Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26

Tabular Output Report in Format: HTML

Building: RestaurantFastFood

Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2023-10-16 08:26:26


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 1280.18 5509.88 5509.88
Net Site Energy 1280.18 5509.88 5509.88
Total Source Energy 2657.12 11436.20 11436.20
Net Source Energy 2657.12 11436.20 11436.20


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 232.34
Net Conditioned Building Area 232.34
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 25.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 183.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 24.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 15.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 265.86 477.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 63.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 168.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
Refrigeration 56.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 609.41 670.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 25.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 183.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 24.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 15.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment Cooking 233.46 477.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 14.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 17.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 63.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
  Water Heater 0.00 168.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 7.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 15.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 32.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 25.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 183.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 24.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 15.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 265.86 477.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 63.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 168.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 775.38
Refrigeration Unassigned 56.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 171.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 1065.59 833.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34
Other 1386.10 2053.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 2622.89 2886.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 171.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 1065.59 833.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34
Other 1386.10 2053.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 2622.89 2886.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.34


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 609.411 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 609.411 100.00
     
Total On-Site and Utility Electric Sources 609.411 100.00
Total Electricity End Uses 609.411 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 775.38 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 775.38 100.00
Total Water End Uses 775.38 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 780.17
Time Not Comfortable Based on Simple ASHRAE 55-2004 5855.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

| Environment |

ZoneCoolingSummaryMonthly

| DINING | KITCHEN | ATTIC |

ZoneHeatingSummaryMonthly

| DINING | KITCHEN | ATTIC |

ZoneElectricSummaryMonthly

| DINING | KITCHEN |

SpaceGainsMonthly

| DINING | KITCHEN | ATTIC |

PeakSpaceGainsMonthly

| DINING | KITCHEN | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| DINING | KITCHEN | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| DINING | KITCHEN | ATTIC |

ComfortReportSimple55Monthly

| DINING | KITCHEN | ATTIC |

OccupantComfortDataSummaryMonthly

| DINING | KITCHEN |

DXReportMonthly

| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |

WindowReportMonthly

| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| DINING | KITCHEN | ATTIC |

WindowEnergyZoneSummaryMonthly

| DINING | KITCHEN | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| Environment |

CoilReportMonthly

| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| DINING | KITCHEN | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC_1:1 | PSZ-AC_2:2 |

MechanicalVentilationLoadsMonthly

| DINING | KITCHEN |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
RunPeriod RUNPERIOD 1
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [m] 8.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Above Ground Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Window Opening Area [m2] 26.02 0.00 6.50 13.01 6.50
Gross Window-Wall Ratio [%] 14.00 0.00 14.00 27.99 14.00
Above Ground Window-Wall Ratio [%] 14.00 0.00 14.00 27.99 14.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Above Ground Wall Area [m2] 185.89 46.47 46.47 46.47 46.47
Window Opening Area [m2] 26.02 0.00 6.50 13.01 6.50
Gross Window-Wall Ratio [%] 14.00 0.00 14.00 27.99 14.00
Above Ground Window-Wall Ratio [%] 14.00 0.00 14.00 27.99 14.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 258.86
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
DINING 116.17 Yes Yes 354.18 1.00 92.94 0.00 26.02 26.02 7.1446 1.33 116.7869
KITCHEN 116.17 Yes Yes 354.18 1.00 92.94 0.00 0.00 0.00 9.9598 18.52 1071.0790
ATTIC 232.34 No No 262.34 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 232.34     708.37   185.89 0.00 26.02 26.02 8.5522 2.48 593.9329
Conditioned Total 232.34     708.37   185.89 0.00 26.02 26.02 8.5522 2.48 593.9329
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 232.34     262.34   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
DINING 116.17 Yes Yes 1.00 DINING GENERAL DINING 7.1446 1.33 116.7869  
KITCHEN 116.17 Yes Yes 1.00 KITCHEN GENERAL KITCHEN 9.9598 18.52 1071.0790  
ATTIC 232.34 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 232.34             8.5522 1.24 593.9329  
Conditioned Total 232.34             8.5522 1.24 593.9329  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 232.34             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 232.34 232.34 0.00 232.34 8.5522 2.48 593.9329
Total 232.34 232.34 0.00 232.34      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 09-SEP-18:40 05-FEB-04:10 - - - - - - - - - - 01-JAN-13:09
Heating 0.00 71708.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 21561.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1583.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1372.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 10924.69 4596.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3996.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 720.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 1952.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 41390.19 77024.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 71708.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 21561.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 1583.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 1372.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment Cooking 9897.19 4596.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInFreezer 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ReachInRefrigerator 570.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 3996.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 720.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 193.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  LowTempRefrigeration 682.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  MedTempRefrigeration 1076.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 27.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 582.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 76.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 49.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 841.99 517.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 201.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 182.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 177.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1930.00 727.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 118.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2506.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 329.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 212.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3623.92 2226.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 868.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 784.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 765.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 8306.70 3129.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 118.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2506.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 329.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 212.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3623.92 2226.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 868.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 784.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 765.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 8306.70 3129.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
DINING DIRECT AIR 2.15
KITCHEN DIRECT AIR 1.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC_1:1 2.15 2.15 2.15 2.15 2.15 2.15 1.00 1.00 2.15
PSZ-AC_2:2 1.26 1.26 1.26 1.26 1.26 1.26 1.00 1.00 1.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC_1:1_OA_CONTROLLER 2.15 0.416056
PSZ-AC_2:2_OA_CONTROLLER 1.26 1.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:SystemModel

Design Size Design Maximum Air Flow Rate [m3/s] Design Electric Power Consumption [W]
PSZ-AC_1:1_ADDAQ FAN 2.15 2298.68
PSZ-AC_2:2_ADDAQ FAN 1.26 1392.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitarySystem

Design Size Supply Air Flow Rate [m3/s] Design Size Heating Supply Air Flow Rate [m3/s] Design Size Cooling Supply Air Flow Rate [m3/s] Design Size No Load Supply Air Flow Rate [m3/s] User-Specified Nominal Cooling Capacity [W] Design Size Nominal Heating Capacity [W] Design Size Maximum Supply Air Temperature [C] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC_1:1_UNITARY_PACKAGE_DX 2.15 2.15 2.15 1.42 53344.97 57366.52 40.00 1.00
PSZ-AC_2:2_UNITARY_PACKAGE_DX 1.26 1.26 1.26 0.829822 31221.92 54456.50 40.00 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:MultiSpeed

User-Specified Speed 2 Rated Air Flow Rate [m3/s] Design Size Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 1 Rated Air Flow Rate [m3/s] User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] User-Specified Speed 2 Rated Sensible Heat Ratio User-Specified Speed 1 Rated Sensible Heat Ratio
PSZ-AC_1:1 COOLING COIL 2.15 1.07 1.43 53344.97 26672.49 0.701080 0.701080
PSZ-AC_2:2 COOLING COIL 1.26 0.628653 0.838207 31221.92 15610.96 0.701080 0.701080
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC_1:1 HEATING COIL 57366.52
PSZ-AC_2:2 HEATING COIL 54456.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000096 0.011518
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000096 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000096
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
DINING_WALL_EAST DINING_WALL_EAST_WINDOW |
DINING_WALL_SOUTH DINING_WALL_SOUTH_WINDOW |
DINING_WALL_WEST DINING_WALL_WEST_WINDOW |
KITCHEN_WALL_EAST KITCHEN_WALL_EAST_DOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 24.20 18.90 15.70 13.60 15.50 17.10 21.20 26.90 27.60 27.90 27.40 26.20


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tampa-MacDill AFB FL USA TMY3 WMO#=747880 27.85 -82.52 -5.00 8.00 101229 1.2032


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.85 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 RestaurantFastFood 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 3 24 4


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 DINING 0.0 0.00 0.00 0.00 7.62 3.81 1.52 1 1 1 0.00 15.24 0.00 7.62 0.00 3.05 3.05 354.18 TARP TARP 116.17 92.94 66.93 26.02 6 3 0 Yes
2 KITCHEN 0.0 0.00 0.00 0.00 7.62 11.43 1.52 1 1 1 0.00 15.24 7.62 15.24 0.00 3.05 3.05 354.18 TARP TARP 116.17 92.94 90.99 0.00 6 1 0 Yes
3 ATTIC 0.0 0.00 0.00 3.05 7.62 7.62 3.64 1 1 1 0.00 15.24 0.00 15.24 3.05 5.59 1.27 262.34 TARP TARP 232.34 0.00 0.00 0.00 6 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 DINING 116.17 87.5 1.327 0.754 7.145 116.787 0.000 0.000 0.000 0.000 123.932 No
2 KITCHEN 116.17 6.3 18.518 5.400E-002 9.960 279.726 791.353 0.000 0.000 0.000 1081.039 No
3 ATTIC 232.34 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DINING BLDG_OCC_SCH DINING 116.17 87.5 87.5 0.754 1.327 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 88 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 KITCHEN BLDG_OCC_SCH KITCHEN 116.17 6.3 6.3 5.400E-002 18.518 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 DINING_LIGHTS LTG_SCH_DINING DINING 116.17 87.5 829.995 7.145 9.481 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 829.995
2 KITCHEN_LIGHTS LTG_SCH_KITCHEN KITCHEN 116.17 6.3 1157.049 9.960 184.440 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1157.049


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 DINING_MISCELEC_EQUIP BLDG_EQUIP_SCH DINING 116.17 87.5 13567.311 116.787 154.976 0.250 0.300 0.000 0.450 Cooking 0.000 3934.520
2 KITCHEN_MISCELEC_EQUIP BLDG_EQUIP_SCH KITCHEN 116.17 6.3 31468.723 270.882 5016.295 0.250 0.300 0.300 0.150 Cooking 0.000 9125.930
3 KITCHEN_REACH-IN-FREEZER ALWAYS_ON KITCHEN 116.17 6.3 457.500 3.938 72.928 0.000 0.250 0.000 0.750 ReachInFreezer 457.500 457.500
4 KITCHEN_REACH-IN-REFRIGERATOR ALWAYS_ON KITCHEN 116.17 6.3 570.000 4.907 90.861 0.000 0.250 0.000 0.750 ReachInRefrigerator 570.000 570.000


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 KITCHEN_MISCGAS_EQUIP FF_GAS_EQUIP_SCH KITCHEN 116.17 6.3 91932.601 791.353 14654.584 0.100 0.200 0.700 0.000 Cooking 0.000 26660.454


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 ATTICROOFDECK 6 2 4 0.167 4.706 0.900 0.900 0.700 0.700 VeryRough
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 NONRES_ROOF 17 2 4 0.167 0.1579 0.900 0.900 0.700 0.700 MediumSmooth
6 NONRES_ROOF_FLOOR 20 2 4 0.167 0.1579 0.900 0.900 0.700 0.700 MediumSmooth
7 NONRES_EXT_WALL_GRD 23 4 7 0.167 0.6929 0.900 0.900 0.700 0.700 Smooth
8 DINING_FLOOR_FFACTOR 42 2 7 0.167 0.3496 0.000 0.900 0.000 0.700 MediumRough
9 KITCHEN_FLOOR_FFACTOR 43 2 7 0.167 0.3496 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 F12 ASPHALT SHINGLES 0.0032 0.040 1120.000 1260.000 0.8000E-01
4 G02 16MM PLYWOOD 0.0159 0.120 544.000 1210.000 0.1325
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
7 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.235
8 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
9 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
10 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.235
11 F07 25MM STUCCO 0.0254 0.720 1856.000 840.000 0.3528E-01
12 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
13 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 1.209
14 G01 16MM GYPSUM BOARD 0.0159 0.160 800.000 1090.000 0.9938E-01
15 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.784
16 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
17 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.784
18 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 4 0.12552254E-09 0.24226224E-10 0.35972174E-10 -0.14154396E-16
14 3 -0.27173896E-03 0.71777257E-04 -0.16206070E-03 0.11981077E-09
15 2 0.48258702 0.15872105 0.47241503 -0.16497355E-03
16 1 -7.8004821 2.4804491 -9.1443147 0.17387321
17 0 11.206599 1.2491899 12.560494  
18 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
19 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
20 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
21 1 -12.650482 3.3590720 -12.650482 0.19281313
22 0 16.907513 1.4507143 16.907513  
23 4 0.22189424E-16 0.18036394E-15 0.14382820E-13 -0.35882886E-16
24 3 -0.84544447E-08 0.11431503E-06 -0.59212216E-04 0.16308097E-12
25 2 0.59356505E-04 0.24350950E-02 1.1796048 -0.77969909E-04
26 1 -0.55627393E-01 0.62087406E-01 -17.347049 0.34328241
27 0 0.15925904 0.39168381E-01 16.271195  
28 4 0.14382820E-13 0.18036394E-15 0.22189424E-16 -0.35882886E-16
29 3 -0.59212216E-04 0.11431503E-06 -0.84544447E-08 0.16308097E-12
30 2 1.1796048 0.24350950E-02 0.59356505E-04 -0.77969909E-04
31 1 -17.347049 0.62087406E-01 -0.55627393E-01 0.34328241
32 0 16.271195 0.39168381E-01 0.15925904  
33 7 -0.33002231E-12 0.10712597E-14 -0.10720425E-12 0.10137879E-15
34 6 0.29661659E-07 0.19687232E-09 0.67865745E-08 -0.14052424E-12
35 5 -0.19512200E-03 0.16741682E-05 -0.10029371E-03 0.67057946E-08
36 4 0.29799499 0.81016957E-03 0.10178761 -0.34398158E-04
37 3 -7.3821031 0.24971312E-01 -2.3732702 0.29576512E-01
38 2 41.252923 0.88368331E-01 15.405914 -0.33759269
39 1 -80.838295 0.39713828E-01 -29.267905 1.0848528
40 0 46.824337 0.79570062E-03 16.288235  
41 7 -0.11889135E-08 -0.13101661E-15 0.72805024E-14 -0.91252007E-16
42 6 0.97710136E-05 0.67347286E-08 0.31779875E-02 -0.26659623E-04
43 5 -0.70792317E-03 0.39963827E-05 -0.22304912 0.19501884E-02
44 4 0.16314426E-01 0.18199987E-03 4.8182940 -0.45156824E-01
45 3 -0.14334616 0.14483103E-02 -37.957847 0.39795111
46 2 0.50909124 0.24102133E-02 116.36021 -1.4162842
47 1 -0.73485211 0.73528917E-03 -143.83447 2.0478426
48 0 0.35828816 0.17591693E-04 60.838472  
49 7 -0.11889135E-08 -0.13101661E-15 0.72805024E-14 -0.91252007E-16
50 6 0.97710136E-05 0.67347286E-08 0.31779875E-02 -0.26659623E-04
51 5 -0.70792317E-03 0.39963827E-05 -0.22304912 0.19501884E-02
52 4 0.16314426E-01 0.18199987E-03 4.8182940 -0.45156824E-01
53 3 -0.14334616 0.14483103E-02 -37.957847 0.39795111
54 2 0.50909124 0.24102133E-02 116.36021 -1.4162842
55 1 -0.73485211 0.73528917E-03 -143.83447 2.0478426
56 0 0.35828816 0.17591693E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 NONRESWINDOW_U_0.537_SHGC_SOUTH_0.25 38 1 VerySmooth 3.053 3.053 1.000 0.251    
2 NONRESWINDOW_U_0.537_SHGC_NORTH_0.25 39 1 VerySmooth 3.053 3.053 1.000 0.251    
3 NONRESWINDOW_U_0.537_SHGC_EAST_0.25 40 1 VerySmooth 3.053 3.053 1.000 0.251    
4 NONRESWINDOW_U_0.537_SHGC_WEST_0.25 41 1 VerySmooth 3.053 3.053 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 NONRES WINDOW GLAZING LAYER SOUTH SpectralAverage   1.38652E-002 0.16139 0.60641 0.60641 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 8.79195E-002 1.00000 No
2 NONRES WINDOW GLAZING LAYER NORTH SpectralAverage   1.38652E-002 0.16139 0.60641 0.60641 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 8.79195E-002 1.00000 No
3 NONRES WINDOW GLAZING LAYER EAST SpectralAverage   1.38652E-002 0.16139 0.60641 0.60641 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 8.79195E-002 1.00000 No
4 NONRES WINDOW GLAZING LAYER WEST SpectralAverage   1.38652E-002 0.16139 0.60641 0.60641 0.27500 0.15630 0.22588 0.00000 0.84000 0.84000 8.79195E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 DINING 3 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 DINING 0  


#Refrigeration Compressor Racks

Number of Refrigeration Compressor Racks
1 2


Refrigeration Compressor Rack

Compressor Rack Name # Refrigerated Cases Connected # WalkIn Coolers Connected Heat Rejection Location Condenser Type COP
1 RACK1 1 0 Zone Air-Cooled 1.500
2 RACK2 1 0 Zone Air-Cooled 3.000


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.3785 29307.1 1.053 0.3093


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 DINING_WALL_EAST 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.28 3 No No
2 DINING_WALL_EAST_WINDOW 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.28 2 No No
3 DINING_WALL_SOUTH 0 46.47 36.58 3.05 0 3.05 30.49 10.16 0.28 3 No No
4 DINING_WALL_SOUTH_WINDOW 0 46.47 36.58 3.05 0 3.05 30.49 10.16 0.28 2 No No
5 DINING_WALL_WEST 0 73.85 42.08 5.59 0 3.05 30.49 10.16 0.28 3 No No
6 DINING_WALL_WEST_WINDOW 0 73.85 42.08 5.59 0 3.05 30.49 10.16 0.28 2 No No
7 DINING_WALL_NORTH 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.28 0 No No
8 DINING_FLOOR 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.28 0 No No
9 DINING_CEILING 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.28 0 No No
10 DINING_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.28 0 No No
11 KITCHEN_WALL_NORTH 0 46.47 49.21 3.05 0 3.05 30.49 10.16 0.00 0 No No
12 KITCHEN_WALL_EAST 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.00 0 No No
13 KITCHEN_WALL_EAST_DOOR 0 73.85 54.29 5.59 0 3.05 30.49 10.16 0.00 0 No No
14 KITCHEN_WALL_WEST 0 73.85 42.08 5.59 0 3.05 30.49 10.16 0.00 0 No No
15 DINING_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
16 KITCHEN_FLOOR 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
17 KITCHEN_CEILING 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
18 KITCHEN_INTERNALMASS_1 0 0.00 0.00 0.00 0 3.05 30.49 10.16 0.00 0 No No
19 ATTIC-FLOOR-DINNING 0 0.00 0.00 0.00 0 1.27 0.00 15.24 -999.00 0 No No
20 ATTIC-FLOOR-KITCHEN 0 0.00 0.00 0.00 0 1.27 0.00 15.24 -999.00 0 No No
21 WEST-ROOF 0 73.85 42.08 5.59 0 1.27 0.00 15.24 -999.00 0 No No
22 EAST-ROOF 0 73.85 54.29 5.59 0 1.27 0.00 15.24 -999.00 0 No No
23 NORTH-ROOF 0 204.09 60.97 2.54 0 1.27 0.00 15.24 -999.00 0 No No
24 SOUTH-ROOF 0 204.09 60.97 2.54 0 1.27 0.00 15.24 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 DINING_INFILTRATION INFIL_SCH_PNNL DINING 116.17 87.5 5.294E-002 4.557E-004 5.696E-004 0.538 0.000 0.000 0.224 0.000
2 DINING_DOOR_INFILTRATION DOOR_INFIL_SCH DINING 116.17 87.5 0.903 7.772E-003 9.714E-003 9.177 1.000 0.000 0.000 0.000
3 KITCHEN_INFILTRATION INFIL_SCH_PNNL KITCHEN 116.17 6.3 5.294E-002 4.557E-004 5.579E-004 0.538 0.000 0.000 0.224 0.000
4 ATTIC_INFILTRATION ALWAYS_ON ATTIC 232.34 0.0 7.290E-002 3.138E-004 2.816E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 DINING Mixing/Well-Stirred
2 KITCHEN Mixing/Well-Stirred
3 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone DINING 1.2000
3 Zone KITCHEN 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone DINING 1.2000
3 Zone KITCHEN 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.7076E-003
2 Clear Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 1.3383E-002
3 Clear Turbid Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.5759E-003
4 Clear Turbid Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 1.2152E-002
5 Intermediate Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.4188E-003
6 Intermediate Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 1.3691E-002
7 Overcast Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT1 1.0943E-003
8 Overcast Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_EAST_WINDOW DINING_DAYLREFPT2 1.0886E-002
9 Clear Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 3.7143E-002
10 Clear Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 3.5809E-002
11 Clear Turbid Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 4.0648E-002
12 Clear Turbid Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 3.9078E-002
13 Intermediate Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 2.8978E-002
14 Intermediate Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 2.8164E-002
15 Overcast Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT1 1.1787E-002
16 Overcast Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_SOUTH_WINDOW DINING_DAYLREFPT2 1.1787E-002
17 Clear Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 1.0442E-002
18 Clear Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.3973E-003
19 Clear Turbid Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 8.7015E-003
20 Clear Turbid Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.1983E-003
21 Intermediate Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 9.9659E-003
22 Intermediate Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.0956E-003
23 Overcast Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT1 1.0887E-002
24 Overcast Sky 01/21 DINING_DAYLCTRL DINING DINING_WALL_WEST_WINDOW DINING_DAYLREFPT2 1.0943E-003


