Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2023-10-16 08:27:22


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 223.77 437.77 437.77
Net Site Energy 223.77 437.77 437.77
Total Source Energy 571.26 1117.58 1117.58
Net Source Energy 571.26 1117.58 1117.58


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 19.88 65.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 7.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 26.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 19.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 25.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 157.80 65.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 19.88 65.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 7.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 26.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 10.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 19.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 25.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 19.88 65.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 7.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 26.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 10.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 48.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 19.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 25.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 142.84 129.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 308.71 129.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 71.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 142.84 129.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 94.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 308.71 129.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 157.798 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 157.798 100.00
     
Total On-Site and Utility Electric Sources 157.798 100.00
Total Electricity End Uses 157.798 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 161.83
Time Setpoint Not Met During Occupied Cooling 3.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 2500.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:27
RunPeriod RUNPERIOD 1
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [m] 359.00
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 6.9815 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 6.9815 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 6.9815 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 6.9815 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 6.9815 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 6.9815 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 6.9815 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 6.9815 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 6.9815 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 6.9815 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             6.9815 9.29 6.7800  
Conditioned Total 511.16             6.9815 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 6.9815 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 27-NOV-16:30 04-JAN-07:10 - - - - - - - - - - 02-JAN-12:09
Heating 6094.16 39908.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2540.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1543.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2751.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 17316.62 39908.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 6094.16 39908.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2540.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 1543.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2751.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 62.94 71.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 23.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 83.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 152.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 63.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 81.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 499.75 71.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 123.14 139.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 45.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 163.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 62.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 123.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 159.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 977.68 139.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 123.14 139.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 45.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 163.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 62.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 123.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 159.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 977.68 139.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.282180
PERIMETER_ZN_1 DIRECT AIR 0.338306
PERIMETER_ZN_2 DIRECT AIR 0.236536
PERIMETER_ZN_3 DIRECT AIR 0.242227
PERIMETER_ZN_4 DIRECT AIR 0.278574
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.282180 0.282180 0.282180 0.282180 0.282180 0.282180 1.00 1.00 0.282180
PSZ-AC:2 0.338306 0.338306 0.338306 0.338306 0.338306 0.338306 1.00 1.000000 0.338306
PSZ-AC:3 0.236536 0.236536 0.236536 0.236536 0.236536 0.236536 1.00 1.00 0.236536
PSZ-AC:4 0.242227 0.242227 0.242227 0.242227 0.242227 0.242227 1.00 1.000000 0.242227
PSZ-AC:5 0.278574 0.278574 0.278574 0.278574 0.278574 0.278574 1.00 1.00 0.278574
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.282180 0.064622
PSZ-AC:2_OA_CONTROLLER 0.338306 0.048988
PSZ-AC:3_OA_CONTROLLER 0.236536 0.029060
PSZ-AC:4_OA_CONTROLLER 0.242227 0.048988
PSZ-AC:5_OA_CONTROLLER 0.278574 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.282180 5391.45 0.794531
PSZ-AC:2 HP COOLING COIL 0.338306 6111.68 0.800884
PSZ-AC:3 HP COOLING COIL 0.236536 3915.51 0.800655
PSZ-AC:4 HP COOLING COIL 0.242227 4626.38 0.794650
PSZ-AC:5 HP COOLING COIL 0.278574 4611.40 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.282180 0.282180 0.282180 0.282180 5391.45 5391.45 40.00 5534.90 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.338306 0.338306 0.338306 0.338306 6111.68 6111.68 40.00 8179.38 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.236536 0.236536 0.236536 0.236536 3915.51 3915.51 40.00 5025.23 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.242227 0.242227 0.242227 0.242227 4626.38 4626.38 40.00 8140.77 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.278574 0.278574 0.278574 0.278574 4611.40 4611.40 40.00 5046.17 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.282180
PSZ-AC:2 FAN 0.338306
PSZ-AC:3 FAN 0.236536
PSZ-AC:4 FAN 0.242227
PSZ-AC:5 FAN 0.278574
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.282180 5391.45
PSZ-AC:2 HEATING COIL 0.338306 6111.68
PSZ-AC:3 HEATING COIL 0.236536 3915.51
PSZ-AC:4 HEATING COIL 0.242227 4626.38
PSZ-AC:5 HEATING COIL 0.278574 4611.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 5534.90
PSZ-AC:2_SUPPHEATCOIL 8179.38
PSZ-AC:3_SUPPHEATCOIL 5025.23
PSZ-AC:4_SUPPHEATCOIL 8140.77
PSZ-AC:5_SUPPHEATCOIL 5046.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 5.40 -2.00 -14.60 -16.90 -11.50 -6.20 4.00 13.40 18.00 19.70 17.90 12.30


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 International Falls Intl Ap MN USA TMY3 WMO#=727470 48.57 -93.40 -6.00 359.00 97086 1.1539


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 3.29 36.60 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 6.981 6.780 0.000 0.000 0.000 0.000 13.761 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1044.832 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1044.832
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 792.050 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 792.050
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 469.854 6.981 129.720 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 469.854


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4610


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 4.810E-002 4.240E-004 5.696E-004 0.500 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 7.646E-002 6.739E-004 9.053E-004 0.795 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 4.810E-002 4.240E-004 5.444E-004 0.500 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 3.207E-002 4.765E-004 5.696E-004 0.562 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.3353E-003
2 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.5711E-003
3 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 2.6235E-003
4 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 2.8389E-003
5 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.4117E-003
6 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.5867E-003
7 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 6.8321E-004
8 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 7.6336E-004
9 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.2189E-002
10 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.2180E-002
11 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.2284E-002
12 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.3145E-002
13 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 1.1303E-002
14 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 7.9568E-003
15 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 5.8315E-003
16 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 3.1637E-003
17 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.2794E-002
18 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.4780E-002
19 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.3425E-002
20 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.6671E-002
21 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 1.0533E-002
22 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 8.1240E-003
23 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 4.8397E-003
24 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 2.9229E-003
25 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.3384E-003
26 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.6108E-003
27 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 2.6299E-003
28 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 2.8920E-003
29 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.4129E-003
30 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.5959E-003
31 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 6.7770E-004
32 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 7.5102E-004
33 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.2426E-003
34 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.2704E-003
35 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 2.5437E-003
36 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 2.5689E-003
37 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.3379E-003
38 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.3566E-003
39 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 6.3990E-004
40 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 6.4824E-004
41 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.2358E-003
42 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.2410E-003
43 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 2.5377E-003
44 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 2.5423E-003
45 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.3330E-003
46 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.3365E-003
47 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 6.3746E-004
48 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 6.3907E-004
49 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.5272E-003
50 Clear Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 4.3434E-003
51 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 3.8912E-003
52 Clear Turbid Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 4.7433E-003
53 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 2.2239E-003
54 Intermediate Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.6679E-003
55 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.0815E-003
56 Overcast Sky 01/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.2159E-003
57 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.6717E-003
58 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.8579E-003
59 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.5821E-003
60 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.7212E-003
61 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.3828E-003
62 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.4505E-003
63 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 1.0724E-003
64 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 1.1461E-003
65 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 6.5112E-003
66 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 5.0631E-003
67 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 5.3169E-003
68 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 4.2756E-003
69 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 4.7321E-003
70 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.8031E-003
71 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 5.2394E-003
72 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 3.3579E-003
73 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.9109E-002
74 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 8.7589E-003
75 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 2.0775E-002
76 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 8.6523E-003
77 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.4098E-002
78 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 7.1283E-003
79 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 6.2521E-003
80 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.6063E-003
81 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 2.1228E-003
82 Clear Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.7173E-003
83 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 2.1703E-003
84 Clear Turbid Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 2.8274E-003
85 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.5240E-003
86 Intermediate Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.7924E-003
87 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.0777E-003
88 Overcast Sky 01/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.1584E-003
89 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 8.2125E-004
90 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 9.7408E-004
91 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.6061E-004
92 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.8157E-004
93 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 5.4233E-004
94 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 6.2765E-004
95 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 6.7633E-004
96 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 7.4639E-004
97 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 5.0504E-003
98 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 4.3166E-003
99 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.0140E-003
100 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 3.3150E-003
101 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.0037E-003
102 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.3591E-003
103 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 4.4158E-003
104 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.8093E-003
105 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 7.2338E-003
106 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 5.2682E-003
107 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 5.5905E-003
108 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.9624E-003
109 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 4.9385E-003
110 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.4684E-003
111 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 6.4051E-003
112 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 3.2906E-003
113 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 8.4092E-004
114 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 1.0335E-003
115 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.7436E-004
116 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 8.2215E-004
117 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 5.4821E-004
118 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 6.3521E-004
119 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 6.8739E-004
120 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 7.7112E-004
121 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 7.5123E-004
122 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 7.7455E-004
123 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 6.0243E-004
124 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 6.2084E-004
125 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 4.9091E-004
126 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 5.0280E-004
127 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 6.4131E-004
128 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 6.5058E-004
129 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 7.4467E-004
130 Clear Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 7.4929E-004
131 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 5.9711E-004
132 Clear Turbid Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 6.0080E-004
133 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 4.8699E-004
134 Intermediate Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 4.8943E-004
135 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 6.3854E-004
136 Overcast Sky 01/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 6.4028E-004
137 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.7718E-003
138 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 2.1598E-003
139 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.7105E-003
140 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 2.1035E-003
141 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.3718E-003
142 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.6014E-003
143 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 1.0794E-003
144 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.1596E-003
145 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.3560E-002
146 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.7838E-003
147 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.3730E-002
148 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.2975E-003
149 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 1.2137E-002
150 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 6.1079E-003
151 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.2277E-003
152 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.5599E-003
153 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 6.5690E-003
154 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 4.9756E-003
155 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 5.1816E-003
156 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 4.0316E-003
157 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 4.2740E-003
158 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.3398E-003
159 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 5.2359E-003
160 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 3.3191E-003
161 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.4746E-003
162 Clear Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.6712E-003
163 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.3236E-003
164 Clear Turbid Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.4680E-003
165 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.2417E-003
166 Intermediate Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.3021E-003
167 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 1.0739E-003
168 Overcast Sky 01/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 1.1472E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3071.15737 3685.38884 0.23515 0.28218 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 29.02533 1.27240E-002 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 1270.88150 1525.05780 5.71766E-002 6.86119E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 3681.70116 4418.04139 0.28192 0.33831 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 30.10000 1.27259E-002 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 4332.16887 5198.60264 0.19489 0.23387 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 2574.39633 3089.27560 0.19711 0.23654 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 25.03667 1.27170E-002 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 2716.29349 3259.55218 0.12220 0.14664 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 2636.24822 3163.49786 0.20186 0.24223 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 29.35600 1.27246E-002 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 4299.51722 5159.42066 0.19342 0.23211 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 3031.92428 3638.30914 0.23215 0.27857 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 26.50400 1.27196E-002 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 2734.00790 3280.80948 0.12300 0.14759 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -32.70000 1.83376E-004 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 4013.25 0.28218 0.28218 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 5534.90 6.86119E-002 6.86119E-002 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
3 PSZ-AC:2 Cooling Sensible 4702.56 0.33831 0.33831 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 8179.38 0.23387 0.23387 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 3080.16 0.23654 0.23654 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 5025.23 0.14664 0.14664 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 3425.12 0.24223 0.24223 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 8140.77 0.23211 0.23211 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 3670.15 0.27857 0.27857 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 5046.17 0.14759 0.14759 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.28218
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.33831
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.23654
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.24223
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.27857
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.28218
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.28218
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.28218
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.28218
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.28218
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.28218
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.33831
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.33831
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.33831
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.33831
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.33831
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.33831
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.23654
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.23654
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.23654
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.23654
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.23654
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.23654
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.24223
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.24223
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.24223
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.24223
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.24223
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.24223
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.27857
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.27857
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.27857
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.27857
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.27857
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.27857
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.28218
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.33831
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.23654
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.24223
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.27857
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.28218
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.28218
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5391.45401
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.79453
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.28218
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.28218
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.28218
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.28218
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5391.45401
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5391.45401
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5534.89763
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.28218
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.28218
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5391.45401
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 5534.89763
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.33831
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.33831
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6111.67793
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80088
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.33831
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.33831
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.33831
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.33831
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6111.67793
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6111.67793
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 8179.38251
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.33831
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.33831
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6111.67793
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 8179.38251
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.23654
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.23654
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 3915.50535
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.23654
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.23654
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.23654
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.23654
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 3915.50535
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 3915.50535
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5025.22724
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.23654
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.23654
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 3915.50535
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 5025.22724
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.24223
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.24223
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4626.38379
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.79465
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.24223
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.24223
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.24223
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.24223
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4626.38379
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4626.38379
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 8140.77125
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.24223
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.24223
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4626.38379
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 8140.77125
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.27857
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.27857
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 4611.39674
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.27857
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.27857
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.27857
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.27857
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 4611.39674
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 4611.39674
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 5046.17493
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.27857
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.27857
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 4611.39674
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 5046.17493
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 5169.9 3.38 11.54 12.09 11.44 11.43
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 5846.2 3.35 11.42 11.96 11.31 11.25
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 3730.1 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 4436.2 3.38 11.54 12.09 11.44 11.43
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 4393.1 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 5616.2 3113.0 7.39 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 6380.7 3543.1 7.39 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 4103.2 2285.2 7.32 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 4819.3 2671.3 7.42 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 4832.4 2691.4 7.35 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 0.1580754724 0.1710604901 Pass Pass 0.9649083366 2.8950598905 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 0.4293485410 0.5221712928 Pass Pass 0.5567406748 0.6757094724 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 0.7130724857 0.6836976774 Pass Pass 0.6170851325 0.5835234632 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 0.7685641423 0.7011309457 Pass Pass 0.6264626162 0.5897118464 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 0.7289300065 0.6962181546 Pass Pass 0.6100727425 0.5799549131 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.2996759988 0.2960126046 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 807.49 39.44 0.00 53.70 -0.114707E+11 -0.114707E+11



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -32.70 0.00 -32.70 Wetbulb [C] 2.40 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 30.10 12.40 21.10 Wetbulb [C] 4.70 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 12.00 13      
Apr 16.00 23      
May 0.00 0      
Jun 190.00 53      
Jul 136.00 41      
Aug 87.00 42      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.473 0.509 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.215 0.223 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.473 0.509 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.242 0.252 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.473 0.509 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.215 0.223 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.473 0.509 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.242 0.252 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.096 0.098 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.096 0.098 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.096 0.098 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.096 0.098 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.096 0.098 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.096 0.098 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.096 0.098 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.096 0.098 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.096 0.098 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.096 0.098 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.292_SHGC_SOUTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.292_SHGC_SOUTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.292_SHGC_SOUTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.292_SHGC_SOUTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.292_SHGC_SOUTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.292_SHGC_SOUTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.292_SHGC_SOUTH_0.399   3.91 0.00 0.00 3.91 3.91 1.658 0.400 0.440             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.292_SHGC_EAST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.292_SHGC_EAST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.292_SHGC_EAST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.292_SHGC_EAST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.292_SHGC_NORTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.292_SHGC_NORTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.292_SHGC_NORTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.292_SHGC_NORTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.292_SHGC_NORTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.292_SHGC_NORTH_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.292_SHGC_WEST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.292_SHGC_WEST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.292_SHGC_WEST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.292_SHGC_WEST_0.399   2.79 0.00 0.00 2.79 2.79 1.658 0.400 0.440             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 1.658 0.400 0.440                      
North Total or Average             16.72 1.658 0.400 0.440                      
Non-North Total or Average             42.93 1.658 0.400 0.440                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 1.00 1.00 1.00 0.00 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 1.00 1.00 1.00 0.03 0.58 0.37 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.22 0.84 0.69 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.07 0.00 1.00 0.00 0.00 1.00 0.26 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.07 0.00 1.00 0.00 0.00 1.00 0.26 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.07 0.00 1.00 0.00 0.00 1.00 0.26 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.10 0.00 1.00 0.00 0.00 1.00 0.77 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 1.00 0.00 0.00 0.85 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 6.9815 149.66 1044.83 LightsWired LTG_SCH_OFFICE 55.32 168.00 44.56 0.0000 Y 8.74
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 36.29 0.0000 Y 5.40
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 37.34 0.0000 Y 3.29
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 6.9815 113.45 792.05 LightsWired LTG_SCH_OFFICE 55.32 168.00 38.50 0.0000 Y 5.72
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 6.9815 67.30 469.85 LightsWired LTG_SCH_OFFICE 55.32 168.00 37.41 0.0000 Y 3.30
Interior Lighting Total       6.9815 511.16 3568.64               26.45


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 792.05 190.01
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.03 792.05 23.92
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 469.85 112.72
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.03 469.85 14.19


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 87.95 AstronomicalClock -   42.55 42.55 0.70
EXTERIOR_LIGHTS_B 200.47 AstronomicalClock -   83.52 63.04 2.37
EXTERIOR_LIGHTS_C 773.25 AstronomicalClock -   83.52 47.99 6.97
Exterior Lighting Total 1061.67           10.04



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5391.45 4283.68 1107.77 0.79 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6111.68 4894.75 1216.93 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   3915.51 3134.97 780.54 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4626.38 3676.35 950.03 0.79 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   4611.40 3692.14 919.26 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   5169.9 3.38 11.54 12.09 11.44 11.43
PSZ-AC:2 HP COOLING COIL   5846.2 3.35 11.42 11.96 11.31 11.25
PSZ-AC:3 HP COOLING COIL   3730.1 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   4436.2 3.38 11.54 12.09 11.44 11.43
PSZ-AC:5 HP COOLING COIL   4393.1 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 5616.2 3113.0 7.39 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 6380.7 3543.1 7.39 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 4103.2 2285.2 7.32 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 4819.3 2671.3 7.42 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 4832.4 2691.4 7.35 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   5391.45 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   5534.90 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   6111.68 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   8179.38 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   3915.51 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   5025.23 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   4626.38 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   8140.77 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   4611.40 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   5046.17 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.28 316.07 1120.11 1.00 1.94 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.34 378.94 1120.11 1.00 1.82 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.24 264.95 1120.11 1.00 2.09 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.24 271.32 1120.11 1.00 2.06 General INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.28 312.03 1120.11 1.00 1.95 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3071.16 3685.39 24.63 0.235 0.282 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 23.89 23.89 0.00908 29.03 0.01272 0.065 0.00
PERIMETER_ZN_1 3681.70 4418.04 38.94 0.282 0.338 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 23.89 23.89 0.00902 30.10 0.01273 0.049 0.00
PERIMETER_ZN_2 2574.40 3089.28 45.90 0.197 0.237 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 23.89 23.89 0.00896 25.04 0.01272 0.029 0.00
PERIMETER_ZN_3 2636.25 3163.50 27.88 0.202 0.242 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 23.89 23.89 0.00922 29.36 0.01272 0.049 0.00
PERIMETER_ZN_4 3031.92 3638.31 54.06 0.232 0.279 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 23.89 23.89 0.00889 26.50 0.01272 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 1270.88 1525.06 10.19 0.057 0.069 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00800 -32.70 0.00018 0.065 0.00
PERIMETER_ZN_1 4332.17 5198.60 45.82 0.195 0.234 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00771 -32.70 0.00018 0.049 0.00
PERIMETER_ZN_2 2716.29 3259.55 48.43 0.122 0.147 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00769 -32.70 0.00018 0.029 0.00
PERIMETER_ZN_3 4299.52 5159.42 45.48 0.193 0.232 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00770 -32.70 0.00018 0.049 0.00
PERIMETER_ZN_4 2734.01 3280.81 48.75 0.123 0.148 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 21.11 21.11 0.00769 -32.70 0.00018 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.28 0.28 0.07 0.07 0.2822 0.2822 0.2822 1.0000 1.0000
PSZ-AC:2 0.34 0.34 0.23 0.23 0.3383 0.3383 0.3383 1.0000 1.0000
PSZ-AC:3 0.24 0.24 0.15 0.15 0.2365 0.2365 0.2365 1.0000 1.0000
PSZ-AC:4 0.24 0.24 0.23 0.23 0.2422 0.2422 0.2422 1.0000 1.0000
PSZ-AC:5 0.28 0.28 0.15 0.15 0.2786 0.2786 0.2786 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5391.454 4283.680 0.282180 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 5397.53 4370.40 0.282180 26.01 17.80 0.00991688 12.80 11.72 0.00850000 29.03 0.01272398 20.82 22.9010 23.89 0.00908760 47.1474 3054.11 0.00 5390.53 4186.54
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 5391.454 5391.454 0.282180 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5391.45 5391.45 0.282180 8.79 7.53 0.00620991 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 22.9010 21.11 0.00800000 49.2257 1270.88 0.00 5398.54 5398.54
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 5534.898 5534.898 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5534.90 5534.90 0.282180 8.79 7.53 0.00620991 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 22.9010 21.11 0.00800000 49.2257 1270.88 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6111.678 4894.748 0.338306 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 6026.15 5112.97 0.338306 25.74 17.42 0.00955714 12.80 11.72 0.00850000 30.10 0.01272586 21.13 14.4803 23.89 0.00902061 46.8070 3681.70 0.00 6110.63 4782.33
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 6111.678 6111.678 0.338306 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 6111.68 6111.68 0.338306 13.32 10.01 0.00661728 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 14.4803 21.11 0.00770668 47.4458 4332.17 0.00 6119.71 6119.71
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 8179.383 8179.383 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8179.38 8179.38 0.338306 13.32 10.01 0.00661728 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 14.4803 21.11 0.00770668 47.4458 4332.17 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 3915.505 3134.970 0.236536 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 3932.12 3375.97 0.236536 24.98 17.06 0.00942565 12.80 11.72 0.00850000 25.04 0.01271700 19.62 12.2857 23.89 0.00896524 46.5208 2570.65 0.00 3914.83 3062.91
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 3915.505 3915.505 0.236536 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 3915.51 3915.51 0.236536 14.50 10.67 0.00676675 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 12.2857 21.11 0.00768886 47.3377 2716.29 0.00 3920.65 3920.65
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 5025.227 5025.227 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5025.23 5025.23 0.236536 14.50 10.67 0.00676675 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 12.2857 21.11 0.00768886 47.3377 2716.29 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4626.384 3676.354 0.242227 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 4621.14 3733.70 0.242227 25.94 17.78 0.00992626 12.80 11.72 0.00850000 29.36 0.01272455 20.91 20.2239 23.89 0.00922214 47.8360 2620.98 0.00 4625.59 3593.02
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 4626.384 4626.384 0.242227 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4626.38 4626.38 0.242227 10.23 8.16 0.00618346 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 20.2239 21.11 0.00770453 47.4327 4299.52 0.00 4632.46 4632.46
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 8140.771 8140.771 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 8140.77 8140.77 0.242227 10.23 8.16 0.00618346 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 20.2239 21.11 0.00770453 47.4327 4299.52 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4611.397 3692.139 0.278574 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 4595.51 4031.89 0.278574 25.11 17.00 0.00929279 12.80 11.72 0.00850000 26.50 0.01271956 20.07 10.4317 23.89 0.00889315 46.1523 3029.12 0.00 4610.61 3607.27
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 4611.397 4611.397 0.278574 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4611.40 4611.40 0.278574 15.50 11.24 0.00690764 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 10.4317 21.11 0.00769079 47.3495 2734.01 0.00 4617.46 4617.46
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 5046.175 5046.175 -999.0 -999.0 -999.000 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 5046.17 5046.17 0.278574 15.50 11.24 0.00690764 40.00 20.69 0.00800000 -32.70 0.00018338 -32.70 10.4317 21.11 0.00769079 47.3495 2734.01 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5391.454 4283.680 0.282180 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.2750 1004.8586 1.1539 PSZ-AC:1 FAN Fan:OnOff 0.282180 0.32561454   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 Sensible 5397.53 4370.40 1.0011 0.32561454 0.282180 26.01 17.80 0.00991688 51421.2 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 316.072 5081.46 29.03 0.01272398 20.82 0.06462207 22.9010 23.89 0.00908308 23.89 0.00908760 47.1474 3054.11 0.00 5390.53 4186.54 0.31275523 26.67 19.44 0.01118466 55322.4 13.58 13.56 0.00967531 38086.8
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5391.454 5391.454 0.282180 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:1 FAN Fan:OnOff 0.282180 0.32561454   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5391.45 5391.45 1.0000 0.32561454 0.282180 8.79 7.53 0.00620991 24461.6 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5391.45 -32.70 0.00018338 -32.70 0.06462207 22.9010 21.11 0.00800000 21.11 0.00800000 49.2257 1270.88 0.00 5398.54 5398.54 0.31986083 21.11 15.56 0.00875166 43444.1 37.64 21.02 0.00875166 60321.9
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5534.898 5534.898 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:1 FAN Fan:OnOff 0.282180 0.32561454   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5534.90 5534.90 1.0000 0.32561454 0.282180 8.79 7.53 0.00620991 24461.6 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5534.90 -32.70 0.00018338 -32.70 0.06462207 22.9010 21.11 0.00800000 21.11 0.00800000 49.2257 1270.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6111.678 4894.748 0.338306 -999.0 -999.000 -999.0000 1.00000 1.00000 1022.6062 1004.8586 1.1539 PSZ-AC:2 FAN Fan:OnOff 0.338306 0.39037953   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 6026.15 5112.97 0.9860 0.39037953 0.338306 25.74 17.42 0.00955714 50220.8 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 378.939 5647.21 30.10 0.01272586 21.13 0.04898771 14.4803 23.89 0.00902061 23.89 0.00902061 46.8070 3681.70 0.00 6110.63 4782.33 0.37496249 26.67 19.44 0.01118466 55322.4 14.20 13.91 0.00979573 39025.7
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6111.678 6111.678 0.338306 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:2 FAN Fan:OnOff 0.338306 0.39037953   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 6111.68 6111.68 1.0000 0.39037953 0.338306 13.32 10.01 0.00661728 30095.0 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6111.68 -32.70 0.00018338 -32.70 0.04898771 14.4803 21.11 0.00770668 21.11 0.00770668 47.4458 4332.17 0.00 6119.71 6119.71 0.38348140 21.11 15.56 0.00875166 43444.1 36.74 20.75 0.00875166 59402.4
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 8179.383 8179.383 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:2 FAN Fan:OnOff 0.338306 0.39037953   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8179.38 8179.38 1.0000 0.39037953 0.338306 13.32 10.01 0.00661728 30095.0 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8179.38 -32.70 0.00018338 -32.70 0.04898771 14.4803 21.11 0.00770668 21.11 0.00770668 47.4458 4332.17 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 3915.505 3134.970 0.236536 -999.0 -999.000 -999.0000 1.00054 1.00000 1022.3618 1004.8586 1.1539 PSZ-AC:3 FAN Fan:OnOff 0.236536 0.27294440   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 Sensible 3932.12 3375.97 1.0042 0.27294440 0.236536 24.98 17.06 0.00942565 49111.4 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 264.945 3667.18 25.04 0.01271700 19.62 0.02906014 12.2857 23.89 0.00896465 23.89 0.00896524 46.5208 2570.65 0.00 3914.83 3062.91 0.26216516 26.67 19.44 0.01118466 55322.4 15.25 14.42 0.00991057 40389.7
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 3915.505 3915.505 0.236536 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:3 FAN Fan:OnOff 0.236536 0.27294440   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 3915.51 3915.51 1.0000 0.27294440 0.236536 14.50 10.67 0.00676675 31673.9 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3915.51 -32.70 0.00018338 -32.70 0.02906014 12.2857 21.11 0.00768886 21.11 0.00768886 47.3377 2716.29 0.00 3920.65 3920.65 0.26812139 21.11 15.56 0.00875166 43444.1 35.43 20.36 0.00875166 58066.8
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5025.227 5025.227 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:3 FAN Fan:OnOff 0.236536 0.27294440   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5025.23 5025.23 1.0000 0.27294440 0.236536 14.50 10.67 0.00676675 31673.9 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5025.23 -32.70 0.00018338 -32.70 0.02906014 12.2857 21.11 0.00768886 21.11 0.00768886 47.3377 2716.29 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4626.384 3676.354 0.242227 -999.0 -999.000 -999.0000 1.00000 1.00000 1023.2924 1004.8586 1.1539 PSZ-AC:4 FAN Fan:OnOff 0.242227 0.27951209   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 Sensible 4621.14 3733.70 0.9989 0.27951209 0.242227 25.94 17.78 0.00992626 51372.5 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 271.321 4349.82 29.36 0.01272455 20.91 0.04898771 20.2239 23.89 0.00921688 23.89 0.00922214 47.8360 2620.98 0.00 4625.59 3593.02 0.26847348 26.67 19.44 0.01118466 55322.4 13.58 13.56 0.00967670 38093.2
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4626.384 4626.384 0.242227 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:4 FAN Fan:OnOff 0.242227 0.27951209   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4626.38 4626.38 1.0000 0.27951209 0.242227 10.23 8.16 0.00618346 25858.3 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4626.38 -32.70 0.00018338 -32.70 0.04898771 20.2239 21.11 0.00770453 21.11 0.00770453 47.4327 4299.52 0.00 4632.46 4632.46 0.27457303 21.11 15.56 0.00875166 43444.1 37.63 21.02 0.00875166 60315.6
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 8140.771 8140.771 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:4 FAN Fan:OnOff 0.242227 0.27951209   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 8140.77 8140.77 1.0000 0.27951209 0.242227 10.23 8.16 0.00618346 25858.3 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8140.77 -32.70 0.00018338 -32.70 0.04898771 20.2239 21.11 0.00770453 21.11 0.00770453 47.4327 4299.52 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 4611.397 3692.139 0.278574 -999.0 -999.000 -999.0000 1.00693 1.00000 1022.1148 1004.8586 1.1539 PSZ-AC:5 FAN Fan:OnOff 0.278574 0.32145401   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 4595.51 4031.89 0.9966 0.32145401 0.278574 25.11 17.00 0.00929279 48907.9 12.80 11.72 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 312.033 4283.48 26.50 0.01271956 20.07 0.02906014 10.4317 23.89 0.00889368 23.89 0.00889315 46.1523 3029.12 0.00 4610.61 3607.27 0.30875901 26.67 19.44 0.01118466 55322.4 15.25 14.42 0.00991057 40389.7
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 4611.397 4611.397 0.278574 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:5 FAN Fan:OnOff 0.278574 0.32145401   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 4611.40 4611.40 1.0000 0.32145401 0.278574 15.50 11.24 0.00690764 33045.3 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 4611.40 -32.70 0.00018338 -32.70 0.02906014 10.4317 21.11 0.00769079 21.11 0.00769079 47.3495 2734.01 0.00 4617.46 4617.46 0.31577382 21.11 15.56 0.00875166 43444.1 35.43 20.36 0.00875166 58066.8
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 5046.175 5046.175 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1539 PSZ-AC:5 FAN Fan:OnOff 0.278574 0.32145401   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 24:00:00 Sensible 5046.17 5046.17 1.0000 0.32145401 0.278574 15.50 11.24 0.00690764 33045.3 40.00 20.69 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5046.17 -32.70 0.00018338 -32.70 0.02906014 10.4317 21.11 0.00769079 21.11 0.00769079 47.3495 2734.01 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2583.17 2995.67 1711.67
PERIMETER_ZN_1 2849.17 3260.17 2168.33
PERIMETER_ZN_2 2388.00 2634.67 1860.83
PERIMETER_ZN_3 2801.83 3473.00 2382.50
PERIMETER_ZN_4 2862.00 3268.17 2250.50
ATTIC 0.00 0.00 0.00
Facility 3379.17 3588.17 2500.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 26.83 3.50 26.50 3.50
PERIMETER_ZN_1 190.00 0.00 107.00 0.00
PERIMETER_ZN_2 209.17 0.00 42.67 0.00
PERIMETER_ZN_3 283.67 0.00 117.50 0.00
PERIMETER_ZN_4 197.00 0.00 38.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 558.83 3.50 161.83 3.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.365 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.364 0.265 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.332 0.060 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.364 0.050 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.364 0.056 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 703501.65 0.00 703501.65 0.00 703501.65 2037921.45 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_1 533299.81 0.00 533299.81 529335.96 1062635.76 1544876.42 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_2 264174.74 0.00 264174.74 143221.87 407396.61 916440.58 6348.75 2411.25 0.00 531.39
PERIMETER_ZN_3 533299.81 0.00 533299.81 214832.80 748132.61 1544876.42 5736.00 3024.00 0.00 0.00
PERIMETER_ZN_4 316360.31 0.00 316360.31 143221.87 459582.18 916440.58 5736.00 3024.00 0.00 0.00
Total Facility 2350636.31 0.00 2350636.31 1030612.49 3381248.80 6960555.45 6348.75 3024.00 0.00 531.39


