Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 08:26:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1541.53 | 6634.73 | 6634.73 |
Net Site Energy | 1541.53 | 6634.73 | 6634.73 |
Total Source Energy | 2581.16 | 11109.28 | 11109.28 |
Net Source Energy | 2581.16 | 11109.28 | 11109.28 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 398.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 57.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 228.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 50.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 436.94 | 1104.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 398.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 57.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 228.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 398.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 24.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 57.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 228.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 50.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 348.14 | 2700.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1360.98 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1880.57 | 4754.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 348.14 | 2700.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1360.98 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1880.57 | 4754.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 436.937 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 436.937 | 100.00 |
Total On-Site and Utility Electric Sources | 436.937 | 100.00 |
Total Electricity End Uses | 436.937 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.50 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3514.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.1446 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9598 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.1446 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9598 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.5522 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 17-JUL-12:00 | 10-JAN-20:40 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 122671.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 13499.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 12274.30 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3199.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 14204.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1687.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31726.58 | 155262.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 122671.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 13499.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 11246.80 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3199.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 14204.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 442.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1050.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 432.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 72.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 76.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 841.99 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 183.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 248.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 159.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1383.78 | 1197.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1859.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 313.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 330.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 788.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1067.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 686.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5955.77 | 5153.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1859.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 313.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 330.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 212.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 788.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1067.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 686.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5955.77 | 5153.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.97 |
KITCHEN DIRECT AIR | 1.36 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.97 | 1.97 | 1.97 | 1.97 | 1.97 | 1.97 | 1.00 | 1.00 | 1.97 |
PSZ-AC_2:2 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.97 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.36 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.97 | 2113.25 |
PSZ-AC_2:2_ADDAQ FAN | 1.36 | 1508.18 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.97 | 1.97 | 1.97 | 1.30 | 34212.85 | 61106.79 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 0.899058 | 28902.52 | 87857.13 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.97 | 0.987457 | 1.32 | 34212.85 | 17106.42 | 0.800310 | 0.800310 |
PSZ-AC_2:2 COOLING COIL | 1.36 | 0.681105 | 0.908140 | 28902.52 | 14451.26 | 0.753840 | 0.753840 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 61106.79 |
PSZ-AC_2:2 HEATING COIL | 87857.13 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.145 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.932 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.960 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.039 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 829.995 | 7.145 | 9.481 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 829.995 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1157.049 | 9.960 | 184.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1157.049 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4391 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.043 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.38584905E-12 | 0.75146531E-15 | -0.12966877E-12 | 0.12247089E-15 |
34 | 6 | 0.32626755E-07 | 0.12794687E-09 | 0.74410738E-08 | -0.15657130E-12 |
35 | 5 | -0.20999199E-03 | 0.10694986E-05 | -0.10771460E-03 | 0.73422529E-08 |
36 | 4 | 0.31512205 | 0.50965885E-03 | 0.10796022 | -0.36842960E-04 |
37 | 3 | -7.7206601 | 0.15495837E-01 | -2.4737779 | 0.31237450E-01 |
38 | 2 | 42.368774 | 0.54174396E-01 | 15.816616 | -0.35002435 |
39 | 1 | -81.692611 | 0.24088120E-01 | -29.635684 | 1.1030598 |
40 | 0 | 46.824332 | 0.47759164E-03 | 16.279740 | |
41 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
42 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
43 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
44 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
45 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
46 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
47 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
48 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 | |
49 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
50 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
51 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
52 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
53 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
54 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
55 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
56 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.36_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.36_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.9740E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.2387E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.8073E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.0469E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.4140E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.3877E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7272E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7316E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.6186E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.4780E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 0.1011 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.9515E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.0474E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.9565E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.8733E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.8734E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8810E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.5059E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.5937E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.1979E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9443E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0315E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7318E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7272E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 19549.83020 | 23459.79624 | 1.64576 | 1.97491 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 7451.85476 | 8942.22572 | 0.36306 | 0.43567 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -27.60000 | 3.41898E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16181.80950 | 19418.17140 | 1.13517 | 1.36221 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 826.88986 | 992.26784 | 3.64710E-002 | 1.14133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60000 | 3.41898E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 27351.17 | 1.97491 | 1.97491 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 30158.27 | 0.43567 | 0.43567 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26239.76 | 1.36221 | 1.36221 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 81648.89 | 1.14133 | 1.14133 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.97491 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36221 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.97491 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.97491 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.97491 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.97491 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.97491 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.97491 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36221 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36221 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36221 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36221 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36221 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36221 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.97491 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.36221 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.97491 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.97491 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2113.25082 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.97491 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.97491 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.97491 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30344 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.97491 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98746 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.31661 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34212.85000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17106.42500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80031 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80031 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34212.85000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 61106.78819 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 61106.78819 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36221 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36221 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1508.18251 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36221 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36221 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36221 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.89906 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36221 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68110 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.90814 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28902.52000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14451.26000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75384 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75384 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28902.52000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 87857.13215 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 87857.13215 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 32771.8 | 11.11 | 11.06 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 27921.9 | 11.55 | 11.49 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 8.8715425808E-002 | 0.3553459222 | Pass | Pass | 0.6322341559 | 2.8164552045 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1791123267 | 0.6690754886 | Pass | Pass | 2.9958309483E-002 | 0.1003622186 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.3051662464 | 0.3428657863 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 474.58 | 139.95 | 1082.70 | 9.05 | 440.71 | 2146.99 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.045 | 0.401 | 0.442 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.045 | 0.401 | 0.442 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.045 | 0.401 | 0.442 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.045 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.1446 | 116.17 | 830.00 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.04 | 0.0000 | Y | 6.71 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9598 | 116.17 | 1157.05 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.51 |
Interior Lighting Total | 8.5522 | 232.34 | 1987.04 | 24.21 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 49.11 | 49.11 | 2.01 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.57 | 62.84 | 13.61 | |
