Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:26:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1408.95 | 6064.12 | 6064.12 |
Net Site Energy | 1408.95 | 6064.12 | 6064.12 |
Total Source Energy | 2469.44 | 10628.45 | 10628.45 |
Net Source Energy | 2469.44 | 10628.45 | 10628.45 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 262.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 59.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 51.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 452.30 | 956.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 262.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 59.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 262.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 36.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 24.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 59.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 216.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 51.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 410.16 | 2063.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1364.48 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1946.68 | 4117.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 410.16 | 2063.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1364.48 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1946.68 | 4117.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 452.298 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 452.298 | 100.00 |
Total On-Site and Utility Electric Sources | 452.298 | 100.00 |
Total Electricity End Uses | 452.298 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 0.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3524.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.1446 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9598 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.1446 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9598 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.5522 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-11:09 | 20-DEC-13:09 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 71666.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12672.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13174.05 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3187.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25918.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2512.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32611.82 | 120568.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 71666.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12672.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3187.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 25918.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1313.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1004.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 284.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 114.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 77.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 841.99 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 186.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 235.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 162.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1432.43 | 1037.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1225.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 494.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 331.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 213.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1011.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 697.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6165.15 | 4463.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1225.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 494.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 331.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 213.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1011.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 697.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6165.15 | 4463.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 2.07 |
KITCHEN DIRECT AIR | 1.47 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 2.07 | 1.00 | 1.00 | 2.07 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.00 | 1.00 | 1.47 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.07 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.47 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 2.07 | 2216.17 |
PSZ-AC_2:2_ADDAQ FAN | 1.47 | 1567.98 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.07 | 2.07 | 2.07 | 1.37 | 34284.00 | 54368.39 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.47 | 1.47 | 1.47 | 0.967123 | 29328.10 | 77635.34 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.07 | 1.04 | 1.38 | 34284.00 | 17142.00 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.47 | 0.732669 | 0.976893 | 29328.10 | 14664.05 | 0.776080 | 0.776080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 54368.39 |
PSZ-AC_2:2 HEATING COIL | 77635.34 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.145 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.932 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.960 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.039 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 829.995 | 7.145 | 9.481 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 829.995 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1157.049 | 9.960 | 184.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1157.049 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4391 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2452 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.043 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.002 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.38584905E-12 | 0.75146531E-15 | -0.12966877E-12 | 0.12247089E-15 |
34 | 6 | 0.32626755E-07 | 0.12794687E-09 | 0.74410738E-08 | -0.15657130E-12 |
35 | 5 | -0.20999199E-03 | 0.10694986E-05 | -0.10771460E-03 | 0.73422529E-08 |
36 | 4 | 0.31512205 | 0.50965885E-03 | 0.10796022 | -0.36842960E-04 |
37 | 3 | -7.7206601 | 0.15495837E-01 | -2.4737779 | 0.31237450E-01 |
38 | 2 | 42.368774 | 0.54174396E-01 | 15.816616 | -0.35002435 |
39 | 1 | -81.692611 | 0.24088120E-01 | -29.635684 | 1.1030598 |
40 | 0 | 46.824332 | 0.47759164E-03 | 16.279740 | |
41 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
42 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
43 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
44 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
45 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
46 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
47 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
48 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 | |
49 | 7 | -0.17135090E-08 | -0.36864923E-15 | 0.71259317E-14 | -0.97083918E-16 |
50 | 6 | 0.68579659E-05 | 0.47011368E-08 | 0.31862738E-02 | -0.26729135E-04 |
51 | 5 | -0.49396463E-03 | 0.27861516E-05 | -0.22352018 | 0.19543461E-02 |
52 | 4 | 0.11367371E-01 | 0.12683264E-03 | 4.8261412 | -0.45232255E-01 |
53 | 3 | -0.99836882E-01 | 0.10087729E-02 | -38.002184 | 0.39844117 |
54 | 2 | 0.35452054 | 0.16782362E-02 | 116.44652 | -1.4174386 |
55 | 1 | -0.51170991 | 0.51154075E-03 | -143.88527 | 2.0486777 |
56 | 0 | 0.24948649 | 0.12321491E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | 38 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
2 | NONRESWINDOW_U_0.379_SHGC_NORTH_0.38 | 39 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
3 | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | 40 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 | ||
4 | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 41 | 1 | VerySmooth | 2.153 | 2.153 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.46913E-002 | 0.29373 | 0.49866 | 0.49866 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11879 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.4319E-003 |
2 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8293E-002 |
3 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.1795E-003 |
4 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.5868E-002 |
5 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.0363E-003 |
6 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9653E-002 |
7 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.6416E-003 |
8 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.6451E-002 |
9 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 7.9035E-002 |
10 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.9565E-002 |
11 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.1615E-002 |
12 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.2291E-002 |
13 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.8960E-002 |
14 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.9101E-002 |
15 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.7798E-002 |
16 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.7798E-002 |
17 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8612E-002 |
18 | Clear Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.4713E-003 |
19 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6258E-002 |
20 | Clear Turbid Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.2296E-003 |
21 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.0066E-002 |
22 | Intermediate Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0718E-003 |
23 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6453E-002 |
24 | Overcast Sky | 12/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.6416E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 19032.58087 | 22839.09704 | 1.72591 | 2.07110 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90000 | 5.47527E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 5671.77760 | 6806.13312 | 0.29709 | 0.41606 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -17.90000 | 9.55238E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16154.12417 | 19384.94900 | 1.22111 | 1.46534 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 32.56800 | 5.47322E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 0.00000 | 0.00000 | 0.00000 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -17.90000 | 9.55238E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26640.43 | 2.07110 | 2.07110 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 23660.53 | 0.41606 | 0.41606 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 26377.17 | 1.46534 | 1.46534 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 64906.04 | 1.14133 | 1.14133 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.07110 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46534 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.07110 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.07110 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.07110 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.07110 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.07110 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.07110 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46534 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46534 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46534 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46534 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46534 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46534 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.07110 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.46534 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.07110 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.07110 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 2216.17118 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.07110 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.07110 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.07110 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.36692 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.07110 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.03555 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.38073 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34284.00000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17142.00000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34284.00000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54368.39045 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 54368.39045 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46534 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46534 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1567.98044 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46534 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46534 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46534 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96712 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46534 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73267 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97689 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29328.10000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14664.05000 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77608 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77608 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29328.10000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 77635.33938 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 77635.33938 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 32768.8 | 11.01 | 10.96 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 28268.8 | 11.43 | 11.38 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | N/A | 2.153 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | N/A | 2.153 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | N/A | 2.153 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.245 | 0.231 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 7.8677544317E-002 | 0.3468055056 | Pass | Pass | 0.2727880082 | 0.9379185771 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1575741408 | 0.6951230968 | Pass | Pass | 3.2743583479E-002 | 9.5013568765E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.4428768151 | 0.5243140302 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 560.86 | 109.80 | 890.41 | 12.34 | 510.48 | 2083.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.236 | 0.245 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.379_SHGC_EAST_0.38 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.153 | 0.381 | 0.420 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.379_SHGC_SOUTH_0.38 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.153 | 0.381 | 0.420 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.379_SHGC_WEST_0.38 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.153 | 0.381 | 0.420 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.153 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.153 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.1446 | 116.17 | 830.00 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.69 | 0.0000 | Y | 6.81 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9598 | 116.17 | 1157.05 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.51 |
