Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2023-10-16 08:28:36


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 156.19 305.56 305.56
Net Site Energy 156.19 305.56 305.56
Total Source Energy 491.19 960.94 960.94
Net Source Energy 491.19 960.94 960.94


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 6.22 1.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 20.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 9.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 18.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 24.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 154.53 1.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 6.22 1.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 20.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 9.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 18.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 24.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 6.22 1.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 20.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 9.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 18.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 24.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 136.03 3.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 302.31 3.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 136.03 3.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 302.31 3.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 154.528 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 154.528 100.00
     
Total On-Site and Utility Electric Sources 154.528 100.00
Total Electricity End Uses 154.528 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 11.83
Time Setpoint Not Met During Occupied Cooling 19.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 1588.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:28
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.9815 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.9815 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.9815 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.9815 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.9815 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.9815 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.9815 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.9815 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.9815 9.29 6.7800  
Conditioned Total 511.16             6.9815 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.9815 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 09-JAN-08:09 13-FEB-06:19 - - - - - - - - - - 02-JAN-12:09
Heating 8158.03 25631.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2495.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1615.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2735.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 18328.75 25631.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 8158.03 25631.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2495.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1615.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2735.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 19.71 1.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 65.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 84.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 58.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 76.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 489.39 1.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 38.56 3.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 127.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 115.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 149.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 957.41 3.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 38.56 3.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 127.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 165.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 61.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 115.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 149.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 957.41 3.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.306054
PERIMETER_ZN_1 DIRECT AIR 0.315580
PERIMETER_ZN_2 DIRECT AIR 0.237364
PERIMETER_ZN_3 DIRECT AIR 0.309123
PERIMETER_ZN_4 DIRECT AIR 0.273755
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.306054 0.306054 0.306054 0.306054 0.306054 0.306054 1.00 1.00 0.306054
PSZ-AC:2 0.315580 0.315580 0.315580 0.315580 0.315580 0.315580 1.00 1.00 0.315580
PSZ-AC:3 0.237364 0.237364 0.237364 0.237364 0.237364 0.237364 1.00 1.000000 0.237364
PSZ-AC:4 0.309123 0.309123 0.309123 0.309123 0.309123 0.309123 1.00 1.00 0.309123
PSZ-AC:5 0.273755 0.273755 0.273755 0.273755 0.273755 0.273755 1.00 1.00 0.273755
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.306054 0.064622
PSZ-AC:2_OA_CONTROLLER 0.315580 0.048988
PSZ-AC:3_OA_CONTROLLER 0.237364 0.029060
PSZ-AC:4_OA_CONTROLLER 0.309123 0.048988
PSZ-AC:5_OA_CONTROLLER 0.273755 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.306054 6499.00 0.753605
PSZ-AC:2 HP COOLING COIL 0.315580 6389.77 0.771577
PSZ-AC:3 HP COOLING COIL 0.237364 4447.77 0.800792
PSZ-AC:4 HP COOLING COIL 0.309123 6280.46 0.769552
PSZ-AC:5 HP COOLING COIL 0.273755 5001.31 0.800128
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.306054 0.306054 0.306054 0.306054 6499.00 6499.00 40.00 3490.52 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.315580 0.315580 0.315580 0.315580 6389.77 6389.77 40.00 5384.13 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.237364 0.237364 0.237364 0.237364 4447.77 4447.77 40.00 3341.42 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.309123 0.309123 0.309123 0.309123 6280.46 6280.46 40.00 5353.69 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.273755 0.273755 0.273755 0.273755 5001.31 5001.31 40.00 3357.98 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.306054
PSZ-AC:2 FAN 0.315580
PSZ-AC:3 FAN 0.237364
PSZ-AC:4 FAN 0.309123
PSZ-AC:5 FAN 0.273755
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.306054 6499.00
PSZ-AC:2 HEATING COIL 0.315580 6389.77
PSZ-AC:3 HEATING COIL 0.237364 4447.77
PSZ-AC:4 HEATING COIL 0.309123 6280.46
PSZ-AC:5 HEATING COIL 0.273755 5001.31
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 3490.52
PSZ-AC:2_SUPPHEATCOIL 5384.13
PSZ-AC:3_SUPPHEATCOIL 3341.42
PSZ-AC:4_SUPPHEATCOIL 5353.69
PSZ-AC:5_SUPPHEATCOIL 3357.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1044.832 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1044.832
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4610


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1754E-003
2 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.2953E-003
3 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.2560E-003
4 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.3595E-003
5 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 8.6527E-004
6 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 9.5604E-004
7 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 4.3251E-004
8 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.8318E-004
9 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.1831E-003
10 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 5.4329E-003
11 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.9012E-003
12 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 5.4447E-003
13 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.2198E-003
14 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.3612E-003
15 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.6930E-003
16 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.9875E-003
17 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 8.4252E-003
18 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 8.1840E-003
19 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 8.8190E-003
20 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 8.9393E-003
21 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 7.0322E-003
22 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 5.1398E-003
23 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 3.0682E-003
24 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.8375E-003
25 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1867E-003
26 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3576E-003
27 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.2702E-003
28 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.4336E-003
29 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 8.7563E-004
30 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 9.9116E-004
31 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 4.2894E-004
32 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.7533E-004
33 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1238E-003
34 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1415E-003
35 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.2137E-003
36 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.2297E-003
37 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 8.2720E-004
38 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 8.3908E-004
39 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 4.0429E-004
40 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 4.0967E-004
41 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1194E-003
42 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1227E-003
43 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.2098E-003
44 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.2128E-003
45 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 8.2407E-004
46 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 8.2629E-004
47 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 4.0268E-004
48 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 4.0373E-004
49 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.8514E-003
50 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.3321E-003
51 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.9471E-003
52 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.4410E-003
53 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.3871E-003
54 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.6630E-003
55 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.8598E-004
56 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.6907E-004
57 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.0446E-003
58 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.1423E-003
59 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 9.9405E-004
60 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.0674E-003
61 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.8786E-004
62 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.2758E-004
63 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.7807E-004
64 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.2474E-004
65 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.6745E-003
66 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.9453E-003
67 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.0414E-003
68 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.5101E-003
69 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.8598E-003
70 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.3229E-003
71 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3215E-003
72 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.1121E-003
73 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.2610E-002
74 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.6303E-003
75 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.3664E-002
76 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 5.5651E-003
77 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 9.5380E-003
78 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.5783E-003
79 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.9598E-003
80 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.2669E-003
81 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.1959E-003
82 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.5235E-003
83 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.1802E-003
84 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.5314E-003
85 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.6853E-004
86 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.1346E-003
87 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.8152E-004
88 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 7.3256E-004
89 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.6227E-004
90 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.4811E-004
91 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.7455E-004
92 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.4239E-004
93 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.1630E-004
94 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.6701E-004
95 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.2791E-004
96 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.7227E-004
97 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.8609E-003
98 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.3025E-003
99 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.2895E-003
100 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.7809E-003
101 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.3883E-003
102 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.3687E-003
103 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.8007E-003
104 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.7666E-003
105 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.0275E-003
106 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.8431E-003
107 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.0777E-003
108 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.1248E-003
109 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.5536E-003
110 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.3069E-003
111 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.0538E-003
112 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.0664E-003
113 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.7183E-004
114 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.8185E-004
115 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.7957E-004
116 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.6184E-004
117 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.1298E-004
118 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.5623E-004
119 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.3509E-004
120 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.8799E-004
121 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.1876E-004
122 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.3248E-004
123 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.3835E-004
124 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.4884E-004
125 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.8349E-004
126 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.8953E-004
127 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.0508E-004
128 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 4.1105E-004
129 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.1482E-004
130 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.1757E-004
131 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.3528E-004
132 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.3740E-004
133 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.8144E-004
134 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.8270E-004
135 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.0325E-004
136 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.0438E-004
137 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 9.0087E-004
138 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0736E-003
139 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.1498E-004
140 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 9.7641E-004
141 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 7.5040E-004
142 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 8.7131E-004
143 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.8264E-004
144 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 7.3330E-004
145 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.6540E-003
146 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.4935E-003
147 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.3229E-003
148 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.0766E-003
149 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.6320E-003
150 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.2048E-003
151 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.9431E-003
152 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.2376E-003
153 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.6069E-003
154 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.7697E-003
155 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.7998E-003
156 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.1870E-003
157 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.2463E-003
158 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.7249E-003
159 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.3183E-003
160 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.0876E-003
161 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 8.0989E-004
162 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 9.1714E-004
163 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.0271E-004
164 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.8045E-004
165 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.7991E-004
166 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.1138E-004
167 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.7906E-004
168 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.2545E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3351.36765 4021.64118 0.25505 0.30605 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.45000 1.44715E-002 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 1012.95253 1215.54304 4.52956E-002 6.46221E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3455.51192 4146.61430 0.26298 0.31558 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 33.92500 1.44724E-002 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 3228.46308 3874.15569 0.14435 0.17323 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2599.19105 3119.02926 0.19780 0.23736 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 31.97750 1.44688E-002 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 2039.89045 2447.86854 9.12094E-002 0.10945 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 3384.84742 4061.81690 0.25760 0.30912 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 33.83000 1.44722E-002 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 3202.72492 3843.26991 0.14320 0.17184 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 2997.66914 3597.20296 0.22813 0.27376 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12000 1.44691E-002 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 2053.89983 2464.67979 9.18358E-002 0.11020 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30000 2.29779E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4680.22 0.30605 0.30605 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 3490.52 6.46221E-002 6.46221E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 4656.06 0.31558 0.31558 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 5384.13 0.17323 0.17323 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3345.00 0.23736 0.23736 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 3341.42 0.10945 0.10945 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 4567.14 0.30912 0.30912 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 5353.69 0.17184 0.17184 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 3820.61 0.27376 0.27376 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 3357.98 0.11020 0.11020 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.30605
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.31558
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.23736
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.30912
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.27376
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.30605
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.30605
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.30605
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.30605
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.30605
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.30605
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.31558
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.31558
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.31558
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.31558
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.31558
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.31558
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.23736
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.23736
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.23736
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.23736
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.23736
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.23736
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.30912
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.30912
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.30912
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.30912
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.30912
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.30912
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.27376
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.27376
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.27376
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.27376
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.27376
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.27376
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.30605
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.31558
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.23736
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.30912
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.27376
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30605
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.30605
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6499.00102
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.75361
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.30605
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.30605
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.30605
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.30605
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6499.00102
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6499.00102
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3490.52070
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.30605
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.30605
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6499.00102
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 3490.52070
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.31558
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.31558
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6389.77146
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.77158
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.31558
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.31558
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.31558
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.31558
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6389.77146
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6389.77146
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5384.12509
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.31558
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.31558
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6389.77146
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 5384.12509
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.23736
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.23736
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4447.76767
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80079
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.23736
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.23736
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.23736
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.23736
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4447.76767
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4447.76767
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3341.41751
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.23736
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.23736
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4447.76767
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 3341.41751
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.30912
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.30912
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6280.46325
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.76955
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.30912
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.30912
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.30912
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.30912
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6280.46325
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6280.46325
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5353.68921
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.30912
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.30912
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6280.46325
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 5353.68921
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.27376
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.27376
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5001.30974
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80013
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.27376
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.27376
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.27376
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.27376
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5001.30974
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5001.30974
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3357.98389
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.27376
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.27376
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5001.30974
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 3357.98389
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 6258.2 3.45 11.76 12.33 11.66 11.76
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 6141.7 3.42 11.67 12.22 11.56 11.62
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 4261.4 3.37 11.50 12.04 11.39 11.37
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 6037.5 3.42 11.67 12.23 11.57 11.63
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4786.5 3.35 11.45 11.98 11.34 11.29


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 6743.6 3726.1 7.44 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 6641.6 3674.8 7.42 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 4636.7 2571.6 7.40 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 6527.1 3611.1 7.46 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 5219.1 2897.0 7.37 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 5.1489710992E-003 4.2068321734E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 7.9711139301E-002 0.1319321969 Pass Pass 0.6076145366 1.9404802477 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 0.1071697075 0.1476925280 Pass Pass 0.4108213250 1.3885361122 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 0.1088699373 0.1440803711 Pass Pass 1.0353274620 3.2350678654 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 0.1201099329 0.1607282974 Pass Pass 0.2857203798 1.0663343333 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.2461207427 0.2397044630 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1081.75 35.63 0.00 50.31 0.301767E+158 0.301767E+158



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.689 0.768 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.689 0.768 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.424_SHGC_SOUTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.424_SHGC_SOUTH_0.249   3.91 0.00 0.00 3.91 3.91 2.409 0.250 0.275             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.424_SHGC_EAST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.424_SHGC_NORTH_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.424_SHGC_WEST_0.249   2.79 0.00 0.00 2.79 2.79 2.409 0.250 0.275             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.409 0.250 0.275                      
North Total or Average             16.72 2.409 0.250 0.275                      
Non-North Total or Average             42.93 2.409 0.250 0.275                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.90 0.86 0.86 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.38 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.38 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.38 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.33 0.00 1.00 0.00 0.00 1.00 0.40 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.09 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.82 0.00 0.00 0.67 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.9815 149.66 1044.83 LightsWired LTG_SCH_OFFICE 55.32 168.00 44.56 0.0000 Y 8.74
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 36.57 0.0000 Y 5.44
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 37.89 0.0000 Y 3.34
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 39.36 0.0000 Y 5.85
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.19 0.0000 Y 3.37
Interior Lighting Total       6.9815 511.16 3568.64               26.74


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 87.95 AstronomicalClock -   41.77 41.77 0.69
EXTERIOR_LIGHTS_B 200.47 AstronomicalClock -   83.77 62.77 2.36
EXTERIOR_LIGHTS_C 773.25 AstronomicalClock -   83.77 47.60 6.91
Exterior Lighting Total 1061.67           9.96



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6499.00 4897.68 1601.32 0.75 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6389.77 4930.20 1459.57 0.77 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4447.77 3561.73 886.03 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6280.46 4833.14 1447.32 0.77 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5001.31 4001.69 999.62 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   6258.2 3.45 11.76 12.33 11.66 11.76
PSZ-AC:2 HP COOLING COIL   6141.7 3.42 11.67 12.22 11.56 11.62
PSZ-AC:3 HP COOLING COIL   4261.4 3.37 11.50 12.04 11.39 11.37
PSZ-AC:4 HP COOLING COIL   6037.5 3.42 11.67 12.23 11.57 11.63
PSZ-AC:5 HP COOLING COIL   4786.5 3.35 11.45 11.98 11.34 11.29
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 6743.6 3726.1 7.44 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 6641.6 3674.8 7.42 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 4636.7 2571.6 7.40 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 6527.1 3611.1 7.46 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 5219.1 2897.0 7.37 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   6499.00 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   3490.52 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   6389.77 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   5384.13 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   4447.77 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   3341.42 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   6280.46 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   5353.69 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   5001.31 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   3357.98 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.31 342.81 1120.11 1.00 1.88 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.32 353.48 1120.11 1.00 1.86 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.24 265.87 1120.11 1.00 2.08 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.31 346.25 1120.11 1.00 1.87 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.27 306.64 1120.11 1.00 1.96 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3351.37 4021.64 26.87 0.255 0.306 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 23.89 23.89 0.00903 33.45 0.01447 0.065 0.00
PERIMETER_ZN_1 3455.51 4146.61 36.55 0.263 0.316 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 23.89 23.89 0.00909 33.92 0.01447 0.049 0.00
PERIMETER_ZN_2 2599.19 3119.03 46.35 0.198 0.237 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 23.89 23.89 0.00899 31.98 0.01447 0.029 0.00
PERIMETER_ZN_3 3384.85 4061.82 35.80 0.258 0.309 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 23.89 23.89 0.00910 33.83 0.01447 0.049 0.00
PERIMETER_ZN_4 2997.67 3597.20 53.45 0.228 0.274 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 23.89 23.89 0.00893 32.12 0.01447 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1012.95 1215.54 8.12 0.045 0.065 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00800 -6.30 0.00230 0.065 0.00
PERIMETER_ZN_1 3228.46 3874.16 34.15 0.144 0.173 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00746 -6.30 0.00230 0.049 0.00
PERIMETER_ZN_2 2039.89 2447.87 36.37 0.091 0.109 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00743 -6.30 0.00230 0.029 0.00
PERIMETER_ZN_3 3202.72 3843.27 33.88 0.143 0.172 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00746 -6.30 0.00230 0.049 0.00
PERIMETER_ZN_4 2053.90 2464.68 36.62 0.092 0.110 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00744 -6.30 0.00230 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.31 0.31 0.06 0.06 0.3061 0.3061 0.3061 1.0000 1.0000
PSZ-AC:2 0.32 0.32 0.17 0.17 0.3156 0.3156 0.3156 1.0000 1.0000
PSZ-AC:3 0.24 0.24 0.11 0.11 0.2374 0.2374 0.2374 1.0000 1.0000
PSZ-AC:4 0.31 0.31 0.17 0.17 0.3091 0.3091 0.3091 1.0000 1.0000
PSZ-AC:5 0.27 0.27 0.11 0.11 0.2738 0.2738 0.2738 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6499.001 4897.681 0.306054 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 6397.29 5052.89 0.306054 26.85 18.34 0.01018234 12.80 11.77 0.00850000 33.45 0.01447152 23.29 21.1146 23.89 0.00904005 47.1915 3323.14 0.00 6497.89 4809.76
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6499.001 6499.001 0.306054 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6499.00 6499.00 0.306054 15.32 11.10 0.00679600 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 21.1146 21.11 0.00800000 49.5265 1012.30 0.00 6507.54 6507.54
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 3490.521 3490.521 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 3490.52 3490.52 0.306054 15.32 11.10 0.00679600 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 21.1146 21.11 0.00800000 49.5265 1012.30 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6389.771 4930.200 0.315580 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 6210.52 5039.79 0.315580 26.39 17.99 0.00992647 12.80 11.77 0.00850000 33.92 0.01447239 23.42 15.5231 23.89 0.00909216 47.4599 3450.08 0.00 6388.68 4838.36
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6389.771 6389.771 0.315580 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6389.77 6389.77 0.315580 16.85 11.60 0.00665977 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.5231 21.11 0.00746131 46.2351 3228.46 0.00 6398.17 6398.17
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 5384.125 5384.125 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5384.13 5384.13 0.315580 16.85 11.60 0.00665977 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.5231 21.11 0.00746131 46.2351 3228.46 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4447.768 3561.735 0.237364 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 4346.87 3633.19 0.237364 25.82 17.60 0.00966217 12.80 11.77 0.00850000 31.98 0.01446884 22.89 12.2429 23.89 0.00899236 46.9452 2593.98 0.00 4447.00 3491.48
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 4447.768 4447.768 0.237364 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4447.77 4447.77 0.237364 17.75 12.11 0.00680567 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 12.2429 21.11 0.00743456 46.0716 2039.89 0.00 4453.61 4453.61
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 3341.418 3341.418 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3341.42 3341.42 0.237364 17.75 12.11 0.00680567 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 12.2429 21.11 0.00743456 46.0716 2039.89 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 6280.463 4833.142 0.309123 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 6113.37 4944.09 0.309123 26.41 18.02 0.00995393 12.80 11.77 0.00850000 33.83 0.01447222 23.39 15.8473 23.89 0.00910457 47.5237 3376.75 0.00 6279.39 4743.34
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 6280.463 6280.463 0.309123 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6280.46 6280.46 0.309123 16.77 11.54 0.00663973 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.8473 21.11 0.00745739 46.2111 3202.72 0.00 6288.72 6288.72
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 5353.689 5353.689 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5353.69 5353.69 0.309123 16.77 11.54 0.00663973 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 15.8473 21.11 0.00745739 46.2111 3202.72 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5001.310 4001.686 0.273755 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 4863.74 4146.99 0.273755 25.71 17.44 0.00951459 12.80 11.77 0.00850000 32.12 0.01446910 22.93 10.6154 23.89 0.00892580 46.6026 2995.84 0.00 5000.45 3922.94
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 5001.310 5001.310 0.273755 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5001.31 5001.31 0.273755 18.20 12.38 0.00689238 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 10.6154 21.11 0.00743804 46.0929 2053.90 0.00 5007.88 5007.88
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 3357.984 3357.984 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3357.98 3357.98 0.273755 18.20 12.38 0.00689238 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 10.6154 21.11 0.00743804 46.0929 2053.90 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6499.001 4897.681 0.306054 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.7685 1004.8586 1.1610 PSZ-AC:1 FAN Fan:OnOff 0.306054 0.35532203   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 Sensible 6397.29 5052.89 0.9843 0.35532203 0.306054 26.85 18.34 0.01018234 52954.1 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 342.814 6054.48 33.45 0.01447152 23.29 0.06462207 21.1146 23.89 0.00903429 23.89 0.00904005 47.1915 3323.14 0.00 6497.89 4809.76 0.34128950 26.67 19.44 0.01118466 55322.4 12.88 12.87 0.00924532 36283.2
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6499.001 6499.001 0.306054 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:1 FAN Fan:OnOff 0.306054 0.35532203   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6499.00 6499.00 1.0000 0.35532203 0.306054 15.32 11.10 0.00679600 32586.6 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6499.00 -6.30 0.00229779 -6.30 0.06462207 21.1146 21.11 0.00800000 21.11 0.00800000 49.5265 1012.30 0.00 6507.54 6507.54 0.34904338 21.11 15.56 0.00875166 43444.1 39.37 21.53 0.00875166 62088.0
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3490.521 3490.521 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:1 FAN Fan:OnOff 0.306054 0.35532203   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 3490.52 3490.52 1.0000 0.35532203 0.306054 15.32 11.10 0.00679600 32586.6 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3490.52 -6.30 0.00229779 -6.30 0.06462207 21.1146 21.11 0.00800000 21.11 0.00800000 49.5265 1012.30 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6389.771 4930.200 0.315580 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.2928 1004.8586 1.1610 PSZ-AC:2 FAN Fan:OnOff 0.315580 0.36638064   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 6210.52 5039.79 0.9719 0.36638064 0.315580 26.39 17.99 0.00992647 51829.8 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 353.483 5857.04 33.92 0.01447239 23.42 0.04898771 15.5231 23.89 0.00909113 23.89 0.00909216 47.4599 3450.08 0.00 6388.68 4838.36 0.35191138 26.67 19.44 0.01118466 55322.4 13.22 13.21 0.00945740 37168.2
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6389.771 6389.771 0.315580 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:2 FAN Fan:OnOff 0.315580 0.36638064   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6389.77 6389.77 1.0000 0.36638064 0.315580 16.85 11.60 0.00665977 33799.9 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6389.77 -6.30 0.00229779 -6.30 0.04898771 15.5231 21.11 0.00746131 21.11 0.00746131 46.2351 3228.46 0.00 6398.17 6398.17 0.35990658 21.11 15.56 0.00875166 43444.1 38.52 21.29 0.00875166 61221.4
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5384.125 5384.125 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:2 FAN Fan:OnOff 0.315580 0.36638064   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5384.13 5384.13 1.0000 0.36638064 0.315580 16.85 11.60 0.00665977 33799.9 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5384.13 -6.30 0.00229779 -6.30 0.04898771 15.5231 21.11 0.00746131 21.11 0.00746131 46.2351 3228.46 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4447.768 3561.735 0.237364 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.8015 1004.8586 1.1610 PSZ-AC:3 FAN Fan:OnOff 0.237364 0.27557403   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 4346.87 3633.19 0.9773 0.27557403 0.237364 25.82 17.60 0.00966217 50576.2 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 265.873 4081.00 31.98 0.01446884 22.89 0.02906014 12.2429 23.89 0.00899161 23.89 0.00899236 46.9452 2593.98 0.00 4447.00 3491.48 0.26469094 26.67 19.44 0.01118466 55322.4 13.77 13.72 0.00976928 38521.6
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4447.768 4447.768 0.237364 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:3 FAN Fan:OnOff 0.237364 0.27557403   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4447.77 4447.77 1.0000 0.27557403 0.237364 17.75 12.11 0.00680567 35084.0 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4447.77 -6.30 0.00229779 -6.30 0.02906014 12.2429 21.11 0.00743456 21.11 0.00743456 46.0716 2039.89 0.00 4453.61 4453.61 0.27070455 21.11 15.56 0.00875166 43444.1 37.22 20.90 0.00875166 59896.0
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3341.418 3341.418 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:3 FAN Fan:OnOff 0.237364 0.27557403   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3341.42 3341.42 1.0000 0.27557403 0.237364 17.75 12.11 0.00680567 35084.0 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3341.42 -6.30 0.00229779 -6.30 0.02906014 12.2429 21.11 0.00743456 21.11 0.00743456 46.0716 2039.89 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6280.463 4833.142 0.309123 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.3439 1004.8586 1.1610 PSZ-AC:4 FAN Fan:OnOff 0.309123 0.35888497   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 6113.37 4944.09 0.9734 0.35888497 0.309123 26.41 18.02 0.00995393 51917.8 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 346.252 5767.12 33.83 0.01447222 23.39 0.04898771 15.8473 23.89 0.00910306 23.89 0.00910457 47.5237 3376.75 0.00 6279.39 4743.34 0.34471172 26.67 19.44 0.01118466 55322.4 13.21 13.18 0.00943756 37106.0
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6280.463 6280.463 0.309123 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:4 FAN Fan:OnOff 0.309123 0.35888497   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6280.46 6280.46 1.0000 0.35888497 0.309123 16.77 11.54 0.00663973 33658.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6280.46 -6.30 0.00229779 -6.30 0.04898771 15.8473 21.11 0.00745739 21.11 0.00745739 46.2111 3202.72 0.00 6288.72 6288.72 0.35254336 21.11 15.56 0.00875166 43444.1 38.58 21.30 0.00875166 61282.2
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5353.689 5353.689 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:4 FAN Fan:OnOff 0.309123 0.35888497   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5353.69 5353.69 1.0000 0.35888497 0.309123 16.77 11.54 0.00663973 33658.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5353.69 -6.30 0.00229779 -6.30 0.04898771 15.8473 21.11 0.00745739 21.11 0.00745739 46.2111 3202.72 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5001.310 4001.686 0.273755 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.5271 1004.8586 1.1610 PSZ-AC:5 FAN Fan:OnOff 0.273755 0.31782335   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 4863.74 4146.99 0.9725 0.31782335 0.273755 25.71 17.44 0.00951459 50081.1 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 306.635 4557.11 32.12 0.01446910 22.93 0.02906014 10.6154 23.89 0.00892619 23.89 0.00892580 46.6026 2995.84 0.00 5000.45 3922.94 0.30527173 26.67 19.44 0.01118466 55322.4 14.11 13.88 0.00980076 38942.1
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5001.310 5001.310 0.273755 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:5 FAN Fan:OnOff 0.273755 0.31782335   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5001.31 5001.31 1.0000 0.31782335 0.273755 18.20 12.38 0.00689238 35757.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5001.31 -6.30 0.00229779 -6.30 0.02906014 10.6154 21.11 0.00743804 21.11 0.00743804 46.0929 2053.90 0.00 5007.88 5007.88 0.31220732 21.11 15.56 0.00875166 43444.1 36.82 20.78 0.00875166 59484.3
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3357.984 3357.984 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 PSZ-AC:5 FAN Fan:OnOff 0.273755 0.31782335   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3357.98 3357.98 1.0000 0.31782335 0.273755 18.20 12.38 0.00689238 35757.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3357.98 -6.30 0.00229779 -6.30 0.02906014 10.6154 21.11 0.00743804 21.11 0.00743804 46.0929 2053.90 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2259.00 2112.33 652.00
PERIMETER_ZN_1 2306.50 2659.00 1109.67
PERIMETER_ZN_2 2083.00 2131.33 976.17
PERIMETER_ZN_3 2470.33 2643.50 1187.50
PERIMETER_ZN_4 2507.67 2547.50 1142.33
ATTIC 0.00 0.00 0.00
Facility 2969.33 2987.67 1588.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 1.33 18.50 1.33 18.50
PERIMETER_ZN_1 10.33 8.50 9.00 8.50
PERIMETER_ZN_2 12.00 6.00 5.50 6.00
PERIMETER_ZN_3 15.00 6.33 8.00 6.33
PERIMETER_ZN_4 11.17 4.67 4.83 4.33
ATTIC 0.00 0.00 0.00 0.00
Facility 30.17 20.17 11.83 19.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.397 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.396 0.411 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.370 0.066 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.396 0.054 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.396 0.061 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762126.79 0.00 762126.79 0.00 762126.79 2037921.45 5484.00 3276.00 0.00 0.00
PERIMETER_ZN_1 579958.83 0.00 579958.83 743513.94 1323472.77 1544876.42 5480.63 3279.37 0.00 30.91
PERIMETER_ZN_2 282135.63 0.00 282135.63 147402.50 429538.14 916440.58 6234.81 2525.19 0.00 538.53
PERIMETER_ZN_3 583046.98 0.00 583046.98 221103.75 804150.73 1544876.42 5476.18 3283.82 0.00 76.50
PERIMETER_ZN_4 344946.09 0.00 344946.09 147402.50 492348.60 916440.58 5480.69 3279.31 0.00 75.58
Total Facility 2552214.32 0.00 2552214.32 1259422.70 3811637.02 6960555.45 6239.50 3288.14 0.00 598.50


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0390 0.0764 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0037 0.0244 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0051 0.0426 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0222 0.0000 0.0222 0.0034 0.0256 0.0291 1008.00 3276.00 0.00
Total Facility 0.1673 0.0000 0.1673 0.0511 0.2185 0.2207 1763.50 3276.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 1027245.19 0.00 1027245.19 2037921.45 5484.00 0.00 3276.00 0.00
PSZ-AC:2 781707.09 0.00 781707.09 1544876.42 5478.33 0.25 3281.42 30.83
PSZ-AC:3 380281.17 0.00 380281.17 916440.58 6222.63 2.66 2534.70 515.93
PSZ-AC:4 785869.51 0.00 785869.51 1544876.42 5471.11 0.21 3288.68 75.12
PSZ-AC:5 464941.29 0.00 464941.29 916440.58 5478.52 0.14 3281.35 74.82