Exterior Lighting Total | 1372.31 | 15.62 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34212.85 | 27380.89 | 6831.96 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28902.52 | 21787.88 | 7114.64 | 0.75 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 32771.8 | 11.11 | 11.06 | ||||
PSZ-AC_2:2 COOLING COIL | 27921.9 | 11.55 | 11.49 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 61106.79 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 87857.13 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.97 | 2113.25 | 1070.05 | 1.00 | 1.32 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1508.18 | 1107.16 | 1.00 | 1.33 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 19549.83 | 23459.80 | 201.94 | 1.646 | 1.975 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.88 | 0.00772 | 33.40 | 0.00631 | 0.416 | 0.00 |
KITCHEN | 16181.81 | 19418.17 | 167.15 | 1.135 | 1.362 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00869 | 31.96 | 0.00630 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7451.85 | 8942.23 | 76.97 | 0.363 | 0.436 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00780 | -27.60 | 0.00034 | 0.416 | 0.00 |
KITCHEN | 826.89 | 992.27 | 8.54 | 0.036 | 1.141 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 18.89 | 18.89 | 0.00483 | -27.60 | 0.00034 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.97 | 1.97 | 0.44 | 0.44 | 1.9749 | 1.9749 | 1.9749 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.36 | 1.36 | 1.14 | 1.14 | 1.3622 | 1.3622 | 1.3622 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34212.850 | 27380.886 | 1.974910 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 17106.42 | 16201.87 | 1.316607 | 25.89 | 14.77 | 0.00742622 | 11.80 | 8.99 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 31.6006 | 23.88 | 0.00772499 | 36.6719 | 19549.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 61106.788 | 61106.788 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 61106.79 | 61106.79 | 1.974914 | 10.76 | 7.72 | 0.00623110 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 21.0671 | 21.11 | 0.00780291 | 43.8361 | 7451.85 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 28902.520 | 21787.876 | 1.362210 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 14451.26 | 14451.26 | 0.908140 | 31.00 | 15.89 | 0.00669217 | 11.77 | 8.65 | 0.00669217 | 31.96 | 0.00630459 | 15.89 | 125.6781 | 26.10 | 0.00869490 | 36.1158 | 16181.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 87857.132 | 87857.132 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:10:00 | 87857.13 | 87857.13 | 1.362210 | -20.95 | -20.95 | 0.00094777 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 83.7854 | 18.89 | 0.00407851 | 26.4460 | 164.20 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34212.850 | 27380.886 | 1.974910 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6450 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.974914 | 2.07986018 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 17106.42 | 16201.87 | 1.0000 | 1.38657099 | 1.316607 | 25.89 | 14.77 | 0.00742622 | 44942.1 | 11.80 | 8.99 | 0.00700000 | 29519.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17106.42 | 33.40 | 0.00630683 | 16.37 | 0.41605618 | 31.6006 | 23.88 | 0.00772499 | 23.88 | 0.00772499 | 36.6719 | 19549.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 61106.788 | 61106.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.974914 | 2.07986018 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 61106.79 | 61106.79 | 1.0000 | 2.07986018 | 1.974914 | 10.76 | 7.72 | 0.00623110 | 26522.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 61106.79 | -27.60 | 0.00034190 | -27.60 | 0.41605618 | 21.0671 | 21.00 | 0.00780291 | 21.11 | 0.00780291 | 43.8361 | 7451.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28902.520 | 21787.876 | 1.362210 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.2804 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.362210 | 1.43459749 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 14451.26 | 14451.26 | 1.0000 | 0.95639845 | 0.908140 | 31.00 | 15.89 | 0.00669217 | 48274.7 | 11.77 | 8.65 | 0.00669217 | 28706.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14451.26 | 31.96 | 0.00630459 | 15.89 | 1.14133354 | 125.6781 | 26.05 | 0.00869490 | 26.10 | 0.00869490 | 36.1158 | 16181.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87857.132 | 87857.132 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.362210 | 1.43459749 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:10:00 | Sensible | 87857.13 | 87857.13 | 1.0000 | 1.43459749 | 1.362210 | -20.95 | -20.95 | 0.00094777 | -18713.5 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87857.13 | -27.60 | 0.00034190 | -27.60 | 1.14133354 | 83.7854 | 13.44 | 0.00407851 | 18.89 | 0.00407851 | 26.4460 | 164.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.97 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.36 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2730.33 | 5226.67 | 1338.17 |
KITCHEN | 4389.33 | 6012.17 | 3467.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4436.50 | 6898.00 | 3514.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 79.33 | 19.50 | 0.50 | 0.67 |
KITCHEN | 0.00 | 120.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 79.33 | 134.83 | 0.50 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.92 | 87.54 | 354.18 | 4.872 | 2.782 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.575 | 0.041 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.92 | 87.54 | 354.18 | 4.066 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.816 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.92 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.57 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12572701.40 | 0.00 | 12572701.40 | 7083434.06 | 19656135.46 | 13120747.55 | 1436.48 | 6231.27 | 1092.25 | 395.97 |
KITCHEN | 24843951.38 | 0.00 | 24843951.38 | 176597.47 | 25020548.86 | 35993094.65 | 8620.52 | 136.63 | 2.84 | 471.60 |
Total Facility | 37416652.78 | 0.00 | 37416652.78 | 7260031.53 | 44676684.31 | 49113842.20 | 8622.62 | 6231.42 | 1094.38 | 684.32 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4741 | 0.0000 | 0.4741 | 0.2709 | 0.7451 | 0.4161 | 0.00 | 6108.01 | 1078.99 |
KITCHEN | 0.9327 | 0.0000 | 0.9327 | 0.0040 | 0.9367 | 1.1413 | 7054.60 | 132.19 | 0.21 |
Total Facility | 1.4069 | 0.0000 | 1.4069 | 0.2749 | 1.6818 | 1.5574 | 7054.60 | 6108.06 | 1079.12 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 13944851.15 | 0.00 | 13944851.15 | 13120747.55 | 1435.70 | 0.05 | 7324.25 | 395.97 |
PSZ-AC_2:2 | 27554457.26 | 0.00 | 27554457.26 | 35993094.65 | 8062.44 | 143.80 | 553.77 | 471.60 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5259 | 0.0000 | 0.5259 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.0345 | 0.0000 | 1.0345 | 1.1413 | 6506.81 | 140.13 | 540.05 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 914.32 | 442.65 | 6226.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 98.27 | 1087.76 | 6472.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0120 | 0.7064 | 0.4615 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.0818 | 1.0659 | 1.0313 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
Electricity:Building | 298.02 | 2110.08 | 01-JAN-01:20 | 18433.35 | 02-JAN-11:10 |
Electricity:Zone:DINING | 77.04 | 295.02 | 01-JAN-01:20 | 4205.23 | 02-JAN-16:30 |
Electricity:SpaceType:GENERAL | 290.08 | 1973.80 | 01-JAN-01:20 | 15139.30 | 02-JAN-11:10 |
InteriorLights:Electricity | 24.21 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:DINING | 6.71 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-16:30 |
InteriorLights:Electricity:SpaceType:GENERAL | 24.21 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 24.21 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 6.71 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 24.21 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:30 |
Electricity:Zone:KITCHEN | 220.98 | 1815.06 | 01-JAN-01:20 | 14339.52 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.53 | 1653.77 | 01-JAN-01:10 | 10143.54 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 50.35 | 849.92 | 10-JAN-23:30 | 4353.01 | 07-SEP-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 42.41 | 764.13 | 10-JAN-23:10 | 2545.36 | 05-SEP-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 14.10 | 0.00 | 01-JAN-11:10 | 1469.12 | 05-SEP-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 28.31 | 683.16 | 28-JAN-01:10 | 1076.23 | 02-MAY-13:10 |
ElectricityPurchased:Facility | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
ElectricityPurchased:Plant | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
Cogeneration:ElectricityPurchased | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
General:Cogeneration:ElectricityPurchased | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
ElectricityNet:Plant | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
Cogeneration:ElectricityNet | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
General:Cogeneration:ElectricityNet | 436.94 | 3747.61 | 11-JAN-01:20 | 31726.58 | 17-JUL-13:00 |
Electricity:HVAC | 80.89 | 0.00 | 01-JAN-01:10 | 16699.65 | 17-JUL-13:00 |
Fans:Electricity | 57.86 | 0.00 | 01-JAN-01:10 | 3504.65 | 10-JAN-21:00 |
General:Fans:Electricity | 57.86 | 0.00 | 01-JAN-01:10 | 3504.65 | 10-JAN-21:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 23.02 | 0.00 | 01-JAN-00:10 | 13499.71 | 17-JUL-13:00 |
General:Cooling:Electricity | 23.02 | 0.00 | 01-JAN-00:10 | 13499.71 | 17-JUL-13:00 |
ExteriorLights:Electricity | 15.62 | 0.00 | 01-JAN-08:20 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.62 | 0.00 | 01-JAN-08:20 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1104.60 | 2558.65 | 07-JAN-03:40 | 155262.47 | 10-JAN-20:40 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 398.63 | 0.00 | 01-JAN-01:10 | 125503.14 | 10-JAN-21:00 |
Heating:NaturalGas | 398.63 | 0.00 | 01-JAN-01:10 | 125503.14 | 10-JAN-21:00 |
General:Heating:NaturalGas | 398.63 | 0.00 | 01-JAN-01:10 | 125503.14 | 10-JAN-21:00 |
NaturalGas:Plant | 228.80 | 720.00 | 03-JAN-00:10 | 28350.18 | 17-FEB-13:50 |
WaterSystems:NaturalGas | 228.80 | 720.00 | 03-JAN-00:10 | 28350.18 | 17-FEB-13:50 |
Water Heater:WaterSystems:NaturalGas | 228.80 | 720.00 | 03-JAN-00:10 | 28350.18 | 17-FEB-13:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-APR-12:40 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1068.15 | 2414.72 | 28-JAN-01:10 | 149181.38 | 10-JAN-21:00 |
EnergyTransfer:Building | 436.97 | 1207.36 | 28-JAN-01:10 | 39233.52 | 09-JAN-12:10 |
EnergyTransfer:Zone:KITCHEN | 327.38 | 1207.36 | 28-JAN-01:10 | 25202.72 | 25-APR-04:10 |
Refrigeration:EnergyTransfer | 133.29 | 2414.72 | 28-JAN-01:10 | 7834.84 | 13-JUN-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.65 | 1207.36 | 28-JAN-01:10 | 3917.42 | 13-JUN-03:30 |
General:Refrigeration:EnergyTransfer | 66.65 | 1207.36 | 28-JAN-01:10 | 3917.42 | 13-JUN-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 66.65 | 1207.36 | 28-JAN-01:10 | 3917.42 | 13-JUN-03:30 |
EnergyTransfer:Plant | 224.24 | 1207.36 | 28-JAN-01:10 | 23894.18 | 27-FEB-14:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.93 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 53.72 | 1059.48 | 28-JAN-01:10 | 2238.70 | 02-MAY-13:10 |
EnergyTransfer:Zone:DINING | 109.60 | 0.00 | 01-JAN-01:10 | 37326.13 | 29-JAN-03:20 |
Heating:EnergyTransfer | 45.88 | 0.00 | 01-JAN-00:10 | 28495.83 | 10-JAN-21:00 |
Heating:EnergyTransfer:Zone:DINING | 45.87 | 0.00 | 01-JAN-00:10 | 28495.83 | 10-JAN-21:00 |
General:Heating:EnergyTransfer | 45.88 | 0.00 | 01-JAN-00:10 | 28495.83 | 10-JAN-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 45.87 | 0.00 | 01-JAN-00:10 | 28495.83 | 10-JAN-21:00 |
Cooling:EnergyTransfer | 324.45 | 0.00 | 01-JAN-01:10 | 29385.76 | 17-JUL-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 63.73 | 0.00 | 01-JAN-01:10 | 17694.05 | 29-JAN-03:30 |
General:Cooling:EnergyTransfer | 324.45 | 0.00 | 01-JAN-01:10 | 29385.76 | 17-JUL-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 63.73 | 0.00 | 01-JAN-01:10 | 17694.05 | 29-JAN-03:30 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1888.98 | 28-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1888.98 | 28-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 260.72 | 0.00 | 01-JAN-01:10 | 21325.32 | 25-APR-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 260.72 | 0.00 | 01-JAN-01:10 | 21325.32 | 25-APR-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 157.59 | 0.00 | 01-JAN-00:10 | 21497.68 | 16-FEB-13:50 |
PlantLoopHeatingDemand:Plant | 157.59 | 0.00 | 01-JAN-00:10 | 21497.68 | 16-FEB-13:50 |
WaterSystems:PlantLoopHeatingDemand | 157.59 | 0.00 | 01-JAN-00:10 | 21497.68 | 16-FEB-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 157.59 | 0.00 | 01-JAN-00:10 | 21497.68 | 16-FEB-13:50 |
EnergyTransfer:HVAC | 406.94 | 0.00 | 01-JAN-01:10 | 100402.51 | 10-JAN-21:00 |
HeatingCoils:EnergyTransfer | 318.91 | 0.00 | 01-JAN-01:10 | 100402.51 | 10-JAN-21:00 |
CoolingCoils:EnergyTransfer | 88.03 | 0.00 | 01-JAN-00:10 | 48661.07 | 17-JUL-13:00 |
WaterSystems:EnergyTransfer | 157.59 | 0.00 | 01-JAN-00:10 | 21497.68 | 16-FEB-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 157.59 | 0.00 | 01-JAN-00:10 | 21497.68 | 16-FEB-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 45.868 | -63.729 | 0.000 | 0.000 | 72.402 | 6.705 | 52.748 | 29.096 | 0.000 | 2.920 | 0.000 | 0.000 | -15.365 | 0.000 | -109.095 | -21.551 |
KITCHEN | 0.000 | 0.000 | 0.014 | -260.708 | 0.000 | 0.000 | 5.162 | 17.506 | 201.243 | 0.000 | 0.000 | 0.018 | 39.927 | 0.000 | 0.000 | 0.000 | -3.162 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.689 | 8.378 | 0.000 | 0.000 | 0.000 | -12.068 | -0.000 |
Total Facility | 0.000 | 0.000 | 45.882 | -324.437 | 0.000 | 0.000 | 77.564 | 24.211 | 253.992 | 29.096 | 0.000 | 6.628 | 48.305 | 0.000 | -15.365 | 0.000 | -124.325 | -21.551 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 29-JAN-04:38 | 0.00 | 0.00 | 0.00 | -38384.13 | 0.00 | 0.00 | 0.00 | 25.01 | 506.27 | 0.00 | 0.00 | 0.00 | 40552.42 | 0.00 | -2236.57 | 0.00 | -462.99 | 0.00 |
