Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:26:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1681.35 | 7236.49 | 7236.49 |
Net Site Energy | 1681.35 | 7236.49 | 7236.49 |
Total Source Energy | 2757.27 | 11867.26 | 11867.26 |
Net Source Energy | 2757.27 | 11867.26 | 11867.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 524.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 55.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 231.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 50.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 448.72 | 1232.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 524.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 55.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 231.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 14.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 28.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 524.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 36.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 24.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 55.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 231.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 50.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 396.04 | 3251.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1363.38 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1931.30 | 5305.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 396.04 | 3251.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1363.38 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1931.30 | 5305.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 448.724 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 448.724 | 100.00 |
Total On-Site and Utility Electric Sources | 448.724 | 100.00 |
Total Electricity End Uses | 448.724 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.17 |
Time Setpoint Not Met During Occupied Cooling | 17.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4334.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.1446 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9598 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.1446 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9598 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.5522 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-11:20 | 02-FEB-20:40 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 140393.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16473.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 13174.05 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3320.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16596.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2648.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 36682.12 | 175376.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 140393.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 16473.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 1065.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 12146.55 | 18386.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 3320.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 16596.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1378.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 568.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 117.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 76.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 841.99 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 250.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 161.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1421.11 | 1336.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2444.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 504.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 331.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 213.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 750.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1079.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 693.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6116.43 | 5750.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 2444.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 504.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 331.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 213.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 750.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1079.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 693.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6116.43 | 5750.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.71 |
KITCHEN DIRECT AIR | 1.26 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.00 | 1.00 | 1.71 |
PSZ-AC_2:2 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.26 | 1.00 | 1.00 | 1.26 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.71 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.26 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.71 | 1825.06 |
PSZ-AC_2:2_ADDAQ FAN | 1.26 | 1393.72 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.13 | 42353.90 | 60066.40 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.26 | 1.26 | 1.26 | 0.830824 | 31259.61 | 90140.13 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.71 | 0.852796 | 1.14 | 42353.90 | 21176.95 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.26 | 0.629412 | 0.839213 | 31259.61 | 15629.81 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 60066.40 |
PSZ-AC_2:2 HEATING COIL | 90140.13 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.145 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.932 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.960 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.039 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 829.995 | 7.145 | 9.481 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 829.995 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1157.049 | 9.960 | 184.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1157.049 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.1220 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.4391 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2403 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 8.098 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.043 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.085 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.25903459E-16 | 0.19239208E-15 | 0.93419673E-14 | -0.39937941E-16 |
24 | 3 | -0.10578823E-07 | 0.88928291E-07 | -0.59588315E-04 | 0.16456517E-12 |
25 | 2 | 0.61888179E-04 | 0.18849407E-02 | 1.1838695 | -0.78434093E-04 |
26 | 1 | -0.42954685E-01 | 0.47924477E-01 | -17.374032 | 0.34435663 |
27 | 0 | 0.12288071 | 0.30178399E-01 | 16.270210 | |
28 | 4 | 0.93419673E-14 | 0.19239208E-15 | 0.25903459E-16 | -0.39937941E-16 |
29 | 3 | -0.59588315E-04 | 0.88928291E-07 | -0.10578823E-07 | 0.16456517E-12 |
30 | 2 | 1.1838695 | 0.18849407E-02 | 0.61888179E-04 | -0.78434093E-04 |
31 | 1 | -17.374032 | 0.47924477E-01 | -0.42954685E-01 | 0.34435663 |
32 | 0 | 16.270210 | 0.30178399E-01 | 0.12288071 | |
33 | 7 | -0.38584905E-12 | 0.75146531E-15 | -0.12966877E-12 | 0.12247089E-15 |
34 | 6 | 0.32626755E-07 | 0.12794687E-09 | 0.74410738E-08 | -0.15657130E-12 |
35 | 5 | -0.20999199E-03 | 0.10694986E-05 | -0.10771460E-03 | 0.73422529E-08 |
36 | 4 | 0.31512205 | 0.50965885E-03 | 0.10796022 | -0.36842960E-04 |
37 | 3 | -7.7206601 | 0.15495837E-01 | -2.4737779 | 0.31237450E-01 |
38 | 2 | 42.368774 | 0.54174396E-01 | 15.816616 | -0.35002435 |
39 | 1 | -81.692611 | 0.24088120E-01 | -29.635684 | 1.1030598 |
40 | 0 | 46.824332 | 0.47759164E-03 | 16.279740 | |
41 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
42 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
43 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
44 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
45 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
46 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
47 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
48 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 | |
49 | 7 | -0.17492660E-08 | -0.39206577E-15 | 0.56910466E-14 | -0.74880728E-16 |
50 | 6 | 0.67235958E-05 | 0.46061729E-08 | 0.31866593E-02 | -0.26732369E-04 |
51 | 5 | -0.48404724E-03 | 0.27298576E-05 | -0.22354209 | 0.19545396E-02 |
52 | 4 | 0.11137682E-01 | 0.12426572E-03 | 4.8265062 | -0.45235764E-01 |
53 | 3 | -0.97815318E-01 | 0.98833577E-03 | -38.004246 | 0.39846397 |
54 | 2 | 0.34733640 | 0.16441863E-02 | 116.45053 | -1.4174923 |
55 | 1 | -0.50133706 | 0.50116224E-03 | -143.88764 | 2.0487166 |
56 | 0 | 0.24442836 | 0.12066061E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_SOUTH_0.4 | 38 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.36_SHGC_NORTH_0.4 | 39 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.36_SHGC_EAST_0.4 | 40 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | 41 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.7609E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.0856E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.5449E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.8639E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.2937E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.2450E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.7272E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.7316E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.5053E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 8.3245E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.9061E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.6815E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 5.1659E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 5.0982E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 1.8733E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 1.8734E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.8751E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.4967E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.6030E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.2070E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9759E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.0614E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.7318E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.7272E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 18433.08345 | 22119.70014 | 1.42133 | 1.70559 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 8016.14806 | 9619.37767 | 0.35804 | 0.42965 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -26.20000 | 3.61342E-004 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 16350.91108 | 19621.09329 | 1.04902 | 1.25882 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 30.24600 | 1.53633E-002 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 1629.83466 | 1955.80159 | 6.47812E-002 | 1.14133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -26.20000 | 3.61342E-004 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 25300.70 | 1.70559 | 1.70559 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 32086.29 | 0.42965 | 0.42965 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 24777.78 | 1.25882 | 1.25882 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 87202.24 | 1.14133 | 1.14133 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70559 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.25882 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70559 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70559 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70559 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70559 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.70559 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.70559 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.25882 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.25882 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.25882 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.25882 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.25882 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.25882 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.70559 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.25882 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.70559 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.70559 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1825.06345 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.70559 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.70559 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.70559 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.12569 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.70559 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85280 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.13706 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 42353.90000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21176.95000 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 42353.90000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60066.39638 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 60066.39638 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.25882 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.25882 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1393.71865 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.25882 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.25882 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.25882 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.83082 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.25882 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62941 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.83921 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31259.61000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15629.80500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31259.61000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 90140.12783 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 90140.12783 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 41141.6 | 11.66 | 11.61 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 30364.9 | 11.84 | 11.78 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.439 | 0.412 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.240 | 0.227 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.122 | 0.119 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.122 | 0.118 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1168337533 | 0.4756051324 | Pass | Pass | 0.1254418987 | 0.3721181293 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1377264262 | 0.6514723951 | Pass | Pass | 3.4006367918E-002 | 9.6503649875E-002 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.1707592974 | 0.1909753657 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 477.19 | 153.52 | 1137.83 | 5.55 | 535.08 | 2309.17 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.412 | 0.439 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.231 | 0.240 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.118 | 0.122 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_EAST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.045 | 0.401 | 0.442 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_SOUTH_0.4 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 2.045 | 0.401 | 0.442 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.36_SHGC_WEST_0.4 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 2.045 | 0.401 | 0.442 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 2.045 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.1446 | 116.17 | 830.00 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 43.50 | 0.0000 | Y | 6.78 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9598 | 116.17 | 1157.05 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.51 |