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0456 0.0000 0.0456 0.0000 0.0456 0.0646 1260.00 3024.00 0.00
PERIMETER_ZN_1 0.0346 0.0000 0.0346 0.0252 0.0597 0.0490 1260.00 3024.00 0.00
PERIMETER_ZN_2 0.0187 0.0000 0.0187 0.0034 0.0221 0.0291 1260.00 2268.00 0.00
PERIMETER_ZN_3 0.0346 0.0000 0.0346 0.0048 0.0393 0.0490 1260.00 3024.00 0.00
PERIMETER_ZN_4 0.0205 0.0000 0.0205 0.0032 0.0237 0.0291 1260.00 3024.00 0.00
Total Facility 0.1540 0.0000 0.1540 0.0365 0.1905 0.2207 1872.75 3024.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 936742.40 0.00 936742.40 2037921.45 5736.00 0.00 3024.00 0.00
PSZ-AC:2 710111.40 0.00 710111.40 1544876.42 5736.00 0.00 3024.00 0.00
PSZ-AC:3 351759.91 0.00 351759.91 916440.58 6331.78 1.31 2426.91 520.19
PSZ-AC:4 710111.40 0.00 710111.40 1544876.42 5736.00 0.00 3024.00 0.00
PSZ-AC:5 421247.22 0.00 421247.22 916440.58 5736.00 0.00 3024.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0607 0.0000 0.0607 0.0646 1260.00 0.00 3024.00
PSZ-AC:2 0.0460 0.0000 0.0460 0.0490 1260.00 0.00 3024.00
PSZ-AC:3 0.0249 0.0000 0.0249 0.0291 1260.00 0.00 2268.00
PSZ-AC:4 0.0460 0.0000 0.0460 0.0490 1260.00 0.00 3024.00
PSZ-AC:5 0.0273 0.0000 0.0273 0.0291 1260.00 0.00 3024.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 2788.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3024.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0860 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0652 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0387 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0652 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0387 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 555
Defaulted Fields 365
Fields with Defaults 1333
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 157.80 1248.68 04-FEB-12:50 17316.62 27-NOV-16:30
Electricity:Building 74.75 677.68 01-JAN-00:10 5866.25 02-JAN-08:10
Electricity:Zone:CORE_ZN 22.88 198.41 01-JAN-00:10 1717.53 02-JAN-08:10
Electricity:SpaceType:GENERAL 74.75 677.68 01-JAN-00:10 5866.25 02-JAN-08:10
InteriorLights:Electricity 26.45 110.04 01-JAN-00:10 2540.94 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 26.45 110.04 01-JAN-00:10 2540.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity 26.45 110.04 01-JAN-00:10 2540.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 8.74 32.22 01-JAN-00:10 743.94 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 26.45 110.04 01-JAN-00:10 2540.94 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_1 16.11 150.41 01-JAN-00:10 1302.00 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.40 24.42 01-JAN-00:10 563.96 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 5.40 24.42 01-JAN-00:10 563.96 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_2 9.65 89.23 01-JAN-00:10 772.36 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 14.49 01-JAN-00:10 334.55 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 3.29 14.49 01-JAN-00:10 334.55 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_3 16.44 150.41 01-JAN-00:10 1302.00 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.72 24.42 01-JAN-00:10 563.96 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 5.72 24.42 01-JAN-00:10 563.96 02-JAN-08:10
Electricity:Zone:PERIMETER_ZN_4 9.66 89.23 01-JAN-00:10 772.36 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.30 14.49 01-JAN-00:10 334.55 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 3.30 14.49 01-JAN-00:10 334.55 02-JAN-08:10
InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 14.14 166.20 01-JAN-00:10 973.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 48.30 567.64 01-JAN-00:10 3325.31 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 10.72 125.99 01-JAN-00:10 738.04 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.36 74.74 01-JAN-00:10 437.82 02-JAN-08:10
ElectricityPurchased:Facility 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
ElectricityPurchased:Plant 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
Cogeneration:ElectricityPurchased 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
General:Cogeneration:ElectricityPurchased 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
ElectricityNet:Plant 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
Cogeneration:ElectricityNet 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
General:Cogeneration:ElectricityNet 157.80 1248.68 22-APR-07:40 17316.62 27-NOV-16:30
ExteriorLights:Electricity 10.04 0.00 01-JAN-08:20 1061.67 01-JAN-06:10
General:ExteriorLights:Electricity 10.04 0.00 01-JAN-08:20 1061.67 01-JAN-06:10
Electricity:HVAC 47.21 0.00 04-FEB-12:50 9345.44 05-DEC-07:10
Fans:Electricity 19.92 0.00 01-JAN-00:40 1543.31 01-JAN-00:30
General:Fans:Electricity 19.92 0.00 01-JAN-00:40 1543.31 01-JAN-00:30
Cooling:Electricity 7.42 0.00 01-JAN-00:10 5202.69 29-JUN-16:00
General:Cooling:Electricity 7.42 0.00 01-JAN-00:10 5202.69 29-JUN-16:00
Heating:Electricity 19.88 0.00 04-FEB-12:50 7802.13 05-DEC-07:10
General:Heating:Electricity 19.88 0.00 04-FEB-12:50 7802.13 05-DEC-07:10
Electricity:Plant 25.80 571.00 01-JAN-00:10 2851.09 28-FEB-12:30
WaterSystems:Electricity 25.80 571.00 01-JAN-00:10 2851.09 28-FEB-12:30
Water Heater:WaterSystems:Electricity 25.80 571.00 01-JAN-00:10 2851.09 28-FEB-12:30
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-08:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 05-JAN-08:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 65.97 0.00 01-JAN-00:40 39908.07 04-JAN-07:10
NaturalGas:HVAC 65.97 0.00 01-JAN-00:40 39908.07 04-JAN-07:10
Heating:NaturalGas 65.97 0.00 01-JAN-00:40 39908.07 04-JAN-07:10
General:Heating:NaturalGas 65.97 0.00 01-JAN-00:40 39908.07 04-JAN-07:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 02-FEB-12:20
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 02-FEB-12:20
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 27-FEB-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 27-FEB-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 211.31 0.00 01-JAN-00:40 63305.87 17-JAN-06:20
EnergyTransfer:Building 91.68 0.00 01-JAN-00:40 32293.09 17-JAN-06:20
EnergyTransfer:Zone:CORE_ZN 14.62 0.00 01-JAN-00:40 6794.66 17-JAN-06:10
Heating:EnergyTransfer 61.32 0.00 01-JAN-00:40 32293.09 17-JAN-06:20
Heating:EnergyTransfer:Zone:CORE_ZN 3.26 0.00 01-JAN-00:40 6794.66 17-JAN-06:10
General:Heating:EnergyTransfer 61.32 0.00 01-JAN-00:40 32293.09 17-JAN-06:20
General:Heating:EnergyTransfer:Zone:CORE_ZN 3.26 0.00 01-JAN-00:40 6794.66 17-JAN-06:10
Cooling:EnergyTransfer 30.36 0.00 01-JAN-00:10 14133.51 24-JUL-14:30
Cooling:EnergyTransfer:Zone:CORE_ZN 11.36 0.00 01-JAN-00:10 3676.29 28-AUG-05:10
General:Cooling:EnergyTransfer 30.36 0.00 01-JAN-00:10 14133.51 24-JUL-14:30
General:Cooling:EnergyTransfer:Zone:CORE_ZN 11.36 0.00 01-JAN-00:10 3676.29 28-AUG-05:10
EnergyTransfer:Zone:PERIMETER_ZN_1 23.54 0.00 01-JAN-00:40 8422.05 09-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 16.42 0.00 01-JAN-00:40 8422.05 09-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 16.42 0.00 01-JAN-00:40 8422.05 09-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 7.12 0.00 01-JAN-00:10 4731.25 01-SEP-14:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 7.12 0.00 01-JAN-00:10 4731.25 01-SEP-14:00
EnergyTransfer:Zone:PERIMETER_ZN_2 14.68 0.00 01-JAN-00:40 5474.11 17-JAN-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 10.93 0.00 01-JAN-00:40 5474.11 17-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 10.93 0.00 01-JAN-00:40 5474.11 17-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 3.75 0.00 01-JAN-00:10 2809.56 24-JUL-10:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 3.75 0.00 01-JAN-00:10 2809.56 24-JUL-10:10
EnergyTransfer:Zone:PERIMETER_ZN_3 24.00 0.00 01-JAN-00:40 6454.65 09-JAN-06:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 19.50 0.00 01-JAN-00:40 6454.65 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 19.50 0.00 01-JAN-00:40 6454.65 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 4.50 0.00 01-JAN-00:10 2560.26 24-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 4.50 0.00 01-JAN-00:10 2560.26 24-JUL-15:00
EnergyTransfer:Zone:PERIMETER_ZN_4 14.85 0.00 01-JAN-00:40 6133.06 04-DEC-06:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 11.21 0.00 01-JAN-00:40 6133.06 04-DEC-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 11.21 0.00 01-JAN-00:40 6133.06 04-DEC-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 3.64 0.00 01-JAN-00:10 2720.17 24-JUL-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 3.64 0.00 01-JAN-00:10 2720.17 24-JUL-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 0.00 01-JAN-00:10 118.30 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 0.00 01-JAN-00:10 118.30 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 118.30 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 118.30 02-JAN-07:10
EnergyTransfer:HVAC 119.64 0.00 01-JAN-00:40 32009.46 17-JAN-07:10
CoolingCoils:EnergyTransfer 33.82 0.00 01-JAN-00:10 21970.87 30-JUN-16:00
HeatingCoils:EnergyTransfer 85.82 0.00 01-JAN-00:40 32009.46 17-JAN-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 0.00 01-JAN-00:10 118.30 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 118.30 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 0.00 01-JAN-00:10 118.30 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 3.260 -11.360 0.000 0.000 5.420 8.739 14.140 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -20.200
PERIMETER_ZN_1 0.000 0.000 16.418 -7.118 0.000 0.000 4.153 5.395 10.719 20.836 0.000 0.092 0.000 0.000 -11.225 0.000 -11.355 -27.916
PERIMETER_ZN_2 0.000 0.000 10.931 -3.746 0.000 0.000 1.808 3.293 6.359 8.155 0.000 0.011 0.000 0.000 -6.237 0.000 -3.008 -17.565
PERIMETER_ZN_3 0.000 0.000 19.499 -4.496 0.000 0.000 4.194 5.724 10.719 4.298 0.000 0.020 0.000 0.000 -9.999 0.000 -4.450 -25.509
PERIMETER_ZN_4 0.000 0.000 11.207 -3.643 0.000 0.000 2.465 3.299 6.359 8.294 0.000 0.009 0.000 0.000 -6.485 0.000 -3.031 -18.474
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 11.018 19.802 0.000 0.000 0.000 -30.820 -0.001
Total Facility 0.000 0.000 61.315 -30.363 0.000 0.000 18.040 26.451 48.296 41.583 0.000 11.149 19.803 0.000 -33.946 0.000 -52.664 -109.664


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 11-SEP-05:02 0.00 0.00 0.00 -4963.75 0.00 0.00 54.65 32.22 486.79 0.00 0.00 0.00 4390.09 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 14-AUG-05:02 0.00 0.00 0.00 -5462.55 0.00 0.00 40.60 24.42 369.02 0.00 0.00 0.00 5555.66 0.00 -309.51 0.00 -217.63 0.00
PERIMETER_ZN_2 07-SEP-10:02 0.00 0.00 0.00 -3604.23 0.00 0.00 244.20 244.18 437.82 1929.35 0.00 0.00 756.88 0.00 -0.00 0.00 -8.20 0.00
PERIMETER_ZN_3 14-AUG-05:02 0.00 0.00 0.00 -3978.32 0.00 0.00 44.72 24.42 369.02 0.00 0.00 0.00 3854.03 0.00 -216.19 0.00 -97.69 0.00
PERIMETER_ZN_4 14-AUG-05:02 0.00 0.00 0.00 -3990.29 0.00 0.00 24.38 14.49 218.91 0.00 0.00 0.00 3968.95 0.00 -165.55 0.00 -70.88 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 07-AUG-05:02 0.00 0.00 0.00 -21253.74 0.00 0.00 188.07 110.04 1662.65 0.00 0.00 179.75 20606.78 0.00 -1012.91 0.00 -480.64 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 17-JAN-06:01 0.00 0.00 7729.22 0.00 0.00 0.00 88.62 32.22 486.79 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8336.86
PERIMETER_ZN_1 17-JAN-06:01 0.00 0.00 9613.30 0.00 0.00 0.00 70.05 24.42 369.02 0.00 0.00 0.00 0.00 0.00 -644.51 0.00 -455.17 -8977.13
PERIMETER_ZN_2 04-DEC-06:01 0.00 0.00 6712.40 0.00 0.00 0.00 41.82 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -389.48 0.00 -288.23 -6309.90
PERIMETER_ZN_3 09-JAN-05:02 0.00 0.00 7367.19 0.00 0.00 0.00 0.00 24.42 314.97 0.00 0.00 0.00 0.00 0.00 -1102.28 0.00 -509.79 -6094.51
PERIMETER_ZN_4 21-FEB-06:01 0.00 0.00 7770.78 0.00 0.00 0.00 41.19 14.49 218.91 0.00 0.00 0.00 0.00 0.00 -213.12 0.00 -150.78 -7681.46
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-JAN-06:01 0.00 0.00 38397.61 0.00 0.00 0.00 311.00 110.04 1662.65 0.00 0.00 1066.07 0.00 0.00 -1853.55 0.00 -885.68 -38808.13



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2822 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2822 0.2290 1.0000 Not calculated 0.0646 0.2290    
PSZ-AC:2 0.3383 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3383 0.1448 1.0000 Not calculated 0.0490 0.1448    
PSZ-AC:3 0.2365 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2365 0.1229 1.0000 Not calculated 0.0291 0.1229    
PSZ-AC:4 0.2422 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2422 0.2022 1.0000 Not calculated 0.0490 0.2022    
PSZ-AC:5 0.2786 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2786 0.1043 1.0000 Not calculated 0.0291 0.1043    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.2822 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.2822 1.0000 1.0000 Not calculated 0.0646 0.2290    
PSZ-AC:2 0.3383 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.3383 1.0000 1.0000 Not calculated 0.0490 0.1448    
PSZ-AC:3 0.2365 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2365 1.0000 1.0000 Not calculated 0.0291 0.1229    
PSZ-AC:4 0.2422 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.2422 1.0000 1.0000 Not calculated 0.0490 0.2022    
PSZ-AC:5 0.2786 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.2786 1.0000 1.0000 Not calculated 0.0291 0.1043    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2822 0.2822 0.2822 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3383 0.3383 0.3383 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2365 0.2365 0.2365 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2422 0.2422 0.2422 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2786 0.2786 0.2786 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2822 0.2822 0.2822 0.2822 0.0646 1.0000
PSZ-AC:2 0.3383 0.3383 0.3383 0.3383 0.0490 1.0000
PSZ-AC:3 0.2365 0.2365 0.2365 0.2365 0.0291 1.0000
PSZ-AC:4 0.2422 0.2422 0.2422 0.2422 0.0490 1.0000
PSZ-AC:5 0.2786 0.2786 0.2786 0.2786 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2822 0.2822 0.2822 No 0.0646 0.9418 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3383 0.3383 0.3383 No 0.0490 0.2095 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2365 0.2365 0.2365 No 0.0291 0.1982 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2422 0.2422 0.2422 No 0.0490 0.2111 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.2786 0.2786 0.2786 No 0.0291 0.1969 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.2822 0.2822 0.2822 0.2822 0.0646 1.0000
PSZ-AC:2 0.3383 0.3383 0.3383 0.3383 0.0490 1.0000
PSZ-AC:3 0.2365 0.2365 0.2365 0.2365 0.0291 1.0000
PSZ-AC:4 0.2422 0.2422 0.2422 0.2422 0.0490 1.0000
PSZ-AC:5 0.2786 0.2786 0.2786 0.2786 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Total gross floor area [m2] 511.16
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 161.83
Number of hours cooling loads not met 3.50
Number of hours not met 165.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 19.88 7802.13 65.97 39908.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 7.42 5202.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 26.45 2540.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 10.04 1061.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 48.30 3325.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 19.92 1543.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 25.80 2851.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 48.30 157.80
Natural Gas 0.00 65.97
Additional 0.00 0.00
Total 48.30 223.77


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 51.75
Space Heating 38.88
Space Cooling 14.51
Fans (All) 38.96
Service Water Heating 50.48
Receptacle Equipment 94.48
Miscellaneous (All) 308.71
Subtotal 308.71


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 129.06
Service Water Heating 0.00
Miscellaneous (All) 129.06
Subtotal 129.06


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 11.82
Space Heating 38.36
Space Cooling 3.31
Fans (All) 8.90
Service Water Heating 11.53
Receptacle Equipment 21.58
Miscellaneous 4.49


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2885. 8760.
BLDG_EQUIP_SCH 3948. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1121. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365
HTGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL January 20.55 365 15.56 365
CLGSETP_SCH_NO_OPTIMUM_W_SB PERIMETER_ZN_2 DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 8742.00 18.00 0.00 0.00 0.00
PERIMETER_ZN_1 8631.33 128.67 0.00 0.00 0.00
PERIMETER_ZN_2 8689.67 70.33 0.00 0.00 0.00
PERIMETER_ZN_3 8751.50 8.50 0.00 0.00 0.00
PERIMETER_ZN_4 8547.33 212.67 0.00 0.00 0.00
ATTIC 7531.67 438.00 358.83 356.83 74.67
Min 7531.67 8.50 0.00 0.00 0.00
Max 8751.50 438.00 358.83 356.83 74.67
Average 8482.25 146.03 59.81 59.47 12.44
Sum 50893.50 876.17 358.83 356.83 74.67


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 7696.17 1063.83 0.00 0.00 0.00
PERIMETER_ZN_1 8129.00 631.00 0.00 0.00 0.00
PERIMETER_ZN_2 8242.50 517.50 0.00 0.00 0.00
PERIMETER_ZN_3 8285.67 474.33 0.00 0.00 0.00
PERIMETER_ZN_4 8162.17 597.83 0.00 0.00 0.00
ATTIC 7522.00 688.17 211.00 170.50 168.33
Min 7522.00 474.33 0.00 0.00 0.00
Max 8285.67 1063.83 211.00 170.50 168.33
Average 8006.25 662.11 35.17 28.42 28.06
Sum 48037.50 3972.67 211.00 170.50 168.33


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17891.67 0.33 0.00 0.00 0.00
PERIMETER_ZN_1 13313.00 43.00 0.00 0.00 0.00
PERIMETER_ZN_2 4787.50 0.50 0.00 0.00 0.00
PERIMETER_ZN_3 13322.00 34.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17891.67 43.00 0.00 0.00 0.00
Average 9353.03 12.97 0.00 0.00 0.00
Sum 56118.17 77.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:27:22

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -16.89
February -11.56
March -6.15
April 3.968
May 13.433
June 18.029
July 19.667
August 17.942
September 12.293
October 5.424
November -2.00
December -14.64
   
Annual Sum or Average 3.363
Minimum of Months -16.89
Maximum of Months 19.667



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134841E+09 3312.40 05-JAN-11:23 -29.1 -29.4 0.221976E+09 304.45 11-JAN-08:09 -27.0 -27.2
February 0.207591E+09 2846.83 01-FEB-10:42 -22.4 -22.9 0.201804E+09 313.74 08-FEB-16:19 4.03 -1.1
March 0.417867E+09 2688.88 15-MAR-08:52 -20.0 -20.5 0.245533E+09 346.15 31-MAR-15:00 8.90 3.77
April 0.503387E+09 1778.48 04-APR-07:53 -7.8 -10.0 0.232382E+09 402.33 13-APR-15:09 20.00 8.11
May 0.886313E+09 4210.69 19-MAY-05:03 14.23 9.76 0.298976E+09 402.38 03-MAY-13:39 14.23 9.76
June 0.158124E+10 4729.97 19-JUN-05:03 17.80 16.77 0.311895E+09 402.36 30-JUN-07:00 25.60 21.60
July 0.208781E+10 4358.21 27-JUL-05:02 10.28 9.90 0.284747E+09 402.36 13-JUL-15:20 10.28 9.90
August 0.232996E+10 4466.39 01-AUG-05:02 17.88 17.34 0.327177E+09 402.37 28-AUG-10:00 18.90 17.44
September 0.153546E+10 4963.73 11-SEP-05:02 12.62 10.52 0.283187E+09 402.36 12-SEP-12:50 12.70 10.05
October 0.913440E+09 1697.82 25-OCT-06:03 -4.2 -4.4 0.268701E+09 402.35 26-OCT-13:30 14.15 8.57
November 0.546147E+09 2228.25 29-NOV-08:53 -14.4 -14.8 0.232320E+09 399.95 01-NOV-15:00 -14.4 -14.8
December 0.215983E+09 3067.58 20-DEC-10:32 -25.7 -26.0 0.211936E+09 304.46 14-DEC-08:09 -25.7 -26.0
                     
Annual Sum or Average 0.113600E+11         0.312064E+10        
Minimum of Months 0.134841E+09 1697.82   -29.1 -29.4 0.201804E+09 304.45   -27.0 -27.2
Maximum of Months 0.232996E+10 4963.73   17.88 17.34 0.327177E+09 402.38   25.60 21.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 38328160.96 1935.92 06-JAN-14:13 -22.6 -23.2 0.165193E+09 230.75 03-JAN-13:09 -22.6 -23.2
February 62170026.99 1789.99 01-FEB-15:43 -19.9 -20.8 0.152114E+09 280.89 28-FEB-15:39 6.10 1.55
March 85509909.80 1369.79 15-MAR-13:43 -11.8 -13.4 0.185368E+09 291.65 31-MAR-15:20 8.50 3.01
April 0.135918E+09 1090.27 13-APR-14:40 19.63 7.88 0.172610E+09 304.99 18-APR-15:00 11.70 5.87
May 0.447540E+09 2454.15 18-MAY-13:50 28.45 16.75 0.214017E+09 305.02 25-MAY-15:09 28.93 19.66
June 0.902758E+09 3908.26 29-JUN-05:02 22.30 19.61 0.231959E+09 305.04 06-JUN-08:50 22.30 19.61
July 0.154850E+10 4712.75 03-JUL-05:02 17.98 16.78 0.215376E+09 305.03 13-JUL-15:20 25.93 20.31
August 0.189719E+10 5462.58 14-AUG-05:02 15.92 13.40 0.247577E+09 305.02 07-AUG-15:00 15.92 13.40
September 0.124266E+10 5433.20 11-SEP-05:02 12.62 10.52 0.209982E+09 305.01 11-SEP-15:09 19.40 15.05
October 0.568659E+09 3590.77 20-OCT-13:50 18.80 10.02 0.194151E+09 305.00 02-OCT-13:50 18.80 10.02
November 0.175861E+09 1257.53 17-NOV-13:20 10.20 3.29 0.174469E+09 304.99 17-NOV-16:19 8.90 2.59
December 12786141.09 1757.32 01-DEC-11:33 -19.2 -19.7 0.158269E+09 230.75 18-DEC-11:00 -22.8 -23.6
                     
Annual Sum or Average 0.711788E+10         0.232108E+10        
Minimum of Months 12786141.09 1090.27   -22.6 -23.2 0.152114E+09 230.75   -22.8 -23.6
Maximum of Months 0.189719E+10 5462.58   28.45 19.61 0.247577E+09 305.04   28.93 20.31



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -21.9 -22.1 71617885.35 136.88 11-JAN-08:09 -27.0 -27.2
February 351426.22 555.36 28-FEB-11:03 -2.4 -4.8 65020396.14 136.88 13-FEB-13:00 -2.4 -4.8
March 4396138.31 846.27 15-MAR-10:03 -17.4 -18.2 78971346.85 138.03 31-MAR-10:09 2.07 -0.7
April 29498312.61 648.01 05-APR-10:05 -5.3 -8.0 72967086.58 176.67 13-APR-15:00 20.00 8.11
May 0.219519E+09 2789.10 18-MAY-10:02 25.42 16.29 94021375.75 190.45 25-MAY-14:09 27.98 19.41
June 0.683799E+09 3015.08 20-JUN-10:02 17.48 13.84 0.102510E+09 190.45 08-JUN-14:09 17.48 13.84
July 0.110805E+10 3412.05 31-JUL-10:03 19.40 13.51 94266375.49 190.45 05-JUL-14:09 19.40 13.51
August 0.102481E+10 3444.25 22-AUG-10:02 21.38 15.21 0.108189E+09 190.45 09-AUG-10:09 21.38 15.21
September 0.519296E+09 3604.14 07-SEP-10:02 20.87 13.37 91975623.06 190.45 14-SEP-14:09 20.32 11.83
October 0.133191E+09 2539.59 20-OCT-10:02 12.25 9.46 82450961.60 190.45 20-OCT-14:09 18.90 10.07
November 23373899.13 514.18 10-NOV-16:33 -3.5 -5.8 73148281.67 165.39 01-NOV-15:00 -3.5 -5.8
December 0.00 0.00 01-DEC-00:05 -8.8 -9.9 68425588.29 136.88 29-DEC-08:09 -16.3 -16.7
                     
Annual Sum or Average 0.374629E+10         0.100356E+10        
Minimum of Months 0.00 0.00   -21.9 -22.1 65020396.14 136.88   -27.0 -27.2
Maximum of Months 0.110805E+10 3604.14   25.42 16.29 0.108189E+09 190.45   27.98 19.41



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -21.9 -22.1 0.166042E+09 230.76 03-JAN-11:00 -20.6 -20.9
February 0.00 0.00 01-FEB-00:05 -23.1 -23.5 0.150783E+09 230.76 13-FEB-14:00 -18.9 -19.8
March 0.00 0.00 01-MAR-00:10 -1.3 -3.3 0.183087E+09 230.78 23-MAR-07:10 -17.6 -17.9
April 12307227.48 393.40 24-APR-15:05 8.90 5.04 0.161471E+09 265.39 13-APR-15:00 8.90 5.04
May 0.260043E+09 1310.13 25-MAY-16:00 29.10 19.63 0.207428E+09 308.88 16-MAY-13:39 29.10 19.63
June 0.721099E+09 2995.72 29-JUN-05:02 22.30 19.61 0.232150E+09 305.02 28-JUN-14:09 22.30 19.61
July 0.122095E+10 3753.37 07-JUL-05:02 13.07 12.22 0.215245E+09 305.02 28-JUL-15:09 29.40 19.88
August 0.129494E+10 3978.41 14-AUG-05:02 15.92 13.40 0.247146E+09 305.02 08-AUG-13:09 15.92 13.40
September 0.660628E+09 2826.35 01-SEP-05:02 15.68 15.63 0.207919E+09 305.02 01-SEP-13:00 25.60 18.11
October 0.287062E+09 948.33 04-OCT-07:10 0.37 0.10 0.181754E+09 305.10 19-OCT-15:09 22.12 13.61
November 39204312.41 824.30 03-NOV-09:05 0.68 -1.5 0.168921E+09 275.49 01-NOV-15:00 0.68 -1.5
December 0.00 0.00 01-DEC-00:05 -8.8 -9.9 0.158802E+09 230.76 18-DEC-11:00 -22.8 -23.6
                     
Annual Sum or Average 0.449624E+10         0.228075E+10        
Minimum of Months 0.00 0.00   -23.1 -23.5 0.150783E+09 230.76   -22.8 -23.6
Maximum of Months 0.129494E+10 3978.41   29.10 19.63 0.247146E+09 308.88   29.40 19.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 567006.03 551.53 20-JAN-16:30 -6.4 -7.8 98964970.09 136.88 11-JAN-08:09 -6.4 -7.8
February 5803168.57 379.06 22-FEB-16:23 -0.9 -3.9 89857263.80 145.51 08-FEB-16:49 -0.9 -3.9
March 15330349.82 459.93 17-MAR-16:00 -1.7 -5.6 0.109188E+09 155.80 31-MAR-15:00 8.90 3.77
April 23332488.38 331.21 13-APR-15:53 20.00 8.11 99061289.15 180.92 13-APR-15:50 20.00 8.11
May 0.248132E+09 1785.54 18-MAY-15:57 28.50 16.32 0.128350E+09 181.14 22-MAY-12:09 15.90 12.01
June 0.571877E+09 2936.08 29-JUN-05:02 22.30 19.61 0.139229E+09 181.25 13-JUN-09:20 22.30 19.61
July 0.988161E+09 3720.01 07-JUL-05:02 13.07 12.22 0.128653E+09 180.95 03-JUL-15:39 13.07 12.22
August 0.105183E+10 3990.34 14-AUG-05:02 15.92 13.40 0.147437E+09 180.95 29-AUG-14:00 25.60 20.24
September 0.524757E+09 2739.50 01-SEP-05:02 15.68 15.63 0.125928E+09 180.94 01-SEP-14:09 25.68 18.06
October 0.180131E+09 1081.21 19-OCT-15:57 21.70 13.55 0.113618E+09 180.93 02-OCT-15:09 21.70 13.55
November 32892766.70 482.91 10-NOV-16:20 -2.6 -5.2 0.101012E+09 170.35 01-NOV-15:00 -2.6 -5.2
December 0.00 0.00 01-DEC-00:05 -8.8 -9.9 94475158.71 136.88 18-DEC-11:00 -22.8 -23.6
                     
Annual Sum or Average 0.364281E+10         0.137577E+10        
Minimum of Months 0.00 0.00   -8.8 -9.9 89857263.80 136.88   -22.8 -23.6
Maximum of Months 0.105183E+10 3990.34   28.50 19.61 0.147437E+09 181.25   25.68 20.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -21.9 -22.1 0.00 0.00 01-JAN-00:10 -21.9 -22.1
February 0.00 0.00 01-FEB-00:05 -23.1 -23.5 0.00 0.00 01-FEB-00:10 -23.1 -23.5
March 0.00 0.00 01-MAR-00:10 -1.3 -3.3 0.00 0.00 01-MAR-00:10 -1.3 -3.3
April 0.00 0.00 01-APR-00:10 3.52 0.38 0.00 0.00 01-APR-00:10 3.52 0.38
May 0.00 0.00 01-MAY-00:10 -0.0 -1.4 0.00 0.00 01-MAY-00:10 -0.0 -1.4
June 0.00 0.00 01-JUN-00:10 11.35 8.93 0.00 0.00 01-JUN-00:10 11.35 8.93
July 0.00 0.00 01-JUL-00:10 15.83 13.57 0.00 0.00 01-JUL-00:10 15.83 13.57
August 0.00 0.00 01-AUG-00:10 17.07 15.36 0.00 0.00 01-AUG-00:10 17.07 15.36
September 0.00 0.00 01-SEP-00:10 19.75 18.15 0.00 0.00 01-SEP-00:10 19.75 18.15
October 0.00 0.00 01-OCT-00:10 7.52 6.57 0.00 0.00 01-OCT-00:10 7.52 6.57
November 0.00 0.00 01-NOV-00:10 3.60 0.51 0.00 0.00 01-NOV-00:10 3.60 0.51
December 0.00 0.00 01-DEC-00:05 -8.8 -9.9 0.00 0.00 01-DEC-00:10 -8.8 -9.9
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   -23.1 -23.5 0.00 0.00   -23.1 -23.5
Maximum of Months 0.00 0.00   19.75 18.15 0.00 0.00   19.75 18.15