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 DINING Cooling 24301.89255 29162.27106 1.79017 2.14820 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 33.90000 1.65364E-002 116.17148 87.54444 0.41606 0.00000
2 DINING Heating 2504.91229 3005.89475 0.10465 0.41606 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:00:00 4.60000 5.25715E-003 116.17148 87.54444 0.41606 0.00000
3 KITCHEN Cooling 17110.94189 20533.13026 1.04776 1.25731 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 33.18900 1.65350E-002 116.17148 6.27330 1.14133 0.00000
4 KITCHEN Heating 0.00000 0.00000 0.00000 1.14133   00:10:00 4.60000 5.25715E-003 116.17148 6.27330 1.14133 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC_1:1 Cooling Sensible 33764.28 2.14820 2.14820 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 PSZ-AC_1:1 Heating Sensible 17806.81 0.41606 0.41606 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
3 PSZ-AC_2:2 Cooling Sensible 29993.22 1.25731 1.25731 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 PSZ-AC_2:2 Heating Sensible 48847.99 1.14133 1.14133 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat DINING DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 2.14820
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat KITCHEN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 1.25731
3 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 2.14820
4 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.14820
5 AirLoopHVAC PSZ-AC_1:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 2.14820
6 AirLoopHVAC PSZ-AC_1:1 Adjusted Heating Design Air Flow Rate [m3/s] 2.14820
7 AirLoopHVAC PSZ-AC_1:1 Adjusted Cooling Design Air Flow Rate [m3/s] 2.14820
8 AirLoopHVAC PSZ-AC_1:1 Adjusted Main Design Air Flow Rate [m3/s] 2.14820
9 AirLoopHVAC PSZ-AC_1:1 User Heating Air Flow Ratio [] 1.00000
10 AirLoopHVAC PSZ-AC_1:1 Calculated Heating Air Flow Ratio [] 1.00000
11 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 1.25731
12 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 1.25731
13 AirLoopHVAC PSZ-AC_2:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 1.25731
14 AirLoopHVAC PSZ-AC_2:2 Adjusted Heating Design Air Flow Rate [m3/s] 1.25731
15 AirLoopHVAC PSZ-AC_2:2 Adjusted Cooling Design Air Flow Rate [m3/s] 1.25731
16 AirLoopHVAC PSZ-AC_2:2 Adjusted Main Design Air Flow Rate [m3/s] 1.25731
17 AirLoopHVAC PSZ-AC_2:2 User Heating Air Flow Ratio [] 1.00000
18 AirLoopHVAC PSZ-AC_2:2 Calculated Heating Air Flow Ratio [] 1.00000
19 AirLoopHVAC PSZ-AC_1:1 Design Supply Air Flow Rate [m3/s] 2.14820
20 AirLoopHVAC PSZ-AC_2:2 Design Supply Air Flow Rate [m3/s] 1.25731
21 Controller:OutdoorAir PSZ-AC_1:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 2.14820
22 Controller:OutdoorAir PSZ-AC_1:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.41606
23 Fan:SystemModel PSZ-AC_1:1_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 2.14820
24 Fan:SystemModel PSZ-AC_1:1_ADDAQ FAN Design Electric Power Consumption [W] 2298.67768
25 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 2.14820
26 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 2.14820
27 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 2.14820
28 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 1.41781
29 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 2.14820
30 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 1.07410
31 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 1.43213
32 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 53344.97000
33 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 26672.48500
34 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
35 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
36 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 53344.97000
37 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 57366.51518
38 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
39 AirLoopHVAC:UnitarySystem PSZ-AC_1:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
40 Coil:Heating:Fuel PSZ-AC_1:1 HEATING COIL Design Size Nominal Capacity [W] 57366.51518
41 Controller:OutdoorAir PSZ-AC_2:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 1.25731
42 Controller:OutdoorAir PSZ-AC_2:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.14133
43 Fan:SystemModel PSZ-AC_2:2_ADDAQ FAN Design Size Design Maximum Air Flow Rate [m3/s] 1.25731
44 Fan:SystemModel PSZ-AC_2:2_ADDAQ FAN Design Electric Power Consumption [W] 1392.03796
45 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Supply Air Flow Rate [m3/s] 1.25731
46 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Heating Supply Air Flow Rate [m3/s] 1.25731
47 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Cooling Supply Air Flow Rate [m3/s] 1.25731
48 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size No Load Supply Air Flow Rate [m3/s] 0.82982
49 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Rated Air Flow Rate [m3/s] 1.25731
50 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL Design Size Speed 1 Rated Air Flow Rate [m3/s] 0.62865
51 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Rated Air Flow Rate [m3/s] 0.83821
52 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] 31221.92000
53 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] 15610.96000
54 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 2 Rated Sensible Heat Ratio 0.70108
55 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL User-Specified Speed 1 Rated Sensible Heat Ratio 0.70108
56 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX User-Specified Nominal Cooling Capacity [W] 31221.92000
57 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Nominal Heating Capacity [W] 54456.50074
58 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Design Size Maximum Supply Air Temperature [C] 40.00000
59 AirLoopHVAC:UnitarySystem PSZ-AC_2:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
60 Coil:Heating:Fuel PSZ-AC_2:2 HEATING COIL Design Size Nominal Capacity [W] 54456.50074
61 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 9.59800E-005
62 PlantLoop SWHSYS1 Plant Loop Volume [m3] 1.15176E-002
63 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 9.59800E-005
64 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 4.10171E-007
65 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 9.59800E-005


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:MultiSpeed PSZ-AC_1:1 COOLING COIL 51818.1     11.66 11.61  
2 Coil:Cooling:DX:MultiSpeed PSZ-AC_2:2 COOLING COIL 30328.3     11.84 11.78  


Zone Surfaces

Zone Name # Surfaces
1 DINING 10
2 KITCHEN 8
3 ATTIC 6


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 DINING_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.693 0.628   16.73 23.24 16.73 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
2 DINING_WALL_EAST_WINDOW Window DINING_WALL_EAST Window5 Detailed Fenestration NONRESWINDOW_U_0.537_SHGC_EAST_0.25 N/A 3.053 No 6.50 6.50 6.50 90.00 90.00 7.11 0.91 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
3 DINING_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.693 0.628   33.46 46.47 33.46 180.00 90.00 15.24 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
4 DINING_WALL_SOUTH_WINDOW Window DINING_WALL_SOUTH Window5 Detailed Fenestration NONRESWINDOW_U_0.537_SHGC_SOUTH_0.25 N/A 3.053 No 13.01 13.01 13.01 180.00 90.00 14.23 0.91 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
5 DINING_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.693 0.628   16.73 23.24 16.73 270.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
6 DINING_WALL_WEST_WINDOW Window DINING_WALL_WEST Window5 Detailed Fenestration NONRESWINDOW_U_0.537_SHGC_WEST_0.25 N/A 3.053 No 6.50 6.50 6.50 270.00 90.00 7.11 0.91 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
7 DINING_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.47 46.47 46.47 0.00 90.00 15.24 3.05 0.00 DINING_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
8 DINING_FLOOR Floor   CTF - ConductionTransferFunction DINING_FLOOR_FFACTOR 0.350 0.322   116.17 116.17 116.17 0.00 180.00 15.24 7.62 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
9 DINING_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.158 0.153   116.17 116.17 116.17 180.00 0.00 15.24 7.62 0.00 ATTIC-FLOOR-DINNING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 DINING_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   232.34 232.34 232.34 0.00 90.00 232.34 1.00 0.00 DINING_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 KITCHEN_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.693 0.628   46.47 46.47 46.47 0.00 90.00 15.24 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
12 KITCHEN_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.693 0.628   21.29 23.24 21.29 90.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
13 KITCHEN_WALL_EAST_DOOR Door KITCHEN_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
14 KITCHEN_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 0.693 0.628   23.24 23.24 23.24 270.00 90.00 7.62 3.05 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
15 DINING_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   46.47 46.47 46.47 180.00 90.00 15.24 3.05 0.00 DINING_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
16 KITCHEN_FLOOR Floor   CTF - ConductionTransferFunction KITCHEN_FLOOR_FFACTOR 0.350 0.322   116.17 116.17 116.17 0.00 180.00 15.24 7.62 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
17 KITCHEN_CEILING Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.158 0.153   116.17 116.17 116.17 180.00 0.00 15.24 7.62 0.00 ATTIC-FLOOR-KITCHEN Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 KITCHEN_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   232.34 232.34 232.34 0.00 90.00 232.34 1.00 0.00 KITCHEN_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 ATTIC-FLOOR-DINNING Floor   CTF - ConductionTransferFunction NONRES_ROOF_FLOOR 0.158 0.152   116.17 116.17 116.17 180.00 180.00 15.24 7.62 0.00 DINING_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
20 ATTIC-FLOOR-KITCHEN Floor   CTF - ConductionTransferFunction NONRES_ROOF_FLOOR 0.158 0.152   116.17 116.17 116.17 0.00 180.00 15.24 7.62 0.00 KITCHEN_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
21 WEST-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   27.38 27.38 27.38 270.00 45.00 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.15 0.85 0.15 0.85 3
22 EAST-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   27.38 27.38 27.38 90.00 45.00 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.15 0.85 0.15 0.85 3
23 NORTH-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   102.05 102.05 102.05 0.00 18.44 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 2.57E-002 0.97 2.57E-002 0.97 4
24 SOUTH-ROOF Roof   CTF - ConductionTransferFunction ATTICROOFDECK 4.706 2.494   102.05 102.05 102.05 180.00 18.44 8.43 15.24 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 2.57E-002 0.97 2.57E-002 0.97 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 DINING RunPeriod: RUNPERIOD 1 9.2753310940E-002 0.2565420689 Pass Pass 6.3346529282E-002 0.1608531536 Pass Pass
2 KITCHEN RunPeriod: RUNPERIOD 1 0.2423773174 0.6802562451 Pass Pass 0.1405943714 0.4209567356 Pass Pass
3 ATTIC RunPeriod: RUNPERIOD 1 0.4806261227 0.4797606647 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 605.65 -27.2 37.26 6.91 1288.71 1911.31



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 4.60 0.00 4.60 Wetbulb [C] 2.50 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 33.90 7.90 25.10 Wetbulb [C] 3.10 270.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 66.00 12      
Feb 66.00 22      
Mar 126.00 32      
Apr 206.00 19      
May 144.00 46      
Jun 99.00 30      
Jul 192.00 52      
Aug 240.00 34      
Sep 310.00 44      
Oct 34.00 10      
Nov 63.00 12      
Dec 35.00 24      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.628 0.693 23.24 16.73 90.00 90.00 E
DINING_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.628 0.693 46.47 33.46 180.00 90.00 S
DINING_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.628 0.693 23.24 16.73 270.00 90.00 W
DINING_FLOOR DINING_FLOOR_FFACTOR 1.00 0.331 0.350 116.17 116.17 0.00 180.00  
KITCHEN_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.628 0.693 46.47 46.47 0.00 90.00 N
KITCHEN_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.628 0.693 23.24 21.29 90.00 90.00 E
KITCHEN_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.628 0.693 23.24 23.24 270.00 90.00 W
KITCHEN_FLOOR KITCHEN_FLOOR_FFACTOR 1.00 0.331 0.350 116.17 116.17 0.00 180.00  
WEST-ROOF ATTICROOFDECK 0.30 2.858 4.706 27.38 27.38 270.00 45.00  
EAST-ROOF ATTICROOFDECK 0.30 2.858 4.706 27.38 27.38 90.00 45.00  
NORTH-ROOF ATTICROOFDECK 0.30 2.858 4.706 102.05 102.05 0.00 18.44  
SOUTH-ROOF ATTICROOFDECK 0.30 2.858 4.706 102.05 102.05 180.00 18.44  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_NORTH INT_WALL 0.30 2.511 6.299 46.47 46.47 0.00 90.00 N
DINING_CEILING NONRES_ROOF 0.30 0.151 0.158 116.17 116.17 180.00 0.00  
DINING_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 46.47 46.47 180.00 90.00 S
KITCHEN_CEILING NONRES_ROOF 0.30 0.151 0.158 116.17 116.17 180.00 0.00  
ATTIC-FLOOR-DINNING NONRES_ROOF_FLOOR 0.30 0.151 0.158 116.17 116.17 180.00 180.00  
ATTIC-FLOOR-KITCHEN NONRES_ROOF_FLOOR 0.30 0.151 0.158 116.17 116.17 0.00 180.00  
DINING_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 232.34   0.00 90.00 N
KITCHEN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 232.34   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
DINING_WALL_EAST_WINDOW NONRESWINDOW_U_0.537_SHGC_EAST_0.25   6.50 0.00 0.00 6.50 6.50 3.053 0.251 0.276             No DINING_WALL_EAST 90.00 90.00 E
DINING_WALL_SOUTH_WINDOW NONRESWINDOW_U_0.537_SHGC_SOUTH_0.25   13.01 0.00 0.00 13.01 13.01 3.053 0.251 0.276             No DINING_WALL_SOUTH 180.00 90.00 S
DINING_WALL_WEST_WINDOW NONRESWINDOW_U_0.537_SHGC_WEST_0.25   6.50 0.00 0.00 6.50 6.50 3.053 0.251 0.276             No DINING_WALL_WEST 270.00 90.00 W
Total or Average             26.02 3.053 0.251 0.276                      
North Total or Average             0.00 - - -                      
Non-North Total or Average             26.02 3.053 0.251 0.276                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
KITCHEN_WALL_EAST_DOOR SWINGING DOOR_CON 1.598 2.101 1.95 KITCHEN_WALL_EAST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
DINING_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
DINING_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
DINING_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
DINING_LIGHTS DINING DINING GENERAL 7.1446 116.17 830.00 LightsWired LTG_SCH_DINING 88.95 168.00 42.92 0.0000 Y 6.69
KITCHEN_LIGHTS KITCHEN KITCHEN GENERAL 9.9598 116.17 1157.05 LightsWired LTG_SCH_KITCHEN 84.44 168.00 80.60 0.0000 Y 17.51
Interior Lighting Total       8.5522 232.34 1987.04               24.19


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
DINING_DAYLREFPT1 DINING DINING_DAYLCTRL SplitFlux Stepped 0.38 830.00 315.40
DINING_DAYLREFPT2 DINING DINING_DAYLCTRL SplitFlux Stepped 0.38 830.00 315.40


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 218.22 AstronomicalClock -   48.73 48.73 2.00
EXTERIOR_LIGHTS_B 1154.09 AstronomicalClock -   83.73 62.73 13.59
Exterior Lighting Total 1372.31           15.58



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed   53344.97 37399.09 15945.88 0.70 3.73    
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed   31221.92 21889.06 9332.86 0.70 3.80    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC_1:1 COOLING COIL   51818.1     11.66 11.61  
PSZ-AC_2:2 COOLING COIL   30328.3     11.84 11.78  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed                
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel   57366.52 0.80
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel   54456.50 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
DINING EXHAUST FAN Fan:ZoneExhaust 1.00 0.00 0.42 0.00 0.00 1.00 0.00 General    
KITCHEN EXHAUST FAN Fan:ZoneExhaust 0.39 124.50 1.56 503.64 323.38 1.00 1.53 General    
PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 0.58 622.50 2.15 2298.68 1070.05 1.00 1.30 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 0.56 622.50 1.26 1392.04 1107.16 1.00 1.35 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000096 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.38 29307.11 0.81 1.05 0.31



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
DINING 24301.89 29162.27 251.03 1.790 2.148 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 23.89 23.86 0.01175 33.90 0.01654 0.416 0.00
KITCHEN 17110.94 20533.13 176.75 1.048 1.257 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 26.11 26.10 0.01017 33.19 0.01654 1.141 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
DINING 2504.91 3005.89 25.87 0.105 0.416 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:00:00 21.11 21.11 0.00751 4.60 0.00526 0.416 0.00
KITCHEN 0.00 0.00 0.00 0.000 1.141   00:10:00 15.56 27.85 0.00466 4.60 0.00526 1.141 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC_1:1 2.15 2.15 0.42 0.42 2.1482 2.1482 2.1482 1.0000 1.0000
PSZ-AC_2:2 1.26 1.26 1.14 1.14 1.2573 1.2573 1.2573 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_1:1 53344.970 37399.092 2.148200 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 26672.49 15389.48 1.432133 25.80 20.29 0.01267300 11.94 11.73 0.00850000 33.90 0.01653638 25.13 29.0515 23.86 0.01174502 63.3761 24301.89 0.00 -999.00 -999.00
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_1:1 57366.515 57366.515 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 57366.52 57366.52 2.148202 17.91 12.94 0.00725161 40.00 21.17 0.00800000 4.60 0.00525715 4.60 19.3676 20.73 0.00773068 50.7927 1343.27 0.00 -999.00 -999.00
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoopHVAC PSZ-AC_2:2 31221.920 21889.064 1.257310 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 15610.96 8249.50 0.838207 32.53 24.41 0.01594756 11.91 11.72 0.00850000 33.19 0.01653504 24.94 136.1637 26.10 0.01016595 48.1272 17110.94 0.00 -999.00 -999.00
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC_2:2 54456.501 54456.501 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 54456.50 54456.50 1.257307 4.18 4.18 0.00520196 40.00 21.17 0.00800000 4.60 0.00525715 4.60 90.7761 27.85 0.00465884 20.0728 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC_1:1 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_1:1 DINING Coincident CoolingDesignCapacity N/A No No unknown No 53344.970 37399.092 2.148200 -999.0 -999.000 -999.0000 1.00000 1.00000 1028.3985 1004.8586 1.2032 PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 2.148202 2.58464553   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 Sensible 26672.49 15389.48 1.0000 1.72309542 1.432133 25.80 20.29 0.01267300 58227.3 11.94 11.73 0.00850000 33439.5 -999.0 -999.00 -999.00 -999.00 0.000 26672.49 33.90 0.01653638 25.13 0.41605618 29.0515 23.85 0.01174502 23.86 0.01174502 63.3761 24301.89 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_1:1 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_1:1 DINING Coincident HeatingDesignCapacity N/A Yes No unknown No 57366.515 57366.515 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 PSZ-AC_1:1_ADDAQ FAN Fan:SystemModel 2.148202 2.58464553   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 57366.52 57366.52 1.0000 2.58464553 2.148202 17.91 12.94 0.00725161 36376.2 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 57366.52 4.60 0.00525715 4.60 0.41605618 19.3676 21.11 0.00773068 20.73 0.00773068 50.7927 1343.27 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:2 COOLING COIL Coil:Cooling:DX:MultiSpeed AirLoop AirLoopHVAC PSZ-AC_2:2 KITCHEN Coincident CoolingDesignCapacity N/A No No unknown No 31221.920 21889.064 1.257310 -999.0 -999.000 -999.0000 1.00000 1.00000 1034.4857 1004.8586 1.2032 PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 1.257307 1.51274965   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 12:30:00 Sensible 15610.96 8249.50 1.0000 1.00850251 0.838207 32.53 24.41 0.01594756 73536.8 11.91 11.72 0.00850000 33414.3 -999.0 -999.00 -999.00 -999.00 0.000 15610.96 33.19 0.01653504 24.94 1.14133354 136.1637 26.06 0.01016595 26.10 0.01016595 48.1272 17110.94 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC_2:2 HEATING COIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC_2:2 KITCHEN Coincident HeatingDesignCapacity N/A Yes No unknown No 54456.501 54456.501 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 PSZ-AC_2:2_ADDAQ FAN Fan:SystemModel 1.257307 1.51274965   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 54456.50 54456.50 1.0000 1.51274965 1.257307 4.18 4.18 0.00520196 17246.1 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 54456.50 4.60 0.00525715 4.60 1.14133354 90.7761 0.00 0.00465884 27.85 0.00465884 20.0728 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
PSZ-AC_1:1_OA_CONTROLLER DifferentialEnthalpy 0.42 2.15 -      
PSZ-AC_2:2_OA_CONTROLLER DifferentialEnthalpy 1.14 1.26 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
DINING 5460.83 5554.50 4096.17
KITCHEN 6496.00 6395.33 5829.33
ATTIC 0.00 0.00 0.00
Facility 6518.67 7145.50 5855.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
DINING 0.83 109.00 0.00 1.50
KITCHEN 0.00 1111.67 0.00 778.67
ATTIC 0.00 0.00 0.00 0.00
Facility 0.83 1130.83 0.00 780.17
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
DINING 36.94 87.54 354.18 4.937 4.166 0.000 0.000
KITCHEN 2.65 6.27 354.18 9.923 0.023 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
DINING 36.94 87.54 354.18 4.083 0.000 0.000 0.000
KITCHEN 2.65 6.27 354.18 8.141 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
DINING PSZ-AC_1:1 36.94 87.54 354.18 116.17 0.4161 0.416
KITCHEN PSZ-AC_2:2 2.65 6.27 354.18 116.17 0.1513 0.092
Total Facility   39.58 93.82 708.37 232.34 0.5673 0.508