Interior Lighting Total | 8.5522 | 232.34 | 1987.04 | 24.31 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 49.26 | 49.26 | 2.02 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.67 | 62.97 | 13.64 | |
Exterior Lighting Total | 1372.31 | 15.66 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34284.00 | 27449.83 | 6834.17 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29328.10 | 22760.95 | 6567.15 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 32768.8 | 11.01 | 10.96 | ||||
PSZ-AC_2:2 COOLING COIL | 28268.8 | 11.43 | 11.38 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 54368.39 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 77635.34 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 2.07 | 2216.17 | 1070.05 | 1.00 | 1.31 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.47 | 1567.98 | 1070.05 | 1.00 | 1.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 19032.58 | 22839.10 | 196.60 | 1.726 | 2.071 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.89 | 0.00757 | 33.90 | 0.00548 | 0.416 | 0.00 |
KITCHEN | 16154.12 | 19384.95 | 166.86 | 1.221 | 1.465 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00870 | 32.57 | 0.00547 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 5671.78 | 6806.13 | 58.59 | 0.297 | 0.416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 21.11 | 21.11 | 0.00777 | -17.90 | 0.00096 | 0.416 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.000 | 1.141 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 18.89 | 21.82 | 0.00045 | -17.90 | 0.00096 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.07 | 2.07 | 0.42 | 0.42 | 2.0711 | 2.0711 | 2.0711 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.47 | 1.47 | 1.14 | 1.14 | 1.4653 | 1.4653 | 1.4653 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34284.000 | 27449.827 | 2.071100 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 17142.00 | 16837.58 | 1.380733 | 25.90 | 13.78 | 0.00714589 | 11.72 | 8.31 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | 30.1330 | 23.89 | 0.00756586 | 33.3378 | 19032.58 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 54368.390 | 54368.390 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 54368.39 | 54368.39 | 2.071097 | 13.27 | 8.29 | 0.00634185 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 20.0887 | 19.57 | 0.00769597 | 44.1344 | 3233.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 29328.100 | 22760.952 | 1.465340 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 14664.05 | 14664.05 | 0.976893 | 31.13 | 14.74 | 0.00618767 | 11.72 | 7.47 | 0.00618767 | 32.57 | 0.00547322 | 14.64 | 116.8330 | 26.10 | 0.00870440 | 33.5572 | 16154.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 77635.339 | 77635.339 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 77635.34 | 77635.34 | 1.465338 | -13.94 | -15.06 | 0.00084652 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 77.8888 | 22.14 | 0.00046356 | 2.2962 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34284.000 | 27449.827 | 2.071100 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1239 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.071097 | 2.02436764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 17142.00 | 16837.58 | 1.0000 | 1.34958069 | 1.380733 | 25.90 | 13.78 | 0.00714589 | 44237.0 | 11.72 | 8.31 | 0.00700000 | 29440.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17142.00 | 33.90 | 0.00547527 | 15.07 | 0.41605618 | 30.1330 | 23.88 | 0.00756586 | 23.89 | 0.00756586 | 33.3378 | 19032.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54368.390 | 54368.390 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 2.071097 | 2.02436764 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 54368.39 | 54368.39 | 1.0000 | 2.02436764 | 2.071097 | 13.27 | 8.29 | 0.00634185 | 29354.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54368.39 | -17.90 | 0.00095524 | -17.90 | 0.41605618 | 20.0887 | 21.11 | 0.00769597 | 19.57 | 0.00769597 | 44.1344 | 3233.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29328.100 | 22760.952 | 1.465340 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1016.3426 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.465338 | 1.43227603 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 14664.05 | 14664.05 | 1.0000 | 0.95485229 | 0.976893 | 31.13 | 14.74 | 0.00618767 | 47110.9 | 11.72 | 7.47 | 0.00618767 | 27389.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14664.05 | 32.57 | 0.00547322 | 14.64 | 1.14133354 | 116.8330 | 26.05 | 0.00870440 | 26.10 | 0.00870440 | 33.5572 | 16154.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 77635.339 | 77635.339 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.465338 | 1.43227603 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 77635.34 | 77635.34 | 1.0000 | 1.43227603 | 1.465338 | -13.94 | -15.06 | 0.00084652 | -11914.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 77635.34 | -17.90 | 0.00095524 | -17.90 | 1.14133354 | 77.8888 | 0.00 | 0.00046356 | 22.14 | 0.00046356 | 2.2962 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 2.07 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.47 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 2746.50 | 4566.50 | 944.00 |
KITCHEN | 4440.33 | 5997.83 | 3453.33 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4510.50 | 6709.33 | 3524.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 71.50 | 37.67 | 0.33 | 0.50 |
KITCHEN | 0.00 | 153.17 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 71.50 | 185.17 | 0.33 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 5.157 | 2.742 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 10.234 | 0.030 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.106 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.538 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 13362889.89 | 0.00 | 13362889.89 | 6981777.24 | 20344667.13 | 13120747.55 | 1429.50 | 5809.37 | 1521.13 | 388.17 |
KITCHEN | 26717261.37 | 0.00 | 26717261.37 | 134202.88 | 26851464.25 | 35993094.65 | 8417.10 | 337.22 | 5.67 | 571.91 |
Total Facility | 40080151.26 | 0.00 | 40080151.26 | 7115980.12 | 47196131.38 | 49113842.20 | 8421.16 | 5809.55 | 1525.67 | 745.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.5032 | 0.0000 | 0.5032 | 0.2676 | 0.7708 | 0.4161 | 0.00 | 5699.99 | 1487.01 |
KITCHEN | 0.9976 | 0.0000 | 0.9976 | 0.0029 | 1.0005 | 1.1413 | 6855.47 | 330.47 | 1.06 |
Total Facility | 1.5008 | 0.0000 | 1.5008 | 0.2705 | 1.7713 | 1.5574 | 6855.47 | 5700.00 | 1487.63 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12767163.79 | 0.00 | 12767163.79 | 13120747.55 | 7253.04 | 11.47 | 1495.49 | 388.13 |
PSZ-AC_2:2 | 25525042.05 | 0.00 | 25525042.05 | 35993094.65 | 8754.88 | 0.48 | 4.64 | 571.91 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.4808 | 0.0000 | 0.4808 | 0.4161 | 5712.90 | 10.47 | 1463.63 |
PSZ-AC_2:2 | 0.9531 | 0.0000 | 0.9531 | 1.1413 | 7186.14 | 0.19 | 0.66 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1166.51 | 605.63 | 5802.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 150.89 | 1313.38 | 6294.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.9144 | 0.6217 | 0.3976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.0038 | 0.9946 | 0.9475 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
Electricity:Building | 298.12 | 2110.08 | 01-JAN-01:20 | 18433.35 | 02-JAN-11:10 |
Electricity:Zone:DINING | 77.14 | 295.02 | 01-JAN-01:20 | 4205.23 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 290.18 | 1973.80 | 01-JAN-01:20 | 15139.30 | 02-JAN-11:10 |
InteriorLights:Electricity | 24.31 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 6.81 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 24.31 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 24.31 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 6.81 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 24.31 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 220.98 | 1815.06 | 01-JAN-01:20 | 14339.52 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.53 | 1653.77 | 01-JAN-01:10 | 10143.54 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 51.16 | 849.93 | 29-NOV-23:30 | 4345.70 | 28-JUL-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 43.22 | 764.16 | 29-NOV-23:30 | 2549.75 | 11-AUG-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 14.40 | 0.00 | 01-JAN-11:10 | 1473.51 | 11-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 28.82 | 683.15 | 21-DEC-01:10 | 1076.23 | 13-APR-13:50 |
ElectricityPurchased:Facility | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
ElectricityPurchased:Plant | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
Cogeneration:ElectricityPurchased | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
General:Cogeneration:ElectricityPurchased | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
ElectricityNet:Plant | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
Cogeneration:ElectricityNet | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
General:Cogeneration:ElectricityNet | 452.30 | 3766.82 | 24-DEC-01:20 | 32611.82 | 16-AUG-11:10 |
Electricity:HVAC | 95.30 | 0.00 | 01-JAN-01:10 | 17507.39 | 26-JUN-17:10 |
Fans:Electricity | 59.03 | 0.00 | 01-JAN-01:10 | 3403.91 | 26-JUN-17:10 |
General:Fans:Electricity | 59.03 | 0.00 | 01-JAN-01:10 | 3403.91 | 26-JUN-17:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 36.26 | 0.00 | 01-JAN-00:10 | 14103.47 | 26-JUN-17:10 |
General:Cooling:Electricity | 36.26 | 0.00 | 01-JAN-00:10 | 14103.47 | 26-JUN-17:10 |
ExteriorLights:Electricity | 15.66 | 0.00 | 01-JAN-07:30 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.66 | 0.00 | 01-JAN-07:30 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:30 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-JAN-12:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 956.66 | 2558.65 | 13-MAR-02:10 | 120568.36 | 20-DEC-13:10 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 262.60 | 0.00 | 01-JAN-01:10 | 87802.17 | 23-DEC-07:10 |
Heating:NaturalGas | 262.60 | 0.00 | 01-JAN-01:10 | 87802.17 | 23-DEC-07:10 |
General:Heating:NaturalGas | 262.60 | 0.00 | 01-JAN-01:10 | 87802.17 | 23-DEC-07:10 |
NaturalGas:Plant | 216.90 | 720.00 | 01-JAN-09:30 | 27774.54 | 11-FEB-13:40 |
WaterSystems:NaturalGas | 216.90 | 720.00 | 01-JAN-09:30 | 27774.54 | 11-FEB-13:40 |
Water Heater:WaterSystems:NaturalGas | 216.90 | 720.00 | 01-JAN-09:30 | 27774.54 | 11-FEB-13:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1006.11 | 2415.77 | 23-DEC-01:10 | 108424.62 | 21-DEC-20:20 |
EnergyTransfer:Building | 440.65 | 1207.88 | 23-DEC-01:10 | 33456.03 | 16-AUG-11:10 |
EnergyTransfer:Zone:KITCHEN | 335.94 | 1207.88 | 23-DEC-01:10 | 23730.85 | 09-MAY-04:10 |
Refrigeration:EnergyTransfer | 136.47 | 2415.77 | 23-DEC-01:10 | 7834.84 | 28-APR-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.23 | 1207.88 | 23-DEC-01:10 | 3917.42 | 28-APR-03:30 |
General:Refrigeration:EnergyTransfer | 68.23 | 1207.88 | 23-DEC-01:10 | 3917.42 | 28-APR-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.23 | 1207.88 | 23-DEC-01:10 | 3917.42 | 28-APR-03:30 |
EnergyTransfer:Plant | 216.37 | 1207.88 | 23-DEC-01:10 | 22561.73 | 18-FEB-13:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 13.00 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.23 | 1059.46 | 21-DEC-01:10 | 2238.70 | 13-APR-13:50 |
EnergyTransfer:Zone:DINING | 104.71 | 0.00 | 01-JAN-01:10 | 25554.99 | 22-DEC-03:20 |
Heating:EnergyTransfer | 23.78 | 0.00 | 01-JAN-00:10 | 18862.01 | 21-DEC-18:10 |
Heating:EnergyTransfer:Zone:DINING | 23.77 | 0.00 | 01-JAN-00:10 | 18862.01 | 21-DEC-18:10 |
General:Heating:EnergyTransfer | 23.78 | 0.00 | 01-JAN-00:10 | 18862.01 | 21-DEC-18:10 |
General:Heating:EnergyTransfer:Zone:DINING | 23.77 | 0.00 | 01-JAN-00:10 | 18862.01 | 21-DEC-18:10 |
Cooling:EnergyTransfer | 348.64 | 0.00 | 01-JAN-01:10 | 29753.15 | 16-AUG-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 80.94 | 0.00 | 01-JAN-01:10 | 15923.15 | 26-JUN-17:20 |
General:Cooling:EnergyTransfer | 348.64 | 0.00 | 01-JAN-01:10 | 29753.15 | 16-AUG-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 80.94 | 0.00 | 01-JAN-01:10 | 15923.15 | 26-JUN-17:20 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 814.24 | 02-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 814.24 | 02-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 267.70 | 0.00 | 01-JAN-01:10 | 19826.70 | 09-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 267.70 | 0.00 | 01-JAN-01:10 | 19826.70 | 09-MAY-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 148.13 | 0.00 | 01-JAN-00:10 | 20163.77 | 14-FEB-13:40 |
PlantLoopHeatingDemand:Plant | 148.13 | 0.00 | 01-JAN-00:10 | 20163.77 | 14-FEB-13:40 |
WaterSystems:PlantLoopHeatingDemand | 148.13 | 0.00 | 01-JAN-00:10 | 20163.77 | 14-FEB-13:40 |
General:WaterSystems:PlantLoopHeatingDemand | 148.13 | 0.00 | 01-JAN-00:10 | 20163.77 | 14-FEB-13:40 |
EnergyTransfer:HVAC | 349.09 | 0.00 | 01-JAN-01:10 | 70241.74 | 23-DEC-07:10 |
HeatingCoils:EnergyTransfer | 210.08 | 0.00 | 01-JAN-01:10 | 70241.74 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 139.01 | 0.00 | 01-JAN-00:10 | 48936.93 | 26-JUN-17:10 |
WaterSystems:EnergyTransfer | 148.13 | 0.00 | 01-JAN-00:10 | 20163.77 | 14-FEB-13:40 |
WaterUse:WaterSystems:EnergyTransfer | 148.13 | 0.00 | 01-JAN-00:10 | 20163.77 | 14-FEB-13:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 23.768 | -80.940 | 0.000 | 0.000 | 71.034 | 6.807 | 52.748 | 32.918 | 0.000 | 4.975 | 0.000 | 0.000 | -14.408 | 0.000 | -81.590 | -15.313 |
KITCHEN | 0.000 | 0.000 | 0.008 | -267.694 | 0.000 | 0.000 | 4.970 | 17.506 | 201.243 | 0.000 | 0.000 | 0.030 | 45.964 | 0.000 | 0.000 | 0.000 | -2.027 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.386 | 10.278 | 0.000 | 0.000 | 0.000 | -13.664 | -0.001 |
