Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 08:27:25


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 166.14 325.02 325.02
Net Site Energy 166.14 325.02 325.02
Total Source Energy 526.14 1029.31 1029.31
Net Source Energy 526.14 1029.31 1029.31


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.40 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 34.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 166.13 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.40 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 34.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 23.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 23.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.40 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 34.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 23.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 23.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 158.60 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 325.01 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 158.60 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 325.01 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 166.130 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 166.130 100.00
     
Total On-Site and Utility Electric Sources 166.130 100.00
Total Electricity End Uses 166.130 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.17
Time Setpoint Not Met During Occupied Cooling 131.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 591.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.9815 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.9815 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.9815 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.9815 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.9815 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.9815 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.9815 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.9815 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.9815 9.29 6.7800  
Conditioned Total 511.16             6.9815 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.9815 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 26-JUN-15:00 02-JAN-06:10 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 4287.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 7627.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2228.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1996.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2720.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 17898.93 4287.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 4287.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 7627.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2228.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1996.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2720.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 1.28 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 108.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 85.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 73.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 74.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 526.13 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 2.50 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 211.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 166.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 143.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 145.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1029.30 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 2.50 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 211.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 166.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 143.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 145.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1029.30 0.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.342104
PERIMETER_ZN_1 DIRECT AIR 0.407174
PERIMETER_ZN_2 DIRECT AIR 0.289849
PERIMETER_ZN_3 DIRECT AIR 0.402596
PERIMETER_ZN_4 DIRECT AIR 0.340601
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.342104 0.342104 0.342104 0.342104 0.342104 0.342104 1.00 1.00 0.342104
PSZ-AC:2 0.407174 0.407174 0.407174 0.407174 0.407174 0.407174 1.00 1.00 0.407174
PSZ-AC:3 0.289849 0.289849 0.289849 0.289849 0.289849 0.289849 1.00 1.00 0.289849
PSZ-AC:4 0.402596 0.402596 0.402596 0.402596 0.402596 0.402596 1.00 1.00 0.402596
PSZ-AC:5 0.340601 0.340601 0.340601 0.340601 0.340601 0.340601 1.00 1.000000 0.340601
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.342104 0.064622
PSZ-AC:2_OA_CONTROLLER 0.407174 0.048988
PSZ-AC:3_OA_CONTROLLER 0.289849 0.029060
PSZ-AC:4_OA_CONTROLLER 0.402596 0.048988
PSZ-AC:5_OA_CONTROLLER 0.340601 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.342104 6327.20 0.800062
PSZ-AC:2 HP COOLING COIL 0.407174 7171.94 0.800521
PSZ-AC:3 HP COOLING COIL 0.289849 4798.03 0.800655
PSZ-AC:4 HP COOLING COIL 0.402596 7100.70 0.800064
PSZ-AC:5 HP COOLING COIL 0.340601 5638.16 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.342104 0.342104 0.342104 0.342104 6327.20 6327.20 40.00 2804.01 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.407174 0.407174 0.407174 0.407174 7171.94 7171.94 40.00 3441.07 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.289849 0.289849 0.289849 0.289849 4798.03 4798.03 40.00 2103.01 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.402596 0.402596 0.402596 0.402596 7100.70 7100.70 40.00 3376.87 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.340601 0.340601 0.340601 0.340601 5638.16 5638.16 40.00 2096.54 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.342104
PSZ-AC:2 FAN 0.407174
PSZ-AC:3 FAN 0.289849
PSZ-AC:4 FAN 0.402596
PSZ-AC:5 FAN 0.340601
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.342104 6327.20
PSZ-AC:2 HEATING COIL 0.407174 7171.94
PSZ-AC:3 HEATING COIL 0.289849 4798.03
PSZ-AC:4 HEATING COIL 0.402596 7100.70
PSZ-AC:5 HEATING COIL 0.340601 5638.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 2804.01
PSZ-AC:2_SUPPHEATCOIL 3441.07
PSZ-AC:3_SUPPHEATCOIL 2103.01
PSZ-AC:4_SUPPHEATCOIL 3376.87
PSZ-AC:5_SUPPHEATCOIL 2096.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1044.832 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1044.832
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4610


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.2198E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.3546E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.3112E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.4308E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 8.8546E-004
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 9.8690E-004
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 4.3251E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.8318E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 7.1154E-003
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 6.4158E-003
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.9925E-003
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 6.6395E-003
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.9033E-003
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.7885E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.6930E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.9875E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 7.2091E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 7.1878E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 7.3301E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 7.6887E-003
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.4507E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 4.8493E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 3.0682E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.8375E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.2202E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3686E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.3133E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.4506E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 8.8630E-004
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 9.9228E-004
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 4.2894E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.7533E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1639E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1797E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.2641E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.2780E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 8.4210E-004
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 8.5300E-004
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 4.0429E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 4.0967E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1599E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1629E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.2606E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.2632E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 8.3924E-004
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 8.4128E-004
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 4.0268E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 4.0373E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.8641E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.2727E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.9681E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.3744E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.3836E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.6393E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.8598E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.6907E-004
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 9.5777E-004
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.0597E-003
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.8602E-004
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.6153E-004
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.2346E-004
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.6049E-004
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.7807E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.2474E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.6461E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.8708E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.9505E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.3870E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.6616E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.1420E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3215E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.1121E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.0463E-002
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.8494E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.0973E-002
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.6316E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 8.6840E-003
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.1822E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.9598E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.2669E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.1078E-003
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.3879E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.0720E-003
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.3635E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.0486E-004
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.0603E-003
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.8152E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 7.3256E-004
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.6367E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.5097E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.7399E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.4192E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.1143E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.5802E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.2791E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.7227E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.8730E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.3665E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.2677E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.8093E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.2214E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.2941E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.8007E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.7666E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.9955E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.8274E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.0816E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.1238E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.7346E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.3631E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.0538E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.0664E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.7466E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.8182E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.8168E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.6296E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.1471E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.6222E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.3509E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.8799E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.2177E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.3527E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.3990E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.5039E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.8194E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.8863E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.0508E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.1105E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.1783E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.2055E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.3676E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.3890E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.7966E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.8106E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.0325E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.0438E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 9.8223E-004
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.1904E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 9.1525E-004
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.1186E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.1498E-004
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 9.4961E-004
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.8264E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 7.3330E-004
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.9023E-003
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.9247E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.8171E-003
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.5649E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.4216E-003
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.5705E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.9431E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.2376E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.6334E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.7909E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.8610E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.2468E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.4099E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.8826E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.3183E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.0876E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 8.6124E-004
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 9.6719E-004
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.6531E-004
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 8.4265E-004
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.3695E-004
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.7043E-004
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.7906E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.2545E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3527.40615 4232.88738 0.28509 0.34210 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 39.64733 5.62931E-003 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 754.29588 905.15506 3.58208E-002 6.46221E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 4198.39141 5038.06970 0.33931 0.40717 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.63007E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 1972.05790 2366.46948 9.36493E-002 0.11238 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2988.70751 3586.44902 0.24154 0.28985 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 37.07600 5.62532E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 1222.04806 1466.45767 5.80326E-002 6.96392E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 4151.18795 4981.42554 0.33550 0.40260 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.63007E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 1917.76615 2301.31939 9.10711E-002 0.10929 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3512.01646 4214.41976 0.28383 0.34060 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 38.05133 5.62683E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 1216.57827 1459.89393 5.77729E-002 6.93275E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 5286.05 0.34210 0.34210 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 2804.01 6.46221E-002 6.46221E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 5834.38 0.40717 0.40717 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 3441.07 0.11238 0.11238 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3951.93 0.28985 0.28985 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 2103.01 6.96392E-002 6.96392E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 5778.62 0.40260 0.40260 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 3376.87 0.10929 0.10929 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 4601.33 0.34060 0.34060 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 2096.54 6.93275E-002 6.93275E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.34210
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.40717
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.28985
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.40260
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.34060
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.34210
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.34210
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.34210
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.34210
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.34210
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.34210
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.40717
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.40717
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.40717
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.40717
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.40717
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.40717
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.28985
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.28985
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.28985
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.28985
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.28985
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.28985
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.40260
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.40260
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.40260
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.40260
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.40260
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.40260
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.34060
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.34060
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.34060
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.34060
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.34060
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.34060
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.34210
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.40717
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.28985
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.40260
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.34060
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.34210
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.34210
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6327.20174
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80006
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.34210
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.34210
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.34210
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.34210
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6327.20174
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6327.20174
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2804.01417
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.34210
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.34210
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6327.20174
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 2804.01417
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.40717
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.40717
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7171.93715
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80052
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.40717
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.40717
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.40717
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.40717
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7171.93715
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7171.93715
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3441.07153
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.40717
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.40717
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7171.93715
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 3441.07153
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.28985
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28985
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4798.02644
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.28985
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.28985
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.28985
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.28985
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4798.02644
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4798.02644
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2103.01195
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.28985
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.28985
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4798.02644
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 2103.01195
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.40260
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.40260
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 7100.69529
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80006
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.40260
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.40260
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.40260
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.40260
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 7100.69529
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 7100.69529
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3376.87040
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.40260
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.40260
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 7100.69529
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 3376.87040
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.34060
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.34060
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5638.16085
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.34060
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.34060
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.34060
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.34060
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5638.16085
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5638.16085
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2096.54382
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.34060
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.34060
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5638.16085
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 2096.54382
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 6058.7 3.36 11.47 12.01 11.36 11.33
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 6852.6 3.33 11.36 11.89 11.25 11.17
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 4570.9 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 6784.9 3.33 11.37 11.90 11.25 11.17
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 5371.2 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 6599.4 3661.7 7.37 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 7495.5 4165.6 7.36 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 5028.0 2800.3 7.34 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 7420.6 4123.8 7.36 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 5908.4 3290.6 7.33 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 1.5802443831E-002 7.6190831905E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 7.1207472490E-002 4.6701249491E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 3.6970818602E-002 2.9110211176E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 2.9242885639E-002 1.5713579160E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 5.7852684058E-002 4.1595123770E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.4967500604 0.4846051900 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1125.06 29.67 0.00 43.94 173.80 1372.48



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.455_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.455_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.455_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.455_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.455_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.455_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.455_SHGC_SOUTH_0.249   3.91 0.00 0.00 3.91 3.91 2.586 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.455_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.455_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.455_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.455_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.455_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.455_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.455_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.455_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.455_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.455_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.455_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.455_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.455_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.455_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.586 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.586 0.250 0.275                      
North Total or Average             16.72 2.586 0.250 0.275                      
Non-North Total or Average             42.93 2.586 0.250 0.275                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.15 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.05 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.9815 149.66 1044.83 LightsWired LTG_SCH_OFFICE 55.32 168.00 44.56 0.0000 Y 8.74
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 36.65 0.0000 Y 5.45
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.04 0.0000 Y 3.36
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 40.01 0.0000 Y 5.95
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.41 0.0000 Y 3.39
Interior Lighting Total       6.9815 511.16 3568.64               26.88


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 87.95 AstronomicalClock -   41.79 41.79 0.69
EXTERIOR_LIGHTS_B 200.47 AstronomicalClock -   83.79 62.79 2.36
EXTERIOR_LIGHTS_C 773.25 AstronomicalClock -   83.79 47.06 6.83
Exterior Lighting Total 1061.67           9.88



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6327.20 5062.16 1265.05 0.80 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7171.94 5741.29 1430.65 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4798.03 3841.57 956.46 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   7100.70 5681.01 1419.68 0.80 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5638.16 4514.22 1123.94 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   6058.7 3.36 11.47 12.01 11.36 11.33
PSZ-AC:2 HP COOLING COIL   6852.6 3.33 11.36 11.89 11.25 11.17
PSZ-AC:3 HP COOLING COIL   4570.9 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   6784.9 3.33 11.37 11.90 11.25 11.17
PSZ-AC:5 HP COOLING COIL   5371.2 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 6599.4 3661.7 7.37 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 7495.5 4165.6 7.36 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 5028.0 2800.3 7.34 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 7420.6 4123.8 7.36 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 5908.4 3290.6 7.33 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   6327.20 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   2804.01 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   7171.94 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   3441.07 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4798.03 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   2103.01 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   7100.70 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   3376.87 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   5638.16 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   2096.54 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.34 383.19 1120.11 1.00 1.81 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.41 456.08 1120.11 1.00 1.71 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.29 324.66 1120.11 1.00 1.92 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.40 450.95 1120.11 1.00 1.71 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.34 381.51 1120.11 1.00 1.81 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3527.41 4232.89 28.28 0.285 0.342 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 23.89 23.89 0.00901 39.65 0.00563 0.065 0.00
PERIMETER_ZN_1 4198.39 5038.07 44.41 0.339 0.407 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 23.89 23.89 0.00872 40.13 0.00563 0.049 0.00
PERIMETER_ZN_2 2988.71 3586.45 53.29 0.242 0.290 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 23.89 23.89 0.00867 37.08 0.00563 0.029 0.00
PERIMETER_ZN_3 4151.19 4981.43 43.91 0.335 0.403 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 23.89 23.89 0.00872 40.13 0.00563 0.049 0.00
PERIMETER_ZN_4 3512.02 4214.42 62.62 0.284 0.341 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 23.89 23.89 0.00865 38.05 0.00563 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 754.30 905.16 6.05 0.036 0.065 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 0.50 0.00432 0.065 0.00
PERIMETER_ZN_1 1972.06 2366.47 20.86 0.094 0.112 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00778 0.50 0.00432 0.049 0.00
PERIMETER_ZN_2 1222.05 1466.46 21.79 0.058 0.070 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 0.50 0.00432 0.029 0.00
PERIMETER_ZN_3 1917.77 2301.32 20.28 0.091 0.109 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00778 0.50 0.00432 0.049 0.00
PERIMETER_ZN_4 1216.58 1459.89 21.69 0.058 0.069 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00777 0.50 0.00432 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.34 0.34 0.06 0.06 0.3421 0.3421 0.3421 1.0000 1.0000
PSZ-AC:2 0.41 0.41 0.11 0.11 0.4072 0.4072 0.4072 1.0000 1.0000
PSZ-AC:3 0.29 0.29 0.07 0.07 0.2898 0.2898 0.2898 1.0000 1.0000
PSZ-AC:4 0.40 0.40 0.11 0.11 0.4026 0.4026 0.4026 1.0000 1.0000
PSZ-AC:5 0.34 0.34 0.07 0.07 0.3406 0.3406 0.3406 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6327.202 5062.155 0.342104 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 5558.59 5558.59 0.342104 27.87 16.60 0.00836937 12.80 11.10 0.00836937 39.65 0.00562931 18.22 18.8896 23.89 0.00901230 44.3013 3500.97 0.00 6326.12 4814.71
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6327.202 6327.202 0.342104 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6327.20 6327.20 0.342104 17.22 11.83 0.00730403 40.00 20.06 0.00800000 0.50 0.00431558 0.50 18.8896 21.11 0.00800000 46.6350 753.53 0.00 6335.52 6335.52
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 2804.014 2804.014 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 2804.01 2804.01 0.342104 17.22 11.83 0.00730403 40.00 20.06 0.00800000 0.50 0.00431558 0.50 18.8896 21.11 0.00800000 46.6350 753.53 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7171.937 5741.289 0.407174 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 6187.82 6187.82 0.407174 26.85 16.24 0.00834646 12.80 11.08 0.00834646 40.13 0.00563007 18.37 12.0312 23.89 0.00871836 42.8754 4191.30 0.00 7170.71 5458.51
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 7171.937 7171.937 0.407174 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7171.94 7171.94 0.407174 18.63 12.44 0.00736758 40.00 20.06 0.00800000 0.50 0.00431558 0.50 12.0312 21.11 0.00778499 45.3981 1972.06 0.00 7181.36 7181.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 3441.072 3441.072 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3441.07 3441.07 0.407174 18.63 12.44 0.00736758 40.00 20.06 0.00800000 0.50 0.00431558 0.50 12.0312 21.11 0.00778499 45.3981 1972.06 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4798.026 3841.565 0.289849 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 4281.82 4281.82 0.289849 26.22 16.05 0.00836568 12.80 11.10 0.00836568 37.08 0.00562532 17.41 10.0260 23.89 0.00867156 42.6480 2984.86 0.00 4797.20 3652.38
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4798.026 4798.026 0.289849 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 4798.03 4798.03 0.289849 19.04 12.65 0.00742340 40.00 20.06 0.00800000 0.50 0.00431558 0.50 10.0260 21.11 0.00776971 45.3102 1222.05 0.00 4804.33 4804.33
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 2103.012 2103.012 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2103.01 2103.01 0.289849 19.04 12.65 0.00742340 40.00 20.06 0.00800000 0.50 0.00431558 0.50 10.0260 21.11 0.00776971 45.3102 1222.05 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 7100.695 5681.013 0.402596 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 6127.48 6127.48 0.402596 26.87 16.25 0.00834435 12.80 11.08 0.00834435 40.13 0.00563007 18.37 12.1680 23.89 0.00872073 42.8869 4144.84 0.00 7099.48 5401.43
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 7100.695 7100.695 0.402596 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 7100.70 7100.70 0.402596 18.60 12.42 0.00735781 40.00 20.06 0.00800000 0.50 0.00431558 0.50 12.1680 21.11 0.00777927 45.3652 1917.77 0.00 7110.03 7110.03
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 3376.870 3376.870 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3376.87 3376.87 0.402596 18.60 12.42 0.00735781 40.00 20.06 0.00800000 0.50 0.00431558 0.50 12.1680 21.11 0.00777927 45.3652 1917.77 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5638.161 4514.223 0.340601 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 4968.55 4968.55 0.340601 26.10 16.03 0.00838897 12.80 11.12 0.00838897 38.05 0.00562683 17.72 8.5320 23.89 0.00864651 42.5265 3509.67 0.00 5637.19 4291.92
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5638.161 5638.161 0.340601 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5638.16 5638.16 0.340601 19.35 12.82 0.00747412 40.00 20.06 0.00800000 0.50 0.00431558 0.50 8.5320 21.11 0.00776874 45.3046 1216.58 0.00 5645.57 5645.57
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 2096.544 2096.544 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2096.54 2096.54 0.340601 19.35 12.82 0.00747412 40.00 20.06 0.00800000 0.50 0.00431558 0.50 8.5320 21.11 0.00776874 45.3046 1216.58 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6327.202 5062.155 0.342104 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.3982 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.342104 0.37398585   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 Sensible 5558.59 5558.59 0.8785 0.37398585 0.342104 27.87 16.60 0.00836937 49369.9 12.80 11.10 0.00836937 33992.4 -999.0 -999.00 -999.00 -999.00 383.193 5175.40 39.65 0.00562931 18.22 0.06462207 18.8896 23.89 0.00900749 23.89 0.00901230 44.3013 3500.97 0.00 6326.12 4814.71 0.35921623 26.67 19.44 0.01118466 55322.4 13.56 13.42 0.00953499 37711.5
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6327.202 6327.202 0.342104 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.342104 0.37398585   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6327.20 6327.20 1.0000 0.37398585 0.342104 17.22 11.83 0.00730403 35800.9 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6327.20 0.50 0.00431558 0.50 0.06462207 18.8896 21.11 0.00800000 21.11 0.00800000 46.6350 753.53 0.00 6335.52 6335.52 0.36737740 21.11 15.56 0.00875166 43444.1 38.00 21.13 0.00875166 60689.4
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2804.014 2804.014 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.342104 0.37398585   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 2804.01 2804.01 1.0000 0.37398585 0.342104 17.22 11.83 0.00730403 35800.9 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2804.01 0.50 0.00431558 0.50 0.06462207 18.8896 21.11 0.00800000 21.11 0.00800000 46.6350 753.53 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7171.937 5741.289 0.407174 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.3557 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.407174 0.44511972   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 6187.82 6187.82 0.8628 0.44511972 0.407174 26.85 16.24 0.00834646 48268.8 12.80 11.08 0.00834646 33934.6 -999.0 -999.00 -999.00 -999.00 456.078 5731.75 40.13 0.00563007 18.37 0.04898771 12.0312 23.89 0.00871797 23.89 0.00871836 42.8754 4191.30 0.00 7170.71 5458.51 0.42754086 26.67 19.44 0.01118466 55322.4 14.18 13.74 0.00961449 38550.4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7171.937 7171.937 0.407174 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.407174 0.44511972   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7171.94 7171.94 1.0000 0.44511972 0.407174 18.63 12.44 0.00736758 37401.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7171.94 0.50 0.00431558 0.50 0.04898771 12.0312 21.11 0.00778499 21.11 0.00778499 45.3981 1972.06 0.00 7181.36 7181.36 0.43725432 21.11 15.56 0.00875166 43444.1 37.20 20.89 0.00875166 59867.9
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3441.072 3441.072 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.407174 0.44511972   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3441.07 3441.07 1.0000 0.44511972 0.407174 18.63 12.44 0.00736758 37401.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3441.07 0.50 0.00431558 0.50 0.04898771 12.0312 21.11 0.00778499 21.11 0.00778499 45.3981 1972.06 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4798.026 3841.565 0.289849 -999.0 -999.000 -999.0000 1.01578 1.00000 1020.3914 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.289849 0.31686101   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 4281.82 4281.82 0.8924 0.31686101 0.289849 26.22 16.05 0.00836568 47672.6 12.80 11.10 0.00836568 33983.1 -999.0 -999.00 -999.00 -999.00 324.662 3957.16 37.08 0.00562532 17.41 0.02906014 10.0260 23.89 0.00867104 23.89 0.00867156 42.6480 2984.86 0.00 4797.20 3652.38 0.30434739 26.67 19.44 0.01118466 55322.4 14.93 14.12 0.00970984 39560.1
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4798.026 4798.026 0.289849 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.289849 0.31686101   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 4798.03 4798.03 1.0000 0.31686101 0.289849 19.04 12.65 0.00742340 37963.7 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4798.03 0.50 0.00431558 0.50 0.02906014 10.0260 21.11 0.00776971 21.11 0.00776971 45.3102 1222.05 0.00 4804.33 4804.33 0.31126198 21.11 15.56 0.00875166 43444.1 36.23 20.60 0.00875166 58879.1
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2103.012 2103.012 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.289849 0.31686101   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2103.01 2103.01 1.0000 0.31686101 0.289849 19.04 12.65 0.00742340 37963.7 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2103.01 0.50 0.00431558 0.50 0.02906014 10.0260 21.11 0.00776971 21.11 0.00776971 45.3102 1222.05 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 7100.695 5681.013 0.402596 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.3517 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.402596 0.44011514   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 6127.48 6127.48 0.8629 0.44011514 0.402596 26.87 16.25 0.00834435 48286.1 12.80 11.08 0.00834435 33929.2 -999.0 -999.00 -999.00 -999.00 450.950 5676.53 40.13 0.00563007 18.37 0.04898771 12.1680 23.89 0.00872037 23.89 0.00872073 42.8869 4144.84 0.00 7099.48 5401.43 0.42273392 26.67 19.44 0.01118466 55322.4 14.17 13.73 0.00960975 38528.2
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 7100.695 7100.695 0.402596 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.402596 0.44011514   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 7100.70 7100.70 1.0000 0.44011514 0.402596 18.60 12.42 0.00735781 37347.8 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 7100.70 0.50 0.00431558 0.50 0.04898771 12.1680 21.11 0.00777927 21.11 0.00777927 45.3652 1917.77 0.00 7110.03 7110.03 0.43233817 21.11 15.56 0.00875166 43444.1 37.22 20.90 0.00875166 59889.6
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3376.870 3376.870 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.402596 0.44011514   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3376.87 3376.87 1.0000 0.44011514 0.402596 18.60 12.42 0.00735781 37347.8 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3376.87 0.50 0.00431558 0.50 0.04898771 12.1680 21.11 0.00777927 21.11 0.00777927 45.3652 1917.77 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5638.161 4514.223 0.340601 -999.0 -999.000 -999.0000 1.01126 1.00000 1020.4347 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.340601 0.37234337   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 4968.55 4968.55 0.8812 0.37234337 0.340601 26.10 16.03 0.00838897 47615.8 12.80 11.12 0.00838897 34041.9 -999.0 -999.00 -999.00 -999.00 381.510 4587.04 38.05 0.00562683 17.72 0.02906014 8.5320 23.89 0.00864662 23.89 0.00864651 42.5265 3509.67 0.00 5637.19 4291.92 0.35763862 26.67 19.44 0.01118466 55322.4 14.93 14.12 0.00970984 39560.1
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5638.161 5638.161 0.340601 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.340601 0.37234337   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5638.16 5638.16 1.0000 0.37234337 0.340601 19.35 12.82 0.00747412 38406.0 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5638.16 0.50 0.00431558 0.50 0.02906014 8.5320 21.11 0.00776874 21.11 0.00776874 45.3046 1216.58 0.00 5645.57 5645.57 0.36576395 21.11 15.56 0.00875166 43444.1 36.23 20.60 0.00875166 58879.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2096.544 2096.544 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.340601 0.37234337   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2096.54 2096.54 1.0000 0.37234337 0.340601 19.35 12.82 0.00747412 38406.0 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2096.54 0.50 0.00431558 0.50 0.02906014 8.5320 21.11 0.00776874 21.11 0.00776874 45.3046 1216.58 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 1957.83 1254.17 173.50
PERIMETER_ZN_1 1795.67 1605.17 335.33
PERIMETER_ZN_2 1538.33 1713.67 359.83
PERIMETER_ZN_3 1642.50 2271.17 345.00
PERIMETER_ZN_4 1841.50 2133.83 529.00
ATTIC 0.00 0.00 0.00
Facility 2225.33 2551.33 591.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 86.50 0.00 86.50
PERIMETER_ZN_1 0.00 73.50 0.00 70.67
PERIMETER_ZN_2 0.00 27.17 0.00 15.17
PERIMETER_ZN_3 0.17 12.17 0.17 12.17
PERIMETER_ZN_4 0.00 33.17 0.00 10.67
ATTIC 0.00 0.00 0.00 0.00
Facility 0.17 164.67 0.17 131.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.398 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.397 0.396 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.371 0.054 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.397 0.043 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.397 0.049 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762126.79 0.00 762126.79 0.00 762126.79 2037921.45 5484.00 3276.00 0.00 0.00
PERIMETER_ZN_1 579343.15 0.00 579343.15 689196.31 1268539.46 1544876.42 5483.97 3276.03 0.00 58.30
PERIMETER_ZN_2 293568.35 0.00 293568.35 117362.86 410931.21 916440.58 6236.16 2523.84 0.00 782.95
PERIMETER_ZN_3 578410.74 0.00 578410.74 176044.29 754455.03 1544876.42 5484.00 3276.00 0.00 28.48
PERIMETER_ZN_4 345367.03 0.00 345367.03 117362.86 462729.89 916440.58 5482.90 3277.10 0.00 137.64
Total Facility 2558816.06 0.00 2558816.06 1099966.32 3658782.38 6960555.45 6236.60 3277.54 0.00 884.41


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0373 0.0748 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0030 0.0237 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0041 0.0415 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0027 0.0249 0.0291 1008.00 3276.00 0.00
Total Facility 0.1673 0.0000 0.1673 0.0471 0.2144 0.2207 1760.60 3276.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 910797.60 0.00 910797.60 2037921.45 5484.00 0.00 3276.00 0.00
PSZ-AC:2 692357.70 0.00 692357.70 1544876.42 5483.44 0.08 3276.47 57.27
PSZ-AC:3 350835.79 0.00 350835.79 916440.58 6212.49 4.08 2543.42 754.13
PSZ-AC:4 691243.41 0.00 691243.41 1544876.42 5483.93 0.03 3276.03 27.85
PSZ-AC:5 412739.02 0.00 412739.02 916440.58 5481.63 0.20 3278.17 130.96


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0591 0.0000 0.0591 0.0646 1008.00 0.00 3276.00
PSZ-AC:2 0.0448 0.0000 0.0448 0.0490 1008.00 0.00 3276.00
PSZ-AC:3 0.0248 0.0000 0.0248 0.0291 1008.00 0.00 2520.00
PSZ-AC:4 0.0448 0.0000 0.0448 0.0490 1008.00 0.00 3276.00
PSZ-AC:5 0.0266 0.0000 0.0266 0.0291 1008.00 0.00 3276.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3333.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3274.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3303.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3419.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0772 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0585 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0347 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0585 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0346 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 555
Defaulted Fields 365
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 166.13 1248.68 01-JAN-08:50 17898.93 26-JUN-16:00
Electricity:Building 75.18 677.68 01-JAN-00:10 5866.25 28-NOV-16:30
Electricity:Zone:CORE_ZN 22.88 198.41 01-JAN-00:10 1717.53 02-JAN-08:10
Electricity:SpaceType:GENERAL 75.18 677.68 01-JAN-00:10 5866.25 28-NOV-16:30
InteriorLights:Electricity 26.88 110.04 01-JAN-00:10 2540.94 28-NOV-16:30
InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.88 110.04 01-JAN-00:10 2540.94 28-NOV-16:30
LightsWired:InteriorLights:Electricity 26.88 110.04 01-JAN-00:10 2540.94 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.88 110.04 01-JAN-00:10 2540.94 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_1 16.17 150.41 01-JAN-00:10 1302.00 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.45 24.42 01-JAN-00:10 563.96 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.45 24.42 01-JAN-00:10 563.96 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_2 9.71 89.23 01-JAN-00:10 772.36 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.36 14.49 01-JAN-00:10 334.55 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.36 14.49 01-JAN-00:10 334.55 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_3 16.67 150.41 01-JAN-00:10 1302.00 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.95 24.42 01-JAN-00:10 563.96 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.95 24.42 01-JAN-00:10 563.96 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_4 9.75 89.23 01-JAN-00:10 772.36 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.39 14.49 01-JAN-00:10 334.55 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.39 14.49 01-JAN-00:10 334.55 28-NOV-16:30
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
ElectricityPurchased:Plant 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
Cogeneration:ElectricityPurchased 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
General:Cogeneration:ElectricityPurchased 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
ElectricityNet:Plant 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
Cogeneration:ElectricityNet 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
General:Cogeneration:ElectricityNet 166.13 1248.68 12-MAR-09:20 17898.93 26-JUN-16:00
ExteriorLights:Electricity 9.88 0.00 01-JAN-07:30 1061.67 01-JAN-06:10
General:ExteriorLights:Electricity 9.88 0.00 01-JAN-07:30 1061.67 01-JAN-06:10
Electricity:HVAC 57.63 0.00 01-JAN-00:20 9721.63 28-JUN-16:00
Fans:Electricity 23.08 0.00 01-JAN-00:10 1996.39 02-JAN-06:10
General:Fans:Electricity 23.08 0.00 01-JAN-00:10 1996.39 02-JAN-06:10
Cooling:Electricity 34.15 0.00 01-JAN-00:10 7725.23 28-JUN-16:00
General:Cooling:Electricity 34.15 0.00 01-JAN-00:10 7725.23 28-JUN-16:00
Heating:Electricity 0.40 0.00 01-JAN-00:20 5954.07 02-JAN-06:20
General:Heating:Electricity 0.40 0.00 01-JAN-00:20 5954.07 02-JAN-06:20
Electricity:Plant 23.44 571.00 01-JAN-00:10 2786.77 27-JAN-12:30
WaterSystems:Electricity 23.44 571.00 01-JAN-00:10 2786.77 27-JAN-12:30
Water Heater:WaterSystems:Electricity 23.44 571.00 01-JAN-00:10 2786.77 27-JAN-12:30
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 20-JAN-10:30
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 20-JAN-10:30