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
DINING 12795774.93 0.00 12795774.93 10441318.23 23237093.16 13120747.55 1408.64 6340.02 1011.33 451.52
KITCHEN 26399674.88 0.00 26399674.88 97131.88 26496806.76 35993094.65 6812.29 1906.66 41.05 978.18
Total Facility 39195449.82 0.00 39195449.82 10538450.11 49733899.92 49113842.20 6830.67 6342.38 1049.24 1007.91


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
DINING 0.4761 0.0000 0.4761 0.4020 0.8781 0.4161 0.00 6202.74 984.26
KITCHEN 0.9487 0.0000 0.9487 0.0022 0.9509 1.1413 5287.38 1899.51 0.11
Total Facility 1.4248 0.0000 1.4248 0.4043 1.8290 1.5574 5287.38 6202.76 984.32


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC_1:1 18523135.92 0.00 18523135.92 13120747.55 1339.37 6.95 7413.68 451.50
PSZ-AC_2:2 38216245.03 0.00 38216245.03 35993094.65 1261.75 7.50 7490.75 978.18


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC_1:1 0.6892 0.0000 0.6892 0.4161 0.00 0.00 7187.00
PSZ-AC_2:2 1.3733 0.0000 1.3733 1.1413 0.00 0.00 7187.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC_1:1 0.00 867.87 435.84 6334.79 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC_2:2 0.00 0.00 277.13 3145.57 4742.47 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC_1:1 0.0000 1.4392 0.9656 0.6023 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC_2:2 0.0000 0.0000 1.2325 1.5523 1.2843 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Surfaces by Class

Total Outdoors
Wall 8 6
Floor 4 2
Roof 6 4
Internal Mass 2 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 3 3
Door 1 1
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 2
Conditioned Zones 2
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 386
Defaulted Fields 263
Fields with Defaults 886
Autosized Fields 39
Autosizable Fields 93
Autocalculated Fields 30
Autocalculatable Fields 60



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
Electricity:Building 298.00 2110.08 01-JAN-01:20 18433.35 02-JAN-11:10
Electricity:Zone:DINING 77.02 295.02 01-JAN-01:20 4205.23 02-JAN-17:40
Electricity:SpaceType:GENERAL 290.06 1973.80 01-JAN-01:20 15139.30 02-JAN-11:10
InteriorLights:Electricity 24.19 50.02 01-JAN-01:20 1583.48 02-JAN-17:40
InteriorLights:Electricity:Zone:DINING 6.69 25.01 01-JAN-01:20 681.55 02-JAN-17:40
InteriorLights:Electricity:SpaceType:GENERAL 24.19 50.02 01-JAN-01:20 1583.48 02-JAN-17:40
LightsWired:InteriorLights:Electricity 24.19 50.02 01-JAN-01:20 1583.48 02-JAN-17:40
LightsWired:InteriorLights:Electricity:Zone:DINING 6.69 25.01 01-JAN-01:20 681.55 02-JAN-17:40
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 24.19 50.02 01-JAN-01:20 1583.48 02-JAN-17:40
Electricity:Zone:KITCHEN 220.98 1815.06 01-JAN-01:20 14339.52 02-JAN-11:10
InteriorLights:Electricity:Zone:KITCHEN 17.51 25.01 01-JAN-01:20 901.93 02-JAN-10:10
LightsWired:InteriorLights:Electricity:Zone:KITCHEN 17.51 25.01 01-JAN-01:20 901.93 02-JAN-10:10
InteriorEquipment:Electricity 265.86 1923.78 01-JAN-01:10 14073.79 01-JAN-11:10
InteriorEquipment:Electricity:Zone:DINING 70.33 270.01 01-JAN-01:10 3930.26 01-JAN-11:10
InteriorEquipment:Electricity:SpaceType:GENERAL 265.86 1923.78 01-JAN-01:10 14073.79 01-JAN-11:10
Cooking:InteriorEquipment:Electricity 233.46 896.28 01-JAN-01:10 13046.29 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:Zone:DINING 70.33 270.01 01-JAN-01:10 3930.26 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL 233.46 896.28 01-JAN-01:10 13046.29 01-JAN-11:10
InteriorEquipment:Electricity:Zone:KITCHEN 195.53 1653.77 01-JAN-01:10 10143.54 01-JAN-11:10
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN 163.13 626.27 01-JAN-01:10 9116.04 01-JAN-11:10
ReachInFreezer:InteriorEquipment:Electricity 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL 14.43 457.50 01-JAN-00:10 457.50 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity 17.98 570.00 01-JAN-00:10 570.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN 17.98 570.00 01-JAN-00:10 570.00 01-JAN-00:10
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 17.98 570.00 01-JAN-00:10 570.00 01-JAN-00:10
Refrigeration:Electricity 56.19 849.95 04-FEB-23:30 4370.28 02-JAN-11:10
Refrigeration:Electricity:Zone:KITCHEN 7.94 85.78 01-JAN-23:30 3294.05 02-JAN-11:10
General:Refrigeration:Electricity 7.94 85.78 01-JAN-23:30 3294.05 02-JAN-11:10
General:Refrigeration:Electricity:Zone:KITCHEN 7.94 85.78 01-JAN-23:30 3294.05 02-JAN-11:10
Electricity:Plant 48.25 764.18 04-FEB-23:30 2560.22 11-JUL-03:30
LowTempRefrigeration:Refrigeration:Electricity 15.95 0.00 01-JAN-11:10 1483.99 11-JUL-03:30
MedTempRefrigeration:Refrigeration:Electricity 32.29 683.18 05-FEB-01:10 1076.23 01-JAN-02:10
ElectricityPurchased:Facility 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
ElectricityPurchased:Plant 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
Cogeneration:ElectricityPurchased 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
General:Cogeneration:ElectricityPurchased 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
ElectricityNet:Plant 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
Cogeneration:ElectricityNet 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
General:Cogeneration:ElectricityNet 609.41 3800.89 05-FEB-01:20 41390.19 09-SEP-18:40
Electricity:HVAC 247.58 0.00 01-JAN-01:10 25620.35 09-SEP-18:20
Fans:Electricity 63.69 0.00 01-JAN-01:10 4002.92 09-SEP-18:20
General:Fans:Electricity 63.69 0.00 01-JAN-01:10 4002.92 09-SEP-18:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 183.89 0.00 01-JAN-00:10 21617.42 09-SEP-18:20
General:Cooling:Electricity 183.89 0.00 01-JAN-00:10 21617.42 09-SEP-18:20
ExteriorLights:Electricity 15.58 0.00 01-JAN-07:30 1372.31 01-JAN-06:10
General:ExteriorLights:Electricity 15.58 0.00 01-JAN-07:30 1372.31 01-JAN-06:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-FEB-12:40
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-FEB-12:40


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 670.77 2558.65 01-JAN-03:30 77024.77 05-FEB-04:10
NaturalGas:Building 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
NaturalGas:Zone:KITCHEN 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
NaturalGas:SpaceType:GENERAL 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
InteriorEquipment:NaturalGas 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
InteriorEquipment:NaturalGas:Zone:KITCHEN 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL 477.16 1838.65 01-JAN-01:10 26660.45 01-JAN-11:10
NaturalGas:HVAC 25.43 0.00 01-JAN-00:10 71708.14 05-FEB-03:30
Heating:NaturalGas 25.43 0.00 01-JAN-00:10 71708.14 05-FEB-03:30
General:Heating:NaturalGas 25.43 0.00 01-JAN-00:10 71708.14 05-FEB-03:30
NaturalGas:Plant 168.19 720.00 01-JAN-03:30 24818.89 21-JAN-13:20
WaterSystems:NaturalGas 168.19 720.00 01-JAN-03:30 24818.89 21-JAN-13:20
Water Heater:WaterSystems:NaturalGas 168.19 720.00 01-JAN-03:30 24818.89 21-JAN-13:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
Water:Plant 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
WaterSystems:Water 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
WaterUse:WaterSystems:Water 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
MainsWater:Facility 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
MainsWater:Plant 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
WaterSystems:MainsWater 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
WaterUse:WaterSystems:MainsWater 775.38 0.00 01-JAN-00:10 0.00 24-APR-12:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1503.37 2418.57 05-FEB-01:10 124945.23 24-OCT-13:00
EnergyTransfer:Building 517.78 1209.29 05-FEB-01:10 35216.12 13-JUN-11:10
EnergyTransfer:Zone:KITCHEN 362.65 1209.29 05-FEB-01:10 22710.43 17-FEB-05:10
Refrigeration:EnergyTransfer 158.19 2418.57 05-FEB-01:10 7834.84 17-JAN-04:30
Refrigeration:EnergyTransfer:Zone:KITCHEN 79.10 1209.29 05-FEB-01:10 3917.42 17-JAN-04:30
General:Refrigeration:EnergyTransfer 79.10 1209.29 05-FEB-01:10 3917.42 17-JAN-04:30
General:Refrigeration:EnergyTransfer:Zone:KITCHEN 79.10 1209.29 05-FEB-01:10 3917.42 17-JAN-04:30
EnergyTransfer:Plant 188.64 1209.29 05-FEB-01:10 17786.37 19-JAN-13:50
LowTempRefrigeration:Refrigeration:EnergyTransfer 13.44 0.00 01-JAN-11:10 1678.72 01-JAN-11:40
MedTempRefrigeration:Refrigeration:EnergyTransfer 65.65 1059.55 05-FEB-01:10 2238.70 01-JAN-02:10
EnergyTransfer:Zone:DINING 155.13 0.00 01-JAN-01:10 20865.66 09-SEP-18:10
Heating:EnergyTransfer 4.62 0.00 01-JAN-00:10 14347.03 05-FEB-07:10
Heating:EnergyTransfer:Zone:DINING 4.61 0.00 01-JAN-00:10 14347.03 05-FEB-07:10
General:Heating:EnergyTransfer 4.62 0.00 01-JAN-00:10 14347.03 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:DINING 4.61 0.00 01-JAN-00:10 14347.03 05-FEB-07:10
Cooling:EnergyTransfer 434.07 0.00 01-JAN-01:10 32410.13 30-AUG-17:10
Cooling:EnergyTransfer:Zone:DINING 150.52 0.00 01-JAN-01:10 20865.66 09-SEP-18:10
General:Cooling:EnergyTransfer 434.07 0.00 01-JAN-01:10 32410.13 30-AUG-17:10
General:Cooling:EnergyTransfer:Zone:DINING 150.52 0.00 01-JAN-01:10 20865.66 09-SEP-18:10
Heating:EnergyTransfer:Zone:KITCHEN 0.00 0.00 01-JAN-00:10 682.70 09-SEP-23:10
General:Heating:EnergyTransfer:Zone:KITCHEN 0.00 0.00 01-JAN-00:10 682.70 09-SEP-23:10
Cooling:EnergyTransfer:Zone:KITCHEN 283.55 0.00 01-JAN-01:10 18919.21 17-FEB-05:10
General:Cooling:EnergyTransfer:Zone:KITCHEN 283.55 0.00 01-JAN-01:10 18919.21 17-FEB-05:10
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 109.55 0.00 01-JAN-00:10 15242.98 21-JAN-13:50
PlantLoopHeatingDemand:Plant 109.55 0.00 01-JAN-00:10 15242.98 21-JAN-13:50
WaterSystems:PlantLoopHeatingDemand 109.55 0.00 01-JAN-00:10 15242.98 21-JAN-13:50
General:WaterSystems:PlantLoopHeatingDemand 109.55 0.00 01-JAN-00:10 15242.98 21-JAN-13:50
EnergyTransfer:HVAC 796.95 0.00 01-JAN-00:10 85006.52 09-SEP-18:20
HeatingCoils:EnergyTransfer 20.34 0.00 01-JAN-00:10 57366.52 05-FEB-03:30
CoolingCoils:EnergyTransfer 776.60 0.00 01-JAN-00:10 85006.52 09-SEP-18:20
WaterSystems:EnergyTransfer 109.55 0.00 01-JAN-00:10 15242.98 21-JAN-13:50
WaterUse:WaterSystems:EnergyTransfer 109.55 0.00 01-JAN-00:10 15242.98 21-JAN-13:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
DINING 0.000 0.000 4.612 -150.521 0.000 0.000 67.036 6.687 52.748 22.448 0.000 28.139 11.753 0.000 -6.756 0.000 -36.147 0.000
KITCHEN 0.000 0.000 0.003 -283.545 0.000 0.000 4.061 17.506 201.243 0.000 0.000 0.062 61.405 0.000 0.000 0.000 -0.736 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.703 13.266 0.000 0.000 0.000 -16.969 -0.000
Total Facility 0.000 0.000 4.616 -434.066 0.000 0.000 71.097 24.193 253.992 22.448 0.000 31.905 86.423 0.000 -6.756 0.000 -53.853 -0.000


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
DINING 05-OCT-02:61 0.00 0.00 0.00 -32316.67 0.00 0.00 0.00 25.01 202.51 0.00 0.00 0.00 32306.52 0.00 -209.22 0.00 -8.15 0.00
KITCHEN 03-JAN-03:11 0.00 0.00 0.00 -53590.93 0.00 0.00 0.00 25.01 1677.05 0.00 0.00 0.00 51987.02 0.00 -0.00 0.00 -98.16 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 18-OCT-02:61 0.00 0.00 0.00 -61995.81 0.00 0.00 0.00 50.02 1879.56 0.00 0.00 226.36 60948.26 0.00 -790.01 0.00 -318.38 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
DINING 05-FEB-07:10 0.00 0.00 14350.63 0.00 0.00 0.00 3598.54 227.19 1524.67 0.00 0.00 0.00 0.00 0.00 -1594.05 0.00 -16736.32 -1370.66
KITCHEN 09-SEP-23:01 0.00 0.00 5465.17 0.00 0.00 0.00 15.62 200.44 2003.46 0.00 0.00 19.96 0.00 0.00 -0.00 0.00 0.00 -7704.65
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-FEB-07:10 -7399.17 7399.17 14350.63 -7399.17 0.00 0.00 3883.13 527.83 7431.98 0.00 0.00 345.43 0.00 0.00 -1594.05 0.00 -16836.77 -709.02



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC_1:1 2.1482 0.0000 87.5444 1.0000 Calculated from schedules 0.4161 2.1482 0.1937 1.0000 Not calculated 0.4161 0.1937    
PSZ-AC_2:2 1.2573 0.0000 6.2733 1.0000 Calculated from schedules 0.1513 1.2573 0.1203 1.0000 Not calculated 0.1513 0.1203    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC_1:1 2.1482 0.0000 87.5444 1.0000 Calculated from schedules 0.4161 2.1482 1.0000 1.0000 Not calculated 0.4161 0.1937    
PSZ-AC_2:2 1.2573 0.0000 6.2733 1.0000 Calculated from schedules 0.1513 1.2573 0.1325 1.0000 Not calculated 0.1513 0.1203    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
DINING PSZ-AC_1:1 0.000000 87.5444 0.003581 116.17 0.4161 1.0000 0.4161 1.000 0.4161
KITCHEN PSZ-AC_2:2 0.009440 6.2733 0.000792 116.17 0.1513 1.0000 0.1513 1.000 0.1513


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC_1:1 0.000000 87.54 0.003581 116.1715 0.4161 0.4161 0.4161
PSZ-AC_2:2 0.009440 6.27 0.000792 116.1715 0.1513 0.1513 0.1513


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
DINING PSZ-AC_1:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.1482 2.1482 2.1482 No 0.4161 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN PSZ-AC_2:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.2573 1.2573 1.2573 No 0.1513 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC_1:1 2.1482 2.1482 2.1482 2.1482 0.4161 1.0000
PSZ-AC_2:2 1.2573 1.2573 1.2573 1.2573 0.1513 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
DINING PSZ-AC_1:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 2.1482 2.1482 2.1482 No 0.4161 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
KITCHEN PSZ-AC_2:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1.2573 1.2573 1.2573 No 0.1513 0.1325 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC_1:1 2.1482 2.1482 2.1482 2.1482 0.4161 1.0000
PSZ-AC_2:2 1.2573 1.2573 1.2573 1.2573 0.1513 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Total gross floor area [m2] 232.34
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
DINING 116.17 116.17 0.00 137.83
KITCHEN 116.17 116.17 0.00 137.83
ATTIC 232.34 0.00 232.34 0.00
Totals 232.34 232.34 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 780.17
Number of hours not met 780.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 25.43 71708.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 183.89 21617.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 24.19 1583.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 15.58 1372.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- Cooking 233.46 13046.29 477.16 26660.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInFreezer 14.43 457.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- ReachInRefrigerator 17.98 570.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 63.69 4002.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 168.19 24818.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- General 7.94 3294.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- LowTempRefrigeration 15.95 1483.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- MedTempRefrigeration 32.29 1076.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 322.05 609.41
Natural Gas 477.16 670.77
Additional 0.00 0.00
Total 799.21 1280.18


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 104.12
Space Heating 0.00
Space Cooling 791.45
Fans (All) 274.14
Service Water Heating 0.00
Receptacle Equipment 1144.28
Miscellaneous (All) 2622.89
Subtotal 2622.89


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 109.44
Service Water Heating 723.87
Miscellaneous (All) 2886.99
Subtotal 2886.99


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 1.89
Space Heating 1.99
Space Cooling 14.36
Fans (All) 4.98
Service Water Heating 13.14
Receptacle Equipment 58.04
Miscellaneous 5.61


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_DINING 4638. 8760.
LTG_SCH_KITCHEN 4403. 8760.
BLDG_EQUIP_SCH 1440. 8760.
FF_GAS_EQUIP_SCH 1442. 8760.
BLDG_OCC_SCH 2960. 7195.
INFIL_SCH_PNNL 3285. 8760.
DOOR_INFIL_SCH 3274. 6570.
VESTIBULE_DOOR_INFIL_SCH 3177. 6570.
BLDG_SWH_SCH 2246. 6360.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 7300. 8760.
ALWAYS_OFF 0. 0.
FAN_SCH 8760. 8760.
MINOA_SCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 6935. 6935.
WORK_EFF_SCH 0. 0.
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED 2774. 8760.
WALKIN_OCC_LGHT_SCH_2 2785. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6935. 6935.
EXTERIOR_LIGHTING_SCHEDULE_B 8213. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 6935. 6935.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE 1950. 7300.
SZ_SYSTEM_OA_MAX_FRAC_SCH 6132. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_NO_OPTIMUM DINING DUAL SP CONTROL January 21.11 365 21.11 365
CLGSETP_SCH_NO_OPTIMUM DINING DUAL SP CONTROL July 23.89 365 23.89 365
HTGSETP_KITCHEN_SCH_NO_OPTIMUM KITCHEN DUAL SP CONTROL January 18.89 365 18.89 365
CLGSETP_KITCHEN_SCH_NO_OPTIMUM KITCHEN DUAL SP CONTROL July 26.11 365 26.11 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
DINING 8310.00 447.00 3.00 0.00 0.00
KITCHEN 6606.67 1801.33 352.00 0.00 0.00
ATTIC 5190.17 675.33 759.50 1046.00 1089.00
Min 5190.17 447.00 3.00 0.00 0.00
Max 8310.00 1801.33 759.50 1046.00 1089.00
Average 6702.28 974.56 371.50 348.67 363.00
Sum 20106.83 2923.67 1114.50 1046.00 1089.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
DINING 254327.00 394.00 4.00 0.00 0.00
KITCHEN 13345.17 2868.00 44.83 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 254327.00 2868.00 44.83 0.00 0.00
Average 89224.06 1087.33 16.28 0.00 0.00
Sum 267672.17 3262.00 48.83 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
DINING 3743.67 5015.00 1.33 0.00 0.00
KITCHEN 2065.50 6592.50 102.00 0.00 0.00
ATTIC 3531.17 2667.67 582.50 520.33 1458.33
Min 2065.50 2667.67 1.33 0.00 0.00
Max 3743.67 6592.50 582.50 520.33 1458.33
Average 3113.44 4758.39 228.61 173.44 486.11
Sum 9340.33 14275.17 685.83 520.33 1458.33