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0666 0.0000 0.0666 0.0646 1008.00 0.00 3276.00
PSZ-AC:2 0.0505 0.0000 0.0505 0.0490 1008.00 0.00 3276.00
PSZ-AC:3 0.0280 0.0000 0.0280 0.0291 1008.00 0.00 2520.00
PSZ-AC:4 0.0505 0.0000 0.0505 0.0490 1008.00 0.00 3276.00
PSZ-AC:5 0.0300 0.0000 0.0300 0.0291 1008.00 0.00 3276.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3276.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3306.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3035.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3351.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3350.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0871 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0660 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0392 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0660 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0392 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 555
Defaulted Fields 365
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 154.53 1248.68 01-JAN-08:00 18328.75 09-JAN-08:10
Electricity:Building 75.03 677.68 01-JAN-00:10 5865.64 30-OCT-07:10
Electricity:Zone:CORE_ZN 22.88 198.41 01-JAN-00:10 1717.53 02-JAN-08:10
Electricity:SpaceType:GENERAL 75.03 677.68 01-JAN-00:10 5865.64 30-OCT-07:10
InteriorLights:Electricity 26.74 110.04 01-JAN-00:10 2540.33 30-OCT-07:10
InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.74 110.04 01-JAN-00:10 2540.33 30-OCT-07:10
LightsWired:InteriorLights:Electricity 26.74 110.04 01-JAN-00:10 2540.33 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.74 110.04 01-JAN-00:10 2540.33 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_1 16.16 150.41 01-JAN-00:10 1301.80 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.44 24.42 01-JAN-00:10 563.75 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.44 24.42 01-JAN-00:10 563.75 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_2 9.70 89.23 01-JAN-00:10 772.25 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.34 14.49 01-JAN-00:10 334.43 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.34 14.49 01-JAN-00:10 334.43 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_3 16.57 150.41 01-JAN-00:10 1301.81 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.85 24.42 01-JAN-00:10 563.77 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.85 24.42 01-JAN-00:10 563.77 30-OCT-07:10
Electricity:Zone:PERIMETER_ZN_4 9.73 89.23 01-JAN-00:10 772.25 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.37 14.49 01-JAN-00:10 334.43 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.37 14.49 01-JAN-00:10 334.43 30-OCT-07:10
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
ElectricityPurchased:Plant 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
Cogeneration:ElectricityPurchased 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
General:Cogeneration:ElectricityPurchased 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
ElectricityNet:Plant 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
Cogeneration:ElectricityNet 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
General:Cogeneration:ElectricityNet 154.53 1248.68 04-MAR-13:30 18328.75 09-JAN-08:10
ExteriorLights:Electricity 9.96 0.00 01-JAN-07:50 1061.67 01-JAN-06:10
General:ExteriorLights:Electricity 9.96 0.00 01-JAN-07:50 1061.67 01-JAN-06:10
Electricity:HVAC 45.43 0.00 01-JAN-00:40 10055.73 09-JAN-06:10
Fans:Electricity 18.59 0.00 01-JAN-00:40 1615.06 02-JAN-06:10
General:Fans:Electricity 18.59 0.00 01-JAN-00:40 1615.06 02-JAN-06:10
Cooling:Electricity 20.61 0.00 01-JAN-00:10 6446.12 07-JUL-16:00
General:Cooling:Electricity 20.61 0.00 01-JAN-00:10 6446.12 07-JUL-16:00
Heating:Electricity 6.22 0.00 01-JAN-00:40 8440.68 09-JAN-06:10
General:Heating:Electricity 6.22 0.00 01-JAN-00:40 8440.68 09-JAN-06:10
Electricity:Plant 24.10 571.00 01-JAN-00:10 2804.93 27-JAN-12:10
WaterSystems:Electricity 24.10 571.00 01-JAN-00:10 2804.93 27-JAN-12:10
Water Heater:WaterSystems:Electricity 24.10 571.00 01-JAN-00:10 2804.93 27-JAN-12:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 10-JAN-11:40
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 10-JAN-11:40


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1.66 0.00 01-JAN-00:10 25631.74 13-FEB-06:20
NaturalGas:HVAC 1.66 0.00 01-JAN-00:10 25631.74 13-FEB-06:20
Heating:NaturalGas 1.66 0.00 01-JAN-00:10 25631.74 13-FEB-06:20
General:Heating:NaturalGas 1.66 0.00 01-JAN-00:10 25631.74 13-FEB-06:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 10-JAN-12:10
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 10-JAN-12:10
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 03-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 03-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 183.04 0.00 01-JAN-00:40 68218.96 02-JAN-06:20
EnergyTransfer:Building 75.93 0.00 01-JAN-00:40 32579.81 02-JAN-06:20
EnergyTransfer:Zone:CORE_ZN 20.72 0.00 01-JAN-00:10 7133.23 02-JAN-06:20
Heating:EnergyTransfer 11.62 0.00 01-JAN-00:40 32579.81 02-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_ZN 0.70 0.00 01-JAN-00:10 7133.23 02-JAN-06:20
General:Heating:EnergyTransfer 11.62 0.00 01-JAN-00:40 32579.81 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.70 0.00 01-JAN-00:10 7133.23 02-JAN-06:20
Cooling:EnergyTransfer 64.31 0.00 01-JAN-00:10 18492.79 17-JUL-05:20
Cooling:EnergyTransfer:Zone:CORE_ZN 20.02 0.00 01-JAN-00:10 4852.06 10-JUL-07:10
General:Cooling:EnergyTransfer 64.31 0.00 01-JAN-00:10 18492.79 17-JUL-05:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 20.02 0.00 01-JAN-00:10 4852.06 10-JUL-07:10
EnergyTransfer:Zone:PERIMETER_ZN_1 18.69 0.00 01-JAN-00:40 7681.66 09-JAN-06:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 3.62 0.00 01-JAN-00:40 7681.66 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 3.62 0.00 01-JAN-00:40 7681.66 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 15.08 0.00 01-JAN-00:10 4865.87 11-OCT-15:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 15.08 0.00 01-JAN-00:10 4865.87 11-OCT-15:10
EnergyTransfer:Zone:PERIMETER_ZN_2 10.52 0.00 01-JAN-00:40 5286.77 02-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 1.82 0.00 01-JAN-00:40 5286.77 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 1.82 0.00 01-JAN-00:40 5286.77 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 8.70 0.00 01-JAN-00:10 3458.32 10-JUL-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 8.70 0.00 01-JAN-00:10 3458.32 10-JUL-10:10
EnergyTransfer:Zone:PERIMETER_ZN_3 15.51 0.00 01-JAN-00:40 7526.83 09-JAN-06:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 3.53 0.00 01-JAN-00:40 7526.83 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 3.53 0.00 01-JAN-00:40 7526.83 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 11.98 0.00 01-JAN-00:10 4018.30 17-JUL-05:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 11.98 0.00 01-JAN-00:10 4018.30 17-JUL-05:10
EnergyTransfer:Zone:PERIMETER_ZN_4 10.49 0.00 01-JAN-00:40 5603.38 09-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 1.95 0.00 01-JAN-00:40 5603.38 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 1.95 0.00 01-JAN-00:40 5603.38 09-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 8.53 0.00 01-JAN-00:10 3221.79 14-AUG-05:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 8.53 0.00 01-JAN-00:10 3221.79 14-AUG-05:20
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 02-FEB-07:10 93.58 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 02-FEB-07:10 93.58 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 02-FEB-07:10 93.58 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 02-FEB-07:10 93.58 02-JAN-07:10
EnergyTransfer:HVAC 107.11 0.00 01-JAN-00:40 36001.25 09-JAN-06:20
CoolingCoils:EnergyTransfer 92.18 0.00 01-JAN-00:10 32059.20 21-AUG-05:10
HeatingCoils:EnergyTransfer 14.93 0.00 01-JAN-00:40 36001.25 09-JAN-06:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 02-FEB-07:10 93.58 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 02-FEB-07:10 93.58 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 02-FEB-07:10 93.58 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.698 -20.022 0.000 0.000 5.108 8.739 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -8.664
PERIMETER_ZN_1 0.000 0.000 3.616 -15.076 0.000 0.000 3.925 5.437 10.719 14.513 0.000 0.869 0.000 0.000 -7.384 0.000 -6.355 -10.264
PERIMETER_ZN_2 0.000 0.000 1.821 -8.704 0.000 0.000 1.706 3.342 6.359 6.957 0.000 0.050 0.000 0.000 -3.888 0.000 -1.417 -6.224
PERIMETER_ZN_3 0.000 0.000 3.529 -11.976 0.000 0.000 3.968 5.852 10.719 4.438 0.000 0.088 0.000 0.000 -6.184 0.000 -2.063 -8.371
PERIMETER_ZN_4 0.000 0.000 1.954 -8.534 0.000 0.000 2.333 3.369 6.359 7.053 0.000 0.048 0.000 0.000 -4.190 0.000 -1.441 -6.950
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 9.673 29.978 0.000 0.000 0.000 -39.651 -0.001
Total Facility 0.000 0.000 11.618 -64.312 0.000 0.000 17.040 26.739 48.296 32.961 0.000 10.727 29.979 0.000 -21.646 0.000 -50.928 -40.473


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 13-OCT-05:03 0.00 0.00 0.00 -6262.61 0.00 0.00 56.29 32.22 486.79 0.00 0.00 0.00 5687.31 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 12-OCT-05:02 0.00 0.00 0.00 -6334.17 0.00 0.00 44.13 24.42 369.02 0.00 0.00 0.00 7112.24 0.00 -717.06 0.00 -498.58 0.00
PERIMETER_ZN_2 15-SEP-05:02 0.00 0.00 0.00 -4017.98 0.00 0.00 26.05 14.49 218.91 0.00 0.00 0.00 4017.74 0.00 -259.20 0.00 0.00 0.00
PERIMETER_ZN_3 15-SEP-05:02 0.00 0.00 0.00 -5551.46 0.00 0.00 44.63 24.42 369.02 0.00 0.00 0.00 5494.68 0.00 -381.30 0.00 0.00 0.00
PERIMETER_ZN_4 15-SEP-05:02 0.00 0.00 0.00 -4497.77 0.00 0.00 25.55 14.49 218.91 0.00 0.00 0.00 4503.44 0.00 -264.61 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 15-SEP-05:02 0.00 0.00 0.00 -25491.94 0.00 0.00 193.29 110.04 1662.65 0.00 0.00 1427.33 23698.90 0.00 -1391.33 0.00 -208.95 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-06:01 0.00 0.00 8234.61 0.00 0.00 0.00 88.29 32.22 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8841.91
PERIMETER_ZN_1 02-JAN-06:01 0.00 0.00 8864.01 0.00 0.00 0.00 68.19 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -481.94 0.00 -434.80 -8408.91
PERIMETER_ZN_2 02-JAN-06:01 0.00 0.00 6614.83 0.00 0.00 0.00 40.45 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -260.48 0.00 -90.17 -6538.03
PERIMETER_ZN_3 02-JAN-06:01 0.00 0.00 8680.02 0.00 0.00 0.00 68.19 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -399.24 0.00 -133.44 -8608.98
PERIMETER_ZN_4 02-JAN-06:01 0.00 0.00 7241.42 0.00 0.00 0.00 40.45 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -266.15 0.00 -90.70 -7158.42
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JAN-06:01 0.00 0.00 39634.89 0.00 0.00 0.00 305.58 110.04 1662.65 0.00 0.00 370.70 0.00 0.00 -1407.80 0.00 -749.11 -39926.95



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3061 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3061 0.2111 1.0000 Not calculated 0.0646 0.2111    
PSZ-AC:2 0.3156 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3156 0.1552 1.0000 Not calculated 0.0490 0.1552    
PSZ-AC:3 0.2374 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2374 0.1224 1.0000 Not calculated 0.0291 0.1224    
PSZ-AC:4 0.3091 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3091 0.1585 1.0000 Not calculated 0.0490 0.1585    
PSZ-AC:5 0.2738 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2738 0.1062 1.0000 Not calculated 0.0291 0.1062    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3061 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3061 1.0000 1.0000 Not calculated 0.0646 0.2111    
PSZ-AC:2 0.3156 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3156 1.0000 1.0000 Not calculated 0.0490 0.1552    
PSZ-AC:3 0.2374 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2374 1.0000 1.0000 Not calculated 0.0291 0.1224    
PSZ-AC:4 0.3091 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3091 1.0000 1.0000 Not calculated 0.0490 0.1585    
PSZ-AC:5 0.2738 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2738 1.0000 1.0000 Not calculated 0.0291 0.1062    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3061 0.3061 0.3061 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3156 0.3156 0.3156 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2374 0.2374 0.2374 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3091 0.3091 0.3091 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2738 0.2738 0.2738 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3061 0.3061 0.3061 0.3061 0.0646 1.0000
PSZ-AC:2 0.3156 0.3156 0.3156 0.3156 0.0490 1.0000
PSZ-AC:3 0.2374 0.2374 0.2374 0.2374 0.0291 1.0000
PSZ-AC:4 0.3091 0.3091 0.3091 0.3091 0.0490 1.0000
PSZ-AC:5 0.2738 0.2738 0.2738 0.2738 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3061 0.3061 0.3061 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3156 0.3156 0.3156 No 0.0490 0.2828 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2374 0.2374 0.2374 No 0.0291 0.2655 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3091 0.3091 0.3091 No 0.0490 0.2851 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2738 0.2738 0.2738 No 0.0291 0.2637 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3061 0.3061 0.3061 0.3061 0.0646 1.0000
PSZ-AC:2 0.3156 0.3156 0.3156 0.3156 0.0490 1.0000
PSZ-AC:3 0.2374 0.2374 0.2374 0.2374 0.0291 1.0000
PSZ-AC:4 0.3091 0.3091 0.3091 0.3091 0.0490 1.0000
PSZ-AC:5 0.2738 0.2738 0.2738 0.2738 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 11.83
Number of hours cooling loads not met 19.83
Number of hours not met 31.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 6.22 8440.68 1.66 25631.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 20.61 6446.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.74 2540.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 9.96 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 18.59 1615.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 24.10 2804.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 154.53
Natural Gas 0.00 1.66
Additional 0.00 0.00
Total 48.30 156.19


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 52.31
Space Heating 12.18
Space Cooling 40.33
Fans (All) 36.37
Service Water Heating 47.16
Receptacle Equipment 94.48
Miscellaneous (All) 302.31
Subtotal 302.31


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 3.25
Service Water Heating 0.00
Miscellaneous (All) 3.25
Subtotal 3.25


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 17.12
Space Heating 5.05
Space Cooling 13.20
Fans (All) 11.90
Service Water Heating 15.43
Receptacle Equipment 30.92
Miscellaneous 6.38


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2885. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365
HTGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL January 20.55 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 7759.67 1000.33 0.00 0.00 0.00
PERIMETER_ZN_1 7743.67 1012.00 4.33 0.00 0.00
PERIMETER_ZN_2 7681.67 1073.17 5.17 0.00 0.00
PERIMETER_ZN_3 7939.17 820.83 0.00 0.00 0.00
PERIMETER_ZN_4 7539.00 1213.17 7.83 0.00 0.00
ATTIC 6221.17 615.00 627.50 747.83 548.50
Min 6221.17 615.00 0.00 0.00 0.00
Max 7939.17 1213.17 627.50 747.83 548.50
Average 7480.72 955.75 107.47 124.64 91.42
Sum 44884.33 5734.50 644.83 747.83 548.50


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 6285.83 2474.17 0.00 0.00 0.00
PERIMETER_ZN_1 6668.33 2091.67 0.00 0.00 0.00
PERIMETER_ZN_2 6779.33 1980.67 0.00 0.00 0.00
PERIMETER_ZN_3 6915.00 1845.00 0.00 0.00 0.00
PERIMETER_ZN_4 6774.50 1985.33 0.17 0.00 0.00
ATTIC 5749.50 1450.33 389.00 335.17 836.00
Min 5749.50 1450.33 0.00 0.00 0.00
Max 6915.00 2474.17 389.00 335.17 836.00
Average 6528.75 1971.19 64.86 55.86 139.33
Sum 39172.50 11827.17 389.17 335.17 836.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17772.67 119.33 0.00 0.00 0.00
PERIMETER_ZN_1 12972.67 383.33 0.00 0.00 0.00
PERIMETER_ZN_2 4767.50 20.50 0.00 0.00 0.00
PERIMETER_ZN_3 13263.00 93.00 0.00 0.00 0.00
PERIMETER_ZN_4 6779.00 25.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17772.67 383.33 0.00 0.00 0.00
Average 9259.14 106.86 0.00 0.00 0.00
Sum 55554.83 641.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:28:36

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.390618E+09 1750.35 27-JAN-06:03 -6.2 -7.5 0.234865E+09 402.34 31-JAN-16:40 19.60 13.44
February 0.473522E+09 1907.54 03-FEB-06:03 -8.4 -9.9 0.229524E+09 402.35 28-FEB-15:50 23.58 12.73
March 0.954749E+09 4679.16 31-MAR-05:03 16.78 15.18 0.315976E+09 402.34 01-MAR-11:39 16.78 15.18
April 0.119595E+10 5338.73 18-APR-05:03 14.22 12.17 0.281707E+09 402.36 14-APR-13:00 14.22 12.17
May 0.191241E+10 5324.13 17-MAY-05:02 16.70 13.07 0.312789E+09 402.37 22-MAY-15:00 27.20 18.18
June 0.279321E+10 6128.05 09-JUN-05:02 13.80 9.25 0.314141E+09 402.37 22-JUN-15:30 29.75 22.28
July 0.292842E+10 5037.64 25-JUL-05:01 21.60 18.09 0.286272E+09 409.94 10-JUL-13:39 21.60 18.09
August 0.334163E+10 5178.37 28-AUG-05:01 21.60 20.47 0.329480E+09 415.60 07-AUG-14:09 21.60 20.47
September 0.249492E+10 5747.77 14-SEP-05:02 12.20 10.90 0.285272E+09 402.37 20-SEP-15:20 25.60 17.21
October 0.178435E+10 6263.62 13-OCT-05:03 6.02 4.50 0.297503E+09 402.37 10-OCT-14:09 6.02 4.50
November 0.113751E+10 4755.97 06-NOV-06:03 9.32 8.73 0.292068E+09 402.36 06-NOV-14:39 20.60 10.81
December 0.615580E+09 1636.64 18-DEC-06:03 -5.0 -6.7 0.252962E+09 402.33 14-DEC-10:00 -5.0 -6.7
                     
Annual Sum or Average 0.200229E+11         0.343256E+10        
Minimum of Months 0.390618E+09 1636.64   -8.4 -9.9 0.229524E+09 402.33   -5.0 -6.7
Maximum of Months 0.334163E+10 6263.62   21.60 20.47 0.329480E+09 415.60   29.75 22.28



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.127723E+09 957.73 26-JAN-13:15 0.00 -4.0 0.178252E+09 304.99 20-JAN-16:49 0.00 -4.0
February 0.235521E+09 2180.46 28-FEB-15:30 24.15 13.12 0.168474E+09 304.99 22-FEB-15:50 24.15 13.12
March 0.441320E+09 2743.76 30-MAR-15:00 27.80 17.08 0.223900E+09 305.37 29-MAR-09:09 27.80 17.08
April 0.491231E+09 2204.20 17-APR-15:00 28.90 16.41 0.202070E+09 305.01 18-APR-13:09 27.70 16.38
May 0.983183E+09 4356.71 19-MAY-05:02 16.60 15.60 0.233472E+09 305.02 18-MAY-14:39 16.60 15.60
June 0.214150E+10 5008.40 05-JUN-05:01 19.40 16.85 0.237868E+09 306.10 23-JUN-12:09 31.78 24.29
July 0.244342E+10 4742.85 25-JUL-05:01 21.60 18.09 0.217119E+09 322.07 07-JUL-12:09 21.60 18.09
August 0.310921E+10 4467.78 29-AUG-16:03 32.20 22.08 0.250288E+09 325.46 07-AUG-12:09 32.20 22.08
September 0.226499E+10 5778.08 15-SEP-05:02 14.90 12.38 0.216711E+09 324.41 06-SEP-12:09 14.90 12.38
October 0.156753E+10 6334.22 12-OCT-05:02 9.22 6.36 0.220701E+09 318.53 10-OCT-14:20 9.22 6.36
November 0.888540E+09 3785.16 06-NOV-14:30 20.60 10.97 0.213359E+09 305.02 01-NOV-15:20 20.60 10.97
December 0.381827E+09 2380.43 12-DEC-14:10 22.80 16.93 0.187277E+09 305.00 14-DEC-16:10 14.82 10.69
                     
Annual Sum or Average 0.150760E+11         0.254949E+10        
Minimum of Months 0.127723E+09 957.73   0.00 -4.0 0.168474E+09 304.99   0.00 -4.0
Maximum of Months 0.310921E+10 6334.22   32.20 22.08 0.250288E+09 325.46   32.20 24.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 7167691.74 528.72 27-JAN-11:05 -1.5 -4.5 73925556.75 172.78 31-JAN-16:00 19.40 13.37
February 32173786.63 1273.74 28-FEB-15:05 24.72 13.51 71449114.15 190.45 28-FEB-15:09 24.72 13.51
March 0.135631E+09 2910.10 14-MAR-10:02 18.27 14.61 97458893.48 190.45 30-MAR-14:09 27.80 17.74
April 0.313691E+09 3691.94 13-APR-10:01 21.65 16.12 90148254.40 190.45 14-APR-14:09 27.20 15.51
May 0.754825E+09 3686.72 17-MAY-10:01 24.68 17.49 0.102790E+09 190.45 09-MAY-14:09 24.68 17.49
June 0.148506E+10 3651.08 05-JUN-05:01 19.40 16.85 0.104358E+09 190.45 08-JUN-14:09 24.18 13.63
July 0.166964E+10 3613.10 10-JUL-09:04 25.87 20.98 95206674.20 190.45 19-JUL-14:09 29.60 23.18
August 0.193428E+10 3594.63 25-AUG-10:01 27.98 18.71 0.109541E+09 190.45 07-AUG-10:09 27.98 18.71
September 0.132918E+10 4018.14 15-SEP-05:02 14.90 12.38 94671238.45 190.45 14-SEP-14:09 14.90 12.38
October 0.704032E+09 3877.41 12-OCT-10:02 15.47 10.28 96668846.58 190.45 12-OCT-14:09 20.60 11.91
November 0.275203E+09 2998.88 08-NOV-11:02 15.47 7.99 92048621.77 190.45 06-NOV-15:09 15.47 7.99
December 63297730.71 1305.01 12-DEC-15:03 22.70 16.14 77255056.09 190.45 13-DEC-15:09 18.12 16.87
                     
Annual Sum or Average 0.870418E+10         0.110552E+10        
Minimum of Months 7167691.74 528.72   -1.5 -4.5 71449114.15 172.78   14.90 7.99
Maximum of Months 0.193428E+10 4018.14   27.98 20.98 0.109541E+09 190.45   29.60 23.18



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 8510329.97 682.86 25-JAN-06:05 4.40 3.91 0.170719E+09 287.88 20-JAN-16:00 4.40 3.91
February 34262463.04 752.06 02-FEB-16:12 1.13 -2.4 0.161188E+09 304.99 27-FEB-16:00 22.20 11.44
March 0.193452E+09 1476.85 30-MAR-15:57 27.80 17.47 0.216574E+09 304.99 30-MAR-14:00 27.80 17.47
April 0.354558E+09 1584.07 19-APR-14:55 26.70 17.60 0.202688E+09 306.96 27-APR-13:20 20.97 11.53
May 0.986054E+09 4773.37 19-MAY-05:02 16.60 15.60 0.234925E+09 305.02 18-MAY-14:39 16.60 15.60
June 0.204482E+10 4945.36 05-JUN-05:01 19.40 16.85 0.238103E+09 305.03 29-JUN-15:00 31.10 23.22
July 0.232103E+10 4767.65 25-JUL-05:01 21.60 18.09 0.216996E+09 305.03 19-JUL-14:00 21.60 18.09
August 0.276152E+10 4166.49 14-AUG-05:01 23.30 20.62 0.249585E+09 305.03 21-AUG-09:39 23.70 22.62
September 0.181302E+10 5551.77 15-SEP-05:02 14.90 12.38 0.216018E+09 305.03 08-SEP-12:39 14.90 12.38
October 0.922321E+09 4344.46 11-OCT-05:01 18.72 16.68 0.220365E+09 305.01 03-OCT-13:09 18.72 16.68
November 0.414881E+09 1355.57 03-NOV-15:00 21.70 17.40 0.206289E+09 305.01 06-NOV-14:09 20.60 11.29
December 0.122169E+09 1115.26 01-DEC-06:05 -3.9 -4.8 0.172925E+09 304.99 14-DEC-16:10 14.82 10.69
                     
Annual Sum or Average 0.119766E+11         0.250638E+10        
Minimum of Months 8510329.97 682.86   -3.9 -4.8 0.161188E+09 287.88   4.40 3.91
Maximum of Months 0.276152E+10 5551.77   27.80 20.62 0.249585E+09 306.96   31.10 23.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 21736496.03 432.69 25-JAN-06:04 4.40 3.91 0.102379E+09 181.00 20-JAN-16:49 4.40 3.91
February 37882058.87 914.84 28-FEB-16:33 23.70 12.80 97621023.08 180.94 28-FEB-11:00 23.70 12.80
March 0.167730E+09 1578.40 30-MAR-15:57 27.80 17.47 0.132430E+09 182.04 28-MAR-12:20 27.80 17.47
April 0.293256E+09 1660.05 17-APR-15:57 28.90 16.41 0.122420E+09 183.72 07-APR-14:20 28.90 16.41
May 0.710126E+09 4017.90 19-MAY-05:02 16.60 15.60 0.140346E+09 180.95 02-MAY-08:20 16.60 15.60
June 0.140112E+10 4043.25 05-JUN-05:01 19.40 16.85 0.141910E+09 180.95 23-JUN-15:00 30.60 23.74
July 0.159196E+10 3932.17 25-JUL-05:01 21.60 18.09 0.129323E+09 180.95 06-JUL-13:09 21.60 18.09
August 0.191932E+10 3716.05 14-AUG-05:01 23.30 20.62 0.148760E+09 180.95 15-AUG-13:50 29.90 23.61
September 0.130248E+10 4497.93 15-SEP-05:02 14.90 12.38 0.128736E+09 180.95 06-SEP-13:00 14.90 12.38
October 0.703826E+09 3817.49 10-OCT-05:01 15.92 14.94 0.131921E+09 180.94 11-OCT-14:00 27.20 20.13
November 0.315242E+09 1591.66 06-NOV-16:25 19.75 10.05 0.125625E+09 180.93 10-NOV-14:00 18.90 12.39
December 69891345.54 552.40 13-DEC-15:30 17.75 16.89 0.106207E+09 180.93 14-DEC-16:10 14.82 10.69
                     
Annual Sum or Average 0.853456E+10         0.150768E+10        
Minimum of Months 21736496.03 432.69   4.40 3.91 97621023.08 180.93   4.40 3.91
Maximum of Months 0.191932E+10 4497.93   28.90 20.62 0.148760E+09 183.72   30.60 23.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70 4.97 0.00 0.00 01-JAN-00:10 5.70 4.97
February 0.00 0.00 01-FEB-00:10 9.92 7.50 0.00 0.00 01-FEB-00:10 9.92 7.50
March 0.00 0.00 01-MAR-00:10 15.32 8.51 0.00 0.00 01-MAR-00:10 15.32 8.51
April 0.00 0.00 01-APR-00:10 12.05 7.82 0.00 0.00 01-APR-00:10 12.05 7.82
May 0.00 0.00 01-MAY-00:10 16.68 16.68 0.00 0.00 01-MAY-00:10 16.68 16.68
June 0.00 0.00 01-JUN-00:10 20.93 18.59 0.00 0.00 01-JUN-00:10 20.93 18.59
July 0.00 0.00 01-JUL-00:10 22.28 21.38 0.00 0.00 01-JUL-00:10 22.28 21.38
August 0.00 0.00 01-AUG-00:10 25.13 21.87 0.00 0.00 01-AUG-00:10 25.13 21.87
September 0.00 0.00 01-SEP-00:10 21.40 18.46 0.00 0.00 01-SEP-00:10 21.40 18.46
October 0.00 0.00 01-OCT-00:10 16.85 15.92 0.00 0.00 01-OCT-00:10 16.85 15.92
November 0.00 0.00 01-NOV-00:10 9.70 6.60 0.00 0.00 01-NOV-00:10 9.70 6.60
December 0.00 0.00 01-DEC-00:10 1.80 1.51 0.00 0.00 01-DEC-00:10 1.80 1.51
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   1.80 1.51 0.00 0.00   1.80 1.51
Maximum of Months 0.00 0.00   25.13 21.87 0.00 0.00   25.13 21.87



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.336960E+09 8234.66 02-JAN-06:01 3.30
February 0.125048E+09 7363.42 07-FEB-06:01 2.20
March 6239571.93 482.18 30-MAR-17:03 26.60
April 14315572.15 575.30 17-APR-17:03 28.03
May 22549198.65 746.70 19-MAY-17:02 30.40
June 43673645.84 995.04 06-JUN-17:02 33.72
July 44444821.43 1087.08 07-JUL-17:01 34.82
August 48657740.56 1073.59 01-AUG-17:02 34.72
September 21456294.49 756.73 07-SEP-17:02 30.50
October 5663287.16 598.01 10-OCT-17:02 28.43
November 619339.79 178.02 27-NOV-18:10 21.60
December 28803161.97 7367.58 26-DEC-06:01 3.30
         
Annual Sum or Average 0.698430E+09      
Minimum of Months 619339.79 178.02   2.20
Maximum of Months 0.336960E+09 8234.66   34.82



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.152583E+10 8864.09 02-JAN-06:01 3.30
February 0.935343E+09 8638.70 06-FEB-06:01 0.50
March 0.245481E+09 7299.88 06-MAR-06:01 3.22
April 0.143588E+09 7334.80 06-APR-05:02 0.18
May 39405184.16 1310.97 11-MAY-06:10 8.17
June 38989653.26 789.37 06-JUN-17:02 33.72
July 37241889.21 845.57 07-JUL-17:01 34.82
August 40288537.88 832.54 01-AUG-17:11 34.43
September 19213137.97 601.62 08-SEP-17:11 30.03
October 31006590.37 2460.31 26-OCT-06:50 2.20
November 0.112101E+09 7274.28 22-NOV-06:01 -3.3
December 0.447030E+09 8416.24 26-DEC-06:01 3.30
         
Annual Sum or Average 0.361552E+10      
Minimum of Months 19213137.97 601.62   -3.3
Maximum of Months 0.152583E+10 8864.09   34.82