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.01 0.00 01-JAN-00:10 4287.22 02-JAN-06:10
NaturalGas:HVAC 0.01 0.00 01-JAN-00:10 4287.22 02-JAN-06:10
Heating:NaturalGas 0.01 0.00 01-JAN-00:10 4287.22 02-JAN-06:10
General:Heating:NaturalGas 0.01 0.00 01-JAN-00:10 4287.22 02-JAN-06:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 06-MAR-13:00
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 06-MAR-13:00
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 25-JAN-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 25-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 255.10 0.00 01-JAN-00:10 57176.36 14-AUG-05:20
EnergyTransfer:Building 114.24 0.00 01-JAN-00:10 26844.27 28-AUG-05:20
EnergyTransfer:Zone:CORE_ZN 29.16 0.00 01-JAN-00:10 6187.43 03-JUL-05:10
Heating:EnergyTransfer 2.53 0.00 01-JAN-00:10 15901.00 02-JAN-06:10
Heating:EnergyTransfer:Zone:CORE_ZN 0.44 0.00 01-JAN-00:10 2728.18 02-JAN-06:10
General:Heating:EnergyTransfer 2.53 0.00 01-JAN-00:10 15901.00 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.44 0.00 01-JAN-00:10 2728.18 02-JAN-06:10
Cooling:EnergyTransfer 111.71 0.00 01-JAN-00:10 26844.27 28-AUG-05:20
Cooling:EnergyTransfer:Zone:CORE_ZN 28.72 0.00 01-JAN-00:10 6187.43 03-JUL-05:10
General:Cooling:EnergyTransfer 111.71 0.00 01-JAN-00:10 26844.27 28-AUG-05:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 28.72 0.00 01-JAN-00:10 6187.43 03-JUL-05:10
EnergyTransfer:Zone:PERIMETER_ZN_1 30.40 0.00 01-JAN-00:10 6302.13 18-SEP-05:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.68 0.00 01-JAN-00:10 3491.79 27-MAR-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.68 0.00 01-JAN-00:10 3491.79 27-MAR-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 29.71 0.00 01-JAN-00:10 6302.13 18-SEP-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 29.71 0.00 01-JAN-00:10 6302.13 18-SEP-05:20
EnergyTransfer:Zone:PERIMETER_ZN_2 16.97 0.00 01-JAN-00:10 4161.81 18-SEP-05:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.34 0.00 01-JAN-00:10 2966.80 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.34 0.00 01-JAN-00:10 2966.80 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 16.63 0.00 01-JAN-00:10 4161.81 18-SEP-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 16.63 0.00 01-JAN-00:10 4161.81 18-SEP-05:20
EnergyTransfer:Zone:PERIMETER_ZN_3 21.51 0.00 01-JAN-00:10 6184.69 18-SEP-05:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.68 0.00 01-JAN-00:10 5854.31 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.68 0.00 01-JAN-00:10 5854.31 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 20.84 0.00 01-JAN-00:10 6184.69 18-SEP-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 20.84 0.00 01-JAN-00:10 6184.69 18-SEP-05:20
EnergyTransfer:Zone:PERIMETER_ZN_4 16.19 0.00 01-JAN-00:10 4798.05 28-AUG-05:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.38 0.00 01-JAN-00:10 2737.19 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.38 0.00 01-JAN-00:10 2737.19 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 15.81 0.00 01-JAN-00:10 4798.05 28-AUG-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 15.81 0.00 01-JAN-00:10 4798.05 28-AUG-05:20
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 24-JAN-07:10 89.24 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 24-JAN-07:10 89.24 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 24-JAN-07:10 89.24 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 24-JAN-07:10 89.24 02-JAN-07:10
EnergyTransfer:HVAC 140.86 0.00 01-JAN-00:10 32977.08 05-SEP-05:20
CoolingCoils:EnergyTransfer 140.05 0.00 01-JAN-00:10 32977.08 05-SEP-05:20
HeatingCoils:EnergyTransfer 0.81 0.00 01-JAN-00:10 18254.83 02-JAN-06:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 24-JAN-07:10 89.24 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 24-JAN-07:10 89.24 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 24-JAN-07:10 89.24 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.440 -28.719 0.000 0.000 4.951 8.739 14.140 0.000 0.000 0.000 0.449 0.000 0.000 0.000 0.000 -0.000
PERIMETER_ZN_1 0.000 0.000 0.685 -29.715 0.000 0.000 3.766 5.449 10.719 20.152 0.000 2.285 0.000 0.000 -6.865 0.000 -3.212 -3.264
PERIMETER_ZN_2 0.000 0.000 0.344 -16.631 0.000 0.000 1.631 3.355 6.359 10.317 0.000 0.186 0.000 0.000 -3.479 0.000 -0.680 -1.402
PERIMETER_ZN_3 0.000 0.000 0.677 -20.838 0.000 0.000 3.804 5.949 10.719 6.008 0.000 0.304 0.001 0.000 -5.332 0.000 -0.953 -0.336
PERIMETER_ZN_4 0.000 0.000 0.384 -15.807 0.000 0.000 2.239 3.388 6.359 9.920 0.000 0.177 0.000 0.000 -3.809 0.000 -0.692 -2.159
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 13.288 27.049 0.000 0.000 0.000 -40.337 -0.001
Total Facility 0.000 0.000 2.530 -111.710 0.000 0.000 16.391 26.879 48.296 46.397 0.000 16.240 27.499 0.000 -19.486 0.000 -45.874 -7.161


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 12-OCT-05:01 0.00 0.00 0.00 -6639.84 0.00 0.00 52.64 32.22 486.79 0.00 0.00 0.00 6068.19 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 10-OCT-05:01 0.00 0.00 0.00 -7053.27 0.00 0.00 32.03 24.42 369.02 0.00 0.00 0.00 7489.46 0.00 -557.73 0.00 -303.93 0.00
PERIMETER_ZN_2 10-OCT-05:01 0.00 0.00 0.00 -4576.94 0.00 0.00 20.81 14.49 218.91 0.00 0.00 0.00 4664.32 0.00 -281.76 0.00 -59.83 0.00
PERIMETER_ZN_3 14-AUG-05:01 0.00 0.00 0.00 -6840.64 0.00 0.00 26.79 24.42 369.02 0.00 0.00 0.00 6650.79 0.00 -210.45 0.00 -19.92 0.00
PERIMETER_ZN_4 10-OCT-05:01 0.00 0.00 0.00 -5301.94 0.00 0.00 20.56 14.49 218.91 0.00 0.00 0.00 5390.98 0.00 -283.11 0.00 -59.89 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 10-OCT-05:01 0.00 0.00 0.00 -30308.79 0.00 0.00 154.42 110.04 1662.65 0.00 0.00 983.77 29419.99 0.00 -1515.40 0.00 -506.69 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-06:01 0.00 0.00 7535.19 0.00 0.00 0.00 79.08 32.22 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8133.28
PERIMETER_ZN_1 02-JAN-06:01 0.00 0.00 8845.88 0.00 0.00 0.00 59.04 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -736.05 0.00 -427.95 -8134.35
PERIMETER_ZN_2 02-JAN-06:01 0.00 0.00 5994.04 0.00 0.00 0.00 38.44 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -340.37 0.00 -44.39 -5881.12
PERIMETER_ZN_3 02-JAN-06:01 0.00 0.00 9133.89 0.00 0.00 0.00 66.89 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -469.57 0.00 -61.35 -9063.30
PERIMETER_ZN_4 02-JAN-06:01 0.00 0.00 6696.10 0.00 0.00 0.00 38.07 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -343.10 0.00 -45.61 -6578.85
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-06:01 0.00 0.00 38205.09 0.00 0.00 0.00 281.51 110.04 1662.65 0.00 0.00 1257.43 0.00 0.00 -1889.09 0.00 -579.31 -39048.32



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3421 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3421 0.1889 1.0000 Not calculated 0.0646 0.1889    
PSZ-AC:2 0.4072 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4072 0.1203 1.0000 Not calculated 0.0490 0.1203    
PSZ-AC:3 0.2898 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2898 0.1003 1.0000 Not calculated 0.0291 0.1003    
PSZ-AC:4 0.4026 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4026 0.1217 1.0000 Not calculated 0.0490 0.1217    
PSZ-AC:5 0.3406 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3406 0.0853 1.0000 Not calculated 0.0291 0.0853    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3421 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3421 1.0000 1.0000 Not calculated 0.0646 0.1889    
PSZ-AC:2 0.4072 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4072 1.0000 1.0000 Not calculated 0.0490 0.1203    
PSZ-AC:3 0.2898 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2898 1.0000 1.0000 Not calculated 0.0291 0.1003    
PSZ-AC:4 0.4026 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4026 1.0000 1.0000 Not calculated 0.0490 0.1217    
PSZ-AC:5 0.3406 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3406 1.0000 1.0000 Not calculated 0.0291 0.0853    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3421 0.3421 0.3421 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4072 0.4072 0.4072 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2898 0.2898 0.2898 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4026 0.4026 0.4026 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3406 0.3406 0.3406 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3421 0.3421 0.3421 0.3421 0.0646 1.0000
PSZ-AC:2 0.4072 0.4072 0.4072 0.4072 0.0490 1.0000
PSZ-AC:3 0.2898 0.2898 0.2898 0.2898 0.0291 1.0000
PSZ-AC:4 0.4026 0.4026 0.4026 0.4026 0.0490 1.0000
PSZ-AC:5 0.3406 0.3406 0.3406 0.3406 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3421 0.3421 0.3421 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4072 0.4072 0.4072 No 0.0490 0.4359 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2898 0.2898 0.2898 No 0.0291 0.4173 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4026 0.4026 0.4026 No 0.0490 0.4483 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3406 0.3406 0.3406 No 0.0291 0.4192 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3421 0.3421 0.3421 0.3421 0.0646 1.0000
PSZ-AC:2 0.4072 0.4072 0.4072 0.4072 0.0490 1.0000
PSZ-AC:3 0.2898 0.2898 0.2898 0.2898 0.0291 1.0000
PSZ-AC:4 0.4026 0.4026 0.4026 0.4026 0.0490 1.0000
PSZ-AC:5 0.3406 0.3406 0.3406 0.3406 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.17
Number of hours cooling loads not met 131.33
Number of hours not met 131.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.40 5954.07 0.01 4287.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 34.15 7725.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.88 2540.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.88 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 23.08 1996.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 23.44 2786.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 166.13
Natural Gas 0.00 0.01
Additional 0.00 0.00
Total 48.30 166.14


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 52.59
Space Heating 0.79
Space Cooling 66.80
Fans (All) 45.16
Service Water Heating 45.85
Receptacle Equipment 94.48
Miscellaneous (All) 325.01
Subtotal 325.01


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.01
Service Water Heating 0.00
Miscellaneous (All) 0.01
Subtotal 0.01


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 16.18
Space Heating 0.25
Space Cooling 20.55
Fans (All) 13.89
Service Water Heating 14.11
Receptacle Equipment 29.07
Miscellaneous 5.95


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2885. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365
HTGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL January 20.55 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 7242.50 1517.50 0.00 0.00 0.00
PERIMETER_ZN_1 7250.50 1509.50 0.00 0.00 0.00
PERIMETER_ZN_2 7126.33 1633.67 0.00 0.00 0.00
PERIMETER_ZN_3 7396.50 1363.50 0.00 0.00 0.00
PERIMETER_ZN_4 6953.33 1806.67 0.00 0.00 0.00
ATTIC 5334.83 940.83 876.67 1303.83 303.83
Min 5334.83 940.83 0.00 0.00 0.00
Max 7396.50 1806.67 876.67 1303.83 303.83
Average 6884.00 1461.94 146.11 217.31 50.64
Sum 41304.00 8771.67 876.67 1303.83 303.83


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 7336.50 1423.50 0.00 0.00 0.00
PERIMETER_ZN_1 7626.83 1133.17 0.00 0.00 0.00
PERIMETER_ZN_2 7618.00 1142.00 0.00 0.00 0.00
PERIMETER_ZN_3 7682.50 1077.50 0.00 0.00 0.00
PERIMETER_ZN_4 7573.17 1186.83 0.00 0.00 0.00
ATTIC 5483.17 1499.17 433.67 363.00 981.00
Min 5483.17 1077.50 0.00 0.00 0.00
Max 7682.50 1499.17 433.67 363.00 981.00
Average 7220.03 1243.69 72.28 60.50 163.50
Sum 43320.17 7462.17 433.67 363.00 981.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:25

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.121777E+10 4447.19 27-JAN-06:03 12.83 5.24 0.293678E+09 402.36 11-JAN-13:50 12.83 5.24
February 0.891212E+09 4061.58 01-FEB-06:03 5.00 3.59 0.265589E+09 402.35 23-FEB-16:00 17.00 10.81
March 0.132791E+10 5812.83 21-MAR-05:03 13.53 8.20 0.323942E+09 402.36 02-MAR-14:09 13.53 8.20
April 0.230693E+10 6551.16 17-APR-05:01 14.33 9.41 0.285380E+09 402.33 07-APR-13:30 14.33 9.41
May 0.297433E+10 6534.59 01-MAY-05:01 13.00 4.59 0.314541E+09 402.33 11-MAY-15:20 32.00 12.93
June 0.368571E+10 6446.27 21-JUN-05:01 18.00 8.30 0.317073E+09 427.18 19-JUN-14:09 18.00 8.30
July 0.352443E+10 6517.69 03-JUL-05:01 20.33 7.70 0.290317E+09 432.95 17-JUL-12:39 35.33 20.95
August 0.381154E+10 6274.78 24-AUG-05:01 19.83 9.70 0.332403E+09 443.03 28-AUG-13:09 37.83 20.53
September 0.328589E+10 6209.40 28-SEP-05:01 21.10 12.25 0.288378E+09 435.03 11-SEP-13:20 21.10 12.25
October 0.268540E+10 6640.33 12-OCT-05:01 7.00 2.99 0.299799E+09 413.67 02-OCT-14:09 7.00 2.99
November 0.182915E+10 6447.32 07-NOV-06:03 8.00 1.94 0.298010E+09 402.36 02-NOV-10:00 8.00 1.94
December 0.117974E+10 4405.09 27-DEC-06:03 6.00 2.08 0.280821E+09 402.36 13-DEC-14:50 6.00 2.08
                     
Annual Sum or Average 0.287200E+11         0.358993E+10        
Minimum of Months 0.891212E+09 4061.58   5.00 1.94 0.265589E+09 402.33   6.00 1.94
Maximum of Months 0.381154E+10 6640.33   21.10 12.25 0.332403E+09 443.03   37.83 20.95



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.185277E+10 4776.38 30-JAN-14:40 24.67 9.55 0.222582E+09 305.00 09-JAN-11:00 24.67 9.55
February 0.667468E+09 3208.37 01-FEB-15:30 15.50 6.96 0.196367E+09 305.01 14-FEB-13:30 18.50 13.14
March 0.804984E+09 2778.65 16-MAR-15:20 28.80 13.79 0.238180E+09 305.03 08-MAR-10:50 28.80 13.79
April 0.184341E+10 6810.99 17-APR-05:01 14.33 9.41 0.215852E+09 304.99 26-APR-12:09 29.00 10.71
May 0.230629E+10 6670.15 01-MAY-05:01 13.00 4.59 0.238468E+09 304.99 19-MAY-12:09 33.33 13.11
June 0.350491E+10 6787.19 19-JUN-05:01 22.17 10.17 0.240482E+09 327.33 19-JUN-12:09 37.17 17.20
July 0.362031E+10 6710.48 31-JUL-05:01 25.83 15.57 0.218706E+09 330.92 17-JUL-12:09 25.83 15.57
August 0.411319E+10 6907.96 14-AUG-05:01 26.00 16.58 0.251683E+09 341.85 28-AUG-12:09 36.33 20.98
September 0.383478E+10 6797.68 25-SEP-05:01 23.72 17.67 0.220793E+09 342.75 11-SEP-12:09 23.72 17.67
October 0.327118E+10 7053.25 10-OCT-05:01 17.67 11.62 0.229305E+09 350.56 02-OCT-12:09 17.67 11.62
November 0.240185E+10 6662.12 02-NOV-05:02 16.00 11.79 0.225437E+09 305.03 14-NOV-13:30 19.50 16.00
December 0.149372E+10 5031.38 26-DEC-14:00 23.00 10.16 0.210457E+09 305.00 13-DEC-11:30 23.00 10.16
                     
Annual Sum or Average 0.297149E+11         0.270831E+10        
Minimum of Months 0.667468E+09 2778.65   13.00 4.59 0.196367E+09 304.99   17.67 9.55
Maximum of Months 0.411319E+10 7053.25   28.80 17.67 0.251683E+09 350.56   37.17 20.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.395930E+09 3028.80 31-JAN-11:02 18.83 8.01 95520642.63 190.45 20-JAN-15:09 18.83 8.01
February 0.160822E+09 3114.02 23-FEB-15:01 17.83 10.29 85004254.00 190.45 01-FEB-15:09 17.83 10.29
March 0.350480E+09 3322.85 17-MAR-12:01 26.70 14.56 0.104179E+09 190.45 20-MAR-14:09 27.70 14.39
April 0.129969E+10 4495.12 17-APR-05:01 14.33 9.41 94729814.34 190.45 21-APR-14:09 28.17 10.52
May 0.174948E+10 4394.27 30-MAY-05:01 18.00 8.75 0.104662E+09 190.45 25-MAY-14:09 18.00 8.75
June 0.251638E+10 4496.34 19-JUN-05:01 22.17 10.17 0.105668E+09 190.46 19-JUN-10:09 34.17 14.95
July 0.250737E+10 4456.12 31-JUL-05:01 25.83 15.57 96072575.74 190.46 31-JUL-10:09 32.33 18.50
August 0.273747E+10 4568.71 14-AUG-05:01 26.00 16.58 0.110405E+09 196.11 14-AUG-10:20 34.33 19.88
September 0.221861E+10 4459.69 25-SEP-05:01 23.72 17.67 95804586.45 190.46 11-SEP-10:09 23.72 17.67
October 0.156245E+10 4576.92 10-OCT-05:01 17.67 11.62 99440278.63 190.45 23-OCT-14:09 22.17 12.82
November 0.807240E+09 4217.69 01-NOV-05:02 19.67 14.77 98146682.60 190.45 20-NOV-13:09 26.17 11.39
December 0.324989E+09 2995.56 26-DEC-11:02 20.33 8.94 90500121.72 190.45 27-DEC-13:09 19.00 10.04
                     
Annual Sum or Average 0.166309E+11         0.118013E+10        
Minimum of Months 0.160822E+09 2995.56   14.33 8.01 85004254.00 190.45   17.83 8.01
Maximum of Months 0.273747E+10 4576.92   26.70 17.67 0.110405E+09 196.11   34.33 19.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.361066E+09 1391.73 27-JAN-16:27 26.50 9.48 0.214179E+09 305.21 12-JAN-11:39 26.50 9.48
February 0.121412E+09 836.00 01-FEB-15:57 16.00 7.03 0.188361E+09 305.00 09-FEB-13:00 20.00 9.81
March 0.355711E+09 1591.04 17-MAR-15:55 26.60 14.13 0.234509E+09 306.37 01-MAR-11:00 26.60 14.13
April 0.143767E+10 6725.14 17-APR-05:01 14.33 9.41 0.215923E+09 304.99 26-APR-12:20 29.00 10.76
May 0.212801E+10 6604.95 01-MAY-05:01 13.00 4.59 0.238500E+09 304.99 31-MAY-12:20 33.33 12.79
June 0.326871E+10 6738.85 19-JUN-05:01 22.17 10.17 0.240238E+09 304.99 30-JUN-07:40 30.33 19.46
July 0.336899E+10 6649.10 31-JUL-05:01 25.83 15.57 0.218284E+09 305.03 14-JUL-10:09 25.83 15.57
August 0.361457E+10 6840.64 14-AUG-05:01 26.00 16.58 0.250578E+09 308.32 28-AUG-12:00 38.00 20.59
September 0.304255E+10 6605.26 27-SEP-05:01 20.00 13.62 0.217755E+09 305.02 25-SEP-07:10 20.00 13.62
October 0.188472E+10 6816.34 10-OCT-05:01 17.67 11.62 0.226499E+09 305.02 03-OCT-07:19 17.67 11.62
November 0.939344E+09 6042.44 01-NOV-05:02 19.67 14.77 0.223323E+09 305.01 02-NOV-10:00 24.00 15.31
December 0.315610E+09 1301.60 22-DEC-16:35 24.33 9.71 0.202620E+09 305.01 20-DEC-13:09 24.33 9.71
                     
Annual Sum or Average 0.208384E+11         0.267077E+10        
Minimum of Months 0.121412E+09 836.00   13.00 4.59 0.188361E+09 304.99   17.67 9.48
Maximum of Months 0.361457E+10 6840.64   26.60 16.58 0.250578E+09 308.32   38.00 20.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.449813E+09 1909.47 31-JAN-16:55 29.00 10.73 0.130285E+09 181.80 05-JAN-11:09 29.00 10.73
February 0.167025E+09 1337.48 28-FEB-16:53 19.00 9.75 0.114388E+09 182.76 10-FEB-11:30 19.00 9.75
March 0.332154E+09 1612.30 16-MAR-15:57 28.80 13.95 0.141438E+09 182.46 06-MAR-15:00 28.80 13.95
April 0.118355E+10 5199.08 17-APR-05:01 14.33 9.41 0.129186E+09 180.92 26-APR-12:20 29.00 10.76
May 0.160384E+10 5101.86 30-MAY-05:01 18.00 8.75 0.142497E+09 180.92 31-MAY-12:20 33.33 12.79
June 0.236474E+10 5190.24 19-JUN-05:01 22.17 10.17 0.143492E+09 180.93 30-JUN-09:50 33.83 19.15
July 0.231516E+10 5182.02 31-JUL-05:01 25.83 15.57 0.130011E+09 180.94 28-JUL-14:09 25.83 15.57
August 0.254270E+10 5277.42 21-AUG-05:01 24.67 16.53 0.149321E+09 180.94 02-AUG-08:00 24.67 16.53
September 0.214066E+10 5211.42 25-SEP-05:01 23.72 17.67 0.129761E+09 180.94 25-SEP-07:10 23.48 17.89
October 0.146473E+10 5301.92 10-OCT-05:01 17.67 11.62 0.135196E+09 180.97 13-OCT-07:10 9.00 2.51
November 0.876797E+09 4894.04 02-NOV-05:02 16.00 11.79 0.133634E+09 181.23 09-NOV-08:09 14.67 6.50
December 0.365875E+09 2069.25 26-DEC-16:23 23.00 10.75 0.122831E+09 181.43 20-DEC-11:30 23.00 10.75
                     
Annual Sum or Average 0.158071E+11         0.160204E+10        
Minimum of Months 0.167025E+09 1337.48   14.33 8.75 0.114388E+09 180.92   9.00 2.51
Maximum of Months 0.254270E+10 5301.92   29.00 17.67 0.149321E+09 182.76   33.83 19.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27 1.81 0.00 0.00 01-JAN-00:10 4.27 1.81
February 0.00 0.00 01-FEB-00:10 11.90 4.43 0.00 0.00 01-FEB-00:10 11.90 4.43
March 0.00 0.00 01-MAR-00:10 11.85 8.83 0.00 0.00 01-MAR-00:10 11.85 8.83
April 0.00 0.00 01-APR-00:10 15.28 7.34 0.00 0.00 01-APR-00:10 15.28 7.34
May 0.00 0.00 01-MAY-00:10 19.10 7.18 0.00 0.00 01-MAY-00:10 19.10 7.18
June 0.00 0.00 01-JUN-00:10 25.83 11.09 0.00 0.00 01-JUN-00:10 25.83 11.09
July 0.00 0.00 01-JUL-00:05 27.73 14.60 0.00 0.00 01-JUL-00:10 27.73 14.60
August 0.00 0.00 01-AUG-00:10 29.40 18.35 0.00 0.00 01-AUG-00:10 29.40 18.35
September 0.00 0.00 01-SEP-00:10 26.22 16.66 0.00 0.00 01-SEP-00:10 26.22 16.66
October 0.00 0.00 01-OCT-00:10 25.15 15.51 0.00 0.00 01-OCT-00:10 25.15 15.51
November 0.00 0.00 01-NOV-00:10 17.23 10.27 0.00 0.00 01-NOV-00:10 17.23 10.27
December 0.00 0.00 01-DEC-00:10 9.20 2.98 0.00 0.00 01-DEC-00:10 9.20 2.98
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   4.27 1.81 0.00 0.00   4.27 1.81
Maximum of Months 0.00 0.00   29.40 18.35 0.00 0.00   29.40 18.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 20465134.30 7535.21 02-JAN-06:01 4.33
February 0.00 0.00 01-FEB-00:10 11.90
March 11949107.54 622.20 20-MAR-17:03 28.53
April 41494274.36 1066.16 14-APR-17:01 34.83
May 62935062.11 1194.83 31-MAY-17:01 36.83
June 87384130.19 1548.36 28-JUN-17:01 41.83
July 63434789.32 1361.58 20-JUL-17:01 39.00
August 66572497.03 1474.00 25-AUG-17:01 40.67
September 54254294.23 1218.79 07-SEP-17:01 37.02
October 28376505.57 979.59 06-OCT-17:01 33.67
November 3095764.69 420.25 01-NOV-17:02 25.67
December 92275.56 110.22 21-DEC-18:02 20.50
         
Annual Sum or Average 0.440054E+09      
Minimum of Months 0.00 0.00   4.33
Maximum of Months 87384130.19 7535.21   41.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 38242415.28 8845.89 02-JAN-06:01 4.33
February 93504995.93 6506.38 13-FEB-06:02 8.00
March 0.130671E+09 8497.00 27-MAR-05:01 2.52
April 43567157.04 878.36 14-APR-17:01 34.83
May 58512131.88 986.80 31-MAY-17:01 36.83
June 73710244.97 1210.12 28-JUN-17:01 41.83
July 54290449.38 1082.22 20-JUL-17:23 39.00
August 57196790.80 1149.78 25-AUG-17:01 40.67
September 46143992.83 938.15 07-SEP-17:01 37.02
October 25943179.97 828.37 04-OCT-17:11 33.67
November 5607713.70 1245.64 24-NOV-07:10 4.50
December 57269081.97 2565.47 06-DEC-07:10 -0.5
         
Annual Sum or Average 0.684659E+09      
Minimum of Months 5607713.70 828.37   -0.5
Maximum of Months 0.130671E+09 8845.89   41.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 37061915.01 5994.05 02-JAN-06:01 4.33
February 22919170.91 4354.97 13-FEB-06:02 8.00
March 32586155.68 5536.96 27-MAR-05:01 2.52
April 27189921.10 577.05 14-APR-17:22 34.50
May 37325498.20 635.23 31-MAY-17:23 36.50
June 46894474.65 772.99 28-JUN-17:23 41.50
July 34841467.83 698.38 20-JUL-17:23 39.00
August 37451050.74 728.89 25-AUG-17:23 40.00
September 31187668.14 623.77 07-SEP-17:22 36.65
October 20459503.04 559.11 04-OCT-17:11 33.67
November 6763226.42 320.35 01-NOV-17:12 25.33
December 9278742.40 3190.55 18-DEC-06:02 3.83
         
Annual Sum or Average 0.343959E+09      
Minimum of Months 6763226.42 320.35   2.52
Maximum of Months 46894474.65 5994.05   41.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.113275E+09 9133.91 02-JAN-06:01 4.33
February 65645826.14 6574.16 06-FEB-06:03 9.00
March 88857095.35 8425.41 27-MAR-05:01 2.52
April 41958690.20 903.29 14-APR-17:01 34.83
May 57729677.89 992.56 31-MAY-17:01 36.83
June 73726039.05 1232.49 28-JUN-17:01 41.83
July 54564831.28 1093.68 20-JUL-17:01 39.00
August 58677109.16 1178.93 25-AUG-17:01 40.67
September 48399494.65 989.15 07-SEP-17:01 37.02
October 30497698.00 865.66 04-OCT-17:11 33.67
November 8246572.30 460.62 01-NOV-17:12 25.33
December 34994232.29 8486.71 18-DEC-06:02 3.83
         