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
DINING 109979.00 144743.33 2.67 0.00 0.00
KITCHEN 3649.67 12596.67 11.67 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 109979.00 144743.33 11.67 0.00 0.00
Average 37876.22 52446.67 4.78 0.00 0.00
Sum 113628.67 157340.00 14.33 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:26:26

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
DINING 0.00 8760.00 0.00 0.00
KITCHEN 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 8760.00 0.00 0.00
Average 0.00 2920.00 0.00 0.00
Sum 0.00 8760.00 0.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
DINING 0.00 254725.00 0.00 0.00
KITCHEN 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 254725.00 0.00 0.00
Average 0.00 84908.33 0.00 0.00
Sum 0.00 254725.00 0.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.498213E+10 25741.88 01-JAN-03:01 17.00 15.00 0.483080E+10 4413.86 19-JAN-12:30 25.50 21.71
February 0.553427E+10 23040.45 01-FEB-03:01 16.50 16.50 0.451960E+10 4681.19 25-FEB-19:19 19.93 17.98
March 0.695525E+10 21834.87 26-MAR-02:62 18.87 16.44 0.509333E+10 4681.27 04-MAR-19:40 18.87 16.44
April 0.101703E+11 26237.42 22-APR-02:61 21.88 19.52 0.517008E+10 4681.39 22-APR-18:49 25.97 21.07
May 0.173124E+11 28283.63 12-MAY-02:61 23.80 20.14 0.544282E+10 4681.66 06-MAY-18:49 23.80 20.14
June 0.181806E+11 28576.16 11-JUN-02:61 23.80 20.14 0.529195E+10 4681.44 24-JUN-18:10 27.02 22.52
July 0.192178E+11 22170.05 11-JUL-02:61 25.32 22.45 0.541281E+10 4681.10 08-JUL-18:00 25.32 22.45
August 0.194100E+11 31476.61 20-AUG-02:61 23.85 18.71 0.547316E+10 4681.39 19-AUG-18:30 23.85 18.71
September 0.168184E+11 27460.28 22-SEP-02:61 22.52 20.41 0.526000E+10 4681.49 02-SEP-18:30 22.52 20.41
October 0.158983E+11 32330.11 05-OCT-02:61 24.00 21.84 0.537229E+10 4681.60 21-OCT-18:00 25.00 24.24
November 0.928098E+10 27076.49 20-NOV-03:01 16.48 14.29 0.504337E+10 4681.01 04-NOV-18:49 16.48 14.29
December 0.676118E+10 26653.38 16-DEC-03:01 20.83 20.26 0.496304E+10 4681.01 09-DEC-19:00 20.83 20.26
                     
Annual Sum or Average 0.150522E+12         0.618733E+11        
Minimum of Months 0.498213E+10 21834.87   16.48 14.29 0.451960E+10 4413.86   16.48 14.29
Maximum of Months 0.194100E+11 32330.11   25.32 22.45 0.547316E+10 4681.66   27.02 24.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.231436E+11 53646.23 03-JAN-03:11 6.00 3.42 0.779357E+10 5135.96 30-JAN-11:09 22.83 19.53
February 0.205277E+11 41504.68 09-FEB-03:01 10.42 9.75 0.706071E+10 5135.98 01-FEB-11:30 10.42 9.75
March 0.226471E+11 45472.42 14-MAR-04:01 8.65 7.48 0.783073E+10 5135.96 23-MAR-10:00 19.40 14.77
April 0.223416E+11 44797.85 11-APR-04:01 11.27 8.57 0.760236E+10 5141.48 28-APR-10:00 30.00 23.29
May 0.244887E+11 25331.59 17-MAY-02:61 22.70 20.09 0.786376E+10 5173.10 26-MAY-10:50 30.82 25.83
June 0.240672E+11 28172.31 07-JUN-02:11 20.77 18.07 0.761868E+10 5178.57 19-JUN-10:50 31.52 26.12
July 0.250604E+11 21620.57 11-JUL-02:61 25.32 22.45 0.787939E+10 5187.95 03-JUL-10:50 25.32 22.45
August 0.255560E+11 27694.58 20-AUG-02:61 23.85 18.71 0.788021E+10 5188.03 14-AUG-10:00 23.85 18.71
September 0.244616E+11 24733.45 22-SEP-02:61 22.52 20.41 0.761703E+10 5175.74 18-SEP-10:50 22.52 20.41
October 0.248790E+11 47822.76 28-OCT-02:61 12.00 6.52 0.786393E+10 5200.09 06-OCT-10:50 12.00 6.52
November 0.229367E+11 49308.04 23-NOV-03:01 10.52 4.09 0.759130E+10 5152.83 02-NOV-10:50 10.52 4.09
December 0.234403E+11 45275.97 04-DEC-03:01 6.83 5.86 0.781281E+10 5136.71 15-DEC-11:00 28.00 23.07
                     
Annual Sum or Average 0.283550E+12         0.924145E+11        
Minimum of Months 0.205277E+11 21620.57   6.00 3.42 0.706071E+10 5135.96   10.42 4.09
Maximum of Months 0.255560E+11 53646.23   25.32 22.45 0.788021E+10 5200.09   31.52 26.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00 16.69 0.00 0.00 01-JAN-00:10 17.00 16.69
February 0.00 0.00 01-FEB-00:05 18.20 18.20 0.00 0.00 01-FEB-00:10 18.20 18.20
March 0.00 0.00 01-MAR-00:10 17.62 17.16 0.00 0.00 01-MAR-00:10 17.62 17.16
April 0.00 0.00 01-APR-00:01 20.72 19.79 0.00 0.00 01-APR-00:10 20.72 19.79
May 0.00 0.00 01-MAY-00:01 22.45 19.11 0.00 0.00 01-MAY-00:10 22.45 19.11
June 0.00 0.00 01-JUN-00:01 22.93 21.40 0.00 0.00 01-JUN-00:10 22.93 21.40
July 0.00 0.00 01-JUL-00:02 25.07 23.10 0.00 0.00 01-JUL-00:10 25.07 23.10
August 0.00 0.00 01-AUG-00:02 25.13 23.55 0.00 0.00 01-AUG-00:10 25.13 23.55
September 0.00 0.00 01-SEP-00:01 24.85 24.22 0.00 0.00 01-SEP-00:10 24.85 24.22
October 0.00 0.00 01-OCT-00:01 22.17 20.64 0.00 0.00 01-OCT-00:10 22.17 20.64
November 0.00 0.00 01-NOV-00:01 21.63 21.01 0.00 0.00 01-NOV-00:10 21.63 21.01
December 0.00 0.00 01-DEC-00:10 14.12 12.36 0.00 0.00 01-DEC-00:10 14.12 12.36
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   14.12 12.36 0.00 0.00   14.12 12.36
Maximum of Months 0.00 0.00   25.13 24.22 0.00 0.00   25.13 24.22



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.157484E+10 10652.08 04-JAN-21:00 3.00
February 0.110654E+10 14347.03 05-FEB-07:10 -3.4
March 0.677015E+09 8149.88 09-MAR-07:10 1.18
April 7410460.41 4987.52 18-APR-02:05 18.52
May 25447065.35 1946.41 02-MAY-23:01 26.93
June 34097108.19 2500.12 28-JUN-23:01 28.22
July 56823629.98 2549.53 02-JUL-23:01 28.30
August 41812976.31 2588.63 24-AUG-23:01 28.52
September 22376806.41 4804.55 09-SEP-23:01 33.88
October 19016269.11 1853.68 01-OCT-03:23 19.75
November 89547936.46 3388.93 15-NOV-21:00 8.90
December 0.957316E+09 10942.32 20-DEC-21:00 3.00
         
Annual Sum or Average 0.461223E+10      
Minimum of Months 7410460.41 1853.68   -3.4
Maximum of Months 0.157484E+10 14347.03   33.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:05 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:01 20.72
May 113322.73 688.01 02-MAY-23:01 26.93
June 323173.51 1868.39 28-JUN-23:01 28.22
July 1280206.75 1977.93 02-JUL-23:01 28.30
August 895574.97 2130.41 24-AUG-23:01 28.52
September 636085.55 5461.61 09-SEP-23:01 33.88
October 66384.33 557.80 13-OCT-23:01 26.83
November 0.00 0.00 01-NOV-00:01 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 3314747.83      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 1280206.75 5461.61   33.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 17.00
February 0.00 0.00 01-FEB-00:05 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:01 20.72
May 0.00 0.00 01-MAY-00:01 22.45
June 0.00 0.00 01-JUN-00:01 22.93
July 0.00 0.00 01-JUL-00:02 25.07
August 0.00 0.00 01-AUG-00:02 25.13
September 0.00 0.00 01-SEP-00:01 24.85
October 0.00 0.00 01-OCT-00:01 22.17
November 0.00 0.00 01-NOV-00:01 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.636474E+09 681.55 02-JAN-17:40 0.597334E+10 3930.26 01-JAN-11:09
February 0.547665E+09 681.55 01-FEB-18:10 0.539527E+10 3930.26 01-FEB-11:09
March 0.575420E+09 681.55 01-MAR-18:10 0.597338E+10 3930.26 01-MAR-11:09
April 0.523348E+09 681.55 01-APR-18:30 0.578064E+10 3930.26 01-APR-10:09
May 0.511301E+09 681.55 01-MAY-18:00 0.597336E+10 3930.26 01-MAY-10:09
June 0.483606E+09 681.55 01-JUN-19:19 0.578068E+10 3930.26 01-JUN-10:09
July 0.494218E+09 681.55 01-JUL-19:19 0.597331E+10 3930.26 01-JUL-10:09
August 0.529251E+09 681.55 01-AUG-19:19 0.597338E+10 3930.26 01-AUG-10:09
September 0.536800E+09 681.55 01-SEP-18:30 0.578064E+10 3930.26 01-SEP-10:09
October 0.581893E+09 681.55 02-OCT-18:19 0.597334E+10 3930.26 01-OCT-10:09
November 0.612884E+09 681.55 01-NOV-17:19 0.578066E+10 3930.26 01-NOV-10:09
December 0.653662E+09 681.55 01-DEC-17:19 0.597331E+10 3930.26 01-DEC-11:09
             
Annual Sum or Average 0.668652E+10     0.703313E+11    
Minimum of Months 0.483606E+09 681.55   0.539527E+10 3930.26  
Maximum of Months 0.653662E+09 681.55   0.597338E+10 3930.26  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.147870E+10 901.93 02-JAN-10:09 0.166069E+11 10143.54 01-JAN-11:09
February 0.133950E+10 901.93 01-FEB-10:09 0.149998E+11 10143.54 01-FEB-11:09
March 0.150425E+10 901.93 01-MAR-10:09 0.166070E+11 10143.54 01-MAR-11:09
April 0.143688E+10 901.93 01-APR-16:10 0.160712E+11 10143.54 01-APR-10:09
May 0.149147E+10 901.93 01-MAY-09:09 0.166070E+11 10143.54 01-MAY-10:09
June 0.145377E+10 901.93 01-JUN-09:09 0.160713E+11 10143.54 01-JUN-10:09
July 0.147476E+10 901.93 01-JUL-16:10 0.166069E+11 10143.54 01-JUL-10:09
August 0.150425E+10 901.93 01-AUG-09:09 0.166070E+11 10143.54 01-AUG-10:09
September 0.143724E+10 901.93 01-SEP-09:09 0.160712E+11 10143.54 01-SEP-10:09
October 0.147852E+10 901.93 02-OCT-09:09 0.166069E+11 10143.54 01-OCT-10:09
November 0.143180E+10 901.93 01-NOV-09:09 0.160712E+11 10143.54 01-NOV-10:09
December 0.147494E+10 901.93 01-DEC-10:09 0.166069E+11 10143.54 01-DEC-11:09
             
Annual Sum or Average 0.175061E+11     0.195533E+12    
Minimum of Months 0.133950E+10 901.93   0.149998E+11 10143.54  
Maximum of Months 0.150425E+10 901.93   0.166070E+11 10143.54  



Table of Contents

Report: SpaceGainsMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.940563E+10 0.636474E+09 0.597334E+10 0.00 0.00 0.00 0.00 84372811.83 0.879379E+10
February 0.852256E+10 0.547665E+09 0.539527E+10 0.00 0.00 0.00 0.00 0.151520E+09 0.644945E+10
March 0.954557E+10 0.575420E+09 0.597338E+10 0.00 0.00 0.00 0.00 0.345787E+09 0.566333E+10
April 0.915225E+10 0.523348E+09 0.578064E+10 0.00 0.00 0.00 0.00 0.110288E+10 0.246401E+10
May 0.947560E+10 0.511301E+09 0.597336E+10 0.00 0.00 0.00 0.00 0.431429E+10 31933812.42
June 0.922788E+10 0.483606E+09 0.578068E+10 0.00 0.00 0.00 0.00 0.508856E+10 28939058.70
July 0.939996E+10 0.494218E+09 0.597331E+10 0.00 0.00 0.00 0.00 0.525679E+10 16482778.24
August 0.954557E+10 0.529251E+09 0.597338E+10 0.00 0.00 0.00 0.00 0.493290E+10 85060924.35
September 0.915225E+10 0.536800E+09 0.578064E+10 0.00 0.00 0.00 0.00 0.322744E+10 0.180424E+09
October 0.940563E+10 0.581893E+09 0.597334E+10 0.00 0.00 0.00 0.00 0.274165E+10 0.119744E+10
November 0.909363E+10 0.612884E+09 0.578066E+10 0.00 0.00 0.00 0.00 0.580493E+09 0.415521E+10
December 0.939996E+10 0.653662E+09 0.597331E+10 0.00 0.00 0.00 0.00 0.312811E+09 0.708075E+10
                   
Annual Sum or Average 0.111326E+12 0.668652E+10 0.703313E+11 0.00 0.00 0.00 0.00 0.281395E+11 0.361468E+11
Minimum of Months 0.852256E+10 0.483606E+09 0.539527E+10 0.00 0.00 0.00 0.00 84372811.83 16482778.24
Maximum of Months 0.954557E+10 0.653662E+09 0.597338E+10 0.00 0.00 0.00 0.00 0.525679E+10 0.879379E+10



Table of Contents

Report: SpaceGainsMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.673993E+09 0.147870E+10 0.124505E+11 0.121577E+11 0.00 0.00 0.00 8812.03 0.131495E+09
February 0.610713E+09 0.133950E+10 0.112456E+11 0.109812E+11 0.00 0.00 0.00 116371.63 94619794.34
March 0.684021E+09 0.150425E+10 0.124505E+11 0.121577E+11 0.00 0.00 0.00 427912.58 0.113752E+09
April 0.655836E+09 0.143688E+10 0.120488E+11 0.117655E+11 0.00 0.00 0.00 2221574.64 51022181.94
May 0.679007E+09 0.149147E+10 0.124505E+11 0.121577E+11 0.00 0.00 0.00 10196023.26 19374329.97
June 0.661256E+09 0.145377E+10 0.120489E+11 0.117655E+11 0.00 0.00 0.00 10603104.41 14389005.83
July 0.673587E+09 0.147476E+10 0.124504E+11 0.121577E+11 0.00 0.00 0.00 10423557.99 11646316.40
August 0.684021E+09 0.150425E+10 0.124505E+11 0.121577E+11 0.00 0.00 0.00 11758874.74 20769104.06
September 0.655836E+09 0.143724E+10 0.120488E+11 0.117655E+11 0.00 0.00 0.00 8211165.11 25808735.95
October 0.673993E+09 0.147852E+10 0.124505E+11 0.121577E+11 0.00 0.00 0.00 7387531.24 58332217.37
November 0.651635E+09 0.143180E+10 0.120489E+11 0.117655E+11 0.00 0.00 0.00 669596.88 75654113.49
December 0.673587E+09 0.147494E+10 0.124504E+11 0.121577E+11 0.00 0.00 0.00 414291.92 0.119530E+09
                   
Annual Sum or Average 0.797748E+10 0.175061E+11 0.146594E+12 0.143147E+12 0.00 0.00 0.00 62438816.44 0.736393E+09
Minimum of Months 0.610713E+09 0.133950E+10 0.112456E+11 0.109812E+11 0.00 0.00 0.00 8812.03 11646316.40
Maximum of Months 0.684021E+09 0.150425E+10 0.124505E+11 0.121577E+11 0.00 0.00 0.00 11758874.74 0.131495E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.354954E+09 0.111691E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.369898E+09 0.119996E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.324348E+09 0.141139E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.324880E+09 0.170383E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.253983E+09 0.164129E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.270215E+09 0.181099E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.264496E+09 0.169708E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.259261E+09 0.161040E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.272492E+09 0.135142E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.257949E+09 0.133743E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.399624E+09 0.108131E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.351285E+09 0.100740E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.370339E+10 0.169694E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.253983E+09 0.100740E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.399624E+09 0.181099E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 9454.80 07-JAN-19:10 681.55 02-JAN-17:40 3930.26 01-JAN-11:09 0.00 0.00 0.00 0.00 1888.90 02-JAN-13:00 17618.72 04-JAN-21:00
February 9454.80 04-FEB-19:10 681.55 01-FEB-18:10 3930.26 01-FEB-11:09 0.00 0.00 0.00 0.00 3917.72 02-FEB-13:00 18783.08 04-FEB-20:00
March 9454.80 04-MAR-19:10 681.55 01-MAR-18:10 3930.26 01-MAR-11:09 0.00 0.00 0.00 0.00 4341.71 30-MAR-13:00 12908.80 09-MAR-21:00
April 9454.80 01-APR-18:10 681.55 01-APR-18:30 3930.26 01-APR-10:09 0.00 0.00 0.00 0.00 6525.85 28-APR-13:00 7311.46 10-APR-19:53
May 9454.80 06-MAY-18:10 681.55 01-MAY-18:00 3930.26 01-MAY-10:09 0.00 0.00 0.00 0.00 7621.04 25-MAY-17:03 987.87 19-MAY-19:00
June 9454.80 03-JUN-18:10 681.55 01-JUN-19:19 3930.26 01-JUN-10:09 0.00 0.00 0.00 0.00 7978.30 13-JUN-17:03 1272.30 07-JUN-06:10
July 9454.80 01-JUL-18:10 681.55 01-JUL-19:19 3930.26 01-JUL-10:09 0.00 0.00 0.00 0.00 8776.11 20-JUL-12:00 1535.46 11-JUL-19:55
August 9454.80 05-AUG-18:10 681.55 01-AUG-19:19 3930.26 01-AUG-10:09 0.00 0.00 0.00 0.00 9361.28 30-AUG-17:03 2820.54 16-AUG-19:00
September 9454.80 02-SEP-18:10 681.55 01-SEP-18:30 3930.26 01-SEP-10:09 0.00 0.00 0.00 0.00 10741.42 09-SEP-18:03 4299.21 07-SEP-18:00
October 9454.80 07-OCT-18:10 681.55 02-OCT-18:19 3930.26 01-OCT-10:09 0.00 0.00 0.00 0.00 7821.25 05-OCT-17:03 7229.65 27-OCT-18:53
November 9454.80 04-NOV-18:10 681.55 01-NOV-17:19 3930.26 01-NOV-10:09 0.00 0.00 0.00 0.00 4891.05 02-NOV-11:55 11633.39 15-NOV-21:00
December 9454.80 02-DEC-19:10 681.55 01-DEC-17:19 3930.26 01-DEC-11:09 0.00 0.00 0.00 0.00 4073.44 13-DEC-14:00 17645.58 20-DEC-21:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 9454.80   681.55   3930.26   0.00 0.00 0.00 0.00 1888.90   987.87  
Maximum of Months 9454.80   681.55   3930.26   0.00 0.00 0.00 0.00 10741.42   18783.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 677.52 07-JAN-19:10 901.93 02-JAN-10:09 7408.73 01-JAN-11:09 7998.14 01-JAN-11:09 0.00 0.00 0.00 1.97 16-JAN-15:00 481.40 09-JAN-03:00
February 677.52 04-FEB-19:10 901.93 01-FEB-10:09 7408.73 01-FEB-11:09 7998.14 01-FEB-11:09 0.00 0.00 0.00 12.19 02-FEB-13:00 509.07 04-FEB-05:00
March 677.52 04-MAR-19:10 901.93 01-MAR-10:09 7408.73 01-MAR-11:09 7998.14 01-MAR-11:09 0.00 0.00 0.00 11.31 27-MAR-15:00 519.60 21-MAR-03:20
April 677.52 01-APR-18:10 901.93 01-APR-16:10 7408.73 01-APR-10:09 7998.14 01-APR-10:09 0.00 0.00 0.00 25.16 29-APR-16:00 349.90 02-APR-01:50
May 677.52 06-MAY-18:10 901.93 01-MAY-09:09 7408.73 01-MAY-10:09 7998.14 01-MAY-10:09 0.00 0.00 0.00 31.08 25-MAY-14:20 188.30 09-MAY-02:00
June 677.52 03-JUN-18:10 901.93 01-JUN-09:09 7408.73 01-JUN-10:09 7998.14 01-JUN-10:09 0.00 0.00 0.00 36.61 08-JUN-15:00 200.84 08-JUN-02:00
July 677.52 01-JUL-18:10 901.93 01-JUL-16:10 7408.73 01-JUL-10:09 7998.14 01-JUL-10:09 0.00 0.00 0.00 52.97 19-JUL-13:00 163.81 31-JUL-02:00
August 677.52 05-AUG-18:10 901.93 01-AUG-09:09 7408.73 01-AUG-10:09 7998.14 01-AUG-10:09 0.00 0.00 0.00 36.98 03-AUG-17:10 255.78 16-AUG-02:00
September 677.52 02-SEP-18:10 901.93 01-SEP-09:09 7408.73 01-SEP-10:09 7998.14 01-SEP-10:09 0.00 0.00 0.00 91.60 10-SEP-02:50 253.61 13-SEP-02:00
October 677.52 07-OCT-18:10 901.93 02-OCT-09:09 7408.73 01-OCT-10:09 7998.14 01-OCT-10:09 0.00 0.00 0.00 44.47 09-OCT-14:00 319.77 29-OCT-01:50
November 677.52 04-NOV-18:10 901.93 01-NOV-09:09 7408.73 01-NOV-10:09 7998.14 01-NOV-10:09 0.00 0.00 0.00 10.00 02-NOV-15:00 334.99 09-NOV-04:40
December 677.52 02-DEC-19:10 901.93 01-DEC-10:09 7408.73 01-DEC-11:09 7998.14 01-DEC-11:09 0.00 0.00 0.00 10.34 13-DEC-14:40 517.61 20-DEC-04:20
                               