Interior Lighting Total | 8.5522 | 232.34 | 1987.04 | 24.28 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 49.24 | 49.24 | 2.02 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.63 | 62.93 | 13.63 | |
Exterior Lighting Total | 1372.31 | 15.65 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 42353.90 | 29693.47 | 12660.43 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31259.61 | 21915.49 | 9344.12 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 41141.6 | 11.66 | 11.61 | ||||
PSZ-AC_2:2 COOLING COIL | 30364.9 | 11.84 | 11.78 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 60066.40 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 90140.13 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.71 | 1825.06 | 1070.05 | 1.00 | 1.34 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.26 | 1393.72 | 1107.16 | 1.00 | 1.35 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 18433.08 | 22119.70 | 190.41 | 1.421 | 1.706 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01138 | 31.20 | 0.01537 | 0.416 | 0.00 |
KITCHEN | 16350.91 | 19621.09 | 168.90 | 1.049 | 1.259 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.01028 | 30.25 | 0.01536 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 8016.15 | 9619.38 | 82.80 | 0.358 | 0.430 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00760 | -26.20 | 0.00036 | 0.416 | 0.00 |
KITCHEN | 1629.83 | 1955.80 | 16.84 | 0.065 | 1.141 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 18.89 | 18.89 | 0.00426 | -26.20 | 0.00036 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.71 | 1.71 | 0.43 | 0.43 | 1.7056 | 1.7056 | 1.7056 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.26 | 1.26 | 1.14 | 1.14 | 1.2588 | 1.2588 | 1.2588 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 42353.900 | 29693.472 | 1.705590 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21176.95 | 12825.69 | 1.137060 | 25.65 | 19.49 | 0.01235065 | 11.89 | 11.30 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 36.5905 | 23.87 | 0.01137807 | 58.6175 | 18433.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 60066.396 | 60066.396 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 60066.40 | 60066.40 | 1.705591 | 9.49 | 7.38 | 0.00583226 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 24.3937 | 21.11 | 0.00759740 | 46.5671 | 8016.15 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 31259.610 | 21915.487 | 1.258820 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 15629.81 | 8477.77 | 0.839213 | 29.85 | 22.46 | 0.01488889 | 11.87 | 11.29 | 0.00850000 | 30.25 | 0.01536331 | 22.87 | 136.0004 | 26.10 | 0.01028027 | 46.4530 | 16350.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 90140.128 | 90140.128 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | 90140.13 | 90140.13 | 1.258825 | -22.04 | -22.04 | 0.00082118 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 90.6666 | 18.44 | 0.00528812 | 38.3840 | 521.69 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 42353.900 | 29693.472 | 1.705590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.7992 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.705591 | 1.95896697 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 21176.95 | 12825.69 | 1.0000 | 1.30597689 | 1.137060 | 25.65 | 19.49 | 0.01235065 | 57254.3 | 11.89 | 11.30 | 0.00850000 | 33397.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21176.95 | 31.20 | 0.01536508 | 23.13 | 0.41605618 | 36.5905 | 23.86 | 0.01137807 | 23.87 | 0.01137807 | 58.6175 | 18433.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60066.396 | 60066.396 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.705591 | 1.95896697 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 60066.40 | 60066.40 | 1.0000 | 1.95896697 | 1.705591 | 9.49 | 7.38 | 0.00583226 | 24220.9 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60066.40 | -26.20 | 0.00036134 | -26.20 | 0.41605618 | 24.3937 | 21.00 | 0.00759740 | 21.11 | 0.00759740 | 46.5671 | 8016.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31259.610 | 21915.487 | 1.258820 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1032.5177 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.258825 | 1.44583032 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 15629.81 | 8477.77 | 1.0000 | 0.96388336 | 0.839213 | 29.85 | 22.46 | 0.01488889 | 68061.6 | 11.87 | 11.29 | 0.00850000 | 33369.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15629.81 | 30.25 | 0.01536331 | 22.87 | 1.14133354 | 136.0004 | 26.05 | 0.01028027 | 26.10 | 0.01028027 | 46.4530 | 16350.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90140.128 | 90140.128 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.258825 | 1.44583032 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:20:00 | Sensible | 90140.13 | 90140.13 | 1.0000 | 1.44583032 | 1.258825 | -22.04 | -22.04 | 0.00082118 | -20130.1 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90140.13 | -26.20 | 0.00036134 | -26.20 | 1.14133354 | 90.6666 | 18.33 | 0.00528812 | 18.44 | 0.00528812 | 38.3840 | 521.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.71 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.26 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3772.33 | 5787.50 | 2530.33 |
KITCHEN | 4976.67 | 6258.00 | 4203.67 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5104.83 | 7090.17 | 4334.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 102.00 | 19.83 | 0.17 | 0.33 |
KITCHEN | 0.00 | 144.83 | 0.00 | 17.50 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 102.00 | 161.00 | 0.17 | 17.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.804 | 2.794 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 9.032 | 0.044 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.085 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.173 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 12403052.53 | 0.00 | 12403052.53 | 7100432.48 | 19503485.01 | 13120747.55 | 1423.29 | 6175.18 | 1161.52 | 403.25 |
KITCHEN | 23446007.76 | 0.00 | 23446007.76 | 193741.04 | 23639748.80 | 35993094.65 | 8669.58 | 83.95 | 6.47 | 494.02 |
Total Facility | 35849060.28 | 0.00 | 35849060.28 | 7294173.53 | 43143233.81 | 49113842.20 | 8673.46 | 6175.73 | 1166.80 | 703.57 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4659 | 0.0000 | 0.4659 | 0.2713 | 0.7372 | 0.4161 | 0.00 | 6046.98 | 1140.02 |
KITCHEN | 0.8768 | 0.0000 | 0.8768 | 0.0043 | 0.8812 | 1.1413 | 7101.48 | 83.59 | 1.93 |
Total Facility | 1.3428 | 0.0000 | 1.3428 | 0.2756 | 1.6183 | 1.5574 | 7101.48 | 6047.20 | 1141.70 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16362453.40 | 0.00 | 16362453.40 | 13120747.55 | 1418.76 | 0.25 | 7340.99 | 403.23 |
PSZ-AC_2:2 | 30929513.48 | 0.00 | 30929513.48 | 35993094.65 | 5448.12 | 573.09 | 2738.79 | 494.02 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6146 | 0.0000 | 0.6146 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1567 | 0.0000 | 1.1567 | 1.1413 | 3938.36 | 565.20 | 2683.44 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 1084.58 | 334.88 | 6170.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 152.57 | 1034.65 | 6493.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.0395 | 0.7702 | 0.5490 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 1.1711 | 1.1853 | 1.1541 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
Electricity:Building | 298.09 | 2110.08 | 01-JAN-01:20 | 18433.35 | 02-JAN-11:10 |
Electricity:Zone:DINING | 77.11 | 295.02 | 01-JAN-01:20 | 4205.23 | 02-JAN-16:40 |
Electricity:SpaceType:GENERAL | 290.15 | 1973.80 | 01-JAN-01:20 | 15139.30 | 02-JAN-11:10 |
InteriorLights:Electricity | 24.28 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:DINING | 6.78 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-16:40 |
InteriorLights:Electricity:SpaceType:GENERAL | 24.28 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 24.28 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 6.78 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 24.28 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-16:40 |
Electricity:Zone:KITCHEN | 220.98 | 1815.06 | 01-JAN-01:20 | 14339.52 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.53 | 1653.77 | 01-JAN-01:10 | 10143.54 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 50.91 | 849.95 | 03-APR-22:30 | 4370.28 | 18-APR-10:10 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 42.97 | 764.18 | 05-FEB-23:10 | 2544.51 | 04-AUG-03:30 |
LowTempRefrigeration:Refrigeration:Electricity | 14.18 | 0.00 | 01-JAN-11:10 | 1468.27 | 04-AUG-03:30 |
MedTempRefrigeration:Refrigeration:Electricity | 28.79 | 683.18 | 01-MAR-01:10 | 1076.23 | 10-APR-13:10 |
ElectricityPurchased:Facility | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
ElectricityPurchased:Plant | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
Cogeneration:ElectricityPurchased | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
General:Cogeneration:ElectricityPurchased | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
ElectricityNet:Plant | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
Cogeneration:ElectricityNet | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
General:Cogeneration:ElectricityNet | 448.72 | 3715.99 | 09-DEC-01:20 | 36682.12 | 04-AUG-11:20 |
Electricity:HVAC | 92.02 | 0.00 | 01-JAN-01:10 | 20615.17 | 04-AUG-13:00 |
Fans:Electricity | 55.03 | 0.00 | 01-JAN-01:10 | 3410.91 | 04-AUG-13:00 |
General:Fans:Electricity | 55.03 | 0.00 | 01-JAN-01:10 | 3410.91 | 04-AUG-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 36.98 | 0.00 | 01-JAN-00:10 | 17204.26 | 04-AUG-13:00 |
General:Cooling:Electricity | 36.98 | 0.00 | 01-JAN-00:10 | 17204.26 | 04-AUG-13:00 |
ExteriorLights:Electricity | 15.65 | 0.00 | 01-JAN-08:00 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.65 | 0.00 | 01-JAN-08:00 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:00 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1232.62 | 2558.65 | 19-JAN-01:20 | 175376.84 | 02-FEB-20:40 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 524.06 | 0.00 | 01-JAN-01:10 | 145381.85 | 02-FEB-07:10 |
Heating:NaturalGas | 524.06 | 0.00 | 01-JAN-01:10 | 145381.85 | 02-FEB-07:10 |
General:Heating:NaturalGas | 524.06 | 0.00 | 01-JAN-01:10 | 145381.85 | 02-FEB-07:10 |
NaturalGas:Plant | 231.41 | 720.00 | 01-JAN-03:10 | 28546.61 | 18-FEB-14:00 |
WaterSystems:NaturalGas | 231.41 | 720.00 | 01-JAN-03:10 | 28546.61 | 18-FEB-14:00 |
Water Heater:WaterSystems:NaturalGas | 231.41 | 720.00 | 01-JAN-03:10 | 28546.61 | 18-FEB-14:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 12-APR-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1254.18 | 2414.82 | 02-FEB-01:10 | 167530.66 | 02-FEB-21:00 |
EnergyTransfer:Building | 457.36 | 1207.41 | 02-FEB-01:10 | 45689.75 | 02-FEB-12:10 |
EnergyTransfer:Zone:KITCHEN | 326.35 | 1207.41 | 02-FEB-01:10 | 22107.11 | 23-MAY-04:10 |
Refrigeration:EnergyTransfer | 136.25 | 2414.81 | 02-FEB-01:00 | 7834.84 | 12-MAY-03:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.13 | 1207.41 | 02-FEB-01:00 | 3917.42 | 12-MAY-03:30 |
General:Refrigeration:EnergyTransfer | 68.13 | 1207.41 | 02-FEB-01:00 | 3917.42 | 12-MAY-03:30 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 68.13 | 1207.41 | 02-FEB-01:00 | 3917.42 | 12-MAY-03:30 |
EnergyTransfer:Plant | 227.85 | 1207.41 | 02-FEB-01:00 | 24168.53 | 19-MAR-13:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.99 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 55.14 | 1059.55 | 01-MAR-01:10 | 2238.70 | 10-APR-13:10 |
EnergyTransfer:Zone:DINING | 131.01 | 0.00 | 01-JAN-01:10 | 34151.96 | 01-FEB-04:10 |
Heating:EnergyTransfer | 69.16 | 0.00 | 01-JAN-00:10 | 33195.92 | 02-FEB-21:00 |
Heating:EnergyTransfer:Zone:DINING | 69.14 | 0.00 | 01-JAN-00:10 | 33195.92 | 02-FEB-21:00 |
General:Heating:EnergyTransfer | 69.16 | 0.00 | 01-JAN-00:10 | 33195.92 | 02-FEB-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 69.14 | 0.00 | 01-JAN-00:10 | 33195.92 | 02-FEB-21:00 |
Cooling:EnergyTransfer | 320.07 | 0.00 | 01-JAN-01:10 | 27734.37 | 07-SEP-11:10 |
Cooling:EnergyTransfer:Zone:DINING | 61.87 | 0.00 | 01-JAN-01:10 | 15969.88 | 01-FEB-04:10 |
General:Cooling:EnergyTransfer | 320.07 | 0.00 | 01-JAN-01:10 | 27734.37 | 07-SEP-11:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 61.87 | 0.00 | 01-JAN-01:10 | 15969.88 | 01-FEB-04:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 2065.36 | 04-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.02 | 0.00 | 01-JAN-00:10 | 2065.36 | 04-FEB-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 258.20 | 0.00 | 01-JAN-01:10 | 18224.07 | 23-MAY-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 258.20 | 0.00 | 01-JAN-01:10 | 18224.07 | 23-MAY-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 159.72 | 0.00 | 01-JAN-00:10 | 22010.43 | 20-FEB-13:10 |