Annual Sum or Average 0.676572E+09      
Minimum of Months 8246572.30 460.62   2.52
Maximum of Months 0.113275E+09 9133.91   41.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 50896479.65 6696.11 02-JAN-06:01 4.33
February 51276931.99 5108.02 13-FEB-06:02 8.00
March 58471991.99 6182.39 27-MAR-05:01 2.52
April 26053201.88 587.67 14-APR-17:22 34.50
May 36000836.93 655.52 31-MAY-17:23 36.50
June 25299510.50 779.10 28-JUN-17:23 41.50
July 30223385.39 730.75 18-JUL-17:23 38.00
August 27632591.64 739.00 25-AUG-17:23 40.00
September 28896628.64 645.21 07-SEP-17:22 36.65
October 21381938.62 587.55 03-OCT-17:23 33.50
November 8608597.53 398.56 01-NOV-05:03 19.67
December 19715177.43 3574.01 18-DEC-06:02 3.83
         
Annual Sum or Average 0.384457E+09      
Minimum of Months 8608597.53 398.56   2.52
Maximum of Months 58471991.99 6696.11   41.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.729889E+09 743.94 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.660244E+09 743.94 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.791184E+09 743.94 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.696458E+09 743.94 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.760537E+09 743.94 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.757753E+09 743.94 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.699242E+09 743.94 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.791184E+09 743.94 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.696458E+09 743.94 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.729889E+09 743.94 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.727106E+09 743.94 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.699242E+09 743.94 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.873919E+10     0.141401E+11    
Minimum of Months 0.660244E+09 743.94   0.107295E+10 973.59  
Maximum of Months 0.791184E+09 743.94   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.449068E+09 553.69 20-JAN-16:00 0.899552E+09 738.04 02-JAN-08:09
February 0.410915E+09 549.27 10-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.485847E+09 542.95 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.427001E+09 520.98 04-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.479936E+09 508.18 05-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.491893E+09 511.59 22-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.445515E+09 523.76 27-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.501621E+09 547.42 04-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.427368E+09 523.29 19-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.445844E+09 529.00 27-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.448628E+09 563.96 28-NOV-16:30 0.888667E+09 738.04 01-NOV-07:10
December 0.434980E+09 563.96 01-DEC-16:30 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.544862E+10     0.107191E+11    
Minimum of Months 0.410915E+09 508.18   0.813362E+09 738.04  
Maximum of Months 0.501621E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.287745E+09 329.47 20-JAN-16:00 0.533626E+09 437.82 02-JAN-08:09
February 0.258446E+09 325.94 10-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.300734E+09 318.22 09-MAR-16:00 0.565383E+09 437.82 01-MAR-08:09
April 0.262234E+09 300.75 03-APR-15:00 0.511694E+09 437.82 03-APR-07:10
May 0.286036E+09 300.05 25-MAY-15:30 0.549505E+09 437.82 01-MAY-07:10
June 0.285991E+09 302.86 02-JUN-15:00 0.542644E+09 437.82 01-JUN-07:10
July 0.262552E+09 310.69 13-JUL-15:00 0.518151E+09 437.82 03-JUL-07:10
August 0.300048E+09 324.49 04-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.263944E+09 309.73 29-SEP-14:30 0.510887E+09 437.82 01-SEP-07:10
October 0.283017E+09 319.73 31-OCT-15:00 0.534030E+09 437.82 02-OCT-07:10
November 0.286421E+09 334.55 28-NOV-16:30 0.527169E+09 437.82 01-NOV-07:10
December 0.277897E+09 334.55 01-DEC-16:30 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.335507E+10     0.635872E+10    
Minimum of Months 0.258446E+09 300.05   0.482497E+09 437.82  
Maximum of Months 0.300734E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.520465E+09 555.48 20-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.463254E+09 551.70 10-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.539622E+09 547.04 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.463245E+09 523.31 04-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.494421E+09 512.62 26-MAY-08:30 0.926320E+09 738.04 01-MAY-07:10
June 0.490470E+09 500.86 12-JUN-09:30 0.914754E+09 738.04 01-JUN-07:10
July 0.452060E+09 521.81 28-JUL-12:39 0.873466E+09 738.04 03-JUL-07:10
August 0.528383E+09 548.31 04-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.468826E+09 540.26 29-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.513170E+09 551.13 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.514541E+09 563.96 28-NOV-16:30 0.888667E+09 738.04 01-NOV-07:10
December 0.500385E+09 563.96 01-DEC-16:30 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.594884E+10     0.107191E+11    
Minimum of Months 0.452060E+09 500.86   0.813362E+09 738.04  
Maximum of Months 0.539622E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.288485E+09 329.97 20-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.259494E+09 327.49 03-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.304135E+09 327.13 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.265925E+09 319.55 04-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.289722E+09 312.98 05-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.288974E+09 312.19 27-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.268560E+09 317.23 27-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.306988E+09 325.85 04-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.266685E+09 322.97 29-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.286169E+09 328.42 27-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.284656E+09 334.55 28-NOV-16:30 0.527169E+09 437.82 01-NOV-07:10
December 0.277755E+09 334.55 01-DEC-16:30 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.338755E+10     0.635872E+10    
Minimum of Months 0.259494E+09 312.19   0.482497E+09 437.82  
Maximum of Months 0.306988E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.729889E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.696458E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.760537E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.757753E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.699242E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.696458E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.729889E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.727106E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.699242E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.873919E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.449068E+09 0.899552E+09 0.00 0.00 0.00 0.00 6434236.95 0.468734E+09
February 0.488155E+09 0.410915E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.522384E+09
March 0.590925E+09 0.485847E+09 0.953087E+09 0.00 0.00 0.00 0.00 20033386.23 0.477328E+09
April 0.513848E+09 0.427001E+09 0.862580E+09 0.00 0.00 0.00 0.00 0.171192E+09 0.162188E+09
May 0.565233E+09 0.479936E+09 0.926320E+09 0.00 0.00 0.00 0.00 0.307678E+09 87071708.00
June 0.565233E+09 0.491893E+09 0.914754E+09 0.00 0.00 0.00 0.00 0.515711E+09 20786826.93
July 0.513848E+09 0.445515E+09 0.873466E+09 0.00 0.00 0.00 0.00 0.414842E+09 18035469.54
August 0.590925E+09 0.501621E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.427446E+09 30307295.16
September 0.513848E+09 0.427368E+09 0.861220E+09 0.00 0.00 0.00 0.00 0.283598E+09 66341263.02
October 0.539540E+09 0.445844E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.122682E+09 0.290456E+09
November 0.539540E+09 0.448628E+09 0.888667E+09 0.00 0.00 0.00 0.00 14405615.77 0.451377E+09
December 0.513848E+09 0.434980E+09 0.872785E+09 0.00 0.00 0.00 0.00 727533.68 0.616760E+09
                   
Annual Sum or Average 0.647448E+10 0.544862E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.228475E+10 0.321177E+10
Minimum of Months 0.488155E+09 0.410915E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 18035469.54
Maximum of Months 0.590925E+09 0.501621E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.515711E+09 0.616760E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.287745E+09 0.533626E+09 0.00 0.00 0.00 0.00 268757.80 0.100319E+09
February 0.211974E+09 0.258446E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 77370937.97
March 0.256600E+09 0.300734E+09 0.565383E+09 0.00 0.00 0.00 0.00 756856.49 0.100548E+09
April 0.223130E+09 0.262234E+09 0.511694E+09 0.00 0.00 0.00 0.00 12640672.25 40401215.95
May 0.245443E+09 0.286036E+09 0.549505E+09 0.00 0.00 0.00 0.00 25152789.15 25478620.26
June 0.245443E+09 0.285991E+09 0.542644E+09 0.00 0.00 0.00 0.00 49718808.19 10140305.67
July 0.223130E+09 0.262552E+09 0.518151E+09 0.00 0.00 0.00 0.00 42094125.90 12400083.24
August 0.256600E+09 0.300048E+09 0.565383E+09 0.00 0.00 0.00 0.00 29387001.42 14794054.26
September 0.223130E+09 0.263944E+09 0.510887E+09 0.00 0.00 0.00 0.00 18668962.53 26482225.14
October 0.234287E+09 0.283017E+09 0.534030E+09 0.00 0.00 0.00 0.00 6515745.83 68496785.94
November 0.234287E+09 0.286421E+09 0.527169E+09 0.00 0.00 0.00 0.00 548910.59 0.101370E+09
December 0.223130E+09 0.277897E+09 0.517747E+09 0.00 0.00 0.00 0.00 53049.20 0.102296E+09
                   
Annual Sum or Average 0.281144E+10 0.335507E+10 0.635872E+10 0.00 0.00 0.00 0.00 0.185806E+09 0.680097E+09
Minimum of Months 0.211974E+09 0.258446E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 10140305.67
Maximum of Months 0.256600E+09 0.300734E+09 0.565383E+09 0.00 0.00 0.00 0.00 49718808.19 0.102296E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.520465E+09 0.899552E+09 0.00 0.00 0.00 0.00 1020308.58 0.139374E+09
February 0.488155E+09 0.463254E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.110621E+09
March 0.590925E+09 0.539622E+09 0.953087E+09 0.00 0.00 0.00 0.00 1563529.18 0.143216E+09
April 0.513848E+09 0.463245E+09 0.862580E+09 0.00 0.00 0.00 0.00 23384088.49 54945052.15
May 0.565233E+09 0.494421E+09 0.926320E+09 0.00 0.00 0.00 0.00 43588412.52 34902245.19
June 0.565233E+09 0.490470E+09 0.914754E+09 0.00 0.00 0.00 0.00 77657545.62 13801593.47
July 0.513848E+09 0.452060E+09 0.873466E+09 0.00 0.00 0.00 0.00 66202458.38 16656821.59
August 0.590925E+09 0.528383E+09 0.953087E+09 0.00 0.00 0.00 0.00 46538261.66 19613965.00
September 0.513848E+09 0.468826E+09 0.861220E+09 0.00 0.00 0.00 0.00 30739120.29 35889182.80
October 0.539540E+09 0.513170E+09 0.900233E+09 0.00 0.00 0.00 0.00 11656263.32 95046426.05
November 0.539540E+09 0.514541E+09 0.888667E+09 0.00 0.00 0.00 0.00 1489092.67 0.144008E+09
December 0.513848E+09 0.500385E+09 0.872785E+09 0.00 0.00 0.00 0.00 265427.05 0.145408E+09
                   
Annual Sum or Average 0.647448E+10 0.594884E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.304105E+09 0.953482E+09
Minimum of Months 0.488155E+09 0.452060E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 13801593.47
Maximum of Months 0.590925E+09 0.539622E+09 0.953087E+09 0.00 0.00 0.00 0.00 77657545.62 0.145408E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.288485E+09 0.533626E+09 0.00 0.00 0.00 0.00 371516.79 0.102169E+09
February 0.289580E+09 0.259494E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 77440784.85
March 0.350544E+09 0.304135E+09 0.565383E+09 0.00 0.00 0.00 0.00 838676.81 0.101584E+09
April 0.304821E+09 0.265925E+09 0.511694E+09 0.00 0.00 0.00 0.00 11294323.68 43280584.39
May 0.335303E+09 0.289722E+09 0.549505E+09 0.00 0.00 0.00 0.00 22947065.35 27054874.57
June 0.335303E+09 0.288974E+09 0.542644E+09 0.00 0.00 0.00 0.00 46506418.35 10729625.02
July 0.304821E+09 0.268560E+09 0.518151E+09 0.00 0.00 0.00 0.00 41067907.55 12774386.86
August 0.350544E+09 0.306988E+09 0.565383E+09 0.00 0.00 0.00 0.00 28567723.77 14849791.88
September 0.304821E+09 0.266685E+09 0.510887E+09 0.00 0.00 0.00 0.00 18057783.83 26895260.42
October 0.320062E+09 0.286169E+09 0.534030E+09 0.00 0.00 0.00 0.00 6605050.05 69724092.01
November 0.320062E+09 0.284656E+09 0.527169E+09 0.00 0.00 0.00 0.00 630599.72 0.102865E+09
December 0.304821E+09 0.277755E+09 0.517747E+09 0.00 0.00 0.00 0.00 51529.50 0.102505E+09
                   
Annual Sum or Average 0.384075E+10 0.338755E+10 0.635872E+10 0.00 0.00 0.00 0.00 0.176939E+09 0.691872E+09
Minimum of Months 0.289580E+09 0.259494E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 10729625.02
Maximum of Months 0.350544E+09 0.306988E+09 0.565383E+09 0.00 0.00 0.00 0.00 46506418.35 0.102865E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.139301E+10 0.235074E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.795377E+09 0.239203E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.932511E+09 0.319318E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.121128E+10 0.438517E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.130692E+10 0.466493E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.109178E+10 0.468437E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.772894E+09 0.420927E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.969508E+09 0.393369E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.844806E+09 0.315710E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133367E+10 0.290239E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.114990E+10 0.236679E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148658E+10 0.209721E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.132882E+11 0.403369E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.772894E+09 0.209721E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148658E+10 0.468437E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 743.94 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 743.94 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 743.94 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 743.94 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 743.94 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 743.94 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 743.94 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 743.94 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 743.94 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 743.94 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 743.94 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 743.94 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 553.69 20-JAN-16:00 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 626.44 31-JAN-17:10 2495.56 12-JAN-07:03
February 732.70 01-FEB-08:09 549.27 10-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2581.70 01-FEB-07:03
March 732.70 01-MAR-08:09 542.95 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 688.42 20-MAR-17:00 2958.60 27-MAR-06:10
April 732.70 03-APR-07:10 520.98 04-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 1531.25 14-APR-16:10 1926.34 21-APR-06:03
May 732.70 01-MAY-07:10 508.18 05-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 1811.28 31-MAY-16:10 1517.07 01-MAY-06:05
June 732.70 01-JUN-07:10 511.59 22-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 2437.73 28-JUN-16:03 682.89 21-JUN-06:05
July 732.70 03-JUL-07:10 523.76 27-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 2092.44 20-JUL-16:03 250.23 27-JUL-06:10
August 732.70 01-AUG-07:10 547.42 04-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 2307.08 25-AUG-16:03 661.52 24-AUG-06:10
September 732.70 01-SEP-07:10 523.29 19-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 1898.76 08-SEP-16:03 1027.70 22-SEP-06:10
October 732.70 02-OCT-07:10 529.00 27-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 1467.81 03-OCT-16:05 2662.61 25-OCT-06:03
November 732.70 01-NOV-07:10 563.96 28-NOV-16:30 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 539.25 01-NOV-16:10 2635.21 24-NOV-07:03
December 732.70 01-DEC-08:09 563.96 01-DEC-16:30 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 46.58 21-DEC-14:55 3340.50 05-DEC-07:10
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   508.18   738.04   0.00 0.00 0.00 0.00 0.00   250.23  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 2437.73   3340.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 329.47 20-JAN-16:00 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 5.94 31-JAN-14:00 146.17 01-JAN-01:00
February 434.65 01-FEB-08:09 325.94 10-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 204.38 02-FEB-23:00
March 434.65 01-MAR-08:09 318.22 09-MAR-16:00 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 12.65 15-MAR-13:00 168.53 28-MAR-04:00
April 434.65 03-APR-07:10 300.75 03-APR-15:00 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 77.40 30-APR-14:53 118.37 16-APR-09:00
May 434.65 01-MAY-07:10 300.05 25-MAY-15:30 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 92.50 31-MAY-18:10 80.97 23-MAY-05:00
June 434.65 01-JUN-07:10 302.86 02-JUN-15:00 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 156.48 30-JUN-18:10 46.35 13-JUN-04:00
July 434.65 03-JUL-07:10 310.69 13-JUL-15:00 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 160.35 22-JUL-17:45 86.73 17-JUL-19:52
August 434.65 01-AUG-07:10 324.49 04-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 140.07 13-AUG-16:05 119.84 05-AUG-17:22
September 434.65 01-SEP-07:10 309.73 29-SEP-14:30 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 84.46 17-SEP-13:00 91.93 03-SEP-05:00
October 434.65 02-OCT-07:10 319.73 31-OCT-15:00 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 57.53 03-OCT-18:10 206.95 22-OCT-13:52
November 434.65 01-NOV-07:10 334.55 28-NOV-16:30 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 12.86 19-NOV-14:55 186.99 29-NOV-02:00
December 434.65 01-DEC-08:09 334.55 01-DEC-16:30 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 4.71 25-DEC-14:00 153.75 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   300.05   437.82   0.00 0.00 0.00 0.00 0.00   46.35  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 160.35   206.95  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 555.48 20-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 30.30 16-JAN-11:53 198.03 01-JAN-01:00
February 732.70 01-FEB-08:09 551.70 10-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 295.02 02-FEB-23:00
March 732.70 01-MAR-08:09 547.04 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 24.27 18-MAR-17:02 245.46 28-MAR-04:00
April 732.70 03-APR-07:10 523.31 04-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 148.51 30-APR-14:53 145.87 21-APR-06:00
May 732.70 01-MAY-07:10 512.62 26-MAY-08:30 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 141.18 31-MAY-18:10 119.39 23-MAY-05:00
June 732.70 01-JUN-07:10 500.86 12-JUN-09:30 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 237.22 30-JUN-18:10 67.85 13-JUN-04:00
July 732.70 03-JUL-07:10 521.81 28-JUL-12:39 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 238.97 22-JUL-17:45 120.19 17-JUL-19:52
August 732.70 01-AUG-07:10 548.31 04-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 209.60 13-AUG-16:05 169.52 05-AUG-17:22
September 732.70 01-SEP-07:10 540.26 29-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 137.44 17-SEP-12:00 131.72 03-SEP-05:00
October 732.70 02-OCT-07:10 551.13 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 92.26 03-OCT-18:10 280.19 22-OCT-13:52
November 732.70 01-NOV-07:10 563.96 28-NOV-16:30 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 46.29 19-NOV-14:55 270.44 29-NOV-02:00
December 732.70 01-DEC-08:09 563.96 01-DEC-16:30 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 19.22 25-DEC-15:53 225.75 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   500.86   738.04   0.00 0.00 0.00 0.00 0.00   67.85  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 238.97   295.02  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 329.97 20-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 11.98 16-JAN-11:53 150.54 01-JAN-01:00
February 434.65 01-FEB-08:09 327.49 03-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 209.41 02-FEB-23:00
March 434.65 01-MAR-08:09 327.13 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 12.65 15-MAR-12:55 170.76 28-MAR-04:00
April 434.65 03-APR-07:10 319.55 04-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 79.12 30-APR-14:43 121.17 26-APR-18:02
May 434.65 01-MAY-07:10 312.98 05-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 74.27 31-MAY-18:10 83.81 23-MAY-05:00
June 434.65 01-JUN-07:10 312.19 27-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 140.70 30-JUN-18:03 48.99 13-JUN-04:00
July 434.65 03-JUL-07:10 317.23 27-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 158.16 22-JUL-18:00 86.37 17-JUL-19:52
August 434.65 01-AUG-07:10 325.85 04-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 143.04 13-AUG-16:00 118.59 05-AUG-17:22
September 434.65 01-SEP-07:10 322.97 29-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 81.40 17-SEP-12:00 90.54 03-SEP-05:00
October 434.65 02-OCT-07:10 328.42 27-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 57.45 01-OCT-14:10 193.60 22-OCT-13:52
November 434.65 01-NOV-07:10 334.55 28-NOV-16:30 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 16.35 19-NOV-13:00 187.40 29-NOV-02:00
December 434.65 01-DEC-08:09 334.55 01-DEC-16:30 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 5.67 25-DEC-14:00 153.75 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   312.19   437.82   0.00 0.00 0.00 0.00 0.00   48.99  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 158.16   209.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1735.79 28-JAN-07:53 4629.77 09-JAN-13:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1401.55 02-FEB-06:00 5700.85 28-FEB-13:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1458.27 19-MAR-07:52 6167.28 26-MAR-12:50
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1657.23 22-APR-06:42 6444.18 27-APR-12:50
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1697.56 14-MAY-06:32 6289.53 27-MAY-12:50
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1465.00 16-JUN-06:03 6158.47 25-JUN-12:50
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1577.25 03-JUL-05:55 6155.72 27-JUL-13:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1650.45 25-AUG-06:42 5957.04 07-AUG-13:40
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1690.23 17-SEP-04:55 5589.48 07-SEP-13:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1576.64 14-OCT-01:00 5453.41 26-OCT-12:40
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1521.13 24-NOV-07:33 5101.17 14-NOV-13:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1830.92 21-DEC-07:05 4258.64 14-DEC-13:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1401.55   4258.64  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1830.92   6444.18  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 4447.19 27-JAN-06:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
February 4061.58 01-FEB-06:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
March 5812.83 21-MAR-05:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
April 6551.16 17-APR-05:01 956.87 289.96 4381.15 0.00 0.00 0.00 0.00 0.00 0.00
May 6534.59 01-MAY-05:01 956.87 289.96 4381.15 0.00 0.00 0.00 0.00 0.00 0.00
June 6446.27 21-JUN-05:01 956.87 289.96 4381.15 0.00 0.00 0.00 0.00 0.00 0.00
July 6517.69 03-JUL-05:01 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
August 6274.78 24-AUG-05:01 850.55 257.74 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
September 6209.40 28-SEP-05:01 850.55 257.74 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
October 6640.33 12-OCT-05:01 744.23 225.53 3407.56 0.00 0.00 0.00 0.00 0.00 0.00
November 6447.32 07-NOV-06:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
December 4405.09 27-DEC-06:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 4061.58   318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6640.33   1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4776.38 30-JAN-14:40 732.70 411.63 738.04 0.00 0.00 0.00 0.00 17.51 0.00
February 3208.37 01-FEB-15:30 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 0.00 185.87
March 2778.65 16-MAR-15:20 732.70 411.63 738.04 0.00 0.00 0.00 0.00 110.78 0.00
April 6810.99 17-APR-05:01 725.37 219.81 3321.19 0.00 0.00 0.00 0.00 0.00 293.21
May 6670.15 01-MAY-05:01 725.37 219.81 3321.19 0.00 0.00 0.00 0.00 0.00 349.03
June 6787.19 19-JUN-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 161.63
July 6710.48 31-JUL-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 67.61
August 6907.96 14-AUG-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 82.78
September 6797.68 25-SEP-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 134.30
October 7053.25 10-OCT-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 303.93
November 6662.12 02-NOV-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 259.69
December 5031.38 26-DEC-14:00 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 0.00 19.49
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2778.65   483.58 146.54 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7053.25   1465.40 823.26 3690.21 0.00 0.00 0.00 0.00 110.78 349.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3028.80 31-JAN-11:02 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 5.35
February 3114.02 23-FEB-15:01 3042.52 2132.85 3064.72 0.00 0.00 0.00 0.00 0.00 14.36
March 3322.85 17-MAR-12:01 3042.52 1876.38 3064.72 0.00 0.00 0.00 0.00 3.35 0.00
April 4495.12 17-APR-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 51.74
May 4394.27 30-MAY-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 32.59
June 4496.34 19-JUN-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 31.84
July 4456.12 31-JUL-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 14.39
August 4568.71 14-AUG-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 14.21
September 4459.69 25-SEP-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 22.48
October 4576.92 10-OCT-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 59.83
November 4217.69 01-NOV-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 8.11
December 2995.56 26-DEC-11:02 2607.88 1486.52 2626.90 0.00 0.00 0.00 0.00 0.00 3.15
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2995.56   286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4576.92   3042.52 2132.85 3064.72 0.00 0.00 0.00 0.00 3.35 59.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1391.73 27-JAN-16:27 2198.10 1511.34 2214.13 0.00 0.00 0.00 0.00 4.30 0.00
February 836.00 01-FEB-15:57 2198.10 1535.63 2214.13 0.00 0.00 0.00 0.00 0.00 11.98
March 1591.04 17-MAR-15:55 2930.79 1858.87 2952.17 0.00 0.00 0.00 0.00 7.78 0.00
April 6725.14 17-APR-05:01 725.37 219.81 3321.19 0.00 0.00 0.00 0.00 0.00 74.02
May 6604.95 01-MAY-05:01 725.37 219.81 3321.19 0.00 0.00 0.00 0.00 0.00 102.19
June 6738.85 19-JUN-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 45.64
July 6649.10 31-JUL-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 18.49
August 6840.64 14-AUG-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 19.92
September 6605.26 27-SEP-05:01 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 51.73
October 6816.34 10-OCT-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 83.04
November 6042.44 01-NOV-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 11.41
December 1301.60 22-DEC-16:35 2930.79 2138.18 2952.17 0.00 0.00 0.00 0.00 0.49 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 836.00   483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6840.64   2930.79 2138.18 3690.21 0.00 0.00 0.00 0.00 7.78 102.19



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1909.47 31-JAN-16:55 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 4.98 0.00
February 1337.48 28-FEB-16:53 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 7.24
March 1612.30 16-MAR-15:57 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 9.30 0.00
April 5199.08 17-APR-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 51.93
May 5101.86 30-MAY-05:01 430.30 130.39 1970.17 0.00 0.00 0.00 0.00 0.00 33.18
June 5190.24 19-JUN-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 29.62
July 5182.02 31-JUL-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 14.16
August 5277.42 21-AUG-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 14.54
September 5211.42 25-SEP-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 22.27
October 5301.92 10-OCT-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 59.89
November 4894.04 02-NOV-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 46.91
December 2069.25 26-DEC-16:23 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 1.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1337.48   286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5301.92   1738.59 976.74 2189.08 0.00 0.00 0.00 0.00 9.30 59.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 787.12 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 963.03 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 979.86 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1235.04 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1055.12 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1234.46 0.00
July 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 690.66 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 612.00 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 689.98 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 499.36 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1307.31 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1053.50 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 499.36 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1307.31 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.124612E+11 13725.18 31-JAN-16:49 2572333.38 4287.22 02-JAN-06:10
February 0.106402E+11 12018.95 01-FEB-15:30 0.00 0.00 01-FEB-00:10
March 0.126830E+11 13297.68 16-MAR-15:39 1735134.53 2356.48 27-MAR-05:10
April 0.129010E+11 15590.30 14-APR-15:50 0.00 0.00 01-APR-00:10
May 0.145711E+11 15981.75 31-MAY-15:39 0.00 0.00 01-MAY-00:10
June 0.161191E+11 17898.93 26-JUN-15:00 0.00 0.00 01-JUN-00:10
July 0.156020E+11 17630.23 31-JUL-15:00 0.00 0.00 01-JUL-00:10
August 0.171858E+11 17840.81 14-AUG-15:39 0.00 0.00 01-AUG-00:10
September 0.150842E+11 17387.65 06-SEP-15:00 0.00 0.00 01-SEP-00:10
October 0.140932E+11 17131.54 02-OCT-14:20 0.00 0.00 01-OCT-00:10
November 0.128619E+11 14701.81 01-NOV-14:30 0.00 0.00 01-NOV-00:10
December 0.119273E+11 13222.18 22-DEC-15:09 892742.81 826.82 18-DEC-06:10
             
Annual Sum or Average 0.166130E+12     5200210.72    
Minimum of Months 0.106402E+11 12018.95   0.00 0.00  
Maximum of Months 0.171858E+11 17898.93   2572333.38 4287.22  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.227565E+10 0.103455E+10 0.405300E+10 0.00 0.189481E+10 0.01 71713340.02 0.107928E+10 0.00 0.00 0.00 0.205220E+10 0.00
February 0.205235E+10 0.860174E+09 0.366466E+10 0.00 0.170969E+10 0.00 72601092.91 0.428550E+09 0.00 0.00 0.00 0.185212E+10 0.00
March 0.242152E+10 0.853606E+09 0.429420E+10 0.00 0.207295E+10 0.00 0.102247E+09 0.872896E+09 0.00 0.00 0.00 0.206554E+10 0.00
April 0.211486E+10 0.731187E+09 0.388642E+10 0.00 0.182590E+10 0.00 0.00 0.241845E+10 0.00 0.00 0.00 0.192422E+10 0.00
May 0.231065E+10 0.673036E+09 0.417360E+10 0.00 0.201648E+10 0.00 0.00 0.342109E+10 0.00 0.00 0.00 0.197625E+10 0.00
June 0.231508E+10 0.621428E+09 0.412149E+10 0.00 0.204861E+10 0.00 0.00 0.512116E+10 0.00 0.00 0.00 0.189131E+10 0.00
July 0.212793E+10 0.656953E+09 0.393546E+10 0.00 0.187450E+10 0.00 0.00 0.510565E+10 0.00 0.00 0.00 0.190146E+10 0.00
August 0.242822E+10 0.722137E+09 0.429420E+10 0.00 0.215010E+10 0.00 0.00 0.564306E+10 0.00 0.00 0.00 0.194806E+10 0.00
September 0.212328E+10 0.779404E+09 0.388029E+10 0.00 0.185848E+10 0.00 0.00 0.456790E+10 0.00 0.00 0.00 0.187482E+10 0.00
October 0.225809E+10 0.907791E+09 0.405607E+10 0.00 0.192505E+10 0.00 64250.96 0.297064E+10 0.00 0.00 0.00 0.197546E+10 0.00
November 0.226135E+10 0.977490E+09 0.400396E+10 0.00 0.190338E+10 0.00 13030533.28 0.174546E+10 0.00 0.00 0.00 0.195721E+10 0.00
December 0.219026E+10 0.106577E+10 0.393240E+10 0.00 0.180268E+10 0.00 0.144523E+09 0.771348E+09 0.00 0.00 0.00 0.202033E+10 0.00
                           