Annual Sum or Average                 0.00 0.00 0.00        
Minimum of Months 677.52   901.93   7408.73   7998.14   0.00 0.00 0.00 1.97   163.81  
Maximum of Months 677.52   901.93   7408.73   7998.14   0.00 0.00 0.00 91.60   519.60  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 581.32 05-JAN-01:00 2164.12 21-JAN-13:30
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 712.77 10-FEB-07:53 2415.43 17-FEB-13:50
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 666.92 14-MAR-07:23 2567.71 13-MAR-13:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 627.43 11-APR-06:53 2731.37 10-APR-13:20
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 577.74 02-MAY-23:00 2705.80 10-MAY-14:20
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 481.28 28-JUN-01:52 2621.90 28-JUN-13:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 517.88 15-JUL-05:00 2690.17 20-JUL-14:03
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 497.66 30-AUG-23:10 2526.51 10-AUG-14:13
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 495.98 01-SEP-06:45 2413.26 02-SEP-15:51
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 434.05 19-OCT-03:53 2130.29 02-OCT-13:20
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 570.50 24-NOV-06:00 2129.89 12-NOV-13:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 834.50 19-DEC-07:52 1954.64 31-DEC-14:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 434.05   1954.64  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 834.50   2731.37  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 25741.88 01-JAN-03:01 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 55.08
February 23040.45 01-FEB-03:01 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 42.30
March 21834.87 26-MAR-02:62 0.00 125.05 1350.05 0.00 0.00 0.00 0.00 0.00 11.85
April 26237.42 22-APR-02:61 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 26.01
May 28283.63 12-MAY-02:61 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 6.75
June 28576.16 11-JUN-02:61 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 7.49
July 22170.05 11-JUL-02:61 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 2.08
August 31476.61 20-AUG-02:61 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 5.24
September 27460.28 22-SEP-02:61 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 12.00
October 32330.11 05-OCT-02:61 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 8.15
November 27076.49 20-NOV-03:01 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 38.36
December 26653.38 16-DEC-03:01 0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 44.14
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 21834.87   0.00 125.05 1350.05 0.00 0.00 0.00 0.00 0.00 2.08
Maximum of Months 32330.11   0.00 250.09 2700.09 0.00 0.00 0.00 0.00 0.00 55.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 53646.23 03-JAN-03:11 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 98.16
February 41504.68 09-FEB-03:01 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 49.96
March 45472.42 14-MAR-04:01 376.40 250.09 36680.07 33095.74 0.00 0.00 0.00 0.00 0.00
April 44797.85 11-APR-04:01 376.40 250.09 36680.07 33095.74 0.00 0.00 0.00 0.00 3.85
May 25331.59 17-MAY-02:61 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 24.50
June 28172.31 07-JUN-02:11 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 112.51
July 21620.57 11-JUL-02:61 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 37.87
August 27694.58 20-AUG-02:61 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 35.36
September 24733.45 22-SEP-02:61 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 39.98
October 47822.76 28-OCT-02:61 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 217.46
November 49308.04 23-NOV-03:01 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 72.92
December 45275.97 04-DEC-03:01 0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 168.98
                       
Annual Sum or Average             0.00 0.00 0.00    
Minimum of Months 21620.57   0.00 250.09 14658.91 5515.96 0.00 0.00 0.00 0.00 0.00
Maximum of Months 53646.23   376.40 250.09 36680.07 33095.74 0.00 0.00 0.00 0.00 217.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.72
February 0.00 01-FEB-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.64 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 251.00 0.00
April 0.00 01-APR-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 87.34 0.00
May 0.00 01-MAY-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 406.88 0.00
June 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 280.92 0.00
July 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.31 0.00
August 0.00 01-AUG-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 208.76 0.00
September 0.00 01-SEP-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 390.43 0.00
October 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 184.55 0.00
November 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 173.02 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 270.80 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 406.88 5.72



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.381751E+11 32416.91 19-JAN-11:00 0.650551E+11 59101.23 05-JAN-07:00
February 0.355494E+11 30948.75 02-FEB-11:00 0.568901E+11 77024.77 05-FEB-04:10
March 0.407080E+11 32937.33 07-MAR-11:50 0.597188E+11 61051.38 11-MAR-11:09
April 0.441664E+11 35393.41 28-APR-11:20 0.534377E+11 46753.71 02-APR-12:39
May 0.600587E+11 37618.05 24-MAY-11:20 0.542005E+11 45797.34 02-MAY-12:20
June 0.606747E+11 38393.69 21-JUN-10:20 0.518011E+11 44703.60 03-JUN-12:50
July 0.662961E+11 40483.59 18-JUL-11:09 0.531572E+11 43918.78 07-JUL-12:20
August 0.647584E+11 38995.42 14-AUG-10:20 0.533022E+11 44046.70 19-AUG-12:39
September 0.599240E+11 41390.19 09-SEP-18:40 0.520560E+11 45257.34 30-SEP-12:50
October 0.559994E+11 40806.52 06-OCT-11:20 0.546800E+11 46316.59 31-OCT-12:30
November 0.424699E+11 36042.76 02-NOV-10:20 0.546799E+11 47125.13 29-NOV-13:00
December 0.406307E+11 34064.55 15-DEC-12:09 0.617936E+11 60115.69 20-DEC-11:20
             
Annual Sum or Average 0.609411E+12     0.670772E+12    
Minimum of Months 0.355494E+11 30948.75   0.518011E+11 43918.78  
Maximum of Months 0.662961E+11 41390.19   0.650551E+11 77024.77  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.211517E+10 0.156348E+10 0.225803E+11 0.00 0.473998E+10 0.79 0.00 0.266237E+10 0.00 0.00 0.00 0.00 0.00
February 0.188717E+10 0.133024E+10 0.203951E+11 0.00 0.428392E+10 0.72 0.00 0.349092E+10 0.00 0.00 0.00 0.00 0.00
March 0.207967E+10 0.134940E+10 0.225804E+11 0.00 0.474593E+10 0.80 0.00 0.530569E+10 0.00 0.00 0.00 0.00 0.00
April 0.196023E+10 0.118630E+10 0.218518E+11 0.00 0.470600E+10 0.77 0.00 0.982859E+10 0.00 0.00 0.00 0.00 0.00
May 0.200277E+10 0.111803E+10 0.225803E+11 0.00 0.573302E+10 0.80 0.00 0.237480E+11 0.00 0.00 0.00 0.00 0.00
June 0.193738E+10 0.102327E+10 0.218520E+11 0.00 0.584960E+10 0.77 0.00 0.252707E+11 0.00 0.00 0.00 0.00 0.00
July 0.196898E+10 0.108839E+10 0.225802E+11 0.00 0.649231E+10 0.79 0.00 0.292374E+11 0.00 0.00 0.00 0.00 0.00
August 0.203350E+10 0.117567E+10 0.225804E+11 0.00 0.629141E+10 0.80 0.00 0.277570E+11 0.00 0.00 0.00 0.00 0.00
September 0.197404E+10 0.125546E+10 0.218518E+11 0.00 0.578325E+10 0.77 0.00 0.243147E+11 0.00 0.00 0.00 0.00 0.00
October 0.206041E+10 0.142268E+10 0.225803E+11 0.00 0.557733E+10 0.79 0.00 0.195095E+11 0.00 0.00 0.00 0.00 0.00
November 0.204468E+10 0.148107E+10 0.218519E+11 0.00 0.470215E+10 0.77 0.00 0.781980E+10 0.00 0.00 0.00 0.00 0.00
December 0.212860E+10 0.159065E+10 0.225802E+11 0.00 0.478876E+10 0.79 0.00 0.494384E+10 0.00 0.00 0.00 0.00 0.00
                           
Annual Sum or Average 0.241926E+11 0.155846E+11 0.265865E+12 0.00 0.636937E+11 9.37 0.00 0.183889E+12 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.188717E+10 0.102327E+10 0.203951E+11 0.00 0.428392E+10 0.72 0.00 0.266237E+10 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.212860E+10 0.159065E+10 0.225804E+11 0.00 0.649231E+10 0.80 0.00 0.292374E+11 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [J] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.405257E+11 0.00 0.858513E+10 0.00 0.159443E+11 0.00 0.00
February 0.366039E+11 0.00 0.600176E+10 0.00 0.142845E+11 0.00 0.00
March 0.405257E+11 0.00 0.385733E+10 0.00 0.153357E+11 0.00 0.00
April 0.392184E+11 0.00 0.184844E+09 0.00 0.140344E+11 0.00 0.00
May 0.405257E+11 0.00 0.00 0.00 0.136747E+11 0.00 0.00
June 0.392184E+11 0.00 0.00 0.00 0.125827E+11 0.00 0.00
July 0.405257E+11 0.00 0.00 0.00 0.126315E+11 0.00 0.00
August 0.405257E+11 0.00 0.00 0.00 0.127765E+11 0.00 0.00
September 0.392184E+11 0.00 0.00 0.00 0.128375E+11 0.00 0.00
October 0.405257E+11 0.00 0.101567E+09 0.00 0.140527E+11 0.00 0.00
November 0.392184E+11 0.00 0.102048E+10 0.00 0.144410E+11 0.00 0.00
December 0.405257E+11 0.00 0.567731E+10 0.00 0.155906E+11 0.00 0.00
               
Annual Sum or Average 0.477158E+12 0.00 0.254284E+11 0.00 0.168186E+12 0.00 0.00
Minimum of Months 0.366039E+11 0.00 0.00 0.00 0.125827E+11 0.00 0.00
Maximum of Months 0.405257E+11 0.00 0.858513E+10 0.00 0.159443E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 1583.48 02-JAN-17:40 1372.31 01-JAN-06:10 14073.79 01-JAN-11:09 0.00 2654.66 19-JAN-11:00 0.00 01-JAN-07:10 0.00 01-JAN-00:10
February 1583.48 01-FEB-18:10 1372.31 01-FEB-06:10 14073.79 01-FEB-11:09 0.00 2862.20 05-FEB-07:10 0.00 01-FEB-12:39 0.00 01-FEB-00:10
March 1583.48 01-MAR-18:10 1372.31 01-MAR-06:10 14073.79 01-MAR-11:09 0.00 2759.95 07-MAR-11:00 0.00 23-MAR-08:30 0.00 01-MAR-00:10
April 1583.48 01-APR-18:30 1372.31 01-APR-05:10 14073.79 01-APR-10:09 0.00 3115.75 28-APR-17:10 0.00 14-APR-10:39 0.00 01-APR-00:10
May 1583.48 01-MAY-18:00 1372.31 01-MAY-05:10 14073.79 01-MAY-10:09 0.00 3398.23 24-MAY-12:00 0.00 12-MAY-10:30 0.00 01-MAY-00:10
June 1583.48 01-JUN-19:19 1372.31 01-JUN-05:10 14073.79 01-JUN-10:09 0.00 3557.89 29-JUN-11:00 0.00 01-JUN-13:20 0.00 01-JUN-00:10
July 1583.48 01-JUL-19:19 1372.31 01-JUL-05:10 14073.79 01-JUL-10:09 0.00 3746.02 20-JUL-11:00 0.00 03-JUL-14:39 0.00 01-JUL-00:10
August 1583.48 01-AUG-19:19 1372.31 01-AUG-05:10 14073.79 01-AUG-10:09 0.00 3647.70 24-AUG-17:00 0.00 05-AUG-14:50 0.00 01-AUG-00:10
September 1583.48 01-SEP-18:30 1372.31 01-SEP-05:10 14073.79 01-SEP-10:09 0.00 4002.92 09-SEP-18:19 0.00 15-SEP-12:30 0.00 01-SEP-00:10
October 1583.48 02-OCT-18:19 1372.31 01-OCT-05:10 14073.79 01-OCT-10:09 0.00 3867.20 06-OCT-11:20 0.00 17-OCT-11:50 0.00 01-OCT-00:10
November 1583.48 01-NOV-17:19 1372.31 01-NOV-05:10 14073.79 01-NOV-10:09 0.00 3184.98 02-NOV-11:00 0.00 25-NOV-10:39 0.00 01-NOV-00:10
December 1583.48 01-DEC-17:19 1372.31 01-DEC-06:10 14073.79 01-DEC-11:09 0.00 2854.69 15-DEC-12:09 0.00 12-DEC-12:50 0.00 01-DEC-00:10
                           
Annual Sum or Average             0.00            
Minimum of Months 1583.48   1372.31   14073.79   0.00 2654.66   0.00   0.00  
Maximum of Months 1583.48   1372.31   14073.79   0.00 4002.92   0.00   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 12620.81 19-JAN-12:09 0.00 0.00 0.00 0.00 0.00
February 11582.52 02-FEB-12:09 0.00 0.00 0.00 0.00 0.00
March 13569.55 30-MAR-12:00 0.00 0.00 0.00 0.00 0.00
April 16023.24 28-APR-16:10 0.00 0.00 0.00 0.00 0.00
May 17860.35 24-MAY-12:00 0.00 0.00 0.00 0.00 0.00
June 18658.41 29-JUN-11:00 0.00 0.00 0.00 0.00 0.00
July 19931.30 20-JUL-11:00 0.00 0.00 0.00 0.00 0.00
August 19446.52 24-AUG-17:30 0.00 0.00 0.00 0.00 0.00
September 21617.42 09-SEP-18:19 0.00 0.00 0.00 0.00 0.00
October 20018.93 06-OCT-11:20 0.00 0.00 0.00 0.00 0.00
November 16045.88 02-NOV-11:00 0.00 0.00 0.00 0.00 0.00
December 14385.05 14-DEC-12:00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00
Minimum of Months 11582.52   0.00 0.00 0.00 0.00 0.00
Maximum of Months 21617.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 32416.91 19-JAN-11:00 1065.50 14073.79 0.00 0.00 2654.66 0.00 0.00 12039.17 0.00
February 30948.75 02-FEB-11:00 1065.50 14073.79 0.00 0.00 2472.42 0.00 0.00 10753.25 0.00
March 32937.33 07-MAR-11:50 1065.50 14073.79 0.00 0.00 2758.06 0.00 0.00 12456.19 0.00
April 35393.41 28-APR-11:20 1065.50 13174.05 0.00 0.00 3043.20 0.00 0.00 15516.75 0.00
May 37618.05 24-MAY-11:20 1065.50 13174.05 0.00 0.00 3382.25 0.00 0.00 17356.12 0.00
June 38393.69 21-JUN-10:20 1065.50 14073.79 0.00 0.00 3063.25 0.00 0.00 15820.85 0.00
July 40483.59 18-JUL-11:09 1065.50 13174.05 0.00 0.00 3729.61 0.00 0.00 19852.33 0.00
August 38995.42 14-AUG-10:20 1065.50 14073.79 0.00 0.00 3158.85 0.00 0.00 16326.99 0.00
September 41390.19 09-SEP-18:40 1583.48 10924.69 1372.31 0.00 3996.20 0.00 0.00 21561.16 0.00
October 40806.52 06-OCT-11:20 1065.50 13174.05 0.00 0.00 3867.20 0.00 0.00 20018.93 0.00
November 36042.76 02-NOV-10:20 1065.50 14073.79 0.00 0.00 2775.03 0.00 0.00 13758.15 0.00
December 34064.55 15-DEC-12:09 1065.50 13174.05 0.00 0.00 2854.69 0.00 0.00 14381.72 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 30948.75   1065.50 10924.69 0.00 0.00 2472.42 0.00 0.00 10753.25 0.00
Maximum of Months 41390.19   1583.48 14073.79 1372.31 0.00 3996.20 0.00 0.00 21561.16 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 26660.45 01-JAN-11:09 0.00 37535.14 05-JAN-07:00 0.00 24818.89 21-JAN-13:20 0.00
February 26660.45 01-FEB-11:09 0.00 71708.14 05-FEB-03:30 0.00 24785.57 04-FEB-13:50 0.00
March 26660.45 01-MAR-11:09 0.00 32023.35 09-MAR-07:10 0.00 24485.01 01-MAR-13:50 0.00
April 26660.45 01-APR-10:09 0.00 9317.90 11-APR-06:10 0.00 23770.56 02-APR-12:39 0.00
May 26660.45 01-MAY-10:09 0.00 0.00 01-MAY-00:10 0.00 22814.19 02-MAY-12:20 0.00
June 26660.45 01-JUN-10:09 0.00 0.00 01-JUN-00:10 0.00 21720.45 03-JUN-12:50 0.00
July 26660.45 01-JUL-10:09 0.00 0.00 01-JUL-00:10 0.00 20935.63 07-JUL-12:20 0.00
August 26660.45 01-AUG-10:09 0.00 0.00 01-AUG-00:10 0.00 21063.55 19-AUG-12:39 0.00
September 26660.45 01-SEP-10:09 0.00 0.00 01-SEP-00:10 0.00 22274.19 30-SEP-12:50 0.00
October 26660.45 01-OCT-10:09 0.00 7815.80 28-OCT-06:10 0.00 23333.44 31-OCT-12:30 0.00
November 26660.45 01-NOV-10:09 0.00 10679.25 12-NOV-07:10 0.00 24141.98 29-NOV-13:00 0.00
December 26660.45 01-DEC-11:09 0.00 36885.69 21-DEC-07:10 0.00 24688.01 30-DEC-13:39 0.00
                   
Annual Sum or Average     0.00     0.00     0.00
Minimum of Months 26660.45   0.00 0.00   0.00 20935.63   0.00
Maximum of Months 26660.45   0.00 71708.14   0.00 24818.89   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.33 24.55 0.00 24.55
February 0.50 20.39 0.00 20.39 0.83 22.95 0.00 22.95
March 0.17 20.53 0.00 20.53 0.67 23.72 0.00 23.72
April 0.00 0.00 0.00 0.00 4.17 24.61 0.00 24.61
May 0.00 0.00 0.00 0.00 15.50 24.78 0.00 24.78
June 0.00 0.00 0.00 0.00 15.00 24.86 0.00 24.86
July 0.00 0.00 0.00 0.00 15.50 25.00 0.00 25.00
August 0.00 0.00 0.00 0.00 15.50 25.06 0.00 25.06
September 0.00 0.00 0.00 0.00 15.17 25.02 0.17 25.01
October 0.00 0.00 0.00 0.00 13.67 24.96 0.33 24.94
November 0.00 0.00 0.00 0.00 6.67 24.69 0.67 24.67
December 0.17 20.54 0.00 20.54 5.00 24.52 0.33 24.52
                 
Annual Sum or Average 0.83 20.45 0.00 20.45 109.00 24.86 1.50 24.85
Minimum of Months 0.00 0.00 0.00 0.00 0.67 22.95 0.00 22.95
Maximum of Months 0.50 20.54 0.00 20.54 15.50 25.06 0.67 25.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 16.67 28.65 0.00 28.65
February 0.00 0.00 0.00 0.00 17.17 29.27 0.00 29.27
March 0.00 0.00 0.00 0.00 20.33 29.31 0.00 29.31
April 0.00 0.00 0.00 0.00 26.00 29.72 1.33 29.57
May 0.00 0.00 0.00 0.00 65.50 28.63 30.50 28.15
June 0.00 0.00 0.00 0.00 150.50 27.84 116.33 27.56
July 0.00 0.00 0.00 0.00 273.33 27.80 236.17 27.64
August 0.00 0.00 0.00 0.00 225.50 27.80 189.00 27.61
September 0.00 0.00 0.00 0.00 152.83 28.08 116.67 27.83
October 0.00 0.00 0.00 0.00 112.67 28.35 79.67 28.07
November 0.00 0.00 0.00 0.00 32.33 28.93 9.00 28.49
December 0.00 0.00 0.00 0.00 18.83 29.17 0.00 29.17
                 