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.852109E+09 6614.87 02-JAN-06:01 3.30
February 0.505456E+09 6388.80 07-FEB-06:01 2.20
March 87224714.98 5707.55 06-MAR-06:01 3.22
April 32693021.79 5406.17 07-APR-05:02 3.22
May 19496446.01 425.86 19-MAY-17:12 30.20
June 25743103.13 501.81 06-JUN-17:23 33.35
July 24836238.63 547.55 13-JUL-17:11 34.23
August 27558369.62 553.25 01-AUG-17:11 34.43
September 14866664.94 414.48 08-SEP-17:11 30.03
October 6046515.15 321.52 10-OCT-17:02 28.43
November 19457311.34 5073.44 21-NOV-06:02 -2.8
December 0.205167E+09 6378.98 26-DEC-06:01 3.30
         
Annual Sum or Average 0.182065E+10      
Minimum of Months 6046515.15 321.52   -2.8
Maximum of Months 0.852109E+09 6614.87   34.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.161392E+10 8680.07 02-JAN-06:01 3.30
February 0.990262E+09 8620.24 06-FEB-06:01 0.50
March 0.180140E+09 7513.52 06-MAR-06:01 3.22
April 70640231.01 7190.36 06-APR-05:02 0.18
May 24656317.44 636.89 19-MAY-17:12 30.20
June 38077772.71 793.35 06-JUN-17:02 33.72
July 37333703.53 859.47 07-JUL-17:01 34.82
August 41075974.18 852.15 01-AUG-17:11 34.43
September 20622721.35 614.94 08-SEP-17:11 30.03
October 7235577.09 515.86 10-OCT-17:02 28.43
November 45387789.55 7509.56 22-NOV-06:01 -3.3
December 0.459832E+09 8313.34 26-DEC-06:01 3.30
         
Annual Sum or Average 0.352918E+10      
Minimum of Months 7235577.09 515.86   -3.3
Maximum of Months 0.161392E+10 8680.07   34.82



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.894970E+09 7241.47 02-JAN-06:01 3.30
February 0.546100E+09 7002.46 07-FEB-06:01 2.20
March 92813161.27 6396.55 06-MAR-06:01 3.22
April 40412457.44 6108.47 07-APR-05:02 3.22
May 20740133.51 429.41 19-MAY-17:12 30.20
June 25615881.06 514.81 06-JUN-17:23 33.35
July 24967348.25 563.13 13-JUL-17:11 34.23
August 27517491.73 564.61 01-AUG-17:11 34.43
September 14925149.63 419.31 08-SEP-17:11 30.03
October 6465055.31 295.26 10-OCT-17:02 28.43
November 24629783.21 5380.33 22-NOV-06:01 -3.3
December 0.234833E+09 7193.92 26-DEC-06:01 3.30
         
Annual Sum or Average 0.195399E+10      
Minimum of Months 6465055.31 295.26   -3.3
Maximum of Months 0.894970E+09 7241.47   34.43



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:10 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:10 25.13
September 0.00 0.00 01-SEP-00:10 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.729889E+09 743.94 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.660244E+09 743.94 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.791184E+09 743.94 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.696458E+09 743.94 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.760537E+09 743.94 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.757753E+09 743.94 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.699242E+09 743.94 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.791184E+09 743.94 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.696458E+09 743.94 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.729889E+09 743.94 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.727106E+09 743.94 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.699242E+09 743.94 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.873919E+10     0.141401E+11    
Minimum of Months 0.660244E+09 743.94   0.107295E+10 973.59  
Maximum of Months 0.791184E+09 743.94   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.463108E+09 555.48 03-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.422088E+09 561.66 01-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.489473E+09 557.19 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.430162E+09 549.90 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.466678E+09 530.86 24-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.464519E+09 526.54 23-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.430371E+09 537.26 27-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.482028E+09 547.03 24-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.432349E+09 552.26 29-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.457415E+09 563.75 30-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.456265E+09 562.18 01-NOV-07:10 0.888667E+09 738.04 01-NOV-07:10
December 0.442377E+09 555.60 06-DEC-08:09 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.543683E+10     0.107191E+11    
Minimum of Months 0.422088E+09 526.54   0.813362E+09 738.04  
Maximum of Months 0.489473E+09 563.75   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.291426E+09 329.58 03-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.261460E+09 333.26 01-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.301998E+09 330.48 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.262505E+09 325.42 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.281760E+09 306.47 02-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.278721E+09 305.08 23-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.258455E+09 315.53 27-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.292206E+09 323.47 24-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.264378E+09 327.47 29-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.285651E+09 334.43 30-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.286209E+09 333.46 01-NOV-07:10 0.527169E+09 437.82 01-NOV-07:10
December 0.277245E+09 329.69 06-DEC-08:09 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.334201E+10     0.635872E+10    
Minimum of Months 0.258455E+09 305.08   0.482497E+09 437.82  
Maximum of Months 0.301998E+09 334.43   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.518802E+09 557.20 03-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.465683E+09 561.82 01-FEB-08:09 0.813362E+09 738.04 01-FEB-08:09
March 0.537651E+09 557.81 21-MAR-07:10 0.953087E+09 738.04 01-MAR-08:09
April 0.460627E+09 550.76 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.478813E+09 528.03 24-MAY-07:10 0.926320E+09 738.04 01-MAY-07:10
June 0.466785E+09 523.67 23-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.433451E+09 536.20 27-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.499799E+09 547.58 24-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.467947E+09 553.82 29-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.510796E+09 563.77 30-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.513119E+09 562.77 01-NOV-07:10 0.888667E+09 738.04 01-NOV-07:10
December 0.498626E+09 557.39 06-DEC-08:09 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.585210E+10     0.107191E+11    
Minimum of Months 0.433451E+09 523.67   0.813362E+09 738.04  
Maximum of Months 0.537651E+09 563.77   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.289807E+09 330.61 03-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.262975E+09 333.26 01-FEB-08:09 0.482497E+09 437.82 01-FEB-08:09
March 0.303801E+09 331.09 21-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.265536E+09 327.73 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.285384E+09 322.18 24-MAY-07:30 0.549505E+09 437.82 01-MAY-07:10
June 0.282531E+09 316.87 23-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.262359E+09 321.62 27-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.296138E+09 326.12 24-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.267793E+09 328.88 29-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.288296E+09 334.43 30-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.285712E+09 333.89 01-NOV-07:10 0.527169E+09 437.82 01-NOV-07:10
December 0.278239E+09 330.68 06-DEC-08:09 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.336857E+10     0.635872E+10    
Minimum of Months 0.262359E+09 316.87   0.482497E+09 437.82  
Maximum of Months 0.303801E+09 334.43   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.729889E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.696458E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.760537E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.757753E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.699242E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.696458E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.729889E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.727106E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.699242E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.873919E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.463108E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.129280E+10
February 0.488155E+09 0.422088E+09 0.813362E+09 0.00 0.00 0.00 0.00 190328.85 0.976934E+09
March 0.590925E+09 0.489473E+09 0.953087E+09 0.00 0.00 0.00 0.00 5747103.98 0.681400E+09
April 0.513848E+09 0.430162E+09 0.862580E+09 0.00 0.00 0.00 0.00 30840995.56 0.386134E+09
May 0.565233E+09 0.466678E+09 0.926320E+09 0.00 0.00 0.00 0.00 72394324.42 0.233440E+09
June 0.565233E+09 0.464519E+09 0.914754E+09 0.00 0.00 0.00 0.00 0.209684E+09 0.106332E+09
July 0.513848E+09 0.430371E+09 0.873466E+09 0.00 0.00 0.00 0.00 0.216417E+09 77242459.38
August 0.590925E+09 0.482028E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.237991E+09 51363109.30
September 0.513848E+09 0.432349E+09 0.861220E+09 0.00 0.00 0.00 0.00 79988208.41 0.161196E+09
October 0.539540E+09 0.457415E+09 0.900233E+09 0.00 0.00 0.00 0.00 15408432.61 0.550487E+09
November 0.539540E+09 0.456265E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.806598E+09
December 0.513848E+09 0.442377E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.103092E+10
                   
Annual Sum or Average 0.647448E+10 0.543683E+10 0.107191E+11 0.00 0.00 0.00 0.00 0.868662E+09 0.635484E+10
Minimum of Months 0.488155E+09 0.422088E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 51363109.30
Maximum of Months 0.590925E+09 0.489473E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.237991E+09 0.129280E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.291426E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.259195E+09
February 0.211974E+09 0.261460E+09 0.482497E+09 0.00 0.00 0.00 0.00 388636.53 0.217328E+09
March 0.256600E+09 0.301998E+09 0.565383E+09 0.00 0.00 0.00 0.00 687858.07 0.141247E+09
April 0.223130E+09 0.262505E+09 0.511694E+09 0.00 0.00 0.00 0.00 1968248.15 84963759.88
May 0.245443E+09 0.281760E+09 0.549505E+09 0.00 0.00 0.00 0.00 3437926.99 60262290.52
June 0.245443E+09 0.278721E+09 0.542644E+09 0.00 0.00 0.00 0.00 14263638.81 34290792.19
July 0.223130E+09 0.258455E+09 0.518151E+09 0.00 0.00 0.00 0.00 12645198.90 26393116.51
August 0.256600E+09 0.292206E+09 0.565383E+09 0.00 0.00 0.00 0.00 12374000.20 20394081.62
September 0.223130E+09 0.264378E+09 0.510887E+09 0.00 0.00 0.00 0.00 3031116.85 39843952.13
October 0.234287E+09 0.285651E+09 0.534030E+09 0.00 0.00 0.00 0.00 713177.29 0.121217E+09
November 0.234287E+09 0.286209E+09 0.527169E+09 0.00 0.00 0.00 0.00 100436.98 0.165325E+09
December 0.223130E+09 0.277245E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.246825E+09
                   
Annual Sum or Average 0.281144E+10 0.334201E+10 0.635872E+10 0.00 0.00 0.00 0.00 49610238.77 0.141728E+10
Minimum of Months 0.211974E+09 0.258455E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 20394081.62
Maximum of Months 0.256600E+09 0.301998E+09 0.565383E+09 0.00 0.00 0.00 0.00 14263638.81 0.259195E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.518802E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.385777E+09
February 0.488155E+09 0.465683E+09 0.813362E+09 0.00 0.00 0.00 0.00 1321795.04 0.321018E+09
March 0.590925E+09 0.537651E+09 0.953087E+09 0.00 0.00 0.00 0.00 1309068.03 0.202275E+09
April 0.513848E+09 0.460627E+09 0.862580E+09 0.00 0.00 0.00 0.00 3778838.37 0.122754E+09
May 0.565233E+09 0.478813E+09 0.926320E+09 0.00 0.00 0.00 0.00 6874162.96 85578671.41
June 0.565233E+09 0.466785E+09 0.914754E+09 0.00 0.00 0.00 0.00 23899270.12 48834378.26
July 0.513848E+09 0.433451E+09 0.873466E+09 0.00 0.00 0.00 0.00 21945677.12 36246385.89
August 0.590925E+09 0.499799E+09 0.953087E+09 0.00 0.00 0.00 0.00 21289131.44 27483523.33
September 0.513848E+09 0.467947E+09 0.861220E+09 0.00 0.00 0.00 0.00 5710442.90 56917280.94
October 0.539540E+09 0.510796E+09 0.900233E+09 0.00 0.00 0.00 0.00 1671577.64 0.174181E+09
November 0.539540E+09 0.513119E+09 0.888667E+09 0.00 0.00 0.00 0.00 271308.72 0.238394E+09
December 0.513848E+09 0.498626E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.363838E+09
                   
Annual Sum or Average 0.647448E+10 0.585210E+10 0.107191E+11 0.00 0.00 0.00 0.00 88071272.35 0.206330E+10
Minimum of Months 0.488155E+09 0.433451E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 27483523.33
Maximum of Months 0.590925E+09 0.537651E+09 0.953087E+09 0.00 0.00 0.00 0.00 23899270.12 0.385777E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.289807E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.261456E+09
February 0.289580E+09 0.262975E+09 0.482497E+09 0.00 0.00 0.00 0.00 595075.10 0.218775E+09
March 0.350544E+09 0.303801E+09 0.565383E+09 0.00 0.00 0.00 0.00 482492.57 0.146219E+09
April 0.304821E+09 0.265536E+09 0.511694E+09 0.00 0.00 0.00 0.00 1898274.09 88695728.36
May 0.335303E+09 0.285384E+09 0.549505E+09 0.00 0.00 0.00 0.00 3561510.29 62123473.65
June 0.335303E+09 0.282531E+09 0.542644E+09 0.00 0.00 0.00 0.00 13737407.28 36001736.73
July 0.304821E+09 0.262359E+09 0.518151E+09 0.00 0.00 0.00 0.00 12218182.03 26554629.65
August 0.350544E+09 0.296138E+09 0.565383E+09 0.00 0.00 0.00 0.00 11551771.79 22431784.59
September 0.304821E+09 0.267793E+09 0.510887E+09 0.00 0.00 0.00 0.00 3193565.95 41461524.59
October 0.320062E+09 0.288296E+09 0.534030E+09 0.00 0.00 0.00 0.00 740989.01 0.123212E+09
November 0.320062E+09 0.285712E+09 0.527169E+09 0.00 0.00 0.00 0.00 32711.88 0.166363E+09
December 0.304821E+09 0.278239E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.247906E+09
                   
Annual Sum or Average 0.384075E+10 0.336857E+10 0.635872E+10 0.00 0.00 0.00 0.00 48011979.99 0.144120E+10
Minimum of Months 0.289580E+09 0.262359E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 22431784.59
Maximum of Months 0.350544E+09 0.303801E+09 0.565383E+09 0.00 0.00 0.00 0.00 13737407.28 0.261456E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.939932E+09 0.214796E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.819860E+09 0.219774E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.872238E+09 0.340625E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.769869E+09 0.410258E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.634224E+09 0.473726E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.647702E+09 0.459819E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.638135E+09 0.460784E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.709968E+09 0.428446E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.877229E+09 0.300869E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.822276E+09 0.275841E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.963597E+09 0.201919E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.977856E+09 0.178254E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.967289E+10 0.396511E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.634224E+09 0.178254E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.977856E+09 0.473726E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 743.94 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 743.94 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 743.94 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 743.94 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 743.94 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 743.94 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 743.94 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 743.94 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 743.94 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 743.94 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 743.94 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 743.94 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 555.48 03-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4813.33 27-JAN-07:50
February 732.70 01-FEB-08:09 561.66 01-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 32.84 28-FEB-15:00 5164.12 03-FEB-07:05
March 732.70 01-MAR-08:09 557.19 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 570.69 30-MAR-16:10 3045.27 06-MAR-07:55
April 732.70 03-APR-07:10 549.90 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 732.56 17-APR-16:10 3318.78 06-APR-06:10
May 732.70 01-MAY-07:10 530.86 24-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 1010.75 19-MAY-16:03 2095.87 11-MAY-06:10
June 732.70 01-JUN-07:10 526.54 23-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 1492.31 06-JUN-17:00 1678.91 08-JUN-06:05
July 732.70 03-JUL-07:10 537.26 27-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 1687.98 07-JUL-16:03 807.53 03-JUL-06:05
August 732.70 01-AUG-07:10 547.03 24-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 1624.43 01-AUG-16:05 852.66 25-AUG-06:10
September 732.70 01-SEP-07:10 552.26 29-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 1105.64 07-SEP-16:03 1776.96 14-SEP-06:05
October 732.70 02-OCT-07:10 563.75 30-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 848.49 10-OCT-16:03 3133.13 26-OCT-06:10
November 732.70 01-NOV-07:10 562.18 01-NOV-07:10 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4113.01 22-NOV-07:10
December 732.70 01-DEC-08:09 555.60 06-DEC-08:09 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4555.72 18-DEC-08:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   526.54   738.04   0.00 0.00 0.00 0.00 0.00   807.53  
Maximum of Months 732.70   563.75   738.04   0.00 0.00 0.00 0.00 1687.98   5164.12  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 329.58 03-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 422.95 07-JAN-18:10
February 434.65 01-FEB-08:09 333.26 01-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 21.45 26-FEB-12:55 539.83 12-FEB-00:53
March 434.65 01-MAR-08:09 330.48 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 15.97 11-MAR-15:53 356.97 22-MAR-05:05
April 434.65 03-APR-07:10 325.42 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 31.06 02-APR-17:00 206.82 05-APR-18:03
May 434.65 01-MAY-07:10 306.47 02-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 28.91 19-MAY-18:10 148.36 10-MAY-04:00
June 434.65 01-JUN-07:10 305.08 23-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 77.01 06-JUN-18:10 115.90 07-JUN-03:00
July 434.65 03-JUL-07:10 315.53 27-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 45.51 21-JUL-18:10 91.58 28-JUL-18:05
August 434.65 01-AUG-07:10 323.47 24-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 53.98 18-AUG-18:10 67.12 07-AUG-21:00
September 434.65 01-SEP-07:10 327.47 29-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 20.03 06-SEP-12:10 112.98 28-SEP-18:05
October 434.65 02-OCT-07:10 334.43 30-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 10.83 11-OCT-14:10 232.65 24-OCT-06:00
November 434.65 01-NOV-07:10 333.46 01-NOV-07:10 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 22.90 19-NOV-14:55 323.98 07-NOV-02:00
December 434.65 01-DEC-08:09 329.69 06-DEC-08:09 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 510.67 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   305.08   437.82   0.00 0.00 0.00 0.00 0.00   67.12  
Maximum of Months 434.65   334.43   437.82   0.00 0.00 0.00 0.00 77.01   539.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 557.20 03-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 634.99 07-JAN-18:20
February 732.70 01-FEB-08:09 561.82 01-FEB-08:09 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 71.69 26-FEB-12:55 819.27 12-FEB-01:00
March 732.70 01-MAR-08:09 557.81 21-MAR-07:10 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 29.06 11-MAR-15:53 532.35 22-MAR-05:10
April 732.70 03-APR-07:10 550.76 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 53.40 16-APR-11:53 304.99 05-APR-18:10
May 732.70 01-MAY-07:10 528.03 24-MAY-07:10 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 47.83 19-MAY-18:10 220.66 10-MAY-04:00
June 732.70 01-JUN-07:10 523.67 23-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 122.19 06-JUN-18:10 170.69 07-JUN-03:00
July 732.70 03-JUL-07:10 536.20 27-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 72.85 15-JUL-17:03 134.94 28-JUL-18:05
August 732.70 01-AUG-07:10 547.58 24-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 93.71 06-AUG-13:53 92.14 07-AUG-21:00
September 732.70 01-SEP-07:10 553.82 29-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 30.51 06-SEP-11:53 165.98 29-SEP-05:00
October 732.70 02-OCT-07:10 563.77 30-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 36.87 08-OCT-14:00 343.23 24-OCT-06:00
November 732.70 01-NOV-07:10 562.77 01-NOV-07:10 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 45.64 19-NOV-14:55 478.29 07-NOV-02:00
December 732.70 01-DEC-08:09 557.39 06-DEC-08:09 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 764.24 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   523.67   738.04   0.00 0.00 0.00 0.00 0.00   92.14  
Maximum of Months 732.70   563.77   738.04   0.00 0.00 0.00 0.00 122.19   819.27  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 330.61 03-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 423.19 07-JAN-18:20
February 434.65 01-FEB-08:09 333.26 01-FEB-08:09 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 41.80 26-FEB-12:55 546.18 12-FEB-01:00
March 434.65 01-MAR-08:09 331.09 21-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 13.88 30-MAR-16:00 354.90 22-MAR-05:10
April 434.65 03-APR-07:10 327.73 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 31.12 16-APR-11:53 226.16 05-APR-18:03
May 434.65 01-MAY-07:10 322.18 24-MAY-07:30 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 28.51 07-MAY-11:55 151.16 10-MAY-04:00
June 434.65 01-JUN-07:10 316.87 23-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 71.30 11-JUN-14:55 117.99 07-JUN-03:00
July 434.65 03-JUL-07:10 321.62 27-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 35.55 15-JUL-17:03 94.22 28-JUL-18:05
August 434.65 01-AUG-07:10 326.12 24-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 57.65 06-AUG-13:53 64.84 07-AUG-21:00
September 434.65 01-SEP-07:10 328.88 29-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 20.34 06-SEP-12:00 114.65 28-SEP-18:05
October 434.65 02-OCT-07:10 334.43 30-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 12.72 08-OCT-14:00 237.22 24-OCT-06:00
November 434.65 01-NOV-07:10 333.89 01-NOV-07:10 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 13.76 19-NOV-14:55 327.76 07-NOV-02:00
December 434.65 01-DEC-08:09 330.68 06-DEC-08:09 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 508.14 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   316.87   437.82   0.00 0.00 0.00 0.00 0.00   64.84  
Maximum of Months 434.65   334.43   437.82   0.00 0.00 0.00 0.00 71.30   546.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1772.89 29-JAN-06:55 5125.86 10-JAN-13:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1440.40 09-FEB-08:32 5866.62 12-FEB-13:50
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1634.01 19-MAR-07:23 6399.49 19-MAR-13:40
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1513.77 10-APR-06:20 7031.80 09-APR-14:20
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1346.12 20-MAY-05:50 6940.11 10-MAY-14:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1619.84 11-JUN-06:03 6352.26 02-JUN-13:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1254.03 05-JUL-03:00 6551.23 12-JUL-14:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1295.08 10-AUG-05:10 7173.65 04-AUG-14:52
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1505.87 15-SEP-07:03 6177.98 15-SEP-13:20
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1651.14 14-OCT-07:23 5356.70 13-OCT-13:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1649.86 23-NOV-07:30 4547.74 21-NOV-13:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1692.48 10-DEC-08:42 4168.68 17-DEC-13:40
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1254.03   4168.68  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1772.89   7173.65  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1750.35 27-JAN-06:03 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
February 1907.54 03-FEB-06:03 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
March 4679.16 31-MAR-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
April 5338.73 18-APR-05:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
May 5324.13 17-MAY-05:02 531.60 161.09 2433.97 0.00 0.00 0.00 0.00 0.00 0.00
June 6128.05 09-JUN-05:02 637.92 193.31 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
July 5037.64 25-JUL-05:01 850.55 257.74 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
August 5178.37 28-AUG-05:01 956.87 289.96 4381.15 0.00 0.00 0.00 0.00 0.00 0.00
September 5747.77 14-SEP-05:02 637.92 193.31 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
October 6263.62 13-OCT-05:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
November 4755.97 06-NOV-06:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
December 1636.64 18-DEC-06:03 1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1636.64   318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6263.62   1063.19 322.18 4867.94 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 957.73 26-JAN-13:15 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 0.00 592.09
February 2180.46 28-FEB-15:30 732.70 411.63 738.04 0.00 0.00 0.00 0.00 7.36 0.00
March 2743.76 30-MAR-15:00 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 102.58 0.00
April 2204.20 17-APR-15:00 1465.40 830.87 1476.09 0.00 0.00 0.00 0.00 118.13 0.00
May 4356.71 19-MAY-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 162.85
June 5008.40 05-JUN-05:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 164.47
July 4742.85 25-JUL-05:01 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 134.76
August 4467.78 29-AUG-16:03 703.39 836.98 1107.06 0.00 0.00 0.00 0.00 1257.97 0.00
September 5778.08 15-SEP-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 208.95
October 6334.22 12-OCT-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 498.58
November 3785.16 06-NOV-14:30 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 94.00
December 2380.43 12-DEC-14:10 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 28.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 957.73   483.58 146.54 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6334.22   1465.40 836.98 2952.17 0.00 0.00 0.00 0.00 1257.97 592.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 528.72 27-JAN-11:05 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 71.83
February 1273.74 28-FEB-15:05 869.29 539.70 875.63 0.00 0.00 0.00 0.00 3.83 0.00
March 2910.10 14-MAR-10:02 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 13.05
April 3691.94 13-APR-10:01 3042.52 1709.29 3064.72 0.00 0.00 0.00 0.00 0.00 3.39
May 3686.72 17-MAY-10:01 3042.52 1709.29 3064.72 0.00 0.00 0.00 0.00 0.99 0.00
June 3651.08 05-JUN-05:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 26.77
July 3613.10 10-JUL-09:04 0.00 1220.92 2189.08 0.00 0.00 0.00 0.00 2.27 0.00
August 3594.63 25-AUG-10:01 3042.52 1709.29 3064.72 0.00 0.00 0.00 0.00 5.42 0.00
September 4018.14 15-SEP-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 0.00
October 3877.41 12-OCT-10:02 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 20.50
November 2998.88 08-NOV-11:02 2607.88 1481.91 2626.90 0.00 0.00 0.00 0.00 0.00 9.19
December 1305.01 12-DEC-15:03 1303.94 911.09 1313.45 0.00 0.00 0.00 0.00 0.00 3.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 528.72   0.00 86.93 875.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4018.14   3042.52 1709.29 3064.72 0.00 0.00 0.00 0.00 5.42 71.83



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 682.86 25-JAN-06:05 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 107.98
February 752.06 02-FEB-16:12 2930.79 2050.40 2952.17 0.00 0.00 0.00 0.00 0.00 150.21
March 1476.85 30-MAR-15:57 2198.10 1422.01 2214.13 0.00 0.00 0.00 0.00 20.82 0.00
April 1584.07 19-APR-14:55 1465.40 906.40 1476.09 0.00 0.00 0.00 0.00 13.00 0.00
May 4773.37 19-MAY-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 0.00
June 4945.36 05-JUN-05:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 37.94
July 4767.65 25-JUL-05:01 644.77 195.39 2952.17 0.00 0.00 0.00 0.00 0.00 45.76
August 4166.49 14-AUG-05:01 805.97 244.23 3690.21 0.00 0.00 0.00 0.00 0.00 44.47
September 5551.77 15-SEP-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 0.00
October 4344.46 11-OCT-05:01 564.18 170.96 2583.15 0.00 0.00 0.00 0.00 0.00 70.20
November 1355.57 03-NOV-15:00 732.70 505.38 738.04 0.00 0.00 0.00 0.00 0.00 6.00
December 1115.26 01-DEC-06:05 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 307.44
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 682.86   483.58 146.54 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5551.77   2930.79 2050.40 3690.21 0.00 0.00 0.00 0.00 20.82 307.44



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 432.69 25-JAN-06:04 382.49 115.91 1751.27 0.00 0.00 0.00 0.00 0.00 73.08
February 914.84 28-FEB-16:33 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 0.75
March 1578.40 30-MAR-15:57 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 13.88 0.00
April 1660.05 17-APR-15:57 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 5.18 0.00
May 4017.90 19-MAY-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 0.00
June 4043.25 05-JUN-05:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 26.23
July 3932.17 25-JUL-05:01 382.49 115.91 1751.27 0.00 0.00 0.00 0.00 0.00 32.70
August 3716.05 14-AUG-05:01 478.11 144.88 2189.08 0.00 0.00 0.00 0.00 0.00 33.50
September 4497.93 15-SEP-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 0.00
October 3817.49 10-OCT-05:01 334.68 101.42 1532.36 0.00 0.00 0.00 0.00 0.00 54.54
November 1591.66 06-NOV-16:25 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 16.62
December 552.40 13-DEC-15:30 434.65 288.08 437.82 0.00 0.00 0.00 0.00 0.00 8.98
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 432.69   286.87 86.93 437.82 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4497.93   1738.59 976.74 2189.08 0.00 0.00 0.00 0.00 13.88 73.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 519.27 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 79.49 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 419.25 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 998.69 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 149.11 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 732.44 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 706.88 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 635.54 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 149.25 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 236.54 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1034.97 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.28
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1034.97 42.28



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.141341E+11 18328.75 09-JAN-08:09 0.852411E+09 25076.86 09-JAN-06:19
February 0.117124E+11 17774.55 06-FEB-08:39 0.604275E+09 25631.74 13-FEB-06:19
March 0.120632E+11 12915.70 30-MAR-15:39 1532049.97 2553.42 06-MAR-06:10
April 0.110940E+11 12780.60 17-APR-14:50 6817009.04 3726.97 06-APR-05:10
May 0.126291E+11 13924.34 30-MAY-14:39 0.00 0.00 01-MAY-00:10
June 0.141590E+11 15444.71 26-JUN-14:30 0.00 0.00 01-JUN-00:10
July 0.140933E+11 16188.53 07-JUL-12:09 0.00 0.00 01-JUL-00:10
August 0.159056E+11 16230.45 07-AUG-15:20 0.00 0.00 01-AUG-00:10
September 0.131667E+11 15689.80 07-SEP-15:30 0.00 0.00 01-SEP-00:10
October 0.123236E+11 14658.71 10-OCT-14:00 0.00 0.00 01-OCT-00:10
November 0.115174E+11 13376.51 22-NOV-07:10 24007087.86 5374.10 22-NOV-06:10
December 0.117293E+11 15127.63 04-DEC-07:30 0.174240E+09 12708.36 04-DEC-06:10
             
Annual Sum or Average 0.154528E+12     0.166328E+10    
Minimum of Months 0.110940E+11 12780.60   0.00 0.00  
Maximum of Months 0.159056E+11 18328.75   0.852411E+09 25631.74  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.229303E+10 0.105175E+10 0.405300E+10 0.00 0.158922E+10 0.02 0.303088E+10 2011123.93 0.00 0.00 0.00 0.211425E+10 0.00
February 0.207245E+10 0.867818E+09 0.366466E+10 0.00 0.143070E+10 0.00 0.169081E+10 78209101.94 0.00 0.00 0.00 0.190779E+10 0.00
March 0.242411E+10 0.860333E+09 0.429420E+10 0.00 0.167314E+10 0.00 0.273961E+09 0.405159E+09 0.00 0.00 0.00 0.213229E+10 0.00
April 0.211529E+10 0.736357E+09 0.388642E+10 0.00 0.145830E+10 0.00 0.122676E+09 0.787453E+09 0.00 0.00 0.00 0.198746E+10 0.00
May 0.227317E+10 0.673460E+09 0.417360E+10 0.00 0.161317E+10 0.00 4285563.24 0.184939E+10 0.00 0.00 0.00 0.204207E+10 0.00
June 0.225031E+10 0.617857E+09 0.412149E+10 0.00 0.162799E+10 0.00 0.00 0.358731E+10 0.00 0.00 0.00 0.195406E+10 0.00
July 0.208388E+10 0.655120E+09 0.393546E+10 0.00 0.148754E+10 0.00 0.00 0.397658E+10 0.00 0.00 0.00 0.195473E+10 0.00
August 0.236135E+10 0.725282E+09 0.429420E+10 0.00 0.171040E+10 0.00 0.00 0.481175E+10 0.00 0.00 0.00 0.200258E+10 0.00
September 0.212893E+10 0.788105E+09 0.388029E+10 0.00 0.147815E+10 0.00 0.00 0.297355E+10 0.00 0.00 0.00 0.191763E+10 0.00
October 0.227205E+10 0.913469E+09 0.405607E+10 0.00 0.153796E+10 0.00 24341439.51 0.149997E+10 0.00 0.00 0.00 0.201975E+10 0.00
November 0.226841E+10 0.990230E+09 0.400396E+10 0.00 0.152917E+10 0.00 0.198979E+09 0.524736E+09 0.00 0.00 0.00 0.200187E+10 0.00
December 0.219573E+10 0.108106E+10 0.393240E+10 0.00 0.145442E+10 0.00 0.877416E+09 0.118081E+09 0.00 0.00 0.00 0.207023E+10 0.00
                           
