Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26
Tabular Output Report in Format: HTML
Building: RestaurantFastFood
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:26:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2083.21 | 8966.09 | 8966.09 |
Net Site Energy | 2083.21 | 8966.09 | 8966.09 |
Total Source Energy | 3128.34 | 13464.32 | 13464.32 |
Net Source Energy | 3128.34 | 13464.32 | 13464.32 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 232.34 |
Net Conditioned Building Area | 232.34 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 927.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 260.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | 49.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 417.73 | 1665.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 927.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 233.46 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 17.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 53.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 | |
Water Heater | 0.00 | 260.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 7.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 13.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 927.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 24.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 15.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 265.86 | 477.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 53.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 260.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.38 |
Refrigeration | Unassigned | 49.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 175.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 265.32 | 5114.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1356.70 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1797.92 | 7168.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 175.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 265.32 | 5114.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Other | 1356.70 | 2053.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1797.92 | 7168.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 417.735 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 417.735 | 100.00 |
Total On-Site and Utility Electric Sources | 417.735 | 100.00 |
Total Electricity End Uses | 417.735 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 775.38 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 775.38 | 100.00 |
Total Water End Uses | 775.38 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4605.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING | KITCHEN |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Above Ground Wall Area [m2] | 185.89 | 46.47 | 46.47 | 46.47 | 46.47 |
Window Opening Area [m2] | 26.02 | 0.00 | 6.50 | 13.01 | 6.50 |
Gross Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Above Ground Window-Wall Ratio [%] | 14.00 | 0.00 | 14.00 | 27.99 | 14.00 |
Total | |
Gross Roof Area [m2] | 258.86 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
DINING | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 26.02 | 26.02 | 7.1446 | 1.33 | 116.7869 |
KITCHEN | 116.17 | Yes | Yes | 354.18 | 1.00 | 92.94 | 0.00 | 0.00 | 0.00 | 9.9598 | 18.52 | 1071.0790 |
ATTIC | 232.34 | No | No | 262.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Conditioned Total | 232.34 | 708.37 | 185.89 | 0.00 | 26.02 | 26.02 | 8.5522 | 2.48 | 593.9329 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 232.34 | 262.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
DINING | 116.17 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 7.1446 | 1.33 | 116.7869 | |
KITCHEN | 116.17 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 9.9598 | 18.52 | 1071.0790 | |
ATTIC | 232.34 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Conditioned Total | 232.34 | 8.5522 | 1.24 | 593.9329 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 232.34 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 232.34 | 232.34 | 0.00 | 232.34 | 8.5522 | 2.48 | 593.9329 |
Total | 232.34 | 232.34 | 0.00 | 232.34 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-10:20 | 12-JAN-13:20 | - | - | - | - | - | - | - | - | - | - | 01-JAN-13:09 |
Heating | 0.00 | 139194.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4922.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 947.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14073.79 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1671.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 33359.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 4328.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25943.38 | 195537.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 139194.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 4922.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 947.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | Cooking | 13046.29 | 22983.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 1671.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 33359.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 3284.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1043.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1005.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 26.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 78.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 841.99 | 517.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 282.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 156.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1322.97 | 1805.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4327.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 217.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 726.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1216.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 672.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5694.02 | 7770.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 4327.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 339.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 217.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 3623.92 | 2226.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 726.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 1216.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 672.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5694.02 | 7770.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
DINING DIRECT AIR | 1.49 |
KITCHEN DIRECT AIR | 1.19 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.49 | 1.00 | 1.00 | 1.49 |
PSZ-AC_2:2 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.19 | 1.00 | 1.00 | 1.19 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.49 | 0.416056 |
PSZ-AC_2:2_OA_CONTROLLER | 1.19 | 1.14 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ FAN | 1.49 | 1596.94 |
PSZ-AC_2:2_ADDAQ FAN | 1.19 | 1323.00 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.49 | 1.49 | 1.49 | 0.984983 | 27559.43 | 64809.84 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.19 | 1.19 | 1.19 | 0.788667 | 23033.63 | 112767.45 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.49 | 0.746200 | 0.994933 | 27559.43 | 13779.72 | 0.800570 | 0.800570 |
PSZ-AC_2:2 COOLING COIL | 1.19 | 0.597475 | 0.796633 | 23033.63 | 11516.82 | 0.790730 | 0.790730 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 64809.84 |
PSZ-AC_2:2 HEATING COIL | 112767.45 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000096 | 0.011518 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000096 | 0.000000 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000096 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RestaurantFastFood | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 24 | 4 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 3.81 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 7.62 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 66.93 | 26.02 | 6 | 3 | 0 | Yes |
2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 1.52 | 1 | 1 | 1 | 0.00 | 15.24 | 7.62 | 15.24 | 0.00 | 3.05 | 3.05 | 354.18 | TARP | TARP | 116.17 | 92.94 | 90.99 | 0.00 | 6 | 1 | 0 | Yes |
3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 7.62 | 7.62 | 3.64 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 15.24 | 3.05 | 5.59 | 1.27 | 262.34 | TARP | TARP | 232.34 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | DINING | 116.17 | 87.5 | 1.327 | 0.754 | 7.145 | 116.787 | 0.000 | 0.000 | 0.000 | 0.000 | 123.932 | No |
2 | KITCHEN | 116.17 | 6.3 | 18.518 | 5.400E-002 | 9.960 | 279.726 | 791.353 | 0.000 | 0.000 | 0.000 | 1081.039 | No |
3 | ATTIC | 232.34 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DINING | BLDG_OCC_SCH | DINING | 116.17 | 87.5 | 87.5 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 88 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | KITCHEN | BLDG_OCC_SCH | KITCHEN | 116.17 | 6.3 | 6.3 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 116.17 | 87.5 | 829.995 | 7.145 | 9.481 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 829.995 |
2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 116.17 | 6.3 | 1157.049 | 9.960 | 184.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1157.049 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 116.17 | 87.5 | 13567.311 | 116.787 | 154.976 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 3934.520 |
2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 31468.723 | 270.882 | 5016.295 | 0.250 | 0.300 | 0.300 | 0.150 | Cooking | 0.000 | 9125.930 |
3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 457.500 | 3.938 | 72.928 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 116.17 | 6.3 | 570.000 | 4.907 | 90.861 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 570.000 | 570.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | KITCHEN_MISCGAS_EQUIP | FF_GAS_EQUIP_SCH | KITCHEN | 116.17 | 6.3 | 91932.601 | 791.353 | 14654.584 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26660.454 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.9832E-01 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.3187 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2034 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.2034 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 10.07 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.904 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.841 |
16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.841 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
23 | 4 | 0.30075618E-16 | 0.17394661E-15 | 0.12402583E-13 | -0.41376697E-16 |
24 | 3 | -0.12971024E-07 | 0.72198543E-07 | -0.59837000E-04 | 0.16553701E-12 |
25 | 2 | 0.68419174E-04 | 0.15226993E-02 | 1.1866788 | -0.78740824E-04 |
26 | 1 | -0.34646128E-01 | 0.38608229E-01 | -17.391783 | 0.34506386 |
27 | 0 | 0.98978059E-01 | 0.24269337E-01 | 16.269565 | |
28 | 4 | 0.12402583E-13 | 0.17394661E-15 | 0.30075618E-16 | -0.41376697E-16 |
29 | 3 | -0.59837000E-04 | 0.72198543E-07 | -0.12971024E-07 | 0.16553701E-12 |
30 | 2 | 1.1866788 | 0.15226993E-02 | 0.68419174E-04 | -0.78740824E-04 |
31 | 1 | -17.391783 | 0.38608229E-01 | -0.34646128E-01 | 0.34506386 |
32 | 0 | 16.269565 | 0.24269337E-01 | 0.98978059E-01 | |
33 | 7 | -0.37367478E-12 | 0.55127043E-15 | -0.12820660E-12 | 0.55286981E-16 |
34 | 6 | 0.34010604E-07 | 0.93765259E-10 | 0.77465858E-08 | -0.16449040E-12 |
35 | 5 | -0.21686405E-03 | 0.77799044E-06 | -0.11113300E-03 | 0.76387383E-08 |
36 | 4 | 0.32293650 | 0.36828090E-03 | 0.11078133 | -0.37969013E-04 |
37 | 3 | -7.8748998 | 0.11131117E-01 | -2.5195851 | 0.31994793E-01 |
38 | 2 | 42.876872 | 0.38708993E-01 | 16.003231 | -0.35568648 |
39 | 1 | -82.081343 | 0.17130956E-01 | -29.802633 | 1.1113449 |
40 | 0 | 46.824329 | 0.33809010E-03 | 16.275995 | |
41 | 7 | -0.20748704E-08 | -0.64863736E-15 | 0.81213421E-14 | -0.11992970E-15 |
42 | 6 | 0.57165587E-05 | 0.38938745E-08 | 0.31895632E-02 | -0.26756729E-04 |
43 | 5 | -0.40949433E-03 | 0.23056113E-05 | -0.22370715 | 0.19559964E-02 |
44 | 4 | 0.94093481E-02 | 0.10493751E-03 | 4.8292555 | -0.45262192E-01 |
45 | 3 | -0.82597656E-01 | 0.83437781E-03 | -38.019778 | 0.39863564 |
46 | 2 | 0.29324730 | 0.13879289E-02 | 116.48076 | -1.4178967 |
47 | 1 | -0.42323371 | 0.42279242E-03 | -143.90543 | 2.0490091 |
48 | 0 | 0.20634108 | 0.10243659E-04 | 60.838472 | |
49 | 7 | -0.20748704E-08 | -0.64863736E-15 | 0.81213421E-14 | -0.11992970E-15 |
50 | 6 | 0.57165587E-05 | 0.38938745E-08 | 0.31895632E-02 | -0.26756729E-04 |
51 | 5 | -0.40949433E-03 | 0.23056113E-05 | -0.22370715 | 0.19559964E-02 |
52 | 4 | 0.94093481E-02 | 0.10493751E-03 | 4.8292555 | -0.45262192E-01 |
53 | 3 | -0.82597656E-01 | 0.83437781E-03 | -38.019778 | 0.39863564 |
54 | 2 | 0.29324730 | 0.13879289E-02 | 116.48076 | -1.4178967 |
55 | 1 | -0.42323371 | 0.42279242E-03 | -143.90543 | 2.0490091 |
56 | 0 | 0.20634108 | 0.10243659E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.29_SHGC_SOUTH_0.45 | 38 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
2 | NONRESWINDOW_U_0.29_SHGC_NORTH_0.45 | 39 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
3 | NONRESWINDOW_U_0.29_SHGC_EAST_0.45 | 40 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
4 | NONRESWINDOW_U_0.29_SHGC_WEST_0.45 | 41 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | DINING | 3 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | DINING | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.053 | 0.3093 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | DINING_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
2 | DINING_WALL_EAST_WINDOW | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
3 | DINING_WALL_SOUTH | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
4 | DINING_WALL_SOUTH_WINDOW | 0 | 46.47 | 36.58 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
5 | DINING_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 3 | No | No |
6 | DINING_WALL_WEST_WINDOW | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 2 | No | No |
7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.28 | 0 | No | No |
11 | KITCHEN_WALL_NORTH | 0 | 46.47 | 49.21 | 3.05 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
12 | KITCHEN_WALL_EAST | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
13 | KITCHEN_WALL_EAST_DOOR | 0 | 73.85 | 54.29 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
14 | KITCHEN_WALL_WEST | 0 | 73.85 | 42.08 | 5.59 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 30.49 | 10.16 | 0.00 | 0 | No | No |
19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
21 | WEST-ROOF | 0 | 73.85 | 42.08 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
22 | EAST-ROOF | 0 | 73.85 | 54.29 | 5.59 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
23 | NORTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
24 | SOUTH-ROOF | 0 | 204.09 | 60.97 | 2.54 | 0 | 1.27 | 0.00 | 15.24 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 116.17 | 87.5 | 5.294E-002 | 4.557E-004 | 5.696E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 116.17 | 87.5 | 0.584 | 5.025E-003 | 6.281E-003 | 5.934 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 116.17 | 6.3 | 5.294E-002 | 4.557E-004 | 5.579E-004 | 0.538 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 232.34 | 0.0 | 7.290E-002 | 3.138E-004 | 2.816E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | DINING | Mixing/Well-Stirred |
2 | KITCHEN | Mixing/Well-Stirred |
3 | ATTIC | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone DINING | 1.2000 |
3 | Zone KITCHEN | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 4.0845E-003 |
2 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.9827E-002 |
3 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 4.1235E-003 |
4 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.8867E-002 |
5 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 2.8004E-003 |
6 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 2.7664E-002 |
7 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT1 | 1.9609E-003 |
8 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_EAST_WINDOW | DINING_DAYLREFPT2 | 1.9595E-002 |
9 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 8.1683E-002 |
10 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 7.7132E-002 |