Total Facility | 0.000 | 0.000 | 23.777 | -348.635 | 0.000 | 0.000 | 76.003 | 24.313 | 253.992 | 32.918 | 0.000 | 8.390 | 56.242 | 0.000 | -14.408 | 0.000 | -97.280 | -15.314 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 17-AUG-02:61 | 0.00 | 0.00 | 0.00 | -28032.95 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 28476.51 | 0.00 | -595.47 | 0.00 | -75.61 | 0.00 |
KITCHEN | 07-NOV-05:01 | 0.00 | 0.00 | 0.00 | -50459.38 | 0.00 | 0.00 | 8.64 | 25.01 | 4931.35 | 0.00 | 0.00 | 0.00 | 45540.64 | 0.00 | -0.00 | 0.00 | -46.26 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-SEP-02:61 | 0.00 | 0.00 | 0.00 | -70790.25 | 0.00 | 0.00 | 0.00 | 50.02 | 1879.56 | 0.00 | 0.00 | 174.80 | 69490.48 | 0.00 | -689.25 | 0.00 | -115.35 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 24-DEC-03:11 | 0.00 | 0.00 | 40421.74 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1936.67 | 0.00 | -737.00 | -37975.58 |
KITCHEN | 02-FEB-05:03 | 0.00 | 0.00 | 8131.76 | 0.00 | 0.00 | 0.00 | 20.03 | 25.01 | 4931.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -56.49 | -13051.65 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-DEC-03:11 | 0.00 | 0.00 | 40421.74 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 1879.56 | 0.00 | 0.00 | 301.67 | 0.00 | 0.00 | -1936.67 | 0.00 | -1512.40 | -39203.91 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0711 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0711 | 0.2009 | 1.0000 | Not calculated | 0.4161 | 0.2009 | ||
PSZ-AC_2:2 | 1.4653 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4653 | 0.1032 | 1.0000 | Not calculated | 0.1513 | 0.1032 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0711 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 2.0711 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2009 | ||
PSZ-AC_2:2 | 1.4653 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.4653 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1032 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0711 | 2.0711 | 2.0711 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4653 | 1.4653 | 1.4653 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0711 | 2.0711 | 2.0711 | 2.0711 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4653 | 1.4653 | 1.4653 | 1.4653 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0711 | 2.0711 | 2.0711 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4653 | 1.4653 | 1.4653 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0711 | 2.0711 | 2.0711 | 2.0711 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.4653 | 1.4653 | 1.4653 | 1.4653 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 0.50 |
Number of hours not met | 0.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 262.60 | 87802.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 36.26 | 14103.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 24.31 | 1583.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.66 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 59.03 | 3403.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 216.90 | 27774.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.40 | 1473.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.82 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 317.03 | 452.30 |
Natural Gas | 477.16 | 956.66 |
Additional | 0.00 | 0.00 |
Total | 794.19 | 1408.95 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 104.64 |
Space Heating | 0.00 |
Space Cooling | 156.08 |
Fans (All) | 254.08 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1144.28 |
Miscellaneous (All) | 1946.68 |
Subtotal | 1946.68 |
Natural Gas [MJ/m2] | |
Space Heating | 1130.23 |
Service Water Heating | 933.53 |
Miscellaneous (All) | 4117.43 |
Subtotal | 4117.43 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.73 |
Space Heating | 18.64 |
Space Cooling | 2.57 |
Fans (All) | 4.19 |
Service Water Heating | 15.39 |
Receptacle Equipment | 52.74 |
Miscellaneous | 4.74 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8357.33 | 402.33 | 0.33 | 0.00 | 0.00 |
ATTIC | 6764.67 | 599.67 | 568.50 | 811.67 | 15.50 |
Min | 6764.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 599.67 | 568.50 | 811.67 | 15.50 |
Average | 7960.67 | 334.00 | 189.61 | 270.56 | 5.17 |
Sum | 23882.00 | 1002.00 | 568.83 | 811.67 | 15.50 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8711.50 | 48.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8135.83 | 624.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 7005.00 | 834.00 | 315.83 | 281.17 | 324.00 |
Min | 7005.00 | 48.50 | 0.00 | 0.00 | 0.00 |
Max | 8711.50 | 834.00 | 315.83 | 281.17 | 324.00 |
Average | 7950.78 | 502.22 | 105.28 | 93.72 | 108.00 |
Sum | 23852.33 | 1506.67 | 315.83 | 281.17 | 324.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 253813.33 | 911.67 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15338.33 | 919.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 253813.33 | 919.67 | 0.00 | 0.00 | 0.00 |
Average | 89717.22 | 610.44 | 0.00 | 0.00 | 0.00 |
Sum | 269151.67 | 1831.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240650E+10 | 17769.51 | 14-JAN-04:08 | -17.0 | -17.0 | 0.452075E+10 | 4413.16 | 20-JAN-12:00 | 21.00 | 6.97 |
February | 0.195088E+10 | 22571.55 | 12-FEB-04:48 | -19.8 | -19.8 | 0.406901E+10 | 4215.70 | 27-FEB-12:00 | 14.00 | 4.76 |
March | 0.341919E+10 | 10170.62 | 05-MAR-00:01 | -9.0 | -9.0 | 0.469424E+10 | 4473.59 | 11-MAR-19:10 | 13.83 | 4.16 |
April | 0.318428E+10 | 9099.97 | 16-APR-23:01 | -6.0 | -6.8 | 0.453889E+10 | 4510.91 | 08-APR-18:10 | -6.0 | -6.8 |
May | 0.688608E+10 | 9883.51 | 17-MAY-12:55 | 29.00 | 11.92 | 0.506193E+10 | 4681.02 | 20-MAY-18:10 | 18.83 | 11.34 |
June | 0.129472E+11 | 25692.29 | 13-JUN-02:61 | 15.22 | 8.40 | 0.526793E+10 | 4681.48 | 17-JUN-18:00 | 23.30 | 16.53 |
July | 0.134265E+11 | 24836.03 | 01-JUL-02:61 | 19.48 | 7.48 | 0.539391E+10 | 4681.13 | 22-JUL-18:00 | 27.00 | 15.92 |
August | 0.136672E+11 | 28042.67 | 17-AUG-02:61 | 14.67 | 6.30 | 0.544562E+10 | 4681.16 | 19-AUG-18:00 | 24.00 | 12.71 |
September | 0.115834E+11 | 27760.92 | 17-SEP-02:61 | 12.70 | 6.80 | 0.514893E+10 | 4681.19 | 02-SEP-18:00 | 12.70 | 6.80 |
October | 0.559969E+10 | 25228.40 | 11-OCT-02:61 | 11.83 | 4.39 | 0.478453E+10 | 4680.68 | 07-OCT-18:10 | 11.83 | 4.39 |
November | 0.336107E+10 | 12699.16 | 30-NOV-03:19 | -14.0 | -14.3 | 0.442623E+10 | 4413.14 | 07-NOV-12:50 | -14.0 | -14.3 |
December | 0.250919E+10 | 27749.90 | 22-DEC-03:11 | -22.7 | -22.7 | 0.452354E+10 | 4413.12 | 01-DEC-12:09 | -22.7 | -22.7 |
Annual Sum or Average | 0.809411E+11 | 0.578755E+11 | ||||||||
Minimum of Months | 0.195088E+10 | 9099.97 | -22.7 | -22.7 | 0.406901E+10 | 4215.70 | -22.7 | -22.7 | ||
Maximum of Months | 0.136672E+11 | 28042.67 | 29.00 | 11.92 | 0.544562E+10 | 4681.48 | 27.00 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220219E+11 | 36600.07 | 05-JAN-05:01 | -17.0 | -17.0 | 0.769971E+10 | 5135.93 | 20-JAN-11:00 | 20.00 | 7.55 |
February | 0.195044E+11 | 38561.27 | 12-FEB-05:01 | -19.8 | -19.8 | 0.694964E+10 | 5116.83 | 18-FEB-11:00 | 18.00 | 6.83 |
March | 0.216462E+11 | 48690.41 | 14-MAR-04:01 | 7.33 | 1.14 | 0.772959E+10 | 5135.93 | 14-MAR-10:09 | 21.00 | 7.12 |
April | 0.213755E+11 | 43131.10 | 21-APR-04:01 | 7.67 | 5.17 | 0.748623E+10 | 5135.93 | 27-APR-10:50 | 17.67 | 8.15 |
May | 0.219687E+11 | 49358.92 | 09-MAY-04:01 | 3.00 | 0.34 | 0.781277E+10 | 5135.97 | 30-MAY-10:00 | 18.00 | 11.53 |
June | 0.225775E+11 | 49600.45 | 09-JUN-03:21 | 7.15 | 3.80 | 0.760604E+10 | 5135.97 | 02-JUN-10:39 | 7.15 | 3.80 |
July | 0.233873E+11 | 48048.47 | 02-JUL-02:11 | 11.67 | 3.81 | 0.785576E+10 | 5135.97 | 28-JUL-10:39 | 19.67 | 16.52 |
August | 0.238143E+11 | 44909.77 | 17-AUG-02:11 | 14.33 | 6.10 | 0.785952E+10 | 5135.97 | 28-AUG-10:39 | 20.67 | 15.18 |
September | 0.231277E+11 | 48339.71 | 15-SEP-03:31 | 9.77 | 4.59 | 0.759041E+10 | 5135.95 | 01-SEP-10:09 | 9.77 | 4.59 |
October | 0.236711E+11 | 49138.00 | 20-OCT-04:01 | 4.00 | 0.33 | 0.775371E+10 | 5135.93 | 05-OCT-10:00 | 4.00 | 0.33 |
November | 0.224592E+11 | 50419.64 | 07-NOV-05:01 | 5.00 | -0.7 | 0.746230E+10 | 5135.93 | 09-NOV-11:00 | 20.00 | 9.32 |
December | 0.221498E+11 | 41343.25 | 22-DEC-05:01 | -21.0 | -21.0 | 0.770043E+10 | 5135.93 | 04-DEC-11:00 | -21.0 | -21.0 |
Annual Sum or Average | 0.267703E+12 | 0.915061E+11 | ||||||||
Minimum of Months | 0.195044E+11 | 36600.07 | -21.0 | -21.0 | 0.694964E+10 | 5116.83 | -21.0 | -21.0 | ||
Maximum of Months | 0.238143E+11 | 50419.64 | 14.33 | 6.10 | 0.785952E+10 | 5135.97 | 21.00 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 | -1.8 | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 | -1.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 | -5.3 | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 | -1.1 | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 | 2.10 | 0.00 | 0.00 | 01-APR-00:10 | 5.90 | 2.10 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 | 4.75 | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 | 4.75 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 | 11.26 | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 | 11.26 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 | 10.91 | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 | 10.91 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 | 15.43 | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 | 15.43 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 | 10.64 | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 | 10.64 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 | 8.03 | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 | 8.03 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 | -5.7 | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 | -0.5 | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 | -0.5 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -5.7 | -5.7 | 0.00 | 0.00 | -5.7 | -5.7 | ||
Maximum of Months | 0.00 | 0.00 | 22.27 | 15.43 | 0.00 | 0.00 | 22.27 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410991E+10 | 33241.15 | 05-JAN-03:21 | -16.0 |
February | 0.443379E+10 | 39899.15 | 12-FEB-04:31 | -19.7 |
March | 0.287715E+10 | 23886.34 | 19-MAR-04:01 | -8.7 |
April | 0.195874E+10 | 21382.49 | 17-APR-04:01 | -8.0 |
May | 81689732.54 | 5417.97 | 01-MAY-02:62 | 5.73 |
June | 3095118.37 | 7532.40 | 14-JUN-03:23 | 22.20 |
July | 5358278.09 | 7748.13 | 09-JUL-02:04 | 18.00 |
August | 2431763.39 | 7822.94 | 19-AUG-02:03 | 15.83 |
September | 52406597.81 | 4494.57 | 30-SEP-03:37 | 20.90 |
October | 0.167078E+10 | 21890.83 | 30-OCT-04:01 | -10.0 |
November | 0.260024E+10 | 25553.67 | 29-NOV-05:01 | -10.0 |
December | 0.597278E+10 | 40405.99 | 24-DEC-03:11 | -20.7 |
Annual Sum or Average | 0.237684E+11 | |||
Minimum of Months | 2431763.39 | 4494.57 | -20.7 | |
Maximum of Months | 0.597278E+10 | 40405.99 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1678992.80 | 7890.49 | 16-JAN-05:03 | -11.0 |
February | 2141367.80 | 8142.36 | 02-FEB-05:03 | -9.0 |
March | 1170324.71 | 5782.43 | 02-MAR-05:03 | -8.0 |
April | 852276.50 | 7648.76 | 17-APR-04:03 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 272764.73 | 4546.08 | 30-OCT-04:03 | -10.0 |
November | 1057446.64 | 8025.73 | 29-NOV-05:03 | -10.0 |
December | 1236307.48 | 6759.68 | 19-DEC-05:03 | -16.4 |
Annual Sum or Average | 8409480.66 | |||
Minimum of Months | 0.00 | 0.00 | -16.4 | |
Maximum of Months | 2141367.80 | 8142.36 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.691040E+09 | 681.55 | 02-JAN-16:40 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.586634E+09 | 681.55 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.586228E+09 | 681.55 | 01-MAR-17:30 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.513489E+09 | 681.55 | 01-APR-17:49 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.484049E+09 | 681.55 | 01-MAY-18:49 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.449005E+09 | 681.55 | 01-JUN-19:19 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.465539E+09 | 681.55 | 01-JUL-19:30 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.520284E+09 | 681.55 | 01-AUG-18:49 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.530210E+09 | 681.55 | 01-SEP-18:30 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.614502E+09 | 681.55 | 02-OCT-17:10 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.660797E+09 | 681.55 | 01-NOV-16:40 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.705598E+09 | 681.55 | 01-DEC-16:19 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.680738E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.449005E+09 | 681.55 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.705598E+09 | 681.55 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147870E+10 | 901.93 | 02-JAN-10:09 | 0.166069E+11 | 10143.54 | 01-JAN-11:09 |
February | 0.133950E+10 | 901.93 | 01-FEB-10:09 | 0.149998E+11 | 10143.54 | 01-FEB-11:09 |
March | 0.150425E+10 | 901.93 | 01-MAR-10:09 | 0.166070E+11 | 10143.54 | 01-MAR-11:09 |
April | 0.143688E+10 | 901.93 | 01-APR-16:10 | 0.160712E+11 | 10143.54 | 01-APR-10:09 |
May | 0.149147E+10 | 901.93 | 01-MAY-09:09 | 0.166070E+11 | 10143.54 | 01-MAY-10:09 |
June | 0.145377E+10 | 901.93 | 01-JUN-09:09 | 0.160713E+11 | 10143.54 | 01-JUN-10:09 |
July | 0.147476E+10 | 901.93 | 01-JUL-16:10 | 0.166069E+11 | 10143.54 | 01-JUL-10:09 |
August | 0.150425E+10 | 901.93 | 01-AUG-09:09 | 0.166070E+11 | 10143.54 | 01-AUG-10:09 |
September | 0.143724E+10 | 901.93 | 01-SEP-09:09 | 0.160712E+11 | 10143.54 | 01-SEP-10:09 |
October | 0.147852E+10 | 901.93 | 02-OCT-09:09 | 0.166069E+11 | 10143.54 | 01-OCT-10:09 |
November | 0.143180E+10 | 901.93 | 01-NOV-09:09 | 0.160712E+11 | 10143.54 | 01-NOV-10:09 |
December | 0.147494E+10 | 901.93 | 01-DEC-10:09 | 0.166069E+11 | 10143.54 | 01-DEC-11:09 |
Annual Sum or Average | 0.175061E+11 | 0.195533E+12 | ||||
Minimum of Months | 0.133950E+10 | 901.93 | 0.149998E+11 | 10143.54 | ||
Maximum of Months | 0.150425E+10 | 901.93 | 0.166070E+11 | 10143.54 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.691040E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116196E+11 |
February | 0.852256E+10 | 0.586634E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111433E+11 |
March | 0.954557E+10 | 0.586228E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27517.93 | 0.938716E+10 |
April | 0.915225E+10 | 0.513489E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816866E+10 |
May | 0.947560E+10 | 0.484049E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83149112.49 | 0.422151E+10 |
June | 0.922788E+10 | 0.449005E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148026E+10 | 0.105563E+10 |