Annual Sum or Average 0.268793E+11 0.988353E+10 0.482958E+11 0.00 0.230826E+11 0.01 0.404179E+09 0.341455E+11 0.00 0.00 0.00 0.234390E+11 0.00
Minimum of Months 0.205235E+10 0.621428E+09 0.366466E+10 0.00 0.170969E+10 0.00 0.00 0.428550E+09 0.00 0.00 0.00 0.185212E+10 0.00
Maximum of Months 0.242822E+10 0.106577E+10 0.429420E+10 0.00 0.215010E+10 0.01 0.144523E+09 0.564306E+10 0.00 0.00 0.00 0.206554E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 2572333.38 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 1735134.53 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 892742.81 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 5200210.72 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 2572333.38 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2511.03 20-JAN-16:00 1061.67 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1996.39 02-JAN-06:10 0.00 20-JAN-10:30 5954.07 02-JAN-06:19
February 2498.29 10-FEB-08:09 1061.67 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1996.39 06-FEB-13:39 0.00 01-FEB-00:10 2362.63 13-FEB-06:10
March 2476.43 21-MAR-07:10 1061.67 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1996.39 02-MAR-09:30 0.00 01-MAR-00:10 3121.40 27-MAR-06:10
April 2357.96 06-APR-07:10 1061.67 01-APR-05:10 3325.31 03-APR-07:10 0.00 1996.39 03-APR-08:39 0.00 01-APR-00:10 0.00 01-APR-00:10
May 2370.51 26-MAY-08:30 1061.67 01-MAY-05:10 3325.31 01-MAY-07:10 0.00 1996.39 01-MAY-08:20 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 2302.08 07-JUN-12:30 1061.67 01-JUN-05:10 3325.31 01-JUN-07:10 0.00 1996.39 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 2393.07 13-JUL-15:00 1061.67 01-JUL-05:10 3325.31 03-JUL-07:10 0.00 1996.39 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2490.01 04-AUG-07:10 1061.67 01-AUG-05:10 3325.31 01-AUG-07:10 0.00 1996.39 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2436.69 29-SEP-07:10 1061.67 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1996.39 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2465.96 27-OCT-07:10 1061.67 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1996.39 02-OCT-05:10 0.00 01-OCT-00:10 54.20 25-OCT-06:00
November 2540.94 28-NOV-16:30 1061.67 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1996.39 08-NOV-09:20 0.00 01-NOV-00:10 389.57 24-NOV-07:19
December 2540.94 01-DEC-16:30 1061.67 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1996.39 08-DEC-09:30 0.00 01-DEC-00:10 2379.23 06-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2302.08   1061.67   3325.31   0.00 1996.39   0.00   0.00  
Maximum of Months 2540.94   1061.67   3325.31   0.00 1996.39   0.00   5954.07  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 3443.73 31-JAN-16:30 0.00 0.00 0.00 2786.77 27-JAN-12:30 0.00
February 1784.87 01-FEB-15:00 0.00 0.00 0.00 2786.53 01-FEB-12:20 0.00
March 3062.18 16-MAR-15:00 0.00 0.00 0.00 2782.48 01-MAR-12:09 0.00
April 5317.76 14-APR-15:00 0.00 0.00 0.00 2772.73 03-APR-11:09 0.00
May 5810.15 31-MAY-15:00 0.00 0.00 0.00 2762.41 01-MAY-11:00 0.00
June 7725.23 28-JUN-15:00 0.00 0.00 0.00 2751.78 01-JUN-11:00 0.00
July 7474.39 31-JUL-15:00 0.00 0.00 0.00 2744.90 03-JUL-11:30 0.00
August 7634.19 14-AUG-15:39 0.00 0.00 0.00 2747.70 31-AUG-11:20 0.00
September 7159.78 06-SEP-15:00 0.00 0.00 0.00 2756.01 29-SEP-11:09 0.00
October 6966.57 02-OCT-14:09 0.00 0.00 0.00 2767.59 31-OCT-11:00 0.00
November 4517.66 01-NOV-14:00 0.00 0.00 0.00 2777.72 30-NOV-12:00 0.00
December 2967.55 22-DEC-15:09 0.00 0.00 0.00 2784.79 29-DEC-12:30 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 1784.87   0.00 0.00 0.00 2744.90   0.00
Maximum of Months 7725.23   0.00 0.00 0.00 2786.77   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 13725.18 31-JAN-16:49 2232.59 3325.31 0.00 0.00 1996.39 0.00 0.00 3421.18 0.00
February 12018.95 01-FEB-15:30 2215.19 3325.31 0.00 0.00 1996.39 0.00 0.00 1755.88 0.00
March 13297.68 16-MAR-15:39 2176.75 3325.31 0.00 0.00 1996.39 0.00 0.00 3054.96 0.00
April 15590.30 14-APR-15:50 2222.97 3325.31 0.00 0.00 1996.39 0.00 0.00 5308.70 0.00
May 15981.75 31-MAY-15:39 2214.63 3325.31 0.00 0.00 1996.39 0.00 0.00 5720.08 0.00
June 17898.93 26-JUN-15:00 2228.92 3325.31 0.00 0.00 1996.39 0.00 0.00 7627.66 0.00
July 17630.23 31-JUL-15:00 2114.81 3325.31 0.00 0.00 1996.39 0.00 0.00 7474.39 0.00
August 17840.81 14-AUG-15:39 2165.24 3325.31 0.00 0.00 1996.39 0.00 0.00 7634.19 0.00
September 17387.65 06-SEP-15:00 2183.18 3325.31 0.00 0.00 1996.39 0.00 0.00 7159.78 0.00
October 17131.54 02-OCT-14:20 2138.99 3325.31 0.00 0.00 1996.39 0.00 0.00 6960.14 0.00
November 14701.81 01-NOV-14:30 2214.40 3325.31 0.00 0.00 1996.39 0.00 0.00 4449.36 0.00
December 13222.18 22-DEC-15:09 2208.30 3325.31 0.00 0.00 1996.39 0.00 0.00 2967.55 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 12018.95   2114.81 3325.31 0.00 0.00 1996.39 0.00 0.00 1755.88 0.00
Maximum of Months 17898.93   2232.59 3325.31 0.00 0.00 1996.39 0.00 0.00 7634.19 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 4287.22 02-JAN-06:10 0.00 0.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 2356.48 27-MAR-05:10 0.00 0.00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 826.82 18-DEC-06:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 4287.22   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.33 24.50 0.33 24.50
May 0.00 0.00 0.00 0.00 1.33 24.65 1.33 24.65
June 0.00 0.00 0.00 0.00 10.17 24.75 10.17 24.75
July 0.00 0.00 0.00 0.00 23.00 24.83 23.00 24.83
August 0.00 0.00 0.00 0.00 26.50 24.91 26.50 24.91
September 0.00 0.00 0.00 0.00 23.00 24.75 23.00 24.75
October 0.00 0.00 0.00 0.00 2.17 24.95 2.17 24.95
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   86.50 24.82 86.50 24.82
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 26.50 24.95 26.50 24.95



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 8.33 24.67 8.33 24.67
July 0.00 0.00 0.00 0.00 6.33 24.80 6.33 24.80
August 0.00 0.00 0.00 0.00 12.00 25.05 11.33 24.90
September 0.00 0.00 0.00 0.00 29.50 24.96 28.17 24.84
October 0.00 0.00 0.00 0.00 17.33 25.01 16.50 24.89
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   73.50 24.94 70.67 24.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 29.50 25.05 28.17 24.90



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 24.45 0.17 24.45
June 0.00 0.00 0.00 0.00 3.50 27.53 1.67 26.63
July 0.00 0.00 0.00 0.00 5.67 26.46 4.00 25.82
August 0.00 0.00 0.00 0.00 12.17 27.49 6.00 26.58
September 0.00 0.00 0.00 0.00 4.83 27.44 2.50 26.61
October 0.00 0.00 0.00 0.00 0.83 24.73 0.83 24.73
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   27.17 27.17 15.17 26.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.17 27.53 6.00 26.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 20.13 0.17 20.13 0.00 20.13 0.00 20.13
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.67 24.75 1.67 24.75
July 0.00 0.00 0.00 0.00 4.17 24.93 4.17 24.93
August 0.00 0.00 0.00 0.00 3.50 24.86 3.50 24.86
September 0.00 0.00 0.00 0.00 2.33 25.01 2.33 25.01
October 0.00 0.00 0.00 0.00 0.50 24.87 0.50 24.87
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 20.13 0.17 20.13 12.17 24.77 12.17 24.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 20.13 0.17 20.13 4.17 25.01 4.17 25.01



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 6.83 28.91 1.83 28.12
July 0.00 0.00 0.00 0.00 11.67 28.73 3.50 27.88
August 0.00 0.00 0.00 0.00 9.33 28.65 2.83 27.74
September 0.00 0.00 0.00 0.00 5.00 27.81 2.17 26.91
October 0.00 0.00 0.00 0.00 0.33 24.85 0.33 24.85
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   33.17 28.57 10.67 27.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 11.67 28.91 3.50 28.12



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 201.50 23.57 7.67 23.52 5.33 23.46
February 248.83 23.65 0.00 23.65 0.00 23.65
March 219.00 23.75 32.17 23.94 2.00 23.94
April 26.67 23.89 124.50 25.38 0.00 25.38
May 2.67 23.89 139.00 25.94 0.00 25.94
June 16.17 27.84 291.33 25.34 16.17 25.46
July 62.33 27.35 338.00 25.35 62.33 25.62
August 42.67 27.18 379.17 25.14 42.67 25.33
September 34.50 27.29 335.17 25.09 34.50 25.28
October 34.33 24.45 192.83 24.97 5.67 25.03
November 95.67 23.92 113.50 24.35 4.83 24.36
December 269.83 23.76 4.50 23.78 0.00 23.78
             
Annual Sum or Average 1254.17 24.18 1957.83 24.73 173.50 24.85
Minimum of Months 2.67 23.57 0.00 23.52 0.00 23.46
Maximum of Months 269.83 27.84 379.17 25.94 62.33 25.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 142.50 23.28 36.17 23.50 4.67 23.44
February 254.00 23.12 0.17 23.11 0.17 23.11
March 321.33 23.28 20.67 23.27 11.67 23.20
April 116.50 23.76 69.17 24.77 0.00 24.77
May 116.00 23.89 103.00 25.17 0.00 25.17
June 43.00 27.32 177.17 26.54 32.67 26.78
July 88.17 27.76 312.83 25.74 88.17 26.10
August 82.83 27.81 368.33 25.59 82.83 25.94
September 72.33 28.13 331.50 25.72 72.33 26.08
October 74.67 25.30 208.83 25.36 27.33 25.62
November 78.83 23.61 145.33 24.30 9.83 24.29
December 215.00 23.38 22.50 23.43 5.67 23.38
             
Annual Sum or Average 1605.17 24.26 1795.67 24.83 335.33 25.06
Minimum of Months 43.00 23.12 0.17 23.11 0.00 23.11
Maximum of Months 321.33 28.13 368.33 26.54 88.17 26.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 287.67 23.42 11.50 23.33 11.50 23.24
February 266.00 23.02 3.00 23.00 3.00 22.98
March 278.67 23.26 14.67 23.21 10.67 23.14
April 51.00 23.87 90.00 25.35 0.00 25.35
May 33.17 23.89 121.83 25.97 0.00 25.97
June 57.67 28.40 231.00 26.38 57.67 26.72
July 90.83 28.12 272.50 26.10 90.83 26.51
August 89.00 27.98 314.17 25.92 89.00 26.29
September 64.67 27.95 272.50 25.81 64.67 26.15
October 76.33 24.73 141.50 25.16 16.00 25.35
November 140.50 23.80 51.33 24.02 2.17 24.02
December 278.17 23.28 14.33 23.17 14.33 23.08
             
Annual Sum or Average 1713.67 24.25 1538.33 24.81 359.83 25.06
Minimum of Months 33.17 23.02 3.00 23.00 0.00 22.98
Maximum of Months 287.67 28.40 314.17 26.38 90.83 26.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 23.14 27.17 22.98 27.17 22.85
February 323.00 22.73 7.00 22.69 7.00 22.66
March 374.67 23.14 17.83 23.06 17.17 22.98
April 139.50 23.88 61.00 24.59 0.00 24.59
May 89.33 23.89 106.00 25.37 0.00 25.37
June 52.17 28.22 212.17 26.42 50.67 26.73
July 85.50 27.94 322.50 25.71 85.50 26.09
August 70.33 27.77 368.67 25.45 70.33 25.77
September 45.67 27.76 323.83 25.32 45.67 25.58
October 143.67 24.11 129.17 24.62 9.00 24.72
November 250.33 23.68 40.67 23.76 6.00 23.74
December 340.00 23.01 26.50 22.87 26.50 22.76
             
Annual Sum or Average 2271.17 23.79 1642.50 24.34 345.00 24.50
Minimum of Months 45.67 22.73 7.00 22.69 0.00 22.66
Maximum of Months 374.67 28.22 368.67 26.42 85.50 26.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 291.67 23.45 14.50 23.36 13.50 23.27
February 310.33 23.06 2.00 23.05 2.00 23.03
March 329.50 23.32 32.50 23.38 13.17 23.30
April 123.17 24.76 117.50 25.77 23.33 26.01
May 114.67 25.74 124.17 26.60 44.50 26.92
June 106.00 29.20 245.17 27.14 106.00 27.62
July 94.33 28.59 326.67 26.05 94.33 26.51
August 95.33 28.56 376.50 25.91 95.33 26.36
September 88.83 28.33 328.67 25.86 88.83 26.30
October 115.50 24.97 170.17 25.32 29.00 25.59
November 159.83 23.81 85.17 24.16 1.50 24.16
December 304.67 23.30 18.50 23.20 17.50 23.09
             
Annual Sum or Average 2133.83 24.61 1841.50 25.04 529.00 25.38
Minimum of Months 88.83 23.06 2.00 23.05 1.50 23.03
Maximum of Months 329.50 29.20 376.50 27.14 106.00 27.62



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.121898E+10 0.273713E+09 194.00 0.119033E+10 28648140.41 0.00 0.74 27-JAN-06:03 0.00 01-JAN-00:10 4282.07 27-JAN-06:03 4282.07 27-JAN-06:03 427.70 09-JAN-11:00 877.66 27-JAN-06:03 0.00
February 0.727038E+09 0.161490E+09 168.11 0.639422E+09 87615949.78 0.00 0.60 01-FEB-06:03 0.00 01-FEB-00:10 3317.79 01-FEB-06:03 3317.79 01-FEB-06:03 451.82 17-FEB-12:00 694.24 01-FEB-06:03 0.00
March 0.134770E+10 0.304035E+09 228.27 0.127579E+10 71903354.52 0.00 1.00 17-MAR-05:03 0.00 01-MAR-00:10 6252.66 17-MAR-05:03 5683.00 21-MAR-05:03 777.96 22-MAR-05:03 1228.60 17-MAR-05:03 0.00
April 0.271151E+10 0.638097E+09 238.84 0.270717E+10 4333407.75 0.00 1.00 03-APR-05:03 0.00 01-APR-00:10 6291.46 26-APR-05:01 6291.46 26-APR-05:01 170.51 10-APR-05:04 1238.72 25-APR-05:01 0.00
May 0.364473E+10 0.884143E+09 263.80 0.364473E+10 -0.0 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 6268.76 11-MAY-05:01 6268.76 11-MAY-05:01 0.00 11-MAY-09:14 1354.98 31-MAY-16:00 0.00
June 0.468574E+10 0.119525E+10 264.00 0.466880E+10 16941009.92 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 6419.62 20-JUN-05:01 6419.62 20-JUN-05:01 628.82 30-JUN-08:20 1656.68 28-JUN-16:00 0.00
July 0.488425E+10 0.117428E+10 240.00 0.436027E+10 0.523978E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:05 6927.93 14-JUL-05:01 6433.60 03-JUL-05:01 2636.20 14-JUL-05:10 1637.63 19-JUL-13:20 0.00
August 0.536791E+10 0.129200E+10 276.00 0.475065E+10 0.617259E+09 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 6818.04 10-AUG-05:01 6444.74 28-AUG-05:01 2206.83 10-AUG-05:09 1601.38 15-AUG-16:03 0.00
September 0.446806E+10 0.104148E+10 240.00 0.396220E+10 0.505852E+09 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 6919.03 05-SEP-05:01 6418.53 18-SEP-05:01 2119.44 05-SEP-05:10 1568.49 06-SEP-15:53 0.00
October 0.310603E+10 0.707098E+09 250.00 0.296045E+10 0.145582E+09 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 6736.22 03-OCT-05:01 6469.96 02-OCT-05:01 1795.22 03-OCT-05:10 1523.85 02-OCT-14:00 0.00
November 0.198493E+10 0.437716E+09 240.10 0.182650E+10 0.158431E+09 0.00 1.00 01-NOV-05:02 0.00 01-NOV-00:10 6712.17 14-NOV-06:03 6251.55 01-NOV-05:02 2560.27 14-NOV-06:03 1302.28 14-NOV-06:03 0.00
December 0.920242E+09 0.204389E+09 188.12 0.911548E+09 8694405.71 0.00 0.68 27-DEC-06:03 0.00 01-DEC-00:10 3891.17 27-DEC-06:03 3749.07 27-DEC-06:03 272.31 13-DEC-11:35 804.84 27-DEC-06:03 0.00
                                       
Annual Sum or Average 0.350671E+11 0.831369E+10 2791.25 0.328979E+11 0.216924E+10 0.00                         0.00
Minimum of Months 0.727038E+09 0.161490E+09 168.11 0.639422E+09 -0.0 0.00 0.60   0.00   3317.79   3317.79   0.00   694.24   0.00
Maximum of Months 0.536791E+10 0.129200E+10 276.00 0.475065E+10 0.617259E+09 0.00 1.00   0.00   6927.93   6469.96   2636.20   1656.68   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.200693E+10 0.437973E+09 193.96 0.200159E+10 5333789.57 0.00 0.82 30-JAN-14:40 0.00 01-JAN-00:10 5272.88 30-JAN-14:40 5272.88 30-JAN-14:40 435.99 09-JAN-11:02 1174.86 31-JAN-16:00 0.00
February 0.671141E+09 0.147634E+09 130.58 0.653687E+09 17454069.23 0.00 0.51 01-FEB-15:30 0.00 01-FEB-00:10 3208.98 01-FEB-15:30 3208.98 01-FEB-15:30 265.18 16-FEB-11:55 681.59 01-FEB-15:30 0.00
March 0.981046E+09 0.225150E+09 169.90 0.977092E+09 3954170.64 0.00 0.56 16-MAR-15:30 0.00 01-MAR-00:10 3500.48 16-MAR-15:20 3500.48 16-MAR-15:20 113.80 17-MAR-11:01 854.00 16-MAR-15:20 0.00
April 0.229137E+10 0.560050E+09 216.62 0.229137E+10 0.00 0.00 1.00 06-APR-05:02 0.00 01-APR-00:10 6965.32 26-APR-05:01 6965.32 26-APR-05:01 0.00 17-APR-08:47 1430.79 14-APR-16:10 0.00
May 0.297241E+10 0.756674E+09 260.64 0.297241E+10 -0.0 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 6967.89 11-MAY-05:01 6967.89 11-MAY-05:01 0.00 15-MAY-09:53 1525.35 31-MAY-16:07 0.00
June 0.441786E+10 0.117553E+10 265.65 0.441107E+10 6788205.31 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 7158.69 19-JUN-05:01 7158.69 19-JUN-05:01 513.91 30-JUN-08:00 1847.50 28-JUN-16:17 0.00
July 0.482926E+10 0.120061E+10 248.23 0.440691E+10 0.422357E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:05 7963.92 14-JUL-05:01 7258.18 31-JUL-05:01 3420.85 14-JUL-05:06 1804.98 19-JUL-12:03 0.00
August 0.547354E+10 0.135999E+10 290.15 0.500290E+10 0.470640E+09 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 7796.57 10-AUG-05:01 7426.98 14-AUG-05:01 2765.43 10-AUG-05:05 1796.76 10-AUG-16:03 0.00
September 0.491176E+10 0.116924E+10 260.67 0.449960E+10 0.412155E+09 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 7804.29 05-SEP-05:01 7213.59 25-SEP-05:01 2300.10 05-SEP-05:10 1783.20 08-SEP-15:00 0.00
October 0.372470E+10 0.849415E+09 248.56 0.363893E+10 85767644.84 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 7652.36 03-OCT-05:01 7416.84 02-OCT-05:01 1915.94 03-OCT-05:06 1719.64 02-OCT-14:00 0.00
November 0.264976E+10 0.573135E+09 219.41 0.256391E+10 85847942.78 0.00 1.00 01-NOV-05:02 0.00 01-NOV-00:10 7629.94 13-NOV-06:02 7013.96 01-NOV-05:02 2741.55 13-NOV-06:02 1478.69 13-NOV-06:02 0.00
December 0.148056E+10 0.318403E+09 170.06 0.147919E+10 1374522.78 0.00 0.83 26-DEC-13:50 0.00 01-DEC-00:10 5438.27 26-DEC-13:55 5438.27 26-DEC-13:55 167.52 13-DEC-10:53 1133.86 26-DEC-14:00 0.00
                                       
Annual Sum or Average 0.364103E+11 0.877381E+10 2674.43 0.348987E+11 0.151167E+10 0.00                         0.00
Minimum of Months 0.671141E+09 0.147634E+09 130.58 0.653687E+09 -0.0 0.00 0.51   0.00   3208.98   3208.98   0.00   681.59   0.00
Maximum of Months 0.547354E+10 0.135999E+10 290.15 0.500290E+10 0.470640E+09 0.00 1.00   0.00   7963.92   7426.98   3420.85   1847.50   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.482011E+09 0.110518E+09 169.89 0.479576E+09 2434932.92 0.00 0.76 31-JAN-11:02 0.00 01-JAN-00:10 3338.75 31-JAN-11:02 3338.75 31-JAN-11:02 426.62 09-JAN-11:02 680.77 31-JAN-11:02 0.00
February 0.181733E+09 40934565.09 110.31 0.172666E+09 9067100.37 0.00 0.76 23-FEB-15:01 0.00 01-FEB-00:10 3453.50 23-FEB-15:01 3392.28 23-FEB-15:01 466.35 16-FEB-11:02 706.80 23-FEB-15:01 0.00
March 0.451443E+09 0.104637E+09 170.25 0.449014E+09 2429558.47 0.00 0.86 17-MAR-12:01 0.00 01-MAR-00:10 3902.83 17-MAR-12:01 3887.85 17-MAR-12:01 131.78 02-MAR-11:02 862.65 17-MAR-12:01 0.00
April 0.155563E+10 0.375174E+09 233.59 0.155563E+10 0.00 0.00 1.00 03-APR-10:02 0.00 01-APR-00:10 4677.96 17-APR-05:01 4677.96 17-APR-05:01 0.00 07-APR-07:48 1026.38 12-APR-10:02 0.00
May 0.212886E+10 0.530955E+09 262.68 0.212886E+10 0.00 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 4684.92 11-MAY-05:01 4684.92 11-MAY-05:01 0.00 05-MAY-07:39 1045.62 19-MAY-10:01 0.00
June 0.306560E+10 0.807653E+09 292.25 0.306311E+10 2487011.41 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 4807.06 19-JUN-05:01 4807.06 19-JUN-05:01 276.63 30-JUN-08:20 1213.19 28-JUN-14:05 0.00
July 0.319063E+10 0.797976E+09 285.44 0.299306E+10 0.197567E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:05 5322.29 14-JUL-05:01 4870.10 31-JUL-05:01 2184.45 14-JUL-05:05 1219.39 19-JUL-14:02 0.00
August 0.349650E+10 0.874755E+09 316.19 0.327909E+10 0.217415E+09 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 5206.90 10-AUG-05:01 4975.53 14-AUG-05:01 1750.07 10-AUG-05:12 1212.75 13-AUG-18:02 0.00
September 0.280561E+10 0.677028E+09 262.63 0.261754E+10 0.188067E+09 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 5227.44 05-SEP-05:01 4890.78 10-SEP-10:12 1525.34 05-SEP-05:08 1173.68 08-SEP-14:05 0.00
October 0.182580E+10 0.427040E+09 241.70 0.178671E+10 39086809.17 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 5099.84 03-OCT-05:01 4956.93 02-OCT-05:01 1229.55 03-OCT-05:05 1138.56 02-OCT-14:02 0.00
November 0.949437E+09 0.214182E+09 224.40 0.912915E+09 36521812.37 0.00 1.00 01-NOV-05:02 0.00 01-NOV-00:10 4861.56 03-NOV-05:02 4669.69 01-NOV-05:02 1143.30 13-NOV-06:02 953.98 03-NOV-05:02 0.00
December 0.339829E+09 76588651.68 146.30 0.339068E+09 761048.05 0.00 0.77 22-DEC-11:02 0.00 01-DEC-00:10 3377.50 22-DEC-11:02 3377.50 22-DEC-11:02 153.35 13-DEC-11:03 702.53 22-DEC-11:02 0.00
                                       
Annual Sum or Average 0.204731E+11 0.503744E+10 2715.62 0.197772E+11 0.695837E+09 0.00                         0.00
Minimum of Months 0.181733E+09 40934565.09 110.31 0.172666E+09 0.00 0.00 0.76   0.00   3338.75   3338.75   0.00   680.77   0.00
Maximum of Months 0.349650E+10 0.874755E+09 316.19 0.327909E+10 0.217415E+09 0.00 1.00   0.00   5322.29   4975.53   2184.45   1219.39   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.491916E+09 0.114632E+09 139.84 0.489707E+09 2209701.37 0.00 0.36 31-JAN-16:50 0.00 01-JAN-00:10 2072.83 31-JAN-16:42 2072.83 31-JAN-16:42 110.52 09-JAN-11:53 527.78 31-JAN-16:50 0.00
February 0.115818E+09 26300526.12 66.84 0.106891E+09 8926185.52 0.00 0.17 16-FEB-15:55 0.00 01-FEB-00:10 1065.42 16-FEB-15:55 960.48 16-FEB-16:00 162.99 16-FEB-13:13 239.89 16-FEB-15:55 0.00
March 0.509276E+09 0.119994E+09 142.04 0.505435E+09 3840627.77 0.00 0.37 16-MAR-15:53 0.00 01-MAR-00:10 2234.79 16-MAR-15:57 2234.79 16-MAR-15:57 105.87 17-MAR-10:50 561.28 16-MAR-15:57 0.00
April 0.188059E+10 0.464476E+09 229.42 0.188059E+10 -0.0 0.00 1.00 12-APR-05:01 0.00 01-APR-00:10 6904.80 26-APR-05:01 6904.80 26-APR-05:01 0.00 27-APR-10:22 1363.53 25-APR-05:01 0.00
May 0.278987E+10 0.709954E+09 263.15 0.278987E+10 -0.0 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 6916.32 11-MAY-05:01 6916.32 11-MAY-05:01 0.00 08-MAY-12:57 1373.76 11-MAY-05:01 0.00
June 0.417865E+10 0.111263E+10 268.41 0.417353E+10 5119547.61 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 7091.57 19-JUN-05:01 7091.57 19-JUN-05:01 380.76 30-JUN-08:20 1728.29 28-JUN-14:55 0.00
July 0.450496E+10 0.112747E+10 250.63 0.415451E+10 0.350448E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:05 7857.95 14-JUL-05:01 7192.84 21-JUL-05:01 3268.82 14-JUL-05:06 1719.96 17-JUL-14:40 0.00
August 0.488881E+10 0.122712E+10 286.17 0.449965E+10 0.389166E+09 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 7688.26 10-AUG-05:01 7350.88 14-AUG-05:01 2633.33 10-AUG-05:05 1761.92 28-AUG-13:00 0.00
September 0.403228E+10 0.975903E+09 242.83 0.370069E+10 0.331589E+09 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 7799.67 05-SEP-05:01 7092.01 20-SEP-05:01 2573.21 05-SEP-05:10 1586.11 11-SEP-14:00 0.00
October 0.231533E+10 0.550759E+09 233.90 0.224388E+10 71446967.56 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 7529.57 03-OCT-05:01 7310.15 02-OCT-05:01 1820.75 03-OCT-05:05 1550.76 02-OCT-14:00 0.00
November 0.116979E+10 0.266576E+09 207.97 0.109970E+10 70083770.02 0.00 1.00 03-NOV-05:02 0.00 01-NOV-00:10 7173.60 03-NOV-05:02 6579.78 01-NOV-05:02 1646.41 13-NOV-06:02 1408.12 03-NOV-05:02 0.00
December 0.314988E+09 71906187.66 111.39 0.314148E+09 840314.21 0.00 0.30 22-DEC-15:25 0.00 01-DEC-00:10 1796.98 22-DEC-15:35 1796.98 22-DEC-15:35 68.39 13-DEC-11:55 430.41 22-DEC-14:55 0.00
                                       