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.985413E+09 7729.21 17-JAN-06:01 -5.9
February 0.581946E+09 7549.12 21-FEB-06:01 2.80
March 0.480926E+09 7191.51 20-MAR-05:01 -8.7
April 0.153502E+09 7217.26 10-APR-05:01 -2.7
May 54190929.00 6962.56 01-MAY-05:01 -3.4
June 19413991.08 1022.43 29-JUN-17:02 34.13
July 15495203.66 624.06 28-JUL-17:02 28.90
August 10703363.39 641.78 08-AUG-17:02 29.22
September 1551095.43 391.53 13-SEP-05:07 3.98
October 22511708.47 5818.31 10-OCT-05:01 3.40
November 0.254206E+09 7513.09 27-NOV-06:01 -7.1
December 0.680206E+09 7445.12 04-DEC-06:01 -9.4
         
Annual Sum or Average 0.326007E+10      
Minimum of Months 1551095.43 391.53   -9.4
Maximum of Months 0.985413E+09 7729.21   34.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.420959E+10 9613.31 17-JAN-06:01 -5.9
February 0.268373E+10 9492.95 21-FEB-06:01 2.80
March 0.258661E+10 9324.31 17-MAR-05:01 -8.1
April 0.114297E+10 9503.52 04-APR-05:01 -9.0
May 0.284670E+09 9313.52 01-MAY-05:01 -3.4
June 52940813.21 1212.83 01-JUN-05:05 14.08
July 21631381.90 588.87 28-JUL-17:12 28.90
August 15949636.60 579.95 08-AUG-17:12 29.03
September 18473093.17 1408.49 21-SEP-06:10 5.10
October 0.320800E+09 8529.79 30-OCT-05:01 -9.9
November 0.141129E+10 9450.84 24-NOV-06:01 -10.5
December 0.366958E+10 9468.21 12-DEC-06:01 -11.6
         
Annual Sum or Average 0.164182E+11      
Minimum of Months 15949636.60 579.95   -11.6
Maximum of Months 0.420959E+10 9613.31   29.03



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.291322E+10 6707.24 17-JAN-06:01 -5.9
February 0.204470E+10 6652.19 21-FEB-06:01 2.80
March 0.175981E+10 6648.91 20-MAR-05:01 -8.7
April 0.628477E+09 6604.44 04-APR-05:01 -9.0
May 0.104727E+09 6637.63 01-MAY-05:01 -3.4
June 24145939.68 568.03 01-JUN-05:05 14.08
July 14207297.84 386.11 28-JUL-17:12 28.90
August 12255702.31 386.21 08-AUG-17:12 29.03
September 13355571.50 315.24 08-SEP-05:04 10.10
October 0.137519E+09 6096.79 30-OCT-05:01 -9.9
November 0.866733E+09 6602.53 28-NOV-06:01 -7.8
December 0.241146E+10 6712.40 04-DEC-06:01 -9.4
         
Annual Sum or Average 0.109306E+11      
Minimum of Months 12255702.31 315.24   -9.9
Maximum of Months 0.291322E+10 6712.40   29.03



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.489635E+10 7367.19 09-JAN-05:02 -33.0
February 0.363290E+10 7131.36 19-FEB-06:12 -23.3
March 0.337202E+10 7203.97 06-MAR-05:22 -18.6
April 0.144946E+10 6911.98 10-APR-05:01 -2.7
May 0.291375E+09 6766.55 01-MAY-05:01 -3.4
June 33835538.13 1038.27 01-JUN-05:05 14.08
July 15764140.26 504.30 28-JUL-17:12 28.90
August 12403570.50 505.62 08-AUG-17:02 29.22
September 17337776.61 292.98 01-SEP-05:06 15.68
October 0.257800E+09 6326.88 30-OCT-05:01 -9.9
November 0.150470E+10 6831.69 24-NOV-06:01 -10.5
December 0.401502E+10 7309.31 25-DEC-08:52 -27.2
         
Annual Sum or Average 0.194990E+11      
Minimum of Months 12403570.50 292.98   -33.0
Maximum of Months 0.489635E+10 7367.19   29.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.294223E+10 7538.88 30-JAN-06:01 -4.0
February 0.205986E+10 7770.76 21-FEB-06:01 2.80
March 0.181534E+10 7526.52 09-MAR-06:01 -1.3
April 0.732944E+09 7657.94 10-APR-05:01 -2.7
May 0.148018E+09 7633.23 01-MAY-05:01 -3.4
June 36743596.10 972.43 01-JUN-05:05 14.08
July 13485730.44 426.01 06-JUL-05:04 15.10
August 12354583.75 425.27 03-AUG-05:04 11.10
September 13227229.60 363.64 08-SEP-05:04 10.10
October 0.145381E+09 7020.07 30-OCT-05:01 -9.9
November 0.873236E+09 7470.80 06-NOV-06:01 -3.9
December 0.241447E+10 7612.82 05-DEC-06:01 -1.1
         
Annual Sum or Average 0.112073E+11      
Minimum of Months 12354583.75 363.64   -9.9
Maximum of Months 0.294223E+10 7770.76   15.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -21.9
February 0.00 0.00 01-FEB-00:05 -23.1
March 0.00 0.00 01-MAR-00:10 -1.3
April 0.00 0.00 01-APR-00:10 3.52
May 0.00 0.00 01-MAY-00:10 -0.0
June 0.00 0.00 01-JUN-00:10 11.35
July 0.00 0.00 01-JUL-00:10 15.83
August 0.00 0.00 01-AUG-00:10 17.07
September 0.00 0.00 01-SEP-00:10 19.75
October 0.00 0.00 01-OCT-00:10 7.52
November 0.00 0.00 01-NOV-00:10 3.60
December 0.00 0.00 01-DEC-00:05 -8.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -23.1
Maximum of Months 0.00 0.00   19.75



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.729889E+09 743.94 02-JAN-08:09 0.118664E+10 973.59 02-JAN-08:09
February 0.660244E+09 743.94 01-FEB-08:09 0.107295E+10 973.59 01-FEB-08:09
March 0.791184E+09 743.94 01-MAR-08:09 0.125726E+10 973.59 01-MAR-08:09
April 0.696458E+09 743.94 03-APR-07:10 0.113787E+10 973.59 03-APR-07:10
May 0.760537E+09 743.94 01-MAY-07:10 0.122195E+10 973.59 01-MAY-07:10
June 0.757753E+09 743.94 01-JUN-07:10 0.120670E+10 973.59 01-JUN-07:10
July 0.699242E+09 743.94 03-JUL-07:10 0.115223E+10 973.59 03-JUL-07:10
August 0.791184E+09 743.94 01-AUG-07:10 0.125726E+10 973.59 01-AUG-07:10
September 0.696458E+09 743.94 01-SEP-07:10 0.113608E+10 973.59 01-SEP-07:10
October 0.729889E+09 743.94 02-OCT-07:10 0.118754E+10 973.59 02-OCT-07:10
November 0.727106E+09 743.94 01-NOV-07:10 0.117228E+10 973.59 01-NOV-07:10
December 0.699242E+09 743.94 01-DEC-08:09 0.115133E+10 973.59 01-DEC-08:09
             
Annual Sum or Average 0.873919E+10     0.141401E+11    
Minimum of Months 0.660244E+09 743.94   0.107295E+10 973.59  
Maximum of Months 0.791184E+09 743.94   0.125726E+10 973.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.468756E+09 563.96 02-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.411746E+09 548.24 02-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.487616E+09 544.41 03-MAR-16:00 0.953087E+09 738.04 01-MAR-08:09
April 0.420829E+09 521.18 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.451927E+09 476.12 19-MAY-08:30 0.926320E+09 738.04 01-MAY-07:10
June 0.450135E+09 521.12 30-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.415155E+09 492.65 03-JUL-07:10 0.873466E+09 738.04 03-JUL-07:10
August 0.479130E+09 537.48 31-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.425760E+09 538.27 19-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.456388E+09 562.60 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.468468E+09 563.96 06-NOV-16:49 0.888667E+09 738.04 01-NOV-07:10
December 0.459178E+09 563.96 01-DEC-16:19 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.539509E+10     0.107191E+11    
Minimum of Months 0.411746E+09 476.12   0.813362E+09 738.04  
Maximum of Months 0.487616E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.290031E+09 334.55 02-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.253998E+09 328.77 02-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.298473E+09 325.26 03-MAR-16:00 0.565383E+09 437.82 01-MAR-08:09
April 0.256132E+09 305.95 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.272775E+09 297.10 05-MAY-15:00 0.549505E+09 437.82 01-MAY-07:10
June 0.271014E+09 307.42 30-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.249977E+09 299.26 25-JUL-15:39 0.518151E+09 437.82 03-JUL-07:10
August 0.289392E+09 318.66 31-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.258973E+09 318.61 19-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.280909E+09 333.75 31-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.289477E+09 334.55 06-NOV-16:49 0.527169E+09 437.82 01-NOV-07:10
December 0.282248E+09 334.55 01-DEC-16:19 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.329340E+10     0.635872E+10    
Minimum of Months 0.249977E+09 297.10   0.482497E+09 437.82  
Maximum of Months 0.298473E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.517791E+09 563.96 02-JAN-08:09 0.899552E+09 738.04 02-JAN-08:09
February 0.451209E+09 552.65 02-FEB-16:00 0.813362E+09 738.04 01-FEB-08:09
March 0.527593E+09 547.15 03-MAR-16:00 0.953087E+09 738.04 01-MAR-08:09
April 0.448347E+09 526.51 03-APR-07:10 0.862580E+09 738.04 03-APR-07:10
May 0.457111E+09 491.40 19-MAY-08:30 0.926320E+09 738.04 01-MAY-07:10
June 0.450751E+09 523.34 30-JUN-07:10 0.914754E+09 738.04 01-JUN-07:10
July 0.417740E+09 496.99 25-JUL-15:30 0.873466E+09 738.04 03-JUL-07:10
August 0.490608E+09 540.31 31-AUG-07:10 0.953087E+09 738.04 01-AUG-07:10
September 0.451251E+09 541.47 19-SEP-07:10 0.861220E+09 738.04 01-SEP-07:10
October 0.497252E+09 562.95 31-OCT-07:10 0.900233E+09 738.04 02-OCT-07:10
November 0.514575E+09 563.96 06-NOV-16:49 0.888667E+09 738.04 01-NOV-07:10
December 0.499934E+09 563.96 01-DEC-16:19 0.872785E+09 738.04 01-DEC-08:09
             
Annual Sum or Average 0.572416E+10     0.107191E+11    
Minimum of Months 0.417740E+09 491.40   0.813362E+09 738.04  
Maximum of Months 0.527593E+09 563.96   0.953087E+09 738.04  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.289850E+09 334.55 02-JAN-08:09 0.533626E+09 437.82 02-JAN-08:09
February 0.253191E+09 324.85 02-FEB-16:00 0.482497E+09 437.82 01-FEB-08:09
March 0.299990E+09 325.33 13-MAR-07:10 0.565383E+09 437.82 01-MAR-08:09
April 0.258543E+09 315.94 03-APR-07:10 0.511694E+09 437.82 03-APR-07:10
May 0.272813E+09 300.88 12-MAY-07:10 0.549505E+09 437.82 01-MAY-07:10
June 0.270920E+09 312.89 30-JUN-07:10 0.542644E+09 437.82 01-JUN-07:10
July 0.251299E+09 302.19 03-JUL-07:10 0.518151E+09 437.82 03-JUL-07:10
August 0.289936E+09 321.19 31-AUG-07:10 0.565383E+09 437.82 01-AUG-07:10
September 0.259657E+09 322.24 19-SEP-07:10 0.510887E+09 437.82 01-SEP-07:10
October 0.280542E+09 333.96 31-OCT-07:10 0.534030E+09 437.82 02-OCT-07:10
November 0.289301E+09 334.55 06-NOV-16:49 0.527169E+09 437.82 01-NOV-07:10
December 0.283080E+09 334.55 01-DEC-16:19 0.517747E+09 437.82 01-DEC-08:09
             
Annual Sum or Average 0.329912E+10     0.635872E+10    
Minimum of Months 0.251299E+09 300.88   0.482497E+09 437.82  
Maximum of Months 0.299990E+09 334.55   0.565383E+09 437.82  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.729889E+09 0.118664E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.696458E+09 0.113787E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.760537E+09 0.122195E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.757753E+09 0.120670E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.699242E+09 0.115223E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.696458E+09 0.113608E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.729889E+09 0.118754E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.727106E+09 0.117228E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.699242E+09 0.115133E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.873919E+10 0.141401E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.660244E+09 0.107295E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.791184E+09 0.125726E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.468756E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.204846E+10
February 0.488155E+09 0.411746E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.160322E+10
March 0.590925E+09 0.487616E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.00 0.136053E+10
April 0.513848E+09 0.420829E+09 0.862580E+09 0.00 0.00 0.00 0.00 1273078.79 0.858676E+09
May 0.565233E+09 0.451927E+09 0.926320E+09 0.00 0.00 0.00 0.00 13180703.22 0.409357E+09
June 0.565233E+09 0.450135E+09 0.914754E+09 0.00 0.00 0.00 0.00 32535519.54 0.219319E+09
July 0.513848E+09 0.415155E+09 0.873466E+09 0.00 0.00 0.00 0.00 29022528.84 0.170458E+09
August 0.590925E+09 0.479130E+09 0.953087E+09 0.00 0.00 0.00 0.00 15303033.71 0.288603E+09
September 0.513848E+09 0.425760E+09 0.861220E+09 0.00 0.00 0.00 0.00 683996.57 0.516021E+09
October 0.539540E+09 0.456388E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.793056E+09
November 0.539540E+09 0.468468E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.118131E+10
December 0.513848E+09 0.459178E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.190573E+10
                   
Annual Sum or Average 0.647448E+10 0.539509E+10 0.107191E+11 0.00 0.00 0.00 0.00 91998860.67 0.113547E+11
Minimum of Months 0.488155E+09 0.411746E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.170458E+09
Maximum of Months 0.590925E+09 0.487616E+09 0.953087E+09 0.00 0.00 0.00 0.00 32535519.54 0.204846E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.290031E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.511009E+09
February 0.211974E+09 0.253998E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.426898E+09
March 0.256600E+09 0.298473E+09 0.565383E+09 0.00 0.00 0.00 0.00 0.00 0.293522E+09
April 0.223130E+09 0.256132E+09 0.511694E+09 0.00 0.00 0.00 0.00 2134063.43 0.238578E+09
May 0.245443E+09 0.272775E+09 0.549505E+09 0.00 0.00 0.00 0.00 888435.22 0.115755E+09
June 0.245443E+09 0.271014E+09 0.542644E+09 0.00 0.00 0.00 0.00 3596172.77 69162244.76
July 0.223130E+09 0.249977E+09 0.518151E+09 0.00 0.00 0.00 0.00 2823478.27 55284425.08
August 0.256600E+09 0.289392E+09 0.565383E+09 0.00 0.00 0.00 0.00 1042190.91 85109632.13
September 0.223130E+09 0.258973E+09 0.510887E+09 0.00 0.00 0.00 0.00 40031.82 0.141740E+09
October 0.234287E+09 0.280909E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 0.194507E+09
November 0.234287E+09 0.289477E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.341831E+09
December 0.223130E+09 0.282248E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.534441E+09
                   
Annual Sum or Average 0.281144E+10 0.329340E+10 0.635872E+10 0.00 0.00 0.00 0.00 10524372.41 0.300784E+10
Minimum of Months 0.211974E+09 0.249977E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 55284425.08
Maximum of Months 0.256600E+09 0.298473E+09 0.565383E+09 0.00 0.00 0.00 0.00 3596172.77 0.534441E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.517791E+09 0.899552E+09 0.00 0.00 0.00 0.00 0.00 0.766001E+09
February 0.488155E+09 0.451209E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 0.639746E+09
March 0.590925E+09 0.527593E+09 0.953087E+09 0.00 0.00 0.00 0.00 0.00 0.438782E+09
April 0.513848E+09 0.448347E+09 0.862580E+09 0.00 0.00 0.00 0.00 4342646.50 0.348571E+09
May 0.565233E+09 0.457111E+09 0.926320E+09 0.00 0.00 0.00 0.00 1620170.63 0.164670E+09
June 0.565233E+09 0.450751E+09 0.914754E+09 0.00 0.00 0.00 0.00 6630671.39 96562143.14
July 0.513848E+09 0.417740E+09 0.873466E+09 0.00 0.00 0.00 0.00 5290678.77 78641670.70
August 0.590925E+09 0.490608E+09 0.953087E+09 0.00 0.00 0.00 0.00 1874560.62 0.117607E+09
September 0.513848E+09 0.451251E+09 0.861220E+09 0.00 0.00 0.00 0.00 65875.46 0.202100E+09
October 0.539540E+09 0.497252E+09 0.900233E+09 0.00 0.00 0.00 0.00 0.00 0.283663E+09
November 0.539540E+09 0.514575E+09 0.888667E+09 0.00 0.00 0.00 0.00 0.00 0.511542E+09
December 0.513848E+09 0.499934E+09 0.872785E+09 0.00 0.00 0.00 0.00 0.00 0.801811E+09
                   
Annual Sum or Average 0.647448E+10 0.572416E+10 0.107191E+11 0.00 0.00 0.00 0.00 19824603.37 0.444970E+10
Minimum of Months 0.488155E+09 0.417740E+09 0.813362E+09 0.00 0.00 0.00 0.00 0.00 78641670.70
Maximum of Months 0.590925E+09 0.527593E+09 0.953087E+09 0.00 0.00 0.00 0.00 6630671.39 0.801811E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.289850E+09 0.533626E+09 0.00 0.00 0.00 0.00 0.00 0.511594E+09
February 0.289580E+09 0.253191E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 0.428034E+09
March 0.350544E+09 0.299990E+09 0.565383E+09 0.00 0.00 0.00 0.00 0.00 0.296278E+09
April 0.304821E+09 0.258543E+09 0.511694E+09 0.00 0.00 0.00 0.00 1351673.54 0.241148E+09
May 0.335303E+09 0.272813E+09 0.549505E+09 0.00 0.00 0.00 0.00 721149.95 0.120519E+09
June 0.335303E+09 0.270920E+09 0.542644E+09 0.00 0.00 0.00 0.00 3307924.08 69927188.16
July 0.304821E+09 0.251299E+09 0.518151E+09 0.00 0.00 0.00 0.00 2693844.03 59905223.40
August 0.350544E+09 0.289936E+09 0.565383E+09 0.00 0.00 0.00 0.00 1049878.98 86899507.67
September 0.304821E+09 0.259657E+09 0.510887E+09 0.00 0.00 0.00 0.00 43868.26 0.143291E+09
October 0.320062E+09 0.280542E+09 0.534030E+09 0.00 0.00 0.00 0.00 0.00 0.195775E+09
November 0.320062E+09 0.289301E+09 0.527169E+09 0.00 0.00 0.00 0.00 0.00 0.342798E+09
December 0.304821E+09 0.283080E+09 0.517747E+09 0.00 0.00 0.00 0.00 0.00 0.535089E+09
                   
Annual Sum or Average 0.384075E+10 0.329912E+10 0.635872E+10 0.00 0.00 0.00 0.00 9168338.83 0.303126E+10
Minimum of Months 0.289580E+09 0.251299E+09 0.482497E+09 0.00 0.00 0.00 0.00 0.00 59905223.40
Maximum of Months 0.350544E+09 0.299990E+09 0.565383E+09 0.00 0.00 0.00 0.00 3307924.08 0.535089E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.128773E+10 0.118785E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110487E+10 0.173324E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.948325E+09 0.273230E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.876167E+09 0.330027E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.755890E+09 0.417710E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.628131E+09 0.403297E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.770962E+09 0.428119E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.660781E+09 0.342418E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.692759E+09 0.256851E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.989716E+09 0.163850E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110994E+10 0.851455E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.119256E+10 0.892702E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.110178E+11 0.308203E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.628131E+09 0.851455E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.128773E+10 0.428119E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 743.94 02-JAN-08:09 973.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 743.94 01-FEB-08:09 973.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 743.94 01-MAR-08:09 973.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 743.94 03-APR-07:10 973.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 743.94 01-MAY-07:10 973.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 743.94 01-JUN-07:10 973.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 743.94 03-JUL-07:10 973.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 743.94 01-AUG-07:10 973.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 743.94 01-SEP-07:10 973.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 743.94 02-OCT-07:10 973.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 743.94 01-NOV-07:10 973.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 743.94 01-DEC-08:09 973.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   743.94   973.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 563.96 02-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 6184.83 06-JAN-07:01
February 732.70 01-FEB-08:09 548.24 02-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 5880.72 14-FEB-07:01
March 732.70 01-MAR-08:09 544.41 03-MAR-16:00 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4696.82 16-MAR-06:02
April 732.70 03-APR-07:10 521.18 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 102.84 23-APR-16:00 3461.92 05-APR-06:05
May 732.70 01-MAY-07:10 476.12 19-MAY-08:30 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 463.96 25-MAY-17:00 2401.28 01-MAY-06:07
June 732.70 01-JUN-07:10 521.12 30-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 978.03 29-JUN-16:10 1194.28 02-JUN-06:03
July 732.70 03-JUL-07:10 492.65 03-JUL-07:10 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 485.54 28-JUL-16:05 1155.27 18-JUL-06:02
August 732.70 01-AUG-07:10 537.48 31-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 596.92 08-AUG-16:03 1344.63 25-AUG-06:05
September 732.70 01-SEP-07:10 538.27 19-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 172.05 01-SEP-16:03 2029.13 06-SEP-06:03
October 732.70 02-OCT-07:10 562.60 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3128.40 30-OCT-07:00
November 732.70 01-NOV-07:10 563.96 06-NOV-16:49 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4107.23 29-NOV-07:03
December 732.70 01-DEC-08:09 563.96 01-DEC-16:19 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 5593.82 20-DEC-07:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   476.12   738.04   0.00 0.00 0.00 0.00 0.00   1155.27  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 978.03   6184.83  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 334.55 02-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 812.99 04-JAN-06:10
February 434.65 01-FEB-08:09 328.77 02-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 967.20 12-FEB-23:00
March 434.65 01-MAR-08:09 325.26 03-MAR-16:00 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 522.51 15-MAR-05:10
April 434.65 03-APR-07:10 305.95 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 124.99 23-APR-15:55 505.04 04-APR-18:02
May 434.65 01-MAY-07:10 297.10 05-MAY-15:00 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 20.04 24-MAY-18:10 203.46 20-MAY-06:00
June 434.65 01-JUN-07:10 307.42 30-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 67.74 29-JUN-18:10 131.73 09-JUN-19:55
July 434.65 03-JUL-07:10 299.26 25-JUL-15:39 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 35.19 23-JUL-14:53 138.45 06-JUL-22:00
August 434.65 01-AUG-07:10 318.66 31-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 23.64 08-AUG-16:00 202.20 27-AUG-06:00
September 434.65 01-SEP-07:10 318.61 19-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 3.91 01-SEP-14:55 258.04 20-SEP-06:00
October 434.65 02-OCT-07:10 333.75 31-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 317.63 31-OCT-19:00
November 434.65 01-NOV-07:10 334.55 06-NOV-16:49 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 524.81 22-NOV-02:00
December 434.65 01-DEC-08:09 334.55 01-DEC-16:19 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 767.54 18-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   297.10   437.82   0.00 0.00 0.00 0.00 0.00   131.73  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 124.99   967.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 563.96 02-JAN-08:09 738.04 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 1177.50 04-JAN-06:10
February 732.70 01-FEB-08:09 552.65 02-FEB-16:00 738.04 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 1450.81 12-FEB-23:00
March 732.70 01-MAR-08:09 547.15 03-MAR-16:00 738.04 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 752.56 15-MAR-05:10
April 732.70 03-APR-07:10 526.51 03-APR-07:10 738.04 03-APR-07:10 0.00 0.00 0.00 0.00 228.84 23-APR-15:55 757.64 04-APR-18:02
May 732.70 01-MAY-07:10 491.40 19-MAY-08:30 738.04 01-MAY-07:10 0.00 0.00 0.00 0.00 36.11 24-MAY-18:10 302.94 20-MAY-06:00
June 732.70 01-JUN-07:10 523.34 30-JUN-07:10 738.04 01-JUN-07:10 0.00 0.00 0.00 0.00 103.69 29-JUN-18:10 194.51 09-JUN-19:55
July 732.70 03-JUL-07:10 496.99 25-JUL-15:30 738.04 03-JUL-07:10 0.00 0.00 0.00 0.00 77.56 23-JUL-14:53 207.07 06-JUL-22:00
August 732.70 01-AUG-07:10 540.31 31-AUG-07:10 738.04 01-AUG-07:10 0.00 0.00 0.00 0.00 35.46 08-AUG-16:00 285.37 27-AUG-06:00
September 732.70 01-SEP-07:10 541.47 19-SEP-07:10 738.04 01-SEP-07:10 0.00 0.00 0.00 0.00 5.87 01-SEP-15:00 383.84 20-SEP-06:00
October 732.70 02-OCT-07:10 562.95 31-OCT-07:10 738.04 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 477.12 31-OCT-19:00
November 732.70 01-NOV-07:10 563.96 06-NOV-16:49 738.04 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 793.50 22-NOV-02:00
December 732.70 01-DEC-08:09 563.96 01-DEC-16:19 738.04 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 1151.79 18-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   491.40   738.04   0.00 0.00 0.00 0.00 0.00   194.51  
Maximum of Months 732.70   563.96   738.04   0.00 0.00 0.00 0.00 228.84   1450.81  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 334.55 02-JAN-08:09 437.82 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 810.14 04-JAN-06:10
February 434.65 01-FEB-08:09 324.85 02-FEB-16:00 437.82 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 967.20 12-FEB-23:00
March 434.65 01-MAR-08:09 325.33 13-MAR-07:10 437.82 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 522.59 15-MAR-05:10
April 434.65 03-APR-07:10 315.94 03-APR-07:10 437.82 03-APR-07:10 0.00 0.00 0.00 0.00 86.34 23-APR-15:55 509.59 04-APR-18:02
May 434.65 01-MAY-07:10 300.88 12-MAY-07:10 437.82 01-MAY-07:10 0.00 0.00 0.00 0.00 10.90 24-MAY-15:00 205.49 20-MAY-06:00
June 434.65 01-JUN-07:10 312.89 30-JUN-07:10 437.82 01-JUN-07:10 0.00 0.00 0.00 0.00 45.96 29-JUN-18:10 158.71 15-JUN-19:53
July 434.65 03-JUL-07:10 302.19 03-JUL-07:10 437.82 03-JUL-07:10 0.00 0.00 0.00 0.00 33.38 15-JUL-18:00 167.16 06-JUL-22:00
August 434.65 01-AUG-07:10 321.19 31-AUG-07:10 437.82 01-AUG-07:10 0.00 0.00 0.00 0.00 23.64 08-AUG-16:00 205.99 27-AUG-06:00
September 434.65 01-SEP-07:10 322.24 19-SEP-07:10 437.82 01-SEP-07:10 0.00 0.00 0.00 0.00 3.91 01-SEP-15:00 260.27 20-SEP-06:00
October 434.65 02-OCT-07:10 333.96 31-OCT-07:10 437.82 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 317.67 31-OCT-19:00
November 434.65 01-NOV-07:10 334.55 06-NOV-16:49 437.82 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 526.31 22-NOV-02:00
December 434.65 01-DEC-08:09 334.55 01-DEC-16:19 437.82 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 767.60 18-DEC-19:01
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   300.88   437.82   0.00 0.00 0.00 0.00 0.00   158.71  
Maximum of Months 434.65   334.55   437.82   0.00 0.00 0.00 0.00 86.34   967.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1895.69 28-JAN-02:45 3818.88 31-JAN-12:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1938.23 17-FEB-07:35 4308.76 13-FEB-13:40
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1673.28 07-MAR-06:01 6971.54 23-MAR-13:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1878.29 22-APR-04:00 5879.47 21-APR-13:10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1656.28 18-MAY-04:55 6996.09 01-MAY-13:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1656.99 04-JUN-04:00 6216.68 14-JUN-13:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1787.84 15-JUL-04:53 6574.50 13-JUL-12:40
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1791.28 05-AUG-03:55 5893.76 05-AUG-13:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1615.97 10-SEP-06:23 4763.99 06-SEP-12:30
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1670.61 25-OCT-07:00 4540.59 09-OCT-12:30
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1635.58 19-NOV-07:20 2818.86 10-NOV-12:50
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1476.61 03-DEC-02:13 2941.05 26-DEC-13:10
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1476.61   2818.86  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1938.23   6996.09  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 3312.40 05-JAN-11:23 3866.15 2975.76 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
February 2846.83 01-FEB-10:42 4832.69 3719.71 4867.94 0.00 0.00 0.00 0.00 0.00 0.00
March 2688.88 15-MAR-08:52 5799.23 4463.65 5841.53 0.00 0.00 0.00 0.00 0.00 0.00
April 1778.48 04-APR-07:53 3866.15 2975.76 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
May 4210.69 19-MAY-05:03 318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
June 4729.97 19-JUN-05:03 425.28 128.87 1947.18 0.00 0.00 0.00 0.00 0.00 0.00
July 4358.21 27-JUL-05:02 637.92 193.31 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
August 4466.39 01-AUG-05:02 637.92 193.31 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
September 4963.73 11-SEP-05:02 637.92 193.31 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
October 1697.82 25-OCT-06:03 608.92 1041.50 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
November 2228.25 29-NOV-08:53 2899.62 2231.82 2920.76 0.00 0.00 0.00 0.00 0.00 0.00
December 3067.58 20-DEC-10:32 3866.15 2975.76 3894.35 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1697.82   318.96 96.65 1460.38 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4963.73   5799.23 4463.65 5841.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1935.92 06-JAN-14:13 2198.10 1234.89 2214.13 0.00 0.00 0.00 0.00 0.00 646.15
February 1789.99 01-FEB-15:43 2198.10 1234.89 2214.13 0.00 0.00 0.00 0.00 0.00 635.42
March 1369.79 15-MAR-13:43 2198.10 1234.89 2214.13 0.00 0.00 0.00 0.00 0.00 586.93
April 1090.27 13-APR-14:40 1465.40 823.26 1476.09 0.00 0.00 0.00 0.00 0.00 63.07
May 2454.15 18-MAY-13:50 732.70 411.63 738.04 0.00 0.00 0.00 0.00 63.43 0.00
June 3908.26 29-JUN-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 45.25
July 4712.75 03-JUL-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 133.53
August 5462.58 14-AUG-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 217.63
September 5433.20 11-SEP-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 401.31
October 3590.77 20-OCT-13:50 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 78.94
November 1257.53 17-NOV-13:20 732.70 411.63 738.04 0.00 0.00 0.00 0.00 0.00 243.72
December 1757.32 01-DEC-11:33 2198.10 1234.89 2214.13 0.00 0.00 0.00 0.00 0.00 704.12
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1090.27   402.98 122.12 738.04 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5462.58   2198.10 1234.89 2214.13 0.00 0.00 0.00 0.00 63.43 704.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:02 0.00 72.44 373.68 0.00 0.00 0.00 0.00 0.00 277.12
February 555.36 28-FEB-11:03 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 40.38
March 846.27 15-MAR-10:03 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 63.88
April 648.01 05-APR-10:05 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 0.00 66.17
May 2789.10 18-MAY-10:02 1738.59 976.74 1751.27 0.00 0.00 0.00 0.00 2.14 0.00
June 3015.08 20-JUN-10:02 2173.23 1220.92 2189.08 0.00 0.00 0.00 0.00 0.00 18.50
July 3412.05 31-JUL-10:03 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 14.73
August 3444.25 22-AUG-10:02 2173.23 1220.92 2189.08 0.00 0.00 0.00 0.00 0.00 2.48
September 3604.14 07-SEP-10:02 2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 0.00 8.20
October 2539.59 20-OCT-10:02 2173.23 1220.92 2189.08 0.00 0.00 0.00 0.00 0.00 12.15
November 514.18 10-NOV-16:33 1303.94 1003.64 1313.45 0.00 0.00 0.00 0.00 0.00 41.48
December 0.00 01-DEC-00:05 0.00 28.98 373.68 0.00 0.00 0.00 0.00 0.00 275.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 28.98 373.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3604.14   2607.88 1465.11 2626.90 0.00 0.00 0.00 0.00 2.14 277.12