KITCHEN | 25-APR-04:01 | 0.00 | 0.00 | 0.00 | -52630.40 | 0.00 | 0.00 | 9.31 | 25.01 | 4931.35 | 0.00 | 0.00 | 0.00 | 47731.61 | 0.00 | -0.00 | 0.00 | -66.89 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-SEP-02:61 | 0.00 | 0.00 | 0.00 | -69211.62 | 0.00 | 0.00 | 0.00 | 50.02 | 1879.56 | 0.00 | 0.00 | 90.55 | 67955.48 | 0.00 | -594.34 | 0.00 | -169.65 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 26-JAN-03:21 | 0.00 | 0.00 | 44749.45 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1825.86 | 0.00 | -662.31 | -42488.80 |
KITCHEN | 28-JAN-05:02 | 0.00 | 0.00 | 16981.95 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 4924.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -113.36 | -21818.42 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JAN-03:21 | 0.00 | 0.00 | 44749.45 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 1879.56 | 0.00 | 0.00 | 235.17 | 0.00 | 0.00 | -1825.86 | 0.00 | -1349.09 | -43739.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9749 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9749 | 0.2107 | 1.0000 | Not calculated | 0.4161 | 0.2107 | ||
PSZ-AC_2:2 | 1.3622 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3622 | 0.1111 | 1.0000 | Not calculated | 0.1513 | 0.1111 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9749 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.9749 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2107 | ||
PSZ-AC_2:2 | 1.3622 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.3622 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1111 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9749 | 1.9749 | 1.9749 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3622 | 1.3622 | 1.3622 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9749 | 1.9749 | 1.9749 | 1.9749 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3622 | 1.3622 | 1.3622 | 1.3622 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9749 | 1.9749 | 1.9749 | No | 0.4161 | 0.9550 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3622 | 1.3622 | 1.3622 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9749 | 1.9749 | 1.9749 | 1.9749 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.3622 | 1.3622 | 1.3622 | 1.3622 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.50 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 1.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 398.63 | 125503.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 23.02 | 13499.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 24.21 | 1583.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.62 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 57.86 | 3504.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 228.80 | 28350.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.10 | 1469.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.31 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 316.21 | 436.94 |
Natural Gas | 477.16 | 1104.60 |
Additional | 0.00 | 0.00 |
Total | 793.37 | 1541.53 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 104.20 |
Space Heating | 0.00 |
Space Cooling | 99.10 |
Fans (All) | 249.04 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1144.28 |
Miscellaneous (All) | 1880.57 |
Subtotal | 1880.57 |
Natural Gas [MJ/m2] | |
Space Heating | 1715.72 |
Service Water Heating | 984.77 |
Miscellaneous (All) | 4754.16 |
Subtotal | 4754.16 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.57 |
Space Heating | 25.86 |
Space Cooling | 1.49 |
Fans (All) | 3.75 |
Service Water Heating | 14.84 |
Receptacle Equipment | 48.20 |
Miscellaneous | 4.28 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8436.00 | 324.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7278.83 | 501.83 | 450.17 | 513.83 | 15.33 |
Min | 7278.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 501.83 | 450.17 | 513.83 | 15.33 |
Average | 8158.28 | 275.28 | 150.06 | 171.28 | 5.11 |
Sum | 24474.83 | 825.83 | 450.17 | 513.83 | 15.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8335.00 | 425.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7470.50 | 669.83 | 236.67 | 197.33 | 185.67 |
Min | 7470.50 | 11.33 | 0.00 | 0.00 | 0.00 |
Max | 8748.67 | 669.83 | 236.67 | 197.33 | 185.67 |
Average | 8184.72 | 368.72 | 78.89 | 65.78 | 61.89 |
Sum | 24554.17 | 1106.17 | 236.67 | 197.33 | 185.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254507.17 | 217.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15666.17 | 591.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254507.17 | 591.83 | 0.00 | 0.00 | 0.00 |
Average | 90057.78 | 269.89 | 0.00 | 0.00 | 0.00 |
Sum | 270173.33 | 809.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124186E+10 | 38384.97 | 29-JAN-04:38 | -30.6 | -30.9 | 0.444739E+10 | 3722.95 | 07-JAN-19:10 | -30.6 | -30.9 |
February | 0.149507E+10 | 28214.96 | 01-FEB-03:59 | -25.0 | -25.2 | 0.405284E+10 | 4412.68 | 27-FEB-12:00 | 17.20 | 6.49 |
March | 0.169817E+10 | 21458.12 | 05-MAR-03:53 | -21.1 | -21.7 | 0.449805E+10 | 3906.86 | 14-MAR-11:00 | 14.40 | 6.37 |
April | 0.300538E+10 | 9405.67 | 28-APR-23:01 | -4.6 | -6.2 | 0.448932E+10 | 4585.37 | 22-APR-18:10 | -4.6 | -6.2 |
May | 0.509939E+10 | 9481.14 | 19-MAY-17:03 | 26.02 | 14.43 | 0.485158E+10 | 4681.22 | 20-MAY-18:10 | 24.13 | 13.93 |
June | 0.911766E+10 | 24179.04 | 21-JUN-02:61 | 20.82 | 13.39 | 0.506256E+10 | 4681.01 | 24-JUN-18:00 | 25.00 | 10.72 |
July | 0.130317E+11 | 26854.42 | 26-JUL-02:61 | 20.82 | 11.39 | 0.533651E+10 | 4681.54 | 01-JUL-18:49 | 20.82 | 11.39 |
August | 0.120610E+11 | 26789.00 | 12-AUG-02:61 | 17.75 | 8.77 | 0.534243E+10 | 4681.12 | 26-AUG-18:00 | 20.60 | 12.09 |
September | 0.844032E+10 | 28572.90 | 03-SEP-02:61 | 16.02 | 9.04 | 0.491092E+10 | 4681.09 | 02-SEP-18:30 | 16.02 | 9.04 |
October | 0.493217E+10 | 8458.58 | 21-OCT-04:01 | -1.0 | -1.9 | 0.470978E+10 | 4413.13 | 12-OCT-11:50 | -1.0 | -1.9 |
November | 0.245585E+10 | 13517.40 | 27-NOV-00:01 | -15.1 | -15.9 | 0.435876E+10 | 4426.07 | 04-NOV-18:10 | -15.1 | -15.9 |
December | 0.115128E+10 | 29844.36 | 29-DEC-03:06 | -25.8 | -26.1 | 0.444677E+10 | 3722.89 | 30-DEC-19:10 | -15.7 | -16.3 |
Annual Sum or Average | 0.637298E+11 | 0.565069E+11 | ||||||||
Minimum of Months | 0.115128E+10 | 8458.58 | -30.6 | -30.9 | 0.405284E+10 | 3722.89 | -30.6 | -30.9 | ||
Maximum of Months | 0.130317E+11 | 38384.97 | 26.02 | 14.43 | 0.534243E+10 | 4681.54 | 25.00 | 13.93 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202744E+11 | 47470.22 | 29-JAN-05:01 | -30.6 | -30.9 | 0.768228E+10 | 5059.52 | 14-JAN-11:00 | -30.6 | -30.9 |
February | 0.188697E+11 | 43672.76 | 01-FEB-05:01 | -25.0 | -25.2 | 0.694745E+10 | 5128.51 | 27-FEB-11:00 | 16.10 | 6.08 |
March | 0.212551E+11 | 38724.60 | 05-MAR-05:01 | -20.3 | -21.0 | 0.769220E+10 | 5089.79 | 14-MAR-10:00 | 12.80 | 5.58 |
April | 0.207427E+11 | 52595.94 | 25-APR-04:01 | 0.68 | -1.1 | 0.748284E+10 | 5135.93 | 07-APR-10:00 | 0.68 | -1.1 |
May | 0.217958E+11 | 46552.92 | 14-MAY-02:61 | 8.30 | 4.34 | 0.777080E+10 | 5135.95 | 30-MAY-10:50 | 18.40 | 10.40 |
June | 0.219148E+11 | 47547.88 | 09-JUN-04:01 | 4.50 | 2.68 | 0.758197E+10 | 5135.98 | 13-JUN-10:00 | 16.70 | 11.51 |
July | 0.233580E+11 | 44323.53 | 08-JUL-02:61 | 7.02 | 3.76 | 0.784977E+10 | 5135.99 | 07-JUL-10:00 | 7.02 | 3.76 |
August | 0.233465E+11 | 44698.44 | 28-AUG-02:11 | 10.00 | 6.00 | 0.784838E+10 | 5135.96 | 23-AUG-10:00 | 10.00 | 6.00 |
September | 0.226591E+11 | 48692.13 | 28-SEP-02:11 | 6.87 | 3.44 | 0.755745E+10 | 5135.97 | 07-SEP-10:39 | 6.87 | 3.44 |
October | 0.234094E+11 | 49733.89 | 20-OCT-04:01 | 4.13 | 1.44 | 0.775341E+10 | 5135.94 | 16-OCT-10:50 | 4.13 | 1.44 |
November | 0.217256E+11 | 35844.31 | 05-NOV-02:61 | 8.80 | 3.68 | 0.746187E+10 | 5124.05 | 17-NOV-11:00 | 14.60 | 6.57 |
December | 0.213659E+11 | 45195.10 | 29-DEC-05:01 | -25.0 | -25.3 | 0.768574E+10 | 5094.80 | 06-DEC-11:00 | -25.0 | -25.3 |
Annual Sum or Average | 0.260717E+12 | 0.913142E+11 | ||||||||
Minimum of Months | 0.188697E+11 | 35844.31 | -30.6 | -30.9 | 0.694745E+10 | 5059.52 | -30.6 | -30.9 | ||
Maximum of Months | 0.234094E+11 | 52595.94 | 10.00 | 6.00 | 0.784977E+10 | 5135.99 | 18.40 | 11.51 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 | -13.9 | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 | -13.9 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 | -4.1 | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 | -4.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 | 0.55 | 0.00 | 0.00 | 01-APR-00:10 | 2.68 | 0.55 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 | -3.0 | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 | -3.0 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 | 10.36 | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 | 10.36 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 | 13.32 | 0.00 | 0.00 | 01-JUL-00:10 | 19.45 | 13.32 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 | 11.96 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 11.96 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 | 11.59 | 0.00 | 0.00 | 01-SEP-00:10 | 18.43 | 11.59 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 | 6.94 | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 | 6.94 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 | 1.54 | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 | 1.54 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -12.4 | -13.9 | 0.00 | 0.00 | -12.4 | -13.9 | ||
Maximum of Months | 0.00 | 0.00 | 19.45 | 13.32 | 0.00 | 0.00 | 19.45 | 13.32 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147254E+11 | 44737.89 | 26-JAN-03:21 | -21.7 |
February | 0.770859E+10 | 44685.85 | 04-FEB-03:21 | -21.9 |
March | 0.572652E+10 | 44709.90 | 05-MAR-03:21 | -20.6 |
April | 0.199534E+10 | 17799.72 | 29-APR-02:62 | -6.7 |
May | 0.109914E+10 | 18228.78 | 09-MAY-02:61 | -1.7 |
June | 41677890.61 | 4147.89 | 17-JUN-04:01 | 2.12 |
July | 1876869.12 | 5477.66 | 25-JUL-02:30 | 21.40 |
August | 1351713.94 | 5351.24 | 17-AUG-22:54 | 7.20 |
September | 0.194516E+09 | 6878.12 | 10-SEP-02:44 | 20.00 |
October | 0.856496E+09 | 6199.55 | 10-OCT-06:10 | -6.1 |
November | 0.382054E+10 | 26180.36 | 27-NOV-03:55 | -15.8 |
December | 0.969617E+10 | 44459.15 | 28-DEC-03:21 | -22.8 |
Annual Sum or Average | 0.458676E+11 | |||
Minimum of Months | 1351713.94 | 4147.89 | -22.8 | |
Maximum of Months | 0.147254E+11 | 44737.89 | 21.40 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8686611.29 | 17000.83 | 28-JAN-05:02 | -27.5 |
February | 1989390.16 | 10076.78 | 03-FEB-05:03 | -16.7 |
March | 95606.21 | 1489.22 | 01-MAR-05:03 | -12.3 |
April | 372923.86 | 5039.89 | 29-APR-04:03 | -7.8 |
May | 32351.04 | 539.18 | 01-MAY-04:04 | -0.6 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 683949.04 | 5479.86 | 12-NOV-05:03 | -10.6 |
December | 2243615.56 | 8738.33 | 17-DEC-05:03 | -9.8 |
Annual Sum or Average | 14104447.18 | |||
Minimum of Months | 0.00 | 0.00 | -27.5 | |
Maximum of Months | 8686611.29 | 17000.83 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:01 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.725348E+09 | 681.55 | 02-JAN-16:30 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.584235E+09 | 681.55 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.580042E+09 | 681.55 | 01-MAR-17:49 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.492597E+09 | 681.55 | 01-APR-18:30 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.462300E+09 | 681.55 | 01-MAY-19:30 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.405996E+09 | 681.55 | 01-JUN-19:00 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.450230E+09 | 681.55 | 01-JUL-20:19 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.478253E+09 | 681.55 | 01-AUG-19:30 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.525410E+09 | 681.55 | 01-SEP-18:49 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.605138E+09 | 681.55 | 02-OCT-17:49 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.669585E+09 | 681.55 | 01-NOV-16:49 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.726006E+09 | 681.55 | 01-DEC-16:40 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.670514E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.405996E+09 | 681.55 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.726006E+09 | 681.55 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147870E+10 | 901.93 | 02-JAN-10:09 | 0.166069E+11 | 10143.54 | 01-JAN-11:09 |
February | 0.133950E+10 | 901.93 | 01-FEB-10:09 | 0.149998E+11 | 10143.54 | 01-FEB-11:09 |
March | 0.150425E+10 | 901.93 | 01-MAR-10:09 | 0.166070E+11 | 10143.54 | 01-MAR-11:09 |
April | 0.143688E+10 | 901.93 | 01-APR-16:10 | 0.160712E+11 | 10143.54 | 01-APR-10:09 |
May | 0.149147E+10 | 901.93 | 01-MAY-09:09 | 0.166070E+11 | 10143.54 | 01-MAY-10:09 |
June | 0.145377E+10 | 901.93 | 01-JUN-09:09 | 0.160713E+11 | 10143.54 | 01-JUN-10:09 |
July | 0.147476E+10 | 901.93 | 01-JUL-16:10 | 0.166069E+11 | 10143.54 | 01-JUL-10:09 |
August | 0.150425E+10 | 901.93 | 01-AUG-09:09 | 0.166070E+11 | 10143.54 | 01-AUG-10:09 |
September | 0.143724E+10 | 901.93 | 01-SEP-09:09 | 0.160712E+11 | 10143.54 | 01-SEP-10:09 |
October | 0.147852E+10 | 901.93 | 02-OCT-09:09 | 0.166069E+11 | 10143.54 | 01-OCT-10:09 |
November | 0.143180E+10 | 901.93 | 01-NOV-09:09 | 0.160712E+11 | 10143.54 | 01-NOV-10:09 |
December | 0.147494E+10 | 901.93 | 01-DEC-10:09 | 0.166069E+11 | 10143.54 | 01-DEC-11:09 |
Annual Sum or Average | 0.175061E+11 | 0.195533E+12 | ||||
Minimum of Months | 0.133950E+10 | 901.93 | 0.149998E+11 | 10143.54 | ||
Maximum of Months | 0.150425E+10 | 901.93 | 0.166070E+11 | 10143.54 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.725348E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202721E+11 |
February | 0.852256E+10 | 0.584235E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138588E+11 |
March | 0.954557E+10 | 0.580042E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129509E+11 |
April | 0.915225E+10 | 0.492597E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833530E+10 |