Annual Sum or Average 0.267387E+11 0.996084E+10 0.482958E+11 0.00 0.185902E+11 0.02 0.622335E+10 0.206142E+11 0.00 0.00 0.00 0.241047E+11 0.00
Minimum of Months 0.207245E+10 0.617857E+09 0.366466E+10 0.00 0.143070E+10 0.00 0.00 2011123.93 0.00 0.00 0.00 0.190779E+10 0.00
Maximum of Months 0.242411E+10 0.108106E+10 0.429420E+10 0.00 0.171040E+10 0.02 0.303088E+10 0.481175E+10 0.00 0.00 0.00 0.213229E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.852411E+09 0.00 0.00 0.00 0.00
February 0.00 0.00 0.604275E+09 0.00 0.00 0.00 0.00
March 0.00 0.00 1532049.97 0.00 0.00 0.00 0.00
April 0.00 0.00 6817009.04 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 24007087.86 0.00 0.00 0.00 0.00
December 0.00 0.00 0.174240E+09 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.166328E+10 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.852411E+09 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2516.81 03-JAN-08:09 1061.67 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1615.06 02-JAN-06:10 0.00 10-JAN-11:39 8440.68 09-JAN-06:10
February 2533.94 01-FEB-08:09 1061.67 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1615.06 03-FEB-06:10 0.00 01-FEB-07:10 8416.21 06-FEB-06:00
March 2520.51 21-MAR-07:10 1061.67 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1615.06 01-MAR-06:10 0.00 01-MAR-00:10 4061.09 20-MAR-05:19
April 2497.75 03-APR-07:10 1061.67 01-APR-05:10 3325.31 03-APR-07:10 0.00 1615.06 03-APR-05:10 0.00 01-APR-00:10 4629.52 06-APR-05:30
May 2427.65 24-MAY-07:10 1061.67 01-MAY-05:10 3325.31 01-MAY-07:10 0.00 1615.06 01-MAY-05:10 0.00 01-MAY-00:10 571.86 11-MAY-06:10
June 2416.10 23-JUN-07:10 1061.67 01-JUN-05:10 3325.31 01-JUN-07:10 0.00 1615.06 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 2454.56 27-JUL-07:10 1061.67 01-JUL-05:10 3325.31 03-JUL-07:10 0.00 1615.06 10-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2488.14 24-AUG-07:10 1061.67 01-AUG-05:10 3325.31 01-AUG-07:10 0.00 1615.06 14-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2506.37 29-SEP-07:10 1061.67 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1615.06 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 2540.33 30-OCT-07:10 1061.67 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1615.06 02-OCT-05:10 0.00 01-OCT-00:10 1702.78 26-OCT-06:49
November 2536.23 01-NOV-07:10 1061.67 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1615.06 01-NOV-05:10 0.00 01-NOV-00:10 5751.34 22-NOV-06:30
December 2517.29 06-DEC-08:09 1061.67 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1615.06 04-DEC-06:10 0.00 01-DEC-00:10 7238.98 04-DEC-06:30
                           
Annual Sum or Average             0.00            
Minimum of Months 2416.10   1061.67   3325.31   0.00 1615.06   0.00   0.00  
Maximum of Months 2540.33   1061.67   3325.31   0.00 1615.06   0.00   8440.68  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 153.58 31-JAN-14:50 0.00 0.00 0.00 2804.93 27-JAN-12:09 0.00
February 1737.91 28-FEB-15:09 0.00 0.00 0.00 2804.93 02-FEB-12:39 0.00
March 3085.65 30-MAR-15:00 0.00 0.00 0.00 2801.83 01-MAR-12:00 0.00
April 3017.93 17-APR-15:00 0.00 0.00 0.00 2793.04 03-APR-11:09 0.00
May 4242.71 30-MAY-14:00 0.00 0.00 0.00 2782.83 01-MAY-11:09 0.00
June 5842.42 26-JUN-05:19 0.00 0.00 0.00 2771.23 02-JUN-11:09 0.00
July 6446.12 07-JUL-15:00 0.00 0.00 0.00 2763.08 03-JUL-11:50 0.00
August 6422.59 07-AUG-14:00 0.00 0.00 0.00 2762.62 31-AUG-11:50 0.00
September 5921.41 07-SEP-15:00 0.00 0.00 0.00 2769.89 29-SEP-11:09 0.00
October 4947.73 10-OCT-15:00 0.00 0.00 0.00 2781.17 31-OCT-11:50 0.00
November 2460.78 02-NOV-14:09 0.00 0.00 0.00 2792.38 30-NOV-12:50 0.00
December 1715.90 12-DEC-15:09 0.00 0.00 0.00 2800.63 29-DEC-12:50 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 153.58   0.00 0.00 0.00 2762.62   0.00
Maximum of Months 6446.12   0.00 0.00 0.00 2804.93   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 18328.75 09-JAN-08:09 2495.23 3325.31 0.00 0.00 1615.06 0.00 8158.03 0.00 0.00
February 17774.55 06-FEB-08:39 2520.13 3325.31 0.00 0.00 1615.06 0.00 7578.11 0.00 0.00
March 12915.70 30-MAR-15:39 2158.42 3325.31 0.00 0.00 1615.06 0.00 0.00 3061.40 0.00
April 12780.60 17-APR-14:50 2181.96 3325.31 0.00 0.00 1615.06 0.00 0.00 2931.28 0.00
May 13924.34 30-MAY-14:39 2064.28 3325.31 0.00 0.00 1615.06 0.00 0.00 4200.98 0.00
June 15444.71 26-JUN-14:30 2085.55 3325.31 0.00 0.00 1615.06 0.00 0.00 5704.13 0.00
July 16188.53 07-JUL-12:09 2284.59 3325.31 0.00 0.00 1615.06 0.00 0.00 6211.18 0.00
August 16230.45 07-AUG-15:20 2178.52 3325.31 0.00 0.00 1615.06 0.00 0.00 6380.39 0.00
September 15689.80 07-SEP-15:30 2145.81 3325.31 0.00 0.00 1615.06 0.00 0.00 5869.85 0.00
October 14658.71 10-OCT-14:00 2190.79 3325.31 0.00 0.00 1615.06 0.00 0.00 4808.16 0.00
November 13376.51 22-NOV-07:10 1185.75 1662.65 1061.67 0.00 1615.06 0.00 5159.75 0.00 0.00
December 15127.63 04-DEC-07:30 1185.75 1662.65 1061.67 0.00 1615.06 0.00 6909.86 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 12780.60   1185.75 1662.65 0.00 0.00 1615.06 0.00 0.00 0.00 0.00
Maximum of Months 18328.75   2520.13 3325.31 1061.67 0.00 1615.06 0.00 8158.03 6380.39 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 25076.86 09-JAN-06:19 0.00 0.00 0.00
February 0.00 0.00 25631.74 13-FEB-06:19 0.00 0.00 0.00
March 0.00 0.00 2553.42 06-MAR-06:10 0.00 0.00 0.00
April 0.00 0.00 3726.97 06-APR-05:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 5374.10 22-NOV-06:10 0.00 0.00 0.00
December 0.00 0.00 12708.36 04-DEC-06:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 25631.74   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 20.00 1.00 20.00 0.00 20.00 0.00 20.00
February 0.33 20.14 0.33 20.14 0.00 20.14 0.00 20.14
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 3.33 24.80 3.33 24.80
July 0.00 0.00 0.00 0.00 5.50 25.09 5.50 25.09
August 0.00 0.00 0.00 0.00 6.83 25.12 6.83 25.12
September 0.00 0.00 0.00 0.00 2.50 24.88 2.50 24.88
October 0.00 0.00 0.00 0.00 0.33 24.51 0.33 24.51
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1.33 20.04 1.33 20.04 18.50 24.38 18.50 24.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.00 20.14 1.00 20.14 6.83 25.12 6.83 25.12



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.67 19.75 5.33 19.90 0.00 19.90 0.00 19.90
February 4.50 18.85 3.50 19.34 0.00 19.34 0.00 19.34
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.96 0.17 24.96
July 0.00 0.00 0.00 0.00 1.83 24.75 1.83 24.75
August 0.00 0.00 0.00 0.00 4.67 24.82 4.67 24.82
September 0.00 0.00 0.00 0.00 1.83 24.59 1.83 24.59
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.17 20.11 0.17 20.11 0.00 20.11 0.00 20.11
                 
Annual Sum or Average 10.33 19.36 9.00 19.67 8.50 21.22 8.50 22.05
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.67 20.11 5.33 20.11 4.67 24.96 4.67 24.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 17.37 3.00 18.21 0.00 18.21 0.00 18.21
February 5.17 16.65 1.83 17.52 0.00 17.52 0.00 17.52
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.94 0.17 24.94
July 0.00 0.00 0.00 0.00 1.67 24.76 1.67 24.76
August 0.00 0.00 0.00 0.00 3.67 24.76 3.67 24.76
September 0.00 0.00 0.00 0.00 0.50 24.62 0.50 24.62
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.67 20.24 0.67 20.24 0.00 20.24 0.00 20.24
                 
Annual Sum or Average 12.00 17.22 5.50 18.09 6.00 19.79 6.00 20.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.17 20.24 3.00 20.24 3.67 24.94 3.67 24.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 7.17 17.93 4.33 18.66 0.00 18.66 0.00 18.66
February 6.67 16.74 2.50 17.59 0.00 17.59 0.00 17.59
March 0.17 20.26 0.17 20.26 0.00 20.26 0.00 20.26
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 25.03 0.17 25.03
July 0.00 0.00 0.00 0.00 1.67 24.85 1.67 24.85
August 0.00 0.00 0.00 0.00 4.00 24.81 4.00 24.81
September 0.00 0.00 0.00 0.00 0.50 24.64 0.50 24.64
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.00 20.12 1.00 20.12 0.00 20.12 0.00 20.12
                 
Annual Sum or Average 15.00 17.58 8.00 18.38 6.33 19.77 6.33 20.67
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7.17 20.26 4.33 20.26 4.00 25.03 4.00 25.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 17.31 2.83 18.18 0.00 18.18 0.00 18.18
February 4.50 16.57 1.50 17.44 0.00 17.44 0.00 17.44
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 24.94 0.17 24.94
July 0.00 0.00 0.00 0.00 1.50 25.96 1.17 25.45
August 0.00 0.00 0.00 0.00 2.67 24.79 2.67 24.79
September 0.00 0.00 0.00 0.00 0.33 24.68 0.33 24.68
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 20.25 0.50 20.25 0.00 20.25 0.00 20.25
                 
Annual Sum or Average 11.17 17.14 4.83 18.04 4.67 19.65 4.33 20.54
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.17 20.25 2.83 20.25 2.67 25.96 2.67 25.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 21.34 181.50 21.26 181.50 21.21
February 323.00 22.10 75.50 21.94 75.50 21.83
March 304.67 23.39 29.67 23.48 7.33 23.49
April 153.33 23.75 79.83 24.08 16.00 24.10
May 49.50 24.54 270.67 24.54 30.17 24.58
June 53.50 26.29 349.83 24.87 53.50 25.03
July 78.17 26.47 340.00 25.04 78.17 25.26
August 103.83 26.43 391.00 25.07 103.83 25.31
September 37.50 26.12 316.17 24.75 37.50 24.88
October 77.83 24.04 157.00 24.46 14.50 24.52
November 245.50 23.51 29.83 23.58 16.00 23.59
December 328.50 22.50 38.00 22.48 38.00 22.46
             
Annual Sum or Average 2112.33 23.18 2259.00 23.71 652.00 23.73
Minimum of Months 37.50 21.34 29.67 21.26 7.33 21.21
Maximum of Months 357.00 26.47 391.00 25.07 181.50 25.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 21.08 226.50 20.88 226.50 20.79
February 317.67 21.56 154.00 21.25 154.00 21.09
March 340.00 22.52 50.50 22.44 37.33 22.31
April 260.83 22.88 41.00 22.87 31.67 22.80
May 168.67 23.56 174.33 23.96 57.00 23.96
June 118.67 25.05 327.50 24.76 105.17 24.86
July 143.67 25.60 340.00 24.99 143.67 25.13
August 175.67 25.78 391.00 25.11 175.67 25.27
September 67.83 25.59 307.67 24.84 58.67 24.99
October 143.00 23.33 169.33 24.03 27.83 24.12
November 252.83 22.81 39.67 22.93 10.83 22.90
December 313.17 21.98 85.00 21.78 81.33 21.63
             
Annual Sum or Average 2659.00 22.89 2306.50 23.29 1109.67 23.27
Minimum of Months 67.83 21.08 39.67 20.88 10.83 20.79
Maximum of Months 357.00 25.78 391.00 25.11 226.50 25.27



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 20.55 248.50 20.46 248.50 20.43
February 266.00 21.23 165.50 20.94 165.50 20.81
March 301.50 22.48 47.67 22.30 44.17 22.14
April 201.33 23.05 32.83 23.08 19.00 23.00
May 82.83 23.59 171.17 24.23 26.00 24.20
June 52.33 25.67 289.50 24.98 47.50 25.09
July 101.17 26.47 280.00 25.38 101.17 25.61
August 118.33 26.52 322.00 25.41 118.33 25.64
September 34.83 25.92 253.67 24.92 29.50 25.05
October 134.33 23.35 104.50 23.90 14.50 23.96
November 269.33 22.82 27.50 22.73 21.83 22.63
December 275.33 21.51 140.17 21.23 140.17 21.10
             
Annual Sum or Average 2131.33 22.67 2083.00 23.10 976.17 22.98
Minimum of Months 34.83 20.55 27.50 20.46 14.50 20.43
Maximum of Months 301.50 26.52 322.00 25.41 248.50 25.64



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.64 312.00 20.57 312.00 20.54
February 323.00 21.13 213.83 20.92 213.83 20.82
March 376.33 22.25 77.50 22.06 75.67 21.91
April 291.83 23.02 37.83 22.94 33.67 22.86
May 134.83 23.64 149.67 24.07 34.17 24.05
June 46.00 25.15 326.67 24.74 36.83 24.81
July 83.33 26.19 340.00 25.01 83.33 25.21
August 113.83 26.31 391.00 25.09 113.83 25.32
September 30.67 25.12 273.83 24.66 20.83 24.73
October 208.50 23.37 96.33 23.70 14.50 23.75
November 338.17 22.64 55.00 22.48 52.17 22.35
December 340.00 21.37 196.67 21.15 196.67 21.05
             
Annual Sum or Average 2643.50 22.46 2470.33 22.84 1187.50 22.69
Minimum of Months 30.67 20.64 37.83 20.57 14.50 20.54
Maximum of Months 376.33 26.31 391.00 25.09 312.00 25.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.78 294.00 20.68 294.00 20.64
February 323.00 21.39 190.67 21.10 190.67 20.97
March 347.17 22.57 64.33 22.49 48.50 22.33
April 230.50 23.17 68.00 23.42 26.17 23.33
May 102.00 23.80 202.50 24.47 29.50 24.46
June 86.33 26.67 336.00 25.30 78.17 25.56
July 109.00 27.12 340.00 25.49 109.00 25.81
August 125.33 27.12 391.00 25.51 125.33 25.82
September 52.50 26.89 294.17 25.16 48.00 25.40
October 167.00 23.53 141.83 24.08 15.67 24.13
November 313.00 22.92 33.67 22.85 25.83 22.75
December 334.67 21.71 151.50 21.43 151.50 21.28
             
Annual Sum or Average 2547.50 22.91 2507.67 23.30 1142.33 23.23
Minimum of Months 52.50 20.78 33.67 20.68 15.67 20.64
Maximum of Months 357.00 27.12 391.00 25.51 294.00 25.82



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 1233535.86 282208.76 2.33 837847.60 395688.26 0.00 0.05 20-JAN-16:53 0.00 01-JAN-00:05 276.39 20-JAN-16:53 189.92 20-JAN-16:57 86.79 20-JAN-16:53 63.15 20-JAN-16:53 0.00
February 0.106183E+09 24187630.58 34.67 0.100585E+09 5598356.84 0.00 0.35 28-FEB-15:00 0.00 01-FEB-00:10 1998.19 28-FEB-15:00 1844.93 28-FEB-15:00 198.99 22-FEB-17:00 465.15 28-FEB-15:00 0.00
March 0.767872E+09 0.170987E+09 164.59 0.605626E+09 0.162246E+09 0.00 1.00 31-MAR-05:03 0.00 01-MAR-00:10 6777.30 31-MAR-05:03 4674.85 31-MAR-05:03 2102.45 31-MAR-05:03 1322.40 31-MAR-05:03 0.00
April 0.139351E+10 0.313265E+09 199.07 0.112296E+10 0.270551E+09 0.00 1.00 18-APR-05:03 0.00 01-APR-00:10 6736.41 19-APR-05:03 5097.70 18-APR-05:03 1950.42 21-APR-05:03 1316.50 19-APR-05:03 0.00
May 0.280332E+10 0.619081E+09 256.75 0.209782E+10 0.705503E+09 0.00 1.00 04-MAY-05:03 0.00 01-MAY-00:10 7047.24 31-MAY-05:02 5197.31 17-MAY-05:02 2987.89 26-MAY-05:03 1353.63 31-MAY-05:02 0.00
June 0.450776E+10 0.999006E+09 263.83 0.330498E+10 0.120278E+10 0.00 1.00 01-JUN-05:02 0.00 01-JUN-00:10 7182.58 26-JUN-05:01 5765.30 09-JUN-05:02 3116.98 23-JUN-05:08 1482.53 26-JUN-13:53 0.00
July 0.484644E+10 0.105998E+10 240.00 0.344449E+10 0.140195E+10 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 7201.64 27-JUL-05:02 5272.44 10-JUL-14:05 3241.86 27-JUL-05:08 1557.53 07-JUL-16:00 0.00
August 0.571505E+10 0.124411E+10 276.00 0.396374E+10 0.175131E+10 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 7276.37 07-AUG-05:01 5151.20 28-AUG-05:01 3368.65 24-AUG-05:10 1540.33 07-AUG-14:53 0.00
September 0.374555E+10 0.807925E+09 239.19 0.276199E+10 0.983566E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 7184.19 07-SEP-05:01 5331.51 15-SEP-05:02 3162.58 28-SEP-05:07 1419.61 11-SEP-15:50 0.00
October 0.209698E+10 0.453717E+09 231.50 0.158988E+10 0.507091E+09 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 7209.66 19-OCT-05:02 5536.30 10-OCT-05:01 3448.35 19-OCT-05:08 1365.46 19-OCT-05:02 0.00
November 0.801127E+09 0.176531E+09 169.86 0.672790E+09 0.128338E+09 0.00 0.99 06-NOV-06:03 0.00 01-NOV-00:10 6641.97 06-NOV-06:03 4190.75 06-NOV-06:03 2451.22 06-NOV-06:03 1300.96 06-NOV-06:03 0.00
December 0.168622E+09 37310653.58 45.01 0.120578E+09 48043601.07 0.00 0.38 13-DEC-13:10 0.00 01-DEC-00:10 2319.55 13-DEC-13:10 1483.72 13-DEC-13:10 836.98 13-DEC-13:20 500.61 13-DEC-13:10 0.00
                                       
Annual Sum or Average 0.269537E+11 0.590638E+10 2122.80 0.197863E+11 0.716737E+10 0.00                         0.00
Minimum of Months 1233535.86 282208.76 2.33 837847.60 395688.26 0.00 0.05   0.00   276.39   189.92   86.79   63.15   0.00
Maximum of Months 0.571505E+10 0.124411E+10 276.00 0.396374E+10 0.175131E+10 0.00 1.00   0.00   7276.37   5765.30   3448.35   1557.53   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 7381041.81 1680444.30 4.75 6620449.42 760592.39 0.00 0.12 31-JAN-14:50 0.00 01-JAN-00:05 676.94 31-JAN-14:50 614.47 31-JAN-14:50 65.66 31-JAN-14:30 153.58 31-JAN-14:50 0.00
February 0.165338E+09 36989371.72 34.41 0.165258E+09 79761.76 0.00 0.45 28-FEB-15:30 0.00 01-FEB-00:10 2548.19 28-FEB-15:30 2548.19 28-FEB-15:30 23.60 22-FEB-15:40 577.11 28-FEB-15:30 0.00
March 0.457223E+09 0.102868E+09 93.69 0.392988E+09 64235789.62 0.00 0.63 30-MAR-14:05 0.00 01-MAR-00:10 3759.05 30-MAR-14:05 3321.38 30-MAR-15:00 695.00 30-MAR-11:52 871.13 30-MAR-14:05 0.00
April 0.667296E+09 0.155272E+09 117.20 0.587279E+09 80016332.76 0.00 0.52 19-APR-14:25 0.00 01-APR-00:10 3099.05 19-APR-14:25 2846.22 17-APR-15:00 718.00 04-APR-13:23 721.26 17-APR-14:45 0.00
May 0.158567E+10 0.362825E+09 201.36 0.122617E+10 0.359501E+09 0.00 1.00 31-MAY-05:02 0.00 01-MAY-00:10 6965.50 31-MAY-05:02 4452.02 19-MAY-05:02 3147.87 31-MAY-05:02 1334.03 31-MAY-05:02 0.00
June 0.357086E+10 0.810118E+09 255.28 0.261902E+10 0.951840E+09 0.00 1.00 05-JUN-05:01 0.00 01-JUN-00:10 7171.90 26-JUN-05:01 5187.36 05-JUN-05:01 3407.74 27-JUN-05:12 1497.61 23-JUN-11:53 0.00
July 0.412391E+10 0.920592E+09 239.87 0.291536E+10 0.120855E+10 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 7238.59 27-JUL-05:02 5286.04 10-JUL-16:05 3853.96 27-JUL-05:05 1565.22 07-JUL-16:20 0.00
August 0.529972E+10 0.116569E+10 275.95 0.367154E+10 0.162818E+10 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 7345.67 21-AUG-05:01 5290.38 29-AUG-16:03 3915.51 24-AUG-05:06 1557.91 01-AUG-17:00 0.00
September 0.333229E+10 0.725055E+09 230.36 0.254946E+10 0.782830E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 7125.67 07-SEP-05:01 5817.36 15-SEP-05:02 3274.23 28-SEP-05:05 1484.28 07-SEP-16:00 0.00
October 0.187841E+10 0.402916E+09 181.05 0.154096E+10 0.337451E+09 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 7227.41 19-OCT-05:02 6095.98 12-OCT-05:02 3913.70 19-OCT-05:04 1437.45 10-OCT-15:53 0.00
November 0.767773E+09 0.166608E+09 129.51 0.709670E+09 58103128.16 0.00 0.67 06-NOV-14:30 0.00 01-NOV-00:10 3955.98 06-NOV-14:00 3946.36 06-NOV-14:30 692.33 02-NOV-12:05 822.38 06-NOV-14:00 0.00
December 0.241002E+09 53255193.23 59.11 0.207976E+09 33025402.32 0.00 0.54 12-DEC-14:00 0.00 01-DEC-00:10 3293.11 12-DEC-14:00 2667.79 12-DEC-14:10 689.05 12-DEC-13:05 712.44 12-DEC-14:00 0.00
                                       
Annual Sum or Average 0.220969E+11 0.490387E+10 1822.54 0.165923E+11 0.550458E+10 0.00                         0.00
Minimum of Months 7381041.81 1680444.30 4.75 6620449.42 79761.76 0.00 0.12   0.00   676.94   614.47   23.60   153.58   0.00
Maximum of Months 0.529972E+10 0.116569E+10 275.95 0.367154E+10 0.162818E+10 0.00 1.00   0.00   7345.67   6095.98   3915.51   1565.22   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 23658480.33 5477847.78 16.65 23658480.33 -0.0 0.00 0.43 28-FEB-15:05 0.00 01-FEB-00:10 1683.86 28-FEB-15:05 1683.86 28-FEB-15:05 0.00 23-FEB-16:10 386.24 28-FEB-15:05 0.00
March 0.158408E+09 36178863.66 73.14 0.135253E+09 23154480.78 0.00 0.84 30-MAR-10:02 0.00 01-MAR-00:10 3785.94 30-MAR-10:02 3107.18 14-MAR-10:02 950.58 30-MAR-10:02 758.97 30-MAR-10:02 0.00
April 0.408828E+09 95057699.38 132.73 0.373297E+09 35531573.94 0.00 1.00 20-APR-10:01 0.00 01-APR-00:10 4607.95 20-APR-10:01 4005.98 13-APR-10:01 882.60 20-APR-10:01 900.64 20-APR-10:01 0.00
May 0.106874E+10 0.245065E+09 227.41 0.901517E+09 0.167219E+09 0.00 1.00 17-MAY-10:01 0.00 01-MAY-00:10 4826.53 31-MAY-05:02 4108.22 18-MAY-10:02 1942.38 31-MAY-05:02 978.35 30-MAY-10:02 0.00
June 0.216531E+10 0.499473E+09 261.14 0.176795E+10 0.397367E+09 0.00 1.00 05-JUN-05:01 0.00 01-JUN-00:10 5002.56 26-JUN-05:01 4067.79 05-JUN-10:02 2274.42 19-JUN-05:12 1054.03 13-JUN-14:03 0.00
July 0.246548E+10 0.561601E+09 240.38 0.195986E+10 0.505627E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 5020.44 27-JUL-05:02 4064.51 24-JUL-12:03 2569.73 31-JUL-05:03 1068.92 07-JUL-14:05 0.00
August 0.293641E+10 0.665727E+09 275.03 0.227938E+10 0.657028E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5117.99 21-AUG-05:01 4068.85 25-AUG-10:01 2575.97 21-AUG-05:06 1062.82 01-AUG-14:03 0.00
September 0.182306E+10 0.406464E+09 236.07 0.151208E+10 0.310982E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 4962.28 05-SEP-05:01 4264.90 15-SEP-10:02 2128.16 05-SEP-05:06 1015.64 06-SEP-12:03 0.00
October 0.848778E+09 0.188288E+09 187.80 0.724080E+09 0.124699E+09 0.00 1.00 02-OCT-10:02 0.00 01-OCT-00:10 5019.02 19-OCT-05:02 4020.87 03-OCT-10:02 2606.66 19-OCT-05:04 938.05 19-OCT-05:02 0.00
November 0.229613E+09 51383294.59 106.49 0.211931E+09 17681723.66 0.00 0.81 02-NOV-10:02 0.00 01-NOV-00:10 3590.48 02-NOV-10:02 3104.16 08-NOV-11:02 742.53 02-NOV-10:02 725.77 02-NOV-10:02 0.00
December 30966362.32 6940882.83 17.46 23710818.12 7255544.20 0.00 0.49 12-DEC-15:03 0.00 01-DEC-00:10 2067.75 12-DEC-15:03 1626.06 12-DEC-15:03 559.95 13-DEC-13:05 448.44 12-DEC-15:03 0.00
                                       
Annual Sum or Average 0.121593E+11 0.276166E+10 1774.31 0.991272E+10 0.224654E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.293641E+10 0.665727E+09 275.03 0.227938E+10 0.657028E+09 0.00 1.00   0.00   5117.99   4264.90   2606.66   1068.92   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00 01-JAN-00:05 0.00
February 13041943.43 3097721.50 6.44 13041943.43 0.00 0.00 0.18 28-FEB-16:53 0.00 01-FEB-00:10 935.93 28-FEB-16:57 935.93 28-FEB-16:57 0.00 28-FEB-13:40 220.37 28-FEB-16:53 0.00
March 0.185854E+09 42604958.79 56.85 0.143467E+09 42387834.07 0.00 0.41 30-MAR-15:53 0.00 01-MAR-00:10 2341.20 30-MAR-15:53 2048.81 30-MAR-15:57 503.63 31-MAR-11:00 562.15 30-MAR-15:53 0.00
April 0.501389E+09 0.117382E+09 113.93 0.423351E+09 78037403.09 0.00 0.43 19-APR-14:55 0.00 01-APR-00:10 2466.45 19-APR-14:55 2092.09 19-APR-14:55 641.55 04-APR-14:05 578.10 19-APR-14:55 0.00
May 0.155623E+10 0.356931E+09 221.48 0.121607E+10 0.340159E+09 0.00 1.00 22-MAY-05:01 0.00 01-MAY-00:10 6799.66 31-MAY-05:02 4864.70 19-MAY-05:02 2898.39 31-MAY-05:02 1307.15 31-MAY-05:02 0.00
June 0.329358E+10 0.755714E+09 260.57 0.251642E+10 0.777156E+09 0.00 1.00 05-JUN-05:01 0.00 01-JUN-00:10 7048.78 26-JUN-05:01 5099.43 05-JUN-05:01 3344.70 19-JUN-05:05 1345.92 26-JUN-05:01 0.00
July 0.374960E+10 0.848416E+09 239.87 0.278959E+10 0.960010E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 7070.31 27-JUL-05:02 4994.70 25-JUL-05:01 3700.79 31-JUL-05:03 1386.64 07-JUL-16:00 0.00
August 0.456536E+10 0.102482E+10 276.00 0.332232E+10 0.124304E+10 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 7214.66 21-AUG-05:01 4773.33 07-AUG-13:05 3761.59 21-AUG-05:06 1417.37 07-AUG-15:00 0.00
September 0.270409E+10 0.601347E+09 237.32 0.209238E+10 0.611710E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 6992.52 05-SEP-05:01 5579.01 15-SEP-05:02 3136.88 05-SEP-05:06 1329.62 07-SEP-05:01 0.00
October 0.112679E+10 0.249947E+09 178.75 0.879668E+09 0.247125E+09 0.00 1.00 11-OCT-05:01 0.00 01-OCT-00:10 7070.16 19-OCT-05:02 4489.98 11-OCT-05:01 3759.32 19-OCT-05:04 1324.06 19-OCT-05:02 0.00
November 0.276722E+09 62009785.46 87.25 0.241410E+09 35312933.23 0.00 0.35 03-NOV-15:00 0.00 01-NOV-00:10 2053.55 03-NOV-15:00 1573.07 03-NOV-15:00 480.48 03-NOV-15:00 450.74 03-NOV-15:00 0.00
December 38698654.60 8680048.11 14.58 26527657.14 12170997.46 0.00 0.22 13-DEC-13:05 0.00 01-DEC-00:10 1303.66 13-DEC-13:05 869.30 13-DEC-13:05 434.37 13-DEC-13:05 288.28 13-DEC-13:05 0.00
                                       