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:02 0.00 122.12 629.93 0.00 0.00 0.00 0.00 0.00 415.68
February 0.00 01-FEB-00:05 0.00 48.85 629.93 0.00 0.00 0.00 0.00 0.00 666.78
March 0.00 01-MAR-00:10 0.00 24.42 314.97 0.00 0.00 0.00 0.00 0.00 240.55
April 393.40 24-APR-15:05 1465.40 927.99 1476.09 0.00 0.00 0.00 0.00 0.00 37.07
May 1310.13 25-MAY-16:00 1465.40 897.44 1476.09 0.00 0.00 0.00 0.00 9.90 0.00
June 2995.72 29-JUN-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 21.86
July 3753.37 07-JUL-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 82.21
August 3978.41 14-AUG-05:02 483.58 146.54 2214.13 0.00 0.00 0.00 0.00 0.00 97.69
September 2826.35 01-SEP-05:02 402.98 122.12 1845.11 0.00 0.00 0.00 0.00 0.00 11.51
October 948.33 04-OCT-07:10 1465.40 1085.51 1476.09 0.00 0.00 0.00 0.00 0.00 38.18
November 824.30 03-NOV-09:05 1465.40 992.96 1476.09 0.00 0.00 0.00 0.00 0.00 68.59
December 0.00 01-DEC-00:05 0.00 48.85 629.93 0.00 0.00 0.00 0.00 0.00 413.10
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 24.42 314.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3978.41   1465.40 1085.51 2214.13 0.00 0.00 0.00 0.00 9.90 666.78



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 551.53 20-JAN-16:30 1303.94 876.08 1313.45 0.00 0.00 0.00 0.00 0.00 70.12
February 379.06 22-FEB-16:23 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 54.51
March 459.93 17-MAR-16:00 869.29 488.37 875.63 0.00 0.00 0.00 0.00 0.00 0.00
April 331.21 13-APR-15:53 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 11.88
May 1785.54 18-MAY-15:57 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 7.01 0.00
June 2936.08 29-JUN-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 15.62
July 3720.01 07-JUL-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 56.73
August 3990.34 14-AUG-05:02 286.87 86.93 1313.45 0.00 0.00 0.00 0.00 0.00 70.88
September 2739.50 01-SEP-05:02 239.06 72.44 1094.54 0.00 0.00 0.00 0.00 0.00 7.60
October 1081.21 19-OCT-15:57 1303.94 732.55 1313.45 0.00 0.00 0.00 0.00 0.00 5.74
November 482.91 10-NOV-16:20 1303.94 926.70 1313.45 0.00 0.00 0.00 0.00 0.00 46.72
December 0.00 01-DEC-00:05 0.00 28.98 373.68 0.00 0.00 0.00 0.00 0.00 275.89
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 28.98 373.68 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3990.34   1303.94 926.70 1313.45 0.00 0.00 0.00 0.00 7.01 275.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 881.29 0.00
February 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1200.29 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 929.00 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 968.20 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1236.78 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 581.82 0.00
July 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 784.47 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 573.71 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 239.35 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.19 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1024.17 0.00
December 0.00 01-DEC-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 536.17 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.19 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1236.78 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.145675E+11 17163.02 30-JAN-08:09 0.239377E+11 39908.07 04-JAN-07:10
February 0.133376E+11 16705.02 07-FEB-08:09 0.135392E+11 39908.07 14-FEB-07:10
March 0.162210E+11 16743.05 27-MAR-07:30 0.780271E+10 39536.55 06-MAR-07:10
April 0.125234E+11 16589.96 03-APR-07:10 0.105841E+10 32891.51 05-APR-06:10
May 0.115491E+11 14689.37 01-MAY-07:19 88239189.10 14332.82 01-MAY-05:19
June 0.119392E+11 14929.01 29-JUN-15:00 0.00 0.00 01-JUN-00:10
July 0.121722E+11 14183.13 21-JUL-15:50 0.00 0.00 01-JUL-00:10
August 0.132660E+11 14666.88 08-AUG-15:30 0.00 0.00 01-AUG-00:10
September 0.110796E+11 13640.20 01-SEP-15:39 0.00 0.00 01-SEP-00:10
October 0.118552E+11 15523.79 30-OCT-07:10 80260658.96 10565.56 30-OCT-06:10
November 0.143851E+11 17316.62 27-NOV-16:30 0.183579E+10 34309.75 29-NOV-07:10
December 0.149025E+11 17076.87 13-DEC-16:49 0.176268E+11 39908.07 26-DEC-07:10
             
Annual Sum or Average 0.157798E+12     0.659692E+11    
Minimum of Months 0.110796E+11 13640.20   0.00 0.00  
Maximum of Months 0.162210E+11 17316.62   0.239377E+11 39908.07  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.229632E+10 0.122566E+10 0.405300E+10 0.00 0.227914E+10 0.02 0.247543E+10 0.00 0.00 0.00 0.00 0.223798E+10 0.00
February 0.203039E+10 0.957636E+09 0.366466E+10 0.00 0.179808E+10 0.02 0.285269E+10 0.00 0.00 0.00 0.00 0.203416E+10 0.00
March 0.240486E+10 0.865123E+09 0.429420E+10 0.00 0.187512E+10 0.00 0.447789E+10 0.00 0.00 0.00 0.00 0.230378E+10 0.00
April 0.208031E+10 0.662980E+09 0.388642E+10 0.00 0.142661E+10 0.00 0.231185E+10 10416972.05 0.00 0.00 0.00 0.214482E+10 0.00
May 0.221516E+10 0.559306E+09 0.417360E+10 0.00 0.152937E+10 0.00 0.332736E+09 0.522514E+09 0.00 0.00 0.00 0.221636E+10 0.00
June 0.220057E+10 0.485768E+09 0.412149E+10 0.00 0.153841E+10 0.00 8655761.74 0.145962E+10 0.00 0.00 0.00 0.212465E+10 0.00
July 0.203341E+10 0.525358E+09 0.393546E+10 0.00 0.140855E+10 0.00 0.00 0.216804E+10 0.00 0.00 0.00 0.210141E+10 0.00
August 0.234025E+10 0.622422E+09 0.429420E+10 0.00 0.161452E+10 0.00 0.00 0.223993E+10 0.00 0.00 0.00 0.215469E+10 0.00
September 0.209210E+10 0.753979E+09 0.388029E+10 0.00 0.139507E+10 0.00 25973951.56 0.892400E+09 0.00 0.00 0.00 0.203982E+10 0.00
October 0.224498E+10 0.976587E+09 0.405607E+10 0.00 0.145692E+10 0.00 0.858790E+09 0.122134E+09 0.00 0.00 0.00 0.213968E+10 0.00
November 0.228893E+10 0.113037E+10 0.400396E+10 0.00 0.156749E+10 0.00 0.327181E+10 1606479.51 0.00 0.00 0.00 0.212088E+10 0.00
December 0.222368E+10 0.127470E+10 0.393240E+10 0.00 0.202773E+10 0.00 0.325939E+10 0.00 0.00 0.00 0.00 0.218459E+10 0.00
                           
Annual Sum or Average 0.264510E+11 0.100399E+11 0.482958E+11 0.00 0.199170E+11 0.04 0.198752E+11 0.741666E+10 0.00 0.00 0.00 0.258028E+11 0.00
Minimum of Months 0.203039E+10 0.485768E+09 0.366466E+10 0.00 0.139507E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.203416E+10 0.00
Maximum of Months 0.240486E+10 0.127470E+10 0.429420E+10 0.00 0.227914E+10 0.02 0.447789E+10 0.223993E+10 0.00 0.00 0.00 0.230378E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.239377E+11 0.00 0.00 0.00 0.00
February 0.00 0.00 0.135392E+11 0.00 0.00 0.00 0.00
March 0.00 0.00 0.780271E+10 0.00 0.00 0.00 0.00
April 0.00 0.00 0.105841E+10 0.00 0.00 0.00 0.00
May 0.00 0.00 88239189.10 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 80260658.96 0.00 0.00 0.00 0.00
November 0.00 0.00 0.183579E+10 0.00 0.00 0.00 0.00
December 0.00 0.00 0.176268E+11 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.659692E+11 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.239377E+11 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 2540.94 02-JAN-08:09 1061.67 01-JAN-06:10 3325.31 02-JAN-08:09 0.00 1543.31 01-JAN-00:30 0.00 05-JAN-08:09 7257.93 19-JAN-07:30
February 2498.45 02-FEB-16:00 1061.67 01-FEB-06:10 3325.31 01-FEB-08:09 0.00 1543.31 01-FEB-06:10 0.00 14-FEB-08:09 7011.84 09-FEB-07:10
March 2483.61 03-MAR-16:00 1061.67 01-MAR-06:10 3325.31 01-MAR-08:09 0.00 1543.31 01-MAR-06:10 0.00 01-MAR-00:10 7723.94 21-MAR-06:10
April 2413.52 03-APR-07:10 1061.67 01-APR-05:10 3325.31 03-APR-07:10 0.00 1543.31 03-APR-05:10 0.00 01-APR-00:10 7108.74 10-APR-06:00
May 2285.98 19-MAY-08:30 675.04 01-MAY-19:30 3325.31 01-MAY-07:10 0.00 1543.31 01-MAY-05:10 0.00 01-MAY-00:10 6170.18 01-MAY-06:19
June 2408.71 30-JUN-07:10 675.04 01-JUN-19:00 3325.31 01-JUN-07:10 0.00 1543.31 01-JUN-05:10 0.00 01-JUN-00:10 486.04 01-JUN-05:10
July 2318.46 03-JUL-07:10 675.04 01-JUL-20:19 3325.31 03-JUL-07:10 0.00 1543.31 03-JUL-05:10 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 2461.57 31-AUG-07:10 1061.67 15-AUG-05:10 3325.31 01-AUG-07:10 0.00 1543.31 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 2464.53 19-SEP-07:10 1061.67 01-SEP-05:10 3325.31 01-SEP-07:10 0.00 1543.31 01-SEP-05:10 0.00 01-SEP-00:10 331.69 21-SEP-06:40
October 2537.20 31-OCT-07:10 1061.67 01-OCT-05:10 3325.31 02-OCT-07:10 0.00 1543.31 02-OCT-05:10 0.00 01-OCT-00:10 6129.62 30-OCT-06:19
November 2540.94 06-NOV-16:49 1061.67 01-NOV-05:10 3325.31 01-NOV-07:10 0.00 1543.31 01-NOV-05:10 0.00 01-NOV-00:10 7192.71 06-NOV-07:10
December 2540.94 01-DEC-16:19 1061.67 01-DEC-06:10 3325.31 01-DEC-08:09 0.00 1543.31 01-DEC-06:10 0.00 01-DEC-00:10 7802.13 05-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2285.98   675.04   3325.31   0.00 1543.31   0.00   0.00  
Maximum of Months 2540.94   1061.67   3325.31   0.00 1543.31   0.00   7802.13  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 0.00 01-JAN-00:10 0.00 0.00 0.00 2848.89 31-JAN-12:09 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 2851.09 28-FEB-12:30 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 2851.00 01-MAR-12:20 0.00
April 460.15 13-APR-15:00 0.00 0.00 0.00 2846.47 04-APR-11:39 0.00
May 3183.98 25-MAY-15:00 0.00 0.00 0.00 2838.04 01-MAY-11:09 0.00
June 5202.69 29-JUN-15:00 0.00 0.00 0.00 2826.44 01-JUN-11:30 0.00
July 4530.55 24-JUL-14:09 0.00 0.00 0.00 2815.03 03-JUL-11:50 0.00
August 4954.59 08-AUG-15:09 0.00 0.00 0.00 2808.50 01-AUG-11:39 0.00
September 3876.61 01-SEP-15:30 0.00 0.00 0.00 2809.69 29-SEP-11:09 0.00
October 1596.05 20-OCT-14:09 0.00 0.00 0.00 2819.17 31-OCT-11:00 0.00
November 188.63 17-NOV-13:20 0.00 0.00 0.00 2830.31 30-NOV-12:30 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 2840.71 29-DEC-12:39 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 0.00   0.00 0.00 0.00 2808.50   0.00
Maximum of Months 5202.69   0.00 0.00 0.00 2851.09   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 17163.02 30-JAN-08:09 2531.27 3325.31 0.00 0.00 1543.31 0.00 7004.60 0.00 0.00
February 16705.02 07-FEB-08:09 2446.38 3325.31 0.00 0.00 1543.31 0.00 6630.90 0.00 0.00
March 16743.05 27-MAR-07:30 2163.93 3325.31 0.00 0.00 1543.31 0.00 6952.32 0.00 0.00
April 16589.96 03-APR-07:10 2413.52 3325.31 0.00 0.00 1543.31 0.00 6550.40 0.00 0.00
May 14689.37 01-MAY-07:19 2206.90 3325.31 0.00 0.00 1543.31 0.00 4860.74 0.00 0.00
June 14929.01 29-JUN-15:00 2086.97 3325.31 0.00 0.00 1543.31 0.00 0.00 5202.69 0.00
July 14183.13 21-JUL-15:50 2058.86 3325.31 0.00 0.00 1543.31 0.00 0.00 4489.09 0.00
August 14666.88 08-AUG-15:30 2081.16 3325.31 0.00 0.00 1543.31 0.00 0.00 4952.46 0.00
September 13640.20 01-SEP-15:39 2138.81 3325.31 0.00 0.00 1543.31 0.00 0.00 3868.78 0.00
October 15523.79 30-OCT-07:10 2522.48 3325.31 0.00 0.00 1543.31 0.00 5437.58 0.00 0.00
November 17316.62 27-NOV-16:30 2540.94 3325.31 1061.67 0.00 1543.31 0.00 6094.16 0.00 0.00
December 17076.87 13-DEC-16:49 2540.94 3325.31 1061.67 0.00 1543.31 0.00 5821.33 0.00 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 13640.20   2058.86 3325.31 0.00 0.00 1543.31 0.00 0.00 0.00 0.00
Maximum of Months 17316.62   2540.94 3325.31 1061.67 0.00 1543.31 0.00 7004.60 5202.69 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 39908.07 04-JAN-07:10 0.00 0.00 0.00
February 0.00 0.00 39908.07 14-FEB-07:10 0.00 0.00 0.00
March 0.00 0.00 39536.55 06-MAR-07:10 0.00 0.00 0.00
April 0.00 0.00 32891.51 05-APR-06:10 0.00 0.00 0.00
May 0.00 0.00 14332.82 01-MAY-05:19 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 10565.56 30-OCT-06:10 0.00 0.00 0.00
November 0.00 0.00 34309.75 29-NOV-07:10 0.00 0.00 0.00
December 0.00 0.00 39908.07 26-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 39908.07   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 11.83 19.61 11.50 19.68 0.00 19.68 0.00 19.68
February 4.50 20.21 4.50 20.21 0.00 20.21 0.00 20.21
March 2.67 20.17 2.67 20.17 0.00 20.17 0.00 20.17
April 0.33 20.31 0.33 20.31 0.00 20.31 0.00 20.31
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.33 24.64 0.33 24.64
July 0.00 0.00 0.00 0.00 1.33 24.75 1.33 24.75
August 0.00 0.00 0.00 0.00 1.50 24.64 1.50 24.64
September 0.00 0.00 0.00 0.00 0.33 24.52 0.33 24.52
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.50 20.26 0.50 20.26 0.00 20.26 0.00 20.26
December 7.00 19.80 7.00 19.80 0.00 19.80 0.00 19.80
                 
Annual Sum or Average 26.83 19.84 26.50 19.87 3.50 20.16 3.50 20.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11.83 20.31 11.50 20.31 1.50 24.75 1.50 24.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 72.00 17.03 37.83 17.76 0.00 17.76 0.00 17.76
February 36.83 17.48 22.50 18.14 0.00 18.14 0.00 18.14
March 21.50 17.90 14.33 18.54 0.00 18.54 0.00 18.54
April 2.50 20.00 2.50 20.00 0.00 20.00 0.00 20.00
May 0.33 20.11 0.33 20.11 0.00 20.11 0.00 20.11
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 20.50 0.17 20.50 0.00 20.50 0.00 20.50
November 5.67 17.63 3.00 18.45 0.00 18.45 0.00 18.45
December 51.00 17.04 26.33 17.80 0.00 17.80 0.00 17.80
                 
Annual Sum or Average 190.00 17.29 107.00 18.01 0.00 18.01 0.00 18.01
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 72.00 20.50 37.83 20.50 0.00 20.50 0.00 20.50



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 74.33 15.47 13.50 16.05 0.00 16.05 0.00 16.05
February 41.33 15.68 8.17 16.35 0.00 16.35 0.00 16.35
March 24.33 16.03 6.50 16.79 0.00 16.79 0.00 16.79
April 5.67 16.89 2.17 17.75 0.00 17.75 0.00 17.75
May 0.33 20.13 0.33 20.13 0.00 20.13 0.00 20.13
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.33 20.39 0.33 20.39 0.00 20.39 0.00 20.39
November 10.33 16.06 2.33 16.80 0.00 16.80 0.00 16.80
December 52.50 15.41 9.33 16.02 0.00 16.02 0.00 16.02
                 
Annual Sum or Average 209.17 15.64 42.67 16.30 0.00 16.30 0.00 16.30
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 74.33 20.39 13.50 20.39 0.00 20.39 0.00 20.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 90.50 16.33 33.33 17.12 0.00 17.12 0.00 17.12
February 60.00 16.53 23.33 17.34 0.00 17.34 0.00 17.34
March 43.33 17.13 21.67 17.93 0.00 17.93 0.00 17.93
April 9.50 18.99 8.00 19.33 0.00 19.33 0.00 19.33
May 1.00 19.74 1.00 19.74 0.00 19.74 0.00 19.74
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.50 20.03 0.50 20.03 0.00 20.03 0.00 20.03
November 14.50 17.36 7.33 18.16 0.00 18.16 0.00 18.16
December 64.33 16.21 22.33 17.02 0.00 17.02 0.00 17.02
                 
Annual Sum or Average 283.67 16.63 117.50 17.45 0.00 17.45 0.00 17.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 90.50 20.03 33.33 20.03 0.00 20.03 0.00 20.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 71.00 15.41 11.67 15.98 0.00 15.98 0.00 15.98
February 40.17 15.64 7.67 16.30 0.00 16.30 0.00 16.30
March 23.83 16.11 6.50 16.91 0.00 16.91 0.00 16.91
April 3.00 17.85 1.67 18.67 0.00 18.67 0.00 18.67
May 0.33 17.52 0.17 18.37 0.00 18.37 0.00 18.37
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 20.39 0.17 20.39 0.00 20.39 0.00 20.39
November 9.17 15.94 1.83 16.64 0.00 16.64 0.00 16.64
December 49.33 15.38 8.33 15.99 0.00 15.99 0.00 15.99
                 
Annual Sum or Average 197.00 15.60 38.00 16.26 0.00 16.26 0.00 16.26
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 71.00 20.39 11.67 20.39 0.00 20.39 0.00 20.39



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.71 352.33 20.70 352.33 20.70
February 323.00 20.83 316.33 20.82 316.33 20.82
March 391.00 20.94 298.67 20.91 298.67 20.89
April 340.00 21.75 97.50 21.57 97.50 21.46
May 261.00 23.18 72.50 23.29 19.33 23.19
June 118.50 24.35 184.17 24.46 49.50 24.54
July 31.67 25.68 316.67 24.59 31.67 24.68
August 44.00 25.64 347.50 24.58 44.00 24.69
September 83.00 23.88 101.67 24.33 6.50 24.34
October 349.50 22.75 2.17 22.74 2.17 22.73
November 357.00 21.28 164.83 21.17 164.83 21.12
December 340.00 20.79 328.83 20.78 328.83 20.78
             
Annual Sum or Average 2995.67 21.76 2583.17 21.99 1711.67 21.79
Minimum of Months 31.67 20.71 2.17 20.70 2.17 20.70
Maximum of Months 391.00 25.68 352.33 24.59 352.33 24.69



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 19.93 357.00 19.93 357.00 19.93
February 323.00 20.25 308.83 20.21 308.83 20.19
March 391.00 20.46 362.67 20.41 362.67 20.39
April 340.00 21.26 233.00 21.02 233.00 20.92
May 305.33 22.39 83.83 22.28 61.67 22.09
June 247.00 23.54 122.17 23.82 56.17 23.89
July 55.50 24.51 247.00 24.54 34.67 24.60
August 65.00 24.54 297.67 24.52 28.33 24.61
September 163.33 23.16 109.50 23.74 5.50 23.75
October 316.00 21.94 120.67 21.68 113.67 21.50
November 357.00 20.86 266.83 20.71 266.83 20.65
December 340.00 20.08 340.00 20.08 340.00 20.08
             
Annual Sum or Average 3260.17 21.31 2849.17 21.40 2168.33 21.18
Minimum of Months 55.50 19.93 83.83 19.93 5.50 19.93
Maximum of Months 391.00 24.54 362.67 24.54 362.67 24.61



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 294.00 19.72 294.00 19.72 294.00 19.72
February 266.00 19.88 266.00 19.88 266.00 19.88
March 322.00 20.06 322.00 20.06 322.00 20.06
April 280.00 20.83 224.17 20.65 224.17 20.58
May 255.67 22.41 58.67 22.22 49.83 22.01
June 134.83 23.69 98.00 24.05 27.50 24.11
July 17.83 24.90 224.83 24.64 12.67 24.67
August 37.67 24.23 215.00 24.56 8.83 24.60
September 158.67 23.34 30.50 23.56 1.00 23.56
October 294.00 21.77 109.17 21.46 109.17 21.28
November 294.00 20.43 265.67 20.38 265.67 20.36
December 280.00 19.88 280.00 19.88 280.00 19.88
             
Annual Sum or Average 2634.67 21.00 2388.00 21.09 1860.83 20.85
Minimum of Months 17.83 19.72 30.50 19.72 1.00 19.72
Maximum of Months 322.00 24.90 322.00 24.64 322.00 24.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 19.86 357.00 19.86 357.00 19.86
February 323.00 20.00 323.00 20.00 323.00 20.00
March 391.00 20.16 391.00 20.16 391.00 20.16
April 340.00 20.59 322.83 20.56 322.83 20.55
May 346.67 22.22 88.67 21.97 85.00 21.78
June 268.00 23.58 107.50 23.79 47.67 23.84
July 44.67 24.44 185.00 24.55 21.33 24.60
August 69.83 24.10 193.33 24.40 17.50 24.44
September 278.83 23.34 21.33 23.41 5.00 23.41
October 357.00 21.45 146.50 21.24 146.50 21.12
November 357.00 20.52 325.67 20.48 325.67 20.46
December 340.00 20.03 340.00 20.03 340.00 20.03
             
Annual Sum or Average 3473.00 21.17 2801.83 21.10 2382.50 20.90
Minimum of Months 44.67 19.86 21.33 19.86 5.00 19.86
Maximum of Months 391.00 24.44 391.00 24.55 391.00 24.60



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 20.00 357.00 20.00 357.00 20.00
February 323.00 20.15 322.00 20.15 322.00 20.15
March 391.00 20.36 383.17 20.35 383.17 20.34
April 340.00 21.14 259.83 20.95 259.83 20.88
May 296.67 22.63 89.67 22.70 53.17 22.53
June 203.17 23.90 133.83 24.36 33.83 24.48
July 50.83 26.38 231.83 25.29 36.00 25.53
August 60.17 25.07 238.33 24.92 22.67 25.08
September 196.17 23.53 65.50 23.92 2.00 23.94
October 353.17 22.00 126.17 21.67 126.17 21.47
November 357.00 20.61 314.67 20.55 314.67 20.52
December 340.00 20.12 340.00 20.12 340.00 20.12
             
Annual Sum or Average 3268.17 21.36 2862.00 21.42 2250.50 21.20
Minimum of Months 50.83 20.00 65.50 20.00 2.00 20.00
Maximum of Months 391.00 26.38 383.17 25.29 383.17 25.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 6803999.73 1550039.45 6.00 6803999.73 0.00 0.00 0.11 13-APR-15:57 0.00 01-APR-00:10 475.30 13-APR-15:57 475.30 13-APR-15:57 0.00 13-APR-14:55 107.84 13-APR-15:57 0.00
May 0.850799E+09 0.190178E+09 156.91 0.696109E+09 0.154690E+09 0.00 1.00 19-MAY-05:03 0.00 01-MAY-00:10 5775.39 26-MAY-05:03 4763.39 19-MAY-05:03 1688.10 26-MAY-05:05 1115.99 26-MAY-05:03 0.00
June 0.219785E+10 0.479832E+09 251.50 0.167550E+10 0.522343E+09 0.00 1.00 09-JUN-05:03 0.00 01-JUN-00:10 5969.62 20-JUN-05:03 5259.48 19-JUN-05:03 2646.74 20-JUN-05:05 1287.18 29-JUN-16:00 0.00
July 0.297533E+10 0.632509E+09 239.87 0.226251E+10 0.712822E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 5993.70 05-JUL-05:03 4802.49 27-JUL-05:02 2491.20 05-JUL-05:10 1133.44 05-JUL-05:03 0.00
August 0.315828E+10 0.667404E+09 275.82 0.235496E+10 0.803320E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5952.89 09-AUG-05:02 4916.43 01-AUG-05:02 2279.33 09-AUG-05:10 1168.81 08-AUG-14:55 0.00
September 0.140086E+10 0.302860E+09 226.45 0.115827E+10 0.242593E+09 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 5925.99 01-SEP-05:02 5435.54 11-SEP-05:02 2260.82 01-SEP-05:08 1129.31 01-SEP-05:02 0.00
October 0.172509E+09 38770023.59 78.72 0.149270E+09 23238600.86 0.00 0.32 20-OCT-14:45 0.00 01-OCT-00:10 1505.07 19-OCT-15:57 1429.36 20-OCT-15:00 287.74 02-OCT-13:20 333.93 19-OCT-15:57 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.107624E+11 0.231310E+10 1235.26 0.830341E+10 0.245901E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.315828E+10 0.667404E+09 275.82 0.235496E+10 0.803320E+09 0.00 1.00   0.00   5993.70   5435.54   2646.74   1287.18   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 36325030.13 8176906.43 19.87 36325030.13 -0.0 0.00 0.24 13-APR-14:55 0.00 01-APR-00:10 1236.34 13-APR-14:55 1236.34 13-APR-14:55 0.00 18-APR-12:37 274.10 13-APR-14:55 0.00
May 0.541826E+09 0.124717E+09 99.33 0.479752E+09 62074479.06 0.00 0.60 25-MAY-14:20 0.00 01-MAY-00:10 3490.38 25-MAY-14:10 3097.14 18-MAY-14:00 741.63 26-MAY-12:05 812.51 25-MAY-14:30 0.00
June 0.137991E+10 0.312579E+09 190.18 0.109823E+10 0.281678E+09 0.00 1.00 29-JUN-05:02 0.00 01-JUN-00:10 6897.42 30-JUN-05:02 4502.84 29-JUN-05:02 3502.86 30-JUN-05:05 1398.40 30-JUN-12:00 0.00
July 0.224443E+10 0.493793E+09 225.24 0.180103E+10 0.443406E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 6701.79 05-JUL-05:03 5368.34 03-JUL-05:02 2677.25 05-JUL-05:03 1279.03 05-JUL-05:03 0.00
August 0.257335E+10 0.555451E+09 256.71 0.205820E+10 0.515152E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 6655.70 09-AUG-05:02 6125.62 14-AUG-05:02 2270.71 09-AUG-05:12 1370.62 08-AUG-14:30 0.00
September 0.117585E+10 0.251616E+09 163.64 0.109253E+10 83313318.99 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 6668.26 01-SEP-05:02 6090.15 11-SEP-05:02 2365.92 01-SEP-05:02 1276.45 01-SEP-05:02 0.00
October 0.283248E+09 61491690.93 55.52 0.279126E+09 4122216.98 0.00 0.66 20-OCT-14:00 0.00 01-OCT-00:10 3677.72 20-OCT-14:00 3677.72 20-OCT-14:00 131.14 02-OCT-12:15 765.57 20-OCT-14:00 0.00
November 7127457.98 1606479.51 3.47 7127457.98 0.00 0.00 0.17 17-NOV-13:20 0.00 01-NOV-00:10 841.96 17-NOV-13:20 841.96 17-NOV-13:20 0.00 17-NOV-16:07 188.63 17-NOV-13:20 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.824207E+10 0.180943E+10 1013.97 0.685232E+10 0.138975E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.257335E+10 0.555451E+09 256.71 0.205820E+10 0.515152E+09 0.00 1.00   0.00   6897.42   6125.62   3502.86   1398.40   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00
May 0.269963E+09 62392328.93 96.38 0.243136E+09 26826419.25 0.00 0.88 18-MAY-10:02 0.00 01-MAY-00:10 3357.35 18-MAY-10:02 3228.78 18-MAY-10:02 457.51 25-MAY-10:02 718.84 18-MAY-10:02 0.00
June 0.951363E+09 0.215332E+09 227.84 0.805918E+09 0.145445E+09 0.00 1.00 26-JUN-10:02 0.00 01-JUN-00:10 4415.49 30-JUN-05:02 3399.60 28-JUN-10:03 2261.74 30-JUN-05:03 902.55 29-JUN-12:02 0.00
July 0.148538E+10 0.326497E+09 236.68 0.126202E+10 0.223358E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 4284.97 05-JUL-05:03 3653.66 19-JUL-10:02 1732.90 05-JUL-05:03 843.20 25-JUL-10:03 0.00
August 0.136776E+10 0.300139E+09 269.11 0.113866E+10 0.229099E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 4242.07 09-AUG-05:02 3857.10 07-AUG-05:02 1371.50 09-AUG-05:03 854.06 09-AUG-14:02 0.00
September 0.508529E+09 0.111897E+09 164.70 0.471128E+09 37401751.78 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 4247.46 01-SEP-05:02 3872.37 07-SEP-10:02 1508.06 01-SEP-05:02 815.68 01-SEP-05:02 0.00
October 31105902.59 7004918.29 23.49 30393428.59 712474.01 0.00 0.71 20-OCT-10:02 0.00 01-OCT-00:10 2618.28 20-OCT-10:02 2531.95 20-OCT-10:02 86.33 20-OCT-10:02 540.38 20-OCT-10:02 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.461410E+10 0.102326E+10 1018.20 0.395126E+10 0.662842E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.148538E+10 0.326497E+09 269.11 0.126202E+10 0.229099E+09 0.00 1.00   0.00   4415.49   3872.37   2261.74   902.55   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00 01-APR-00:10 0.00
May 0.268415E+09 62262598.28 67.67 0.224096E+09 44319551.27 0.00 0.53 25-MAY-15:55 0.00 01-MAY-00:10 2300.19 25-MAY-15:55 1881.74 25-MAY-16:00 555.05 26-MAY-12:10 546.89 25-MAY-15:55 0.00
June 0.105380E+10 0.237806E+09 185.64 0.817789E+09 0.236014E+09 0.00 1.00 29-JUN-05:02 0.00 01-JUN-00:10 5209.28 30-JUN-05:02 3379.17 29-JUN-05:02 2669.31 30-JUN-05:05 1019.71 30-JUN-05:12 0.00
July 0.175559E+10 0.385670E+09 234.43 0.138012E+10 0.375477E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 5063.56 05-JUL-05:03 4151.52 07-JUL-05:02 2073.87 05-JUL-05:03 967.48 05-JUL-05:03 0.00
August 0.174944E+10 0.381478E+09 265.13 0.134571E+10 0.403726E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 5010.44 09-AUG-05:02 4390.18 14-AUG-05:02 1705.67 09-AUG-05:03 963.03 09-AUG-05:02 0.00
September 0.469000E+09 0.103773E+09 131.05 0.405857E+09 63143030.13 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 5020.62 01-SEP-05:02 3202.95 01-SEP-05:02 1817.67 01-SEP-05:02 963.95 01-SEP-05:02 0.00
October 5181769.82 1183438.64 4.75 5103038.31 78731.51 0.00 0.12 20-OCT-15:37 0.00 01-OCT-00:10 459.56 20-OCT-15:37 459.56 20-OCT-15:37 23.56 19-OCT-15:00 104.22 20-OCT-15:37 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.530143E+10 0.117217E+10 888.67 0.417867E+10 0.112276E+10 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.175559E+10 0.385670E+09 265.13 0.138012E+10 0.403726E+09 0.00 1.00   0.00   5209.28   4390.18   2669.31   1019.71   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00 01-MAR-00:10 0.00
April 3033490.71 690026.17 3.64 3033490.71 -0.0 0.00 0.13 13-APR-15:53 0.00 01-APR-00:10 511.50 13-APR-16:00 511.50 13-APR-16:00 0.00 21-APR-16:55 115.42 13-APR-16:00 0.00
May 0.357924E+09 82964309.56 103.99 0.317113E+09 40810722.48 0.00 0.61 25-MAY-15:55 0.00 01-MAY-00:10 2648.69 25-MAY-15:55 2268.07 25-MAY-16:00 474.98 26-MAY-05:03 627.31 25-MAY-15:55 0.00
June 0.932694E+09 0.214071E+09 214.09 0.759178E+09 0.173516E+09 0.00 1.00 29-JUN-05:02 0.00 01-JUN-00:10 5211.60 30-JUN-05:02 3478.49 29-JUN-05:02 2563.84 30-JUN-05:05 1016.20 30-JUN-05:12 0.00
July 0.147514E+10 0.329575E+09 238.22 0.121365E+10 0.261490E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:10 5060.33 05-JUL-05:03 4331.54 06-JUL-05:02 1929.70 05-JUL-05:03 965.33 05-JUL-05:03 0.00
August 0.151639E+10 0.335457E+09 273.24 0.123358E+10 0.282810E+09 0.00 1.00 01-AUG-05:02 0.00 01-AUG-00:10 4996.23 09-AUG-05:02 4586.23 14-AUG-05:02 1545.40 09-AUG-05:03 960.10 09-AUG-05:02 0.00
September 0.550982E+09 0.122254E+09 177.22 0.501139E+09 49842648.59 0.00 1.00 01-SEP-05:02 0.00 01-SEP-00:10 4999.95 01-SEP-05:02 3266.13 01-SEP-05:02 1733.82 01-SEP-05:02 960.43 01-SEP-05:02 0.00
October 60781895.20 13683629.88 35.64 59132419.10 1649476.10 0.00 0.34 19-OCT-15:53 0.00 01-OCT-00:10 1388.74 19-OCT-15:53 1318.06 19-OCT-15:57 70.71 19-OCT-15:53 307.29 19-OCT-15:53 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00 01-NOV-00:10 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00 01-DEC-00:05 0.00
                                       