May | 0.947560E+10 | 0.462300E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44397383.97 | 0.663250E+10 |
June | 0.922788E+10 | 0.405996E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408438E+09 | 0.317474E+10 |
July | 0.939996E+10 | 0.450230E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121638E+10 | 0.159968E+10 |
August | 0.954557E+10 | 0.478253E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912223E+09 | 0.232742E+10 |
September | 0.915225E+10 | 0.525410E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336316E+09 | 0.452175E+10 |
October | 0.940563E+10 | 0.605138E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2335693.92 | 0.776100E+10 |
November | 0.909363E+10 | 0.669585E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111254E+11 |
December | 0.939996E+10 | 0.726006E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165360E+11 |
Annual Sum or Average | 0.111326E+12 | 0.670514E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292009E+10 | 0.109095E+12 |
Minimum of Months | 0.852256E+10 | 0.405996E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159968E+10 |
Maximum of Months | 0.954557E+10 | 0.726006E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121638E+10 | 0.202721E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147870E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482782E+09 |
February | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365507E+09 |
March | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326666E+09 |
April | 0.655836E+09 | 0.143688E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228854E+09 |
May | 0.679007E+09 | 0.149147E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 270058.55 | 0.240347E+09 |
June | 0.661256E+09 | 0.145377E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2286050.45 | 0.146708E+09 |
July | 0.673587E+09 | 0.147476E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6835788.39 | 98411695.85 |
August | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6191280.84 | 0.112600E+09 |
September | 0.655836E+09 | 0.143724E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2600254.23 | 0.187368E+09 |
October | 0.673993E+09 | 0.147852E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242616E+09 |
November | 0.651635E+09 | 0.143180E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334351E+09 |
December | 0.673587E+09 | 0.147494E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395435E+09 |
Annual Sum or Average | 0.797748E+10 | 0.175061E+11 | 0.146594E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 18183432.47 | 0.316165E+10 |
Minimum of Months | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98411695.85 |
Maximum of Months | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6835788.39 | 0.482782E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393193E+09 | 0.439599E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315685E+09 | 0.586368E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334825E+09 | 0.102744E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272252E+09 | 0.118294E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205531E+09 | 0.157113E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172050E+09 | 0.170156E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236757E+09 | 0.172852E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265041E+09 | 0.144591E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283829E+09 | 0.101193E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380260E+09 | 0.687147E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403937E+09 | 0.396014E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425998E+09 | 0.289131E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368936E+10 | 0.120677E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172050E+09 | 0.289131E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425998E+09 | 0.172852E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 681.55 | 02-JAN-16:30 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 32063.35 | 10-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 681.55 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 27085.34 | 04-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 681.55 | 01-MAR-17:49 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 26223.23 | 04-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 681.55 | 01-APR-18:30 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 14648.61 | 28-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 681.55 | 01-MAY-19:30 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1876.26 | 20-MAY-17:10 | 12076.70 | 22-MAY-19:00 |
June | 9454.80 | 03-JUN-18:10 | 681.55 | 01-JUN-19:00 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3653.38 | 29-JUN-13:00 | 8556.10 | 16-JUN-11:02 |
July | 9454.80 | 01-JUL-18:10 | 681.55 | 01-JUL-20:19 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5961.22 | 17-JUL-17:03 | 4901.82 | 07-JUL-19:52 |
August | 9454.80 | 05-AUG-18:10 | 681.55 | 01-AUG-19:30 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5569.70 | 05-AUG-18:03 | 6927.49 | 17-AUG-12:00 |
September | 9454.80 | 02-SEP-18:10 | 681.55 | 01-SEP-18:49 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4412.47 | 02-SEP-17:03 | 9993.82 | 18-SEP-20:00 |
October | 9454.80 | 07-OCT-18:10 | 681.55 | 02-OCT-17:49 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 307.33 | 18-OCT-14:00 | 12269.69 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 681.55 | 01-NOV-16:49 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 18451.04 | 26-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 681.55 | 01-DEC-16:40 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 26333.41 | 29-DEC-19:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4901.82 | |||||
Maximum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 5961.22 | 32063.35 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.93 | 02-JAN-10:09 | 7408.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 954.79 | 06-JAN-03:51 |
February | 677.52 | 04-FEB-19:10 | 901.93 | 01-FEB-10:09 | 7408.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 909.74 | 17-FEB-04:10 |
March | 677.52 | 04-MAR-19:10 | 901.93 | 01-MAR-10:09 | 7408.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1045.89 | 17-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 901.93 | 01-APR-16:10 | 7408.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 733.41 | 27-APR-02:00 |
May | 677.52 | 06-MAY-18:10 | 901.93 | 01-MAY-09:09 | 7408.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 18.98 | 20-MAY-16:00 | 1509.57 | 22-MAY-03:55 |
June | 677.52 | 03-JUN-18:10 | 901.93 | 01-JUN-09:09 | 7408.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 45.49 | 29-JUN-15:00 | 726.19 | 14-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 901.93 | 01-JUL-16:10 | 7408.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 49.56 | 25-JUL-14:55 | 403.50 | 05-JUL-01:00 |
August | 677.52 | 05-AUG-18:10 | 901.93 | 01-AUG-09:09 | 7408.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 45.31 | 11-AUG-14:00 | 517.39 | 23-AUG-03:20 |
September | 677.52 | 02-SEP-18:10 | 901.93 | 01-SEP-09:09 | 7408.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 46.29 | 02-SEP-14:00 | 904.93 | 12-SEP-03:20 |
October | 677.52 | 07-OCT-18:10 | 901.93 | 02-OCT-09:09 | 7408.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 623.24 | 31-OCT-03:40 |
November | 677.52 | 04-NOV-18:10 | 901.93 | 01-NOV-09:09 | 7408.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 881.21 | 28-NOV-04:57 |
December | 677.52 | 02-DEC-19:10 | 901.93 | 01-DEC-10:09 | 7408.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 1462.91 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 403.50 | ||||||
Maximum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 49.56 | 1509.57 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.00 | 11-JAN-08:31 | 1524.90 | 28-JAN-14:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.65 | 05-FEB-23:53 | 1589.79 | 05-FEB-13:40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.89 | 01-MAR-07:00 | 2021.28 | 07-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.18 | 11-APR-06:53 | 2233.15 | 29-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512.91 | 13-MAY-03:52 | 2552.19 | 09-MAY-12:30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.51 | 20-JUN-04:55 | 2223.07 | 03-JUN-13:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.90 | 12-JUL-02:51 | 2425.20 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.31 | 07-AUG-02:52 | 2126.54 | 03-AUG-12:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 616.11 | 03-SEP-04:55 | 2036.40 | 17-SEP-13:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.53 | 27-OCT-07:05 | 1472.22 | 10-OCT-12:40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.05 | 14-NOV-07:35 | 1166.37 | 12-NOV-13:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.04 | 29-DEC-06:00 | 1157.63 | 29-DEC-13:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 487.51 | 1157.63 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.00 | 2552.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 38384.97 | 29-JAN-04:38 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.99 |
February | 28214.96 | 01-FEB-03:59 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.67 |
March | 21458.12 | 05-MAR-03:53 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.01 |
April | 9405.67 | 28-APR-23:01 | 5252.67 | 1514.58 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.92 |
May | 9481.14 | 19-MAY-17:03 | 25212.80 | 490.72 | 9757.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.84 | 0.00 |
June | 24179.04 | 21-JUN-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.44 |
July | 26854.42 | 26-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.07 |
August | 26789.00 | 12-AUG-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.43 |
September | 28572.90 | 03-SEP-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.91 |
October | 8458.58 | 21-OCT-04:01 | 0.00 | 250.09 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.36 |
November | 13517.40 | 27-NOV-00:01 | 5252.67 | 1135.93 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.78 |
December | 29844.36 | 29-DEC-03:06 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8458.58 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38384.97 | 25212.80 | 1514.58 | 16200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.84 | 462.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 47470.22 | 29-JAN-05:01 | 0.00 | 250.09 | 36578.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 122.98 |
February | 43672.76 | 01-FEB-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 51.84 |
March | 38724.60 | 05-MAR-05:01 | 0.00 | 250.09 | 36578.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 |
April | 52595.94 | 25-APR-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 66.89 |
May | 46552.92 | 14-MAY-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 134.82 |
June | 47547.88 | 09-JUN-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 98.88 |
July | 44323.53 | 08-JUL-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 309.02 |
August | 44698.44 | 28-AUG-02:11 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 194.53 |
September | 48692.13 | 28-SEP-02:11 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 301.78 |
October | 49733.89 | 20-OCT-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 53.99 |
November | 35844.31 | 05-NOV-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 197.42 |
December | 45195.10 | 29-DEC-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35844.31 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52595.94 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 309.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.31 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.16 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.56 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.56 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.49 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.65 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.47 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.26 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.07 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.21 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 440.21 | 39.54 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.363372E+11 | 22426.57 | 09-JAN-11:09 | 0.172076E+12 | 155262.47 | 10-JAN-20:40 |
February | 0.321704E+11 | 22099.09 | 10-FEB-11:09 | 0.118644E+12 | 124366.03 | 09-FEB-11:09 |
March | 0.351105E+11 | 21961.36 | 03-MAR-11:09 | 0.113918E+12 | 120911.49 | 04-MAR-11:20 |
April | 0.335695E+11 | 21600.99 | 27-APR-10:09 | 0.806906E+11 | 80074.21 | 28-APR-12:09 |
May | 0.355259E+11 | 24391.91 | 20-MAY-10:20 | 0.737274E+11 | 76921.48 | 08-MAY-10:20 |
June | 0.373450E+11 | 27861.57 | 23-JUN-10:20 | 0.587907E+11 | 57523.23 | 16-JUN-12:00 |
July | 0.425577E+11 | 31726.58 | 17-JUL-12:00 | 0.583437E+11 | 49417.76 | 01-JUL-12:50 |
August | 0.411169E+11 | 29871.86 | 10-AUG-10:00 | 0.583442E+11 | 53112.46 | 17-AUG-12:50 |
September | 0.372041E+11 | 28281.47 | 02-SEP-17:10 | 0.602879E+11 | 58240.96 | 12-SEP-12:20 |
October | 0.355158E+11 | 23162.26 | 18-OCT-10:20 | 0.720947E+11 | 69450.56 | 04-OCT-10:09 |
November | 0.344020E+11 | 21855.81 | 27-NOV-11:09 | 0.965309E+11 | 105644.30 | 26-NOV-11:09 |
December | 0.360823E+11 | 22254.13 | 28-DEC-11:09 | 0.141148E+12 | 133713.81 | 31-DEC-08:09 |
Annual Sum or Average | 0.436937E+12 | 0.110460E+13 | ||||
Minimum of Months | 0.321704E+11 | 21600.99 | 0.583437E+11 | 49417.76 | ||