July | 0.939996E+10 | 0.465539E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153771E+10 | 0.976076E+09 |
August | 0.954557E+10 | 0.520284E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127632E+10 | 0.127198E+10 |
September | 0.915225E+10 | 0.530210E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585598E+09 | 0.234933E+10 |
October | 0.940563E+10 | 0.614502E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11438862.25 | 0.807590E+10 |
November | 0.909363E+10 | 0.660797E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100410E+11 |
December | 0.939996E+10 | 0.705598E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132795E+11 |
Annual Sum or Average | 0.111326E+12 | 0.680738E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497450E+10 | 0.815896E+11 |
Minimum of Months | 0.852256E+10 | 0.449005E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976076E+09 |
Maximum of Months | 0.954557E+10 | 0.705598E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153771E+10 | 0.132795E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147870E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144473E+09 |
February | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219561E+09 |
March | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249337E+09 |
April | 0.655836E+09 | 0.143688E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248562E+09 |
May | 0.679007E+09 | 0.149147E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 246235.16 | 0.153652E+09 |
June | 0.661256E+09 | 0.145377E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 9923865.45 | 78597870.25 |
July | 0.673587E+09 | 0.147476E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10493119.82 | 78162363.46 |
August | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 6752265.00 | 77699633.38 |
September | 0.655836E+09 | 0.143724E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2569779.27 | 0.110105E+09 |
October | 0.673993E+09 | 0.147852E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 9310.07 | 0.181951E+09 |
November | 0.651635E+09 | 0.143180E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172439E+09 |
December | 0.673587E+09 | 0.147494E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312697E+09 |
Annual Sum or Average | 0.797748E+10 | 0.175061E+11 | 0.146594E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 29994574.77 | 0.202724E+10 |
Minimum of Months | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77699633.38 |
Maximum of Months | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 10493119.82 | 0.312697E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384958E+09 | 0.739970E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310037E+09 | 0.895298E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279190E+09 | 0.115325E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192468E+09 | 0.118924E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193081E+09 | 0.150786E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227241E+09 | 0.165414E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206422E+09 | 0.149047E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232804E+09 | 0.152853E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313331E+09 | 0.116149E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329384E+09 | 0.972914E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327221E+09 | 0.795766E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389471E+09 | 0.574717E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338561E+10 | 0.136637E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192468E+09 | 0.574717E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389471E+09 | 0.165414E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 681.55 | 02-JAN-16:40 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 21584.43 | 05-JAN-19:00 |
February | 9454.80 | 04-FEB-19:10 | 681.55 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 20957.26 | 11-FEB-20:00 |
March | 9454.80 | 04-MAR-19:10 | 681.55 | 01-MAR-17:30 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.86 | 14-MAR-13:00 | 17993.55 | 04-MAR-20:00 |
April | 9454.80 | 01-APR-18:10 | 681.55 | 01-APR-17:49 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 12096.65 | 15-APR-18:53 |
May | 9454.80 | 06-MAY-18:10 | 681.55 | 01-MAY-18:49 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.26 | 17-MAY-13:00 | 8121.52 | 11-MAY-19:53 |
June | 9454.80 | 03-JUN-18:10 | 681.55 | 01-JUN-19:19 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6263.83 | 26-JUN-17:03 | 4109.16 | 02-JUN-20:00 |
July | 9454.80 | 01-JUL-18:10 | 681.55 | 01-JUL-19:30 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5539.34 | 17-JUL-11:55 | 3836.70 | 05-JUL-19:56 |
August | 9454.80 | 05-AUG-18:10 | 681.55 | 01-AUG-18:49 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5366.60 | 16-AUG-17:03 | 4343.10 | 22-AUG-19:55 |
September | 9454.80 | 02-SEP-18:10 | 681.55 | 01-SEP-18:30 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2982.03 | 08-SEP-12:55 | 10849.92 | 21-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 681.55 | 02-OCT-17:10 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 876.76 | 11-OCT-13:00 | 15348.90 | 30-OCT-18:00 |
November | 9454.80 | 04-NOV-18:10 | 681.55 | 01-NOV-16:40 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 19319.69 | 29-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 681.55 | 01-DEC-16:19 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 23801.50 | 21-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3836.70 | |||||
Maximum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6263.83 | 23801.50 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.93 | 02-JAN-10:09 | 7408.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 567.50 | 13-JAN-04:53 |
February | 677.52 | 04-FEB-19:10 | 901.93 | 01-FEB-10:09 | 7408.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 537.65 | 24-FEB-04:40 |
March | 677.52 | 04-MAR-19:10 | 901.93 | 01-MAR-10:09 | 7408.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1199.36 | 19-MAR-02:00 |
April | 677.52 | 01-APR-18:10 | 901.93 | 01-APR-16:10 | 7408.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 793.50 | 10-APR-03:50 |
May | 677.52 | 06-MAY-18:10 | 901.93 | 01-MAY-09:09 | 7408.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 10.16 | 17-MAY-13:00 | 535.01 | 03-MAY-03:10 |
June | 677.52 | 03-JUN-18:10 | 901.93 | 01-JUN-09:09 | 7408.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 54.85 | 14-JUN-12:00 | 339.08 | 09-JUN-02:00 |
July | 677.52 | 01-JUL-18:10 | 901.93 | 01-JUL-16:10 | 7408.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 48.47 | 16-JUL-12:00 | 349.81 | 03-JUL-03:10 |
August | 677.52 | 05-AUG-18:10 | 901.93 | 01-AUG-09:09 | 7408.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 45.08 | 02-AUG-15:23 | 373.98 | 16-AUG-01:30 |
September | 677.52 | 02-SEP-18:10 | 901.93 | 01-SEP-09:09 | 7408.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.33 | 09-SEP-14:52 | 352.02 | 02-SEP-02:10 |
October | 677.52 | 07-OCT-18:10 | 901.93 | 02-OCT-09:09 | 7408.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 2.83 | 11-OCT-14:00 | 507.77 | 29-OCT-03:40 |
November | 677.52 | 04-NOV-18:10 | 901.93 | 01-NOV-09:09 | 7408.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 833.93 | 01-NOV-04:00 |
December | 677.52 | 02-DEC-19:10 | 901.93 | 01-DEC-10:09 | 7408.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 810.18 | 24-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 339.08 | ||||||
Maximum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 54.85 | 1199.36 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.38 | 08-JAN-03:53 | 1659.87 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.89 | 07-FEB-07:55 | 1977.44 | 12-FEB-13:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.76 | 23-MAR-06:53 | 2236.76 | 26-MAR-12:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579.13 | 07-APR-03:51 | 2463.90 | 24-APR-12:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.36 | 13-MAY-05:23 | 2308.87 | 09-MAY-12:20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.06 | 06-JUN-22:00 | 2181.72 | 22-JUN-12:40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.16 | 01-JUL-05:23 | 2250.14 | 03-JUL-12:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.33 | 15-AUG-03:00 | 2159.33 | 24-AUG-13:20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.73 | 28-SEP-06:42 | 1943.29 | 20-SEP-12:30 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.79 | 14-OCT-07:12 | 1939.63 | 04-OCT-13:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.82 | 30-NOV-07:53 | 1820.18 | 12-NOV-12:30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 699.13 | 23-DEC-08:41 | 1495.49 | 21-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.16 | 1495.49 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 746.38 | 2463.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17769.51 | 14-JAN-04:08 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.67 |
February | 22571.55 | 12-FEB-04:48 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 445.41 |
March | 10170.62 | 05-MAR-00:01 | 5252.67 | 1514.58 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 |
April | 9099.97 | 16-APR-23:01 | 5252.67 | 1135.93 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.43 |
May | 9883.51 | 17-MAY-12:55 | 14707.47 | 327.14 | 6776.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.25 | 0.00 |
June | 25692.29 | 13-JUN-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.84 |
July | 24836.03 | 01-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.90 |
August | 28042.67 | 17-AUG-02:61 | 0.00 | 200.07 | 2160.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.61 |
September | 27760.92 | 17-SEP-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 |
October | 25228.40 | 11-OCT-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.05 |
November | 12699.16 | 30-NOV-03:19 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.29 |
December | 27749.90 | 22-DEC-03:11 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9099.97 | 0.00 | 200.07 | 2160.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28042.67 | 14707.47 | 1514.58 | 6776.30 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.25 | 557.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 36600.07 | 05-JAN-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 33.34 |
February | 38561.27 | 12-FEB-05:01 | 0.00 | 250.09 | 36578.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 122.43 |
March | 48690.41 | 14-MAR-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 59.88 |
April | 43131.10 | 21-APR-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
May | 49358.92 | 09-MAY-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 76.28 |
June | 49600.45 | 09-JUN-03:21 | 0.00 | 250.09 | 21234.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 172.44 |
July | 48048.47 | 02-JUL-02:11 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 167.08 |
August | 44909.77 | 17-AUG-02:11 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 120.31 |
September | 48339.71 | 15-SEP-03:31 | 0.00 | 250.09 | 21234.78 | 13789.89 | 0.00 | 0.00 | 0.00 | 0.00 | 152.59 |
October | 49138.00 | 20-OCT-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 65.54 |
November | 50419.64 | 07-NOV-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 46.26 |
December | 41343.25 | 22-DEC-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 48.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 36600.07 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 | |
Maximum of Months | 50419.64 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 172.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.29 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.93 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.25 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.66 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.65 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.79 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.11 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.46 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.11 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.97 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.46 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.357831E+11 | 22236.47 | 05-JAN-11:09 | 0.106192E+12 | 118174.11 | 05-JAN-13:09 |
February | 0.322357E+11 | 21779.65 | 01-FEB-11:09 | 0.103150E+12 | 99554.26 | 12-FEB-07:10 |
March | 0.354825E+11 | 23415.25 | 14-MAR-10:20 | 0.919975E+11 | 96469.40 | 04-MAR-13:09 |
April | 0.339784E+11 | 22284.04 | 19-APR-10:00 | 0.814958E+11 | 80170.32 | 03-APR-10:20 |
May | 0.366087E+11 | 26846.03 | 17-MAY-10:20 | 0.616622E+11 | 54163.33 | 02-MAY-10:39 |
June | 0.428880E+11 | 32529.80 | 26-JUN-16:10 | 0.560968E+11 | 49287.88 | 01-JUN-12:39 |
July | 0.448139E+11 | 32559.59 | 17-JUL-11:09 | 0.572484E+11 | 48689.06 | 01-JUL-12:30 |
August | 0.439855E+11 | 32611.82 | 16-AUG-11:09 | 0.570590E+11 | 48328.41 | 31-AUG-12:50 |
September | 0.398756E+11 | 29323.10 | 09-SEP-10:00 | 0.564516E+11 | 50617.10 | 22-SEP-10:20 |
October | 0.359815E+11 | 25608.86 | 11-OCT-10:20 | 0.779764E+11 | 91424.11 | 30-OCT-12:30 |
November | 0.346133E+11 | 23032.87 | 09-NOV-11:20 | 0.898183E+11 | 95309.94 | 29-NOV-20:00 |
December | 0.360523E+11 | 22292.43 | 20-DEC-11:09 | 0.117508E+12 | 120568.36 | 20-DEC-13:09 |
Annual Sum or Average | 0.452298E+12 | 0.956656E+12 | ||||
Minimum of Months | 0.322357E+11 | 21779.65 | 0.560968E+11 | 48328.41 | ||