PlantLoopHeatingDemand:Plant | 159.72 | 0.00 | 01-JAN-00:10 | 22010.43 | 20-FEB-13:10 |
WaterSystems:PlantLoopHeatingDemand | 159.72 | 0.00 | 01-JAN-00:10 | 22010.43 | 20-FEB-13:10 |
General:WaterSystems:PlantLoopHeatingDemand | 159.72 | 0.00 | 01-JAN-00:10 | 22010.43 | 20-FEB-13:10 |
EnergyTransfer:HVAC | 568.97 | 0.00 | 01-JAN-01:10 | 116305.48 | 02-FEB-07:10 |
HeatingCoils:EnergyTransfer | 419.25 | 0.00 | 01-JAN-01:10 | 116305.48 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 149.72 | 0.00 | 01-JAN-00:10 | 73156.38 | 04-AUG-12:00 |
WaterSystems:EnergyTransfer | 159.72 | 0.00 | 01-JAN-00:10 | 22010.43 | 20-FEB-13:10 |
WaterUse:WaterSystems:EnergyTransfer | 159.72 | 0.00 | 01-JAN-00:10 | 22010.43 | 20-FEB-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 69.138 | -61.873 | 0.000 | 0.000 | 72.369 | 6.778 | 52.748 | 24.831 | 0.000 | 2.381 | 0.001 | 0.000 | -15.791 | 0.000 | -128.538 | -22.045 |
KITCHEN | 0.000 | 0.000 | 0.024 | -258.193 | 0.000 | 0.000 | 5.131 | 17.506 | 201.243 | 0.000 | 0.000 | 0.014 | 38.478 | 0.000 | 0.000 | 0.000 | -4.203 | -0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.203 | 9.622 | 0.000 | 0.000 | 0.000 | -12.825 | -0.000 |
Total Facility | 0.000 | 0.000 | 69.161 | -320.066 | 0.000 | 0.000 | 77.500 | 24.284 | 253.992 | 24.831 | 0.000 | 5.599 | 48.100 | 0.000 | -15.791 | 0.000 | -145.566 | -22.045 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 02-FEB-04:47 | 0.00 | 0.00 | 0.00 | -43907.65 | 0.00 | 0.00 | 0.00 | 25.01 | 506.27 | 0.00 | 0.00 | 0.00 | 46885.90 | 0.00 | -2535.68 | 0.00 | -973.85 | 0.00 |
KITCHEN | 03-FEB-05:01 | 0.00 | 0.00 | 0.00 | -52096.77 | 0.00 | 0.00 | 21.27 | 25.01 | 4931.35 | 0.00 | 0.00 | 0.00 | 47236.83 | 0.00 | -0.00 | 0.00 | -117.69 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-FEB-00:01 | 0.00 | 0.00 | 0.00 | -69267.23 | 0.00 | 0.00 | 388.29 | 263.92 | 2308.40 | 0.00 | 0.00 | 63.69 | 69280.22 | 0.00 | -2447.83 | 0.00 | -589.47 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 03-APR-02:61 | 0.00 | 0.00 | 42889.97 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1108.13 | 0.00 | -879.58 | -41129.77 |
KITCHEN | 04-FEB-05:02 | 0.00 | 0.00 | 18568.54 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 4924.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -105.57 | -23412.79 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-APR-02:61 | 0.00 | 0.00 | 42889.97 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 1879.56 | 0.00 | 0.00 | 100.46 | 0.00 | 0.00 | -1108.13 | 0.00 | -1820.35 | -41991.52 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7056 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.7056 | 0.2439 | 1.0000 | Not calculated | 0.4161 | 0.2439 | ||
PSZ-AC_2:2 | 1.2588 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2588 | 0.1202 | 1.0000 | Not calculated | 0.1513 | 0.1202 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.7056 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.7056 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2439 | ||
PSZ-AC_2:2 | 1.2588 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.2588 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1202 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7056 | 1.7056 | 1.7056 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2588 | 1.2588 | 1.2588 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7056 | 1.7056 | 1.7056 | 1.7056 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2588 | 1.2588 | 1.2588 | 1.2588 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7056 | 1.7056 | 1.7056 | No | 0.4161 | 0.9684 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2588 | 1.2588 | 1.2588 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.7056 | 1.7056 | 1.7056 | 1.7056 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.2588 | 1.2588 | 1.2588 | 1.2588 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.17 |
Number of hours cooling loads not met | 17.83 |
Number of hours not met | 18.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 524.06 | 145381.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 36.98 | 17204.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 24.28 | 1583.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.65 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 55.03 | 3410.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 231.41 | 28546.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 14.18 | 1468.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 28.79 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 316.77 | 448.72 |
Natural Gas | 477.16 | 1232.62 |
Additional | 0.00 | 0.00 |
Total | 793.93 | 1681.35 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 104.52 |
Space Heating | 0.00 |
Space Cooling | 159.18 |
Fans (All) | 236.86 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1144.28 |
Miscellaneous (All) | 1931.30 |
Subtotal | 1931.30 |
Natural Gas [MJ/m2] | |
Space Heating | 2255.53 |
Service Water Heating | 995.98 |
Miscellaneous (All) | 5305.19 |
Subtotal | 5305.19 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.44 |
Space Heating | 31.17 |
Space Cooling | 2.20 |
Fans (All) | 3.27 |
Service Water Heating | 13.76 |
Receptacle Equipment | 44.19 |
Miscellaneous | 3.96 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8330.17 | 418.17 | 11.67 | 0.00 | 0.00 |
ATTIC | 7260.83 | 420.67 | 413.33 | 505.50 | 159.67 |
Min | 7260.83 | 12.33 | 0.00 | 0.00 | 0.00 |
Max | 8747.67 | 420.67 | 413.33 | 505.50 | 159.67 |
Average | 8112.89 | 283.72 | 141.67 | 168.50 | 53.22 |
Sum | 24338.67 | 851.17 | 425.00 | 505.50 | 159.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254721.00 | 4.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16176.17 | 81.83 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254721.00 | 81.83 | 0.00 | 0.00 | 0.00 |
Average | 90299.06 | 28.61 | 0.00 | 0.00 | 0.00 |
Sum | 270897.17 | 85.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 7977.17 | 782.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 6393.83 | 2365.00 | 1.17 | 0.00 | 0.00 |
ATTIC | 7199.17 | 726.67 | 278.17 | 220.33 | 335.67 |
Min | 6393.83 | 726.67 | 0.00 | 0.00 | 0.00 |
Max | 7977.17 | 2365.00 | 278.17 | 220.33 | 335.67 |
Average | 7190.06 | 1291.50 | 93.11 | 73.44 | 111.89 |
Sum | 21570.17 | 3874.50 | 279.33 | 220.33 | 335.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 232671.17 | 22053.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 11473.83 | 4784.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 232671.17 | 22053.83 | 0.00 | 0.00 | 0.00 |
Average | 81381.67 | 8946.00 | 0.00 | 0.00 | 0.00 |
Sum | 244145.00 | 26838.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.950671E+09 | 35572.57 | 31-JAN-04:01 | -31.0 | -31.2 | 0.444696E+10 | 3722.96 | 07-JAN-19:10 | -31.0 | -31.2 |
February | 0.849591E+09 | 43908.49 | 02-FEB-04:47 | -35.9 | -36.0 | 0.402521E+10 | 3722.94 | 04-FEB-19:10 | -20.0 | -20.6 |
March | 0.131752E+10 | 16659.09 | 08-MAR-05:02 | -14.7 | -15.0 | 0.451826E+10 | 4080.04 | 25-MAR-18:10 | 14.82 | 10.05 |
April | 0.307599E+10 | 17974.74 | 16-APR-02:61 | 19.90 | 16.73 | 0.449568E+10 | 4681.48 | 15-APR-18:10 | 19.90 | 16.73 |
May | 0.635538E+10 | 11721.16 | 31-MAY-12:00 | 29.40 | 19.85 | 0.496205E+10 | 4681.28 | 27-MAY-18:30 | 29.40 | 19.85 |
June | 0.102097E+11 | 23440.90 | 30-JUN-02:61 | 22.70 | 19.31 | 0.509287E+10 | 4681.48 | 10-JUN-18:49 | 22.70 | 19.31 |
July | 0.120295E+11 | 22861.48 | 26-JUL-02:61 | 23.80 | 19.72 | 0.537647E+10 | 4681.64 | 01-JUL-18:10 | 23.80 | 19.72 |
August | 0.119483E+11 | 24336.71 | 30-AUG-02:61 | 12.98 | 11.99 | 0.541285E+10 | 4681.01 | 19-AUG-18:10 | 12.98 | 11.99 |
September | 0.895331E+10 | 23295.67 | 02-SEP-02:61 | 10.92 | 9.49 | 0.487821E+10 | 4681.01 | 02-SEP-18:00 | 20.00 | 16.38 |
October | 0.363053E+10 | 8967.64 | 18-OCT-23:01 | -0.8 | -2.1 | 0.456708E+10 | 4413.38 | 20-OCT-11:00 | 21.10 | 12.25 |
November | 0.178756E+10 | 25239.21 | 26-NOV-03:28 | -25.0 | -25.3 | 0.431929E+10 | 4110.10 | 03-NOV-11:00 | -25.0 | -25.3 |
December | 0.765565E+09 | 21447.06 | 09-DEC-04:35 | -22.8 | -23.0 | 0.444519E+10 | 3722.94 | 09-DEC-19:10 | -20.0 | -20.4 |
Annual Sum or Average | 0.618736E+11 | 0.565401E+11 | ||||||||
Minimum of Months | 0.765565E+09 | 8967.64 | -35.9 | -36.0 | 0.402521E+10 | 3722.94 | -31.0 | -31.2 | ||
Maximum of Months | 0.120295E+11 | 43908.49 | 29.40 | 19.85 | 0.541285E+10 | 4681.64 | 29.40 | 19.85 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195114E+11 | 49203.45 | 31-JAN-05:01 | -30.6 | -30.8 | 0.768046E+10 | 5037.31 | 13-JAN-11:00 | -30.6 | -30.8 |
February | 0.180454E+11 | 52123.75 | 03-FEB-05:01 | -33.9 | -34.0 | 0.693785E+10 | 5049.24 | 24-FEB-11:00 | 6.10 | 3.16 |
March | 0.207362E+11 | 35115.88 | 08-MAR-05:01 | -14.7 | -15.0 | 0.769704E+10 | 5089.24 | 28-MAR-10:00 | 12.80 | 7.63 |
April | 0.204080E+11 | 42610.47 | 11-APR-04:01 | 11.70 | 8.68 | 0.748149E+10 | 5135.94 | 17-APR-10:00 | 15.60 | 11.49 |
May | 0.215982E+11 | 46813.04 | 23-MAY-04:01 | 6.02 | 5.72 | 0.781276E+10 | 5135.98 | 16-MAY-10:00 | 6.02 | 5.72 |
June | 0.221632E+11 | 44469.85 | 02-JUN-04:01 | 7.70 | 6.83 | 0.759051E+10 | 5140.83 | 30-JUN-10:00 | 28.30 | 23.10 |
July | 0.234415E+11 | 40189.36 | 24-JUL-02:11 | 10.73 | 10.12 | 0.785594E+10 | 5142.08 | 03-JUL-10:00 | 10.73 | 10.12 |
August | 0.237513E+11 | 43261.95 | 07-AUG-02:61 | 9.32 | 8.14 | 0.785940E+10 | 5173.14 | 04-AUG-10:00 | 9.32 | 8.14 |
September | 0.230435E+11 | 47492.68 | 15-SEP-02:61 | 6.78 | 5.64 | 0.756282E+10 | 5135.99 | 12-SEP-10:00 | 6.78 | 5.64 |
October | 0.233071E+11 | 45240.31 | 03-OCT-04:01 | 7.35 | 6.70 | 0.773181E+10 | 5135.94 | 20-OCT-10:00 | 18.10 | 11.43 |
November | 0.214478E+11 | 43151.75 | 26-NOV-05:01 | -25.2 | -25.5 | 0.745405E+10 | 5128.20 | 08-NOV-11:50 | -25.2 | -25.5 |
December | 0.207462E+11 | 40585.99 | 11-DEC-05:01 | -22.2 | -22.6 | 0.768045E+10 | 5036.86 | 05-DEC-11:00 | -22.2 | -22.6 |
Annual Sum or Average | 0.258200E+12 | 0.913446E+11 | ||||||||
Minimum of Months | 0.180454E+11 | 35115.88 | -33.9 | -34.0 | 0.693785E+10 | 5036.86 | -30.6 | -30.8 | ||
Maximum of Months | 0.237513E+11 | 52123.75 | 11.70 | 10.12 | 0.785940E+10 | 5173.14 | 28.30 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 | -24.4 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 | -12.0 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -12.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 | -2.2 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 | 5.15 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 | 10.69 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 | 15.94 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.94 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 | 17.82 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 | 15.67 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 | 1.39 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 | -0.5 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202460E+11 | 40562.23 | 07-JAN-04:31 | -25.2 |
February | 0.137268E+11 | 39951.14 | 03-FEB-04:41 | -33.9 |
March | 0.769738E+10 | 40987.11 | 01-MAR-03:01 | -5.8 |
April | 0.341460E+10 | 42891.93 | 03-APR-02:61 | -6.1 |
May | 0.154816E+09 | 9581.35 | 02-MAY-02:62 | 2.80 |
June | 15766869.56 | 5179.77 | 05-JUN-07:04 | 9.50 |
July | 519224.65 | 917.81 | 25-JUL-23:01 | 25.00 |
August | 157776.13 | 579.38 | 02-AUG-23:01 | 24.40 |
September | 0.223811E+09 | 5125.76 | 30-SEP-06:10 | 0.60 |
October | 0.140234E+10 | 8839.78 | 31-OCT-16:53 | 3.50 |
November | 0.751999E+10 | 40594.73 | 26-NOV-04:31 | -25.0 |
December | 0.147353E+11 | 39523.25 | 10-DEC-03:18 | -21.3 |
Annual Sum or Average | 0.691374E+11 | |||
Minimum of Months | 157776.13 | 579.38 | -33.9 | |
Maximum of Months | 0.202460E+11 | 42891.93 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6159146.12 | 12105.99 | 03-JAN-05:03 | -20.7 |
February | 6898798.76 | 18588.22 | 04-FEB-05:02 | -30.6 |
March | 2853695.39 | 9453.48 | 05-MAR-05:03 | -8.0 |
April | 730014.05 | 8305.26 | 03-APR-04:03 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 1930079.85 | 11820.30 | 28-NOV-05:03 | -21.1 |
December | 5186235.49 | 10631.96 | 10-DEC-05:02 | -22.3 |
Annual Sum or Average | 23757969.66 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 6898798.76 | 18588.22 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:01 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.704255E+09 | 681.55 | 02-JAN-16:40 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.589812E+09 | 681.55 | 01-FEB-17:19 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.578177E+09 | 681.55 | 01-MAR-17:30 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.509120E+09 | 681.55 | 01-APR-17:00 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.468965E+09 | 681.55 | 01-MAY-18:49 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.446421E+09 | 681.55 | 01-JUN-18:00 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.455749E+09 | 681.55 | 01-JUL-19:30 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.490937E+09 | 681.55 | 01-AUG-19:30 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.528104E+09 | 681.55 | 01-SEP-18:40 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.604655E+09 | 681.55 | 02-OCT-17:40 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.671300E+09 | 681.55 | 01-NOV-16:30 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.730386E+09 | 681.55 | 01-DEC-16:30 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.677788E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.446421E+09 | 681.55 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.730386E+09 | 681.55 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147870E+10 | 901.93 | 02-JAN-10:09 | 0.166069E+11 | 10143.54 | 01-JAN-11:09 |
February | 0.133950E+10 | 901.93 | 01-FEB-10:09 | 0.149998E+11 | 10143.54 | 01-FEB-11:09 |
March | 0.150425E+10 | 901.93 | 01-MAR-10:09 | 0.166070E+11 | 10143.54 | 01-MAR-11:09 |
April | 0.143688E+10 | 901.93 | 01-APR-16:10 | 0.160712E+11 | 10143.54 | 01-APR-10:09 |
May | 0.149147E+10 | 901.93 | 01-MAY-09:09 | 0.166070E+11 | 10143.54 | 01-MAY-10:09 |
June | 0.145377E+10 | 901.93 | 01-JUN-09:09 | 0.160713E+11 | 10143.54 | 01-JUN-10:09 |
July | 0.147476E+10 | 901.93 | 01-JUL-16:10 | 0.166069E+11 | 10143.54 | 01-JUL-10:09 |
August | 0.150425E+10 | 901.93 | 01-AUG-09:09 | 0.166070E+11 | 10143.54 | 01-AUG-10:09 |