Maximum of Months | 0.425577E+11 | 31726.58 | 0.172076E+12 | 155262.47 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.220404E+10 | 0.182697E+10 | 0.225803E+11 | 0.00 | 0.577179E+10 | 0.79 | 0.00 | 558847.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192374E+10 | 0.147021E+10 | 0.203951E+11 | 0.00 | 0.475917E+10 | 0.72 | 0.00 | 3908088.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208429E+10 | 0.137575E+10 | 0.225804E+11 | 0.00 | 0.505892E+10 | 0.80 | 0.00 | 690885.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192947E+10 | 0.107679E+10 | 0.218518E+11 | 0.00 | 0.455744E+10 | 0.77 | 0.00 | 0.115465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195377E+10 | 0.902406E+09 | 0.225803E+11 | 0.00 | 0.462091E+10 | 0.80 | 0.00 | 0.113315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185977E+10 | 0.782966E+09 | 0.218520E+11 | 0.00 | 0.441523E+10 | 0.77 | 0.00 | 0.398532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192499E+10 | 0.840614E+09 | 0.225802E+11 | 0.00 | 0.470728E+10 | 0.79 | 0.00 | 0.782105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.198250E+10 | 0.101099E+10 | 0.225804E+11 | 0.00 | 0.466877E+10 | 0.80 | 0.00 | 0.621644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196265E+10 | 0.122006E+10 | 0.218518E+11 | 0.00 | 0.447094E+10 | 0.77 | 0.00 | 0.332262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208365E+10 | 0.152231E+10 | 0.225803E+11 | 0.00 | 0.462837E+10 | 0.79 | 0.00 | 0.419097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210138E+10 | 0.170338E+10 | 0.218519E+11 | 0.00 | 0.477767E+10 | 0.77 | 0.00 | 6065225.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220094E+10 | 0.189201E+10 | 0.225802E+11 | 0.00 | 0.542720E+10 | 0.79 | 0.00 | 567797.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242112E+11 | 0.156245E+11 | 0.265865E+12 | 0.00 | 0.578637E+11 | 9.37 | 0.00 | 0.230249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185977E+10 | 0.782966E+09 | 0.203951E+11 | 0.00 | 0.441523E+10 | 0.72 | 0.00 | 558847.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220404E+10 | 0.189201E+10 | 0.225804E+11 | 0.00 | 0.577179E+10 | 0.80 | 0.00 | 0.782105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.110364E+12 | 0.00 | 0.211857E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.626210E+11 | 0.00 | 0.194194E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.520440E+11 | 0.00 | 0.213479E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.215469E+11 | 0.00 | 0.199252E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.136085E+11 | 0.00 | 0.195931E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.165245E+10 | 0.00 | 0.179198E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.161675E+09 | 0.00 | 0.176563E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.457574E+09 | 0.00 | 0.173609E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.407798E+10 | 0.00 | 0.169915E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.132568E+11 | 0.00 | 0.183121E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.385879E+11 | 0.00 | 0.187245E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.802552E+11 | 0.00 | 0.203670E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.398635E+12 | 0.00 | 0.228804E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.161675E+09 | 0.00 | 0.169915E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.110364E+12 | 0.00 | 0.213479E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1583.48 | 02-JAN-16:30 | 1372.31 | 01-JAN-06:10 | 14073.79 | 01-JAN-11:09 | 0.00 | 3504.65 | 10-JAN-20:00 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1583.48 | 01-FEB-17:19 | 1372.31 | 01-FEB-06:10 | 14073.79 | 01-FEB-11:09 | 0.00 | 3105.87 | 01-FEB-07:10 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1583.48 | 01-MAR-17:49 | 1372.31 | 01-MAR-06:10 | 14073.79 | 01-MAR-11:09 | 0.00 | 3075.87 | 04-MAR-22:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1583.48 | 01-APR-18:30 | 1372.31 | 01-APR-05:10 | 14073.79 | 01-APR-10:09 | 0.00 | 2566.42 | 29-APR-06:10 | 0.00 | 01-APR-12:39 | 0.00 | 01-APR-00:10 |
May | 1583.48 | 01-MAY-19:30 | 1372.31 | 01-MAY-05:10 | 14073.79 | 01-MAY-10:09 | 0.00 | 2412.53 | 08-MAY-06:10 | 0.00 | 16-MAY-08:39 | 0.00 | 01-MAY-00:10 |
June | 1583.48 | 01-JUN-19:00 | 1372.31 | 01-JUN-20:10 | 14073.79 | 01-JUN-10:09 | 0.00 | 2392.03 | 29-JUN-12:00 | 0.00 | 01-JUN-17:10 | 0.00 | 01-JUN-00:10 |
July | 1583.48 | 01-JUL-20:19 | 1372.31 | 01-JUL-20:30 | 14073.79 | 01-JUL-10:09 | 0.00 | 3199.95 | 17-JUL-12:00 | 0.00 | 06-JUL-14:39 | 0.00 | 01-JUL-00:10 |
August | 1583.48 | 01-AUG-19:30 | 1372.31 | 01-AUG-19:00 | 14073.79 | 01-AUG-10:09 | 0.00 | 2833.63 | 05-AUG-18:10 | 0.00 | 22-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 1583.48 | 01-SEP-18:49 | 1372.31 | 01-SEP-05:10 | 14073.79 | 01-SEP-10:09 | 0.00 | 2712.77 | 02-SEP-17:10 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1583.48 | 02-OCT-17:49 | 1372.31 | 01-OCT-05:10 | 14073.79 | 01-OCT-10:09 | 0.00 | 2488.55 | 10-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1583.48 | 01-NOV-16:49 | 1372.31 | 01-NOV-05:10 | 14073.79 | 01-NOV-10:09 | 0.00 | 2852.88 | 26-NOV-07:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1583.48 | 01-DEC-16:40 | 1372.31 | 01-DEC-06:10 | 14073.79 | 01-DEC-11:09 | 0.00 | 3289.79 | 31-DEC-07:10 | 0.00 | 21-DEC-10:50 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 2392.03 | 0.00 | 0.00 | ||||||
Maximum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 3504.65 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 383.75 | 24-JAN-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 612.98 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 153.83 | 10-MAR-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3506.56 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6388.55 | 20-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9518.81 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 13499.71 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11532.50 | 05-AUG-18:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11070.56 | 02-SEP-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5075.15 | 18-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 770.24 | 18-NOV-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 173.89 | 10-DEC-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 153.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13499.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 22426.57 | 09-JAN-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 3167.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22099.09 | 10-FEB-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2840.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21961.36 | 03-MAR-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2702.54 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21600.99 | 27-APR-10:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2324.28 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24391.91 | 20-MAY-10:20 | 947.12 | 14073.79 | 0.00 | 0.00 | 1952.21 | 0.00 | 0.00 | 3106.64 | 0.00 |
June | 27861.57 | 23-JUN-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 1952.21 | 0.00 | 0.00 | 6445.08 | 0.00 |
July | 31726.58 | 17-JUL-12:00 | 1065.50 | 12274.30 | 0.00 | 0.00 | 3199.95 | 0.00 | 0.00 | 13499.71 | 0.00 |
August | 29871.86 | 10-AUG-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2508.72 | 0.00 | 0.00 | 9694.43 | 0.00 |
September | 28281.47 | 02-SEP-17:10 | 1065.50 | 11824.43 | 0.00 | 0.00 | 2712.77 | 0.00 | 0.00 | 11070.56 | 0.00 |
October | 23162.26 | 18-OCT-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 1952.21 | 0.00 | 0.00 | 1769.47 | 0.00 |
November | 21855.81 | 27-NOV-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2596.76 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22254.13 | 28-DEC-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2995.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 21600.99 | 947.12 | 11824.43 | 0.00 | 0.00 | 1952.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31726.58 | 1065.50 | 14073.79 | 0.00 | 0.00 | 3199.95 | 0.00 | 0.00 | 13499.71 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 125503.14 | 10-JAN-20:00 | 0.00 | 28301.98 | 31-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 98226.89 | 01-FEB-07:10 | 0.00 | 28350.18 | 17-FEB-13:50 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 93872.04 | 04-MAR-22:00 | 0.00 | 28331.49 | 01-MAR-13:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 51545.16 | 29-APR-03:49 | 0.00 | 28093.76 | 01-APR-12:00 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 37050.03 | 08-MAY-06:10 | 0.00 | 27675.80 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 19998.80 | 17-JUN-05:10 | 0.00 | 27037.60 | 01-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 5087.32 | 08-JUL-05:10 | 0.00 | 26434.61 | 01-JUL-12:50 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 6714.26 | 17-AUG-22:30 | 0.00 | 26014.84 | 01-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 23674.76 | 17-SEP-06:10 | 0.00 | 26265.41 | 29-SEP-12:00 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 43489.31 | 10-OCT-06:10 | 0.00 | 26899.04 | 31-OCT-12:20 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 76383.49 | 12-NOV-03:09 | 0.00 | 27511.87 | 30-NOV-13:39 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 112343.18 | 31-DEC-07:10 | 0.00 | 28016.13 | 31-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 5087.32 | 0.00 | 26014.84 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 125503.14 | 0.00 | 28350.18 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.83 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 12.67 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 | 0.00 | 19.73 |
March | 10.83 | 19.97 | 0.17 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
April | 3.67 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 | 0.00 | 20.39 |
May | 2.83 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.56 | 0.00 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.68 | 0.50 | 24.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.70 | 0.17 | 24.69 |
September | 0.17 | 20.54 | 0.00 | 20.54 | 4.50 | 24.54 | 0.00 | 24.54 |
October | 0.67 | 20.46 | 0.17 | 20.43 | 0.00 | 20.43 | 0.00 | 20.43 |
November | 6.83 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
December | 18.83 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
Annual Sum or Average | 79.33 | 19.74 | 0.50 | 19.74 | 19.50 | 20.71 | 0.67 | 20.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 | 0.00 | 19.40 |
Maximum of Months | 22.83 | 20.54 | 0.17 | 20.54 | 7.17 | 24.70 | 0.50 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.98 | 0.00 | 26.98 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.95 | 0.00 | 26.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.63 | 0.00 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.30 | 0.00 | 28.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 29.24 | 0.00 | 29.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 29.85 | 0.00 | 29.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 29.82 | 0.00 | 29.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 29.35 | 0.00 | 29.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.90 | 0.00 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.49 | 0.00 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.87 | 0.00 | 26.87 |
Annual Sum or Average | 0.00 | 0.00 | 120.00 | 29.10 | 0.00 | 29.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.87 | 0.00 | 26.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 29.85 | 0.00 | 29.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.86 | 354.50 | 20.79 | 354.50 | 20.76 |
February | 543.83 | 20.93 | 216.00 | 20.81 | 216.00 | 20.74 |
March | 612.00 | 20.89 | 204.17 | 20.76 | 204.17 | 20.69 |
April | 543.83 | 21.14 | 90.00 | 20.98 | 90.00 | 20.86 |
May | 448.50 | 21.25 | 107.00 | 21.43 | 43.83 | 21.31 |
June | 228.50 | 21.64 | 267.83 | 22.82 | 5.67 | 22.79 |
July | 107.67 | 22.11 | 447.33 | 23.56 | 10.00 | 23.56 |
August | 141.00 | 21.76 | 383.50 | 23.32 | 0.83 | 23.32 |
September | 289.50 | 21.53 | 244.00 | 22.53 | 22.00 | 22.52 |
October | 509.17 | 21.25 | 52.33 | 21.25 | 27.50 | 21.14 |
November | 583.67 | 21.04 | 106.33 | 20.89 | 106.33 | 20.79 |
December | 609.00 | 20.87 | 257.33 | 20.77 | 257.33 | 20.71 |
Annual Sum or Average | 5226.67 | 21.11 | 2730.33 | 21.49 | 1338.17 | 21.34 |
Minimum of Months | 107.67 | 20.86 | 52.33 | 20.76 | 0.83 | 20.69 |
Maximum of Months | 612.00 | 22.11 | 447.33 | 23.56 | 354.50 | 23.56 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.81 | 426.50 | 18.75 | 426.50 | 18.72 |
February | 526.50 | 18.96 | 304.67 | 18.91 | 293.50 | 18.83 |
March | 607.00 | 19.06 | 282.67 | 18.90 | 281.00 | 18.82 |
April | 474.17 | 19.64 | 230.67 | 20.25 | 138.83 | 20.08 |
May | 461.50 | 21.45 | 319.33 | 22.45 | 200.00 | 22.67 |
June | 422.83 | 24.81 | 479.83 | 25.18 | 333.33 | 25.41 |
July | 493.67 | 25.94 | 582.83 | 25.84 | 478.00 | 25.92 |
August | 460.83 | 25.73 | 552.33 | 25.71 | 429.17 | 25.82 |
September | 428.00 | 23.77 | 410.33 | 24.52 | 281.83 | 24.84 |
October | 415.50 | 20.44 | 245.83 | 21.62 | 106.33 | 21.73 |
November | 506.50 | 19.27 | 226.33 | 19.48 | 171.17 | 19.29 |
December | 605.67 | 18.92 | 328.00 | 18.81 | 328.00 | 18.75 |
Annual Sum or Average | 6012.17 | 21.17 | 4389.33 | 21.83 | 3467.67 | 21.94 |
Minimum of Months | 415.50 | 18.81 | 226.33 | 18.75 | 106.33 | 18.72 |
Maximum of Months | 610.00 | 25.94 | 582.83 | 25.84 | 478.00 | 25.92 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.85823 | 15.05614 | -0.6291 | 14.44227 |
February | 551.00000 | 20.96539 | 18.49686 | -0.5196 | 12.10896 |
March | 612.00000 | 20.88870 | 20.10328 | -0.5139 | 11.65168 |
April | 590.00000 | 21.35636 | 25.66102 | -0.3385 | 9.41133 |
May | 611.00000 | 21.94489 | 29.64776 | -1.1971 | 38.41024 |
June | 592.00000 | 22.99768 | 36.91480 | -0.7005 | 19.15408 |
July | 609.00000 | 23.56228 | 38.97611 | -0.4370 | 10.90862 |
August | 612.00000 | 23.38628 | 35.17517 | -0.5254 | 13.54813 |
September | 590.00000 | 22.69414 | 36.76894 | -0.7835 | 22.99100 |
October | 610.00000 | 21.67004 | 28.31572 | -0.1632 | 7.63199 |
November | 591.00000 | 21.06803 | 21.88890 | -0.4128 | 9.83714 |
December | 609.00000 | 20.86764 | 17.51290 | -0.5666 | 12.76369 |
Annual Sum or Average | 7187.00000 | 21.86062 | 27.07933 | -0.5661 | 15.26576 |
Minimum of Months | 551.00000 | 20.85823 | 15.05614 | -1.1971 | 7.63199 |
Maximum of Months | 612.00000 | 23.56228 | 38.97611 | -0.1632 | 38.41024 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.80739 | 21.76690 | -0.7235 | 16.95923 |
February | 551.00000 | 19.19390 | 25.81479 | -0.5955 | 14.90807 |
