 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.1971E-003
167 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.0190E-003
168 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.0886E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3142.47736 3770.97283 0.23651 0.28381 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 29.49400 1.33655E-002 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 1067.63376 1281.16051 4.72142E-002 6.46221E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -16.30000 9.24091E-004 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3382.27755 4058.73306 0.25459 0.30550 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 30.30000 1.33670E-002 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 3716.57752 4459.89303 0.16434 0.19721 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -16.30000 9.24091E-004 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2567.83780 3081.40536 0.19326 0.23191 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 26.76600 1.33607E-002 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 2321.55693 2785.86831 0.10266 0.12319 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -16.30000 9.24091E-004 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 2843.05417 3411.66501 0.21399 0.25678 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 29.92800 1.33663E-002 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 3677.28244 4412.73893 0.16261 0.19513 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -16.30000 9.24091E-004 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 2970.15623 3564.18747 0.22354 0.26825 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.06800 1.33630E-002 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 2337.58779 2805.10535 0.10337 0.12404 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -16.30000 9.24091E-004 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4139.90 0.28381 0.28381 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 4291.75 6.46221E-002 6.46221E-002 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 4366.49 0.30550 0.30550 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 6556.65 0.19721 0.19721 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3132.37 0.23191 0.23191 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 4027.65 0.12319 0.12319 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 3707.90 0.25678 0.25678 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 6510.19 0.19513 0.19513 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 3652.32 0.26825 0.26825 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 4046.60 0.12404 0.12404 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.28381
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.30550
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.23191
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.25678
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.26825
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.28381
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.28381
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.28381
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.28381
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.28381
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.28381
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.30550
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.30550
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.30550
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.30550
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.30550
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.30550
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.23191
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.23191
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.23191
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.23191
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.23191
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.23191
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.25678
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.25678
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.25678
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.25678
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.25678
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.25678
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.26825
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.26825
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.26825
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.26825
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.26825
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.26825
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.28381
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.30550
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.23191
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.25678
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.26825
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.28381
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28381
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5623.56631
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.78015
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.28381
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.28381
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.28381
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.28381
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5623.56631
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5623.56631
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 4291.75227
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.28381
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.28381
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5623.56631
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 4291.75227
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30550
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.30550
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5829.62382
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.79494
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.30550
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.30550
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.30550
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.30550
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5829.62382
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5829.62382
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 6556.65442
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.30550
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.30550
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5829.62382
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 6556.65442
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.23191
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.23191
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4050.15555
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80049
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.23191
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.23191
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.23191
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.23191
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4050.15555
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4050.15555
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 4027.64656
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.23191
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.23191
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4050.15555
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 4027.64656
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.25678
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.25678
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5061.34314
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.78177
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.25678
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.25678
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.25678
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.25678
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5061.34314
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5061.34314
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 6510.18720
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.25678
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.25678
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5061.34314
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 6510.18720
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.26825
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.26825
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4645.18063
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80046
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.26825
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.26825
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.26825
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.26825
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4645.18063
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4645.18063
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 4046.60341
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.26825
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.26825
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4645.18063
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 4046.60341
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 5400.6 3.41 11.62 12.17 11.52 11.55
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 5589.7 3.38 11.54 12.09 11.43 11.43
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 3868.3 3.33 11.35 11.87 11.23 11.14
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 4859.6 3.40 11.61 12.16 11.51 11.53
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4434.8 3.32 11.33 11.85 11.21 11.11


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 5849.9 3238.9 7.42 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 6072.9 3366.3 7.41 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 4234.4 2353.9 7.35 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 5266.1 2916.1 7.40 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 4858.3 2701.5 7.37 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 7.2803523017E-002 0.1306328674 Pass Pass 0.5309054497 3.3745476147 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 0.2877849091 0.2840181842 Pass Pass 0.6758562038 1.0647200490 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 0.3160587401 0.3096972901 Pass Pass 0.6674127333 1.0402533583 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 0.3055142495 0.2986701643 Pass Pass 0.6736619954 1.0571116937 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 0.3166245764 0.3106071937 Pass Pass 0.6652232110 1.0356558580 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.1342124511 0.1377461976 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 907.26 43.50 0.00 40.05 -0.103095E+11 -0.103095E+11



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 5.10 270.00
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 30.30 9.30 21.80 Wetbulb [C] 5.70 240.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 44.00 33      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 67.00 33      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.473 0.509 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.219 0.227 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.473 0.509 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.246 0.257 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.473 0.509 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.219 0.227 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.473 0.509 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.246 0.257 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.118 0.122 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.118 0.122 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.118 0.122 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.118 0.122 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.118 0.122 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.118 0.122 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.118 0.122 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.118 0.122 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.118 0.122 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.118 0.122 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.363_SHGC_SOUTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.363_SHGC_SOUTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.363_SHGC_SOUTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.363_SHGC_SOUTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.363_SHGC_SOUTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.363_SHGC_SOUTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.363_SHGC_SOUTH_0.378   3.91 0.00 0.00 3.91 3.91 2.062 0.379 0.417             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.363_SHGC_EAST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.363_SHGC_EAST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.363_SHGC_EAST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.363_SHGC_EAST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.363_SHGC_NORTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.363_SHGC_NORTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.363_SHGC_NORTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.363_SHGC_NORTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.363_SHGC_NORTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.363_SHGC_NORTH_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.363_SHGC_WEST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.363_SHGC_WEST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.363_SHGC_WEST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.363_SHGC_WEST_0.378   2.79 0.00 0.00 2.79 2.79 2.062 0.379 0.417             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.062 0.379 0.417                      
North Total or Average             16.72 2.062 0.379 0.417                      
Non-North Total or Average             42.93 2.062 0.379 0.417                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 1.00 1.00 1.00 0.00 0.31 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 1.00 1.00 1.00 0.00 0.31 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 1.00 1.00 1.00 0.00 0.31 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 1.00 1.00 1.00 0.00 0.31 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 1.00 1.00 1.00 0.00 0.31 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 1.00 1.00 1.00 0.03 0.31 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.64 0.39 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.55 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 1.00 0.00 0.00 0.83 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 1.00 0.00 0.00 0.83 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 1.00 0.00 0.00 0.83 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 1.00 0.00 0.00 0.83 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.9815 149.66 1044.83 LightsWired LTG_SCH_OFFICE 55.32 168.00 44.56 0.0000 Y 8.74
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 36.33 0.0000 Y 5.40
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 37.25 0.0000 Y 3.29
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.25 0.0000 Y 5.69
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 37.35 0.0000 Y 3.29
Interior Lighting Total       6.9815 511.16 3568.64               26.41


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 87.95 AstronomicalClock -   42.04 42.04 0.69
EXTERIOR_LIGHTS_B 200.47 AstronomicalClock -   83.67 62.85 2.37
EXTERIOR_LIGHTS_C 773.25 AstronomicalClock -   83.67 47.45 6.89
Exterior Lighting Total 1061.67           9.95



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5623.57 4387.24 1236.33 0.78 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5829.62 4634.19 1195.43 0.79 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4050.16 3242.10 808.05 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5061.34 3956.80 1104.54 0.78 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4645.18 3718.27 926.92 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   5400.6 3.41 11.62 12.17 11.52 11.55
PSZ-AC:2 HP COOLING COIL   5589.7 3.38 11.54 12.09 11.43 11.43
PSZ-AC:3 HP COOLING COIL   3868.3 3.33 11.35 11.87 11.23 11.14
PSZ-AC:4 HP COOLING COIL   4859.6 3.40 11.61 12.16 11.51 11.53
PSZ-AC:5 HP COOLING COIL   4434.8 3.32 11.33 11.85 11.21 11.11
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 5849.9 3238.9 7.42 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 6072.9 3366.3 7.41 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 4234.4 2353.9 7.35 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 5266.1 2916.1 7.40 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 4858.3 2701.5 7.37 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   5623.57 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   4291.75 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   5829.62 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   6556.65 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4050.16 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   4027.65 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   5061.34 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   6510.19 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   4645.18 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   4046.60 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.28 317.90 1120.11 1.00 1.94 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.31 342.20 1120.11 1.00 1.88 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.23 259.77 1120.11 1.00 2.10 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.26 287.63 1120.11 1.00 2.01 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.27 300.47 1120.11 1.00 1.98 General BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3142.48 3770.97 25.20 0.237 0.284 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 23.89 23.89 0.00907 29.49 0.01337 0.065 0.00
PERIMETER_ZN_1 3382.28 4058.73 35.78 0.255 0.306 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 23.89 23.89 0.00913 30.30 0.01337 0.049 0.00
PERIMETER_ZN_2 2567.84 3081.41 45.79 0.193 0.232 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 23.89 23.89 0.00903 26.77 0.01336 0.029 0.00
PERIMETER_ZN_3 2843.05 3411.67 30.07 0.214 0.257 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 23.89 23.89 0.00925 29.93 0.01337 0.049 0.00
PERIMETER_ZN_4 2970.16 3564.19 52.96 0.224 0.268 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 23.89 23.89 0.00896 28.07 0.01336 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1067.63 1281.16 8.56 0.047 0.065 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00800 -16.30 0.00092 0.065 0.00
PERIMETER_ZN_1 3716.58 4459.89 39.31 0.164 0.197 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00740 -16.30 0.00092 0.049 0.00
PERIMETER_ZN_2 2321.56 2785.87 41.39 0.103 0.123 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00737 -16.30 0.00092 0.029 0.00
PERIMETER_ZN_3 3677.28 4412.74 38.90 0.163 0.195 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00740 -16.30 0.00092 0.049 0.00
PERIMETER_ZN_4 2337.59 2805.11 41.68 0.103 0.124 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00737 -16.30 0.00092 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.28 0.28 0.06 0.06 0.2838 0.2838 0.2838 1.0000 1.0000
PSZ-AC:2 0.31 0.31 0.20 0.20 0.3055 0.3055 0.3055 1.0000 1.0000
PSZ-AC:3 0.23 0.23 0.12 0.12 0.2319 0.2319 0.2319 1.0000 1.0000
PSZ-AC:4 0.26 0.26 0.20 0.20 0.2568 0.2568 0.2568 1.0000 1.0000
PSZ-AC:5 0.27 0.27 0.12 0.12 0.2683 0.2683 0.2683 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5623.566 4387.236 0.283813 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 5655.04 4488.88 0.283813 26.10 18.11 0.01004788 12.80 11.87 0.00850000 29.49 0.01336553 21.60 22.7692 23.89 0.00907388 47.8932 3127.02 0.00 5622.60 4328.03
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5623.566 5623.566 0.283813 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 5623.57 5623.57 0.283813 12.59 9.60 0.00638887 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 22.7692 21.11 0.00800000 50.0789 1066.97 0.00 5630.96 5630.96
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 4291.752 4291.752 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 4291.75 4291.75 0.283813 12.59 9.60 0.00638887 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 22.7692 21.11 0.00800000 50.0789 1066.97 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 5829.624 4634.189 0.305503 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 5797.93 4736.52 0.305503 25.85 17.85 0.00981312 12.80 11.87 0.00850000 30.30 0.01336696 21.83 16.0351 23.89 0.00913443 48.2110 3382.28 0.00 5828.62 4569.29
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 5829.624 5829.624 0.305503 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5829.62 5829.62 0.305503 15.11 10.67 0.00636547 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 16.0351 21.11 0.00740464 46.4008 3716.58 0.00 5837.28 5837.28
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 6556.654 6556.654 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6556.65 6556.65 0.305503 15.11 10.67 0.00636547 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 16.0351 21.11 0.00740464 46.4008 3716.58 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4050.156 3242.104 0.231915 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 4068.81 3415.37 0.231915 25.18 17.43 0.00957060 12.80 11.87 0.00850000 26.77 0.01336069 20.80 12.5305 23.89 0.00902765 47.6524 2567.84 0.00 4049.46 3196.03
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4050.156 4050.156 0.231915 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4050.16 4050.16 0.231915 16.42 11.42 0.00656068 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 12.5305 21.11 0.00736816 46.1753 2321.56 0.00 4055.48 4055.48
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 4027.647 4027.647 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4027.65 4027.65 0.231915 16.42 11.42 0.00656068 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 12.5305 21.11 0.00736816 46.1753 2321.56 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 5061.343 3956.804 0.256784 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 5070.67 4025.91 0.256784 25.97 18.06 0.01003343 12.80 11.87 0.00850000 29.93 0.01336630 21.72 19.0774 23.89 0.00925005 48.8105 2836.75 0.00 5060.47 3902.60
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 5061.343 5061.343 0.256784 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5061.34 5061.34 0.256784 13.97 9.96 0.00616361 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 19.0774 21.11 0.00739881 46.3647 3677.28 0.00 5067.99 5067.99
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 6510.187 6510.187 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6510.19 6510.19 0.256784 13.97 9.96 0.00616361 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 19.0774 21.11 0.00739881 46.3647 3677.28 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4645.181 3718.265 0.268252 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 4628.08 3970.04 0.268252 25.28 17.35 0.00943358 12.80 11.87 0.00850000 28.07 0.01336300 21.18 10.8332 23.89 0.00895558 47.2774 2968.12 0.00 4644.38 3665.63
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4645.181 4645.181 0.268252 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4645.18 4645.18 0.268252 17.06 11.80 0.00667358 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 10.8332 21.11 0.00737211 46.1998 2337.59 0.00 4651.29 4651.29
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 4046.603 4046.603 -999.0 -999.0 -999.000 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4046.60 4046.60 0.268252 17.06 11.80 0.00667358 40.00 20.89 0.00800000 -16.30 0.00092409 -16.30 10.8332 21.11 0.00737211 46.1998 2337.59 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5623.566 4387.236 0.283813 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.5185 1004.8586 1.1739 PSZ-AC:1 FAN Fan:OnOff 0.283813 0.33317582   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 Sensible 5655.04 4488.88 1.0056 0.33317582 0.283813 26.10 18.11 0.01004788 51840.7 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 317.902 5337.14 29.49 0.01336553 21.60 0.06462207 22.7692 23.89 0.00906978 23.89 0.00907388 47.8932 3127.02 0.00 5622.60 4328.03 0.32001789 26.67 19.44 0.01118466 55322.4 13.44 13.43 0.00959859 37752.7
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5623.566 5623.566 0.283813 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:1 FAN Fan:OnOff 0.283813 0.33317582   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 5623.57 5623.57 1.0000 0.33317582 0.283813 12.59 9.60 0.00638887 28780.7 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5623.57 -16.30 0.00092409 -16.30 0.06462207 22.7692 21.11 0.00800000 21.11 0.00800000 50.0789 1066.97 0.00 5630.96 5630.96 0.32728850 21.11 15.56 0.00875166 43444.1 37.96 21.12 0.00875166 60649.0
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4291.752 4291.752 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:1 FAN Fan:OnOff 0.283813 0.33317582   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 4291.75 4291.75 1.0000 0.33317582 0.283813 12.59 9.60 0.00638887 28780.7 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4291.75 -16.30 0.00092409 -16.30 0.06462207 22.7692 21.11 0.00800000 21.11 0.00800000 50.0789 1066.97 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5829.624 4634.189 0.305503 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.0821 1004.8586 1.1739 PSZ-AC:2 FAN Fan:OnOff 0.305503 0.35863712   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 5797.93 4736.52 0.9946 0.35863712 0.305503 25.85 17.85 0.00981312 50987.7 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 342.196 5455.73 30.30 0.01336696 21.83 0.04898771 16.0351 23.89 0.00913443 23.89 0.00913443 48.2110 3382.28 0.00 5828.62 4569.29 0.34447367 26.67 19.44 0.01118466 55322.4 13.70 13.68 0.00975129 38402.0
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5829.624 5829.624 0.305503 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:2 FAN Fan:OnOff 0.305503 0.35863712   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5829.62 5829.62 1.0000 0.35863712 0.305503 15.11 10.67 0.00636547 31281.4 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5829.62 -16.30 0.00092409 -16.30 0.04898771 16.0351 21.11 0.00740464 21.11 0.00740464 46.4008 3716.58 0.00 5837.28 5837.28 0.35229989 21.11 15.56 0.00875166 43444.1 37.34 20.93 0.00875166 60013.2
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 6556.654 6556.654 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:2 FAN Fan:OnOff 0.305503 0.35863712   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6556.65 6556.65 1.0000 0.35863712 0.305503 15.11 10.67 0.00636547 31281.4 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6556.65 -16.30 0.00092409 -16.30 0.04898771 16.0351 21.11 0.00740464 21.11 0.00740464 46.4008 3716.58 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4050.156 3242.104 0.231915 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.6313 1004.8586 1.1739 PSZ-AC:3 FAN Fan:OnOff 0.231915 0.27225070   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 Sensible 4068.81 3415.37 1.0046 0.27225070 0.231915 25.18 17.43 0.00957060 49688.3 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 259.770 3809.04 26.77 0.01336069 20.80 0.02906014 12.5305 23.89 0.00902765 23.89 0.00902765 47.6524 2567.84 0.00 4049.46 3196.03 0.26149886 26.67 19.44 0.01118466 55322.4 14.72 14.22 0.00990508 39836.8
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4050.156 4050.156 0.231915 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:3 FAN Fan:OnOff 0.231915 0.27225070   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4050.16 4050.16 1.0000 0.27225070 0.231915 16.42 11.42 0.00656068 33108.3 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4050.16 -16.30 0.00092409 -16.30 0.02906014 12.5305 21.11 0.00736816 21.11 0.00736816 46.1753 2321.56 0.00 4055.48 4055.48 0.26743995 21.11 15.56 0.00875166 43444.1 35.96 20.52 0.00875166 58608.2
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4027.647 4027.647 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:3 FAN Fan:OnOff 0.231915 0.27225070   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4027.65 4027.65 1.0000 0.27225070 0.231915 16.42 11.42 0.00656068 33108.3 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4027.65 -16.30 0.00092409 -16.30 0.02906014 12.5305 21.11 0.00736816 21.11 0.00736816 46.1753 2321.56 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5061.343 3956.804 0.256784 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.4916 1004.8586 1.1739 PSZ-AC:4 FAN Fan:OnOff 0.256784 0.30144552   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 5070.67 4025.91 1.0018 0.30144552 0.256784 25.97 18.06 0.01003343 51676.3 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 287.626 4783.05 29.93 0.01336630 21.72 0.04898771 19.0774 23.89 0.00924771 23.89 0.00925005 48.8105 2836.75 0.00 5060.47 3902.60 0.28954070 26.67 19.44 0.01118466 55322.4 13.49 13.47 0.00961675 37844.8
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5061.343 5061.343 0.256784 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:4 FAN Fan:OnOff 0.256784 0.30144552   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5061.34 5061.34 1.0000 0.30144552 0.256784 13.97 9.96 0.00616361 29614.3 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5061.34 -16.30 0.00092409 -16.30 0.04898771 19.0774 21.11 0.00739881 21.11 0.00739881 46.3647 3677.28 0.00 5067.99 5067.99 0.29611888 21.11 15.56 0.00875166 43444.1 37.87 21.09 0.00875166 60558.8
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 6510.187 6510.187 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:4 FAN Fan:OnOff 0.256784 0.30144552   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6510.19 6510.19 1.0000 0.30144552 0.256784 13.97 9.96 0.00616361 29614.3 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6510.19 -16.30 0.00092409 -16.30 0.04898771 19.0774 21.11 0.00739881 21.11 0.00739881 46.3647 3677.28 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4645.181 3718.265 0.268252 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.3766 1004.8586 1.1739 PSZ-AC:5 FAN Fan:OnOff 0.268252 0.31490728   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 4628.08 3970.04 0.9963 0.31490728 0.268252 25.28 17.35 0.00943358 49433.7 12.80 11.87 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 300.471 4327.61 28.07 0.01336300 21.18 0.02906014 10.8332 23.89 0.00895619 23.89 0.00895558 47.2774 2968.12 0.00 4644.38 3665.63 0.30247082 26.67 19.44 0.01118466 55322.4 14.82 14.27 0.00991595 39967.6
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4645.181 4645.181 0.268252 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:5 FAN Fan:OnOff 0.268252 0.31490728   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4645.18 4645.18 1.0000 0.31490728 0.268252 17.06 11.80 0.00667358 34040.0 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4645.18 -16.30 0.00092409 -16.30 0.02906014 10.8332 21.11 0.00737211 21.11 0.00737211 46.1998 2337.59 0.00 4651.29 4651.29 0.30934277 21.11 15.56 0.00875166 43444.1 35.84 20.48 0.00875166 58480.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 4046.603 4046.603 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1739 PSZ-AC:5 FAN Fan:OnOff 0.268252 0.31490728   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4046.60 4046.60 1.0000 0.31490728 0.268252 17.06 11.80 0.00667358 34040.0 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4046.60 -16.30 0.00092409 -16.30 0.02906014 10.8332 21.11 0.00737211 21.11 0.00737211 46.1998 2337.59 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2061.50 2789.83 1080.50
PERIMETER_ZN_1 2568.67 3120.83 1776.00
PERIMETER_ZN_2 2251.00 2525.50 1547.83
PERIMETER_ZN_3 2560.67 3227.67 1981.50
PERIMETER_ZN_4 2646.33 3062.67 1861.83
ATTIC 0.00 0.00 0.00
Facility 3143.83 3360.50 2129.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 13.00 5.17 13.00 5.17
PERIMETER_ZN_1 71.67 0.83 48.67 0.83
PERIMETER_ZN_2 83.17 0.67 28.00 0.67
PERIMETER_ZN_3 107.83 0.83 53.00 0.83
PERIMETER_ZN_4 84.67 0.83 25.33 0.83
ATTIC 0.00 0.00 0.00 0.00
Facility 181.83 5.17 67.33 5.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.366 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.365 0.281 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.332 0.085 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.365 0.070 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.365 0.079 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 703501.65 0.00 703501.65 0.00 703501.65 2037921.45 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_1 533299.81 0.00 533299.81 601346.83 1134646.63 1544876.42 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_2 254083.49 0.00 254083.49 195477.06 449560.55 916440.58 6463.86 2296.14 0.00 496.09
PERIMETER_ZN_3 533299.81 0.00 533299.81 293215.59 826515.39 1544876.42 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_4 316360.31 0.00 316360.31 195477.06 511837.37 916440.58 5736.00 3024.00 0.00 0.00
Total Facility 2340545.06 0.00 2340545.06 1285516.53 3626061.59 6960555.45 6463.86 3024.00 0.00 496.09


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0456 0.0000 0.0456 0.0000 0.0456 0.0646 1260.00 3024.00 0.00
PERIMETER_ZN_1 0.0346 0.0000 0.0346 0.0266 0.0612 0.0490 1260.00 3024.00 0.00
PERIMETER_ZN_2 0.0187 0.0000 0.0187 0.0048 0.0235 0.0291 1260.00 2268.00 0.00
PERIMETER_ZN_3 0.0346 0.0000 0.0346 0.0067 0.0412 0.0490 1260.00 3024.00 0.00
PERIMETER_ZN_4 0.0205 0.0000 0.0205 0.0044 0.0250 0.0291 1260.00 3024.00 0.00
Total Facility 0.1540 0.0000 0.1540 0.0426 0.1965 0.2207 1987.86 3024.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 969496.08 0.00 969496.08 2037921.45 5736.00 0.00 3024.00 0.00
PSZ-AC:2 734940.81 0.00 734940.81 1544876.42 5736.00 0.00 3024.00 0.00
PSZ-AC:3 350152.62 0.00 350152.62 916440.58 6446.45 1.32 2312.24 479.59
PSZ-AC:4 734940.81 0.00 734940.81 1544876.42 5736.00 0.00 3024.00 0.00
PSZ-AC:5 435976.34 0.00 435976.34 916440.58 5736.00 0.00 3024.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0629 0.0000 0.0629 0.0646 1260.00 0.00 3024.00
PSZ-AC:2 0.0477 0.0000 0.0477 0.0490 1260.00 0.00 3024.00
PSZ-AC:3 0.0257 0.0000 0.0257 0.0291 1260.00 0.00 2268.00
PSZ-AC:4 0.0477 0.0000 0.0477 0.0490 1260.00 0.00 3024.00
PSZ-AC:5 0.0283 0.0000 0.0283 0.0291 1260.00 0.00 3024.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 2747.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0891 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0675 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0400 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0675 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0400 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 555
Defaulted Fields 365
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 156.65 1248.68 14-JAN-11:00 17692.60 02-JAN-08:30
Electricity:Building 74.70 677.68 01-JAN-00:10 5866.25 02-JAN-16:50
Electricity:Zone:CORE_ZN 22.88 198.41 01-JAN-00:10 1717.53 02-JAN-08:10
Electricity:SpaceType:GENERAL 74.70 677.68 01-JAN-00:10 5866.25 02-JAN-16:50
InteriorLights:Electricity 26.41 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.41 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
LightsWired:InteriorLights:Electricity 26.41 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.41 110.04 01-JAN-00:10 2540.94 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_1 16.12 150.41 01-JAN-00:10 1302.00 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.40 24.42 01-JAN-00:10 563.96 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.40 24.42 01-JAN-00:10 563.96 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_2 9.64 89.23 01-JAN-00:10 772.36 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 14.49 01-JAN-00:10 334.55 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 14.49 01-JAN-00:10 334.55 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_3 16.41 150.41 01-JAN-00:10 1302.00 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.69 24.42 01-JAN-00:10 563.96 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.69 24.42 01-JAN-00:10 563.96 02-JAN-16:50
Electricity:Zone:PERIMETER_ZN_4 9.65 89.23 01-JAN-00:10 772.36 02-JAN-16:50
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.29 14.49 01-JAN-00:10 334.55 02-JAN-16:50
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.29 14.49 01-JAN-00:10 334.55 02-JAN-16:50
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
ElectricityPurchased:Plant 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
Cogeneration:ElectricityPurchased 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
General:Cogeneration:ElectricityPurchased 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
ElectricityNet:Plant 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
Cogeneration:ElectricityNet 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
General:Cogeneration:ElectricityNet 156.65 1248.68 01-APR-10:00 17692.60 02-JAN-08:30
ExteriorLights:Electricity 9.95 0.00 01-JAN-08:00 1061.67 01-JAN-06:10
General:ExteriorLights:Electricity 9.95 0.00 01-JAN-08:00 1061.67 01-JAN-06:10
Electricity:HVAC 46.91 0.00 11-JAN-01:30 9187.21 02-JAN-09:20
Fans:Electricity 17.79 0.00 01-JAN-00:40 1507.96 02-JAN-06:10
General:Fans:Electricity 17.79 0.00 01-JAN-00:40 1507.96 02-JAN-06:10
Cooling:Electricity 9.21 0.00 01-JAN-00:10 5147.04 21-JUL-05:10
General:Cooling:Electricity 9.21 0.00 01-JAN-00:10 5147.04 21-JUL-05:10
Heating:Electricity 19.92 0.00 11-JAN-01:30 7679.25 02-JAN-09:20
General:Heating:Electricity 19.92 0.00 11-JAN-01:30 7679.25 02-JAN-09:20
Electricity:Plant 25.09 571.00 01-JAN-00:10 2829.27 17-FEB-12:20
WaterSystems:Electricity 25.09 571.00 01-JAN-00:10 2829.27 17-FEB-12:20
Water Heater:WaterSystems:Electricity 25.09 571.00 01-JAN-00:10 2829.27 17-FEB-12:20
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 06-FEB-19:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 06-FEB-19:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 13.88 0.00 01-JAN-00:20 31791.05 06-FEB-07:10
NaturalGas:HVAC 13.88 0.00 01-JAN-00:20 31791.05 06-FEB-07:10
Heating:NaturalGas 13.88 0.00 01-JAN-00:20 31791.05 06-FEB-07:10
General:Heating:NaturalGas 13.88 0.00 01-JAN-00:20 31791.05 06-FEB-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 23-MAR-11:30
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 23-MAR-11:30
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 16-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 16-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 162.34 0.00 01-JAN-00:40 63943.13 13-FEB-06:10
EnergyTransfer:Building 71.85 0.00 01-JAN-00:40 32490.14 13-FEB-06:20
EnergyTransfer:Zone:CORE_ZN 15.41 0.00 01-JAN-00:10 7172.28 02-JAN-06:10
Heating:EnergyTransfer 34.67 0.00 01-JAN-00:40 32490.14 13-FEB-06:20
Heating:EnergyTransfer:Zone:CORE_ZN 1.93 0.00 01-JAN-00:10 7172.28 02-JAN-06:10
General:Heating:EnergyTransfer 34.67 0.00 01-JAN-00:40 32490.14 13-FEB-06:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 1.93 0.00 01-JAN-00:10 7172.28 02-JAN-06:10
Cooling:EnergyTransfer 37.18 0.00 01-JAN-00:10 14612.99 07-AUG-05:10
Cooling:EnergyTransfer:Zone:CORE_ZN 13.48 0.00 01-JAN-00:10 4590.81 07-AUG-05:10
General:Cooling:EnergyTransfer 37.18 0.00 01-JAN-00:10 14612.99 07-AUG-05:10
General:Cooling:EnergyTransfer:Zone:CORE_ZN 13.48 0.00 01-JAN-00:10 4590.81 07-AUG-05:10
EnergyTransfer:Zone:PERIMETER_ZN_1 18.18 0.00 01-JAN-00:40 7949.96 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 9.90 0.00 01-JAN-00:40 7949.96 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 9.90 0.00 01-JAN-00:40 7949.96 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 8.28 0.00 01-JAN-00:10 4282.33 21-SEP-14:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 8.28 0.00 01-JAN-00:10 4282.33 21-SEP-14:10
EnergyTransfer:Zone:PERIMETER_ZN_2 10.68 0.00 01-JAN-00:40 5633.11 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 6.00 0.00 01-JAN-00:40 5633.11 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 6.00 0.00 01-JAN-00:40 5633.11 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 4.68 0.00 01-JAN-00:10 2712.64 17-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 4.68 0.00 01-JAN-00:10 2712.64 17-JUL-08:30
EnergyTransfer:Zone:PERIMETER_ZN_3 16.70 0.00 01-JAN-00:40 6831.96 13-FEB-06:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 10.61 0.00 01-JAN-00:40 6831.96 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 10.61 0.00 01-JAN-00:40 6831.96 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 6.10 0.00 01-JAN-00:10 2789.39 21-JUL-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 6.10 0.00 01-JAN-00:10 2789.39 21-JUL-13:50
EnergyTransfer:Zone:PERIMETER_ZN_4 10.88 0.00 01-JAN-00:40 6230.72 13-FEB-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 6.23 0.00 01-JAN-00:40 6230.72 13-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 6.23 0.00 01-JAN-00:40 6230.72 13-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 4.65 0.00 01-JAN-00:10 2663.23 14-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 4.65 0.00 01-JAN-00:10 2663.23 14-AUG-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 110.31 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 110.31 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 110.31 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 110.31 02-JAN-07:10
EnergyTransfer:HVAC 90.49 0.00 01-JAN-00:40 32127.81 13-FEB-07:10
CoolingCoils:EnergyTransfer 42.08 0.00 01-JAN-00:10 26174.36 21-JUL-05:10
HeatingCoils:EnergyTransfer 48.40 0.00 01-JAN-00:40 32127.81 13-FEB-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 0.00 01-JAN-00:10 110.31 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 110.31 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 110.31 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 1.931 -13.480 0.000 0.000 5.338 8.739 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -16.669
PERIMETER_ZN_1 0.000 0.000 9.899 -8.276 0.000 0.000 4.108 5.402 10.719 16.275 0.000 0.106 0.000 0.000 -9.761 0.000 -9.447 -19.025
PERIMETER_ZN_2 0.000 0.000 6.000 -4.679 0.000 0.000 1.785 3.285 6.359 7.549 0.000 0.012 0.000 0.000 -5.226 0.000 -3.024 -12.060
PERIMETER_ZN_3 0.000 0.000 10.607 -6.095 0.000 0.000 4.146 5.687 10.719 4.301 0.000 0.022 0.000 0.000 -8.217 0.000 -4.465 -16.705
PERIMETER_ZN_4 0.000 0.000 6.235 -4.650 0.000 0.000 2.438 3.295 6.359 7.585 0.000 0.012 0.000 0.000 -5.446 0.000 -3.054 -12.773
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 8.989 24.537 0.000 0.000 0.000 -33.526 -0.000
Total Facility 0.000 0.000 34.672 -37.180 0.000 0.000 17.815 26.408 48.296 35.710 0.000 9.141 24.538 0.000 -28.650 0.000 -53.516 -77.233