Annual Sum or Average 0.00   0.00   1111.67 28.11 778.67 27.82
Minimum of Months 0.00 0.00 0.00 0.00 16.67 27.80 0.00 27.56
Maximum of Months 0.00 0.00 0.00 0.00 273.33 29.72 236.17 29.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 495.17 21.77 216.83 22.26 132.17 22.38
February 423.17 22.18 281.50 22.68 179.83 22.79
March 442.83 22.31 288.50 22.86 173.33 23.01
April 330.83 23.38 457.50 23.68 243.67 23.73
May 490.33 24.03 611.00 24.01 490.33 24.02
June 486.50 24.04 592.00 24.03 486.50 24.03
July 600.00 24.04 609.00 24.04 600.00 24.04
August 558.50 24.04 612.00 24.03 558.50 24.03
September 569.17 24.01 590.00 24.01 569.17 24.01
October 380.00 23.82 550.17 23.91 342.50 23.94
November 326.50 22.80 375.67 23.38 164.17 23.49
December 451.50 22.10 276.67 22.71 156.00 22.86
             
Annual Sum or Average 5554.50 23.27 5460.83 23.58 4096.17 23.67
Minimum of Months 326.50 21.77 216.83 22.26 132.17 22.38
Maximum of Months 600.00 24.04 612.00 24.04 600.00 24.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 444.33 23.13 386.67 24.01 251.50 24.35
February 436.67 24.28 434.33 24.74 333.83 24.97
March 464.33 24.76 488.17 25.17 363.67 25.39
April 522.17 26.08 577.33 26.01 518.83 26.04
May 611.00 26.31 611.00 26.31 611.00 26.31
June 592.00 26.51 592.00 26.51 592.00 26.51
July 609.00 26.85 609.00 26.85 609.00 26.85
August 612.00 26.70 612.00 26.70 612.00 26.70
September 590.00 26.55 590.00 26.55 590.00 26.55
October 579.00 26.41 605.00 26.38 575.67 26.40
November 480.00 25.70 538.17 25.74 441.83 25.85
December 454.83 24.31 452.33 24.80 330.00 25.09
             
Annual Sum or Average 6395.33 25.77 6496.00 25.93 5829.33 26.05
Minimum of Months 436.67 23.13 386.67 24.01 251.50 24.35
Maximum of Months 612.00 26.85 612.00 26.85 612.00 26.85



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 610.00000 22.14233 48.83777 0.09505 8.82648
February 551.00000 22.54748 53.23290 0.22104 9.84507
March 612.00000 22.71494 51.98858 0.24374 9.84807
April 590.00000 23.57046 60.43781 0.52966 12.26741
May 611.00000 24.00220 70.29264 -0.0894 5.45196
June 592.00000 24.01436 70.65321 -0.0621 5.44931
July 609.00000 24.03436 74.85776 -0.0086 5.45072
August 612.00000 24.02543 73.05520 -0.0032 5.42391
September 590.00000 24.00376 73.61758 -0.0162 5.40286
October 610.00000 23.83649 64.55382 0.69947 16.37875
November 591.00000 23.22181 54.49396 0.44195 11.51272
December 609.00000 22.51733 52.09307 0.22668 10.08383
           
Annual Sum or Average 7187.00000 23.38953 62.39240 0.18913 8.82057
Minimum of Months 551.00000 22.14233 48.83777 -0.0894 5.40286
Maximum of Months 612.00000 24.03436 74.85776 0.69947 16.37875



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 610.00000 23.30945 49.20992 0.58496 21.72017
February 551.00000 24.19332 51.09561 0.80874 27.53736
March 612.00000 24.57971 49.63826 0.88955 28.35925
April 590.00000 25.85396 54.79095 1.25020 38.82523
May 611.00000 26.31420 63.43041 0.92296 23.56440
June 592.00000 26.50744 64.11306 1.00976 27.53226
July 609.00000 26.85360 66.60221 1.15776 34.50153
August 612.00000 26.69896 65.09429 1.10797 32.06146
September 590.00000 26.54581 64.22530 1.04040 28.91559
October 610.00000 26.30372 58.04684 1.43172 47.73968
November 591.00000 25.37428 50.59205 1.11749 34.46632
December 609.00000 24.08878 50.31265 0.79325 26.39046
           
Annual Sum or Average 7187.00000 25.55774 57.30182 1.01016 30.97787
Minimum of Months 551.00000 23.30945 49.20992 0.58496 21.72017
Maximum of Months 612.00000 26.85360 66.60221 1.43172 47.73968



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_1:1 COOLING COIL

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.352064E+10 0.950244E+09 104.76 0.207354E+10 0.144710E+10 0.00 1.00 01-JAN-03:01 0.00 01-JAN-00:10 56104.16 31-JAN-03:02 29681.25 01-JAN-03:01 33495.83 31-JAN-03:02 13078.58 31-JAN-03:02 0.00 01-JAN-00:10
February 0.480265E+10 0.128556E+10 132.94 0.284682E+10 0.195583E+10 0.00 1.00 01-FEB-03:01 0.00 01-FEB-00:05 56430.21 03-FEB-03:02 24592.28 28-FEB-04:21 33398.72 03-FEB-03:02 13100.93 03-FEB-03:02 0.00 01-FEB-00:05
March 0.784703E+10 0.208508E+10 209.41 0.472190E+10 0.312513E+10 0.00 1.00 06-MAR-03:02 0.00 01-MAR-00:10 57474.50 07-MAR-03:02 30307.84 26-MAR-02:62 34240.28 07-MAR-03:02 13173.97 07-MAR-03:02 0.00 01-MAR-00:10
April 0.155971E+11 0.405097E+10 351.59 0.932027E+10 0.627681E+10 0.00 1.00 01-APR-02:62 0.00 01-APR-00:01 58472.44 28-APR-02:61 29867.49 13-APR-02:61 35911.94 29-APR-02:61 13246.94 28-APR-02:61 0.00 01-APR-00:01
May 0.436523E+11 0.108036E+11 630.86 0.232996E+11 0.203527E+11 0.00 1.00 01-MAY-11:02 0.00 01-MAY-00:01 58472.44 02-MAY-02:61 30845.65 12-MAY-02:61 37273.45 24-MAY-02:61 13246.94 02-MAY-02:61 0.00 01-MAY-00:01
June 0.473906E+11 0.115785E+11 608.43 0.248804E+11 0.225102E+11 0.00 1.00 01-JUN-02:61 0.00 01-JUN-00:01 58472.44 26-JUN-02:61 31071.78 11-JUN-02:61 37363.93 30-JUN-02:61 13246.94 02-JUN-02:61 0.00 01-JUN-00:01
July 0.550529E+11 0.132670E+11 631.44 0.265286E+11 0.285243E+11 0.00 1.00 01-JUL-02:61 0.00 01-JUL-00:02 58472.44 06-JUL-02:61 26630.19 19-JUL-02:61 38617.80 15-JUL-02:02 13246.94 01-JUL-02:61 0.00 01-JUL-00:02
August 0.522512E+11 0.126715E+11 629.54 0.261096E+11 0.261417E+11 0.00 1.00 01-AUG-02:61 0.00 01-AUG-00:02 58472.44 13-AUG-02:61 36684.28 20-AUG-03:21 38124.24 18-AUG-02:61 13246.94 01-AUG-02:61 0.00 01-AUG-00:02
September 0.446788E+11 0.108872E+11 605.20 0.217384E+11 0.229404E+11 0.00 1.00 01-SEP-02:61 0.00 01-SEP-00:01 58472.44 02-SEP-02:61 28646.93 09-SEP-18:10 39111.08 05-SEP-02:61 13815.56 10-SEP-02:61 0.00 01-SEP-00:01
October 0.359045E+11 0.882359E+10 532.73 0.187010E+11 0.172034E+11 0.00 1.00 01-OCT-02:61 0.00 01-OCT-00:01 58472.44 07-OCT-02:61 39270.58 05-OCT-02:61 40959.39 07-OCT-02:61 13246.94 06-OCT-02:61 0.00 01-OCT-00:01
November 0.123724E+11 0.316711E+10 280.89 0.684362E+10 0.552874E+10 0.00 1.00 01-NOV-02:61 0.00 01-NOV-00:01 58472.44 02-NOV-02:61 31619.45 20-NOV-03:01 36926.60 03-NOV-02:61 13246.94 02-NOV-02:61 0.00 01-NOV-00:01
December 0.736770E+10 0.191418E+10 181.58 0.410964E+10 0.325806E+10 0.00 1.00 09-DEC-03:02 0.00 01-DEC-00:10 57249.59 16-DEC-03:01 26677.40 09-DEC-03:02 34713.93 12-DEC-03:02 13158.01 16-DEC-03:01 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.330438E+12 0.814845E+11 4899.36 0.171173E+12 0.159264E+12 0.00                            
Minimum of Months 0.352064E+10 0.950244E+09 104.76 0.207354E+10 0.144710E+10 0.00 1.00   0.00   56104.16   24592.28   33398.72   13078.58   0.00  
Maximum of Months 0.550529E+11 0.132670E+11 631.44 0.265286E+11 0.285243E+11 0.00 1.00   0.00   58472.44   39270.58   40959.39   13815.56   0.00  



Table of Contents

Report: DXReportMonthly

For: PSZ-AC_2:2 COOLING COIL

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP}
January 0.702908E+10 0.171213E+10 197.38 0.379778E+10 0.323131E+10 0.00 1.00 01-JAN-03:01 0.00 01-JAN-00:10 32708.49 20-JAN-03:15 23129.54 03-JAN-03:11 21243.72 20-JAN-03:15 7511.90 20-JAN-03:11 0.00 01-JAN-00:10
February 0.907962E+10 0.220536E+10 244.06 0.495957E+10 0.412005E+10 0.00 1.00 01-FEB-03:01 0.00 01-FEB-00:05 32451.90 03-FEB-03:11 25645.09 12-FEB-04:31 20306.96 03-FEB-04:31 7494.80 03-FEB-03:11 0.00 01-FEB-00:05
March 0.133759E+11 0.322061E+10 329.95 0.761923E+10 0.575667E+10 0.00 1.00 01-MAR-03:11 0.00 01-MAR-00:10 33375.86 07-MAR-04:31 23771.81 04-MAR-03:11 21048.81 07-MAR-04:31 7557.09 07-MAR-04:31 0.00 01-MAR-00:10
April 0.243659E+11 0.577762E+10 498.68 0.139858E+11 0.103801E+11 0.00 1.00 01-APR-01:32 0.00 01-APR-00:01 34222.93 27-APR-11:08 23786.78 28-APR-14:10 21593.05 29-APR-02:61 7987.42 28-APR-15:23 0.00 01-APR-00:01
May 0.569690E+11 0.129444E+11 647.87 0.298855E+11 0.270835E+11 0.00 1.00 01-MAY-01:32 0.00 01-MAY-00:01 34222.93 14-MAY-02:42 25218.72 07-MAY-13:55 23116.32 24-MAY-00:42 8123.75 07-MAY-13:55 0.00 01-MAY-00:01
June 0.601472E+11 0.136921E+11 637.68 0.311257E+11 0.290216E+11 0.00 1.00 01-JUN-00:42 0.00 01-JUN-00:01 34222.93 29-JUN-20:25 26307.95 14-JUN-14:00 23600.87 29-JUN-21:00 8263.48 14-JUN-14:00 0.00 01-JUN-00:01
July 0.703141E+11 0.159705E+11 677.07 0.324113E+11 0.379028E+11 0.00 1.00 01-JUL-00:42 0.00 01-JUL-00:02 34222.93 02-JUL-20:30 26701.66 07-JUL-15:00 23136.24 15-JUL-02:61 8411.94 21-JUL-15:53 0.00 01-JUL-00:02
August 0.663768E+11 0.150855E+11 672.67 0.318028E+11 0.345740E+11 0.00 1.00 01-AUG-00:42 0.00 01-AUG-00:02 34222.93 09-AUG-19:00 28405.68 30-AUG-15:55 24576.94 09-AUG-18:58 8439.85 30-AUG-15:55 0.00 01-AUG-00:02
September 0.594407E+11 0.134276E+11 633.38 0.269407E+11 0.325000E+11 0.00 1.00 01-SEP-00:42 0.00 01-SEP-00:01 34222.93 03-SEP-18:46 24174.72 01-SEP-14:00 23858.92 05-SEP-02:61 8453.90 09-SEP-16:53 0.00 01-SEP-00:01
October 0.467311E+11 0.106860E+11 592.22 0.231206E+11 0.236105E+11 0.00 1.00 01-OCT-01:22 0.00 01-OCT-00:01 34222.93 06-OCT-04:09 26387.11 27-OCT-02:51 25074.25 25-OCT-02:53 8136.08 05-OCT-15:00 0.00 01-OCT-00:01
November 0.196038E+11 0.465269E+10 412.79 0.104582E+11 0.914563E+10 0.00 1.00 01-NOV-01:32 0.00 01-NOV-00:01 34222.93 01-NOV-10:53 26930.03 23-NOV-03:01 23074.99 01-NOV-02:52 7704.40 01-NOV-14:00 0.00 01-NOV-00:01
December 0.127318E+11 0.302967E+10 292.82 0.661157E+10 0.612027E+10 0.00 1.00 01-DEC-03:11 0.00 01-DEC-00:10 34222.93 12-DEC-14:01 24864.33 26-DEC-04:21 22014.35 15-DEC-04:31 7617.30 12-DEC-13:43 0.00 01-DEC-00:10
                                         
Annual Sum or Average 0.446165E+12 0.102404E+12 5836.58 0.222719E+12 0.223446E+12 0.00                            
Minimum of Months 0.702908E+10 0.171213E+10 197.38 0.379778E+10 0.323131E+10 0.00 1.00   0.00   32451.90   23129.54   20306.96   7494.80   0.00  
Maximum of Months 0.703141E+11 0.159705E+11 677.07 0.324113E+11 0.379028E+11 0.00 1.00   0.00   34222.93   28405.68   25074.25   8453.90   0.00  



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 80.27 40.87 39.40 95.31 120.78 0.00 0.00 0.00
February 89.38 43.15 46.23 112.70 102.37 0.00 0.00 0.00
March 105.14 50.71 54.44 146.57 85.76 0.00 0.00 0.00
April 115.38 52.18 63.20 183.36 55.27 0.00 0.00 0.00
May 118.93 51.57 67.36 231.36 15.59 0.00 0.00 0.00
June 120.61 47.83 72.78 242.69 13.69 0.00 0.00 0.00
July 116.29 42.56 73.73 234.97 9.55 0.00 0.00 0.00
August 107.16 36.84 70.32 214.25 14.55 0.00 0.00 0.00
September 94.92 32.63 62.29 180.06 20.96 0.00 0.00 0.00
October 93.80 39.58 54.22 167.31 37.47 0.00 0.00 0.00
November 83.05 42.37 40.68 116.08 81.22 0.00 0.00 0.00
December 65.39 29.62 35.77 80.20 107.54 0.00 0.00 0.00
                 
Annual Sum or Average 99.23 42.47 56.75 167.37 55.15 0.00 0.00 0.00
Minimum of Months 65.39 29.62 35.77 80.20 9.55 0.00 0.00 0.00
Maximum of Months 120.61 52.18 73.73 242.69 120.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 360.57 257.15 103.42 532.52 228.38 0.00 0.00 0.00
February 327.02 211.67 115.35 491.08 198.05 0.00 0.00 0.00
March 208.78 94.22 114.56 322.83 175.11 0.00 0.00 0.00
April 154.74 36.26 118.48 262.99 115.94 0.00 0.00 0.00
May 118.23 5.02 113.21 255.83 32.41 0.00 0.00 0.00
June 116.80 1.09 115.71 260.44 28.72 0.00 0.00 0.00
July 122.27 2.25 120.02 271.59 19.53 0.00 0.00 0.00
August 143.84 17.27 126.57 317.17 30.26 0.00 0.00 0.00
September 172.58 45.48 127.10 350.41 43.08 0.00 0.00 0.00
October 267.76 139.48 128.28 498.63 75.20 0.00 0.00 0.00
November 340.75 234.61 106.14 543.98 157.23 0.00 0.00 0.00
December 352.32 253.02 99.30 539.84 203.71 0.00 0.00 0.00
                 
Annual Sum or Average 223.26 107.59 115.67 386.78 108.48 0.00 0.00 0.00
Minimum of Months 116.80 1.09 99.30 255.83 19.53 0.00 0.00 0.00
Maximum of Months 360.57 257.15 128.28 543.98 228.38 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: DINING_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 85.38 46.17 39.21 108.26 124.71 0.00 0.00 0.00
February 96.67 48.93 47.74 128.05 106.09 0.00 0.00 0.00
March 95.28 42.18 53.10 133.35 88.96 0.00 0.00 0.00
April 118.34 54.44 63.90 190.10 56.38 0.00 0.00 0.00
May 98.41 32.06 66.35 196.90 16.20 0.00 0.00 0.00
June 109.32 38.33 70.99 222.93 14.21 0.00 0.00 0.00
July 99.79 27.68 72.11 205.07 9.77 0.00 0.00 0.00
August 100.90 30.89 70.01 205.03 14.98 0.00 0.00 0.00
September 92.91 31.87 61.04 177.93 21.33 0.00 0.00 0.00
October 95.12 41.10 54.02 172.80 38.36 0.00 0.00 0.00
November 81.53 40.97 40.56 118.35 84.24 0.00 0.00 0.00
December 78.43 41.71 36.72 104.76 108.18 0.00 0.00 0.00
                 
Annual Sum or Average 95.95 39.60 56.35 163.77 56.69 0.00 0.00 0.00
Minimum of Months 78.43 27.68 36.72 104.76 9.77 0.00 0.00 0.00
Maximum of Months 118.34 54.44 72.11 222.93 124.71 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_EAST_WINDOW

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.214993E+09 0.109475E+09 0.105518E+09 0.255273E+09 0.323505E+09
February 0.216234E+09 0.104392E+09 0.111842E+09 0.272633E+09 0.247642E+09
March 0.281615E+09 0.135815E+09 0.145800E+09 0.392561E+09 0.229707E+09
April 0.299071E+09 0.135261E+09 0.163810E+09 0.475267E+09 0.143267E+09
May 0.318537E+09 0.138123E+09 0.180414E+09 0.619673E+09 41758436.09
June 0.312629E+09 0.123980E+09 0.188649E+09 0.629051E+09 35495213.97
July 0.311467E+09 0.113980E+09 0.197487E+09 0.629346E+09 25588290.91
August 0.287007E+09 98674989.71 0.188332E+09 0.573850E+09 38982340.17
September 0.246034E+09 84585602.86 0.161449E+09 0.466719E+09 54322373.60
October 0.251237E+09 0.106021E+09 0.145216E+09 0.448135E+09 0.100373E+09
November 0.215259E+09 0.109812E+09 0.105447E+09 0.300868E+09 0.210516E+09
December 0.175132E+09 79330662.88 95801096.14 0.214797E+09 0.288048E+09
           
Annual Sum or Average 0.312922E+10 0.133945E+10 0.178976E+10 0.527817E+10 0.173921E+10
Minimum of Months 0.175132E+09 79330662.88 95801096.14 0.214797E+09 25588290.91
Maximum of Months 0.318537E+09 0.138123E+09 0.197487E+09 0.629346E+09 0.323505E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.965759E+09 0.688754E+09 0.277006E+09 0.142631E+10 0.611696E+09
February 0.791126E+09 0.512082E+09 0.279044E+09 0.118803E+10 0.479132E+09
March 0.559187E+09 0.252361E+09 0.306826E+09 0.864669E+09 0.469004E+09
April 0.401093E+09 93985801.80 0.307107E+09 0.681682E+09 0.300506E+09
May 0.316680E+09 13458402.47 0.303222E+09 0.685213E+09 86813793.59
June 0.302735E+09 2821766.29 0.299913E+09 0.675062E+09 74453902.40
July 0.327478E+09 6018982.18 0.321459E+09 0.727417E+09 52297356.16
August 0.385260E+09 46242650.92 0.339017E+09 0.849498E+09 81044655.47
September 0.447336E+09 0.117892E+09 0.329444E+09 0.908252E+09 0.111657E+09
October 0.717179E+09 0.373582E+09 0.343597E+09 0.133553E+10 0.201405E+09
November 0.883216E+09 0.608103E+09 0.275113E+09 0.141000E+10 0.407547E+09
December 0.943664E+09 0.677689E+09 0.265976E+09 0.144592E+10 0.545607E+09
           