Annual Sum or Average 0.271923E+11 0.676772E+10 2442.58 0.259586E+11 0.123367E+10 0.00                         0.00
Minimum of Months 0.115818E+09 26300526.12 66.84 0.106891E+09 -0.0 0.00 0.17   0.00   1065.42   960.48   0.00   239.89   0.00
Maximum of Months 0.488881E+10 0.122712E+10 286.17 0.449965E+10 0.389166E+09 0.00 1.00   0.00   7857.95   7350.88   3268.82   1761.92   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.621054E+09 0.142443E+09 168.45 0.618184E+09 2870140.41 0.00 0.52 31-JAN-17:00 0.00 01-JAN-00:10 2453.74 31-JAN-16:55 2453.74 31-JAN-16:55 123.50 09-JAN-11:53 608.92 31-JAN-16:55 0.00
February 0.232005E+09 52190327.40 108.87 0.220816E+09 11189040.38 0.00 0.33 22-FEB-16:23 0.00 01-FEB-00:10 1634.00 22-FEB-16:23 1575.01 22-FEB-16:27 120.10 16-FEB-13:13 359.03 22-FEB-16:23 0.00
March 0.510326E+09 0.119080E+09 166.17 0.506227E+09 4098171.96 0.00 0.45 16-MAR-15:53 0.00 01-MAR-00:10 2151.54 16-MAR-15:57 2151.54 16-MAR-15:57 133.24 06-MAR-16:36 534.27 16-MAR-15:57 0.00
April 0.154530E+10 0.380650E+09 237.65 0.154530E+10 -0.0 0.00 1.00 05-APR-05:02 0.00 01-APR-00:10 5526.57 26-APR-05:01 5526.57 26-APR-05:01 0.00 27-APR-09:44 1089.53 25-APR-05:01 0.00
May 0.210755E+10 0.539359E+09 270.78 0.210755E+10 -0.0 0.00 1.00 01-MAY-05:01 0.00 01-MAY-00:10 5525.98 11-MAY-05:01 5525.98 11-MAY-05:01 0.00 11-MAY-05:02 1097.65 11-MAY-05:01 0.00
June 0.305244E+10 0.830088E+09 312.59 0.304895E+10 3491500.52 0.00 1.00 01-JUN-05:01 0.00 01-JUN-00:10 5641.31 19-JUN-05:01 5641.31 19-JUN-05:01 246.08 30-JUN-08:20 1400.35 04-JUN-16:53 0.00
July 0.313005E+10 0.805326E+09 289.85 0.290474E+10 0.225310E+09 0.00 1.00 01-JUL-17:52 0.00 01-JUL-00:05 6248.30 14-JUL-05:01 5785.10 16-JUL-18:32 2549.42 14-JUL-05:12 1425.21 22-JUL-17:33 0.00
August 0.345936E+10 0.889191E+09 317.77 0.320819E+10 0.251176E+09 0.00 1.00 01-AUG-05:01 0.00 01-AUG-00:10 6114.87 10-AUG-05:01 5824.07 14-AUG-05:01 2054.73 10-AUG-05:04 1430.53 13-AUG-17:42 0.00
September 0.285503E+10 0.704246E+09 264.31 0.264025E+10 0.214783E+09 0.00 1.00 01-SEP-05:01 0.00 01-SEP-00:10 6139.87 11-SEP-05:01 5692.90 25-SEP-05:01 1793.21 11-SEP-05:07 1269.85 04-SEP-17:03 0.00
October 0.182891E+10 0.436327E+09 250.76 0.178216E+10 46747971.51 0.00 1.00 02-OCT-05:01 0.00 01-OCT-00:10 5989.97 03-OCT-05:01 5826.04 02-OCT-05:01 1418.64 03-OCT-05:12 1210.07 02-OCT-05:01 0.00
November 0.112346E+10 0.253851E+09 223.97 0.107222E+10 51238403.55 0.00 1.00 01-NOV-05:02 0.00 01-NOV-00:10 5721.54 03-NOV-05:02 5502.89 01-NOV-05:02 1499.04 13-NOV-06:02 1122.52 03-NOV-05:02 0.00
December 0.444613E+09 0.100062E+09 146.28 0.443760E+09 852970.73 0.00 0.50 22-DEC-16:23 0.00 01-DEC-00:10 2452.46 22-DEC-16:27 2452.46 22-DEC-16:27 59.10 13-DEC-11:55 555.43 22-DEC-16:27 0.00
                                       
Annual Sum or Average 0.209101E+11 0.525281E+10 2757.43 0.200983E+11 0.811757E+09 0.00                         0.00
Minimum of Months 0.232005E+09 52190327.40 108.87 0.220816E+09 -0.0 0.00 0.33   0.00   1634.00   1575.01   0.00   359.03   0.00
Maximum of Months 0.345936E+10 0.889191E+09 317.77 0.320819E+10 0.251176E+09 0.00 1.00   0.00   6248.30   5826.04   2549.42   1430.53   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.01 79.38 19.63 153.01 48.91 0.00 0.00 0.00
February 62.18 42.38 19.80 88.19 43.76 0.00 0.00 0.00
March 45.92 22.53 23.40 68.86 39.37 0.00 0.00 0.00
April 30.16 7.23 22.93 54.67 23.97 0.00 0.00 0.00
May 22.05 0.00 22.05 43.98 16.89 0.00 0.00 0.00
June 21.96 0.00 21.96 58.41 8.07 0.00 0.00 0.00
July 20.93 0.06 20.87 52.17 7.32 0.00 0.00 0.00
August 21.31 1.68 19.62 52.71 9.04 0.00 0.00 0.00
September 36.58 13.44 23.14 74.75 14.05 0.00 0.00 0.00
October 70.22 48.58 21.64 116.60 34.86 0.00 0.00 0.00
November 84.41 65.04 19.37 127.83 47.32 0.00 0.00 0.00
December 91.99 73.15 18.84 134.99 59.76 0.00 0.00 0.00
                 
Annual Sum or Average 50.54 29.44 21.11 85.56 29.39 0.00 0.00 0.00
Minimum of Months 20.93 0.00 18.84 43.98 7.32 0.00 0.00 0.00
Maximum of Months 99.01 79.38 23.40 153.01 59.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.01 79.38 19.63 153.01 48.91 0.00 0.00 0.00
February 62.18 42.38 19.80 88.19 43.76 0.00 0.00 0.00
March 45.91 22.52 23.39 68.83 39.38 0.00 0.00 0.00
April 30.01 7.16 22.84 54.29 23.97 0.00 0.00 0.00
May 22.05 0.00 22.05 43.97 16.89 0.00 0.00 0.00
June 21.96 0.00 21.96 58.41 8.07 0.00 0.00 0.00
July 20.93 0.06 20.86 52.17 7.32 0.00 0.00 0.00
August 21.28 1.67 19.61 52.65 9.03 0.00 0.00 0.00
September 36.49 13.41 23.08 74.54 14.05 0.00 0.00 0.00
October 70.22 48.58 21.64 116.60 34.86 0.00 0.00 0.00
November 84.41 65.04 19.37 127.83 47.32 0.00 0.00 0.00
December 91.99 73.15 18.84 134.99 59.76 0.00 0.00 0.00
                 
Annual Sum or Average 50.52 29.43 21.09 85.51 29.39 0.00 0.00 0.00
Minimum of Months 20.93 0.00 18.84 43.97 7.32 0.00 0.00 0.00
Maximum of Months 99.01 79.38 23.39 153.01 59.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.01 79.38 19.63 153.01 48.91 0.00 0.00 0.00
February 62.18 42.38 19.80 88.19 43.76 0.00 0.00 0.00
March 45.91 22.52 23.39 68.83 39.38 0.00 0.00 0.00
April 30.01 7.16 22.84 54.29 23.97 0.00 0.00 0.00
May 22.05 0.00 22.05 43.97 16.89 0.00 0.00 0.00
June 21.96 0.00 21.96 58.41 8.07 0.00 0.00 0.00
July 20.93 0.06 20.86 52.17 7.32 0.00 0.00 0.00
August 21.28 1.67 19.61 52.65 9.03 0.00 0.00 0.00
September 36.48 13.40 23.07 74.53 14.05 0.00 0.00 0.00
October 70.22 48.58 21.64 116.60 34.86 0.00 0.00 0.00
November 84.41 65.04 19.37 127.83 47.32 0.00 0.00 0.00
December 91.99 73.15 18.84 134.99 59.76 0.00 0.00 0.00
                 
Annual Sum or Average 50.52 29.43 21.09 85.51 29.39 0.00 0.00 0.00
Minimum of Months 20.93 0.00 18.84 43.97 7.32 0.00 0.00 0.00
Maximum of Months 99.01 79.38 23.39 153.01 59.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.01 79.38 19.63 153.01 48.91 0.00 0.00 0.00
February 62.18 42.38 19.80 88.19 43.76 0.00 0.00 0.00
March 45.91 22.52 23.39 68.83 39.38 0.00 0.00 0.00
April 30.01 7.16 22.84 54.29 23.97 0.00 0.00 0.00
May 22.05 0.00 22.05 43.97 16.89 0.00 0.00 0.00
June 21.96 0.00 21.96 58.41 8.07 0.00 0.00 0.00
July 20.93 0.06 20.86 52.17 7.32 0.00 0.00 0.00
August 21.28 1.67 19.61 52.65 9.03 0.00 0.00 0.00
September 36.48 13.40 23.07 74.52 14.05 0.00 0.00 0.00
October 70.22 48.58 21.64 116.60 34.86 0.00 0.00 0.00
November 84.41 65.04 19.37 127.83 47.32 0.00 0.00 0.00
December 91.99 73.15 18.84 134.99 59.76 0.00 0.00 0.00
                 
Annual Sum or Average 50.52 29.43 21.09 85.51 29.39 0.00 0.00 0.00
Minimum of Months 20.93 0.00 18.84 43.97 7.32 0.00 0.00 0.00
Maximum of Months 99.01 79.38 23.39 153.01 59.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.01 79.38 19.63 153.01 48.91 0.00 0.00 0.00
February 62.18 42.38 19.80 88.19 43.76 0.00 0.00 0.00
March 45.91 22.52 23.39 68.83 39.38 0.00 0.00 0.00
April 30.01 7.16 22.84 54.29 23.97 0.00 0.00 0.00
May 22.05 0.00 22.05 43.97 16.89 0.00 0.00 0.00
June 21.96 0.00 21.96 58.41 8.07 0.00 0.00 0.00
July 20.93 0.06 20.86 52.17 7.32 0.00 0.00 0.00
August 21.28 1.67 19.61 52.65 9.03 0.00 0.00 0.00
September 36.49 13.41 23.08 74.53 14.03 0.00 0.00 0.00
October 70.22 48.58 21.64 116.60 34.86 0.00 0.00 0.00
November 84.41 65.04 19.37 127.83 47.32 0.00 0.00 0.00
December 91.99 73.15 18.84 134.99 59.76 0.00 0.00 0.00
                 
Annual Sum or Average 50.52 29.43 21.09 85.51 29.39 0.00 0.00 0.00
Minimum of Months 20.93 0.00 18.84 43.97 7.32 0.00 0.00 0.00
Maximum of Months 99.01 79.38 23.39 153.01 59.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.01 79.38 19.63 153.01 48.91 0.00 0.00 0.00
February 62.18 42.38 19.80 88.19 43.76 0.00 0.00 0.00
March 45.92 22.53 23.40 68.84 39.36 0.00 0.00 0.00
April 30.14 7.24 22.91 54.62 23.95 0.00 0.00 0.00
May 22.05 0.00 22.05 43.98 16.89 0.00 0.00 0.00
June 21.96 0.00 21.96 58.41 8.07 0.00 0.00 0.00
July 20.93 0.06 20.87 52.17 7.32 0.00 0.00 0.00
August 21.31 1.69 19.62 52.72 9.03 0.00 0.00 0.00
September 36.60 13.45 23.15 74.76 14.00 0.00 0.00 0.00
October 70.22 48.58 21.64 116.60 34.86 0.00 0.00 0.00
November 84.41 65.04 19.37 127.83 47.32 0.00 0.00 0.00
December 91.99 73.15 18.84 134.99 59.76 0.00 0.00 0.00
                 
Annual Sum or Average 50.55 29.44 21.11 85.56 29.38 0.00 0.00 0.00
Minimum of Months 20.93 0.00 18.84 43.98 7.32 0.00 0.00 0.00
Maximum of Months 99.01 79.38 23.40 153.01 59.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 138.97 111.21 27.76 214.12 68.62 0.00 0.00 0.00
February 87.57 59.38 28.19 123.93 61.09 0.00 0.00 0.00
March 72.65 37.73 34.92 111.41 55.07 0.00 0.00 0.00
April 52.16 17.71 34.45 96.92 34.01 0.00 0.00 0.00
May 32.89 1.13 31.76 65.01 24.16 0.00 0.00 0.00
June 31.18 0.00 31.18 81.17 11.68 0.00 0.00 0.00
July 30.23 0.43 29.80 73.87 10.49 0.00 0.00 0.00
August 35.84 6.50 29.34 86.14 12.96 0.00 0.00 0.00
September 59.54 24.55 34.99 120.27 19.97 0.00 0.00 0.00
October 101.71 70.65 31.06 168.50 49.14 0.00 0.00 0.00
November 118.61 91.12 27.49 179.08 66.29 0.00 0.00 0.00
December 129.16 102.48 26.68 188.99 83.69 0.00 0.00 0.00
                 
Annual Sum or Average 74.20 43.56 30.64 125.87 41.36 0.00 0.00 0.00
Minimum of Months 30.23 0.00 26.68 65.01 10.49 0.00 0.00 0.00
Maximum of Months 138.97 111.21 34.99 214.12 83.69 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.51 23.58 13.94 49.75 43.70 0.00 0.00 0.00
February 36.62 21.12 15.50 43.69 41.64 0.00 0.00 0.00
March 45.40 23.41 21.99 61.69 36.50 0.00 0.00 0.00
April 64.60 38.16 26.44 106.54 22.34 0.00 0.00 0.00
May 66.52 38.98 27.54 116.50 16.39 0.00 0.00 0.00
June 69.26 42.41 26.85 137.05 8.13 0.00 0.00 0.00
July 58.16 32.42 25.74 114.33 7.58 0.00 0.00 0.00
August 55.55 31.42 24.13 109.44 9.25 0.00 0.00 0.00
September 45.65 21.94 23.70 85.42 13.21 0.00 0.00 0.00
October 46.71 28.42 18.28 71.45 32.52 0.00 0.00 0.00
November 36.13 21.78 14.35 45.74 44.50 0.00 0.00 0.00
December 33.05 20.05 12.99 37.63 55.87 0.00 0.00 0.00
                 
Annual Sum or Average 49.66 28.68 20.98 81.78 27.58 0.00 0.00 0.00
Minimum of Months 33.05 20.05 12.99 37.63 7.58 0.00 0.00 0.00
Maximum of Months 69.26 42.41 27.54 137.05 55.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.51 23.58 13.94 49.75 43.70 0.00 0.00 0.00
February 36.62 21.12 15.50 43.69 41.64 0.00 0.00 0.00
March 45.40 23.41 21.99 61.69 36.50 0.00 0.00 0.00
April 64.60 38.16 26.44 106.54 22.34 0.00 0.00 0.00
May 66.52 38.98 27.54 116.50 16.39 0.00 0.00 0.00
June 69.26 42.41 26.85 137.05 8.13 0.00 0.00 0.00
July 58.16 32.42 25.74 114.33 7.58 0.00 0.00 0.00
August 55.55 31.42 24.13 109.44 9.25 0.00 0.00 0.00
September 45.65 21.94 23.70 85.42 13.21 0.00 0.00 0.00
October 46.71 28.42 18.28 71.45 32.52 0.00 0.00 0.00
November 36.13 21.78 14.35 45.74 44.50 0.00 0.00 0.00
December 33.05 20.05 12.99 37.63 55.87 0.00 0.00 0.00
                 
Annual Sum or Average 49.65 28.68 20.98 81.78 27.58 0.00 0.00 0.00
Minimum of Months 33.05 20.05 12.99 37.63 7.58 0.00 0.00 0.00
Maximum of Months 69.26 42.41 27.54 137.05 55.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.51 23.58 13.94 49.75 43.70 0.00 0.00 0.00
February 36.62 21.12 15.50 43.69 41.64 0.00 0.00 0.00
March 45.40 23.41 21.99 61.69 36.50 0.00 0.00 0.00
April 64.60 38.16 26.44 106.54 22.34 0.00 0.00 0.00
May 66.52 38.98 27.54 116.50 16.39 0.00 0.00 0.00
June 69.26 42.41 26.85 137.05 8.13 0.00 0.00 0.00
July 58.16 32.42 25.74 114.33 7.58 0.00 0.00 0.00
August 55.55 31.42 24.13 109.44 9.25 0.00 0.00 0.00
September 45.65 21.94 23.70 85.42 13.21 0.00 0.00 0.00
October 46.71 28.42 18.28 71.45 32.52 0.00 0.00 0.00
November 36.13 21.78 14.35 45.74 44.50 0.00 0.00 0.00
December 33.05 20.05 12.99 37.63 55.87 0.00 0.00 0.00
                 
Annual Sum or Average 49.65 28.68 20.98 81.78 27.58 0.00 0.00 0.00
Minimum of Months 33.05 20.05 12.99 37.63 7.58 0.00 0.00 0.00
Maximum of Months 69.26 42.41 27.54 137.05 55.87 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.54 23.60 13.95 49.83 43.70 0.00 0.00 0.00
February 36.63 21.12 15.51 43.70 41.64 0.00 0.00 0.00
March 45.40 23.41 21.99 61.69 36.50 0.00 0.00 0.00
April 64.60 38.16 26.44 106.54 22.34 0.00 0.00 0.00
May 66.52 38.98 27.54 116.50 16.39 0.00 0.00 0.00
June 69.26 42.41 26.85 137.05 8.13 0.00 0.00 0.00
July 58.16 32.42 25.74 114.33 7.58 0.00 0.00 0.00
August 55.55 31.42 24.13 109.44 9.25 0.00 0.00 0.00
September 45.65 21.94 23.70 85.42 13.21 0.00 0.00 0.00
October 46.71 28.43 18.28 71.46 32.52 0.00 0.00 0.00
November 36.14 21.79 14.35 45.77 44.49 0.00 0.00 0.00
December 33.08 20.08 13.01 37.72 55.86 0.00 0.00 0.00
                 
Annual Sum or Average 49.66 28.68 20.98 81.80 27.58 0.00 0.00 0.00
Minimum of Months 33.08 20.08 13.01 37.72 7.58 0.00 0.00 0.00
Maximum of Months 69.26 42.41 27.54 137.05 55.86 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.69 0.00 11.69 10.82 45.09 0.00 0.00 0.00
February 13.09 0.00 13.09 7.88 42.93 0.00 0.00 0.00
March 17.42 0.00 17.42 18.81 37.92 0.00 0.00 0.00
April 21.57 0.21 21.36 36.88 22.35 0.00 0.00 0.00
May 24.83 1.78 23.05 48.38 15.58 0.00 0.00 0.00
June 28.45 4.72 23.73 71.04 7.80 0.00 0.00 0.00
July 24.39 2.33 22.06 59.20 7.15 0.00 0.00 0.00
August 20.02 0.46 19.56 50.28 8.73 0.00 0.00 0.00
September 18.77 0.00 18.77 41.15 12.97 0.00 0.00 0.00
October 14.71 0.00 14.71 20.74 33.57 0.00 0.00 0.00
November 12.18 0.00 12.18 9.38 46.12 0.00 0.00 0.00
December 10.86 0.00 10.86 5.86 58.56 0.00 0.00 0.00
                 
Annual Sum or Average 18.18 0.79 17.39 31.81 28.17 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 5.86 7.15 0.00 0.00 0.00
Maximum of Months 28.45 4.72 23.73 71.04 58.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.69 0.00 11.69 10.82 45.09 0.00 0.00 0.00
February 13.09 0.00 13.09 7.88 42.93 0.00 0.00 0.00
March 17.42 0.00 17.42 18.81 37.92 0.00 0.00 0.00
April 21.53 0.20 21.33 36.87 22.44 0.00 0.00 0.00
May 24.70 1.70 23.00 48.04 15.58 0.00 0.00 0.00
June 28.35 4.66 23.69 70.79 7.80 0.00 0.00 0.00
July 24.29 2.28 22.01 58.94 7.15 0.00 0.00 0.00
August 19.94 0.43 19.51 50.07 8.73 0.00 0.00 0.00
September 18.77 0.00 18.76 41.15 12.97 0.00 0.00 0.00
October 14.71 0.00 14.71 20.74 33.57 0.00 0.00 0.00
November 12.18 0.00 12.18 9.38 46.12 0.00 0.00 0.00
December 10.86 0.00 10.86 5.86 58.56 0.00 0.00 0.00
                 
Annual Sum or Average 18.15 0.77 17.37 31.72 28.18 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 5.86 7.15 0.00 0.00 0.00
Maximum of Months 28.35 4.66 23.69 70.79 58.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.69 0.00 11.69 10.82 45.09 0.00 0.00 0.00
February 13.09 0.00 13.09 7.88 42.93 0.00 0.00 0.00
March 17.42 0.00 17.42 18.81 37.92 0.00 0.00 0.00
April 21.52 0.20 21.32 36.86 22.45 0.00 0.00 0.00
May 24.70 1.70 23.00 48.04 15.58 0.00 0.00 0.00
June 28.35 4.66 23.69 70.79 7.80 0.00 0.00 0.00
July 24.29 2.28 22.01 58.94 7.15 0.00 0.00 0.00
August 19.94 0.43 19.51 50.07 8.73 0.00 0.00 0.00
September 18.77 0.00 18.76 41.15 12.97 0.00 0.00 0.00
October 14.71 0.00 14.71 20.74 33.57 0.00 0.00 0.00
November 12.18 0.00 12.18 9.38 46.12 0.00 0.00 0.00
December 10.86 0.00 10.86 5.86 58.56 0.00 0.00 0.00
                 
Annual Sum or Average 18.15 0.77 17.37 31.72 28.18 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 5.86 7.15 0.00 0.00 0.00
Maximum of Months 28.35 4.66 23.69 70.79 58.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.69 0.00 11.69 10.82 45.09 0.00 0.00 0.00
February 13.09 0.00 13.09 7.88 42.93 0.00 0.00 0.00
March 17.42 0.00 17.42 18.81 37.92 0.00 0.00 0.00
April 21.52 0.20 21.32 36.86 22.45 0.00 0.00 0.00
May 24.70 1.70 23.00 48.04 15.58 0.00 0.00 0.00
June 28.35 4.66 23.69 70.79 7.80 0.00 0.00 0.00
July 24.29 2.28 22.01 58.94 7.15 0.00 0.00 0.00
August 19.94 0.43 19.51 50.07 8.73 0.00 0.00 0.00
September 18.77 0.00 18.76 41.15 12.97 0.00 0.00 0.00
October 14.71 0.00 14.71 20.74 33.57 0.00 0.00 0.00
November 12.18 0.00 12.18 9.38 46.12 0.00 0.00 0.00
December 10.86 0.00 10.86 5.86 58.56 0.00 0.00 0.00
                 
Annual Sum or Average 18.15 0.77 17.37 31.72 28.18 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 5.86 7.15 0.00 0.00 0.00
Maximum of Months 28.35 4.66 23.69 70.79 58.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.69 0.00 11.69 10.82 45.09 0.00 0.00 0.00
February 13.09 0.00 13.09 7.88 42.93 0.00 0.00 0.00
March 17.42 0.00 17.42 18.81 37.92 0.00 0.00 0.00
April 21.53 0.20 21.33 36.88 22.45 0.00 0.00 0.00
May 24.70 1.70 23.00 48.04 15.58 0.00 0.00 0.00
June 28.35 4.66 23.69 70.79 7.80 0.00 0.00 0.00
July 24.29 2.28 22.01 58.94 7.15 0.00 0.00 0.00
August 19.94 0.43 19.51 50.07 8.73 0.00 0.00 0.00
September 18.77 0.00 18.76 41.15 12.98 0.00 0.00 0.00
October 14.71 0.00 14.71 20.74 33.57 0.00 0.00 0.00
November 12.18 0.00 12.18 9.38 46.12 0.00 0.00 0.00
December 10.86 0.00 10.86 5.86 58.56 0.00 0.00 0.00
                 
Annual Sum or Average 18.15 0.77 17.37 31.72 28.18 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 5.86 7.15 0.00 0.00 0.00
Maximum of Months 28.35 4.66 23.69 70.79 58.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.69 0.00 11.69 10.82 45.09 0.00 0.00 0.00
February 13.09 0.00 13.09 7.88 42.93 0.00 0.00 0.00
March 17.42 0.00 17.42 18.81 37.92 0.00 0.00 0.00
April 21.58 0.21 21.37 36.99 22.45 0.00 0.00 0.00
May 24.84 1.77 23.07 48.39 15.58 0.00 0.00 0.00
June 28.45 4.72 23.73 71.03 7.80 0.00 0.00 0.00
July 24.37 2.31 22.05 59.12 7.15 0.00 0.00 0.00
August 20.00 0.45 19.55 50.22 8.73 0.00 0.00 0.00
September 18.77 0.00 18.76 41.15 12.98 0.00 0.00 0.00
October 14.71 0.00 14.71 20.74 33.57 0.00 0.00 0.00
November 12.18 0.00 12.18 9.38 46.12 0.00 0.00 0.00
December 10.86 0.00 10.86 5.86 58.56 0.00 0.00 0.00
                 
Annual Sum or Average 18.18 0.79 17.39 31.81 28.18 0.00 0.00 0.00
Minimum of Months 10.86 0.00 10.86 5.86 7.15 0.00 0.00 0.00
Maximum of Months 28.45 4.72 23.73 71.03 58.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.37 24.53 14.84 58.14 48.33 0.00 0.00 0.00
February 31.29 15.19 16.10 37.87 43.89 0.00 0.00 0.00
March 41.15 19.66 21.49 57.63 39.02 0.00 0.00 0.00
April 63.10 35.63 27.46 107.04 25.60 0.00 0.00 0.00
May 62.82 34.64 28.19 113.07 19.11 0.00 0.00 0.00
June 66.94 38.72 28.22 134.40 9.81 0.00 0.00 0.00
July 48.13 22.02 26.11 98.26 8.44 0.00 0.00 0.00
August 46.21 22.83 23.38 94.63 10.05 0.00 0.00 0.00
September 40.34 16.78 23.56 77.84 14.36 0.00 0.00 0.00
October 42.09 24.03 18.06 66.92 35.49 0.00 0.00 0.00
November 39.24 23.79 15.45 55.11 48.35 0.00 0.00 0.00
December 31.62 18.05 13.56 40.96 60.49 0.00 0.00 0.00
                 
Annual Sum or Average 46.08 24.69 21.39 78.66 30.20 0.00 0.00 0.00
Minimum of Months 31.29 15.19 13.56 37.87 8.44 0.00 0.00 0.00
Maximum of Months 66.94 38.72 28.22 134.40 60.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.34 24.51 14.83 58.06 48.33 0.00 0.00 0.00
February 31.28 15.19 16.10 37.87 43.89 0.00 0.00 0.00
March 41.15 19.66 21.49 57.63 39.02 0.00 0.00 0.00
April 63.10 35.63 27.46 107.04 25.60 0.00 0.00 0.00
May 62.82 34.64 28.19 113.07 19.11 0.00 0.00 0.00
June 66.94 38.72 28.22 134.40 9.81 0.00 0.00 0.00
July 48.13 22.02 26.11 98.26 8.44 0.00 0.00 0.00
August 46.21 22.83 23.38 94.63 10.05 0.00 0.00 0.00
September 40.33 16.78 23.56 77.83 14.36 0.00 0.00 0.00
October 42.09 24.03 18.06 66.92 35.49 0.00 0.00 0.00
November 39.23 23.78 15.45 55.07 48.35 0.00 0.00 0.00
December 31.58 18.03 13.55 40.86 60.49 0.00 0.00 0.00
                 
Annual Sum or Average 46.07 24.68 21.38 78.64 30.20 0.00 0.00 0.00
Minimum of Months 31.28 15.19 13.55 37.87 8.44 0.00 0.00 0.00
Maximum of Months 66.94 38.72 28.22 134.40 60.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.34 24.51 14.83 58.06 48.33 0.00 0.00 0.00
February 31.28 15.19 16.10 37.87 43.89 0.00 0.00 0.00
March 41.15 19.66 21.49 57.63 39.02 0.00 0.00 0.00
April 63.10 35.63 27.46 107.04 25.60 0.00 0.00 0.00
May 62.82 34.64 28.19 113.07 19.11 0.00 0.00 0.00
June 66.94 38.72 28.22 134.40 9.81 0.00 0.00 0.00
July 48.13 22.02 26.11 98.26 8.44 0.00 0.00 0.00
August 46.21 22.83 23.38 94.63 10.05 0.00 0.00 0.00
September 40.33 16.78 23.56 77.83 14.36 0.00 0.00 0.00
October 42.09 24.03 18.06 66.92 35.49 0.00 0.00 0.00
November 39.23 23.78 15.45 55.07 48.35 0.00 0.00 0.00
December 31.58 18.03 13.55 40.86 60.49 0.00 0.00 0.00
                 
Annual Sum or Average 46.07 24.68 21.38 78.64 30.20 0.00 0.00 0.00
Minimum of Months 31.28 15.19 13.55 37.87 8.44 0.00 0.00 0.00
Maximum of Months 66.94 38.72 28.22 134.40 60.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.34 24.51 14.83 58.06 48.33 0.00 0.00 0.00
February 31.29 15.19 16.10 37.87 43.89 0.00 0.00 0.00
March 41.15 19.66 21.49 57.63 39.02 0.00 0.00 0.00
April 63.10 35.63 27.46 107.04 25.60 0.00 0.00 0.00
May 62.82 34.64 28.19 113.07 19.11 0.00 0.00 0.00
June 66.94 38.72 28.22 134.40 9.81 0.00 0.00 0.00
July 48.13 22.02 26.11 98.26 8.44 0.00 0.00 0.00
August 46.21 22.83 23.38 94.63 10.05 0.00 0.00 0.00
September 40.34 16.78 23.56 77.84 14.36 0.00 0.00 0.00
October 42.09 24.03 18.06 66.92 35.49 0.00 0.00 0.00
November 39.23 23.78 15.45 55.07 48.35 0.00 0.00 0.00
December 31.58 18.03 13.55 40.86 60.49 0.00 0.00 0.00
                 
Annual Sum or Average 46.07 24.68 21.38 78.64 30.20 0.00 0.00 0.00
Minimum of Months 31.29 15.19 13.55 37.87 8.44 0.00 0.00 0.00
Maximum of Months 66.94 38.72 28.22 134.40 60.49 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265178E+09 0.212609E+09 52569758.64 0.409827E+09 0.131005E+09
February 0.150424E+09 0.102533E+09 47890940.68 0.213356E+09 0.105857E+09
March 0.123002E+09 60336682.08 62664846.39 0.184427E+09 0.105454E+09
April 78182586.22 18747979.57 59434606.64 0.141702E+09 62138472.90
May 59071916.44 943.98 59070972.46 0.117790E+09 45237782.13
June 56932267.71 0.15 56932267.57 0.151398E+09 20915404.67
July 56056335.08 170502.84 55885832.23 0.139727E+09 19597833.35
August 57065009.07 4512002.59 52553006.48 0.141171E+09 24199729.50
September 94806089.26 34830561.73 59975527.53 0.193755E+09 36423013.95
October 0.188079E+09 0.130119E+09 57959509.18 0.312310E+09 93371743.50
November 0.218794E+09 0.168574E+09 50219488.66 0.331347E+09 0.122651E+09
December 0.246381E+09 0.195921E+09 50460401.57 0.361550E+09 0.160054E+09
           