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 03-JUL-05:01 0.00 0.00 0.00 -5179.75 0.00 0.00 53.02 32.22 486.79 0.00 0.00 0.00 4607.73 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 04-AUG-05:02 0.00 0.00 0.00 -5237.24 0.00 0.00 44.80 24.42 369.02 0.00 0.00 0.00 5557.67 0.00 -514.80 0.00 -243.88 0.00
PERIMETER_ZN_2 28-SEP-14:01 0.00 0.00 0.00 -3666.15 0.00 0.00 244.20 274.34 437.82 0.00 0.00 0.00 2792.93 0.00 -29.93 0.00 -53.21 0.00
PERIMETER_ZN_3 18-AUG-05:02 0.00 0.00 0.00 -4301.34 0.00 0.00 44.83 24.42 369.02 0.00 0.00 0.00 4277.96 0.00 -327.40 0.00 -87.49 0.00
PERIMETER_ZN_4 04-AUG-05:02 0.00 0.00 0.00 -4096.57 0.00 0.00 25.77 14.49 218.91 0.00 0.00 0.00 4190.20 0.00 -284.76 0.00 -68.04 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 18-AUG-05:02 0.00 0.00 0.00 -21468.50 0.00 0.00 192.86 110.04 1662.65 0.00 0.00 926.45 20185.42 0.00 -1202.21 0.00 -406.72 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-06:01 0.00 0.00 7730.92 0.00 0.00 0.00 90.55 32.22 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8340.48
PERIMETER_ZN_1 13-FEB-06:01 0.00 0.00 9007.15 0.00 0.00 0.00 71.33 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -885.08 0.00 -1456.48 -7130.36
PERIMETER_ZN_2 18-DEC-06:01 0.00 0.00 6531.42 0.00 0.00 0.00 40.59 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -275.18 0.00 -142.87 -6387.35
PERIMETER_ZN_3 13-FEB-06:01 0.00 0.00 7614.13 0.00 0.00 0.00 71.48 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -690.19 0.00 -1132.08 -6256.79
PERIMETER_ZN_4 18-DEC-06:01 0.00 0.00 7510.92 0.00 0.00 0.00 40.57 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -269.24 0.00 -144.23 -7371.41
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-06:01 0.00 0.00 37252.23 0.00 0.00 0.00 313.66 110.04 1662.65 0.00 0.00 433.00 0.00 0.00 -1627.79 0.00 -982.61 -37161.18



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2838 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2838 0.2277 1.0000 Not calculated 0.0646 0.2277    
PSZ-AC:2 0.3055 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3055 0.1604 1.0000 Not calculated 0.0490 0.1604    
PSZ-AC:3 0.2319 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2319 0.1253 1.0000 Not calculated 0.0291 0.1253    
PSZ-AC:4 0.2568 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2568 0.1908 1.0000 Not calculated 0.0490 0.1908    
PSZ-AC:5 0.2683 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2683 0.1083 1.0000 Not calculated 0.0291 0.1083    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2838 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2838 1.0000 1.0000 Not calculated 0.0646 0.2277    
PSZ-AC:2 0.3055 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3055 1.0000 1.0000 Not calculated 0.0490 0.1604    
PSZ-AC:3 0.2319 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2319 1.0000 1.0000 Not calculated 0.0291 0.1253    
PSZ-AC:4 0.2568 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2568 1.0000 1.0000 Not calculated 0.0490 0.1908    
PSZ-AC:5 0.2683 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2683 1.0000 1.0000 Not calculated 0.0291 0.1083    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2838 0.2838 0.2838 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3055 0.3055 0.3055 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2319 0.2319 0.2319 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2568 0.2568 0.2568 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2683 0.2683 0.2683 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2838 0.2838 0.2838 0.2838 0.0646 1.0000
PSZ-AC:2 0.3055 0.3055 0.3055 0.3055 0.0490 1.0000
PSZ-AC:3 0.2319 0.2319 0.2319 0.2319 0.0291 1.0000
PSZ-AC:4 0.2568 0.2568 0.2568 0.2568 0.0490 1.0000
PSZ-AC:5 0.2683 0.2683 0.2683 0.2683 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2838 0.2838 0.2838 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3055 0.3055 0.3055 No 0.0490 0.2484 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2319 0.2319 0.2319 No 0.0291 0.2359 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2568 0.2568 0.2568 No 0.0490 0.2511 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2683 0.2683 0.2683 No 0.0291 0.2343 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2838 0.2838 0.2838 0.2838 0.0646 1.0000
PSZ-AC:2 0.3055 0.3055 0.3055 0.3055 0.0490 1.0000
PSZ-AC:3 0.2319 0.2319 0.2319 0.2319 0.0291 1.0000
PSZ-AC:4 0.2568 0.2568 0.2568 0.2568 0.0490 1.0000
PSZ-AC:5 0.2683 0.2683 0.2683 0.2683 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 67.33
Number of hours cooling loads not met 5.17
Number of hours not met 72.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 19.92 7679.25 13.88 31791.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 9.21 5147.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.41 2540.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.95 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 17.79 1507.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 25.09 2829.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 156.65
Natural Gas 0.00 13.88
Additional 0.00 0.00
Total 48.30 170.53


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 51.66
Space Heating 38.97
Space Cooling 18.01
Fans (All) 34.80
Service Water Heating 49.08
Receptacle Equipment 94.48
Miscellaneous (All) 306.47
Subtotal 306.47


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 27.15
Service Water Heating 0.00
Miscellaneous (All) 27.15
Subtotal 27.15


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 15.49
Space Heating 19.82
Space Cooling 5.40
Fans (All) 10.43
Service Water Heating 14.71
Receptacle Equipment 28.32
Miscellaneous 5.83


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2885. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365
HTGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL January 20.55 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 8675.83 84.17 0.00 0.00 0.00
PERIMETER_ZN_1 8601.33 158.67 0.00 0.00 0.00
PERIMETER_ZN_2 8617.67 142.33 0.00 0.00 0.00
PERIMETER_ZN_3 8728.33 31.67 0.00 0.00 0.00
PERIMETER_ZN_4 8462.83 297.17 0.00 0.00 0.00
ATTIC 7273.50 480.17 472.33 475.67 58.33
Min 7273.50 31.67 0.00 0.00 0.00
Max 8728.33 480.17 472.33 475.67 58.33
Average 8393.25 199.03 78.72 79.28 9.72
Sum 50359.50 1194.17 472.33 475.67 58.33


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 7647.67 1112.33 0.00 0.00 0.00
PERIMETER_ZN_1 7969.83 790.17 0.00 0.00 0.00
PERIMETER_ZN_2 7962.67 797.33 0.00 0.00 0.00
PERIMETER_ZN_3 8060.83 699.17 0.00 0.00 0.00
PERIMETER_ZN_4 7892.33 867.67 0.00 0.00 0.00
ATTIC 7188.83 874.67 281.17 231.50 183.83
Min 7188.83 699.17 0.00 0.00 0.00
Max 8060.83 1112.33 281.17 231.50 183.83
Average 7787.03 856.89 46.86 38.58 30.64
Sum 46722.17 5141.33 281.17 231.50 183.83


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17858.33 33.67 0.00 0.00 0.00
PERIMETER_ZN_1 13312.33 43.67 0.00 0.00 0.00
PERIMETER_ZN_2 4783.00 5.00 0.00 0.00 0.00
PERIMETER_ZN_3 13340.33 15.67 0.00 0.00 0.00
PERIMETER_ZN_4 6803.50 0.50 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17858.33 43.67 0.00 0.00 0.00
Average 9349.58 16.42 0.00 0.00 0.00
Sum 56097.50 98.50 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:02

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -3.40
February -4.23
March 2.667
April 7.472
May 13.731
June 18.627
July 22.029
August 20.690
September 16.545
October 9.725
November 6.035
December -2.18
   
Annual Sum or Average 9.049
Minimum of Months -4.23
Maximum of Months 22.029



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.273901E+09 1789.12 24-JAN-12:53 -7.8 -10.0 0.223374E+09 326.05 11-JAN-16:00 -7.8 -10.0
February 0.300450E+09 1891.30 08-FEB-09:23 -8.9 -9.8 0.201806E+09 314.70 22-FEB-16:00 11.70 5.56
March 0.582030E+09 1756.30 07-MAR-10:12 -6.8 -9.0 0.261864E+09 402.34 17-MAR-14:20 10.20 7.87
April 0.550499E+09 1191.12 17-APR-09:02 0.87 -1.8 0.244238E+09 402.33 27-APR-15:00 12.80 8.33
May 0.874019E+09 1960.83 24-MAY-05:05 18.80 15.75 0.304665E+09 402.35 19-MAY-12:00 18.80 15.75
June 0.194347E+10 4711.76 16-JUN-05:03 11.88 9.40 0.312621E+09 402.37 28-JUN-14:50 24.82 19.12
July 0.232883E+10 5179.77 03-JUL-05:01 11.78 11.11 0.285063E+09 402.37 05-JUL-13:00 22.20 20.99
August 0.263242E+10 4913.60 07-AUG-05:01 20.10 18.54 0.327646E+09 402.36 28-AUG-14:09 24.50 20.30
September 0.186268E+10 4797.29 12-SEP-05:02 9.40 8.57 0.284125E+09 402.36 06-SEP-12:50 9.40 8.57
October 0.100255E+10 4284.34 06-OCT-05:03 10.50 9.00 0.289218E+09 402.36 05-OCT-15:09 10.50 9.00
November 0.737723E+09 1311.78 03-NOV-07:15 2.07 0.67 0.253494E+09 402.34 01-NOV-15:00 2.07 0.67
December 0.391539E+09 2029.76 11-DEC-16:42 -10.7 -11.2 0.214316E+09 358.28 01-DEC-11:00 -10.7 -11.2
                     
Annual Sum or Average 0.134801E+11         0.320243E+10        
Minimum of Months 0.273901E+09 1191.12   -10.7 -11.2 0.201806E+09 314.70   -10.7 -11.2
Maximum of Months 0.263242E+10 5179.77   20.10 18.54 0.327646E+09 402.37   24.82 20.99



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 37827858.77 1119.61 04-JAN-15:07 -5.7 -7.4 0.167493E+09 231.14 06-JAN-14:50 -2.3 -5.1
February 39988403.06 920.34 28-FEB-13:30 0.00 -2.9 0.151197E+09 245.09 22-FEB-15:30 0.00 -2.9
March 0.189652E+09 1565.04 15-MAR-13:45 25.92 15.99 0.194779E+09 305.00 15-MAR-14:20 25.93 16.12
April 0.148413E+09 848.46 21-APR-14:35 14.80 8.34 0.173159E+09 304.99 20-APR-15:39 14.80 8.34
May 0.241497E+09 1277.06 26-MAY-14:00 21.70 13.77 0.213941E+09 305.42 23-MAY-09:50 21.70 13.77
June 0.104017E+10 4491.55 26-JUN-05:02 20.60 16.79 0.234489E+09 305.02 12-JUN-12:50 20.60 16.79
July 0.171658E+10 4474.09 05-JUL-05:02 19.32 16.63 0.215745E+09 305.03 11-JUL-13:00 27.20 21.32
August 0.215210E+10 5237.22 04-AUG-05:02 12.20 10.63 0.248062E+09 305.03 07-AUG-14:09 22.15 20.23
September 0.164273E+10 5233.46 11-SEP-05:02 11.20 9.59 0.214322E+09 305.02 13-SEP-12:09 22.70 18.70
October 0.773066E+09 3560.78 11-OCT-14:30 22.20 14.37 0.211566E+09 305.02 23-OCT-08:39 9.80 9.21
November 0.277337E+09 1692.79 01-NOV-12:30 11.40 6.63 0.182484E+09 304.99 16-NOV-14:39 17.20 13.27
December 16768540.66 764.09 04-DEC-14:40 0.00 -2.9 0.159726E+09 248.10 01-DEC-13:39 0.00 -2.9
                     
Annual Sum or Average 0.827612E+10         0.236696E+10        
Minimum of Months 16768540.66 764.09   -5.7 -7.4 0.151197E+09 231.14   -2.3 -5.1
Maximum of Months 0.215210E+10 5237.22   25.92 16.79 0.248062E+09 305.42   27.20 21.32



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 208418.31 597.95 06-JAN-11:04 -5.3 -7.0 72050019.98 136.88 04-JAN-08:09 -5.3 -7.0
February 577293.84 587.11 16-FEB-11:05 -3.6 -5.3 65061422.40 136.88 06-FEB-13:00 -3.6 -5.3
March 19572352.19 516.27 24-MAR-12:05 -1.0 -3.9 82396056.21 180.92 16-MAR-15:39 -1.0 -3.9
April 50627885.54 425.52 17-APR-10:04 2.30 0.10 75082462.73 180.92 21-APR-10:00 13.90 7.21
May 0.161327E+09 2272.02 26-MAY-10:02 18.98 12.55 95499343.31 190.45 23-MAY-14:09 18.98 12.55
June 0.833545E+09 3471.52 30-JUN-10:02 20.68 13.98 0.103090E+09 190.45 30-JUN-14:09 23.48 12.45
July 0.122976E+10 3505.90 03-JUL-10:02 21.88 16.38 94488916.83 190.45 06-JUL-14:09 22.12 12.54
August 0.130106E+10 3664.71 03-AUG-10:02 23.58 14.65 0.108507E+09 190.45 22-AUG-14:09 22.88 13.18
September 0.780555E+09 3666.23 28-SEP-14:01 14.95 11.14 93657555.12 190.45 20-SEP-14:09 14.95 11.14
October 0.231794E+09 2796.79 11-OCT-10:02 17.15 12.50 90996872.26 190.45 05-OCT-14:09 17.15 12.50
November 67237616.37 417.91 03-NOV-08:63 2.98 1.33 76582466.73 180.30 01-NOV-14:09 2.98 1.33
December 2470384.61 407.46 21-DEC-11:10 0.60 0.13 68726577.03 143.28 01-DEC-13:39 0.60 0.13
                     
Annual Sum or Average 0.467873E+10         0.102614E+10        
Minimum of Months 208418.31 407.46   -5.3 -7.0 65061422.40 136.88   -5.3 -7.0
Maximum of Months 0.130106E+10 3666.23   23.58 16.38 0.108507E+09 190.45   23.48 13.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0 -1.6 0.167409E+09 230.75 04-JAN-08:09 -13.1 -14.0
February 0.00 0.00 01-FEB-00:05 -3.3 -4.7 0.151182E+09 230.75 06-FEB-15:39 -13.3 -13.7
March 34761178.61 644.44 17-MAR-16:00 6.10 4.13 0.189347E+09 304.99 15-MAR-13:30 6.10 4.13
April 76836012.42 540.64 21-APR-07:42 6.55 4.03 0.165017E+09 279.74 07-APR-15:00 6.55 4.03
May 0.199622E+09 855.38 26-MAY-15:53 21.70 12.82 0.211163E+09 306.56 10-MAY-12:30 21.70 12.82
June 0.103265E+10 3957.83 21-JUN-05:02 18.30 16.18 0.235485E+09 305.02 12-JUN-13:39 18.30 16.18
July 0.153643E+10 3848.27 12-JUL-05:02 12.48 10.81 0.215746E+09 305.02 31-JUL-14:09 25.10 19.46
August 0.169399E+10 4301.48 18-AUG-05:02 15.28 12.93 0.247794E+09 305.02 15-AUG-14:00 15.28 12.93
September 0.955311E+09 3911.99 18-SEP-05:02 9.50 8.65 0.213777E+09 305.01 21-SEP-13:09 25.10 16.52
October 0.391038E+09 1148.34 05-OCT-15:23 18.90 12.81 0.199711E+09 305.01 05-OCT-13:39 18.90 12.81
November 0.166825E+09 803.45 28-NOV-11:55 1.10 0.86 0.172561E+09 287.38 16-NOV-16:00 1.10 0.86
December 7727745.08 509.24 01-DEC-14:43 7.38 5.84 0.159703E+09 241.39 01-DEC-13:30 7.38 5.84
                     
Annual Sum or Average 0.609518E+10         0.232889E+10        
Minimum of Months 0.00 0.00   -3.3 -4.7 0.151182E+09 230.75   -13.3 -14.0
Maximum of Months 0.169399E+10 4301.48   21.70 16.18 0.247794E+09 306.56   25.10 19.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 301190.03 449.44 06-JAN-15:50 -2.2 -4.8 99397800.35 136.88 04-JAN-08:09 -2.2 -4.8
February 3092780.58 443.82 28-FEB-16:42 -0.4 -2.9 89810401.29 138.78 22-FEB-16:00 -0.4 -2.9
March 35596963.12 408.51 07-MAR-16:53 -2.2 -5.1 0.113449E+09 181.28 15-MAR-13:30 25.55 15.84
April 45672938.50 557.98 21-APR-15:55 13.30 8.77 0.101779E+09 180.93 20-APR-15:00 13.30 8.77
May 0.153810E+09 1250.27 26-MAY-15:53 21.70 12.82 0.129875E+09 182.15 09-MAY-14:20 21.70 12.82
June 0.847430E+09 3662.53 21-JUN-05:02 18.30 16.18 0.140842E+09 180.95 28-JUN-15:30 25.55 18.29
July 0.115556E+10 3625.24 12-JUL-05:02 12.48 10.81 0.128707E+09 180.95 26-JUL-15:20 26.83 21.45
August 0.130765E+10 4096.55 04-AUG-05:02 12.20 10.63 0.147787E+09 180.95 14-AUG-13:50 27.93 22.12
September 0.765555E+09 3927.85 11-SEP-05:02 11.20 9.59 0.127618E+09 180.94 12-SEP-14:00 21.70 17.01
October 0.249575E+09 1459.80 11-OCT-15:57 21.70 14.52 0.123092E+09 180.93 13-OCT-12:50 12.12 10.12
November 83030560.31 325.42 01-NOV-07:15 5.40 2.81 0.105256E+09 180.92 16-NOV-16:00 18.30 13.48
December 2647855.28 286.12 15-DEC-16:00 2.80 1.43 94847501.59 146.25 01-DEC-13:30 2.80 1.43
                     
Annual Sum or Average 0.464992E+10         0.140246E+10        
Minimum of Months 301190.03 286.12   -2.2 -5.1 89810401.29 136.88   -2.2 -4.8
Maximum of Months 0.130765E+10 4096.55   21.70 16.18 0.147787E+09 182.15   27.93 22.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0 -1.6 0.00 0.00 01-JAN-00:10 -1.0 -1.6
February 0.00 0.00 01-FEB-00:05 -3.3 -4.7 0.00 0.00 01-FEB-00:10 -3.3 -4.7
March 0.00 0.00 01-MAR-00:10 -4.9 -6.9 0.00 0.00 01-MAR-00:10 -4.9 -6.9
April 0.00 0.00 01-APR-00:10 4.10 3.72 0.00 0.00 01-APR-00:10 4.10 3.72
May 0.00 0.00 01-MAY-00:10 6.67 6.11 0.00 0.00 01-MAY-00:10 6.67 6.11
June 0.00 0.00 01-JUN-00:10 17.05 14.04 0.00 0.00 01-JUN-00:10 17.05 14.04
July 0.00 0.00 01-JUL-00:10 16.82 13.50 0.00 0.00 01-JUL-00:10 16.82 13.50
August 0.00 0.00 01-AUG-00:10 18.85 16.93 0.00 0.00 01-AUG-00:10 18.85 16.93
September 0.00 0.00 01-SEP-00:10 14.65 12.90 0.00 0.00 01-SEP-00:10 14.65 12.90
October 0.00 0.00 01-OCT-00:10 14.42 12.28 0.00 0.00 01-OCT-00:10 14.42 12.28
November 0.00 0.00 01-NOV-00:10 6.53 4.43 0.00 0.00 01-NOV-00:10 6.53 4.43
December 0.00 0.00 01-DEC-00:10 4.95 3.07 0.00 0.00 01-DEC-00:10 4.95 3.07
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -4.9 -6.9 0.00 0.00   -4.9 -6.9
Maximum of Months 0.00 0.00   18.85 16.93 0.00 0.00   18.85 16.93



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.646871E+09 7730.92 02-JAN-06:01 -1.1
February 0.499800E+09 7554.34 27-FEB-06:01 -2.3
March 0.231252E+09 7229.82 27-MAR-05:01 -6.1
April 72152831.21 7248.18 17-APR-05:01 -4.0
May 18425232.63 4778.46 01-MAY-05:01 1.70
June 9565605.17 456.71 20-JUN-17:02 26.60
July 20061830.17 642.11 20-JUL-17:03 29.40
August 16058991.75 647.62 09-AUG-17:02 29.32
September 2550320.10 385.33 29-SEP-05:07 10.50
October 14120583.27 392.01 06-OCT-05:07 10.50
November 42863695.60 7633.61 27-NOV-06:01 18.30
December 0.357801E+09 7217.93 04-DEC-06:01 -1.8
         
Annual Sum or Average 0.193152E+10      
Minimum of Months 2550320.10 385.33   -6.1
Maximum of Months 0.646871E+09 7730.92   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.267675E+10 8851.88 02-JAN-06:01 -1.1
February 0.246616E+10 9007.15 13-FEB-06:01 -9.4
March 0.123080E+10 8749.68 20-MAR-05:01 -2.8
April 0.663210E+09 8629.47 17-APR-05:01 -4.0
May 0.151833E+09 7679.68 01-MAY-05:01 1.70
June 25772679.66 445.84 14-JUN-06:30 8.60
July 22058640.47 558.02 20-JUL-17:25 29.40
August 18541279.95 562.69 09-AUG-17:12 29.23
September 8757393.96 460.30 21-SEP-05:04 12.12
October 91279418.04 7367.56 30-OCT-05:01 -0.1
November 0.490132E+09 8182.70 24-NOV-06:01 -3.8
December 0.205387E+10 8781.25 04-DEC-06:01 -1.8
         
Annual Sum or Average 0.989916E+10      
Minimum of Months 8757393.96 445.84   -9.4
Maximum of Months 0.267675E+10 9007.15   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.168341E+10 6421.92 02-JAN-06:01 -1.1
February 0.154934E+10 6507.06 22-FEB-06:01 -2.6
March 0.822829E+09 6470.53 28-MAR-05:01 -2.7
April 0.291249E+09 6299.26 17-APR-05:01 -4.0
May 47639386.82 5911.40 01-MAY-05:01 1.70
June 17596642.41 328.55 12-JUN-05:04 22.30
July 15589566.14 386.61 20-JUL-17:25 29.40
August 14515840.94 387.72 09-AUG-17:12 29.23
September 8438770.33 342.28 18-SEP-05:04 9.50
October 38256578.82 5716.65 30-OCT-05:01 -0.1
November 0.240642E+09 6243.28 24-NOV-06:01 -3.8
December 0.127081E+10 6531.41 18-DEC-06:01 1.78
         
Annual Sum or Average 0.600031E+10      
Minimum of Months 8438770.33 328.55   -4.0
Maximum of Months 0.168341E+10 6531.41   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.283648E+10 7468.88 02-JAN-06:01 -1.1
February 0.266583E+10 7614.13 13-FEB-06:01 -9.4
March 0.171997E+10 7501.78 05-MAR-08:52 -8.3
April 0.664960E+09 7370.36 17-APR-05:01 -4.0
May 97972113.01 6588.18 01-MAY-05:01 1.70
June 19557508.47 384.53 20-JUN-17:02 26.60
July 18899731.58 511.64 20-JUL-17:25 29.40
August 16600781.07 526.29 09-AUG-17:12 29.23
September 11899037.28 359.27 18-SEP-05:04 9.50
October 72550012.75 6422.18 30-OCT-05:01 -0.1
November 0.422807E+09 6995.43 24-NOV-06:01 -3.8
December 0.205917E+10 7374.58 18-DEC-06:01 1.78
         
Annual Sum or Average 0.106067E+11      
Minimum of Months 11899037.28 359.27   -9.4
Maximum of Months 0.283648E+10 7614.13   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175275E+10 7281.35 18-JAN-06:01 2.80
February 0.160385E+10 7149.61 17-FEB-06:01 1.10
March 0.869747E+09 7258.36 02-MAR-06:01 1.10
April 0.338813E+09 6983.50 05-APR-05:01 1.60
May 63441961.38 6641.31 01-MAY-05:01 1.70
June 16115294.27 387.95 30-JUN-05:04 16.20
July 15100418.17 424.54 20-JUL-17:25 29.40
August 13991089.86 414.07 02-AUG-05:03 11.60
September 8563765.22 416.89 11-SEP-05:04 11.20
October 42971954.64 6528.25 30-OCT-05:01 -0.1
November 0.243309E+09 6781.81 29-NOV-06:01 1.70
December 0.126595E+10 7510.91 18-DEC-06:01 1.78
         
Annual Sum or Average 0.623460E+10      
Minimum of Months 8563765.22 387.95   -0.1
Maximum of Months 0.175275E+10 7510.91   29.40



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:03 -1.0
February 0.00 0.00 01-FEB-00:05 -3.3
March 0.00 0.00 01-MAR-00:10 -4.9
April 0.00 0.00 01-APR-00:10 4.10
May 0.00 0.00 01-MAY-00:10 6.67
June 0.00 0.00 01-JUN-00:10 17.05
July 0.00 0.00 01-JUL-00:10 16.82
August 0.00 0.00 01-AUG-00:10 18.85
September 0.00 0.00 01-SEP-00:10 14.65
October 0.00 0.00 01-OCT-00:10 14.42
November 0.00 0.00 01-NOV-00:10 6.53
December 0.00 0.00 01-DEC-00:10 4.95
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -4.9
Maximum of Months 0.00 0.00   18.85