Annual Sum or Average 0.489695E+10 0.109869E+10 1046.03 0.408683E+10 0.810119E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.151639E+10 0.335457E+09 273.24 0.123358E+10 0.282810E+09 0.00 1.00   0.00   5211.60   4586.23   2563.84   1016.20   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.27 67.65 28.62 86.25 93.63 0.00 0.00 0.00
February 121.78 83.16 38.61 123.35 77.67 0.00 0.00 0.00
March 106.92 68.61 38.31 111.77 62.94 0.00 0.00 0.00
April 89.32 47.47 41.85 100.35 39.95 0.00 0.00 0.00
May 66.51 18.35 48.16 78.35 22.37 0.00 0.00 0.00
June 56.82 9.67 47.16 70.11 15.86 0.00 0.00 0.00
July 62.75 14.46 48.29 79.71 16.76 0.00 0.00 0.00
August 74.31 28.71 45.60 93.14 20.89 0.00 0.00 0.00
September 90.23 48.94 41.30 107.00 32.78 0.00 0.00 0.00
October 77.63 46.56 31.07 82.56 44.87 0.00 0.00 0.00
November 69.49 44.27 25.22 66.56 60.33 0.00 0.00 0.00
December 74.19 49.23 24.96 61.61 91.10 0.00 0.00 0.00
                 
Annual Sum or Average 81.92 43.67 38.25 88.13 48.14 0.00 0.00 0.00
Minimum of Months 56.82 9.67 24.96 61.61 15.86 0.00 0.00 0.00
Maximum of Months 121.78 83.16 48.29 123.35 93.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.26 67.65 28.62 86.25 93.63 0.00 0.00 0.00
February 121.77 83.16 38.61 123.35 77.66 0.00 0.00 0.00
March 106.92 68.61 38.31 111.77 62.94 0.00 0.00 0.00
April 89.20 47.41 41.78 100.16 40.00 0.00 0.00 0.00
May 66.41 18.31 48.10 78.16 22.37 0.00 0.00 0.00
June 56.79 9.65 47.13 70.04 15.86 0.00 0.00 0.00
July 62.68 14.43 48.25 79.59 16.76 0.00 0.00 0.00
August 74.18 28.66 45.53 92.89 20.89 0.00 0.00 0.00
September 90.18 48.91 41.27 106.93 32.81 0.00 0.00 0.00
October 77.63 46.56 31.06 82.56 44.87 0.00 0.00 0.00
November 69.49 44.27 25.22 66.56 60.33 0.00 0.00 0.00
December 74.19 49.23 24.95 61.61 91.09 0.00 0.00 0.00
                 
Annual Sum or Average 81.88 43.65 38.23 88.06 48.15 0.00 0.00 0.00
Minimum of Months 56.79 9.65 24.95 61.61 15.86 0.00 0.00 0.00
Maximum of Months 121.77 83.16 48.25 123.35 93.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.26 67.65 28.62 86.25 93.63 0.00 0.00 0.00
February 121.77 83.16 38.61 123.35 77.66 0.00 0.00 0.00
March 106.92 68.61 38.31 111.77 62.94 0.00 0.00 0.00
April 89.19 47.41 41.78 100.16 40.00 0.00 0.00 0.00
May 66.41 18.31 48.10 78.16 22.37 0.00 0.00 0.00
June 56.79 9.65 47.13 70.04 15.86 0.00 0.00 0.00
July 62.68 14.43 48.25 79.59 16.76 0.00 0.00 0.00
August 74.18 28.66 45.53 92.89 20.89 0.00 0.00 0.00
September 90.18 48.91 41.26 106.92 32.82 0.00 0.00 0.00
October 77.63 46.56 31.06 82.56 44.87 0.00 0.00 0.00
November 69.49 44.27 25.22 66.56 60.33 0.00 0.00 0.00
December 74.19 49.23 24.95 61.61 91.09 0.00 0.00 0.00
                 
Annual Sum or Average 81.88 43.65 38.23 88.06 48.15 0.00 0.00 0.00
Minimum of Months 56.79 9.65 24.95 61.61 15.86 0.00 0.00 0.00
Maximum of Months 121.77 83.16 48.25 123.35 93.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.26 67.65 28.62 86.25 93.63 0.00 0.00 0.00
February 121.77 83.16 38.61 123.35 77.66 0.00 0.00 0.00
March 106.92 68.61 38.31 111.77 62.94 0.00 0.00 0.00
April 89.19 47.41 41.78 100.16 40.00 0.00 0.00 0.00
May 66.41 18.31 48.10 78.16 22.37 0.00 0.00 0.00
June 56.79 9.65 47.13 70.04 15.86 0.00 0.00 0.00
July 62.68 14.43 48.25 79.59 16.76 0.00 0.00 0.00
August 74.18 28.66 45.53 92.89 20.89 0.00 0.00 0.00
September 90.18 48.91 41.26 106.92 32.82 0.00 0.00 0.00
October 77.63 46.56 31.06 82.56 44.87 0.00 0.00 0.00
November 69.49 44.27 25.22 66.56 60.33 0.00 0.00 0.00
December 74.19 49.23 24.95 61.61 91.09 0.00 0.00 0.00
                 
Annual Sum or Average 81.88 43.65 38.23 88.06 48.15 0.00 0.00 0.00
Minimum of Months 56.79 9.65 24.95 61.61 15.86 0.00 0.00 0.00
Maximum of Months 121.77 83.16 48.25 123.35 93.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.26 67.65 28.62 86.25 93.63 0.00 0.00 0.00
February 121.77 83.16 38.61 123.35 77.66 0.00 0.00 0.00
March 106.92 68.61 38.31 111.77 62.94 0.00 0.00 0.00
April 89.20 47.41 41.78 100.16 40.00 0.00 0.00 0.00
May 66.41 18.31 48.10 78.16 22.37 0.00 0.00 0.00
June 56.79 9.65 47.13 70.04 15.86 0.00 0.00 0.00
July 62.68 14.43 48.25 79.59 16.76 0.00 0.00 0.00
August 74.18 28.66 45.53 92.89 20.89 0.00 0.00 0.00
September 90.18 48.91 41.27 106.92 32.81 0.00 0.00 0.00
October 77.63 46.56 31.06 82.56 44.87 0.00 0.00 0.00
November 69.49 44.27 25.22 66.56 60.33 0.00 0.00 0.00
December 74.19 49.23 24.95 61.61 91.09 0.00 0.00 0.00
                 
Annual Sum or Average 81.88 43.65 38.23 88.06 48.15 0.00 0.00 0.00
Minimum of Months 56.79 9.65 24.95 61.61 15.86 0.00 0.00 0.00
Maximum of Months 121.77 83.16 48.25 123.35 93.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 96.27 67.65 28.62 86.25 93.63 0.00 0.00 0.00
February 121.78 83.16 38.61 123.35 77.67 0.00 0.00 0.00
March 106.92 68.61 38.31 111.77 62.94 0.00 0.00 0.00
April 89.33 47.48 41.85 100.28 39.86 0.00 0.00 0.00
May 66.51 18.35 48.16 78.34 22.37 0.00 0.00 0.00
June 56.82 9.67 47.16 70.11 15.86 0.00 0.00 0.00
July 62.75 14.46 48.29 79.72 16.76 0.00 0.00 0.00
August 74.31 28.71 45.60 93.13 20.89 0.00 0.00 0.00
September 90.22 48.93 41.29 106.96 32.76 0.00 0.00 0.00
October 77.63 46.56 31.07 82.56 44.87 0.00 0.00 0.00
November 69.49 44.27 25.22 66.56 60.33 0.00 0.00 0.00
December 74.19 49.23 24.96 61.61 91.10 0.00 0.00 0.00
                 
Annual Sum or Average 81.92 43.67 38.25 88.12 48.13 0.00 0.00 0.00
Minimum of Months 56.82 9.67 24.96 61.61 15.86 0.00 0.00 0.00
Maximum of Months 121.78 83.16 48.29 123.35 93.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 135.52 94.78 40.74 121.71 130.33 0.00 0.00 0.00
February 171.51 116.51 55.00 173.97 108.19 0.00 0.00 0.00
March 150.82 96.13 54.69 157.63 87.52 0.00 0.00 0.00
April 135.64 74.22 61.42 155.60 55.60 0.00 0.00 0.00
May 107.15 34.85 72.29 130.68 31.34 0.00 0.00 0.00
June 92.09 21.08 71.01 117.35 22.25 0.00 0.00 0.00
July 102.16 29.39 72.77 133.40 23.56 0.00 0.00 0.00
August 117.28 49.12 68.17 149.70 29.25 0.00 0.00 0.00
September 128.42 69.09 59.32 152.49 45.75 0.00 0.00 0.00
October 109.81 65.24 44.57 116.86 62.61 0.00 0.00 0.00
November 98.07 62.03 36.04 94.05 84.05 0.00 0.00 0.00
December 104.53 68.97 35.56 86.99 126.67 0.00 0.00 0.00
                 
Annual Sum or Average 120.75 64.79 55.96 132.23 67.09 0.00 0.00 0.00
Minimum of Months 92.09 21.08 35.56 86.99 22.25 0.00 0.00 0.00
Maximum of Months 171.51 116.51 72.77 173.97 130.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.64 12.74 16.91 12.57 105.96 0.00 0.00 0.00
February 46.47 20.25 26.22 29.92 81.65 0.00 0.00 0.00
March 63.29 32.24 31.05 51.90 62.05 0.00 0.00 0.00
April 87.19 47.38 39.81 90.75 35.67 0.00 0.00 0.00
May 93.21 41.24 51.97 108.85 20.23 0.00 0.00 0.00
June 105.74 50.84 54.91 131.78 15.22 0.00 0.00 0.00
July 103.87 49.01 54.86 130.83 15.87 0.00 0.00 0.00
August 80.06 35.31 44.75 96.24 19.47 0.00 0.00 0.00
September 64.48 29.33 35.15 68.54 30.20 0.00 0.00 0.00
October 39.04 15.22 23.81 31.52 43.06 0.00 0.00 0.00
November 24.90 8.62 16.29 13.00 62.50 0.00 0.00 0.00
December 22.85 8.75 14.10 7.93 102.98 0.00 0.00 0.00
                 
Annual Sum or Average 63.46 29.26 34.19 64.64 49.46 0.00 0.00 0.00
Minimum of Months 22.85 8.62 14.10 7.93 15.22 0.00 0.00 0.00
Maximum of Months 105.74 50.84 54.91 131.78 105.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.64 12.74 16.90 12.57 105.96 0.00 0.00 0.00
February 46.47 20.25 26.22 29.92 81.65 0.00 0.00 0.00
March 63.29 32.24 31.05 51.90 62.05 0.00 0.00 0.00
April 87.19 47.38 39.81 90.74 35.67 0.00 0.00 0.00
May 93.21 41.24 51.97 108.85 20.23 0.00 0.00 0.00
June 105.74 50.84 54.90 131.78 15.22 0.00 0.00 0.00
July 103.87 49.01 54.86 130.82 15.87 0.00 0.00 0.00
August 80.06 35.31 44.75 96.24 19.47 0.00 0.00 0.00
September 64.48 29.33 35.15 68.54 30.20 0.00 0.00 0.00
October 39.04 15.22 23.81 31.52 43.06 0.00 0.00 0.00
November 24.90 8.62 16.29 13.00 62.50 0.00 0.00 0.00
December 22.85 8.75 14.09 7.93 102.98 0.00 0.00 0.00
                 
Annual Sum or Average 63.45 29.26 34.19 64.64 49.46 0.00 0.00 0.00
Minimum of Months 22.85 8.62 14.09 7.93 15.22 0.00 0.00 0.00
Maximum of Months 105.74 50.84 54.90 131.78 105.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.64 12.74 16.90 12.57 105.96 0.00 0.00 0.00
February 46.47 20.25 26.22 29.92 81.65 0.00 0.00 0.00
March 63.29 32.24 31.05 51.90 62.05 0.00 0.00 0.00
April 87.19 47.38 39.81 90.74 35.67 0.00 0.00 0.00
May 93.21 41.24 51.97 108.85 20.23 0.00 0.00 0.00
June 105.74 50.84 54.90 131.78 15.22 0.00 0.00 0.00
July 103.87 49.01 54.86 130.82 15.87 0.00 0.00 0.00
August 80.06 35.31 44.75 96.24 19.47 0.00 0.00 0.00
September 64.48 29.33 35.15 68.54 30.20 0.00 0.00 0.00
October 39.04 15.22 23.81 31.52 43.06 0.00 0.00 0.00
November 24.90 8.62 16.29 13.00 62.50 0.00 0.00 0.00
December 22.85 8.75 14.09 7.93 102.98 0.00 0.00 0.00
                 
Annual Sum or Average 63.45 29.26 34.19 64.64 49.46 0.00 0.00 0.00
Minimum of Months 22.85 8.62 14.09 7.93 15.22 0.00 0.00 0.00
Maximum of Months 105.74 50.84 54.90 131.78 105.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.77 12.79 16.98 12.60 105.76 0.00 0.00 0.00
February 46.58 20.30 26.28 30.05 81.56 0.00 0.00 0.00
March 63.31 32.25 31.06 51.94 62.04 0.00 0.00 0.00
April 87.19 47.38 39.81 90.75 35.67 0.00 0.00 0.00
May 93.21 41.24 51.97 108.85 20.23 0.00 0.00 0.00
June 105.74 50.84 54.91 131.78 15.22 0.00 0.00 0.00
July 103.87 49.01 54.86 130.83 15.87 0.00 0.00 0.00
August 80.06 35.31 44.75 96.24 19.47 0.00 0.00 0.00
September 64.49 29.33 35.16 68.55 30.20 0.00 0.00 0.00
October 39.07 15.24 23.83 31.58 43.06 0.00 0.00 0.00
November 24.99 8.65 16.34 13.09 62.44 0.00 0.00 0.00
December 22.95 8.79 14.16 7.95 102.81 0.00 0.00 0.00
                 
Annual Sum or Average 63.50 29.28 34.22 64.67 49.41 0.00 0.00 0.00
Minimum of Months 22.95 8.65 14.16 7.95 15.22 0.00 0.00 0.00
Maximum of Months 105.74 50.84 54.91 131.78 105.76 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.16 0.00 13.16 0.19 117.56 0.00 0.00 0.00
February 20.36 0.00 20.36 2.31 90.81 0.00 0.00 0.00
March 25.18 0.00 25.18 5.87 67.80 0.00 0.00 0.00
April 33.16 0.26 32.90 21.07 37.17 0.00 0.00 0.00
May 46.32 2.50 43.82 47.83 19.43 0.00 0.00 0.00
June 51.83 5.72 46.12 61.64 14.29 0.00 0.00 0.00
July 49.63 4.25 45.39 59.57 15.04 0.00 0.00 0.00
August 37.62 0.64 36.98 40.44 18.65 0.00 0.00 0.00
September 29.15 0.01 29.15 23.07 30.50 0.00 0.00 0.00
October 20.02 0.00 20.02 8.38 44.46 0.00 0.00 0.00
November 13.24 0.00 13.24 1.30 67.41 0.00 0.00 0.00
December 11.09 0.00 11.09 0.02 112.61 0.00 0.00 0.00
                 
Annual Sum or Average 29.28 1.12 28.16 22.76 52.84 0.00 0.00 0.00
Minimum of Months 11.09 0.00 11.09 0.02 14.29 0.00 0.00 0.00
Maximum of Months 51.83 5.72 46.12 61.64 117.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.16 0.00 13.16 0.19 117.56 0.00 0.00 0.00
February 20.36 0.00 20.36 2.31 90.81 0.00 0.00 0.00
March 25.18 0.00 25.18 5.87 67.80 0.00 0.00 0.00
April 33.14 0.26 32.88 21.06 37.20 0.00 0.00 0.00
May 46.20 2.46 43.74 47.64 19.46 0.00 0.00 0.00
June 51.69 5.65 46.04 61.36 14.29 0.00 0.00 0.00
July 49.48 4.19 45.29 59.29 15.04 0.00 0.00 0.00
August 37.55 0.62 36.93 40.32 18.65 0.00 0.00 0.00
September 29.15 0.01 29.15 23.07 30.49 0.00 0.00 0.00
October 20.02 0.00 20.02 8.38 44.46 0.00 0.00 0.00
November 13.24 0.00 13.24 1.30 67.41 0.00 0.00 0.00
December 11.09 0.00 11.09 0.02 112.61 0.00 0.00 0.00
                 
Annual Sum or Average 29.23 1.10 28.13 22.69 52.84 0.00 0.00 0.00
Minimum of Months 11.09 0.00 11.09 0.02 14.29 0.00 0.00 0.00
Maximum of Months 51.69 5.65 46.04 61.36 117.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.16 0.00 13.16 0.19 117.56 0.00 0.00 0.00
February 20.36 0.00 20.36 2.31 90.81 0.00 0.00 0.00
March 25.18 0.00 25.18 5.87 67.80 0.00 0.00 0.00
April 33.13 0.25 32.88 21.05 37.21 0.00 0.00 0.00
May 46.20 2.46 43.74 47.64 19.46 0.00 0.00 0.00
June 51.69 5.65 46.04 61.36 14.29 0.00 0.00 0.00
July 49.48 4.19 45.29 59.29 15.04 0.00 0.00 0.00
August 37.55 0.62 36.93 40.32 18.65 0.00 0.00 0.00
September 29.15 0.01 29.15 23.07 30.49 0.00 0.00 0.00
October 20.02 0.00 20.02 8.38 44.46 0.00 0.00 0.00
November 13.24 0.00 13.24 1.30 67.41 0.00 0.00 0.00
December 11.09 0.00 11.09 0.02 112.61 0.00 0.00 0.00
                 
Annual Sum or Average 29.23 1.10 28.13 22.69 52.84 0.00 0.00 0.00
Minimum of Months 11.09 0.00 11.09 0.02 14.29 0.00 0.00 0.00
Maximum of Months 51.69 5.65 46.04 61.36 117.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.16 0.00 13.16 0.19 117.56 0.00 0.00 0.00
February 20.36 0.00 20.36 2.31 90.81 0.00 0.00 0.00
March 25.18 0.00 25.18 5.87 67.80 0.00 0.00 0.00
April 33.13 0.25 32.88 21.05 37.21 0.00 0.00 0.00
May 46.20 2.46 43.74 47.64 19.46 0.00 0.00 0.00
June 51.69 5.65 46.04 61.36 14.29 0.00 0.00 0.00
July 49.48 4.19 45.29 59.29 15.04 0.00 0.00 0.00
August 37.55 0.62 36.93 40.32 18.65 0.00 0.00 0.00
September 29.15 0.01 29.15 23.07 30.50 0.00 0.00 0.00
October 20.02 0.00 20.02 8.38 44.46 0.00 0.00 0.00
November 13.24 0.00 13.24 1.30 67.41 0.00 0.00 0.00
December 11.09 0.00 11.09 0.02 112.61 0.00 0.00 0.00
                 
Annual Sum or Average 29.23 1.10 28.13 22.69 52.84 0.00 0.00 0.00
Minimum of Months 11.09 0.00 11.09 0.02 14.29 0.00 0.00 0.00
Maximum of Months 51.69 5.65 46.04 61.36 117.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.16 0.00 13.16 0.19 117.56 0.00 0.00 0.00
February 20.36 0.00 20.36 2.31 90.81 0.00 0.00 0.00
March 25.18 0.00 25.18 5.87 67.80 0.00 0.00 0.00
April 33.14 0.26 32.88 21.06 37.20 0.00 0.00 0.00
May 46.20 2.46 43.74 47.64 19.46 0.00 0.00 0.00
June 51.69 5.65 46.04 61.36 14.29 0.00 0.00 0.00
July 49.48 4.19 45.29 59.29 15.04 0.00 0.00 0.00
August 37.55 0.62 36.93 40.32 18.65 0.00 0.00 0.00
September 29.15 0.01 29.15 23.07 30.50 0.00 0.00 0.00
October 20.02 0.00 20.02 8.38 44.46 0.00 0.00 0.00
November 13.24 0.00 13.24 1.30 67.41 0.00 0.00 0.00
December 11.09 0.00 11.09 0.02 112.61 0.00 0.00 0.00
                 
Annual Sum or Average 29.23 1.10 28.13 22.69 52.84 0.00 0.00 0.00
Minimum of Months 11.09 0.00 11.09 0.02 14.29 0.00 0.00 0.00
Maximum of Months 51.69 5.65 46.04 61.36 117.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 13.16 0.00 13.16 0.19 117.56 0.00 0.00 0.00
February 20.36 0.00 20.36 2.31 90.81 0.00 0.00 0.00
March 25.18 0.00 25.18 5.87 67.80 0.00 0.00 0.00
April 33.16 0.26 32.90 21.08 37.18 0.00 0.00 0.00
May 46.32 2.51 43.81 47.87 19.46 0.00 0.00 0.00
June 51.80 5.70 46.11 61.58 14.29 0.00 0.00 0.00
July 49.61 4.24 45.37 59.53 15.04 0.00 0.00 0.00
August 37.62 0.64 36.98 40.45 18.65 0.00 0.00 0.00
September 29.15 0.01 29.15 23.07 30.50 0.00 0.00 0.00
October 20.02 0.00 20.02 8.38 44.46 0.00 0.00 0.00
November 13.24 0.00 13.24 1.30 67.41 0.00 0.00 0.00
December 11.09 0.00 11.09 0.02 112.61 0.00 0.00 0.00
                 
Annual Sum or Average 29.27 1.12 28.15 22.76 52.84 0.00 0.00 0.00
Minimum of Months 11.09 0.00 11.09 0.02 14.29 0.00 0.00 0.00
Maximum of Months 51.80 5.70 46.11 61.58 117.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.12 12.98 17.13 14.19 108.28 0.00 0.00 0.00
February 48.93 22.85 26.08 35.20 84.96 0.00 0.00 0.00
March 64.08 33.33 30.74 54.97 64.89 0.00 0.00 0.00
April 81.22 41.46 39.76 84.41 38.26 0.00 0.00 0.00
May 99.21 47.78 51.43 118.20 22.34 0.00 0.00 0.00
June 95.43 41.52 53.91 119.12 16.15 0.00 0.00 0.00
July 101.61 47.29 54.32 128.24 17.34 0.00 0.00 0.00
August 83.88 38.34 45.54 102.26 20.72 0.00 0.00 0.00
September 66.15 30.22 35.92 71.71 31.70 0.00 0.00 0.00
October 41.82 17.24 24.58 36.27 44.64 0.00 0.00 0.00
November 25.49 8.90 16.59 14.43 64.10 0.00 0.00 0.00
December 22.86 8.29 14.58 8.18 104.64 0.00 0.00 0.00
                 
Annual Sum or Average 63.48 29.22 34.26 65.77 51.38 0.00 0.00 0.00
Minimum of Months 22.86 8.29 14.58 8.18 16.15 0.00 0.00 0.00
Maximum of Months 101.61 47.78 54.32 128.24 108.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.99 12.93 17.06 14.16 108.48 0.00 0.00 0.00
February 48.81 22.80 26.01 35.06 85.04 0.00 0.00 0.00
March 64.05 33.32 30.73 54.93 64.90 0.00 0.00 0.00
April 81.22 41.46 39.76 84.41 38.26 0.00 0.00 0.00
May 99.21 47.78 51.43 118.20 22.34 0.00 0.00 0.00
June 95.43 41.52 53.91 119.12 16.15 0.00 0.00 0.00
July 101.61 47.29 54.31 128.24 17.34 0.00 0.00 0.00
August 83.87 38.34 45.53 102.26 20.72 0.00 0.00 0.00
September 66.14 30.22 35.92 71.70 31.70 0.00 0.00 0.00
October 41.78 17.23 24.55 36.20 44.64 0.00 0.00 0.00
November 25.40 8.86 16.54 14.32 64.16 0.00 0.00 0.00
December 22.76 8.25 14.51 8.17 104.81 0.00 0.00 0.00
                 
Annual Sum or Average 63.44 29.21 34.23 65.74 51.42 0.00 0.00 0.00
Minimum of Months 22.76 8.25 14.51 8.17 16.15 0.00 0.00 0.00
Maximum of Months 101.61 47.78 54.31 128.24 108.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 29.99 12.93 17.06 14.16 108.48 0.00 0.00 0.00
February 48.81 22.80 26.01 35.06 85.04 0.00 0.00 0.00
March 64.05 33.32 30.73 54.93 64.90 0.00 0.00 0.00
April 81.22 41.46 39.76 84.41 38.26 0.00 0.00 0.00
May 99.21 47.78 51.43 118.20 22.34 0.00 0.00 0.00
June 95.43 41.52 53.91 119.12 16.15 0.00 0.00 0.00
July 101.61 47.29 54.31 128.24 17.34 0.00 0.00 0.00
August 83.87 38.34 45.53 102.26 20.72 0.00 0.00 0.00
September 66.14 30.22 35.92 71.70 31.70 0.00 0.00 0.00
October 41.78 17.23 24.55 36.20 44.64 0.00 0.00 0.00
November 25.40 8.86 16.54 14.32 64.16 0.00 0.00 0.00
December 22.76 8.25 14.51 8.17 104.81 0.00 0.00 0.00
                 
Annual Sum or Average 63.44 29.21 34.23 65.74 51.42 0.00 0.00 0.00
Minimum of Months 22.76 8.25 14.51 8.17 16.15 0.00 0.00 0.00
Maximum of Months 101.61 47.78 54.31 128.24 108.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 30.00 12.93 17.06 14.16 108.47 0.00 0.00 0.00
February 48.81 22.80 26.02 35.07 85.04 0.00 0.00 0.00
March 64.05 33.32 30.73 54.93 64.90 0.00 0.00 0.00
April 81.22 41.46 39.76 84.41 38.26 0.00 0.00 0.00
May 99.21 47.78 51.43 118.20 22.34 0.00 0.00 0.00
June 95.43 41.52 53.91 119.12 16.15 0.00 0.00 0.00
July 101.61 47.29 54.32 128.24 17.34 0.00 0.00 0.00
August 83.88 38.34 45.53 102.26 20.72 0.00 0.00 0.00
September 66.14 30.22 35.92 71.70 31.70 0.00 0.00 0.00
October 41.78 17.23 24.56 36.21 44.64 0.00 0.00 0.00
November 25.40 8.86 16.54 14.32 64.16 0.00 0.00 0.00
December 22.76 8.25 14.51 8.17 104.81 0.00 0.00 0.00
                 
Annual Sum or Average 63.44 29.21 34.23 65.74 51.42 0.00 0.00 0.00
Minimum of Months 22.76 8.25 14.51 8.17 16.15 0.00 0.00 0.00
Maximum of Months 101.61 47.78 54.32 128.24 108.47 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.257838E+09 0.181189E+09 76649510.03 0.231017E+09 0.250773E+09
February 0.294601E+09 0.201189E+09 93412372.79 0.298416E+09 0.187887E+09
March 0.286371E+09 0.183768E+09 0.102603E+09 0.299366E+09 0.168591E+09
April 0.231512E+09 0.123045E+09 0.108467E+09 0.260101E+09 0.103546E+09
May 0.178132E+09 49152916.46 0.128979E+09 0.209846E+09 59922972.43
June 0.147281E+09 25053896.69 0.122227E+09 0.181722E+09 41104427.50
July 0.168065E+09 38726336.62 0.129339E+09 0.213503E+09 44900552.28
August 0.199044E+09 76896605.89 0.122148E+09 0.249460E+09 55951026.36
September 0.233884E+09 0.126843E+09 0.107041E+09 0.277340E+09 84974198.46
October 0.207926E+09 0.124718E+09 83208068.59 0.221123E+09 0.120192E+09
November 0.180127E+09 0.114753E+09 65374194.53 0.172522E+09 0.156365E+09
December 0.198702E+09 0.131860E+09 66841503.00 0.165009E+09 0.243989E+09
           
Annual Sum or Average 0.258348E+10 0.137720E+10 0.120629E+10 0.277943E+10 0.151820E+10
Minimum of Months 0.147281E+09 25053896.69 65374194.53 0.165009E+09 41104427.50
Maximum of Months 0.294601E+09 0.201189E+09 0.129339E+09 0.299366E+09 0.250773E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.257836E+09 0.181189E+09 76646730.05 0.231014E+09 0.250772E+09
February 0.294598E+09 0.201189E+09 93408890.40 0.298412E+09 0.187887E+09
March 0.286366E+09 0.183768E+09 0.102598E+09 0.299362E+09 0.168591E+09
April 0.231194E+09 0.122891E+09 0.108303E+09 0.259609E+09 0.103677E+09
May 0.177865E+09 49032398.01 0.128832E+09 0.209337E+09 59922267.00
June 0.147187E+09 25019683.95 0.122167E+09 0.181550E+09 41103828.53
July 0.167888E+09 38656283.52 0.129232E+09 0.213177E+09 44899704.98
August 0.198692E+09 76753450.18 0.121939E+09 0.248804E+09 55950532.90
September 0.233752E+09 0.126785E+09 0.106967E+09 0.277152E+09 85034062.90
October 0.207922E+09 0.124718E+09 83203605.46 0.221118E+09 0.120191E+09
November 0.180124E+09 0.114753E+09 65371284.91 0.172519E+09 0.156364E+09
December 0.198699E+09 0.131860E+09 66838949.61 0.165007E+09 0.243989E+09
           