Annual Sum or Average 0.180114E+11 0.407095E+10 1693.04 0.136642E+11 0.434711E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.456536E+10 0.102482E+10 276.00 0.332232E+10 0.124304E+10 0.00 1.00   0.00   7214.66   5579.01   3761.59   1417.37   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 211082.76 48470.86 0.61 172191.55 38891.21 0.00 0.04 20-JAN-16:50 0.00 01-JAN-00:05 186.68 20-JAN-16:50 152.85 20-JAN-16:50 33.82 20-JAN-16:50 42.78 20-JAN-16:50 0.00
February 36573187.90 8456530.37 19.68 36573187.90 0.00 0.00 0.28 28-FEB-16:33 0.00 01-FEB-00:10 1214.65 28-FEB-16:40 1214.65 28-FEB-16:40 0.00 28-FEB-16:20 280.68 28-FEB-16:45 0.00
March 0.230134E+09 52520199.21 85.00 0.195439E+09 34695112.61 0.00 0.49 30-MAR-15:53 0.00 01-MAR-00:10 2222.32 30-MAR-15:53 2018.74 30-MAR-15:57 303.83 29-MAR-15:40 527.93 30-MAR-15:53 0.00
April 0.454799E+09 0.106476E+09 134.79 0.404938E+09 49861278.49 0.00 0.49 17-APR-15:53 0.00 01-APR-00:10 2214.65 17-APR-15:53 2137.86 17-APR-15:57 394.61 04-APR-14:05 539.31 17-APR-15:53 0.00
May 0.114970E+10 0.265483E+09 233.14 0.938011E+09 0.211690E+09 0.00 1.00 19-MAY-05:02 0.00 01-MAY-00:10 5425.97 31-MAY-05:02 4304.05 19-MAY-05:02 2151.13 31-MAY-05:02 1041.93 31-MAY-05:02 0.00
June 0.224196E+10 0.522996E+09 262.93 0.177774E+10 0.464221E+09 0.00 1.00 05-JUN-05:01 0.00 01-JUN-00:10 5631.76 26-JUN-05:01 4345.55 05-JUN-05:01 2533.59 19-JUN-05:03 1072.10 26-JUN-05:01 0.00
July 0.253617E+10 0.585990E+09 247.14 0.196043E+10 0.575738E+09 0.00 1.00 03-JUL-05:01 0.00 01-JUL-00:10 5643.24 27-JUL-05:02 4259.08 25-JUL-05:01 2834.85 31-JUL-05:03 1082.04 09-JUL-17:33 0.00
August 0.310566E+10 0.711410E+09 282.02 0.235517E+10 0.750493E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5743.51 21-AUG-05:01 3995.35 14-AUG-05:01 2814.72 23-AUG-05:06 1080.79 10-AUG-05:01 0.00
September 0.192358E+10 0.432764E+09 237.64 0.155638E+10 0.367202E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 5585.36 05-SEP-05:01 4756.75 15-SEP-05:02 2349.53 05-SEP-05:05 1059.75 27-SEP-05:01 0.00
October 0.920297E+09 0.205098E+09 195.26 0.766183E+09 0.154114E+09 0.00 1.00 10-OCT-05:01 0.00 01-OCT-00:10 5645.04 19-OCT-05:02 4013.16 10-OCT-05:01 2931.32 19-OCT-05:04 1054.83 19-OCT-05:02 0.00
November 0.305039E+09 68204206.17 116.99 0.279515E+09 25523332.06 0.00 0.40 06-NOV-16:30 0.00 01-NOV-00:10 1756.04 06-NOV-16:25 1756.04 06-NOV-16:25 283.00 03-NOV-15:00 381.62 06-NOV-16:25 0.00
December 52858001.57 11894382.38 26.74 40960873.33 11897128.25 0.00 0.23 12-DEC-14:35 0.00 01-DEC-00:10 1032.35 12-DEC-14:35 799.83 12-DEC-14:40 282.94 13-DEC-12:00 233.89 12-DEC-14:35 0.00
                                       
Annual Sum or Average 0.129570E+11 0.297134E+10 1841.94 0.103115E+11 0.264547E+10 0.00                         0.00
Minimum of Months 211082.76 48470.86 0.61 172191.55 0.00 0.00 0.04   0.00   186.68   152.85   0.00   42.78   0.00
Maximum of Months 0.310566E+10 0.711410E+09 282.02 0.235517E+10 0.750493E+09 0.00 1.00   0.00   5743.51   4756.75   2931.32   1082.04   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.57 44.10 18.47 76.69 58.58 0.00 0.00 0.00
February 58.35 39.57 18.78 77.58 50.06 0.00 0.00 0.00
March 47.54 23.96 23.58 66.84 34.13 0.00 0.00 0.00
April 29.18 6.11 23.06 43.13 27.36 0.00 0.00 0.00
May 23.62 0.00 23.62 35.84 18.56 0.00 0.00 0.00
June 24.48 0.00 24.48 45.30 13.41 0.00 0.00 0.00
July 23.90 0.06 23.84 45.53 10.42 0.00 0.00 0.00
August 25.44 1.62 23.82 49.49 9.57 0.00 0.00 0.00
September 31.98 10.13 21.86 53.39 19.96 0.00 0.00 0.00
October 55.43 36.11 19.33 82.86 38.08 0.00 0.00 0.00
November 60.80 40.81 19.99 82.87 47.40 0.00 0.00 0.00
December 61.72 43.86 17.86 78.62 53.41 0.00 0.00 0.00
                 
Annual Sum or Average 42.01 20.44 21.57 61.44 31.65 0.00 0.00 0.00
Minimum of Months 23.62 0.00 17.86 35.84 9.57 0.00 0.00 0.00
Maximum of Months 62.57 44.10 24.48 82.87 58.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.57 44.10 18.47 76.69 58.58 0.00 0.00 0.00
February 58.35 39.57 18.78 77.58 50.06 0.00 0.00 0.00
March 47.53 23.95 23.58 66.82 34.13 0.00 0.00 0.00
April 29.07 6.07 23.01 42.89 27.38 0.00 0.00 0.00
May 23.62 0.00 23.62 35.83 18.56 0.00 0.00 0.00
June 24.48 0.00 24.48 45.30 13.41 0.00 0.00 0.00
July 23.90 0.06 23.84 45.53 10.42 0.00 0.00 0.00
August 25.40 1.61 23.79 49.41 9.57 0.00 0.00 0.00
September 31.90 10.09 21.81 53.20 19.97 0.00 0.00 0.00
October 55.43 36.11 19.33 82.86 38.08 0.00 0.00 0.00
November 60.80 40.81 19.99 82.87 47.39 0.00 0.00 0.00
December 61.72 43.86 17.86 78.62 53.41 0.00 0.00 0.00
                 
Annual Sum or Average 41.99 20.43 21.56 61.39 31.65 0.00 0.00 0.00
Minimum of Months 23.62 0.00 17.86 35.83 9.57 0.00 0.00 0.00
Maximum of Months 62.57 44.10 24.48 82.87 58.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.57 44.10 18.47 76.69 58.58 0.00 0.00 0.00
February 58.35 39.57 18.78 77.58 50.06 0.00 0.00 0.00
March 47.53 23.95 23.58 66.82 34.13 0.00 0.00 0.00
April 29.07 6.07 23.01 42.89 27.38 0.00 0.00 0.00
May 23.62 0.00 23.62 35.83 18.56 0.00 0.00 0.00
June 24.48 0.00 24.48 45.30 13.41 0.00 0.00 0.00
July 23.90 0.06 23.84 45.53 10.42 0.00 0.00 0.00
August 25.40 1.61 23.79 49.41 9.57 0.00 0.00 0.00
September 31.89 10.09 21.80 53.19 19.97 0.00 0.00 0.00
October 55.43 36.11 19.33 82.86 38.08 0.00 0.00 0.00
November 60.80 40.81 19.99 82.87 47.39 0.00 0.00 0.00
December 61.72 43.86 17.86 78.62 53.41 0.00 0.00 0.00
                 
Annual Sum or Average 41.99 20.43 21.56 61.39 31.65 0.00 0.00 0.00
Minimum of Months 23.62 0.00 17.86 35.83 9.57 0.00 0.00 0.00
Maximum of Months 62.57 44.10 24.48 82.87 58.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.57 44.10 18.47 76.69 58.58 0.00 0.00 0.00
February 58.35 39.57 18.78 77.58 50.06 0.00 0.00 0.00
March 47.53 23.95 23.58 66.82 34.13 0.00 0.00 0.00
April 29.07 6.07 23.01 42.89 27.38 0.00 0.00 0.00
May 23.62 0.00 23.62 35.83 18.56 0.00 0.00 0.00
June 24.48 0.00 24.48 45.30 13.41 0.00 0.00 0.00
July 23.90 0.06 23.84 45.53 10.42 0.00 0.00 0.00
August 25.40 1.61 23.79 49.41 9.57 0.00 0.00 0.00
September 31.89 10.09 21.80 53.19 19.97 0.00 0.00 0.00
October 55.43 36.11 19.33 82.86 38.08 0.00 0.00 0.00
November 60.80 40.81 19.99 82.87 47.39 0.00 0.00 0.00
December 61.72 43.86 17.86 78.62 53.41 0.00 0.00 0.00
                 
Annual Sum or Average 41.99 20.43 21.56 61.39 31.65 0.00 0.00 0.00
Minimum of Months 23.62 0.00 17.86 35.83 9.57 0.00 0.00 0.00
Maximum of Months 62.57 44.10 24.48 82.87 58.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.57 44.10 18.47 76.69 58.58 0.00 0.00 0.00
February 58.35 39.57 18.78 77.58 50.06 0.00 0.00 0.00
March 47.53 23.95 23.58 66.82 34.13 0.00 0.00 0.00
April 29.07 6.07 23.01 42.89 27.38 0.00 0.00 0.00
May 23.62 0.00 23.62 35.83 18.56 0.00 0.00 0.00
June 24.48 0.00 24.48 45.30 13.41 0.00 0.00 0.00
July 23.90 0.06 23.84 45.53 10.42 0.00 0.00 0.00
August 25.40 1.61 23.79 49.41 9.57 0.00 0.00 0.00
September 31.90 10.09 21.81 53.20 19.95 0.00 0.00 0.00
October 55.43 36.11 19.33 82.86 38.08 0.00 0.00 0.00
November 60.80 40.81 19.99 82.87 47.39 0.00 0.00 0.00
December 61.72 43.86 17.86 78.62 53.41 0.00 0.00 0.00
                 
Annual Sum or Average 41.99 20.43 21.56 61.39 31.65 0.00 0.00 0.00
Minimum of Months 23.62 0.00 17.86 35.83 9.57 0.00 0.00 0.00
Maximum of Months 62.57 44.10 24.48 82.87 58.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 62.57 44.10 18.47 76.69 58.58 0.00 0.00 0.00
February 58.35 39.57 18.78 77.58 50.06 0.00 0.00 0.00
March 47.54 23.96 23.58 66.83 34.12 0.00 0.00 0.00
April 29.17 6.11 23.06 43.07 27.32 0.00 0.00 0.00
May 23.62 0.00 23.62 35.84 18.56 0.00 0.00 0.00
June 24.48 0.00 24.48 45.30 13.41 0.00 0.00 0.00
July 23.90 0.06 23.84 45.53 10.42 0.00 0.00 0.00
August 25.43 1.62 23.81 49.48 9.57 0.00 0.00 0.00
September 31.99 10.13 21.86 53.34 19.90 0.00 0.00 0.00
October 55.43 36.11 19.33 82.86 38.08 0.00 0.00 0.00
November 60.80 40.81 19.99 82.87 47.40 0.00 0.00 0.00
December 61.72 43.86 17.86 78.62 53.41 0.00 0.00 0.00
                 
Annual Sum or Average 42.01 20.44 21.57 61.43 31.64 0.00 0.00 0.00
Minimum of Months 23.62 0.00 17.86 35.84 9.57 0.00 0.00 0.00
Maximum of Months 62.57 44.10 24.48 82.87 58.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 88.13 61.78 26.35 107.94 81.53 0.00 0.00 0.00
February 82.22 55.44 26.78 109.15 69.78 0.00 0.00 0.00
March 73.71 38.76 34.95 106.20 47.73 0.00 0.00 0.00
April 48.63 13.68 34.94 75.66 38.36 0.00 0.00 0.00
May 36.57 1.42 35.15 57.01 26.11 0.00 0.00 0.00
June 35.14 0.00 35.13 64.31 18.99 0.00 0.00 0.00
July 34.91 0.38 34.53 65.94 14.77 0.00 0.00 0.00
August 41.95 5.39 36.56 81.85 13.63 0.00 0.00 0.00
September 51.91 18.75 33.17 88.05 28.12 0.00 0.00 0.00
October 79.61 51.88 27.74 119.04 53.29 0.00 0.00 0.00
November 85.66 57.17 28.49 116.55 66.28 0.00 0.00 0.00
December 86.91 61.45 25.46 110.62 74.54 0.00 0.00 0.00
                 
Annual Sum or Average 62.02 30.39 31.63 91.78 44.29 0.00 0.00 0.00
Minimum of Months 34.91 0.00 25.46 57.01 13.63 0.00 0.00 0.00
Maximum of Months 88.13 61.78 36.56 119.04 81.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.61 11.25 13.36 19.29 60.33 0.00 0.00 0.00
February 31.07 16.84 14.24 32.94 49.41 0.00 0.00 0.00
March 38.62 17.60 21.03 47.28 31.47 0.00 0.00 0.00
April 46.21 20.90 25.30 67.15 25.22 0.00 0.00 0.00
May 50.34 21.08 29.26 79.07 17.91 0.00 0.00 0.00
June 52.00 21.54 30.46 90.76 13.12 0.00 0.00 0.00
July 50.91 21.30 29.60 90.54 10.60 0.00 0.00 0.00
August 46.71 18.46 28.25 84.33 9.58 0.00 0.00 0.00
September 38.80 17.26 21.54 60.92 18.96 0.00 0.00 0.00
October 33.40 17.38 16.02 42.46 36.07 0.00 0.00 0.00
November 26.82 12.27 14.55 26.81 45.64 0.00 0.00 0.00
December 23.30 10.77 12.53 18.86 52.74 0.00 0.00 0.00
                 
Annual Sum or Average 38.60 17.22 21.39 55.15 30.82 0.00 0.00 0.00
Minimum of Months 23.30 10.77 12.53 18.86 9.58 0.00 0.00 0.00
Maximum of Months 52.00 21.54 30.46 90.76 60.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.61 11.25 13.36 19.29 60.33 0.00 0.00 0.00
February 31.07 16.84 14.24 32.94 49.41 0.00 0.00 0.00
March 38.62 17.60 21.03 47.28 31.47 0.00 0.00 0.00
April 46.21 20.90 25.30 67.15 25.21 0.00 0.00 0.00
May 50.34 21.08 29.26 79.07 17.91 0.00 0.00 0.00
June 52.00 21.54 30.46 90.76 13.12 0.00 0.00 0.00
July 50.91 21.30 29.60 90.54 10.60 0.00 0.00 0.00
August 46.71 18.46 28.25 84.33 9.57 0.00 0.00 0.00
September 38.80 17.26 21.54 60.92 18.96 0.00 0.00 0.00
October 33.40 17.38 16.02 42.45 36.07 0.00 0.00 0.00
November 26.82 12.27 14.55 26.80 45.64 0.00 0.00 0.00
December 23.30 10.77 12.53 18.86 52.74 0.00 0.00 0.00
                 
Annual Sum or Average 38.60 17.22 21.39 55.15 30.82 0.00 0.00 0.00
Minimum of Months 23.30 10.77 12.53 18.86 9.57 0.00 0.00 0.00
Maximum of Months 52.00 21.54 30.46 90.76 60.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.61 11.25 13.36 19.29 60.33 0.00 0.00 0.00
February 31.07 16.84 14.24 32.94 49.41 0.00 0.00 0.00
March 38.62 17.60 21.03 47.28 31.47 0.00 0.00 0.00
April 46.21 20.90 25.30 67.15 25.21 0.00 0.00 0.00
May 50.34 21.08 29.26 79.07 17.91 0.00 0.00 0.00
June 52.00 21.54 30.46 90.76 13.12 0.00 0.00 0.00
July 50.91 21.30 29.60 90.54 10.60 0.00 0.00 0.00
August 46.71 18.46 28.25 84.33 9.57 0.00 0.00 0.00
September 38.80 17.26 21.54 60.92 18.96 0.00 0.00 0.00
October 33.40 17.38 16.02 42.45 36.07 0.00 0.00 0.00
November 26.82 12.27 14.55 26.80 45.64 0.00 0.00 0.00
December 23.30 10.77 12.53 18.86 52.74 0.00 0.00 0.00
                 
Annual Sum or Average 38.60 17.22 21.39 55.15 30.82 0.00 0.00 0.00
Minimum of Months 23.30 10.77 12.53 18.86 9.57 0.00 0.00 0.00
Maximum of Months 52.00 21.54 30.46 90.76 60.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 24.64 11.27 13.37 19.32 60.28 0.00 0.00 0.00
February 31.08 16.84 14.24 32.95 49.41 0.00 0.00 0.00
March 38.62 17.60 21.03 47.28 31.47 0.00 0.00 0.00
April 46.21 20.90 25.30 67.15 25.22 0.00 0.00 0.00
May 50.34 21.08 29.26 79.07 17.91 0.00 0.00 0.00
June 52.00 21.54 30.46 90.76 13.12 0.00 0.00 0.00
July 50.91 21.30 29.60 90.54 10.60 0.00 0.00 0.00
August 46.71 18.46 28.25 84.33 9.58 0.00 0.00 0.00
September 38.80 17.26 21.54 60.92 18.96 0.00 0.00 0.00
October 33.40 17.38 16.02 42.46 36.07 0.00 0.00 0.00
November 26.83 12.28 14.55 26.84 45.63 0.00 0.00 0.00
December 23.34 10.79 12.55 18.92 52.70 0.00 0.00 0.00
                 
Annual Sum or Average 38.61 17.22 21.39 55.16 30.82 0.00 0.00 0.00
Minimum of Months 23.34 10.79 12.55 18.92 9.58 0.00 0.00 0.00
Maximum of Months 52.00 21.54 30.46 90.76 60.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.15 0.00 11.15 2.37 66.88 0.00 0.00 0.00
February 12.43 0.00 12.43 6.88 54.14 0.00 0.00 0.00
March 17.46 0.00 17.46 15.20 33.19 0.00 0.00 0.00
April 21.13 0.09 21.04 27.10 26.17 0.00 0.00 0.00
May 25.07 0.72 24.35 37.78 17.63 0.00 0.00 0.00
June 27.28 1.58 25.70 50.11 12.65 0.00 0.00 0.00
July 25.85 1.11 24.74 49.16 10.03 0.00 0.00 0.00
August 23.28 0.24 23.05 45.24 9.03 0.00 0.00 0.00
September 17.60 0.00 17.60 26.18 18.95 0.00 0.00 0.00
October 13.47 0.00 13.47 12.06 37.89 0.00 0.00 0.00
November 11.95 0.00 11.95 6.49 49.16 0.00 0.00 0.00
December 10.31 0.00 10.31 2.26 57.70 0.00 0.00 0.00
                 
Annual Sum or Average 18.11 0.31 17.80 23.49 32.68 0.00 0.00 0.00
Minimum of Months 10.31 0.00 10.31 2.26 9.03 0.00 0.00 0.00
Maximum of Months 27.28 1.58 25.70 50.11 66.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.15 0.00 11.15 2.37 66.88 0.00 0.00 0.00
February 12.42 0.00 12.42 6.88 54.14 0.00 0.00 0.00
March 17.46 0.00 17.46 15.20 33.19 0.00 0.00 0.00
April 21.10 0.09 21.02 27.10 26.23 0.00 0.00 0.00
May 24.98 0.69 24.29 37.60 17.65 0.00 0.00 0.00
June 27.20 1.55 25.66 49.93 12.65 0.00 0.00 0.00
July 25.77 1.08 24.69 48.95 10.03 0.00 0.00 0.00
August 23.22 0.22 23.00 45.10 9.03 0.00 0.00 0.00
September 17.60 0.00 17.60 26.18 18.95 0.00 0.00 0.00
October 13.47 0.00 13.47 12.06 37.89 0.00 0.00 0.00
November 11.95 0.00 11.95 6.49 49.16 0.00 0.00 0.00
December 10.31 0.00 10.31 2.26 57.70 0.00 0.00 0.00
                 
Annual Sum or Average 18.08 0.30 17.78 23.43 32.68 0.00 0.00 0.00
Minimum of Months 10.31 0.00 10.31 2.26 9.03 0.00 0.00 0.00
Maximum of Months 27.20 1.55 25.66 49.93 66.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.15 0.00 11.15 2.37 66.88 0.00 0.00 0.00
February 12.42 0.00 12.42 6.88 54.14 0.00 0.00 0.00
March 17.46 0.00 17.46 15.20 33.19 0.00 0.00 0.00
April 21.10 0.08 21.02 27.10 26.24 0.00 0.00 0.00
May 24.98 0.69 24.29 37.60 17.65 0.00 0.00 0.00
June 27.20 1.55 25.66 49.93 12.65 0.00 0.00 0.00
July 25.77 1.08 24.69 48.95 10.03 0.00 0.00 0.00
August 23.22 0.22 23.00 45.10 9.03 0.00 0.00 0.00
September 17.60 0.00 17.60 26.18 18.95 0.00 0.00 0.00
October 13.47 0.00 13.47 12.06 37.89 0.00 0.00 0.00
November 11.95 0.00 11.95 6.49 49.16 0.00 0.00 0.00
December 10.31 0.00 10.31 2.26 57.70 0.00 0.00 0.00
                 
Annual Sum or Average 18.08 0.30 17.78 23.43 32.68 0.00 0.00 0.00
Minimum of Months 10.31 0.00 10.31 2.26 9.03 0.00 0.00 0.00
Maximum of Months 27.20 1.55 25.66 49.93 66.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.15 0.00 11.15 2.37 66.88 0.00 0.00 0.00
February 12.42 0.00 12.42 6.88 54.14 0.00 0.00 0.00
March 17.46 0.00 17.46 15.20 33.19 0.00 0.00 0.00
April 21.10 0.08 21.02 27.10 26.24 0.00 0.00 0.00
May 24.98 0.69 24.29 37.60 17.65 0.00 0.00 0.00
June 27.20 1.55 25.66 49.93 12.65 0.00 0.00 0.00
July 25.77 1.08 24.69 48.95 10.03 0.00 0.00 0.00
August 23.22 0.22 23.00 45.10 9.03 0.00 0.00 0.00
September 17.60 0.00 17.60 26.18 18.95 0.00 0.00 0.00
October 13.47 0.00 13.47 12.06 37.89 0.00 0.00 0.00
November 11.95 0.00 11.95 6.49 49.16 0.00 0.00 0.00
December 10.31 0.00 10.31 2.26 57.70 0.00 0.00 0.00
                 
Annual Sum or Average 18.08 0.30 17.78 23.43 32.68 0.00 0.00 0.00
Minimum of Months 10.31 0.00 10.31 2.26 9.03 0.00 0.00 0.00
Maximum of Months 27.20 1.55 25.66 49.93 66.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.15 0.00 11.15 2.37 66.88 0.00 0.00 0.00
February 12.42 0.00 12.42 6.88 54.14 0.00 0.00 0.00
March 17.46 0.00 17.46 15.20 33.19 0.00 0.00 0.00
April 21.10 0.08 21.02 27.10 26.24 0.00 0.00 0.00
May 24.98 0.69 24.29 37.60 17.65 0.00 0.00 0.00
June 27.20 1.55 25.66 49.93 12.65 0.00 0.00 0.00
July 25.77 1.08 24.69 48.95 10.03 0.00 0.00 0.00
August 23.22 0.22 23.00 45.10 9.03 0.00 0.00 0.00
September 17.60 0.00 17.60 26.19 18.96 0.00 0.00 0.00
October 13.47 0.00 13.47 12.06 37.89 0.00 0.00 0.00
November 11.95 0.00 11.95 6.49 49.16 0.00 0.00 0.00
December 10.31 0.00 10.31 2.26 57.70 0.00 0.00 0.00
                 
Annual Sum or Average 18.08 0.30 17.78 23.44 32.68 0.00 0.00 0.00
Minimum of Months 10.31 0.00 10.31 2.26 9.03 0.00 0.00 0.00
Maximum of Months 27.20 1.55 25.66 49.93 66.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.15 0.00 11.15 2.37 66.88 0.00 0.00 0.00
February 12.43 0.00 12.43 6.88 54.14 0.00 0.00 0.00
March 17.46 0.00 17.46 15.20 33.19 0.00 0.00 0.00
April 21.13 0.09 21.04 27.15 26.22 0.00 0.00 0.00
May 25.06 0.72 24.34 37.79 17.65 0.00 0.00 0.00
June 27.28 1.58 25.70 50.10 12.65 0.00 0.00 0.00
July 25.84 1.10 24.74 49.13 10.03 0.00 0.00 0.00
August 23.28 0.23 23.05 45.24 9.03 0.00 0.00 0.00
September 17.60 0.00 17.60 26.19 18.96 0.00 0.00 0.00
October 13.47 0.00 13.47 12.06 37.89 0.00 0.00 0.00
November 11.95 0.00 11.95 6.49 49.16 0.00 0.00 0.00
December 10.31 0.00 10.31 2.26 57.70 0.00 0.00 0.00
                 
Annual Sum or Average 18.11 0.31 17.80 23.50 32.68 0.00 0.00 0.00
Minimum of Months 10.31 0.00 10.31 2.26 9.03 0.00 0.00 0.00
Maximum of Months 27.28 1.58 25.70 50.10 66.88 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.38 11.94 13.44 22.37 63.23 0.00 0.00 0.00
February 28.98 13.67 15.30 32.32 52.68 0.00 0.00 0.00
March 42.48 20.61 21.87 55.91 34.20 0.00 0.00 0.00
April 47.27 21.60 25.67 70.59 27.85 0.00 0.00 0.00
May 47.04 17.67 29.37 75.41 19.73 0.00 0.00 0.00
June 49.33 18.75 30.58 87.35 14.62 0.00 0.00 0.00
July 46.51 17.05 29.46 84.15 11.47 0.00 0.00 0.00
August 45.82 17.07 28.74 83.48 10.64 0.00 0.00 0.00
September 37.82 15.86 21.95 60.17 20.22 0.00 0.00 0.00
October 34.02 17.70 16.31 46.11 39.11 0.00 0.00 0.00
November 27.27 12.37 14.90 31.06 49.53 0.00 0.00 0.00
December 22.56 10.01 12.55 20.64 56.49 0.00 0.00 0.00
                 
Annual Sum or Average 37.92 16.20 21.71 55.92 33.21 0.00 0.00 0.00
Minimum of Months 22.56 10.01 12.55 20.64 10.64 0.00 0.00 0.00
Maximum of Months 49.33 21.60 30.58 87.35 63.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.35 11.93 13.42 22.35 63.27 0.00 0.00 0.00
February 28.97 13.67 15.30 32.31 52.68 0.00 0.00 0.00
March 42.48 20.61 21.87 55.91 34.19 0.00 0.00 0.00
April 47.27 21.60 25.67 70.59 27.84 0.00 0.00 0.00
May 47.04 17.67 29.37 75.41 19.73 0.00 0.00 0.00
June 49.33 18.75 30.58 87.35 14.62 0.00 0.00 0.00
July 46.51 17.05 29.46 84.14 11.46 0.00 0.00 0.00
August 45.81 17.07 28.74 83.48 10.64 0.00 0.00 0.00
September 37.82 15.86 21.95 60.17 20.22 0.00 0.00 0.00
October 34.02 17.70 16.31 46.11 39.11 0.00 0.00 0.00
November 27.25 12.36 14.89 31.03 49.53 0.00 0.00 0.00
December 22.52 9.99 12.53 20.57 56.52 0.00 0.00 0.00
                 
Annual Sum or Average 37.91 16.20 21.71 55.91 33.22 0.00 0.00 0.00
Minimum of Months 22.52 9.99 12.53 20.57 10.64 0.00 0.00 0.00
Maximum of Months 49.33 21.60 30.58 87.35 63.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.35 11.93 13.42 22.35 63.27 0.00 0.00 0.00
February 28.97 13.67 15.30 32.31 52.68 0.00 0.00 0.00
March 42.48 20.61 21.87 55.91 34.19 0.00 0.00 0.00
April 47.27 21.60 25.67 70.59 27.84 0.00 0.00 0.00
May 47.04 17.67 29.37 75.41 19.73 0.00 0.00 0.00
June 49.33 18.75 30.58 87.35 14.62 0.00 0.00 0.00
July 46.51 17.05 29.46 84.14 11.46 0.00 0.00 0.00
August 45.81 17.07 28.74 83.48 10.64 0.00 0.00 0.00
September 37.82 15.86 21.95 60.17 20.22 0.00 0.00 0.00
October 34.02 17.70 16.31 46.11 39.11 0.00 0.00 0.00
November 27.25 12.36 14.89 31.03 49.53 0.00 0.00 0.00
December 22.52 9.99 12.53 20.57 56.52 0.00 0.00 0.00
                 
Annual Sum or Average 37.91 16.20 21.71 55.91 33.22 0.00 0.00 0.00
Minimum of Months 22.52 9.99 12.53 20.57 10.64 0.00 0.00 0.00
Maximum of Months 49.33 21.60 30.58 87.35 63.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 25.35 11.93 13.43 22.35 63.27 0.00 0.00 0.00
February 28.97 13.67 15.30 32.31 52.68 0.00 0.00 0.00
March 42.48 20.61 21.87 55.91 34.20 0.00 0.00 0.00
April 47.27 21.60 25.67 70.59 27.85 0.00 0.00 0.00
May 47.04 17.67 29.37 75.41 19.73 0.00 0.00 0.00
June 49.33 18.75 30.58 87.35 14.62 0.00 0.00 0.00
July 46.51 17.05 29.46 84.15 11.47 0.00 0.00 0.00
August 45.82 17.07 28.74 83.48 10.64 0.00 0.00 0.00
September 37.82 15.86 21.95 60.17 20.22 0.00 0.00 0.00
October 34.02 17.70 16.31 46.11 39.11 0.00 0.00 0.00
November 27.25 12.36 14.89 31.03 49.53 0.00 0.00 0.00
December 22.52 9.99 12.53 20.57 56.52 0.00 0.00 0.00
                 