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.729889E+09 743.94 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.660244E+09 743.94 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.791184E+09 743.94 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.696458E+09 743.94 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.760537E+09 743.94 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.757753E+09 743.94 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.699242E+09 743.94 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.791184E+09 743.94 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.696458E+09 743.94 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.729889E+09 743.94 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.727106E+09 743.94 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.699242E+09 743.94 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.873919E+10     0.141401E+11    
Minimum of Months 0.660244E+09 743.94   0.107295E+10 973.59  
Maximum of Months 0.791184E+09 743.94   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.469930E+09 563.96 02-JAN-16:49 0.899552E+09 738.04 02-JAN-08:09
February 0.414544E+09 551.52 01-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.482682E+09 537.60 17-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.421866E+09 530.05 12-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.459107E+09 514.98 11-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.450886E+09 491.93 19-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.418202E+09 510.89 11-JUL-07:30 0.873466E+09 738.04 03-JUL-07:10
August 0.474407E+09 513.90 24-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.425943E+09 535.75 26-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.452667E+09 549.78 26-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.472063E+09 563.96 06-NOV-16:00 0.888667E+09 738.04 01-NOV-07:10
December 0.459599E+09 563.96 01-DEC-16:40 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.540190E+10     0.107191E+11    
Minimum of Months 0.414544E+09 491.93   0.813362E+09 738.04  
Maximum of Months 0.482682E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.288184E+09 334.55 02-JAN-16:49 0.533626E+09 437.82 02-JAN-08:09
February 0.252422E+09 329.00 01-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.295195E+09 317.71 17-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.255891E+09 312.79 12-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.277807E+09 301.81 11-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.271454E+09 283.83 30-JUN-15:00 0.542644E+09 437.82 01-JUN-07:10
July 0.251403E+09 298.81 11-JUL-07:30 0.518151E+09 437.82 03-JUL-07:10
August 0.285858E+09 305.15 28-AUG-15:00 0.565383E+09 437.82 01-AUG-07:10
September 0.259111E+09 316.55 26-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.277645E+09 325.85 26-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.290043E+09 334.55 06-NOV-16:00 0.527169E+09 437.82 01-NOV-07:10
December 0.280300E+09 334.55 01-DEC-16:40 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.328531E+10     0.635872E+10    
Minimum of Months 0.251403E+09 283.83   0.482497E+09 437.82  
Maximum of Months 0.295195E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.512551E+09 563.96 02-JAN-16:49 0.899552E+09 738.04 02-JAN-08:09
February 0.444333E+09 553.95 01-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.517384E+09 541.62 17-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.440054E+09 533.31 12-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.467467E+09 517.52 11-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.451849E+09 491.77 19-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.420127E+09 513.50 11-JUL-07:30 0.873466E+09 738.04 03-JUL-07:10
August 0.483664E+09 517.24 24-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.449611E+09 539.46 26-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.493198E+09 560.71 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.512271E+09 563.96 06-NOV-16:00 0.888667E+09 738.04 01-NOV-07:10
December 0.494723E+09 563.96 01-DEC-16:40 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.568723E+10     0.107191E+11    
Minimum of Months 0.420127E+09 491.77   0.813362E+09 738.04  
Maximum of Months 0.517384E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.288384E+09 334.55 02-JAN-16:49 0.533626E+09 437.82 02-JAN-08:09
February 0.252725E+09 328.54 01-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.295761E+09 322.83 17-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.257495E+09 318.38 12-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.278184E+09 311.30 11-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.272255E+09 304.81 21-JUN-08:09 0.542644E+09 437.82 01-JUN-07:10
July 0.252567E+09 309.46 11-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.288397E+09 312.21 24-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.259314E+09 321.65 26-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.278956E+09 332.76 31-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.289512E+09 334.55 06-NOV-16:00 0.527169E+09 437.82 01-NOV-07:10
December 0.280971E+09 334.55 01-DEC-16:40 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.329452E+10     0.635872E+10    
Minimum of Months 0.252567E+09 304.81   0.482497E+09 437.82  
Maximum of Months 0.295761E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.729889E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.696458E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.760537E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.757753E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.699242E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.696458E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.729889E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.727106E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.699242E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.873919E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.469930E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.154401E+10
February 0.488155E+09 0.414544E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.150616E+10
March 0.590925E+09 0.482682E+09 0.953087E+09 0.00 0.00 0.00 0.00 1117263.78 0.107982E+10
April 0.513848E+09 0.421866E+09 0.862580E+09 0.00 0.00 0.00 0.00 0.00 0.757382E+09
May 0.565233E+09 0.459107E+09 0.926320E+09 0.00 0.00 0.00 0.00 1050438.04 0.454319E+09
June 0.565233E+09 0.450886E+09 0.914754E+09 0.00 0.00 0.00 0.00 18886131.24 0.278686E+09
July 0.513848E+09 0.418202E+09 0.873466E+09 0.00 0.00 0.00 0.00 47676196.50 0.140999E+09
August 0.590925E+09 0.474407E+09 0.953087E+09 0.00 0.00 0.00 0.00 35563712.88 0.215500E+09
September 0.513848E+09 0.425943E+09 0.861220E+09 0.00 0.00 0.00 0.00 1718797.08 0.341763E+09
October 0.539540E+09 0.452667E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.711332E+09
November 0.539540E+09 0.472063E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.914455E+09
December 0.513848E+09 0.459599E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.150253E+10
                   
Annual Sum or Average 0.647448E+10 0.540190E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.106013E+09 0.944696E+10
Minimum of Months 0.488155E+09 0.414544E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.140999E+09
Maximum of Months 0.590925E+09 0.482682E+09 0.953087E+09 0.00 0.00 0.00 0.00 47676196.50 0.154401E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.288184E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.482686E+09
February 0.211974E+09 0.252422E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.513260E+09
March 0.256600E+09 0.295195E+09 0.565383E+09 0.00 0.00 0.00 0.00 176216.11 0.305016E+09
April 0.223130E+09 0.255891E+09 0.511694E+09 0.00 0.00 0.00 0.00 0.00 0.239807E+09
May 0.245443E+09 0.277807E+09 0.549505E+09 0.00 0.00 0.00 0.00 631002.35 0.139009E+09
June 0.245443E+09 0.271454E+09 0.542644E+09 0.00 0.00 0.00 0.00 2284765.41 95587773.62
July 0.223130E+09 0.251403E+09 0.518151E+09 0.00 0.00 0.00 0.00 5058842.58 58712450.67
August 0.256600E+09 0.285858E+09 0.565383E+09 0.00 0.00 0.00 0.00 3397845.66 74319019.86
September 0.223130E+09 0.259111E+09 0.510887E+09 0.00 0.00 0.00 0.00 81539.38 0.107712E+09
October 0.234287E+09 0.277645E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 0.216873E+09
November 0.234287E+09 0.290043E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.280782E+09
December 0.223130E+09 0.280300E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.510712E+09
                   
Annual Sum or Average 0.281144E+10 0.328531E+10 0.635872E+10 0.00 0.00 0.00 0.00 11630211.50 0.302448E+10
Minimum of Months 0.211974E+09 0.251403E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 58712450.67
Maximum of Months 0.256600E+09 0.295195E+09 0.565383E+09 0.00 0.00 0.00 0.00 5058842.58 0.513260E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.512551E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.725107E+09
February 0.488155E+09 0.444333E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.770437E+09
March 0.590925E+09 0.517384E+09 0.953087E+09 0.00 0.00 0.00 0.00 311956.75 0.456111E+09
April 0.513848E+09 0.440054E+09 0.862580E+09 0.00 0.00 0.00 0.00 926.44 0.349835E+09
May 0.565233E+09 0.467467E+09 0.926320E+09 0.00 0.00 0.00 0.00 1204684.46 0.195909E+09
June 0.565233E+09 0.451849E+09 0.914754E+09 0.00 0.00 0.00 0.00 5213827.42 0.136110E+09
July 0.513848E+09 0.420127E+09 0.873466E+09 0.00 0.00 0.00 0.00 8989914.52 81218330.06
August 0.590925E+09 0.483664E+09 0.953087E+09 0.00 0.00 0.00 0.00 6454435.83 0.102861E+09
September 0.513848E+09 0.449611E+09 0.861220E+09 0.00 0.00 0.00 0.00 249635.20 0.152517E+09
October 0.539540E+09 0.493198E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.311613E+09
November 0.539540E+09 0.512271E+09 0.888667E+09 0.00 0.00 0.00 0.00 3481.12 0.414809E+09
December 0.513848E+09 0.494723E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.768055E+09
                   
Annual Sum or Average 0.647448E+10 0.568723E+10 0.107191E+11 0.00 0.00 0.00 0.00 22428861.73 0.446458E+10
Minimum of Months 0.488155E+09 0.420127E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 81218330.06
Maximum of Months 0.590925E+09 0.517384E+09 0.953087E+09 0.00 0.00 0.00 0.00 8989914.52 0.770437E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.288384E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.483691E+09
February 0.289580E+09 0.252725E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.514529E+09
March 0.350544E+09 0.295761E+09 0.565383E+09 0.00 0.00 0.00 0.00 167898.00 0.309350E+09
April 0.304821E+09 0.257495E+09 0.511694E+09 0.00 0.00 0.00 0.00 0.00 0.242500E+09
May 0.335303E+09 0.278184E+09 0.549505E+09 0.00 0.00 0.00 0.00 529893.31 0.142953E+09
June 0.335303E+09 0.272255E+09 0.542644E+09 0.00 0.00 0.00 0.00 2555675.07 0.102035E+09
July 0.304821E+09 0.252567E+09 0.518151E+09 0.00 0.00 0.00 0.00 5074709.17 63566033.44
August 0.350544E+09 0.288397E+09 0.565383E+09 0.00 0.00 0.00 0.00 3360731.90 78112308.30
September 0.304821E+09 0.259314E+09 0.510887E+09 0.00 0.00 0.00 0.00 138537.39 0.108914E+09
October 0.320062E+09 0.278956E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 0.215526E+09
November 0.320062E+09 0.289512E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.280910E+09
December 0.304821E+09 0.280971E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.511919E+09
                   
Annual Sum or Average 0.384075E+10 0.329452E+10 0.635872E+10 0.00 0.00 0.00 0.00 11827444.83 0.305401E+10
Minimum of Months 0.289580E+09 0.252567E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 63566033.44
Maximum of Months 0.350544E+09 0.295761E+09 0.565383E+09 0.00 0.00 0.00 0.00 5074709.17 0.514529E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.928776E+09 0.120618E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.717832E+09 0.178143E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.921050E+09 0.285209E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.650786E+09 0.354743E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.691280E+09 0.420619E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.587684E+09 0.467172E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.569419E+09 0.449707E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.597475E+09 0.383632E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.790769E+09 0.287011E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.824491E+09 0.193131E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.876300E+09 0.107465E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.833354E+09 0.105168E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.898921E+10 0.335262E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.569419E+09 0.105168E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.928776E+09 0.467172E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 743.94 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 743.94 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 743.94 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 743.94 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 743.94 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 743.94 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 743.94 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 743.94 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 743.94 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 743.94 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 743.94 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 743.94 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 563.96 02-JAN-16:49 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 3562.39 31-JAN-17:50
February 732.70 01-FEB-08:09 551.52 01-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 3998.80 07-FEB-07:02
March 732.70 01-MAR-08:09 537.60 17-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 104.96 15-MAR-11:53 3602.66 07-MAR-07:03
April 732.70 03-APR-07:10 530.05 12-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2548.88 17-APR-06:05
May 732.70 01-MAY-07:10 514.98 11-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 86.85 14-MAY-14:53 1808.48 01-MAY-06:10
June 732.70 01-JUN-07:10 491.93 19-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 571.54 27-JUN-12:00 1429.98 13-JUN-06:03
July 732.70 03-JUL-07:10 510.89 11-JUL-07:30 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 563.94 21-JUL-12:00 1038.05 03-JUL-06:03
August 732.70 01-AUG-07:10 513.90 24-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 559.59 10-AUG-12:00 1162.24 03-AUG-06:05
September 732.70 01-SEP-07:10 535.75 26-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 202.91 15-SEP-12:00 1676.43 05-SEP-06:03
October 732.70 02-OCT-07:10 549.78 26-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2423.34 17-OCT-07:00
November 732.70 01-NOV-07:10 563.96 06-NOV-16:00 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2451.53 24-NOV-07:10
December 732.70 01-DEC-08:09 563.96 01-DEC-16:40 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3888.52 11-DEC-07:02
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   491.93   738.04   0.00 0.00 0.00 0.00 0.00   1038.05  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 571.54   3998.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 334.55 02-JAN-16:49 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 886.86 12-JAN-06:10
February 434.65 01-FEB-08:09 329.00 01-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 931.69 13-FEB-06:10
March 434.65 01-MAR-08:09 317.71 17-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 9.81 14-MAR-13:55 493.29 02-MAR-06:06
April 434.65 03-APR-07:10 312.79 12-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 403.50 16-APR-06:55
May 434.65 01-MAY-07:10 301.81 11-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 68.14 14-MAY-14:53 209.38 11-MAY-18:10
June 434.65 01-JUN-07:10 283.83 30-JUN-15:00 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 39.84 17-JUN-17:10 244.94 13-JUN-03:00
July 434.65 03-JUL-07:10 298.81 11-JUL-07:30 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 48.07 21-JUL-03:00 181.43 06-JUL-02:00
August 434.65 01-AUG-07:10 305.15 28-AUG-15:00 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 59.93 13-AUG-13:00 171.81 30-AUG-18:05
September 434.65 01-SEP-07:10 316.55 26-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 3.58 15-SEP-12:10 263.03 29-SEP-19:00
October 434.65 02-OCT-07:10 325.85 26-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 263.84 23-OCT-18:10
November 434.65 01-NOV-07:10 334.55 06-NOV-16:00 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 468.34 17-NOV-06:05
December 434.65 01-DEC-08:09 334.55 01-DEC-16:40 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 716.83 09-DEC-18:20
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   283.83   437.82   0.00 0.00 0.00 0.00 0.00   171.81  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 68.14   931.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 563.96 02-JAN-16:49 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 1296.51 12-JAN-06:10
February 732.70 01-FEB-08:09 553.95 01-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1334.02 13-FEB-06:10
March 732.70 01-MAR-08:09 541.62 17-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 12.81 14-MAR-13:55 739.72 02-MAR-06:10
April 732.70 03-APR-07:10 533.31 12-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 1.17 08-APR-12:55 605.56 16-APR-06:55
May 732.70 01-MAY-07:10 517.52 11-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 116.66 14-MAY-14:53 312.71 11-MAY-18:10
June 732.70 01-JUN-07:10 491.77 19-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 66.25 17-JUN-17:10 356.74 13-JUN-03:00
July 732.70 03-JUL-07:10 513.50 11-JUL-07:30 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 76.08 21-JUL-03:00 266.94 06-JUL-02:00
August 732.70 01-AUG-07:10 517.24 24-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 117.53 13-AUG-13:00 252.06 30-AUG-18:10
September 732.70 01-SEP-07:10 539.46 26-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 8.49 16-SEP-13:00 393.78 29-SEP-19:00
October 732.70 02-OCT-07:10 560.71 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 382.86 23-OCT-18:10
November 732.70 01-NOV-07:10 563.96 06-NOV-16:00 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 4.14 26-NOV-14:00 692.81 17-NOV-06:10
December 732.70 01-DEC-08:09 563.96 01-DEC-16:40 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1080.13 09-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   491.77   738.04   0.00 0.00 0.00 0.00 0.00   252.06  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 117.53   1334.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 334.55 02-JAN-16:49 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 886.86 12-JAN-06:10
February 434.65 01-FEB-08:09 328.54 01-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 945.88 13-FEB-06:10
March 434.65 01-MAR-08:09 322.83 17-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 8.45 12-MAR-12:52 494.52 02-MAR-06:05
April 434.65 03-APR-07:10 318.38 12-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 403.60 16-APR-06:55
May 434.65 01-MAY-07:10 311.30 11-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 52.37 14-MAY-14:53 226.88 06-MAY-17:03
June 434.65 01-JUN-07:10 304.81 21-JUN-08:09 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 32.23 12-JUN-13:00 247.53 13-JUN-03:00
July 434.65 03-JUL-07:10 309.46 11-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 47.35 21-JUL-03:00 185.07 06-JUL-02:00
August 434.65 01-AUG-07:10 312.21 24-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 59.58 13-AUG-13:00 173.41 30-AUG-18:05
September 434.65 01-SEP-07:10 321.65 26-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 5.24 16-SEP-13:00 274.90 29-SEP-19:00
October 434.65 02-OCT-07:10 332.76 31-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 262.33 23-OCT-18:10
November 434.65 01-NOV-07:10 334.55 06-NOV-16:00 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 465.13 17-NOV-06:05
December 434.65 01-DEC-08:09 334.55 01-DEC-16:40 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 718.83 09-DEC-18:05
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   304.81   437.82   0.00 0.00 0.00 0.00 0.00   173.41  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 59.58   945.88  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1446.49 10-JAN-07:45 3905.29 30-JAN-13:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1576.49 14-FEB-19:55 5527.50 08-FEB-13:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1588.79 08-MAR-07:13 6182.77 07-MAR-13:30
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1608.69 07-APR-04:55 6999.10 06-APR-12:40
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1487.33 27-MAY-05:05 6616.09 08-MAY-12:20
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1240.76 12-JUN-00:05 6644.82 14-JUN-12:50
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1513.88 13-JUL-02:00 6549.83 03-JUL-12:50
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1225.57 12-AUG-03:00 6027.59 16-AUG-13:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1293.70 10-SEP-22:20 5730.39 10-SEP-13:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1312.78 09-OCT-22:55 4625.90 17-OCT-13:50
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1284.09 25-NOV-21:00 3265.92 24-NOV-13:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1336.32 16-DEC-08:00 3531.43 10-DEC-12:50
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1225.57   3265.92  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1608.69   6999.10  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1789.12 24-JAN-12:53 1769.91 1983.82 2745.52 0.00 0.00 0.00 0.00 0.00 0.00
February 1891.30 08-FEB-09:23 3866.15 2975.76 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
March 1756.30 07-MAR-10:12 4832.69 3719.71 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
April 1191.12 17-APR-09:02 4832.69 3719.71 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
May 1960.83 24-MAY-05:05 212.64 64.44 973.59 0.00 0.00 0.00 0.00 0.00 0.00
June 4711.76 16-JUN-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
July 5179.77 03-JUL-05:01 744.23 225.53 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
August 4913.60 07-AUG-05:01 850.55 257.74 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
September 4797.29 12-SEP-05:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
October 4284.34 06-OCT-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
November 1311.78 03-NOV-07:15 1933.08 1487.88 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
December 2029.76 11-DEC-16:42 3866.15 2975.76 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1191.12   212.64 64.44 973.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5179.77   4832.69 3719.71 4867.94 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1119.61 04-JAN-15:07 2198.10 1234.89 2214.13 0.00 0.00 0.00 0.00 0.00 515.54
February 920.34 28-FEB-13:30 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 386.16
March 1565.04 15-MAR-13:45 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 34.05 0.00
April 848.46 21-APR-14:35 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 0.00 156.39
May 1277.06 26-MAY-14:00 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 32.09
June 4491.55 26-JUN-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 85.05
July 4474.09 05-JUL-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 132.89
August 5237.22 04-AUG-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 243.88
September 5233.46 11-SEP-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 187.85
October 3560.78 11-OCT-14:30 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 25.18
November 1692.79 01-NOV-12:30 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 207.34
December 764.09 04-DEC-14:40 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 396.51
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 764.09   402.98 122.12 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5237.22   2198.10 1234.89 2214.13 0.00 0.00 0.00 0.00 34.05 515.54



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 597.95 06-JAN-11:04 2173.23 1220.92 2189.08 0.00 0.00 0.00 0.00 0.00 6.47
February 587.11 16-FEB-11:05 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 101.26
March 516.27 24-MAR-12:05 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 41.50
April 425.52 17-APR-10:04 2173.23 1220.92 2189.08 0.00 0.00 0.00 0.00 0.00 58.61
May 2272.02 26-MAY-10:02 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 5.13
June 3471.52 30-JUN-10:02 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 7.39
July 3505.90 03-JUL-10:02 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 3.19
August 3664.71 03-AUG-10:02 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 0.42
September 3666.23 28-SEP-14:01 3477.17 2194.75 3502.53 0.00 0.00 0.00 0.00 0.00 53.21
October 2796.79 11-OCT-10:02 2173.23 1220.92 2189.08 0.00 0.00 0.00 0.00 0.00 10.92
November 417.91 03-NOV-08:63 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 68.60
December 407.46 21-DEC-11:10 869.29 496.36 875.63 0.00 0.00 0.00 0.00 0.00 32.35
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 407.46   869.29 496.36 875.63 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 3666.23   3477.17 2194.75 3502.53 0.00 0.00 0.00 0.00 0.00 101.26



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:03 0.00 73.27 377.96 0.00 0.00 0.00 0.00 0.00 233.80
February 0.00 01-FEB-00:05 0.00 48.85 629.93 0.00 0.00 0.00 0.00 0.00 306.92
March 644.44 17-MAR-16:00 732.70 451.29 738.04 0.00 0.00 0.00 0.00 0.00 112.67
April 540.64 21-APR-07:42 4396.19 2515.36 4428.26 0.00 0.00 0.00 0.00 0.00 32.40
May 855.38 26-MAY-15:53 2198.10 1254.23 2214.13 0.00 0.00 0.00 0.00 0.00 7.76
June 3957.83 21-JUN-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 74.35
July 3848.27 12-JUL-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 9.06
August 4301.48 18-AUG-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 87.49
September 3911.99 18-SEP-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 100.05
October 1148.34 05-OCT-15:23 2198.10 1405.43 2214.13 0.00 0.00 0.00 0.00 0.00 20.92
November 803.45 28-NOV-11:55 1465.40 977.93 1476.09 0.00 0.00 0.00 0.00 0.00 73.80
December 509.24 01-DEC-14:43 2198.10 1549.32 2214.13 0.00 0.00 0.00 0.00 0.00 176.72
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 48.85 377.96 0.00 0.00 0.00 0.00 0.00 7.76
Maximum of Months 4301.48   4396.19 2515.36 4428.26 0.00 0.00 0.00 0.00 0.00 306.92



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 449.44 06-JAN-15:50 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 28.11
February 443.82 28-FEB-16:42 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 68.58
March 408.51 07-MAR-16:53 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 54.34
April 557.98 21-APR-15:55 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 40.04
May 1250.27 26-MAY-15:53 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 5.17
June 3662.53 21-JUN-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 51.89
July 3625.24 12-JUL-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 6.19
August 4096.55 04-AUG-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 68.04
September 3927.85 11-SEP-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 11.82
October 1459.80 11-OCT-15:57 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 2.34
November 325.42 01-NOV-07:15 869.29 661.42 875.63 0.00 0.00 0.00 0.00 0.00 32.75
December 286.12 15-DEC-16:00 869.29 613.02 875.63 0.00 0.00 0.00 0.00 0.00 45.53
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 286.12   239.06 72.44 875.63 0.00 0.00 0.00 0.00 0.00 2.34
Maximum of Months 4096.55   1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 68.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 443.39 0.00
February 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1177.94 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 536.66 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 218.96 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 190.02 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1037.01 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 838.66 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 193.41 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 446.49 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 373.14 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 587.32 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 535.95 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 190.02 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1177.94 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.168356E+11 17692.60 02-JAN-08:30 0.389345E+10 31492.82 04-JAN-07:10
February 0.146819E+11 17175.65 27-FEB-08:30 0.506695E+10 31791.05 06-FEB-07:10
March 0.142584E+11 15938.53 27-MAR-07:19 0.129986E+10 31744.64 07-MAR-07:10
April 0.112214E+11 16002.48 17-APR-07:19 0.221310E+09 17076.58 17-APR-05:10
May 0.110561E+11 11429.92 10-MAY-15:20 5037769.39 3825.04 01-MAY-05:10
June 0.121047E+11 14073.03 27-JUN-12:39 0.00 0.00 01-JUN-00:10
July 0.125435E+11 14453.68 20-JUL-12:00 0.00 0.00 01-JUL-00:10
August 0.136468E+11 14325.58 14-AUG-15:20 0.00 0.00 01-AUG-00:10
September 0.116625E+11 13476.46 15-SEP-12:20 0.00 0.00 01-SEP-00:10
October 0.113158E+11 13014.52 30-OCT-06:40 12674828.03 4657.87 30-OCT-05:10
November 0.119644E+11 15399.90 24-NOV-08:30 65828193.40 11165.14 24-NOV-06:10
December 0.153615E+11 16626.64 28-DEC-16:49 0.331070E+10 31791.05 11-DEC-07:10
             
Annual Sum or Average 0.156653E+12     0.138758E+11    
Minimum of Months 0.110561E+11 11429.92   0.00 0.00  
Maximum of Months 0.168356E+11 17692.60   0.506695E+10 31791.05  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.228894E+10 0.115049E+10 0.405300E+10 0.00 0.160883E+10 0.02 0.555258E+10 0.00 0.00 0.00 0.00 0.218181E+10 0.00
February 0.202427E+10 0.918778E+09 0.366466E+10 0.00 0.152947E+10 0.01 0.456649E+10 0.00 0.00 0.00 0.00 0.197817E+10 0.00
March 0.238221E+10 0.859449E+09 0.429420E+10 0.00 0.161450E+10 0.00 0.284718E+10 32358361.75 0.00 0.00 0.00 0.222847E+10 0.00
April 0.207177E+10 0.688048E+09 0.388642E+10 0.00 0.136001E+10 0.00 0.112659E+10 10672449.34 0.00 0.00 0.00 0.207788E+10 0.00
May 0.224310E+10 0.596891E+09 0.417360E+10 0.00 0.149198E+10 0.00 0.115903E+09 0.290433E+09 0.00 0.00 0.00 0.214415E+10 0.00
June 0.220420E+10 0.535304E+09 0.412149E+10 0.00 0.150524E+10 0.00 486115.47 0.168379E+10 0.00 0.00 0.00 0.205421E+10 0.00
July 0.204154E+10 0.567545E+09 0.393546E+10 0.00 0.137832E+10 0.00 0.00 0.257810E+10 0.00 0.00 0.00 0.204254E+10 0.00
August 0.232351E+10 0.659836E+09 0.429420E+10 0.00 0.158199E+10 0.00 0.00 0.269268E+10 0.00 0.00 0.00 0.209455E+10 0.00
September 0.209044E+10 0.763648E+09 0.388029E+10 0.00 0.136883E+10 0.00 0.00 0.156726E+10 0.00 0.00 0.00 0.199198E+10 0.00
October 0.223236E+10 0.948559E+09 0.405607E+10 0.00 0.142480E+10 0.00 0.224425E+09 0.339384E+09 0.00 0.00 0.00 0.209019E+10 0.00
November 0.229099E+10 0.106731E+10 0.400396E+10 0.00 0.142370E+10 0.00 0.109467E+10 13615544.68 0.00 0.00 0.00 0.207020E+10 0.00
December 0.221484E+10 0.119062E+10 0.393240E+10 0.00 0.149840E+10 0.00 0.438931E+10 0.00 0.00 0.00 0.00 0.213597E+10 0.00
                           
Annual Sum or Average 0.264082E+11 0.994647E+10 0.482958E+11 0.00 0.177861E+11 0.03 0.199176E+11 0.920828E+10 0.00 0.00 0.00 0.250901E+11 0.00
Minimum of Months 0.202427E+10 0.535304E+09 0.366466E+10 0.00 0.136001E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.197817E+10 0.00
Maximum of Months 0.238221E+10 0.119062E+10 0.429420E+10 0.00 0.161450E+10 0.02 0.555258E+10 0.269268E+10 0.00 0.00 0.00 0.222847E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.389345E+10 0.00 0.00 0.00 0.00
February 0.00 0.00 0.506695E+10 0.00 0.00 0.00 0.00
March 0.00 0.00 0.129986E+10 0.00 0.00 0.00 0.00
April 0.00 0.00 0.221310E+09 0.00 0.00 0.00 0.00
May 0.00 0.00 5037769.39 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 12674828.03 0.00 0.00 0.00 0.00
November 0.00 0.00 65828193.40 0.00 0.00 0.00 0.00
December 0.00 0.00 0.331070E+10 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.138758E+11 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.506695E+10 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2540.94 02-JAN-16:49 1061.67 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1507.96 02-JAN-06:10 0.00 02-JAN-07:10 7679.25 02-JAN-09:20
February 2505.58 01-FEB-16:00 1061.67 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1507.96 01-FEB-06:10 0.00 06-FEB-19:10 7412.45 27-FEB-08:39
March 2463.70 17-MAR-07:10 1061.67 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1507.96 01-MAR-06:10 0.00 01-MAR-00:10 6743.91 20-MAR-06:10
April 2438.47 12-APR-07:10 1061.67 01-APR-05:10 3325.31 03-APR-07:10 0.00 1507.96 03-APR-05:10 0.00 01-APR-00:10 7270.51 03-APR-06:10
May 2389.55 11-MAY-07:10 1061.67 01-MAY-05:10 3325.31 01-MAY-07:10 0.00 1507.96 01-MAY-05:10 0.00 01-MAY-00:10 4113.42 01-MAY-06:10
June 2311.31 19-JUN-07:10 675.04 01-JUN-19:49 3325.31 01-JUN-07:10 0.00 1507.96 01-JUN-05:10 0.00 01-JUN-00:10 117.15 14-JUN-06:30
July 2376.09 11-JUL-07:30 675.04 01-JUL-19:00 3325.31 03-JUL-07:10 0.00 1507.96 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2387.16 24-AUG-07:10 1061.67 02-AUG-05:10 3325.31 01-AUG-07:10 0.00 1507.96 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2457.35 26-SEP-07:10 1061.67 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1507.96 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2500.14 26-OCT-07:10 1061.67 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1507.96 02-OCT-05:10 0.00 01-OCT-00:10 5180.85 30-OCT-06:19
November 2540.94 06-NOV-16:00 1061.67 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1507.96 01-NOV-05:10 0.00 01-NOV-00:10 7044.88 24-NOV-07:10
December 2540.94 01-DEC-16:40 1061.67 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1507.96 01-DEC-06:10 0.00 01-DEC-00:10 7280.08 19-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2311.31   675.04   3325.31   0.00 1507.96   0.00   0.00  
Maximum of Months 2540.94   1061.67   3325.31   0.00 1507.96   0.00   7679.25  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 0.00 01-JAN-00:10 0.00 0.00 0.00 2828.33 31-JAN-12:39 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 2829.27 17-FEB-12:20 0.00
March 1282.54 15-MAR-14:50 0.00 0.00 0.00 2828.63 01-MAR-12:50 0.00
April 404.27 21-APR-14:00 0.00 0.00 0.00 2822.62 04-APR-11:00 0.00
May 1799.92 10-MAY-14:00 0.00 0.00 0.00 2813.68 01-MAY-11:50 0.00
June 4482.18 27-JUN-12:00 0.00 0.00 0.00 2802.84 02-JUN-11:00 0.00
July 5147.04 21-JUL-05:10 0.00 0.00 0.00 2793.79 03-JUL-11:30 0.00
August 5025.92 14-AUG-05:10 0.00 0.00 0.00 2788.88 31-AUG-11:20 0.00
September 3794.41 15-SEP-12:09 0.00 0.00 0.00 2793.60 29-SEP-11:09 0.00
October 2121.63 11-OCT-15:39 0.00 0.00 0.00 2802.91 31-OCT-11:09 0.00
November 413.33 01-NOV-12:50 0.00 0.00 0.00 2813.48 29-NOV-12:50 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 2822.69 29-DEC-12:00 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 0.00   0.00 0.00 0.00 2788.88   0.00
Maximum of Months 5147.04   0.00 0.00 0.00 2829.27   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 17692.60 02-JAN-08:30 2463.32 3325.31 0.00 0.00 1507.96 0.00 7650.34 0.00 0.00
February 17175.65 27-FEB-08:30 2183.03 3325.31 0.00 0.00 1507.96 0.00 7411.12 0.00 0.00
March 15938.53 27-MAR-07:19 2203.44 3325.31 0.00 0.00 1507.96 0.00 6155.69 0.00 0.00
April 16002.48 17-APR-07:19 2148.12 3325.31 0.00 0.00 1507.96 0.00 6278.11 0.00 0.00
May 11429.92 10-MAY-15:20 2087.43 3325.31 0.00 0.00 1507.96 0.00 0.00 1742.39 0.00
June 14073.03 27-JUN-12:39 2055.57 3325.31 0.00 0.00 1507.96 0.00 0.00 4402.57 0.00
July 14453.68 20-JUL-12:00 2055.57 3325.31 0.00 0.00 1507.96 0.00 0.00 4787.13 0.00
August 14325.58 14-AUG-15:20 2058.61 3325.31 0.00 0.00 1507.96 0.00 0.00 4682.69 0.00
September 13476.46 15-SEP-12:20 2096.78 3325.31 0.00 0.00 1507.96 0.00 0.00 3768.47 0.00
October 13014.52 30-OCT-06:40 1185.75 1662.65 1061.67 0.00 1507.96 0.00 4901.76 0.00 0.00
November 15399.90 24-NOV-08:30 2238.38 3325.31 0.00 0.00 1507.96 0.00 5588.73 0.00 0.00
December 16626.64 28-DEC-16:49 2540.94 3325.31 1061.67 0.00 1507.96 0.00 5415.60 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 11429.92   1185.75 1662.65 0.00 0.00 1507.96 0.00 0.00 0.00 0.00
Maximum of Months 17692.60   2540.94 3325.31 1061.67 0.00 1507.96 0.00 7650.34 4787.13 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 31492.82 04-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 31791.05 06-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 31744.64 07-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 17076.58 17-APR-05:10 0.00 0.00 0.00
May 0.00 0.00 3825.04 01-MAY-05:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 4657.87 30-OCT-05:10 0.00 0.00 0.00
November 0.00 0.00 11165.14 24-NOV-06:10 0.00 0.00 0.00
December 0.00 0.00 31791.05 11-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 31791.05   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 19.94 2.17 19.94 0.00 19.94 0.00 19.94
February 5.67 20.01 5.67 20.01 0.00 20.01 0.00 20.01
March 0.50 20.16 0.50 20.16 0.00 20.16 0.00 20.16
April 0.17 20.55 0.17 20.55 0.00 20.55 0.00 20.55
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.55 0.17 24.55
July 0.00 0.00 0.00 0.00 2.50 24.70 2.50 24.70
August 0.00 0.00 0.00 0.00 2.17 24.79 2.17 24.79
September 0.00 0.00 0.00 0.00 0.33 24.61 0.33 24.61
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 4.50 20.03 4.50 20.03 0.00 20.03 0.00 20.03
                 