September | 0.143724E+10 | 901.93 | 01-SEP-09:09 | 0.160712E+11 | 10143.54 | 01-SEP-10:09 |
October | 0.147852E+10 | 901.93 | 02-OCT-09:09 | 0.166069E+11 | 10143.54 | 01-OCT-10:09 |
November | 0.143180E+10 | 901.93 | 01-NOV-09:09 | 0.160712E+11 | 10143.54 | 01-NOV-10:09 |
December | 0.147494E+10 | 901.93 | 01-DEC-10:09 | 0.166069E+11 | 10143.54 | 01-DEC-11:09 |
Annual Sum or Average | 0.175061E+11 | 0.195533E+12 | ||||
Minimum of Months | 0.133950E+10 | 901.93 | 0.149998E+11 | 10143.54 | ||
Maximum of Months | 0.150425E+10 | 901.93 | 0.166070E+11 | 10143.54 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.704255E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253695E+11 |
February | 0.852256E+10 | 0.589812E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192232E+11 |
March | 0.954557E+10 | 0.578177E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146218E+11 |
April | 0.915225E+10 | 0.509120E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101913E+09 | 0.949164E+10 |
May | 0.947560E+10 | 0.468965E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106225E+09 | 0.483074E+10 |
June | 0.922788E+10 | 0.446421E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703412E+09 | 0.243722E+10 |
July | 0.939996E+10 | 0.455749E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537443E+09 | 0.147047E+10 |
August | 0.954557E+10 | 0.490937E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551020E+09 | 0.193214E+10 |
September | 0.915225E+10 | 0.528104E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381482E+09 | 0.435825E+10 |
October | 0.940563E+10 | 0.604655E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915946E+10 |
November | 0.909363E+10 | 0.671300E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145513E+11 |
December | 0.939996E+10 | 0.730386E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210920E+11 |
Annual Sum or Average | 0.111326E+12 | 0.677788E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238150E+10 | 0.128538E+12 |
Minimum of Months | 0.852256E+10 | 0.446421E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147047E+10 |
Maximum of Months | 0.954557E+10 | 0.730386E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703412E+09 | 0.253695E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147870E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725564E+09 |
February | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550910E+09 |
March | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486472E+09 |
April | 0.655836E+09 | 0.143688E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 1353687.30 | 0.312200E+09 |
May | 0.679007E+09 | 0.149147E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 485054.72 | 0.196862E+09 |
June | 0.661256E+09 | 0.145377E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 5728013.37 | 0.124976E+09 |
July | 0.673587E+09 | 0.147476E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 1765607.56 | 94081549.12 |
August | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 2401670.36 | 0.124675E+09 |
September | 0.655836E+09 | 0.143724E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 2150875.69 | 0.175164E+09 |
October | 0.673993E+09 | 0.147852E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294145E+09 |
November | 0.651635E+09 | 0.143180E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485497E+09 |
December | 0.673587E+09 | 0.147494E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632583E+09 |
Annual Sum or Average | 0.797748E+10 | 0.175061E+11 | 0.146594E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 13884908.99 | 0.420313E+10 |
Minimum of Months | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94081549.12 |
Maximum of Months | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 5728013.37 | 0.725564E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293535E+09 | 0.608410E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290409E+09 | 0.730229E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248250E+09 | 0.105849E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215436E+09 | 0.131321E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194063E+09 | 0.158942E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205005E+09 | 0.164273E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261396E+09 | 0.172019E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218944E+09 | 0.146522E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325982E+09 | 0.105487E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337777E+09 | 0.787750E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291660E+09 | 0.495523E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320927E+09 | 0.358904E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320338E+10 | 0.128249E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194063E+09 | 0.358904E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337777E+09 | 0.172019E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 681.55 | 02-JAN-16:40 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 32972.66 | 30-JAN-21:00 |
February | 9454.80 | 04-FEB-19:10 | 681.55 | 01-FEB-17:19 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 37181.40 | 02-FEB-21:00 |
March | 9454.80 | 04-MAR-19:10 | 681.55 | 01-MAR-17:30 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 20565.31 | 05-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 681.55 | 01-APR-17:00 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2810.25 | 15-APR-17:03 | 15728.67 | 03-APR-20:00 |
May | 9454.80 | 06-MAY-18:10 | 681.55 | 01-MAY-18:49 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.19 | 31-MAY-12:00 | 10328.30 | 01-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 681.55 | 01-JUN-18:00 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3817.95 | 26-JUN-17:03 | 7628.51 | 01-JUN-17:52 |
July | 9454.80 | 01-JUL-18:10 | 681.55 | 01-JUL-19:30 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2982.65 | 26-JUL-17:55 | 4425.28 | 10-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 681.55 | 01-AUG-19:30 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3866.24 | 04-AUG-11:53 | 4799.13 | 06-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 681.55 | 01-SEP-18:40 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3722.43 | 07-SEP-13:00 | 10622.64 | 29-SEP-20:00 |
October | 9454.80 | 07-OCT-18:10 | 681.55 | 02-OCT-17:40 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 13229.49 | 31-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 681.55 | 01-NOV-16:30 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 31543.74 | 25-NOV-20:00 |
December | 9454.80 | 02-DEC-19:10 | 681.55 | 01-DEC-16:30 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 29972.83 | 09-DEC-19:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4425.28 | |||||
Maximum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3866.24 | 37181.40 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.93 | 02-JAN-10:09 | 7408.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2061.82 | 29-JAN-05:00 |
February | 677.52 | 04-FEB-19:10 | 901.93 | 01-FEB-10:09 | 7408.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1458.75 | 28-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 901.93 | 01-MAR-10:09 | 7408.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 1359.44 | 21-MAR-03:10 |
April | 677.52 | 01-APR-18:10 | 901.93 | 01-APR-16:10 | 7408.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 42.81 | 15-APR-15:00 | 980.77 | 03-APR-00:20 |
May | 677.52 | 06-MAY-18:10 | 901.93 | 01-MAY-09:09 | 7408.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 19.22 | 31-MAY-13:00 | 759.90 | 02-MAY-03:08 |
June | 677.52 | 03-JUN-18:10 | 901.93 | 01-JUN-09:09 | 7408.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 57.26 | 11-JUN-14:53 | 565.94 | 02-JUN-04:00 |
July | 677.52 | 01-JUL-18:10 | 901.93 | 01-JUL-16:10 | 7408.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 28.52 | 25-JUL-15:53 | 354.35 | 25-JUL-02:10 |
August | 677.52 | 05-AUG-18:10 | 901.93 | 01-AUG-09:09 | 7408.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 25.11 | 03-AUG-16:00 | 389.94 | 19-AUG-02:00 |
September | 677.52 | 02-SEP-18:10 | 901.93 | 01-SEP-09:09 | 7408.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 30.12 | 06-SEP-14:00 | 491.22 | 26-SEP-03:20 |
October | 677.52 | 07-OCT-18:10 | 901.93 | 02-OCT-09:09 | 7408.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 812.95 | 24-OCT-03:40 |
November | 677.52 | 04-NOV-18:10 | 901.93 | 01-NOV-09:09 | 7408.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1560.21 | 21-NOV-04:10 |
December | 677.52 | 02-DEC-19:10 | 901.93 | 01-DEC-10:09 | 7408.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 2718.11 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 354.35 | ||||||
Maximum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 57.26 | 2718.11 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.89 | 25-JAN-04:52 | 1885.40 | 31-JAN-13:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.61 | 28-FEB-24:00 | 1993.34 | 02-FEB-14:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 499.19 | 01-MAR-00:13 | 2293.04 | 05-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.33 | 05-APR-23:10 | 2609.96 | 05-APR-12:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.14 | 03-MAY-02:00 | 2618.52 | 21-MAY-13:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.26 | 07-JUN-23:00 | 2666.64 | 09-JUN-13:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.59 | 23-JUL-23:00 | 2470.66 | 05-JUL-13:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.35 | 05-AUG-05:00 | 2213.86 | 16-AUG-12:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.75 | 08-SEP-03:51 | 2106.23 | 07-SEP-13:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 520.15 | 20-OCT-07:03 | 1845.19 | 23-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.99 | 01-NOV-00:01 | 1489.26 | 25-NOV-12:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 415.55 | 04-DEC-07:55 | 1150.10 | 15-DEC-13:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 405.26 | 1150.10 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.75 | 2666.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 35572.57 | 31-JAN-04:01 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.90 |
February | 43908.49 | 02-FEB-04:47 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.85 |
March | 16659.09 | 08-MAR-05:02 | 5252.67 | 250.09 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.25 |
April | 17974.74 | 16-APR-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 |
May | 11721.16 | 31-MAY-12:00 | 8404.27 | 163.57 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.19 | 0.00 |
June | 23440.90 | 30-JUN-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.38 |
July | 22861.48 | 26-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.96 |
August | 24336.71 | 30-AUG-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.52 |
September | 23295.67 | 02-SEP-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.50 |
October | 8967.64 | 18-OCT-23:01 | 4727.40 | 1022.34 | 3659.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.86 |
November | 25239.21 | 26-NOV-03:28 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 988.03 |
December | 21447.06 | 09-DEC-04:35 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1976.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8967.64 | 0.00 | 163.57 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43908.49 | 8404.27 | 1022.34 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2974.19 | 1976.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 49203.45 | 31-JAN-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 208.12 |
February | 52123.75 | 03-FEB-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 117.69 |
March | 35115.88 | 08-MAR-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 81.41 |
April | 42610.47 | 11-APR-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 114.45 |
May | 46813.04 | 23-MAY-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 52.68 |
June | 44469.85 | 02-JUN-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 130.47 |
July | 40189.36 | 24-JUL-02:11 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 180.46 |
August | 43261.95 | 07-AUG-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 283.04 |
September | 47492.68 | 15-SEP-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 196.65 |
October | 45240.31 | 03-OCT-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 69.89 |
November | 43151.75 | 26-NOV-05:01 | 0.00 | 250.09 | 36578.48 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 207.44 |
December | 40585.99 | 11-DEC-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 170.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 35115.88 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 52.68 | |
Maximum of Months | 52123.75 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 283.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.41 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.88 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.85 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.48 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.68 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.62 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.47 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.21 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.45 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.94 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.99 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.99 | 7.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.360714E+11 | 22190.13 | 30-JAN-11:09 | 0.203106E+12 | 156484.66 | 30-JAN-13:09 |
February | 0.320797E+11 | 22382.64 | 02-FEB-11:09 | 0.155232E+12 | 175376.84 | 02-FEB-20:40 |
March | 0.348208E+11 | 21553.30 | 01-MAR-11:09 | 0.122863E+12 | 107779.34 | 05-MAR-20:30 |
April | 0.343425E+11 | 29979.11 | 18-APR-10:00 | 0.885757E+11 | 90017.59 | 03-APR-10:20 |
May | 0.364075E+11 | 29578.35 | 31-MAY-10:20 | 0.641639E+11 | 59161.25 | 02-MAY-10:09 |
June | 0.416155E+11 | 33551.78 | 30-JUN-11:09 | 0.583038E+11 | 53254.19 | 05-JUN-10:20 |
July | 0.456747E+11 | 33564.46 | 26-JUL-17:00 | 0.582668E+11 | 49496.91 | 01-JUL-12:39 |
August | 0.448861E+11 | 36682.12 | 04-AUG-11:20 | 0.579544E+11 | 49016.07 | 01-AUG-12:50 |