Annual Sum or Average 0.159397E+10 0.928355E+09 0.665617E+09 0.269836E+10 0.926903E+09
Minimum of Months 56056335.08 0.15 47890940.68 0.117790E+09 19597833.35
Maximum of Months 0.265178E+09 0.212609E+09 62664846.39 0.409827E+09 0.160054E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265177E+09 0.212609E+09 52568628.79 0.409827E+09 0.131002E+09
February 0.150422E+09 0.102533E+09 47889171.46 0.213354E+09 0.105856E+09
March 0.122964E+09 60315306.77 62648446.71 0.184357E+09 0.105468E+09
April 77779436.39 18570520.95 59208915.45 0.140723E+09 62135932.47
May 59064949.89 0.00 59064949.89 0.117779E+09 45235269.59
June 56930568.63 0.00 56930568.63 0.151399E+09 20913822.83
July 56052432.58 169331.62 55883100.96 0.139721E+09 19596705.29
August 56999227.25 4484605.37 52514621.88 0.141010E+09 24198410.49
September 94570528.18 34748348.68 59822179.50 0.193217E+09 36421644.33
October 0.188077E+09 0.130119E+09 57957985.50 0.312310E+09 93369142.45
November 0.218792E+09 0.168574E+09 50218063.63 0.331346E+09 0.122648E+09
December 0.246380E+09 0.195921E+09 50459179.60 0.361550E+09 0.160051E+09
           
Annual Sum or Average 0.159321E+10 0.928044E+09 0.665166E+09 0.269659E+10 0.926896E+09
Minimum of Months 56052432.58 0.00 47889171.46 0.117779E+09 19596705.29
Maximum of Months 0.265177E+09 0.212609E+09 62648446.71 0.409827E+09 0.160051E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265177E+09 0.212609E+09 52568628.79 0.409827E+09 0.131002E+09
February 0.150422E+09 0.102533E+09 47889171.46 0.213354E+09 0.105856E+09
March 0.122964E+09 60315306.77 62648446.71 0.184357E+09 0.105468E+09
April 77779436.39 18570520.95 59208915.45 0.140723E+09 62135932.47
May 59064949.89 0.00 59064949.89 0.117779E+09 45235269.59
June 56930568.63 0.00 56930568.63 0.151399E+09 20913822.83
July 56052432.58 169331.62 55883100.96 0.139721E+09 19596705.29
August 56998696.69 4484096.99 52514599.70 0.141008E+09 24198410.49
September 94547760.92 34745652.63 59802108.29 0.193171E+09 36421943.63
October 0.188077E+09 0.130119E+09 57957985.50 0.312310E+09 93369142.45
November 0.218792E+09 0.168574E+09 50218063.63 0.331346E+09 0.122648E+09
December 0.246380E+09 0.195921E+09 50459179.60 0.361550E+09 0.160051E+09
           
Annual Sum or Average 0.159319E+10 0.928041E+09 0.665146E+09 0.269655E+10 0.926896E+09
Minimum of Months 56052432.58 0.00 47889171.46 0.117779E+09 19596705.29
Maximum of Months 0.265177E+09 0.212609E+09 62648446.71 0.409827E+09 0.160051E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265177E+09 0.212609E+09 52568628.79 0.409827E+09 0.131002E+09
February 0.150422E+09 0.102533E+09 47889171.46 0.213354E+09 0.105856E+09
March 0.122964E+09 60315306.77 62648446.71 0.184357E+09 0.105468E+09
April 77779436.39 18570520.95 59208915.45 0.140723E+09 62135932.47
May 59064949.89 0.00 59064949.89 0.117779E+09 45235269.59
June 56930568.63 0.00 56930568.63 0.151399E+09 20913822.83
July 56052432.58 169331.62 55883100.96 0.139721E+09 19596705.29
August 56998697.52 4484097.82 52514599.70 0.141008E+09 24198402.99
September 94548151.80 34745658.65 59802493.15 0.193168E+09 36418157.65
October 0.188077E+09 0.130119E+09 57957985.50 0.312310E+09 93369142.45
November 0.218792E+09 0.168574E+09 50218063.63 0.331346E+09 0.122648E+09
December 0.246380E+09 0.195921E+09 50459179.60 0.361550E+09 0.160051E+09
           
Annual Sum or Average 0.159319E+10 0.928041E+09 0.665146E+09 0.269654E+10 0.926892E+09
Minimum of Months 56052432.58 0.00 47889171.46 0.117779E+09 19596705.29
Maximum of Months 0.265177E+09 0.212609E+09 62648446.71 0.409827E+09 0.160051E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265177E+09 0.212609E+09 52568628.79 0.409827E+09 0.131002E+09
February 0.150422E+09 0.102533E+09 47889171.46 0.213354E+09 0.105856E+09
March 0.122964E+09 60315306.77 62648446.71 0.184357E+09 0.105468E+09
April 77779436.39 18570520.95 59208915.45 0.140723E+09 62135932.47
May 59064949.89 0.00 59064949.89 0.117779E+09 45235269.59
June 56930568.63 0.00 56930568.63 0.151399E+09 20913822.83
July 56052432.58 169331.62 55883100.96 0.139721E+09 19596705.29
August 56999321.60 4484721.90 52514599.70 0.141010E+09 24198075.11
September 94576834.34 34749275.90 59827558.44 0.193184E+09 36374908.65
October 0.188077E+09 0.130119E+09 57957985.50 0.312310E+09 93369142.45
November 0.218792E+09 0.168574E+09 50218063.63 0.331346E+09 0.122648E+09
December 0.246380E+09 0.195921E+09 50459179.60 0.361550E+09 0.160051E+09
           
Annual Sum or Average 0.159322E+10 0.928045E+09 0.665171E+09 0.269656E+10 0.926849E+09
Minimum of Months 56052432.58 0.00 47889171.46 0.117779E+09 19596705.29
Maximum of Months 0.265177E+09 0.212609E+09 62648446.71 0.409827E+09 0.160051E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.265178E+09 0.212609E+09 52569758.58 0.409827E+09 0.131005E+09
February 0.150424E+09 0.102533E+09 47890940.59 0.213356E+09 0.105857E+09
March 0.123005E+09 60337824.33 62667423.22 0.184394E+09 0.105412E+09
April 78133110.68 18760717.64 59372393.04 0.141570E+09 62076558.41
May 59071669.29 949.45 59070719.84 0.117790E+09 45237782.00
June 56932267.65 0.17 56932267.48 0.151398E+09 20915404.59
July 56056598.56 170998.11 55885600.45 0.139729E+09 19597833.29
August 57074380.73 4521414.42 52552966.32 0.141203E+09 24199122.70
September 94859344.60 34860879.56 59998465.05 0.193771E+09 36298513.52
October 0.188079E+09 0.130119E+09 57959509.10 0.312310E+09 93371743.36
November 0.218794E+09 0.168574E+09 50219488.59 0.331347E+09 0.122651E+09
December 0.246381E+09 0.195921E+09 50460401.51 0.361550E+09 0.160054E+09
           
Annual Sum or Average 0.159399E+10 0.928409E+09 0.665580E+09 0.269824E+10 0.926675E+09
Minimum of Months 56056598.56 0.17 47890940.59 0.117790E+09 19597833.29
Maximum of Months 0.265178E+09 0.212609E+09 62667423.22 0.409827E+09 0.160054E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.372227E+09 0.297867E+09 74359880.74 0.573496E+09 0.183794E+09
February 0.211856E+09 0.143650E+09 68205992.45 0.299805E+09 0.147793E+09
March 0.194585E+09 0.101060E+09 93524599.47 0.298403E+09 0.147486E+09
April 0.135191E+09 45904329.13 89286902.37 0.251219E+09 88148443.86
May 88099954.90 3021369.87 85078585.03 0.174118E+09 64698413.87
June 80828902.75 0.00 80828902.75 0.210387E+09 30263494.36
July 80962298.03 1143927.77 79818370.25 0.197848E+09 28089163.58
August 95983996.56 17403077.86 78580918.70 0.230722E+09 34700121.82
September 0.154316E+09 63630667.34 90685271.98 0.311737E+09 51750173.48
October 0.272427E+09 0.189238E+09 83189002.02 0.451300E+09 0.131606E+09
November 0.307427E+09 0.236175E+09 71252341.71 0.464168E+09 0.171835E+09
December 0.345950E+09 0.274488E+09 71462447.27 0.506197E+09 0.224146E+09
           
Annual Sum or Average 0.233985E+10 0.137358E+10 0.966273E+09 0.396940E+10 0.130431E+10
Minimum of Months 80828902.75 0.00 68205992.45 0.174118E+09 28089163.58
Maximum of Months 0.372227E+09 0.297867E+09 93524599.47 0.573496E+09 0.224146E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100478E+09 63150174.27 37327402.41 0.133256E+09 0.117045E+09
February 88600292.57 51091515.84 37508776.73 0.105702E+09 0.100729E+09
March 0.121609E+09 62706684.43 58902778.57 0.165229E+09 97767730.70
April 0.167432E+09 98906075.00 68526090.45 0.276159E+09 57903323.10
May 0.178167E+09 0.104415E+09 73752208.96 0.312038E+09 43898528.76
June 0.179527E+09 0.109920E+09 69607895.73 0.355225E+09 21082673.45
July 0.155776E+09 86835197.69 68941211.43 0.306232E+09 20305058.43
August 0.148776E+09 84150345.22 64625799.70 0.293134E+09 24766023.38
September 0.118315E+09 56876785.08 61437854.90 0.221403E+09 34232867.21
October 0.125097E+09 76133404.74 48964054.00 0.191384E+09 87109708.30
November 93639837.96 56445199.83 37194638.13 0.118549E+09 0.115339E+09
December 88509852.72 53704888.29 34804964.42 0.100791E+09 0.149650E+09
           
Annual Sum or Average 0.156593E+10 0.904335E+09 0.661594E+09 0.257910E+10 0.869828E+09
Minimum of Months 88509852.72 51091515.84 34804964.42 0.100791E+09 20305058.43
Maximum of Months 0.179527E+09 0.109920E+09 73752208.96 0.355225E+09 0.149650E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100476E+09 63150174.27 37326272.61 0.133256E+09 0.117042E+09
February 88598523.44 51091515.84 37507007.60 0.105700E+09 0.100728E+09
March 0.121607E+09 62706684.43 58900243.99 0.165227E+09 97765741.20
April 0.167430E+09 98906075.00 68524279.90 0.276159E+09 57900866.77
May 0.178165E+09 0.104415E+09 73750298.99 0.312038E+09 43896098.69
June 0.179526E+09 0.109920E+09 69606196.89 0.355226E+09 21081079.02
July 0.155774E+09 86835197.69 68938952.86 0.306231E+09 20303932.57
August 0.148774E+09 84150345.22 64623735.14 0.293133E+09 24764639.85
September 0.118312E+09 56876785.08 61435281.03 0.221400E+09 34231351.08
October 0.125096E+09 76133404.74 48962530.39 0.191383E+09 87107069.09
November 93638413.00 56445199.83 37193213.18 0.118549E+09 0.115337E+09
December 88508630.81 53704888.29 34803742.52 0.100791E+09 0.149647E+09
           
Annual Sum or Average 0.156591E+10 0.904335E+09 0.661572E+09 0.257909E+10 0.869804E+09
Minimum of Months 88508630.81 51091515.84 34803742.52 0.100791E+09 20303932.57
Maximum of Months 0.179526E+09 0.109920E+09 73750298.99 0.355226E+09 0.149647E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100476E+09 63150174.27 37326272.61 0.133256E+09 0.117042E+09
February 88598523.44 51091515.84 37507007.60 0.105700E+09 0.100728E+09
March 0.121607E+09 62706684.43 58900243.99 0.165227E+09 97765741.20
April 0.167430E+09 98906075.00 68524279.90 0.276159E+09 57900866.77
May 0.178165E+09 0.104415E+09 73750298.99 0.312038E+09 43896098.69
June 0.179526E+09 0.109920E+09 69606196.89 0.355226E+09 21081079.02
July 0.155774E+09 86835197.69 68938952.86 0.306231E+09 20303932.57
August 0.148774E+09 84150345.22 64623735.14 0.293133E+09 24764639.85
September 0.118312E+09 56876785.08 61435281.03 0.221400E+09 34231351.08
October 0.125096E+09 76133404.74 48962530.39 0.191383E+09 87107069.09
November 93638413.00 56445199.83 37193213.18 0.118549E+09 0.115337E+09
December 88508630.81 53704888.29 34803742.52 0.100791E+09 0.149647E+09
           
Annual Sum or Average 0.156591E+10 0.904335E+09 0.661572E+09 0.257909E+10 0.869804E+09
Minimum of Months 88508630.81 51091515.84 34803742.52 0.100791E+09 20303932.57
Maximum of Months 0.179526E+09 0.109920E+09 73750298.99 0.355226E+09 0.149647E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.100557E+09 63204672.97 37352137.73 0.133470E+09 0.117045E+09
February 88603412.49 51093328.72 37510083.78 0.105709E+09 0.100728E+09
March 0.121609E+09 62706684.43 58902800.61 0.165229E+09 97767730.81
April 0.167432E+09 98906075.00 68526090.54 0.276159E+09 57903323.22
May 0.178167E+09 0.104415E+09 73752209.06 0.312038E+09 43898528.88
June 0.179527E+09 0.109920E+09 69607895.82 0.355225E+09 21082673.53
July 0.155776E+09 86835197.69 68941211.55 0.306232E+09 20305058.49
August 0.148776E+09 84150345.22 64625799.81 0.293134E+09 24766023.46
September 0.118315E+09 56876785.08 61437855.04 0.221403E+09 34232867.29
October 0.125102E+09 76136419.05 48965236.27 0.191395E+09 87109708.44
November 93676125.74 56470239.89 37205885.86 0.118639E+09 0.115330E+09
December 88614024.86 53770829.57 34843195.29 0.101038E+09 0.149616E+09
           
Annual Sum or Average 0.156616E+10 0.904485E+09 0.661670E+09 0.257967E+10 0.869785E+09
Minimum of Months 88603412.49 51093328.72 34843195.29 0.101038E+09 20305058.49
Maximum of Months 0.179527E+09 0.109920E+09 73752209.06 0.355225E+09 0.149616E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31305053.93 0.00 31305053.93 28989085.79 0.120780E+09
February 31669556.41 0.00 31669556.41 19057461.08 0.103846E+09
March 46660428.21 0.00 46660428.21 50378825.13 0.101560E+09
April 55914091.78 556194.62 55357897.16 95592178.74 57922087.46
May 66498954.92 4757988.64 61740966.28 0.129570E+09 41716455.14
June 73746086.68 12243519.74 61502566.94 0.184146E+09 20213256.51
July 65330526.99 6251048.12 59079478.87 0.158564E+09 19155211.05
August 53621787.81 1239827.49 52381960.33 0.134658E+09 23374420.46
September 48654248.11 12946.38 48641301.73 0.106662E+09 33612334.20
October 39390282.78 0.00 39390282.78 55554942.23 89915840.25
November 31582547.23 0.00 31582547.23 24302348.64 0.119536E+09
December 29090790.15 0.00 29090790.15 15699091.18 0.156859E+09
           
Annual Sum or Average 0.573464E+09 25061524.98 0.548403E+09 0.100317E+10 0.888491E+09
Minimum of Months 29090790.15 0.00 29090790.15 15699091.18 19155211.05
Maximum of Months 73746086.68 12243519.74 61740966.28 0.184146E+09 0.156859E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31303924.08 0.00 31303924.08 28988943.31 0.120777E+09
February 31667787.18 0.00 31667787.18 19055983.94 0.103844E+09
March 46657893.50 0.00 46657893.50 50376298.83 0.101558E+09
April 55801596.31 520275.95 55281320.36 95555875.37 58159267.59
May 66154606.28 4562672.48 61591933.80 0.128666E+09 41720419.40
June 73496014.65 12080640.12 61415374.53 0.183477E+09 20211647.23
July 65065144.23 6103327.34 58961816.89 0.157875E+09 19154049.52
August 53405008.67 1141434.84 52263573.83 0.134104E+09 23373204.15
September 48650115.11 12894.95 48637220.16 0.106658E+09 33612700.70
October 39388759.10 0.00 39388759.10 55554322.50 89912952.67
November 31581122.20 0.00 31581122.20 24301572.30 0.119533E+09
December 29089568.18 0.00 29089568.18 15698746.96 0.156856E+09
           
Annual Sum or Average 0.572262E+09 24421245.68 0.547840E+09 0.100031E+10 0.888713E+09
Minimum of Months 29089568.18 0.00 29089568.18 15698746.96 19154049.52
Maximum of Months 73496014.65 12080640.12 61591933.80 0.183477E+09 0.156856E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31303924.08 0.00 31303924.08 28988943.31 0.120777E+09
February 31667787.18 0.00 31667787.18 19055983.94 0.103844E+09
March 46657893.50 0.00 46657893.50 50376298.83 0.101558E+09
April 55783308.77 514411.04 55268897.73 95551305.71 58201038.39
May 66154606.28 4562672.48 61591933.80 0.128666E+09 41720419.40
June 73496014.65 12080640.12 61415374.53 0.183477E+09 20211647.23
July 65065144.23 6103327.34 58961816.89 0.157875E+09 19154049.52
August 53403308.12 1141351.57 52261956.55 0.134102E+09 23374274.11
September 48644501.14 12504.20 48631996.94 0.106656E+09 33622102.02
October 39388759.10 0.00 39388759.10 55554322.50 89912952.67
November 31581122.20 0.00 31581122.20 24301572.30 0.119533E+09
December 29089568.18 0.00 29089568.18 15698746.96 0.156856E+09
           
Annual Sum or Average 0.572236E+09 24414906.76 0.547821E+09 0.100030E+10 0.888765E+09
Minimum of Months 29089568.18 0.00 29089568.18 15698746.96 19154049.52
Maximum of Months 73496014.65 12080640.12 61591933.80 0.183477E+09 0.156856E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31303924.08 0.00 31303924.08 28988943.31 0.120777E+09
February 31667787.18 0.00 31667787.18 19055983.94 0.103844E+09
March 46657893.50 0.00 46657893.50 50376298.83 0.101558E+09
April 55783308.77 514411.04 55268897.73 95551305.71 58201038.39
May 66154606.28 4562672.48 61591933.80 0.128666E+09 41720419.40
June 73496014.65 12080640.12 61415374.53 0.183477E+09 20211647.23
July 65065144.23 6103327.34 58961816.89 0.157875E+09 19154049.52
August 53403077.88 1141336.97 52261740.91 0.134102E+09 23375264.24
September 48642415.38 12392.03 48630023.35 0.106660E+09 33630585.18
October 39388759.10 0.00 39388759.10 55554322.50 89912952.67
November 31581122.20 0.00 31581122.20 24301572.30 0.119533E+09
December 29089568.18 0.00 29089568.18 15698746.96 0.156856E+09
           
Annual Sum or Average 0.572234E+09 24414779.99 0.547819E+09 0.100031E+10 0.888775E+09
Minimum of Months 29089568.18 0.00 29089568.18 15698746.96 19154049.52
Maximum of Months 73496014.65 12080640.12 61591933.80 0.183477E+09 0.156856E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31303924.08 0.00 31303924.08 28988943.31 0.120777E+09
February 31667787.18 0.00 31667787.18 19055983.94 0.103844E+09
March 46657893.50 0.00 46657893.50 50376298.83 0.101558E+09
April 55804686.36 520031.44 55284654.92 95599538.65 58200418.18
May 66154606.28 4562672.48 61591933.80 0.128666E+09 41720419.40
June 73496014.65 12080640.12 61415374.53 0.183477E+09 20211647.23
July 65065144.23 6103327.34 58961816.89 0.157875E+09 19154049.52
August 53404571.78 1141406.29 52263165.49 0.134106E+09 23375516.44
September 48645429.04 12658.45 48632770.59 0.106668E+09 33632635.26
October 39388759.10 0.00 39388759.10 55554322.50 89912952.67
November 31581122.20 0.00 31581122.20 24301572.30 0.119533E+09
December 29089568.18 0.00 29089568.18 15698746.96 0.156856E+09
           
Annual Sum or Average 0.572260E+09 24420736.13 0.547839E+09 0.100037E+10 0.888777E+09
Minimum of Months 29089568.18 0.00 29089568.18 15698746.96 19154049.52
Maximum of Months 73496014.65 12080640.12 61591933.80 0.183477E+09 0.156856E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31305053.87 0.00 31305053.87 28989085.78 0.120780E+09
February 31669556.31 0.00 31669556.31 19057461.00 0.103846E+09
March 46660428.08 0.00 46660428.08 50378825.00 0.101560E+09
April 55936369.73 553884.34 55382485.39 95888050.38 58198586.04
May 66531304.28 4750258.94 61781045.33 0.129603E+09 41722900.27
June 73740894.33 12229155.53 61511738.80 0.184098E+09 20213256.42
July 65266963.07 6196520.69 59070442.38 0.158352E+09 19155208.31
August 53574784.74 1211152.08 52363632.66 0.134518E+09 23375493.93
September 48648961.88 12696.78 48636265.10 0.106673E+09 33634328.59
October 39390282.70 0.00 39390282.70 55554942.20 89915840.10
November 31582547.16 0.00 31582547.16 24302348.60 0.119536E+09
December 29090790.09 0.00 29090790.09 15699091.16 0.156859E+09
           
Annual Sum or Average 0.573398E+09 24953668.36 0.548444E+09 0.100311E+10 0.888797E+09
Minimum of Months 29090790.09 0.00 29090790.09 15699091.16 19155208.31
Maximum of Months 73740894.33 12229155.53 61781045.33 0.184098E+09 0.156859E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.105436E+09 65694993.47 39741060.34 0.155714E+09 0.129449E+09
February 75689239.69 36744885.92 38944353.77 91618195.38 0.106169E+09
March 0.110208E+09 52646082.21 57561544.55 0.154352E+09 0.104508E+09
April 0.163549E+09 92360257.48 71188485.42 0.277442E+09 66348440.67
May 0.168262E+09 92768111.36 75494257.15 0.302851E+09 51193076.54
June 0.173517E+09 0.100359E+09 73157892.73 0.348369E+09 25434781.83
July 0.128919E+09 58981466.12 69937480.79 0.263186E+09 22617406.00
August 0.123766E+09 61152023.95 62613698.31 0.253464E+09 26906656.84
September 0.104549E+09 43492064.00 61057182.62 0.201751E+09 37226775.78
October 0.112727E+09 64352586.77 48374330.52 0.179252E+09 95062769.70
November 0.101714E+09 61655510.47 40058667.80 0.142841E+09 0.125325E+09
December 84687873.55 48357026.99 36330846.56 0.109704E+09 0.162023E+09
           
Annual Sum or Average 0.145302E+10 0.778564E+09 0.674460E+09 0.248054E+10 0.952263E+09
Minimum of Months 75689239.69 36744885.92 36330846.56 91618195.38 22617406.00
Maximum of Months 0.173517E+09 0.100359E+09 75494257.15 0.348369E+09 0.162023E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.105360E+09 65643990.77 39715711.56 0.155510E+09 0.129446E+09
February 75683962.22 36742904.39 38941057.83 91608425.69 0.106168E+09
March 0.110205E+09 52646082.21 57558983.36 0.154349E+09 0.104506E+09
April 0.163547E+09 92360257.48 71186674.87 0.277442E+09 66345794.54
May 0.168260E+09 92768111.36 75492347.18 0.302851E+09 51190360.33
June 0.173515E+09 0.100359E+09 73156193.89 0.348370E+09 25432937.40
July 0.128917E+09 58981466.12 69935222.22 0.263184E+09 22616130.75
August 0.123764E+09 61152023.95 62611633.75 0.253463E+09 26905073.53
September 0.104547E+09 43492064.00 61054608.75 0.201748E+09 37225066.29
October 0.112721E+09 64349287.03 48371284.09 0.179238E+09 95059869.47
November 0.101671E+09 61629315.93 40042162.08 0.142735E+09 0.125326E+09
December 84583382.12 48290463.15 36292918.97 0.109428E+09 0.162020E+09
           
Annual Sum or Average 0.145277E+10 0.778415E+09 0.674359E+09 0.247993E+10 0.952241E+09
Minimum of Months 75683962.22 36742904.39 36292918.97 91608425.69 22616130.75
Maximum of Months 0.173515E+09 0.100359E+09 75492347.18 0.348370E+09 0.162020E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.105360E+09 65643990.77 39715711.56 0.155510E+09 0.129446E+09
February 75683962.22 36742904.39 38941057.83 91608425.69 0.106168E+09
March 0.110205E+09 52646082.21 57558983.36 0.154349E+09 0.104506E+09
April 0.163547E+09 92360257.48 71186674.87 0.277442E+09 66345794.54
May 0.168260E+09 92768111.36 75492347.18 0.302851E+09 51190360.33
June 0.173515E+09 0.100359E+09 73156193.89 0.348370E+09 25432937.40
July 0.128917E+09 58981466.12 69935222.22 0.263184E+09 22616130.75
August 0.123764E+09 61152023.95 62611633.75 0.253463E+09 26905073.53
September 0.104547E+09 43492064.00 61054608.75 0.201748E+09 37225066.29
October 0.112721E+09 64349287.03 48371284.09 0.179238E+09 95059869.47
November 0.101671E+09 61629315.93 40042162.08 0.142735E+09 0.125326E+09
December 84583382.12 48290463.15 36292918.97 0.109428E+09 0.162020E+09
           
Annual Sum or Average 0.145277E+10 0.778415E+09 0.674359E+09 0.247993E+10 0.952241E+09
Minimum of Months 75683962.22 36742904.39 36292918.97 91608425.69 22616130.75
Maximum of Months 0.173515E+09 0.100359E+09 75492347.18 0.348370E+09 0.162020E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.105361E+09 65643990.77 39716841.41 0.155510E+09 0.129449E+09
February 75685731.44 36742904.39 38942827.05 91609991.15 0.106169E+09
March 0.110208E+09 52646082.21 57561518.06 0.154352E+09 0.104508E+09
April 0.163549E+09 92360257.48 71188485.51 0.277442E+09 66348440.81
May 0.168262E+09 92768111.36 75494257.25 0.302851E+09 51193076.68
June 0.173517E+09 0.100359E+09 73157892.82 0.348369E+09 25434781.93
July 0.128919E+09 58981466.12 69937480.91 0.263186E+09 22617406.06
August 0.123766E+09 61152023.95 62613698.42 0.253464E+09 26906656.93
September 0.104549E+09 43492064.00 61057182.76 0.201751E+09 37226775.87
October 0.112722E+09 64349287.03 48372807.77 0.179239E+09 95062769.84
November 0.101673E+09 61629315.93 40043587.11 0.142736E+09 0.125328E+09
December 84584604.09 48290463.15 36294140.94 0.109429E+09 0.162024E+09
           
Annual Sum or Average 0.145280E+10 0.778415E+09 0.674381E+09 0.247994E+10 0.952268E+09
Minimum of Months 75685731.44 36742904.39 36294140.94 91609991.15 22617406.06
Maximum of Months 0.173517E+09 0.100359E+09 75494257.25 0.348369E+09 0.162024E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1132.19 362.09 733.01 587.48 145.52 0.00 0.00
February 653.08 323.63 460.64 313.68 146.97 0.00 0.00
March 524.43 291.30 348.14 172.86 175.27 0.00 0.00
April 423.37 177.81 232.49 60.84 171.65 0.00 0.00
May 328.86 125.49 165.21 1.13 164.08 0.00 0.00
June 431.62 60.08 162.97 0.00 162.97 0.00 0.00
July 386.87 54.38 155.80 0.81 154.99 0.00 0.00
August 402.15 67.16 163.58 16.57 147.01 0.00 0.00
September 567.89 104.19 278.64 105.06 173.58 0.00 0.00
October 868.11 258.30 523.03 362.14 160.89 0.00 0.00
November 946.08 350.20 625.07 481.34 143.74 0.00 0.00
December 998.92 442.23 681.09 541.37 139.72 0.00 0.00
               
Annual Sum or Average 639.02 217.70 377.37 220.15 157.22 0.00 0.00
Minimum of Months 328.86 54.38 155.80 0.00 139.72 0.00 0.00
Maximum of Months 1132.19 442.23 733.01 587.48 175.27 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 199.09 174.80 150.08 94.33 55.75 0.00 0.00
February 174.77 166.55 146.50 84.48 62.02 0.00 0.00
March 246.76 146.01 181.61 93.65 87.97 0.00 0.00
April 426.17 89.36 258.38 152.63 105.75 0.00 0.00
May 466.01 65.56 266.08 155.94 110.14 0.00 0.00
June 548.19 32.53 277.05 169.63 107.42 0.00 0.00
July 457.33 30.32 232.64 129.68 102.96 0.00 0.00
August 437.77 36.99 222.19 125.67 96.51 0.00 0.00
September 341.67 52.83 182.58 87.77 94.81 0.00 0.00
October 285.82 130.09 186.82 113.70 73.12 0.00 0.00
November 182.98 177.99 144.52 87.12 57.40 0.00 0.00
December 150.61 223.47 132.22 80.23 51.99 0.00 0.00
               