Annual Sum or Average 13.00 20.02 13.00 20.02 5.17 20.80 5.17 21.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.67 20.55 5.67 20.55 2.50 24.79 2.50 24.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 23.50 18.02 14.67 18.73 0.00 18.73 0.00 18.73
February 28.67 17.52 17.67 18.19 0.00 18.19 0.00 18.19
March 5.00 19.95 5.00 19.95 0.00 19.95 0.00 19.95
April 1.00 19.94 1.00 19.94 0.00 19.94 0.00 19.94
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 24.68 0.33 24.68
August 0.00 0.00 0.00 0.00 0.50 24.78 0.50 24.78
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 20.13 0.17 20.13 0.00 20.13 0.00 20.13
December 13.33 18.27 10.17 18.75 0.00 18.75 0.00 18.75
                 
Annual Sum or Average 71.67 18.03 48.67 18.65 0.83 18.69 0.83 18.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 28.67 20.13 17.67 20.13 0.50 24.78 0.50 24.78



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 24.17 15.95 5.33 16.64 0.00 16.64 0.00 16.64
February 31.50 16.32 10.67 17.11 0.00 17.11 0.00 17.11
March 8.00 17.08 3.50 17.95 0.00 17.95 0.00 17.95
April 1.33 18.13 0.83 18.86 0.00 18.86 0.00 18.86
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 24.59 0.33 24.59
August 0.00 0.00 0.00 0.00 0.33 24.66 0.33 24.66
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.33 0.50 20.33 0.00 20.33 0.00 20.33
December 17.67 16.81 7.17 17.66 0.00 17.66 0.00 17.66
                 
Annual Sum or Average 83.17 16.44 28.00 17.26 0.67 17.30 0.67 17.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 31.50 20.33 10.67 20.33 0.33 24.66 0.33 24.66



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 33.50 16.78 13.33 17.59 0.00 17.59 0.00 17.59
February 35.00 16.99 16.50 17.79 0.00 17.79 0.00 17.79
March 14.50 17.72 8.50 18.47 0.00 18.47 0.00 18.47
April 3.17 19.46 2.83 19.70 0.00 19.70 0.00 19.70
May 0.17 20.53 0.17 20.53 0.00 20.53 0.00 20.53
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 24.71 0.33 24.71
August 0.00 0.00 0.00 0.00 0.50 24.55 0.50 24.55
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.17 20.24 1.17 20.24 0.00 20.24 0.00 20.24
December 20.33 17.29 10.50 18.08 0.00 18.08 0.00 18.08
                 
Annual Sum or Average 107.83 17.19 53.00 18.00 0.83 18.03 0.83 18.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35.00 20.53 16.50 20.53 0.50 24.71 0.50 24.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 27.00 15.72 4.67 16.33 0.00 16.33 0.00 16.33
February 30.67 16.29 9.83 17.09 0.00 17.09 0.00 17.09
March 8.17 16.78 3.00 17.66 0.00 17.66 0.00 17.66
April 0.67 20.16 0.67 20.16 0.00 20.16 0.00 20.16
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 24.58 0.33 24.58
August 0.00 0.00 0.00 0.00 0.50 24.63 0.50 24.63
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.43 0.50 20.43 0.00 20.43 0.00 20.43
December 17.67 16.67 6.67 17.51 0.00 17.51 0.00 17.51
                 
Annual Sum or Average 84.67 16.29 25.33 17.09 0.83 17.15 0.83 17.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30.67 20.43 9.83 20.43 0.50 24.63 0.50 24.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.86 309.67 20.84 309.67 20.83
February 323.00 20.86 257.17 20.83 257.17 20.82
March 391.00 21.54 148.33 21.42 148.33 21.35
April 340.00 22.21 20.00 22.13 20.00 22.07
May 293.00 23.53 5.17 23.55 1.83 23.55
June 41.17 24.77 230.50 24.61 24.67 24.67
July 43.33 25.87 317.33 24.70 43.33 24.83
August 30.83 25.82 336.17 24.67 30.83 24.76
September 19.33 25.23 194.50 24.66 17.83 24.72
October 254.17 23.41 15.83 23.48 0.00 23.48
November 357.00 22.09 10.50 22.06 10.50 22.03
December 340.00 20.96 216.33 20.91 216.33 20.88
             
Annual Sum or Average 2789.83 22.02 2061.50 22.37 1080.50 22.19
Minimum of Months 19.33 20.86 5.17 20.83 0.00 20.82
Maximum of Months 391.00 25.87 336.17 24.70 309.67 24.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.29 351.33 20.28 351.33 20.28
February 323.00 20.26 316.17 20.24 316.17 20.24
March 390.00 21.07 262.00 20.85 262.00 20.76
April 340.00 21.33 165.50 21.10 165.50 20.98
May 374.00 22.55 37.00 22.42 37.00 22.30
June 169.67 23.74 133.50 24.01 33.83 24.05
July 68.67 25.00 274.50 24.64 56.67 24.74
August 50.83 24.70 300.00 24.61 30.50 24.67
September 74.33 23.80 199.00 24.32 15.83 24.37
October 276.33 22.78 32.17 22.85 9.67 22.79
November 357.00 21.38 167.17 21.15 167.17 21.03
December 340.00 20.37 330.33 20.35 330.33 20.35
             
Annual Sum or Average 3120.83 21.57 2568.67 21.72 1776.00 21.50
Minimum of Months 50.83 20.26 32.17 20.24 9.67 20.24
Maximum of Months 390.00 25.00 351.33 24.64 351.33 24.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 20.02 293.83 20.02 293.83 20.02
February 266.00 20.00 266.00 20.00 266.00 20.00
March 322.00 20.67 259.67 20.50 259.67 20.43
April 280.00 21.16 156.83 20.90 156.83 20.78
May 305.33 22.72 23.00 22.60 23.00 22.49
June 89.17 23.92 138.50 24.28 14.50 24.30
July 29.67 25.33 259.00 24.72 28.83 24.78
August 28.33 24.68 255.67 24.68 15.67 24.71
September 63.17 23.76 115.00 24.31 6.00 24.34
October 273.83 22.70 21.50 22.58 21.50 22.47
November 294.00 20.96 188.67 20.78 188.67 20.70
December 280.00 20.12 273.33 20.11 273.33 20.10
             
Annual Sum or Average 2525.50 21.31 2251.00 21.50 1547.83 21.24
Minimum of Months 28.33 20.00 21.50 20.00 6.00 20.00
Maximum of Months 322.00 25.33 293.83 24.72 293.83 24.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.19 353.67 20.18 353.67 20.18
February 323.00 20.17 323.00 20.17 323.00 20.17
March 391.00 20.71 316.33 20.56 316.33 20.51
April 340.00 20.89 244.00 20.76 244.00 20.71
May 374.00 22.44 49.33 22.27 49.33 22.14
June 163.17 23.82 110.00 24.08 17.50 24.10
July 39.17 24.97 246.67 24.64 32.00 24.70
August 46.67 24.34 222.67 24.60 17.00 24.63
September 139.67 23.76 75.50 24.01 9.17 24.04
October 357.00 22.39 48.00 22.22 48.00 22.08
November 357.00 20.88 241.00 20.76 241.00 20.71
December 340.00 20.30 330.50 20.29 330.50 20.28
             
Annual Sum or Average 3227.67 21.37 2560.67 21.41 1981.50 21.19
Minimum of Months 39.17 20.17 48.00 20.17 9.17 20.17
Maximum of Months 391.00 24.97 353.67 24.64 353.67 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.23 353.50 20.23 353.50 20.23
February 323.00 20.22 323.00 20.22 323.00 20.22
March 391.00 20.89 302.83 20.72 302.83 20.66
April 340.00 21.38 179.17 21.15 179.17 21.03
May 346.83 22.86 35.33 22.82 25.17 22.71
June 92.33 24.11 189.67 24.68 15.50 24.73
July 53.83 26.40 282.33 25.12 48.67 25.31
August 52.33 26.24 269.50 25.15 38.33 25.36
September 83.33 23.84 138.67 24.47 6.33 24.49
October 326.00 22.75 28.67 22.65 25.67 22.54
November 357.00 21.10 213.17 20.91 213.17 20.83
December 340.00 20.32 330.50 20.31 330.50 20.30
             
Annual Sum or Average 3062.67 21.55 2646.33 21.72 1861.83 21.49
Minimum of Months 52.33 20.22 28.67 20.22 6.33 20.22
Maximum of Months 391.00 26.40 353.50 25.15 353.50 25.36



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 56494357.96 12920209.02 21.72 42291866.26 14202491.70 0.00 0.31 15-MAR-15:03 0.00 01-MAR-00:10 1621.07 16-MAR-15:00 1319.31 15-MAR-15:07 480.98 16-MAR-15:00 375.31 15-MAR-14:53 0.00
April 20111778.65 4585329.48 15.42 18682179.81 1429598.84 0.00 0.12 21-APR-14:55 0.00 01-APR-00:10 585.72 21-APR-14:55 554.11 21-APR-15:00 56.70 20-APR-15:55 132.78 21-APR-14:55 0.00
May 0.686516E+09 0.152638E+09 178.93 0.562687E+09 0.123829E+09 0.00 0.52 24-MAY-05:05 0.00 01-MAY-00:10 2745.55 24-MAY-05:05 2433.05 24-MAY-05:05 700.09 17-MAY-13:30 583.95 24-MAY-05:05 0.00
June 0.254655E+10 0.548246E+09 261.86 0.197430E+10 0.572248E+09 0.00 1.00 02-JUN-05:03 0.00 01-JUN-00:10 6248.38 28-JUN-05:02 5299.18 16-JUN-05:03 2636.74 28-JUN-05:08 1182.06 28-JUN-05:02 0.00
July 0.344557E+10 0.735228E+09 239.97 0.260528E+10 0.840297E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 6223.70 31-JUL-05:02 5638.48 03-JUL-05:01 2401.98 28-JUL-05:08 1234.52 20-JUL-13:53 0.00
August 0.359635E+10 0.767940E+09 275.90 0.283586E+10 0.760489E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 6195.96 15-AUG-05:01 5344.63 07-AUG-05:01 2276.44 29-AUG-05:13 1194.74 15-AUG-05:01 0.00
September 0.225810E+10 0.481284E+09 238.65 0.178166E+10 0.476436E+09 0.00 1.00 01-SEP-05:03 0.00 01-SEP-00:10 6169.03 15-SEP-05:02 5287.44 12-SEP-05:02 2308.09 15-SEP-05:15 1177.06 15-SEP-05:02 0.00
October 0.553122E+09 0.122339E+09 149.16 0.441408E+09 0.111714E+09 0.00 1.00 06-OCT-05:03 0.00 01-OCT-00:10 5974.14 13-OCT-05:03 4845.71 06-OCT-05:03 1648.32 13-OCT-05:03 1158.45 13-OCT-05:03 0.00
November 17369577.75 3946937.35 12.23 14618340.86 2751236.90 0.00 0.15 16-NOV-17:00 0.00 01-NOV-00:10 749.75 16-NOV-17:00 553.32 16-NOV-17:00 196.43 16-NOV-17:00 168.80 16-NOV-17:00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.131802E+11 0.282913E+10 1393.85 0.102768E+11 0.290340E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.359635E+10 0.767940E+09 275.90 0.283586E+10 0.840297E+09 0.00 1.00   0.00   6248.38   5638.48   2636.74   1234.52   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 59515600.81 13844890.98 14.64 51918134.88 7597465.93 0.00 0.41 15-MAR-13:50 0.00 01-MAR-00:10 2150.39 15-MAR-13:50 2025.04 15-MAR-13:45 360.03 14-MAR-13:30 501.87 15-MAR-13:50 0.00
April 19092559.83 4341706.57 14.58 19034788.16 57771.67 0.00 0.14 21-APR-14:55 0.00 01-APR-00:10 666.27 21-APR-14:55 666.27 21-APR-14:55 13.64 20-APR-15:30 150.48 21-APR-14:55 0.00
May 0.183413E+09 41738904.99 70.55 0.167803E+09 15610925.83 0.00 0.34 10-MAY-14:30 0.00 01-MAY-00:10 1820.97 10-MAY-14:30 1546.06 23-MAY-14:30 316.13 10-MAY-15:00 426.40 10-MAY-14:30 0.00
June 0.144330E+10 0.320926E+09 216.63 0.115780E+10 0.285505E+09 0.00 1.00 19-JUN-05:02 0.00 01-JUN-00:10 6326.09 28-JUN-05:02 5029.24 26-JUN-05:02 2317.52 28-JUN-05:02 1214.75 27-JUN-05:02 0.00
July 0.258316E+10 0.568414E+09 230.63 0.201335E+10 0.569817E+09 0.00 1.00 05-JUL-05:02 0.00 01-JUL-00:10 6669.45 21-JUL-05:02 5012.46 05-JUL-05:02 3429.70 21-JUL-05:07 1276.12 21-JUL-05:12 0.00
August 0.288198E+10 0.629322E+09 264.25 0.240847E+10 0.473507E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 6599.60 14-AUG-05:01 5823.61 04-AUG-05:02 2924.83 14-AUG-05:09 1283.06 10-AUG-12:00 0.00
September 0.192046E+10 0.410102E+09 211.98 0.167264E+10 0.247819E+09 0.00 1.00 11-SEP-05:02 0.00 01-SEP-00:10 6340.22 14-SEP-05:02 5860.97 11-SEP-05:02 2117.49 14-SEP-05:04 1215.86 14-SEP-05:02 0.00
October 0.526264E+09 0.114718E+09 106.36 0.488049E+09 38214992.42 0.00 0.72 11-OCT-14:30 0.00 01-OCT-00:10 3959.26 11-OCT-14:30 3802.22 11-OCT-14:30 483.54 12-OCT-15:00 829.66 11-OCT-14:30 0.00
November 42867674.00 9631655.94 18.28 42022386.53 845287.47 0.00 0.27 01-NOV-12:30 0.00 01-NOV-00:10 1307.17 01-NOV-12:30 1307.17 01-NOV-12:30 86.03 16-NOV-16:40 288.80 01-NOV-12:30 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.966006E+10 0.211304E+10 1147.90 0.802109E+10 0.163897E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.288198E+10 0.629322E+09 264.25 0.240847E+10 0.569817E+09 0.00 1.00   0.00   6669.45   5860.97   3429.70   1283.06   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 7693504.08 1831946.34 5.97 6752241.94 941262.14 0.00 0.18 15-MAR-15:30 0.00 01-MAR-00:10 625.70 15-MAR-15:30 559.03 15-MAR-15:20 67.88 15-MAR-15:55 149.58 15-MAR-15:20 0.00
April 1172832.10 269366.06 3.62 1172832.10 0.00 0.00 0.04 21-APR-14:55 0.00 01-APR-00:10 146.75 21-APR-14:55 146.75 21-APR-14:55 0.00 21-APR-15:20 33.65 21-APR-14:55 0.00
May 0.153986E+09 34848041.98 87.14 0.143846E+09 10140372.69 0.00 0.67 26-MAY-10:02 0.00 01-MAY-00:10 2560.97 26-MAY-10:02 2483.29 26-MAY-10:02 248.57 10-MAY-14:05 532.38 26-MAY-10:02 0.00
June 0.108412E+10 0.241110E+09 242.20 0.931737E+09 0.152380E+09 0.00 1.00 12-JUN-05:02 0.00 01-JUN-00:10 4386.15 27-JUN-05:02 3741.39 30-JUN-10:02 1526.78 27-JUN-05:02 889.54 27-JUN-10:02 0.00
July 0.170121E+10 0.376515E+09 238.26 0.141856E+10 0.282651E+09 0.00 1.00 03-JUL-10:02 0.00 01-JUL-00:10 4637.67 21-JUL-05:02 3810.84 03-JUL-10:02 2396.16 21-JUL-05:05 932.86 21-JUL-14:03 0.00
August 0.170030E+10 0.376476E+09 272.81 0.147514E+10 0.225155E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 4586.02 14-AUG-05:01 3998.73 03-AUG-10:02 2095.58 14-AUG-05:07 884.57 10-AUG-10:02 0.00
September 0.939766E+09 0.206096E+09 221.11 0.832338E+09 0.107427E+09 0.00 1.00 13-SEP-05:02 0.00 01-SEP-00:10 4391.90 14-SEP-05:02 3868.84 20-SEP-10:02 1434.53 14-SEP-05:02 843.58 14-SEP-05:02 0.00
October 0.150570E+09 33784464.95 83.97 0.137914E+09 12656266.55 0.00 0.79 11-OCT-10:02 0.00 01-OCT-00:10 3075.43 11-OCT-10:02 2945.83 11-OCT-10:02 275.24 04-OCT-10:03 626.62 11-OCT-10:02 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.573881E+10 0.127093E+10 1155.07 0.494746E+10 0.791352E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.170121E+10 0.376515E+09 272.81 0.147514E+10 0.282651E+09 0.00 1.00   0.00   4637.67   3998.73   2396.16   932.86   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 4728869.66 1144548.92 3.00 4138994.95 589874.71 0.00 0.13 15-MAR-15:55 0.00 01-MAR-00:10 574.62 15-MAR-15:55 497.84 15-MAR-16:00 76.78 15-MAR-15:55 137.39 15-MAR-15:55 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00
May 89450447.92 20505853.47 46.54 79117432.24 10333015.68 0.00 0.26 10-MAY-15:00 0.00 01-MAY-00:10 1183.31 10-MAY-15:00 1069.67 23-MAY-15:58 256.30 10-MAY-15:00 279.60 10-MAY-15:00 0.00
June 0.137629E+10 0.305391E+09 234.28 0.109507E+10 0.281219E+09 0.00 1.00 19-JUN-05:02 0.00 01-JUN-00:10 5474.63 27-JUN-05:02 4385.84 21-JUN-05:02 1979.24 27-JUN-05:02 1053.76 27-JUN-05:02 0.00
July 0.230172E+10 0.506354E+09 239.50 0.178599E+10 0.515727E+09 0.00 1.00 05-JUL-05:02 0.00 01-JUL-00:10 5778.44 21-JUL-05:02 4298.35 12-JUL-05:02 2985.27 21-JUL-05:05 1107.94 21-JUL-05:12 0.00
August 0.231926E+10 0.510363E+09 273.11 0.189460E+10 0.424663E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5710.57 14-AUG-05:01 4759.68 21-AUG-05:02 2649.84 14-AUG-05:07 1080.70 14-AUG-05:01 0.00
September 0.113564E+10 0.249060E+09 207.71 0.932161E+09 0.203482E+09 0.00 1.00 14-SEP-05:02 0.00 01-SEP-00:10 5480.34 14-SEP-05:02 4366.89 18-SEP-05:02 1901.66 14-SEP-05:02 1053.47 14-SEP-05:02 0.00
October 0.123415E+09 27778203.92 54.07 0.105306E+09 18109582.33 0.00 0.28 05-OCT-15:40 0.00 01-OCT-00:10 1278.99 12-OCT-15:30 1143.16 05-OCT-15:23 284.18 12-OCT-15:30 282.54 12-OCT-15:30 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.735051E+10 0.162060E+10 1058.21 0.589639E+10 0.145412E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.231926E+10 0.510363E+09 273.11 0.189460E+10 0.515727E+09 0.00 1.00   0.00   5778.44   4759.68   2985.27   1107.94   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00 01-JAN-00:03 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 10987712.17 2616766.49 7.31 9585770.63 1401941.54 0.00 0.19 15-MAR-13:20 0.00 01-MAR-00:10 787.09 15-MAR-13:20 701.96 15-MAR-13:20 85.13 15-MAR-13:20 187.56 15-MAR-13:20 0.00
April 6471949.29 1476047.23 8.67 6350575.79 121373.50 0.00 0.13 20-APR-15:55 0.00 01-APR-00:10 507.17 20-APR-15:55 491.79 21-APR-15:55 32.98 20-APR-16:00 115.01 20-APR-15:55 0.00
May 0.179266E+09 40703061.24 96.08 0.164035E+09 15230705.03 0.00 0.37 31-MAY-15:55 0.00 01-MAY-00:10 1560.50 31-MAY-15:55 1474.20 26-MAY-15:53 223.32 10-MAY-15:03 345.59 31-MAY-15:55 0.00
June 0.119820E+10 0.268115E+09 248.21 0.100630E+10 0.191897E+09 0.00 1.00 12-JUN-05:02 0.00 01-JUN-00:10 5034.37 27-JUN-05:02 4204.74 21-JUN-05:02 1693.70 27-JUN-05:02 968.01 27-JUN-05:02 0.00
July 0.174629E+10 0.391587E+09 239.57 0.141638E+10 0.329918E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 5319.22 21-JUL-05:02 4212.28 12-JUL-05:02 2743.99 21-JUL-05:05 1016.84 21-JUL-05:07 0.00
August 0.182908E+10 0.408574E+09 274.22 0.155704E+10 0.272037E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5273.39 14-AUG-05:01 4670.71 04-AUG-05:02 2349.84 14-AUG-05:07 992.16 14-AUG-05:01 0.00
September 0.999658E+09 0.220718E+09 227.33 0.866249E+09 0.133409E+09 0.00 1.00 13-SEP-05:02 0.00 01-SEP-00:10 5035.70 14-SEP-05:02 4537.13 11-SEP-05:02 1659.49 14-SEP-05:02 967.39 14-SEP-05:02 0.00
October 0.181598E+09 40764214.68 87.25 0.163224E+09 18373603.13 0.00 0.43 11-OCT-15:53 0.00 01-OCT-00:10 1815.03 11-OCT-15:53 1683.45 11-OCT-15:57 247.32 12-OCT-15:25 395.58 11-OCT-15:53 0.00
November 160423.89 36951.39 1.00 136784.47 23639.42 0.00 0.02 16-NOV-16:40 0.00 01-NOV-00:10 68.13 16-NOV-16:40 58.07 16-NOV-16:40 10.06 16-NOV-16:40 15.69 16-NOV-16:40 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00 01-DEC-00:10 0.00
                                       
Annual Sum or Average 0.615171E+10 0.137459E+10 1189.63 0.518930E+10 0.962413E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.182908E+10 0.408574E+09 274.22 0.155704E+10 0.329918E+09 0.00 1.00   0.00   5319.22   4670.71   2743.99   1016.84   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.11 38.65 26.45 56.31 72.10 0.00 0.00 0.00
February 73.89 36.46 37.44 63.41 70.23 0.00 0.00 0.00
March 90.55 51.85 38.70 95.12 50.85 0.00 0.00 0.00
April 64.92 23.59 41.33 68.18 38.38 0.00 0.00 0.00
May 49.28 8.61 40.67 52.31 25.29 0.00 0.00 0.00
June 46.45 3.16 43.29 53.25 18.24 0.00 0.00 0.00
July 48.05 5.50 42.55 62.83 13.52 0.00 0.00 0.00
August 58.84 14.91 43.93 77.37 18.90 0.00 0.00 0.00
September 79.95 38.43 41.52 99.88 30.19 0.00 0.00 0.00
October 81.36 47.33 34.04 90.16 43.33 0.00 0.00 0.00
November 58.22 33.50 24.72 57.82 51.66 0.00 0.00 0.00
December 54.25 28.66 25.60 44.58 71.60 0.00 0.00 0.00
                 
Annual Sum or Average 64.18 27.51 36.67 68.46 41.87 0.00 0.00 0.00
Minimum of Months 46.45 3.16 24.72 44.58 13.52 0.00 0.00 0.00
Maximum of Months 90.55 51.85 43.93 99.88 72.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.11 38.65 26.45 56.31 72.10 0.00 0.00 0.00
February 73.89 36.46 37.44 63.41 70.23 0.00 0.00 0.00
March 90.55 51.85 38.70 95.12 50.85 0.00 0.00 0.00
April 64.79 23.54 41.25 68.01 38.45 0.00 0.00 0.00
May 49.23 8.59 40.64 52.21 25.29 0.00 0.00 0.00
June 46.43 3.16 43.28 53.23 18.24 0.00 0.00 0.00
July 48.02 5.49 42.53 62.78 13.52 0.00 0.00 0.00
August 58.72 14.86 43.85 77.13 18.90 0.00 0.00 0.00
September 79.88 38.40 41.48 99.76 30.21 0.00 0.00 0.00
October 81.36 47.33 34.03 90.16 43.33 0.00 0.00 0.00
November 58.22 33.50 24.72 57.82 51.66 0.00 0.00 0.00
December 54.25 28.66 25.60 44.58 71.60 0.00 0.00 0.00
                 
Annual Sum or Average 64.15 27.50 36.65 68.40 41.88 0.00 0.00 0.00
Minimum of Months 46.43 3.16 24.72 44.58 13.52 0.00 0.00 0.00
Maximum of Months 90.55 51.85 43.85 99.76 72.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.11 38.65 26.45 56.31 72.10 0.00 0.00 0.00
February 73.89 36.46 37.44 63.41 70.23 0.00 0.00 0.00
March 90.55 51.85 38.70 95.12 50.85 0.00 0.00 0.00
April 64.79 23.54 41.25 68.01 38.45 0.00 0.00 0.00
May 49.23 8.59 40.64 52.21 25.29 0.00 0.00 0.00
June 46.43 3.16 43.28 53.23 18.24 0.00 0.00 0.00
July 48.02 5.49 42.53 62.78 13.52 0.00 0.00 0.00
August 58.72 14.86 43.85 77.13 18.90 0.00 0.00 0.00
September 79.87 38.40 41.48 99.76 30.22 0.00 0.00 0.00
October 81.36 47.33 34.03 90.16 43.33 0.00 0.00 0.00
November 58.22 33.50 24.72 57.82 51.66 0.00 0.00 0.00
December 54.25 28.66 25.60 44.58 71.60 0.00 0.00 0.00
                 
Annual Sum or Average 64.14 27.50 36.65 68.40 41.88 0.00 0.00 0.00
Minimum of Months 46.43 3.16 24.72 44.58 13.52 0.00 0.00 0.00
Maximum of Months 90.55 51.85 43.85 99.76 72.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.11 38.65 26.45 56.31 72.10 0.00 0.00 0.00
February 73.89 36.46 37.44 63.41 70.23 0.00 0.00 0.00
March 90.55 51.85 38.70 95.12 50.85 0.00 0.00 0.00
April 64.79 23.54 41.25 68.01 38.45 0.00 0.00 0.00
May 49.23 8.59 40.64 52.21 25.29 0.00 0.00 0.00
June 46.43 3.16 43.28 53.23 18.24 0.00 0.00 0.00
July 48.02 5.49 42.53 62.78 13.52 0.00 0.00 0.00
August 58.72 14.86 43.85 77.13 18.90 0.00 0.00 0.00
September 79.87 38.40 41.48 99.76 30.22 0.00 0.00 0.00
October 81.36 47.33 34.03 90.16 43.33 0.00 0.00 0.00
November 58.22 33.50 24.72 57.82 51.66 0.00 0.00 0.00
December 54.25 28.66 25.60 44.58 71.60 0.00 0.00 0.00
                 