March | 612.00000 | 19.09160 | 27.99656 | -0.5989 | 14.17269 |
April | 590.00000 | 20.60131 | 32.53933 | -0.2198 | 12.57681 |
May | 611.00000 | 22.10030 | 34.92184 | -0.7904 | 34.41494 |
June | 592.00000 | 24.59846 | 38.21672 | 0.09611 | 15.26402 |
July | 609.00000 | 25.57645 | 38.93291 | 0.45658 | 13.02704 |
August | 612.00000 | 25.27851 | 35.85797 | 0.33304 | 12.81879 |
September | 590.00000 | 23.78084 | 38.58603 | -0.1478 | 21.01790 |
October | 610.00000 | 21.56054 | 33.43537 | 0.06504 | 12.74598 |
November | 591.00000 | 19.92725 | 28.21237 | -0.3707 | 12.34804 |
December | 609.00000 | 18.94174 | 24.38705 | -0.6494 | 15.12954 |
Annual Sum or Average | 7187.00000 | 21.63551 | 31.74303 | -0.2605 | 16.30487 |
Minimum of Months | 551.00000 | 18.80739 | 21.76690 | -0.7904 | 12.34804 |
Maximum of Months | 612.00000 | 25.57645 | 38.93291 | 0.45658 | 34.41494 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.121422E+09 | 35961147.72 | 17.17 | 0.121421E+09 | 1026.48 | 0.00 | 0.35 | 07-APR-13:57 | 0.00 | 01-APR-00:01 | 5006.38 | 07-APR-13:57 | 5006.38 | 07-APR-13:57 | 1.75 | 24-APR-16:10 | 1431.70 | 07-APR-13:57 | 0.00 | 01-APR-00:01 |
May | 0.152521E+10 | 0.423855E+09 | 89.61 | 0.148059E+10 | 44619170.39 | 0.00 | 0.76 | 20-MAY-17:05 | 0.00 | 01-MAY-00:01 | 11957.43 | 20-MAY-17:05 | 11957.43 | 20-MAY-17:05 | 1141.85 | 19-MAY-12:00 | 3073.59 | 20-MAY-17:05 | 0.00 | 01-MAY-00:01 |
June | 0.633336E+10 | 0.168187E+10 | 234.99 | 0.582480E+10 | 0.508554E+09 | 0.00 | 1.00 | 13-JUN-02:61 | 0.00 | 01-JUN-00:01 | 33752.60 | 22-JUN-02:62 | 28137.45 | 21-JUN-02:42 | 10311.66 | 22-JUN-02:62 | 8092.16 | 21-JUN-02:42 | 0.00 | 01-JUN-00:01 |
July | 0.129342E+11 | 0.342288E+10 | 388.82 | 0.122195E+11 | 0.714729E+09 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 | 33752.60 | 14-JUL-02:62 | 33727.61 | 26-JUL-03:47 | 13111.34 | 01-JUL-02:62 | 8092.16 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 |
August | 0.101070E+11 | 0.268328E+10 | 332.20 | 0.986905E+10 | 0.237905E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 33752.60 | 09-AUG-02:41 | 33752.60 | 07-AUG-02:61 | 9540.61 | 01-AUG-02:61 | 8092.16 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.510252E+10 | 0.135515E+10 | 190.69 | 0.470967E+10 | 0.392843E+09 | 0.00 | 1.00 | 01-SEP-02:62 | 0.00 | 01-SEP-00:01 | 33752.60 | 05-SEP-02:41 | 33059.60 | 10-SEP-02:61 | 13732.11 | 07-SEP-02:62 | 8092.16 | 01-SEP-02:62 | 0.00 | 01-SEP-00:01 |
October | 0.541827E+09 | 0.155372E+09 | 43.26 | 0.541770E+09 | 57048.30 | 0.00 | 0.63 | 18-OCT-13:00 | 0.00 | 01-OCT-00:01 | 9517.23 | 18-OCT-13:00 | 9517.23 | 18-OCT-13:00 | 103.55 | 19-OCT-03:07 | 2536.43 | 18-OCT-13:00 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.366655E+11 | 0.975837E+10 | 1296.72 | 0.347668E+11 | 0.189871E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.129342E+11 | 0.342288E+10 | 388.82 | 0.122195E+11 | 0.714729E+09 | 0.00 | 1.00 | 0.00 | 33752.60 | 33752.60 | 13732.11 | 8092.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1849533.74 | 558847.11 | 0.52 | 1614470.51 | 235063.23 | 0.00 | 0.28 | 24-JAN-04:08 | 0.00 | 01-JAN-00:01 | 3267.77 | 24-JAN-04:08 | 2918.20 | 24-JAN-04:08 | 349.57 | 24-JAN-04:08 | 952.05 | 24-JAN-04:08 | 0.00 | 01-JAN-00:01 |
February | 12976646.36 | 3908088.71 | 3.31 | 12601189.24 | 375457.12 | 0.00 | 0.33 | 28-FEB-04:06 | 0.00 | 01-FEB-00:01 | 3889.19 | 28-FEB-04:06 | 2981.10 | 21-FEB-04:10 | 1114.57 | 28-FEB-04:06 | 1119.51 | 28-FEB-04:06 | 0.00 | 01-FEB-00:01 |
March | 2288946.60 | 690885.72 | 0.65 | 1859821.67 | 429124.93 | 0.00 | 0.21 | 28-MAR-03:10 | 0.00 | 01-MAR-00:01 | 2458.38 | 28-MAR-03:10 | 2062.78 | 28-MAR-03:10 | 488.38 | 24-MAR-03:10 | 727.74 | 28-MAR-03:10 | 0.00 | 01-MAR-00:01 |
April | 0.276311E+09 | 79504185.28 | 36.29 | 0.269952E+09 | 6359785.32 | 0.00 | 1.00 | 07-APR-02:61 | 0.00 | 01-APR-00:01 | 28513.70 | 07-APR-02:61 | 25750.26 | 07-APR-02:61 | 6522.59 | 25-APR-04:01 | 6836.14 | 07-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.263288E+10 | 0.709291E+09 | 141.20 | 0.245255E+10 | 0.180337E+09 | 0.00 | 1.00 | 03-MAY-02:61 | 0.00 | 01-MAY-00:01 | 28513.70 | 28-MAY-02:61 | 25888.49 | 29-MAY-02:61 | 11603.32 | 19-MAY-02:61 | 6836.14 | 19-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.896661E+10 | 0.230345E+10 | 315.87 | 0.804748E+10 | 0.919135E+09 | 0.00 | 1.00 | 01-JUN-02:11 | 0.00 | 01-JUN-00:01 | 28513.70 | 01-JUN-02:11 | 26040.96 | 21-JUN-00:42 | 15672.73 | 13-JUN-04:01 | 6836.14 | 01-JUN-02:11 | 0.00 | 01-JUN-00:01 |
July | 0.171896E+11 | 0.439817E+10 | 455.59 | 0.160393E+11 | 0.115029E+10 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 28513.70 | 19-JUL-02:11 | 27316.16 | 17-JUL-14:00 | 15338.55 | 01-JUL-02:11 | 7684.57 | 17-JUL-14:00 | 0.00 | 01-JUL-00:01 |
August | 0.136721E+11 | 0.353317E+10 | 408.26 | 0.130672E+11 | 0.604857E+09 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 28513.70 | 05-AUG-02:11 | 28513.70 | 11-AUG-02:51 | 11923.79 | 14-AUG-03:31 | 6836.14 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 |
September | 0.763809E+10 | 0.196747E+10 | 252.70 | 0.673564E+10 | 0.902442E+09 | 0.00 | 1.00 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 | 28513.70 | 04-SEP-02:22 | 25538.45 | 10-SEP-02:61 | 16241.26 | 08-SEP-03:31 | 6836.14 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 |
October | 0.949512E+09 | 0.263725E+09 | 69.17 | 0.923406E+09 | 26106143.19 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 28513.70 | 17-OCT-04:01 | 25708.90 | 19-OCT-03:31 | 12782.23 | 01-OCT-02:61 | 6836.14 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 22248458.07 | 6065225.08 | 4.55 | 18359385.51 | 3889072.56 | 0.00 | 1.00 | 05-NOV-02:61 | 0.00 | 01-NOV-00:01 | 28513.70 | 18-NOV-03:01 | 22707.61 | 18-NOV-03:01 | 5806.09 | 18-NOV-03:01 | 6836.14 | 18-NOV-03:01 | 0.00 | 01-NOV-00:01 |
December | 1865924.23 | 567797.41 | 0.68 | 1568642.75 | 297281.49 | 0.00 | 0.22 | 05-DEC-04:10 | 0.00 | 01-DEC-00:01 | 2505.33 | 05-DEC-04:10 | 2197.73 | 05-DEC-04:10 | 393.65 | 08-DEC-04:10 | 740.94 | 05-DEC-04:10 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.513663E+11 | 0.132666E+11 | 1688.77 | 0.475716E+11 | 0.379476E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1849533.74 | 558847.11 | 0.52 | 1568642.75 | 235063.23 | 0.00 | 0.21 | 0.00 | 2458.38 | 2062.78 | 349.57 | 727.74 | 0.00 | |||||||
Maximum of Months | 0.171896E+11 | 0.439817E+10 | 455.59 | 0.160393E+11 | 0.115029E+10 | 0.00 | 1.00 | 0.00 | 28513.70 | 28513.70 | 16241.26 | 7684.57 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.67 | 35.61 | 42.06 | 42.30 | 263.48 | 0.00 | 0.00 | 0.00 |
February | 121.48 | 60.31 | 61.17 | 94.70 | 192.08 | 0.00 | 0.00 | 0.00 |
March | 163.35 | 67.59 | 95.76 | 141.64 | 152.98 | 0.00 | 0.00 | 0.00 |
April | 208.41 | 103.29 | 105.13 | 213.92 | 105.22 | 0.00 | 0.00 | 0.00 |
May | 230.22 | 102.43 | 127.79 | 252.07 | 82.90 | 0.00 | 0.00 | 0.00 |
June | 297.99 | 153.35 | 144.65 | 368.53 | 54.71 | 0.00 | 0.00 | 0.00 |
July | 312.75 | 176.81 | 135.94 | 413.15 | 46.00 | 0.00 | 0.00 | 0.00 |
August | 271.79 | 151.43 | 120.36 | 350.06 | 52.33 | 0.00 | 0.00 | 0.00 |
September | 192.27 | 99.25 | 93.02 | 226.51 | 75.81 | 0.00 | 0.00 | 0.00 |
October | 137.94 | 70.04 | 67.90 | 136.31 | 112.79 | 0.00 | 0.00 | 0.00 |
November | 87.42 | 40.82 | 46.61 | 63.51 | 160.21 | 0.00 | 0.00 | 0.00 |
December | 64.48 | 27.69 | 36.79 | 33.21 | 225.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.79 | 90.88 | 89.92 | 195.22 | 126.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.48 | 27.69 | 36.79 | 33.21 | 46.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 312.75 | 176.81 | 144.65 | 413.15 | 263.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 476.87 | 340.59 | 136.28 | 459.30 | 485.87 | 0.00 | 0.00 | 0.00 |
February | 607.29 | 436.79 | 170.50 | 646.05 | 357.39 | 0.00 | 0.00 | 0.00 |
March | 542.84 | 304.83 | 238.01 | 580.59 | 309.72 | 0.00 | 0.00 | 0.00 |
April | 436.35 | 208.71 | 227.64 | 487.50 | 221.66 | 0.00 | 0.00 | 0.00 |
May | 387.69 | 128.76 | 258.93 | 441.23 | 175.80 | 0.00 | 0.00 | 0.00 |
June | 385.21 | 112.34 | 272.86 | 491.60 | 120.86 | 0.00 | 0.00 | 0.00 |
July | 415.29 | 153.41 | 261.88 | 585.49 | 98.78 | 0.00 | 0.00 | 0.00 |
August | 493.55 | 248.84 | 244.71 | 673.58 | 111.42 | 0.00 | 0.00 | 0.00 |
September | 547.40 | 335.41 | 211.99 | 696.35 | 157.63 | 0.00 | 0.00 | 0.00 |
October | 572.28 | 395.72 | 176.56 | 671.72 | 224.78 | 0.00 | 0.00 | 0.00 |
November | 521.75 | 377.93 | 143.82 | 561.60 | 298.91 | 0.00 | 0.00 | 0.00 |
December | 453.48 | 327.46 | 126.02 | 447.92 | 414.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.83 | 279.86 | 205.97 | 561.25 | 247.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 385.21 | 112.34 | 126.02 | 441.23 | 98.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 607.29 | 436.79 | 272.86 | 696.35 | 485.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 70.35 | 28.35 | 42.00 | 36.44 | 274.16 | 0.00 | 0.00 | 0.00 |
February | 120.08 | 59.03 | 61.06 | 94.57 | 196.33 | 0.00 | 0.00 | 0.00 |
March | 153.68 | 56.31 | 97.37 | 129.77 | 159.02 | 0.00 | 0.00 | 0.00 |
April | 200.63 | 88.89 | 111.74 | 206.09 | 109.96 | 0.00 | 0.00 | 0.00 |
May | 248.16 | 113.17 | 134.99 | 277.78 | 86.07 | 0.00 | 0.00 | 0.00 |
June | 269.99 | 124.02 | 145.97 | 332.75 | 58.70 | 0.00 | 0.00 | 0.00 |
July | 276.57 | 139.76 | 136.82 | 366.85 | 49.48 | 0.00 | 0.00 | 0.00 |
August | 234.85 | 115.26 | 119.59 | 302.46 | 55.06 | 0.00 | 0.00 | 0.00 |
September | 188.92 | 95.51 | 93.41 | 223.84 | 79.42 | 0.00 | 0.00 | 0.00 |
October | 135.03 | 67.09 | 67.94 | 134.77 | 117.50 | 0.00 | 0.00 | 0.00 |
November | 95.59 | 47.42 | 48.17 | 77.42 | 165.96 | 0.00 | 0.00 | 0.00 |
December | 64.25 | 27.12 | 37.13 | 35.32 | 232.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.74 | 80.24 | 91.50 | 185.30 | 131.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.25 | 27.12 | 37.13 | 35.32 | 49.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 276.57 | 139.76 | 145.97 | 366.85 | 274.16 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208034E+09 | 95375044.62 | 0.112659E+09 | 0.113297E+09 | 0.705694E+09 |
February | 0.293895E+09 | 0.145912E+09 | 0.147983E+09 | 0.229101E+09 | 0.464687E+09 |
March | 0.437508E+09 | 0.181028E+09 | 0.256480E+09 | 0.379379E+09 | 0.409740E+09 |
April | 0.540210E+09 | 0.267724E+09 | 0.272486E+09 | 0.554487E+09 | 0.272721E+09 |
May | 0.616624E+09 | 0.274358E+09 | 0.342265E+09 | 0.675156E+09 | 0.222050E+09 |
June | 0.772393E+09 | 0.397472E+09 | 0.374921E+09 | 0.955236E+09 | 0.141796E+09 |
July | 0.837670E+09 | 0.473556E+09 | 0.364113E+09 | 0.110657E+10 | 0.123196E+09 |
August | 0.727972E+09 | 0.405603E+09 | 0.322369E+09 | 0.937605E+09 | 0.140153E+09 |
September | 0.498357E+09 | 0.257250E+09 | 0.241107E+09 | 0.587110E+09 | 0.196487E+09 |
October | 0.369463E+09 | 0.187607E+09 | 0.181856E+09 | 0.365089E+09 | 0.302105E+09 |
November | 0.226605E+09 | 0.105795E+09 | 0.120811E+09 | 0.164620E+09 | 0.415266E+09 |
December | 0.172706E+09 | 74177329.95 | 98528252.36 | 88959581.35 | 0.604909E+09 |
Annual Sum or Average | 0.570144E+10 | 0.286586E+10 | 0.283558E+10 | 0.615661E+10 | 0.399880E+10 |
Minimum of Months | 0.172706E+09 | 74177329.95 | 98528252.36 | 88959581.35 | 0.123196E+09 |
Maximum of Months | 0.837670E+09 | 0.473556E+09 | 0.374921E+09 | 0.110657E+10 | 0.705694E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127726E+10 | 0.912241E+09 | 0.365015E+09 | 0.123019E+10 | 0.130135E+10 |
February | 0.146916E+10 | 0.105667E+10 | 0.412485E+09 | 0.156292E+10 | 0.864602E+09 |
March | 0.145394E+10 | 0.816465E+09 | 0.637475E+09 | 0.155506E+10 | 0.829544E+09 |
April | 0.113102E+10 | 0.540975E+09 | 0.590048E+09 | 0.126360E+10 | 0.574542E+09 |
May | 0.103838E+10 | 0.344875E+09 | 0.693508E+09 | 0.118180E+10 | 0.470859E+09 |
June | 0.998456E+09 | 0.291197E+09 | 0.707259E+09 | 0.127423E+10 | 0.313279E+09 |
July | 0.111232E+10 | 0.410885E+09 | 0.701431E+09 | 0.156818E+10 | 0.264560E+09 |
August | 0.132191E+10 | 0.666484E+09 | 0.655430E+09 | 0.180411E+10 | 0.298434E+09 |
September | 0.141887E+10 | 0.869384E+09 | 0.549482E+09 | 0.180493E+10 | 0.408570E+09 |
October | 0.153279E+10 | 0.105991E+10 | 0.472887E+09 | 0.179913E+10 | 0.602059E+09 |
November | 0.135237E+10 | 0.979604E+09 | 0.372769E+09 | 0.145567E+10 | 0.774767E+09 |
December | 0.121460E+10 | 0.877063E+09 | 0.337536E+09 | 0.119971E+10 | 0.110961E+10 |
Annual Sum or Average | 0.153211E+11 | 0.882575E+10 | 0.649533E+10 | 0.176995E+11 | 0.781218E+10 |
Minimum of Months | 0.998456E+09 | 0.291197E+09 | 0.337536E+09 | 0.118180E+10 | 0.264560E+09 |
Maximum of Months | 0.153279E+10 | 0.105991E+10 | 0.707259E+09 | 0.180493E+10 | 0.130135E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.188435E+09 | 75940472.51 | 0.112494E+09 | 97588476.67 | 0.734313E+09 |
February | 0.290504E+09 | 0.142797E+09 | 0.147707E+09 | 0.228783E+09 | 0.474970E+09 |
March | 0.411608E+09 | 0.150819E+09 | 0.260789E+09 | 0.347583E+09 | 0.425928E+09 |
April | 0.520022E+09 | 0.230393E+09 | 0.289629E+09 | 0.534176E+09 | 0.285021E+09 |
May | 0.664671E+09 | 0.303125E+09 | 0.361546E+09 | 0.743993E+09 | 0.230535E+09 |
June | 0.699810E+09 | 0.321448E+09 | 0.378362E+09 | 0.862476E+09 | 0.152139E+09 |
July | 0.740773E+09 | 0.374323E+09 | 0.366450E+09 | 0.982568E+09 | 0.132519E+09 |
August | 0.629016E+09 | 0.308707E+09 | 0.320309E+09 | 0.810096E+09 | 0.147473E+09 |
September | 0.489681E+09 | 0.247563E+09 | 0.242119E+09 | 0.580183E+09 | 0.205856E+09 |
October | 0.361654E+09 | 0.179686E+09 | 0.181968E+09 | 0.360972E+09 | 0.314703E+09 |
November | 0.247758E+09 | 0.122909E+09 | 0.124849E+09 | 0.200670E+09 | 0.430173E+09 |
December | 0.172090E+09 | 72634167.83 | 99455701.26 | 94597711.25 | 0.623565E+09 |
Annual Sum or Average | 0.541602E+10 | 0.253035E+10 | 0.288568E+10 | 0.584369E+10 | 0.415719E+10 |
Minimum of Months | 0.172090E+09 | 72634167.83 | 99455701.26 | 94597711.25 | 0.132519E+09 |
Maximum of Months | 0.740773E+09 | 0.374323E+09 | 0.378362E+09 | 0.982568E+09 | 0.734313E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 497.54 | 983.01 | 624.90 | 404.55 | 220.34 | 0.00 | 0.00 |
February | 806.77 | 717.26 | 848.86 | 556.13 | 292.73 | 0.00 | 0.00 |