11 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 9.6947E-002 |
12 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 9.1055E-002 |
13 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 4.4012E-002 |
14 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 4.2890E-002 |
15 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT1 | 2.1211E-002 |
16 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_SOUTH_WINDOW | DINING_DAYLREFPT2 | 2.1211E-002 |
17 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.4509E-002 |
18 | Clear Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 3.1981E-003 |
19 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.1105E-002 |
20 | Clear Turbid Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.8495E-003 |
21 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 2.1983E-002 |
22 | Intermediate Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 2.3028E-003 |
23 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT1 | 1.9597E-002 |
24 | Overcast Sky | 01/21 | DINING_DAYLCTRL | DINING | DINING_WALL_WEST_WINDOW | DINING_DAYLREFPT2 | 1.9609E-003 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | DINING | Cooling | 16628.28270 | 19953.93924 | 1.24367 | 1.49240 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 27.29800 | 7.00699E-003 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
2 | DINING | Heating | 7441.23215 | 8929.47858 | 0.32169 | 0.41606 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90000 | 6.45023E-005 | 116.17148 | 87.54444 | 0.41606 | 0.00000 |
3 | KITCHEN | Cooling | 15977.32275 | 19172.78730 | 0.99579 | 1.19495 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.48200 | 7.00575E-003 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
4 | KITCHEN | Heating | 644.63384 | 773.56061 | 2.52600E-002 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -41.90000 | 6.45023E-005 | 116.17148 | 6.27330 | 1.14133 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 21431.84 | 1.49240 | 1.49240 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 40590.10 | 0.41606 | 0.41606 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 19849.51 | 1.19495 | 1.19495 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 111347.57 | 1.14133 | 1.14133 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.49240 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.19495 |
3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.49240 |
4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.49240 |
5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.49240 |
6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.49240 |
7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.49240 |
8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.49240 |
9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.19495 |
12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.19495 |
13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.19495 |
14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.19495 |
15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.19495 |
16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.19495 |
17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.49240 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.19495 |
21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.49240 |
22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41606 |
23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.49240 |
24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 1596.93748 |
25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.49240 |
26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.49240 |
27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.49240 |
28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98498 |
29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.49240 |
30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.74620 |
31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.99493 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 27559.43000 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 13779.71500 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80057 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80057 |
36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 27559.43000 |
37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 64809.83876 |
38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 64809.83876 |
41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.19495 |
42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.14133 |
43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.19495 |
44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 1322.99995 |
45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.19495 |
46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.19495 |
47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.19495 |
48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78867 |
49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.19495 |
50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.59748 |
51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.79663 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23033.63000 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 11516.81500 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79073 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79073 |
56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23033.63000 |
57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 112767.44873 |
58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 112767.44873 |
61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 9.59800E-005 |
62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.15176E-002 |
63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 9.59800E-005 |
64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 4.10171E-007 |
65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 9.59800E-005 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 26474.8 | 11.26 | 11.21 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 22167.6 | 11.35 | 11.30 |
Zone Name | # Surfaces | |
1 | DINING | 10 |
2 | KITCHEN | 8 |
3 | ATTIC | 6 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.319 | 0.304 | 16.73 | 23.24 | 16.73 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 6.50 | 6.50 | 6.50 | 90.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.319 | 0.304 | 33.46 | 46.47 | 33.46 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 13.01 | 13.01 | 13.01 | 180.00 | 90.00 | 14.23 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.319 | 0.304 | 16.73 | 23.24 | 16.73 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 6.50 | 6.50 | 6.50 | 270.00 | 90.00 | 7.11 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.203 | 0.194 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.319 | 0.304 | 46.47 | 46.47 | 46.47 | 0.00 | 90.00 | 15.24 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.319 | 0.304 | 21.29 | 23.24 | 21.29 | 90.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.319 | 0.304 | 23.24 | 23.24 | 23.24 | 270.00 | 90.00 | 7.62 | 3.05 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 46.47 | 46.47 | 46.47 | 180.00 | 90.00 | 15.24 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.203 | 0.194 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 9.832E-002 | 9.653E-002 | 116.17 | 116.17 | 116.17 | 180.00 | 0.00 | 15.24 | 7.62 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 232.34 | 232.34 | 232.34 | 0.00 | 90.00 | 232.34 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 116.17 | 116.17 | 116.17 | 180.00 | 180.00 | 15.24 | 7.62 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 9.832E-002 | 9.602E-002 | 116.17 | 116.17 | 116.17 | 0.00 | 180.00 | 15.24 | 7.62 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 270.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
22 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 27.38 | 27.38 | 27.38 | 90.00 | 45.00 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
23 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 0.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
24 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 102.05 | 102.05 | 102.05 | 180.00 | 18.44 | 8.43 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1327252715 | 0.5514502129 | Pass | Pass | 0.1367637937 | 0.3697343488 | Pass | Pass |
2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 0.1296103622 | 0.6068900789 | Pass | Pass | 5.4831917393E-002 | 0.2256061963 | Pass | Pass |
3 | ATTIC | RunPeriod: RUNPERIOD 1 | 5.8579311258E-002 | 4.9308610138E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 287.18 | 223.63 | 1692.44 | 4.92 | 430.29 | 2638.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.304 | 0.319 | 23.24 | 16.73 | 90.00 | 90.00 | E |
DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.304 | 0.319 | 46.47 | 33.46 | 180.00 | 90.00 | S |
DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.304 | 0.319 | 23.24 | 16.73 | 270.00 | 90.00 | W |
DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 116.17 | 116.17 | 0.00 | 180.00 | |
KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.304 | 0.319 | 46.47 | 46.47 | 0.00 | 90.00 | N |
KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.304 | 0.319 | 23.24 | 21.29 | 90.00 | 90.00 | E |
KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.304 | 0.319 | 23.24 | 23.24 | 270.00 | 90.00 | W |
KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.197 | 0.203 | 116.17 | 116.17 | 0.00 | 180.00 | |
WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 270.00 | 45.00 | |
EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 27.38 | 27.38 | 90.00 | 45.00 | |
NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 0.00 | 18.44 | |
SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 102.05 | 102.05 | 180.00 | 18.44 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 0.00 | 90.00 | N |
DINING_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 180.00 | 0.00 | |
DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 46.47 | 46.47 | 180.00 | 90.00 | S |
KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 180.00 | 0.00 | |
ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 180.00 | 180.00 | |
ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.096 | 0.098 | 116.17 | 116.17 | 0.00 | 180.00 | |
DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N | ||
KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 232.34 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.29_SHGC_EAST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.647 | 0.451 | 0.497 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.29_SHGC_SOUTH_0.45 | 13.01 | 0.00 | 0.00 | 13.01 | 13.01 | 1.647 | 0.451 | 0.497 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.29_SHGC_WEST_0.45 | 6.50 | 0.00 | 0.00 | 6.50 | 6.50 | 1.647 | 0.451 | 0.497 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 26.02 | 1.647 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 26.02 | 1.647 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | KITCHEN_WALL_EAST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
DINING_LIGHTS | DINING | DINING | GENERAL | 7.1446 | 116.17 | 830.00 | LightsWired | LTG_SCH_DINING | 88.95 | 168.00 | 47.43 | 0.0000 | Y | 7.39 |
KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 9.9598 | 116.17 | 1157.05 | LightsWired | LTG_SCH_KITCHEN | 84.44 | 168.00 | 80.60 | 0.0000 | Y | 17.51 |
Interior Lighting Total | 8.5522 | 232.34 | 1987.04 | 24.90 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
DINING_DAYLREFPT1 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
DINING_DAYLREFPT2 | DINING | DINING_DAYLCTRL | SplitFlux | Stepped | 0.38 | 830.00 | 315.40 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 218.22 | AstronomicalClock | - | 51.74 | 51.74 | 2.12 | |
EXTERIOR_LIGHTS_B | 1154.09 | AstronomicalClock | - | 83.06 | 63.95 | 13.85 | |
Exterior Lighting Total | 1372.31 | 15.97 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 27559.43 | 22063.25 | 5496.18 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23033.63 | 18213.38 | 4820.25 | 0.79 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 26474.8 | 11.26 | 11.21 | ||||
PSZ-AC_2:2 COOLING COIL | 22167.6 | 11.35 | 11.30 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 64809.84 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 112767.45 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.42 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 124.50 | 1.56 | 503.64 | 323.38 | 1.00 | 1.53 | General | ||
PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.58 | 622.50 | 1.49 | 1596.94 | 1070.05 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.56 | 622.50 | 1.19 | 1323.00 | 1107.16 | 1.00 | 1.36 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000096 | 0.00 | 0.00 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.05 | 0.31 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 16628.28 | 19953.94 | 171.76 | 1.244 | 1.492 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 23.89 | 23.88 | 0.00798 | 27.30 | 0.00701 | 0.416 | 0.00 |
KITCHEN | 15977.32 | 19172.79 | 165.04 | 0.996 | 1.195 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.11 | 26.10 | 0.00872 | 26.48 | 0.00701 | 1.141 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
DINING | 7441.23 | 8929.48 | 76.86 | 0.322 | 0.416 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00797 | -41.90 | 0.00006 | 0.416 | 0.00 |
KITCHEN | 644.63 | 773.56 | 6.66 | 0.025 | 1.141 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 18.89 | 18.89 | 0.00474 | -41.90 | 0.00006 | 1.141 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.49 | 1.49 | 0.42 | 0.42 | 1.4924 | 1.4924 | 1.4924 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.19 | 1.19 | 1.14 | 1.14 | 1.1950 | 1.1950 | 1.1950 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 27559.430 | 22063.253 | 1.492400 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 13779.72 | 12433.92 | 0.994933 | 24.86 | 15.85 | 0.00770766 | 11.91 | 10.04 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 41.8175 | 23.88 | 0.00797866 | 42.6205 | 16618.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 64809.839 | 64809.839 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 64809.84 | 64809.84 | 1.492399 | 3.54 | 3.54 | 0.00575679 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 27.8783 | 19.27 | 0.00795712 | 56.3833 | 4377.30 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 23033.630 | 18213.382 | 1.194950 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 11516.82 | 11505.91 | 0.796633 | 27.40 | 16.15 | 0.00700714 | 11.88 | 10.02 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 143.2696 | 26.09 | 0.00894742 | 41.8298 | 14078.83 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 112767.449 | 112767.449 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 112767.45 | 112767.45 | 1.194951 | -39.22 | -39.22 | 0.00029378 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 95.5130 | 18.73 | 0.00517428 | 38.0830 | 280.61 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 27559.430 | 22063.253 | 1.492400 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.1682 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.492399 | 1.76914842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 13779.72 | 12433.92 | 1.0000 | 1.17943307 | 0.994933 | 24.86 | 15.85 | 0.00770766 | 44615.6 | 11.91 | 10.04 | 0.00700000 | 29633.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13779.72 | 27.40 | 0.00700714 | 16.15 | 0.41605618 | 41.8175 | 23.88 | 0.00797866 | 23.88 | 0.00797866 | 42.6205 | 16618.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 64809.839 | 64809.839 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 1.492399 | 1.76914842 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 64809.84 | 64809.84 | 1.0000 | 1.76914842 | 1.492399 | 3.54 | 3.54 | 0.00575679 | 17996.2 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64809.84 | -41.90 | 0.00006450 | -41.90 | 0.41605618 | 27.8783 | 21.11 | 0.00795712 | 19.27 | 0.00795712 | 56.3833 | 4377.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23033.630 | 18213.382 | 1.194950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.8659 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.194951 | 1.41654134 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 11516.82 | 11505.91 | 1.0000 | 0.94436046 | 0.796633 | 27.40 | 16.15 | 0.00700714 | 45414.0 | 11.88 | 10.02 | 0.00700000 | 29601.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11516.82 | 27.40 | 0.00700714 | 16.15 | 1.14133354 | 143.2696 | 26.04 | 0.00894742 | 26.09 | 0.00894742 | 41.8298 | 14078.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 112767.449 | 112767.449 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.194951 | 1.41654134 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 112767.45 | 112767.45 | 1.0000 | 1.41654134 | 1.194951 | -39.22 | -39.22 | 0.00029378 | -38699.2 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 112767.45 | -41.90 | 0.00006450 | -41.90 | 1.14133354 | 95.5130 | 17.77 | 0.00517428 | 18.73 | 0.00517428 | 38.0830 | 280.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.49 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 1.14 | 1.19 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