September | 0.380097E+11 | 31016.92 | 11-SEP-10:00 | 0.602380E+11 | 53311.59 | 27-SEP-10:39 |
October | 0.348142E+11 | 21288.04 | 26-OCT-10:09 | 0.771642E+11 | 62129.18 | 26-OCT-10:20 |
November | 0.341796E+11 | 21709.20 | 24-NOV-11:09 | 0.118019E+12 | 141218.07 | 26-NOV-07:10 |
December | 0.358225E+11 | 21985.32 | 11-DEC-11:09 | 0.168738E+12 | 138285.54 | 09-DEC-11:09 |
Annual Sum or Average | 0.448724E+12 | 0.123262E+13 | ||||
Minimum of Months | 0.320797E+11 | 21288.04 | 0.579544E+11 | 49016.07 | ||
Maximum of Months | 0.456747E+11 | 36682.12 | 0.203106E+12 | 175376.84 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.218295E+10 | 0.176768E+10 | 0.225803E+11 | 0.00 | 0.560365E+10 | 0.79 | 0.00 | 104000.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192931E+10 | 0.143728E+10 | 0.203951E+11 | 0.00 | 0.474202E+10 | 0.72 | 0.00 | 119293.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208243E+10 | 0.137081E+10 | 0.225804E+11 | 0.00 | 0.473651E+10 | 0.80 | 0.00 | 2789430.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.194600E+10 | 0.110066E+10 | 0.218518E+11 | 0.00 | 0.427501E+10 | 0.77 | 0.00 | 0.109438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196044E+10 | 0.962129E+09 | 0.225803E+11 | 0.00 | 0.417708E+10 | 0.80 | 0.00 | 0.216532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190019E+10 | 0.853777E+09 | 0.218520E+11 | 0.00 | 0.426119E+10 | 0.77 | 0.00 | 0.818007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.193051E+10 | 0.906316E+09 | 0.225802E+11 | 0.00 | 0.449004E+10 | 0.79 | 0.00 | 0.109747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.199519E+10 | 0.105051E+10 | 0.225804E+11 | 0.00 | 0.446329E+10 | 0.80 | 0.00 | 0.100121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196534E+10 | 0.122582E+10 | 0.218518E+11 | 0.00 | 0.412465E+10 | 0.77 | 0.00 | 0.441240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208317E+10 | 0.150008E+10 | 0.225803E+11 | 0.00 | 0.428898E+10 | 0.79 | 0.00 | 0.133072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210310E+10 | 0.165316E+10 | 0.218519E+11 | 0.00 | 0.461049E+10 | 0.77 | 0.00 | 8467441.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220532E+10 | 0.182285E+10 | 0.225802E+11 | 0.00 | 0.526006E+10 | 0.79 | 0.00 | 369569.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242840E+11 | 0.156511E+11 | 0.265865E+12 | 0.00 | 0.550330E+11 | 9.37 | 0.00 | 0.369839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.190019E+10 | 0.853777E+09 | 0.203951E+11 | 0.00 | 0.412465E+10 | 0.72 | 0.00 | 104000.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220532E+10 | 0.182285E+10 | 0.225804E+11 | 0.00 | 0.560365E+10 | 0.80 | 0.00 | 0.109747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.141011E+12 | 0.00 | 0.215692E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.988034E+11 | 0.00 | 0.198245E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.605585E+11 | 0.00 | 0.217783E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.290609E+11 | 0.00 | 0.202963E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.379832E+10 | 0.00 | 0.198399E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.101045E+10 | 0.00 | 0.180749E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 18898763.50 | 0.00 | 0.177222E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 65351841.44 | 0.00 | 0.173633E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.402147E+10 | 0.00 | 0.169980E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.182413E+11 | 0.00 | 0.183972E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.599059E+11 | 0.00 | 0.188941E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.107561E+12 | 0.00 | 0.206513E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.524057E+12 | 0.00 | 0.231409E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 18898763.50 | 0.00 | 0.169980E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.141011E+12 | 0.00 | 0.217783E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1583.48 | 02-JAN-16:40 | 1372.31 | 01-JAN-06:10 | 14073.79 | 01-JAN-11:09 | 0.00 | 3143.92 | 30-JAN-20:00 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1583.48 | 01-FEB-17:19 | 1372.31 | 01-FEB-06:10 | 14073.79 | 01-FEB-11:09 | 0.00 | 3352.92 | 02-FEB-20:00 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1583.48 | 01-MAR-17:30 | 1372.31 | 01-MAR-06:10 | 14073.79 | 01-MAR-11:09 | 0.00 | 2637.14 | 05-MAR-20:00 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1583.48 | 01-APR-17:00 | 1372.31 | 01-APR-05:10 | 14073.79 | 01-APR-10:09 | 0.00 | 2374.07 | 03-APR-06:10 | 0.00 | 12-APR-11:00 | 0.00 | 01-APR-00:10 |
May | 1583.48 | 01-MAY-18:49 | 1372.31 | 01-MAY-19:10 | 14073.79 | 01-MAY-10:09 | 0.00 | 2171.48 | 31-MAY-11:09 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1583.48 | 01-JUN-18:00 | 1372.31 | 01-JUN-19:40 | 14073.79 | 01-JUN-10:09 | 0.00 | 2844.19 | 30-JUN-11:09 | 0.00 | 01-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 1583.48 | 01-JUL-19:30 | 1372.31 | 01-JUL-19:00 | 14073.79 | 01-JUL-10:09 | 0.00 | 3205.69 | 26-JUL-17:00 | 0.00 | 04-JUL-13:20 | 0.00 | 01-JUL-00:10 |
August | 1583.48 | 01-AUG-19:30 | 1372.31 | 01-AUG-19:40 | 14073.79 | 01-AUG-10:09 | 0.00 | 3410.91 | 04-AUG-12:00 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1583.48 | 01-SEP-18:40 | 1372.31 | 01-SEP-05:10 | 14073.79 | 01-SEP-10:09 | 0.00 | 2368.73 | 11-SEP-11:09 | 0.00 | 12-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 1583.48 | 02-OCT-17:40 | 1372.31 | 01-OCT-05:10 | 14073.79 | 01-OCT-10:09 | 0.00 | 2204.03 | 23-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1583.48 | 01-NOV-16:30 | 1372.31 | 01-NOV-05:10 | 14073.79 | 01-NOV-10:09 | 0.00 | 3062.03 | 26-NOV-07:10 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1583.48 | 01-DEC-16:30 | 1372.31 | 01-DEC-06:10 | 14073.79 | 01-DEC-11:09 | 0.00 | 2961.47 | 08-DEC-20:00 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 2171.48 | 0.00 | 0.00 | ||||||
Maximum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 3410.91 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 173.33 | 13-JAN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 135.65 | 21-FEB-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 884.90 | 24-MAR-03:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10675.84 | 18-APR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10297.01 | 31-MAY-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14135.82 | 11-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15731.09 | 26-JUL-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17204.26 | 04-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11706.15 | 06-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3669.64 | 20-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1323.76 | 03-NOV-03:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 201.78 | 05-DEC-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 135.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17204.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 22190.13 | 30-JAN-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2931.31 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22382.64 | 02-FEB-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 3123.82 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21553.30 | 01-MAR-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2282.39 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29979.11 | 18-APR-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2238.22 | 0.00 | 0.00 | 10037.28 | 0.00 |
May | 29578.35 | 31-MAY-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 1885.12 | 0.00 | 0.00 | 8209.31 | 0.00 |
June | 33551.78 | 30-JUN-11:09 | 1065.50 | 13174.05 | 0.00 | 0.00 | 2844.19 | 0.00 | 0.00 | 13874.06 | 0.00 |
July | 33564.46 | 26-JUL-17:00 | 1065.50 | 11824.43 | 0.00 | 0.00 | 3205.69 | 0.00 | 0.00 | 15731.09 | 0.00 |
August | 36682.12 | 04-AUG-11:20 | 1065.50 | 13174.05 | 0.00 | 0.00 | 3320.91 | 0.00 | 0.00 | 16473.12 | 0.00 |
September | 31016.92 | 11-SEP-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2363.66 | 0.00 | 0.00 | 10952.99 | 0.00 |
October | 21288.04 | 26-OCT-10:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 1998.47 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21709.20 | 24-NOV-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2448.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21985.32 | 11-DEC-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2726.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 21288.04 | 1065.50 | 11824.43 | 0.00 | 0.00 | 1885.12 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36682.12 | 1065.50 | 14073.79 | 0.00 | 0.00 | 3320.91 | 0.00 | 0.00 | 16473.12 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 123314.21 | 31-JAN-07:10 | 0.00 | 28490.62 | 31-JAN-13:00 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 145381.85 | 02-FEB-07:10 | 0.00 | 28546.61 | 18-FEB-13:00 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 75083.00 | 04-MAR-03:30 | 0.00 | 28526.59 | 01-MAR-13:00 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 53072.68 | 03-APR-06:10 | 0.00 | 28305.61 | 01-APR-12:00 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 25040.60 | 02-MAY-06:10 | 0.00 | 27846.71 | 01-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 11474.11 | 03-JUN-06:10 | 0.00 | 27176.04 | 01-JUN-12:50 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 1988.61 | 23-JUL-05:10 | 0.00 | 26513.76 | 01-JUL-12:39 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 4717.08 | 07-AUG-06:10 | 0.00 | 26032.92 | 01-AUG-12:50 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 30112.30 | 30-SEP-06:10 | 0.00 | 26307.52 | 29-SEP-12:20 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 36357.14 | 23-OCT-06:10 | 0.00 | 26958.01 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 119298.41 | 26-NOV-07:10 | 0.00 | 27631.92 | 30-NOV-13:00 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 104337.66 | 08-DEC-20:00 | 0.00 | 28180.74 | 31-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 1988.61 | 0.00 | 26032.92 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 145381.85 | 0.00 | 28546.61 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 19.00 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 | 0.00 | 19.71 |
March | 12.83 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 | 0.00 | 19.92 |
April | 6.67 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 | 0.00 | 20.30 |
May | 0.33 | 20.48 | 0.00 | 20.48 | 0.17 | 21.81 | 0.00 | 21.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.54 | 0.00 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.61 | 0.17 | 24.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.64 | 0.17 | 24.63 |
September | 0.33 | 20.53 | 0.00 | 20.53 | 5.00 | 24.39 | 0.00 | 24.39 |
October | 0.67 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
November | 11.33 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 | 0.00 | 19.61 |
December | 24.33 | 19.51 | 0.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Annual Sum or Average | 102.00 | 19.62 | 0.17 | 19.62 | 19.83 | 20.44 | 0.33 | 20.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 | 0.00 | 19.31 |
Maximum of Months | 26.50 | 20.53 | 0.17 | 20.53 | 6.67 | 24.64 | 0.17 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.73 | 0.00 | 26.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.18 | 0.00 | 27.18 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.13 | 0.00 | 28.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 28.37 | 0.00 | 28.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 29.65 | 0.00 | 29.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 | 29.52 | 6.67 | 29.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 29.31 | 10.83 | 28.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 29.38 | 0.00 | 29.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.68 | 0.00 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.58 | 0.00 | 27.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 144.83 | 29.12 | 17.50 | 28.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 29.65 | 10.83 | 29.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.84 | 467.00 | 20.80 | 467.00 | 20.79 |
February | 551.00 | 20.84 | 314.00 | 20.77 | 314.00 | 20.74 |
March | 607.83 | 20.93 | 224.00 | 20.81 | 223.33 | 20.74 |
April | 528.00 | 21.12 | 178.00 | 21.23 | 126.67 | 21.13 |
May | 436.33 | 21.71 | 213.33 | 22.28 | 81.67 | 22.34 |
June | 326.17 | 22.66 | 415.33 | 23.34 | 162.67 | 23.43 |
July | 355.33 | 23.69 | 562.17 | 23.80 | 321.17 | 23.82 |
August | 331.17 | 23.45 | 526.17 | 23.70 | 263.33 | 23.74 |
September | 286.67 | 21.37 | 295.17 | 22.55 | 24.00 | 22.52 |
October | 559.83 | 21.04 | 69.83 | 21.04 | 39.17 | 20.91 |
November | 586.17 | 20.93 | 156.50 | 20.81 | 156.50 | 20.73 |
December | 609.00 | 20.84 | 350.83 | 20.77 | 350.83 | 20.73 |
Annual Sum or Average | 5787.50 | 21.42 | 3772.33 | 21.79 | 2530.33 | 21.76 |
Minimum of Months | 286.67 | 20.84 | 69.83 | 20.77 | 24.00 | 20.73 |
Maximum of Months | 610.00 | 23.69 | 562.17 | 23.80 | 467.00 | 23.82 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.73 | 511.50 | 18.71 | 511.50 | 18.71 |
February | 551.00 | 18.74 | 375.00 | 18.70 | 375.00 | 18.69 |
March | 575.33 | 18.99 | 310.33 | 19.03 | 283.50 | 18.93 |
April | 499.83 | 20.11 | 284.33 | 20.69 | 212.83 | 20.73 |
May | 406.00 | 23.81 | 448.17 | 24.42 | 267.67 | 24.70 |
June | 469.17 | 25.56 | 539.83 | 25.58 | 425.33 | 25.73 |
July | 565.50 | 26.10 | 606.00 | 26.03 | 565.50 | 26.05 |
August | 534.00 | 26.06 | 604.33 | 25.94 | 530.50 | 25.99 |
September | 442.67 | 24.23 | 433.67 | 24.76 | 319.83 | 25.03 |
October | 488.67 | 20.04 | 194.83 | 20.68 | 106.17 | 20.69 |
November | 506.83 | 19.02 | 267.67 | 19.29 | 204.83 | 19.14 |
December | 609.00 | 18.73 | 401.00 | 18.69 | 401.00 | 18.68 |
Annual Sum or Average | 6258.00 | 21.51 | 4976.67 | 22.05 | 4203.67 | 22.17 |
Minimum of Months | 406.00 | 18.73 | 194.83 | 18.69 | 106.17 | 18.68 |
Maximum of Months | 610.00 | 26.10 | 606.00 | 26.03 | 565.50 | 26.05 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.83893 | 14.60408 | -0.6667 | 15.32317 |
February | 551.00000 | 20.84339 | 19.22463 | -0.6020 | 13.74771 |
March | 612.00000 | 20.95057 | 25.73997 | -0.4949 | 11.61790 |
April | 590.00000 | 21.40308 | 34.55026 | -0.2855 | 10.07965 |
May | 611.00000 | 22.29777 | 49.92716 | -0.9260 | 27.24243 |
June | 592.00000 | 23.18725 | 57.17984 | -0.4973 | 14.53156 |