Annual Sum or Average 327.15 110.33 198.63 114.71 83.92 0.00 0.00
Minimum of Months 150.61 30.32 132.22 80.23 51.99 0.00 0.00
Maximum of Months 548.19 223.47 277.05 169.63 110.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 64.94 270.56 70.13 0.00 70.13 0.00 0.00
February 47.26 257.55 78.54 0.00 78.54 0.00 0.00
March 112.85 227.51 104.52 0.00 104.52 0.00 0.00
April 221.35 134.60 129.25 1.23 128.03 0.00 0.00
May 288.91 93.46 148.47 10.36 138.10 0.00 0.00
June 425.21 46.79 170.32 28.08 142.24 0.00 0.00
July 354.10 42.91 145.93 13.76 132.17 0.00 0.00
August 300.77 52.36 119.78 2.62 117.16 0.00 0.00
September 246.91 77.83 112.61 0.03 112.58 0.00 0.00
October 124.45 201.42 88.24 0.00 88.24 0.00 0.00
November 56.25 276.70 73.11 0.00 73.11 0.00 0.00
December 35.17 351.38 65.17 0.00 65.17 0.00 0.00
               
Annual Sum or Average 190.50 169.09 108.95 4.68 104.27 0.00 0.00
Minimum of Months 35.17 42.91 65.17 0.00 65.17 0.00 0.00
Maximum of Months 425.21 351.38 170.32 28.08 142.24 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 232.32 193.32 157.38 98.05 59.32 0.00 0.00
February 151.47 175.54 125.14 60.75 64.39 0.00 0.00
March 230.51 156.07 164.59 78.62 85.96 0.00 0.00
April 428.15 102.39 252.39 142.53 109.86 0.00 0.00
May 452.29 76.45 251.29 138.54 112.74 0.00 0.00
June 537.61 39.25 267.77 154.87 112.90 0.00 0.00
July 393.05 33.78 192.53 88.08 104.44 0.00 0.00
August 378.53 40.18 184.83 91.33 93.51 0.00 0.00
September 311.34 57.45 161.34 67.12 94.22 0.00 0.00
October 267.68 141.97 168.34 96.10 72.24 0.00 0.00
November 220.31 193.40 156.92 95.12 61.80 0.00 0.00
December 163.53 241.97 126.36 72.14 54.22 0.00 0.00
               
Annual Sum or Average 314.57 120.78 184.28 98.74 85.54 0.00 0.00
Minimum of Months 151.47 33.78 125.14 60.75 54.22 0.00 0.00
Maximum of Months 537.61 241.97 267.77 154.87 112.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.303246E+10 0.969810E+09 0.196329E+10 0.157352E+10 0.389774E+09 0.00 0.00
February 0.157992E+10 0.782921E+09 0.111439E+10 0.758846E+09 0.355545E+09 0.00 0.00
March 0.140464E+10 0.780207E+09 0.932447E+09 0.462996E+09 0.469451E+09 0.00 0.00
April 0.109736E+10 0.460886E+09 0.602625E+09 0.157695E+09 0.444930E+09 0.00 0.00
May 0.880809E+09 0.336109E+09 0.442503E+09 3023263.30 0.439480E+09 0.00 0.00
June 0.111877E+10 0.155738E+09 0.422416E+09 0.31 0.422416E+09 0.00 0.00
July 0.103618E+10 0.145664E+09 0.417285E+09 2162755.22 0.415122E+09 0.00 0.00
August 0.107713E+10 0.179888E+09 0.438119E+09 44374016.95 0.393745E+09 0.00 0.00
September 0.147196E+10 0.270066E+09 0.722225E+09 0.272311E+09 0.449914E+09 0.00 0.00
October 0.232516E+10 0.691825E+09 0.140089E+10 0.969954E+09 0.430940E+09 0.00 0.00
November 0.245225E+10 0.907729E+09 0.162018E+10 0.124762E+10 0.372564E+09 0.00 0.00
December 0.267550E+10 0.118446E+10 0.182423E+10 0.145001E+10 0.374220E+09 0.00 0.00
               
Annual Sum or Average 0.201521E+11 0.686530E+10 0.119006E+11 0.694252E+10 0.495810E+10 0.00 0.00
Minimum of Months 0.880809E+09 0.145664E+09 0.417285E+09 0.31 0.355545E+09 0.00 0.00
Maximum of Months 0.303246E+10 0.118446E+10 0.196329E+10 0.157352E+10 0.469451E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.533237E+09 0.468173E+09 0.401987E+09 0.252655E+09 0.149332E+09 0.00 0.00
February 0.422811E+09 0.402912E+09 0.354401E+09 0.204368E+09 0.150033E+09 0.00 0.00
March 0.660912E+09 0.391067E+09 0.486433E+09 0.250827E+09 0.235606E+09 0.00 0.00
April 0.110464E+10 0.231608E+09 0.669725E+09 0.395624E+09 0.274101E+09 0.00 0.00
May 0.124815E+10 0.175589E+09 0.712664E+09 0.417659E+09 0.295005E+09 0.00 0.00
June 0.142090E+10 84327504.36 0.718107E+09 0.439678E+09 0.278428E+09 0.00 0.00
July 0.122493E+10 81217982.07 0.623101E+09 0.347341E+09 0.275760E+09 0.00 0.00
August 0.117253E+10 99061326.53 0.595100E+09 0.336601E+09 0.258499E+09 0.00 0.00
September 0.885605E+09 0.136928E+09 0.473253E+09 0.227507E+09 0.245746E+09 0.00 0.00
October 0.765545E+09 0.348434E+09 0.500391E+09 0.304537E+09 0.195854E+09 0.00 0.00
November 0.474285E+09 0.461344E+09 0.374593E+09 0.225806E+09 0.148787E+09 0.00 0.00
December 0.403407E+09 0.598554E+09 0.354141E+09 0.214885E+09 0.139256E+09 0.00 0.00
               
Annual Sum or Average 0.103170E+11 0.347922E+10 0.626390E+10 0.361749E+10 0.264641E+10 0.00 0.00
Minimum of Months 0.403407E+09 81217982.07 0.354141E+09 0.204368E+09 0.139256E+09 0.00 0.00
Maximum of Months 0.142090E+10 0.598554E+09 0.718107E+09 0.439678E+09 0.295005E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.173934E+09 0.724666E+09 0.187826E+09 0.00 0.187826E+09 0.00 0.00
February 0.114339E+09 0.623069E+09 0.190010E+09 0.00 0.190010E+09 0.00 0.00
March 0.302263E+09 0.609355E+09 0.279952E+09 0.00 0.279952E+09 0.00 0.00
April 0.573728E+09 0.348873E+09 0.335023E+09 3179208.43 0.331844E+09 0.00 0.00
May 0.773828E+09 0.250313E+09 0.397649E+09 27758937.51 0.369890E+09 0.00 0.00
June 0.110215E+10 0.121273E+09 0.441471E+09 72795235.74 0.368676E+09 0.00 0.00
July 0.948418E+09 0.114927E+09 0.390858E+09 36860878.18 0.353997E+09 0.00 0.00
August 0.805590E+09 0.140248E+09 0.320813E+09 7016509.23 0.313796E+09 0.00 0.00
September 0.639978E+09 0.201745E+09 0.291886E+09 76092.80 0.291810E+09 0.00 0.00
October 0.333327E+09 0.539483E+09 0.236336E+09 0.00 0.236336E+09 0.00 0.00
November 0.145811E+09 0.717205E+09 0.189490E+09 0.00 0.189490E+09 0.00 0.00
December 94193170.17 0.941143E+09 0.174540E+09 0.00 0.174540E+09 0.00 0.00
               
Annual Sum or Average 0.600756E+10 0.533230E+10 0.343585E+10 0.147687E+09 0.328817E+10 0.00 0.00
Minimum of Months 94193170.17 0.114927E+09 0.174540E+09 0.00 0.174540E+09 0.00 0.00
Maximum of Months 0.110215E+10 0.941143E+09 0.441471E+09 72795235.74 0.369890E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.622244E+09 0.517789E+09 0.421516E+09 0.262627E+09 0.158889E+09 0.00 0.00
February 0.366445E+09 0.424673E+09 0.302743E+09 0.146974E+09 0.155769E+09 0.00 0.00
March 0.617401E+09 0.418028E+09 0.440825E+09 0.210584E+09 0.230241E+09 0.00 0.00
April 0.110977E+10 0.265388E+09 0.654191E+09 0.369441E+09 0.284750E+09 0.00 0.00
May 0.121140E+10 0.204767E+09 0.673046E+09 0.371072E+09 0.301973E+09 0.00 0.00
June 0.139348E+10 0.101735E+09 0.694064E+09 0.401436E+09 0.292628E+09 0.00 0.00
July 0.105274E+10 90467073.55 0.515671E+09 0.235926E+09 0.279745E+09 0.00 0.00
August 0.101386E+10 0.107623E+09 0.495059E+09 0.244608E+09 0.250451E+09 0.00 0.00
September 0.806997E+09 0.148904E+09 0.418192E+09 0.173968E+09 0.244224E+09 0.00 0.00
October 0.716966E+09 0.380245E+09 0.450890E+09 0.257400E+09 0.193490E+09 0.00 0.00
November 0.571049E+09 0.501305E+09 0.406730E+09 0.246543E+09 0.160187E+09 0.00 0.00
December 0.437988E+09 0.648086E+09 0.338439E+09 0.193228E+09 0.145211E+09 0.00 0.00
               
Annual Sum or Average 0.992034E+10 0.380901E+10 0.581137E+10 0.311381E+10 0.269756E+10 0.00 0.00
Minimum of Months 0.366445E+09 90467073.55 0.302743E+09 0.146974E+09 0.145211E+09 0.00 0.00
Maximum of Months 0.139348E+10 0.648086E+09 0.694064E+09 0.401436E+09 0.301973E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.523510E+09 -410124354.4 0.00 0.00 744.00 0.00 -113385787.0 58.99 0.00 0.00
February 0.470987E+09 -367452596.0 0.00 0.00 672.00 0.00 -103534611.5 58.99 0.00 0.00
March 0.535677E+09 -422737846.6 0.00 0.00 744.00 0.00 -112938679.3 58.99 0.00 0.00
April 0.444029E+09 -338538028.5 0.00 0.00 720.00 0.00 -105491186.4 58.99 0.00 0.00
May 0.446172E+09 -338334055.1 0.00 0.00 744.00 0.00 -107838186.4 58.99 0.00 0.00
June 0.410975E+09 -308482416.5 0.00 0.00 720.00 0.00 -102492777.7 58.99 0.00 0.00
July 0.372674E+09 -267751647.0 0.00 0.00 744.00 0.00 -104922104.2 58.99 0.00 0.00
August 0.418867E+09 -312734071.2 0.00 0.00 744.00 0.00 -106132744.1 58.99 0.00 0.00
September 0.394238E+09 -291927569.2 0.00 0.00 720.00 0.00 -102310356.0 58.99 0.00 0.00
October 0.445381E+09 -337231671.0 0.00 0.00 744.00 0.00 -108149602.1 58.99 0.00 0.00
November 0.477698E+09 -370164980.9 0.00 0.00 720.00 0.00 -107533412.3 59.00 0.00 0.00
December 0.491038E+09 -377836800.0 0.00 0.00 744.00 0.00 -113200957.5 58.99 0.00 0.00
                     
Annual Sum or Average 0.543125E+10 -0.414332E+10 0.00 0.00 8760.00 0.00 -0.128793E+10 58.99 0.00 0.00
Minimum of Months 0.372674E+09 -422737846.6 0.00 0.00 672.00 0.00 -113385787.0 58.99 0.00 0.00
Maximum of Months 0.535677E+09 -267751647.0 0.00 0.00 744.00 0.00 -102310356.0 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.75 0.73 01-JAN-08:30 2453.94 28.91 180.00 280.17 584.21 21.13 157.83 239.17
February 241.00 0.76 0.73 01-FEB-08:00 2854.48 28.94 148.50 205.50 481.15 21.20 126.00 156.00
March 344.33 0.78 0.73 02-MAR-08:50 442.95 16.93 2.33 233.00 342.11 21.04 197.67 170.00
April 380.33 0.79 0.73 01-APR-11:00 328.13 16.31 0.00 154.83 247.84 20.50 152.00 51.17
May 403.17 0.82 0.73 03-MAY-11:20 255.56 15.73 0.00 36.00 193.09 20.01 59.83 0.00
June 418.17 0.85 0.73 04-JUN-12:30 214.60 14.79 0.00 6.17 165.56 19.12 14.33 0.00
July 399.50 0.83 0.73 01-JUL-12:20 245.73 15.33 0.00 49.83 184.70 19.60 82.83 0.00
August 361.83 0.81 0.73 01-AUG-09:50 278.00 15.86 0.00 74.83 208.62 20.12 86.67 15.83
September 350.17 0.78 0.73 01-SEP-08:39 406.64 16.78 0.00 222.33 305.88 20.97 209.50 142.83
October 348.00 0.76 0.73 01-OCT-08:09 787.82 17.66 22.67 268.33 425.61 20.96 159.33 214.00
November 288.50 0.75 0.73 01-NOV-08:30 2246.79 27.49 157.17 249.67 594.57 23.81 169.67 221.67
December 290.67 0.74 0.73 01-DEC-07:40 2008.49 28.30 161.67 263.33 686.63 24.64 185.83 242.67
                         
Annual Sum or Average 4135.50 0.79     910.56 19.47 672.33 2044.00 346.20 20.93 1601.50 1453.33
Minimum of Months 241.00 0.74 0.73   214.60 14.79 0.00 6.17 165.56 19.12 14.33 0.00
Maximum of Months 418.17 0.85 0.73   2854.48 28.94 180.00 280.17 686.63 24.64 209.50 242.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.83 0.73 01-JAN-08:09 1005.15 17.60 56.17 96.83 749.83 23.82 99.67 86.83
February 241.00 0.82 0.73 01-FEB-08:09 1114.95 17.74 42.17 88.83 944.46 24.63 96.00 74.83
March 344.33 0.82 0.73 01-MAR-07:49 332.07 14.35 0.33 123.50 279.87 19.37 98.33 94.17
April 380.33 0.82 0.73 01-APR-07:10 335.33 14.13 0.00 123.67 302.15 19.52 77.67 112.50
May 403.17 0.82 0.73 01-MAY-06:30 336.13 14.19 0.00 137.50 309.58 19.77 75.33 127.33
June 418.17 0.83 0.73 01-JUN-06:10 310.00 13.54 0.00 131.33 289.51 19.16 43.17 124.50
July 399.50 0.82 0.73 01-JUL-06:10 316.83 14.11 0.00 131.00 285.45 19.45 70.50 120.17
August 361.83 0.82 0.73 01-AUG-06:49 323.15 14.17 0.00 124.17 289.40 19.60 74.33 111.17
September 350.17 0.82 0.73 01-SEP-06:00 328.27 14.59 0.00 117.83 273.63 19.45 102.83 93.50
October 348.00 0.83 0.73 01-OCT-07:40 396.31 14.06 7.33 117.33 304.42 18.94 78.33 96.17
November 288.50 0.84 0.73 01-NOV-08:09 941.93 18.14 54.00 84.50 535.30 22.60 83.50 75.33
December 290.67 0.83 0.73 01-DEC-07:00 1414.89 20.59 85.33 95.33 769.81 24.19 92.00 75.00
                         
Annual Sum or Average 4135.50 0.82     548.07 15.33 245.33 1371.83 414.90 20.60 991.67 1191.50
Minimum of Months 241.00 0.82 0.73   310.00 13.54 0.00 84.50 273.63 18.94 43.17 74.83
Maximum of Months 418.17 0.84 0.73   1414.89 20.59 85.33 137.50 944.46 24.63 102.83 127.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.92 0.85 23-JAN-14:30 112.39 11.52 0.00 0.00 90.07 15.97 0.00 0.00
February 241.00 0.90 0.82 14-FEB-14:30 140.85 12.61 0.00 0.00 105.22 16.66 0.00 0.00
March 344.33 0.89 0.74 14-MAR-14:30 164.28 13.81 0.00 0.00 118.40 17.69 0.00 0.00
April 380.33 0.86 0.74 25-APR-09:30 200.38 15.02 0.00 0.00 144.74 18.87 0.00 0.00
May 403.17 0.83 0.73 31-MAY-18:10 233.38 15.88 0.00 4.33 166.66 19.77 6.83 1.67
June 418.17 0.83 0.73 01-JUN-18:10 238.21 15.76 0.00 32.33 238.21 22.98 94.67 50.17
July 399.50 0.83 0.74 14-JUL-16:30 238.09 15.82 0.00 15.33 165.61 19.56 18.50 0.00
August 361.83 0.86 0.74 08-AUG-15:30 201.68 15.14 0.00 0.17 143.14 18.96 0.17 0.00
September 350.17 0.87 0.74 17-SEP-15:30 188.52 14.52 0.00 1.67 133.89 18.32 1.33 0.00
October 348.00 0.91 0.74 07-OCT-09:30 131.84 12.35 0.00 0.00 100.32 16.47 0.00 0.00
November 288.50 0.91 0.82 03-NOV-14:30 122.70 12.17 0.00 0.00 95.03 16.56 0.00 0.00
December 290.67 0.92 0.85 31-DEC-12:30 113.38 11.70 0.00 0.00 89.62 16.18 0.00 0.00
                         
Annual Sum or Average 4135.50 0.87     179.81 14.07 0.00 53.83 137.61 18.40 121.50 51.83
Minimum of Months 241.00 0.83 0.73   112.39 11.52 0.00 0.00 89.62 15.97 0.00 0.00
Maximum of Months 418.17 0.92 0.85   238.21 15.88 0.00 32.33 238.21 22.98 94.67 50.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.84 0.73 01-JAN-14:20 1481.47 19.73 85.00 106.00 828.43 23.25 104.67 89.33
February 241.00 0.83 0.73 01-FEB-14:20 925.25 17.22 40.67 83.33 426.45 21.47 87.00 66.50
March 344.33 0.83 0.73 02-MAR-13:39 315.63 14.43 0.00 123.67 257.38 19.19 98.83 84.33
April 380.33 0.82 0.73 01-APR-14:09 348.04 14.33 0.00 137.00 312.92 19.62 118.17 119.17
May 403.17 0.82 0.73 01-MAY-13:50 331.38 14.33 0.00 128.83 303.71 19.61 97.17 117.50
June 418.17 0.83 0.73 01-JUN-14:09 316.33 13.84 0.00 133.00 296.47 19.26 90.33 123.50
July 399.50 0.83 0.73 01-JUL-14:09 292.25 14.28 0.00 112.00 257.98 19.38 99.33 90.33
August 361.83 0.83 0.73 01-AUG-13:20 292.59 14.07 0.00 99.50 257.14 19.18 73.67 85.00
September 350.17 0.82 0.73 01-SEP-13:30 314.88 14.78 0.00 115.33 285.90 19.69 109.00 84.83
October 348.00 0.84 0.73 01-OCT-13:20 395.97 14.20 7.33 110.17 664.25 21.66 100.00 90.33
November 288.50 0.83 0.73 01-NOV-13:09 985.65 17.99 52.83 100.67 675.98 23.16 95.00 86.33
December 290.67 0.84 0.73 01-DEC-13:30 898.31 18.41 60.67 95.33 527.39 22.33 92.83 72.33
                         
Annual Sum or Average 4135.50 0.83     533.21 15.40 246.50 1344.83 408.46 20.48 1166.00 1109.50
Minimum of Months 241.00 0.82 0.73   292.25 13.84 0.00 83.33 257.14 19.18 73.67 66.50
Maximum of Months 418.17 0.84 0.73   1481.47 19.73 85.00 137.00 828.43 23.25 118.17 123.50



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 18732484.72 5593.71 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 18732484.72     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 18732484.72 5593.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 40224242.85 6340.52 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.105034E+09 7128.30 13-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.130711E+09 5964.58 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 172725.35 145.85 25-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 1679761.66 1660.37 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 80480651.07 3274.51 06-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.358303E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130711E+09 7128.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 23128207.03 4818.16 03-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 19727661.13 4768.83 13-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 21737676.49 3990.31 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 15121179.24 3658.51 18-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 79714723.90     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 23128207.03 4818.16   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 77368323.56 7130.50 03-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 65361114.85 7277.63 06-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 65496823.28 6167.36 28-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1544345.79 483.62 24-NOV-06:10 0.00 0.00 0.00 0.00 0.00
December 57289567.43 6174.22 18-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.267060E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 77368323.56 7277.63   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 22953711.17 5661.82 03-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 22093619.97 5603.86 13-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 18135113.74 4689.01 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 15742421.42 4065.18 18-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 78924866.31     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 22953711.17 5661.82   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 342124.51 2804.01 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 342124.51     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 342124.51 2804.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 191375.15 3189.59 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 294948.99 3441.07 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 486324.14     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 294948.99 3441.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 378542.15 2103.01 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 180258.17 2103.01 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 558800.32     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 378542.15 2103.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 858617.92 3376.87 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 733196.71 3376.87 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 714194.25 3307.27 18-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2306008.89     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 858617.92 3376.87   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 287206.97 2096.54 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 179703.76 2096.54 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 466910.73     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 287206.97 2096.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.121898E+10 0.119033E+10 4282.07 27-JAN-06:03 4282.07 0.00
February 0.00 0.00 0.727038E+09 0.639422E+09 3317.79 01-FEB-06:03 3317.79 0.00
March 0.00 0.00 0.134770E+10 0.127579E+10 6252.66 17-MAR-05:03 5632.32 0.00
April 0.00 0.00 0.271151E+10 0.270717E+10 6291.46 26-APR-05:01 6291.46 0.00
May 0.00 0.00 0.364473E+10 0.364473E+10 6268.76 11-MAY-05:01 6268.76 0.00
June 0.00 0.00 0.468574E+10 0.466880E+10 6419.62 20-JUN-05:01 6419.62 0.00
July 0.00 0.00 0.488425E+10 0.436027E+10 6927.93 14-JUL-05:01 4550.25 0.00
August 0.00 0.00 0.536791E+10 0.475065E+10 6818.04 10-AUG-05:01 4869.78 0.00
September 0.00 0.00 0.446806E+10 0.396220E+10 6919.03 05-SEP-05:01 5169.21 0.00
October 0.00 0.00 0.310603E+10 0.296045E+10 6736.22 03-OCT-05:01 5361.12 0.00
November 0.00 0.00 0.198493E+10 0.182650E+10 6712.17 14-NOV-06:03 4151.90 0.00
December 0.00 0.00 0.920242E+09 0.911548E+09 3891.17 27-DEC-06:03 3749.07 0.00
                 
Annual Sum or Average 0.00 0.00 0.350671E+11 0.328979E+11       0.00
Minimum of Months 0.00 0.00 0.727038E+09 0.639422E+09 3317.79   3317.79 0.00
Maximum of Months 0.00 0.00 0.536791E+10 0.475065E+10 6927.93   6419.62 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.200693E+10 0.200159E+10 5272.88 30-JAN-14:40 5272.88 0.00
February 0.00 0.00 0.671141E+09 0.653687E+09 3208.98 01-FEB-15:30 3208.98 0.00
March 0.00 0.00 0.981046E+09 0.977092E+09 3500.48 16-MAR-15:20 3500.48 0.00
April 0.00 0.00 0.229137E+10 0.229137E+10 6965.32 26-APR-05:01 6965.32 0.00
May 0.00 0.00 0.297241E+10 0.297241E+10 6967.89 11-MAY-05:01 6967.89 0.00
June 0.00 0.00 0.441786E+10 0.441107E+10 7158.69 19-JUN-05:01 7158.69 0.00
July 0.00 0.00 0.482926E+10 0.440691E+10 7963.92 14-JUL-05:01 4775.94 0.00
August 0.00 0.00 0.547354E+10 0.500290E+10 7796.57 10-AUG-05:01 5273.47 0.00
September 0.00 0.00 0.491176E+10 0.449960E+10 7804.29 05-SEP-05:01 6244.21 0.00
October 0.00 0.00 0.372470E+10 0.363893E+10 7652.36 03-OCT-05:01 6302.71 0.00
November 0.00 0.00 0.264976E+10 0.256391E+10 7629.94 13-NOV-06:02 4888.40 0.00
December 0.00 0.00 0.148056E+10 0.147919E+10 5438.27 26-DEC-13:55 5438.27 0.00
                 
Annual Sum or Average 0.00 0.00 0.364103E+11 0.348987E+11       0.00
Minimum of Months 0.00 0.00 0.671141E+09 0.653687E+09 3208.98   3208.98 0.00
Maximum of Months 0.00 0.00 0.547354E+10 0.500290E+10 7963.92   7158.69 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.482011E+09 0.479576E+09 3338.75 31-JAN-11:02 3338.75 0.00
February 0.00 0.00 0.181733E+09 0.172666E+09 3453.50 23-FEB-15:01 3392.28 0.00
March 0.00 0.00 0.451443E+09 0.449014E+09 3902.83 17-MAR-12:01 3887.85 0.00
April 0.00 0.00 0.155563E+10 0.155563E+10 4677.96 17-APR-05:01 4677.96 0.00
May 0.00 0.00 0.212886E+10 0.212886E+10 4684.92 11-MAY-05:01 4684.92 0.00
June 0.00 0.00 0.306560E+10 0.306311E+10 4807.06 19-JUN-05:01 4807.06 0.00
July 0.00 0.00 0.319063E+10 0.299306E+10 5322.29 14-JUL-05:01 3288.73 0.00
August 0.00 0.00 0.349650E+10 0.327909E+10 5206.90 10-AUG-05:01 3621.55 0.00
September 0.00 0.00 0.280561E+10 0.261754E+10 5227.44 05-SEP-05:01 4178.37 0.00
October 0.00 0.00 0.182580E+10 0.178671E+10 5099.84 03-OCT-05:01 4215.63 0.00
November 0.00 0.00 0.949437E+09 0.912915E+09 4861.56 03-NOV-05:02 4233.97 0.00
December 0.00 0.00 0.339829E+09 0.339068E+09 3377.50 22-DEC-11:02 3377.50 0.00
                 
Annual Sum or Average 0.00 0.00 0.204731E+11 0.197772E+11       0.00
Minimum of Months 0.00 0.00 0.181733E+09 0.172666E+09 3338.75   3288.73 0.00
Maximum of Months 0.00 0.00 0.349650E+10 0.327909E+10 5322.29   4807.06 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.491916E+09 0.489707E+09 2072.83 31-JAN-16:42 2072.83 0.00
February 0.00 0.00 0.115818E+09 0.106891E+09 1065.42 16-FEB-15:55 960.46 0.00
March 0.00 0.00 0.509276E+09 0.505435E+09 2234.79 16-MAR-15:57 2234.79 0.00
April 0.00 0.00 0.188059E+10 0.188059E+10 6904.80 26-APR-05:01 6904.80 0.00
May 0.00 0.00 0.278987E+10 0.278987E+10 6916.32 11-MAY-05:01 6916.32 0.00
June 0.00 0.00 0.417865E+10 0.417353E+10 7091.57 19-JUN-05:01 7091.57 0.00
July 0.00 0.00 0.450496E+10 0.415451E+10 7857.95 14-JUL-05:01 4827.97 0.00
August 0.00 0.00 0.488881E+10 0.449965E+10 7688.26 10-AUG-05:01 5302.56 0.00
September 0.00 0.00 0.403228E+10 0.370069E+10 7799.67 05-SEP-05:01 5770.03 0.00
October 0.00 0.00 0.231533E+10 0.224388E+10 7529.57 03-OCT-05:01 6148.52 0.00
November 0.00 0.00 0.116979E+10 0.109970E+10 7173.60 03-NOV-05:02 6175.88 0.00
December 0.00 0.00 0.314988E+09 0.314148E+09 1796.98 22-DEC-15:35 1796.98 0.00
                 
Annual Sum or Average 0.00 0.00 0.271923E+11 0.259586E+11       0.00
Minimum of Months 0.00 0.00 0.115818E+09 0.106891E+09 1065.42   960.46 0.00
Maximum of Months 0.00 0.00 0.488881E+10 0.449965E+10 7857.95   7091.57 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.621054E+09 0.618184E+09 2453.74 31-JAN-16:55 2453.74 0.00
February 0.00 0.00 0.232005E+09 0.220816E+09 1634.00 22-FEB-16:23 1574.76 0.00
March 0.00 0.00 0.510326E+09 0.506227E+09 2151.54 16-MAR-15:57 2151.54 0.00
April 0.00 0.00 0.154530E+10 0.154530E+10 5526.57 26-APR-05:01 5526.57 0.00
May 0.00 0.00 0.210755E+10 0.210755E+10 5525.98 11-MAY-05:01 5525.98 0.00
June 0.00 0.00 0.305244E+10 0.304895E+10 5641.31 19-JUN-05:01 5641.31 0.00
July 0.00 0.00 0.313005E+10 0.290474E+10 6248.30 14-JUL-05:01 3849.09 0.00
August 0.00 0.00 0.345936E+10 0.320819E+10 6114.87 10-AUG-05:01 4234.23 0.00
September 0.00 0.00 0.285503E+10 0.264025E+10 6139.87 11-SEP-05:01 4897.23 0.00
October 0.00 0.00 0.182891E+10 0.178216E+10 5989.97 03-OCT-05:01 4972.44 0.00
November 0.00 0.00 0.112346E+10 0.107222E+10 5721.54 03-NOV-05:02 5024.60 0.00
December 0.00 0.00 0.444613E+09 0.443760E+09 2452.46 22-DEC-16:27 2452.46 0.00
                 