DINING | 3932.83 | 6000.17 | 3053.83 |
KITCHEN | 5338.83 | 6105.67 | 4463.50 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 5480.83 | 7059.33 | 4605.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
DINING | 150.33 | 9.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 93.67 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 150.33 | 101.67 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.556 | 2.851 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 8.612 | 0.019 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
DINING | 36.94 | 87.54 | 354.18 | 4.093 | 0.000 | 0.000 | 0.000 |
KITCHEN | 2.65 | 6.27 | 354.18 | 7.782 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
DINING | PSZ-AC_1:1 | 36.94 | 87.54 | 354.18 | 116.17 | 0.4161 | 0.416 |
KITCHEN | PSZ-AC_2:2 | 2.65 | 6.27 | 354.18 | 116.17 | 0.1513 | 0.092 |
Total Facility | 39.58 | 93.82 | 708.37 | 232.34 | 0.5673 | 0.508 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
DINING | 11725715.66 | 0.00 | 11725715.66 | 7180182.88 | 18905898.54 | 13120747.55 | 1437.10 | 6527.81 | 795.09 | 402.00 |
KITCHEN | 22169151.85 | 0.00 | 22169151.85 | 85214.71 | 22254366.56 | 35993094.65 | 8757.35 | 0.47 | 2.18 | 395.11 |
Total Facility | 33894867.51 | 0.00 | 33894867.51 | 7265397.59 | 41160265.09 | 49113842.20 | 8759.36 | 6528.08 | 796.90 | 631.80 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
DINING | 0.4413 | 0.0000 | 0.4413 | 0.2761 | 0.7174 | 0.4161 | 0.00 | 6394.35 | 792.65 |
KITCHEN | 0.8359 | 0.0000 | 0.8359 | 0.0019 | 0.8378 | 1.1413 | 7186.77 | 0.22 | 0.02 |
Total Facility | 1.2772 | 0.0000 | 1.2772 | 0.2780 | 1.5552 | 1.5574 | 7186.77 | 6394.38 | 792.67 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16478032.27 | 0.00 | 16478032.27 | 13120747.55 | 1431.97 | 0.70 | 7327.34 | 401.77 |
PSZ-AC_2:2 | 31153563.18 | 0.00 | 31153563.18 | 35993094.65 | 4823.13 | 385.15 | 3551.72 | 395.11 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.6201 | 0.0000 | 0.6201 | 0.4161 | 0.00 | 0.00 | 7187.00 |
PSZ-AC_2:2 | 1.1746 | 0.0000 | 1.1746 | 1.1413 | 3326.69 | 375.13 | 3485.18 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 819.42 | 246.44 | 6522.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 0.00 | 47.17 | 964.94 | 6570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.9698 | 0.7584 | 0.5848 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.1781 | 1.1745 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Surfaces by ClassTotal | Outdoors | |
Wall | 8 | 6 |
Floor | 4 | 2 |
Roof | 6 | 4 |
Internal Mass | 2 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 3 | 3 |
Door | 1 | 1 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 2 |
Unconditioned Zones | 1 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 386 |
Defaulted Fields | 263 |
Fields with Defaults | 886 |
Autosized Fields | 39 |
Autosizable Fields | 93 |
Autocalculated Fields | 30 |
Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
Electricity:Building | 298.70 | 2110.08 | 01-JAN-01:20 | 18951.32 | 02-JAN-11:10 |
Electricity:Zone:DINING | 77.72 | 295.02 | 01-JAN-01:20 | 4611.81 | 02-JAN-11:10 |
Electricity:SpaceType:GENERAL | 290.76 | 1973.80 | 01-JAN-01:20 | 15657.27 | 02-JAN-11:10 |
InteriorLights:Electricity | 24.90 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-10:10 |
InteriorLights:Electricity:Zone:DINING | 7.39 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 24.90 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity | 24.90 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:DINING | 7.39 | 25.01 | 01-JAN-01:20 | 681.55 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 24.90 | 50.02 | 01-JAN-01:20 | 1583.48 | 02-JAN-10:10 |
Electricity:Zone:KITCHEN | 220.98 | 1815.06 | 01-JAN-01:20 | 14339.52 | 02-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 17.51 | 25.01 | 01-JAN-01:20 | 901.93 | 02-JAN-10:10 |
InteriorEquipment:Electricity | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 265.86 | 1923.78 | 01-JAN-01:10 | 14073.79 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:DINING | 70.33 | 270.01 | 01-JAN-01:10 | 3930.26 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 233.46 | 896.28 | 01-JAN-01:10 | 13046.29 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:KITCHEN | 195.53 | 1653.77 | 01-JAN-01:10 | 10143.54 | 01-JAN-11:10 |
Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 163.13 | 626.27 | 01-JAN-01:10 | 9116.04 | 01-JAN-11:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 17.98 | 570.00 | 01-JAN-00:10 | 570.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 49.36 | 849.95 | 06-FEB-23:30 | 4343.24 | 30-JUN-10:20 |
Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
General:Refrigeration:Electricity:Zone:KITCHEN | 7.94 | 85.78 | 01-JAN-23:30 | 3294.05 | 02-JAN-11:10 |
Electricity:Plant | 41.42 | 764.17 | 16-NOV-23:10 | 2534.76 | 25-JUL-03:40 |
LowTempRefrigeration:Refrigeration:Electricity | 13.71 | 0.00 | 01-JAN-11:10 | 1458.53 | 25-JUL-03:40 |
MedTempRefrigeration:Refrigeration:Electricity | 27.70 | 683.18 | 17-JAN-01:10 | 1076.23 | 14-JUN-01:40 |
ElectricityPurchased:Facility | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
ElectricityPurchased:Plant | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
Cogeneration:ElectricityPurchased | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
General:Cogeneration:ElectricityPurchased | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
ElectricityNet:Plant | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
Cogeneration:ElectricityNet | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
General:Cogeneration:ElectricityNet | 417.73 | 3415.98 | 15-JUN-02:50 | 25943.38 | 22-JUL-10:20 |
Electricity:HVAC | 61.65 | 0.00 | 01-JAN-01:10 | 9640.76 | 29-JUL-17:10 |
Fans:Electricity | 53.28 | 0.00 | 01-JAN-01:10 | 3027.22 | 12-JAN-21:00 |
General:Fans:Electricity | 53.28 | 0.00 | 01-JAN-01:10 | 3027.22 | 12-JAN-21:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 8.36 | 0.00 | 01-JAN-00:10 | 7543.67 | 29-JUL-17:10 |
General:Cooling:Electricity | 8.36 | 0.00 | 01-JAN-00:10 | 7543.67 | 29-JUL-17:10 |
ExteriorLights:Electricity | 15.97 | 0.00 | 01-JAN-11:20 | 1372.31 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 15.97 | 0.00 | 01-JAN-11:20 | 1372.31 | 01-JAN-06:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1665.47 | 2558.65 | 29-JAN-01:20 | 195537.21 | 12-JAN-13:20 |
NaturalGas:Building | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 477.16 | 1838.65 | 01-JAN-01:10 | 26660.45 | 01-JAN-11:10 |
NaturalGas:HVAC | 927.58 | 0.00 | 01-JAN-01:10 | 151588.84 | 12-JAN-21:00 |
Heating:NaturalGas | 927.58 | 0.00 | 01-JAN-01:10 | 151588.84 | 12-JAN-21:00 |
General:Heating:NaturalGas | 927.58 | 0.00 | 01-JAN-01:10 | 151588.84 | 12-JAN-21:00 |
NaturalGas:Plant | 260.73 | 720.00 | 01-JAN-03:10 | 33363.77 | 03-JAN-13:20 |
WaterSystems:NaturalGas | 260.73 | 720.00 | 01-JAN-03:10 | 33363.77 | 03-JAN-13:20 |
Water Heater:WaterSystems:NaturalGas | 260.73 | 720.00 | 01-JAN-03:10 | 33363.77 | 03-JAN-13:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:Water | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Facility | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
MainsWater:Plant | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
WaterUse:WaterSystems:MainsWater | 775.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-13:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1514.44 | 2414.82 | 12-JAN-01:10 | 182638.27 | 12-JAN-13:10 |
EnergyTransfer:Building | 492.89 | 1207.41 | 12-JAN-01:10 | 53114.67 | 12-JAN-12:10 |
EnergyTransfer:Zone:KITCHEN | 318.25 | 1207.41 | 12-JAN-01:10 | 24614.10 | 08-SEP-04:10 |
Refrigeration:EnergyTransfer | 129.44 | 2414.81 | 12-JAN-01:00 | 7834.84 | 27-JUN-03:40 |
Refrigeration:EnergyTransfer:Zone:KITCHEN | 64.72 | 1207.40 | 12-JAN-01:00 | 3917.42 | 27-JUN-03:40 |
General:Refrigeration:EnergyTransfer | 64.72 | 1207.40 | 12-JAN-01:00 | 3917.42 | 27-JUN-03:40 |
General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 64.72 | 1207.40 | 12-JAN-01:00 | 3917.42 | 27-JUN-03:40 |
EnergyTransfer:Plant | 247.90 | 1207.40 | 12-JAN-01:00 | 25693.04 | 08-MAY-13:00 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.84 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 51.88 | 1059.55 | 17-JAN-01:10 | 2238.70 | 14-JUN-01:40 |
EnergyTransfer:Zone:DINING | 174.64 | 0.00 | 01-JAN-01:10 | 37708.05 | 12-JAN-21:00 |
Heating:EnergyTransfer | 131.02 | 0.00 | 01-JAN-00:10 | 37708.05 | 12-JAN-21:00 |
Heating:EnergyTransfer:Zone:DINING | 130.96 | 0.00 | 01-JAN-00:10 | 37708.05 | 12-JAN-21:00 |
General:Heating:EnergyTransfer | 131.02 | 0.00 | 01-JAN-00:10 | 37708.05 | 12-JAN-21:00 |
General:Heating:EnergyTransfer:Zone:DINING | 130.96 | 0.00 | 01-JAN-00:10 | 37708.05 | 12-JAN-21:00 |
Cooling:EnergyTransfer | 297.15 | 0.00 | 01-JAN-01:10 | 23853.86 | 08-SEP-04:10 |
Cooling:EnergyTransfer:Zone:DINING | 43.68 | 0.00 | 01-JAN-01:10 | 14612.34 | 12-JAN-03:10 |
General:Cooling:EnergyTransfer | 297.15 | 0.00 | 01-JAN-01:10 | 23853.86 | 08-SEP-04:10 |
General:Cooling:EnergyTransfer:Zone:DINING | 43.68 | 0.00 | 01-JAN-01:10 | 14612.34 | 12-JAN-03:10 |
Heating:EnergyTransfer:Zone:KITCHEN | 0.06 | 0.00 | 01-JAN-00:10 | 5199.01 | 29-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:KITCHEN | 0.06 | 0.00 | 01-JAN-00:10 | 5199.01 | 29-JAN-05:10 |
Cooling:EnergyTransfer:Zone:KITCHEN | 253.47 | 0.00 | 01-JAN-01:10 | 20735.07 | 08-SEP-04:10 |
General:Cooling:EnergyTransfer:Zone:KITCHEN | 253.47 | 0.00 | 01-JAN-01:10 | 20735.07 | 08-SEP-04:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Facility | 183.18 | 0.00 | 01-JAN-00:10 | 23245.68 | 23-JAN-13:50 |
PlantLoopHeatingDemand:Plant | 183.18 | 0.00 | 01-JAN-00:10 | 23245.68 | 23-JAN-13:50 |
WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23245.68 | 23-JAN-13:50 |
General:WaterSystems:PlantLoopHeatingDemand | 183.18 | 0.00 | 01-JAN-00:10 | 23245.68 | 23-JAN-13:50 |
EnergyTransfer:HVAC | 773.65 | 0.00 | 01-JAN-01:10 | 121271.07 | 12-JAN-21:00 |
HeatingCoils:EnergyTransfer | 742.07 | 0.00 | 01-JAN-01:10 | 121271.07 | 12-JAN-21:00 |
CoolingCoils:EnergyTransfer | 31.59 | 0.00 | 01-JAN-00:10 | 31646.41 | 29-JUL-17:10 |
WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23245.68 | 23-JAN-13:50 |
WaterUse:WaterSystems:EnergyTransfer | 183.18 | 0.00 | 01-JAN-00:10 | 23245.68 | 23-JAN-13:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
DINING | 0.000 | 0.000 | 130.962 | -43.679 | 0.000 | 0.000 | 73.849 | 7.389 | 52.748 | 24.872 | 0.000 | 0.222 | 0.001 | 0.000 | -19.556 | 0.000 | -195.814 | -30.993 |
KITCHEN | 0.000 | 0.000 | 0.058 | -253.460 | 0.000 | 0.000 | 5.399 | 17.506 | 201.243 | 0.000 | 0.000 | 0.000 | 31.453 | 0.000 | 0.000 | 0.000 | -2.200 | -0.001 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.319 | 3.953 | 0.000 | 0.000 | 0.000 | -9.271 | -0.000 |
Total Facility | 0.000 | 0.000 | 131.020 | -297.139 | 0.000 | 0.000 | 79.248 | 24.895 | 253.992 | 24.872 | 0.000 | 5.541 | 35.406 | 0.000 | -19.556 | 0.000 | -207.286 | -30.994 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 12-JAN-03:21 | 0.00 | 0.00 | 0.00 | -33549.30 | 0.00 | 0.00 | 0.00 | 25.01 | 202.51 | 0.00 | 0.00 | 0.00 | 35667.24 | 0.00 | -2093.76 | 0.00 | -251.69 | 0.00 |
KITCHEN | 12-JAN-05:01 | 0.00 | 0.00 | 0.00 | -54217.13 | 0.00 | 0.00 | 22.06 | 25.01 | 4931.35 | 0.00 | 0.00 | 0.00 | 49238.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JAN-00:01 | 0.00 | 0.00 | 0.00 | -73768.50 | 0.00 | 0.00 | 388.29 | 263.92 | 2308.40 | 0.00 | 0.00 | 394.57 | 72691.21 | 0.00 | -2096.10 | 0.00 | -181.78 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
DINING | 04-DEC-05:01 | 0.00 | 0.00 | 42269.11 | 0.00 | 0.00 | 0.00 | 420.92 | 25.01 | 1219.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1381.35 | 0.00 | -68.76 | -42484.67 |
KITCHEN | 29-JAN-05:03 | 0.00 | 0.00 | 51943.56 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 4924.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -100.41 | -56792.98 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JAN-05:03 | 0.00 | 0.00 | 55532.45 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 | 6139.86 | 0.00 | 0.00 | 387.14 | 0.00 | 0.00 | -1746.03 | 0.00 | -207.28 | -60156.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4924 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.4924 | 0.2788 | 1.0000 | Not calculated | 0.4161 | 0.2788 | ||
PSZ-AC_2:2 | 1.1950 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1950 | 0.1266 | 1.0000 | Not calculated | 0.1513 | 0.1266 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.4924 | 0.0000 | 87.5444 | 1.0000 | Calculated from schedules | 0.4161 | 1.4924 | 1.0000 | 1.0000 | Not calculated | 0.4161 | 0.2788 | ||
PSZ-AC_2:2 | 1.1950 | 0.0000 | 6.2733 | 1.0000 | Calculated from schedules | 0.1513 | 1.1950 | 0.1325 | 1.0000 | Not calculated | 0.1513 | 0.1266 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
DINING | PSZ-AC_1:1 | 0.000000 | 87.5444 | 0.003581 | 116.17 | 0.4161 | 1.0000 | 0.4161 | 1.000 | 0.4161 |
KITCHEN | PSZ-AC_2:2 | 0.009440 | 6.2733 | 0.000792 | 116.17 | 0.1513 | 1.0000 | 0.1513 | 1.000 | 0.1513 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 87.54 | 0.003581 | 116.1715 | 0.4161 | 0.4161 | 0.4161 |
PSZ-AC_2:2 | 0.009440 | 6.27 | 0.000792 | 116.1715 | 0.1513 | 0.1513 | 0.1513 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4924 | 1.4924 | 1.4924 | No | 0.4161 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1950 | 1.1950 | 1.1950 | No | 0.1513 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4924 | 1.4924 | 1.4924 | 1.4924 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1950 | 1.1950 | 1.1950 | 1.1950 | 0.1513 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4924 | 1.4924 | 1.4924 | No | 0.4161 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1950 | 1.1950 | 1.1950 | No | 0.1513 | 0.1325 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.4924 | 1.4924 | 1.4924 | 1.4924 | 0.4161 | 1.0000 |
PSZ-AC_2:2 | 1.1950 | 1.1950 | 1.1950 | 1.1950 | 0.1513 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 232.34 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
DINING | 116.17 | 116.17 | 0.00 | 137.83 |
KITCHEN | 116.17 | 116.17 | 0.00 | 137.83 |
ATTIC | 232.34 | 0.00 | 232.34 | 0.00 |
Totals | 232.34 | 232.34 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 927.58 | 151588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 8.36 | 7543.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 24.90 | 1583.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 15.97 | 1372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 233.46 | 13046.29 | 477.16 | 26660.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 17.98 | 570.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 53.28 | 3027.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 260.73 | 33363.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.94 | 3294.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 13.71 | 1458.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 27.70 | 1076.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 315.22 | 417.73 |
Natural Gas | 477.16 | 1665.47 |
Additional | 0.00 | 0.00 |
Total | 792.38 | 2083.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 107.15 |
Space Heating | 0.00 |
Space Cooling | 35.99 |
Fans (All) | 229.33 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1144.28 |
Miscellaneous (All) | 1797.92 |
Subtotal | 1797.92 |
Natural Gas [MJ/m2] | |
Space Heating | 3992.29 |
Service Water Heating | 1122.20 |