July | 609.00000 | 23.74242 | 62.32408 | -0.2353 | 7.16944 |
August | 612.00000 | 23.60205 | 60.38187 | -0.2854 | 8.40625 |
September | 590.00000 | 22.62341 | 44.31770 | -0.7451 | 22.48185 |
October | 610.00000 | 21.26085 | 34.27554 | -0.2438 | 7.96930 |
November | 591.00000 | 20.95276 | 27.93608 | -0.4421 | 10.51644 |
December | 609.00000 | 20.83947 | 17.44593 | -0.6114 | 13.86006 |
Annual Sum or Average | 7187.00000 | 21.88558 | 37.44179 | -0.5023 | 13.56887 |
Minimum of Months | 551.00000 | 20.83893 | 14.60408 | -0.9260 | 7.16944 |
Maximum of Months | 612.00000 | 23.74242 | 62.32408 | -0.2353 | 27.24243 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72642 | 21.96490 | -0.7584 | 17.79224 |
February | 551.00000 | 18.73675 | 27.41365 | -0.7183 | 16.65986 |
March | 612.00000 | 19.29548 | 33.92529 | -0.5328 | 14.13542 |
April | 590.00000 | 20.67915 | 40.88344 | -0.1546 | 15.29404 |
May | 611.00000 | 23.82993 | 49.16885 | -0.1260 | 17.97675 |
June | 592.00000 | 25.16350 | 53.91143 | 0.40790 | 16.14660 |
July | 609.00000 | 25.94450 | 56.20491 | 0.71234 | 17.19289 |
August | 612.00000 | 25.77655 | 54.69806 | 0.65595 | 16.74965 |
September | 590.00000 | 24.06711 | 44.90636 | 0.00939 | 19.42673 |
October | 610.00000 | 20.75745 | 40.36911 | -0.0855 | 11.58679 |
November | 591.00000 | 19.64061 | 34.68690 | -0.4076 | 13.32201 |
December | 609.00000 | 18.73157 | 25.18050 | -0.7093 | 16.26092 |
Annual Sum or Average | 7187.00000 | 21.79848 | 40.35113 | -0.1385 | 16.03965 |
Minimum of Months | 551.00000 | 18.72642 | 21.96490 | -0.7584 | 11.58679 |
Maximum of Months | 612.00000 | 25.94450 | 56.20491 | 0.71234 | 19.42673 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.185026E+10 | 0.483925E+09 | 53.79 | 0.120115E+10 | 0.649113E+09 | 0.00 | 1.00 | 16-APR-02:61 | 0.00 | 01-APR-00:01 | 42008.43 | 16-APR-02:61 | 24103.28 | 16-APR-02:61 | 17905.15 | 16-APR-02:61 | 10211.93 | 16-APR-02:61 | 0.00 | 01-APR-00:01 |
May | 0.292442E+10 | 0.793271E+09 | 112.82 | 0.192783E+10 | 0.996581E+09 | 0.00 | 1.00 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 | 21463.65 | 31-MAY-12:00 | 15108.24 | 31-MAY-12:00 | 7128.36 | 30-MAY-18:00 | 5158.18 | 31-MAY-12:00 | 0.00 | 01-MAY-00:01 |
June | 0.135770E+11 | 0.346882E+10 | 325.51 | 0.832831E+10 | 0.524870E+10 | 0.00 | 1.00 | 10-JUN-02:62 | 0.00 | 01-JUN-00:01 | 45651.34 | 26-JUN-02:61 | 26894.12 | 24-JUN-02:61 | 25430.09 | 26-JUN-02:61 | 10460.98 | 26-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.179727E+11 | 0.457239E+10 | 426.97 | 0.101572E+11 | 0.781547E+10 | 0.00 | 1.00 | 01-JUL-02:62 | 0.00 | 01-JUL-00:01 | 46352.67 | 04-JUL-02:61 | 24808.49 | 25-JUL-02:62 | 28724.48 | 04-JUL-02:61 | 10512.15 | 04-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.162614E+11 | 0.415695E+10 | 387.33 | 0.938714E+10 | 0.687423E+10 | 0.00 | 1.00 | 01-AUG-02:62 | 0.00 | 01-AUG-00:01 | 46424.91 | 03-AUG-02:61 | 25277.83 | 19-AUG-02:61 | 30495.24 | 04-AUG-02:02 | 10517.57 | 03-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.723274E+10 | 0.192884E+10 | 211.49 | 0.537520E+10 | 0.185754E+10 | 0.00 | 1.00 | 02-SEP-02:61 | 0.00 | 01-SEP-00:01 | 43478.56 | 12-SEP-02:41 | 30813.80 | 18-SEP-02:61 | 24057.39 | 12-SEP-02:41 | 10311.73 | 12-SEP-02:41 | 0.00 | 01-SEP-00:01 |
October | 0.105929E+09 | 31569632.84 | 10.33 | 91747921.72 | 14181550.49 | 0.00 | 0.34 | 20-OCT-15:10 | 0.00 | 01-OCT-00:01 | 6025.76 | 20-OCT-15:10 | 5420.73 | 20-OCT-14:55 | 663.55 | 20-OCT-13:00 | 1757.91 | 20-OCT-15:10 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.599244E+11 | 0.154358E+11 | 1528.24 | 0.364686E+11 | 0.234558E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.179727E+11 | 0.457239E+10 | 426.97 | 0.101572E+11 | 0.781547E+10 | 0.00 | 1.00 | 0.00 | 46424.91 | 30813.80 | 30495.24 | 10517.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 341526.32 | 104000.09 | 0.08 | 254493.27 | 87033.05 | 0.00 | 0.09 | 13-JAN-04:40 | 0.00 | 01-JAN-00:01 | 1138.42 | 13-JAN-04:40 | 848.31 | 13-JAN-04:40 | 290.11 | 13-JAN-04:40 | 346.67 | 13-JAN-04:40 | 0.00 | 01-JAN-00:01 |
February | 389251.89 | 119293.38 | 0.14 | 318536.87 | 70715.02 | 0.00 | 0.07 | 21-FEB-04:40 | 0.00 | 01-FEB-00:01 | 886.70 | 21-FEB-04:40 | 742.34 | 21-FEB-04:40 | 144.36 | 21-FEB-04:40 | 271.30 | 21-FEB-04:40 | 0.00 | 01-FEB-00:01 |
March | 10343664.96 | 2789430.52 | 1.44 | 6615578.37 | 3728086.58 | 0.00 | 1.00 | 20-MAR-02:61 | 0.00 | 01-MAR-00:01 | 15401.86 | 20-MAR-02:61 | 11408.09 | 24-MAR-03:42 | 6839.48 | 20-MAR-02:61 | 3695.46 | 20-MAR-02:61 | 0.00 | 01-MAR-00:01 |
April | 0.251929E+10 | 0.610450E+09 | 68.10 | 0.165128E+10 | 0.868006E+09 | 0.00 | 1.00 | 11-APR-02:61 | 0.00 | 01-APR-00:01 | 30839.09 | 11-APR-04:01 | 22033.68 | 18-APR-02:61 | 15037.62 | 17-APR-02:11 | 7393.64 | 11-APR-04:01 | 0.00 | 01-APR-00:01 |
May | 0.540548E+10 | 0.137205E+10 | 195.18 | 0.343091E+10 | 0.197457E+10 | 0.00 | 1.00 | 05-MAY-02:11 | 0.00 | 01-MAY-00:01 | 30839.09 | 12-MAY-02:61 | 20633.79 | 05-MAY-02:11 | 18430.53 | 12-MAY-02:61 | 7393.64 | 05-MAY-02:11 | 0.00 | 01-MAY-00:01 |
June | 0.197604E+11 | 0.471125E+10 | 386.30 | 0.119393E+11 | 0.782108E+10 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 34264.26 | 30-JUN-10:45 | 21884.66 | 25-JUN-14:10 | 20383.39 | 26-JUN-03:42 | 8061.07 | 11-JUN-14:53 | 0.00 | 01-JUN-00:01 |
July | 0.271110E+11 | 0.640233E+10 | 517.43 | 0.144930E+11 | 0.126180E+11 | 0.00 | 1.00 | 01-JUL-02:11 | 0.00 | 01-JUL-00:01 | 34264.26 | 03-JUL-13:10 | 18854.78 | 02-JUL-11:07 | 22533.63 | 26-JUL-19:00 | 7713.70 | 26-JUL-14:53 | 0.00 | 01-JUL-00:01 |
August | 0.246604E+11 | 0.585513E+10 | 477.17 | 0.134050E+11 | 0.112554E+11 | 0.00 | 1.00 | 01-AUG-02:11 | 0.00 | 01-AUG-00:01 | 34264.26 | 03-AUG-10:20 | 21235.28 | 04-AUG-14:55 | 23513.86 | 04-AUG-04:02 | 8133.55 | 04-AUG-14:55 | 0.00 | 01-AUG-00:01 |
September | 0.993672E+10 | 0.248356E+10 | 266.63 | 0.741161E+10 | 0.252511E+10 | 0.00 | 1.00 | 01-SEP-02:11 | 0.00 | 01-SEP-00:01 | 31528.16 | 12-SEP-03:18 | 22144.11 | 26-SEP-04:01 | 19424.57 | 12-SEP-03:18 | 7439.99 | 12-SEP-03:18 | 0.00 | 01-SEP-00:01 |
October | 0.358843E+09 | 0.101502E+09 | 34.54 | 0.267537E+09 | 91306382.13 | 0.00 | 1.00 | 02-OCT-02:61 | 0.00 | 01-OCT-00:01 | 30839.09 | 10-OCT-04:01 | 23787.05 | 12-OCT-02:61 | 14862.92 | 10-OCT-03:21 | 7393.64 | 03-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 32605531.55 | 8467441.21 | 2.48 | 18006994.74 | 14598536.81 | 0.00 | 1.00 | 03-NOV-02:61 | 0.00 | 01-NOV-00:01 | 30839.09 | 03-NOV-03:21 | 17855.20 | 07-NOV-05:01 | 14747.31 | 08-NOV-03:01 | 7393.64 | 03-NOV-03:21 | 0.00 | 01-NOV-00:01 |
December | 1212601.72 | 369569.55 | 0.33 | 913996.65 | 298605.06 | 0.00 | 0.11 | 05-DEC-04:40 | 0.00 | 01-DEC-00:01 | 1330.02 | 05-DEC-04:40 | 928.85 | 05-DEC-04:40 | 401.16 | 05-DEC-04:40 | 403.55 | 05-DEC-04:40 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.897970E+11 | 0.215481E+11 | 1949.82 | 0.526247E+11 | 0.371723E+11 | 0.00 | ||||||||||||||
Minimum of Months | 341526.32 | 104000.09 | 0.08 | 254493.27 | 70715.02 | 0.00 | 0.07 | 0.00 | 886.70 | 742.34 | 144.36 | 271.30 | 0.00 | |||||||
Maximum of Months | 0.271110E+11 | 0.640233E+10 | 517.43 | 0.144930E+11 | 0.126180E+11 | 0.00 | 1.00 | 0.00 | 34264.26 | 23787.05 | 23513.86 | 8133.55 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.29 | 34.27 | 49.02 | 35.88 | 293.32 | 0.00 | 0.00 | 0.00 |
February | 110.40 | 48.55 | 61.86 | 63.93 | 230.59 | 0.00 | 0.00 | 0.00 |
March | 150.00 | 59.54 | 90.46 | 119.59 | 147.52 | 0.00 | 0.00 | 0.00 |
April | 184.19 | 80.66 | 103.53 | 183.69 | 101.74 | 0.00 | 0.00 | 0.00 |
May | 231.33 | 101.08 | 130.25 | 270.15 | 58.19 | 0.00 | 0.00 | 0.00 |
June | 254.57 | 110.86 | 143.71 | 324.24 | 41.65 | 0.00 | 0.00 | 0.00 |
July | 257.30 | 118.73 | 138.58 | 333.00 | 37.88 | 0.00 | 0.00 | 0.00 |
August | 216.90 | 93.51 | 123.39 | 279.79 | 45.10 | 0.00 | 0.00 | 0.00 |
September | 193.46 | 91.42 | 102.04 | 232.24 | 74.38 | 0.00 | 0.00 | 0.00 |
October | 123.28 | 51.49 | 71.79 | 112.37 | 113.49 | 0.00 | 0.00 | 0.00 |
November | 72.74 | 23.63 | 49.11 | 38.96 | 181.19 | 0.00 | 0.00 | 0.00 |
December | 56.34 | 24.20 | 32.15 | 24.69 | 265.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.40 | 69.93 | 91.47 | 168.78 | 132.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.34 | 23.63 | 32.15 | 24.69 | 37.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 257.30 | 118.73 | 143.71 | 333.00 | 293.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.48 | 330.85 | 152.62 | 433.42 | 526.64 | 0.00 | 0.00 | 0.00 |
February | 518.04 | 349.99 | 168.05 | 486.30 | 418.97 | 0.00 | 0.00 | 0.00 |
March | 450.81 | 237.38 | 213.43 | 450.81 | 293.64 | 0.00 | 0.00 | 0.00 |
April | 406.15 | 189.88 | 216.27 | 453.73 | 211.07 | 0.00 | 0.00 | 0.00 |
May | 336.48 | 91.22 | 245.26 | 403.60 | 124.11 | 0.00 | 0.00 | 0.00 |
June | 326.67 | 66.51 | 260.16 | 428.03 | 87.63 | 0.00 | 0.00 | 0.00 |
July | 345.81 | 87.13 | 258.67 | 468.12 | 79.20 | 0.00 | 0.00 | 0.00 |
August | 389.61 | 139.72 | 249.89 | 532.56 | 94.71 | 0.00 | 0.00 | 0.00 |
September | 472.12 | 248.77 | 223.35 | 605.78 | 152.59 | 0.00 | 0.00 | 0.00 |
October | 493.00 | 309.28 | 183.71 | 558.76 | 225.53 | 0.00 | 0.00 | 0.00 |
November | 371.96 | 232.86 | 139.11 | 356.61 | 339.91 | 0.00 | 0.00 | 0.00 |
December | 396.65 | 300.45 | 96.19 | 381.64 | 487.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 415.30 | 214.57 | 200.73 | 463.12 | 252.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 326.67 | 66.51 | 96.19 | 356.61 | 79.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 518.04 | 349.99 | 260.16 | 605.78 | 526.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 82.60 | 33.42 | 49.18 | 36.99 | 299.87 | 0.00 | 0.00 | 0.00 |
February | 121.12 | 59.69 | 61.44 | 78.81 | 237.64 | 0.00 | 0.00 | 0.00 |
March | 144.60 | 53.80 | 90.80 | 112.89 | 151.69 | 0.00 | 0.00 | 0.00 |
April | 210.92 | 104.30 | 106.63 | 221.96 | 103.87 | 0.00 | 0.00 | 0.00 |
May | 211.53 | 84.50 | 127.03 | 246.44 | 60.46 | 0.00 | 0.00 | 0.00 |
June | 248.21 | 107.57 | 140.64 | 316.52 | 43.20 | 0.00 | 0.00 | 0.00 |
July | 266.50 | 126.59 | 139.91 | 347.36 | 39.23 | 0.00 | 0.00 | 0.00 |
August | 232.99 | 106.93 | 126.06 | 303.78 | 46.76 | 0.00 | 0.00 | 0.00 |
September | 188.60 | 89.52 | 99.08 | 225.63 | 76.21 | 0.00 | 0.00 | 0.00 |
October | 131.42 | 58.43 | 72.99 | 124.77 | 117.59 | 0.00 | 0.00 | 0.00 |
November | 78.67 | 29.09 | 49.58 | 49.03 | 184.75 | 0.00 | 0.00 | 0.00 |
December | 60.50 | 28.52 | 31.98 | 32.21 | 271.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 164.98 | 73.54 | 91.44 | 175.17 | 135.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.50 | 28.52 | 31.98 | 32.21 | 39.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.50 | 126.59 | 140.64 | 347.36 | 299.87 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223086E+09 | 91800452.76 | 0.131286E+09 | 96096552.56 | 0.785636E+09 |
February | 0.267083E+09 | 0.117442E+09 | 0.149642E+09 | 0.154652E+09 | 0.557846E+09 |
March | 0.401765E+09 | 0.159472E+09 | 0.242293E+09 | 0.320319E+09 | 0.395123E+09 |
April | 0.477415E+09 | 0.209075E+09 | 0.268340E+09 | 0.476133E+09 | 0.263704E+09 |
May | 0.619582E+09 | 0.270729E+09 | 0.348853E+09 | 0.723572E+09 | 0.155843E+09 |
June | 0.659839E+09 | 0.287349E+09 | 0.372490E+09 | 0.840434E+09 | 0.107958E+09 |
July | 0.689159E+09 | 0.317993E+09 | 0.371166E+09 | 0.891908E+09 | 0.101449E+09 |
August | 0.580948E+09 | 0.250459E+09 | 0.330489E+09 | 0.749376E+09 | 0.120807E+09 |
September | 0.501438E+09 | 0.236955E+09 | 0.264483E+09 | 0.601972E+09 | 0.192784E+09 |
October | 0.330203E+09 | 0.137923E+09 | 0.192280E+09 | 0.300985E+09 | 0.303981E+09 |
November | 0.188538E+09 | 61240585.29 | 0.127298E+09 | 0.100977E+09 | 0.469633E+09 |
December | 0.150911E+09 | 64804922.64 | 86106467.03 | 66131528.01 | 0.711303E+09 |
Annual Sum or Average | 0.508997E+10 | 0.220524E+10 | 0.288472E+10 | 0.532256E+10 | 0.416607E+10 |
Minimum of Months | 0.150911E+09 | 61240585.29 | 86106467.03 | 66131528.01 | 0.101449E+09 |
Maximum of Months | 0.689159E+09 | 0.317993E+09 | 0.372490E+09 | 0.891908E+09 | 0.785636E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129495E+10 | 0.886161E+09 | 0.408788E+09 | 0.116087E+10 | 0.141056E+10 |
February | 0.125324E+10 | 0.846697E+09 | 0.406541E+09 | 0.117647E+10 | 0.101358E+10 |
March | 0.120745E+10 | 0.635802E+09 | 0.571647E+09 | 0.120745E+10 | 0.786478E+09 |
April | 0.105274E+10 | 0.492176E+09 | 0.560564E+09 | 0.117608E+10 | 0.547104E+09 |
May | 0.901232E+09 | 0.244336E+09 | 0.656896E+09 | 0.108099E+10 | 0.332413E+09 |
June | 0.846735E+09 | 0.172400E+09 | 0.674336E+09 | 0.110946E+10 | 0.227128E+09 |
July | 0.926207E+09 | 0.233379E+09 | 0.692828E+09 | 0.125381E+10 | 0.212129E+09 |
August | 0.104353E+10 | 0.374233E+09 | 0.669294E+09 | 0.142641E+10 | 0.253682E+09 |
September | 0.122374E+10 | 0.644811E+09 | 0.578931E+09 | 0.157018E+10 | 0.395501E+09 |
October | 0.132044E+10 | 0.828389E+09 | 0.492049E+09 | 0.149659E+10 | 0.604050E+09 |
November | 0.964130E+09 | 0.603563E+09 | 0.360567E+09 | 0.924334E+09 | 0.881034E+09 |
December | 0.106238E+10 | 0.804736E+09 | 0.257639E+09 | 0.102217E+10 | 0.130648E+10 |
Annual Sum or Average | 0.130968E+11 | 0.676668E+10 | 0.633008E+10 | 0.146048E+11 | 0.797013E+10 |
Minimum of Months | 0.846735E+09 | 0.172400E+09 | 0.257639E+09 | 0.924334E+09 | 0.212129E+09 |
Maximum of Months | 0.132044E+10 | 0.886161E+09 | 0.692828E+09 | 0.157018E+10 | 0.141056E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.221247E+09 | 89518934.04 | 0.131728E+09 | 99086423.42 | 0.803182E+09 |
February | 0.293024E+09 | 0.144393E+09 | 0.148631E+09 | 0.190661E+09 | 0.574890E+09 |
March | 0.387289E+09 | 0.144093E+09 | 0.243197E+09 | 0.302369E+09 | 0.406299E+09 |
April | 0.546716E+09 | 0.270341E+09 | 0.276375E+09 | 0.575318E+09 | 0.269218E+09 |
May | 0.566574E+09 | 0.226333E+09 | 0.340242E+09 | 0.660072E+09 | 0.161938E+09 |
June | 0.643362E+09 | 0.278817E+09 | 0.364545E+09 | 0.820409E+09 | 0.111964E+09 |
July | 0.713801E+09 | 0.339066E+09 | 0.374735E+09 | 0.930358E+09 | 0.105082E+09 |
August | 0.624042E+09 | 0.286394E+09 | 0.337648E+09 | 0.813649E+09 | 0.125252E+09 |
September | 0.488849E+09 | 0.232033E+09 | 0.256817E+09 | 0.584826E+09 | 0.197532E+09 |
October | 0.352005E+09 | 0.156497E+09 | 0.195508E+09 | 0.334185E+09 | 0.314942E+09 |
November | 0.203902E+09 | 75402587.82 | 0.128499E+09 | 0.127089E+09 | 0.478876E+09 |