Annual Sum or Average 0.258212E+10 0.137661E+10 0.120551E+10 0.277706E+10 0.151838E+10
Minimum of Months 0.147187E+09 25019683.95 65371284.91 0.165007E+09 41103828.53
Maximum of Months 0.294598E+09 0.201189E+09 0.129232E+09 0.299362E+09 0.250772E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.257836E+09 0.181189E+09 76646730.05 0.231014E+09 0.250772E+09
February 0.294598E+09 0.201189E+09 93408890.40 0.298412E+09 0.187887E+09
March 0.286366E+09 0.183768E+09 0.102598E+09 0.299362E+09 0.168591E+09
April 0.231187E+09 0.122889E+09 0.108298E+09 0.259605E+09 0.103684E+09
May 0.177865E+09 49032398.01 0.128832E+09 0.209337E+09 59922267.00
June 0.147187E+09 25019683.95 0.122167E+09 0.181550E+09 41103828.53
July 0.167888E+09 38656283.52 0.129232E+09 0.213177E+09 44899704.98
August 0.198692E+09 76753455.61 0.121939E+09 0.248804E+09 55950528.08
September 0.233735E+09 0.126781E+09 0.106954E+09 0.277149E+09 85059700.72
October 0.207922E+09 0.124718E+09 83203605.46 0.221118E+09 0.120191E+09
November 0.180124E+09 0.114753E+09 65371284.91 0.172519E+09 0.156364E+09
December 0.198699E+09 0.131860E+09 66838949.61 0.165007E+09 0.243989E+09
           
Annual Sum or Average 0.258210E+10 0.137661E+10 0.120549E+10 0.277705E+10 0.151841E+10
Minimum of Months 0.147187E+09 25019683.95 65371284.91 0.165007E+09 41103828.53
Maximum of Months 0.294598E+09 0.201189E+09 0.129232E+09 0.299362E+09 0.250772E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.257836E+09 0.181189E+09 76646730.05 0.231014E+09 0.250772E+09
February 0.294598E+09 0.201189E+09 93408890.40 0.298412E+09 0.187887E+09
March 0.286366E+09 0.183768E+09 0.102598E+09 0.299362E+09 0.168591E+09
April 0.231187E+09 0.122889E+09 0.108298E+09 0.259605E+09 0.103684E+09
May 0.177865E+09 49032398.01 0.128832E+09 0.209337E+09 59922267.00
June 0.147187E+09 25019683.95 0.122167E+09 0.181550E+09 41103828.53
July 0.167888E+09 38656283.52 0.129232E+09 0.213177E+09 44899704.98
August 0.198692E+09 76753473.78 0.121939E+09 0.248804E+09 55950517.80
September 0.233735E+09 0.126781E+09 0.106954E+09 0.277149E+09 85059973.78
October 0.207922E+09 0.124718E+09 83203605.46 0.221118E+09 0.120191E+09
November 0.180124E+09 0.114753E+09 65371284.91 0.172519E+09 0.156364E+09
December 0.198699E+09 0.131860E+09 66838949.61 0.165007E+09 0.243989E+09
           
Annual Sum or Average 0.258210E+10 0.137661E+10 0.120549E+10 0.277705E+10 0.151841E+10
Minimum of Months 0.147187E+09 25019683.95 65371284.91 0.165007E+09 41103828.53
Maximum of Months 0.294598E+09 0.201189E+09 0.129232E+09 0.299362E+09 0.250772E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.257836E+09 0.181189E+09 76646730.05 0.231014E+09 0.250772E+09
February 0.294598E+09 0.201189E+09 93408890.40 0.298412E+09 0.187887E+09
March 0.286366E+09 0.183768E+09 0.102598E+09 0.299362E+09 0.168591E+09
April 0.231195E+09 0.122891E+09 0.108304E+09 0.259606E+09 0.103672E+09
May 0.177865E+09 49032398.01 0.128832E+09 0.209337E+09 59922267.00
June 0.147187E+09 25019683.95 0.122167E+09 0.181550E+09 41103828.53
July 0.167888E+09 38656283.52 0.129232E+09 0.213177E+09 44899704.98
August 0.198692E+09 76753646.20 0.121939E+09 0.248804E+09 55950507.53
September 0.233749E+09 0.126784E+09 0.106965E+09 0.277149E+09 85036947.92
October 0.207922E+09 0.124718E+09 83203605.46 0.221118E+09 0.120191E+09
November 0.180124E+09 0.114753E+09 65371284.91 0.172519E+09 0.156364E+09
December 0.198699E+09 0.131860E+09 66838949.61 0.165007E+09 0.243989E+09
           
Annual Sum or Average 0.258212E+10 0.137661E+10 0.120551E+10 0.277705E+10 0.151838E+10
Minimum of Months 0.147187E+09 25019683.95 65371284.91 0.165007E+09 41103828.53
Maximum of Months 0.294598E+09 0.201189E+09 0.129232E+09 0.299362E+09 0.250772E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.257838E+09 0.181189E+09 76649509.89 0.231017E+09 0.250773E+09
February 0.294601E+09 0.201189E+09 93412372.61 0.298416E+09 0.187887E+09
March 0.286371E+09 0.183768E+09 0.102603E+09 0.299366E+09 0.168591E+09
April 0.231534E+09 0.123064E+09 0.108470E+09 0.259921E+09 0.103313E+09
May 0.178128E+09 49142727.61 0.128985E+09 0.209824E+09 59917601.64
June 0.147285E+09 25055141.05 0.122229E+09 0.181728E+09 41104425.38
July 0.168066E+09 38729330.53 0.129337E+09 0.213510E+09 44900552.24
August 0.199033E+09 76892089.39 0.122141E+09 0.249435E+09 55949934.27
September 0.233858E+09 0.126828E+09 0.107029E+09 0.277234E+09 84924246.62
October 0.207926E+09 0.124718E+09 83208068.36 0.221123E+09 0.120192E+09
November 0.180127E+09 0.114753E+09 65374194.38 0.172522E+09 0.156365E+09
December 0.198702E+09 0.131860E+09 66841502.87 0.165009E+09 0.243989E+09
           
Annual Sum or Average 0.258347E+10 0.137719E+10 0.120628E+10 0.277910E+10 0.151791E+10
Minimum of Months 0.147285E+09 25055141.05 65374194.38 0.165009E+09 41104425.38
Maximum of Months 0.294601E+09 0.201189E+09 0.129337E+09 0.299366E+09 0.250773E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.362979E+09 0.253848E+09 0.109131E+09 0.325996E+09 0.349080E+09
February 0.414926E+09 0.281869E+09 0.133057E+09 0.420875E+09 0.261726E+09
March 0.403950E+09 0.257461E+09 0.146489E+09 0.422198E+09 0.234405E+09
April 0.351573E+09 0.192371E+09 0.159202E+09 0.403313E+09 0.144103E+09
May 0.286982E+09 93353918.66 0.193628E+09 0.350014E+09 83931328.42
June 0.238691E+09 54644438.14 0.184047E+09 0.304175E+09 57675067.72
July 0.273621E+09 78708763.27 0.194913E+09 0.357285E+09 63110299.13
August 0.314125E+09 0.131552E+09 0.182573E+09 0.400969E+09 78344185.41
September 0.332856E+09 0.179091E+09 0.153765E+09 0.395257E+09 0.118573E+09
October 0.294108E+09 0.174731E+09 0.119376E+09 0.313008E+09 0.167694E+09
November 0.254186E+09 0.160771E+09 93415840.03 0.243780E+09 0.217866E+09
December 0.279986E+09 0.184738E+09 95248031.67 0.232999E+09 0.339264E+09
           
Annual Sum or Average 0.380798E+10 0.204314E+10 0.176484E+10 0.416987E+10 0.211577E+10
Minimum of Months 0.238691E+09 54644438.14 93415840.03 0.232999E+09 57675067.72
Maximum of Months 0.414926E+09 0.281869E+09 0.194913E+09 0.422198E+09 0.349080E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79392916.74 34112682.87 45280233.88 33658986.42 0.283807E+09
February 0.112419E+09 48988532.35 63430762.29 72377333.73 0.197519E+09
March 0.169513E+09 86357142.82 83156221.75 0.139022E+09 0.166190E+09
April 0.226000E+09 0.122801E+09 0.103199E+09 0.235215E+09 92466633.64
May 0.249660E+09 0.110458E+09 0.139202E+09 0.291541E+09 54182075.24
June 0.274081E+09 0.131765E+09 0.142316E+09 0.341573E+09 39455934.73
July 0.278203E+09 0.131263E+09 0.146940E+09 0.350405E+09 42498647.74
August 0.214432E+09 94563492.40 0.119869E+09 0.257767E+09 52145550.72
September 0.167143E+09 76029266.07 91114207.40 0.177666E+09 78281422.56
October 0.104557E+09 40778390.71 63778351.72 84422690.99 0.115339E+09
November 64552102.16 22335771.08 42216331.08 33703358.95 0.162011E+09
December 61197830.16 23443920.45 37753909.72 21244359.23 0.275817E+09
           
Annual Sum or Average 0.200115E+10 0.922895E+09 0.107826E+10 0.203860E+10 0.155971E+10
Minimum of Months 61197830.16 22335771.08 37753909.72 21244359.23 39455934.73
Maximum of Months 0.278203E+09 0.131765E+09 0.146940E+09 0.350405E+09 0.283807E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79390136.91 34112682.87 45277454.04 33658139.41 0.283808E+09
February 0.112416E+09 48988532.35 63427280.09 72375197.11 0.197519E+09
March 0.169509E+09 86357142.82 83151853.05 0.139019E+09 0.166191E+09
April 0.225995E+09 0.122801E+09 0.103194E+09 0.235210E+09 92466211.82
May 0.249653E+09 0.110458E+09 0.139194E+09 0.291532E+09 54181236.18
June 0.274074E+09 0.131765E+09 0.142310E+09 0.341566E+09 39455292.19
July 0.278197E+09 0.131263E+09 0.146934E+09 0.350397E+09 42497730.11
August 0.214426E+09 94563492.40 0.119863E+09 0.257760E+09 52144865.23
September 0.167138E+09 76029266.07 91108916.80 0.177660E+09 78280789.27
October 0.104552E+09 40778390.71 63773888.82 84418245.54 0.115339E+09
November 64549192.70 22335771.08 42213421.62 33701791.34 0.162011E+09
December 61195276.90 23443920.45 37751356.46 21243928.74 0.275818E+09
           
Annual Sum or Average 0.200109E+10 0.922895E+09 0.107820E+10 0.203854E+10 0.155971E+10
Minimum of Months 61195276.90 22335771.08 37751356.46 21243928.74 39455292.19
Maximum of Months 0.278197E+09 0.131765E+09 0.146934E+09 0.350397E+09 0.283808E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79390136.91 34112682.87 45277454.04 33658139.41 0.283808E+09
February 0.112416E+09 48988532.35 63427280.09 72375197.11 0.197519E+09
March 0.169509E+09 86357142.82 83151853.05 0.139019E+09 0.166191E+09
April 0.225995E+09 0.122801E+09 0.103194E+09 0.235210E+09 92466211.82
May 0.249653E+09 0.110458E+09 0.139194E+09 0.291532E+09 54181236.18
June 0.274074E+09 0.131765E+09 0.142310E+09 0.341566E+09 39455292.19
July 0.278197E+09 0.131263E+09 0.146934E+09 0.350397E+09 42497730.11
August 0.214426E+09 94563492.40 0.119863E+09 0.257760E+09 52144865.23
September 0.167138E+09 76029266.07 91108916.80 0.177660E+09 78280789.27
October 0.104552E+09 40778390.71 63773888.82 84418245.54 0.115339E+09
November 64549192.70 22335771.08 42213421.62 33701791.34 0.162011E+09
December 61195276.90 23443920.45 37751356.46 21243928.74 0.275818E+09
           
Annual Sum or Average 0.200109E+10 0.922895E+09 0.107820E+10 0.203854E+10 0.155971E+10
Minimum of Months 61195276.90 22335771.08 37751356.46 21243928.74 39455292.19
Maximum of Months 0.278197E+09 0.131765E+09 0.146934E+09 0.350397E+09 0.283808E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 79726441.89 34244628.20 45481813.69 33754157.84 0.283276E+09
February 0.112692E+09 49107062.56 63584831.16 72688442.62 0.197314E+09
March 0.169570E+09 86385214.75 83184473.40 0.139108E+09 0.166167E+09
April 0.226000E+09 0.122801E+09 0.103199E+09 0.235215E+09 92466633.66
May 0.249660E+09 0.110458E+09 0.139202E+09 0.291541E+09 54182075.29
June 0.274081E+09 0.131765E+09 0.142316E+09 0.341573E+09 39455934.76
July 0.278203E+09 0.131263E+09 0.146940E+09 0.350405E+09 42498647.79
August 0.214433E+09 94563542.10 0.119869E+09 0.257767E+09 52145550.76
September 0.167157E+09 76033588.02 91123461.22 0.177690E+09 78281422.60
October 0.104651E+09 40816637.96 63834148.81 84593595.07 0.115337E+09
November 64763310.39 22416264.80 42347045.59 33929057.95 0.161847E+09
December 61475556.65 23538230.03 37937326.62 21289496.30 0.275359E+09
           
Annual Sum or Average 0.200241E+10 0.923391E+09 0.107902E+10 0.203955E+10 0.155833E+10
Minimum of Months 61475556.65 22416264.80 37937326.62 21289496.30 39455934.76
Maximum of Months 0.278203E+09 0.131765E+09 0.146940E+09 0.350405E+09 0.283276E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35259115.87 0.00 35259115.87 504196.73 0.314863E+09
February 49258985.08 0.00 49258985.08 5584056.16 0.219687E+09
March 67437558.37 0.00 67437558.37 15731137.09 0.181606E+09
April 85959829.45 677510.45 85282319.01 54605207.84 96333659.06
May 0.124057E+09 6695504.96 0.117362E+09 0.128096E+09 52047298.50
June 0.134354E+09 14816248.65 0.119538E+09 0.159776E+09 37033993.22
July 0.132939E+09 11376030.50 0.121563E+09 0.159556E+09 40291338.00
August 0.100761E+09 1725770.24 99034902.95 0.108317E+09 49940885.47
September 75567566.02 18556.34 75549009.67 59795364.01 79044537.98
October 53624574.16 0.00 53624574.16 22446795.06 0.119070E+09
November 34315779.04 0.00 34315779.04 3368462.69 0.174735E+09
December 29694869.01 0.00 29694869.01 57092.12 0.301622E+09
           
Annual Sum or Average 0.923229E+09 35309621.14 0.887920E+09 0.717837E+09 0.166627E+10
Minimum of Months 29694869.01 0.00 29694869.01 57092.12 37033993.22
Maximum of Months 0.134354E+09 14816248.65 0.121563E+09 0.159776E+09 0.314863E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35256335.89 0.00 35256335.89 503974.22 0.314864E+09
February 49255502.70 0.00 49255502.70 5582693.60 0.219689E+09
March 67433189.45 0.00 67433189.45 15728614.30 0.181607E+09
April 85896860.60 662633.58 85234227.03 54581036.44 96419110.69
May 0.123750E+09 6584466.84 0.117165E+09 0.127608E+09 52126605.07
June 0.133973E+09 14649258.95 0.119323E+09 0.159055E+09 37033298.63
July 0.132531E+09 11214207.34 0.121317E+09 0.158797E+09 40290383.79
August 0.100575E+09 1667127.70 98907663.35 0.107993E+09 49954933.04
September 75564924.96 18668.21 75546256.75 59790083.38 79040792.28
October 53620111.03 0.00 53620111.03 22442799.10 0.119070E+09
November 34312869.42 0.00 34312869.42 3367417.23 0.174736E+09
December 29692315.62 0.00 29692315.62 57003.90 0.301624E+09
           
Annual Sum or Average 0.921861E+09 34796362.62 0.887065E+09 0.715507E+09 0.166645E+10
Minimum of Months 29692315.62 0.00 29692315.62 57003.90 37033298.63
Maximum of Months 0.133973E+09 14649258.95 0.121317E+09 0.159055E+09 0.314864E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35256335.89 0.00 35256335.89 503974.22 0.314864E+09
February 49255502.70 0.00 49255502.70 5582693.60 0.219689E+09
March 67433189.45 0.00 67433189.45 15728614.30 0.181607E+09
April 85870319.01 657027.95 85213291.06 54571414.85 96456670.25
May 0.123750E+09 6584466.84 0.117165E+09 0.127608E+09 52126605.07
June 0.133973E+09 14649258.95 0.119323E+09 0.159055E+09 37033298.63
July 0.132531E+09 11214141.76 0.121317E+09 0.158797E+09 40290383.79
August 0.100571E+09 1666484.55 98904724.71 0.107988E+09 49956127.62
September 75564277.94 18641.66 75545636.27 59791099.81 79042758.34
October 53620111.03 0.00 53620111.03 22442799.10 0.119070E+09
November 34312869.42 0.00 34312869.42 3367417.23 0.174736E+09
December 29692315.62 0.00 29692315.62 57003.90 0.301624E+09
           
Annual Sum or Average 0.921830E+09 34790021.71 0.887040E+09 0.715493E+09 0.166649E+10
Minimum of Months 29692315.62 0.00 29692315.62 57003.90 37033298.63
Maximum of Months 0.133973E+09 14649258.95 0.121317E+09 0.159055E+09 0.314864E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35256335.89 0.00 35256335.89 503974.22 0.314864E+09
February 49255502.70 0.00 49255502.70 5582693.60 0.219689E+09
March 67433189.45 0.00 67433189.45 15728614.30 0.181607E+09
April 85870319.01 657027.95 85213291.06 54571414.85 96456670.25
May 0.123750E+09 6584466.84 0.117165E+09 0.127608E+09 52126605.07
June 0.133973E+09 14649258.95 0.119323E+09 0.159055E+09 37033298.63
July 0.132531E+09 11214141.76 0.121317E+09 0.158797E+09 40290383.79
August 0.100570E+09 1666475.18 98903344.07 0.107986E+09 49956769.07
September 75564119.18 18682.79 75545436.39 59792602.49 79044448.88
October 53620111.03 0.00 53620111.03 22442799.10 0.119070E+09
November 34312869.42 0.00 34312869.42 3367417.23 0.174736E+09
December 29692315.62 0.00 29692315.62 57003.90 0.301624E+09
           
Annual Sum or Average 0.921828E+09 34790053.47 0.887038E+09 0.715493E+09 0.166650E+10
Minimum of Months 29692315.62 0.00 29692315.62 57003.90 37033298.63
Maximum of Months 0.133973E+09 14649258.95 0.121317E+09 0.159055E+09 0.314864E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35256335.89 0.00 35256335.89 503974.22 0.314864E+09
February 49255502.70 0.00 49255502.70 5582693.60 0.219689E+09
March 67433189.45 0.00 67433189.45 15728614.30 0.181607E+09
April 85895105.93 661819.69 85233286.24 54590106.00 96432430.93
May 0.123750E+09 6584466.84 0.117165E+09 0.127608E+09 52126605.07
June 0.133973E+09 14649258.95 0.119323E+09 0.159055E+09 37033298.63
July 0.132531E+09 11214168.92 0.121317E+09 0.158797E+09 40290383.79
August 0.100572E+09 1667390.03 98904184.29 0.107991E+09 49957367.34
September 75564463.22 18791.94 75545671.28 59794382.54 79045586.25
October 53620111.03 0.00 53620111.03 22442799.10 0.119070E+09
November 34312869.42 0.00 34312869.42 3367417.23 0.174736E+09
December 29692315.62 0.00 29692315.62 57003.90 0.301624E+09
           
Annual Sum or Average 0.921855E+09 34795896.37 0.887059E+09 0.715518E+09 0.166647E+10
Minimum of Months 29692315.62 0.00 29692315.62 57003.90 37033298.63
Maximum of Months 0.133973E+09 14649258.95 0.121317E+09 0.159055E+09 0.314864E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 35259115.73 0.00 35259115.73 504196.72 0.314863E+09
February 49258984.90 0.00 49258984.90 5584056.09 0.219687E+09
March 67437558.14 0.00 67437558.14 15731136.96 0.181606E+09
April 85958168.38 675751.22 85282417.17 54641554.04 96376644.11
May 0.124060E+09 6730145.51 0.117330E+09 0.128213E+09 52125583.93
June 0.134277E+09 14764998.29 0.119512E+09 0.159610E+09 37033981.70
July 0.132881E+09 11353703.26 0.121527E+09 0.159444E+09 40290647.10
August 0.100768E+09 1727013.61 99041363.93 0.108345E+09 49957908.05
September 75567044.57 18722.65 75548321.92 59800388.32 79050090.62
October 53624573.93 0.00 53624573.93 22446794.85 0.119070E+09
November 34315778.89 0.00 34315778.89 3368462.63 0.174735E+09
December 29694868.87 0.00 29694868.87 57092.12 0.301622E+09
           
Annual Sum or Average 0.923102E+09 35270334.54 0.887832E+09 0.717745E+09 0.166642E+10
Minimum of Months 29694868.87 0.00 29694868.87 57092.12 37033981.70
Maximum of Months 0.134277E+09 14764998.29 0.121527E+09 0.159610E+09 0.314863E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80660867.98 34770518.31 45890349.67 37996808.43 0.290023E+09
February 0.118369E+09 55273901.09 63094901.62 85152726.49 0.205523E+09
March 0.171619E+09 89280185.71 82339168.78 0.147222E+09 0.173805E+09
April 0.210533E+09 0.107467E+09 0.103066E+09 0.218783E+09 99179945.65
May 0.265730E+09 0.127983E+09 0.137747E+09 0.316583E+09 59832926.79
June 0.247356E+09 0.107609E+09 0.139747E+09 0.308759E+09 41853062.52
July 0.272157E+09 0.126674E+09 0.145483E+09 0.343476E+09 46453429.71
August 0.224652E+09 0.102691E+09 0.121961E+09 0.273903E+09 55501446.54
September 0.171454E+09 78339688.70 93114808.48 0.185870E+09 82167620.98
October 0.112012E+09 46182178.90 65829345.36 97157006.72 0.119563E+09
November 66069716.40 23056825.56 43012890.84 37393524.84 0.166137E+09
December 61240543.57 22199576.07 39040967.51 21905583.06 0.280275E+09
           
Annual Sum or Average 0.200185E+10 0.921526E+09 0.108033E+10 0.207420E+10 0.162031E+10
Minimum of Months 61240543.57 22199576.07 39040967.51 21905583.06 41853062.52
Maximum of Months 0.272157E+09 0.127983E+09 0.145483E+09 0.343476E+09 0.290023E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80338468.73 34642231.36 45696237.37 37914397.48 0.290540E+09
February 0.118088E+09 55154639.68 62933703.40 84827489.43 0.205718E+09
March 0.171557E+09 89252093.09 82304694.00 0.147127E+09 0.173824E+09
April 0.210528E+09 0.107467E+09 0.103061E+09 0.218778E+09 99179649.72
May 0.265722E+09 0.127983E+09 0.137740E+09 0.316574E+09 59832105.57
June 0.247349E+09 0.107609E+09 0.139741E+09 0.308752E+09 41852436.63
July 0.272151E+09 0.126674E+09 0.145476E+09 0.343468E+09 46452634.26
August 0.224645E+09 0.102691E+09 0.121955E+09 0.273895E+09 55500890.87
September 0.171438E+09 78335045.59 93102822.72 0.185843E+09 82167182.69
October 0.111905E+09 46141093.63 65763978.17 96967883.06 0.119564E+09
November 65832828.91 22973133.17 42859695.73 37128574.22 0.166296E+09
December 60968112.27 22104495.12 38863617.15 21873702.41 0.280735E+09
           
Annual Sum or Average 0.200052E+10 0.921026E+09 0.107950E+10 0.207315E+10 0.162166E+10
Minimum of Months 60968112.27 22104495.12 38863617.15 21873702.41 41852436.63
Maximum of Months 0.272151E+09 0.127983E+09 0.145476E+09 0.343468E+09 0.290540E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80338468.73 34642231.36 45696237.37 37914397.48 0.290540E+09
February 0.118088E+09 55154639.68 62933703.40 84827489.43 0.205718E+09
March 0.171557E+09 89252093.09 82304694.00 0.147127E+09 0.173824E+09
April 0.210528E+09 0.107467E+09 0.103061E+09 0.218778E+09 99179649.72
May 0.265722E+09 0.127983E+09 0.137740E+09 0.316574E+09 59832105.57
June 0.247349E+09 0.107609E+09 0.139741E+09 0.308752E+09 41852436.63
July 0.272151E+09 0.126674E+09 0.145476E+09 0.343468E+09 46452634.26
August 0.224645E+09 0.102691E+09 0.121955E+09 0.273895E+09 55500890.87
September 0.171438E+09 78335045.59 93102822.72 0.185843E+09 82167182.69
October 0.111905E+09 46141093.63 65763978.17 96967883.06 0.119564E+09
November 65832828.91 22973133.17 42859695.73 37128574.22 0.166296E+09
December 60968112.27 22104495.12 38863617.15 21873702.41 0.280735E+09
           
Annual Sum or Average 0.200052E+10 0.921026E+09 0.107950E+10 0.207315E+10 0.162166E+10
Minimum of Months 60968112.27 22104495.12 38863617.15 21873702.41 41852436.63
Maximum of Months 0.272151E+09 0.127983E+09 0.145476E+09 0.343468E+09 0.290540E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 80341248.72 34642231.36 45699017.35 37915223.43 0.290539E+09
February 0.118092E+09 55154639.68 62937185.79 84829651.41 0.205717E+09
March 0.171561E+09 89252093.09 82309062.93 0.147130E+09 0.173823E+09
April 0.210533E+09 0.107467E+09 0.103066E+09 0.218783E+09 99179945.66
May 0.265730E+09 0.127983E+09 0.137747E+09 0.316583E+09 59832926.84
June 0.247356E+09 0.107609E+09 0.139747E+09 0.308759E+09 41853062.55
July 0.272157E+09 0.126674E+09 0.145483E+09 0.343476E+09 46453429.75
August 0.224651E+09 0.102691E+09 0.121961E+09 0.273902E+09 55501446.57
September 0.171443E+09 78335045.59 93108113.60 0.185849E+09 82167621.00
October 0.111910E+09 46141093.63 65768441.30 96972262.50 0.119564E+09
November 65835738.52 22973133.17 42862605.35 37130134.52 0.166295E+09
December 60970665.66 22104495.12 38866170.54 21874213.60 0.280734E+09
           
Annual Sum or Average 0.200058E+10 0.921026E+09 0.107955E+10 0.207320E+10 0.162166E+10
Minimum of Months 60970665.66 22104495.12 38866170.54 21874213.60 41853062.55
Maximum of Months 0.272157E+09 0.127983E+09 0.145483E+09 0.343476E+09 0.290539E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 639.22 692.09 713.11 500.67 212.45 0.00 0.00
February 914.08 574.17 902.17 615.49 286.67 0.00 0.00
March 828.24 465.18 792.32 507.79 284.53 0.00 0.00
April 756.79 295.34 671.06 358.81 312.25 0.00 0.00
May 599.99 165.56 505.79 144.78 361.01 0.00 0.00
June 537.74 117.40 432.87 79.02 353.85 0.00 0.00
July 611.19 124.14 478.38 116.04 362.35 0.00 0.00
August 707.54 154.58 562.64 221.16 341.48 0.00 0.00
September 794.13 242.53 669.59 362.61 306.97 0.00 0.00
October 612.19 331.85 575.58 344.62 230.96 0.00 0.00
November 493.39 446.00 515.02 327.66 187.36 0.00 0.00
December 456.62 673.23 549.65 364.36 185.29 0.00 0.00
               
Annual Sum or Average 660.71 355.95 612.11 326.74 285.37 0.00 0.00
Minimum of Months 456.62 117.40 432.87 79.02 185.29 0.00 0.00
Maximum of Months 914.08 692.09 902.17 615.49 362.35 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 50.30 423.64 118.69 50.99 67.70 0.00 0.00
February 119.78 326.49 185.99 81.05 104.94 0.00 0.00
March 207.65 248.18 253.17 128.98 124.20 0.00 0.00
April 362.98 142.70 348.76 189.51 159.25 0.00 0.00
May 435.39 80.92 372.84 164.96 207.88 0.00 0.00
June 527.11 60.89 422.96 203.34 219.62 0.00 0.00
July 523.30 63.47 415.47 196.03 219.44 0.00 0.00
August 384.95 77.88 320.24 141.22 179.01 0.00 0.00
September 274.18 120.80 257.94 117.33 140.61 0.00 0.00
October 126.14 172.25 156.18 60.91 95.27 0.00 0.00
November 52.09 249.95 99.70 34.50 65.20 0.00 0.00
December 31.74 411.74 91.50 35.05 56.45 0.00 0.00
               
Annual Sum or Average 258.60 197.79 253.86 117.07 136.79 0.00 0.00
Minimum of Months 31.74 60.89 91.50 34.50 56.45 0.00 0.00
Maximum of Months 527.11 423.64 422.96 203.34 219.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1.13 705.34 78.98 0.00 78.98 0.00 0.00
February 13.85 544.86 122.16 0.00 122.16 0.00 0.00
March 35.24 406.83 151.06 0.00 151.06 0.00 0.00
April 126.37 223.18 198.86 1.54 197.32 0.00 0.00
May 286.25 116.72 277.45 14.85 262.60 0.00 0.00
June 368.68 85.73 310.39 34.02 276.37 0.00 0.00
July 356.25 90.26 297.17 25.23 271.94 0.00 0.00
August 242.16 111.90 225.44 3.78 221.66 0.00 0.00
September 138.41 182.97 174.92 0.04 174.88 0.00 0.00
October 50.28 266.73 120.12 0.00 120.12 0.00 0.00
November 7.80 404.48 79.43 0.00 79.43 0.00 0.00
December 0.13 675.68 66.52 0.00 66.52 0.00 0.00
               
Annual Sum or Average 136.27 317.05 175.47 6.65 168.82 0.00 0.00
Minimum of Months 0.13 85.73 66.52 0.00 66.52 0.00 0.00
Maximum of Months 368.68 705.34 310.39 34.02 276.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 56.65 433.70 120.10 51.78 68.32 0.00 0.00
February 140.39 340.06 195.37 91.24 104.13 0.00 0.00
March 219.76 259.59 256.23 133.30 122.93 0.00 0.00
April 337.62 153.06 324.89 165.84 159.05 0.00 0.00
May 472.79 89.36 396.84 191.13 205.71 0.00 0.00
June 476.47 64.59 381.72 166.06 215.65 0.00 0.00
July 512.95 69.37 406.44 189.18 217.26 0.00 0.00
August 409.05 82.89 335.50 153.36 182.14 0.00 0.00
September 286.81 126.80 264.57 120.89 143.68 0.00 0.00
October 144.89 178.56 167.16 68.92 98.24 0.00 0.00
November 57.39 256.56 101.69 35.48 66.20 0.00 0.00
December 32.68 419.08 91.15 33.05 58.11 0.00 0.00
               
Annual Sum or Average 262.99 205.65 253.79 116.84 136.95 0.00 0.00
Minimum of Months 32.68 64.59 91.15 33.05 58.11 0.00 0.00
Maximum of Months 512.95 433.70 406.44 191.13 217.26 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.171208E+10 0.185370E+10 0.191000E+10 0.134098E+10 0.569017E+09 0.00 0.00
February 0.221135E+10 0.138904E+10 0.218252E+10 0.148900E+10 0.693517E+09 0.00 0.00
March 0.221835E+10 0.124593E+10 0.212216E+10 0.136007E+10 0.762087E+09 0.00 0.00
April 0.196160E+10 0.765518E+09 0.173938E+10 0.930041E+09 0.809342E+09 0.00 0.00
May 0.160702E+10 0.443446E+09 0.135470E+10 0.387779E+09 0.966922E+09 0.00 0.00
June 0.139382E+10 0.304294E+09 0.112200E+10 0.204832E+09 0.917172E+09 0.00 0.00
July 0.163700E+10 0.332508E+09 0.128130E+10 0.310790E+09 0.970515E+09 0.00 0.00
August 0.189507E+10 0.414040E+09 0.150697E+10 0.592354E+09 0.914616E+09 0.00 0.00
September 0.205840E+10 0.628629E+09 0.173557E+10 0.939893E+09 0.795676E+09 0.00 0.00
October 0.163970E+10 0.888817E+09 0.154165E+10 0.923039E+09 0.618607E+09 0.00 0.00
November 0.127888E+10 0.115603E+10 0.133494E+10 0.849289E+09 0.485649E+09 0.00 0.00
December 0.122302E+10 0.180317E+10 0.147219E+10 0.975901E+09 0.496287E+09 0.00 0.00
               