Maximum of Months | 0.448139E+11 | 32611.82 | 0.117508E+12 | 120568.36 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.216974E+10 | 0.170593E+10 | 0.225803E+11 | 0.00 | 0.522396E+10 | 0.79 | 0.00 | 43004572.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192613E+10 | 0.140517E+10 | 0.203951E+11 | 0.00 | 0.485463E+10 | 0.72 | 0.00 | 15392255.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209048E+10 | 0.136422E+10 | 0.225804E+11 | 0.00 | 0.505061E+10 | 0.80 | 0.00 | 0.248047E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195037E+10 | 0.112619E+10 | 0.218518E+11 | 0.00 | 0.479132E+10 | 0.77 | 0.00 | 0.206923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197552E+10 | 0.101730E+10 | 0.225803E+11 | 0.00 | 0.466021E+10 | 0.80 | 0.00 | 0.188097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190278E+10 | 0.917178E+09 | 0.218520E+11 | 0.00 | 0.476418E+10 | 0.77 | 0.00 | 0.889107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.194030E+10 | 0.966854E+09 | 0.225802E+11 | 0.00 | 0.493909E+10 | 0.79 | 0.00 | 0.967125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202454E+10 | 0.108921E+10 | 0.225804E+11 | 0.00 | 0.489775E+10 | 0.80 | 0.00 | 0.867087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196745E+10 | 0.123570E+10 | 0.218518E+11 | 0.00 | 0.462198E+10 | 0.77 | 0.00 | 0.571842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209302E+10 | 0.147703E+10 | 0.225803E+11 | 0.00 | 0.490187E+10 | 0.79 | 0.00 | 0.661940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209259E+10 | 0.160046E+10 | 0.218519E+11 | 0.00 | 0.491471E+10 | 0.77 | 0.00 | 0.173725E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218054E+10 | 0.175369E+10 | 0.225802E+11 | 0.00 | 0.541405E+10 | 0.79 | 0.00 | 82588444.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.243134E+11 | 0.156589E+11 | 0.265865E+12 | 0.00 | 0.590344E+11 | 9.37 | 0.00 | 0.362642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190278E+10 | 0.917178E+09 | 0.203951E+11 | 0.00 | 0.462198E+10 | 0.72 | 0.00 | 15392255.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.218054E+10 | 0.175369E+10 | 0.225804E+11 | 0.00 | 0.541405E+10 | 0.80 | 0.00 | 0.967125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.455609E+11 | 0.00 | 0.201057E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.481888E+11 | 0.00 | 0.183572E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.313973E+11 | 0.00 | 0.200745E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.235512E+11 | 0.00 | 0.187261E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.275584E+10 | 0.00 | 0.183806E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 19528137.87 | 0.00 | 0.168588E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 7725416.31 | 0.00 | 0.167149E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 3426217.62 | 0.00 | 0.165298E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.999627E+09 | 0.00 | 0.162336E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.198929E+11 | 0.00 | 0.175578E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.326649E+11 | 0.00 | 0.179350E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.575583E+11 | 0.00 | 0.194240E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.262600E+12 | 0.00 | 0.216898E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 3426217.62 | 0.00 | 0.162336E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.575583E+11 | 0.00 | 0.201057E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1583.48 | 02-JAN-16:40 | 1372.31 | 01-JAN-06:10 | 14073.79 | 01-JAN-11:09 | 0.00 | 3175.45 | 05-JAN-18:00 | 0.00 | 12-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 1583.48 | 01-FEB-17:19 | 1372.31 | 01-FEB-06:10 | 14073.79 | 01-FEB-11:09 | 0.00 | 3149.80 | 12-FEB-07:10 | 0.00 | 01-FEB-11:20 | 0.00 | 01-FEB-00:10 |
March | 1583.48 | 01-MAR-17:30 | 1372.31 | 01-MAR-06:10 | 14073.79 | 01-MAR-11:09 | 0.00 | 3013.46 | 19-MAR-06:00 | 0.00 | 05-MAR-08:50 | 0.00 | 01-MAR-00:10 |
April | 1583.48 | 01-APR-17:49 | 1372.31 | 01-APR-05:10 | 14073.79 | 01-APR-10:09 | 0.00 | 2703.59 | 17-APR-06:10 | 0.00 | 13-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 1583.48 | 01-MAY-18:49 | 1372.31 | 01-MAY-18:49 | 14073.79 | 01-MAY-10:09 | 0.00 | 2399.87 | 02-MAY-06:10 | 0.00 | 02-MAY-08:39 | 0.00 | 01-MAY-00:10 |
June | 1583.48 | 01-JUN-19:19 | 1372.31 | 01-JUN-19:19 | 14073.79 | 01-JUN-10:09 | 0.00 | 3403.91 | 26-JUN-17:10 | 0.00 | 13-JUN-06:49 | 0.00 | 01-JUN-00:10 |
July | 1583.48 | 01-JUL-19:30 | 1372.31 | 01-JUL-19:30 | 14073.79 | 01-JUL-10:09 | 0.00 | 3163.58 | 17-JUL-11:09 | 0.00 | 03-JUL-08:30 | 0.00 | 01-JUL-00:10 |
August | 1583.48 | 01-AUG-18:49 | 1372.31 | 01-AUG-19:10 | 14073.79 | 01-AUG-10:09 | 0.00 | 3212.15 | 16-AUG-12:00 | 0.00 | 04-AUG-13:20 | 0.00 | 01-AUG-00:10 |
September | 1583.48 | 01-SEP-18:30 | 1372.31 | 01-SEP-05:10 | 14073.79 | 01-SEP-10:09 | 0.00 | 2535.27 | 09-SEP-11:09 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1583.48 | 02-OCT-17:10 | 1372.31 | 01-OCT-05:10 | 14073.79 | 01-OCT-10:09 | 0.00 | 2755.45 | 30-OCT-06:10 | 0.00 | 04-OCT-07:49 | 0.00 | 01-OCT-00:10 |
November | 1583.48 | 01-NOV-16:40 | 1372.31 | 01-NOV-05:10 | 14073.79 | 01-NOV-10:09 | 0.00 | 3006.61 | 29-NOV-20:00 | 0.00 | 04-NOV-09:39 | 0.00 | 01-NOV-00:10 |
December | 1583.48 | 01-DEC-16:19 | 1372.31 | 01-DEC-06:10 | 14073.79 | 01-DEC-11:09 | 0.00 | 3289.88 | 21-DEC-18:10 | 0.00 | 18-DEC-06:19 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 2399.87 | 0.00 | 0.00 | ||||||
Maximum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 3403.91 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 2653.53 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1686.74 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4772.65 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3536.14 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7019.04 | 17-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14103.47 | 26-JUN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12729.32 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 12963.94 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9788.42 | 09-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6184.53 | 11-OCT-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3772.14 | 07-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3028.50 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1686.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14103.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 22236.47 | 05-JAN-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2977.65 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21779.65 | 01-FEB-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2507.26 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23415.25 | 14-MAR-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2017.30 | 0.00 | 0.00 | 1963.97 | 0.00 |
April | 22284.04 | 19-APR-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2017.30 | 0.00 | 0.00 | 2610.05 | 0.00 |
May | 26846.03 | 17-MAY-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2017.30 | 0.00 | 0.00 | 5387.43 | 0.00 |
June | 32529.80 | 26-JUN-16:10 | 1065.50 | 12724.18 | 0.00 | 0.00 | 3246.98 | 0.00 | 0.00 | 13899.29 | 0.00 |
July | 32559.59 | 17-JUL-11:09 | 1065.50 | 13174.05 | 0.00 | 0.00 | 3163.58 | 0.00 | 0.00 | 12637.00 | 0.00 |
August | 32611.82 | 16-AUG-11:09 | 1065.50 | 13174.05 | 0.00 | 0.00 | 3187.88 | 0.00 | 0.00 | 12672.14 | 0.00 |
September | 29323.10 | 09-SEP-10:00 | 947.12 | 14073.79 | 0.00 | 0.00 | 2530.42 | 0.00 | 0.00 | 9264.79 | 0.00 |
October | 25608.86 | 11-OCT-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2017.30 | 0.00 | 0.00 | 4157.57 | 0.00 |
November | 23032.87 | 09-NOV-11:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2017.30 | 0.00 | 0.00 | 1570.92 | 0.00 |
December | 22292.43 | 20-DEC-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 3033.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 21779.65 | 947.12 | 12724.18 | 0.00 | 0.00 | 2017.30 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32611.82 | 1065.50 | 14073.79 | 0.00 | 0.00 | 3246.98 | 0.00 | 0.00 | 13899.29 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 79638.30 | 05-JAN-18:00 | 0.00 | 27747.68 | 31-JAN-13:30 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 80882.08 | 12-FEB-07:10 | 0.00 | 27774.54 | 11-FEB-13:39 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 70793.10 | 19-MAR-06:00 | 0.00 | 27738.47 | 01-MAR-13:39 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 67960.49 | 03-APR-02:30 | 0.00 | 27461.92 | 01-APR-12:50 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 25829.44 | 02-MAY-06:10 | 0.00 | 26967.08 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 2349.96 | 09-JUN-05:10 | 0.00 | 26304.73 | 01-JUN-12:39 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 2099.08 | 09-JUL-02:09 | 0.00 | 25705.91 | 01-JUL-12:30 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 1937.17 | 19-AUG-02:09 | 0.00 | 25345.26 | 31-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 26582.27 | 22-SEP-06:10 | 0.00 | 25740.21 | 30-SEP-12:39 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 67960.49 | 30-OCT-02:09 | 0.00 | 26396.46 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 67960.49 | 02-NOV-02:09 | 0.00 | 27010.29 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 87802.17 | 23-DEC-07:10 | 0.00 | 27498.81 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1937.17 | 0.00 | 25345.26 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 87802.17 | 0.00 | 27774.54 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
February | 18.50 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 | 0.00 | 19.74 |
March | 12.50 | 19.92 | 0.17 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
April | 6.83 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 | 0.00 | 19.81 |
May | 0.17 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 24.58 | 0.00 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 24.63 | 0.17 | 24.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 24.67 | 0.33 | 24.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 24.69 | 0.00 | 24.69 |
October | 4.50 | 19.40 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
November | 7.33 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
December | 13.00 | 19.69 | 0.00 | 19.69 | 0.00 | 19.69 | 0.00 | 19.69 |
Annual Sum or Average | 71.50 | 19.75 | 0.33 | 19.76 | 37.67 | 21.44 | 0.50 | 21.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 | 0.00 | 19.43 |
Maximum of Months | 18.50 | 20.47 | 0.17 | 20.47 | 13.33 | 24.69 | 0.33 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.27 | 0.00 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.17 | 0.00 | 27.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.85 | 0.00 | 27.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.68 | 0.00 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 28.51 | 0.00 | 28.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 30.13 | 0.00 | 30.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 30.19 | 0.00 | 30.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 30.34 | 0.00 | 30.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 30.01 | 0.00 | 30.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 28.14 | 0.00 | 28.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.53 | 0.00 | 27.53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.27 | 0.00 | 27.27 |
Annual Sum or Average | 0.00 | 0.00 | 153.17 | 29.40 | 0.00 | 29.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.17 | 0.00 | 27.17 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 30.34 | 0.00 | 30.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 585.83 | 20.97 | 112.33 | 20.81 | 112.33 | 20.69 |
February | 535.17 | 20.94 | 148.33 | 20.80 | 148.33 | 20.70 |
March | 537.50 | 21.08 | 106.33 | 20.92 | 106.33 | 20.80 |
April | 518.17 | 21.15 | 85.17 | 21.02 | 82.50 | 20.90 |
May | 368.67 | 21.67 | 104.67 | 22.05 | 12.33 | 21.99 |
June | 98.17 | 23.27 | 468.17 | 23.78 | 53.83 | 23.78 |
July | 131.67 | 23.55 | 513.33 | 23.83 | 104.50 | 23.83 |
August | 85.00 | 23.31 | 522.67 | 23.81 | 51.83 | 23.81 |
September | 123.17 | 21.94 | 356.50 | 23.37 | 1.50 | 23.35 |
October | 458.33 | 21.20 | 103.83 | 21.35 | 49.00 | 21.24 |
November | 544.50 | 21.05 | 67.17 | 20.91 | 63.50 | 20.77 |
December | 580.33 | 20.98 | 158.00 | 20.83 | 158.00 | 20.73 |
Annual Sum or Average | 4566.50 | 21.29 | 2746.50 | 21.88 | 944.00 | 21.77 |
Minimum of Months | 85.00 | 20.94 | 67.17 | 20.80 | 1.50 | 20.69 |
Maximum of Months | 585.83 | 23.55 | 522.67 | 23.83 | 158.00 | 23.83 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 558.00 | 18.98 | 233.67 | 19.15 | 192.83 | 19.00 |
February | 519.83 | 18.96 | 238.50 | 19.02 | 214.33 | 18.90 |
March | 510.17 | 19.58 | 258.00 | 20.12 | 175.67 | 19.98 |
April | 468.50 | 19.70 | 230.33 | 20.50 | 133.00 | 20.43 |
May | 385.17 | 23.58 | 421.50 | 24.33 | 235.33 | 24.62 |
June | 503.67 | 26.05 | 586.17 | 25.97 | 500.33 | 26.00 |
July | 552.17 | 26.08 | 604.33 | 26.03 | 551.67 | 26.04 |
August | 533.00 | 26.06 | 609.67 | 25.96 | 532.67 | 26.00 |
September | 455.17 | 25.51 | 532.00 | 25.61 | 414.17 | 25.74 |
October | 441.17 | 20.52 | 251.67 | 21.66 | 129.00 | 21.84 |
November | 515.33 | 19.29 | 184.33 | 19.68 | 127.17 | 19.58 |
December | 555.67 | 19.02 | 290.17 | 19.19 | 247.17 | 19.04 |
Annual Sum or Average | 5997.83 | 21.90 | 4440.33 | 22.74 | 3453.33 | 22.96 |
Minimum of Months | 385.17 | 18.96 | 184.33 | 19.02 | 127.17 | 18.90 |
Maximum of Months | 558.00 | 26.08 | 609.67 | 26.03 | 551.67 | 26.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 21.08721 | 24.07774 | -0.3997 | 9.94771 |
February | 551.00000 | 21.02310 | 21.63750 | -0.4459 | 10.83705 |
March | 612.00000 | 21.41946 | 22.06727 | -0.3363 | 9.72645 |
April | 590.00000 | 21.48107 | 27.10633 | -0.2976 | 9.21317 |
May | 611.00000 | 22.53330 | 32.11899 | -0.9557 | 27.60273 |
June | 592.00000 | 23.77850 | 36.00804 | -0.4039 | 9.14555 |
July | 609.00000 | 23.82789 | 38.95910 | -0.3680 | 8.46358 |
August | 612.00000 | 23.79899 | 37.53250 | -0.3584 | 8.34531 |
September | 590.00000 | 23.45799 | 28.97896 | -0.5287 | 13.27846 |
October | 610.00000 | 21.84764 | 25.12644 | -0.1377 | 8.16363 |
November | 591.00000 | 21.26730 | 25.83421 | -0.3030 | 8.78796 |
December | 609.00000 | 21.11395 | 17.88413 | -0.4344 | 10.77724 |
Annual Sum or Average | 7187.00000 | 22.22694 | 28.15211 | -0.4142 | 11.20633 |
Minimum of Months | 551.00000 | 21.02310 | 17.88413 | -0.9557 | 8.16363 |
Maximum of Months | 612.00000 | 23.82789 | 38.95910 | -0.1377 | 27.60273 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 19.45161 | 31.25768 | -0.4831 | 13.32302 |
February | 551.00000 | 19.26494 | 28.88982 | -0.5477 | 14.07850 |
March | 612.00000 | 20.43150 | 28.55781 | -0.2749 | 13.39651 |
April | 590.00000 | 20.67636 | 33.27144 | -0.1823 | 13.14097 |
May | 611.00000 | 23.72452 | 34.42918 | -0.2483 | 18.05346 |
June | 592.00000 | 25.85212 | 35.40419 | 0.52386 | 12.40591 |
July | 609.00000 | 25.94451 | 37.53517 | 0.57258 | 13.21574 |
August | 612.00000 | 25.86492 | 36.92850 | 0.55553 | 12.91222 |
September | 590.00000 | 25.21641 | 30.32627 | 0.29670 | 13.60507 |
October | 610.00000 | 21.48783 | 30.46372 | 0.03421 | 13.39353 |
November | 591.00000 | 19.91674 | 32.78857 | -0.3356 | 12.36373 |
December | 609.00000 | 19.52065 | 24.40688 | -0.4956 | 14.05036 |
Annual Sum or Average | 7187.00000 | 22.29823 | 32.03908 | -0.0458 | 13.66668 |
Minimum of Months | 551.00000 | 19.26494 | 24.40688 | -0.5477 | 12.36373 |