Annual Sum or Average 0.704071E+10 0.339299E+10 0.364772E+10 0.121976E+11 0.342116E+10
Minimum of Months 0.302735E+09 2821766.29 0.265976E+09 0.675062E+09 52297356.16
Maximum of Months 0.965759E+09 0.688754E+09 0.343597E+09 0.144592E+10 0.611696E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: DINING_WALL_WEST_WINDOW

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.228679E+09 0.123657E+09 0.105022E+09 0.289971E+09 0.334036E+09
February 0.233859E+09 0.118365E+09 0.115494E+09 0.309790E+09 0.256658E+09
March 0.255188E+09 0.112965E+09 0.142223E+09 0.357167E+09 0.238271E+09
April 0.306725E+09 0.141099E+09 0.165626E+09 0.492733E+09 0.146135E+09
May 0.263581E+09 85861901.14 0.177719E+09 0.527368E+09 43402981.74
June 0.283363E+09 99360233.75 0.184003E+09 0.577834E+09 36826760.70
July 0.267279E+09 74138973.77 0.193140E+09 0.549251E+09 26170256.45
August 0.270253E+09 82728047.85 0.187525E+09 0.549145E+09 40123882.27
September 0.240830E+09 82616000.38 0.158214E+09 0.461188E+09 55284123.45
October 0.254779E+09 0.110087E+09 0.144692E+09 0.462815E+09 0.102738E+09
November 0.211331E+09 0.106206E+09 0.105125E+09 0.306755E+09 0.218339E+09
December 0.210059E+09 0.111706E+09 98352510.44 0.280592E+09 0.289761E+09
           
Annual Sum or Average 0.302593E+10 0.124879E+10 0.177714E+10 0.516461E+10 0.178775E+10
Minimum of Months 0.210059E+09 74138973.77 98352510.44 0.280592E+09 26170256.45
Maximum of Months 0.306725E+09 0.141099E+09 0.193140E+09 0.577834E+09 0.334036E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 719.99 457.77 526.22 344.19 182.03 0.00 0.00
February 718.45 393.13 513.07 303.75 209.32 0.00 0.00
March 591.54 338.62 409.20 187.10 222.09 0.00 0.00
April 627.93 219.06 388.46 142.88 245.58 0.00 0.00
May 683.07 63.20 335.57 88.65 246.92 0.00 0.00
June 725.18 55.75 346.73 87.25 259.48 0.00 0.00
July 711.22 38.44 338.35 72.48 265.86 0.00 0.00
August 735.84 59.19 351.90 84.99 266.90 0.00 0.00
September 707.56 84.52 360.42 109.99 250.43 0.00 0.00
October 836.81 149.09 456.69 220.17 236.52 0.00 0.00
November 769.72 314.00 505.33 317.95 187.38 0.00 0.00
December 714.79 409.43 496.14 324.35 171.79 0.00 0.00
               
Annual Sum or Average 711.83 214.24 418.44 189.66 228.77 0.00 0.00
Minimum of Months 591.54 38.44 335.57 72.48 171.79 0.00 0.00
Maximum of Months 836.81 457.77 526.22 344.19 266.90 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.192842E+10 0.122610E+10 0.140943E+10 0.921885E+09 0.487546E+09 0.00 0.00
February 0.173807E+10 0.951053E+09 0.124122E+10 0.734839E+09 0.506381E+09 0.00 0.00
March 0.158438E+10 0.906969E+09 0.109599E+10 0.501141E+09 0.594849E+09 0.00 0.00
April 0.162759E+10 0.567812E+09 0.100689E+10 0.370346E+09 0.636543E+09 0.00 0.00
May 0.182954E+10 0.169265E+09 0.898798E+09 0.237444E+09 0.661355E+09 0.00 0.00
June 0.187968E+10 0.144508E+09 0.898727E+09 0.226162E+09 0.672565E+09 0.00 0.00
July 0.190493E+10 0.102970E+09 0.906224E+09 0.194138E+09 0.712086E+09 0.00 0.00
August 0.197087E+10 0.158527E+09 0.942520E+09 0.227646E+09 0.714874E+09 0.00 0.00
September 0.183398E+10 0.219087E+09 0.934200E+09 0.285093E+09 0.649107E+09 0.00 0.00
October 0.224130E+10 0.399335E+09 0.122320E+10 0.589690E+09 0.633505E+09 0.00 0.00
November 0.199511E+10 0.813887E+09 0.130981E+10 0.824121E+09 0.485685E+09 0.00 0.00
December 0.191450E+10 0.109661E+10 0.132885E+10 0.868726E+09 0.460129E+09 0.00 0.00
               
Annual Sum or Average 0.224484E+11 0.675613E+10 0.131959E+11 0.598123E+10 0.721462E+10 0.00 0.00
Minimum of Months 0.158438E+10 0.102970E+09 0.898727E+09 0.194138E+09 0.460129E+09 0.00 0.00
Maximum of Months 0.224130E+10 0.122610E+10 0.140943E+10 0.921885E+09 0.714874E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.57 11.02 8.64 3.24 3.13 48.31 209.17 0.01
February 15.49 12.82 10.40 2.82 4.36 58.07 218.23 0.02
March 17.07 13.58 10.72 3.68 7.24 76.61 186.08 0.03
April 21.23 17.54 15.23 2.65 11.47 90.28 216.86 0.02
May 26.90 22.82 21.10 3.11 19.64 106.10 173.47 0.04
June 27.61 23.37 21.62 2.44 19.77 115.40 187.69 0.03
July 27.94 24.58 23.34 2.53 20.70 123.49 154.05 0.05
August 27.43 23.90 22.52 3.20 20.40 118.51 145.78 0.03
September 26.23 23.37 22.24 3.39 19.02 101.73 135.58 0.05
October 24.23 20.47 18.40 4.11 16.60 78.24 178.15 0.01
November 18.91 15.31 12.62 2.63 7.99 49.56 205.43 0.01
December 15.68 12.88 10.53 3.17 6.01 45.08 191.18 0.02
                 
Annual Sum or Average 21.89 18.50 16.48 3.09 13.08 84.44 183.16 0.03
Minimum of Months 13.57 11.02 8.64 2.44 3.13 45.08 135.58 0.01
Maximum of Months 27.94 24.58 23.34 4.11 20.70 123.49 218.23 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 27.00 02-JAN-14:00 18.67 14.00 1.50 17.75 146.50 0.00
February 28.30 02-FEB-12:00 20.78 17.20 6.60 17.93 127.50 748.50
March 30.00 26-MAR-13:00 19.88 14.40 3.00 19.52 288.50 548.00
April 33.30 28-APR-14:00 23.06 18.80 4.10 23.15 150.50 762.50
May 33.90 07-MAY-13:00 23.76 19.40 4.10 23.15 287.50 507.50
June 35.00 14-JUN-13:00 23.95 19.40 2.10 24.16 194.50 712.50
July 36.10 21-JUL-15:00 25.96 22.20 1.50 26.65 216.00 245.00
August 36.30 30-AUG-15:00 23.74 18.50 2.40 25.33 116.00 698.50
September 36.40 09-SEP-16:00 26.65 23.40 4.40 26.48 114.00 401.50
October 34.00 05-OCT-14:00 24.05 20.00 2.60 29.55 169.50 606.00
November 30.00 01-NOV-13:00 25.01 23.30 2.00 26.48 216.50 118.00
December 30.00 13-DEC-14:00 21.84 18.00 3.10 20.92 101.50 682.50
                 
Annual Sum or Average                
Minimum of Months 27.00   18.67 14.00 1.50 17.75 101.50 0.00
Maximum of Months 36.40   26.65 23.40 6.60 29.55 288.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.00 05-JAN-05:00 -0.0 -0.0 2.10 -16.0 0.00 0.00
February -3.4 05-FEB-07:10 -5.4 -9.4 4.68 -21.3 0.00 0.00
March 1.10 09-MAR-05:00 -2.1 -7.3 3.60 -14.4 0.00 0.00
April 8.30 11-APR-05:00 6.95 5.50 0.00 -6.9 0.00 0.00
May 21.10 07-MAY-00:00 19.58 18.90 0.00 11.46 0.00 0.00
June 20.60 07-JUN-01:00 18.00 16.70 3.60 10.50 0.00 0.00
July 22.20 11-JUL-19:00 21.37 21.10 2.10 20.22 0.00 0.00
August 20.20 25-AUG-23:00 20.20 20.20 5.30 11.84 0.00 0.00
September 19.20 07-SEP-17:00 19.20 19.20 2.50 16.85 35.00 7.00
October 10.00 28-OCT-04:00 5.56 0.00 3.60 -0.1 0.00 0.00
November 7.20 12-NOV-07:49 4.12 0.18 4.60 -9.0 36.00 517.00
December 0.00 21-DEC-04:00 -0.9 -2.0 2.10 -16.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -3.4   -5.4 -9.4 0.00 -21.3 0.00 0.00
Maximum of Months 22.20   21.37 21.10 5.30 20.22 36.00 517.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 22.11 31-JAN-12:00 25.00 21.00 5.70 20.92 336.50 96.00
February 21.49 24-FEB-12:00 27.70 18.80 4.10 17.75 165.00 746.50
March 22.77 30-MAR-12:00 29.40 20.00 2.50 27.14 340.00 0.00
April 25.55 28-APR-15:00 32.20 23.30 3.60 22.47 156.00 575.50
May 25.84 27-MAY-13:00 31.70 23.90 3.10 22.13 168.50 735.50
June 26.52 29-JUN-16:00 29.40 25.60 1.50 26.32 164.00 36.00
July 27.17 22-JUL-10:00 32.20 25.60 2.10 21.96 191.00 719.50
August 27.24 07-AUG-12:00 31.00 26.00 3.10 27.95 473.00 200.00
September 27.79 10-SEP-12:00 35.00 25.50 2.90 24.66 239.50 662.00
October 28.18 07-OCT-07:00 29.00 28.00 2.60 21.09 95.00 500.50
November 25.01 01-NOV-13:00 30.00 23.30 2.00 26.48 216.50 118.00
December 24.12 12-DEC-13:00 27.00 23.00 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 21.49   25.00 18.80 1.50 17.75 95.00 0.00
Maximum of Months 28.18   35.00 28.00 5.70 27.95 473.00 746.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 31-JAN-12:00 25.00 22.11 5.70 20.92 336.50 96.00
February 20.20 02-FEB-22:00 21.50 20.56 4.80 14.65 0.00 0.00
March 21.10 07-MAR-08:00 23.30 21.69 2.00 13.91 126.00 566.50
April 23.30 28-APR-15:00 32.20 25.55 3.60 22.47 156.00 575.50
May 24.40 26-MAY-08:20 27.07 25.09 3.10 23.71 252.67 47.33
June 25.60 29-JUN-14:00 27.20 26.00 5.10 24.16 335.00 238.00
July 25.60 02-JUL-05:00 26.10 25.71 2.60 19.52 30.50 8.50
August 26.60 09-AUG-18:00 26.60 26.60 1.90 19.52 26.00 23.00
September 25.50 10-SEP-12:00 35.00 27.79 2.90 24.66 239.50 662.00
October 28.00 07-OCT-07:00 29.00 28.18 2.60 21.09 95.00 500.50
November 23.80 01-NOV-10:00 26.10 24.39 2.00 22.64 228.50 113.00
December 23.00 12-DEC-13:00 27.00 24.12 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 20.20   21.50 20.56 1.90 13.91 0.00 0.00
Maximum of Months 28.00   35.00 28.18 5.70 24.66 336.50 662.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.46 29.60 0.00
February 18.00 13.00 16.00 20.78 36.65 0.00
March 18.00 13.00 16.00 22.23 38.94 0.00
April 18.00 13.00 16.00 24.49 49.11 0.00
May 18.00 13.00 16.00 26.95 46.95 0.00
June 18.00 13.00 16.00 28.93 51.71 0.00
July 18.00 13.00 16.00 29.89 48.43 0.00
August 18.00 13.00 16.00 29.58 45.50 0.00
September 18.00 13.00 16.00 28.08 39.22 0.00
October 18.00 13.00 16.00 25.80 37.51 0.00
November 18.00 13.00 16.00 23.35 31.26 0.00
December 18.00 13.00 16.00 21.40 27.18 0.00
             
Annual Sum or Average 18.00 13.00 16.00 25.18 40.17 0.00
Minimum of Months 18.00 13.00 16.00 20.46 27.18 0.00
Maximum of Months 18.00 13.00 16.00 29.89 51.71 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.113242E+11 -0.106137E+11 0.00 0.00 744.00 0.00 -710443206.6 58.98 0.00 0.00
February 0.101335E+11 -0.950669E+10 0.00 0.00 672.00 0.00 -626850261.8 58.98 0.00 0.00
March 0.108327E+11 -0.101464E+11 0.00 0.00 744.00 0.00 -686272930.1 58.98 0.00 0.00
April 0.983237E+10 -0.919120E+10 0.00 0.00 720.00 0.00 -641168240.5 58.98 0.00 0.00
May 0.948901E+10 -0.883519E+10 0.00 0.00 744.00 0.00 -653820089.9 58.98 0.00 0.00
June 0.865641E+10 -0.802693E+10 0.00 0.00 720.00 0.00 -629481205.3 58.98 0.00 0.00
July 0.864889E+10 -0.800450E+10 0.00 0.00 744.00 0.00 -644383556.2 58.98 0.00 0.00
August 0.876312E+10 -0.811603E+10 0.00 0.00 744.00 0.00 -647088550.3 58.99 0.00 0.00
September 0.886382E+10 -0.823508E+10 0.00 0.00 720.00 0.00 -628742051.0 58.98 0.00 0.00
October 0.979670E+10 -0.914238E+10 0.00 0.00 744.00 0.00 -654316310.2 58.98 0.00 0.00
November 0.101567E+11 -0.950687E+10 0.00 0.00 720.00 0.00 -649838716.2 58.99 0.00 0.00
December 0.110386E+11 -0.103432E+11 0.00 0.00 744.00 0.00 -695350389.4 58.99 0.00 0.00
                     
Annual Sum or Average 0.117536E+12 -0.109668E+12 0.00 0.00 8760.00 0.00 -0.786776E+10 58.98 0.00 0.00
Minimum of Months 0.864889E+10 -0.106137E+11 0.00 0.00 672.00 0.00 -710443206.6 58.98 0.00 0.00
Maximum of Months 0.113242E+11 -0.800450E+10 0.00 0.00 744.00 0.00 -626850261.8 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.29 0.24 01-JAN-07:00 1652.44 23.22 108.50 289.83 1743.67 25.12 132.00 296.50
February 295.50 0.28 0.24 01-FEB-11:39 1737.02 24.20 118.83 283.17 1268.23 20.63 50.67 279.17
March 296.00 0.27 0.24 02-MAR-12:39 1164.93 18.31 1.50 333.17 1750.48 20.44 49.50 334.67
April 347.33 0.29 0.24 01-APR-07:19 1119.55 17.50 0.00 335.67 1090.25 17.58 0.17 335.00
May 353.67 0.27 0.24 01-MAY-06:49 975.35 17.84 0.00 369.00 1175.70 17.77 0.00 368.67
June 394.00 0.28 0.24 01-JUN-06:30 1058.34 17.53 0.00 368.67 1134.44 17.48 0.00 368.33
July 390.00 0.27 0.24 01-JUL-06:30 1008.77 17.87 0.00 373.67 1057.85 17.82 0.00 373.83
August 380.83 0.28 0.24 01-AUG-06:00 1048.79 18.10 0.00 356.17 1073.54 18.09 0.00 356.17
September 342.17 0.28 0.24 01-SEP-06:00 1069.34 18.37 4.50 325.67 1120.30 18.37 4.50 329.00
October 330.00 0.27 0.24 01-OCT-06:00 1404.11 21.23 70.83 318.50 1291.46 21.46 64.33 317.33
November 308.00 0.28 0.24 01-NOV-07:49 1367.41 23.23 103.00 289.17 1654.74 24.14 117.83 291.00
December 282.83 0.28 0.24 01-DEC-07:49 1598.93 23.71 104.00 280.50 1586.20 24.04 103.67 281.17
                         
Annual Sum or Average 4027.67 0.28     1244.45 19.87 511.17 3923.17 1305.83 20.01 522.67 3930.83
Minimum of Months 282.83 0.27 0.24   975.35 17.50 0.00 280.50 1057.85 17.48 0.00 279.17
Maximum of Months 394.00 0.29 0.24   1737.02 24.20 118.83 373.67 1750.48 25.12 132.00 373.83



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:1 HEATING COIL

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.605784E+10 18537.74 21-JAN-07:05 0.00 0.00 0.00 0.00 0.00
February 0.402515E+10 57366.52 05-FEB-03:03 0.00 0.00 0.00 0.00 0.00
March 0.282659E+10 16883.03 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.147875E+09 7454.32 11-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:02 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:01 0.00 0.00 0.00 0.00 0.00
October 81253841.58 6252.64 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.816387E+09 8543.40 12-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.409292E+10 18733.11 20-DEC-21:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180480E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.605784E+10 57366.52   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:2 HEATING COIL

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.810268E+09 17071.98 05-JAN-05:15 0.00 0.00 0.00 0.00 0.00
February 0.776258E+09 22559.03 05-FEB-05:15 0.00 0.00 0.00 0.00 0.00
March 0.259271E+09 12167.57 09-MAR-05:06 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:01 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:01 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:02 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:02 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:01 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:01 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:01 0.00 0.00 0.00 0.00 0.00
December 0.448931E+09 18156.70 21-DEC-05:15 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.229473E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.810268E+09 22559.03   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_1:1 COOLING COIL

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.352064E+10 0.207354E+10 56104.16 31-JAN-03:02 22608.33 0.00
February 0.00 0.00 0.480265E+10 0.284682E+10 56430.21 03-FEB-03:02 23031.49 0.00
March 0.00 0.00 0.784703E+10 0.472190E+10 57474.50 07-MAR-03:02 23234.22 0.00
April 0.00 0.00 0.155971E+11 0.932027E+10 58472.44 28-APR-02:61 24188.88 0.00
May 0.00 0.00 0.436523E+11 0.232996E+11 58472.44 02-MAY-02:61 25168.20 0.00
June 0.00 0.00 0.473906E+11 0.248804E+11 58472.44 26-JUN-02:61 25535.40 0.00
July 0.00 0.00 0.550529E+11 0.265286E+11 58472.44 06-JUL-02:61 21474.38 0.00
August 0.00 0.00 0.522512E+11 0.261096E+11 58472.44 13-AUG-02:61 23246.00 0.00
September 0.00 0.00 0.446788E+11 0.217384E+11 58472.44 02-SEP-02:61 22852.56 0.00
October 0.00 0.00 0.359045E+11 0.187010E+11 58472.44 07-OCT-02:61 17513.05 0.00
November 0.00 0.00 0.123724E+11 0.684362E+10 58472.44 02-NOV-02:61 23182.86 0.00
December 0.00 0.00 0.736770E+10 0.410964E+10 57249.59 16-DEC-03:01 23761.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.330438E+12 0.171173E+12       0.00
Minimum of Months 0.00 0.00 0.352064E+10 0.207354E+10 56104.16   17513.05 0.00
Maximum of Months 0.00 0.00 0.550529E+11 0.265286E+11 58472.44   25535.40 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC_2:2 COOLING COIL

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.702908E+10 0.379778E+10 32708.49 20-JAN-03:15 11464.77 0.00
February 0.00 0.00 0.907962E+10 0.495957E+10 32451.90 03-FEB-03:11 12156.97 0.00
March 0.00 0.00 0.133759E+11 0.761923E+10 33375.86 07-MAR-04:31 12327.06 0.00
April 0.00 0.00 0.243659E+11 0.139858E+11 34222.93 27-APR-11:08 16818.00 0.00
May 0.00 0.00 0.569690E+11 0.298855E+11 34222.93 14-MAY-02:42 12915.38 0.00
June 0.00 0.00 0.601472E+11 0.311257E+11 34222.93 29-JUN-20:25 10988.44 0.00
July 0.00 0.00 0.703141E+11 0.324113E+11 34222.93 02-JUL-20:30 14642.99 0.00
August 0.00 0.00 0.663768E+11 0.318028E+11 34222.93 09-AUG-19:00 9646.05 0.00
September 0.00 0.00 0.594407E+11 0.269407E+11 34222.93 03-SEP-18:46 17220.09 0.00
October 0.00 0.00 0.467311E+11 0.231206E+11 34222.93 06-OCT-04:09 10307.32 0.00
November 0.00 0.00 0.196038E+11 0.104582E+11 34222.93 01-NOV-10:53 13200.20 0.00
December 0.00 0.00 0.127318E+11 0.661157E+10 34222.93 12-DEC-14:01 14775.11 0.00
                 