Annual Sum or Average 37.91 16.20 21.71 55.91 33.22 0.00 0.00 0.00
Minimum of Months 22.52 9.99 12.53 20.57 10.64 0.00 0.00 0.00
Maximum of Months 49.33 21.60 30.58 87.35 63.27 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167588E+09 0.118109E+09 49479347.85 0.205399E+09 0.156897E+09
February 0.141158E+09 95730054.89 45427997.60 0.187677E+09 0.121096E+09
March 0.127341E+09 64173711.14 63167084.70 0.179035E+09 91415016.26
April 75625256.81 15841686.65 59783570.15 0.111781E+09 70928892.34
May 63271619.38 1249.52 63270369.86 95990872.67 49700063.83
June 63443099.09 0.22 63443098.87 0.117417E+09 34766524.24
July 64010990.83 157845.97 63853144.86 0.121961E+09 27909699.96
August 68132346.18 4335113.93 63797232.25 0.132543E+09 25622247.44
September 82902802.20 26245422.49 56657379.70 0.138384E+09 51736855.78
October 0.148470E+09 96706110.07 51763552.53 0.221926E+09 0.101991E+09
November 0.157594E+09 0.105772E+09 51822323.90 0.214788E+09 0.122849E+09
December 0.165322E+09 0.117477E+09 47845115.87 0.210586E+09 0.143062E+09
           
Annual Sum or Average 0.132486E+10 0.644549E+09 0.680310E+09 0.193749E+10 0.997975E+09
Minimum of Months 63271619.38 0.22 45427997.60 95990872.67 25622247.44
Maximum of Months 0.167588E+09 0.118109E+09 63853144.86 0.221926E+09 0.156897E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167586E+09 0.118109E+09 49477343.39 0.205397E+09 0.156896E+09
February 0.141156E+09 95730054.89 45426174.48 0.187675E+09 0.121095E+09
March 0.127314E+09 64159938.42 63153900.34 0.178984E+09 91421239.48
April 75361366.10 15723941.54 59637424.56 0.111179E+09 70965238.12
May 63259129.51 0.00 63259129.51 95967607.46 49698827.66
June 63439660.92 0.00 63439660.92 0.117413E+09 34765262.29
July 64004961.36 156622.62 63848338.74 0.121950E+09 27908628.32
August 68043819.79 4311525.93 63732293.87 0.132347E+09 25621009.53
September 82690783.38 26164362.45 56526420.93 0.137905E+09 51749779.00
October 0.148468E+09 96706110.07 51761598.73 0.221924E+09 0.101990E+09
November 0.157592E+09 0.105772E+09 51820337.48 0.214786E+09 0.122848E+09
December 0.165320E+09 0.117477E+09 47843279.03 0.210584E+09 0.143060E+09
           
Annual Sum or Average 0.132424E+10 0.644310E+09 0.679926E+09 0.193611E+10 0.998018E+09
Minimum of Months 63259129.51 0.00 45426174.48 95967607.46 25621009.53
Maximum of Months 0.167586E+09 0.118109E+09 63848338.74 0.221924E+09 0.156896E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167586E+09 0.118109E+09 49477343.39 0.205397E+09 0.156896E+09
February 0.141156E+09 95730054.89 45426174.48 0.187675E+09 0.121095E+09
March 0.127314E+09 64159938.42 63153900.34 0.178984E+09 91421239.48
April 75361366.10 15723941.54 59637424.56 0.111179E+09 70965238.12
May 63259129.51 0.00 63259129.51 95967607.46 49698827.66
June 63439660.92 0.00 63439660.92 0.117413E+09 34765262.29
July 64004961.36 156622.62 63848338.74 0.121950E+09 27908628.32
August 68043529.32 4311255.25 63732274.06 0.132346E+09 25621009.53
September 82668763.98 26161261.69 56507502.28 0.137879E+09 51769663.14
October 0.148468E+09 96706110.07 51761598.73 0.221924E+09 0.101990E+09
November 0.157592E+09 0.105772E+09 51820337.48 0.214786E+09 0.122848E+09
December 0.165320E+09 0.117477E+09 47843279.03 0.210584E+09 0.143060E+09
           
Annual Sum or Average 0.132421E+10 0.644307E+09 0.679907E+09 0.193608E+10 0.998038E+09
Minimum of Months 63259129.51 0.00 45426174.48 95967607.46 25621009.53
Maximum of Months 0.167586E+09 0.118109E+09 63848338.74 0.221924E+09 0.156896E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167586E+09 0.118109E+09 49477343.39 0.205397E+09 0.156896E+09
February 0.141156E+09 95730054.89 45426174.48 0.187675E+09 0.121095E+09
March 0.127314E+09 64159938.42 63153900.34 0.178984E+09 91421239.48
April 75361366.10 15723941.54 59637424.56 0.111179E+09 70965238.12
May 63259129.51 0.00 63259129.51 95967607.46 49698827.66
June 63439660.92 0.00 63439660.92 0.117413E+09 34765262.29
July 64004961.36 156622.62 63848338.74 0.121950E+09 27908628.32
August 68043527.25 4311253.19 63732274.06 0.132346E+09 25621006.43
September 82671501.57 26161256.85 56510244.72 0.137878E+09 51764007.55
October 0.148468E+09 96706110.07 51761598.73 0.221924E+09 0.101990E+09
November 0.157592E+09 0.105772E+09 51820337.48 0.214786E+09 0.122848E+09
December 0.165320E+09 0.117477E+09 47843279.03 0.210584E+09 0.143060E+09
           
Annual Sum or Average 0.132422E+10 0.644307E+09 0.679910E+09 0.193608E+10 0.998032E+09
Minimum of Months 63259129.51 0.00 45426174.48 95967607.46 25621006.43
Maximum of Months 0.167586E+09 0.118109E+09 63848338.74 0.221924E+09 0.156896E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167586E+09 0.118109E+09 49477343.39 0.205397E+09 0.156896E+09
February 0.141156E+09 95730054.89 45426174.48 0.187675E+09 0.121095E+09
March 0.127314E+09 64159938.42 63153900.34 0.178984E+09 91421239.48
April 75361366.10 15723941.54 59637424.56 0.111179E+09 70965238.12
May 63259129.51 0.00 63259129.51 95967607.46 49698827.66
June 63439660.92 0.00 63439660.92 0.117413E+09 34765262.29
July 64004961.36 156622.62 63848338.74 0.121950E+09 27908628.32
August 68043744.16 4311470.10 63732274.06 0.132347E+09 25620969.63
September 82697132.52 26164549.68 56532582.83 0.137883E+09 51714962.67
October 0.148468E+09 96706110.07 51761598.73 0.221924E+09 0.101990E+09
November 0.157592E+09 0.105772E+09 51820337.48 0.214786E+09 0.122848E+09
December 0.165320E+09 0.117477E+09 47843279.03 0.210584E+09 0.143060E+09
           
Annual Sum or Average 0.132424E+10 0.644310E+09 0.679932E+09 0.193609E+10 0.997983E+09
Minimum of Months 63259129.51 0.00 45426174.48 95967607.46 25620969.63
Maximum of Months 0.167586E+09 0.118109E+09 63848338.74 0.221924E+09 0.156896E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.167588E+09 0.118109E+09 49479347.75 0.205399E+09 0.156897E+09
February 0.141158E+09 95730054.89 45427997.50 0.187677E+09 0.121096E+09
March 0.127335E+09 64170669.10 63164103.30 0.179000E+09 91393428.77
April 75610339.89 15838047.94 59772291.95 0.111631E+09 70805352.27
May 63271126.17 1456.43 63269669.74 95990151.34 49700063.76
June 63443110.72 1.52 63443109.20 0.117417E+09 34766524.17
July 64010320.81 157614.46 63852706.35 0.121960E+09 27909699.90
August 68122900.47 4337208.43 63785692.04 0.132531E+09 25622174.70
September 82915999.83 26251957.62 56664042.21 0.138257E+09 51569986.65
October 0.148470E+09 96706110.07 51763552.43 0.221926E+09 0.101991E+09
November 0.157594E+09 0.105772E+09 51822323.80 0.214788E+09 0.122849E+09
December 0.165322E+09 0.117477E+09 47845115.78 0.210586E+09 0.143062E+09
           
Annual Sum or Average 0.132484E+10 0.644551E+09 0.680290E+09 0.193716E+10 0.997662E+09
Minimum of Months 63271126.17 1.52 45427997.50 95990151.34 25622174.70
Maximum of Months 0.167588E+09 0.118109E+09 63852706.35 0.221926E+09 0.156897E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.236051E+09 0.165472E+09 70578978.82 0.289110E+09 0.218367E+09
February 0.198908E+09 0.134119E+09 64789198.32 0.264056E+09 0.168801E+09
March 0.197427E+09 0.103821E+09 93606291.39 0.284438E+09 0.127838E+09
April 0.126040E+09 35463841.22 90576566.45 0.196103E+09 99427970.20
May 97944464.59 3810509.71 94133954.88 0.152690E+09 69931336.94
June 91070628.87 12022.53 91058606.33 0.166694E+09 49228741.66
July 93504521.95 1007216.50 92497305.44 0.176613E+09 39564693.96
August 0.112361E+09 14442796.34 97918165.50 0.219218E+09 36513684.41
September 0.134563E+09 48597088.03 85966257.89 0.228213E+09 72892522.66
October 0.213240E+09 0.138950E+09 74289511.30 0.318825E+09 0.142722E+09
November 0.222038E+09 0.148188E+09 73850201.68 0.302089E+09 0.171788E+09
December 0.232770E+09 0.164586E+09 68184221.79 0.296292E+09 0.199635E+09
           
Annual Sum or Average 0.195592E+10 0.958470E+09 0.997449E+09 0.289434E+10 0.139671E+10
Minimum of Months 91070628.87 12022.53 64789198.32 0.152690E+09 36513684.41
Maximum of Months 0.236051E+09 0.165472E+09 97918165.50 0.318825E+09 0.218367E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 65924770.96 30135469.38 35789301.58 51673331.37 0.161581E+09
February 75172428.95 40727462.79 34444966.17 79691349.90 0.119533E+09
March 0.103449E+09 47131248.16 56318214.38 0.126646E+09 84285187.36
April 0.119769E+09 54179622.65 65589144.50 0.174063E+09 65358275.09
May 0.134844E+09 56471295.11 78372654.70 0.211784E+09 47972666.13
June 0.134775E+09 55819635.90 78955611.16 0.235256E+09 34014824.51
July 0.136349E+09 57059205.19 79290027.69 0.242508E+09 28387948.99
August 0.125111E+09 49439049.54 75672129.23 0.225869E+09 25646455.42
September 0.100566E+09 44736294.46 55829968.02 0.157909E+09 49143735.13
October 89463150.46 46553845.64 42909304.82 0.113713E+09 96614021.34
November 69506862.03 31802652.54 37704209.49 69478878.57 0.118296E+09
December 62413596.67 28846750.53 33566846.14 50526589.54 0.141254E+09
           
Annual Sum or Average 0.121734E+10 0.542903E+09 0.674442E+09 0.173912E+10 0.972087E+09
Minimum of Months 62413596.67 28846750.53 33566846.14 50526589.54 25646455.42
Maximum of Months 0.136349E+09 57059205.19 79290027.69 0.242508E+09 0.161581E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 65922766.61 30135469.38 35787297.23 51672097.22 0.161580E+09
February 75170605.93 40727462.79 34443143.14 79689995.62 0.119532E+09
March 0.103447E+09 47131248.16 56315427.03 0.126643E+09 84283721.69
April 0.119766E+09 54179622.65 65586017.77 0.174060E+09 65356769.08
May 0.134840E+09 56471295.11 78369039.68 0.211779E+09 47971363.70
June 0.134772E+09 55819635.90 78952175.81 0.235251E+09 34013508.80
July 0.136346E+09 57059205.19 79286430.52 0.242504E+09 28386824.24
August 0.125108E+09 49439049.54 75668622.44 0.225864E+09 25645224.48
September 0.100563E+09 44736294.46 55827178.09 0.157906E+09 49142268.84
October 89461196.76 46553845.64 42907351.12 0.113711E+09 96612547.91
November 69504875.71 31802652.54 37702223.17 69477082.15 0.118294E+09
December 62411759.92 28846750.53 33565009.39 50525256.46 0.141253E+09
           
Annual Sum or Average 0.121731E+10 0.542903E+09 0.674410E+09 0.173908E+10 0.972071E+09
Minimum of Months 62411759.92 28846750.53 33565009.39 50525256.46 25645224.48
Maximum of Months 0.136346E+09 57059205.19 79286430.52 0.242504E+09 0.161580E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 65922766.61 30135469.38 35787297.23 51672097.22 0.161580E+09
February 75170605.93 40727462.79 34443143.14 79689995.62 0.119532E+09
March 0.103447E+09 47131248.16 56315427.03 0.126643E+09 84283721.69
April 0.119766E+09 54179622.65 65586017.77 0.174060E+09 65356769.08
May 0.134840E+09 56471295.11 78369039.68 0.211779E+09 47971363.70
June 0.134772E+09 55819635.90 78952175.81 0.235251E+09 34013508.80
July 0.136346E+09 57059205.19 79286430.52 0.242504E+09 28386824.24
August 0.125108E+09 49439049.54 75668622.44 0.225864E+09 25645224.48
September 0.100563E+09 44736294.46 55827178.09 0.157906E+09 49142268.84
October 89461196.76 46553845.64 42907351.12 0.113711E+09 96612547.91
November 69504875.71 31802652.54 37702223.17 69477082.15 0.118294E+09
December 62411759.92 28846750.53 33565009.39 50525256.46 0.141253E+09
           
Annual Sum or Average 0.121731E+10 0.542903E+09 0.674410E+09 0.173908E+10 0.972071E+09
Minimum of Months 62411759.92 28846750.53 33565009.39 50525256.46 25645224.48
Maximum of Months 0.136346E+09 57059205.19 79286430.52 0.242504E+09 0.161580E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 65997192.58 30175681.90 35821510.69 51741395.06 0.161466E+09
February 75180419.27 40732237.87 34448181.40 79703517.36 0.119525E+09
March 0.103449E+09 47131249.91 56318244.95 0.126646E+09 84285148.19
April 0.119769E+09 54179622.65 65589144.66 0.174063E+09 65358275.17
May 0.134844E+09 56471295.11 78372654.89 0.211784E+09 47972666.20
June 0.134775E+09 55819635.90 78955611.33 0.235256E+09 34014824.58
July 0.136349E+09 57059205.19 79290027.88 0.242508E+09 28387949.05
August 0.125111E+09 49439049.54 75672129.41 0.225869E+09 25646455.48
September 0.100566E+09 44736294.46 55829968.16 0.157909E+09 49143735.20
October 89464969.39 46555206.12 42909763.27 0.113718E+09 96613990.23
November 69549080.08 31824289.63 37724790.45 69571152.43 0.118285E+09
December 62510290.86 28898282.27 33612008.60 50676437.54 0.141162E+09
           
Annual Sum or Average 0.121757E+10 0.543022E+09 0.674544E+09 0.173945E+10 0.971861E+09
Minimum of Months 62510290.86 28898282.27 33612008.60 50676437.54 25646455.48
Maximum of Months 0.136349E+09 57059205.19 79290027.88 0.242508E+09 0.161466E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29858458.89 0.00 29858458.89 6338374.54 0.179129E+09
February 30058875.22 0.00 30058875.22 16653832.40 0.130986E+09
March 46764552.98 0.00 46764552.98 40716219.39 88905008.48
April 54770980.85 235560.59 54535420.26 70241404.16 67833627.77
May 67143570.36 1937883.74 65205686.62 0.101203E+09 47222578.05
June 70707968.97 4101721.96 66606247.02 0.129876E+09 32797719.50
July 69242681.67 2980113.72 66262567.95 0.131668E+09 26857461.99
August 62355177.95 631115.59 61724062.37 0.121173E+09 24187591.35
September 45629841.70 6248.62 45623593.08 67864969.21 49117097.32
October 36075149.09 0.00 36075149.09 32312601.53 0.101493E+09
November 30977747.97 0.00 30977747.97 16818479.06 0.127427E+09
December 27616552.75 0.00 27616552.75 6047039.76 0.154551E+09
           
Annual Sum or Average 0.571202E+09 9892644.22 0.561309E+09 0.740914E+09 0.103051E+10
Minimum of Months 27616552.75 0.00 27616552.75 6047039.76 24187591.35
Maximum of Months 70707968.97 4101721.96 66606247.02 0.131668E+09 0.179129E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29856454.44 0.00 29856454.44 6337514.47 0.179129E+09
February 30057052.09 0.00 30057052.09 16652500.44 0.130985E+09
March 46761765.49 0.00 46761765.49 40713343.98 88903657.93
April 54701359.92 220504.16 54480855.77 70235292.34 67979369.83
May 66910554.99 1844639.00 65065915.99 0.100715E+09 47280222.85
June 70514018.11 4015587.94 66498430.17 0.129417E+09 32796557.25
July 69009234.47 2879552.58 66129681.89 0.131110E+09 26856570.33
August 62187568.88 580754.45 61606814.43 0.120790E+09 24187800.29
September 45626603.34 6228.73 45620374.60 67861785.44 49116955.28
October 36073195.29 0.00 36073195.29 32310852.87 0.101491E+09
November 30975761.55 0.00 30975761.55 16816867.25 0.127426E+09
December 27614715.91 0.00 27614715.91 6046012.58 0.154550E+09
           
Annual Sum or Average 0.570288E+09 9547266.86 0.560741E+09 0.739005E+09 0.103070E+10
Minimum of Months 27614715.91 0.00 27614715.91 6046012.58 24187800.29
Maximum of Months 70514018.11 4015587.94 66498430.17 0.131110E+09 0.179129E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29856454.44 0.00 29856454.44 6337514.47 0.179129E+09
February 30057052.09 0.00 30057052.09 16652500.44 0.130985E+09
March 46761765.49 0.00 46761765.49 40713343.98 88903657.93
April 54688484.50 217588.21 54470896.29 70235083.00 68008512.69
May 66910554.99 1844639.00 65065915.99 0.100715E+09 47280222.85
June 70514018.11 4015587.94 66498430.17 0.129417E+09 32796557.25
July 69009234.47 2879552.58 66129681.89 0.131110E+09 26856570.33
August 62187032.34 580760.65 61606271.69 0.120791E+09 24189580.64
September 45625148.33 6122.93 45619025.41 67865417.70 49123513.25
October 36073195.29 0.00 36073195.29 32310852.87 0.101491E+09
November 30975761.55 0.00 30975761.55 16816867.25 0.127426E+09
December 27614715.91 0.00 27614715.91 6046012.58 0.154550E+09
           
Annual Sum or Average 0.570273E+09 9544251.30 0.560729E+09 0.739009E+09 0.103074E+10
Minimum of Months 27614715.91 0.00 27614715.91 6046012.58 24189580.64
Maximum of Months 70514018.11 4015587.94 66498430.17 0.131110E+09 0.179129E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29856454.44 0.00 29856454.44 6337514.47 0.179129E+09
February 30057052.09 0.00 30057052.09 16652500.44 0.130985E+09
March 46761765.49 0.00 46761765.49 40713343.98 88903657.93
April 54688484.50 217588.21 54470896.29 70235083.00 68008512.69
May 66910554.99 1844639.00 65065915.99 0.100715E+09 47280222.85
June 70514018.11 4015587.94 66498430.17 0.129417E+09 32796557.25
July 69009234.47 2879552.58 66129681.89 0.131110E+09 26856570.33
August 62187612.63 580773.37 61606839.26 0.120794E+09 24191550.50
September 45625785.48 6106.04 45619679.43 67871153.07 49128321.30
October 36073195.29 0.00 36073195.29 32310852.87 0.101491E+09
November 30975761.55 0.00 30975761.55 16816867.25 0.127426E+09
December 27614715.91 0.00 27614715.91 6046012.58 0.154550E+09
           
Annual Sum or Average 0.570275E+09 9544247.14 0.560730E+09 0.739018E+09 0.103075E+10
Minimum of Months 27614715.91 0.00 27614715.91 6046012.58 24191550.50
Maximum of Months 70514018.11 4015587.94 66498430.17 0.131110E+09 0.179129E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29856454.44 0.00 29856454.44 6337514.47 0.179129E+09
February 30057052.09 0.00 30057052.09 16652500.44 0.130985E+09
March 46761765.49 0.00 46761765.49 40713343.98 88903657.93
April 54699998.39 220288.29 54479710.10 70255522.63 68002987.09
May 66910554.99 1844639.00 65065915.99 0.100715E+09 47280222.85
June 70514018.11 4015587.94 66498430.17 0.129417E+09 32796557.25
July 69009234.47 2879552.58 66129681.89 0.131110E+09 26856570.33
August 62188417.43 580791.32 61607626.11 0.120797E+09 24193272.12
September 45626979.42 6139.43 45620839.99 67877170.42 49132099.34
October 36073195.29 0.00 36073195.29 32310852.87 0.101491E+09
November 30975761.55 0.00 30975761.55 16816867.25 0.127426E+09
December 27614715.91 0.00 27614715.91 6046012.58 0.154550E+09
           
Annual Sum or Average 0.570288E+09 9546998.55 0.560741E+09 0.739048E+09 0.103075E+10
Minimum of Months 27614715.91 0.00 27614715.91 6046012.58 24193272.12
Maximum of Months 70514018.11 4015587.94 66498430.17 0.131110E+09 0.179129E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 29858458.79 0.00 29858458.79 6338374.49 0.179129E+09
February 30058875.12 0.00 30058875.12 16653832.33 0.130986E+09
March 46764552.83 0.00 46764552.83 40716219.24 88905008.41
April 54775524.76 236614.94 54538909.82 70384537.97 67969851.16
May 67128347.19 1926449.99 65201897.20 0.101220E+09 47281415.27
June 70704149.42 4094484.04 66609665.38 0.129856E+09 32797719.43
July 69217787.95 2954448.33 66263339.61 0.131587E+09 26857680.05
August 62353295.99 626714.88 61726581.11 0.121165E+09 24194515.32
September 45630710.79 6153.13 45624557.66 67882593.03 49133746.83
October 36075148.99 0.00 36075148.99 32312601.44 0.101493E+09
November 30977747.87 0.00 30977747.87 16818478.97 0.127427E+09
December 27616552.65 0.00 27616552.65 6047039.71 0.154551E+09
           
Annual Sum or Average 0.571161E+09 9844865.32 0.561316E+09 0.740982E+09 0.103073E+10
Minimum of Months 27616552.65 0.00 27616552.65 6047039.71 24194515.32
Maximum of Months 70704149.42 4094484.04 66609665.38 0.131587E+09 0.179129E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67976074.45 31987527.74 35988546.71 59925964.94 0.169366E+09
February 70101915.23 33079084.95 37022830.27 78183466.12 0.127443E+09
March 0.113784E+09 55206550.11 58577416.18 0.149758E+09 91588024.42
April 0.122527E+09 55992998.48 66533926.49 0.182976E+09 72175005.49
May 0.125985E+09 47316269.98 78668517.73 0.201985E+09 52833696.89
June 0.127867E+09 48602968.17 79263887.80 0.226418E+09 37892462.41
July 0.124574E+09 45675756.70 78898490.49 0.225376E+09 30708744.00
August 0.122711E+09 45726754.88 76984160.68 0.223596E+09 28493603.96
September 98019444.74 41121843.41 56897601.33 0.155963E+09 52421993.89
October 91110818.15 47413293.70 43697524.45 0.123513E+09 0.104749E+09
November 70679630.44 32063989.35 38615641.09 80508210.73 0.128371E+09
December 60412493.23 26808800.80 33603692.43 55269567.57 0.151311E+09
           
Annual Sum or Average 0.119575E+10 0.510996E+09 0.684752E+09 0.176347E+10 0.104735E+10
Minimum of Months 60412493.23 26808800.80 33603692.43 55269567.57 28493603.96
Maximum of Months 0.127867E+09 55992998.48 79263887.80 0.226418E+09 0.169366E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67905777.51 31949059.29 35956718.22 59851928.85 0.169464E+09
February 70092658.99 33075121.57 37017537.43 78168210.18 0.127446E+09
March 0.113781E+09 55206549.18 58574544.45 0.149754E+09 91586662.34
April 0.122524E+09 55992998.48 66530799.76 0.182972E+09 72173662.54
May 0.125981E+09 47316269.98 78664902.71 0.201980E+09 52832500.12
June 0.127863E+09 48602968.17 79260452.45 0.226414E+09 37891204.74
July 0.124571E+09 45675756.70 78894893.31 0.225372E+09 30707624.57
August 0.122707E+09 45726754.88 76980653.90 0.223591E+09 28492336.91
September 98016654.82 41121843.41 56894811.40 0.155960E+09 52420549.43
October 91107194.34 47411997.89 43695196.45 0.123507E+09 0.104748E+09
November 70637792.16 32045167.10 38592625.06 80421579.10 0.128379E+09
December 60316636.62 26758468.04 33558168.58 55100134.05 0.151375E+09
           
Annual Sum or Average 0.119550E+10 0.510883E+09 0.684621E+09 0.176309E+10 0.104752E+10
Minimum of Months 60316636.62 26758468.04 33558168.58 55100134.05 28492336.91
Maximum of Months 0.127863E+09 55992998.48 79260452.45 0.226414E+09 0.169464E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67905777.51 31949059.29 35956718.22 59851928.85 0.169464E+09
February 70092658.99 33075121.57 37017537.43 78168210.18 0.127446E+09
March 0.113781E+09 55206549.18 58574544.45 0.149754E+09 91586662.34
April 0.122524E+09 55992998.48 66530799.76 0.182972E+09 72173662.54
May 0.125981E+09 47316269.98 78664902.71 0.201980E+09 52832500.12
June 0.127863E+09 48602968.17 79260452.45 0.226414E+09 37891204.74
July 0.124571E+09 45675756.70 78894893.31 0.225372E+09 30707624.57
August 0.122707E+09 45726754.88 76980653.90 0.223591E+09 28492336.91
September 98016654.82 41121843.41 56894811.40 0.155960E+09 52420549.43
October 91107194.34 47411997.89 43695196.45 0.123507E+09 0.104748E+09
November 70637792.16 32045167.10 38592625.06 80421579.10 0.128379E+09
December 60316636.62 26758468.04 33558168.58 55100134.05 0.151375E+09
           
Annual Sum or Average 0.119550E+10 0.510883E+09 0.684621E+09 0.176309E+10 0.104752E+10
Minimum of Months 60316636.62 26758468.04 33558168.58 55100134.05 28492336.91
Maximum of Months 0.127863E+09 55992998.48 79260452.45 0.226414E+09 0.169464E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 67907781.97 31949059.29 35958722.68 59853036.70 0.169464E+09
February 70094482.11 33075121.57 37019360.55 78169686.42 0.127447E+09
March 0.113784E+09 55206549.18 58577331.94 0.149757E+09 91588024.49
April 0.122527E+09 55992998.48 66533926.65 0.182976E+09 72175005.56
May 0.125985E+09 47316269.98 78668517.92 0.201985E+09 52833696.95
June 0.127867E+09 48602968.17 79263887.98 0.226418E+09 37892462.47
July 0.124574E+09 45675756.70 78898490.68 0.225376E+09 30708744.06
August 0.122711E+09 45726754.88 76984160.86 0.223596E+09 28493604.03
September 98019444.88 41121843.41 56897601.47 0.155963E+09 52421993.96
October 91109148.14 47411997.89 43697150.26 0.123509E+09 0.104750E+09
November 70639778.58 32045167.10 38594611.48 80423253.59 0.128380E+09
December 60318473.46 26758468.04 33560005.42 55101330.55 0.151376E+09
           
Annual Sum or Average 0.119554E+10 0.510883E+09 0.684654E+09 0.176313E+10 0.104753E+10
Minimum of Months 60318473.46 26758468.04 33560005.42 55101330.55 28493604.03
Maximum of Months 0.127867E+09 55992998.48 79263887.98 0.226418E+09 0.169464E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 568.06 433.00 463.55 326.36 137.19 0.00 0.00
February 574.61 370.11 432.31 292.87 139.45 0.00 0.00
March 507.16 252.51 358.93 182.50 176.43 0.00 0.00
April 333.39 202.52 223.27 50.17 173.10 0.00 0.00
May 272.01 137.44 178.29 1.42 176.86 0.00 0.00
June 336.10 99.47 181.99 0.00 181.98 0.00 0.00
July 339.13 77.29 178.30 0.73 177.57 0.00 0.00
August 378.46 71.03 194.44 15.07 179.37 0.00 0.00
September 407.54 147.81 243.48 79.38 164.11 0.00 0.00
October 616.18 281.76 412.21 268.51 143.69 0.00 0.00
November 613.74 350.65 450.46 302.01 148.45 0.00 0.00
December 582.36 395.01 457.25 324.61 132.63 0.00 0.00
               
Annual Sum or Average 460.21 234.15 314.01 152.99 161.01 0.00 0.00
Minimum of Months 272.01 71.03 178.29 0.00 132.63 0.00 0.00
Maximum of Months 616.18 433.00 463.55 326.36 181.98 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 77.19 241.26 98.48 45.02 53.46 0.00 0.00
February 131.77 197.64 124.29 67.34 56.95 0.00 0.00
March 189.13 125.87 154.49 70.39 84.11 0.00 0.00
April 268.61 100.86 184.83 83.61 101.22 0.00 0.00
May 316.28 71.64 201.38 84.34 117.04 0.00 0.00
June 363.05 52.49 207.98 86.14 121.84 0.00 0.00
July 362.17 42.39 203.63 85.21 118.41 0.00 0.00
August 337.32 38.30 186.84 73.83 113.01 0.00 0.00
September 243.68 75.84 155.19 69.04 86.16 0.00 0.00
October 169.82 144.29 133.61 69.53 64.08 0.00 0.00
November 107.25 182.55 107.28 49.09 58.19 0.00 0.00
December 75.51 210.92 93.24 43.10 50.15 0.00 0.00
               