Miscellaneous (All) | 7168.17 |
Subtotal | 7168.17 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 1.20 |
Space Heating | 44.53 |
Space Cooling | 0.40 |
Fans (All) | 2.56 |
Service Water Heating | 12.52 |
Receptacle Equipment | 35.67 |
Miscellaneous | 3.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_DINING | 4638. | 8760. |
LTG_SCH_KITCHEN | 4403. | 8760. |
BLDG_EQUIP_SCH | 1440. | 8760. |
FF_GAS_EQUIP_SCH | 1442. | 8760. |
BLDG_OCC_SCH | 2960. | 7195. |
INFIL_SCH_PNNL | 3285. | 8760. |
DOOR_INFIL_SCH | 3274. | 6570. |
VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
BLDG_SWH_SCH | 2246. | 6360. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7300. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
WORK_EFF_SCH | 0. | 0. |
KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 1950. | 7300. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.11 | 365 | 26.11 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8507.33 | 252.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 7873.83 | 477.50 | 334.50 | 74.17 | 0.00 |
Min | 7873.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 477.50 | 334.50 | 74.17 | 0.00 |
Average | 8380.39 | 243.39 | 111.50 | 24.72 | 0.00 |
Sum | 25141.17 | 730.17 | 334.50 | 74.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
DINING | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN | 16258.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254725.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 90327.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 270983.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
KITCHEN | 8120.33 | 639.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 8006.33 | 613.33 | 113.17 | 25.50 | 1.67 |
Min | 8006.33 | 2.83 | 0.00 | 0.00 | 0.00 |
Max | 8757.17 | 639.67 | 113.17 | 25.50 | 1.67 |
Average | 8294.61 | 418.61 | 37.72 | 8.50 | 0.56 |
Sum | 24883.83 | 1255.83 | 113.17 | 25.50 | 1.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
DINING | 254695.50 | 29.50 | 0.00 | 0.00 | 0.00 |
KITCHEN | 15009.33 | 1248.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 254695.50 | 1248.67 | 0.00 | 0.00 | 0.00 |
Average | 89901.61 | 426.06 | 0.00 | 0.00 | 0.00 |
Sum | 269704.83 | 1278.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:26:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 8760.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 0.00 | 0.00 |
Average | 0.00 | 2920.00 | 0.00 | 0.00 |
Sum | 0.00 | 8760.00 | 0.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
DINING | 0.00 | 254725.00 | 0.00 | 0.00 |
KITCHEN | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 254725.00 | 0.00 | 0.00 |
Average | 0.00 | 84908.33 | 0.00 | 0.00 |
Sum | 0.00 | 254725.00 | 0.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTFASTFOOD
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.721328E+09 | 33546.38 | 12-JAN-03:21 | -37.5 | -37.6 | 0.444690E+10 | 3722.96 | 28-JAN-19:10 | -22.8 | -23.5 |
February | 0.679168E+09 | 30724.45 | 27-FEB-04:47 | -35.8 | -35.9 | 0.402513E+10 | 3722.97 | 25-FEB-19:10 | -35.8 | -35.9 |
March | 0.731503E+09 | 22146.35 | 01-MAR-00:01 | -28.9 | -29.2 | 0.449093E+10 | 3722.88 | 04-MAR-19:10 | -13.3 | -14.5 |
April | 0.217029E+10 | 17199.84 | 03-APR-04:02 | -21.1 | -21.6 | 0.433876E+10 | 4031.18 | 22-APR-18:10 | 12.62 | 5.42 |
May | 0.574263E+10 | 8623.52 | 11-MAY-04:01 | 3.48 | 0.36 | 0.480244E+10 | 4681.01 | 13-MAY-18:00 | 18.30 | 8.64 |
June | 0.875144E+10 | 20001.12 | 24-JUN-02:62 | 16.52 | 11.39 | 0.505423E+10 | 4681.05 | 17-JUN-18:00 | 16.52 | 11.39 |
July | 0.101324E+11 | 22250.16 | 30-JUL-02:61 | 16.60 | 13.98 | 0.520528E+10 | 4681.66 | 08-JUL-18:19 | 16.60 | 13.98 |
August | 0.858446E+10 | 23147.14 | 05-AUG-02:61 | 16.02 | 11.75 | 0.509832E+10 | 4681.23 | 26-AUG-18:19 | 20.60 | 14.00 |
September | 0.358208E+10 | 9711.95 | 28-SEP-23:01 | -1.2 | -2.4 | 0.440477E+10 | 4666.99 | 02-SEP-18:10 | -1.2 | -2.4 |
October | 0.112304E+10 | 16664.58 | 26-OCT-23:01 | -16.7 | -17.3 | 0.444788E+10 | 3722.79 | 07-OCT-18:10 | -16.7 | -17.3 |
November | 0.697885E+09 | 22099.71 | 29-NOV-00:01 | -28.8 | -29.0 | 0.430083E+10 | 3722.97 | 25-NOV-19:10 | -28.8 | -29.0 |
December | 0.763825E+09 | 26486.20 | 15-DEC-04:41 | -33.1 | -33.2 | 0.444527E+10 | 3722.97 | 02-DEC-19:10 | -33.1 | -33.2 |
Annual Sum or Average | 0.436801E+11 | 0.550607E+11 | ||||||||
Minimum of Months | 0.679168E+09 | 8623.52 | -37.5 | -37.6 | 0.402513E+10 | 3722.79 | -35.8 | -35.9 | ||
Maximum of Months | 0.101324E+11 | 33546.38 | 16.60 | 13.98 | 0.520528E+10 | 4681.66 | 20.60 | 14.00 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194894E+11 | 54245.45 | 12-JAN-05:01 | -37.9 | -38.0 | 0.768047E+10 | 5036.86 | 18-JAN-11:00 | -10.6 | -10.8 |
February | 0.173920E+11 | 52717.34 | 27-FEB-05:01 | -36.1 | -36.2 | 0.693767E+10 | 5036.86 | 02-FEB-11:00 | -36.1 | -36.2 |
March | 0.200400E+11 | 45881.60 | 01-MAR-05:01 | -28.3 | -28.7 | 0.768298E+10 | 5041.89 | 20-MAR-10:00 | 5.00 | 1.39 |
April | 0.207263E+11 | 39743.20 | 03-APR-04:01 | -21.1 | -21.6 | 0.745009E+10 | 5082.90 | 20-APR-10:50 | 10.60 | 4.57 |
May | 0.217743E+11 | 50770.11 | 12-MAY-04:01 | 3.58 | 0.54 | 0.778240E+10 | 5135.93 | 31-MAY-10:50 | 18.62 | 10.48 |
June | 0.216506E+11 | 47751.41 | 02-JUN-04:01 | 3.68 | 2.64 | 0.758949E+10 | 5135.95 | 20-JUN-10:00 | 18.90 | 12.97 |
July | 0.230771E+11 | 39945.19 | 31-JUL-02:61 | 8.12 | 7.57 | 0.784120E+10 | 5135.96 | 24-JUL-10:30 | 8.12 | 7.57 |
August | 0.235633E+11 | 44129.25 | 22-AUG-04:01 | 5.60 | 5.10 | 0.782791E+10 | 5135.96 | 08-AUG-10:00 | 5.60 | 5.10 |
September | 0.230406E+11 | 50030.14 | 08-SEP-04:01 | 2.12 | 1.22 | 0.748401E+10 | 5103.53 | 19-SEP-10:00 | 11.70 | 6.96 |
October | 0.227338E+11 | 38688.23 | 31-OCT-04:01 | -17.9 | -18.4 | 0.768712E+10 | 5081.48 | 04-OCT-10:00 | -17.9 | -18.4 |
November | 0.201056E+11 | 47398.49 | 28-NOV-05:01 | -27.7 | -27.9 | 0.743258E+10 | 5036.86 | 02-NOV-10:09 | -27.7 | -27.9 |
December | 0.198742E+11 | 52468.08 | 15-DEC-05:01 | -33.2 | -33.3 | 0.768036E+10 | 5036.86 | 19-DEC-11:09 | -15.4 | -15.8 |
Annual Sum or Average | 0.253467E+12 | 0.910763E+11 | ||||||||
Minimum of Months | 0.173920E+11 | 38688.23 | -37.9 | -38.0 | 0.693767E+10 | 5036.86 | -36.1 | -36.2 | ||
Maximum of Months | 0.235633E+11 | 54245.45 | 8.12 | 7.57 | 0.784120E+10 | 5135.96 | 18.90 | 12.97 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 | -29.2 | 0.00 | 0.00 | 01-MAR-00:10 | -28.9 | -29.2 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 | -13.3 | 0.00 | 0.00 | 01-APR-00:10 | -11.7 | -13.3 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 | 2.18 | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 | 8.14 | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 | 13.77 | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 | 11.83 | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 | 5.90 | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 | 0.12 | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.00 | 0.00 | -28.9 | -29.2 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.00 | 0.00 | 16.35 | 13.77 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.261329E+11 | 40558.25 | 13-JAN-04:31 | -33.0 |
February | 0.208453E+11 | 42000.58 | 16-FEB-05:01 | -19.9 |
March | 0.161988E+11 | 42257.57 | 06-MAR-05:01 | -20.2 |
April | 0.496347E+10 | 41750.70 | 03-APR-04:01 | -21.1 |
May | 0.331149E+09 | 10549.53 | 21-MAY-05:02 | 3.68 |
June | 86824.28 | 1447.07 | 02-JUN-04:04 | 3.68 |
July | 276032.92 | 159.34 | 05-JUL-06:10 | 8.30 |
August | 60192700.23 | 8322.13 | 21-AUG-07:03 | 5.87 |
September | 0.154398E+10 | 12319.40 | 17-SEP-05:08 | 1.20 |
October | 0.964567E+10 | 25399.76 | 27-OCT-04:01 | -17.7 |
November | 0.237611E+11 | 42123.01 | 13-NOV-05:01 | -20.2 |
December | 0.274790E+11 | 42268.42 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.130962E+12 | |||
Minimum of Months | 86824.28 | 159.34 | -33.0 | |
Maximum of Months | 0.274790E+11 | 42268.42 | 8.30 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14913772.50 | 51990.07 | 29-JAN-05:03 | -27.6 |
February | 7717052.99 | 11894.77 | 27-FEB-05:02 | -36.1 |
March | 7168520.26 | 12304.40 | 14-MAR-04:03 | -18.8 |
April | 2416006.22 | 10800.82 | 09-APR-04:03 | -13.4 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 2008897.45 | 12173.08 | 22-OCT-04:03 | -18.6 |
November | 11452546.96 | 13389.30 | 19-NOV-05:03 | -17.8 |
December | 12309200.59 | 13318.38 | 12-DEC-05:03 | -23.8 |
Annual Sum or Average | 57985996.96 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 14913772.50 | 51990.07 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:01 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:01 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:01 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:01 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.964751E+09 | 681.55 | 02-JAN-10:09 | 0.597334E+10 | 3930.26 | 01-JAN-11:09 |
February | 0.704860E+09 | 681.55 | 01-FEB-15:20 | 0.539527E+10 | 3930.26 | 01-FEB-11:09 |
March | 0.617992E+09 | 681.55 | 01-MAR-17:19 | 0.597338E+10 | 3930.26 | 01-MAR-11:09 |
April | 0.421151E+09 | 681.55 | 01-APR-19:40 | 0.578064E+10 | 3930.26 | 01-APR-10:09 |
May | 0.386727E+09 | 681.55 | 01-MAY-20:30 | 0.597336E+10 | 3930.26 | 01-MAY-10:09 |
June | 0.337898E+09 | 681.55 | 02-JUN-20:40 | 0.578068E+10 | 3930.26 | 01-JUN-10:09 |
July | 0.360050E+09 | 681.55 | 14-JUL-20:00 | 0.597331E+10 | 3930.26 | 01-JUL-10:09 |
August | 0.440291E+09 | 681.55 | 02-AUG-20:30 | 0.597338E+10 | 3930.26 | 01-AUG-10:09 |
September | 0.542055E+09 | 681.55 | 01-SEP-19:10 | 0.578064E+10 | 3930.26 | 01-SEP-10:09 |
October | 0.703054E+09 | 681.55 | 02-OCT-17:19 | 0.597334E+10 | 3930.26 | 01-OCT-10:09 |
November | 0.845151E+09 | 681.55 | 01-NOV-09:09 | 0.578066E+10 | 3930.26 | 01-NOV-10:09 |
December | 0.106518E+10 | 681.55 | 01-DEC-10:09 | 0.597331E+10 | 3930.26 | 01-DEC-11:09 |
Annual Sum or Average | 0.738916E+10 | 0.703313E+11 | ||||
Minimum of Months | 0.337898E+09 | 681.55 | 0.539527E+10 | 3930.26 | ||
Maximum of Months | 0.106518E+10 | 681.55 | 0.597338E+10 | 3930.26 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.147870E+10 | 901.93 | 02-JAN-10:09 | 0.166069E+11 | 10143.54 | 01-JAN-11:09 |
February | 0.133950E+10 | 901.93 | 01-FEB-10:09 | 0.149998E+11 | 10143.54 | 01-FEB-11:09 |
March | 0.150425E+10 | 901.93 | 01-MAR-10:09 | 0.166070E+11 | 10143.54 | 01-MAR-11:09 |
April | 0.143688E+10 | 901.93 | 01-APR-16:10 | 0.160712E+11 | 10143.54 | 01-APR-10:09 |
May | 0.149147E+10 | 901.93 | 01-MAY-09:09 | 0.166070E+11 | 10143.54 | 01-MAY-10:09 |
June | 0.145377E+10 | 901.93 | 01-JUN-09:09 | 0.160713E+11 | 10143.54 | 01-JUN-10:09 |
July | 0.147476E+10 | 901.93 | 01-JUL-16:10 | 0.166069E+11 | 10143.54 | 01-JUL-10:09 |
August | 0.150425E+10 | 901.93 | 01-AUG-09:09 | 0.166070E+11 | 10143.54 | 01-AUG-10:09 |
September | 0.143724E+10 | 901.93 | 01-SEP-09:09 | 0.160712E+11 | 10143.54 | 01-SEP-10:09 |
October | 0.147852E+10 | 901.93 | 02-OCT-09:09 | 0.166069E+11 | 10143.54 | 01-OCT-10:09 |
November | 0.143180E+10 | 901.93 | 01-NOV-09:09 | 0.160712E+11 | 10143.54 | 01-NOV-10:09 |
December | 0.147494E+10 | 901.93 | 01-DEC-10:09 | 0.166069E+11 | 10143.54 | 01-DEC-11:09 |
Annual Sum or Average | 0.175061E+11 | 0.195533E+12 | ||||
Minimum of Months | 0.133950E+10 | 901.93 | 0.149998E+11 | 10143.54 | ||
Maximum of Months | 0.150425E+10 | 901.93 | 0.166070E+11 | 10143.54 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.940563E+10 | 0.964751E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299301E+11 |
February | 0.852256E+10 | 0.704860E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247840E+11 |
March | 0.954557E+10 | 0.617992E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228793E+11 |
April | 0.915225E+10 | 0.421151E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129682E+11 |
May | 0.947560E+10 | 0.386727E+09 | 0.597336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664332E+10 |
June | 0.922788E+10 | 0.337898E+09 | 0.578068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64727443.81 | 0.377029E+10 |
July | 0.939996E+10 | 0.360050E+09 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138294E+09 | 0.323433E+10 |
August | 0.954557E+10 | 0.440291E+09 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18573286.52 | 0.492902E+10 |
September | 0.915225E+10 | 0.542055E+09 | 0.578064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925840E+10 |
October | 0.940563E+10 | 0.703054E+09 | 0.597334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175445E+11 |
November | 0.909363E+10 | 0.845151E+09 | 0.578066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286011E+11 |
December | 0.939996E+10 | 0.106518E+10 | 0.597331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312717E+11 |
Annual Sum or Average | 0.111326E+12 | 0.738916E+10 | 0.703313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221595E+09 | 0.195814E+12 |
Minimum of Months | 0.852256E+10 | 0.337898E+09 | 0.539527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323433E+10 |
Maximum of Months | 0.954557E+10 | 0.106518E+10 | 0.597338E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138294E+09 | 0.312717E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.673993E+09 | 0.147870E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231862E+09 |
February | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191598E+09 |
March | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300662E+09 |
April | 0.655836E+09 | 0.143688E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296326E+09 |
May | 0.679007E+09 | 0.149147E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198942E+09 |
June | 0.661256E+09 | 0.145377E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 55019.80 | 0.123538E+09 |
July | 0.673587E+09 | 0.147476E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306457.71 | 91626861.24 |
August | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118694E+09 |
September | 0.655836E+09 | 0.143724E+10 | 0.120488E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118346E+09 |
October | 0.673993E+09 | 0.147852E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255941E+09 |
November | 0.651635E+09 | 0.143180E+10 | 0.120489E+11 | 0.117655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93484440.87 |
December | 0.673587E+09 | 0.147494E+10 | 0.124504E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179405E+09 |
Annual Sum or Average | 0.797748E+10 | 0.175061E+11 | 0.146594E+12 | 0.143147E+12 | 0.00 | 0.00 | 0.00 | 361477.51 | 0.220042E+10 |
Minimum of Months | 0.610713E+09 | 0.133950E+10 | 0.112456E+11 | 0.109812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91626861.24 |
Maximum of Months | 0.684021E+09 | 0.150425E+10 | 0.124505E+11 | 0.121577E+11 | 0.00 | 0.00 | 0.00 | 306457.71 | 0.300662E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.844852E+09 | 10547664.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601409E+09 | 0.168026E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436754E+09 | 0.763507E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295156E+09 | 0.130970E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191431E+09 | 0.158532E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98493585.26 | 0.168502E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118505E+09 | 0.158909E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199707E+09 | 0.122580E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323710E+09 | 0.631941E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398308E+09 | 0.260878E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891080E+09 | 41288608.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919363E+09 | 347053.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531877E+10 | 0.927146E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98493585.26 | 347053.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919363E+09 | 0.168502E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9454.80 | 07-JAN-19:10 | 681.55 | 02-JAN-10:09 | 3930.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 41433.83 | 12-JAN-12:05 |
February | 9454.80 | 04-FEB-19:10 | 681.55 | 01-FEB-15:20 | 3930.26 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 35838.72 | 27-FEB-12:05 |
March | 9454.80 | 04-MAR-19:10 | 681.55 | 01-MAR-17:19 | 3930.26 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 29494.28 | 01-MAR-21:00 |