March | 838.88 | 608.59 | 859.86 | 428.73 | 431.13 | 0.00 | 0.00 |
April | 888.27 | 417.60 | 845.39 | 400.88 | 444.51 | 0.00 | 0.00 |
May | 954.64 | 328.33 | 866.07 | 344.37 | 521.70 | 0.00 | 0.00 |
June | 1178.58 | 219.96 | 953.19 | 389.71 | 563.48 | 0.00 | 0.00 |
July | 1356.57 | 185.33 | 1004.61 | 469.97 | 534.65 | 0.00 | 0.00 |
August | 1317.43 | 210.15 | 1000.19 | 515.53 | 484.66 | 0.00 | 0.00 |
September | 1137.12 | 303.29 | 928.59 | 530.17 | 398.42 | 0.00 | 0.00 |
October | 932.35 | 444.62 | 845.25 | 532.86 | 312.39 | 0.00 | 0.00 |
November | 677.12 | 599.67 | 704.76 | 466.17 | 238.59 | 0.00 | 0.00 |
December | 481.38 | 837.87 | 582.21 | 382.27 | 199.94 | 0.00 | 0.00 |
Annual Sum or Average | 922.64 | 487.22 | 838.36 | 450.98 | 387.39 | 0.00 | 0.00 |
Minimum of Months | 481.38 | 185.33 | 582.21 | 344.37 | 199.94 | 0.00 | 0.00 |
Maximum of Months | 1356.57 | 983.01 | 1004.61 | 556.13 | 563.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133261E+10 | 0.263289E+10 | 0.167372E+10 | 0.108356E+10 | 0.590168E+09 | 0.00 | 0.00 |
February | 0.195173E+10 | 0.173519E+10 | 0.205356E+10 | 0.134538E+10 | 0.708175E+09 | 0.00 | 0.00 |
March | 0.224687E+10 | 0.163006E+10 | 0.230306E+10 | 0.114831E+10 | 0.115474E+10 | 0.00 | 0.00 |
April | 0.230239E+10 | 0.108241E+10 | 0.219126E+10 | 0.103909E+10 | 0.115216E+10 | 0.00 | 0.00 |
May | 0.255690E+10 | 0.879398E+09 | 0.231968E+10 | 0.922358E+09 | 0.139732E+10 | 0.00 | 0.00 |
June | 0.305487E+10 | 0.570142E+09 | 0.247066E+10 | 0.101012E+10 | 0.146054E+10 | 0.00 | 0.00 |
July | 0.363343E+10 | 0.496381E+09 | 0.269076E+10 | 0.125876E+10 | 0.143200E+10 | 0.00 | 0.00 |
August | 0.352861E+10 | 0.562862E+09 | 0.267890E+10 | 0.138079E+10 | 0.129811E+10 | 0.00 | 0.00 |
September | 0.294743E+10 | 0.786116E+09 | 0.240690E+10 | 0.137420E+10 | 0.103271E+10 | 0.00 | 0.00 |
October | 0.249721E+10 | 0.119088E+10 | 0.226391E+10 | 0.142720E+10 | 0.836710E+09 | 0.00 | 0.00 |
November | 0.175509E+10 | 0.155434E+10 | 0.182674E+10 | 0.120831E+10 | 0.618428E+09 | 0.00 | 0.00 |
December | 0.128932E+10 | 0.224414E+10 | 0.155939E+10 | 0.102387E+10 | 0.535520E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.290965E+11 | 0.153648E+11 | 0.264385E+11 | 0.142220E+11 | 0.122166E+11 | 0.00 | 0.00 |
Minimum of Months | 0.128932E+10 | 0.496381E+09 | 0.155939E+10 | 0.922358E+09 | 0.535520E+09 | 0.00 | 0.00 |
Maximum of Months | 0.363343E+10 | 0.263289E+10 | 0.269076E+10 | 0.142720E+10 | 0.146054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.155607E+11 | -0.147612E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -799419444.2 | 58.99 | 0.00 | 0.00 |
February | 0.142827E+11 | -0.135683E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -714467291.4 | 58.99 | 0.00 | 0.00 |
March | 0.156884E+11 | -0.148964E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -792041832.9 | 58.99 | 0.00 | 0.00 |
April | 0.145907E+11 | -0.138525E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -738170568.5 | 58.99 | 0.00 | 0.00 |
May | 0.142724E+11 | -0.135383E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -734043101.3 | 58.99 | 0.00 | 0.00 |
June | 0.129696E+11 | -0.123051E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -664557803.3 | 58.99 | 0.00 | 0.00 |
July | 0.127067E+11 | -0.120382E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -668432231.7 | 58.99 | 0.00 | 0.00 |
August | 0.124677E+11 | -0.117945E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -673259455.9 | 58.99 | 0.00 | 0.00 |
September | 0.122223E+11 | -0.115437E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -678637535.5 | 58.99 | 0.00 | 0.00 |
October | 0.132342E+11 | -0.124913E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -742852114.9 | 58.99 | 0.00 | 0.00 |
November | 0.136212E+11 | -0.128715E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -749673602.7 | 58.99 | 0.00 | 0.00 |
December | 0.148982E+11 | -0.141034E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -794786311.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.166515E+12 | -0.157765E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.875034E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.122223E+11 | -0.148964E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -799419444.2 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.156884E+11 | -0.115437E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -664557803.3 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.29 | 0.24 | 01-JAN-08:50 | 4095.58 | 30.02 | 142.50 | 229.83 | 4050.53 | 29.71 | 141.33 | 228.33 |
February | 275.00 | 0.27 | 0.24 | 01-FEB-08:20 | 6981.46 | 35.26 | 241.83 | 258.67 | 6198.11 | 31.79 | 189.33 | 259.33 |
March | 304.00 | 0.26 | 0.24 | 01-MAR-07:49 | 2435.24 | 22.23 | 125.00 | 328.33 | 2506.69 | 22.24 | 131.83 | 330.00 |
April | 325.17 | 0.26 | 0.24 | 01-APR-08:39 | 2489.62 | 21.23 | 80.50 | 360.00 | 1848.85 | 19.42 | 54.50 | 361.67 |
May | 385.83 | 0.26 | 0.24 | 01-MAY-05:00 | 2178.83 | 19.13 | 33.67 | 410.17 | 2123.89 | 19.25 | 41.00 | 412.83 |
June | 434.17 | 0.27 | 0.24 | 01-JUN-13:39 | 2092.09 | 18.66 | 10.83 | 435.00 | 2446.44 | 18.65 | 25.33 | 432.83 |
July | 417.33 | 0.26 | 0.24 | 01-JUL-06:40 | 2439.91 | 19.03 | 12.00 | 420.67 | 2589.72 | 18.97 | 28.67 | 425.17 |
August | 421.33 | 0.27 | 0.24 | 01-AUG-05:40 | 1855.50 | 18.84 | 41.17 | 404.00 | 2038.97 | 18.75 | 45.83 | 403.33 |
September | 352.17 | 0.28 | 0.24 | 01-SEP-06:40 | 2207.28 | 21.10 | 100.33 | 337.00 | 2500.15 | 21.16 | 101.33 | 339.83 |
October | 317.67 | 0.27 | 0.24 | 01-OCT-07:40 | 2586.02 | 25.89 | 153.50 | 304.67 | 2946.92 | 26.10 | 155.50 | 306.83 |
November | 269.50 | 0.28 | 0.24 | 01-NOV-07:49 | 4668.52 | 32.30 | 195.17 | 248.00 | 4789.69 | 32.57 | 196.00 | 248.67 |
December | 236.83 | 0.29 | 0.24 | 01-DEC-08:50 | 3189.58 | 29.94 | 141.67 | 229.67 | 3186.52 | 29.85 | 141.50 | 229.67 |
Annual Sum or Average | 3965.83 | 0.27 | 2914.94 | 23.44 | 1278.17 | 3966.00 | 2942.66 | 23.07 | 1252.17 | 3978.50 | ||
Minimum of Months | 226.83 | 0.26 | 0.24 | 1855.50 | 18.66 | 10.83 | 229.67 | 1848.85 | 18.65 | 25.33 | 228.33 | |
Maximum of Months | 434.17 | 0.29 | 0.24 | 6981.46 | 35.26 | 241.83 | 435.00 | 6198.11 | 32.57 | 196.00 | 432.83 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.429676E+11 | 61106.79 | 06-JAN-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260560E+11 | 61106.79 | 01-FEB-03:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228968E+11 | 61106.79 | 01-MAR-03:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109620E+11 | 50861.75 | 29-APR-02:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.705590E+10 | 29074.76 | 08-MAY-02:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113506E+10 | 11898.65 | 17-JUN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129340E+09 | 5238.87 | 25-JUL-02:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.365642E+09 | 10977.82 | 17-AUG-22:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258253E+10 | 11016.57 | 17-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724303E+10 | 30232.00 | 10-OCT-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176420E+11 | 61106.79 | 12-NOV-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334781E+11 | 61106.79 | 13-DEC-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.129340E+09 | 5238.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.429676E+11 | 61106.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453240E+11 | 74868.70 | 29-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.240408E+11 | 53750.77 | 10-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187384E+11 | 45542.12 | 04-MAR-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627548E+10 | 34765.95 | 29-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.383093E+10 | 20661.81 | 01-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.186895E+09 | 13032.62 | 17-JUN-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 416945.18 | 639.12 | 17-AUG-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.679853E+09 | 8781.26 | 18-SEP-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.336245E+10 | 24439.51 | 10-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132283E+11 | 43747.19 | 27-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307261E+11 | 56760.40 | 29-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453240E+11 | 74868.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.121422E+09 | 0.121421E+09 | 5006.38 | 07-APR-13:57 | 5006.38 | 0.00 |
May | 0.00 | 0.00 | 0.152521E+10 | 0.148059E+10 | 11957.43 | 20-MAY-17:05 | 11957.43 | 0.00 |
June | 0.00 | 0.00 | 0.633336E+10 | 0.582480E+10 | 33752.60 | 22-JUN-02:62 | 23440.94 | 0.00 |
July | 0.00 | 0.00 | 0.129342E+11 | 0.122195E+11 | 33752.60 | 14-JUL-02:62 | 25528.98 | 0.00 |
August | 0.00 | 0.00 | 0.101070E+11 | 0.986905E+10 | 33752.60 | 09-AUG-02:41 | 28551.06 | 0.00 |
September | 0.00 | 0.00 | 0.510252E+10 | 0.470967E+10 | 33752.60 | 05-SEP-02:41 | 27674.98 | 0.00 |
October | 0.00 | 0.00 | 0.541827E+09 | 0.541770E+09 | 9517.23 | 18-OCT-13:00 | 9517.23 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.366655E+11 | 0.347668E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.129342E+11 | 0.122195E+11 | 33752.60 | 28551.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1849533.74 | 1614470.51 | 3267.77 | 24-JAN-04:08 | 2918.20 | 0.00 |
February | 0.00 | 0.00 | 12976646.36 | 12601189.24 | 3889.19 | 28-FEB-04:06 | 2774.61 | 0.00 |
March | 0.00 | 0.00 | 2288946.60 | 1859821.67 | 2458.38 | 28-MAR-03:10 | 2062.78 | 0.00 |
April | 0.00 | 0.00 | 0.276311E+09 | 0.269952E+09 | 28513.70 | 07-APR-02:61 | 25750.26 | 0.00 |
May | 0.00 | 0.00 | 0.263288E+10 | 0.245255E+10 | 28513.70 | 28-MAY-02:61 | 17942.28 | 0.00 |
June | 0.00 | 0.00 | 0.896661E+10 | 0.804748E+10 | 28513.70 | 01-JUN-02:11 | 17324.75 | 0.00 |
July | 0.00 | 0.00 | 0.171896E+11 | 0.160393E+11 | 28513.70 | 19-JUL-02:11 | 14991.11 | 0.00 |
August | 0.00 | 0.00 | 0.136721E+11 | 0.130672E+11 | 28513.70 | 05-AUG-02:11 | 24805.14 | 0.00 |
September | 0.00 | 0.00 | 0.763809E+10 | 0.673564E+10 | 28513.70 | 04-SEP-02:22 | 24909.98 | 0.00 |
October | 0.00 | 0.00 | 0.949512E+09 | 0.923406E+09 | 28513.70 | 17-OCT-04:01 | 22055.45 | 0.00 |
November | 0.00 | 0.00 | 22248458.07 | 18359385.51 | 28513.70 | 18-NOV-03:01 | 22707.61 | 0.00 |
December | 0.00 | 0.00 | 1865924.23 | 1568642.75 | 2505.33 | 05-DEC-04:10 | 2197.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.513663E+11 | 0.475716E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1849533.74 | 1568642.75 | 2458.38 | 2062.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.171896E+11 | 0.160393E+11 | 28513.70 | 25750.26 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5805.42 | 21844.83 | 31-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5903.21 | 21964.06 | 19-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5857.98 | 21923.21 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5636.88 | 21375.37 | 01-APR-12:33 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5347.89 | 20360.19 | 01-MAY-12:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5040.33 | 19102.42 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4784.94 | 18008.68 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4696.93 | 17310.83 | 01-AUG-12:35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4744.79 | 17755.50 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4955.45 | 18794.00 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5259.20 | 20009.52 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5557.66 | 21145.53 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 5295.67 | ||||
Minimum of Months | 0.00 | 0.00 | 4696.93 | 17310.83 | ||
Maximum of Months | 0.00 | 0.00 | 5903.21 | 21964.06 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112907E+10 | 0.25 | 503.64 | 01-JAN-00:01 | 0.30 |
February | 0.102137E+10 | 0.25 | 503.64 | 01-FEB-00:01 | 0.30 |
March | 0.113294E+10 | 0.25 | 503.64 | 01-MAR-00:01 | 0.30 |
April | 0.112526E+10 | 0.26 | 503.64 | 01-APR-04:01 | 0.30 |
May | 0.118386E+10 | 0.26 | 503.64 | 01-MAY-04:01 | 0.30 |
June | 0.119772E+10 | 0.28 | 503.64 | 01-JUN-00:55 | 0.30 |
July | 0.127005E+10 | 0.28 | 503.64 | 01-JUL-00:15 | 0.30 |
August | 0.126563E+10 | 0.28 | 503.64 | 01-AUG-00:13 | 0.30 |
September | 0.119624E+10 | 0.28 | 503.64 | 01-SEP-00:16 | 0.30 |
October | 0.119431E+10 | 0.27 | 503.64 | 01-OCT-02:61 | 0.30 |
November | 0.112059E+10 | 0.26 | 503.64 | 01-NOV-03:45 | 0.30 |
December | 0.113542E+10 | 0.26 | 503.64 | 01-DEC-00:01 | 0.30 |
Annual Sum or Average | 0.139725E+11 | 0.27 | |||
Minimum of Months | 0.102137E+10 | 0.25 | 503.64 | 0.30 | |
Maximum of Months | 0.127005E+10 | 0.28 | 503.64 | 0.30 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.282889E+10 | 0.68 | 2113.25 | 06-JAN-03:01 | 1.01 |
February | 0.227339E+10 | 0.63 | 2113.25 | 01-FEB-03:06 | 1.01 |
March | 0.238579E+10 | 0.63 | 2113.25 | 01-MAR-03:45 | 1.01 |
April | 0.205917E+10 | 0.57 | 1758.95 | 29-APR-02:08 | 1.01 |
May | 0.203633E+10 | 0.55 | 1232.93 | 08-MAY-04:01 | 0.77 |
June | 0.185519E+10 | 0.52 | 1505.39 | 21-JUN-02:61 | 0.85 |
July | 0.192501E+10 | 0.53 | 1635.53 | 17-JUL-02:61 | 0.89 |
August | 0.191634E+10 | 0.53 | 1336.95 | 09-AUG-02:61 | 0.80 |
September | 0.188942E+10 | 0.53 | 1693.10 | 05-SEP-02:61 | 0.90 |
October | 0.203803E+10 | 0.54 | 1198.74 | 10-OCT-06:10 | 0.76 |
November | 0.221307E+10 | 0.59 | 2113.25 | 12-NOV-03:10 | 1.01 |
December | 0.262790E+10 | 0.65 | 2113.25 | 13-DEC-03:03 | 1.01 |
Annual Sum or Average | 0.260485E+11 | 0.58 | |||
Minimum of Months | 0.185519E+10 | 0.52 | 1198.74 | 0.76 | |
Maximum of Months | 0.282889E+10 | 0.68 | 2113.25 | 1.01 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.181382E+10 | 0.63 | 1374.40 | 29-JAN-05:02 | 1.00 |
February | 0.146440E+10 | 0.59 | 1156.89 | 10-FEB-05:03 | 0.92 |
March | 0.154020E+10 | 0.57 | 1072.35 | 04-MAR-23:30 | 0.89 |
April | 0.137301E+10 | 0.56 | 1508.18 | 07-APR-04:01 | 1.04 |
May | 0.140072E+10 | 0.56 | 1508.18 | 19-MAY-02:61 | 1.04 |
June | 0.136232E+10 | 0.58 | 1508.18 | 01-JUN-02:11 | 1.04 |
July | 0.151223E+10 | 0.61 | 1508.18 | 01-JUL-02:11 | 1.03 |
August | 0.148680E+10 | 0.60 | 1508.18 | 01-AUG-02:11 | 1.04 |