Annual Sum or Average 220.60 123.29 154.41 68.87 85.55 0.00 0.00
Minimum of Months 75.51 38.30 93.24 43.10 50.15 0.00 0.00
Maximum of Months 363.05 241.26 207.98 86.14 121.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 14.20 401.27 66.88 0.00 66.88 0.00 0.00
February 41.30 324.86 74.55 0.00 74.55 0.00 0.00
March 91.21 199.16 104.76 0.00 104.76 0.00 0.00
April 162.65 157.33 126.67 0.52 126.15 0.00 0.00
May 225.99 105.89 150.06 4.20 145.86 0.00 0.00
June 299.92 75.92 163.38 9.36 154.02 0.00 0.00
July 294.09 60.16 154.76 6.52 148.24 0.00 0.00
August 270.87 54.19 139.43 1.34 138.10 0.00 0.00
September 157.11 113.72 105.62 0.01 105.60 0.00 0.00
October 72.38 227.36 80.81 0.00 80.81 0.00 0.00
November 38.93 294.97 71.70 0.00 71.70 0.00 0.00
December 13.54 346.22 61.86 0.00 61.86 0.00 0.00
               
Annual Sum or Average 140.73 196.10 108.56 1.84 106.72 0.00 0.00
Minimum of Months 13.54 54.19 61.86 0.00 61.86 0.00 0.00
Maximum of Months 299.92 401.27 163.38 9.36 154.02 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 89.41 253.05 101.44 47.73 53.71 0.00 0.00
February 129.25 210.72 115.90 54.69 61.21 0.00 0.00
March 223.65 136.78 169.93 82.45 87.48 0.00 0.00
April 282.37 111.38 189.08 86.41 102.67 0.00 0.00
May 301.65 78.90 188.15 70.66 117.48 0.00 0.00
June 349.41 58.48 197.32 75.00 122.32 0.00 0.00
July 336.58 45.86 186.04 68.21 117.83 0.00 0.00
August 333.92 42.55 183.26 68.29 114.97 0.00 0.00
September 240.68 80.90 151.26 63.46 87.80 0.00 0.00
October 184.45 156.44 136.06 70.81 65.26 0.00 0.00
November 124.14 198.11 109.03 49.46 59.57 0.00 0.00
December 82.35 226.04 90.12 39.98 50.13 0.00 0.00
               
Annual Sum or Average 223.64 132.86 151.65 64.80 86.84 0.00 0.00
Minimum of Months 82.35 42.55 90.12 39.98 50.13 0.00 0.00
Maximum of Months 349.41 253.05 197.32 86.41 122.32 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.152148E+10 0.115973E+10 0.124157E+10 0.874126E+09 0.367447E+09 0.00 0.00
February 0.139010E+10 0.895368E+09 0.104585E+10 0.708499E+09 0.337350E+09 0.00 0.00
March 0.135839E+10 0.676310E+09 0.961358E+09 0.488805E+09 0.472553E+09 0.00 0.00
April 0.864151E+09 0.524942E+09 0.578721E+09 0.130039E+09 0.448682E+09 0.00 0.00
May 0.728538E+09 0.368123E+09 0.477524E+09 3813215.65 0.473711E+09 0.00 0.00
June 0.871179E+09 0.257821E+09 0.471715E+09 12024.27 0.471703E+09 0.00 0.00
July 0.908330E+09 0.207015E+09 0.477546E+09 1949167.42 0.475597E+09 0.00 0.00
August 0.101368E+10 0.190240E+09 0.520791E+09 40360623.16 0.480430E+09 0.00 0.00
September 0.105633E+10 0.383134E+09 0.631110E+09 0.205746E+09 0.425364E+09 0.00 0.00
October 0.165037E+10 0.754657E+09 0.110405E+10 0.719187E+09 0.384863E+09 0.00 0.00
November 0.159081E+10 0.908872E+09 0.116760E+10 0.782820E+09 0.384776E+09 0.00 0.00
December 0.155979E+10 0.105799E+10 0.122469E+10 0.869446E+09 0.355248E+09 0.00 0.00
               
Annual Sum or Average 0.145131E+11 0.738421E+10 0.990253E+10 0.482480E+10 0.507772E+10 0.00 0.00
Minimum of Months 0.728538E+09 0.190240E+09 0.471715E+09 12024.27 0.337350E+09 0.00 0.00
Maximum of Months 0.165037E+10 0.115973E+10 0.124157E+10 0.874126E+09 0.480430E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.206753E+09 0.646202E+09 0.263767E+09 0.120582E+09 0.143185E+09 0.00 0.00
February 0.318775E+09 0.478121E+09 0.300694E+09 0.162915E+09 0.137779E+09 0.00 0.00
March 0.506578E+09 0.337138E+09 0.413792E+09 0.188525E+09 0.225267E+09 0.00 0.00
April 0.696246E+09 0.261430E+09 0.479069E+09 0.216718E+09 0.262350E+09 0.00 0.00
May 0.847126E+09 0.191888E+09 0.539369E+09 0.225885E+09 0.313483E+09 0.00 0.00
June 0.941015E+09 0.136057E+09 0.539094E+09 0.223279E+09 0.315816E+09 0.00 0.00
July 0.970024E+09 0.113550E+09 0.545390E+09 0.228237E+09 0.317153E+09 0.00 0.00
August 0.903465E+09 0.102583E+09 0.500438E+09 0.197756E+09 0.302682E+09 0.00 0.00
September 0.631630E+09 0.196572E+09 0.402259E+09 0.178945E+09 0.223314E+09 0.00 0.00
October 0.454854E+09 0.386453E+09 0.357851E+09 0.186217E+09 0.171634E+09 0.00 0.00
November 0.278004E+09 0.473169E+09 0.278066E+09 0.127232E+09 0.150833E+09 0.00 0.00
December 0.202247E+09 0.564916E+09 0.249747E+09 0.115439E+09 0.134309E+09 0.00 0.00
               
Annual Sum or Average 0.695672E+10 0.388808E+10 0.486954E+10 0.217173E+10 0.269781E+10 0.00 0.00
Minimum of Months 0.202247E+09 0.102583E+09 0.249747E+09 0.115439E+09 0.134309E+09 0.00 0.00
Maximum of Months 0.970024E+09 0.646202E+09 0.545390E+09 0.228237E+09 0.317153E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 38026806.90 0.107477E+10 0.179143E+09 0.00 0.179143E+09 0.00 0.00
February 99917666.51 0.785909E+09 0.180346E+09 0.00 0.180346E+09 0.00 0.00
March 0.244286E+09 0.533425E+09 0.280576E+09 0.00 0.280576E+09 0.00 0.00
April 0.421587E+09 0.407803E+09 0.328325E+09 1348144.40 0.326977E+09 0.00 0.00
May 0.605279E+09 0.283621E+09 0.401914E+09 11242889.72 0.390671E+09 0.00 0.00
June 0.777399E+09 0.196782E+09 0.423468E+09 24258557.75 0.399210E+09 0.00 0.00
July 0.787693E+09 0.161141E+09 0.414497E+09 17452772.37 0.397045E+09 0.00 0.00
August 0.725507E+09 0.145143E+09 0.373459E+09 3580910.26 0.369878E+09 0.00 0.00
September 0.407223E+09 0.294752E+09 0.273765E+09 36998.89 0.273728E+09 0.00 0.00
October 0.193869E+09 0.608950E+09 0.216443E+09 0.00 0.216443E+09 0.00 0.00
November 0.100904E+09 0.764557E+09 0.185859E+09 0.00 0.185859E+09 0.00 0.00
December 36278129.79 0.927303E+09 0.165692E+09 0.00 0.165692E+09 0.00 0.00
               
Annual Sum or Average 0.443797E+10 0.618416E+10 0.342349E+10 57920273.39 0.336557E+10 0.00 0.00
Minimum of Months 36278129.79 0.145143E+09 0.165692E+09 0.00 0.165692E+09 0.00 0.00
Maximum of Months 0.787693E+09 0.107477E+10 0.423468E+09 24258557.75 0.399210E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.239482E+09 0.677757E+09 0.271695E+09 0.127835E+09 0.143861E+09 0.00 0.00
February 0.312690E+09 0.509781E+09 0.280382E+09 0.132304E+09 0.148077E+09 0.00 0.00
March 0.599024E+09 0.366349E+09 0.455130E+09 0.220826E+09 0.234304E+09 0.00 0.00
April 0.731897E+09 0.288697E+09 0.490101E+09 0.223972E+09 0.266129E+09 0.00 0.00
May 0.807929E+09 0.211332E+09 0.503932E+09 0.189265E+09 0.314667E+09 0.00 0.00
June 0.905663E+09 0.151567E+09 0.511461E+09 0.194412E+09 0.317049E+09 0.00 0.00
July 0.901495E+09 0.122833E+09 0.498290E+09 0.182703E+09 0.315587E+09 0.00 0.00
August 0.894373E+09 0.113972E+09 0.490837E+09 0.182907E+09 0.307930E+09 0.00 0.00
September 0.623845E+09 0.209685E+09 0.392072E+09 0.164487E+09 0.227585E+09 0.00 0.00
October 0.494037E+09 0.418996E+09 0.364434E+09 0.189649E+09 0.174785E+09 0.00 0.00
November 0.321775E+09 0.513509E+09 0.282595E+09 0.128199E+09 0.154396E+09 0.00 0.00
December 0.220561E+09 0.605426E+09 0.241364E+09 0.107084E+09 0.134280E+09 0.00 0.00
               
Annual Sum or Average 0.705277E+10 0.418990E+10 0.478229E+10 0.204364E+10 0.273865E+10 0.00 0.00
Minimum of Months 0.220561E+09 0.113972E+09 0.241364E+09 0.107084E+09 0.134280E+09 0.00 0.00
Maximum of Months 0.905663E+09 0.677757E+09 0.511461E+09 0.223972E+09 0.317049E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.584980E+09 -459998739.5 0.00 0.00 744.00 0.00 -124980777.9 58.99 0.00 0.00
February 0.526718E+09 -417142354.6 0.00 0.00 672.00 0.00 -109575738.1 58.99 0.00 0.00
March 0.602929E+09 -487604953.9 0.00 0.00 744.00 0.00 -115324286.8 58.99 0.00 0.00
April 0.506363E+09 -397146624.3 0.00 0.00 720.00 0.00 -109216773.5 58.98 0.00 0.00
May 0.512856E+09 -402368842.7 0.00 0.00 744.00 0.00 -110487307.9 58.99 0.00 0.00
June 0.474161E+09 -369232906.1 0.00 0.00 720.00 0.00 -104928254.6 58.99 0.00 0.00
July 0.425399E+09 -318346846.2 0.00 0.00 744.00 0.00 -107052597.8 58.99 0.00 0.00
August 0.472398E+09 -365188997.4 0.00 0.00 744.00 0.00 -107209471.9 58.99 0.00 0.00
September 0.438221E+09 -333313481.6 0.00 0.00 720.00 0.00 -104907413.1 58.99 0.00 0.00
October 0.489662E+09 -378593403.6 0.00 0.00 744.00 0.00 -111069036.8 58.99 0.00 0.00
November 0.522482E+09 -412043767.1 0.00 0.00 720.00 0.00 -110438350.8 58.99 0.00 0.00
December 0.540169E+09 -420553378.4 0.00 0.00 744.00 0.00 -119616062.7 58.99 0.00 0.00
                     
Annual Sum or Average 0.609634E+10 -0.476153E+10 0.00 0.00 8760.00 0.00 -0.133481E+10 58.99 0.00 0.00
Minimum of Months 0.425399E+09 -487604953.9 0.00 0.00 672.00 0.00 -124980777.9 58.98 0.00 0.00
Maximum of Months 0.602929E+09 -318346846.2 0.00 0.00 744.00 0.00 -104907413.1 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.77 0.73 01-JAN-11:09 1357.39 25.32 140.33 210.00 590.81 23.33 162.50 172.33
February 263.00 0.78 0.73 01-FEB-13:50 2244.30 26.36 138.50 188.67 425.11 20.52 114.50 146.50
March 351.67 0.78 0.73 01-MAR-12:39 457.91 17.12 4.00 221.83 354.18 21.27 180.83 172.33
April 369.33 0.79 0.73 01-APR-11:20 355.06 16.49 0.00 176.33 263.15 20.67 173.17 88.17
May 407.00 0.79 0.73 01-MAY-09:50 322.23 16.47 0.00 179.50 234.41 20.67 204.17 32.17
June 411.67 0.80 0.73 01-JUN-10:39 304.25 16.14 0.00 156.67 222.79 20.35 186.83 18.50
July 411.00 0.80 0.73 01-JUL-09:20 320.53 16.35 0.00 186.33 233.24 20.53 209.50 30.33
August 390.50 0.78 0.73 01-AUG-10:09 387.05 17.15 0.00 233.83 279.81 21.33 251.83 117.83
September 298.50 0.78 0.73 01-SEP-09:09 428.52 17.45 6.50 187.00 315.42 21.28 183.50 129.17
October 293.50 0.77 0.73 01-OCT-10:00 1314.52 23.32 113.50 231.67 417.05 20.93 131.67 164.67
November 299.00 0.77 0.73 01-NOV-09:39 1384.30 25.62 148.50 221.50 515.58 25.66 243.67 191.67
December 285.17 0.76 0.73 01-DEC-07:00 897.31 23.99 112.33 206.00 655.95 24.66 190.67 169.50
                         
Annual Sum or Average 4071.00 0.78     736.86 19.58 663.67 2399.33 357.48 21.63 2232.83 1433.17
Minimum of Months 263.00 0.76 0.73   304.25 16.14 0.00 156.67 222.79 20.35 114.50 18.50
Maximum of Months 411.67 0.80 0.73   2244.30 26.36 148.50 233.83 655.95 25.66 251.83 191.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.84 0.73 04-JAN-08:00 602.68 17.22 49.33 75.83 344.14 20.95 89.33 46.33
February 263.00 0.84 0.73 02-FEB-08:20 847.84 16.92 41.00 76.00 526.03 21.06 68.50 51.33
March 351.67 0.83 0.73 02-MAR-08:50 308.16 14.70 1.83 109.33 244.97 19.40 86.50 68.50
April 369.33 0.82 0.73 02-APR-09:30 320.47 14.58 0.00 123.50 266.04 19.50 94.33 93.17
May 407.00 0.81 0.73 01-MAY-08:20 337.86 15.14 0.00 146.83 285.17 20.04 133.33 111.00
June 411.67 0.81 0.73 01-JUN-07:19 335.62 15.08 0.00 141.83 285.87 20.00 133.33 114.83
July 411.00 0.81 0.73 01-JUL-06:19 343.43 15.20 0.00 145.33 293.06 20.13 145.17 115.83
August 390.50 0.80 0.73 01-AUG-06:00 354.39 15.50 0.00 148.83 292.61 20.32 152.67 106.83
September 298.50 0.82 0.73 01-SEP-08:09 332.58 14.83 0.67 102.33 273.27 19.64 91.17 77.50
October 293.50 0.83 0.73 01-OCT-11:20 1015.95 16.86 45.33 95.67 250.31 18.74 57.33 68.50
November 299.00 0.83 0.73 01-NOV-09:39 700.17 17.49 54.83 80.83 527.37 22.95 105.83 59.67
December 285.17 0.83 0.73 01-DEC-08:09 813.16 19.63 76.83 83.50 402.56 22.25 90.83 47.17
                         
Annual Sum or Average 4071.00 0.82     495.90 15.94 269.83 1329.83 323.94 20.34 1248.33 960.67
Minimum of Months 263.00 0.80 0.73   308.16 14.58 0.00 75.83 244.97 18.74 57.33 46.33
Maximum of Months 411.67 0.84 0.73   1015.95 19.63 76.83 148.83 527.37 22.95 152.67 115.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.91 0.82 30-JAN-14:30 124.38 12.15 0.00 0.00 90.37 16.19 0.00 0.00
February 263.00 0.91 0.80 22-FEB-11:30 132.90 12.29 0.00 0.00 97.19 16.29 0.00 0.00
March 351.67 0.88 0.74 29-MAR-10:30 172.17 14.12 0.00 0.00 123.25 18.00 0.00 0.00
April 369.33 0.85 0.74 24-APR-09:30 208.71 15.11 0.00 0.00 145.59 18.86 0.00 0.00
May 407.00 0.81 0.74 30-MAY-15:30 263.73 16.31 0.00 25.50 179.73 20.12 44.83 0.00
June 411.67 0.80 0.73 28-JUN-16:30 286.82 16.56 0.00 70.83 202.51 21.63 137.67 5.33
July 411.00 0.80 0.73 12-JUL-09:20 282.34 16.50 0.00 52.83 194.88 21.32 114.00 1.33
August 390.50 0.81 0.74 09-AUG-09:30 263.81 16.24 0.00 18.33 177.96 19.98 36.17 0.00
September 298.50 0.86 0.74 05-SEP-11:30 196.90 14.85 0.00 0.00 138.54 18.61 0.00 0.00
October 293.50 0.90 0.74 02-OCT-12:20 139.97 12.71 0.00 0.00 103.58 16.78 0.00 0.00
November 299.00 0.91 0.82 10-NOV-14:30 129.87 12.46 0.00 0.00 94.63 16.44 0.00 0.00
December 285.17 0.92 0.84 28-DEC-12:30 120.47 12.20 0.00 0.00 88.28 16.32 0.00 0.00
                         
Annual Sum or Average 4071.00 0.86     202.96 14.56 0.00 167.50 142.54 18.67 332.67 6.67
Minimum of Months 263.00 0.80 0.73   120.47 12.15 0.00 0.00 88.28 16.19 0.00 0.00
Maximum of Months 411.67 0.92 0.84   286.82 16.56 0.00 70.83 202.51 21.63 137.67 5.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.84 0.73 04-JAN-13:00 976.35 19.24 74.50 85.67 572.49 22.87 104.83 51.50
February 263.00 0.84 0.73 01-FEB-14:20 300.04 14.05 0.00 89.33 404.11 21.15 97.83 65.50
March 351.67 0.82 0.73 01-MAR-13:30 332.96 14.99 0.00 125.33 268.14 19.65 108.17 85.00
April 369.33 0.82 0.73 01-APR-14:09 325.17 14.87 0.00 131.50 268.72 19.62 105.83 88.83
May 407.00 0.81 0.73 01-MAY-13:20 331.81 15.38 0.00 141.17 276.13 20.14 147.17 102.83
June 411.67 0.81 0.73 01-JUN-13:09 331.71 15.31 0.00 140.33 279.23 20.11 144.67 107.50
July 411.00 0.81 0.73 01-JUL-14:09 334.06 15.36 0.00 138.50 279.19 20.12 149.00 106.00
August 390.50 0.81 0.73 01-AUG-13:09 360.61 15.79 0.00 156.83 295.06 20.48 164.00 114.83
September 298.50 0.82 0.73 01-SEP-13:39 345.38 15.33 3.17 112.17 276.89 19.95 108.33 82.33
October 293.50 0.83 0.73 01-OCT-12:30 964.99 17.18 49.17 98.50 267.04 19.03 74.50 66.17
November 299.00 0.83 0.73 01-NOV-13:09 695.18 17.72 55.33 87.50 454.14 22.88 109.17 63.83
December 285.17 0.84 0.73 01-DEC-13:50 771.42 19.48 77.33 76.33 393.53 22.31 92.00 47.50
                         
Annual Sum or Average 4071.00 0.82     482.38 16.11 259.50 1383.17 327.33 20.60 1405.50 981.83
Minimum of Months 263.00 0.81 0.73   300.04 14.05 0.00 76.33 267.04 19.03 74.50 47.50
Maximum of Months 411.67 0.84 0.73   976.35 19.48 77.33 156.83 572.49 22.88 164.00 114.83



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.783592E+09 7349.08 19-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.320487E+09 6336.73 08-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 4150536.18 774.32 20-MAR-05:17 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 1651688.63 411.30 22-NOV-06:40 0.00 0.00 0.00 0.00 0.00
December 0.119621E+09 5550.85 26-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122950E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.783592E+09 7349.08   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.168171E+10 7225.57 19-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.104560E+10 6852.03 16-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.314694E+09 6565.64 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.156171E+09 5755.14 27-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 12985995.96 1703.61 11-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 39208475.12 3196.16 26-OCT-06:50 0.00 0.00 0.00 0.00 0.00
November 0.151132E+09 3607.99 21-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.550591E+09 5887.37 29-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.395209E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168171E+10 7225.57   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.100250E+10 5029.54 19-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.577963E+09 4769.53 16-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.101365E+09 4570.19 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 28996660.77 3788.20 07-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 3011089.50 391.75 26-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 28569969.46 4464.56 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.269599E+09 4475.61 06-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.201200E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.100250E+10 5029.54   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.201327E+10 7101.96 19-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.120256E+10 6734.81 16-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.239084E+09 6940.83 24-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 69752737.81 6397.78 10-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 6575211.92 754.26 26-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 95072182.39 6397.78 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.637749E+09 6319.78 06-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.426406E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.201327E+10 7101.96   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.106615E+10 5655.49 19-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.621893E+09 5363.12 16-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 91887675.46 5138.96 27-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 26661051.68 4259.66 07-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 1066232.39 192.34 26-OCT-06:00 0.00 0.00 0.00 0.00 0.00
November 34026107.20 4589.64 24-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.300379E+09 4990.48 06-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.214206E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106615E+10 5655.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 34132540.35 3490.52 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 17890264.62 3490.52 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 1869539.64 3490.52 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 53892344.61     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 34132540.35 3490.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.312641E+09 5384.13 06-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.187772E+09 5384.13 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 248365.96 2688.70 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 3507825.14 4464.91 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 15024334.31 4975.94 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 65763905.55 5384.13 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.584957E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.312641E+09 5384.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 86055915.69 3341.42 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 68490962.35 3341.42 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 347781.84 2428.64 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 556043.18 3341.42 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 941549.53 3341.42 21-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 16301826.80 3341.42 01-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.172694E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 86055915.69 3341.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.192454E+09 5353.69 05-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.152425E+09 5353.69 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 427366.37 2957.25 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 802859.52 4400.12 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2381149.69 5234.51 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 44021705.56 5353.69 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.392512E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.192454E+09 5353.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 56645252.84 3357.98 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 56842471.43 3357.98 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 202125.81 2695.01 06-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 586879.39 3357.98 06-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 858636.76 3357.98 21-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 11434703.73 3357.98 01-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.126570E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 56842471.43 3357.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 1233535.86 837847.60 276.39 20-JAN-16:53 189.60 0.00
February 0.00 0.00 0.106183E+09 0.100585E+09 1998.19 28-FEB-15:00 1844.93 0.00
March 0.00 0.00 0.767872E+09 0.605626E+09 6777.30 31-MAR-05:03 4674.85 0.00
April 0.00 0.00 0.139351E+10 0.112296E+10 6736.41 19-APR-05:03 4817.11 0.00
May 0.00 0.00 0.280332E+10 0.209782E+10 7047.24 31-MAY-05:02 4220.92 0.00
June 0.00 0.00 0.450776E+10 0.330498E+10 7182.58 26-JUN-05:01 4577.40 0.00
July 0.00 0.00 0.484644E+10 0.344449E+10 7201.64 27-JUL-05:02 4093.52 0.00
August 0.00 0.00 0.571505E+10 0.396374E+10 7276.37 07-AUG-05:01 4423.00 0.00
September 0.00 0.00 0.374555E+10 0.276199E+10 7184.19 07-SEP-05:01 4218.09 0.00
October 0.00 0.00 0.209698E+10 0.158988E+10 7209.66 19-OCT-05:02 3834.88 0.00
November 0.00 0.00 0.801127E+09 0.672790E+09 6641.97 06-NOV-06:03 4190.75 0.00
December 0.00 0.00 0.168622E+09 0.120578E+09 2319.55 13-DEC-13:10 1483.72 0.00
                 
Annual Sum or Average 0.00 0.00 0.269537E+11 0.197863E+11       0.00
Minimum of Months 0.00 0.00 1233535.86 837847.60 276.39   189.60 0.00
Maximum of Months 0.00 0.00 0.571505E+10 0.396374E+10 7276.37   4817.11 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 7381041.81 6620449.42 676.94 31-JAN-14:50 614.47 0.00
February 0.00 0.00 0.165338E+09 0.165258E+09 2548.19 28-FEB-15:30 2548.19 0.00
March 0.00 0.00 0.457223E+09 0.392988E+09 3759.05 30-MAR-14:05 3283.05 0.00
April 0.00 0.00 0.667296E+09 0.587279E+09 3099.05 19-APR-14:25 2635.17 0.00
May 0.00 0.00 0.158567E+10 0.122617E+10 6965.50 31-MAY-05:02 3817.63 0.00
June 0.00 0.00 0.357086E+10 0.261902E+10 7171.90 26-JUN-05:01 4089.34 0.00
July 0.00 0.00 0.412391E+10 0.291536E+10 7238.59 27-JUL-05:02 3424.14 0.00
August 0.00 0.00 0.529972E+10 0.367154E+10 7345.67 21-AUG-05:01 3625.48 0.00
September 0.00 0.00 0.333229E+10 0.254946E+10 7125.67 07-SEP-05:01 4064.39 0.00
October 0.00 0.00 0.187841E+10 0.154096E+10 7227.41 19-OCT-05:02 3328.20 0.00
November 0.00 0.00 0.767773E+09 0.709670E+09 3955.98 06-NOV-14:00 3909.87 0.00
December 0.00 0.00 0.241002E+09 0.207976E+09 3293.11 12-DEC-14:00 2665.69 0.00
                 
Annual Sum or Average 0.00 0.00 0.220969E+11 0.165923E+11       0.00
Minimum of Months 0.00 0.00 7381041.81 6620449.42 676.94   614.47 0.00
Maximum of Months 0.00 0.00 0.529972E+10 0.367154E+10 7345.67   4089.34 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 23658480.33 23658480.33 1683.86 28-FEB-15:05 1683.86 0.00
March 0.00 0.00 0.158408E+09 0.135253E+09 3785.94 30-MAR-10:02 2835.36 0.00
April 0.00 0.00 0.408828E+09 0.373297E+09 4607.95 20-APR-10:01 3725.35 0.00
May 0.00 0.00 0.106874E+10 0.901517E+09 4826.53 31-MAY-05:02 2884.15 0.00
June 0.00 0.00 0.216531E+10 0.176795E+10 5002.56 26-JUN-05:01 2999.99 0.00
July 0.00 0.00 0.246548E+10 0.195986E+10 5020.44 27-JUL-05:02 2558.03 0.00
August 0.00 0.00 0.293641E+10 0.227938E+10 5117.99 21-AUG-05:01 2636.30 0.00
September 0.00 0.00 0.182306E+10 0.151208E+10 4962.28 05-SEP-05:01 2988.65 0.00
October 0.00 0.00 0.848778E+09 0.724080E+09 5019.02 19-OCT-05:02 2431.75 0.00
November 0.00 0.00 0.229613E+09 0.211931E+09 3590.48 02-NOV-10:02 2847.95 0.00
December 0.00 0.00 30966362.32 23710818.12 2067.75 12-DEC-15:03 1626.06 0.00
                 
Annual Sum or Average 0.00 0.00 0.121593E+11 0.991272E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.293641E+10 0.227938E+10 5117.99   3725.35 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 13041943.43 13041943.43 935.93 28-FEB-16:57 935.93 0.00
March 0.00 0.00 0.185854E+09 0.143467E+09 2341.20 30-MAR-15:53 2048.71 0.00
April 0.00 0.00 0.501389E+09 0.423351E+09 2466.45 19-APR-14:55 2092.09 0.00
May 0.00 0.00 0.155623E+10 0.121607E+10 6799.66 31-MAY-05:02 3901.27 0.00
June 0.00 0.00 0.329358E+10 0.251642E+10 7048.78 26-JUN-05:01 4016.38 0.00
July 0.00 0.00 0.374960E+10 0.278959E+10 7070.31 27-JUL-05:02 3509.60 0.00
August 0.00 0.00 0.456536E+10 0.332232E+10 7214.66 21-AUG-05:01 3518.51 0.00
September 0.00 0.00 0.270409E+10 0.209238E+10 6992.52 05-SEP-05:01 3980.46 0.00
October 0.00 0.00 0.112679E+10 0.879668E+09 7070.16 19-OCT-05:02 3324.97 0.00
November 0.00 0.00 0.276722E+09 0.241410E+09 2053.55 03-NOV-15:00 1573.07 0.00
December 0.00 0.00 38698654.60 26527657.14 1303.66 13-DEC-13:05 869.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.180114E+11 0.136642E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.456536E+10 0.332232E+10 7214.66   4016.38 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 211082.76 172191.55 186.68 20-JAN-16:50 152.85 0.00
February 0.00 0.00 36573187.90 36573187.90 1214.65 28-FEB-16:40 1214.65 0.00
March 0.00 0.00 0.230134E+09 0.195439E+09 2222.32 30-MAR-15:53 2018.56 0.00
April 0.00 0.00 0.454799E+09 0.404938E+09 2214.65 17-APR-15:53 2137.76 0.00
May 0.00 0.00 0.114970E+10 0.938011E+09 5425.97 31-MAY-05:02 3274.84 0.00
June 0.00 0.00 0.224196E+10 0.177774E+10 5631.76 26-JUN-05:01 3431.23 0.00
July 0.00 0.00 0.253617E+10 0.196043E+10 5643.24 27-JUL-05:02 2899.65 0.00
August 0.00 0.00 0.310566E+10 0.235517E+10 5743.51 21-AUG-05:01 3089.36 0.00
September 0.00 0.00 0.192358E+10 0.155638E+10 5585.36 05-SEP-05:01 3401.88 0.00
October 0.00 0.00 0.920297E+09 0.766183E+09 5645.04 19-OCT-05:02 2737.40 0.00
November 0.00 0.00 0.305039E+09 0.279515E+09 1756.04 06-NOV-16:25 1756.04 0.00
December 0.00 0.00 52858001.57 40960873.33 1032.35 12-DEC-14:35 799.83 0.00
                 
Annual Sum or Average 0.00 0.00 0.129570E+11 0.103115E+11       0.00
Minimum of Months 0.00 0.00 211082.76 172191.55 186.68   152.85 0.00
Maximum of Months 0.00 0.00 0.310566E+10 0.235517E+10 5743.51   3431.23 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 252.01 601.05 31-JAN-12:13
February 0.00 0.00 01-FEB-00:10 26.83 601.07 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     23.46    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   252.01 601.07  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.336918E+09 0.35 342.81 02-JAN-06:01 0.95
February 0.304830E+09 0.35 342.81 01-FEB-06:01 0.94
March 0.369005E+09 0.38 342.81 01-MAR-06:05 0.95
April 0.320874E+09 0.34 342.81 03-APR-05:10 0.94
May 0.352961E+09 0.36 342.81 01-MAY-05:10 0.94
June 0.352961E+09 0.37 342.81 01-JUN-05:02 0.94
July 0.320874E+09 0.33 342.81 03-JUL-05:01 0.94
August 0.369005E+09 0.38 342.81 01-AUG-05:02 0.94
September 0.320874E+09 0.34 342.81 01-SEP-05:02 0.94
October 0.336918E+09 0.35 342.81 02-OCT-05:02 0.94
November 0.336918E+09 0.36 342.81 01-NOV-05:10 0.95
December 0.320874E+09 0.33 342.81 01-DEC-06:02 0.95
           