Annual Sum or Average 64.14 27.50 36.65 68.40 41.88 0.00 0.00 0.00
Minimum of Months 46.43 3.16 24.72 44.58 13.52 0.00 0.00 0.00
Maximum of Months 90.55 51.85 43.85 99.76 72.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.11 38.65 26.45 56.31 72.10 0.00 0.00 0.00
February 73.89 36.46 37.44 63.41 70.23 0.00 0.00 0.00
March 90.55 51.85 38.70 95.12 50.85 0.00 0.00 0.00
April 64.79 23.54 41.25 68.01 38.45 0.00 0.00 0.00
May 49.23 8.59 40.64 52.21 25.29 0.00 0.00 0.00
June 46.43 3.16 43.28 53.23 18.24 0.00 0.00 0.00
July 48.02 5.49 42.53 62.78 13.52 0.00 0.00 0.00
August 58.72 14.86 43.85 77.13 18.90 0.00 0.00 0.00
September 79.88 38.40 41.48 99.76 30.20 0.00 0.00 0.00
October 81.36 47.33 34.03 90.16 43.33 0.00 0.00 0.00
November 58.22 33.50 24.72 57.82 51.66 0.00 0.00 0.00
December 54.25 28.66 25.60 44.58 71.60 0.00 0.00 0.00
                 
Annual Sum or Average 64.15 27.50 36.65 68.40 41.88 0.00 0.00 0.00
Minimum of Months 46.43 3.16 24.72 44.58 13.52 0.00 0.00 0.00
Maximum of Months 90.55 51.85 43.85 99.76 72.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 65.11 38.65 26.45 56.31 72.10 0.00 0.00 0.00
February 73.89 36.46 37.44 63.41 70.23 0.00 0.00 0.00
March 90.55 51.85 38.70 95.12 50.85 0.00 0.00 0.00
April 64.94 23.60 41.34 68.16 38.31 0.00 0.00 0.00
May 49.28 8.61 40.68 52.31 25.29 0.00 0.00 0.00
June 46.44 3.16 43.28 53.25 18.24 0.00 0.00 0.00
July 48.05 5.50 42.54 62.82 13.52 0.00 0.00 0.00
August 58.84 14.91 43.92 77.37 18.90 0.00 0.00 0.00
September 79.95 38.43 41.52 99.83 30.14 0.00 0.00 0.00
October 81.36 47.33 34.04 90.16 43.33 0.00 0.00 0.00
November 58.22 33.50 24.72 57.82 51.66 0.00 0.00 0.00
December 54.25 28.66 25.60 44.58 71.60 0.00 0.00 0.00
                 
Annual Sum or Average 64.18 27.51 36.67 68.45 41.86 0.00 0.00 0.00
Minimum of Months 46.44 3.16 24.72 44.58 13.52 0.00 0.00 0.00
Maximum of Months 90.55 51.85 43.92 99.83 72.10 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.99 54.15 37.83 79.79 100.07 0.00 0.00 0.00
February 104.71 51.08 53.63 90.44 97.41 0.00 0.00 0.00
March 128.06 72.64 55.42 134.79 70.77 0.00 0.00 0.00
April 103.71 41.57 62.13 114.57 53.32 0.00 0.00 0.00
May 81.50 19.90 61.59 93.15 35.30 0.00 0.00 0.00
June 76.19 10.88 65.31 92.85 25.58 0.00 0.00 0.00
July 79.19 14.73 64.46 107.27 19.04 0.00 0.00 0.00
August 95.65 29.06 66.59 128.80 26.52 0.00 0.00 0.00
September 120.05 59.05 61.00 151.54 42.19 0.00 0.00 0.00
October 115.02 66.31 48.72 127.53 60.41 0.00 0.00 0.00
November 82.34 46.93 35.41 81.86 71.81 0.00 0.00 0.00
December 76.78 40.15 36.64 63.32 99.28 0.00 0.00 0.00
                 
Annual Sum or Average 96.20 42.16 54.04 105.56 58.27 0.00 0.00 0.00
Minimum of Months 76.19 10.88 35.41 63.32 19.04 0.00 0.00 0.00
Maximum of Months 128.06 72.64 66.59 151.54 100.07 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.65 8.89 17.76 11.54 76.34 0.00 0.00 0.00
February 38.86 12.05 26.81 20.01 71.56 0.00 0.00 0.00
March 55.92 23.70 32.21 46.99 49.10 0.00 0.00 0.00
April 73.88 32.98 40.90 74.56 34.50 0.00 0.00 0.00
May 81.69 35.96 45.73 92.66 23.69 0.00 0.00 0.00
June 91.17 39.99 51.18 111.99 17.37 0.00 0.00 0.00
July 87.75 38.47 49.28 114.83 12.87 0.00 0.00 0.00
August 79.62 33.54 46.08 101.40 17.76 0.00 0.00 0.00
September 66.83 29.93 36.89 76.90 27.72 0.00 0.00 0.00
October 45.63 19.29 26.34 41.46 41.53 0.00 0.00 0.00
November 25.74 8.54 17.20 17.05 50.92 0.00 0.00 0.00
December 20.55 4.43 16.13 6.10 75.66 0.00 0.00 0.00
                 
Annual Sum or Average 57.94 24.04 33.91 59.84 41.44 0.00 0.00 0.00
Minimum of Months 20.55 4.43 16.13 6.10 12.87 0.00 0.00 0.00
Maximum of Months 91.17 39.99 51.18 114.83 76.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.65 8.89 17.76 11.54 76.34 0.00 0.00 0.00
February 38.85 12.05 26.81 20.01 71.56 0.00 0.00 0.00
March 55.91 23.70 32.21 46.99 49.09 0.00 0.00 0.00
April 73.88 32.98 40.90 74.56 34.50 0.00 0.00 0.00
May 81.69 35.96 45.73 92.66 23.69 0.00 0.00 0.00
June 91.17 39.99 51.18 111.99 17.37 0.00 0.00 0.00
July 87.75 38.47 49.28 114.83 12.87 0.00 0.00 0.00
August 79.62 33.54 46.08 101.40 17.76 0.00 0.00 0.00
September 66.82 29.93 36.89 76.89 27.72 0.00 0.00 0.00
October 45.62 19.29 26.33 41.46 41.53 0.00 0.00 0.00
November 25.74 8.54 17.20 17.05 50.92 0.00 0.00 0.00
December 20.55 4.43 16.12 6.10 75.66 0.00 0.00 0.00
                 
Annual Sum or Average 57.94 24.04 33.90 59.83 41.44 0.00 0.00 0.00
Minimum of Months 20.55 4.43 16.12 6.10 12.87 0.00 0.00 0.00
Maximum of Months 91.17 39.99 51.18 114.83 76.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.65 8.89 17.76 11.54 76.34 0.00 0.00 0.00
February 38.85 12.05 26.81 20.01 71.56 0.00 0.00 0.00
March 55.91 23.70 32.21 46.99 49.09 0.00 0.00 0.00
April 73.88 32.98 40.90 74.56 34.50 0.00 0.00 0.00
May 81.69 35.96 45.73 92.66 23.69 0.00 0.00 0.00
June 91.17 39.99 51.18 111.99 17.37 0.00 0.00 0.00
July 87.75 38.47 49.28 114.83 12.87 0.00 0.00 0.00
August 79.62 33.54 46.08 101.40 17.76 0.00 0.00 0.00
September 66.82 29.93 36.89 76.89 27.72 0.00 0.00 0.00
October 45.62 19.29 26.33 41.46 41.53 0.00 0.00 0.00
November 25.74 8.54 17.20 17.05 50.92 0.00 0.00 0.00
December 20.55 4.43 16.12 6.10 75.66 0.00 0.00 0.00
                 
Annual Sum or Average 57.94 24.04 33.90 59.83 41.44 0.00 0.00 0.00
Minimum of Months 20.55 4.43 16.12 6.10 12.87 0.00 0.00 0.00
Maximum of Months 91.17 39.99 51.18 114.83 76.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 26.73 8.92 17.81 11.60 76.24 0.00 0.00 0.00
February 38.90 12.06 26.84 20.07 71.53 0.00 0.00 0.00
March 55.92 23.70 32.22 47.00 49.09 0.00 0.00 0.00
April 73.88 32.98 40.90 74.56 34.50 0.00 0.00 0.00
May 81.69 35.96 45.73 92.66 23.69 0.00 0.00 0.00
June 91.17 39.99 51.18 111.99 17.37 0.00 0.00 0.00
July 87.75 38.47 49.28 114.83 12.87 0.00 0.00 0.00
August 79.62 33.54 46.08 101.40 17.76 0.00 0.00 0.00
September 66.83 29.93 36.89 76.90 27.72 0.00 0.00 0.00
October 45.65 19.30 26.35 41.51 41.53 0.00 0.00 0.00
November 25.80 8.56 17.24 17.14 50.91 0.00 0.00 0.00
December 20.64 4.45 16.19 6.16 75.57 0.00 0.00 0.00
                 
Annual Sum or Average 57.97 24.05 33.92 59.86 41.42 0.00 0.00 0.00
Minimum of Months 20.64 4.45 16.19 6.16 12.87 0.00 0.00 0.00
Maximum of Months 91.17 39.99 51.18 114.83 76.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.29 0.00 14.29 0.29 83.85 0.00 0.00 0.00
February 21.75 0.00 21.75 1.80 77.93 0.00 0.00 0.00
March 26.73 0.00 26.73 10.68 53.26 0.00 0.00 0.00
April 34.14 0.14 34.00 22.98 35.61 0.00 0.00 0.00
May 39.92 1.65 38.27 36.81 22.64 0.00 0.00 0.00
June 47.88 3.94 43.94 54.07 16.51 0.00 0.00 0.00
July 44.52 2.81 41.71 56.80 12.24 0.00 0.00 0.00
August 38.50 0.58 37.92 46.03 17.14 0.00 0.00 0.00
September 29.31 0.01 29.31 27.14 27.94 0.00 0.00 0.00
October 21.65 0.00 21.65 11.11 42.67 0.00 0.00 0.00
November 14.43 0.00 14.43 3.74 52.64 0.00 0.00 0.00
December 13.30 0.00 13.30 0.35 80.65 0.00 0.00 0.00
                 
Annual Sum or Average 28.90 0.76 28.13 22.77 43.42 0.00 0.00 0.00
Minimum of Months 13.30 0.00 13.30 0.29 12.24 0.00 0.00 0.00
Maximum of Months 47.88 3.94 43.94 56.80 83.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.29 0.00 14.29 0.29 83.85 0.00 0.00 0.00
February 21.75 0.00 21.75 1.80 77.93 0.00 0.00 0.00
March 26.73 0.00 26.73 10.68 53.26 0.00 0.00 0.00
April 34.11 0.13 33.98 22.98 35.65 0.00 0.00 0.00
May 39.82 1.61 38.21 36.64 22.67 0.00 0.00 0.00
June 47.75 3.89 43.87 53.83 16.51 0.00 0.00 0.00
July 44.40 2.76 41.64 56.57 12.24 0.00 0.00 0.00
August 38.42 0.56 37.86 45.89 17.15 0.00 0.00 0.00
September 29.31 0.01 29.30 27.14 27.94 0.00 0.00 0.00
October 21.65 0.00 21.65 11.11 42.67 0.00 0.00 0.00
November 14.43 0.00 14.43 3.74 52.64 0.00 0.00 0.00
December 13.30 0.00 13.30 0.35 80.65 0.00 0.00 0.00
                 
Annual Sum or Average 28.86 0.75 28.11 22.71 43.43 0.00 0.00 0.00
Minimum of Months 13.30 0.00 13.30 0.29 12.24 0.00 0.00 0.00
Maximum of Months 47.75 3.89 43.87 56.57 83.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.29 0.00 14.29 0.29 83.85 0.00 0.00 0.00
February 21.75 0.00 21.75 1.80 77.93 0.00 0.00 0.00
March 26.73 0.00 26.73 10.68 53.26 0.00 0.00 0.00
April 34.10 0.13 33.97 22.98 35.66 0.00 0.00 0.00
May 39.82 1.61 38.21 36.64 22.67 0.00 0.00 0.00
June 47.75 3.89 43.87 53.83 16.51 0.00 0.00 0.00
July 44.40 2.76 41.64 56.57 12.24 0.00 0.00 0.00
August 38.42 0.56 37.86 45.89 17.15 0.00 0.00 0.00
September 29.31 0.01 29.31 27.14 27.94 0.00 0.00 0.00
October 21.65 0.00 21.65 11.11 42.67 0.00 0.00 0.00
November 14.43 0.00 14.43 3.74 52.64 0.00 0.00 0.00
December 13.30 0.00 13.30 0.35 80.65 0.00 0.00 0.00
                 
Annual Sum or Average 28.86 0.75 28.11 22.71 43.43 0.00 0.00 0.00
Minimum of Months 13.30 0.00 13.30 0.29 12.24 0.00 0.00 0.00
Maximum of Months 47.75 3.89 43.87 56.57 83.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.29 0.00 14.29 0.29 83.85 0.00 0.00 0.00
February 21.75 0.00 21.75 1.80 77.93 0.00 0.00 0.00
March 26.73 0.00 26.73 10.68 53.26 0.00 0.00 0.00
April 34.10 0.13 33.97 22.98 35.66 0.00 0.00 0.00
May 39.82 1.61 38.21 36.64 22.67 0.00 0.00 0.00
June 47.75 3.89 43.87 53.83 16.51 0.00 0.00 0.00
July 44.40 2.76 41.64 56.57 12.24 0.00 0.00 0.00
August 38.42 0.56 37.86 45.89 17.15 0.00 0.00 0.00
September 29.31 0.01 29.31 27.14 27.94 0.00 0.00 0.00
October 21.65 0.00 21.65 11.11 42.67 0.00 0.00 0.00
November 14.43 0.00 14.43 3.74 52.64 0.00 0.00 0.00
December 13.30 0.00 13.30 0.35 80.65 0.00 0.00 0.00
                 
Annual Sum or Average 28.86 0.75 28.11 22.71 43.43 0.00 0.00 0.00
Minimum of Months 13.30 0.00 13.30 0.29 12.24 0.00 0.00 0.00
Maximum of Months 47.75 3.89 43.87 56.57 83.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.29 0.00 14.29 0.29 83.85 0.00 0.00 0.00
February 21.75 0.00 21.75 1.80 77.93 0.00 0.00 0.00
March 26.73 0.00 26.73 10.68 53.26 0.00 0.00 0.00
April 34.11 0.13 33.98 22.98 35.65 0.00 0.00 0.00
May 39.82 1.61 38.21 36.64 22.67 0.00 0.00 0.00
June 47.75 3.89 43.87 53.83 16.51 0.00 0.00 0.00
July 44.40 2.76 41.64 56.57 12.24 0.00 0.00 0.00
August 38.41 0.56 37.86 45.89 17.15 0.00 0.00 0.00
September 29.31 0.01 29.31 27.14 27.94 0.00 0.00 0.00
October 21.65 0.00 21.65 11.11 42.67 0.00 0.00 0.00
November 14.43 0.00 14.43 3.74 52.64 0.00 0.00 0.00
December 13.30 0.00 13.30 0.35 80.65 0.00 0.00 0.00
                 
Annual Sum or Average 28.86 0.75 28.11 22.71 43.43 0.00 0.00 0.00
Minimum of Months 13.30 0.00 13.30 0.29 12.24 0.00 0.00 0.00
Maximum of Months 47.75 3.89 43.87 56.57 83.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 14.29 0.00 14.29 0.29 83.85 0.00 0.00 0.00
February 21.75 0.00 21.75 1.80 77.93 0.00 0.00 0.00
March 26.73 0.00 26.73 10.68 53.26 0.00 0.00 0.00
April 34.14 0.14 34.00 22.99 35.62 0.00 0.00 0.00
May 39.93 1.65 38.28 36.85 22.67 0.00 0.00 0.00
June 47.90 3.95 43.95 54.12 16.51 0.00 0.00 0.00
July 44.52 2.81 41.71 56.81 12.24 0.00 0.00 0.00
August 38.49 0.58 37.91 46.03 17.15 0.00 0.00 0.00
September 29.31 0.01 29.31 27.14 27.94 0.00 0.00 0.00
October 21.65 0.00 21.65 11.11 42.67 0.00 0.00 0.00
November 14.43 0.00 14.43 3.74 52.64 0.00 0.00 0.00
December 13.30 0.00 13.30 0.35 80.65 0.00 0.00 0.00
                 
Annual Sum or Average 28.90 0.76 28.14 22.78 43.43 0.00 0.00 0.00
Minimum of Months 13.30 0.00 13.30 0.29 12.24 0.00 0.00 0.00
Maximum of Months 47.90 3.95 43.95 56.81 83.85 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.79 5.54 17.25 7.18 79.09 0.00 0.00 0.00
February 36.82 9.79 27.03 17.55 74.00 0.00 0.00 0.00
March 58.06 25.21 32.85 50.00 50.81 0.00 0.00 0.00
April 70.22 28.92 41.30 70.78 36.29 0.00 0.00 0.00
May 82.63 37.19 45.44 94.53 25.42 0.00 0.00 0.00
June 99.72 46.74 52.98 124.01 19.37 0.00 0.00 0.00
July 88.89 38.77 50.12 116.83 14.48 0.00 0.00 0.00
August 80.77 34.44 46.32 104.02 19.26 0.00 0.00 0.00
September 64.10 27.96 36.13 74.19 29.25 0.00 0.00 0.00
October 41.60 14.96 26.64 37.08 42.88 0.00 0.00 0.00
November 24.63 7.34 17.29 15.83 51.93 0.00 0.00 0.00
December 21.31 4.85 16.46 7.09 76.95 0.00 0.00 0.00
                 
Annual Sum or Average 57.72 23.54 34.18 60.15 43.16 0.00 0.00 0.00
Minimum of Months 21.31 4.85 16.46 7.09 14.48 0.00 0.00 0.00
Maximum of Months 99.72 46.74 52.98 124.01 79.09 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.72 5.52 17.20 7.14 79.18 0.00 0.00 0.00
February 36.78 9.78 27.00 17.50 74.03 0.00 0.00 0.00
March 58.05 25.20 32.85 49.99 50.81 0.00 0.00 0.00
April 70.22 28.92 41.30 70.78 36.29 0.00 0.00 0.00
May 82.63 37.19 45.44 94.53 25.42 0.00 0.00 0.00
June 99.72 46.74 52.98 124.01 19.37 0.00 0.00 0.00
July 88.89 38.77 50.12 116.83 14.48 0.00 0.00 0.00
August 80.76 34.44 46.32 104.02 19.26 0.00 0.00 0.00
September 64.09 27.96 36.13 74.18 29.25 0.00 0.00 0.00
October 41.58 14.95 26.63 37.03 42.88 0.00 0.00 0.00
November 24.58 7.32 17.26 15.75 51.94 0.00 0.00 0.00
December 21.23 4.82 16.40 7.03 77.03 0.00 0.00 0.00
                 
Annual Sum or Average 57.70 23.53 34.16 60.12 43.18 0.00 0.00 0.00
Minimum of Months 21.23 4.82 16.40 7.03 14.48 0.00 0.00 0.00
Maximum of Months 99.72 46.74 52.98 124.01 79.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.72 5.52 17.20 7.14 79.18 0.00 0.00 0.00
February 36.78 9.78 27.00 17.50 74.03 0.00 0.00 0.00
March 58.05 25.20 32.85 49.99 50.81 0.00 0.00 0.00
April 70.22 28.92 41.30 70.78 36.29 0.00 0.00 0.00
May 82.63 37.19 45.44 94.53 25.42 0.00 0.00 0.00
June 99.72 46.74 52.98 124.01 19.37 0.00 0.00 0.00
July 88.89 38.77 50.12 116.83 14.48 0.00 0.00 0.00
August 80.76 34.44 46.32 104.02 19.26 0.00 0.00 0.00
September 64.09 27.96 36.13 74.18 29.25 0.00 0.00 0.00
October 41.58 14.95 26.63 37.03 42.88 0.00 0.00 0.00
November 24.58 7.32 17.26 15.75 51.94 0.00 0.00 0.00
December 21.23 4.82 16.40 7.03 77.03 0.00 0.00 0.00
                 
Annual Sum or Average 57.70 23.53 34.16 60.12 43.18 0.00 0.00 0.00
Minimum of Months 21.23 4.82 16.40 7.03 14.48 0.00 0.00 0.00
Maximum of Months 99.72 46.74 52.98 124.01 79.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 22.72 5.52 17.20 7.14 79.18 0.00 0.00 0.00
February 36.78 9.78 27.00 17.50 74.02 0.00 0.00 0.00
March 58.05 25.20 32.85 50.00 50.81 0.00 0.00 0.00
April 70.22 28.92 41.30 70.78 36.29 0.00 0.00 0.00
May 82.63 37.19 45.44 94.53 25.42 0.00 0.00 0.00
June 99.72 46.74 52.98 124.01 19.37 0.00 0.00 0.00
July 88.89 38.77 50.12 116.83 14.48 0.00 0.00 0.00
August 80.77 34.44 46.32 104.02 19.26 0.00 0.00 0.00
September 64.09 27.96 36.13 74.18 29.25 0.00 0.00 0.00
October 41.58 14.95 26.63 37.03 42.88 0.00 0.00 0.00
November 24.58 7.32 17.26 15.75 51.94 0.00 0.00 0.00
December 21.23 4.82 16.40 7.03 77.03 0.00 0.00 0.00
                 
Annual Sum or Average 57.70 23.53 34.16 60.12 43.18 0.00 0.00 0.00
Minimum of Months 21.23 4.82 16.40 7.03 14.48 0.00 0.00 0.00
Maximum of Months 99.72 46.74 52.98 124.01 79.18 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174383E+09 0.103530E+09 70853647.19 0.150816E+09 0.193113E+09
February 0.178762E+09 88194009.43 90567647.84 0.153409E+09 0.169912E+09
March 0.242540E+09 0.138880E+09 0.103660E+09 0.254777E+09 0.136201E+09
April 0.168264E+09 61134344.41 0.107130E+09 0.176733E+09 99478602.37
May 0.131997E+09 23055501.63 0.108941E+09 0.140105E+09 67728826.46
June 0.120386E+09 8188293.47 0.112198E+09 0.138022E+09 47266418.71
July 0.128696E+09 14739511.64 0.113956E+09 0.168273E+09 36218910.72
August 0.157593E+09 39942518.92 0.117650E+09 0.207234E+09 50634608.73
September 0.207227E+09 99606222.52 0.107620E+09 0.258879E+09 78253466.52
October 0.217926E+09 0.126764E+09 91161913.95 0.241481E+09 0.116044E+09
November 0.150903E+09 86828693.45 64073990.86 0.149874E+09 0.133893E+09
December 0.145316E+09 76755673.71 68560255.02 0.119395E+09 0.191786E+09
           
Annual Sum or Average 0.202399E+10 0.867618E+09 0.115637E+10 0.215900E+10 0.132053E+10
Minimum of Months 0.120386E+09 8188293.47 64073990.86 0.119395E+09 36218910.72
Maximum of Months 0.242540E+09 0.138880E+09 0.117650E+09 0.258879E+09 0.193113E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174380E+09 0.103530E+09 70850365.01 0.150813E+09 0.193112E+09
February 0.178757E+09 88194009.43 90563080.28 0.153405E+09 0.169912E+09
March 0.242535E+09 0.138880E+09 0.103655E+09 0.254772E+09 0.136201E+09
April 0.167928E+09 61010354.53 0.106918E+09 0.176288E+09 99657506.75
May 0.131858E+09 23002143.14 0.108856E+09 0.139844E+09 67728386.09
June 0.120357E+09 8181642.54 0.112175E+09 0.137971E+09 47265608.27
July 0.128624E+09 14713539.34 0.113910E+09 0.168138E+09 36218034.44
August 0.157263E+09 39802763.96 0.117460E+09 0.206596E+09 50634449.60
September 0.207051E+09 99531417.40 0.107520E+09 0.258591E+09 78300599.33
October 0.217921E+09 0.126764E+09 91157510.43 0.241476E+09 0.116043E+09
November 0.150899E+09 86828693.45 64070788.28 0.149871E+09 0.133893E+09
December 0.145313E+09 76755673.71 68556955.59 0.119392E+09 0.191786E+09
           
Annual Sum or Average 0.202289E+10 0.867193E+09 0.115569E+10 0.215716E+10 0.132075E+10
Minimum of Months 0.120357E+09 8181642.54 64070788.28 0.119392E+09 36218034.44
Maximum of Months 0.242535E+09 0.138880E+09 0.117460E+09 0.258591E+09 0.193112E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174380E+09 0.103530E+09 70850365.01 0.150813E+09 0.193112E+09
February 0.178757E+09 88194009.43 90563080.28 0.153405E+09 0.169912E+09
March 0.242535E+09 0.138880E+09 0.103655E+09 0.254772E+09 0.136201E+09
April 0.167926E+09 61010209.90 0.106916E+09 0.176287E+09 99660856.81
May 0.131858E+09 23002143.14 0.108856E+09 0.139844E+09 67728386.09
June 0.120357E+09 8181642.54 0.112175E+09 0.137971E+09 47265608.27
July 0.128624E+09 14713539.34 0.113910E+09 0.168138E+09 36218034.44
August 0.157263E+09 39802761.31 0.117460E+09 0.206596E+09 50634493.74
September 0.207034E+09 99527608.85 0.107506E+09 0.258583E+09 78324905.23
October 0.217921E+09 0.126764E+09 91157510.43 0.241476E+09 0.116043E+09
November 0.150899E+09 86828693.45 64070788.28 0.149871E+09 0.133893E+09
December 0.145313E+09 76755673.71 68556955.59 0.119392E+09 0.191786E+09
           
Annual Sum or Average 0.202287E+10 0.867189E+09 0.115568E+10 0.215715E+10 0.132078E+10
Minimum of Months 0.120357E+09 8181642.54 64070788.28 0.119392E+09 36218034.44
Maximum of Months 0.242535E+09 0.138880E+09 0.117460E+09 0.258583E+09 0.193112E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174380E+09 0.103530E+09 70850365.01 0.150813E+09 0.193112E+09
February 0.178757E+09 88194009.43 90563080.28 0.153405E+09 0.169912E+09
March 0.242535E+09 0.138880E+09 0.103655E+09 0.254772E+09 0.136201E+09
April 0.167926E+09 61010209.90 0.106916E+09 0.176287E+09 99660856.81
May 0.131858E+09 23002143.14 0.108856E+09 0.139844E+09 67728386.09
June 0.120357E+09 8181642.54 0.112175E+09 0.137971E+09 47265608.27
July 0.128624E+09 14713539.34 0.113910E+09 0.168138E+09 36218034.44
August 0.157263E+09 39802836.97 0.117460E+09 0.206596E+09 50634233.20
September 0.207035E+09 99527298.56 0.107508E+09 0.258582E+09 78322131.52
October 0.217921E+09 0.126764E+09 91157510.43 0.241476E+09 0.116043E+09
November 0.150899E+09 86828693.45 64070788.28 0.149871E+09 0.133893E+09
December 0.145313E+09 76755673.71 68556955.59 0.119392E+09 0.191786E+09
           
Annual Sum or Average 0.202287E+10 0.867189E+09 0.115568E+10 0.215715E+10 0.132078E+10
Minimum of Months 0.120357E+09 8181642.54 64070788.28 0.119392E+09 36218034.44
Maximum of Months 0.242535E+09 0.138880E+09 0.117460E+09 0.258582E+09 0.193112E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174380E+09 0.103530E+09 70850365.01 0.150813E+09 0.193112E+09
February 0.178757E+09 88194009.43 90563080.28 0.153405E+09 0.169912E+09
March 0.242535E+09 0.138880E+09 0.103655E+09 0.254772E+09 0.136201E+09
April 0.167929E+09 61010373.85 0.106918E+09 0.176287E+09 99656964.57
May 0.131858E+09 23002143.14 0.108856E+09 0.139844E+09 67728386.09
June 0.120357E+09 8181642.54 0.112175E+09 0.137971E+09 47265608.27
July 0.128624E+09 14713539.34 0.113910E+09 0.168138E+09 36218034.44
August 0.157263E+09 39803282.55 0.117460E+09 0.206596E+09 50632811.70
September 0.207056E+09 99530548.48 0.107526E+09 0.258585E+09 78288053.75
October 0.217921E+09 0.126764E+09 91157510.43 0.241476E+09 0.116043E+09
November 0.150899E+09 86828693.45 64070788.28 0.149871E+09 0.133893E+09
December 0.145313E+09 76755673.71 68556955.59 0.119392E+09 0.191786E+09
           
Annual Sum or Average 0.202289E+10 0.867193E+09 0.115570E+10 0.215715E+10 0.132074E+10
Minimum of Months 0.120357E+09 8181642.54 64070788.28 0.119392E+09 36218034.44
Maximum of Months 0.242535E+09 0.138880E+09 0.117460E+09 0.258585E+09 0.193112E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174383E+09 0.103530E+09 70853647.02 0.150816E+09 0.193113E+09
February 0.178762E+09 88194009.43 90567647.61 0.153409E+09 0.169912E+09
March 0.242540E+09 0.138880E+09 0.103660E+09 0.254777E+09 0.136201E+09
April 0.168314E+09 61169563.49 0.107145E+09 0.176665E+09 99292485.92
May 0.131997E+09 23051898.63 0.108945E+09 0.140102E+09 67728804.66
June 0.120382E+09 8187539.40 0.112194E+09 0.138014E+09 47266418.67
July 0.128688E+09 14738140.87 0.113950E+09 0.168260E+09 36218910.67
August 0.157590E+09 39941725.46 0.117648E+09 0.207219E+09 50628150.26
September 0.207236E+09 99606001.77 0.107630E+09 0.258766E+09 78129786.41
October 0.217926E+09 0.126764E+09 91161913.73 0.241481E+09 0.116044E+09
November 0.150903E+09 86828693.45 64073990.69 0.149874E+09 0.133893E+09
December 0.145316E+09 76755673.71 68560254.85 0.119395E+09 0.191786E+09
           