Maximum of Months | 612.00000 | 25.94451 | 37.53517 | 0.57258 | 18.05346 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 53809127.97 | 15932643.92 | 8.50 | 53809127.97 | 0.00 | 0.00 | 0.31 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 | 4419.96 | 20-JAN-13:55 | 4419.96 | 20-JAN-13:55 | 0.00 | 20-JAN-14:50 | 1276.31 | 20-JAN-13:55 | 0.00 | 01-JAN-00:01 |
February | 14180113.23 | 4282741.42 | 2.83 | 14180113.23 | 0.00 | 0.00 | 0.17 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 | 2301.25 | 18-FEB-14:00 | 2301.25 | 18-FEB-14:00 | 0.00 | 18-FEB-13:40 | 688.30 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.344232E+09 | 98832612.53 | 27.86 | 0.344232E+09 | -0.0 | 0.00 | 0.59 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 | 8918.63 | 14-MAR-13:00 | 8918.63 | 14-MAR-13:00 | 0.00 | 13-MAR-14:47 | 2399.24 | 14-MAR-13:00 | 0.00 | 01-MAR-00:01 |
April | 0.213920E+09 | 63598544.10 | 31.00 | 0.213840E+09 | 79340.59 | 0.00 | 0.39 | 20-APR-13:00 | 0.00 | 01-APR-00:01 | 5598.07 | 20-APR-13:00 | 5598.07 | 20-APR-13:00 | 29.98 | 27-APR-16:10 | 1586.01 | 20-APR-13:00 | 0.00 | 01-APR-00:01 |
May | 0.256529E+10 | 0.715533E+09 | 148.95 | 0.251359E+10 | 51695210.42 | 0.00 | 0.81 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 | 12861.05 | 17-MAY-12:55 | 12861.05 | 17-MAY-12:55 | 1368.33 | 31-MAY-18:40 | 3264.21 | 17-MAY-12:55 | 0.00 | 01-MAY-00:01 |
June | 0.143498E+11 | 0.382159E+10 | 418.18 | 0.134486E+11 | 0.901177E+09 | 0.00 | 1.00 | 02-JUN-02:61 | 0.00 | 01-JUN-00:01 | 33822.78 | 18-JUN-02:62 | 33822.78 | 14-JUN-02:61 | 13891.36 | 18-JUN-02:62 | 8108.98 | 02-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.154833E+11 | 0.409645E+10 | 449.25 | 0.142218E+11 | 0.126153E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 33822.78 | 10-JUL-02:62 | 33822.78 | 01-JUL-02:61 | 17444.14 | 31-JUL-02:61 | 8108.98 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.142425E+11 | 0.375771E+10 | 426.56 | 0.132552E+11 | 0.987256E+09 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 34504.60 | 04-AUG-02:41 | 33822.78 | 15-AUG-02:41 | 20442.38 | 04-AUG-02:41 | 8154.88 | 04-AUG-02:41 | 0.00 | 01-AUG-00:01 |
September | 0.931954E+10 | 0.248647E+10 | 336.85 | 0.909785E+10 | 0.221692E+09 | 0.00 | 1.00 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 | 33822.78 | 11-SEP-02:41 | 33822.78 | 30-SEP-02:61 | 12648.30 | 01-SEP-02:61 | 8108.98 | 01-SEP-02:61 | 0.00 | 01-SEP-00:01 |
October | 0.990675E+09 | 0.277728E+09 | 69.72 | 0.990456E+09 | 219230.32 | 0.00 | 1.00 | 11-OCT-02:61 | 0.00 | 01-OCT-00:01 | 16891.99 | 11-OCT-02:61 | 16762.62 | 11-OCT-02:61 | 640.42 | 08-OCT-03:19 | 4053.00 | 11-OCT-02:61 | 0.00 | 01-OCT-00:01 |
November | 0.242959E+09 | 70771275.41 | 22.83 | 0.242959E+09 | 0.00 | 0.00 | 0.47 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 | 6836.98 | 07-NOV-14:00 | 6836.98 | 07-NOV-14:00 | 0.00 | 06-NOV-13:55 | 1899.34 | 07-NOV-14:00 | 0.00 | 01-NOV-00:01 |
December | 0.109548E+09 | 32267633.76 | 11.83 | 0.109548E+09 | 0.00 | 0.00 | 0.38 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 | 5425.77 | 01-DEC-14:00 | 5425.77 | 01-DEC-14:00 | 0.00 | 01-DEC-14:10 | 1541.45 | 01-DEC-14:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.579297E+11 | 0.154412E+11 | 1954.37 | 0.545061E+11 | 0.342365E+10 | 0.00 | ||||||||||||||
Minimum of Months | 14180113.23 | 4282741.42 | 2.83 | 14180113.23 | -0.0 | 0.00 | 0.17 | 0.00 | 2301.25 | 2301.25 | 0.00 | 688.30 | 0.00 | |||||||
Maximum of Months | 0.154833E+11 | 0.409645E+10 | 449.25 | 0.142218E+11 | 0.126153E+10 | 0.00 | 1.00 | 0.00 | 34504.60 | 33822.78 | 20442.38 | 8154.88 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 92301176.36 | 27071929.04 | 14.04 | 90952869.17 | 1348307.20 | 0.00 | 0.59 | 20-JAN-05:01 | 0.00 | 01-JAN-00:01 | 7654.63 | 20-JAN-05:01 | 6653.49 | 20-JAN-05:01 | 1480.52 | 27-JAN-04:06 | 2058.28 | 20-JAN-05:01 | 0.00 | 01-JAN-00:01 |
February | 37467528.24 | 11109514.27 | 6.98 | 36655280.56 | 812247.68 | 0.00 | 0.29 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 | 3434.86 | 18-FEB-14:00 | 3434.86 | 18-FEB-14:00 | 989.02 | 28-FEB-04:04 | 998.44 | 18-FEB-14:00 | 0.00 | 01-FEB-00:01 |
March | 0.529316E+09 | 0.149214E+09 | 49.97 | 0.525938E+09 | 3378343.74 | 0.00 | 1.00 | 10-MAR-04:21 | 0.00 | 01-MAR-00:01 | 28933.55 | 14-MAR-02:61 | 28210.50 | 16-MAR-03:21 | 6161.18 | 17-MAR-04:01 | 6936.79 | 14-MAR-02:61 | 0.00 | 01-MAR-00:01 |
April | 0.499173E+09 | 0.143325E+09 | 55.86 | 0.484861E+09 | 14312095.42 | 0.00 | 1.00 | 07-APR-03:21 | 0.00 | 01-APR-00:01 | 28933.55 | 07-APR-03:21 | 25120.70 | 07-APR-03:21 | 10473.50 | 21-APR-02:61 | 6936.79 | 07-APR-03:21 | 0.00 | 01-APR-00:01 |
May | 0.432905E+10 | 0.116544E+10 | 220.15 | 0.410632E+10 | 0.222735E+09 | 0.00 | 1.00 | 05-MAY-02:61 | 0.00 | 01-MAY-00:01 | 28933.55 | 25-MAY-02:61 | 25800.14 | 11-MAY-02:11 | 14562.44 | 22-MAY-02:61 | 6936.79 | 05-MAY-04:01 | 0.00 | 01-MAY-00:01 |
June | 0.197927E+11 | 0.506948E+10 | 478.37 | 0.183000E+11 | 0.149272E+10 | 0.00 | 1.00 | 01-JUN-02:11 | 0.00 | 01-JUN-00:01 | 28933.55 | 30-JUN-03:14 | 28933.55 | 14-JUN-01:22 | 16914.63 | 21-JUN-02:11 | 8262.77 | 26-JUN-15:00 | 0.00 | 01-JUN-00:01 |
July | 0.219210E+11 | 0.557480E+10 | 523.56 | 0.197371E+11 | 0.218393E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 28933.55 | 15-JUL-02:61 | 28933.55 | 01-JUL-02:41 | 16510.21 | 31-JUL-02:61 | 7588.02 | 16-JUL-13:00 | 0.00 | 01-JUL-00:01 |
August | 0.193154E+11 | 0.491316E+10 | 488.47 | 0.177183E+11 | 0.159709E+10 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 29397.80 | 04-AUG-02:11 | 28933.55 | 15-AUG-02:52 | 19763.88 | 04-AUG-02:11 | 7617.03 | 16-AUG-14:00 | 0.00 | 01-AUG-00:01 |
September | 0.126277E+11 | 0.323195E+10 | 398.78 | 0.121480E+11 | 0.479777E+09 | 0.00 | 1.00 | 01-SEP-01:32 | 0.00 | 01-SEP-00:01 | 28933.55 | 03-SEP-02:11 | 28933.55 | 30-SEP-03:11 | 16081.19 | 01-SEP-02:11 | 6936.79 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 |
October | 0.139969E+10 | 0.384212E+09 | 94.20 | 0.137310E+10 | 26589554.50 | 0.00 | 1.00 | 01-OCT-02:61 | 0.00 | 01-OCT-00:01 | 28933.55 | 10-OCT-04:01 | 24656.52 | 20-OCT-04:01 | 10834.37 | 09-OCT-02:61 | 6936.79 | 06-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 0.361768E+09 | 0.102954E+09 | 29.71 | 0.356462E+09 | 5305991.32 | 0.00 | 1.00 | 07-NOV-04:21 | 0.00 | 01-NOV-00:01 | 28933.55 | 07-NOV-04:21 | 27086.31 | 07-NOV-05:01 | 8977.77 | 10-NOV-05:01 | 6936.79 | 07-NOV-04:21 | 0.00 | 01-NOV-00:01 |
December | 0.173684E+09 | 50320811.14 | 18.85 | 0.173136E+09 | 547938.59 | 0.00 | 0.46 | 02-DEC-15:00 | 0.00 | 01-DEC-00:01 | 5697.97 | 02-DEC-15:00 | 5697.97 | 02-DEC-15:00 | 704.12 | 29-DEC-04:06 | 1587.31 | 02-DEC-15:00 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.810793E+11 | 0.208230E+11 | 2378.94 | 0.750507E+11 | 0.602855E+10 | 0.00 | ||||||||||||||
Minimum of Months | 37467528.24 | 11109514.27 | 6.98 | 36655280.56 | 547938.59 | 0.00 | 0.29 | 0.00 | 3434.86 | 3434.86 | 704.12 | 998.44 | 0.00 | |||||||
Maximum of Months | 0.219210E+11 | 0.557480E+10 | 523.56 | 0.197371E+11 | 0.218393E+10 | 0.00 | 1.00 | 0.00 | 29397.80 | 28933.55 | 19763.88 | 8262.77 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.83 | 74.05 | 46.78 | 109.66 | 183.75 | 0.00 | 0.00 | 0.00 |
February | 160.51 | 101.33 | 59.18 | 155.65 | 188.61 | 0.00 | 0.00 | 0.00 |
March | 193.73 | 113.00 | 80.73 | 203.31 | 141.20 | 0.00 | 0.00 | 0.00 |
April | 198.68 | 96.78 | 101.90 | 205.13 | 122.40 | 0.00 | 0.00 | 0.00 |
May | 232.26 | 97.01 | 135.24 | 275.03 | 71.48 | 0.00 | 0.00 | 0.00 |
June | 283.38 | 148.77 | 134.61 | 390.94 | 41.62 | 0.00 | 0.00 | 0.00 |
July | 257.61 | 122.67 | 134.94 | 359.57 | 38.68 | 0.00 | 0.00 | 0.00 |
August | 259.84 | 143.11 | 116.73 | 357.31 | 46.04 | 0.00 | 0.00 | 0.00 |
September | 216.20 | 117.44 | 98.75 | 281.46 | 68.82 | 0.00 | 0.00 | 0.00 |
October | 156.57 | 85.79 | 70.78 | 168.61 | 143.36 | 0.00 | 0.00 | 0.00 |
November | 121.87 | 68.81 | 53.06 | 116.68 | 169.93 | 0.00 | 0.00 | 0.00 |
December | 105.51 | 60.78 | 44.73 | 90.22 | 213.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.37 | 102.41 | 89.96 | 226.47 | 118.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.51 | 60.78 | 44.73 | 90.22 | 38.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 283.38 | 148.77 | 135.24 | 390.94 | 213.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 739.67 | 608.46 | 131.21 | 870.41 | 341.91 | 0.00 | 0.00 | 0.00 |
February | 709.48 | 565.64 | 143.84 | 829.97 | 357.20 | 0.00 | 0.00 | 0.00 |
March | 523.08 | 344.16 | 178.92 | 620.14 | 282.05 | 0.00 | 0.00 | 0.00 |
April | 338.79 | 136.23 | 202.56 | 367.73 | 255.72 | 0.00 | 0.00 | 0.00 |
May | 310.46 | 56.91 | 253.56 | 370.26 | 154.00 | 0.00 | 0.00 | 0.00 |
June | 286.24 | 52.32 | 233.92 | 423.28 | 90.20 | 0.00 | 0.00 | 0.00 |
July | 297.96 | 53.36 | 244.61 | 443.39 | 82.19 | 0.00 | 0.00 | 0.00 |
August | 379.37 | 158.59 | 220.78 | 562.32 | 95.92 | 0.00 | 0.00 | 0.00 |
September | 488.10 | 272.35 | 215.74 | 678.17 | 143.67 | 0.00 | 0.00 | 0.00 |
October | 583.62 | 414.09 | 169.53 | 725.50 | 282.42 | 0.00 | 0.00 | 0.00 |
November | 711.06 | 566.82 | 144.24 | 855.06 | 323.74 | 0.00 | 0.00 | 0.00 |
December | 679.96 | 550.35 | 129.61 | 780.59 | 393.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 502.82 | 313.51 | 189.30 | 626.08 | 232.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 286.24 | 52.32 | 129.61 | 367.73 | 82.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.67 | 608.46 | 253.56 | 870.41 | 393.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.54 | 81.45 | 47.09 | 124.18 | 186.93 | 0.00 | 0.00 | 0.00 |
February | 155.00 | 96.05 | 58.95 | 149.66 | 189.62 | 0.00 | 0.00 | 0.00 |
March | 181.49 | 100.13 | 81.36 | 186.99 | 142.69 | 0.00 | 0.00 | 0.00 |
April | 170.88 | 72.35 | 98.53 | 169.60 | 124.82 | 0.00 | 0.00 | 0.00 |
May | 208.86 | 73.63 | 135.23 | 246.55 | 74.80 | 0.00 | 0.00 | 0.00 |
June | 255.45 | 122.91 | 132.54 | 355.97 | 44.92 | 0.00 | 0.00 | 0.00 |
July | 208.13 | 76.24 | 131.90 | 291.83 | 40.87 | 0.00 | 0.00 | 0.00 |
August | 217.23 | 107.32 | 109.92 | 297.52 | 47.40 | 0.00 | 0.00 | 0.00 |
September | 192.62 | 92.37 | 100.25 | 251.11 | 71.85 | 0.00 | 0.00 | 0.00 |
October | 162.04 | 92.62 | 69.42 | 178.07 | 144.16 | 0.00 | 0.00 | 0.00 |
November | 132.97 | 80.73 | 52.24 | 131.70 | 170.47 | 0.00 | 0.00 | 0.00 |
December | 107.40 | 63.44 | 43.96 | 93.57 | 213.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 176.77 | 88.16 | 88.61 | 206.63 | 120.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 107.40 | 63.44 | 43.96 | 93.57 | 40.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 255.45 | 122.91 | 135.23 | 355.97 | 213.23 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.323634E+09 | 0.198332E+09 | 0.125301E+09 | 0.293702E+09 | 0.492165E+09 |
February | 0.388307E+09 | 0.245136E+09 | 0.143171E+09 | 0.376544E+09 | 0.456284E+09 |
March | 0.518891E+09 | 0.302664E+09 | 0.216227E+09 | 0.544558E+09 | 0.378179E+09 |
April | 0.514985E+09 | 0.250858E+09 | 0.264127E+09 | 0.531695E+09 | 0.317254E+09 |
May | 0.622077E+09 | 0.259843E+09 | 0.362233E+09 | 0.736644E+09 | 0.191461E+09 |
June | 0.734513E+09 | 0.385599E+09 | 0.348914E+09 | 0.101330E+10 | 0.107869E+09 |
July | 0.689989E+09 | 0.328555E+09 | 0.361434E+09 | 0.963077E+09 | 0.103590E+09 |
August | 0.695948E+09 | 0.383303E+09 | 0.312646E+09 | 0.957029E+09 | 0.123323E+09 |
September | 0.560385E+09 | 0.304416E+09 | 0.255968E+09 | 0.729557E+09 | 0.178386E+09 |
October | 0.419358E+09 | 0.229784E+09 | 0.189574E+09 | 0.451618E+09 | 0.383985E+09 |
November | 0.315887E+09 | 0.178353E+09 | 0.137534E+09 | 0.302430E+09 | 0.440470E+09 |
December | 0.282589E+09 | 0.162791E+09 | 0.119798E+09 | 0.241645E+09 | 0.571149E+09 |
Annual Sum or Average | 0.606656E+10 | 0.322964E+10 | 0.283693E+10 | 0.714180E+10 | 0.374412E+10 |
Minimum of Months | 0.282589E+09 | 0.162791E+09 | 0.119798E+09 | 0.241645E+09 | 0.103590E+09 |
Maximum of Months | 0.734513E+09 | 0.385599E+09 | 0.362233E+09 | 0.101330E+10 | 0.571149E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.198113E+10 | 0.162969E+10 | 0.351438E+09 | 0.233130E+10 | 0.915773E+09 |
February | 0.171637E+10 | 0.136840E+10 | 0.347973E+09 | 0.200787E+10 | 0.864136E+09 |
March | 0.140103E+10 | 0.921796E+09 | 0.479232E+09 | 0.166098E+10 | 0.755451E+09 |
April | 0.878139E+09 | 0.353102E+09 | 0.525036E+09 | 0.953150E+09 | 0.662835E+09 |
May | 0.831542E+09 | 0.152415E+09 | 0.679127E+09 | 0.991703E+09 | 0.412476E+09 |
June | 0.741924E+09 | 0.135602E+09 | 0.606321E+09 | 0.109714E+10 | 0.233808E+09 |
July | 0.798069E+09 | 0.142912E+09 | 0.655158E+09 | 0.118759E+10 | 0.220137E+09 |
August | 0.101610E+10 | 0.424769E+09 | 0.591335E+09 | 0.150612E+10 | 0.256900E+09 |
September | 0.126514E+10 | 0.705942E+09 | 0.559202E+09 | 0.175782E+10 | 0.372405E+09 |
October | 0.156317E+10 | 0.110910E+10 | 0.454065E+09 | 0.194318E+10 | 0.756446E+09 |
November | 0.184306E+10 | 0.146919E+10 | 0.373876E+09 | 0.221631E+10 | 0.839136E+09 |
December | 0.182120E+10 | 0.147405E+10 | 0.347146E+09 | 0.209074E+10 | 0.105454E+10 |
Annual Sum or Average | 0.158569E+11 | 0.988698E+10 | 0.596991E+10 | 0.197439E+11 | 0.734405E+10 |
Minimum of Months | 0.741924E+09 | 0.135602E+09 | 0.347146E+09 | 0.953150E+09 | 0.220137E+09 |
Maximum of Months | 0.198113E+10 | 0.162969E+10 | 0.679127E+09 | 0.233130E+10 | 0.105454E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.344274E+09 | 0.218150E+09 | 0.126124E+09 | 0.332598E+09 | 0.500678E+09 |
February | 0.374970E+09 | 0.232370E+09 | 0.142600E+09 | 0.362056E+09 | 0.458733E+09 |
March | 0.486109E+09 | 0.268197E+09 | 0.217912E+09 | 0.500826E+09 | 0.382190E+09 |
April | 0.442930E+09 | 0.187528E+09 | 0.255401E+09 | 0.439592E+09 | 0.323533E+09 |
May | 0.559419E+09 | 0.197216E+09 | 0.362203E+09 | 0.660371E+09 | 0.200332E+09 |
June | 0.662133E+09 | 0.318577E+09 | 0.343556E+09 | 0.922665E+09 | 0.116420E+09 |
July | 0.557464E+09 | 0.204188E+09 | 0.353276E+09 | 0.781633E+09 | 0.109479E+09 |
August | 0.581834E+09 | 0.287434E+09 | 0.294401E+09 | 0.796873E+09 | 0.126957E+09 |
September | 0.499271E+09 | 0.239433E+09 | 0.259837E+09 | 0.650874E+09 | 0.186244E+09 |
October | 0.434019E+09 | 0.248074E+09 | 0.185945E+09 | 0.476932E+09 | 0.386115E+09 |
November | 0.344648E+09 | 0.209243E+09 | 0.135404E+09 | 0.341376E+09 | 0.441858E+09 |
December | 0.287660E+09 | 0.169928E+09 | 0.117732E+09 | 0.250617E+09 | 0.571126E+09 |
Annual Sum or Average | 0.557473E+10 | 0.278034E+10 | 0.279439E+10 | 0.651641E+10 | 0.380366E+10 |
Minimum of Months | 0.287660E+09 | 0.169928E+09 | 0.117732E+09 | 0.250617E+09 | 0.109479E+09 |
Maximum of Months | 0.662133E+09 | 0.318577E+09 | 0.362203E+09 | 0.922665E+09 | 0.571126E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1075.76 | 684.11 | 989.04 | 763.95 | 225.08 | 0.00 | 0.00 |