Annual Sum or Average 0.208363E+11 0.112251E+11 0.193034E+11 0.103040E+11 0.899941E+10 0.00 0.00
Minimum of Months 0.122302E+10 0.304294E+09 0.112200E+10 0.204832E+09 0.485649E+09 0.00 0.00
Maximum of Months 0.221835E+10 0.185370E+10 0.218252E+10 0.148900E+10 0.970515E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.134712E+09 0.113468E+10 0.317900E+09 0.136583E+09 0.181317E+09 0.00 0.00
February 0.289783E+09 0.789838E+09 0.449943E+09 0.196073E+09 0.253870E+09 0.00 0.00
March 0.556168E+09 0.664738E+09 0.678101E+09 0.345457E+09 0.332644E+09 0.00 0.00
April 0.940850E+09 0.369866E+09 0.903990E+09 0.491202E+09 0.412788E+09 0.00 0.00
May 0.116614E+10 0.216727E+09 0.998625E+09 0.441832E+09 0.556793E+09 0.00 0.00
June 0.136628E+10 0.157822E+09 0.109631E+10 0.527058E+09 0.569252E+09 0.00 0.00
July 0.140160E+10 0.169993E+09 0.111280E+10 0.525051E+09 0.587749E+09 0.00 0.00
August 0.103105E+10 0.208581E+09 0.857718E+09 0.378254E+09 0.479464E+09 0.00 0.00
September 0.710676E+09 0.313124E+09 0.668577E+09 0.304121E+09 0.364456E+09 0.00 0.00
October 0.337853E+09 0.461355E+09 0.418312E+09 0.163152E+09 0.255160E+09 0.00 0.00
November 0.135013E+09 0.647858E+09 0.258414E+09 89423578.03 0.168990E+09 0.00 0.00
December 85020084.25 0.110281E+10 0.245064E+09 93869991.37 0.151194E+09 0.00 0.00
               
Annual Sum or Average 0.815515E+10 0.623739E+10 0.800575E+10 0.369208E+10 0.431368E+10 0.00 0.00
Minimum of Months 85020084.25 0.157822E+09 0.245064E+09 89423578.03 0.151194E+09 0.00 0.00
Maximum of Months 0.140160E+10 0.113468E+10 0.111280E+10 0.527058E+09 0.587749E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 3024290.33 0.188918E+10 0.211544E+09 0.00 0.211544E+09 0.00 0.00
February 33498886.67 0.131813E+10 0.295540E+09 0.00 0.295540E+09 0.00 0.00
March 94376731.25 0.108964E+10 0.404608E+09 0.00 0.404608E+09 0.00 0.00
April 0.327556E+09 0.578471E+09 0.515451E+09 3991770.83 0.511459E+09 0.00 0.00
May 0.766699E+09 0.312636E+09 0.743116E+09 39763517.84 0.703353E+09 0.00 0.00
June 0.955607E+09 0.222201E+09 0.804522E+09 88178282.75 0.716344E+09 0.00 0.00
July 0.954187E+09 0.241744E+09 0.795945E+09 67586393.53 0.728358E+09 0.00 0.00
August 0.648606E+09 0.299711E+09 0.603816E+09 10120261.30 0.593696E+09 0.00 0.00
September 0.358762E+09 0.474266E+09 0.453392E+09 112063.60 0.453280E+09 0.00 0.00
October 0.134665E+09 0.714419E+09 0.321730E+09 0.00 0.321730E+09 0.00 0.00
November 20206588.68 0.104841E+10 0.205883E+09 0.00 0.205883E+09 0.00 0.00
December 342199.86 0.180974E+10 0.178159E+09 0.00 0.178159E+09 0.00 0.00
               
Annual Sum or Average 0.429753E+10 0.999855E+10 0.553371E+10 0.209752E+09 0.532395E+10 0.00 0.00
Minimum of Months 342199.86 0.222201E+09 0.178159E+09 0.00 0.178159E+09 0.00 0.00
Maximum of Months 0.955607E+09 0.188918E+10 0.804522E+09 88178282.75 0.728358E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.151727E+09 0.116163E+10 0.321679E+09 0.138697E+09 0.182982E+09 0.00 0.00
February 0.339625E+09 0.822664E+09 0.472637E+09 0.220738E+09 0.251899E+09 0.00 0.00
March 0.588605E+09 0.695275E+09 0.686294E+09 0.357036E+09 0.329258E+09 0.00 0.00
April 0.875122E+09 0.396719E+09 0.842120E+09 0.429868E+09 0.412252E+09 0.00 0.00
May 0.126631E+10 0.239330E+09 0.106290E+10 0.511930E+09 0.550973E+09 0.00 0.00
June 0.123502E+10 0.167411E+09 0.989411E+09 0.430435E+09 0.558976E+09 0.00 0.00
July 0.137389E+10 0.185812E+09 0.108862E+10 0.506696E+09 0.581919E+09 0.00 0.00
August 0.109560E+10 0.222005E+09 0.898594E+09 0.410762E+09 0.487831E+09 0.00 0.00
September 0.743405E+09 0.328670E+09 0.685773E+09 0.313345E+09 0.372429E+09 0.00 0.00
October 0.388064E+09 0.478255E+09 0.447731E+09 0.184605E+09 0.263126E+09 0.00 0.00
November 0.148753E+09 0.664996E+09 0.263571E+09 91976225.08 0.171595E+09 0.00 0.00
December 87521496.35 0.112247E+10 0.244147E+09 88513061.42 0.155634E+09 0.00 0.00
               
Annual Sum or Average 0.829364E+10 0.648524E+10 0.800348E+10 0.368460E+10 0.431887E+10 0.00 0.00
Minimum of Months 87521496.35 0.167411E+09 0.244147E+09 88513061.42 0.155634E+09 0.00 0.00
Maximum of Months 0.137389E+10 0.116163E+10 0.108862E+10 0.511930E+09 0.581919E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -16.9 -17.4 -20.0 3.73 -31.9 33.25 98.18 0.00
February -11.6 -12.7 -16.7 4.33 -26.7 48.91 138.70 0.00
March -6.2 -7.6 -10.8 3.55 -19.4 56.69 163.76 0.01
April 3.97 0.41 -4.8 4.72 -9.1 70.41 207.70 0.01
May 13.43 8.45 3.53 3.60 2.20 102.27 202.62 0.00
June 18.03 14.19 11.55 3.74 7.84 104.36 210.60 0.06
July 19.67 16.51 14.78 3.14 8.97 101.67 223.82 0.04
August 17.94 15.20 13.59 3.45 8.99 87.39 175.79 0.04
September 12.29 9.87 7.80 3.78 3.34 70.27 143.96 0.00
October 5.42 3.47 1.07 3.53 -4.7 51.74 90.11 0.00
November -2.0 -3.6 -6.9 4.42 -13.7 34.68 65.95 0.00
December -14.6 -15.1 -18.1 3.91 -28.3 29.58 68.99 0.00
                 
Annual Sum or Average 3.36 1.04 -2.0 3.82 -8.4 66.03 149.18 0.01
Minimum of Months -16.9 -17.4 -20.0 3.14 -31.9 29.58 65.95 0.00
Maximum of Months 19.67 16.51 14.78 4.72 8.99 104.36 223.82 0.06



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 1.10 29-JAN-14:00 -1.0 -4.4 2.60 -11.4 145.00 110.00
February 8.90 20-FEB-15:00 2.87 -6.7 8.80 -9.0 49.00 646.00
March 11.10 26-MAR-15:00 5.48 -1.1 5.20 -5.7 53.00 842.00
April 26.70 23-APR-15:00 16.95 11.10 11.30 12.03 75.50 811.00
May 29.40 25-MAY-17:00 19.26 13.90 1.50 16.49 47.50 582.00
June 35.00 29-JUN-15:00 24.72 21.10 6.70 24.66 132.00 705.00
July 31.10 15-JUL-14:20 25.35 23.33 8.07 19.93 299.67 518.33
August 30.60 08-AUG-14:00 23.36 20.60 6.70 17.93 163.50 672.50
September 26.10 01-SEP-14:00 17.82 13.30 3.60 14.28 112.00 751.50
October 22.20 19-OCT-14:00 13.62 7.20 6.70 8.15 35.50 701.50
November 18.30 01-NOV-14:00 13.44 10.00 3.10 11.84 105.00 30.50
December 1.10 28-DEC-02:00 0.43 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 1.10   -1.0 -6.7 1.50 -11.4 0.00 0.00
Maximum of Months 35.00   25.35 23.33 11.30 24.66 299.67 842.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -35.6 06-JAN-08:00 -35.7 -37.8 0.00 -57.8 27.00 381.00
February -33.3 14-FEB-06:00 -33.4 -36.7 0.00 -55.6 0.00 0.00
March -28.9 05-MAR-06:00 -29.1 -32.2 1.50 -50.6 27.00 41.50
April -13.9 05-APR-05:00 -14.4 -16.1 0.00 -32.5 14.50 199.00
May -3.9 01-MAY-05:00 -6.2 -12.2 0.00 -22.4 35.00 415.00
June 1.10 04-JUN-04:00 0.62 0.00 0.00 -14.9 37.00 169.50
July 6.10 02-JUL-04:00 6.10 6.10 0.00 -8.8 33.50 204.50
August 4.40 19-AUG-03:00 4.40 4.40 0.00 -10.7 0.00 0.00
September 1.10 06-SEP-03:00 1.10 1.10 0.00 -14.7 0.00 0.00
October -10.0 30-OCT-03:00 -10.7 -12.8 1.50 -28.2 0.00 0.00
November -20.6 29-NOV-05:00 -20.8 -22.2 2.10 -37.8 0.00 0.00
December -31.1 24-DEC-06:19 -31.3 -35.1 3.33 -53.1 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -35.6   -35.7 -37.8 0.00 -57.8 0.00 0.00
Maximum of Months 6.10   6.10 6.10 3.33 -8.8 37.00 415.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -0.5 16-JAN-12:00 0.00 -1.1 5.70 -6.6 172.50 3.00
February 3.34 21-FEB-12:00 6.70 -1.1 7.70 -6.0 270.00 303.00
March 5.48 26-MAR-15:00 11.10 -1.1 5.20 -5.7 53.00 842.00
April 16.95 23-APR-15:00 26.70 11.10 11.30 12.03 75.50 811.00
May 19.91 26-MAY-11:00 25.60 17.20 6.20 22.64 300.50 6.00
June 24.72 29-JUN-15:00 35.00 21.10 6.70 24.66 132.00 705.00
July 25.76 15-JUL-13:00 31.10 23.90 7.70 18.99 333.00 421.00
August 23.36 08-AUG-14:00 30.60 20.60 6.70 17.93 163.50 672.50
September 18.67 01-SEP-00:00 19.00 17.50 2.80 16.30 0.00 0.00
October 13.72 19-OCT-13:00 21.70 7.80 5.70 7.75 54.50 739.00
November 14.29 21-NOV-12:00 15.00 13.90 5.20 11.46 134.50 25.50
December 0.43 28-DEC-02:00 1.10 -0.6 4.60 -5.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -0.5   0.00 -1.1 2.80 -6.6 0.00 0.00
Maximum of Months 25.76   35.00 23.90 11.30 24.66 333.00 842.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 16-JAN-11:00 -0.6 -0.8 5.70 -7.3 164.50 5.00
February -0.6 21-FEB-08:00 4.40 2.25 8.80 -6.6 123.00 89.50
March 0.00 29-MAR-20:00 1.70 0.95 1.50 -4.8 0.00 0.00
April 11.10 23-APR-13:00 24.40 16.08 10.80 9.72 98.50 903.50
May 17.20 26-MAY-11:00 25.60 19.91 6.20 22.64 300.50 6.00
June 22.80 29-JUN-23:19 26.30 23.71 5.20 14.28 0.00 0.00
July 23.90 15-JUL-13:00 31.10 25.76 7.70 18.99 333.00 421.00
August 20.60 08-AUG-14:00 30.60 23.36 6.70 17.93 163.50 672.50
September 17.92 01-SEP-00:10 19.75 18.15 3.22 13.23 0.00 0.00
October 12.20 07-OCT-12:20 14.47 13.17 3.43 9.20 163.17 18.50
November 13.90 21-NOV-12:00 15.00 14.29 5.20 11.46 134.50 25.50
December -0.0 05-DEC-17:00 0.00 -0.0 1.50 -6.4 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -0.6 -0.8 1.50 -7.3 0.00 0.00
Maximum of Months 23.90   31.10 25.76 10.80 22.64 333.00 903.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 1.89 11.66 0.00
February 18.00 13.00 16.00 0.58 19.92 0.00
March 18.00 13.00 16.00 0.81 26.63 0.00
April 18.00 13.00 16.00 2.58 37.52 0.00
May 18.00 13.00 16.00 5.43 45.25 0.00
June 18.00 13.00 16.00 8.61 47.76 0.00
July 18.00 13.00 16.00 11.25 48.86 0.00
August 18.00 13.00 16.00 12.66 38.94 0.00
September 18.00 13.00 16.00 12.41 29.23 0.00
October 18.00 13.00 16.00 10.60 17.37 0.00
November 18.00 13.00 16.00 7.72 10.89 0.00
December 18.00 13.00 16.00 4.55 9.11 0.00
             
Annual Sum or Average 18.00 13.00 16.00 6.63 28.63 0.00
Minimum of Months 18.00 13.00 16.00 0.58 9.11 0.00
Maximum of Months 18.00 13.00 16.00 12.66 48.86 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.709381E+09 -580499476.2 0.00 0.00 744.00 0.00 -128881626.4 59.00 0.00 0.00
February 0.652601E+09 -537229565.9 0.00 0.00 672.00 0.00 -115371801.7 59.00 0.00 0.00
March 0.773859E+09 -647674043.0 0.00 0.00 744.00 0.00 -126184907.0 59.00 0.00 0.00
April 0.665146E+09 -546364691.7 0.00 0.00 720.00 0.00 -118780868.3 58.99 0.00 0.00
May 0.686531E+09 -571513938.6 0.00 0.00 744.00 0.00 -115017255.4 59.00 0.00 0.00
June 0.644471E+09 -536056234.7 0.00 0.00 720.00 0.00 -108414954.1 58.99 0.00 0.00
July 0.570968E+09 -461617952.1 0.00 0.00 744.00 0.00 -109349873.5 58.99 0.00 0.00
August 0.625848E+09 -516014936.0 0.00 0.00 744.00 0.00 -109833100.6 58.99 0.00 0.00
September 0.558969E+09 -451290355.4 0.00 0.00 720.00 0.00 -107678213.8 58.99 0.00 0.00
October 0.610055E+09 -492297262.1 0.00 0.00 744.00 0.00 -117757798.0 58.99 0.00 0.00
November 0.641609E+09 -521135405.9 0.00 0.00 720.00 0.00 -120473185.1 58.99 0.00 0.00
December 0.654687E+09 -526568596.6 0.00 0.00 744.00 0.00 -128118186.6 58.99 0.00 0.00
                     
Annual Sum or Average 0.779412E+10 -0.638826E+10 0.00 0.00 8760.00 0.00 -0.140586E+10 58.99 0.00 0.00
Minimum of Months 0.558969E+09 -647674043.0 0.00 0.00 672.00 0.00 -128881626.4 58.99 0.00 0.00
Maximum of Months 0.773859E+09 -451290355.4 0.00 0.00 744.00 0.00 -107678213.8 59.00 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.76 0.73 01-JAN-08:00 811.06 23.12 80.83 196.00 1556.78 30.60 205.00 176.67
February 265.33 0.76 0.73 01-FEB-08:50 1750.08 25.68 121.83 216.67 2047.47 32.49 257.67 212.67
March 254.17 0.76 0.73 02-MAR-10:39 3804.42 28.40 140.83 248.50 716.09 22.99 230.00 197.17
April 296.33 0.77 0.73 01-APR-10:39 657.49 17.55 4.17 247.83 529.87 21.92 241.00 185.83
May 437.50 0.78 0.73 01-MAY-08:30 527.71 17.90 0.00 287.83 398.60 22.26 299.17 227.50
June 401.83 0.78 0.73 01-JUN-07:40 505.64 17.93 0.00 261.50 377.36 22.29 285.17 188.50
July 409.17 0.77 0.73 01-JUL-07:30 553.32 18.30 0.17 288.50 415.22 22.69 309.00 217.50
August 352.83 0.76 0.73 01-AUG-07:00 660.82 18.61 6.00 261.33 505.25 22.98 277.00 206.33
September 344.17 0.77 0.73 01-SEP-07:40 755.62 18.69 13.17 245.33 544.39 22.71 239.83 207.67
October 299.00 0.76 0.73 01-OCT-07:10 1340.10 25.20 145.50 229.83 553.27 23.26 212.67 180.33
November 255.50 0.77 0.73 01-NOV-08:30 804.41 25.14 120.17 175.17 1211.21 30.15 219.33 154.50
December 226.33 0.76 0.73 01-DEC-08:20 717.07 22.93 76.83 152.83 1194.66 31.39 205.50 134.83
                         
Annual Sum or Average 3785.50 0.77     989.48 21.01 709.50 2811.33 757.61 24.85 2981.33 2289.50
Minimum of Months 226.33 0.76 0.73   505.64 17.55 0.00 152.83 377.36 21.92 205.00 134.83
Maximum of Months 437.50 0.78 0.73   3804.42 28.40 145.50 288.50 2047.47 32.49 309.00 227.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.81 0.73 01-JAN-08:39 669.93 21.03 72.00 93.83 314.39 22.67 107.83 41.50
February 265.33 0.80 0.73 01-FEB-08:00 905.73 19.35 49.50 130.17 599.67 24.56 155.17 88.50
March 254.17 0.80 0.73 02-MAR-10:50 1385.84 19.02 39.83 141.17 1100.35 23.68 134.00 100.17
April 296.33 0.80 0.73 01-APR-10:39 497.31 15.56 1.17 170.50 424.32 20.63 147.17 119.83
May 437.50 0.79 0.73 01-MAY-05:40 477.41 16.46 0.00 234.67 401.87 22.51 251.17 173.83
June 401.83 0.78 0.73 01-JUN-05:10 515.86 16.62 0.00 220.67 478.61 23.22 241.17 170.67
July 409.17 0.78 0.73 01-JUL-04:00 525.99 16.83 0.00 228.33 467.06 23.12 256.00 181.83
August 352.83 0.78 0.73 01-AUG-07:40 507.62 16.83 0.33 189.50 415.30 21.71 197.67 132.83
September 344.17 0.80 0.73 01-SEP-06:49 490.79 16.61 8.33 162.33 353.77 21.15 160.50 108.83
October 299.00 0.81 0.73 01-OCT-06:00 986.75 19.71 78.50 124.50 380.16 22.47 142.00 59.83
November 255.50 0.82 0.73 05-NOV-08:09 632.34 20.05 78.50 80.00 223.76 21.40 90.00 26.33
December 226.33 0.82 0.73 01-DEC-08:50 537.04 20.66 69.17 60.33 187.18 19.37 41.67 16.33
                         
Annual Sum or Average 3785.50 0.79     649.98 17.91 397.33 1836.00 444.26 22.27 1924.33 1220.50
Minimum of Months 226.33 0.78 0.73   477.41 15.56 0.00 60.33 187.18 19.37 41.67 16.33
Maximum of Months 437.50 0.82 0.73   1385.84 21.03 78.50 234.67 1100.35 24.56 256.00 181.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.89 0.74 30-JAN-12:30 153.49 13.33 0.00 0.00 110.19 17.47 0.00 0.00
February 265.33 0.86 0.74 26-FEB-12:30 194.50 14.64 0.00 1.67 141.84 18.80 6.00 0.00
March 254.17 0.85 0.73 24-MAR-10:30 213.62 15.23 0.00 5.33 159.11 19.40 23.17 0.00
April 296.33 0.83 0.73 06-APR-14:30 244.90 15.75 0.00 19.83 178.11 19.72 46.33 1.00
May 437.50 0.78 0.73 01-MAY-05:40 358.21 17.30 0.00 168.50 230.05 22.11 224.33 5.67
June 401.83 0.76 0.73 01-JUN-05:30 402.79 19.61 33.17 237.33 294.26 23.38 280.00 20.33
July 409.17 0.76 0.73 01-JUL-05:30 385.68 19.25 27.00 230.17 256.64 21.94 249.33 0.33
August 352.83 0.78 0.73 01-AUG-08:20 333.43 17.28 0.00 116.50 222.13 21.17 154.83 0.00
September 344.17 0.83 0.74 03-SEP-11:30 237.43 15.84 0.00 4.33 167.74 19.76 15.17 0.00
October 299.00 0.87 0.74 07-OCT-11:30 191.22 14.62 0.00 0.17 133.24 18.51 0.00 0.00
November 255.50 0.90 0.81 01-NOV-13:30 147.87 13.17 0.00 0.00 103.56 17.02 0.00 0.00
December 226.33 0.90 0.82 04-DEC-12:20 141.80 13.08 0.00 0.00 99.65 17.04 0.00 0.00
                         
Annual Sum or Average 3785.50 0.82     269.08 16.18 60.17 783.83 186.64 20.09 999.17 27.33
Minimum of Months 226.33 0.76 0.73   141.80 13.08 0.00 0.00 99.65 17.02 0.00 0.00
Maximum of Months 437.50 0.90 0.82   402.79 19.61 33.17 237.33 294.26 23.38 280.00 20.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 243.33 0.81 0.73 01-JAN-13:50 598.37 20.81 66.00 98.33 299.30 22.47 112.00 38.33
February 265.33 0.80 0.73 01-FEB-13:30 905.86 19.65 50.17 133.67 607.61 24.82 161.33 87.50
March 254.17 0.80 0.73 02-MAR-11:20 1340.69 19.29 39.67 145.67 990.17 23.74 152.67 94.50
April 296.33 0.80 0.73 01-APR-11:20 475.87 15.75 1.00 163.33 397.09 20.69 151.83 112.00
May 437.50 0.79 0.73 01-MAY-13:09 478.85 16.60 0.00 241.00 394.74 21.43 233.33 175.17
June 401.83 0.78 0.73 01-JUN-10:50 490.92 16.95 0.00 207.00 414.43 21.92 229.67 150.00
July 409.17 0.78 0.73 01-JUL-09:39 523.08 17.12 0.00 220.00 442.91 22.10 232.83 168.33
August 352.83 0.78 0.73 01-AUG-10:20 541.18 17.21 2.83 199.83 476.09 22.21 208.00 152.00
September 344.17 0.79 0.73 01-SEP-13:09 538.12 16.85 6.67 174.17 755.25 23.16 180.83 119.33
October 299.00 0.80 0.73 01-OCT-11:20 1084.22 20.35 81.67 133.33 409.03 22.79 146.00 76.33
November 255.50 0.82 0.73 01-NOV-12:50 576.76 19.92 74.00 78.50 221.11 21.29 93.00 28.33
December 226.33 0.82 0.73 01-DEC-12:30 376.70 18.71 41.83 58.17 186.51 19.47 49.17 15.33
                         
Annual Sum or Average 3785.50 0.79     639.67 18.02 363.83 1853.00 468.30 22.17 1950.67 1217.17
Minimum of Months 226.33 0.78 0.73   376.70 15.75 0.00 58.17 186.51 19.47 49.17 15.33
Maximum of Months 437.50 0.82 0.73   1340.69 20.81 81.67 241.00 990.17 24.82 233.33 175.17



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.455418E+09 2945.85 17-JAN-13:00 0.00 0.00 0.00 0.00 0.00
February 0.686000E+09 4527.48 21-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.101196E+10 4358.87 28-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.360802E+09 3350.70 12-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 48751709.30 3499.49 02-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 56793796.98 4967.55 16-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.703810E+09 5712.70 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.703027E+09 3080.74 06-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.402656E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.101196E+10 5712.70   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.812638E+09 3521.39 15-JAN-20:03 0.00 0.00 0.00 0.00 0.00
February 0.966746E+09 5132.29 21-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.184937E+10 4941.15 28-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.118581E+10 6807.45 18-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.261722E+09 5863.19 15-MAY-05:02 0.00 0.00 0.00 0.00 0.00
June 7610197.26 1115.65 12-JUN-06:08 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 8809198.97 1927.94 21-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.452015E+09 6456.43 31-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.144932E+10 6573.39 01-NOV-05:03 0.00 0.00 0.00 0.00 0.00
December 0.118030E+10 3564.38 05-DEC-18:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.817433E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.184937E+10 6807.45   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.588848E+09 2325.25 29-JAN-12:23 0.00 0.00 0.00 0.00 0.00
February 0.856583E+09 3288.05 21-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.129405E+10 3165.60 28-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.657734E+09 4361.26 18-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 77287320.93 3756.31 15-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 226069.84 406.44 01-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.188879E+09 4136.37 31-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.931216E+09 4211.30 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.786304E+09 2238.92 05-DEC-11:05 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.538113E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.129405E+10 4361.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.833365E+09 2817.20 29-JAN-12:53 0.00 0.00 0.00 0.00 0.00
February 0.139953E+10 4139.71 21-FEB-09:25 0.00 0.00 0.00 0.00 0.00
March 0.228979E+10 3920.35 26-MAR-10:15 0.00 0.00 0.00 0.00 0.00
April 0.158296E+10 5165.67 18-APR-05:13 0.00 0.00 0.00 0.00 0.00
May 0.286429E+09 4739.26 16-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 500839.59 875.47 01-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.473197E+09 4887.35 31-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.168055E+10 4975.89 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.110111E+10 2698.49 05-DEC-19:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.964743E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.228979E+10 5165.67   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.629960E+09 2693.82 16-JAN-09:13 0.00 0.00 0.00 0.00 0.00
February 0.873475E+09 3872.43 21-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.138633E+10 3728.21 28-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.789215E+09 5136.37 18-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.109790E+09 4423.91 15-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 342819.85 847.98 01-JUN-05:05 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.198159E+09 4871.52 31-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.991922E+09 4959.77 01-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.834558E+09 2635.01 06-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.581375E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138633E+10 5136.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.267988E+10 5534.90 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.136110E+10 5534.90 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.619666E+09 5534.90 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 36764886.19 5534.90 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 1976001.79 3632.72 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 320901.37 3270.16 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.101150E+09 5534.90 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.172949E+10 5534.90 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.653035E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.267988E+10 5534.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.479212E+10 8179.38 01-JAN-00:42 0.00 0.00 0.00 0.00 0.00
February 0.272425E+10 8179.38 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.165026E+10 8179.38 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.279998E+09 8179.38 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 23383389.38 5639.06 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 24838738.26 5807.89 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.469972E+09 8179.38 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.371027E+10 8179.38 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.136751E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.479212E+10 8179.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.306671E+10 5025.23 01-JAN-00:06 0.00 0.00 0.00 0.00 0.00
February 0.170485E+10 5025.23 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.919306E+09 5025.23 03-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.100937E+09 5025.23 05-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 6611761.81 4325.52 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 9009600.32 4388.35 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.199220E+09 5025.23 29-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.224902E+10 5025.23 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.825567E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.306671E+10 5025.23   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.560913E+10 8140.77 04-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 0.336335E+10 8140.77 13-FEB-07:02 0.00 0.00 0.00 0.00 0.00
March 0.217036E+10 7896.28 06-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.344222E+09 7068.46 05-APR-06:05 0.00 0.00 0.00 0.00 0.00
May 30725268.69 3928.80 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 24267541.24 4232.92 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.549697E+09 7217.53 29-NOV-07:03 0.00 0.00 0.00 0.00 0.00
December 0.424390E+10 8140.77 20-DEC-07:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163356E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.560913E+10 8140.77   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.300234E+10 5046.17 01-JAN-00:06 0.00 0.00 0.00 0.00 0.00
February 0.167782E+10 5046.17 01-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.882575E+09 5046.17 02-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 84804734.14 5046.17 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 7894929.61 4931.88 01-MAY-05:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 5771745.98 5046.17 30-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.148593E+09 5046.17 06-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.216880E+10 5046.17 01-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.797860E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.300234E+10 5046.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 6803999.73 6803999.73 475.30 13-APR-15:57 475.30 0.00
May 0.00 0.00 0.850799E+09 0.696109E+09 5775.39 26-MAY-05:03 4148.29 0.00
June 0.00 0.00 0.219785E+10 0.167550E+10 5969.62 20-JUN-05:03 3349.84 0.00
July 0.00 0.00 0.297533E+10 0.226251E+10 5993.70 05-JUL-05:03 3616.00 0.00
August 0.00 0.00 0.315828E+10 0.235496E+10 5952.89 09-AUG-05:02 3824.81 0.00
September 0.00 0.00 0.140086E+10 0.115827E+10 5925.99 01-SEP-05:02 3793.82 0.00
October 0.00 0.00 0.172509E+09 0.149270E+09 1505.07 19-OCT-15:57 1294.42 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.107624E+11 0.830341E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.315828E+10 0.235496E+10 5993.70   4148.29 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 36325030.13 36325030.13 1236.34 13-APR-14:55 1236.34 0.00
May 0.00 0.00 0.541826E+09 0.479752E+09 3490.38 25-MAY-14:10 2925.72 0.00
June 0.00 0.00 0.137991E+10 0.109823E+10 6897.42 30-JUN-05:02 3429.13 0.00
July 0.00 0.00 0.224443E+10 0.180103E+10 6701.79 05-JUL-05:03 4024.54 0.00
August 0.00 0.00 0.257335E+10 0.205820E+10 6655.70 09-AUG-05:02 4549.75 0.00
September 0.00 0.00 0.117585E+10 0.109253E+10 6668.26 01-SEP-05:02 4302.34 0.00
October 0.00 0.00 0.283248E+09 0.279126E+09 3677.72 20-OCT-14:00 3677.72 0.00
November 0.00 0.00 7127457.98 7127457.98 841.96 17-NOV-13:20 841.96 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.824207E+10 0.685232E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.257335E+10 0.205820E+10 6897.42   4549.75 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.269963E+09 0.243136E+09 3357.35 18-MAY-10:02 3228.78 0.00
June 0.00 0.00 0.951363E+09 0.805918E+09 4415.49 30-JUN-05:02 2164.10 0.00
July 0.00 0.00 0.148538E+10 0.126202E+10 4284.97 05-JUL-05:03 2552.07 0.00
August 0.00 0.00 0.136776E+10 0.113866E+10 4242.07 09-AUG-05:02 2915.97 0.00
September 0.00 0.00 0.508529E+09 0.471128E+09 4247.46 01-SEP-05:02 2739.41 0.00
October 0.00 0.00 31105902.59 30393428.59 2618.28 20-OCT-10:02 2531.95 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.461410E+10 0.395126E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.148538E+10 0.126202E+10 4415.49   3228.78 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.00 0.00 0.268415E+09 0.224096E+09 2300.19 25-MAY-15:55 1881.70 0.00
June 0.00 0.00 0.105380E+10 0.817789E+09 5209.28 30-JUN-05:02 2556.65 0.00
July 0.00 0.00 0.175559E+10 0.138012E+10 5063.56 05-JUL-05:03 2989.69 0.00
August 0.00 0.00 0.174944E+10 0.134571E+10 5010.44 09-AUG-05:02 3340.01 0.00
September 0.00 0.00 0.469000E+09 0.405857E+09 5020.62 01-SEP-05:02 3202.95 0.00
October 0.00 0.00 5181769.82 5103038.31 459.56 20-OCT-15:37 459.56 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.530143E+10 0.417867E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.175559E+10 0.138012E+10 5209.28   3340.01 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 01-FEB-00:05 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.00 0.00 3033490.71 3033490.71 511.50 13-APR-16:00 511.50 0.00
May 0.00 0.00 0.357924E+09 0.317113E+09 2648.69 25-MAY-15:55 2267.81 0.00
June 0.00 0.00 0.932694E+09 0.759178E+09 5211.60 30-JUN-05:02 2693.80 0.00
July 0.00 0.00 0.147514E+10 0.121365E+10 5060.33 05-JUL-05:03 3130.63 0.00
August 0.00 0.00 0.151639E+10 0.123358E+10 4996.23 09-AUG-05:02 3518.43 0.00
September 0.00 0.00 0.550982E+09 0.501139E+09 4999.95 01-SEP-05:02 3266.13 0.00
October 0.00 0.00 60781895.20 59132419.10 1388.74 19-OCT-15:53 1318.03 0.00
November 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00
                 