September | 0.138528E+10 | 0.58 | 1508.18 | 01-SEP-02:11 | 1.04 |
October | 0.139603E+10 | 0.56 | 1508.18 | 01-OCT-02:61 | 1.04 |
November | 0.144401E+10 | 0.57 | 1053.86 | 27-NOV-05:03 | 0.88 |
December | 0.166389E+10 | 0.60 | 1187.89 | 29-DEC-05:03 | 0.94 |
Annual Sum or Average | 0.178427E+11 | 0.58 | |||
Minimum of Months | 0.136232E+10 | 0.56 | 1053.86 | 0.88 | |
Maximum of Months | 0.181382E+10 | 0.63 | 1508.18 | 1.04 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.40 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.65 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.59 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.26 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 49.98 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 51.78 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 52.42 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 52.22 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 52.18 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.03 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.72 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.58 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.40 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 52.42 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 36.34 | 36.34 | 5805.42 | 21844.83 | 31-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.11 | 51.11 | 5903.21 | 21964.06 | 19-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.02 | 51.02 | 5857.98 | 21923.21 | 01-MAR-13:30 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.16 | 51.16 | 5636.88 | 21375.37 | 01-APR-12:33 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 37.23 | 37.23 | 5347.89 | 20360.19 | 01-MAY-12:35 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.62 | 51.62 | 5040.33 | 19102.42 | 01-JUN-12:20 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 51.94 | 51.94 | 4784.94 | 18008.68 | 01-JUL-12:40 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.00 | 52.00 | 4696.93 | 17310.83 | 01-AUG-12:35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.42 | 52.42 | 4744.79 | 17755.50 | 30-SEP-12:40 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.08 | 40.08 | 4955.45 | 18794.00 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.19 | 52.19 | 5259.20 | 20009.52 | 30-NOV-13:30 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.43 | 51.43 | 5557.66 | 21145.53 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 5295.67 | ||||||
Minimum of Months | 0.00 | 0.00 | 36.34 | 36.34 | 4696.93 | 17310.83 | ||
Maximum of Months | 0.00 | 0.00 | 52.42 | 52.42 | 5903.21 | 21964.06 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.282889E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.227339E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.238579E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.209513E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.246019E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.353707E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.534789E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.459962E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.324458E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.219340E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.221307E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.262790E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.358069E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.209513E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.534789E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.181438E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.146831E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.154089E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.145251E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.211001E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.366576E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.591040E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.501996E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.335275E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.165976E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145008E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166446E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.311093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.145008E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.591040E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.282889E+10 | 0.00 | 0.429676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227339E+10 | 0.00 | 0.260560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238579E+10 | 0.00 | 0.228968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205917E+10 | 0.121422E+09 | 0.109620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203633E+10 | 0.152521E+10 | 0.705590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185519E+10 | 0.632824E+10 | 0.113506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192501E+10 | 0.129051E+11 | 0.129340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191634E+10 | 0.100888E+11 | 0.365642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188942E+10 | 0.508309E+10 | 0.258253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203803E+10 | 0.541827E+09 | 0.724303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221307E+10 | 0.00 | 0.176420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262790E+10 | 0.00 | 0.334781E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260485E+11 | 0.365938E+11 | 0.172514E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185519E+10 | 0.00 | 0.129340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282889E+10 | 0.129051E+11 | 0.429676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.181382E+10 | 1849533.74 | 0.453240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146440E+10 | 12976646.36 | 0.240408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154020E+10 | 2288946.60 | 0.187384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137301E+10 | 0.274857E+09 | 0.627548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140072E+10 | 0.262818E+10 | 0.383093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136232E+10 | 0.894677E+10 | 0.186895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151223E+10 | 0.171116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148680E+10 | 0.136275E+11 | 416945.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138528E+10 | 0.760378E+10 | 0.679853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139603E+10 | 0.942541E+09 | 0.336245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144401E+10 | 21666778.58 | 0.132283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166389E+10 | 1865924.23 | 0.307261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178427E+11 | 0.511759E+11 | 0.146394E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136232E+10 | 1849533.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181382E+10 | 0.171116E+11 | 0.453240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.282889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.205917E+10 | 0.00 | 0.00 | 0.00 | 35961147.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203633E+10 | 0.00 | 0.00 | 0.00 | 0.423855E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.185519E+10 | 0.00 | 0.00 | 0.00 | 0.168187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192501E+10 | 0.00 | 0.00 | 0.00 | 0.342288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191634E+10 | 0.00 | 0.00 | 0.00 | 0.268328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.188942E+10 | 0.00 | 0.00 | 0.00 | 0.135515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203803E+10 | 0.00 | 0.00 | 0.00 | 0.155372E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.221307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.262790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.260485E+11 | 0.00 | 0.00 | 0.00 | 0.975837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.185519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.282889E+10 | 0.00 | 0.00 | 0.00 | 0.342288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.181382E+10 | 0.00 | 0.00 | 0.00 | 558847.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146440E+10 | 0.00 | 0.00 | 0.00 | 3908088.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154020E+10 | 0.00 | 0.00 | 0.00 | 690885.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137301E+10 | 0.00 | 0.00 | 0.00 | 79504185.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140072E+10 | 0.00 | 0.00 | 0.00 | 0.709291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136232E+10 | 0.00 | 0.00 | 0.00 | 0.230345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151223E+10 | 0.00 | 0.00 | 0.00 | 0.439817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148680E+10 | 0.00 | 0.00 | 0.00 | 0.353317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138528E+10 | 0.00 | 0.00 | 0.00 | 0.196747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139603E+10 | 0.00 | 0.00 | 0.00 | 0.263725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144401E+10 | 0.00 | 0.00 | 0.00 | 6065225.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166389E+10 | 0.00 | 0.00 | 0.00 | 567797.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178427E+11 | 0.00 | 0.00 | 0.00 | 0.132666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136232E+10 | 0.00 | 0.00 | 0.00 | 558847.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181382E+10 | 0.00 | 0.00 | 0.00 | 0.439817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.310478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317736E+11 | 0.00 | 0.00 | 3.62 |
February | 0.407673E+10 | 0.00 | 0.00 | 304862.96 | 0.00 | 0.201527E+11 | 0.237889E+09 | 0.00 | 3.61 |
March | 0.523154E+10 | 0.00 | 0.00 | 4392.92 | 0.00 | 0.186211E+11 | 21064977.64 | 0.00 | 3.61 |
April | 0.644171E+10 | 0.00 | 0.00 | 3108176.06 | 0.00 | 0.891043E+10 | 0.126178E+10 | 0.00 | 3.79 |
May | 0.656631E+10 | 11766160.69 | 0.00 | 12346019.61 | 0.00 | 0.521509E+10 | 0.285372E+10 | 0.00 | 4.25 |
June | 0.460238E+10 | 0.220900E+09 | 0.00 | 25454908.59 | 0.00 | 0.328058E+09 | 0.449431E+10 | 0.00 | 4.73 |
July | 0.224629E+10 | 0.763312E+09 | 0.00 | 38030834.56 | 0.00 | 251721.46 | 0.435746E+10 | 0.00 | 4.84 |
August | 0.300180E+10 | 0.501100E+09 | 0.00 | 34872981.40 | 0.00 | 10173134.49 | 0.530051E+10 | 0.00 | 4.96 |
September | 0.529778E+10 | 0.254225E+09 | 0.00 | 20884428.10 | 0.00 | 0.143018E+10 | 0.444055E+10 | 0.00 | 4.59 |
October | 0.879019E+10 | 0.00 | 0.00 | 5821732.69 | 0.00 | 0.472681E+10 | 0.219034E+10 | 0.00 | 3.94 |
November | 0.668964E+10 | 0.00 | 0.00 | 259423.99 | 0.00 | 0.140556E+11 | 0.295918E+09 | 0.00 | 3.56 |
December | 0.383407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263005E+11 | 0.00 | 0.00 | 3.62 |
Annual Sum or Average | 0.598832E+11 | 0.175130E+10 | 0.00 | 0.141088E+09 | 0.00 | 0.131524E+12 | 0.254535E+11 | 0.00 | 4.10 |
Minimum of Months | 0.224629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251721.46 | 0.00 | 0.00 | 3.56 |
Maximum of Months | 0.879019E+10 | 0.763312E+09 | 0.00 | 38030834.56 | 0.00 | 0.317736E+11 | 0.530051E+10 | 0.00 | 4.96 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.758582E+11 | 0.00 | 0.00 | 102866.36 | 5955385.96 | 64232348.47 | 0.116280E+09 | 0.00 | 8.50 |
February | 0.526550E+11 | 0.00 | 0.00 | 816660.41 | 0.00 | 16023496.42 | 0.118690E+10 | 0.00 | 8.13 |
March | 0.517221E+11 | 0.00 | 0.00 | 284424.16 | 0.00 | 3266330.49 | 0.584787E+09 | 0.00 | 8.03 |
April | 0.334998E+11 | 0.00 | 0.00 | 8806693.54 | 0.00 | 4276856.59 | 0.547387E+10 | 0.00 | 7.82 |
May | 0.253594E+11 | 0.00 | 0.00 | 31822972.22 | 0.00 | 1736635.32 | 0.107881E+11 | 0.00 | 7.87 |
June | 0.932962E+10 | 21209959.36 | 0.00 | 67623349.40 | 0.00 | 0.00 | 0.166840E+11 | 0.00 | 8.05 |
July | 0.396588E+10 | 0.646159E+09 | 0.00 | 96743564.64 | 0.00 | 0.00 | 0.161724E+11 | 0.00 | 8.30 |
August | 0.517364E+10 | 0.625209E+09 | 0.00 | 85103035.75 | 0.00 | 0.00 | 0.181511E+11 | 0.00 | 8.27 |
September | 0.127148E+11 | 0.225214E+09 | 0.00 | 52642067.89 | 0.00 | 0.00 | 0.152596E+11 | 0.00 | 8.08 |
October | 0.271303E+11 | 0.00 | 0.00 | 17497848.38 | 0.00 | 0.00 | 0.108457E+11 | 0.00 | 7.84 |
November | 0.421602E+11 | 0.00 | 0.00 | 3216311.26 | 0.00 | 9984294.78 | 0.430386E+10 | 0.00 | 7.90 |
December | 0.632875E+11 | 0.00 | 0.00 | 246526.04 | 0.00 | 22095767.28 | 0.507780E+09 | 0.00 | 8.26 |
Annual Sum or Average | 0.402856E+12 | 0.151779E+10 | 0.00 | 0.364906E+09 | 5955385.96 | 0.121616E+09 | 0.100074E+12 | 0.00 | 8.09 |
Minimum of Months | 0.396588E+10 | 0.00 | 0.00 | 102866.36 | 0.00 | 0.00 | 0.116280E+09 | 0.00 | 7.82 |
Maximum of Months | 0.758582E+11 | 0.646159E+09 | 0.00 | 96743564.64 | 5955385.96 | 64232348.47 | 0.181511E+11 | 0.00 | 8.50 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.123517E+11 | 0.227966E+11 | 0.152370E+12 | 0.00 | 0.379113E+11 |
February | 0.219453E+11 | 0.162879E+11 | 0.111278E+12 | 43834070.75 | 0.278969E+11 |
March | 0.407942E+11 | 0.159562E+11 | 0.111553E+12 | 0.00 | 0.287644E+11 |
April | 0.466461E+11 | 0.113522E+11 | 0.873230E+11 | 0.388411E+09 | 0.251274E+11 |
May | 0.638455E+11 | 0.100884E+11 | 0.806945E+11 | 0.111647E+10 | 0.319112E+11 |
June | 0.715181E+11 | 0.610977E+10 | 0.588898E+11 | 0.165644E+10 | 0.462943E+11 |
July | 0.718586E+11 | 0.364708E+10 | 0.451264E+11 | 0.163145E+10 | 0.683043E+11 |
August | 0.591735E+11 | 0.454215E+10 | 0.524274E+11 | 0.200761E+10 | 0.577364E+11 |
September | 0.429760E+11 | 0.680049E+10 | 0.637566E+11 | 0.152422E+10 | 0.398604E+11 |
October | 0.256077E+11 | 0.102375E+11 | 0.862654E+11 | 0.664826E+09 | 0.238987E+11 |
November | 0.111387E+11 | 0.133775E+11 | 0.101248E+12 | 13017433.98 | 0.225698E+11 |
December | 0.672246E+10 | 0.187579E+11 | 0.131765E+12 | 0.00 | 0.304348E+11 |
Annual Sum or Average | 0.474578E+12 | 0.139954E+12 | 0.108270E+13 | 0.904627E+10 | 0.440710E+12 |
Minimum of Months | 0.672246E+10 | 0.364708E+10 | 0.451264E+11 | 0.00 | 0.225698E+11 |
Maximum of Months | 0.718586E+11 | 0.227966E+11 | 0.152370E+12 | 0.200761E+10 | 0.683043E+11 |