February | 1110.60 | 710.75 | 1024.99 | 763.02 | 261.96 | 0.00 | 0.00 |
March | 993.09 | 548.60 | 898.31 | 557.29 | 341.01 | 0.00 | 0.00 |
April | 724.75 | 485.23 | 708.35 | 305.36 | 403.00 | 0.00 | 0.00 |
May | 878.50 | 286.93 | 751.58 | 227.55 | 524.03 | 0.00 | 0.00 |
June | 1161.38 | 167.94 | 825.07 | 323.99 | 501.08 | 0.00 | 0.00 |
July | 1088.93 | 155.88 | 763.71 | 252.26 | 511.45 | 0.00 | 0.00 |
August | 1211.78 | 183.99 | 856.44 | 409.01 | 447.42 | 0.00 | 0.00 |
September | 1202.18 | 275.79 | 896.91 | 482.17 | 414.74 | 0.00 | 0.00 |
October | 1063.94 | 561.70 | 902.23 | 592.50 | 309.73 | 0.00 | 0.00 |
November | 1086.46 | 647.16 | 965.89 | 716.35 | 249.54 | 0.00 | 0.00 |
December | 935.12 | 790.93 | 892.86 | 674.57 | 218.29 | 0.00 | 0.00 |
Annual Sum or Average | 1043.84 | 456.88 | 871.96 | 504.09 | 367.87 | 0.00 | 0.00 |
Minimum of Months | 724.75 | 155.88 | 708.35 | 227.55 | 218.29 | 0.00 | 0.00 |
Maximum of Months | 1211.78 | 790.93 | 1024.99 | 763.95 | 524.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.288130E+10 | 0.183232E+10 | 0.264904E+10 | 0.204617E+10 | 0.602863E+09 | 0.00 | 0.00 |
February | 0.268677E+10 | 0.171945E+10 | 0.247965E+10 | 0.184591E+10 | 0.633744E+09 | 0.00 | 0.00 |
March | 0.265990E+10 | 0.146936E+10 | 0.240603E+10 | 0.149266E+10 | 0.913371E+09 | 0.00 | 0.00 |
April | 0.187854E+10 | 0.125773E+10 | 0.183605E+10 | 0.791489E+09 | 0.104456E+10 | 0.00 | 0.00 |
May | 0.235297E+10 | 0.768524E+09 | 0.201304E+10 | 0.609474E+09 | 0.140356E+10 | 0.00 | 0.00 |
June | 0.301030E+10 | 0.435288E+09 | 0.213857E+10 | 0.839779E+09 | 0.129879E+10 | 0.00 | 0.00 |
July | 0.291660E+10 | 0.417510E+09 | 0.204552E+10 | 0.675655E+09 | 0.136987E+10 | 0.00 | 0.00 |
August | 0.324564E+10 | 0.492796E+09 | 0.229389E+10 | 0.109551E+10 | 0.119838E+10 | 0.00 | 0.00 |
September | 0.311606E+10 | 0.714845E+09 | 0.232480E+10 | 0.124979E+10 | 0.107501E+10 | 0.00 | 0.00 |
October | 0.284964E+10 | 0.150446E+10 | 0.241654E+10 | 0.158696E+10 | 0.829585E+09 | 0.00 | 0.00 |
November | 0.281609E+10 | 0.167744E+10 | 0.250360E+10 | 0.185679E+10 | 0.646814E+09 | 0.00 | 0.00 |
December | 0.250463E+10 | 0.211844E+10 | 0.239145E+10 | 0.180677E+10 | 0.584676E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.329185E+11 | 0.144082E+11 | 0.274982E+11 | 0.158970E+11 | 0.116012E+11 | 0.00 | 0.00 |
Minimum of Months | 0.187854E+10 | 0.417510E+09 | 0.183605E+10 | 0.609474E+09 | 0.584676E+09 | 0.00 | 0.00 |
Maximum of Months | 0.324564E+10 | 0.211844E+10 | 0.264904E+10 | 0.204617E+10 | 0.140356E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.146863E+11 | -0.139022E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -784032022.4 | 58.99 | 0.00 | 0.00 |
February | 0.134252E+11 | -0.127131E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -712065990.0 | 58.99 | 0.00 | 0.00 |
March | 0.146622E+11 | -0.138960E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -766198175.3 | 58.99 | 0.00 | 0.00 |
April | 0.136207E+11 | -0.128844E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -736275722.3 | 58.99 | 0.00 | 0.00 |
May | 0.132917E+11 | -0.125884E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -703321133.5 | 58.99 | 0.00 | 0.00 |
June | 0.121140E+11 | -0.114722E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -641803104.1 | 59.00 | 0.00 | 0.00 |
July | 0.119470E+11 | -0.112854E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -661563850.8 | 58.99 | 0.00 | 0.00 |
August | 0.117952E+11 | -0.111328E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -662357087.5 | 58.98 | 0.00 | 0.00 |
September | 0.116086E+11 | -0.109559E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -652740477.3 | 58.99 | 0.00 | 0.00 |
October | 0.126270E+11 | -0.118832E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -743788028.5 | 58.99 | 0.00 | 0.00 |
November | 0.129815E+11 | -0.122321E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -749406366.0 | 58.99 | 0.00 | 0.00 |
December | 0.141355E+11 | -0.133522E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -783305239.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.156895E+12 | -0.148298E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.859686E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.116086E+11 | -0.139022E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -784032022.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.146863E+11 | -0.109559E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -641803104.1 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.29 | 0.24 | 01-JAN-07:00 | 7912.12 | 33.05 | 198.83 | 262.00 | 8114.34 | 33.56 | 200.00 | 263.50 |
February | 245.50 | 0.26 | 0.24 | 01-FEB-10:39 | 2943.41 | 25.87 | 109.50 | 265.50 | 3664.97 | 26.69 | 116.83 | 264.67 |
March | 296.17 | 0.26 | 0.24 | 01-MAR-06:00 | 1952.53 | 21.18 | 68.33 | 335.00 | 1962.34 | 21.31 | 76.67 | 332.50 |
April | 296.67 | 0.26 | 0.24 | 03-APR-09:39 | 2079.80 | 18.99 | 26.33 | 354.50 | 2464.39 | 18.91 | 22.83 | 355.83 |
May | 415.33 | 0.27 | 0.24 | 01-MAY-05:49 | 1484.10 | 19.04 | 17.83 | 406.67 | 1641.68 | 19.01 | 24.67 | 408.17 |
June | 421.50 | 0.26 | 0.24 | 01-JUN-05:19 | 1543.99 | 18.53 | 2.50 | 413.00 | 1716.32 | 18.49 | 2.67 | 413.33 |
July | 430.33 | 0.27 | 0.24 | 01-JUL-05:19 | 1481.80 | 18.72 | 9.33 | 414.00 | 1662.90 | 18.65 | 15.00 | 416.33 |
August | 394.50 | 0.28 | 0.24 | 01-AUG-05:00 | 2096.83 | 18.48 | 18.00 | 383.50 | 2471.96 | 18.38 | 12.83 | 381.00 |
September | 354.00 | 0.26 | 0.24 | 01-SEP-05:00 | 1804.80 | 19.09 | 41.00 | 347.17 | 1977.03 | 19.06 | 53.17 | 345.50 |
October | 262.67 | 0.26 | 0.24 | 01-OCT-06:30 | 2805.59 | 22.39 | 93.33 | 305.50 | 2382.06 | 22.04 | 71.00 | 303.67 |
November | 257.67 | 0.28 | 0.24 | 01-NOV-08:39 | 10348.49 | 36.74 | 224.33 | 262.67 | 9326.73 | 34.02 | 185.67 | 263.00 |
December | 251.17 | 0.28 | 0.24 | 01-DEC-07:49 | 7659.60 | 34.45 | 191.00 | 253.67 | 7556.07 | 34.79 | 193.17 | 253.67 |
Annual Sum or Average | 3902.00 | 0.27 | 3281.34 | 22.86 | 1000.33 | 4003.17 | 3377.32 | 22.75 | 974.50 | 4001.17 | ||
Minimum of Months | 245.50 | 0.26 | 0.24 | 1481.80 | 18.48 | 2.50 | 253.67 | 1641.68 | 18.38 | 2.67 | 253.67 | |
Maximum of Months | 430.33 | 0.29 | 0.24 | 10348.49 | 36.74 | 224.33 | 414.00 | 9326.73 | 34.79 | 200.00 | 416.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188687E+11 | 54368.39 | 02-JAN-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204660E+11 | 54368.39 | 01-FEB-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141601E+11 | 54368.39 | 02-MAR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112288E+11 | 54368.39 | 02-APR-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175268E+10 | 22417.91 | 03-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15622510.30 | 6958.88 | 14-JUN-03:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6180333.05 | 8396.33 | 09-JUL-02:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2740974.09 | 9298.41 | 19-AUG-02:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.566113E+09 | 11085.74 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.914138E+10 | 54368.39 | 30-OCT-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143628E+11 | 54368.39 | 02-NOV-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232479E+11 | 54368.39 | 07-DEC-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2740974.09 | 6958.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232479E+11 | 54368.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.175800E+11 | 42234.93 | 14-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180850E+11 | 40538.15 | 12-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.109577E+11 | 38625.02 | 05-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.761219E+10 | 36823.00 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.451991E+09 | 13579.42 | 03-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.233589E+09 | 10236.16 | 21-SEP-22:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.677292E+10 | 36039.82 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117692E+11 | 39711.54 | 30-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.227987E+11 | 47666.32 | 22-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.962613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.227987E+11 | 47666.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 53809127.97 | 53809127.97 | 4419.96 | 20-JAN-13:55 | 4419.96 | 0.00 |
February | 0.00 | 0.00 | 14180113.23 | 14180113.23 | 2301.25 | 18-FEB-14:00 | 2301.25 | 0.00 |
March | 0.00 | 0.00 | 0.344232E+09 | 0.344232E+09 | 8918.63 | 14-MAR-13:00 | 8918.63 | 0.00 |
April | 0.00 | 0.00 | 0.213920E+09 | 0.213840E+09 | 5598.07 | 20-APR-13:00 | 5598.07 | 0.00 |
May | 0.00 | 0.00 | 0.256529E+10 | 0.251359E+10 | 12861.05 | 17-MAY-12:55 | 12861.05 | 0.00 |
June | 0.00 | 0.00 | 0.143498E+11 | 0.134486E+11 | 33822.78 | 18-JUN-02:62 | 19931.42 | 0.00 |
July | 0.00 | 0.00 | 0.154833E+11 | 0.142218E+11 | 33822.78 | 10-JUL-02:62 | 32336.99 | 0.00 |
August | 0.00 | 0.00 | 0.142425E+11 | 0.132552E+11 | 34504.60 | 04-AUG-02:41 | 14062.22 | 0.00 |
September | 0.00 | 0.00 | 0.931954E+10 | 0.909785E+10 | 33822.78 | 11-SEP-02:41 | 32645.58 | 0.00 |
October | 0.00 | 0.00 | 0.990675E+09 | 0.990456E+09 | 16891.99 | 11-OCT-02:61 | 16762.62 | 0.00 |
November | 0.00 | 0.00 | 0.242959E+09 | 0.242959E+09 | 6836.98 | 07-NOV-14:00 | 6836.98 | 0.00 |
December | 0.00 | 0.00 | 0.109548E+09 | 0.109548E+09 | 5425.77 | 01-DEC-14:00 | 5425.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.579297E+11 | 0.545061E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14180113.23 | 14180113.23 | 2301.25 | 2301.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.154833E+11 | 0.142218E+11 | 34504.60 | 32645.58 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 92301176.36 | 90952869.17 | 7654.63 | 20-JAN-05:01 | 6653.49 | 0.00 |
February | 0.00 | 0.00 | 37467528.24 | 36655280.56 | 3434.86 | 18-FEB-14:00 | 3434.86 | 0.00 |
March | 0.00 | 0.00 | 0.529316E+09 | 0.525938E+09 | 28933.55 | 14-MAR-02:61 | 26964.64 | 0.00 |
April | 0.00 | 0.00 | 0.499173E+09 | 0.484861E+09 | 28933.55 | 07-APR-03:21 | 25120.70 | 0.00 |
May | 0.00 | 0.00 | 0.432905E+10 | 0.410632E+10 | 28933.55 | 25-MAY-02:61 | 16628.38 | 0.00 |
June | 0.00 | 0.00 | 0.197927E+11 | 0.183000E+11 | 28933.55 | 30-JUN-03:14 | 25662.62 | 0.00 |
July | 0.00 | 0.00 | 0.219210E+11 | 0.197371E+11 | 28933.55 | 15-JUL-02:61 | 19593.30 | 0.00 |
August | 0.00 | 0.00 | 0.193154E+11 | 0.177183E+11 | 29397.80 | 04-AUG-02:11 | 9633.92 | 0.00 |
September | 0.00 | 0.00 | 0.126277E+11 | 0.121480E+11 | 28933.55 | 03-SEP-02:11 | 20961.67 | 0.00 |
October | 0.00 | 0.00 | 0.139969E+10 | 0.137310E+10 | 28933.55 | 10-OCT-04:01 | 22672.19 | 0.00 |
November | 0.00 | 0.00 | 0.361768E+09 | 0.356462E+09 | 28933.55 | 07-NOV-04:21 | 25564.81 | 0.00 |
December | 0.00 | 0.00 | 0.173684E+09 | 0.173136E+09 | 5697.97 | 02-DEC-15:00 | 5697.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.810793E+11 | 0.750507E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 37467528.24 | 36655280.56 | 3434.86 | 3434.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219210E+11 | 0.197371E+11 | 29397.80 | 26964.64 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5483.23 | 20523.21 | 31-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 5547.98 | 20577.87 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5483.14 | 20496.16 | 01-MAR-13:57 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5262.70 | 19904.91 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 4992.17 | 18933.93 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 4719.11 | 17791.60 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4503.75 | 16849.19 | 01-JUL-12:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4449.62 | 16327.70 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4517.86 | 16894.96 | 30-SEP-12:47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4728.18 | 17888.76 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5011.59 | 18995.58 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5276.51 | 19977.12 | 31-DEC-13:25 |
Annual Sum or Average | 0.00 | 4994.78 | ||||
Minimum of Months | 0.00 | 0.00 | 4449.62 | 16327.70 | ||
Maximum of Months | 0.00 | 0.00 | 5547.98 | 20577.87 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114379E+10 | 0.28 | 503.64 | 01-JAN-00:01 | 0.33 |
February | 0.102929E+10 | 0.28 | 503.64 | 01-FEB-00:01 | 0.33 |
March | 0.115763E+10 | 0.28 | 503.64 | 01-MAR-00:01 | 0.33 |
April | 0.113113E+10 | 0.28 | 503.64 | 01-APR-02:62 | 0.33 |
May | 0.120876E+10 | 0.29 | 503.64 | 01-MAY-04:01 | 0.32 |
June | 0.123944E+10 | 0.31 | 503.64 | 01-JUN-00:55 | 0.32 |
July | 0.128366E+10 | 0.31 | 503.64 | 01-JUL-00:10 | 0.33 |
August | 0.128452E+10 | 0.31 | 503.64 | 01-AUG-00:16 | 0.32 |
September | 0.122605E+10 | 0.31 | 503.64 | 01-SEP-00:13 | 0.33 |
October | 0.119217E+10 | 0.29 | 503.64 | 01-OCT-01:20 | 0.32 |
November | 0.112490E+10 | 0.28 | 503.64 | 01-NOV-04:01 | 0.33 |
December | 0.114847E+10 | 0.28 | 503.64 | 01-DEC-00:01 | 0.33 |
Annual Sum or Average | 0.141698E+11 | 0.29 | |||
Minimum of Months | 0.102929E+10 | 0.28 | 503.64 | 0.32 | |
Maximum of Months | 0.128452E+10 | 0.31 | 503.64 | 0.33 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.246513E+10 | 0.65 | 2216.17 | 02-JAN-03:02 | 1.08 |
February | 0.234028E+10 | 0.67 | 2216.17 | 01-FEB-03:03 | 1.08 |
March | 0.235389E+10 | 0.63 | 2216.17 | 02-MAR-03:02 | 1.08 |
April | 0.220602E+10 | 0.62 | 2216.17 | 02-APR-02:62 | 1.08 |
May | 0.202234E+10 | 0.56 | 1154.03 | 03-MAY-04:01 | 0.77 |
June | 0.194712E+10 | 0.57 | 1465.06 | 26-JUN-17:17 | 0.88 |
July | 0.201215E+10 | 0.57 | 1513.40 | 15-JUL-02:61 | 0.89 |
August | 0.201541E+10 | 0.57 | 2142.95 | 26-AUG-02:61 | 1.05 |
September | 0.194957E+10 | 0.57 | 1157.60 | 22-SEP-06:10 | 0.77 |
October | 0.221389E+10 | 0.59 | 2216.17 | 30-OCT-02:70 | 1.09 |
November | 0.228747E+10 | 0.62 | 2216.17 | 02-NOV-02:65 | 1.09 |
December | 0.258691E+10 | 0.66 | 2216.17 | 07-DEC-03:03 | 1.08 |
Annual Sum or Average | 0.264002E+11 | 0.61 | |||
Minimum of Months | 0.194712E+10 | 0.56 | 1154.03 | 0.77 | |
Maximum of Months | 0.258691E+10 | 0.67 | 2216.17 | 1.09 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161505E+10 | 0.61 | 1139.00 | 14-JAN-05:03 | 0.93 |
February | 0.148505E+10 | 0.61 | 1118.44 | 12-FEB-05:03 | 0.93 |
March | 0.153909E+10 | 0.59 | 1567.98 | 14-MAR-04:01 | 1.08 |
April | 0.145417E+10 | 0.59 | 1567.98 | 21-APR-02:61 | 1.08 |
May | 0.142911E+10 | 0.58 | 1567.98 | 05-MAY-04:01 | 1.08 |
June | 0.157762E+10 | 0.65 | 1567.98 | 01-JUN-02:11 | 1.08 |
July | 0.164327E+10 | 0.65 | 1567.98 | 01-JUL-02:61 | 1.08 |
August | 0.159783E+10 | 0.64 | 1567.98 | 01-AUG-02:11 | 1.08 |