Annual Sum or Average 0.202404E+10 0.867646E+09 0.115639E+10 0.215878E+10 0.132021E+10
Minimum of Months 0.120382E+09 8187539.40 64073990.69 0.119395E+09 36218910.67
Maximum of Months 0.242540E+09 0.138880E+09 0.117648E+09 0.258766E+09 0.193113E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.246373E+09 0.145046E+09 0.101326E+09 0.213701E+09 0.268020E+09
February 0.253313E+09 0.123561E+09 0.129753E+09 0.218796E+09 0.235661E+09
March 0.343002E+09 0.194572E+09 0.148430E+09 0.361010E+09 0.189541E+09
April 0.268808E+09 0.107757E+09 0.161051E+09 0.296963E+09 0.138202E+09
May 0.218286E+09 53310501.00 0.164976E+09 0.249501E+09 94540209.54
June 0.197475E+09 28189244.84 0.169285E+09 0.240662E+09 66306698.46
July 0.212094E+09 39452209.40 0.172642E+09 0.287319E+09 51004382.95
August 0.256195E+09 77831995.47 0.178363E+09 0.344976E+09 71033831.06
September 0.311169E+09 0.153050E+09 0.158118E+09 0.392783E+09 0.109351E+09
October 0.308080E+09 0.177598E+09 0.130482E+09 0.341588E+09 0.161789E+09
November 0.213426E+09 0.121648E+09 91778064.88 0.212174E+09 0.186143E+09
December 0.205660E+09 0.107536E+09 98124153.68 0.169600E+09 0.265912E+09
           
Annual Sum or Average 0.303388E+10 0.132955E+10 0.170433E+10 0.332907E+10 0.183750E+10
Minimum of Months 0.197475E+09 28189244.84 91778064.88 0.169600E+09 51004382.95
Maximum of Months 0.343002E+09 0.194572E+09 0.178363E+09 0.392783E+09 0.268020E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71374908.81 23805065.88 47569842.93 30921430.45 0.204478E+09
February 94000346.29 29143298.84 64857047.45 48413969.53 0.173115E+09
March 0.149766E+09 63482962.69 86282744.38 0.125863E+09 0.131496E+09
April 0.191509E+09 85484659.04 0.106024E+09 0.193267E+09 89431574.49
May 0.218806E+09 96324394.74 0.122481E+09 0.248180E+09 63452357.47
June 0.236319E+09 0.103662E+09 0.132658E+09 0.290282E+09 45017248.16
July 0.235030E+09 0.103033E+09 0.131997E+09 0.307573E+09 34464767.20
August 0.213265E+09 89836790.88 0.123428E+09 0.271589E+09 47581323.93
September 0.173211E+09 77585081.32 95625485.80 0.199316E+09 71842358.79
October 0.122203E+09 51665085.16 70538006.76 0.111056E+09 0.111228E+09
November 66727498.56 22145136.59 44582361.97 44189955.10 0.131987E+09
December 55045865.55 11855367.35 43190498.20 16344144.52 0.202647E+09
           
Annual Sum or Average 0.182726E+10 0.758023E+09 0.106923E+10 0.188700E+10 0.130674E+10
Minimum of Months 55045865.55 11855367.35 43190498.20 16344144.52 34464767.20
Maximum of Months 0.236319E+09 0.103662E+09 0.132658E+09 0.307573E+09 0.204478E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71371626.81 23805065.88 47566560.93 30920346.08 0.204479E+09
February 93995778.96 29143298.84 64852480.12 48410793.77 0.173117E+09
March 0.149761E+09 63482962.69 86277644.46 0.125857E+09 0.131496E+09
April 0.191503E+09 85484659.04 0.106018E+09 0.193261E+09 89431084.34
May 0.218800E+09 96324394.74 0.122476E+09 0.248174E+09 63451641.45
June 0.236314E+09 0.103662E+09 0.132652E+09 0.290276E+09 45016317.07
July 0.235024E+09 0.103033E+09 0.131991E+09 0.307566E+09 34463807.88
August 0.213259E+09 89836790.88 0.123422E+09 0.271582E+09 47580334.70
September 0.173206E+09 77585081.32 95620813.27 0.199311E+09 71841369.97
October 0.122199E+09 51665085.16 70533603.47 0.111051E+09 0.111228E+09
November 66724296.15 22145136.59 44579159.56 44187782.75 0.131988E+09
December 55042566.30 11855367.35 43187198.94 16342991.34 0.202649E+09
           
Annual Sum or Average 0.182720E+10 0.758023E+09 0.106918E+10 0.188694E+10 0.130674E+10
Minimum of Months 55042566.30 11855367.35 43187198.94 16342991.34 34463807.88
Maximum of Months 0.236314E+09 0.103662E+09 0.132652E+09 0.307566E+09 0.204479E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71371626.81 23805065.88 47566560.93 30920346.08 0.204479E+09
February 93995778.96 29143298.84 64852480.12 48410793.77 0.173117E+09
March 0.149761E+09 63482962.69 86277644.46 0.125857E+09 0.131496E+09
April 0.191503E+09 85484659.04 0.106018E+09 0.193261E+09 89431084.34
May 0.218800E+09 96324394.74 0.122476E+09 0.248174E+09 63451641.45
June 0.236314E+09 0.103662E+09 0.132652E+09 0.290276E+09 45016317.07
July 0.235024E+09 0.103033E+09 0.131991E+09 0.307566E+09 34463807.88
August 0.213259E+09 89836790.88 0.123422E+09 0.271582E+09 47580334.70
September 0.173206E+09 77585081.32 95620813.27 0.199311E+09 71841369.97
October 0.122199E+09 51665085.16 70533603.47 0.111051E+09 0.111228E+09
November 66724296.15 22145136.59 44579159.56 44187782.75 0.131988E+09
December 55042566.30 11855367.35 43187198.94 16342991.34 0.202649E+09
           
Annual Sum or Average 0.182720E+10 0.758023E+09 0.106918E+10 0.188694E+10 0.130674E+10
Minimum of Months 55042566.30 11855367.35 43187198.94 16342991.34 34463807.88
Maximum of Months 0.236314E+09 0.103662E+09 0.132652E+09 0.307566E+09 0.204479E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 71598375.43 23883334.90 47715040.53 31066782.19 0.204212E+09
February 94110061.12 29176312.43 64933748.69 48548754.34 0.173056E+09
March 0.149776E+09 63490209.54 86286200.59 0.125874E+09 0.131484E+09
April 0.191509E+09 85484659.04 0.106024E+09 0.193267E+09 89431574.52
May 0.218806E+09 96324394.74 0.122481E+09 0.248180E+09 63452357.51
June 0.236319E+09 0.103662E+09 0.132658E+09 0.290282E+09 45017248.21
July 0.235030E+09 0.103033E+09 0.131997E+09 0.307573E+09 34464767.25
August 0.213265E+09 89836790.88 0.123428E+09 0.271589E+09 47581323.98
September 0.173216E+09 77586710.40 95628828.14 0.199325E+09 71842358.85
October 0.122263E+09 51695017.84 70567608.41 0.111174E+09 0.111228E+09
November 66872278.53 22198094.02 44674184.51 44439620.61 0.131969E+09
December 55278507.67 11917915.37 43360592.30 16511152.08 0.202406E+09
           
Annual Sum or Average 0.182804E+10 0.758288E+09 0.106975E+10 0.188783E+10 0.130614E+10
Minimum of Months 55278507.67 11917915.37 43360592.30 16511152.08 34464767.25
Maximum of Months 0.236319E+09 0.103662E+09 0.132658E+09 0.307573E+09 0.204212E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38270537.47 0.00 38270537.47 766348.23 0.224584E+09
February 52621067.04 0.00 52621067.04 4362419.94 0.188534E+09
March 71587758.25 0.00 71587758.25 28615700.55 0.142644E+09
April 88480020.63 360247.13 88119773.51 59562289.23 92290405.33
May 0.106927E+09 4414100.18 0.102513E+09 98597163.56 60634926.09
June 0.124105E+09 10211126.92 0.113894E+09 0.140159E+09 42804367.06
July 0.119233E+09 7522972.15 0.111710E+09 0.152121E+09 32785467.67
August 0.103114E+09 1562096.55 0.101552E+09 0.123293E+09 45916527.21
September 75975841.01 15960.03 75959880.98 70357562.97 72424193.02
October 57980744.34 0.00 57980744.34 29755187.09 0.114295E+09
November 37397501.86 0.00 37397501.86 9684296.21 0.136434E+09
December 35613910.99 0.00 35613910.99 948272.56 0.216014E+09
           
Annual Sum or Average 0.911306E+09 24086502.96 0.887220E+09 0.718222E+09 0.136936E+10
Minimum of Months 35613910.99 0.00 35613910.99 766348.23 32785467.67
Maximum of Months 0.124105E+09 10211126.92 0.113894E+09 0.152121E+09 0.224584E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38267255.29 0.00 38267255.29 765920.45 0.224586E+09
February 52616499.47 0.00 52616499.47 4360412.63 0.188537E+09
March 71582658.06 0.00 71582658.06 28611029.76 0.142644E+09
April 88416372.30 347120.22 88069252.08 59555905.77 92394890.57
May 0.106645E+09 4299967.42 0.102345E+09 98145770.16 60730217.70
June 0.123781E+09 10070109.70 0.113711E+09 0.139534E+09 42805224.01
July 0.118918E+09 7393519.20 0.111524E+09 0.151515E+09 32784504.77
August 0.102895E+09 1499727.18 0.101396E+09 0.122907E+09 45930966.65
September 75974231.22 16091.62 75958139.60 70352543.81 72418697.88
October 57976340.82 0.00 57976340.82 29751081.15 0.114295E+09
November 37394299.29 0.00 37394299.29 9682344.80 0.136434E+09
December 35610611.56 0.00 35610611.56 947612.71 0.216016E+09
           
Annual Sum or Average 0.910078E+09 23626535.34 0.886451E+09 0.716129E+09 0.136958E+10
Minimum of Months 35610611.56 0.00 35610611.56 765920.45 32784504.77
Maximum of Months 0.123781E+09 10070109.70 0.113711E+09 0.151515E+09 0.224586E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38267255.29 0.00 38267255.29 765920.45 0.224586E+09
February 52616499.47 0.00 52616499.47 4360412.63 0.188537E+09
March 71582658.06 0.00 71582658.06 28611029.76 0.142644E+09
April 88393771.74 342857.08 88050914.65 59555904.95 92435252.62
May 0.106645E+09 4299967.42 0.102345E+09 98145770.16 60730217.70
June 0.123781E+09 10070109.70 0.113711E+09 0.139534E+09 42805224.01
July 0.118918E+09 7393507.52 0.111524E+09 0.151515E+09 32784504.77
August 0.102893E+09 1499597.84 0.101394E+09 0.122907E+09 45933605.52
September 75974729.12 16058.30 75958670.82 70352649.56 72418214.34
October 57976340.82 0.00 57976340.82 29751081.15 0.114295E+09
November 37394299.29 0.00 37394299.29 9682344.80 0.136434E+09
December 35610611.56 0.00 35610611.56 947612.71 0.216016E+09
           
Annual Sum or Average 0.910054E+09 23622097.86 0.886431E+09 0.716128E+09 0.136962E+10
Minimum of Months 35610611.56 0.00 35610611.56 765920.45 32784504.77
Maximum of Months 0.123781E+09 10070109.70 0.113711E+09 0.151515E+09 0.224586E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38267255.29 0.00 38267255.29 765920.45 0.224586E+09
February 52616499.47 0.00 52616499.47 4360412.63 0.188537E+09
March 71582658.06 0.00 71582658.06 28611029.76 0.142644E+09
April 88393771.74 342857.08 88050914.65 59555904.95 92435252.62
May 0.106645E+09 4299967.42 0.102345E+09 98145770.16 60730217.70
June 0.123781E+09 10070109.70 0.113711E+09 0.139534E+09 42805224.01
July 0.118918E+09 7393507.52 0.111524E+09 0.151515E+09 32784504.77
August 0.102892E+09 1499559.95 0.101392E+09 0.122907E+09 45936431.55
September 75974868.31 16009.55 75958858.76 70352761.11 72418149.12
October 57976340.82 0.00 57976340.82 29751081.15 0.114295E+09
November 37394299.29 0.00 37394299.29 9682344.80 0.136434E+09
December 35610611.56 0.00 35610611.56 947612.71 0.216016E+09
           
Annual Sum or Average 0.910052E+09 23622011.22 0.886430E+09 0.716129E+09 0.136962E+10
Minimum of Months 35610611.56 0.00 35610611.56 765920.45 32784504.77
Maximum of Months 0.123781E+09 10070109.70 0.113711E+09 0.151515E+09 0.224586E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38267255.29 0.00 38267255.29 765920.45 0.224586E+09
February 52616499.47 0.00 52616499.47 4360412.63 0.188537E+09
March 71582658.06 0.00 71582658.06 28611029.76 0.142644E+09
April 88416870.35 346329.08 88070541.27 59564786.43 92404559.59
May 0.106645E+09 4299967.42 0.102345E+09 98145770.16 60730217.70
June 0.123781E+09 10070109.70 0.113711E+09 0.139534E+09 42805224.01
July 0.118918E+09 7393527.37 0.111524E+09 0.151515E+09 32784504.77
August 0.102891E+09 1499698.55 0.101391E+09 0.122909E+09 45939130.01
September 75975233.70 15984.45 75959249.25 70352878.17 72417956.25
October 57976340.82 0.00 57976340.82 29751081.15 0.114295E+09
November 37394299.29 0.00 37394299.29 9682344.80 0.136434E+09
December 35610611.56 0.00 35610611.56 947612.71 0.216016E+09
           
Annual Sum or Average 0.910074E+09 23625616.56 0.886449E+09 0.716139E+09 0.136959E+10
Minimum of Months 35610611.56 0.00 35610611.56 765920.45 32784504.77
Maximum of Months 0.123781E+09 10070109.70 0.113711E+09 0.151515E+09 0.224586E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 38270537.29 0.00 38270537.29 766348.21 0.224584E+09
February 52621066.80 0.00 52621066.80 4362419.84 0.188534E+09
March 71587757.98 0.00 71587757.98 28615700.31 0.142644E+09
April 88483050.21 357309.09 88125741.12 59598185.11 92327243.94
May 0.106941E+09 4422679.26 0.102518E+09 98708827.45 60722640.96
June 0.124164E+09 10236100.89 0.113928E+09 0.140274E+09 42806139.11
July 0.119255E+09 7527845.45 0.111727E+09 0.152158E+09 32785467.62
August 0.103102E+09 1562795.46 0.101539E+09 0.123294E+09 45939261.99
September 75980018.26 15985.84 75964032.42 70357987.31 72418689.43
October 57980744.11 0.00 57980744.11 29755186.88 0.114295E+09
November 37397501.70 0.00 37397501.70 9684296.11 0.136434E+09
December 35613910.82 0.00 35613910.82 948272.52 0.216014E+09
           
Annual Sum or Average 0.911396E+09 24122715.99 0.887274E+09 0.718523E+09 0.136950E+10
Minimum of Months 35613910.82 0.00 35613910.82 766348.21 32785467.62
Maximum of Months 0.124164E+09 10236100.89 0.113928E+09 0.152158E+09 0.224584E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 61039880.77 14845296.60 46194584.17 19228202.43 0.211832E+09
February 89081619.05 23683914.48 65397704.57 42449318.36 0.179030E+09
March 0.155502E+09 67510243.23 87991544.61 0.133929E+09 0.136098E+09
April 0.182009E+09 74951622.71 0.107058E+09 0.183468E+09 94054893.70
May 0.221315E+09 99606218.85 0.121708E+09 0.253200E+09 68085198.28
June 0.258478E+09 0.121160E+09 0.137318E+09 0.321432E+09 50199383.67
July 0.238080E+09 0.103844E+09 0.134236E+09 0.312911E+09 38791914.39
August 0.216325E+09 92253735.19 0.124071E+09 0.278604E+09 51581857.51
September 0.166136E+09 72485263.82 93651143.37 0.192291E+09 75820833.41
October 0.111433E+09 40079848.81 71353160.21 99304881.43 0.114856E+09
November 63848411.74 19029488.31 44818923.43 41038905.94 0.134612E+09
December 57071240.03 12982305.47 44088934.56 18982000.43 0.206104E+09
           
Annual Sum or Average 0.182032E+10 0.742432E+09 0.107789E+10 0.189684E+10 0.136107E+10
Minimum of Months 57071240.03 12982305.47 44088934.56 18982000.43 38791914.39
Maximum of Months 0.258478E+09 0.121160E+09 0.137318E+09 0.321432E+09 0.211832E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60844337.41 14779412.82 46064924.59 19121305.97 0.212080E+09
February 88977942.30 23655586.77 65322355.53 42324371.28 0.179083E+09
March 0.155486E+09 67503855.29 87982521.08 0.133905E+09 0.136101E+09
April 0.182004E+09 74951622.71 0.107052E+09 0.183461E+09 94054535.58
May 0.221309E+09 99606218.85 0.121703E+09 0.253194E+09 68084597.17
June 0.258472E+09 0.121160E+09 0.137313E+09 0.321426E+09 50198599.93
July 0.238075E+09 0.103844E+09 0.134230E+09 0.312904E+09 38791036.59
August 0.216319E+09 92253735.19 0.124065E+09 0.278597E+09 51580945.02
September 0.166128E+09 72483763.74 93644091.87 0.192279E+09 75819978.32
October 0.111367E+09 40050436.28 71316729.37 99181331.76 0.114856E+09
November 63712241.04 18984835.91 44727405.13 40813455.42 0.134629E+09
December 56853036.67 12922214.27 43930822.39 18822448.63 0.206324E+09
           
Annual Sum or Average 0.181955E+10 0.742195E+09 0.107735E+10 0.189603E+10 0.136160E+10
Minimum of Months 56853036.67 12922214.27 43930822.39 18822448.63 38791036.59
Maximum of Months 0.258472E+09 0.121160E+09 0.137313E+09 0.321426E+09 0.212080E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60844337.41 14779412.82 46064924.59 19121305.97 0.212080E+09
February 88977942.30 23655586.77 65322355.53 42324371.28 0.179083E+09
March 0.155486E+09 67503855.29 87982521.08 0.133905E+09 0.136101E+09
April 0.182004E+09 74951622.71 0.107052E+09 0.183461E+09 94054535.58
May 0.221309E+09 99606218.85 0.121703E+09 0.253194E+09 68084597.17
June 0.258472E+09 0.121160E+09 0.137313E+09 0.321426E+09 50198599.93
July 0.238075E+09 0.103844E+09 0.134230E+09 0.312904E+09 38791036.59
August 0.216319E+09 92253735.19 0.124065E+09 0.278597E+09 51580945.02
September 0.166128E+09 72483763.74 93644091.87 0.192279E+09 75819978.32
October 0.111367E+09 40050436.28 71316729.37 99181331.76 0.114856E+09
November 63712241.04 18984835.91 44727405.13 40813455.42 0.134629E+09
December 56853036.67 12922214.27 43930822.39 18822448.63 0.206324E+09
           
Annual Sum or Average 0.181955E+10 0.742195E+09 0.107735E+10 0.189603E+10 0.136160E+10
Minimum of Months 56853036.67 12922214.27 43930822.39 18822448.63 38791036.59
Maximum of Months 0.258472E+09 0.121160E+09 0.137313E+09 0.321426E+09 0.212080E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 60847619.58 14779412.82 46068206.76 19122297.64 0.212078E+09
February 88982509.87 23655586.77 65326923.10 42327613.18 0.179081E+09
March 0.155491E+09 67503855.29 87987621.27 0.133910E+09 0.136101E+09
April 0.182009E+09 74951622.71 0.107058E+09 0.183468E+09 94054893.72
May 0.221315E+09 99606218.85 0.121708E+09 0.253200E+09 68085198.31
June 0.258478E+09 0.121160E+09 0.137318E+09 0.321432E+09 50199383.71
July 0.238080E+09 0.103844E+09 0.134236E+09 0.312911E+09 38791914.44
August 0.216325E+09 92253735.19 0.124071E+09 0.278604E+09 51581857.56
September 0.166133E+09 72483763.74 93648764.64 0.192284E+09 75820833.46
October 0.111372E+09 40050436.28 71321132.89 99185671.57 0.114857E+09
November 63715443.61 18984835.91 44730607.70 40815620.95 0.134629E+09
December 56856336.10 12922214.27 43934121.82 18823666.51 0.206322E+09
           
Annual Sum or Average 0.181960E+10 0.742195E+09 0.107741E+10 0.189608E+10 0.136160E+10
Minimum of Months 56856336.10 12922214.27 43934121.82 18823666.51 38791914.44
Maximum of Months 0.258478E+09 0.121160E+09 0.137318E+09 0.321432E+09 0.212078E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 417.61 532.65 482.62 286.08 196.55 0.00 0.00
February 470.91 518.82 548.06 269.81 278.25 0.00 0.00
March 705.51 375.87 671.38 383.76 287.62 0.00 0.00
April 522.89 283.73 492.71 182.91 309.80 0.00 0.00
May 406.61 187.01 376.98 71.47 305.51 0.00 0.00
June 412.26 134.99 354.81 29.82 324.99 0.00 0.00
July 484.02 100.18 367.37 47.71 319.66 0.00 0.00
August 592.07 139.94 448.19 118.33 329.86 0.00 0.00
September 750.28 223.35 599.46 289.50 309.96 0.00 0.00
October 668.47 320.35 603.20 350.28 252.93 0.00 0.00
November 428.77 381.74 431.65 247.92 183.72 0.00 0.00
December 330.76 528.89 402.31 212.09 190.22 0.00 0.00
               
Annual Sum or Average 516.08 309.52 481.15 207.18 273.97 0.00 0.00
Minimum of Months 330.76 100.18 354.81 29.82 183.72 0.00 0.00
Maximum of Months 750.28 532.65 671.38 383.76 329.86 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 46.22 305.27 106.67 35.58 71.09 0.00 0.00
February 80.10 286.21 155.47 48.20 107.27 0.00 0.00
March 187.97 196.37 223.66 94.81 128.85 0.00 0.00
April 298.25 138.01 295.53 131.92 163.61 0.00 0.00
May 370.64 94.76 326.77 143.85 182.91 0.00 0.00
June 447.96 69.47 364.69 159.97 204.71 0.00 0.00
July 459.33 51.47 351.00 153.87 197.12 0.00 0.00
August 405.59 71.06 318.49 134.16 184.33 0.00 0.00
September 307.59 110.87 267.30 119.73 147.57 0.00 0.00
October 165.89 166.11 182.52 77.17 105.35 0.00 0.00
November 68.29 203.68 103.03 34.20 68.83 0.00 0.00
December 24.46 302.54 82.29 17.73 64.56 0.00 0.00
               
Annual Sum or Average 239.37 165.73 231.79 96.16 135.63 0.00 0.00
Minimum of Months 24.46 51.47 82.29 17.73 64.56 0.00 0.00
Maximum of Months 459.33 305.27 364.69 159.97 204.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.72 503.10 85.73 0.00 85.73 0.00 0.00
February 10.82 467.60 130.50 0.00 130.50 0.00 0.00
March 64.10 319.54 160.36 0.00 160.36 0.00 0.00
April 137.88 213.84 204.70 0.81 203.89 0.00 0.00
May 220.23 135.99 239.12 9.72 229.40 0.00 0.00
June 323.52 99.09 286.80 23.43 263.37 0.00 0.00
July 339.88 73.44 266.64 16.66 249.98 0.00 0.00
August 275.61 102.89 230.66 3.41 227.25 0.00 0.00
September 162.86 167.64 175.87 0.04 175.83 0.00 0.00
October 66.65 256.04 129.88 0.00 129.88 0.00 0.00
November 22.41 315.82 86.56 0.00 86.56 0.00 0.00
December 2.12 483.90 79.78 0.00 79.78 0.00 0.00
               
Annual Sum or Average 136.39 260.57 173.23 4.53 168.70 0.00 0.00
Minimum of Months 1.72 73.44 79.78 0.00 79.78 0.00 0.00
Maximum of Months 339.88 503.10 286.80 23.43 263.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 28.59 316.63 90.94 22.10 68.84 0.00 0.00
February 70.03 296.08 147.16 39.12 108.04 0.00 0.00
March 199.99 203.26 232.22 100.81 131.40 0.00 0.00
April 283.12 145.15 280.87 115.67 165.21 0.00 0.00
May 378.13 101.68 330.51 148.75 181.76 0.00 0.00
June 496.03 77.47 398.88 186.97 211.91 0.00 0.00
July 467.31 57.93 355.55 155.08 200.47 0.00 0.00
August 416.07 77.03 323.06 137.77 185.29 0.00 0.00
September 296.73 117.01 256.38 111.86 144.52 0.00 0.00
October 148.17 171.53 166.35 59.82 106.52 0.00 0.00
November 63.07 207.75 98.38 29.31 69.06 0.00 0.00
December 28.17 308.04 84.99 19.32 65.67 0.00 0.00
               
Annual Sum or Average 240.52 172.69 230.82 94.15 136.67 0.00 0.00
Minimum of Months 28.17 57.93 84.99 19.32 65.67 0.00 0.00
Maximum of Months 496.03 316.63 398.88 186.97 211.91 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.111854E+10 0.142665E+10 0.129266E+10 0.766224E+09 0.526435E+09 0.00 0.00
February 0.113922E+10 0.125512E+10 0.132587E+10 0.652725E+09 0.673140E+09 0.00 0.00
March 0.188963E+10 0.100673E+10 0.179822E+10 0.102785E+10 0.770371E+09 0.00 0.00
April 0.135533E+10 0.735432E+09 0.127710E+10 0.474102E+09 0.802993E+09 0.00 0.00
May 0.108907E+10 0.500899E+09 0.100971E+10 0.191426E+09 0.818287E+09 0.00 0.00
June 0.106858E+10 0.349899E+09 0.919670E+09 77291647.86 0.842378E+09 0.00 0.00
July 0.129640E+10 0.268312E+09 0.983973E+09 0.127784E+09 0.856189E+09 0.00 0.00
August 0.158581E+10 0.374827E+09 0.120043E+10 0.316928E+09 0.883502E+09 0.00 0.00
September 0.194472E+10 0.578925E+09 0.155381E+10 0.750380E+09 0.803428E+09 0.00 0.00
October 0.179044E+10 0.858031E+09 0.161562E+10 0.938180E+09 0.677436E+09 0.00 0.00
November 0.111138E+10 0.989476E+09 0.111883E+10 0.642620E+09 0.476209E+09 0.00 0.00
December 0.885909E+09 0.141658E+10 0.107754E+10 0.568070E+09 0.509472E+09 0.00 0.00
               
Annual Sum or Average 0.162750E+11 0.976088E+10 0.151734E+11 0.653358E+10 0.863984E+10 0.00 0.00
Minimum of Months 0.885909E+09 0.268312E+09 0.919670E+09 77291647.86 0.476209E+09 0.00 0.00
Maximum of Months 0.194472E+10 0.142665E+10 0.179822E+10 0.102785E+10 0.883502E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.123808E+09 0.817627E+09 0.285717E+09 95298532.54 0.190418E+09 0.00 0.00
February 0.193778E+09 0.692399E+09 0.376102E+09 0.116606E+09 0.259496E+09 0.00 0.00
March 0.503448E+09 0.525968E+09 0.599063E+09 0.253939E+09 0.345124E+09 0.00 0.00
April 0.773056E+09 0.357725E+09 0.766022E+09 0.341939E+09 0.424084E+09 0.00 0.00
May 0.992710E+09 0.253808E+09 0.875212E+09 0.385298E+09 0.489914E+09 0.00 0.00
June 0.116112E+10 0.180067E+09 0.945266E+09 0.414647E+09 0.530620E+09 0.00 0.00
July 0.123028E+10 0.137857E+09 0.940109E+09 0.412133E+09 0.527976E+09 0.00 0.00
August 0.108634E+10 0.190323E+09 0.853047E+09 0.359347E+09 0.493700E+09 0.00 0.00
September 0.797264E+09 0.287367E+09 0.692838E+09 0.310342E+09 0.382496E+09 0.00 0.00
October 0.444332E+09 0.444912E+09 0.488863E+09 0.206690E+09 0.282173E+09 0.00 0.00
November 0.177005E+09 0.527931E+09 0.267048E+09 88633503.78 0.178415E+09 0.00 0.00
December 65514871.52 0.810324E+09 0.220410E+09 47484017.43 0.172925E+09 0.00 0.00
               