Annual Sum or Average 0.00 0.00 0.489695E+10 0.408683E+10       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.151639E+10 0.123358E+10 5211.60   3518.43 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 338.90 816.93 31-JAN-12:20
February 0.00 0.00 01-FEB-00:05 312.53 827.04 24-FEB-12:20
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:05 0.00 0.00 01-DEC-00:05
             
Annual Sum or Average 0.00     52.76    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   338.90 827.04  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.324628E+09 0.37 316.07 01-JAN-00:10 0.97
February 0.281051E+09 0.35 316.07 01-FEB-06:01 0.96
March 0.340220E+09 0.39 316.07 01-MAR-06:01 0.96
April 0.295843E+09 0.35 316.07 03-APR-05:01 0.96
May 0.325428E+09 0.37 316.07 01-MAY-05:01 0.96
June 0.325428E+09 0.38 316.07 01-JUN-05:05 0.95
July 0.295843E+09 0.33 316.07 03-JUL-05:02 0.94
August 0.340220E+09 0.38 316.07 01-AUG-05:02 0.95
September 0.295843E+09 0.34 316.07 01-SEP-05:02 0.94
October 0.310636E+09 0.35 316.07 02-OCT-05:10 0.95
November 0.310636E+09 0.36 316.07 01-NOV-05:01 0.96
December 0.295843E+09 0.34 316.07 01-DEC-06:01 0.95
           
Annual Sum or Average 0.374162E+10 0.36      
Minimum of Months 0.281051E+09 0.33 316.07   0.94
Maximum of Months 0.340220E+09 0.39 316.07   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.554714E+09 0.59 378.94 01-JAN-00:02 0.97
February 0.419676E+09 0.47 378.94 01-FEB-01:40 0.97
March 0.454750E+09 0.44 378.94 01-MAR-06:01 0.96
April 0.359346E+09 0.37 378.94 03-APR-05:01 0.96
May 0.390156E+09 0.37 378.94 01-MAY-05:01 0.96
June 0.390156E+09 0.38 378.94 01-JUN-05:05 0.95
July 0.354687E+09 0.33 378.94 03-JUL-05:02 0.95
August 0.407890E+09 0.38 378.94 01-AUG-05:02 0.95
September 0.354687E+09 0.34 378.94 01-SEP-05:02 0.94
October 0.372421E+09 0.35 378.94 02-OCT-05:10 0.96
November 0.392577E+09 0.40 378.94 01-NOV-05:01 0.96
December 0.491512E+09 0.51 378.94 01-DEC-06:01 0.96
           
Annual Sum or Average 0.494257E+10 0.41      
Minimum of Months 0.354687E+09 0.33 378.94   0.94
Maximum of Months 0.554714E+09 0.59 378.94   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.434459E+09 0.67 264.95 01-JAN-00:06 0.97
February 0.330486E+09 0.60 264.95 01-FEB-00:05 0.96
March 0.311049E+09 0.51 264.95 01-MAR-06:01 0.96
April 0.205263E+09 0.34 264.95 03-APR-03:53 0.96
May 0.212772E+09 0.31 264.95 01-MAY-05:01 0.96
June 0.222201E+09 0.37 264.95 01-JUN-05:05 0.95
July 0.212002E+09 0.34 264.95 03-JUL-05:02 0.95
August 0.238484E+09 0.39 264.95 01-AUG-05:02 0.95
September 0.198522E+09 0.32 264.95 01-SEP-05:02 0.94
October 0.200543E+09 0.28 264.95 02-OCT-05:10 0.96
November 0.237431E+09 0.39 264.95 01-NOV-05:01 0.96
December 0.381821E+09 0.58 264.95 01-DEC-06:01 0.96
           
Annual Sum or Average 0.318503E+10 0.42      
Minimum of Months 0.198522E+09 0.28 264.95   0.94
Maximum of Months 0.434459E+09 0.67 264.95   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.454896E+09 0.66 271.32 01-JAN-00:06 0.97
February 0.368092E+09 0.60 271.32 01-FEB-00:05 0.96
March 0.368915E+09 0.53 271.32 01-MAR-06:01 0.96
April 0.266379E+09 0.39 271.32 02-APR-03:15 0.96
May 0.279616E+09 0.37 271.32 01-MAY-05:01 0.96
June 0.279352E+09 0.38 271.32 01-JUN-05:05 0.95
July 0.253956E+09 0.33 271.32 03-JUL-05:02 0.95
August 0.292050E+09 0.38 271.32 01-AUG-05:02 0.95
September 0.253956E+09 0.34 271.32 01-SEP-05:02 0.94
October 0.266654E+09 0.35 271.32 02-OCT-05:10 0.96
November 0.294857E+09 0.43 271.32 01-NOV-05:01 0.96
December 0.406263E+09 0.57 271.32 01-DEC-06:01 0.96
           
Annual Sum or Average 0.378499E+10 0.44      
Minimum of Months 0.253956E+09 0.33 271.32   0.94
Maximum of Months 0.454896E+09 0.66 271.32   0.97



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.510439E+09 0.65 312.03 01-JAN-00:06 0.97
February 0.398771E+09 0.59 312.03 01-FEB-00:15 0.96
March 0.400190E+09 0.51 312.03 01-MAR-06:01 0.96
April 0.299784E+09 0.39 312.03 02-APR-09:12 0.96
May 0.321403E+09 0.37 312.03 01-MAY-05:01 0.96
June 0.321270E+09 0.38 312.03 01-JUN-05:05 0.95
July 0.292063E+09 0.33 312.03 03-JUL-05:02 0.95
August 0.335873E+09 0.38 312.03 01-AUG-05:02 0.95
September 0.292063E+09 0.34 312.03 01-SEP-05:02 0.94
October 0.306667E+09 0.35 312.03 02-OCT-05:10 0.96
November 0.331993E+09 0.42 312.03 01-NOV-05:01 0.96
December 0.452291E+09 0.57 312.03 01-DEC-06:01 0.96
           
Annual Sum or Average 0.426281E+10 0.44      
Minimum of Months 0.292063E+09 0.33 312.03   0.94
Maximum of Months 0.510439E+09 0.65 312.03   0.97



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.02 0.01 0.00 02-JAN-07:02 0.00 0.00 39.80 0.00
February 0.02 0.00 0.00 01-FEB-07:02 0.00 0.00 0.98 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 0.42 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.42 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.42 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.42 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.42 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.42 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.42 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.42 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.42 0.00
December 0.00 0.00 0.00 01-DEC-00:05 0.00 0.00 0.42 0.00
                 
Annual Sum or Average 0.04 0.01            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.42 0.00
Maximum of Months 0.02 0.01 0.00   0.00 0.00 39.80 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 48.89 48.89 338.90 816.93 31-JAN-12:20
February 0.00 0.00 01-FEB-00:05 0.99 0.99 312.53 827.04 24-FEB-12:20
March 0.00 0.00 01-MAR-00:10 0.42 0.42 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.42 0.42 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.42 0.42 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.42 0.42 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:10 0.42 0.42 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:10 0.42 0.42 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.42 0.42 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.42 0.42 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.42 0.42 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:05 0.42 0.42 0.00 0.00 01-DEC-00:05
                 
Annual Sum or Average 0.00         52.76    
Minimum of Months 0.00 0.00   0.42 0.42 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 338.90 827.04  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.625635E+09 0.00 0.00
February 0.00 0.00 0.00 0.652163E+09 0.00 0.00
March 0.00 0.00 0.00 0.916963E+09 0.00 0.00
April 0.00 0.00 0.00 0.485016E+09 0.00 0.00
May 0.00 0.00 0.00 0.536466E+09 0.00 0.00
June 0.00 0.00 0.00 0.805260E+09 0.00 0.00
July 0.00 0.00 0.00 0.928352E+09 0.00 0.00
August 0.00 0.00 0.00 0.100762E+10 0.00 0.00
September 0.00 0.00 0.00 0.599279E+09 0.00 0.00
October 0.00 0.00 0.00 0.390748E+09 0.00 0.00
November 0.00 0.00 0.00 0.705192E+09 0.00 0.00
December 0.00 0.00 0.00 0.747770E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.840047E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.390748E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.100762E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.108176E+10 0.00 0.00
February 0.00 0.00 0.00 0.948881E+09 0.00 0.00
March 0.00 0.00 0.00 0.143604E+10 0.00 0.00
April 0.00 0.00 0.00 0.903946E+09 0.00 0.00
May 0.00 0.00 0.00 0.608828E+09 0.00 0.00
June 0.00 0.00 0.00 0.705202E+09 0.00 0.00
July 0.00 0.00 0.00 0.848480E+09 0.00 0.00
August 0.00 0.00 0.00 0.963341E+09 0.00 0.00
September 0.00 0.00 0.00 0.610135E+09 0.00 0.00
October 0.00 0.00 0.00 0.644556E+09 0.00 0.00
November 0.00 0.00 0.00 0.112346E+10 0.00 0.00
December 0.00 0.00 0.00 0.122812E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.111028E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.608828E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.143604E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.844051E+09 0.00 0.00
February 0.00 0.00 0.00 0.808609E+09 0.00 0.00
March 0.00 0.00 0.00 0.101082E+10 0.00 0.00
April 0.00 0.00 0.00 0.518796E+09 0.00 0.00
May 0.00 0.00 0.00 0.305189E+09 0.00 0.00
June 0.00 0.00 0.00 0.437605E+09 0.00 0.00
July 0.00 0.00 0.00 0.538499E+09 0.00 0.00
August 0.00 0.00 0.00 0.538623E+09 0.00 0.00
September 0.00 0.00 0.00 0.311161E+09 0.00 0.00
October 0.00 0.00 0.00 0.302153E+09 0.00 0.00
November 0.00 0.00 0.00 0.720603E+09 0.00 0.00
December 0.00 0.00 0.00 0.899978E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.723609E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.302153E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.101082E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.989619E+09 0.00 0.00
February 0.00 0.00 0.00 0.107370E+10 0.00 0.00
March 0.00 0.00 0.00 0.150377E+10 0.00 0.00
April 0.00 0.00 0.00 0.924422E+09 0.00 0.00
May 0.00 0.00 0.00 0.442280E+09 0.00 0.00
June 0.00 0.00 0.00 0.517317E+09 0.00 0.00
July 0.00 0.00 0.00 0.639627E+09 0.00 0.00
August 0.00 0.00 0.00 0.673528E+09 0.00 0.00
September 0.00 0.00 0.00 0.358479E+09 0.00 0.00
October 0.00 0.00 0.00 0.480491E+09 0.00 0.00
November 0.00 0.00 0.00 0.109547E+10 0.00 0.00
December 0.00 0.00 0.00 0.108946E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.978817E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.358479E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.150377E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.946513E+09 0.00 0.00
February 0.00 0.00 0.00 0.896003E+09 0.00 0.00
March 0.00 0.00 0.00 0.116183E+10 0.00 0.00
April 0.00 0.00 0.00 0.672513E+09 0.00 0.00
May 0.00 0.00 0.00 0.446516E+09 0.00 0.00
June 0.00 0.00 0.00 0.535448E+09 0.00 0.00
July 0.00 0.00 0.00 0.621638E+09 0.00 0.00
August 0.00 0.00 0.00 0.671330E+09 0.00 0.00
September 0.00 0.00 0.00 0.415041E+09 0.00 0.00
October 0.00 0.00 0.00 0.423456E+09 0.00 0.00
November 0.00 0.00 0.00 0.858355E+09 0.00 0.00
December 0.00 0.00 0.00 0.100581E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.865445E+10 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.415041E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.116183E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.324628E+09 0.00 0.313529E+10 0.00 0.00 0.00 0.00 0.00
February 0.281051E+09 0.00 0.204710E+10 0.00 0.00 0.00 0.00 0.00
March 0.340220E+09 0.00 0.163162E+10 0.00 0.00 0.00 0.00 0.00
April 0.295843E+09 6803999.73 0.397567E+09 0.00 0.00 0.00 0.00 0.00
May 0.325428E+09 0.850799E+09 50727711.09 0.00 0.00 0.00 0.00 0.00
June 0.325428E+09 0.219785E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.295843E+09 0.297533E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.340220E+09 0.315828E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.295843E+09 0.140086E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.310636E+09 0.172509E+09 57114698.35 0.00 0.00 0.00 0.00 0.00
November 0.310636E+09 0.00 0.804960E+09 0.00 0.00 0.00 0.00 0.00
December 0.295843E+09 0.00 0.243252E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.374162E+10 0.107624E+11 0.105569E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.281051E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.340220E+09 0.315828E+10 0.313529E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.554714E+09 0.00 0.560476E+10 0.00 0.00 0.00 0.00 0.00
February 0.419676E+09 0.00 0.369100E+10 0.00 0.00 0.00 0.00 0.00
March 0.454750E+09 0.00 0.349963E+10 0.00 0.00 0.00 0.00 0.00
April 0.359346E+09 36325030.13 0.146581E+10 0.00 0.00 0.00 0.00 0.00
May 0.390156E+09 0.541826E+09 0.285106E+09 0.00 0.00 0.00 0.00 0.00
June 0.390156E+09 0.137991E+10 7610197.26 0.00 0.00 0.00 0.00 0.00
July 0.354687E+09 0.224443E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.407890E+09 0.257335E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.354687E+09 0.117585E+10 8809198.97 0.00 0.00 0.00 0.00 0.00
October 0.372421E+09 0.283248E+09 0.476854E+09 0.00 0.00 0.00 0.00 0.00
November 0.392577E+09 7127457.98 0.191929E+10 0.00 0.00 0.00 0.00 0.00
December 0.491512E+09 0.00 0.489057E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.494257E+10 0.824207E+10 0.218494E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.354687E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.554714E+09 0.257335E+10 0.560476E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.434459E+09 0.00 0.365556E+10 0.00 0.00 0.00 0.00 0.00
February 0.330486E+09 0.00 0.256143E+10 0.00 0.00 0.00 0.00 0.00
March 0.311049E+09 0.00 0.221336E+10 0.00 0.00 0.00 0.00 0.00
April 0.205263E+09 0.00 0.758672E+09 0.00 0.00 0.00 0.00 0.00
May 0.212772E+09 0.269963E+09 83899082.74 0.00 0.00 0.00 0.00 0.00
June 0.222201E+09 0.951363E+09 226069.84 0.00 0.00 0.00 0.00 0.00
July 0.212002E+09 0.148538E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.238484E+09 0.136776E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.198522E+09 0.508529E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.200543E+09 31105902.59 0.197889E+09 0.00 0.00 0.00 0.00 0.00
November 0.237431E+09 0.00 0.113044E+10 0.00 0.00 0.00 0.00 0.00
December 0.381821E+09 0.00 0.303532E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.318503E+10 0.461410E+10 0.136368E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.198522E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.434459E+09 0.148538E+10 0.365556E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.454896E+09 0.00 0.644249E+10 0.00 0.00 0.00 0.00 0.00
February 0.368092E+09 0.00 0.476289E+10 0.00 0.00 0.00 0.00 0.00
March 0.368915E+09 0.00 0.446015E+10 0.00 0.00 0.00 0.00 0.00
April 0.266379E+09 0.00 0.192718E+10 0.00 0.00 0.00 0.00 0.00
May 0.279616E+09 0.268415E+09 0.317154E+09 0.00 0.00 0.00 0.00 0.00
June 0.279352E+09 0.105380E+10 500839.59 0.00 0.00 0.00 0.00 0.00
July 0.253956E+09 0.175559E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.292050E+09 0.174944E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.253956E+09 0.469000E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.266654E+09 5181769.82 0.497465E+09 0.00 0.00 0.00 0.00 0.00
November 0.294857E+09 0.00 0.223025E+10 0.00 0.00 0.00 0.00 0.00
December 0.406263E+09 0.00 0.534501E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.378499E+10 0.530143E+10 0.259831E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.253956E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.454896E+09 0.175559E+10 0.644249E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.510439E+09 0.00 0.363230E+10 0.00 0.00 0.00 0.00 0.00
February 0.398771E+09 0.00 0.255130E+10 0.00 0.00 0.00 0.00 0.00
March 0.400190E+09 0.00 0.226890E+10 0.00 0.00 0.00 0.00 0.00
April 0.299784E+09 3033490.71 0.874020E+09 0.00 0.00 0.00 0.00 0.00
May 0.321403E+09 0.357924E+09 0.117685E+09 0.00 0.00 0.00 0.00 0.00
June 0.321270E+09 0.932694E+09 342819.85 0.00 0.00 0.00 0.00 0.00
July 0.292063E+09 0.147514E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.335873E+09 0.151639E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.292063E+09 0.550982E+09 0.00 0.00 0.00 0.00 0.00 0.00
October 0.306667E+09 60781895.20 0.203931E+09 0.00 0.00 0.00 0.00 0.00
November 0.331993E+09 0.00 0.114051E+10 0.00 0.00 0.00 0.00 0.00
December 0.452291E+09 0.00 0.300336E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.426281E+10 0.489695E+10 0.137923E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.292063E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.510439E+09 0.151639E+10 0.363230E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.324628E+09 0.00 0.00 0.301007E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.281051E+09 0.00 0.00 0.371112E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.340220E+09 0.00 0.00 0.576743E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.295843E+09 0.00 0.00 0.187623E+09 1550039.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.325428E+09 0.00 0.00 20860524.71 0.190178E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.325428E+09 0.00 0.00 0.00 0.479832E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.295843E+09 0.00 0.00 0.00 0.632509E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.340220E+09 0.00 0.00 0.00 0.667404E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.295843E+09 0.00 0.00 576059.15 0.302860E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.310636E+09 0.00 0.00 41342104.13 38770023.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.310636E+09 0.00 0.00 0.394557E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.295843E+09 0.00 0.00 0.451926E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.374162E+10 0.00 0.00 0.234575E+10 0.231310E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.281051E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.340220E+09 0.00 0.00 0.576743E+09 0.667404E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.554714E+09 0.00 0.00 0.527044E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.419676E+09 0.00 0.00 0.529205E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.454750E+09 0.00 0.00 0.981291E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.359346E+09 0.00 0.00 0.536423E+09 8176906.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.390156E+09 0.00 0.00 93955409.94 0.124717E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.390156E+09 0.00 0.00 2466617.94 0.312579E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.354687E+09 0.00 0.00 0.00 0.493793E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.407890E+09 0.00 0.00 0.00 0.555451E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.354687E+09 0.00 0.00 3832599.27 0.251616E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.372421E+09 0.00 0.00 0.210643E+09 61491690.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.392577E+09 0.00 0.00 0.729277E+09 1606479.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.491512E+09 0.00 0.00 0.736610E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.494257E+10 0.00 0.00 0.435075E+10 0.180943E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.354687E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.554714E+09 0.00 0.00 0.981291E+09 0.555451E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.434459E+09 0.00 0.00 0.409592E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.330486E+09 0.00 0.00 0.478123E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.311049E+09 0.00 0.00 0.699771E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.205263E+09 0.00 0.00 0.313534E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.212772E+09 0.00 0.00 30025023.73 62392328.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.222201E+09 0.00 0.00 72234.56 0.215332E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.212002E+09 0.00 0.00 0.00 0.326497E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.238484E+09 0.00 0.00 0.00 0.300139E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.198522E+09 0.00 0.00 741582.35 0.111897E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.200543E+09 0.00 0.00 94605475.65 7004918.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.237431E+09 0.00 0.00 0.483173E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.381821E+09 0.00 0.00 0.518157E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.318503E+10 0.00 0.00 0.302779E+10 0.102326E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.198522E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.434459E+09 0.00 0.00 0.699771E+09 0.326497E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.454896E+09 0.00 0.00 0.534722E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.368092E+09 0.00 0.00 0.705607E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.368915E+09 0.00 0.00 0.113486E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.266379E+09 0.00 0.00 0.658043E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.279616E+09 0.00 0.00 0.100401E+09 62262598.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.279352E+09 0.00 0.00 159035.02 0.237806E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.253956E+09 0.00 0.00 0.00 0.385670E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.292050E+09 0.00 0.00 0.00 0.381478E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.253956E+09 0.00 0.00 750000.00 0.103773E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.266654E+09 0.00 0.00 0.212653E+09 1183438.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.294857E+09 0.00 0.00 0.800615E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.406263E+09 0.00 0.00 0.683197E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.378499E+10 0.00 0.00 0.483100E+10 0.117217E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.253956E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.454896E+09 0.00 0.00 0.113486E+10 0.385670E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.510439E+09 0.00 0.00 0.436075E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.398771E+09 0.00 0.00 0.497232E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.400190E+09 0.00 0.00 0.761637E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.299784E+09 0.00 0.00 0.372039E+09 690026.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.321403E+09 0.00 0.00 42148870.00 82964309.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.321270E+09 0.00 0.00 107874.23 0.214071E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.292063E+09 0.00 0.00 0.00 0.329575E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.335873E+09 0.00 0.00 0.00 0.335457E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.292063E+09 0.00 0.00 723710.78 0.122254E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.306667E+09 0.00 0.00 0.103105E+09 13683629.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.331993E+09 0.00 0.00 0.526362E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.452291E+09 0.00 0.00 0.553515E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.426281E+10 0.00 0.00 0.329295E+10 0.109869E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.292063E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.510439E+09 0.00 0.00 0.761637E+09 0.335457E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103395E+10 0.00 0.00 0.00 0.00 0.209846E+10 0.00 0.00 0.17
February 0.114526E+10 0.00 0.00 0.00 0.00 0.128536E+10 0.00 0.00 0.17
March 0.152705E+10 0.00 0.00 0.00 0.00 0.960470E+09 0.00 0.00 0.19
April 0.129866E+10 0.00 0.00 45055.83 0.00 0.221223E+09 35144388.20 0.00 0.17
May 0.501922E+09 9690518.95 0.00 2325631.50 883416.88 31888932.14 0.439921E+09 0.00 0.19
June 64153284.13 0.169959E+09 0.00 4445968.28 11937702.46 0.00 0.428611E+09 0.00 0.19
July 12551566.64 0.196095E+09 0.00 4675321.95 13647193.44 0.00 0.170993E+09 0.00 0.17
August 18442262.93 0.149077E+09 0.00 5576891.81 14433557.52 0.00 0.293350E+09 0.00 0.19
September 0.123937E+09 3134967.11 0.00 5256322.58 138277.67 0.00 0.886845E+09 0.00 0.17
October 0.111472E+10 0.00 0.00 1182813.59 0.00 10541965.28 0.543719E+09 0.00 0.18
November 0.144348E+10 0.00 0.00 0.00 0.00 0.501054E+09 0.00 0.00 0.18
December 0.125463E+10 0.00 0.00 0.00 0.00 0.151749E+10 0.00 0.00 0.16
                   
Annual Sum or Average 0.953875E+10 0.527955E+09 0.00 23508005.54 41040147.98 0.662650E+10 0.279858E+10 0.00 0.18
Minimum of Months 12551566.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16
Maximum of Months 0.152705E+10 0.196095E+09 0.00 5576891.81 14433557.52 0.209846E+10 0.886845E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.139746E+09 0.00 0.00 0.00 0.00 0.192314E+10 0.00 0.00 0.17
February 0.209516E+09 0.00 0.00 0.00 0.00 0.135320E+10 0.00 0.00 0.17
March 0.210300E+09 0.00 0.00 0.00 0.00 0.133740E+10 0.00 0.00 0.19
April 0.328437E+09 0.00 0.00 129252.95 0.00 0.501638E+09 49942636.33 0.00 0.17
May 0.279245E+09 19507692.44 0.00 565199.45 1759812.15 0.105940E+09 60537203.08 0.00 0.18
June 0.115916E+09 0.132190E+09 0.00 1635520.45 9367530.07 8228857.63 0.128680E+09 0.00 0.19
July 28667580.35 0.167091E+09 0.00 2642521.55 10966537.47 0.00 78938998.53 0.00 0.17
August 50620698.30 0.146161E+09 0.00 3318988.40 10807020.05 0.00 0.146988E+09 0.00 0.19
September 0.238000E+09 7514691.55 0.00 3999344.98 245010.27 9088506.88 0.325775E+09 0.00 0.17
October 0.538243E+09 0.00 0.00 1259642.43 0.00 0.219702E+09 0.164673E+09 0.00 0.17
November 0.436547E+09 0.00 0.00 39927.94 0.00 0.712832E+09 15557783.18 0.00 0.18
December 89264526.20 0.00 0.00 0.00 0.00 0.170981E+10 0.00 0.00 0.16
                   
Annual Sum or Average 0.266450E+10 0.472464E+09 0.00 13590398.15 33145910.01 0.788099E+10 0.971093E+09 0.00 0.18
Minimum of Months 28667580.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16
Maximum of Months 0.538243E+09 0.167091E+09 0.00 3999344.98 10966537.47 0.192314E+10 0.325775E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.120967E+10 0.00 0.00 0.17
February 1145694.60 0.00 0.00 0.00 0.00 0.877187E+09 0.00 0.00 0.16
March 15771194.04 0.00 0.00 0.00 0.00 0.797198E+09 0.00 0.00 0.16
April 0.124067E+09 0.00 0.00 0.00 0.00 0.290532E+09 0.00 0.00 0.13
May 0.141066E+09 10227433.75 0.00 510135.42 1017063.82 38385614.05 31597633.32 0.00 0.14
June 27877657.30 78942630.53 0.00 1837975.06 7281221.66 0.00 90203313.21 0.00 0.15
July 4026608.56 0.106391E+09 0.00 2167023.38 8874493.93 0.00 37042718.08 0.00 0.14
August 8441947.23 84861457.11 0.00 2023098.89 9598942.34 0.00 77189770.81 0.00 0.16
September 0.104707E+09 3955701.24 0.00 1921848.33 268810.61 0.00 0.173016E+09 0.00 0.14
October 0.263487E+09 0.00 0.00 151542.61 0.00 0.115180E+09 42962757.80 0.00 0.13
November 0.103989E+09 0.00 0.00 0.00 0.00 0.464585E+09 0.00 0.00 0.14
December 0.00 0.00 0.00 0.00 0.00 0.103585E+10 0.00 0.00 0.16
                   
Annual Sum or Average 0.794579E+09 0.284378E+09 0.00 8611623.69 27040532.35 0.482859E+10 0.452012E+09 0.00 0.15
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.13
Maximum of Months 0.263487E+09 0.106391E+09 0.00 2167023.38 9598942.34 0.120967E+10 0.173016E+09 0.00 0.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.00 0.00 0.211529E+10 0.00 0.00 0.17
February 0.00 0.00 0.00 0.00 0.00 0.160133E+10 0.00 0.00 0.17
March 0.00 0.00 0.00 0.00 0.00 0.158936E+10 0.00 0.00 0.19
April 82036410.14 0.00 0.00 0.00 0.00 0.803603E+09 0.00 0.00 0.17
May 0.304214E+09 12403178.48 0.00 294279.85 1349488.23 0.129194E+09 30316468.33 0.00 0.18
June 0.142621E+09 0.133266E+09 0.00 1326360.54 11105039.63 0.00 0.140713E+09 0.00 0.19
July 11645358.87 0.168665E+09 0.00 2402604.27 13522567.98 0.00 0.100382E+09 0.00 0.17
August 24379121.20 0.131871E+09 0.00 2765885.58 14414839.18 0.00 0.186371E+09 0.00 0.19
September 0.315626E+09 4546173.38 0.00 1587496.72 388297.30 0.00 0.301780E+09 0.00 0.17
October 0.654552E+09 0.00 0.00 17357.33 0.00 0.271175E+09 9300588.20 0.00 0.17
November 0.154039E+09 0.00 0.00 0.00 0.00 0.103355E+10 0.00 0.00 0.18
December 0.00 0.00 0.00 0.00 0.00 0.184401E+10 0.00 0.00 0.16
                   
Annual Sum or Average 0.168911E+10 0.450752E+09 0.00 8393984.28 40780232.33 0.938752E+10 0.768863E+09 0.00 0.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16
Maximum of Months 0.654552E+09 0.168665E+09 0.00 2765885.58 14414839.18 0.211529E+10 0.301780E+09 0.00 0.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 1549167.59 0.00 0.00 0.00 0.00 0.125271E+10 0.00 0.00 0.17
February 18449019.18 0.00 0.00 0.00 0.00 0.930458E+09 0.00 0.00 0.17
March 50052979.28 0.00 0.00 0.00 0.00 0.891275E+09 0.00 0.00 0.19
April 0.151904E+09 0.00 0.00 8587.13 0.00 0.378588E+09 4409643.64 0.00 0.17
May 0.192433E+09 11674551.59 0.00 408226.04 840159.96 51296506.80 38910234.27 0.00 0.18
June 59349312.57 89102897.39 0.00 1104012.21 7251651.08 0.00 0.100585E+09 0.00 0.19
July 5447586.38 0.115292E+09 0.00 1739384.31 8799044.15 0.00 53230349.73 0.00 0.17
August 8273430.28 91811594.53 0.00 1949976.64 9644973.83 0.00 0.102041E+09 0.00 0.19
September 0.130838E+09 3410179.46 0.00 1691345.80 220222.49 0.00 0.234833E+09 0.00 0.17
October 0.362044E+09 0.00 0.00 250438.66 0.00 0.138369E+09 70112917.14 0.00 0.17
November 0.137090E+09 0.00 0.00 0.00 0.00 0.565852E+09 0.00 0.00 0.18
December 0.00 0.00 0.00 0.00 0.00 0.109183E+10 0.00 0.00 0.16
                   
Annual Sum or Average 0.111743E+10 0.311291E+09 0.00 7151970.80 26756051.50 0.530038E+10 0.604123E+09 0.00 0.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16
Maximum of Months 0.362044E+09 0.115292E+09 0.00 1949976.64 9644973.83 0.125271E+10 0.234833E+09 0.00 0.19



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:27:22

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.205709E+11 0.377049E+10 0.00 0.977920E+10 -0.105530E+19
February 0.411005E+11 0.377934E+10 0.00 0.742895E+10 -0.964100E+18
March 0.668625E+11 0.420949E+10 0.00 0.740827E+10 -0.104970E+19
April 0.933852E+11 0.414701E+10 0.00 0.434406E+10 -0.985900E+18
May 0.115244E+12 0.433672E+10 0.00 0.236907E+10 -0.996300E+18
June 0.120276E+12 0.341773E+10 0.00 0.676084E+09 -0.103550E+19
July 0.123395E+12 0.286976E+10 0.00 -293327793.3 -0.112560E+19
August 0.100851E+12 0.267886E+10 0.00 0.270308E+09 -0.100210E+19
September 0.704695E+11 0.257437E+10 0.00 0.287905E+10 -0.835200E+18
October 0.346326E+11 0.200065E+10 0.00 0.465125E+10 -0.766000E+18
November 0.105632E+11 0.214649E+10 0.00 0.563667E+10 -0.700400E+18
December 0.101432E+11 0.350903E+10 0.00 0.854868E+10 -0.954500E+18
           
Annual Sum or Average 0.807494E+12 0.394399E+11 0.00 0.536983E+11 -0.114706E+20
Minimum of Months 0.101432E+11 0.200065E+10 0.00 -293327793.3 -0.112560E+19
Maximum of Months 0.123395E+12 0.433672E+10 0.00 0.977920E+10 -0.700400E+18