Annual Sum or Average 0.00 0.00 0.209101E+11 0.200983E+11       0.00
Minimum of Months 0.00 0.00 0.232005E+09 0.220816E+09 1634.00   1574.76 0.00
Maximum of Months 0.00 0.00 0.345936E+10 0.320819E+10 6248.30   5641.31 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 164.82 513.97 23-JAN-12:13
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     14.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   164.82 513.97  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.376602E+09 0.37 383.19 02-JAN-06:01 1.01
February 0.340735E+09 0.37 383.19 01-FEB-06:03 1.01
March 0.412469E+09 0.40 383.19 01-MAR-06:10 1.01
April 0.358669E+09 0.36 383.19 03-APR-05:03 1.01
May 0.394536E+09 0.39 383.19 01-MAY-05:01 1.01
June 0.394536E+09 0.40 383.19 01-JUN-05:01 1.01
July 0.358669E+09 0.35 383.19 03-JUL-05:01 1.00
August 0.412469E+09 0.40 383.19 01-AUG-05:01 1.00
September 0.358669E+09 0.36 383.19 01-SEP-05:01 1.00
October 0.376602E+09 0.37 383.19 02-OCT-05:01 1.00
November 0.376602E+09 0.38 383.19 01-NOV-05:02 1.01
December 0.358669E+09 0.35 383.19 01-DEC-06:05 1.01
           
Annual Sum or Average 0.451923E+10 0.38      
Minimum of Months 0.340735E+09 0.35 383.19   1.00
Maximum of Months 0.412469E+09 0.40 383.19   1.01



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.448234E+09 0.37 456.08 02-JAN-06:01 1.01
February 0.405545E+09 0.37 456.08 01-FEB-06:03 1.01
March 0.490923E+09 0.41 456.08 01-MAR-06:10 1.01
April 0.426889E+09 0.37 456.08 03-APR-05:03 1.02
May 0.469578E+09 0.39 456.08 01-MAY-05:01 1.02
June 0.469939E+09 0.40 456.08 01-JUN-05:01 1.01
July 0.428783E+09 0.36 456.08 03-JUL-05:01 1.02
August 0.495022E+09 0.42 456.08 01-AUG-05:01 1.00
September 0.433124E+09 0.40 456.08 01-SEP-05:01 1.00
October 0.452378E+09 0.39 456.08 02-OCT-05:01 1.00
November 0.448234E+09 0.38 456.08 01-NOV-05:02 1.01
December 0.426889E+09 0.35 456.08 01-DEC-06:05 1.01
           
Annual Sum or Average 0.539554E+10 0.38      
Minimum of Months 0.405545E+09 0.35 456.08   1.00
Maximum of Months 0.495022E+09 0.42 456.08   1.02



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.251830E+09 0.36 324.66 02-JAN-06:01 1.01
February 0.223183E+09 0.32 324.66 01-FEB-06:03 1.01
March 0.273497E+09 0.38 324.66 01-MAR-06:10 1.01
April 0.261119E+09 0.37 324.66 03-APR-05:03 1.02
May 0.294147E+09 0.40 324.66 01-MAY-05:01 1.02
June 0.316281E+09 0.45 324.66 01-JUN-05:01 1.01
July 0.293016E+09 0.43 324.66 03-JUL-05:01 1.02
August 0.333726E+09 0.47 324.66 01-AUG-05:01 1.00
September 0.282251E+09 0.40 324.66 01-SEP-05:01 1.00
October 0.277059E+09 0.38 324.66 02-OCT-05:01 1.00
November 0.260405E+09 0.39 324.66 01-NOV-05:02 1.01
December 0.237944E+09 0.33 324.66 01-DEC-06:05 1.01
           
Annual Sum or Average 0.330446E+10 0.39      
Minimum of Months 0.223183E+09 0.32 324.66   1.00
Maximum of Months 0.333726E+09 0.47 324.66   1.02



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.443194E+09 0.37 450.95 02-JAN-06:01 1.01
February 0.400985E+09 0.37 450.95 01-FEB-06:03 1.01
March 0.485403E+09 0.41 450.95 01-MAR-06:10 1.01
April 0.422090E+09 0.37 450.95 03-APR-05:03 1.02
May 0.464299E+09 0.39 450.95 01-MAY-05:01 1.02
June 0.465326E+09 0.41 450.95 01-JUN-05:01 1.01
July 0.424578E+09 0.37 450.95 03-JUL-05:01 1.02
August 0.488237E+09 0.42 450.95 01-AUG-05:01 1.00
September 0.422687E+09 0.37 450.95 01-SEP-05:01 1.00
October 0.443194E+09 0.37 450.95 02-OCT-05:01 1.00
November 0.443194E+09 0.38 450.95 01-NOV-05:02 1.01
December 0.422090E+09 0.35 450.95 01-DEC-06:05 1.01
           
Annual Sum or Average 0.532528E+10 0.38      
Minimum of Months 0.400985E+09 0.35 450.95   1.00
Maximum of Months 0.488237E+09 0.42 450.95   1.02



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.374948E+09 0.37 381.51 02-JAN-06:01 1.01
February 0.339239E+09 0.37 381.51 01-FEB-06:03 1.01
March 0.410658E+09 0.41 381.51 01-MAR-06:10 1.01
April 0.357133E+09 0.37 381.51 03-APR-05:03 1.02
May 0.393916E+09 0.40 381.51 01-MAY-05:01 1.02
June 0.402528E+09 0.46 381.51 01-JUN-05:01 1.01
July 0.369450E+09 0.42 381.51 01-JUL-17:52 1.01
August 0.420646E+09 0.46 381.51 01-AUG-05:01 1.00
September 0.361752E+09 0.40 381.51 01-SEP-05:01 1.00
October 0.375818E+09 0.38 381.51 02-OCT-05:01 1.00
November 0.374948E+09 0.38 381.51 01-NOV-05:02 1.01
December 0.357094E+09 0.35 381.51 01-DEC-06:05 1.01
           
Annual Sum or Average 0.453813E+10 0.40      
Minimum of Months 0.339239E+09 0.35 381.51   1.00
Maximum of Months 0.420646E+09 0.46 381.51   1.02



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.01 0.00 0.00 02-JAN-07:10 0.00 0.00 34.77 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 18.53 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 18.53 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 18.53 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 18.53 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 18.53 0.00
July 0.00 0.00 0.00 01-JUL-00:05 0.00 0.00 18.53 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 18.53 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 18.53 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 18.53 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 18.53 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 18.53 0.00
                 
Annual Sum or Average 0.01 0.00            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 18.53 0.00
Maximum of Months 0.01 0.00 0.00   0.00 0.00 34.77 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.89 48.89 164.82 513.97 23-JAN-12:13
February 0.00 0.00 01-FEB-00:10 18.53 18.53 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 18.53 18.53 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 18.53 18.53 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 18.53 18.53 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 18.53 18.53 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 18.53 18.53 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:10 18.53 18.53 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 18.53 18.53 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 18.53 18.53 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 18.53 18.53 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 18.53 18.53 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         14.00    
Minimum of Months 0.00 0.00   18.53 18.53 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 164.82 513.97  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.656752E+09 0.00 0.00
February 0.00 0.00 0.00 0.502226E+09 0.00 0.00
March 0.00 0.00 0.00 0.717494E+09 0.00 0.00
April 0.00 0.00 0.00 0.996766E+09 0.00 0.00
May 0.00 0.00 0.00 0.127868E+10 0.00 0.00
June 0.00 0.00 0.00 0.158978E+10 0.00 0.00
July 0.00 0.00 0.00 0.153295E+10 0.00 0.00
August 0.00 0.00 0.00 0.170447E+10 0.00 0.00
September 0.00 0.00 0.00 0.140015E+10 0.00 0.00
October 0.00 0.00 0.00 0.108370E+10 0.00 0.00
November 0.00 0.00 0.00 0.814497E+09 0.00 0.00
December 0.00 0.00 0.00 0.566237E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.128437E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.502226E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.170447E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.900008E+09 0.00 0.00
February 0.00 0.00 0.00 0.588821E+09 0.00 0.00
March 0.00 0.00 0.00 0.762194E+09 0.00 0.00
April 0.00 0.00 0.00 0.986939E+09 0.00 0.00
May 0.00 0.00 0.00 0.122625E+10 0.00 0.00
June 0.00 0.00 0.00 0.164547E+10 0.00 0.00
July 0.00 0.00 0.00 0.162939E+10 0.00 0.00
August 0.00 0.00 0.00 0.185501E+10 0.00 0.00
September 0.00 0.00 0.00 0.160237E+10 0.00 0.00
October 0.00 0.00 0.00 0.130186E+10 0.00 0.00
November 0.00 0.00 0.00 0.102216E+10 0.00 0.00
December 0.00 0.00 0.00 0.778579E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.142990E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.588821E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.185501E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.370167E+09 0.00 0.00
February 0.00 0.00 0.00 0.270936E+09 0.00 0.00
March 0.00 0.00 0.00 0.386979E+09 0.00 0.00
April 0.00 0.00 0.00 0.636294E+09 0.00 0.00
May 0.00 0.00 0.00 0.825103E+09 0.00 0.00
June 0.00 0.00 0.00 0.112393E+10 0.00 0.00
July 0.00 0.00 0.00 0.109099E+10 0.00 0.00
August 0.00 0.00 0.00 0.120848E+10 0.00 0.00
September 0.00 0.00 0.00 0.959279E+09 0.00 0.00
October 0.00 0.00 0.00 0.704099E+09 0.00 0.00
November 0.00 0.00 0.00 0.474767E+09 0.00 0.00
December 0.00 0.00 0.00 0.323636E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.837467E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.270936E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.120848E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.583025E+09 0.00 0.00
February 0.00 0.00 0.00 0.449767E+09 0.00 0.00
March 0.00 0.00 0.00 0.629807E+09 0.00 0.00
April 0.00 0.00 0.00 0.886565E+09 0.00 0.00
May 0.00 0.00 0.00 0.117425E+10 0.00 0.00
June 0.00 0.00 0.00 0.157796E+10 0.00 0.00
July 0.00 0.00 0.00 0.155205E+10 0.00 0.00
August 0.00 0.00 0.00 0.171536E+10 0.00 0.00
September 0.00 0.00 0.00 0.139859E+10 0.00 0.00
October 0.00 0.00 0.00 0.993953E+09 0.00 0.00
November 0.00 0.00 0.00 0.710523E+09 0.00 0.00
December 0.00 0.00 0.00 0.519260E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.121911E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.449767E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.171536E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.525198E+09 0.00 0.00
February 0.00 0.00 0.00 0.399089E+09 0.00 0.00
March 0.00 0.00 0.00 0.537369E+09 0.00 0.00
April 0.00 0.00 0.00 0.737783E+09 0.00 0.00
May 0.00 0.00 0.00 0.933274E+09 0.00 0.00
June 0.00 0.00 0.00 0.123262E+10 0.00 0.00
July 0.00 0.00 0.00 0.117478E+10 0.00 0.00
August 0.00 0.00 0.00 0.130984E+10 0.00 0.00
September 0.00 0.00 0.00 0.106600E+10 0.00 0.00
October 0.00 0.00 0.00 0.812145E+09 0.00 0.00
November 0.00 0.00 0.00 0.628980E+09 0.00 0.00
December 0.00 0.00 0.00 0.466493E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.982356E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.399089E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.130984E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.376602E+09 0.121898E+10 19074609.23 0.00 0.00 0.00 0.00 0.00
February 0.340735E+09 0.727038E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.412469E+09 0.134770E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.358669E+09 0.271151E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.394536E+09 0.364473E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.394536E+09 0.468574E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.358669E+09 0.488425E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.412469E+09 0.536791E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.358669E+09 0.446806E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.376602E+09 0.310603E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.376602E+09 0.198493E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.358669E+09 0.920242E+09 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.451923E+10 0.350671E+11 19074609.23 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.340735E+09 0.727038E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.412469E+09 0.536791E+10 19074609.23 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.448234E+09 0.200693E+10 40415618.00 0.00 0.00 0.00 0.00 0.00
February 0.405545E+09 0.671141E+09 0.105034E+09 0.00 0.00 0.00 0.00 0.00
March 0.490923E+09 0.981046E+09 0.131006E+09 0.00 0.00 0.00 0.00 0.00
April 0.426889E+09 0.229137E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.469578E+09 0.297241E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.469939E+09 0.441786E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.428783E+09 0.482926E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.495022E+09 0.547354E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.433124E+09 0.491176E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.452378E+09 0.372470E+10 172725.35 0.00 0.00 0.00 0.00 0.00
November 0.448234E+09 0.264976E+10 1679761.66 0.00 0.00 0.00 0.00 0.00
December 0.426889E+09 0.148056E+10 80480651.07 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.539554E+10 0.364103E+11 0.358789E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.405545E+09 0.671141E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.495022E+09 0.547354E+10 0.131006E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.251830E+09 0.482011E+09 23506749.18 0.00 0.00 0.00 0.00 0.00
February 0.223183E+09 0.181733E+09 19727661.13 0.00 0.00 0.00 0.00 0.00
March 0.273497E+09 0.451443E+09 21917934.66 0.00 0.00 0.00 0.00 0.00
April 0.261119E+09 0.155563E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.294147E+09 0.212886E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.316281E+09 0.306560E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.293016E+09 0.319063E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.333726E+09 0.349650E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.282251E+09 0.280561E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.277059E+09 0.182580E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.260405E+09 0.949437E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.237944E+09 0.339829E+09 15121179.24 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.330446E+10 0.204731E+11 80273524.21 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.223183E+09 0.181733E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.333726E+09 0.349650E+10 23506749.18 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.443194E+09 0.491916E+09 78226941.49 0.00 0.00 0.00 0.00 0.00
February 0.400985E+09 0.115818E+09 65361114.85 0.00 0.00 0.00 0.00 0.00
March 0.485403E+09 0.509276E+09 66230019.99 0.00 0.00 0.00 0.00 0.00
April 0.422090E+09 0.188059E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.464299E+09 0.278987E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.465326E+09 0.417865E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.424578E+09 0.450496E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.488237E+09 0.488881E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.422687E+09 0.403228E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.443194E+09 0.231533E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.443194E+09 0.116979E+10 1544345.79 0.00 0.00 0.00 0.00 0.00
December 0.422090E+09 0.314988E+09 58003761.68 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.532528E+10 0.271923E+11 0.269366E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.400985E+09 0.115818E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.488237E+09 0.488881E+10 78226941.49 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.374948E+09 0.621054E+09 23240918.15 0.00 0.00 0.00 0.00 0.00
February 0.339239E+09 0.232005E+09 22093619.97 0.00 0.00 0.00 0.00 0.00
March 0.410658E+09 0.510326E+09 18314817.50 0.00 0.00 0.00 0.00 0.00
April 0.357133E+09 0.154530E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393916E+09 0.210755E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.402528E+09 0.305244E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.369450E+09 0.313005E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.420646E+09 0.345936E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.361752E+09 0.285503E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.375818E+09 0.182891E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.374948E+09 0.112346E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.357094E+09 0.444613E+09 15742421.42 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.453813E+10 0.209101E+11 79391777.04 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339239E+09 0.232005E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.420646E+09 0.345936E+10 23240918.15 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.376602E+09 0.00 0.00 6437254.08 0.273713E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.340735E+09 0.00 0.00 0.00 0.161490E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.412469E+09 0.00 0.00 990000.00 0.304035E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.358669E+09 0.00 0.00 0.00 0.638097E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.394536E+09 0.00 0.00 0.00 0.884143E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.394536E+09 0.00 0.00 0.00 0.119525E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.358669E+09 0.00 0.00 0.00 0.117428E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.412469E+09 0.00 0.00 0.00 0.129200E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.358669E+09 0.00 0.00 0.00 0.104148E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.376602E+09 0.00 0.00 0.00 0.707098E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.376602E+09 0.00 0.00 179721.28 0.437716E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.358669E+09 0.00 0.00 3179337.50 0.204389E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.451923E+10 0.00 0.00 10786312.86 0.831369E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.340735E+09 0.00 0.00 0.00 0.161490E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.412469E+09 0.00 0.00 6437254.08 0.129200E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.448234E+09 0.00 0.00 13800975.32 0.437973E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.405545E+09 0.00 0.00 35641368.88 0.147634E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.490923E+09 0.00 0.00 46121692.65 0.225150E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.426889E+09 0.00 0.00 0.00 0.560050E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.469578E+09 0.00 0.00 0.00 0.756674E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.469939E+09 0.00 0.00 0.00 0.117553E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.428783E+09 0.00 0.00 0.00 0.120061E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.495022E+09 0.00 0.00 0.00 0.135999E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.433124E+09 0.00 0.00 0.00 0.116924E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.452378E+09 0.00 0.00 64250.96 0.849415E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.448234E+09 0.00 0.00 788303.26 0.573135E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.426889E+09 0.00 0.00 33287542.40 0.318403E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.539554E+10 0.00 0.00 0.129704E+09 0.877381E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.405545E+09 0.00 0.00 0.00 0.147634E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.495022E+09 0.00 0.00 46121692.65 0.135999E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.251830E+09 0.00 0.00 7819722.44 0.110518E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.223183E+09 0.00 0.00 6818725.76 40934565.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.273497E+09 0.00 0.00 8845038.09 0.104637E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.261119E+09 0.00 0.00 0.00 0.375174E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.294147E+09 0.00 0.00 0.00 0.530955E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.316281E+09 0.00 0.00 0.00 0.807653E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.293016E+09 0.00 0.00 0.00 0.797976E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.333726E+09 0.00 0.00 0.00 0.874755E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.282251E+09 0.00 0.00 0.00 0.677028E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.277059E+09 0.00 0.00 0.00 0.427040E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.260405E+09 0.00 0.00 180000.00 0.214182E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.237944E+09 0.00 0.00 9103612.66 76588651.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.330446E+10 0.00 0.00 32767098.95 0.503744E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.223183E+09 0.00 0.00 0.00 40934565.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.333726E+09 0.00 0.00 9103612.66 0.874755E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.443194E+09 0.00 0.00 25198363.51 0.114632E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.400985E+09 0.00 0.00 22481497.73 26300526.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.485403E+09 0.00 0.00 24409317.70 0.119994E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.422090E+09 0.00 0.00 0.00 0.464476E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.464299E+09 0.00 0.00 0.00 0.709954E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.465326E+09 0.00 0.00 0.00 0.111263E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.424578E+09 0.00 0.00 0.00 0.112747E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.488237E+09 0.00 0.00 0.00 0.122712E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.422687E+09 0.00 0.00 0.00 0.975903E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.443194E+09 0.00 0.00 0.00 0.550759E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.443194E+09 0.00 0.00 752508.73 0.266576E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.422090E+09 0.00 0.00 25264379.00 71906187.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.532528E+10 0.00 0.00 98106066.68 0.676772E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.400985E+09 0.00 0.00 0.00 26300526.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.488237E+09 0.00 0.00 25264379.00 0.122712E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.374948E+09 0.00 0.00 7807024.67 0.142443E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.339239E+09 0.00 0.00 7659500.54 52190327.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.410658E+09 0.00 0.00 7631382.80 0.119080E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.357133E+09 0.00 0.00 0.00 0.380650E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393916E+09 0.00 0.00 0.00 0.539359E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.402528E+09 0.00 0.00 0.00 0.830088E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.369450E+09 0.00 0.00 0.00 0.805326E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.420646E+09 0.00 0.00 0.00 0.889191E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.361752E+09 0.00 0.00 0.00 0.704246E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.375818E+09 0.00 0.00 0.00 0.436327E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.374948E+09 0.00 0.00 180000.00 0.253851E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.357094E+09 0.00 0.00 9337728.86 0.100062E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.453813E+10 0.00 0.00 32615636.87 0.525281E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339239E+09 0.00 0.00 0.00 52190327.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.420646E+09 0.00 0.00 9337728.86 0.889191E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.252615E+09 0.00 0.00 6561625.15 0.00 9283723.79 0.708411E+09 0.00 0.19
February 0.338104E+09 0.00 0.00 3965244.84 0.00 0.00 0.707932E+09 0.00 0.19
March 0.295025E+09 0.00 0.00 6465692.42 0.00 0.00 0.739250E+09 0.00 0.21
April 26326931.47 1151832.97 0.00 14008248.79 97863.18 0.00 0.447049E+09 0.00 0.19
May 10615950.56 15538667.76 0.00 16891193.80 1859533.96 0.00 0.288688E+09 0.00 0.20
June 918225.58 0.156212E+09 0.00 14036267.01 16015155.88 0.00 0.102224E+09 0.00 0.21
July 0.00 0.472762E+09 0.00 6017184.42 32228542.59 0.00 22789282.78 0.00 0.18
August 121725.01 0.535051E+09 0.00 5124325.60 27033756.38 0.00 23101767.10 0.00 0.21
September 990662.58 0.318172E+09 0.00 5867233.83 16441594.02 0.00 37655561.74 0.00 0.19
October 42909462.15 70588098.62 0.00 12335591.98 3414805.64 0.00 0.548283E+09 0.00 0.19
November 0.101029E+09 164128.05 0.00 9819491.69 8830.03 0.00 0.718204E+09 0.00 0.20
December 0.352924E+09 0.00 0.00 5857483.85 0.00 0.00 0.838603E+09 0.00 0.18
                   
Annual Sum or Average 0.142158E+10 0.156964E+10 0.00 0.106950E+09 97100081.67 9283723.79 0.518219E+10 0.00 0.19
Minimum of Months 0.00 0.00 0.00 3965244.84 0.00 0.00 22789282.78 0.00 0.18
Maximum of Months 0.352924E+09 0.535051E+09 0.00 16891193.80 32228542.59 9283723.79 0.838603E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.154003E+09 351696.21 0.00 9389714.46 0.00 24639169.27 0.233937E+09 0.00 0.19
February 0.200965E+09 0.00 0.00 3070663.74 0.00 62164289.99 0.261323E+09 0.00 0.19
March 0.192570E+09 3530189.99 0.00 3001839.57 642754.80 72058610.55 0.174995E+09 0.00 0.21
April 44838808.90 75440142.81 0.00 4230475.59 9266010.50 0.00 85054830.74 0.00 0.19
May 5667777.29 0.161972E+09 0.00 3442774.35 20762396.14 0.00 46348953.27 0.00 0.20
June 197631.11 0.370194E+09 0.00 1750936.01 36159793.78 0.00 12664681.61 0.00 0.21
July 0.00 0.481454E+09 0.00 541944.78 33335373.52 0.00 690845.11 0.00 0.18
August 139037.99 0.533379E+09 0.00 997276.11 30219620.11 0.00 4610902.93 0.00 0.21
September 133079.13 0.346064E+09 0.00 1604310.25 21239944.39 0.00 8705497.01 0.00 0.19
October 59904327.78 96222891.22 0.00 8953746.07 5987087.44 0.00 0.172313E+09 0.00 0.19
November 0.112166E+09 6122676.80 0.00 11008918.30 84869.70 1516528.88 0.238533E+09 0.00 0.20
December 0.215256E+09 0.00 0.00 7619611.16 0.00 41715262.93 0.309278E+09 0.00 0.18
                   
Annual Sum or Average 0.985841E+09 0.207473E+10 0.00 55612210.38 0.157698E+09 0.202094E+09 0.154846E+10 0.00 0.19
Minimum of Months 0.00 0.00 0.00 541944.78 0.00 0.00 690845.11 0.00 0.18
Maximum of Months 0.215256E+09 0.533379E+09 0.00 11008918.30 36159793.78 72058610.55 0.309278E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111896E+09 0.00 0.00 2207832.47 0.00 9952728.97 0.109178E+09 0.00 0.15
February 0.128210E+09 0.00 0.00 788169.95 0.00 20495343.80 0.121996E+09 0.00 0.15
March 0.117136E+09 336649.12 0.00 1725628.92 11879.95 22027636.02 0.100604E+09 0.00 0.16
April 10581289.98 28787468.32 0.00 4730594.46 2266173.15 0.00 71004075.33 0.00 0.16
May 793850.67 64890101.32 0.00 4054872.20 7149522.95 0.00 31165784.45 0.00 0.17
June 136328.27 0.191098E+09 0.00 1576058.90 16975148.30 0.00 8456218.59 0.00 0.19
July 0.00 0.286987E+09 0.00 395635.58 20508597.87 0.00 391329.74 0.00 0.17
August 23653.57 0.314574E+09 0.00 667609.05 18255709.49 0.00 3290692.01 0.00 0.20
September 132966.80 0.202267E+09 0.00 941169.85 12839127.30 0.00 4591256.16 0.00 0.17
October 29525166.79 50882889.35 0.00 4767597.89 2920751.96 0.00 0.103920E+09 0.00 0.16
November 60402921.48 3064808.68 0.00 4082264.95 50048.81 0.00 0.137504E+09 0.00 0.16
December 0.148745E+09 18826.32 0.00 1693526.15 0.00 13884813.06 0.138104E+09 0.00 0.14
                   
Annual Sum or Average 0.607583E+09 0.114291E+10 0.00 27630960.37 80976959.79 66360521.84 0.830205E+09 0.00 0.17
Minimum of Months 0.00 0.00 0.00 395635.58 0.00 0.00 391329.74 0.00 0.14
Maximum of Months 0.148745E+09 0.314574E+09 0.00 4767597.89 20508597.87 22027636.02 0.138104E+09 0.00 0.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.249016E+09 0.00 0.00 1524099.66 0.00 33809663.05 0.186061E+09 0.00 0.19
February 0.384235E+09 0.00 0.00 367498.24 0.00 52892358.53 0.137157E+09 0.00 0.19
March 0.282294E+09 190848.27 0.00 1463669.94 30220.98 58304361.43 0.162659E+09 0.00 0.21
April 29120755.30 43910454.32 0.00 4842004.78 3626003.63 0.00 0.135563E+09 0.00 0.19
May 1565903.48 0.105132E+09 0.00 4486477.17 11457501.50 0.00 61050391.84 0.00 0.20
June 266866.74 0.314521E+09 0.00 2361412.46 27067767.04 0.00 16002055.78 0.00 0.21
July 0.00 0.493101E+09 0.00 606301.75 33716092.30 0.00 748184.09 0.00 0.18
August 43311.00 0.545673E+09 0.00 1025890.48 30269198.21 0.00 5884162.34 0.00 0.21
September 204266.90 0.349629E+09 0.00 1581771.36 21120837.91 0.00 8440559.43 0.00 0.19
October 63654387.31 85140167.80 0.00 5422779.36 4878430.72 0.00 0.212380E+09 0.00 0.19
November 0.148782E+09 3171106.44 0.00 4264070.03 250481.70 0.00 0.262761E+09 0.00 0.20
December 0.367675E+09 0.00 0.00 1196378.99 0.00 49154673.26 0.202141E+09 0.00 0.18
                   
Annual Sum or Average 0.152686E+10 0.194047E+10 0.00 29142354.24 0.132417E+09 0.194161E+09 0.139085E+10 0.00 0.19
Minimum of Months 0.00 0.00 0.00 367498.24 0.00 0.00 748184.09 0.00 0.18
Maximum of Months 0.384235E+09 0.545673E+09 0.00 5422779.36 33716092.30 58304361.43 0.262761E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.136350E+09 0.00 0.00 2375708.07 0.00 12559884.73 0.138681E+09 0.00 0.19
February 0.185343E+09 0.00 0.00 828405.41 0.00 26727661.02 0.132792E+09 0.00 0.19
March 0.161798E+09 133722.42 0.00 1492977.52 3335.40 24562460.35 0.117444E+09 0.00 0.21
April 12113766.01 26835244.32 0.00 3788065.88 845116.88 0.00 87029621.88 0.00 0.19
May 1752017.69 63349114.19 0.00 3131519.03 4104527.32 0.00 35517806.92 0.00 0.20
June 118291.36 0.195177E+09 0.00 1453680.08 10407294.52 0.00 9058758.95 0.00 0.21
July 6815.29 0.305888E+09 0.00 390364.55 18738623.37 0.00 424626.87 0.00 0.19
August 47537.28 0.340513E+09 0.00 677480.97 15250175.55 0.00 3492960.65 0.00 0.21
September 277164.85 0.217231E+09 0.00 866931.50 11151224.45 0.00 4709255.51 0.00 0.19
October 25120756.21 53176372.23 0.00 4332052.27 2403610.64 0.00 0.139049E+09 0.00 0.19
November 68040522.05 3148628.41 0.00 4184543.81 26700.78 0.00 0.173119E+09 0.00 0.20
December 0.186390E+09 0.00 0.00 1848668.90 0.00 18455813.91 0.169684E+09 0.00 0.18
                   
Annual Sum or Average 0.777359E+09 0.120545E+10 0.00 25370398.00 62930608.91 82305820.01 0.101100E+10 0.00 0.20
Minimum of Months 6815.29 0.00 0.00 390364.55 0.00 0.00 424626.87 0.00 0.18
Maximum of Months 0.186390E+09 0.340513E+09 0.00 4332052.27 18738623.37 26727661.02 0.173119E+09 0.00 0.21



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:27:25

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.582168E+11 0.175241E+10 0.00 0.770903E+10 0.578984E+10
February 0.646876E+11 0.209295E+10 0.00 0.755036E+10 0.221667E+10
March 0.914278E+11 0.318203E+10 0.00 0.755321E+10 0.453920E+10
April 0.126899E+12 0.341849E+10 0.00 0.352536E+10 0.124028E+11
May 0.133940E+12 0.330224E+10 0.00 0.193286E+10 0.170645E+11
June 0.140282E+12 0.312944E+10 0.00 -676870058.7 0.245214E+11
July 0.125205E+12 0.276828E+10 0.00 -0.241820E+10 0.256448E+11
August 0.110669E+12 0.236616E+10 0.00 -0.227739E+10 0.283292E+11
September 0.892430E+11 0.197333E+10 0.00 -990119171.7 0.236406E+11
October 0.777178E+11 0.202569E+10 0.00 0.449841E+10 0.157713E+11
November 0.611551E+11 0.193542E+10 0.00 0.735696E+10 0.963263E+10
December 0.456217E+11 0.171893E+10 0.00 0.101764E+11 0.424765E+10
           
Annual Sum or Average 0.112506E+13 0.296654E+11 0.00 0.439400E+11 0.173801E+12
Minimum of Months 0.456217E+11 0.171893E+10 0.00 -0.241820E+10 0.221667E+10
Maximum of Months 0.140282E+12 0.341849E+10 0.00 0.101764E+11 0.283292E+11