Annual Sum or Average 0.754865E+10 0.522631E+10 0.730970E+10 0.303236E+10 0.427734E+10 0.00 0.00
Minimum of Months 65514871.52 0.137857E+09 0.220410E+09 47484017.43 0.172925E+09 0.00 0.00
Maximum of Months 0.123028E+10 0.817627E+09 0.945266E+09 0.414647E+09 0.530620E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 4596378.23 0.134751E+10 0.229610E+09 0.00 0.229610E+09 0.00 0.00
February 26166490.29 0.113122E+10 0.315708E+09 0.00 0.315708E+09 0.00 0.00
March 0.171676E+09 0.855862E+09 0.429506E+09 0.00 0.429506E+09 0.00 0.00
April 0.357388E+09 0.554283E+09 0.530584E+09 2096719.67 0.528487E+09 0.00 0.00
May 0.589859E+09 0.364249E+09 0.640448E+09 26036649.14 0.614412E+09 0.00 0.00
June 0.838568E+09 0.256831E+09 0.743393E+09 60727666.60 0.682665E+09 0.00 0.00
July 0.910339E+09 0.196709E+09 0.714160E+09 44624879.21 0.669535E+09 0.00 0.00
August 0.738202E+09 0.275580E+09 0.617787E+09 9123475.52 0.608663E+09 0.00 0.00
September 0.422126E+09 0.434516E+09 0.455855E+09 96089.79 0.455759E+09 0.00 0.00
October 0.178515E+09 0.685770E+09 0.347867E+09 0.00 0.347867E+09 0.00 0.00
November 58097967.34 0.818606E+09 0.224372E+09 0.00 0.224372E+09 0.00 0.00
December 5686995.92 0.129609E+10 0.213670E+09 0.00 0.213670E+09 0.00 0.00
               
Annual Sum or Average 0.430122E+10 0.821723E+10 0.546296E+10 0.142705E+09 0.532025E+10 0.00 0.00
Minimum of Months 4596378.23 0.196709E+09 0.213670E+09 0.00 0.213670E+09 0.00 0.00
Maximum of Months 0.910339E+09 0.134751E+10 0.743393E+09 60727666.60 0.682665E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 76575237.17 0.848053E+09 0.243576E+09 59183535.06 0.184393E+09 0.00 0.00
February 0.169421E+09 0.716272E+09 0.356020E+09 94650674.78 0.261369E+09 0.00 0.00
March 0.535646E+09 0.544399E+09 0.621966E+09 0.270022E+09 0.351944E+09 0.00 0.00
April 0.733857E+09 0.376219E+09 0.728026E+09 0.299806E+09 0.428220E+09 0.00 0.00
May 0.101279E+10 0.272340E+09 0.885247E+09 0.398425E+09 0.486822E+09 0.00 0.00
June 0.128572E+10 0.200796E+09 0.103390E+10 0.484638E+09 0.549262E+09 0.00 0.00
July 0.125163E+10 0.155166E+09 0.952310E+09 0.415377E+09 0.536933E+09 0.00 0.00
August 0.111440E+10 0.206326E+09 0.865286E+09 0.369015E+09 0.496271E+09 0.00 0.00
September 0.769132E+09 0.303282E+09 0.664525E+09 0.289937E+09 0.374588E+09 0.00 0.00
October 0.396853E+09 0.459426E+09 0.445539E+09 0.160231E+09 0.285308E+09 0.00 0.00
November 0.163481E+09 0.538499E+09 0.254988E+09 75983996.04 0.179004E+09 0.00 0.00
December 75439760.03 0.825062E+09 0.227634E+09 51748948.29 0.175885E+09 0.00 0.00
               
Annual Sum or Average 0.758495E+10 0.544584E+10 0.727902E+10 0.296902E+10 0.431000E+10 0.00 0.00
Minimum of Months 75439760.03 0.155166E+09 0.227634E+09 51748948.29 0.175885E+09 0.00 0.00
Maximum of Months 0.128572E+10 0.848053E+09 0.103390E+10 0.484638E+09 0.549262E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -3.4 -4.9 -8.7 5.96 -14.4 41.15 62.17 0.00
February -4.2 -5.4 -8.1 6.66 -15.1 65.72 71.39 0.00
March 2.67 0.66 -2.8 5.20 -8.9 69.76 141.76 0.00
April 7.47 4.95 1.92 5.29 -2.7 89.32 159.79 0.00
May 13.73 9.66 5.81 4.79 3.34 93.75 203.34 0.03
June 18.63 14.47 11.49 5.10 8.69 105.42 236.95 0.00
July 22.03 18.19 16.11 4.43 13.39 102.98 214.28 0.00
August 20.69 16.39 13.72 4.23 11.88 99.24 178.64 0.00
September 16.55 13.42 11.22 4.10 7.08 75.66 154.97 0.03
October 9.73 7.36 4.97 4.79 0.13 58.70 104.01 0.00
November 6.03 3.70 0.77 5.87 -3.2 41.19 58.47 0.00
December -2.2 -3.2 -5.3 6.59 -12.0 40.52 44.30 0.00
                 
Annual Sum or Average 9.05 6.33 3.49 5.24 -0.9 73.64 136.19 0.01
Minimum of Months -4.2 -5.4 -8.7 4.10 -15.1 40.52 44.30 0.00
Maximum of Months 22.03 18.19 16.11 6.66 13.39 105.42 236.95 0.03



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 11-JAN-15:00 10.14 8.90 13.40 7.15 65.50 1.00
February 12.80 22-FEB-17:00 6.18 -2.2 14.90 3.48 0.00 0.00
March 26.10 15-MAR-13:00 16.06 9.40 6.70 14.65 249.50 400.00
April 21.10 08-APR-12:00 13.43 7.80 8.20 11.46 330.00 283.50
May 26.10 10-MAY-13:00 17.84 13.30 5.20 13.35 258.50 457.00
June 30.60 12-JUN-13:00 20.23 15.00 8.20 17.93 252.00 572.00
July 31.70 21-JUL-13:00 21.73 17.20 5.20 22.47 330.00 231.00
August 30.60 10-AUG-13:00 20.24 15.00 5.70 19.70 220.50 635.00
September 27.20 16-SEP-13:09 19.53 15.68 8.80 17.30 207.00 564.67
October 22.20 11-OCT-12:00 14.14 8.30 6.20 6.95 121.00 665.00
November 19.40 05-NOV-13:00 13.85 10.00 12.40 14.84 133.00 3.50
December 15.00 01-DEC-10:00 12.41 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 11.70   6.18 -2.2 5.20 3.48 0.00 0.00
Maximum of Months 31.70   21.73 17.20 14.90 22.47 330.00 665.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -13.9 31-JAN-01:00 -14.5 -17.2 1.50 -25.9 0.00 0.00
February -16.7 07-FEB-06:00 -17.3 -20.6 6.20 -35.1 0.00 0.00
March -13.3 07-MAR-05:19 -13.9 -16.7 2.43 -32.2 0.00 0.00
April -4.4 17-APR-05:00 -5.4 -7.8 2.10 -20.5 35.00 151.50
May 1.70 01-MAY-04:00 0.96 0.00 0.00 -14.2 0.00 0.00
June 6.70 04-JUN-04:00 5.40 3.90 2.10 -7.3 20.00 104.00
July 11.70 03-JUL-03:00 11.07 10.60 2.10 -1.2 0.00 0.00
August 11.10 01-AUG-04:00 10.75 10.60 2.10 -0.8 0.00 0.00
September 6.10 05-SEP-05:00 5.59 5.00 2.10 -6.2 24.50 41.00
October -2.8 17-OCT-04:10 -3.2 -4.0 2.18 -19.4 0.00 0.00
November -3.9 24-NOV-05:00 -4.5 -5.6 2.10 -18.1 0.00 0.00
December -18.9 11-DEC-05:00 -19.4 -23.3 2.10 -35.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -18.9   -19.4 -23.3 0.00 -35.1 0.00 0.00
Maximum of Months 11.70   11.07 10.60 6.20 -0.8 35.00 151.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 10.21 11-JAN-17:00 11.10 9.40 10.30 6.55 0.00 0.00
February 6.89 01-FEB-03:00 7.20 6.70 3.60 2.22 0.00 0.00
March 17.83 14-MAR-12:00 25.00 13.90 6.20 14.10 197.00 562.50
April 13.78 08-APR-13:00 20.60 8.90 10.30 9.72 268.50 325.50
May 18.19 10-MAY-14:00 26.10 13.90 5.20 16.85 273.00 238.00
June 23.75 27-JUN-12:00 30.60 21.10 9.30 21.09 304.00 606.00
July 24.79 21-JUL-01:00 28.90 23.30 8.80 27.46 0.00 0.00
August 23.42 13-AUG-15:00 29.40 21.10 9.80 19.87 212.00 276.00
September 21.17 15-SEP-11:00 26.10 18.90 3.60 16.30 204.00 464.50
October 15.23 12-OCT-14:00 18.30 13.30 10.30 9.13 148.00 367.50
November 13.96 05-NOV-14:00 18.30 11.10 11.30 14.10 72.00 6.00
December 12.41 01-DEC-10:00 15.00 10.60 12.90 10.69 56.50 11.50
                 
Annual Sum or Average                
Minimum of Months 6.89   7.20 6.70 3.60 2.22 0.00 0.00
Maximum of Months 24.79   30.60 23.30 12.90 27.46 304.00 606.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 9.40 11-JAN-13:00 10.00 9.66 12.90 5.54 95.50 2.00
February 6.70 01-FEB-04:10 7.20 6.89 3.52 2.22 0.00 0.00
March 15.00 14-MAR-10:20 20.33 16.97 4.80 10.50 159.17 592.83
April 11.10 08-APR-21:00 13.90 12.23 12.90 9.72 0.00 0.00
May 15.60 17-MAY-12:00 16.70 15.97 6.70 13.54 184.00 0.00
June 21.70 27-JUN-14:00 25.60 22.78 8.20 16.85 255.50 530.00
July 23.30 20-JUL-20:00 25.60 24.03 4.60 24.16 0.00 0.00
August 21.70 14-AUG-03:20 23.70 22.19 5.00 21.90 0.00 0.00
September 20.00 15-SEP-18:00 21.70 20.51 0.00 19.52 0.00 0.00
October 14.40 01-OCT-07:19 14.60 14.50 3.77 10.56 67.50 30.17
November 11.70 05-NOV-15:00 12.80 12.14 7.20 8.74 28.00 4.50
December 11.10 01-DEC-12:00 13.90 12.22 10.30 6.35 158.00 84.50
                 
Annual Sum or Average                
Minimum of Months 6.70   7.20 6.89 0.00 2.22 0.00 0.00
Maximum of Months 23.30   25.60 24.03 12.90 24.16 255.50 592.83



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 7.32 12.49 0.00
February 18.00 13.00 16.00 6.57 19.26 0.00
March 18.00 13.00 16.00 7.29 28.63 0.00
April 18.00 13.00 16.00 9.34 37.44 0.00
May 18.00 13.00 16.00 12.19 46.60 0.00
June 18.00 13.00 16.00 15.07 54.01 0.00
July 18.00 13.00 16.00 17.20 50.29 0.00
August 18.00 13.00 16.00 18.01 43.20 0.00
September 18.00 13.00 16.00 17.27 32.93 0.00
October 18.00 13.00 16.00 15.18 21.28 0.00
November 18.00 13.00 16.00 12.32 12.54 0.00
December 18.00 13.00 16.00 9.45 10.96 0.00
             
Annual Sum or Average 18.00 13.00 16.00 12.30 30.86 0.00
Minimum of Months 18.00 13.00 16.00 6.57 10.96 0.00
Maximum of Months 18.00 13.00 16.00 18.01 54.01 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.652548E+09 -525273621.0 0.00 0.00 744.00 0.00 -127274266.4 59.00 0.00 0.00
February 0.596850E+09 -482172939.3 0.00 0.00 672.00 0.00 -114676699.2 58.99 0.00 0.00
March 0.698847E+09 -575507779.1 0.00 0.00 744.00 0.00 -123338922.2 58.99 0.00 0.00
April 0.597532E+09 -480854438.1 0.00 0.00 720.00 0.00 -116677340.5 58.99 0.00 0.00
May 0.614325E+09 -499536828.2 0.00 0.00 744.00 0.00 -114788214.8 58.99 0.00 0.00
June 0.574524E+09 -467343686.0 0.00 0.00 720.00 0.00 -107180353.1 59.00 0.00 0.00
July 0.512972E+09 -404172504.6 0.00 0.00 744.00 0.00 -108799732.3 58.99 0.00 0.00
August 0.565377E+09 -456354231.4 0.00 0.00 744.00 0.00 -109022515.3 58.99 0.00 0.00
September 0.511068E+09 -404351508.3 0.00 0.00 720.00 0.00 -106716278.4 58.99 0.00 0.00
October 0.560486E+09 -445681224.3 0.00 0.00 744.00 0.00 -114804511.0 58.99 0.00 0.00
November 0.591117E+09 -474372400.7 0.00 0.00 720.00 0.00 -116744241.5 58.99 0.00 0.00
December 0.605227E+09 -479140694.3 0.00 0.00 744.00 0.00 -126085818.8 58.99 0.00 0.00
                     
Annual Sum or Average 0.708087E+10 -0.569476E+10 0.00 0.00 8760.00 0.00 -0.138611E+10 58.99 0.00 0.00
Minimum of Months 0.511068E+09 -575507779.1 0.00 0.00 672.00 0.00 -127274266.4 58.99 0.00 0.00
Maximum of Months 0.698847E+09 -404172504.6 0.00 0.00 744.00 0.00 -106716278.4 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.77 0.73 01-JAN-11:09 701.00 22.61 81.67 176.67 1253.86 28.81 210.83 150.17
February 262.50 0.76 0.73 01-FEB-12:00 1261.32 24.53 112.33 204.50 632.23 26.17 244.00 184.67
March 339.33 0.76 0.73 01-MAR-07:49 2356.15 24.78 154.83 259.33 566.57 22.98 248.00 210.00
April 371.17 0.77 0.73 01-APR-07:00 555.90 17.82 0.00 253.17 421.37 22.10 261.00 189.17
May 332.17 0.77 0.73 01-MAY-08:09 496.90 17.92 0.00 243.67 374.86 22.30 257.33 167.00
June 430.67 0.78 0.73 01-JUN-07:40 444.09 17.55 0.00 269.67 329.39 21.88 290.33 181.67
July 439.00 0.78 0.73 01-JUL-07:49 465.24 17.62 0.00 274.67 344.78 21.94 290.33 198.00
August 406.00 0.77 0.73 01-AUG-07:30 556.24 18.21 0.00 279.17 415.21 22.53 295.17 220.17
September 289.17 0.76 0.73 01-SEP-07:00 793.50 19.15 5.83 246.83 582.75 23.28 254.00 199.00
October 314.33 0.76 0.73 01-OCT-08:39 1372.76 23.33 109.50 227.33 635.13 23.14 231.50 195.50
November 258.33 0.78 0.73 01-NOV-07:49 902.37 24.85 120.17 165.33 698.83 25.97 203.50 133.50
December 230.67 0.77 0.73 01-DEC-08:20 695.70 23.68 88.67 149.67 1087.65 30.12 217.83 128.50
                         
Annual Sum or Average 3928.50 0.77     854.46 20.52 673.00 2750.00 565.21 23.80 3003.83 2157.33
Minimum of Months 230.67 0.76 0.73   444.09 17.55 0.00 149.67 329.39 21.88 203.50 128.50
Maximum of Months 439.00 0.78 0.73   2356.15 24.85 154.83 279.17 1253.86 30.12 295.17 220.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.81 0.73 04-JAN-08:30 709.05 20.79 72.67 95.17 330.70 22.62 116.33 48.50
February 262.50 0.79 0.73 02-FEB-09:00 780.21 19.23 47.67 136.00 521.69 24.15 163.17 86.17
March 339.33 0.80 0.73 01-MAR-07:40 1024.78 18.61 51.67 160.33 374.51 21.19 154.67 104.00
April 371.17 0.79 0.73 01-APR-06:00 445.52 16.05 0.00 184.33 361.15 20.80 178.50 126.67
May 332.17 0.79 0.73 01-MAY-05:00 481.36 16.30 0.00 187.00 414.50 21.43 193.67 132.00
June 430.67 0.79 0.73 01-JUN-06:49 452.79 16.26 0.00 211.00 386.41 21.29 220.33 158.67
July 439.00 0.79 0.73 01-JUL-05:40 453.86 16.24 0.00 208.17 383.14 21.19 222.67 155.17
August 406.00 0.79 0.73 01-AUG-06:10 473.11 16.52 0.00 219.50 387.29 21.40 225.67 155.00
September 289.17 0.79 0.73 01-SEP-07:40 519.94 16.79 0.00 164.83 432.72 21.79 166.00 118.50
October 314.33 0.80 0.73 01-OCT-08:09 531.47 16.74 11.17 134.17 482.91 22.96 154.17 86.83
November 258.33 0.82 0.73 01-NOV-07:00 703.47 19.73 74.17 89.17 270.78 21.70 103.83 38.83
December 230.67 0.81 0.73 01-DEC-08:20 535.18 20.15 63.50 76.50 211.08 21.11 86.33 23.83
                         
Annual Sum or Average 3928.50 0.80     577.23 17.50 320.83 1866.17 383.75 21.71 1985.33 1234.17
Minimum of Months 230.67 0.79 0.73   445.52 16.05 0.00 76.50 211.08 20.80 86.33 23.83
Maximum of Months 439.00 0.82 0.73   1024.78 20.79 74.17 219.50 521.69 24.15 225.67 158.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.89 0.74 27-JAN-12:30 163.60 13.93 0.00 0.00 114.58 17.81 0.00 0.00
February 262.50 0.85 0.74 11-FEB-10:30 216.60 15.12 0.00 0.83 149.00 18.89 4.83 0.00
March 339.33 0.84 0.74 31-MAR-12:30 228.95 15.58 0.00 10.50 162.27 19.53 15.17 0.00
April 371.17 0.81 0.73 23-APR-12:20 268.20 16.23 0.00 46.00 186.83 20.06 90.83 0.00
May 332.17 0.78 0.73 02-MAY-09:20 323.91 17.34 0.00 109.83 230.66 21.35 164.33 1.50
June 430.67 0.77 0.73 01-JUN-07:00 357.92 17.61 0.00 227.33 274.52 22.86 279.17 20.17
July 439.00 0.78 0.73 01-JUL-08:30 342.35 17.40 0.00 194.50 234.91 21.27 234.17 1.17
August 406.00 0.78 0.73 01-AUG-07:00 319.43 17.02 0.00 111.33 213.53 20.89 172.50 0.00
September 289.17 0.81 0.73 02-SEP-10:00 259.07 16.33 0.00 21.83 186.87 20.32 69.33 0.00
October 314.33 0.86 0.74 05-OCT-11:30 200.58 14.79 0.00 0.00 141.44 18.68 1.67 0.00
November 258.33 0.89 0.74 05-NOV-11:30 157.90 13.44 0.00 0.00 110.31 17.18 0.00 0.00
December 230.67 0.89 0.74 09-DEC-12:39 164.66 13.88 0.00 0.00 113.49 17.65 0.00 0.00
                         
Annual Sum or Average 3928.50 0.82     263.28 15.98 0.00 722.17 185.97 20.00 1032.00 22.83
Minimum of Months 230.67 0.77 0.73   157.90 13.44 0.00 0.00 110.31 17.18 0.00 0.00
Maximum of Months 439.00 0.89 0.74   357.92 17.61 0.00 227.33 274.52 22.86 279.17 20.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 255.17 0.81 0.73 04-JAN-13:09 478.43 20.06 65.00 86.67 245.24 22.03 110.83 32.67
February 262.50 0.79 0.73 01-FEB-13:30 681.09 19.11 47.17 136.50 477.42 24.15 164.00 83.00
March 339.33 0.79 0.73 01-MAR-13:09 1011.95 18.78 51.67 165.50 731.60 23.06 171.67 110.67
April 371.17 0.80 0.73 01-APR-11:30 440.16 16.28 0.00 176.50 350.49 20.87 177.83 119.67
May 332.17 0.78 0.73 01-MAY-11:30 481.07 16.50 0.00 189.00 416.40 21.50 199.00 131.83
June 430.67 0.79 0.73 01-JUN-13:20 479.29 16.50 0.00 223.50 456.72 21.46 233.67 177.17
July 439.00 0.79 0.73 01-JUL-11:39 463.76 16.52 0.00 219.00 389.19 21.39 231.17 166.33
August 406.00 0.79 0.73 01-AUG-10:30 477.10 16.74 0.00 204.50 388.12 21.44 219.00 149.67
September 289.17 0.79 0.73 01-SEP-10:00 521.15 17.06 3.67 166.50 413.59 21.84 176.83 116.17
October 314.33 0.80 0.73 01-OCT-12:09 796.38 19.06 56.33 135.50 426.48 22.87 154.83 85.00
November 258.33 0.82 0.73 01-NOV-11:39 666.43 19.58 70.83 83.67 240.68 21.23 100.17 33.33
December 230.67 0.81 0.73 01-DEC-13:30 410.31 18.75 39.67 78.17 227.55 21.54 96.83 29.17
                         
Annual Sum or Average 3928.50 0.80     569.93 17.69 334.33 1865.00 406.77 21.88 2035.83 1234.67
Minimum of Months 230.67 0.78 0.73   410.31 16.28 0.00 78.17 227.55 20.87 96.83 29.17
Maximum of Months 439.00 0.82 0.73   1011.95 20.06 70.83 223.50 731.60 24.15 233.67 177.17



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.153009E+10 5451.77 17-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.107080E+10 5420.47 01-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.583616E+09 6263.77 14-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.134292E+09 5641.37 04-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 3188260.04 4546.53 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 2485519.03 786.67 30-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.104207E+09 7532.17 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.987643E+09 5195.34 14-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.441632E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153009E+10 7532.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.252334E+10 5651.53 17-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.200701E+10 5619.09 01-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.138687E+10 6493.28 14-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.795740E+09 6276.26 20-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.151725E+09 5669.27 02-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 1416604.18 850.64 14-JUN-06:30 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 96787605.01 3628.77 30-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 0.705829E+09 6729.95 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.203573E+10 6176.98 01-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.970445E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.252334E+10 6729.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.172681E+10 3926.43 17-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.133334E+10 3903.89 01-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.912749E+09 4511.24 14-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.329374E+09 4360.46 20-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 27880697.38 3938.75 02-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 30377863.65 3305.01 18-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.330034E+09 5424.75 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.127098E+10 4291.48 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.596154E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.172681E+10 5424.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.273911E+10 4906.72 17-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.225476E+10 4878.55 01-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.189851E+10 5799.79 15-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.886244E+09 5449.11 20-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.102310E+09 5093.03 09-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.105956E+09 5171.66 31-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.742593E+09 6779.13 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.204638E+10 5362.92 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.107759E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.273911E+10 6779.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.187468E+10 4503.27 17-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.145837E+10 4477.42 01-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.977932E+09 5174.00 14-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.390034E+09 4996.10 07-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 32122991.75 4517.41 02-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 34933145.54 3790.56 18-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.335820E+09 6221.73 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.134116E+10 4921.96 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.644505E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.187468E+10 6221.73   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.252215E+09 4291.75 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.403033E+09 4291.75 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 62414631.43 4291.75 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 5114594.68 3993.30 17-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 1387.39 20.81 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1085385.09 3635.45 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.237466E+09 4291.75 11-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.961330E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.403033E+09 4291.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.106177E+10 6556.65 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.125154E+10 6556.65 05-FEB-21:33 0.00 0.00 0.00 0.00 0.00
March 0.311160E+09 6556.65 07-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 69391834.40 5310.30 17-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 1127433.00 2856.28 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 5161977.03 3742.01 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 22497258.27 4928.78 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.838413E+09 6556.65 11-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.356106E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.125154E+10 6556.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.389862E+09 4027.65 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.582393E+09 4027.65 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.126421E+09 4027.65 01-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 22095985.23 4027.65 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 795814.62 2610.70 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1288149.55 3253.32 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 6894538.85 4027.65 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.371308E+09 4027.65 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.150106E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.582393E+09 4027.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.108310E+10 6510.19 04-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.128394E+10 6510.19 05-FEB-21:33 0.00 0.00 0.00 0.00 0.00
March 0.429879E+09 6510.19 07-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 63791972.51 4468.79 17-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 1474292.01 2380.38 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 2373755.18 3285.66 17-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 17600877.67 4153.27 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.885478E+09 6510.19 10-DEC-20:53 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.376764E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128394E+10 6510.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.327809E+09 4046.60 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.532657E+09 4046.60 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.110014E+09 4046.60 01-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 16653673.84 4046.60 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 631288.50 2889.75 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1315980.66 3742.67 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 4584494.85 4046.60 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.315896E+09 4046.60 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.130956E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.532657E+09 4046.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 56494357.96 42291866.26 1621.07 16-MAR-15:00 1140.08 0.00
April 0.00 0.00 20111778.65 18682179.81 585.72 21-APR-14:55 553.91 0.00
May 0.00 0.00 0.686516E+09 0.562687E+09 2745.55 24-MAY-05:05 2433.05 0.00
June 0.00 0.00 0.254655E+10 0.197430E+10 6248.38 28-JUN-05:02 3705.60 0.00
July 0.00 0.00 0.344557E+10 0.260528E+10 6223.70 31-JUL-05:02 4007.54 0.00
August 0.00 0.00 0.359635E+10 0.283586E+10 6195.96 15-AUG-05:01 4161.34 0.00
September 0.00 0.00 0.225810E+10 0.178166E+10 6169.03 15-SEP-05:02 3958.11 0.00
October 0.00 0.00 0.553122E+09 0.441408E+09 5974.14 13-OCT-05:03 4325.82 0.00
November 0.00 0.00 17369577.75 14618340.86 749.75 16-NOV-17:00 553.32 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.131802E+11 0.102768E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.359635E+10 0.283586E+10 6248.38   4325.82 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 59515600.81 51918134.88 2150.39 15-MAR-13:50 2024.99 0.00
April 0.00 0.00 19092559.83 19034788.16 666.27 21-APR-14:55 666.27 0.00
May 0.00 0.00 0.183413E+09 0.167803E+09 1820.97 10-MAY-14:30 1509.00 0.00
June 0.00 0.00 0.144330E+10 0.115780E+10 6326.09 28-JUN-05:02 4008.57 0.00
July 0.00 0.00 0.258316E+10 0.201335E+10 6669.45 21-JUL-05:02 3276.89 0.00
August 0.00 0.00 0.288198E+10 0.240847E+10 6599.60 14-AUG-05:01 3830.51 0.00
September 0.00 0.00 0.192046E+10 0.167264E+10 6340.22 14-SEP-05:02 4293.37 0.00
October 0.00 0.00 0.526264E+09 0.488049E+09 3959.26 11-OCT-14:30 3802.22 0.00
November 0.00 0.00 42867674.00 42022386.53 1307.17 01-NOV-12:30 1307.17 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.966006E+10 0.802109E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.288198E+10 0.240847E+10 6669.45   4293.37 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 7693504.08 6752241.94 625.70 15-MAR-15:30 558.66 0.00
April 0.00 0.00 1172832.10 1172832.10 146.75 21-APR-14:55 146.75 0.00
May 0.00 0.00 0.153986E+09 0.143846E+09 2560.97 26-MAY-10:02 2483.29 0.00
June 0.00 0.00 0.108412E+10 0.931737E+09 4386.15 27-JUN-05:02 2859.37 0.00
July 0.00 0.00 0.170121E+10 0.141856E+10 4637.67 21-JUL-05:02 2266.94 0.00
August 0.00 0.00 0.170030E+10 0.147514E+10 4586.02 14-AUG-05:01 2581.72 0.00
September 0.00 0.00 0.939766E+09 0.832338E+09 4391.90 14-SEP-05:02 2957.37 0.00
October 0.00 0.00 0.150570E+09 0.137914E+09 3075.43 11-OCT-10:02 2945.83 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.573881E+10 0.494746E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.170121E+10 0.147514E+10 4637.67   2957.37 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 4728869.66 4138994.95 574.62 15-MAR-15:55 497.84 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 89450447.92 79117432.24 1183.31 10-MAY-15:00 927.02 0.00
June 0.00 0.00 0.137629E+10 0.109507E+10 5474.63 27-JUN-05:02 3495.39 0.00
July 0.00 0.00 0.230172E+10 0.178599E+10 5778.44 21-JUL-05:02 2814.21 0.00
August 0.00 0.00 0.231926E+10 0.189460E+10 5710.57 14-AUG-05:01 3130.56 0.00
September 0.00 0.00 0.113564E+10 0.932161E+09 5480.34 14-SEP-05:02 3578.68 0.00
October 0.00 0.00 0.123415E+09 0.105306E+09 1278.99 12-OCT-15:30 994.81 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.735051E+10 0.589639E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.231926E+10 0.189460E+10 5778.44   3578.68 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:03 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 10987712.17 9585770.63 787.09 15-MAR-13:20 701.96 0.00
April 0.00 0.00 6471949.29 6350575.79 507.17 20-APR-15:55 474.30 0.00
May 0.00 0.00 0.179266E+09 0.164035E+09 1560.50 31-MAY-15:55 1442.97 0.00
June 0.00 0.00 0.119820E+10 0.100630E+10 5034.37 27-JUN-05:02 3340.67 0.00
July 0.00 0.00 0.174629E+10 0.141638E+10 5319.22 21-JUL-05:02 2609.32 0.00
August 0.00 0.00 0.182908E+10 0.155704E+10 5273.39 14-AUG-05:01 3071.69 0.00
September 0.00 0.00 0.999658E+09 0.866249E+09 5035.70 14-SEP-05:02 3376.20 0.00
October 0.00 0.00 0.181598E+09 0.163224E+09 1815.03 11-OCT-15:53 1683.42 0.00
November 0.00 0.00 160423.89 136784.47 68.13 16-NOV-16:40 58.07 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.615171E+10 0.518930E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.182908E+10 0.155704E+10 5319.22   3376.20 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 298.63 716.38 31-JAN-12:20
February 0.00 0.00 01-FEB-00:05 176.45 719.62 15-FEB-12:20
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     38.90    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   298.63 719.62  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.313491E+09 0.35 317.90 02-JAN-06:01 0.94
February 0.282678E+09 0.35 317.90 01-FEB-06:01 0.94
March 0.342189E+09 0.38 317.90 01-MAR-06:01 0.94
April 0.297556E+09 0.34 317.90 03-APR-05:01 0.93
May 0.327312E+09 0.36 317.90 01-MAY-05:01 0.93
June 0.327312E+09 0.37 317.90 01-JUN-05:10 0.93
July 0.297556E+09 0.33 317.90 03-JUL-05:01 0.94
August 0.342189E+09 0.37 317.90 01-AUG-05:02 0.93
September 0.297556E+09 0.34 317.90 01-SEP-05:03 0.93
October 0.312434E+09 0.34 317.90 02-OCT-05:05 0.93
November 0.312434E+09 0.36 317.90 01-NOV-05:05 0.93
December 0.297556E+09 0.33 317.90 01-DEC-06:01 0.94
           