Annual Sum or Average 0.404301E+10 0.35      
Minimum of Months 0.304830E+09 0.33 342.81   0.94
Maximum of Months 0.369005E+09 0.38 342.81   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.357798E+09 0.38 353.48 02-JAN-06:01 0.95
February 0.320922E+09 0.36 353.48 01-FEB-06:01 0.95
March 0.380489E+09 0.38 353.48 01-MAR-06:05 0.95
April 0.330860E+09 0.34 353.48 03-APR-05:10 0.94
May 0.363946E+09 0.36 353.48 01-MAY-05:10 0.94
June 0.363946E+09 0.37 353.48 01-JUN-05:02 0.94
July 0.330860E+09 0.33 353.48 03-JUL-05:01 0.94
August 0.380489E+09 0.38 353.48 01-AUG-05:02 0.93
September 0.330860E+09 0.34 353.48 01-SEP-05:02 0.94
October 0.347403E+09 0.35 353.48 02-OCT-05:02 0.94
November 0.347403E+09 0.36 353.48 01-NOV-05:10 0.95
December 0.330860E+09 0.33 353.48 01-DEC-06:02 0.95
           
Annual Sum or Average 0.418584E+10 0.36      
Minimum of Months 0.320922E+09 0.33 353.48   0.93
Maximum of Months 0.380489E+09 0.38 353.48   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.219254E+09 0.37 265.87 02-JAN-06:01 0.95
February 0.195133E+09 0.34 265.87 01-FEB-06:01 0.95
March 0.220882E+09 0.31 265.87 01-MAR-06:05 0.95
April 0.195466E+09 0.31 265.87 03-APR-05:10 0.94
May 0.224053E+09 0.36 265.87 01-MAY-05:10 0.94
June 0.238871E+09 0.38 265.87 01-JUN-05:02 0.94
July 0.223281E+09 0.34 265.87 03-JUL-05:01 0.94
August 0.257103E+09 0.38 265.87 01-AUG-05:02 0.93
September 0.215314E+09 0.35 265.87 01-SEP-05:02 0.94
October 0.211984E+09 0.34 265.87 02-OCT-05:02 0.94
November 0.203191E+09 0.31 265.87 01-NOV-05:10 0.95
December 0.191579E+09 0.26 265.87 01-DEC-06:02 0.95
           
Annual Sum or Average 0.259611E+10 0.34      
Minimum of Months 0.191579E+09 0.26 265.87   0.93
Maximum of Months 0.257103E+09 0.38 265.87   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.361489E+09 0.41 346.25 02-JAN-06:01 0.95
February 0.326562E+09 0.40 346.25 01-FEB-06:01 0.95
March 0.372705E+09 0.38 346.25 01-MAR-06:05 0.95
April 0.324091E+09 0.34 346.25 03-APR-05:10 0.94
May 0.356501E+09 0.36 346.25 01-MAY-05:10 0.94
June 0.356501E+09 0.37 346.25 01-JUN-05:02 0.94
July 0.324091E+09 0.33 346.25 03-JUL-05:01 0.94
August 0.372705E+09 0.38 346.25 01-AUG-05:02 0.93
September 0.324091E+09 0.34 346.25 01-SEP-05:02 0.94
October 0.340296E+09 0.35 346.25 02-OCT-05:02 0.94
November 0.340296E+09 0.36 346.25 01-NOV-05:10 0.95
December 0.324091E+09 0.33 346.25 01-DEC-06:02 0.95
           
Annual Sum or Average 0.412342E+10 0.36      
Minimum of Months 0.324091E+09 0.33 346.25   0.93
Maximum of Months 0.372705E+09 0.41 346.25   0.95



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.313756E+09 0.40 306.64 02-JAN-06:01 0.95
February 0.283249E+09 0.39 306.64 01-FEB-06:01 0.95
March 0.330062E+09 0.38 306.64 01-MAR-06:05 0.95
April 0.287011E+09 0.34 306.64 03-APR-05:10 0.94
May 0.315712E+09 0.36 306.64 01-MAY-05:10 0.94
June 0.315712E+09 0.37 306.64 01-JUN-05:02 0.94
July 0.288429E+09 0.34 306.64 03-JUL-05:01 0.94
August 0.331099E+09 0.39 306.64 01-AUG-05:02 0.93
September 0.287011E+09 0.34 306.64 01-SEP-05:02 0.94
October 0.301361E+09 0.35 306.64 02-OCT-05:02 0.94
November 0.301361E+09 0.36 306.64 01-NOV-05:10 0.95
December 0.287011E+09 0.33 306.64 01-DEC-06:02 0.95
           
Annual Sum or Average 0.364177E+10 0.36      
Minimum of Months 0.283249E+09 0.33 306.64   0.93
Maximum of Months 0.331099E+09 0.40 306.64   0.95



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:05 0.00 0.00 36.25 0.00
February 0.00 0.00 0.00 01-FEB-07:10 0.00 0.00 13.42 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 13.42 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 13.42 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 13.42 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 13.42 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 13.42 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 13.42 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 13.42 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 13.42 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 13.42 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 13.42 0.00
                 
Annual Sum or Average 0.02 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 13.42 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 36.25 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 48.89 48.89 252.01 601.05 31-JAN-12:13
February 0.00 0.00 01-FEB-00:10 13.42 13.42 26.83 601.07 01-FEB-12:20
March 0.00 0.00 01-MAR-00:10 13.42 13.42 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 13.42 13.42 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 13.42 13.42 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 13.42 13.42 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 13.42 13.42 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 13.42 13.42 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 13.42 13.42 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 13.42 13.42 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 13.42 13.42 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 13.42 13.42 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         23.46    
Minimum of Months 0.00 0.00   13.42 13.42 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 252.01 601.07  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.688754E+09 0.00 0.00
February 0.00 0.00 0.00 0.475199E+09 0.00 0.00
March 0.00 0.00 0.00 0.542025E+09 0.00 0.00
April 0.00 0.00 0.00 0.635369E+09 0.00 0.00
May 0.00 0.00 0.00 0.972042E+09 0.00 0.00
June 0.00 0.00 0.00 0.135197E+10 0.00 0.00
July 0.00 0.00 0.00 0.138085E+10 0.00 0.00
August 0.00 0.00 0.00 0.161311E+10 0.00 0.00
September 0.00 0.00 0.00 0.112880E+10 0.00 0.00
October 0.00 0.00 0.00 0.791145E+09 0.00 0.00
November 0.00 0.00 0.00 0.517630E+09 0.00 0.00
December 0.00 0.00 0.00 0.415652E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.105126E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.415652E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.161311E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.105752E+10 0.00 0.00
February 0.00 0.00 0.00 0.776624E+09 0.00 0.00
March 0.00 0.00 0.00 0.589777E+09 0.00 0.00
April 0.00 0.00 0.00 0.542821E+09 0.00 0.00
May 0.00 0.00 0.00 0.731057E+09 0.00 0.00
June 0.00 0.00 0.00 0.117406E+10 0.00 0.00
July 0.00 0.00 0.00 0.125145E+10 0.00 0.00
August 0.00 0.00 0.00 0.154618E+10 0.00 0.00
September 0.00 0.00 0.00 0.105592E+10 0.00 0.00
October 0.00 0.00 0.00 0.764207E+09 0.00 0.00
November 0.00 0.00 0.00 0.577914E+09 0.00 0.00
December 0.00 0.00 0.00 0.596931E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.106645E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.542821E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.154618E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.658229E+09 0.00 0.00
February 0.00 0.00 0.00 0.447038E+09 0.00 0.00
March 0.00 0.00 0.00 0.292575E+09 0.00 0.00
April 0.00 0.00 0.00 0.303254E+09 0.00 0.00
May 0.00 0.00 0.00 0.469118E+09 0.00 0.00
June 0.00 0.00 0.00 0.738345E+09 0.00 0.00
July 0.00 0.00 0.00 0.784882E+09 0.00 0.00
August 0.00 0.00 0.00 0.922829E+09 0.00 0.00
September 0.00 0.00 0.00 0.621778E+09 0.00 0.00
October 0.00 0.00 0.00 0.401887E+09 0.00 0.00
November 0.00 0.00 0.00 0.271155E+09 0.00 0.00
December 0.00 0.00 0.00 0.309425E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.622051E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.271155E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.922829E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.119976E+10 0.00 0.00
February 0.00 0.00 0.00 0.822457E+09 0.00 0.00
March 0.00 0.00 0.00 0.497641E+09 0.00 0.00
April 0.00 0.00 0.00 0.469225E+09 0.00 0.00
May 0.00 0.00 0.00 0.713432E+09 0.00 0.00
June 0.00 0.00 0.00 0.111221E+10 0.00 0.00
July 0.00 0.00 0.00 0.117251E+10 0.00 0.00
August 0.00 0.00 0.00 0.139753E+10 0.00 0.00
September 0.00 0.00 0.00 0.925439E+09 0.00 0.00
October 0.00 0.00 0.00 0.593169E+09 0.00 0.00
November 0.00 0.00 0.00 0.447085E+09 0.00 0.00
December 0.00 0.00 0.00 0.578070E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.992853E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.447085E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.139753E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.788120E+09 0.00 0.00
February 0.00 0.00 0.00 0.561341E+09 0.00 0.00
March 0.00 0.00 0.00 0.415246E+09 0.00 0.00
April 0.00 0.00 0.00 0.405463E+09 0.00 0.00
May 0.00 0.00 0.00 0.581195E+09 0.00 0.00
June 0.00 0.00 0.00 0.838708E+09 0.00 0.00
July 0.00 0.00 0.00 0.874419E+09 0.00 0.00
August 0.00 0.00 0.00 0.104251E+10 0.00 0.00
September 0.00 0.00 0.00 0.719774E+09 0.00 0.00
October 0.00 0.00 0.00 0.507364E+09 0.00 0.00
November 0.00 0.00 0.00 0.389389E+09 0.00 0.00
December 0.00 0.00 0.00 0.423474E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.754700E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.389389E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.104251E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.336918E+09 1233535.86 0.817725E+09 0.00 0.00 0.00 0.00 0.00
February 0.304830E+09 0.106183E+09 0.338377E+09 0.00 0.00 0.00 0.00 0.00
March 0.369005E+09 0.767872E+09 4150536.18 0.00 0.00 0.00 0.00 0.00
April 0.320874E+09 0.139351E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.352961E+09 0.280332E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352961E+09 0.450776E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.320874E+09 0.484644E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.369005E+09 0.571505E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.320874E+09 0.374555E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.336918E+09 0.209698E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.336918E+09 0.801127E+09 1651688.63 0.00 0.00 0.00 0.00 0.00
December 0.320874E+09 0.168622E+09 0.121491E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.404301E+10 0.269537E+11 0.128339E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.304830E+09 1233535.86 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.369005E+09 0.571505E+10 0.817725E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.357798E+09 7381041.81 0.199435E+10 0.00 0.00 0.00 0.00 0.00
February 0.320922E+09 0.165338E+09 0.123337E+10 0.00 0.00 0.00 0.00 0.00
March 0.380489E+09 0.457223E+09 0.314942E+09 0.00 0.00 0.00 0.00 0.00
April 0.330860E+09 0.667296E+09 0.159679E+09 0.00 0.00 0.00 0.00 0.00
May 0.363946E+09 0.158567E+10 12985995.96 0.00 0.00 0.00 0.00 0.00
June 0.363946E+09 0.357086E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.330860E+09 0.412391E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.380489E+09 0.529972E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.330860E+09 0.333229E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.347403E+09 0.187841E+10 39208475.12 0.00 0.00 0.00 0.00 0.00
November 0.347403E+09 0.767773E+09 0.166156E+09 0.00 0.00 0.00 0.00 0.00
December 0.330860E+09 0.241002E+09 0.616355E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.418584E+10 0.220969E+11 0.453704E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.320922E+09 7381041.81 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.380489E+09 0.529972E+10 0.199435E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.219254E+09 0.00 0.108855E+10 0.00 0.00 0.00 0.00 0.00
February 0.195133E+09 23658480.33 0.646454E+09 0.00 0.00 0.00 0.00 0.00
March 0.220882E+09 0.158408E+09 0.101712E+09 0.00 0.00 0.00 0.00 0.00
April 0.195466E+09 0.408828E+09 29552703.95 0.00 0.00 0.00 0.00 0.00
May 0.224053E+09 0.106874E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.238871E+09 0.216531E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.223281E+09 0.246548E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.257103E+09 0.293641E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.215314E+09 0.182306E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.211984E+09 0.848778E+09 3011089.50 0.00 0.00 0.00 0.00 0.00
November 0.203191E+09 0.229613E+09 29511518.99 0.00 0.00 0.00 0.00 0.00
December 0.191579E+09 30966362.32 0.285901E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.259611E+10 0.121593E+11 0.218470E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.191579E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.257103E+09 0.293641E+10 0.108855E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.361489E+09 0.00 0.220573E+10 0.00 0.00 0.00 0.00 0.00
February 0.326562E+09 13041943.43 0.135498E+10 0.00 0.00 0.00 0.00 0.00
March 0.372705E+09 0.185854E+09 0.239511E+09 0.00 0.00 0.00 0.00 0.00
April 0.324091E+09 0.501389E+09 70555597.33 0.00 0.00 0.00 0.00 0.00
May 0.356501E+09 0.155623E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.356501E+09 0.329358E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.324091E+09 0.374960E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.372705E+09 0.456536E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.324091E+09 0.270409E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.340296E+09 0.112679E+10 6575211.92 0.00 0.00 0.00 0.00 0.00
November 0.340296E+09 0.276722E+09 97453332.08 0.00 0.00 0.00 0.00 0.00
December 0.324091E+09 38698654.60 0.681771E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.412342E+10 0.180114E+11 0.465658E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.324091E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.372705E+09 0.456536E+10 0.220573E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.313756E+09 211082.76 0.112280E+10 0.00 0.00 0.00 0.00 0.00
February 0.283249E+09 36573187.90 0.678736E+09 0.00 0.00 0.00 0.00 0.00
March 0.330062E+09 0.230134E+09 92089801.26 0.00 0.00 0.00 0.00 0.00
April 0.287011E+09 0.454799E+09 27247931.07 0.00 0.00 0.00 0.00 0.00
May 0.315712E+09 0.114970E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.315712E+09 0.224196E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.288429E+09 0.253617E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.331099E+09 0.310566E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.287011E+09 0.192358E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.301361E+09 0.920297E+09 1066232.39 0.00 0.00 0.00 0.00 0.00
November 0.301361E+09 0.305039E+09 34884743.96 0.00 0.00 0.00 0.00 0.00
December 0.287011E+09 52858001.57 0.311813E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.364177E+10 0.129570E+11 0.226863E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.283249E+09 211082.76 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331099E+09 0.310566E+10 0.112280E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.336918E+09 0.00 0.00 0.351555E+09 282208.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.304830E+09 0.00 0.00 0.146181E+09 24187630.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.369005E+09 0.00 0.00 2032472.45 0.170987E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.320874E+09 0.00 0.00 1230000.00 0.313265E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.352961E+09 0.00 0.00 0.00 0.619081E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.352961E+09 0.00 0.00 0.00 0.999006E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.320874E+09 0.00 0.00 0.00 0.105998E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.369005E+09 0.00 0.00 0.00 0.124411E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.320874E+09 0.00 0.00 0.00 0.807925E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.336918E+09 0.00 0.00 510000.00 0.453717E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.336918E+09 0.00 0.00 4181863.25 0.176531E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.320874E+09 0.00 0.00 57467627.76 37310653.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.404301E+10 0.00 0.00 0.563157E+09 0.590638E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.304830E+09 0.00 0.00 0.00 282208.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.369005E+09 0.00 0.00 0.351555E+09 0.124411E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.357798E+09 0.00 0.00 0.698045E+09 1680444.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.320922E+09 0.00 0.00 0.418713E+09 36989371.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.380489E+09 0.00 0.00 0.106420E+09 0.102868E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.330860E+09 0.00 0.00 56688813.98 0.155272E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.363946E+09 0.00 0.00 4285563.24 0.362825E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.363946E+09 0.00 0.00 0.00 0.810118E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.330860E+09 0.00 0.00 0.00 0.920592E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.380489E+09 0.00 0.00 0.00 0.116569E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.330860E+09 0.00 0.00 0.00 0.725055E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.347403E+09 0.00 0.00 13887555.72 0.402916E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.347403E+09 0.00 0.00 63902520.38 0.166608E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.330860E+09 0.00 0.00 0.212815E+09 53255193.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.418584E+10 0.00 0.00 0.157476E+10 0.490387E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.320922E+09 0.00 0.00 0.00 1680444.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.380489E+09 0.00 0.00 0.698045E+09 0.116569E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.219254E+09 0.00 0.00 0.438975E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.195133E+09 0.00 0.00 0.246427E+09 5477847.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.220882E+09 0.00 0.00 35514507.27 36178863.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.195466E+09 0.00 0.00 12730415.80 95057699.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.224053E+09 0.00 0.00 0.00 0.245065E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.238871E+09 0.00 0.00 0.00 0.499473E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.223281E+09 0.00 0.00 0.00 0.561601E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.257103E+09 0.00 0.00 0.00 0.665727E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.215314E+09 0.00 0.00 0.00 0.406464E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.211984E+09 0.00 0.00 1614725.26 0.188288E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.203191E+09 0.00 0.00 16580805.33 51383294.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.191579E+09 0.00 0.00 0.110905E+09 6940882.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.259611E+10 0.00 0.00 0.862747E+09 0.276166E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.191579E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.257103E+09 0.00 0.00 0.438975E+09 0.665727E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.361489E+09 0.00 0.00 0.838275E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.326562E+09 0.00 0.00 0.492798E+09 3097721.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.372705E+09 0.00 0.00 82330537.07 42604958.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.324091E+09 0.00 0.00 27751477.47 0.117382E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.356501E+09 0.00 0.00 0.00 0.356931E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.356501E+09 0.00 0.00 0.00 0.755714E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.324091E+09 0.00 0.00 0.00 0.848416E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.372705E+09 0.00 0.00 0.00 0.102482E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.324091E+09 0.00 0.00 0.00 0.601347E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.340296E+09 0.00 0.00 2925248.23 0.249947E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.340296E+09 0.00 0.00 44779613.86 62009785.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.324091E+09 0.00 0.00 0.245299E+09 8680048.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.412342E+10 0.00 0.00 0.173416E+10 0.407095E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.324091E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.372705E+09 0.00 0.00 0.838275E+09 0.102482E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.313756E+09 0.00 0.00 0.474315E+09 48470.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.283249E+09 0.00 0.00 0.269635E+09 8456530.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.330062E+09 0.00 0.00 32663486.89 52520199.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.287011E+09 0.00 0.00 11975772.22 0.106476E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.315712E+09 0.00 0.00 0.00 0.265483E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.315712E+09 0.00 0.00 0.00 0.522996E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.288429E+09 0.00 0.00 0.00 0.585990E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.331099E+09 0.00 0.00 0.00 0.711410E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.287011E+09 0.00 0.00 0.00 0.432764E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.301361E+09 0.00 0.00 903910.31 0.205098E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.301361E+09 0.00 0.00 19823994.21 68204206.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.287011E+09 0.00 0.00 0.124569E+09 11894382.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.364177E+10 0.00 0.00 0.933887E+09 0.297134E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.283249E+09 0.00 0.00 0.00 48470.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.331099E+09 0.00 0.00 0.474315E+09 0.711410E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.116214E+10 0.00 0.00 6566.39 0.00 0.566024E+09 12390496.92 0.00 0.19
February 0.100412E+10 0.00 0.00 433945.79 0.00 0.259827E+09 0.133787E+09 0.00 0.19
March 0.627511E+09 1854854.33 0.00 2860186.97 325058.71 0.00 0.571658E+09 0.00 0.21
April 0.221051E+09 9854347.98 0.00 5100776.68 676562.45 0.00 0.457661E+09 0.00 0.19
May 20383004.25 0.183020E+09 0.00 4095015.77 10863997.35 0.00 0.229143E+09 0.00 0.20
June 3548430.31 0.799291E+09 0.00 2731027.51 54744768.98 0.00 72458904.77 0.00 0.21
July 372977.13 0.985999E+09 0.00 793433.06 66591148.69 0.00 1746408.14 0.00 0.18
August 0.00 0.128345E+10 0.00 468335.70 90965273.18 0.00 2096029.34 0.00 0.21
September 7540689.47 0.444219E+09 0.00 4446101.94 27612225.34 0.00 93861031.89 0.00 0.19
October 0.131711E+09 0.132302E+09 0.00 5544031.40 8517331.46 0.00 0.632187E+09 0.00 0.19
November 0.479420E+09 0.00 0.00 3935689.07 679342.81 0.00 0.791109E+09 0.00 0.20
December 0.113496E+10 0.00 0.00 674788.18 0.00 84176922.12 0.196778E+09 0.00 0.18
                   
Annual Sum or Average 0.479276E+10 0.383999E+10 0.00 31089898.46 0.260976E+09 0.910028E+09 0.319488E+10 0.00 0.19
Minimum of Months 0.00 0.00 0.00 6566.39 0.00 0.00 1746408.14 0.00 0.18
Maximum of Months 0.116214E+10 0.128345E+10 0.00 5544031.40 90965273.18 0.566024E+09 0.791109E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.299205E+09 0.00 0.00 13315.03 0.00 0.717040E+09 8572390.64 0.00 0.19
February 0.234955E+09 0.00 0.00 603466.40 0.00 0.473873E+09 45555621.45 0.00 0.19
March 0.334814E+09 6577312.80 0.00 1016289.97 1121970.62 0.139087E+09 0.100188E+09 0.00 0.21
April 0.197420E+09 18246630.17 0.00 854160.88 1784893.14 75580699.75 57265262.91 0.00 0.19
May 95670399.36 0.131467E+09 0.00 1147534.05 8502970.77 9611397.73 61319977.56 0.00 0.20
June 16278071.04 0.538514E+09 0.00 1193286.22 34628447.65 0.00 27752673.85 0.00 0.21
July 1093719.33 0.652714E+09 0.00 900352.04 41022539.43 0.00 4207788.67 0.00 0.18
August 119023.66 0.876174E+09 0.00 714299.73 53340131.52 0.00 3993053.28 0.00 0.21
September 23057190.13 0.322378E+09 0.00 2631829.56 16264672.95 0.00 49131790.23 0.00 0.19
October 0.206159E+09 0.104080E+09 0.00 3792846.91 4674952.86 20503872.34 0.208242E+09 0.00 0.19
November 0.349876E+09 1508194.36 0.00 3047493.68 900439.03 77010564.84 0.234117E+09 0.00 0.20
December 0.381163E+09 93541.25 0.00 877534.44 0.00 0.244240E+09 0.114516E+09 0.00 0.18
                   
Annual Sum or Average 0.213981E+10 0.265175E+10 0.00 16792408.91 0.162241E+09 0.175695E+10 0.914862E+09 0.00 0.19
Minimum of Months 119023.66 0.00 0.00 13315.03 0.00 0.00 3993053.28 0.00 0.18
Maximum of Months 0.381163E+09 0.876174E+09 0.00 3792846.91 53340131.52 0.717040E+09 0.234117E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 56334775.30 0.00 0.00 0.00 0.00 0.447455E+09 0.00 0.00 0.16
February 96411865.63 0.00 13347.85 56651.86 0.00 0.269079E+09 12059421.48 1177.61 0.15
March 0.176032E+09 2269655.11 0.00 345839.52 800569.49 63640756.80 40260349.54 0.00 0.16
April 0.109492E+09 7306073.88 0.00 975211.83 648375.34 20284570.81 49798913.46 0.00 0.15
May 37866190.10 79848803.20 0.00 1208226.12 6709246.28 0.00 47327332.50 0.00 0.16
June 3081663.79 0.314439E+09 0.00 1114707.24 26594308.69 0.00 21879621.32 0.00 0.18
July 138436.93 0.398758E+09 0.00 450583.78 31725555.37 0.00 1548164.75 0.00 0.16
August 23483.06 0.521875E+09 0.00 341588.89 42981386.44 0.00 1740894.32 0.00 0.19
September 5996659.89 0.186756E+09 0.00 1674854.80 13840937.63 0.00 30567802.98 0.00 0.16
October 0.107496E+09 53704684.95 0.00 1927648.70 4551247.21 739690.62 0.120857E+09 0.00 0.15
November 0.224289E+09 535550.07 43417.78 859871.00 924646.59 14494836.52 93810128.67 299.01 0.15
December 0.194508E+09 0.00 0.00 62037.15 125721.14 0.148334E+09 10580600.62 0.00 0.14
                   
Annual Sum or Average 0.101167E+10 0.156549E+10 56765.63 9017220.87 0.128902E+09 0.964028E+09 0.430430E+09 1476.62 0.16
Minimum of Months 23483.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.14
Maximum of Months 0.224289E+09 0.521875E+09 43417.78 1927648.70 42981386.44 0.447455E+09 0.120857E+09 1177.61 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 92666150.67 0.00 0.00 0.00 0.00 0.990544E+09 0.00 0.00 0.20
February 0.186061E+09 0.00 2319.44 19583.47 0.00 0.626099E+09 2614508.84 1195.69 0.20
March 0.410671E+09 3552934.49 0.00 299245.63 1573843.31 0.146337E+09 52155856.93 0.00 0.21
April 0.254701E+09 12592215.15 0.00 792484.46 1502612.10 48343439.86 68557329.13 0.00 0.19
May 87426290.27 0.151372E+09 0.00 1375420.70 12142269.25 0.00 83966694.53 0.00 0.20
June 9057952.38 0.619812E+09 0.00 1301548.62 46666339.70 0.00 38005770.78 0.00 0.21
July 274603.20 0.760752E+09 0.00 783406.93 55402698.43 0.00 2681926.05 0.00 0.18
August 0.00 0.997070E+09 0.00 549509.89 74825654.21 0.00 2785353.97 0.00 0.21
September 9813629.50 0.359885E+09 0.00 2220351.80 24528325.86 0.00 57928507.86 0.00 0.19
October 0.253392E+09 0.103243E+09 0.00 2012661.66 7837046.11 692416.68 0.229616E+09 0.00 0.19
November 0.490791E+09 307704.94 1450348.29 869772.56 455464.83 58611456.18 0.159243E+09 6924.25 0.20
December 0.359985E+09 0.00 0.00 73753.53 10127.88 0.377420E+09 20314732.38 0.00 0.18
                   
Annual Sum or Average 0.215484E+10 0.300859E+10 1452667.73 10297739.23 0.224944E+09 0.224805E+10 0.717869E+09 8119.94 0.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.18
Maximum of Months 0.490791E+09 0.997070E+09 1450348.29 2220351.80 74825654.21 0.990544E+09 0.229616E+09 6924.25 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.123368E+09 0.00 0.00 255.34 0.00 0.507490E+09 807171.68 0.00 0.19
February 0.136549E+09 0.00 7172.06 105100.23 0.00 0.324070E+09 12731532.91 834.32 0.19
March 0.241228E+09 2879326.13 0.00 437684.86 547706.71 72113914.50 53267334.00 0.00 0.21
April 0.142241E+09 7748791.47 0.00 817182.03 649870.03 23968747.71 59678775.53 0.00 0.19
May 44135107.81 90088699.73 0.00 1002791.46 6337781.34 0.00 56095546.30 0.00 0.20
June 2669937.54 0.361259E+09 0.00 924976.15 26240068.61 0.00 26414296.34 0.00 0.21
July 176190.71 0.442709E+09 0.00 320119.15 31525192.23 0.00 1498047.99 0.00 0.18
August 22782.15 0.583612E+09 0.00 287702.70 42868607.18 0.00 1515841.01 0.00 0.21
September 5767486.44 0.210092E+09 0.00 1634424.92 13655488.75 0.00 35317751.56 0.00 0.19
October 0.125058E+09 62503320.93 0.00 1791333.91 4564462.03 0.00 0.163958E+09 0.00 0.19
November 0.275761E+09 220572.01 43780.53 1009137.23 952855.94 21274078.31 0.129713E+09 506.80 0.20
December 0.252392E+09 0.00 0.00 108738.55 0.00 0.182074E+09 21166671.19 0.00 0.18
                   
Annual Sum or Average 0.134937E+10 0.176111E+10 50952.59 8439446.53 0.127342E+09 0.113099E+10 0.562164E+09 1341.12 0.19
Minimum of Months 22782.15 0.00 0.00 255.34 0.00 0.00 807171.68 0.00 0.18
Maximum of Months 0.275761E+09 0.583612E+09 43780.53 1791333.91 42868607.18 0.507490E+09 0.163958E+09 834.32 0.21



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:28:36

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.509966E+11 0.347582E+10 0.00 0.125274E+11 0.223227E+166
February 0.567824E+11 0.322538E+10 0.00 0.998918E+10 0.215313E+166
March 0.948414E+11 0.382593E+10 0.00 0.784091E+10 0.249349E+166
April 0.115011E+12 0.391734E+10 0.00 0.515353E+10 0.274566E+166
May 0.132095E+12 0.409481E+10 0.00 0.219803E+10 0.285325E+166
June 0.134366E+12 0.320759E+10 0.00 -0.219917E+10 0.285429E+166
July 0.128697E+12 0.276419E+10 0.00 -0.458889E+10 0.283929E+166
August 0.117825E+12 0.198241E+10 0.00 -0.606637E+10 0.281239E+166
September 0.863187E+11 0.159184E+10 0.00 -556854267.1 0.250151E+166
October 0.748712E+11 0.241557E+10 0.00 0.567776E+10 0.243556E+166
November 0.485935E+11 0.239849E+10 0.00 0.912460E+10 0.218210E+166
December 0.413500E+11 0.272631E+10 0.00 0.112087E+11 0.207347E+166
           
Annual Sum or Average 0.108175E+13 0.356257E+11 0.00 0.503088E+11 0.301764E+167
Minimum of Months 0.413500E+11 0.159184E+10 0.00 -0.606637E+10 0.207347E+166
Maximum of Months 0.134366E+12 0.409481E+10 0.00 0.125274E+11 0.285429E+166