December | 0.162038E+09 | 76386940.35 | 85651040.84 | 86278391.79 | 0.725854E+09 |
Annual Sum or Average | 0.520285E+10 | 0.231927E+10 | 0.288357E+10 | 0.552430E+10 | 0.427503E+10 |
Minimum of Months | 0.162038E+09 | 75402587.82 | 85651040.84 | 86278391.79 | 0.105082E+09 |
Maximum of Months | 0.713801E+09 | 0.339066E+09 | 0.374735E+09 | 0.930358E+09 | 0.803182E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 452.71 | 1066.26 | 649.37 | 398.55 | 250.82 | 0.00 | 0.00 |
February | 581.68 | 839.84 | 749.56 | 458.22 | 291.34 | 0.00 | 0.00 |
March | 663.01 | 572.56 | 745.41 | 350.72 | 394.69 | 0.00 | 0.00 |
April | 843.63 | 400.92 | 801.26 | 374.84 | 426.42 | 0.00 | 0.00 |
May | 909.21 | 231.77 | 779.34 | 276.81 | 502.54 | 0.00 | 0.00 |
June | 1062.55 | 166.24 | 829.45 | 284.94 | 544.51 | 0.00 | 0.00 |
July | 1144.08 | 151.92 | 869.61 | 332.45 | 537.16 | 0.00 | 0.00 |
August | 1110.45 | 180.91 | 839.50 | 340.16 | 499.34 | 0.00 | 0.00 |
September | 1056.23 | 295.75 | 854.18 | 429.71 | 424.47 | 0.00 | 0.00 |
October | 786.04 | 446.74 | 747.70 | 419.21 | 328.49 | 0.00 | 0.00 |
November | 424.04 | 685.28 | 523.37 | 285.57 | 237.79 | 0.00 | 0.00 |
December | 402.85 | 988.67 | 513.49 | 353.17 | 160.32 | 0.00 | 0.00 |
Annual Sum or Average | 787.40 | 500.73 | 741.68 | 358.04 | 383.64 | 0.00 | 0.00 |
Minimum of Months | 402.85 | 151.92 | 513.49 | 276.81 | 160.32 | 0.00 | 0.00 |
Maximum of Months | 1144.08 | 1066.26 | 869.61 | 458.22 | 544.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121255E+10 | 0.285588E+10 | 0.173928E+10 | 0.106748E+10 | 0.671801E+09 | 0.00 | 0.00 |
February | 0.140720E+10 | 0.203174E+10 | 0.181335E+10 | 0.110853E+10 | 0.704813E+09 | 0.00 | 0.00 |
March | 0.177579E+10 | 0.153356E+10 | 0.199650E+10 | 0.939367E+09 | 0.105714E+10 | 0.00 | 0.00 |
April | 0.218668E+10 | 0.103918E+10 | 0.207687E+10 | 0.971592E+09 | 0.110528E+10 | 0.00 | 0.00 |
May | 0.243522E+10 | 0.620785E+09 | 0.208739E+10 | 0.741397E+09 | 0.134599E+10 | 0.00 | 0.00 |
June | 0.275413E+10 | 0.430881E+09 | 0.214994E+10 | 0.738566E+09 | 0.141137E+10 | 0.00 | 0.00 |
July | 0.306431E+10 | 0.406901E+09 | 0.232917E+10 | 0.890438E+09 | 0.143873E+10 | 0.00 | 0.00 |
August | 0.297424E+10 | 0.484551E+09 | 0.224852E+10 | 0.911086E+09 | 0.133743E+10 | 0.00 | 0.00 |
September | 0.273774E+10 | 0.766581E+09 | 0.221403E+10 | 0.111380E+10 | 0.110023E+10 | 0.00 | 0.00 |
October | 0.210534E+10 | 0.119655E+10 | 0.200265E+10 | 0.112281E+10 | 0.879837E+09 | 0.00 | 0.00 |
November | 0.109912E+10 | 0.177626E+10 | 0.135657E+10 | 0.740207E+09 | 0.616364E+09 | 0.00 | 0.00 |
December | 0.107899E+10 | 0.264804E+10 | 0.137532E+10 | 0.945928E+09 | 0.429397E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.248313E+11 | 0.157909E+11 | 0.233896E+11 | 0.112912E+11 | 0.120984E+11 | 0.00 | 0.00 |
Minimum of Months | 0.107899E+10 | 0.406901E+09 | 0.135657E+10 | 0.738566E+09 | 0.429397E+09 | 0.00 | 0.00 |
Maximum of Months | 0.306431E+10 | 0.285588E+10 | 0.232917E+10 | 0.112281E+10 | 0.143873E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.158700E+11 | -0.150673E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -802703059.8 | 58.99 | 0.00 | 0.00 |
February | 0.146102E+11 | -0.138859E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -724207485.0 | 58.99 | 0.00 | 0.00 |
March | 0.160397E+11 | -0.152505E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -789186496.0 | 58.99 | 0.00 | 0.00 |
April | 0.148892E+11 | -0.141520E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -737177323.1 | 58.99 | 0.00 | 0.00 |
May | 0.144719E+11 | -0.137705E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -701371688.7 | 58.99 | 0.00 | 0.00 |
June | 0.130946E+11 | -0.124409E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -653756792.6 | 58.98 | 0.00 | 0.00 |
July | 0.127591E+11 | -0.120978E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -661365084.6 | 58.99 | 0.00 | 0.00 |
August | 0.124701E+11 | -0.118060E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -664139079.4 | 59.00 | 0.00 | 0.00 |
September | 0.122267E+11 | -0.115534E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -673242846.7 | 58.99 | 0.00 | 0.00 |
October | 0.133046E+11 | -0.125466E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -758021018.2 | 58.99 | 0.00 | 0.00 |
November | 0.137573E+11 | -0.130013E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -756066082.3 | 58.98 | 0.00 | 0.00 |
December | 0.151290E+11 | -0.143283E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -800753473.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.168622E+12 | -0.159901E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.872199E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.122267E+11 | -0.152505E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -802703059.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.160397E+11 | -0.115534E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -653756792.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.28 | 0.24 | 01-JAN-09:39 | 5707.55 | 34.46 | 166.00 | 245.17 | 5748.08 | 34.39 | 166.17 | 246.67 |
February | 226.83 | 0.27 | 0.24 | 01-FEB-07:00 | 6733.27 | 34.70 | 194.00 | 256.17 | 7388.13 | 35.59 | 198.17 | 256.50 |
March | 334.33 | 0.25 | 0.24 | 01-MAR-07:49 | 1758.51 | 21.27 | 102.50 | 337.50 | 2098.00 | 22.33 | 139.17 | 334.67 |
April | 285.17 | 0.27 | 0.24 | 01-APR-06:40 | 2714.64 | 19.14 | 35.33 | 359.17 | 1968.58 | 19.39 | 38.17 | 356.50 |
May | 428.67 | 0.26 | 0.24 | 01-MAY-05:40 | 1506.79 | 18.98 | 25.33 | 413.33 | 2086.46 | 18.94 | 14.50 | 414.33 |
June | 400.67 | 0.27 | 0.24 | 01-JUN-05:10 | 1982.16 | 19.11 | 23.83 | 414.00 | 1671.39 | 19.12 | 22.83 | 412.50 |
July | 414.00 | 0.26 | 0.24 | 01-JUL-05:40 | 2175.28 | 19.31 | 22.33 | 422.33 | 1757.70 | 19.38 | 32.83 | 423.17 |
August | 410.83 | 0.26 | 0.24 | 01-AUG-05:40 | 1833.64 | 19.43 | 46.83 | 398.00 | 2060.82 | 19.33 | 51.00 | 393.83 |
September | 326.50 | 0.26 | 0.24 | 01-SEP-05:00 | 2063.06 | 21.82 | 122.67 | 344.67 | 2120.39 | 20.32 | 66.83 | 346.33 |
October | 325.17 | 0.27 | 0.24 | 01-OCT-06:40 | 2656.39 | 24.51 | 144.33 | 309.33 | 2744.08 | 25.60 | 168.00 | 309.33 |
November | 254.83 | 0.27 | 0.24 | 01-NOV-07:49 | 3943.47 | 29.78 | 187.50 | 248.67 | 3955.79 | 29.75 | 186.17 | 249.00 |
December | 186.17 | 0.28 | 0.24 | 01-DEC-07:00 | 4831.05 | 32.37 | 127.00 | 223.67 | 4835.22 | 32.50 | 127.00 | 224.00 |
Annual Sum or Average | 3807.33 | 0.26 | 2796.55 | 23.19 | 1197.67 | 3972.00 | 2836.88 | 23.31 | 1210.83 | 3966.83 | ||
Minimum of Months | 186.17 | 0.25 | 0.24 | 1506.79 | 18.98 | 22.33 | 223.67 | 1671.39 | 18.94 | 14.50 | 224.00 | |
Maximum of Months | 428.67 | 0.28 | 0.24 | 6733.27 | 34.70 | 194.00 | 422.33 | 7388.13 | 35.59 | 198.17 | 423.17 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.563249E+11 | 60066.40 | 03-JAN-03:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.404870E+11 | 60066.40 | 01-FEB-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279583E+11 | 60066.40 | 04-MAR-03:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147164E+11 | 59033.05 | 03-APR-02:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.256562E+10 | 17650.86 | 02-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.795177E+09 | 10318.81 | 05-JUN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15119010.80 | 3106.41 | 23-JUL-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 52281473.15 | 3773.75 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.264016E+10 | 14041.69 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.105896E+11 | 19301.76 | 27-OCT-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270794E+11 | 60066.40 | 12-NOV-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458086E+11 | 60066.40 | 04-DEC-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 15119010.80 | 3106.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563249E+11 | 60066.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.564841E+11 | 70060.72 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385557E+11 | 82407.79 | 04-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.204885E+11 | 48547.89 | 08-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.853236E+10 | 37346.07 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.473034E+09 | 12639.69 | 03-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13183479.12 | 2095.60 | 03-JUN-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.577021E+09 | 16230.68 | 30-SEP-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.400344E+10 | 18565.88 | 28-OCT-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208453E+11 | 62983.57 | 26-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402401E+11 | 63332.25 | 10-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190213E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.564841E+11 | 82407.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.185026E+10 | 0.120115E+10 | 42008.43 | 16-APR-02:61 | 24103.28 | 0.00 |
May | 0.00 | 0.00 | 0.292442E+10 | 0.192783E+10 | 21463.65 | 31-MAY-12:00 | 15108.24 | 0.00 |
June | 0.00 | 0.00 | 0.135770E+11 | 0.832831E+10 | 45651.34 | 26-JUN-02:61 | 20221.25 | 0.00 |
July | 0.00 | 0.00 | 0.179727E+11 | 0.101572E+11 | 46352.67 | 04-JUL-02:61 | 17628.19 | 0.00 |
August | 0.00 | 0.00 | 0.162614E+11 | 0.938714E+10 | 46424.91 | 03-AUG-02:61 | 18774.91 | 0.00 |
September | 0.00 | 0.00 | 0.723274E+10 | 0.537520E+10 | 43478.56 | 12-SEP-02:41 | 19421.16 | 0.00 |
October | 0.00 | 0.00 | 0.105929E+09 | 91747921.72 | 6025.76 | 20-OCT-15:10 | 5409.40 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.599244E+11 | 0.364686E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179727E+11 | 0.101572E+11 | 46424.91 | 24103.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 341526.32 | 254493.27 | 1138.42 | 13-JAN-04:40 | 848.31 | 0.00 |
February | 0.00 | 0.00 | 389251.89 | 318536.87 | 886.70 | 21-FEB-04:40 | 742.34 | 0.00 |
March | 0.00 | 0.00 | 10343664.96 | 6615578.37 | 15401.86 | 20-MAR-02:61 | 8562.38 | 0.00 |
April | 0.00 | 0.00 | 0.251929E+10 | 0.165128E+10 | 30839.09 | 11-APR-04:01 | 20782.92 | 0.00 |
May | 0.00 | 0.00 | 0.540548E+10 | 0.343091E+10 | 30839.09 | 12-MAY-02:61 | 12408.56 | 0.00 |
June | 0.00 | 0.00 | 0.197604E+11 | 0.119393E+11 | 34264.26 | 30-JUN-10:45 | 17857.62 | 0.00 |
July | 0.00 | 0.00 | 0.271110E+11 | 0.144930E+11 | 34264.26 | 03-JUL-13:10 | 16513.21 | 0.00 |
August | 0.00 | 0.00 | 0.246604E+11 | 0.134050E+11 | 34264.26 | 03-AUG-10:20 | 15905.15 | 0.00 |
September | 0.00 | 0.00 | 0.993672E+10 | 0.741161E+10 | 31528.16 | 12-SEP-03:18 | 12103.59 | 0.00 |
October | 0.00 | 0.00 | 0.358843E+09 | 0.267537E+09 | 30839.09 | 10-OCT-04:01 | 16612.46 | 0.00 |
November | 0.00 | 0.00 | 32605531.55 | 18006994.74 | 30839.09 | 03-NOV-03:21 | 16901.80 | 0.00 |
December | 0.00 | 0.00 | 1212601.72 | 913996.65 | 1330.02 | 05-DEC-04:40 | 928.85 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.897970E+11 | 0.526247E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 341526.32 | 254493.27 | 886.70 | 742.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.271110E+11 | 0.144930E+11 | 34264.26 | 20782.92 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 5920.55 | 22340.31 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6035.72 | 22493.48 | 21-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 5991.19 | 22457.15 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 5752.95 | 21864.37 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 5435.00 | 20758.77 | 01-MAY-12:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 5093.16 | 19371.44 | 01-JUN-12:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 4807.28 | 18146.76 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 4701.22 | 17350.88 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 4748.56 | 17791.38 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 4976.00 | 18924.08 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 5309.18 | 20267.23 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 5642.26 | 21537.74 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 5363.82 | ||||
Minimum of Months | 0.00 | 0.00 | 4701.22 | 17350.88 | ||
Maximum of Months | 0.00 | 0.00 | 6035.72 | 22493.48 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112547E+10 | 0.23 | 503.64 | 01-JAN-00:01 | 0.28 |
February | 0.101760E+10 | 0.23 | 503.64 | 01-FEB-00:01 | 0.28 |
March | 0.113487E+10 | 0.23 | 503.64 | 01-MAR-00:01 | 0.28 |
April | 0.112071E+10 | 0.24 | 503.64 | 01-APR-04:01 | 0.28 |
May | 0.121587E+10 | 0.25 | 503.64 | 01-MAY-02:15 | 0.28 |
June | 0.122070E+10 | 0.26 | 503.64 | 01-JUN-00:50 | 0.28 |
July | 0.128401E+10 | 0.26 | 503.64 | 01-JUL-00:14 | 0.27 |
August | 0.127700E+10 | 0.26 | 503.64 | 01-AUG-00:17 | 0.27 |
September | 0.120273E+10 | 0.25 | 503.64 | 01-SEP-00:18 | 0.27 |
October | 0.117576E+10 | 0.24 | 503.64 | 01-OCT-03:20 | 0.28 |
November | 0.111360E+10 | 0.24 | 503.64 | 01-NOV-03:20 | 0.28 |
December | 0.112623E+10 | 0.23 | 503.64 | 01-DEC-00:01 | 0.28 |
Annual Sum or Average | 0.140145E+11 | 0.24 | |||
Minimum of Months | 0.101760E+10 | 0.23 | 503.64 | 0.27 | |
Maximum of Months | 0.128401E+10 | 0.26 | 503.64 | 0.28 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270979E+10 | 0.65 | 1825.06 | 03-JAN-03:07 | 0.93 |
February | 0.224269E+10 | 0.63 | 1825.06 | 01-FEB-03:01 | 0.93 |
March | 0.216579E+10 | 0.58 | 1825.06 | 04-MAR-03:07 | 0.92 |
April | 0.185163E+10 | 0.54 | 1793.67 | 03-APR-02:61 | 0.92 |
May | 0.167698E+10 | 0.47 | 1024.47 | 19-MAY-05:12 | 0.69 |
June | 0.161401E+10 | 0.48 | 1825.06 | 26-JUN-02:61 | 0.91 |
July | 0.167085E+10 | 0.48 | 1825.06 | 03-JUL-02:61 | 0.91 |
August | 0.167208E+10 | 0.49 | 1825.06 | 03-AUG-02:61 | 0.91 |
September | 0.163766E+10 | 0.48 | 1146.28 | 11-SEP-02:61 | 0.73 |
October | 0.182349E+10 | 0.51 | 1037.23 | 31-OCT-16:53 | 0.69 |
November | 0.209492E+10 | 0.57 | 1825.06 | 12-NOV-03:02 | 0.92 |
December | 0.251609E+10 | 0.63 | 1825.06 | 04-DEC-03:02 | 0.92 |
Annual Sum or Average | 0.236760E+11 | 0.54 | |||
Minimum of Months | 0.161401E+10 | 0.47 | 1024.47 | 0.69 | |
Maximum of Months | 0.270979E+10 | 0.65 | 1825.06 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176839E+10 | 0.60 | 1207.44 | 30-JAN-05:03 | 0.90 |
February | 0.148173E+10 | 0.57 | 1321.99 | 04-FEB-05:02 | 0.94 |
March | 0.143585E+10 | 0.53 | 1007.87 | 08-MAR-05:03 | 0.82 |
April | 0.130267E+10 | 0.52 | 1393.72 | 11-APR-04:01 | 0.95 |
May | 0.128423E+10 | 0.52 | 1393.72 | 05-MAY-02:11 | 0.95 |