Annual Sum or Average 0.375026E+10 0.35      
Minimum of Months 0.282678E+09 0.33 317.90   0.93
Maximum of Months 0.342189E+09 0.38 317.90   0.94



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.365943E+09 0.44 342.20 01-JAN-00:10 0.94
February 0.355543E+09 0.46 342.20 01-FEB-06:01 0.94
March 0.372831E+09 0.39 342.20 01-MAR-06:01 0.95
April 0.320648E+09 0.34 342.20 03-APR-05:01 0.94
May 0.352325E+09 0.36 342.20 01-MAY-05:01 0.94
June 0.352325E+09 0.37 342.20 01-JUN-05:10 0.93
July 0.320295E+09 0.33 342.20 03-JUL-05:01 0.93
August 0.368340E+09 0.38 342.20 01-AUG-05:02 0.93
September 0.320295E+09 0.34 342.20 01-SEP-05:03 0.93
October 0.336310E+09 0.34 342.20 02-OCT-05:05 0.94
November 0.336310E+09 0.36 342.20 01-NOV-05:05 0.94
December 0.344173E+09 0.37 342.20 01-DEC-06:01 0.94
           
Annual Sum or Average 0.414534E+10 0.37      
Minimum of Months 0.320295E+09 0.33 342.20   0.93
Maximum of Months 0.372831E+09 0.46 342.20   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.262045E+09 0.50 259.77 01-JAN-00:10 0.94
February 0.250398E+09 0.52 259.77 01-FEB-06:01 0.94
March 0.234536E+09 0.39 259.77 01-MAR-06:01 0.95
April 0.188800E+09 0.28 259.77 03-APR-05:01 0.94
May 0.206838E+09 0.30 259.77 01-MAY-05:01 0.94
June 0.220102E+09 0.38 259.77 01-JUN-05:10 0.93
July 0.210011E+09 0.33 259.77 03-JUL-05:01 0.93
August 0.238433E+09 0.38 259.77 01-AUG-05:02 0.93
September 0.200522E+09 0.34 259.77 01-SEP-05:03 0.93
October 0.198071E+09 0.29 259.77 02-OCT-05:05 0.94
November 0.196972E+09 0.29 259.77 01-NOV-05:05 0.94
December 0.240201E+09 0.41 259.77 01-DEC-06:01 0.94
           
Annual Sum or Average 0.264693E+10 0.37      
Minimum of Months 0.188800E+09 0.28 259.77   0.93
Maximum of Months 0.262045E+09 0.52 259.77   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.332828E+09 0.50 287.63 01-JAN-00:10 0.94
February 0.319584E+09 0.51 287.63 01-FEB-06:01 0.94
March 0.330304E+09 0.43 287.63 01-MAR-06:01 0.95
April 0.270748E+09 0.35 287.63 03-APR-05:01 0.94
May 0.296140E+09 0.36 287.63 01-MAY-05:01 0.94
June 0.296140E+09 0.37 287.63 01-JUN-05:10 0.93
July 0.269218E+09 0.33 287.63 03-JUL-05:01 0.93
August 0.309601E+09 0.38 287.63 01-AUG-05:02 0.93
September 0.269218E+09 0.34 287.63 01-SEP-05:03 0.93
October 0.282679E+09 0.34 287.63 02-OCT-05:05 0.94
November 0.282679E+09 0.36 287.63 01-NOV-05:05 0.94
December 0.304462E+09 0.41 287.63 01-DEC-06:01 0.94
           
Annual Sum or Average 0.356360E+10 0.39      
Minimum of Months 0.269218E+09 0.33 287.63   0.93
Maximum of Months 0.332828E+09 0.51 287.63   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.334524E+09 0.50 300.47 01-JAN-00:10 0.94
February 0.321271E+09 0.51 300.47 01-FEB-06:01 0.94
March 0.334637E+09 0.41 300.47 01-MAR-06:01 0.95
April 0.282261E+09 0.35 300.47 03-APR-05:01 0.94
May 0.309365E+09 0.36 300.47 01-MAY-05:01 0.94
June 0.309365E+09 0.37 300.47 01-JUN-05:10 0.93
July 0.281241E+09 0.33 300.47 03-JUL-05:01 0.93
August 0.323427E+09 0.38 300.47 01-AUG-05:02 0.93
September 0.281241E+09 0.34 300.47 01-SEP-05:03 0.93
October 0.295303E+09 0.34 300.47 02-OCT-05:05 0.94
November 0.295303E+09 0.36 300.47 01-NOV-05:05 0.94
December 0.312007E+09 0.41 300.47 01-DEC-06:01 0.94
           
Annual Sum or Average 0.367994E+10 0.39      
Minimum of Months 0.281241E+09 0.33 300.47   0.93
Maximum of Months 0.334637E+09 0.51 300.47   0.95



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:05 0.00 0.00 33.99 0.00
February 0.01 0.00 0.00 01-FEB-07:10 0.00 0.00 6.69 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 6.52 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 6.52 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 6.52 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 6.52 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 6.52 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 6.52 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 6.52 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 6.52 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 6.52 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 6.52 0.00
                 
Annual Sum or Average 0.03 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 6.52 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 33.99 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:03 48.89 48.89 298.63 716.38 31-JAN-12:20
February 0.00 0.00 01-FEB-00:05 6.71 6.71 176.45 719.62 15-FEB-12:20
March 0.00 0.00 01-MAR-00:10 6.52 6.52 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 6.52 6.52 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 6.52 6.52 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 6.52 6.52 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 6.52 6.52 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 6.52 6.52 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 6.52 6.52 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 6.52 6.52 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 6.52 6.52 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 6.52 6.52 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         38.90    
Minimum of Months 0.00 0.00   6.52 6.52 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 298.63 719.62  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.110786E+10 0.00 0.00
February 0.00 0.00 0.00 0.873617E+09 0.00 0.00
March 0.00 0.00 0.00 0.649190E+09 0.00 0.00
April 0.00 0.00 0.00 0.369648E+09 0.00 0.00
May 0.00 0.00 0.00 0.481603E+09 0.00 0.00
June 0.00 0.00 0.00 0.875558E+09 0.00 0.00
July 0.00 0.00 0.00 0.103278E+10 0.00 0.00
August 0.00 0.00 0.00 0.111013E+10 0.00 0.00
September 0.00 0.00 0.00 0.778840E+09 0.00 0.00
October 0.00 0.00 0.00 0.439827E+09 0.00 0.00
November 0.00 0.00 0.00 0.377094E+09 0.00 0.00
December 0.00 0.00 0.00 0.853178E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.894932E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.369648E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.111013E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.161189E+10 0.00 0.00
February 0.00 0.00 0.00 0.139489E+10 0.00 0.00
March 0.00 0.00 0.00 0.996279E+09 0.00 0.00
April 0.00 0.00 0.00 0.627729E+09 0.00 0.00
May 0.00 0.00 0.00 0.445186E+09 0.00 0.00
June 0.00 0.00 0.00 0.673737E+09 0.00 0.00
July 0.00 0.00 0.00 0.888710E+09 0.00 0.00
August 0.00 0.00 0.00 0.997661E+09 0.00 0.00
September 0.00 0.00 0.00 0.730398E+09 0.00 0.00
October 0.00 0.00 0.00 0.497020E+09 0.00 0.00
November 0.00 0.00 0.00 0.627998E+09 0.00 0.00
December 0.00 0.00 0.00 0.138234E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.108738E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.445186E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.161189E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.114283E+10 0.00 0.00
February 0.00 0.00 0.00 0.967401E+09 0.00 0.00
March 0.00 0.00 0.00 0.656549E+09 0.00 0.00
April 0.00 0.00 0.00 0.325493E+09 0.00 0.00
May 0.00 0.00 0.00 0.251784E+09 0.00 0.00
June 0.00 0.00 0.00 0.461212E+09 0.00 0.00
July 0.00 0.00 0.00 0.586525E+09 0.00 0.00
August 0.00 0.00 0.00 0.614909E+09 0.00 0.00
September 0.00 0.00 0.00 0.406618E+09 0.00 0.00
October 0.00 0.00 0.00 0.249819E+09 0.00 0.00
November 0.00 0.00 0.00 0.336776E+09 0.00 0.00
December 0.00 0.00 0.00 0.918840E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.691876E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.249819E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.114283E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.166603E+10 0.00 0.00
February 0.00 0.00 0.00 0.145905E+10 0.00 0.00
March 0.00 0.00 0.00 0.114301E+10 0.00 0.00
April 0.00 0.00 0.00 0.604075E+09 0.00 0.00
May 0.00 0.00 0.00 0.351667E+09 0.00 0.00
June 0.00 0.00 0.00 0.601530E+09 0.00 0.00
July 0.00 0.00 0.00 0.775572E+09 0.00 0.00
August 0.00 0.00 0.00 0.819964E+09 0.00 0.00
September 0.00 0.00 0.00 0.518278E+09 0.00 0.00
October 0.00 0.00 0.00 0.360112E+09 0.00 0.00
November 0.00 0.00 0.00 0.576516E+09 0.00 0.00
December 0.00 0.00 0.00 0.134177E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.102176E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.351667E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.166603E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.130127E+10 0.00 0.00
February 0.00 0.00 0.00 0.111100E+10 0.00 0.00
March 0.00 0.00 0.00 0.794612E+09 0.00 0.00
April 0.00 0.00 0.00 0.445937E+09 0.00 0.00
May 0.00 0.00 0.00 0.361776E+09 0.00 0.00
June 0.00 0.00 0.00 0.577479E+09 0.00 0.00
July 0.00 0.00 0.00 0.672827E+09 0.00 0.00
August 0.00 0.00 0.00 0.732000E+09 0.00 0.00
September 0.00 0.00 0.00 0.501958E+09 0.00 0.00
October 0.00 0.00 0.00 0.356777E+09 0.00 0.00
November 0.00 0.00 0.00 0.442027E+09 0.00 0.00
December 0.00 0.00 0.00 0.103873E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.833639E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.356777E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.130127E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.313491E+09 0.00 0.178230E+10 0.00 0.00 0.00 0.00 0.00
February 0.282678E+09 0.00 0.147383E+10 0.00 0.00 0.00 0.00 0.00
March 0.342189E+09 56494357.96 0.646030E+09 0.00 0.00 0.00 0.00 0.00
April 0.297556E+09 20111778.65 0.139406E+09 0.00 0.00 0.00 0.00 0.00
May 0.327312E+09 0.686516E+09 3189647.42 0.00 0.00 0.00 0.00 0.00
June 0.327312E+09 0.254655E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.297556E+09 0.344557E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.342189E+09 0.359635E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.297556E+09 0.225810E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.312434E+09 0.553122E+09 2485519.03 0.00 0.00 0.00 0.00 0.00
November 0.312434E+09 17369577.75 0.105292E+09 0.00 0.00 0.00 0.00 0.00
December 0.297556E+09 0.00 0.122511E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.375026E+10 0.131802E+11 0.537765E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.282678E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.342189E+09 0.359635E+10 0.178230E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.365943E+09 0.00 0.358511E+10 0.00 0.00 0.00 0.00 0.00
February 0.355543E+09 0.00 0.325855E+10 0.00 0.00 0.00 0.00 0.00
March 0.372831E+09 59515600.81 0.169803E+10 0.00 0.00 0.00 0.00 0.00
April 0.320648E+09 19092559.83 0.865132E+09 0.00 0.00 0.00 0.00 0.00
May 0.352325E+09 0.183413E+09 0.152852E+09 0.00 0.00 0.00 0.00 0.00
June 0.352325E+09 0.144330E+10 1416604.18 0.00 0.00 0.00 0.00 0.00
July 0.320295E+09 0.258316E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.368340E+09 0.288198E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.320295E+09 0.192046E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.336310E+09 0.526264E+09 0.101950E+09 0.00 0.00 0.00 0.00 0.00
November 0.336310E+09 42867674.00 0.728326E+09 0.00 0.00 0.00 0.00 0.00
December 0.344173E+09 0.00 0.287414E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.414534E+10 0.966006E+10 0.132655E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.320295E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.372831E+09 0.288198E+10 0.358511E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.262045E+09 0.00 0.211667E+10 0.00 0.00 0.00 0.00 0.00
February 0.250398E+09 0.00 0.191574E+10 0.00 0.00 0.00 0.00 0.00
March 0.234536E+09 7693504.08 0.103917E+10 0.00 0.00 0.00 0.00 0.00
April 0.188800E+09 1172832.10 0.351470E+09 0.00 0.00 0.00 0.00 0.00
May 0.206838E+09 0.153986E+09 28676512.00 0.00 0.00 0.00 0.00 0.00
June 0.220102E+09 0.108412E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.210011E+09 0.170121E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.238433E+09 0.170030E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.200522E+09 0.939766E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.198071E+09 0.150570E+09 31666013.20 0.00 0.00 0.00 0.00 0.00
November 0.196972E+09 0.00 0.336929E+09 0.00 0.00 0.00 0.00 0.00
December 0.240201E+09 0.00 0.164228E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.264693E+10 0.573881E+10 0.746260E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.188800E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.262045E+09 0.170121E+10 0.211667E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.332828E+09 0.00 0.382221E+10 0.00 0.00 0.00 0.00 0.00
February 0.319584E+09 0.00 0.353870E+10 0.00 0.00 0.00 0.00 0.00
March 0.330304E+09 4728869.66 0.232839E+10 0.00 0.00 0.00 0.00 0.00
April 0.270748E+09 0.00 0.950036E+09 0.00 0.00 0.00 0.00 0.00
May 0.296140E+09 89450447.92 0.103784E+09 0.00 0.00 0.00 0.00 0.00
June 0.296140E+09 0.137629E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.269218E+09 0.230172E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.309601E+09 0.231926E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.269218E+09 0.113564E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.282679E+09 0.123415E+09 0.108330E+09 0.00 0.00 0.00 0.00 0.00
November 0.282679E+09 0.00 0.760194E+09 0.00 0.00 0.00 0.00 0.00
December 0.304462E+09 0.00 0.293186E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.356360E+10 0.735051E+10 0.145435E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.269218E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.332828E+09 0.231926E+10 0.382221E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.334524E+09 0.00 0.220249E+10 0.00 0.00 0.00 0.00 0.00
February 0.321271E+09 0.00 0.199102E+10 0.00 0.00 0.00 0.00 0.00
March 0.334637E+09 10987712.17 0.108795E+10 0.00 0.00 0.00 0.00 0.00
April 0.282261E+09 6471949.29 0.406687E+09 0.00 0.00 0.00 0.00 0.00
May 0.309365E+09 0.179266E+09 32754280.25 0.00 0.00 0.00 0.00 0.00
June 0.309365E+09 0.119820E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.281241E+09 0.174629E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.323427E+09 0.182908E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.281241E+09 0.999658E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.295303E+09 0.181598E+09 36249126.20 0.00 0.00 0.00 0.00 0.00
November 0.295303E+09 160423.89 0.340405E+09 0.00 0.00 0.00 0.00 0.00
December 0.312007E+09 0.00 0.165706E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.367994E+10 0.615171E+10 0.775462E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.281241E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.334637E+09 0.182908E+10 0.220249E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.313491E+09 0.00 0.00 0.794366E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.282678E+09 0.00 0.00 0.590939E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.342189E+09 0.00 0.00 0.294081E+09 12920209.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.297556E+09 0.00 0.00 67506292.49 4585329.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.327312E+09 0.00 0.00 1653647.92 0.152638E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.327312E+09 0.00 0.00 0.00 0.548246E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.297556E+09 0.00 0.00 0.00 0.735228E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.342189E+09 0.00 0.00 0.00 0.767940E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.297556E+09 0.00 0.00 0.00 0.481284E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.312434E+09 0.00 0.00 5054140.33 0.122339E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.312434E+09 0.00 0.00 60713233.02 3946937.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.297556E+09 0.00 0.00 0.555622E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.375026E+10 0.00 0.00 0.236993E+10 0.282913E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.282678E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.342189E+09 0.00 0.00 0.794366E+09 0.767940E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.365943E+09 0.00 0.00 0.124595E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.355543E+09 0.00 0.00 0.103935E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.372831E+09 0.00 0.00 0.609603E+09 13844890.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.320648E+09 0.00 0.00 0.302738E+09 4341706.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.352325E+09 0.00 0.00 51122565.07 41738904.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352325E+09 0.00 0.00 486115.47 0.320926E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.320295E+09 0.00 0.00 0.00 0.568414E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.368340E+09 0.00 0.00 0.00 0.629322E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.320295E+09 0.00 0.00 0.00 0.410102E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.336310E+09 0.00 0.00 45992606.46 0.114718E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.336310E+09 0.00 0.00 0.282056E+09 9631655.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.344173E+09 0.00 0.00 0.103817E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.414534E+10 0.00 0.00 0.461547E+10 0.211304E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.320295E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.372831E+09 0.00 0.00 0.124595E+10 0.629322E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.262045E+09 0.00 0.00 0.880785E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.250398E+09 0.00 0.00 0.717003E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.234536E+09 0.00 0.00 0.420181E+09 1831946.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.188800E+09 0.00 0.00 0.136424E+09 269366.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.206838E+09 0.00 0.00 10097037.47 34848041.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.220102E+09 0.00 0.00 0.00 0.241110E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.210011E+09 0.00 0.00 0.00 0.376515E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.238433E+09 0.00 0.00 0.00 0.376476E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.200522E+09 0.00 0.00 0.00 0.206096E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.198071E+09 0.00 0.00 17963511.55 33784464.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.196972E+09 0.00 0.00 0.139804E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.240201E+09 0.00 0.00 0.678639E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.264693E+10 0.00 0.00 0.300090E+10 0.127093E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.188800E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.262045E+09 0.00 0.00 0.880785E+09 0.376515E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.332828E+09 0.00 0.00 0.133320E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.319584E+09 0.00 0.00 0.113947E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.330304E+09 0.00 0.00 0.811562E+09 1144548.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.270748E+09 0.00 0.00 0.333327E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.296140E+09 0.00 0.00 35021757.30 20505853.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.296140E+09 0.00 0.00 0.00 0.305391E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.269218E+09 0.00 0.00 0.00 0.506354E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.309601E+09 0.00 0.00 0.00 0.510363E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.269218E+09 0.00 0.00 0.00 0.249060E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.282679E+09 0.00 0.00 49655325.62 27778203.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.282679E+09 0.00 0.00 0.293837E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.304462E+09 0.00 0.00 0.103731E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.356360E+10 0.00 0.00 0.503339E+10 0.162060E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.269218E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.332828E+09 0.00 0.00 0.133320E+10 0.510363E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.334524E+09 0.00 0.00 0.966748E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.321271E+09 0.00 0.00 0.789724E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.334637E+09 0.00 0.00 0.457357E+09 2616766.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.282261E+09 0.00 0.00 0.162200E+09 1476047.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.309365E+09 0.00 0.00 11707883.18 40703061.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.309365E+09 0.00 0.00 0.00 0.268115E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.281241E+09 0.00 0.00 0.00 0.391587E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.323427E+09 0.00 0.00 0.00 0.408574E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.281241E+09 0.00 0.00 0.00 0.220718E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.295303E+09 0.00 0.00 20709869.59 40764214.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.295303E+09 0.00 0.00 0.146688E+09 36951.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.312007E+09 0.00 0.00 0.726722E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.367994E+10 0.00 0.00 0.328186E+10 0.137459E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.281241E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.334637E+09 0.00 0.00 0.966748E+09 0.408574E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.113279E+10 0.00 0.00 0.00 0.00 0.111498E+10 0.00 0.00 0.17
February 0.107387E+10 0.00 0.00 0.00 0.00 0.957200E+09 0.00 0.00 0.17
March 0.140591E+10 0.00 0.00 193771.27 0.00 0.371844E+09 92453096.40 0.00 0.19
April 0.123374E+10 0.00 0.00 136794.25 0.00 83646216.76 0.108911E+09 0.00 0.17
May 0.426779E+09 101133.01 0.00 2931469.77 0.00 1301929.20 0.691199E+09 0.00 0.18
June 38841190.73 0.118924E+09 0.00 5365074.69 5885968.45 0.00 0.430556E+09 0.00 0.19
July 5381088.02 0.343624E+09 0.00 3342739.50 25100715.40 0.00 91958915.73 0.00 0.17
August 18010742.85 0.193195E+09 0.00 6359288.02 11056326.05 0.00 0.215360E+09 0.00 0.19
September 39225701.16 47595113.73 0.00 6751662.54 2945194.07 0.00 0.484585E+09 0.00 0.17
October 0.608146E+09 0.00 0.00 2401402.99 0.00 0.00 0.737682E+09 0.00 0.18
November 0.152849E+10 0.00 0.00 160234.65 0.00 38060755.43 95956520.16 0.00 0.18
December 0.132246E+10 0.00 0.00 0.00 0.00 0.741363E+09 0.00 0.00 0.17
                   
Annual Sum or Average 0.883365E+10 0.703439E+09 0.00 27642437.69 44988203.97 0.330840E+10 0.294866E+10 0.00 0.18
Minimum of Months 5381088.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.152849E+10 0.343624E+09 0.00 6751662.54 25100715.40 0.111498E+10 0.737682E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.116979E+09 0.00 0.00 0.00 0.00 0.127612E+10 0.00 0.00 0.17
February 0.139849E+09 0.00 0.00 0.00 0.00 0.111944E+10 0.00 0.00 0.17
March 0.388101E+09 50265.55 0.00 104733.71 1279.17 0.680048E+09 7667836.84 0.00 0.19
April 0.353256E+09 0.00 0.00 87997.82 0.00 0.350988E+09 36186557.89 0.00 0.17
May 0.363843E+09 1120334.14 0.00 439279.29 0.00 68786593.33 0.112193E+09 0.00 0.18
June 95513517.85 89435475.03 0.00 2106335.85 4452123.05 543307.17 0.176895E+09 0.00 0.19
July 19600820.12 0.260903E+09 0.00 1717672.87 17381389.07 0.00 41801746.11 0.00 0.17
August 32673447.47 0.160951E+09 0.00 3900192.21 8370641.85 0.00 0.101058E+09 0.00 0.19
September 88627724.79 50613331.63 0.00 5316301.36 1877933.13 0.00 0.212673E+09 0.00 0.17
October 0.407405E+09 0.00 0.00 2029021.67 0.00 44605999.38 0.278335E+09 0.00 0.18
November 0.517929E+09 0.00 0.00 207505.75 0.00 0.336423E+09 53984271.27 0.00 0.18
December 63368264.01 0.00 0.00 0.00 0.00 0.119838E+10 0.00 0.00 0.17
                   
Annual Sum or Average 0.258715E+10 0.563073E+09 0.00 15909040.53 32083366.28 0.507534E+10 0.102079E+10 0.00 0.18
Minimum of Months 19600820.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.517929E+09 0.260903E+09 0.00 5316301.36 17381389.07 0.127612E+10 0.278335E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 483849.91 0.00 0.00 0.00 0.00 0.730233E+09 0.00 0.00 0.15
February 2060738.34 0.00 0.00 0.00 0.00 0.645613E+09 0.00 0.00 0.15
March 73787726.58 0.00 0.00 9205.77 17274.74 0.435274E+09 1907771.41 0.00 0.15
April 0.181298E+09 0.00 0.00 8538.78 0.00 0.153135E+09 6181643.14 0.00 0.13
May 0.176858E+09 738580.56 0.00 561083.06 0.00 12178420.89 78069877.78 0.00 0.14
June 21789948.85 59139514.47 0.00 2157564.70 3797970.72 0.00 0.103672E+09 0.00 0.15
July 1550912.78 0.158691E+09 0.00 1525349.51 14137591.42 0.00 23933515.56 0.00 0.14
August 5820315.64 91395925.83 0.00 2654850.03 7005186.66 0.00 55123345.14 0.00 0.16
September 30073468.22 27299999.31 0.00 2822818.56 2208933.23 0.00 0.121220E+09 0.00 0.14
October 0.227415E+09 0.00 0.00 578583.23 0.00 16687442.62 96962942.17 0.00 0.13
November 0.201877E+09 0.00 0.00 506.47 0.00 0.203253E+09 2211953.89 0.00 0.14
December 11470978.04 0.00 0.00 0.00 0.00 0.636528E+09 0.00 0.00 0.14
                   
Annual Sum or Average 0.934487E+09 0.337265E+09 0.00 10318500.13 27166956.78 0.283290E+10 0.489283E+09 0.00 0.14
Minimum of Months 483849.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13
Maximum of Months 0.227415E+09 0.158691E+09 0.00 2822818.56 14137591.42 0.730233E+09 0.121220E+09 0.00 0.16



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.143086E+10 0.00 0.00 0.17
February 0.00 0.00 0.00 0.00 0.00 0.129273E+10 0.00 0.00 0.17
March 0.116600E+09 0.00 0.00 2779.84 2681.27 0.989930E+09 986578.86 0.00 0.19
April 0.287514E+09 0.00 0.00 0.00 0.00 0.461477E+09 0.00 0.00 0.17
May 0.458869E+09 312479.32 0.00 208861.45 2900.32 52068624.15 75471595.86 0.00 0.18
June 59465953.57 0.101906E+09 0.00 2281334.22 6277162.59 0.00 0.225746E+09 0.00 0.19
July 2426549.95 0.287134E+09 0.00 1714462.96 23637088.36 0.00 57587901.66 0.00 0.17
August 12358878.40 0.168231E+09 0.00 3389423.11 11890979.33 0.00 0.124462E+09 0.00 0.19
September 81808165.52 45191885.68 0.00 3094291.79 3363774.73 0.00 0.248352E+09 0.00 0.17
October 0.560385E+09 0.00 0.00 465830.39 0.00 56723770.58 0.134514E+09 0.00 0.17
November 0.452576E+09 0.00 0.00 0.00 0.00 0.462638E+09 0.00 0.00 0.18
December 22814952.73 0.00 0.00 0.00 0.00 0.127151E+10 0.00 0.00 0.17
                   
Annual Sum or Average 0.205482E+10 0.602776E+09 0.00 11156983.77 45174586.60 0.601794E+10 0.867120E+09 0.00 0.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.560385E+09 0.287134E+09 0.00 3389423.11 23637088.36 0.143086E+10 0.248352E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 2571427.70 0.00 0.00 0.00 0.00 0.842579E+09 0.00 0.00 0.17
February 12757322.79 0.00 0.00 0.00 0.00 0.751502E+09 0.00 0.00 0.17
March 0.141459E+09 0.00 0.00 11869.17 1870.10 0.512000E+09 2573536.42 0.00 0.19
April 0.226722E+09 0.00 0.00 29449.05 0.00 0.215937E+09 11849494.81 0.00 0.17
May 0.235726E+09 595696.51 0.00 459481.36 0.00 19474039.37 0.100624E+09 0.00 0.18
June 27283720.04 67757696.49 0.00 1844053.20 3868056.64 0.00 0.136710E+09 0.00 0.19
July 1872479.76 0.177814E+09 0.00 1186535.98 13940080.43 0.00 31907650.76 0.00 0.17
August 8842748.50 0.104770E+09 0.00 2501003.35 6730407.10 0.00 69986155.11 0.00 0.19
September 30602355.16 29246453.49 0.00 2556257.23 2160478.18 0.00 0.162174E+09 0.00 0.17
October 0.303066E+09 0.00 0.00 590334.54 0.00 24152208.12 0.127026E+09 0.00 0.18
November 0.304374E+09 0.00 0.00 120.25 0.00 0.242050E+09 1182650.64 0.00 0.18
December 14240202.60 0.00 0.00 0.00 0.00 0.749843E+09 0.00 0.00 0.17
                   
Annual Sum or Average 0.130952E+10 0.380184E+09 0.00 9179104.14 26700892.45 0.335754E+10 0.644034E+09 0.00 0.18
Minimum of Months 1872479.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
Maximum of Months 0.304374E+09 0.177814E+09 0.00 2556257.23 13940080.43 0.842579E+09 0.162174E+09 0.00 0.19



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:27:02

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.199739E+11 0.365113E+10 0.00 0.665604E+10 -0.769600E+18
February 0.426524E+11 0.444611E+10 0.00 0.600571E+10 -0.797800E+18
March 0.743217E+11 0.410666E+10 0.00 0.527899E+10 -0.892200E+18
April 0.968954E+11 0.454555E+10 0.00 0.380032E+10 -0.914500E+18
May 0.126741E+12 0.450227E+10 0.00 0.294780E+10 -0.989500E+18
June 0.141857E+12 0.447236E+10 0.00 0.872606E+09 -0.981500E+18
July 0.132791E+12 0.366604E+10 0.00 -0.103576E+10 -0.102370E+19
August 0.110523E+12 0.332248E+10 0.00 -100776664.3 -0.985700E+18
September 0.790853E+11 0.248029E+10 0.00 0.131384E+10 -0.888200E+18
October 0.469134E+11 0.253974E+10 0.00 0.371714E+10 -0.761800E+18
November 0.183590E+11 0.217382E+10 0.00 0.454946E+10 -0.631300E+18
December 0.171431E+11 0.359714E+10 0.00 0.604894E+10 -0.673600E+18
           
Annual Sum or Average 0.907256E+12 0.435036E+11 0.00 0.400543E+11 -0.103094E+20
Minimum of Months 0.171431E+11 0.217382E+10 0.00 -0.103576E+10 -0.102370E+19
Maximum of Months 0.141857E+12 0.454555E+10 0.00 0.665604E+10 -0.631300E+18