April | 9454.80 | 01-APR-18:10 | 681.55 | 01-APR-19:40 | 3930.26 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 19621.55 | 01-APR-19:00 |
May | 9454.80 | 06-MAY-18:10 | 681.55 | 01-MAY-20:30 | 3930.26 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 10372.16 | 26-MAY-20:00 |
June | 9454.80 | 03-JUN-18:10 | 681.55 | 02-JUN-20:40 | 3930.26 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1565.78 | 20-JUN-17:55 | 6196.04 | 24-JUN-19:00 |
July | 9454.80 | 01-JUL-18:10 | 681.55 | 14-JUL-20:00 | 3930.26 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2795.15 | 29-JUL-17:03 | 6251.62 | 05-JUL-12:00 |
August | 9454.80 | 05-AUG-18:10 | 681.55 | 02-AUG-20:30 | 3930.26 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 962.89 | 11-AUG-17:05 | 8809.83 | 30-AUG-19:53 |
September | 9454.80 | 02-SEP-18:10 | 681.55 | 01-SEP-19:10 | 3930.26 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 14981.81 | 30-SEP-19:00 |
October | 9454.80 | 07-OCT-18:10 | 681.55 | 02-OCT-17:19 | 3930.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 25585.29 | 30-OCT-20:00 |
November | 9454.80 | 04-NOV-18:10 | 681.55 | 01-NOV-09:09 | 3930.26 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 33983.32 | 30-NOV-21:00 |
December | 9454.80 | 02-DEC-19:10 | 681.55 | 01-DEC-10:09 | 3930.26 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 38104.39 | 15-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6196.04 | |||||
Maximum of Months | 9454.80 | 681.55 | 3930.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2795.15 | 41433.83 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 677.52 | 07-JAN-19:10 | 901.93 | 02-JAN-10:09 | 7408.73 | 01-JAN-11:09 | 7998.14 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1509.23 | 29-JAN-01:10 |
February | 677.52 | 04-FEB-19:10 | 901.93 | 01-FEB-10:09 | 7408.73 | 01-FEB-11:09 | 7998.14 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1040.11 | 24-FEB-05:00 |
March | 677.52 | 04-MAR-19:10 | 901.93 | 01-MAR-10:09 | 7408.73 | 01-MAR-11:09 | 7998.14 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 792.22 | 25-MAR-04:00 |
April | 677.52 | 01-APR-18:10 | 901.93 | 01-APR-16:10 | 7408.73 | 01-APR-10:09 | 7998.14 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 853.64 | 07-APR-03:35 |
May | 677.52 | 06-MAY-18:10 | 901.93 | 01-MAY-09:09 | 7408.73 | 01-MAY-10:09 | 7998.14 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 609.44 | 26-MAY-02:00 |
June | 677.52 | 03-JUN-18:10 | 901.93 | 01-JUN-09:09 | 7408.73 | 01-JUN-10:09 | 7998.14 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 11.20 | 30-JUN-15:00 | 642.57 | 25-JUN-01:30 |
July | 677.52 | 01-JUL-18:10 | 901.93 | 01-JUL-16:10 | 7408.73 | 01-JUL-10:09 | 7998.14 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 33.20 | 21-JUL-16:00 | 392.52 | 30-JUL-01:00 |
August | 677.52 | 05-AUG-18:10 | 901.93 | 01-AUG-09:09 | 7408.73 | 01-AUG-10:09 | 7998.14 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 459.60 | 30-AUG-01:00 |
September | 677.52 | 02-SEP-18:10 | 901.93 | 01-SEP-09:09 | 7408.73 | 01-SEP-10:09 | 7998.14 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 317.29 | 30-SEP-02:00 |
October | 677.52 | 07-OCT-18:10 | 901.93 | 02-OCT-09:09 | 7408.73 | 01-OCT-10:09 | 7998.14 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 778.08 | 21-OCT-04:00 |
November | 677.52 | 04-NOV-18:10 | 901.93 | 01-NOV-09:09 | 7408.73 | 01-NOV-10:09 | 7998.14 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 633.62 | 10-NOV-05:00 |
December | 677.52 | 02-DEC-19:10 | 901.93 | 01-DEC-10:09 | 7408.73 | 01-DEC-11:09 | 7998.14 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 632.82 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 0.00 | 317.29 | ||||||
Maximum of Months | 677.52 | 901.93 | 7408.73 | 7998.14 | 0.00 | 0.00 | 0.00 | 33.20 | 1509.23 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.09 | 13-JAN-01:00 | 344.40 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.58 | 17-FEB-04:53 | 923.59 | 27-FEB-13:30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.91 | 27-MAR-07:32 | 1822.19 | 26-MAR-13:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.30 | 01-APR-00:45 | 1866.98 | 27-APR-13:50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.85 | 22-MAY-03:30 | 2001.79 | 31-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.69 | 07-JUN-01:00 | 2045.50 | 08-JUN-13:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.10 | 11-JUL-24:00 | 2117.91 | 23-JUL-12:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.95 | 22-AUG-05:10 | 1911.26 | 09-AUG-13:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.99 | 19-SEP-01:55 | 1302.27 | 07-SEP-12:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.42 | 31-OCT-07:55 | 782.27 | 22-OCT-12:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.17 | 18-NOV-03:53 | 490.49 | 06-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.41 | 28-DEC-10:00 | 91.97 | 27-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.10 | 91.97 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 880.91 | 2117.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33546.38 | 12-JAN-03:21 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.69 |
February | 30724.45 | 27-FEB-04:47 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22146.35 | 01-MAR-00:01 | 5252.67 | 1135.93 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 |
April | 17199.84 | 03-APR-04:02 | 5252.67 | 250.09 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.39 |
May | 8623.52 | 11-MAY-04:01 | 5252.67 | 250.09 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.94 |
June | 20001.12 | 24-JUN-02:62 | 0.00 | 150.06 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 |
July | 22250.16 | 30-JUL-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.94 |
August | 23147.14 | 05-AUG-02:61 | 0.00 | 250.09 | 2700.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.27 |
September | 9711.95 | 28-SEP-23:01 | 5252.67 | 1135.93 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.22 |
October | 16664.58 | 26-OCT-23:01 | 5252.67 | 1135.93 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.75 |
November | 22099.71 | 29-NOV-00:01 | 5252.67 | 1135.93 | 4065.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26486.20 | 15-DEC-04:41 | 0.00 | 250.09 | 6750.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8623.52 | 0.00 | 150.06 | 1620.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33546.38 | 5252.67 | 1135.93 | 16263.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54245.45 | 12-JAN-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52717.34 | 27-FEB-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 45881.60 | 01-MAR-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39743.20 | 03-APR-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 109.10 |
May | 50770.11 | 12-MAY-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 |
June | 47751.41 | 02-JUN-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 27.71 |
July | 39945.19 | 31-JUL-02:61 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 183.30 |
August | 44129.25 | 22-AUG-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50030.14 | 08-SEP-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 |
October | 38688.23 | 31-OCT-04:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 147.17 |
November | 47398.49 | 28-NOV-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52468.08 | 15-DEC-05:01 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 38688.23 | 0.00 | 250.09 | 14658.91 | 5515.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54245.45 | 376.40 | 250.09 | 36680.07 | 33095.74 | 0.00 | 0.00 | 0.00 | 0.00 | 183.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.88 | 0.00 |
February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.83 | 0.00 |
March | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.84 | 0.00 |
April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.71 | 0.00 |
May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.80 | 0.00 |
June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 | 0.00 |
July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.64 | 0.00 |
August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.53 | 0.00 |
September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.22 | 0.00 |
October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.37 | 0.00 |
November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.46 | 0.00 |
December | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.75 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.367157E+11 | 23722.75 | 03-JAN-11:09 | 0.235597E+12 | 195537.21 | 12-JAN-13:20 |
February | 0.324018E+11 | 21997.80 | 27-FEB-11:09 | 0.197438E+12 | 173032.72 | 27-FEB-11:20 |
March | 0.349167E+11 | 21593.45 | 01-MAR-11:09 | 0.182786E+12 | 138043.70 | 01-MAR-08:30 |
April | 0.325669E+11 | 21464.29 | 03-APR-10:09 | 0.109638E+12 | 114360.92 | 03-APR-07:10 |
May | 0.334914E+11 | 21493.45 | 31-MAY-10:20 | 0.709274E+11 | 72591.30 | 27-MAY-10:09 |
June | 0.344781E+11 | 25503.61 | 30-JUN-10:00 | 0.612945E+11 | 55448.07 | 25-JUN-10:20 |
July | 0.371238E+11 | 25943.38 | 22-JUL-10:20 | 0.624499E+11 | 55277.77 | 05-JUL-10:20 |
August | 0.357837E+11 | 23413.50 | 05-AUG-10:20 | 0.640779E+11 | 57662.10 | 30-AUG-10:20 |
September | 0.329805E+11 | 21258.41 | 29-SEP-10:09 | 0.788223E+11 | 80923.73 | 29-SEP-10:09 |
October | 0.349467E+11 | 21570.11 | 31-OCT-10:09 | 0.135999E+12 | 123758.73 | 27-OCT-10:09 |
November | 0.352366E+11 | 22212.76 | 29-NOV-11:09 | 0.223150E+12 | 157312.86 | 30-NOV-11:20 |
December | 0.370931E+11 | 23907.79 | 15-DEC-11:09 | 0.243295E+12 | 180940.17 | 15-DEC-13:20 |
Annual Sum or Average | 0.417735E+12 | 0.166547E+13 | ||||
Minimum of Months | 0.324018E+11 | 21258.41 | 0.612945E+11 | 55277.77 | ||
Maximum of Months | 0.371238E+11 | 25943.38 | 0.243295E+12 | 195537.21 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.244345E+10 | 0.244451E+10 | 0.225803E+11 | 0.00 | 0.531174E+10 | 0.79 | 0.00 | 166227.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204436E+10 | 0.175016E+10 | 0.203951E+11 | 0.00 | 0.465314E+10 | 0.72 | 0.00 | 93523.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212224E+10 | 0.141939E+10 | 0.225804E+11 | 0.00 | 0.484278E+10 | 0.80 | 0.00 | 221924.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.185803E+10 | 0.872334E+09 | 0.218518E+11 | 0.00 | 0.408157E+10 | 0.77 | 0.00 | 1084380.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.187820E+10 | 0.501260E+09 | 0.225803E+11 | 0.00 | 0.389749E+10 | 0.80 | 0.00 | 0.273811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.179167E+10 | 0.231324E+09 | 0.218520E+11 | 0.00 | 0.378655E+10 | 0.77 | 0.00 | 0.231870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183481E+10 | 0.347762E+09 | 0.225802E+11 | 0.00 | 0.394245E+10 | 0.79 | 0.00 | 0.373855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.194454E+10 | 0.709620E+09 | 0.225804E+11 | 0.00 | 0.392846E+10 | 0.80 | 0.00 | 0.201629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.197929E+10 | 0.115583E+10 | 0.218518E+11 | 0.00 | 0.388314E+10 | 0.77 | 0.00 | 12297777.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218157E+10 | 0.171416E+10 | 0.225803E+11 | 0.00 | 0.445235E+10 | 0.79 | 0.00 | 1589806.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227695E+10 | 0.217354E+10 | 0.218519E+11 | 0.00 | 0.512091E+10 | 0.77 | 0.00 | 187636.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254012E+10 | 0.265365E+10 | 0.225802E+11 | 0.00 | 0.538190E+10 | 0.79 | 0.00 | 103773.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248952E+11 | 0.159735E+11 | 0.265865E+12 | 0.00 | 0.532825E+11 | 9.37 | 0.00 | 0.836310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179167E+10 | 0.231324E+09 | 0.203951E+11 | 0.00 | 0.378655E+10 | 0.72 | 0.00 | 93523.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.254012E+10 | 0.265365E+10 | 0.225804E+11 | 0.00 | 0.538190E+10 | 0.80 | 0.00 | 0.373855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.405257E+11 | 0.00 | 0.172040E+12 | 0.00 | 0.230313E+11 | 0.00 | 0.00 |
February | 0.366039E+11 | 0.00 | 0.140031E+12 | 0.00 | 0.208035E+11 | 0.00 | 0.00 |
March | 0.405257E+11 | 0.00 | 0.119186E+12 | 0.00 | 0.230738E+11 | 0.00 | 0.00 |
April | 0.392184E+11 | 0.00 | 0.481533E+11 | 0.00 | 0.222658E+11 | 0.00 | 0.00 |
May | 0.405257E+11 | 0.00 | 0.758615E+10 | 0.00 | 0.228156E+11 | 0.00 | 0.00 |
June | 0.392184E+11 | 0.00 | 0.764831E+09 | 0.00 | 0.213112E+11 | 0.00 | 0.00 |
July | 0.405257E+11 | 0.00 | 0.678909E+09 | 0.00 | 0.212452E+11 | 0.00 | 0.00 |
August | 0.405257E+11 | 0.00 | 0.269058E+10 | 0.00 | 0.208616E+11 | 0.00 | 0.00 |
September | 0.392184E+11 | 0.00 | 0.194341E+11 | 0.00 | 0.201697E+11 | 0.00 | 0.00 |
October | 0.405257E+11 | 0.00 | 0.742286E+11 | 0.00 | 0.212442E+11 | 0.00 | 0.00 |
November | 0.392184E+11 | 0.00 | 0.162711E+12 | 0.00 | 0.212206E+11 | 0.00 | 0.00 |
December | 0.405257E+11 | 0.00 | 0.180077E+12 | 0.00 | 0.226918E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.477158E+12 | 0.00 | 0.927581E+12 | 0.00 | 0.260734E+12 | 0.00 | 0.00 |
Minimum of Months | 0.366039E+11 | 0.00 | 0.678909E+09 | 0.00 | 0.201697E+11 | 0.00 | 0.00 |
Maximum of Months | 0.405257E+11 | 0.00 | 0.180077E+12 | 0.00 | 0.230738E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 1583.48 | 02-JAN-10:09 | 1372.31 | 01-JAN-06:10 | 14073.79 | 01-JAN-11:09 | 0.00 | 3027.22 | 12-JAN-20:00 | 0.00 | 01-JAN-07:10 | 0.00 | 01-JAN-00:10 |
February | 1583.48 | 01-FEB-15:20 | 1372.31 | 01-FEB-06:10 | 14073.79 | 01-FEB-11:09 | 0.00 | 2812.52 | 27-FEB-12:30 | 0.00 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 1583.48 | 01-MAR-17:19 | 1372.31 | 01-MAR-06:10 | 14073.79 | 01-MAR-11:09 | 0.00 | 2637.68 | 01-MAR-07:10 | 0.00 | 01-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 1583.48 | 01-APR-19:40 | 1372.31 | 01-APR-05:10 | 14073.79 | 01-APR-10:09 | 0.00 | 2444.75 | 03-APR-06:10 | 0.00 | 01-APR-06:10 | 0.00 | 01-APR-00:10 |
May | 1583.48 | 01-MAY-20:30 | 1372.31 | 01-MAY-21:10 | 14073.79 | 01-MAY-10:09 | 0.00 | 1962.40 | 27-MAY-06:00 | 0.00 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 1583.48 | 02-JUN-20:40 | 1372.31 | 01-JUN-22:49 | 14073.79 | 01-JUN-10:09 | 0.00 | 1953.86 | 30-JUN-12:20 | 0.00 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 1583.48 | 14-JUL-20:00 | 1372.31 | 11-JUL-22:00 | 14073.79 | 01-JUL-10:09 | 0.00 | 2097.09 | 29-JUL-17:10 | 0.00 | 01-JUL-06:10 | 0.00 | 01-JUL-00:10 |
August | 1583.48 | 02-AUG-20:30 | 1372.31 | 01-AUG-21:00 | 14073.79 | 01-AUG-10:09 | 0.00 | 1962.01 | 31-AUG-06:10 | 0.00 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 1583.48 | 01-SEP-19:10 | 1372.31 | 01-SEP-05:10 | 14073.79 | 01-SEP-10:09 | 0.00 | 2079.29 | 30-SEP-06:10 | 0.00 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 1583.48 | 02-OCT-17:19 | 1372.31 | 01-OCT-05:10 | 14073.79 | 01-OCT-10:09 | 0.00 | 2455.40 | 22-OCT-06:10 | 0.00 | 01-OCT-06:10 | 0.00 | 01-OCT-00:10 |
November | 1583.48 | 01-NOV-09:09 | 1372.31 | 01-NOV-05:10 | 14073.79 | 01-NOV-10:09 | 0.00 | 2759.00 | 30-NOV-20:00 | 0.00 | 01-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 1583.48 | 01-DEC-10:09 | 1372.31 | 01-DEC-06:10 | 14073.79 | 01-DEC-11:09 | 0.00 | 2896.99 | 15-DEC-12:30 | 0.00 | 01-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | ||||||||||||
Minimum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 1953.86 | 0.00 | 0.00 | ||||||
Maximum of Months | 1583.48 | 1372.31 | 14073.79 | 0.00 | 3027.22 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 134.15 | 20-JAN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89.27 | 10-FEB-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 126.54 | 21-MAR-03:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 252.01 | 21-APR-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3234.90 | 31-MAY-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6991.48 | 30-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7543.67 | 29-JUL-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5539.50 | 11-AUG-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 686.19 | 04-SEP-02:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 292.71 | 10-OCT-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 123.30 | 21-NOV-04:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 54.68 | 08-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 54.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7543.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 23722.75 | 03-JAN-11:09 | 1583.48 | 14073.79 | 1372.31 | 0.00 | 2573.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21997.80 | 27-FEB-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2738.98 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21593.45 | 01-MAR-11:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2334.63 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21464.29 | 03-APR-10:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2205.47 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21493.45 | 31-MAY-10:20 | 1065.50 | 14073.79 | 0.00 | 0.00 | 1671.61 | 0.00 | 0.00 | 375.47 | 0.00 |