September | 0.144636E+10 | 0.62 | 1567.98 | 01-SEP-02:11 | 1.08 |
October | 0.149581E+10 | 0.60 | 1567.98 | 06-OCT-04:01 | 1.08 |
November | 0.150233E+10 | 0.60 | 1567.98 | 07-NOV-05:01 | 1.08 |
December | 0.167867E+10 | 0.62 | 1204.81 | 22-DEC-05:03 | 0.96 |
Annual Sum or Average | 0.184644E+11 | 0.61 | |||
Minimum of Months | 0.142911E+10 | 0.58 | 1118.44 | 0.93 | |
Maximum of Months | 0.167867E+10 | 0.65 | 1567.98 | 1.08 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.93 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 51.50 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 51.28 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.33 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 50.77 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 52.13 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:02 | 0.00 | 0.00 | 52.99 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 52.94 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 53.02 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 51.33 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:05 | 0.00 | 0.00 | 52.45 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.93 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.93 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 53.02 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 37.60 | 37.60 | 5483.23 | 20523.21 | 31-JAN-13:46 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 51.08 | 51.08 | 5547.98 | 20577.87 | 14-FEB-13:45 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 51.37 | 51.37 | 5483.14 | 20496.16 | 01-MAR-13:57 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.64 | 51.64 | 5262.70 | 19904.91 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 38.72 | 38.72 | 4992.17 | 18933.93 | 01-MAY-12:40 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 51.99 | 51.99 | 4719.11 | 17791.60 | 01-JUN-13:00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 53.05 | 53.05 | 4503.75 | 16849.19 | 01-JUL-12:35 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.89 | 52.89 | 4449.62 | 16327.70 | 31-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.91 | 52.91 | 4517.86 | 16894.96 | 30-SEP-12:47 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 40.99 | 40.99 | 4728.18 | 17888.76 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 52.38 | 52.38 | 5011.59 | 18995.58 | 30-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 52.28 | 52.28 | 5276.51 | 19977.12 | 31-DEC-13:25 |
Annual Sum or Average | 0.00 | 4994.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 37.60 | 37.60 | 4449.62 | 16327.70 | ||
Maximum of Months | 0.00 | 0.00 | 53.05 | 53.05 | 5547.98 | 20577.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.248106E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.234457E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.245273E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.226962E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.273788E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.576871E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.610860E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.577312E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.443604E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.249162E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.235825E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.261918E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.418414E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.226962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.610860E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164212E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149616E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168831E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.159750E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.259455E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.664710E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.721808E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.651099E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.467831E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.188002E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.160529E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.172899E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.392874E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149616E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.721808E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.246513E+10 | 53809127.97 | 0.188687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234028E+10 | 14180113.23 | 0.204660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235389E+10 | 0.344232E+09 | 0.141601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220602E+10 | 0.213920E+09 | 0.112288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202234E+10 | 0.256529E+10 | 0.175268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194712E+10 | 0.143216E+11 | 15622510.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201215E+10 | 0.154431E+11 | 6180333.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201541E+10 | 0.142050E+11 | 2740974.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194957E+10 | 0.929791E+10 | 0.566113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221389E+10 | 0.990675E+09 | 0.914138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228747E+10 | 0.242959E+09 | 0.143628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258691E+10 | 0.109548E+09 | 0.232479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264002E+11 | 0.578023E+11 | 0.113819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.194712E+10 | 14180113.23 | 2740974.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.258691E+10 | 0.154431E+11 | 0.232479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161505E+10 | 92301176.36 | 0.175800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148505E+10 | 37467528.24 | 0.180850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153909E+10 | 0.526178E+09 | 0.109577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145417E+10 | 0.497674E+09 | 0.761219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142911E+10 | 0.432507E+10 | 0.451991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157762E+10 | 0.197318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164327E+10 | 0.218344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159783E+10 | 0.192578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144636E+10 | 0.125830E+11 | 0.233589E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149581E+10 | 0.139969E+10 | 0.677292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150233E+10 | 0.361112E+09 | 0.117692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167867E+10 | 0.173684E+09 | 0.227987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184644E+11 | 0.808201E+11 | 0.962613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142911E+10 | 37467528.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167867E+10 | 0.218344E+11 | 0.227987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.246513E+10 | 0.00 | 0.00 | 0.00 | 15932643.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234028E+10 | 0.00 | 0.00 | 0.00 | 4282741.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235389E+10 | 0.00 | 0.00 | 0.00 | 98832612.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.220602E+10 | 0.00 | 0.00 | 0.00 | 63598544.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202234E+10 | 0.00 | 0.00 | 0.00 | 0.715533E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194712E+10 | 0.00 | 0.00 | 0.00 | 0.382159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.201215E+10 | 0.00 | 0.00 | 0.00 | 0.409645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201541E+10 | 0.00 | 0.00 | 0.00 | 0.375771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194957E+10 | 0.00 | 0.00 | 0.00 | 0.248647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221389E+10 | 0.00 | 0.00 | 0.00 | 0.277728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228747E+10 | 0.00 | 0.00 | 0.00 | 70771275.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258691E+10 | 0.00 | 0.00 | 0.00 | 32267633.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264002E+11 | 0.00 | 0.00 | 0.00 | 0.154412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.194712E+10 | 0.00 | 0.00 | 0.00 | 4282741.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.258691E+10 | 0.00 | 0.00 | 0.00 | 0.409645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161505E+10 | 0.00 | 0.00 | 0.00 | 27071929.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148505E+10 | 0.00 | 0.00 | 0.00 | 11109514.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153909E+10 | 0.00 | 0.00 | 0.00 | 0.149214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145417E+10 | 0.00 | 0.00 | 0.00 | 0.143325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142911E+10 | 0.00 | 0.00 | 0.00 | 0.116544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157762E+10 | 0.00 | 0.00 | 0.00 | 0.506948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164327E+10 | 0.00 | 0.00 | 0.00 | 0.557480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159783E+10 | 0.00 | 0.00 | 0.00 | 0.491316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144636E+10 | 0.00 | 0.00 | 0.00 | 0.323195E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149581E+10 | 0.00 | 0.00 | 0.00 | 0.384212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150233E+10 | 0.00 | 0.00 | 0.00 | 0.102954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167867E+10 | 0.00 | 0.00 | 0.00 | 50320811.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184644E+11 | 0.00 | 0.00 | 0.00 | 0.208230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142911E+10 | 0.00 | 0.00 | 0.00 | 11109514.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167867E+10 | 0.00 | 0.00 | 0.00 | 0.557480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.662553E+10 | 0.00 | 0.00 | 1496047.55 | 0.00 | 0.149813E+11 | 0.674705E+09 | 0.00 | 3.71 |
February | 0.539203E+10 | 0.00 | 0.00 | 936809.04 | 0.00 | 0.169054E+11 | 0.410664E+09 | 0.00 | 3.67 |
March | 0.600493E+10 | 0.00 | 0.00 | 6239396.86 | 0.00 | 0.118082E+11 | 0.173532E+10 | 0.00 | 3.95 |
April | 0.608411E+10 | 0.00 | 0.00 | 5527900.52 | 0.00 | 0.930451E+10 | 0.183643E+10 | 0.00 | 3.97 |
May | 0.646743E+10 | 10637232.60 | 0.00 | 18737104.45 | 0.00 | 0.627822E+09 | 0.422563E+10 | 0.00 | 4.61 |
June | 0.100036E+10 | 0.907279E+09 | 0.00 | 35961577.70 | 0.00 | 510016.56 | 0.420495E+10 | 717.84 | 4.98 |
July | 0.740737E+09 | 0.104208E+10 | 0.00 | 33607825.06 | 0.00 | 907719.43 | 0.416419E+10 | 0.00 | 5.04 |
August | 0.895493E+09 | 0.696777E+09 | 0.00 | 40199510.18 | 0.00 | 1161613.07 | 0.509625E+10 | 0.00 | 5.17 |
September | 0.230371E+10 | 0.191692E+09 | 0.00 | 42223870.26 | 0.00 | 0.340299E+09 | 0.577383E+10 | 0.00 | 5.26 |
October | 0.765196E+10 | 0.00 | 0.00 | 12683554.07 | 0.00 | 0.647556E+10 | 0.315680E+10 | 0.00 | 4.17 |
November | 0.746710E+10 | 0.00 | 0.00 | 3703681.00 | 0.00 | 0.112436E+11 | 0.114150E+10 | 0.00 | 3.81 |
December | 0.610469E+10 | 0.00 | 0.00 | 1911078.52 | 0.00 | 0.180727E+11 | 0.772384E+09 | 0.00 | 3.73 |
Annual Sum or Average | 0.567381E+11 | 0.284846E+10 | 0.00 | 0.203228E+09 | 0.00 | 0.897620E+11 | 0.331927E+11 | 717.84 | 4.34 |
Minimum of Months | 0.740737E+09 | 0.00 | 0.00 | 936809.04 | 0.00 | 510016.56 | 0.410664E+09 | 0.00 | 3.67 |
Maximum of Months | 0.765196E+10 | 0.104208E+10 | 0.00 | 42223870.26 | 0.00 | 0.180727E+11 | 0.577383E+10 | 717.84 | 5.26 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.495268E+11 | 0.00 | 0.00 | 2938940.81 | 1218424.28 | 14807808.24 | 0.218347E+10 | 0.00 | 8.68 |
February | 0.473800E+11 | 0.00 | 0.00 | 1895934.10 | 7446201.38 | 15200810.58 | 0.140744E+10 | 0.00 | 8.70 |
March | 0.385309E+11 | 0.00 | 0.00 | 12888470.59 | 5532932.34 | 12536552.32 | 0.613958E+10 | 0.00 | 8.56 |
April | 0.344044E+11 | 0.00 | 0.00 | 14380868.73 | 0.00 | 5146175.32 | 0.635517E+10 | 0.00 | 8.49 |
May | 0.146608E+11 | 0.00 | 0.00 | 49241391.97 | 0.00 | 0.00 | 0.167553E+11 | 0.00 | 8.44 |
June | 0.201179E+10 | 0.106599E+10 | 0.00 | 99149259.18 | 0.00 | 0.00 | 0.145356E+11 | 0.00 | 8.98 |
July | 0.145335E+10 | 0.106102E+10 | 0.00 | 0.100625E+09 | 0.00 | 0.00 | 0.137748E+11 | 0.00 | 9.03 |
August | 0.163848E+10 | 0.769854E+09 | 0.00 | 0.113397E+09 | 0.00 | 0.00 | 0.166582E+11 | 0.00 | 8.97 |
September | 0.529512E+10 | 49129578.68 | 0.00 | 89919636.80 | 0.00 | 0.00 | 0.184469E+11 | 0.00 | 8.69 |
October | 0.310964E+11 | 0.00 | 0.00 | 24637151.89 | 4689007.97 | 2782033.59 | 0.105744E+11 | 0.00 | 8.48 |
November | 0.415886E+11 | 0.00 | 0.00 | 7173813.67 | 0.00 | 8358668.52 | 0.418375E+10 | 0.00 | 8.56 |
December | 0.540768E+11 | 0.00 | 0.00 | 3556725.27 | 6478694.17 | 13444982.87 | 0.253448E+10 | 0.00 | 8.72 |
Annual Sum or Average | 0.321664E+12 | 0.294599E+10 | 0.00 | 0.519804E+09 | 25365260.14 | 72277031.44 | 0.113549E+12 | 0.00 | 8.69 |
Minimum of Months | 0.145335E+10 | 0.00 | 0.00 | 1895934.10 | 0.00 | 0.00 | 0.140744E+10 | 0.00 | 8.44 |
Maximum of Months | 0.540768E+11 | 0.106599E+10 | 0.00 | 0.113397E+09 | 7446201.38 | 15200810.58 | 0.184469E+11 | 0.00 | 9.03 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.279216E+11 | 0.138786E+11 | 0.103614E+12 | 0.200671E+09 | 0.283304E+11 |
February | 0.365659E+11 | 0.136126E+11 | 0.967601E+11 | 0.110230E+09 | 0.273809E+11 |
March | 0.480675E+11 | 0.124173E+11 | 0.910454E+11 | 0.611674E+09 | 0.286273E+11 |
April | 0.517629E+11 | 0.112616E+11 | 0.844175E+11 | 0.646630E+09 | 0.268458E+11 |
May | 0.637350E+11 | 0.746006E+10 | 0.659000E+11 | 0.161721E+10 | 0.363265E+11 |
June | 0.698454E+11 | 0.267405E+10 | 0.347403E+11 | 0.158965E+10 | 0.726768E+11 |
July | 0.647094E+11 | 0.230118E+10 | 0.318470E+11 | 0.159028E+10 | 0.766008E+11 |
August | 0.634189E+11 | 0.295398E+10 | 0.380858E+11 | 0.192352E+10 | 0.732543E+11 |
September | 0.463465E+11 | 0.442446E+10 | 0.506280E+11 | 0.226272E+10 | 0.548725E+11 |
October | 0.366407E+11 | 0.107195E+11 | 0.871466E+11 | 0.112639E+10 | 0.291967E+11 |
November | 0.303794E+11 | 0.123983E+11 | 0.939132E+11 | 0.389432E+09 | 0.261125E+11 |
December | 0.214635E+11 | 0.156989E+11 | 0.112311E+12 | 0.274894E+09 | 0.302553E+11 |
Annual Sum or Average | 0.560857E+12 | 0.109801E+12 | 0.890408E+12 | 0.123433E+11 | 0.510480E+12 |
Minimum of Months | 0.214635E+11 | 0.230118E+10 | 0.318470E+11 | 0.110230E+09 | 0.261125E+11 |
Maximum of Months | 0.698454E+11 | 0.156989E+11 | 0.112311E+12 | 0.226272E+10 | 0.766008E+11 |