June | 0.142648E+10 | 0.56 | 1393.72 | 01-JUN-02:61 | 0.95 |
July | 0.153518E+10 | 0.58 | 1393.72 | 01-JUL-02:11 | 0.95 |
August | 0.151421E+10 | 0.58 | 1393.72 | 01-AUG-02:11 | 0.95 |
September | 0.128426E+10 | 0.53 | 1393.72 | 01-SEP-02:11 | 0.95 |
October | 0.128974E+10 | 0.51 | 1393.72 | 03-OCT-04:01 | 0.95 |
November | 0.140198E+10 | 0.54 | 1393.72 | 03-NOV-04:01 | 0.95 |
December | 0.161775E+10 | 0.57 | 1145.02 | 10-DEC-05:02 | 0.88 |
Annual Sum or Average | 0.173425E+11 | 0.55 | |||
Minimum of Months | 0.128423E+10 | 0.51 | 1007.87 | 0.82 | |
Maximum of Months | 0.176839E+10 | 0.60 | 1393.72 | 0.95 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 49.23 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.41 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.37 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 51.02 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:10 | 0.00 | 0.00 | 49.86 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:10 | 0.00 | 0.00 | 51.82 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:03 | 0.00 | 0.00 | 52.62 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:10 | 0.00 | 0.00 | 52.23 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 52.29 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 50.93 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 51.96 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 51.48 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 49.23 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 52.62 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 35.94 | 35.94 | 5920.55 | 22340.31 | 31-JAN-13:20 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 50.69 | 50.69 | 6035.72 | 22493.48 | 21-FEB-13:15 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 50.66 | 50.66 | 5991.19 | 22457.15 | 01-MAR-13:40 |
April | 0.00 | 0.00 | 01-APR-00:01 | 51.08 | 51.08 | 5752.95 | 21864.37 | 01-APR-12:40 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 36.72 | 36.72 | 5435.00 | 20758.77 | 01-MAY-12:45 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 52.04 | 52.04 | 5093.16 | 19371.44 | 01-JUN-12:17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 52.61 | 52.61 | 4807.28 | 18146.76 | 01-JUL-12:30 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 52.17 | 52.17 | 4701.22 | 17350.88 | 01-AUG-12:40 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 52.24 | 52.24 | 4748.56 | 17791.38 | 30-SEP-12:30 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 39.95 | 39.95 | 4976.00 | 18924.08 | 31-OCT-12:40 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 51.69 | 51.69 | 5309.18 | 20267.23 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 51.34 | 51.34 | 5642.26 | 21537.74 | 31-DEC-13:15 |
Annual Sum or Average | 0.00 | 5363.82 | ||||||
Minimum of Months | 0.00 | 0.00 | 35.94 | 35.94 | 4701.22 | 17350.88 | ||
Maximum of Months | 0.00 | 0.00 | 52.61 | 52.61 | 6035.72 | 22493.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.270979E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.224269E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.216579E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.233556E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.247025E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.508282E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.624324E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.582903E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.356650E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.185506E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.209492E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.251609E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.391117E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.185506E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.624324E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176849E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148185E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143864E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.191312E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.265627E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.613774E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.793752E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.736934E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.376782E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.139124E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.141044E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.161812E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.388906E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.139124E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.793752E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.270979E+10 | 0.00 | 0.563249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224269E+10 | 0.00 | 0.404870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216579E+10 | 0.00 | 0.279583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185163E+10 | 0.184941E+10 | 0.147164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167698E+10 | 0.292442E+10 | 0.256562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161401E+10 | 0.135178E+11 | 0.795177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167085E+10 | 0.179044E+11 | 15119010.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167208E+10 | 0.162018E+11 | 52281473.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163766E+10 | 0.720682E+10 | 0.264016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182349E+10 | 0.105929E+09 | 0.105896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209492E+10 | 0.00 | 0.270794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251609E+10 | 0.00 | 0.458086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236760E+11 | 0.597106E+11 | 0.229033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161401E+10 | 0.00 | 15119010.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270979E+10 | 0.179044E+11 | 0.563249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176839E+10 | 341526.32 | 0.564841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148173E+10 | 389251.89 | 0.385557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143585E+10 | 10343664.96 | 0.204885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130267E+10 | 0.251677E+10 | 0.853236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128423E+10 | 0.539777E+10 | 0.473034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142648E+10 | 0.196669E+11 | 13183479.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153518E+10 | 0.269892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151421E+10 | 0.245435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128426E+10 | 0.990273E+10 | 0.577021E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128974E+10 | 0.357245E+09 | 0.400344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140198E+10 | 30808052.90 | 0.208453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161775E+10 | 1212601.72 | 0.402401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173425E+11 | 0.894173E+11 | 0.190213E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128423E+10 | 341526.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176839E+10 | 0.269892E+11 | 0.564841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.270979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185163E+10 | 0.00 | 0.00 | 0.00 | 0.483925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167698E+10 | 0.00 | 0.00 | 0.00 | 0.793271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161401E+10 | 0.00 | 0.00 | 0.00 | 0.346882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.167085E+10 | 0.00 | 0.00 | 0.00 | 0.457239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167208E+10 | 0.00 | 0.00 | 0.00 | 0.415695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163766E+10 | 0.00 | 0.00 | 0.00 | 0.192884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182349E+10 | 0.00 | 0.00 | 0.00 | 31569632.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.209492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.251609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.236760E+11 | 0.00 | 0.00 | 0.00 | 0.154358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270979E+10 | 0.00 | 0.00 | 0.00 | 0.457239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176839E+10 | 0.00 | 0.00 | 0.00 | 104000.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148173E+10 | 0.00 | 0.00 | 0.00 | 119293.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143585E+10 | 0.00 | 0.00 | 0.00 | 2789430.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130267E+10 | 0.00 | 0.00 | 0.00 | 0.610450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128423E+10 | 0.00 | 0.00 | 0.00 | 0.137205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142648E+10 | 0.00 | 0.00 | 0.00 | 0.471125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153518E+10 | 0.00 | 0.00 | 0.00 | 0.640233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151421E+10 | 0.00 | 0.00 | 0.00 | 0.585513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128426E+10 | 0.00 | 0.00 | 0.00 | 0.248356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128974E+10 | 0.00 | 0.00 | 0.00 | 0.101502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140198E+10 | 0.00 | 0.00 | 0.00 | 8467441.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161775E+10 | 0.00 | 0.00 | 0.00 | 369569.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173425E+11 | 0.00 | 0.00 | 0.00 | 0.215481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128423E+10 | 0.00 | 0.00 | 0.00 | 104000.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176839E+10 | 0.00 | 0.00 | 0.00 | 0.640233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.166049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406172E+11 | 0.00 | 0.00 | 3.64 |
February | 0.198175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301805E+11 | 0.00 | 0.00 | 3.64 |
March | 0.370335E+10 | 0.00 | 0.00 | 189530.92 | 0.00 | 0.224974E+11 | 0.145872E+09 | 0.00 | 3.63 |
April | 0.508283E+10 | 0.297854E+09 | 0.00 | 2721966.26 | 0.00 | 0.118095E+11 | 0.706206E+09 | 0.00 | 3.76 |
May | 0.727915E+10 | 0.248116E+09 | 0.00 | 8998656.71 | 0.00 | 0.105623E+10 | 0.287927E+10 | 0.00 | 4.12 |
June | 0.357829E+10 | 0.246957E+10 | 0.00 | 15651777.24 | 3203735.97 | 0.168246E+09 | 0.299174E+10 | 0.00 | 4.60 |
July | 0.118000E+10 | 0.291395E+10 | 0.00 | 21842284.19 | 1861245.34 | 13534.52 | 0.392697E+10 | 0.00 | 5.06 |
August | 0.181840E+10 | 0.270250E+10 | 0.00 | 22103854.27 | 7147134.73 | 0.00 | 0.437622E+10 | 0.00 | 4.94 |
September | 0.572431E+10 | 0.762765E+09 | 0.00 | 16275189.99 | 0.00 | 0.124539E+10 | 0.336438E+10 | 0.00 | 4.37 |
October | 0.952496E+10 | 0.00 | 0.00 | 1756448.84 | 0.00 | 0.686444E+10 | 0.875893E+09 | 0.00 | 3.66 |
November | 0.485825E+10 | 0.00 | 0.00 | 90732.24 | 0.00 | 0.209583E+11 | 0.126901E+09 | 0.00 | 3.60 |
December | 0.184558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350411E+11 | 0.00 | 0.00 | 3.61 |
Annual Sum or Average | 0.482374E+11 | 0.939476E+10 | 0.00 | 89630440.66 | 12212116.04 | 0.170438E+12 | 0.193935E+11 | 0.00 | 4.06 |
Minimum of Months | 0.118000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 |
Maximum of Months | 0.952496E+10 | 0.291395E+10 | 0.00 | 22103854.27 | 7147134.73 | 0.406172E+11 | 0.437622E+10 | 0.00 | 5.06 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.879469E+11 | 0.00 | 0.00 | 26054.31 | 0.00 | 71736240.88 | 15883837.29 | 0.00 | 8.04 |
February | 0.671195E+11 | 0.00 | 0.00 | 40692.34 | 0.00 | 60616417.07 | 22027014.20 | 0.00 | 7.81 |
March | 0.515463E+11 | 0.00 | 0.00 | 1034919.35 | 0.00 | 21960779.77 | 0.135415E+10 | 0.00 | 7.46 |
April | 0.341670E+11 | 0.156388E+09 | 0.00 | 11933459.40 | 0.00 | 10216281.63 | 0.383262E+10 | 0.00 | 7.33 |
May | 0.128153E+11 | 71964729.22 | 0.00 | 40046641.41 | 0.00 | 0.00 | 0.158753E+11 | 0.00 | 7.37 |
June | 0.570520E+10 | 0.319611E+10 | 0.00 | 52009663.00 | 2345029.28 | 0.00 | 0.114053E+11 | 0.00 | 7.89 |
July | 0.173188E+10 | 0.367828E+10 | 0.00 | 71329690.90 | 3992780.75 | 0.00 | 0.104267E+11 | 0.00 | 8.08 |
August | 0.216681E+10 | 0.370755E+10 | 0.00 | 69145293.97 | 6086230.39 | 0.00 | 0.126261E+11 | 0.00 | 8.02 |
September | 0.114195E+11 | 0.246349E+09 | 0.00 | 55536472.52 | 0.00 | 0.00 | 0.142791E+11 | 0.00 | 7.51 |
October | 0.317550E+11 | 0.00 | 0.00 | 9103697.50 | 0.00 | 0.00 | 0.673992E+10 | 0.00 | 7.21 |
November | 0.498955E+11 | 0.00 | 0.00 | 2514529.54 | 0.00 | 17736454.20 | 0.335495E+10 | 0.00 | 7.49 |
December | 0.724555E+11 | 0.00 | 0.00 | 56850.38 | 0.00 | 42564502.91 | 26338297.51 | 0.00 | 7.72 |
Annual Sum or Average | 0.428724E+12 | 0.110567E+11 | 0.00 | 0.312778E+09 | 12424040.42 | 0.224831E+09 | 0.799584E+11 | 0.00 | 7.66 |
Minimum of Months | 0.173188E+10 | 0.00 | 0.00 | 26054.31 | 0.00 | 0.00 | 15883837.29 | 0.00 | 7.21 |
Maximum of Months | 0.879469E+11 | 0.370755E+10 | 0.00 | 71329690.90 | 6086230.39 | 71736240.88 | 0.158753E+11 | 0.00 | 8.08 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.195618E+11 | 0.283950E+11 | 0.184533E+12 | 0.00 | 0.442651E+11 |
February | 0.246961E+11 | 0.219979E+11 | 0.144143E+12 | 0.00 | 0.344144E+11 |
March | 0.413528E+11 | 0.179302E+11 | 0.121476E+12 | 7089874.58 | 0.293421E+11 |
April | 0.518836E+11 | 0.124467E+11 | 0.896648E+11 | 0.223129E+09 | 0.308123E+11 |
May | 0.618470E+11 | 0.785975E+10 | 0.697940E+11 | 0.732245E+09 | 0.351090E+11 |
June | 0.654132E+11 | 0.309186E+10 | 0.365985E+11 | 0.974273E+09 | 0.681833E+11 |
July | 0.660296E+11 | 0.117161E+10 | 0.241941E+11 | 0.117832E+10 | 0.846150E+11 |
August | 0.572009E+11 | 0.193049E+10 | 0.307750E+11 | 0.122989E+10 | 0.773957E+11 |
September | 0.386917E+11 | 0.598126E+10 | 0.624116E+11 | 0.103058E+10 | 0.463291E+11 |
October | 0.273591E+11 | 0.118463E+11 | 0.938973E+11 | 0.174571E+09 | 0.224480E+11 |
November | 0.143343E+11 | 0.171399E+11 | 0.121538E+12 | 52239.64 | 0.268948E+11 |
December | 0.882065E+10 | 0.237286E+11 | 0.158805E+12 | 0.00 | 0.352714E+11 |
Annual Sum or Average | 0.477191E+12 | 0.153520E+12 | 0.113783E+13 | 0.555016E+10 | 0.535080E+12 |
Minimum of Months | 0.882065E+10 | 0.117161E+10 | 0.241941E+11 | 0.00 | 0.224480E+11 |
Maximum of Months | 0.660296E+11 | 0.283950E+11 | 0.184533E+12 | 0.122989E+10 | 0.846150E+11 |