June | 25503.61 | 30-JUN-10:00 | 1065.50 | 14073.79 | 0.00 | 0.00 | 1913.11 | 0.00 | 0.00 | 5893.97 | 0.00 |
July | 25943.38 | 22-JUL-10:20 | 947.12 | 14073.79 | 0.00 | 0.00 | 1671.61 | 0.00 | 0.00 | 4922.76 | 0.00 |
August | 23413.50 | 05-AUG-10:20 | 947.12 | 14073.79 | 0.00 | 0.00 | 1671.61 | 0.00 | 0.00 | 2398.62 | 0.00 |
September | 21258.41 | 29-SEP-10:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 1978.75 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21570.11 | 31-OCT-10:09 | 1065.50 | 14073.79 | 0.00 | 0.00 | 2311.29 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22212.76 | 29-NOV-11:09 | 1410.82 | 14073.79 | 0.00 | 0.00 | 2608.62 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23907.79 | 15-DEC-11:09 | 1583.48 | 14073.79 | 1372.31 | 0.00 | 2758.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||||||||
Minimum of Months | 21258.41 | 947.12 | 14073.79 | 0.00 | 0.00 | 1671.61 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25943.38 | 1583.48 | 14073.79 | 1372.31 | 0.00 | 2758.68 | 0.00 | 0.00 | 5893.97 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 26660.45 | 01-JAN-11:09 | 0.00 | 151588.84 | 12-JAN-20:00 | 0.00 | 33363.77 | 03-JAN-13:20 | 0.00 |
February | 26660.45 | 01-FEB-11:09 | 0.00 | 132018.92 | 27-FEB-07:10 | 0.00 | 33360.64 | 17-FEB-13:20 | 0.00 |
March | 26660.45 | 01-MAR-11:09 | 0.00 | 113328.43 | 01-MAR-07:10 | 0.00 | 33361.24 | 29-MAR-12:20 | 0.00 |
April | 26660.45 | 01-APR-10:09 | 0.00 | 90093.94 | 03-APR-06:10 | 0.00 | 33361.38 | 03-APR-12:20 | 0.00 |
May | 26660.45 | 01-MAY-10:09 | 0.00 | 31224.63 | 27-MAY-06:00 | 0.00 | 33235.35 | 03-MAY-12:20 | 0.00 |
June | 26660.45 | 01-JUN-10:09 | 0.00 | 7346.62 | 02-JUN-06:10 | 0.00 | 30095.40 | 01-JUN-12:20 | 0.00 |
July | 26660.45 | 01-JUL-10:09 | 0.00 | 7327.16 | 05-JUL-06:10 | 0.00 | 28404.82 | 02-JUL-12:00 | 0.00 |
August | 26660.45 | 01-AUG-10:09 | 0.00 | 31348.34 | 31-AUG-06:10 | 0.00 | 28130.20 | 01-AUG-12:00 | 0.00 |
September | 26660.45 | 01-SEP-10:09 | 0.00 | 45068.30 | 30-SEP-06:10 | 0.00 | 28100.35 | 30-SEP-12:00 | 0.00 |
October | 26660.45 | 01-OCT-10:09 | 0.00 | 89745.51 | 22-OCT-06:10 | 0.00 | 28351.82 | 31-OCT-12:50 | 0.00 |
November | 26660.45 | 01-NOV-10:09 | 0.00 | 120246.81 | 30-NOV-20:00 | 0.00 | 28759.59 | 27-NOV-13:30 | 0.00 |
December | 26660.45 | 01-DEC-11:09 | 0.00 | 136184.47 | 15-DEC-12:30 | 0.00 | 33360.57 | 29-DEC-13:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 26660.45 | 0.00 | 7327.16 | 0.00 | 28100.35 | 0.00 | |||
Maximum of Months | 26660.45 | 0.00 | 151588.84 | 0.00 | 33363.77 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 22.33 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
March | 22.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
April | 7.67 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 | 0.00 | 19.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.50 | 0.00 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.56 | 0.00 | 24.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.56 | 0.00 | 24.56 |
September | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
October | 8.83 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 | 0.00 | 19.85 |
November | 31.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
December | 28.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 150.33 | 19.25 | 0.00 | 19.25 | 9.00 | 19.55 | 0.00 | 19.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.00 | 20.51 | 0.00 | 20.51 | 4.50 | 24.56 | 0.00 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.79 | 0.00 | 26.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.15 | 0.00 | 27.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.74 | 0.00 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 29.26 | 0.00 | 29.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 29.57 | 0.00 | 29.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 29.37 | 0.00 | 29.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.70 | 0.00 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.06 | 0.00 | 27.06 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.90 | 0.00 | 26.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.71 | 0.00 | 26.71 |
Annual Sum or Average | 0.00 | 0.00 | 93.67 | 28.85 | 0.00 | 28.85 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 29.57 | 0.00 | 29.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 20.83 | 606.50 | 20.83 | 606.50 | 20.83 |
February | 551.00 | 20.84 | 518.83 | 20.83 | 518.83 | 20.82 |
March | 612.00 | 20.84 | 372.33 | 20.77 | 372.33 | 20.74 |
April | 588.83 | 20.92 | 147.67 | 20.77 | 147.67 | 20.66 |
May | 504.00 | 21.35 | 34.00 | 21.28 | 23.17 | 21.17 |
June | 239.50 | 21.65 | 254.67 | 22.80 | 0.50 | 22.80 |
July | 199.33 | 21.66 | 375.00 | 23.07 | 6.00 | 23.07 |
August | 312.67 | 21.44 | 245.33 | 22.47 | 2.67 | 22.45 |
September | 572.83 | 21.10 | 36.83 | 20.98 | 34.50 | 20.87 |
October | 610.00 | 20.86 | 172.50 | 20.72 | 172.50 | 20.63 |
November | 591.00 | 20.83 | 570.33 | 20.83 | 570.33 | 20.83 |
December | 609.00 | 20.83 | 598.83 | 20.83 | 598.83 | 20.83 |
Annual Sum or Average | 6000.17 | 21.01 | 3932.83 | 21.17 | 3053.83 | 21.06 |
Minimum of Months | 199.33 | 20.83 | 34.00 | 20.72 | 0.50 | 20.63 |
Maximum of Months | 612.00 | 21.66 | 606.50 | 23.07 | 606.50 | 23.07 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 610.00 | 18.72 | 589.50 | 18.72 | 589.50 | 18.72 |
February | 551.00 | 18.73 | 499.83 | 18.72 | 499.83 | 18.71 |
March | 612.00 | 18.73 | 512.83 | 18.71 | 512.83 | 18.71 |
April | 563.50 | 19.16 | 272.67 | 19.01 | 264.83 | 18.90 |
May | 353.00 | 21.11 | 290.17 | 22.57 | 93.67 | 22.71 |
June | 383.00 | 25.56 | 524.00 | 25.46 | 343.83 | 25.63 |
July | 429.00 | 25.76 | 568.67 | 25.57 | 404.67 | 25.71 |
August | 394.17 | 24.75 | 491.00 | 24.97 | 311.17 | 25.22 |
September | 404.00 | 19.36 | 205.33 | 20.38 | 58.33 | 20.21 |
October | 606.00 | 18.97 | 241.67 | 18.84 | 241.67 | 18.77 |
November | 591.00 | 18.73 | 557.33 | 18.72 | 557.33 | 18.72 |
December | 609.00 | 18.72 | 585.83 | 18.72 | 585.83 | 18.72 |
Annual Sum or Average | 6105.67 | 20.28 | 5338.83 | 20.67 | 4463.50 | 20.63 |
Minimum of Months | 353.00 | 18.72 | 205.33 | 18.71 | 58.33 | 18.71 |
Maximum of Months | 612.00 | 25.76 | 589.50 | 25.57 | 589.50 | 25.71 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 20.83470 | 11.19935 | -0.7619 | 17.97197 |
February | 551.00000 | 20.83568 | 12.45724 | -0.7275 | 17.02926 |
March | 612.00000 | 20.83754 | 13.76147 | -0.6233 | 14.23162 |
April | 590.00000 | 20.92471 | 19.00335 | -0.4526 | 10.65203 |
May | 611.00000 | 21.78001 | 27.70664 | -1.1882 | 37.06880 |
June | 592.00000 | 22.92979 | 40.63561 | -0.6698 | 17.33901 |
July | 609.00000 | 23.08022 | 48.81024 | -0.5466 | 14.33888 |
August | 612.00000 | 22.56381 | 44.81615 | -0.7487 | 20.69753 |
September | 590.00000 | 21.17500 | 34.68707 | -1.3777 | 44.87027 |
October | 610.00000 | 20.86224 | 21.84181 | -0.5033 | 11.28842 |
November | 591.00000 | 20.83483 | 10.35622 | -0.7130 | 16.47881 |
December | 609.00000 | 20.83432 | 10.23063 | -0.7629 | 17.98584 |
Annual Sum or Average | 7187.00000 | 21.46312 | 24.71231 | -0.7560 | 19.99516 |
Minimum of Months | 551.00000 | 20.83432 | 10.23063 | -1.3777 | 10.65203 |
Maximum of Months | 612.00000 | 23.08022 | 48.81024 | -0.4526 | 44.87027 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 610.00000 | 18.72494 | 18.14568 | -0.7849 | 18.56086 |
February | 551.00000 | 18.72566 | 20.29260 | -0.7802 | 18.48221 |
March | 612.00000 | 18.72814 | 22.50325 | -0.7457 | 17.40274 |
April | 590.00000 | 19.35335 | 28.48330 | -0.5319 | 13.58588 |
May | 611.00000 | 22.42733 | 33.34798 | -0.6959 | 26.80372 |
June | 592.00000 | 24.94513 | 41.29702 | 0.22401 | 11.34622 |
July | 609.00000 | 25.15208 | 47.40208 | 0.36375 | 12.82443 |
August | 612.00000 | 24.30320 | 45.05306 | 0.07526 | 14.90880 |
September | 590.00000 | 20.69888 | 41.19906 | -1.1576 | 40.07430 |
October | 610.00000 | 18.99721 | 30.25228 | -0.5746 | 13.41152 |
November | 591.00000 | 18.72563 | 17.59922 | -0.7555 | 17.60931 |
December | 609.00000 | 18.72437 | 16.87428 | -0.7819 | 18.45346 |
Annual Sum or Average | 7187.00000 | 20.80876 | 30.26714 | -0.5093 | 18.59891 |
Minimum of Months | 551.00000 | 18.72437 | 16.87428 | -1.1576 | 11.34622 |
Maximum of Months | 612.00000 | 25.15208 | 47.40208 | 0.36375 | 40.07430 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 | 0.00 | 01-MAR-00:01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 | 0.00 | 01-APR-00:01 |
May | 0.265606E+09 | 78125819.02 | 43.69 | 0.265601E+09 | 4462.29 | 0.00 | 0.49 | 31-MAY-17:03 | 0.00 | 01-MAY-00:01 | 5776.41 | 31-MAY-17:03 | 5776.41 | 31-MAY-17:03 | 52.06 | 31-MAY-03:51 | 1595.97 | 31-MAY-17:03 | 0.00 | 01-MAY-00:01 |
June | 0.317892E+10 | 0.866383E+09 | 211.16 | 0.301629E+10 | 0.162629E+09 | 0.00 | 1.00 | 11-JUN-02:62 | 0.00 | 01-JUN-00:01 | 27188.68 | 22-JUN-02:62 | 24336.09 | 24-JUN-02:62 | 9318.03 | 30-JUN-02:62 | 6518.46 | 14-JUN-02:62 | 0.00 | 01-JUN-00:01 |
July | 0.565353E+10 | 0.149851E+10 | 264.04 | 0.512251E+10 | 0.531021E+09 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 27188.68 | 13-JUL-02:62 | 25527.98 | 13-JUL-02:62 | 11247.37 | 15-JUL-02:61 | 6518.46 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.259825E+10 | 0.711684E+09 | 157.71 | 0.235609E+10 | 0.242161E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 27188.68 | 13-AUG-02:62 | 23628.97 | 12-AUG-02:41 | 12337.66 | 13-AUG-02:62 | 6518.46 | 02-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 | 0.00 | 01-SEP-00:01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 | 0.00 | 01-OCT-00:01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 | 0.00 | 01-NOV-00:01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.116963E+11 | 0.315471E+10 | 676.60 | 0.107605E+11 | 0.935815E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.565353E+10 | 0.149851E+10 | 264.04 | 0.512251E+10 | 0.531021E+09 | 0.00 | 1.00 | 0.00 | 27188.68 | 25527.98 | 12337.66 | 6518.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 542446.61 | 166227.36 | 0.32 | 465125.55 | 77321.05 | 0.00 | 0.13 | 03-JAN-04:49 | 0.00 | 01-JAN-00:01 | 1150.74 | 03-JAN-04:49 | 1065.56 | 03-JAN-04:49 | 87.78 | 20-JAN-04:40 | 347.64 | 03-JAN-04:49 | 0.00 | 01-JAN-00:01 |
February | 307431.95 | 93523.15 | 0.10 | 264851.56 | 42580.39 | 0.00 | 0.10 | 10-FEB-05:00 | 0.00 | 01-FEB-00:01 | 880.42 | 10-FEB-05:00 | 781.73 | 14-FEB-04:57 | 142.46 | 10-FEB-05:00 | 267.82 | 10-FEB-05:00 | 0.00 | 01-FEB-00:01 |
March | 727286.32 | 221924.06 | 0.36 | 611419.98 | 115866.34 | 0.00 | 0.10 | 24-MAR-04:00 | 0.00 | 01-MAR-00:01 | 898.18 | 24-MAR-04:00 | 745.84 | 24-MAR-04:00 | 152.34 | 24-MAR-04:00 | 273.10 | 24-MAR-04:00 | 0.00 | 01-MAR-00:01 |
April | 3611128.12 | 1084380.63 | 1.64 | 2822804.85 | 788323.28 | 0.00 | 0.35 | 28-APR-03:06 | 0.00 | 01-APR-00:01 | 3314.72 | 28-APR-03:06 | 2458.88 | 28-APR-03:06 | 855.84 | 28-APR-03:06 | 949.20 | 28-APR-03:06 | 0.00 | 01-APR-00:01 |
May | 0.687197E+09 | 0.195685E+09 | 87.85 | 0.676813E+09 | 10384625.61 | 0.00 | 1.00 | 07-MAY-02:61 | 0.00 | 01-MAY-00:01 | 22723.77 | 12-MAY-04:01 | 21564.44 | 13-MAY-02:61 | 5695.44 | 16-MAY-04:01 | 5448.00 | 09-MAY-02:61 | 0.00 | 01-MAY-00:01 |
June | 0.546698E+10 | 0.145231E+10 | 313.96 | 0.503915E+10 | 0.427834E+09 | 0.00 | 1.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 | 22723.77 | 02-JUN-04:01 | 19080.62 | 04-JUN-02:11 | 10578.12 | 28-JUN-02:21 | 5448.00 | 01-JUN-02:61 | 0.00 | 01-JUN-00:01 |
July | 0.874469E+10 | 0.224004E+10 | 367.09 | 0.745251E+10 | 0.129218E+10 | 0.00 | 1.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 | 22723.77 | 28-JUL-03:21 | 19276.75 | 13-JUL-02:11 | 12513.24 | 16-JUL-04:01 | 5448.00 | 01-JUL-02:61 | 0.00 | 01-JUL-00:01 |
August | 0.493295E+10 | 0.130461E+10 | 258.39 | 0.409050E+10 | 0.842453E+09 | 0.00 | 1.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 | 22723.77 | 07-AUG-02:61 | 18753.81 | 11-AUG-02:11 | 12177.91 | 13-AUG-02:11 | 5448.00 | 01-AUG-02:61 | 0.00 | 01-AUG-00:01 |
September | 46461962.54 | 12297777.17 | 5.94 | 30466714.89 | 15995247.64 | 0.00 | 1.00 | 01-SEP-03:21 | 0.00 | 01-SEP-00:01 | 22723.77 | 08-SEP-04:01 | 15876.69 | 08-SEP-04:01 | 8074.44 | 01-SEP-04:01 | 5448.00 | 08-SEP-04:01 | 0.00 | 01-SEP-00:01 |
October | 5391986.92 | 1589806.42 | 2.13 | 3903978.64 | 1488008.28 | 0.00 | 0.88 | 06-OCT-04:01 | 0.00 | 01-OCT-00:01 | 9709.47 | 06-OCT-04:01 | 8301.06 | 06-OCT-04:01 | 1408.41 | 06-OCT-04:01 | 2409.35 | 06-OCT-04:01 | 0.00 | 01-OCT-00:01 |
November | 613146.72 | 187636.10 | 0.35 | 558194.13 | 54952.58 | 0.00 | 0.14 | 17-NOV-04:32 | 0.00 | 01-NOV-00:01 | 1266.26 | 17-NOV-04:32 | 1192.74 | 17-NOV-04:32 | 79.86 | 14-NOV-04:40 | 381.42 | 17-NOV-04:32 | 0.00 | 01-NOV-00:01 |
December | 341753.33 | 103773.77 | 0.17 | 323280.20 | 18473.12 | 0.00 | 0.16 | 19-DEC-04:44 | 0.00 | 01-DEC-00:01 | 1460.34 | 19-DEC-04:44 | 1397.66 | 19-DEC-04:44 | 66.41 | 01-DEC-04:40 | 437.73 | 19-DEC-04:44 | 0.00 | 01-DEC-00:01 |
Annual Sum or Average | 0.198898E+11 | 0.520839E+10 | 1038.29 | 0.172984E+11 | 0.259143E+10 | 0.00 | ||||||||||||||
Minimum of Months | 307431.95 | 93523.15 | 0.10 | 264851.56 | 18473.12 | 0.00 | 0.10 | 0.00 | 880.42 | 745.84 | 66.41 | 267.82 | 0.00 | |||||||
Maximum of Months | 0.874469E+10 | 0.224004E+10 | 367.09 | 0.745251E+10 | 0.129218E+10 | 0.00 | 1.00 | 0.00 | 22723.77 | 21564.44 | 12513.24 | 5448.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.47 | 3.93 | 8.54 | 1.20 | 327.08 | 0.00 | 0.00 | 0.00 |
February | 68.87 | 32.88 | 35.99 | 36.86 | 270.55 | 0.00 | 0.00 | 0.00 |
March | 196.32 | 99.40 | 96.92 | 168.49 | 197.10 | 0.00 | 0.00 | 0.00 |
April | 269.82 | 136.46 | 133.36 | 257.81 | 104.12 | 0.00 | 0.00 | 0.00 |
May | 391.91 | 220.54 | 171.36 | 440.22 | 50.23 | 0.00 | 0.00 | 0.00 |
June | 360.64 | 167.96 | 192.68 | 415.40 | 25.49 | 0.00 | 0.00 | 0.00 |
July | 342.54 | 165.82 | 176.72 | 403.04 | 29.60 | 0.00 | 0.00 | 0.00 |
August | 271.29 | 131.88 | 139.41 | 306.51 | 47.44 | 0.00 | 0.00 | 0.00 |
September | 167.86 | 73.46 | 94.40 | 162.32 | 88.62 | 0.00 | 0.00 | 0.00 |
October | 88.69 | 35.59 | 53.10 | 64.71 | 172.73 | 0.00 | 0.00 | 0.00 |
November | 18.88 | 6.61 | 12.27 | 1.62 | 319.34 | 0.00 | 0.00 | 0.00 |
December | 2.70 | 0.65 | 2.05 | 0.00 | 353.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 183.36 | 89.99 | 93.37 | 189.19 | 164.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.70 | 0.65 | 2.05 | 0.00 | 25.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 391.91 | 220.54 | 192.68 | 440.22 | 353.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 113.33 | 74.62 | 38.72 | 67.61 | 605.11 | 0.00 | 0.00 | 0.00 |
February | 390.11 | 271.23 | 118.87 | 335.54 | 481.00 | 0.00 | 0.00 | 0.00 |
March | 670.26 | 454.20 | 216.06 | 665.23 | 363.33 | 0.00 | 0.00 | 0.00 |
April | 818.14 | 508.98 | 309.16 | 907.73 | 224.47 | 0.00 | 0.00 | 0.00 |
May | 674.92 | 349.87 | 325.06 | 773.94 | 112.26 | 0.00 | 0.00 | 0.00 |
June | 616.27 | 252.79 | 363.48 | 721.96 | 62.08 | 0.00 | 0.00 | 0.00 |
July | 593.71 | 258.72 | 335.00 | 710.18 | 66.96 | 0.00 | 0.00 | 0.00 |
August | 614.67 | 338.80 | 275.87 | 723.25 | 100.81 | 0.00 | 0.00 | 0.00 |
September | 496.56 | 299.00 | 197.55 | 536.71 | 177.84 | 0.00 | 0.00 | 0.00 |
October | 357.33 | 226.62 | 130.72 | 330.55 | 316.98 | 0.00 | 0.00 | 0.00 |
November | 191.49 | 133.63 | 57.86 | 128.86 | 567.98 | 0.00 | 0.00 | 0.00 |
December | 33.98 | 23.94 | 10.05 | 6.58 | 675.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 464.11 | 265.63 | 198.48 | 492.74 | 312.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.98 | 23.94 | 10.05 | 6.58 | 62.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.14 | 508.98 | 363.48 | 907.73 | 675.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 6.56 | 1.17 | 5.38 | 0.00 | 333.18 | 0.00 | 0.00 | 0.00 |