Annual Sum or Average 0.00 0.00 0.446165E+12 0.222719E+12       0.00
Minimum of Months 0.00 0.00 0.702908E+10 0.379778E+10 32451.90   9646.05 0.00
Maximum of Months 0.00 0.00 0.703141E+11 0.324113E+11 34222.93   17220.09 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 4254.37 15592.50 23-JAN-14:00
February 0.00 0.00 01-FEB-00:05 4221.30 15569.42 01-FEB-13:18
March 0.00 0.00 01-MAR-00:10 4082.37 15214.15 01-MAR-13:20
April 0.00 0.00 01-APR-00:01 3837.93 14424.18 01-APR-12:20
May 0.00 0.00 01-MAY-00:01 3592.70 13466.64 01-MAY-12:20
June 0.00 0.00 01-JUN-00:01 3392.17 12546.63 01-JUN-12:54
July 0.00 0.00 01-JUL-00:02 3281.63 11954.37 01-JUL-12:50
August 0.00 0.00 01-AUG-00:02 3326.57 12191.44 31-AUG-12:30
September 0.00 0.00 01-SEP-00:01 3470.58 12952.17 30-SEP-12:20
October 0.00 0.00 01-OCT-00:01 3706.31 13938.47 31-OCT-12:35
November 0.00 0.00 01-NOV-00:01 3961.23 14835.32 30-NOV-13:30
December 0.00 0.00 01-DEC-00:10 4152.81 15448.38 31-DEC-14:00
             
Annual Sum or Average 0.00     3770.83    
Minimum of Months 0.00 0.00   3281.63 11954.37  
Maximum of Months 0.00 0.00   4254.37 15592.50  



Table of Contents

Report: FanReportMonthly

For: DINING EXHAUST FAN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.00 -0.0 0.00 01-JAN-00:10 0.00
February 0.00 -0.0 0.00 01-FEB-00:05 0.00
March 0.00 0.00 0.00 01-MAR-00:10 -0.0
April 0.00 -0.0 0.00 01-APR-00:01 0.00
May 0.00 -0.0 0.00 01-MAY-00:01 0.00
June 0.00 0.00 0.00 01-JUN-00:01 0.00
July 0.00 -0.0 0.00 01-JUL-00:02 0.00
August 0.00 -0.0 0.00 01-AUG-00:02 0.00
September 0.00 0.00 0.00 01-SEP-00:01 0.00
October 0.00 -0.0 0.00 01-OCT-00:01 0.00
November 0.00 0.00 0.00 01-NOV-00:01 0.00
December 0.00 0.00 0.00 01-DEC-00:10 -0.0
           
Annual Sum or Average 0.00 0.00      
Minimum of Months 0.00 -0.0 0.00   -0.0
Maximum of Months 0.00 0.00 0.00   0.00



Table of Contents

Report: FanReportMonthly

For: KITCHEN EXHAUST FAN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.122435E+10 0.24 503.64 01-JAN-00:10 0.26
February 0.111641E+10 0.24 503.64 01-FEB-00:05 0.26
March 0.124747E+10 0.24 503.64 01-MAR-00:10 0.26
April 0.123389E+10 0.25 503.64 01-APR-00:14 0.26
May 0.128737E+10 0.25 503.64 01-MAY-00:13 0.26
June 0.124666E+10 0.25 503.64 01-JUN-00:10 0.26
July 0.128896E+10 0.25 503.64 01-JUL-00:07 0.26
August 0.128891E+10 0.25 503.64 01-AUG-00:07 0.26
September 0.124613E+10 0.25 503.64 01-SEP-00:06 0.26
October 0.128451E+10 0.25 503.64 01-OCT-00:10 0.26
November 0.122428E+10 0.25 503.64 01-NOV-00:13 0.26
December 0.123779E+10 0.24 503.64 01-DEC-00:10 0.26
           
Annual Sum or Average 0.149267E+11 0.25      
Minimum of Months 0.111641E+10 0.24 503.64   0.26
Maximum of Months 0.128896E+10 0.25 503.64   0.26



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_1:1_ADDAQ FAN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.220334E+10 0.47 1382.24 20-JAN-03:01 0.67
February 0.196062E+10 0.47 2298.68 05-FEB-03:03 0.88
March 0.212869E+10 0.46 1325.37 09-MAR-07:10 0.67
April 0.201069E+10 0.46 2298.68 28-APR-02:61 0.87
May 0.214058E+10 0.48 2298.68 02-MAY-02:61 0.87
June 0.214803E+10 0.49 2298.68 01-JUN-02:61 0.87
July 0.232502E+10 0.50 2298.68 01-JUL-02:61 0.87
August 0.229723E+10 0.49 2298.68 01-AUG-02:61 0.87
September 0.212953E+10 0.48 2298.68 01-SEP-02:61 0.87
October 0.217489E+10 0.48 2298.68 03-OCT-02:61 0.87
November 0.202838E+10 0.46 2298.68 02-NOV-02:61 0.87
December 0.216444E+10 0.46 2298.68 16-DEC-03:01 0.87
           
Annual Sum or Average 0.257114E+11 0.47      
Minimum of Months 0.196062E+10 0.46 1325.37   0.67
Maximum of Months 0.232502E+10 0.50 2298.68   0.88



Table of Contents

Report: FanReportMonthly

For: PSZ-AC_2:2_ADDAQ FAN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.131229E+10 0.50 1392.04 01-JAN-03:01 0.91
February 0.120689E+10 0.51 1392.04 01-FEB-03:01 0.90
March 0.136978E+10 0.52 1392.04 01-MAR-03:11 0.91
April 0.146142E+10 0.55 1392.04 01-APR-02:11 0.90
May 0.230506E+10 0.68 1392.04 01-MAY-02:11 0.90
June 0.245490E+10 0.72 1392.04 01-JUN-02:61 0.90
July 0.287832E+10 0.76 1392.04 01-JUL-02:61 0.90
August 0.270527E+10 0.74 1392.04 01-AUG-02:61 0.90
September 0.240759E+10 0.71 1392.04 01-SEP-02:61 0.90
October 0.211793E+10 0.65 1392.04 01-OCT-02:61 0.90
November 0.144948E+10 0.54 1392.04 01-NOV-02:11 0.90
December 0.138652E+10 0.52 1392.04 01-DEC-03:11 0.91
           
Annual Sum or Average 0.230555E+11 0.62      
Minimum of Months 0.120689E+10 0.50 1392.04   0.90
Maximum of Months 0.287832E+10 0.76 1392.04   0.91



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.79 0.24 0.00 01-JAN-07:10 0.00 0.00 52.41 0.10
February 0.72 0.22 0.00 01-FEB-06:10 0.00 0.00 53.08 0.10
March 0.80 0.24 0.00 01-MAR-06:10 0.00 0.00 53.23 0.10
April 0.77 0.23 0.00 01-APR-06:10 0.00 0.00 53.93 0.10
May 0.80 0.24 0.00 01-MAY-05:10 0.00 0.00 53.09 0.10
June 0.77 0.23 0.00 01-JUN-05:10 0.00 0.00 54.70 0.10
July 0.79 0.24 0.00 01-JUL-06:05 0.00 0.00 53.99 0.10
August 0.80 0.24 0.00 01-AUG-05:10 0.00 0.00 54.87 0.10
September 0.77 0.23 0.00 01-SEP-05:10 0.00 0.00 54.52 0.10
October 0.79 0.24 0.00 01-OCT-06:10 0.00 0.00 53.37 0.10
November 0.77 0.23 0.00 01-NOV-05:10 0.00 0.00 53.74 0.10
December 0.79 0.24 0.00 01-DEC-06:10 0.00 0.00 53.39 0.10
                 
Annual Sum or Average 9.37 2.81            
Minimum of Months 0.72 0.22 0.00   0.00 0.00 52.41 0.10
Maximum of Months 0.80 0.24 0.00   0.00 0.00 54.87 0.10



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 42.52 42.52 4254.37 15592.50 23-JAN-14:00
February 0.00 0.00 01-FEB-00:05 53.02 53.02 4221.30 15569.42 01-FEB-13:18
March 0.00 0.00 01-MAR-00:10 53.16 53.16 4082.37 15214.15 01-MAR-13:20
April 0.00 0.00 01-APR-00:01 53.39 53.39 3837.93 14424.18 01-APR-12:20
May 0.00 0.00 01-MAY-00:01 44.65 44.65 3592.70 13466.64 01-MAY-12:20
June 0.00 0.00 01-JUN-00:01 54.71 54.71 3392.17 12546.63 01-JUN-12:54
July 0.00 0.00 01-JUL-00:02 54.20 54.20 3281.63 11954.37 01-JUL-12:50
August 0.00 0.00 01-AUG-00:02 54.82 54.82 3326.57 12191.44 31-AUG-12:30
September 0.00 0.00 01-SEP-00:01 54.67 54.67 3470.58 12952.17 30-SEP-12:20
October 0.00 0.00 01-OCT-00:01 45.20 45.20 3706.31 13938.47 31-OCT-12:35
November 0.00 0.00 01-NOV-00:01 53.84 53.84 3961.23 14835.32 30-NOV-13:30
December 0.00 0.00 01-DEC-00:10 53.30 53.30 4152.81 15448.38 31-DEC-14:00
                 
Annual Sum or Average 0.00         3770.83    
Minimum of Months 0.00 0.00   42.52 42.52 3281.63 11954.37  
Maximum of Months 0.00 0.00   54.82 54.82 4254.37 15592.50  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_1:1

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.315358E+10 0.00 0.00
February 0.00 0.00 0.00 0.324618E+10 0.00 0.00
March 0.00 0.00 0.00 0.421377E+10 0.00 0.00
April 0.00 0.00 0.00 0.606165E+10 0.00 0.00
May 0.00 0.00 0.00 0.129442E+11 0.00 0.00
June 0.00 0.00 0.00 0.137266E+11 0.00 0.00
July 0.00 0.00 0.00 0.155920E+11 0.00 0.00
August 0.00 0.00 0.00 0.149687E+11 0.00 0.00
September 0.00 0.00 0.00 0.130167E+11 0.00 0.00
October 0.00 0.00 0.00 0.109985E+11 0.00 0.00
November 0.00 0.00 0.00 0.519549E+10 0.00 0.00
December 0.00 0.00 0.00 0.407862E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.107196E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.315358E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.155920E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC_2:2

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.302442E+10 0.00 0.00
February 0.00 0.00 0.00 0.341225E+10 0.00 0.00
March 0.00 0.00 0.00 0.459039E+10 0.00 0.00
April 0.00 0.00 0.00 0.723905E+10 0.00 0.00
May 0.00 0.00 0.00 0.152494E+11 0.00 0.00
June 0.00 0.00 0.00 0.161470E+11 0.00 0.00
July 0.00 0.00 0.00 0.188488E+11 0.00 0.00
August 0.00 0.00 0.00 0.177908E+11 0.00 0.00
September 0.00 0.00 0.00 0.158352E+11 0.00 0.00
October 0.00 0.00 0.00 0.128039E+11 0.00 0.00
November 0.00 0.00 0.00 0.610217E+10 0.00 0.00
December 0.00 0.00 0.00 0.441619E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.125460E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.302442E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.188488E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_1:1

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.220334E+10 0.351266E+10 0.605784E+10 0.00 0.00 0.00 0.00 0.00
February 0.196062E+10 0.479424E+10 0.402515E+10 0.00 0.00 0.00 0.00 0.00
March 0.212869E+10 0.782938E+10 0.282659E+10 0.00 0.00 0.00 0.00 0.00
April 0.201069E+10 0.155595E+11 0.147875E+09 0.00 0.00 0.00 0.00 0.00
May 0.214058E+10 0.436512E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.214803E+10 0.473863E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.232502E+10 0.550506E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.229723E+10 0.522333E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.212953E+10 0.446764E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.217489E+10 0.358767E+11 81253841.58 0.00 0.00 0.00 0.00 0.00
November 0.202838E+10 0.123463E+11 0.816387E+09 0.00 0.00 0.00 0.00 0.00
December 0.216444E+10 0.734680E+10 0.409292E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.257114E+11 0.330263E+12 0.180480E+11 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.196062E+10 0.351266E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.232502E+10 0.550506E+11 0.605784E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC_2:2

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.131229E+10 0.702359E+10 0.810268E+09 0.00 0.00 0.00 0.00 0.00
February 0.120689E+10 0.906505E+10 0.776258E+09 0.00 0.00 0.00 0.00 0.00
March 0.136978E+10 0.133523E+11 0.259271E+09 0.00 0.00 0.00 0.00 0.00
April 0.146142E+10 0.243268E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.230506E+10 0.569092E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.245490E+10 0.600759E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.287832E+10 0.702583E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.270527E+10 0.663249E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.240759E+10 0.594006E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.211793E+10 0.466872E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144948E+10 0.195754E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138652E+10 0.126976E+11 0.448931E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.230555E+11 0.445697E+12 0.229473E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.120689E+10 0.702359E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.287832E+10 0.702583E+11 0.810268E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_1:1

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.220334E+10 0.00 0.00 0.00 0.950244E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.196062E+10 0.00 0.00 0.00 0.128556E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.212869E+10 0.00 0.00 0.00 0.208508E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.201069E+10 0.00 0.00 0.00 0.405097E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.214058E+10 0.00 0.00 0.00 0.108036E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.214803E+10 0.00 0.00 0.00 0.115785E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.232502E+10 0.00 0.00 0.00 0.132670E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.229723E+10 0.00 0.00 0.00 0.126715E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.212953E+10 0.00 0.00 0.00 0.108872E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.217489E+10 0.00 0.00 0.00 0.882359E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.202838E+10 0.00 0.00 0.00 0.316711E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.216444E+10 0.00 0.00 0.00 0.191418E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.257114E+11 0.00 0.00 0.00 0.814845E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.196062E+10 0.00 0.00 0.00 0.950244E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.232502E+10 0.00 0.00 0.00 0.132670E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC_2:2

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.131229E+10 0.00 0.00 0.00 0.171213E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.120689E+10 0.00 0.00 0.00 0.220536E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.136978E+10 0.00 0.00 0.00 0.322061E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.146142E+10 0.00 0.00 0.00 0.577762E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.230506E+10 0.00 0.00 0.00 0.129444E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.245490E+10 0.00 0.00 0.00 0.136921E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.287832E+10 0.00 0.00 0.00 0.159705E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.270527E+10 0.00 0.00 0.00 0.150855E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.240759E+10 0.00 0.00 0.00 0.134276E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.211793E+10 0.00 0.00 0.00 0.106860E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144948E+10 0.00 0.00 0.00 0.465269E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138652E+10 0.00 0.00 0.00 0.302967E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.230555E+11 0.00 0.00 0.00 0.102404E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.120689E+10 0.00 0.00 0.00 0.171213E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.287832E+10 0.00 0.00 0.00 0.159705E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DINING

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.497035E+10 0.324957E+09 0.00 6691897.92 0.00 0.460318E+10 0.211900E+10 0.00 4.17
February 0.401377E+10 0.518392E+09 0.00 9537937.72 0.00 0.309624E+10 0.235930E+10 0.00 4.30
March 0.398838E+10 0.984360E+09 0.00 10944211.13 0.00 0.205427E+10 0.258936E+10 0.00 4.53
April 0.187816E+10 0.252581E+10 0.00 14545031.64 8137069.09 26824880.63 0.322241E+10 0.00 4.92
May 15867692.51 0.118004E+11 0.00 1032681.91 0.115546E+09 0.00 7515572.71 0.00 3.74
June 13861121.31 0.137118E+11 0.00 904873.31 0.159432E+09 0.00 35399497.43 0.00 3.79
July 1478079.54 0.173076E+11 0.00 852467.07 0.246255E+09 0.00 4122033.65 0.00 3.81
August 21291219.77 0.154336E+11 0.00 1233970.18 0.192397E+09 0.00 76009658.04 0.00 3.83
September 25440124.36 0.124568E+11 0.00 1477063.27 0.124478E+09 0.00 0.159450E+09 0.00 3.84
October 0.785424E+09 0.912016E+10 0.00 7973590.99 85338859.84 45682548.04 0.148954E+10 0.00 4.34
November 0.329685E+10 0.211382E+10 0.00 13193404.81 9179357.83 0.464251E+09 0.342384E+10 0.00 4.82
December 0.439930E+10 0.102225E+10 0.00 8641799.09 163563.40 0.300008E+10 0.246607E+10 115.75 4.44
                   
Annual Sum or Average 0.234102E+11 0.873200E+11 0.00 77028929.06 0.940926E+09 0.132905E+11 0.179520E+11 115.75 4.21
Minimum of Months 1478079.54 0.324957E+09 0.00 852467.07 0.00 0.00 4122033.65 0.00 3.74
Maximum of Months 0.497035E+10 0.173076E+11 0.00 14545031.64 0.246255E+09 0.460318E+10 0.342384E+10 115.75 4.92



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: KITCHEN

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.171243E+11 0.296298E+09 0.00 35764630.77 356004.08 0.00 0.119005E+11 0.00 7.37
February 0.104394E+11 0.307551E+09 0.00 50047123.63 44995.00 0.00 0.129344E+11 0.00 7.49
March 0.929889E+10 0.117575E+10 0.00 52924983.27 167944.29 0.00 0.133865E+11 0.00 7.60
April 0.195051E+10 0.353828E+10 0.00 64763001.40 7915755.32 0.00 0.110685E+11 0.00 8.00
May 91159216.52 0.225731E+11 0.00 5863549.39 61604087.07 0.00 0.453656E+09 0.00 9.61
June 45557146.38 0.259561E+11 0.00 5092997.61 71987947.59 0.00 0.467088E+09 0.00 9.94
July 6631313.74 0.342105E+11 0.00 2701463.43 95001298.35 0.00 0.261928E+09 0.00 10.43
August 60107446.88 0.302881E+11 0.00 3919368.20 77873486.02 0.00 0.350573E+09 0.00 10.16
September 99486113.28 0.252096E+11 0.00 5830879.79 59485949.43 0.00 0.467149E+09 0.00 9.86
October 0.804850E+09 0.175403E+11 0.00 34322350.10 40598249.33 0.00 0.562775E+10 0.00 9.11
November 0.461754E+10 0.377055E+10 0.00 55831357.27 7516751.26 0.00 0.140227E+11 0.00 7.88
December 0.117866E+11 0.164229E+10 0.00 39057425.65 1877922.95 0.00 0.128097E+11 0.00 7.57
                   
Annual Sum or Average 0.563250E+11 0.166508E+12 0.00 0.356119E+09 0.424430E+09 0.00 0.837505E+11 0.00 8.76
Minimum of Months 6631313.74 0.296298E+09 0.00 2701463.43 44995.00 0.00 0.261928E+09 0.00 7.37
Maximum of Months 0.171243E+11 0.342105E+11 0.00 64763001.40 95001298.35 0.00 0.140227E+11 0.00 10.43



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:26:26

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.391400E+11 0.111042E+11 0.708662E+11 0.710602E+09 0.380135E+11
February 0.435774E+11 0.819418E+10 0.562941E+11 0.779862E+09 0.417993E+11
March 0.511989E+11 0.726850E+10 0.531395E+11 0.101704E+10 0.526460E+11
April 0.601892E+11 0.188182E+10 0.250799E+11 0.131685E+10 0.777008E+11
May 0.608132E+11 -0.102410E+11 -0.401330E+11 7929630.68 0.154641E+12
June 0.612687E+11 -0.119835E+11 -0.469094E+11 20771834.50 0.162773E+12
July 0.624867E+11 -0.150091E+11 -0.623261E+11 3574992.11 0.185294E+12
August 0.582093E+11 -0.136470E+11 -0.545159E+11 45941170.57 0.176455E+12
September 0.488848E+11 -0.105832E+11 -0.445781E+11 86021349.04 0.155603E+12
October 0.485449E+11 -0.627257E+10 -0.156338E+11 0.586616E+09 0.129306E+12
November 0.363064E+11 0.383784E+10 0.387944E+11 0.134955E+10 0.646143E+11
December 0.350296E+11 0.822457E+10 0.571781E+11 0.987606E+09 0.498676E+11
           
Annual Sum or Average 0.605649E+12 -0.272252E+11 0.372561E+11 0.691237E+10 0.128871E+13
Minimum of Months 0.350296E+11 -0.150091E+11 -0.623261E+11 3574992.11 0.380135E+11
Maximum of Months 0.624867E+11 0.111042E+11 0.708662E+11 0.134955E+10 0.185294E+12