February | 38.72 | 13.48 | 25.24 | 7.97 | 280.10 | 0.00 | 0.00 | 0.00 |
March | 116.15 | 49.94 | 66.21 | 68.24 | 201.07 | 0.00 | 0.00 | 0.00 |
April | 275.47 | 142.71 | 132.76 | 271.42 | 110.61 | 0.00 | 0.00 | 0.00 |
May | 267.86 | 121.94 | 145.92 | 281.77 | 52.38 | 0.00 | 0.00 | 0.00 |
June | 293.59 | 125.14 | 168.45 | 330.26 | 28.72 | 0.00 | 0.00 | 0.00 |
July | 245.66 | 92.90 | 152.76 | 278.45 | 31.81 | 0.00 | 0.00 | 0.00 |
August | 201.90 | 85.47 | 116.43 | 217.58 | 48.92 | 0.00 | 0.00 | 0.00 |
September | 122.21 | 51.17 | 71.04 | 104.89 | 90.42 | 0.00 | 0.00 | 0.00 |
October | 47.88 | 14.41 | 33.47 | 18.44 | 179.61 | 0.00 | 0.00 | 0.00 |
November | 19.17 | 6.97 | 12.19 | 2.08 | 318.43 | 0.00 | 0.00 | 0.00 |
December | 1.72 | 0.18 | 1.54 | 0.00 | 354.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 136.76 | 58.92 | 77.84 | 132.28 | 168.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1.72 | 0.18 | 1.54 | 0.00 | 28.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 293.59 | 142.71 | 168.45 | 330.26 | 354.57 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33406330.99 | 10537136.12 | 22869194.87 | 3226761.12 | 0.876054E+09 |
February | 0.166612E+09 | 79541053.38 | 87071048.34 | 89161456.02 | 0.654503E+09 |
March | 0.525821E+09 | 0.266231E+09 | 0.259590E+09 | 0.451277E+09 | 0.527912E+09 |
April | 0.699367E+09 | 0.353696E+09 | 0.345671E+09 | 0.668243E+09 | 0.269870E+09 |
May | 0.104968E+10 | 0.590701E+09 | 0.458983E+09 | 0.117908E+10 | 0.134534E+09 |
June | 0.934777E+09 | 0.435357E+09 | 0.499420E+09 | 0.107672E+10 | 66067123.10 |
July | 0.917449E+09 | 0.444125E+09 | 0.473324E+09 | 0.107951E+10 | 79288814.57 |
August | 0.726627E+09 | 0.353224E+09 | 0.373403E+09 | 0.820958E+09 | 0.127058E+09 |
September | 0.435081E+09 | 0.190396E+09 | 0.244685E+09 | 0.420745E+09 | 0.229706E+09 |
October | 0.237556E+09 | 95337472.44 | 0.142219E+09 | 0.173320E+09 | 0.462644E+09 |
November | 48941107.64 | 17131191.25 | 31809916.40 | 4192838.95 | 0.827732E+09 |
December | 7227790.12 | 1737208.36 | 5490581.76 | 0.00 | 0.946660E+09 |
Annual Sum or Average | 0.578255E+10 | 0.283801E+10 | 0.294454E+10 | 0.596644E+10 | 0.520203E+10 |
Minimum of Months | 7227790.12 | 1737208.36 | 5490581.76 | 0.00 | 66067123.10 |
Maximum of Months | 0.104968E+10 | 0.590701E+09 | 0.499420E+09 | 0.117908E+10 | 0.946660E+09 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.303553E+09 | 0.199851E+09 | 0.103703E+09 | 0.181083E+09 | 0.162072E+10 |
February | 0.943745E+09 | 0.656167E+09 | 0.287578E+09 | 0.811737E+09 | 0.116365E+10 |
March | 0.179522E+10 | 0.121652E+10 | 0.578697E+09 | 0.178176E+10 | 0.973141E+09 |
April | 0.212063E+10 | 0.131927E+10 | 0.801355E+09 | 0.235283E+10 | 0.581825E+09 |
May | 0.180771E+10 | 0.937085E+09 | 0.870627E+09 | 0.207293E+10 | 0.300689E+09 |
June | 0.159738E+10 | 0.655229E+09 | 0.942147E+09 | 0.187133E+10 | 0.160915E+09 |
July | 0.159020E+10 | 0.692946E+09 | 0.897256E+09 | 0.190215E+10 | 0.179348E+09 |
August | 0.164633E+10 | 0.907433E+09 | 0.738892E+09 | 0.193714E+10 | 0.269998E+09 |
September | 0.128707E+10 | 0.775010E+09 | 0.512062E+09 | 0.139114E+10 | 0.460957E+09 |
October | 0.957081E+09 | 0.606968E+09 | 0.350113E+09 | 0.885340E+09 | 0.848992E+09 |
November | 0.496330E+09 | 0.346368E+09 | 0.149962E+09 | 0.334001E+09 | 0.147219E+10 |
December | 91017042.54 | 64112229.54 | 26904813.00 | 17634971.86 | 0.180932E+10 |
Annual Sum or Average | 0.146363E+11 | 0.837696E+10 | 0.625930E+10 | 0.155391E+11 | 0.984175E+10 |
Minimum of Months | 91017042.54 | 64112229.54 | 26904813.00 | 17634971.86 | 0.160915E+09 |
Maximum of Months | 0.212063E+10 | 0.131927E+10 | 0.942147E+09 | 0.235283E+10 | 0.180932E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 17568618.43 | 3146750.06 | 14421868.37 | 0.00 | 0.892376E+09 |
February | 93662356.85 | 32610008.09 | 61052348.76 | 19273989.01 | 0.677626E+09 |
March | 0.311094E+09 | 0.133766E+09 | 0.177328E+09 | 0.182778E+09 | 0.538547E+09 |
April | 0.714031E+09 | 0.369904E+09 | 0.344127E+09 | 0.703523E+09 | 0.286693E+09 |
May | 0.717444E+09 | 0.326610E+09 | 0.390834E+09 | 0.754688E+09 | 0.140295E+09 |
June | 0.760984E+09 | 0.324371E+09 | 0.436612E+09 | 0.856035E+09 | 74453345.90 |
July | 0.657968E+09 | 0.248819E+09 | 0.409149E+09 | 0.745812E+09 | 85191946.12 |
August | 0.540768E+09 | 0.228928E+09 | 0.311840E+09 | 0.582774E+09 | 0.131015E+09 |
September | 0.316763E+09 | 0.132640E+09 | 0.184123E+09 | 0.271869E+09 | 0.234372E+09 |
October | 0.128250E+09 | 38595138.25 | 89655180.19 | 49393171.68 | 0.481056E+09 |
November | 49680924.51 | 18079027.49 | 31601897.02 | 5391486.95 | 0.825367E+09 |
December | 4607881.08 | 487178.14 | 4120702.94 | 0.00 | 0.949681E+09 |
Annual Sum or Average | 0.431282E+10 | 0.185796E+10 | 0.245487E+10 | 0.417154E+10 | 0.531667E+10 |
Minimum of Months | 4607881.08 | 487178.14 | 4120702.94 | 0.00 | 74453345.90 |
Maximum of Months | 0.760984E+09 | 0.369904E+09 | 0.436612E+09 | 0.856035E+09 | 0.949681E+09 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.17 | 1238.72 | 132.37 | 79.72 | 52.64 | 0.00 | 0.00 |
February | 326.20 | 977.49 | 497.69 | 317.59 | 180.10 | 0.00 | 0.00 |
March | 859.89 | 719.42 | 982.73 | 603.54 | 379.19 | 0.00 | 0.00 |
April | 1400.70 | 402.93 | 1363.44 | 788.15 | 575.29 | 0.00 | 0.00 |
May | 1474.39 | 193.33 | 1334.69 | 692.35 | 642.34 | 0.00 | 0.00 |
June | 1453.15 | 101.81 | 1270.50 | 545.89 | 724.61 | 0.00 | 0.00 |
July | 1381.75 | 118.44 | 1181.91 | 517.43 | 664.47 | 0.00 | 0.00 |
August | 1235.95 | 185.77 | 1087.86 | 556.15 | 531.71 | 0.00 | 0.00 |
September | 789.34 | 342.30 | 786.62 | 423.63 | 362.99 | 0.00 | 0.00 |
October | 385.47 | 641.08 | 493.91 | 276.62 | 217.29 | 0.00 | 0.00 |
November | 88.11 | 1161.29 | 229.53 | 147.21 | 82.32 | 0.00 | 0.00 |
December | 1.05 | 1378.00 | 38.40 | 24.77 | 13.63 | 0.00 | 0.00 |
Annual Sum or Average | 788.69 | 620.10 | 784.23 | 414.54 | 369.69 | 0.00 | 0.00 |
Minimum of Months | 1.05 | 101.81 | 38.40 | 24.77 | 13.63 | 0.00 | 0.00 |
Maximum of Months | 1474.39 | 1378.00 | 1363.44 | 788.15 | 724.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112958E+09 | 0.331780E+10 | 0.354528E+09 | 0.213535E+09 | 0.140994E+09 | 0.00 | 0.00 |
February | 0.789153E+09 | 0.236475E+10 | 0.120402E+10 | 0.768318E+09 | 0.435701E+09 | 0.00 | 0.00 |
March | 0.230312E+10 | 0.192691E+10 | 0.263213E+10 | 0.161652E+10 | 0.101562E+10 | 0.00 | 0.00 |
April | 0.363060E+10 | 0.104439E+10 | 0.353403E+10 | 0.204287E+10 | 0.149115E+10 | 0.00 | 0.00 |
May | 0.394901E+10 | 0.517826E+09 | 0.357484E+10 | 0.185440E+10 | 0.172044E+10 | 0.00 | 0.00 |
June | 0.376655E+10 | 0.263898E+09 | 0.329314E+10 | 0.141496E+10 | 0.187818E+10 | 0.00 | 0.00 |
July | 0.370088E+10 | 0.317234E+09 | 0.316562E+10 | 0.138589E+10 | 0.177973E+10 | 0.00 | 0.00 |
August | 0.331038E+10 | 0.497570E+09 | 0.291372E+10 | 0.148958E+10 | 0.142414E+10 | 0.00 | 0.00 |
September | 0.204596E+10 | 0.887238E+09 | 0.203892E+10 | 0.109805E+10 | 0.940870E+09 | 0.00 | 0.00 |
October | 0.103244E+10 | 0.171708E+10 | 0.132289E+10 | 0.740901E+09 | 0.581987E+09 | 0.00 | 0.00 |
November | 0.228369E+09 | 0.301008E+10 | 0.594952E+09 | 0.381578E+09 | 0.213374E+09 | 0.00 | 0.00 |
December | 2816761.81 | 0.369085E+10 | 0.102853E+09 | 66336616.05 | 36516097.70 | 0.00 | 0.00 |
Annual Sum or Average | 0.248722E+11 | 0.195556E+11 | 0.247316E+11 | 0.130729E+11 | 0.116587E+11 | 0.00 | 0.00 |
Minimum of Months | 2816761.81 | 0.263898E+09 | 0.102853E+09 | 66336616.05 | 36516097.70 | 0.00 | 0.00 |
Maximum of Months | 0.394901E+10 | 0.369085E+10 | 0.357484E+10 | 0.204287E+10 | 0.187818E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.170512E+11 | -0.162503E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -800841673.8 | 58.99 | 0.00 | 0.00 |
February | 0.154019E+11 | -0.146781E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -723737645.2 | 58.99 | 0.00 | 0.00 |
March | 0.170851E+11 | -0.162844E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -800659957.5 | 58.99 | 0.00 | 0.00 |
April | 0.164819E+11 | -0.157202E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -761694294.6 | 58.99 | 0.00 | 0.00 |
May | 0.168749E+11 | -0.161467E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -728203707.5 | 58.99 | 0.00 | 0.00 |
June | 0.157125E+11 | -0.150549E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -657633747.9 | 58.99 | 0.00 | 0.00 |
July | 0.156050E+11 | -0.149293E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -675680471.4 | 58.99 | 0.00 | 0.00 |
August | 0.152967E+11 | -0.146062E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -690510284.0 | 58.99 | 0.00 | 0.00 |
September | 0.147893E+11 | -0.140556E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -733731438.2 | 58.99 | 0.00 | 0.00 |
October | 0.156063E+11 | -0.148148E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -791569877.0 | 58.98 | 0.00 | 0.00 |
November | 0.156392E+11 | -0.148661E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -773040410.3 | 58.99 | 0.00 | 0.00 |
December | 0.167743E+11 | -0.159741E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -800266013.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.192318E+12 | -0.183381E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.893757E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.147893E+11 | -0.162844E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -800841673.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.170851E+11 | -0.140556E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -657633747.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.46 | 0.24 | 03-JAN-11:30 | 312.84 | 12.68 | 0.00 | 68.83 | 317.85 | 12.64 | 0.00 | 69.33 |
February | 205.83 | 0.34 | 0.24 | 01-FEB-10:50 | 765.04 | 16.16 | 0.00 | 171.17 | 777.34 | 16.30 | 0.00 | 172.00 |
March | 329.50 | 0.30 | 0.24 | 01-MAR-09:20 | 4920.66 | 30.12 | 232.83 | 302.00 | 4782.56 | 29.90 | 217.67 | 304.33 |
April | 421.83 | 0.28 | 0.24 | 01-APR-06:00 | 2688.54 | 22.26 | 199.00 | 405.17 | 2181.18 | 21.06 | 159.83 | 406.33 |
May | 545.00 | 0.30 | 0.24 | 01-MAY-04:40 | 2028.91 | 18.28 | 100.83 | 491.83 | 2911.01 | 19.63 | 140.17 | 488.50 |
June | 583.50 | 0.31 | 0.24 | 01-JUN-03:30 | 1783.67 | 18.10 | 118.00 | 519.00 | 1976.94 | 18.11 | 93.83 | 516.33 |
July | 562.83 | 0.30 | 0.24 | 01-JUL-03:49 | 1937.50 | 18.28 | 118.33 | 509.33 | 2018.67 | 18.20 | 111.00 | 504.50 |
August | 467.17 | 0.29 | 0.24 | 01-AUG-04:49 | 2423.11 | 20.94 | 164.00 | 435.00 | 2458.29 | 20.84 | 151.83 | 430.67 |
September | 356.33 | 0.30 | 0.24 | 01-SEP-06:19 | 4089.19 | 28.98 | 244.00 | 328.17 | 3851.77 | 28.49 | 230.67 | 325.17 |
October | 265.50 | 0.31 | 0.24 | 01-OCT-07:40 | 1568.95 | 23.52 | 102.83 | 237.67 | 1597.92 | 23.34 | 100.67 | 237.00 |
November | 135.83 | 0.37 | 0.24 | 01-NOV-09:50 | 407.66 | 14.53 | 0.00 | 119.83 | 408.27 | 14.48 | 0.00 | 120.67 |
December | 71.17 | 0.75 | 0.24 | 04-DEC-11:09 | 104.30 | 8.12 | 0.00 | 7.50 | 105.39 | 8.04 | 0.00 | 8.17 |
Annual Sum or Average | 4053.17 | 0.31 | 2282.76 | 20.66 | 1279.83 | 3595.50 | 2362.32 | 20.62 | 1205.67 | 3583.00 | ||
Minimum of Months | 71.17 | 0.28 | 0.24 | 104.30 | 8.12 | 0.00 | 7.50 | 105.39 | 8.04 | 0.00 | 8.17 | |
Maximum of Months | 583.50 | 0.75 | 0.24 | 4920.66 | 30.12 | 244.00 | 519.00 | 4782.56 | 29.90 | 230.67 | 516.33 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.711335E+11 | 64809.84 | 01-JAN-03:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.580245E+11 | 64809.84 | 01-FEB-03:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510887E+11 | 64809.84 | 01-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.226321E+11 | 64809.84 | 03-APR-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.503882E+10 | 19706.88 | 28-MAY-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.611865E+09 | 9288.11 | 02-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543127E+09 | 5861.73 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.184649E+10 | 15491.41 | 21-AUG-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114712E+11 | 21764.33 | 17-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.343776E+11 | 64809.84 | 22-OCT-02:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.679064E+11 | 64809.84 | 03-NOV-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.741361E+11 | 64809.84 | 01-DEC-03:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.398810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.543127E+09 | 5861.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.741361E+11 | 64809.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.664986E+11 | 112767.45 | 29-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540002E+11 | 81777.32 | 27-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.442604E+11 | 61983.30 | 31-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158906E+11 | 48648.35 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103010E+10 | 16143.84 | 27-MAY-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.305969E+09 | 12636.62 | 31-AUG-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.407614E+10 | 20599.89 | 30-SEP-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.250052E+11 | 55328.29 | 22-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.622620E+11 | 65089.43 | 28-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699256E+11 | 70830.01 | 15-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.699256E+11 | 112767.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:01 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.265606E+09 | 0.265601E+09 | 5776.41 | 31-MAY-17:03 | 5776.41 | 0.00 |
June | 0.00 | 0.00 | 0.317892E+10 | 0.301629E+10 | 27188.68 | 22-JUN-02:62 | 21825.80 | 0.00 |
July | 0.00 | 0.00 | 0.565353E+10 | 0.512251E+10 | 27188.68 | 13-JUL-02:62 | 25527.98 | 0.00 |
August | 0.00 | 0.00 | 0.259825E+10 | 0.235609E+10 | 27188.68 | 13-AUG-02:62 | 14851.02 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116963E+11 | 0.107605E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.565353E+10 | 0.512251E+10 | 27188.68 | 25527.98 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 542446.61 | 465125.55 | 1150.74 | 03-JAN-04:49 | 1065.56 | 0.00 |
February | 0.00 | 0.00 | 307431.95 | 264851.56 | 880.42 | 10-FEB-05:00 | 737.96 | 0.00 |
March | 0.00 | 0.00 | 727286.32 | 611419.98 | 898.18 | 24-MAR-04:00 | 745.84 | 0.00 |
April | 0.00 | 0.00 | 3611128.12 | 2822804.85 | 3314.72 | 28-APR-03:06 | 2458.88 | 0.00 |
May | 0.00 | 0.00 | 0.687197E+09 | 0.676813E+09 | 22723.77 | 12-MAY-04:01 | 19080.49 | 0.00 |
June | 0.00 | 0.00 | 0.546698E+10 | 0.503915E+10 | 22723.77 | 02-JUN-04:01 | 15652.96 | 0.00 |
July | 0.00 | 0.00 | 0.874469E+10 | 0.745251E+10 | 22723.77 | 28-JUL-03:21 | 12505.72 | 0.00 |
August | 0.00 | 0.00 | 0.493295E+10 | 0.409050E+10 | 22723.77 | 07-AUG-02:61 | 11451.61 | 0.00 |
September | 0.00 | 0.00 | 46461962.54 | 30466714.89 | 22723.77 | 08-SEP-04:01 | 15876.69 | 0.00 |
October | 0.00 | 0.00 | 5391986.92 | 3903978.64 | 9709.47 | 06-OCT-04:01 | 8301.06 | 0.00 |
November | 0.00 | 0.00 | 613146.72 | 558194.13 | 1266.26 | 17-NOV-04:32 | 1192.74 | 0.00 |
December | 0.00 | 0.00 | 341753.33 | 323280.20 | 1460.34 | 19-DEC-04:44 | 1397.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198898E+11 | 0.172984E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 307431.95 | 264851.56 | 880.42 | 737.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.874469E+10 | 0.745251E+10 | 22723.77 | 19080.49 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 6366.98 | 23784.70 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 6366.83 | 23784.22 | 14-FEB-13:17 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 6381.12 | 23784.91 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 6363.59 | 23785.72 | 04-APR-12:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 6327.88 | 23785.68 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 6106.49 | 23161.86 | 01-JUN-12:37 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 5867.29 | 22208.14 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 5749.24 | 21474.89 | 01-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 5715.81 | 21341.52 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 5825.50 | 21971.08 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 6032.25 | 22878.95 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 6261.40 | 23782.64 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.27 | ||||
Minimum of Months | 0.00 | 0.00 | 5715.81 | 21341.52 | ||
Maximum of Months | 0.00 | 0.00 | 6381.12 | 23785.72 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:01 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:01 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112677E+10 | 0.23 | 503.64 | 01-JAN-00:01 | 0.27 |
February | 0.101649E+10 | 0.23 | 503.64 | 01-FEB-00:01 | 0.27 |
March | 0.112663E+10 | 0.23 | 503.64 | 01-MAR-00:01 | 0.27 |
April | 0.110190E+10 | 0.23 | 503.64 | 01-APR-04:01 | 0.27 |
May | 0.119703E+10 | 0.24 | 503.64 | 01-MAY-03:35 | 0.27 |
June | 0.121023E+10 | 0.25 | 503.64 | 01-JUN-01:30 | 0.27 |
July | 0.126419E+10 | 0.25 | 503.64 | 01-JUL-00:35 | 0.27 |
August | 0.124964E+10 | 0.25 | 503.64 | 01-AUG-00:45 | 0.27 |
September | 0.115210E+10 | 0.24 | 503.64 | 01-SEP-02:62 | 0.27 |
October | 0.114406E+10 | 0.23 | 503.64 | 01-OCT-04:01 | 0.27 |
November | 0.109395E+10 | 0.23 | 503.64 | 01-NOV-04:01 | 0.27 |
December | 0.112708E+10 | 0.23 | 503.64 | 01-DEC-00:01 | 0.27 |
Annual Sum or Average | 0.138101E+11 | 0.23 | |||
Minimum of Months | 0.101649E+10 | 0.23 | 503.64 | 0.27 | |
Maximum of Months | 0.126419E+10 | 0.25 | 503.64 | 0.27 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.253558E+10 | 0.66 | 1596.94 | 01-JAN-03:09 | 0.90 |
February | 0.218960E+10 | 0.64 | 1596.94 | 01-FEB-03:10 | 0.90 |
March | 0.222328E+10 | 0.62 | 1596.94 | 01-MAR-03:01 | 0.90 |
April | 0.172368E+10 | 0.55 | 1596.94 | 03-APR-02:70 | 0.90 |
May | 0.150049E+10 | 0.47 | 915.99 | 21-MAY-05:02 | 0.67 |
June | 0.139368E+10 | 0.46 | 776.09 | 02-JUN-04:04 | 0.61 |
July | 0.144216E+10 | 0.47 | 1340.72 | 30-JUL-02:61 | 0.82 |
August | 0.145876E+10 | 0.47 | 1102.38 | 05-AUG-02:61 | 0.74 |
September | 0.154958E+10 | 0.49 | 960.54 | 17-SEP-05:08 | 0.69 |
October | 0.194928E+10 | 0.57 | 1596.94 | 22-OCT-02:65 | 0.90 |
November | 0.244537E+10 | 0.65 | 1596.94 | 03-NOV-02:62 | 0.90 |
December | 0.258132E+10 | 0.66 | 1596.94 | 01-DEC-03:08 | 0.90 |
Annual Sum or Average | 0.229928E+11 | 0.56 | |||
Minimum of Months | 0.139368E+10 | 0.46 | 776.09 | 0.61 | |
Maximum of Months | 0.258132E+10 | 0.66 | 1596.94 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164939E+10 | 0.58 | 1323.00 | 29-JAN-05:03 | 0.93 |
February | 0.144705E+10 | 0.56 | 1104.85 | 27-FEB-05:02 | 0.86 |
March | 0.149287E+10 | 0.54 | 965.52 | 31-MAR-04:03 | 0.80 |
April | 0.125599E+10 | 0.50 | 871.65 | 03-APR-04:03 | 0.76 |
May | 0.119996E+10 | 0.49 | 1323.00 | 09-MAY-04:01 | 0.93 |
June | 0.118264E+10 | 0.51 | 1323.00 | 01-JUN-02:61 | 0.92 |
July | 0.123611E+10 | 0.52 | 1323.00 | 01-JUL-02:61 | 0.92 |
August | 0.122006E+10 | 0.51 | 1323.00 | 01-AUG-02:61 | 0.92 |
September | 0.118147E+10 | 0.50 | 1323.00 | 08-SEP-04:01 | 0.93 |
October | 0.135901E+10 | 0.52 | 918.67 | 22-OCT-04:03 | 0.78 |
November | 0.158159E+10 | 0.57 | 987.38 | 28-NOV-05:03 | 0.81 |
December | 0.167351E+10 | 0.58 | 1027.79 | 15-DEC-05:03 | 0.83 |
Annual Sum or Average | 0.164796E+11 | 0.53 | |||
Minimum of Months | 0.118147E+10 | 0.49 | 871.65 | 0.76 | |
Maximum of Months | 0.167351E+10 | 0.58 | 1323.00 | 0.93 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.79 | 0.24 | 0.00 | 01-JAN-07:10 | 0.00 | 0.00 | 48.31 | 0.10 |
February | 0.72 | 0.22 | 0.00 | 01-FEB-06:10 | 0.00 | 0.00 | 50.18 | 0.10 |
March | 0.80 | 0.24 | 0.00 | 01-MAR-06:10 | 0.00 | 0.00 | 50.31 | 0.10 |
April | 0.77 | 0.23 | 0.00 | 01-APR-06:10 | 0.00 | 0.00 | 49.84 | 0.10 |
May | 0.80 | 0.24 | 0.00 | 01-MAY-05:03 | 0.00 | 0.00 | 45.55 | 0.10 |
June | 0.77 | 0.23 | 0.00 | 01-JUN-05:05 | 0.00 | 0.00 | 49.86 | 0.10 |
July | 0.79 | 0.24 | 0.00 | 01-JUL-06:10 | 0.00 | 0.00 | 50.62 | 0.10 |
August | 0.80 | 0.24 | 0.00 | 01-AUG-05:05 | 0.00 | 0.00 | 50.49 | 0.10 |
September | 0.77 | 0.23 | 0.00 | 01-SEP-05:10 | 0.00 | 0.00 | 51.07 | 0.10 |
October | 0.79 | 0.24 | 0.00 | 01-OCT-06:10 | 0.00 | 0.00 | 49.39 | 0.10 |
November | 0.77 | 0.23 | 0.00 | 01-NOV-05:10 | 0.00 | 0.00 | 50.85 | 0.10 |
December | 0.79 | 0.24 | 0.00 | 01-DEC-06:10 | 0.00 | 0.00 | 50.54 | 0.10 |
Annual Sum or Average | 9.37 | 2.81 | ||||||
Minimum of Months | 0.72 | 0.22 | 0.00 | 0.00 | 0.00 | 45.55 | 0.10 | |
Maximum of Months | 0.80 | 0.24 | 0.00 | 0.00 | 0.00 | 51.07 | 0.10 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 33.62 | 33.62 | 6366.98 | 23784.70 | 03-JAN-13:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 49.97 | 49.97 | 6366.83 | 23784.22 | 14-FEB-13:17 |
March | 0.00 | 0.00 | 01-MAR-00:01 | 49.87 | 49.87 | 6381.12 | 23784.91 | 19-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:01 | 49.87 | 49.87 | 6363.59 | 23785.72 | 04-APR-12:38 |
May | 0.00 | 0.00 | 01-MAY-00:01 | 33.73 | 33.73 | 6327.88 | 23785.68 | 02-MAY-12:38 |
June | 0.00 | 0.00 | 01-JUN-00:01 | 50.02 | 50.02 | 6106.49 | 23161.86 | 01-JUN-12:37 |
July | 0.00 | 0.00 | 01-JUL-00:01 | 50.88 | 50.88 | 5867.29 | 22208.14 | 01-JUL-13:00 |
August | 0.00 | 0.00 | 01-AUG-00:01 | 50.68 | 50.68 | 5749.24 | 21474.89 | 01-AUG-12:30 |
September | 0.00 | 0.00 | 01-SEP-00:01 | 50.88 | 50.88 | 5715.81 | 21341.52 | 30-SEP-12:35 |
October | 0.00 | 0.00 | 01-OCT-00:01 | 36.14 | 36.14 | 5825.50 | 21971.08 | 31-OCT-12:20 |
November | 0.00 | 0.00 | 01-NOV-00:01 | 50.67 | 50.67 | 6032.25 | 22878.95 | 30-NOV-13:40 |
December | 0.00 | 0.00 | 01-DEC-00:01 | 50.36 | 50.36 | 6261.40 | 23782.64 | 31-DEC-13:30 |
Annual Sum or Average | 0.00 | 6112.27 | ||||||
Minimum of Months | 0.00 | 0.00 | 33.62 | 33.62 | 5715.81 | 21341.52 | ||
Maximum of Months | 0.00 | 0.00 | 50.88 | 50.88 | 6381.12 | 23785.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.253558E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.218960E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.222328E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172368E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157862E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226006E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.294067E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.217044E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.154958E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.194928E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.244537E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.258132E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.261475E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.154958E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.294067E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164956E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144714E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.149309E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.125707E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.139565E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.263495E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.347614E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.252467E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.119377E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.136060E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.158178E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.167361E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.216880E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.119377E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.347614E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.253558E+10 | 0.00 | 0.711335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218960E+10 | 0.00 | 0.580245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222328E+10 | 0.00 | 0.510887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172368E+10 | 0.00 | 0.226321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150049E+10 | 0.265606E+09 | 0.503882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139368E+10 | 0.317503E+10 | 0.611865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144216E+10 | 0.564571E+10 | 0.543127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145876E+10 | 0.259356E+10 | 0.184649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154958E+10 | 0.00 | 0.114712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194928E+10 | 0.00 | 0.343776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244537E+10 | 0.00 | 0.679064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258132E+10 | 0.00 | 0.741361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229928E+11 | 0.116799E+11 | 0.398810E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139368E+10 | 0.00 | 0.543127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.258132E+10 | 0.564571E+10 | 0.741361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164939E+10 | 542446.61 | 0.664986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144705E+10 | 307431.95 | 0.540002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149287E+10 | 727286.32 | 0.442604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125599E+10 | 3611128.12 | 0.158906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119996E+10 | 0.685910E+09 | 0.103010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118264E+10 | 0.545705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123611E+10 | 0.873878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122006E+10 | 0.492828E+10 | 0.305969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118147E+10 | 46461962.54 | 0.407614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135901E+10 | 5391986.92 | 0.250052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158159E+10 | 613146.72 | 0.622620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167351E+10 | 341753.33 | 0.699256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164796E+11 | 0.198680E+11 | 0.343255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118147E+10 | 307431.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167351E+10 | 0.873878E+10 | 0.699256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.253558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150049E+10 | 0.00 | 0.00 | 0.00 | 78125819.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139368E+10 | 0.00 | 0.00 | 0.00 | 0.866383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144216E+10 | 0.00 | 0.00 | 0.00 | 0.149851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145876E+10 | 0.00 | 0.00 | 0.00 | 0.711684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.194928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229928E+11 | 0.00 | 0.00 | 0.00 | 0.315471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.258132E+10 | 0.00 | 0.00 | 0.00 | 0.149851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164939E+10 | 0.00 | 0.00 | 0.00 | 166227.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144705E+10 | 0.00 | 0.00 | 0.00 | 93523.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149287E+10 | 0.00 | 0.00 | 0.00 | 221924.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125599E+10 | 0.00 | 0.00 | 0.00 | 1084380.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.119996E+10 | 0.00 | 0.00 | 0.00 | 0.195685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118264E+10 | 0.00 | 0.00 | 0.00 | 0.145231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.123611E+10 | 0.00 | 0.00 | 0.00 | 0.224004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.122006E+10 | 0.00 | 0.00 | 0.00 | 0.130461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118147E+10 | 0.00 | 0.00 | 0.00 | 12297777.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135901E+10 | 0.00 | 0.00 | 0.00 | 1589806.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158159E+10 | 0.00 | 0.00 | 0.00 | 187636.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167351E+10 | 0.00 | 0.00 | 0.00 | 103773.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164796E+11 | 0.00 | 0.00 | 0.00 | 0.520839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118147E+10 | 0.00 | 0.00 | 0.00 | 93523.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167351E+10 | 0.00 | 0.00 | 0.00 | 0.224004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.188420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489117E+11 | 0.00 | 0.00 | 3.68 |
February | 0.166746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406824E+11 | 0.00 | 0.00 | 3.63 |
March | 0.194116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384773E+11 | 0.00 | 0.00 | 3.62 |
April | 0.676196E+10 | 0.00 | 0.00 | 43325.83 | 0.00 | 0.172172E+11 | 0.115420E+09 | 0.00 | 3.61 |
May | 0.984070E+10 | 0.00 | 0.00 | 4941572.55 | 0.00 | 0.217912E+10 | 0.257099E+10 | 0.00 | 3.81 |
June | 0.514785E+10 | 6977151.15 | 0.00 | 19488151.66 | 0.00 | 645936.56 | 0.571803E+10 | 0.00 | 4.45 |
July | 0.461372E+10 | 42435263.88 | 0.00 | 25711678.72 | 0.00 | 25905594.42 | 0.540054E+10 | 0.00 | 4.49 |
August | 0.712202E+10 | 0.00 | 0.00 | 16486145.55 | 0.00 | 0.496274E+09 | 0.493423E+10 | 0.00 | 4.25 |
September | 0.966687E+10 | 0.00 | 0.00 | 400460.10 | 0.00 | 0.747478E+10 | 0.542391E+09 | 0.00 | 3.58 |
October | 0.424050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261576E+11 | 0.00 | 0.00 | 3.61 |
November | 0.187084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478861E+11 | 0.00 | 0.00 | 3.64 |
December | 0.203594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504980E+11 | 0.00 | 0.00 | 3.66 |
Annual Sum or Average | 0.567932E+11 | 49412415.03 | 0.00 | 67071334.42 | 0.00 | 0.280007E+12 | 0.192816E+11 | 0.00 | 3.84 |
Minimum of Months | 0.166746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 645936.56 | 0.00 | 0.00 | 3.58 |
Maximum of Months | 0.984070E+10 | 42435263.88 | 0.00 | 25711678.72 | 0.00 | 0.504980E+11 | 0.571803E+10 | 0.00 | 4.49 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.973320E+11 | 0.00 | 0.00 | 51267.61 | 0.00 | 92236193.70 | 27067068.66 | 0.00 | 7.68 |
February | 0.819830E+11 | 0.00 | 0.00 | 39175.77 | 0.00 | 71161658.28 | 18354645.11 | 0.00 | 7.51 |
March | 0.762682E+11 | 0.00 | 0.00 | 43804.04 | 0.00 | 72288756.15 | 22161927.05 | 0.00 | 7.30 |
April | 0.475959E+11 | 0.00 | 0.00 | 499901.42 | 0.00 | 18534434.22 | 0.101400E+10 | 0.00 | 6.98 |
May | 0.217366E+11 | 0.00 | 0.00 | 19937389.27 | 0.00 | 0.00 | 0.130376E+11 | 0.00 | 6.89 |
June | 0.729895E+10 | 0.00 | 0.00 | 53860235.94 | 0.00 | 0.00 | 0.208505E+11 | 0.00 | 7.09 |
July | 0.616753E+10 | 0.00 | 0.00 | 63958152.83 | 0.00 | 0.00 | 0.201060E+11 | 0.00 | 7.17 |
August | 0.112055E+11 | 0.00 | 0.00 | 48156951.01 | 0.00 | 0.00 | 0.197413E+11 | 0.00 | 7.02 |
September | 0.308237E+11 | 0.00 | 0.00 | 6371596.37 | 0.00 | 0.00 | 0.712519E+10 | 0.00 | 6.89 |
October | 0.581654E+11 | 0.00 | 0.00 | 501973.08 | 0.00 | 19755055.33 | 0.639645E+09 | 0.00 | 7.09 |
November | 0.935919E+11 | 0.00 | 0.00 | 163524.48 | 0.00 | 85652081.85 | 50462760.42 | 0.00 | 7.61 |
December | 0.101041E+12 | 0.00 | 0.00 | 92282.46 | 0.00 | 96337448.89 | 41357116.33 | 0.00 | 7.70 |
Annual Sum or Average | 0.633209E+12 | 0.00 | 0.00 | 0.193676E+09 | 0.00 | 0.455966E+09 | 0.826737E+11 | 0.00 | 7.24 |
Minimum of Months | 0.616753E+10 | 0.00 | 0.00 | 39175.77 | 0.00 | 0.00 | 18354645.11 | 0.00 | 6.89 |
Maximum of Months | 0.101041E+12 | 0.00 | 0.00 | 63958152.83 | 0.00 | 96337448.89 | 0.208505E+11 | 0.00 | 7.70 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:26:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.827993E+10 | 0.311773E+11 | 0.218021E+12 | 0.00 | 0.470110E+11 |
February | 0.341330E+09 | 0.262304E+11 | 0.185228E+12 | 0.00 | 0.417684E+11 |
March | 0.215306E+11 | 0.254623E+11 | 0.177935E+12 | 0.00 | 0.405115E+11 |
April | 0.455034E+11 | 0.161508E+11 | 0.120006E+12 | 0.00 | 0.276324E+11 |
May | 0.601864E+11 | 0.102190E+11 | 0.899976E+11 | 0.528723E+09 | 0.243415E+11 |
June | 0.630236E+11 | 0.721492E+10 | 0.724267E+11 | 0.160926E+10 | 0.330857E+11 |
July | 0.569967E+11 | 0.630710E+10 | 0.688391E+11 | 0.145337E+10 | 0.416268E+11 |
August | 0.414656E+11 | 0.783665E+10 | 0.804717E+11 | 0.131907E+10 | 0.321219E+11 |
September | 0.172768E+11 | 0.114529E+11 | 0.986246E+11 | 4699075.94 | 0.207237E+11 |
October | 0.390067E+10 | 0.195276E+11 | 0.143491E+12 | 0.00 | 0.276386E+11 |
November | -0.477795E+10 | 0.296417E+11 | 0.211784E+12 | 0.00 | 0.451497E+11 |
December | -0.998357E+10 | 0.324073E+11 | 0.225618E+12 | 0.00 | 0.486755E+11 |
Annual Sum or Average | 0.287184E+12 | 0.223628E+12 | 0.169244E+13 | 0.491512E+10 | 0.430287E+12 |
Minimum of Months | -0.998357E+10 | 0.630710E+10 | 0.688391E+11 | 0.00 | 0.207237E+11 |
Maximum of Months | 0.630236E+11 | 0.324073E+11 | 0.225618E+12 | 0.160926E+10 | 0.486755E+11 |